IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
Models: AK150LS,
Exhaust Fan
AK200LS, AK300LS
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT
YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH
INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions
should always be followed to reduce the risk of fire,
electric shock and injury to person, including the following:
1. Read all instructions before installing or using exhaust fan.
2. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer.
6. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
7. Ducted fans must always be vented to the outdoors.
8. This unit must be grounded.
9. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off
power unit.
3. Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the
service panel.
4. Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-related construction.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
DO NOT USE THIS FAN WITH ANY SOLID-STATE SPEED CONTROL
DEVICE.
10. Acceptable for use over a bathtub or shower when installed
in a GFCI protected branch circuit.
11. NEVER place a switch where it can be reached from a tub or
shower.
5. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA)
and the American Society for Heating, Refrigeration, and Air
Conditioning Engineers (ASHRAE), and the local code authorities.
WARNING: DO NOT USE IN KITCHENS
CAUTION: FOR GENERAL VENTILATING USE ONLY. DO
NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS
AND VAPORS.
SAVE THESE INSTRUCTIONS
210572051 Rev. A 8-05
1 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Ducting
Wire Compartment
Cover
Screw
Duct
Collar
Figure 9
2. Run wiring from an approved wall switch carrying the appropriate
rating. One neutral (white), one ground (green or bare copper), and
one hot (black lead connected to the switch). Secure the electrical
wires to the housing with an approved electrical connector. Make
sure you leave enough wiring in the box to make the connection
to the fan’s receptacle.
Figure 6
SECTION 4
Wiring
3. From where you have chosen to access the fan’s junction box,
connect the white wire from the house to the white wire from the
fan’s receptacle. Connect the black wire from the wall switch to
the black wire from the fan’s receptacle. Connect the ground wire
from the house to the green wire from the fan housing (Figure 10).
Use approved methods for all connections.
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE
PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF
INSTALLING ELECTRICAL WIRING, SECURE THE SERVICES OF A
QUALIFIED ELECTRICIAN.
Supply from
house
NOTE: This unit includes a side access panel for wiring that does not
require the removal of the fan’s blower assembly. If you choose to wire
the unit from the inside, you will need to remove the blower assembly
and internal wiring compartment. Both methods are equally effective.
1a. External Wire Compartment: Remove the wire compartment cover
screw and place cover in a secure place (Figure 7).
Ground
White
Hot (Black)
Figure 10
Screw
NOTE: The fan’s receptacle wires might need to be pulled outside
compartment for connection. Only pull the three loose wires outside of
compartment. Additional wires will be present.
Wire
Compartment
Cover
4. Carefully tuck wire back inside wire compartment and replace wire
compartment cover securing with the screw that was removed earlier.
Figure 7
SECTION 5
Completing the Installation
1b. Internal Wire Compartment: Using a 7/16" socket, remove the two
hex nuts holding the blower assembly in place. Lift up on the
assembly and slide it out of the tabs on the housing (Figure 8).
Remove the wire compartment cover screw and place the cover
in a secure place (Figure 9).
1. If the fan’s blower assembly was removed during the wiring
process, reinstall the blower by reversing the directions in Section
4 (Wiring), Step 1b.
2. Plug the fan’s quick connect motor cord into the receptacle. This
cord will only fit one way into the receptacle (Figure 11).
Plug
Tabs
Hex Nuts
Figure 8
Figure 11
NOTE: If the fan motor plug is connected to the fan housing receptacle,
unplug so the blower assembly can be completely removed.
3. Install the ceiling mounting flange to cover any gaps which exist
between the housing and the finished ceiling. Line up the slots in
the ceiling mounting flange with the screws on the inside of the
210572051 Rev. A 8-05
3 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
housing and press flange in place so it is tight against the ceiling.
Tighten both screws inside the housing. Install drywall screws (not
included) through the holes in the flange and into the ceiling. Install
as many drywall screws needed to ensure the flange fits tightly
against the ceiling (Figure 12).
SECTION 6
Use and Care
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE
PANEL BEFORE SERVICING THE UNIT.
1. Cleaning the Grill: Remove grill and use a mild detergent, such as
dishwashing liquid, and dry with a soft cloth. NEVER USE ANY
ABRASIVE PADS OR SCOURING POWDERS. Completely dry grill
before reinstalling. Refer to instructions in Section 5 Finishing the
Installation, to reinstall grill.
Screws
2. Cleaning the Fan Assembly: Wipe all parts with a dry cloth or gently
Ceiling
vacuum the fan. NEVER IMMERSE ELECTRICAL PARTS IN WATER.
Mounting
Flange
Slots
Drywall Screw
Figure 12
4. Install the grill by squeezing the two ends of the springs together
and installing them up into the slots on the fan’s housing. Push the
grill up into position (Figure 13).
Figure 13
5. Restore power and test your installation.
Troubleshooting Guide
Trouble
Probable Cause
Suggested Remedy
1. Fan does not operate when the switch is on.
1a. A fuse may be blown or a circuit tripped.
1a. Replace fuse or reset circuit breaker.
1b. Connector plug from motor is not plugged in.
1b. Turn off power to unit. Remove Grill and plug motor into receptacle
in housing. Restore power to unit.
1c. Wiring is not connected properly.
1d. Motor has stopped operating.
2. Obstruction in the exhaust ducting.
1c. Turn off power to unit. Check that all wires are connected.
1d. Replace motor.
2. Fan is operating, but air moves slower than normal.
3. Fan is operating louder than normal.
2. Check for any obstructions in the ducting. The most common are bird nests
in the roof cap or wall cap where the fan exhausts to the outside.
3a. Motor is loose.
3a. Turn off power to unit. Remove grill and check that all screws are fully
tightened. Restore power to unit.
3b. Fan blade is hitting housing of unit.
3b. Call your dealer for service.
210572051 Rev. A 8-05
4 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY
All products manufactured by Air King Limited are warranted for one year from the date of purchase against defects in workmanship and/or
material. In addition, all ventilating/exhaust fans, heaters, combination fan lights and/or heaters, and range hoods are guaranteed for five years
from the date of purchase against defects in workmanship and/or material.
This warranty does not cover any labor or shipping costs or the cost of replacement components as part of routine maintenance such as: range
hood grease filters, charcoal filters or combination charcoal/grease filters; replacement light bulbs in range hoods or bathroom fan/light/bulb
heater combinations. As well, any damage or failure caused by abuse, misuse, abnormal usage, faulty installation, or improper maintenance
will not be covered by this warranty.
In order to make a claim on this warranty, you must be the original consumer of the product. You will be required to present to Air King the
original bill of sale showing: date of purchase, place of purchase and model purchased. Failure to meet these requirements will void your
warranty.
Air King will not be held responsible for any bodily injury or damages to personal property or real estate whether caused directly or indirectly
by the product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages and some states do
not allow limitations on how long an implied warranty lasts, so these exclusions or limitations may not apply to you. This warranty gives you
specific legal rights and you may have other rights which vary from state to state and province to province.
FOR PARTS OR TECHNICAL ASSISTANCE
Please call: 1-800-465-7300, MONDAY THROUGH FRIDAY, BETWEEN THE HOURS OF 8 AM AND 4:00 PM EST.
PLEASE DO NOT RETURN PRODUCT TO PLACE OF PURCHASE.
Reference the type and style of product (located on label inside of the product) when you call.
For more information please visit our website: wwwairkinglimited.com
Installer: _________________________________________________________ Installation Date:_________________________________________
Place of Purchase: _________________________________________________ Model Number: __________________________________________
210572051 Rev. A 8-05
5 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
REPLACEMENT PARTS DIAGRAM
2
1
27
3
24
24
3
5
26
6
8
2
4
29
23
28
15
7
24
22
16
17
14
13
25
18
19
11
21
20
12
9
10
#
1
2
3
4
5
6
7
8
Qty. Description
Replacement Part #
5S1202044
5S1202045
5S1202041
5S5202007
5S5202003
5S5202008
5S5202009
5S5202010
5S1202046
5S1202048
5S1202049
5S1202050
5S1202031
5S1202032
5S2202022
5S2202023
5S2202014
#
18
Qty. Description
Replacement Part #
5S2202024
5S2202025
5S2202020
5S2202027
5S2202017
5S2202012
5S2202010
5S1202051
5S1202004
5S1202052
5S1999010
5S1202053
5S1202054
5S1202007
5S1999003
5S1999002
1
2
4
1
2
1
2
1
2
1
2
1
2
2
1
1
1
Fan Housing
Mounting Bar
Nuts
Metal Collar
Bushing
Spring
Damper
Rod
Grill Springs
Grill
Flange Screw
Ceiling Flange
Nuts
Blower Grommet
Blower Housing
Blower Wheel
Nut
1
1
1
3
5
1
1
1
1
1
6
1
1
1
1
1
Motor - AK150LS, AK200LS
Motor - AK300LS
Motor Plate
Screw
Screw
Motor Cap Harness - AK150LS
Motor Cap Harness - AK200LS
Motor Cap Harness - AK300LS
Internal Wire Cover - AK150LS, AK200LS
Internal Wire Cover - AK300LS
Screw
19
20
21
22
9
23
10
11
12
13
14
15
16
17
24
25
26
27
28
29
Outlet Gasket
Collar Gasket
External Wire Cover
14 ga Ground Wire
#10 Ground Screw
210572051 Rev. A 8-05
6 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTRUCTIONS IMPORTANTES –
MANUEL D’OPÉRATION
Modéles: AK150LS,
Ventilateur d’Évacuation
AK200LS, AK300LS
LIRE ET CONSERVER CES INSTRUCTIONS
LIRE SOIGNEUSEMENT AVANT DE TENTER D’ASSEMBLER, INSTALLER, OPÉRER OU DE RÉPARER LE PRODUIT DÉCRIT. PROTÉGEZ
VOUS-MÊME ET LES AUTRES EN OBSERVANT TOUTE L’INFORMATION DE SÉCURITÉ. FAILLIR À SE CONFORMER AUX
INSTRUCTIONS PEUT RÉSULTER EN BLESSURE PERSONNELLE GRAVE ET/OU EN DOMMAGE À LA PROPRIÉTÉ.
CONSERVER CES INSTRUCTIONS POUR RÉFÉRENCES FUTURES.
INSTRUCTIONS GÉNÉRALES DE SÉCURITÉ
Lors de l’utilisation d’appareils électriques, des précautions de base doivent
toujours être suivies pour réduire les risques d’incendie, de choc
électrique et de blessures corporelles, incluant ce qui suit:
1. Bien lire toutes les instructions avant d’installer ou d’utiliser
le ventilateur d’évacuation.
2. Utiliser cette unité seulement de la manière pour laquelle le
fabricant l’a conçu. Si vous aviez des questions, veuillez
contacter le fabricant.
AVERTISSEMENT:POUR USAGE DE VENTILATION
GÉNÉRALE EXCLUSIVEMENT. NE PAS UTILISER POUR ÉVACUER
DU MATÉRIEL ET DES VAPEURS DANGEREUSES OU EXPLOSIVES.
6. Lors de coupe ou de perçage des murs et plafonds, ne pas
endommager le filage électrique et autres utilités cachées.
3. Avant d’effectuer un service ou de nettoyer l’unité, couper
l’alimentation électrique dans le panneau de distribution et
verrouiller le dispositif de déconnexion afin d’éviter que
l’alimentation ne revienne accidentellement. Lorsque le
dispositif ne peut être verrouillé, fixer solidement un avis
d’avertissement, tel qu’une étiquette, au panneau de distribution.
4. Le travail d’installation et le câblage électrique doivent être
effectués par une(des) personne(s) qualifiée(s) en conformité
avec tous les codes et normes applicables, incluant la
construction relative aux incendies.
5. De l’air en quantité suffisante est requis pour la bonne
combustion et l’évacuation de gaz par le conduit (cheminée)
provenant d’équipement de brûlage au combustible pour
prévenir un refoulement. Suivre les directives du fabricant
de l’équipement de chauffage et les normes de sécurité telles
que celles publiées par la National Fire Protection Association
(NFPA) et de la American Society for Heating, Refrigeration,
and Air Conditioning Engineers (ASHRAE), et de celles des
autorités locales du code.
7. Les ventilateurs avec conduits doivent toujours être évacués
vers l’extérieur.
8. Cette unité doit être mise à la terre.
9. Pour éviter des dommages aux roulements des moteurs et/ou
des hélices bruyantes ou déséquilibrées, empêcher la
poussière de cloison sèche, poussière de construction, etc.,
d’atteindre l’unité de puissance.
AVERTISSEMENT: POUR RÉDUIRE LES RISQUES
D’INCENDIE OU DE CHOC ÉLECTRIQUE, NE PAS UTILISER CE
VENTILATEUR AVEC UN RÉGULATEUR DE VITESSE ÉLECTRONIQUE.
10. Acceptable pour utilisation au-dessus d’une baignoire ou
d’une douche lorsque installé dans un circuit protégé par un
disjoncteur de fuite de terre.
11. NE JAMAIS placer un interrupteur à un endroit qui puisse
être atteint de la baignoire ou de la douche.
AVERTISSEMENT: NE PAS UTILISER DANS LES CUISINES
CONSERVER CES INSTRUCTIONS
210572051 Rev. A 8-05
7 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTRUCTIONS D’INSTALLATION
Support
Châssis
Écrou
AVERTISSEMENT:VOUS ASSURER QUE L’ALIMENTATION
EST COUPÉE AU PANNEAU DE SERVICE AVANT DE COMMENCER
L’INSTALLATION.
SECTION 1
Préparation du Ventilateur d’évacuation
1. Sortir le ventilateur de sa boite et confirmer que toutes les pièces
sont présentes. En plus du ventilateur d’évacuation vous devriez avoir:
1 - Grille
1 - Ensemble de clapet (attaché)
2 - Supports de montage
1 - Bride de montage
4 - Écrous 10-32
1 - Feuillet d’instructions / sécurité
Solive
Figure 3
1c. Installation sur des solives de 61 cm (24 po) au centre ou plus
larges que des solives de 40,6 cm (16 po): Installer deux chevêtres
de 5,08 cm x 10,16 cm (2x4 po) (non-compris) entre les solives
(Figure 4). Installer les supports de montage dans le second jeu de
fentes sur le châssis du ventilateur et fixer en place avec les quatre
écrous #10-32 inclus tel qu’indiqué. Centrer le châssis du ventilateur
entre les solives et fixer les supports de montage avec des vis ou
des clous (non-compris) au chevêtre. Ajuster la hauteur du châssis
pour qu’il soit à effleurement avec le plafond fini en desserrant les
écrous de support de montage et en glissant le châssis vers le
haut ou vers le bas sur le support de montage. Serrer à fond tous
les quatre écrous pour fixer le châssis en place. (Figure 5).
2. Choisir un emplacement pour votre ventilateur. Pour assurer la
meilleure performance du débit d’air et sonore, il est recommandé
que la longueur des conduits et que le nombre de coudes soient
gardés au minimum et que des conduits rigides isolés soient utilisés.
Ce ventilateur nécessitera au moins
20,3cm (8po) de dégagement dans le
plafond ou le mur, et s’installe au travers
de cloison sèche d’une épaisseur de
jusqu’à 1,9cm (3/4po).
3. Sélectionner l’alvéole défonçable la
mieux appropriée et l’enlever à l’aide d’un
tournevis à lame plate (Figure 1).
Solive
SECTION 2
Figure 1
Chevêtre de
5,08 cm x 10,16 cm
(2x4 po)
Montage du Châssis
1a. Installation sur des solives en 5,08 cm x 10,16 cm (2x4 po) au centre
de 40,6 cm (16 po): Installer les supports de montage dans le second
jeu de fentes sur le châssis du ventilateur et fixer en place avec les
quatre écrous #10-32 inclus tel qu’indiqué. Centrer le châssis du
ventilateur entre les solives et fixer les supports de montage avec
des vis ou des clous (non-compris) à la solive. Ajuster la hauteur du
châssis pour qu’il soit à effleurement avec le plafond fini en desserrant
les écrous de support de montage et en glissant le châssis vers le
haut ou vers le bas sur le support de montage. Serrer à fond tous
les quatre écrous pour fixer le châssis en place. (Figure 2).
Plafond
Solive
Figure 4
Support
Châssis
Support
Châssis
Écrou
Écrou
Chevêtre
Figure 5
Solive
Figure 2
SECTION 3
Conduits
1b. Installation sur des solives en 5,08 cm x 15,24 cm (2x6 po) au centre
de 40,6 cm (16 po): Installer les supports de montage dans le second
jeu de fentes sur le châssis du ventilateur et fixer en place avec les
quatre écrous #10-32 inclus tel qu’indiqué. Centrer le châssis du
ventilateur entre les solives et fixer les supports de montage avec
des vis ou des clous (non-compris) à la solive. Ajuster la hauteur du
châssis pour qu’il soit à effleurement avec le plafond fini en desserrant
les écrous de support de montage et en glissant le châssis vers le
haut ou vers le bas sur le support de montage. Serrer à fond tous
les quatre écrous pour fixer le châssis en place. (Figure 3).
AVERTISSEMENT: TOUS LES CONDUITS DOIVENT ÊTRE
CONFORMES AUX CODES DU BÂTIMENT LOCAUX ET NATIONAUX.
1. Raccorder le conduit au collet de conduit du ventilateur (Figure 6).
Fixer en place à l’aide de ruban ou de serre-joint. Toujours évacuer
le ventilateur vers l’extérieur au travers de chapeau mural ou de toit.
210572051 Rev. A 8-05
8 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Couvercle du
Compartiment de
Câblage
Conduits
Vis
Collet du
Conduit
Figure 9
2. Courir le câblage d’un commutateur mural approuvé et de capacité
appropriée. Un neutre (blanc), un de mise à la terre (vert ou cuivre
nu), et un vivant (fil noir raccordé à l’interrupteur mural). Fixer les
câbles électriques au châssis avec un connecteur électrique
approuvé. Vous assurer de laisser suffisamment de câble dans la
boîte pour faire le raccordement au réceptacle du ventilateur.
Figure 6
SECTION 4
Câblage
3. Par là où vous avez choisi d’accéder à la boîte de jonction du
ventilateur, connecter le fil blanc provenant de la résidence au fil
blanc du réceptacle du ventilateur. Connecter le fil noir de
l’interrupteur mural au fil noir du réceptacle du ventilateur. Connecter
le fil de mise à la terre provenant de la résidence au fil vert du
réceptacle du ventilateur (Figure 10). Utiliser des méthodes
approuvées pour toutes les connexions.
AVERTISSEMENT:VOUS ASSURER QUE L’ALIMENTATION
EST COUPÉE AU PANNEAU DE SERVICE AVANT DE COMMENCER
L’INSTALLATION.
AVERTISSEMENT:TOUTES LES CONNEXIONS DOIVENT
ÊTRE FAITES EN CONFORMITÉ AVEC LES CODES ÉLECTRIQUES LOCAUX
OU NATIONAUX. SI VOUS N’ÊTES PAS FAMILIER AVEC LES MÉTHODES
D’INSTALLATION DE CÂBLAGE ÉLECTRIQUE, RECOURREZ AUX
SERVICES D’UN ÉLECTRICIEN QUALIFIÉ.
Alimentation provenant
de la résidence
REMARQUE: Cette unité possède un panneau d’accès latéral pour le
câblage qui ne requiert pas l’enlèvement de l’assemblage de la soufflante
du ventilateur. Si vous choisissez de raccorder l’unité par l’intérieur, vous
aurez besoin d’enlever l’assemblage de la soufflante et le compartiment
de câblage intérieur. Les deux méthodes sont également efficaces.
Fil de Masse
Blanc
1a. Compartiment de Câblage Extérieur : Enlever la vis du couvercle
du compartiment à câblage et mettre ce couvercle dans un endroit
fiable (Figure 7).
Fil Chaud (Noir)
Figure 10
REMARQUE: Les fils du réceptacle du ventilateur pourraient nécessiter
d’être tirés à l’extérieur du compartiment pour le raccordement. Tirer
uniquement les trois fils lâches à l’extérieur du compartiment. Des fils
additionnels y sont présents.
Vis
4. Regrouper soigneusement les fils à l’intérieur du compartiment
pour le raccordement et replacer le couvercle du compartiment
en le fixant avec la vis qui fut enlevée précédemment.
Couvercle du
Compartiment
de Câblage
SECTION 5
Figure 7
Complétion de l’installation
1b. Compartiment de Câblage Intérieur: Enlever les trois vis retenant
en place l’assemblage de la soufflante et soulever pour sortir
l’assemblage hors du châssis (Figure 8). Enlever la vis du couvercle
du compartiment à câblage et mettre ce couvercle dans un endroit
fiable (Figure 9).
1. Si l’assemblage de la soufflante du ventilateur a été enlevé durant
le processus de raccordement, réinstaller la soufflante en inversant
les instructions à l’étape 1b de la Section 4 Câblage.
2. Brancher le cordon à raccordement rapide dans le réceptacle. Ce cordon
ne s’ajuste que d’une seule façon dans le réceptacle (Figure 11).
Raccord
Onglets
Écrou
Hexagonal
Figure 11
Figure 8
3. Installer la bride de montage du plafond pour couvrir tout espacement
qui existe entre le châssis et le plafond fini. Aligner les fentes dans
la bride de montage du plafond avec les vis à l’intérieur du châssis
REMARQUE: Si le raccord du moteur de ventilateur est raccordé au
réceptacle du châssis, le débrancher afin que l’assemblage de la
soufflante soit complètement enlevé.
210572051 Rev. A 8-05
9 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
et presser la bride en place de sorte qu’elle soit bien serrée contre
le plafond. Serrer les deux vis à l’intérieur du châssis. Installer des
vis pour cloison sèche (non-comprises) au travers des trous dans
la bride et dans le plafond. Installer autant de vis pour cloison
sèche que requis pour assurer que la bride s’ajuste solidement
contre le plafond. (Figure 12).
SECTION 6
Utilisation et entretien
AVERTISSEMENT:VOUS ASSURER QUE L’ALIMENTATION
EST COUPÉE AU PANNEAU DE SERVICE AVANT DE COMMENCER
L’INSTALLATION.
1. Nettoyage de la grille: Retirer la grille et utiliser un détergent doux,
tel que du liquide pour la vaisselle, puis sécher à l’aide d’un chiffon
doux. NE JAMAIS UTILISER D’ABRASIF OU DE POUDRE À RÉCURER.
Sécher complètement la grille avant de la réinstaller. Pour réinstaller
la grille, vous référer à la Section 6 - Complétion de l’installation.
Vis
2. Nettoyage de l’assemblage du ventilateur: Nettoyer toutes les
parties à l’aide d’un chiffon sec ou passer délicatement l’aspirateur
sur le ventilateur. NE JAMAIS IMMERGER LES PARTIES
ÉLECTRIQUES DANS L’EAU.
Bride de
Montage du
Plafond
Fentes
Vis pour
Cloison Sèche
Figure 12
4. Installer la grille en pressant ensemble les deux extrémités des
ressorts et en les installant dans les fentes du châssis du ventilateur.
Pousser la grille en position (Figure 13).
Figure 13
5. Restaurer l’alimentation et tester votre installation.
Guide de dépannage
Trouble
1. Le ventilateur ne fonctionne pas lorsque
l’interrupteur est à la position en marche.
Cause Possible
Solution Suggérée
1a. Remplacer le fusible ou réinitialiser le disjoncteur.
1a. Un fusible peut être grillé ou un disjoncteur
peut être décle.nché.
1b. La fiche de raccord du moteur n’est
pas connectée.
1b. Couper l’alimentation à l’unité. Retirer la grille et brancher le moteur dans
le réceptacle dans le cabinet. Remettre l’alimentation sur l’unité.
1c. Le câblage n’est pas raccordé correctement.
1d. La moteur est terminee
1c. Couper l’alimentation de l’unité. Vérifier que tous les fils sont raccordés.
1d. Remplacez la moteur
2. Le ventilateur fonctionne, mais l’air circule
plus lentement que la normale.
2. Obstruction dans les conduits d’évacuation.
2. Vérifier pour toute obstruction dans les conduits. Les plus courantes sont
des nids d’oiseau dans le chapeau de toit ou mural là où le ventilateur
s’évacue vers l’extérieur.
3. Le ventilateur fonctionne de manière plus
bruyante que la normale.
3a. Le moteur est lâche.
3a. Couper l’alimentation à l’unité. Retirer la grille et vérifier que toutes les
vis sont complètement serrées. Remettre l’alimentation sur l’unité.
3b. L’hélice du ventilateur frotte contre le cabinet de l’unité.
3b. Appeler votre marchand pour un service.
210572051 Rev. A 8-05
10 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
GARANTIE LIMITÉE
Tous les produits fabriqués par Air King Limited sont garantis pour un an à partir de la date d’achat contre les défauts de main d’œuvre et/ou
de matériel. De plus, tous les ventilateurs / évacuateurs, chaufferettes, combinés ventilateur/ lumière et/ou les chaufferettes et les hottes de
cuisine sont garantis pour cinq années à partir de la date d’achat contre les défauts de main d’œuvre et/ou de matériel.
Cette garantie ne couvre pas de coûts de transport ou de main d’œuvre ou le coût de remplacement de composantes faisant partie d’entretien
de routine tels que : Filtres à graisse des hottes de cuisine, filtres au charbon ou combiné filtre à graisse/ charbon ; ampoules électriques de
remplacement dans les hottes de cuisine ou les combinés ventilateur/ lumière/ chaufferette pour salle de bain. Aussi, tout dommage ou
défaillance causé par un abus, une mauvaise utilisation, une installation fautive ou un entretien incorrect ne sera pas couvert par cette garantie.
De manière à effectuer une réclamation sous cette garantie, vous devez être l’acheteur original du produit. Il vous sera exigé de présenter la
facture d’achat originale à Air King, qui démontrera : La date d’achat, l’endroit de l’achat et le modèle acheté. Le manquement à rencontrer
ces exigences annulera votre garantie.
Air King ne sera pas tenu responsable de quelque blessure corporelle ou dommage à la propriété ou à l’immeuble que ce soit causé directement
ou indirectement par le produit. Certains États ne permettent pas de limitation sur la durée de la garantie implicite, ou l’exclusion ou la limitation
de dommages indirects ou accessoires, ainsi, ces limitations et exclusions peuvent ne pas s’appliquer à vous. Cette garantie vous donne des
droits légaux spécifiques et vous pouvez aussi avoir des droits qui varient d’un État à l’autre et d’une province à l’autre.
POUR DES PIÈCES OU DE L’ASSISTANCE TECHNIQUE
Veuillez appeler au 1-800-465-7300, DU LUNDI AU VENDREDI ENTRE 8:00 HRE ET 16:00 HRE HNE.
VEUILLEZ NE PAS RETOURNER CE PRODUIT À L’ENDROIT DE L’ACHAT D’ORIGINE.
Référencer le type et le style du produit (localisé sur l’étiquette à l’intérieur du produit) lorsque vous appelez.
Installateur: ______________________________________________________ Date d’installation: _______________________________________
Endroit de l’achat: _________________________________________________ Numéro de modèle:_______________________________________
210572051 Rev. A 8-05
11 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
DIAGRAMME DES PIÈCES DE REMPLACEMENT
2
1
27
3
24
24
3
5
26
6
8
2
4
29
23
28
15
7
24
22
16
17
14
13
25
18
19
11
21
20
12
9
10
# de pièce
# de pièce
#
1
2
3
4
5
6
7
8
Qté. Description
de remplacement
5S1202044
5S1202045
5S1202041
5S5202007
5S5202003
5S5202008
5S5202009
5S5202010
5S1202046
5S1202048
5S1202049
5S1202050
5S1202031
5S1202032
5S2202022
5S2202023
5S2202014
#
18
Qté. Description
de remplacement
1
2
4
1
2
1
2
1
2
1
2
1
2
2
1
1
1
Cabinet du ventilateur
Barre de montage
Écrou
Collet de Métal
Bague
Ressort
Clapet
Barre
Ressorts de la grille
Grille
Vis de la bride
Bride du plafond
Écrou
Passe-fil de la Soufflante
Cabinet de la Soufflante
Roue de la Soufflante
Écrou
1
1
1
3
5
1
1
1
1
1
6
1
1
1
1
1
Moteur - AK150LS, AK200LS
Moteur - AK300LS
Plaque de Moteur
Vis
Vis
Harnais du Capuchon du Moteur - AK150LS
Harnais du Capuchon du Moteur - AK200LS
Harnais du Capuchon du Moteur - AK300LS
Couvercle de Câble Interne - AK150LS, AK200LS
Couvercle de Câble Interne - AK300LS
Vis
Joint - Extérieur
Joint – Collet
Couvercle de Câble Externe
Fil de mise à la terre de calibre # 14
Vis #10 de mise à la terre
5S2202024
5S2202025
5S2202020
5S2202027
5S2202017
5S2202012
5S2202010
5S1202051
5S1202004
5S1202052
5S1999010
5S1202053
5S1202054
5S1202007
5S1999003
5S1999002
19
20
21
22
9
23
10
11
12
13
14
15
16
17
24
25
26
27
28
29
210572051 Rev. A 8-05
12 of 12
Download from Www.Somanuals.com. All Manuals Search And Download.
|