#90111 1109
LEM-1DL Supplemental Instructions
Single Master Station with Door Release
- REFER TO INSTALLATION MANUAL INSIDE LEM-1DL BOX FOR STANDARD
INSTALLATION INFORMATION -
The LEM-1DL master station provides communication to and from a door station, and has a separate button
for door release. This supplemental instruction manual addresses many of the additional functions and
modifications for the LEM-1DL system, including installation and troubleshooting information.
MASTER STATION:
LEM-1DL:
1-call master station with “Normally Open” door release button
DOOR STATIONS: (Note: Door stations are weather resistant, made for outdoor use)
LE-D:
LE-DA:
Surface mount, plastic door station (included with LEM-1DLS Set)
Flush mount in 2-gang box, stainless steel cover
LS-NVP/C:
LE-SS:
LE-SSR:
Vandal resistant flush mount in 3-gang box, white powder-coat finish
Vandal resistant flush mount sub in 2-gang box, stainless steel
Vandal resistant, red mushroom button, flush mount in 2-gang box,
stainless steel
LEM-1DL
LE-SS-1G:
Vandal resistant flush mount sub in 1-gang box, stainless steel
OPTIONAL COMPONENTS & ACCESSORIES:
RY-AC/A:
DAK-2S:
External signaling relay (Requires 12VDC power supply)
Dual master adaptor kit
(1 per 2 master stations. Use 2 DAK-2S for up to 4 total master stations)
Surface mount box for LS-NVP/C
Surface mount box for LE-SS, LE-SSR, LE-DA
Surface mount box for LE-SS-1G
Door strike (for interior wood frame doors only)
AC 12V Transformer (used for door strike and for each master station)
12V DC Power Supply, 2.5A, UL Listed
LE-D
LE-DA
LE-SS
SBX-NVP:
SBX-2G:
SBX-1G-SS:
EL-12S:
PT-1210N:
PS-1225UL:
822202:
LS-VNP/C
2 conductor, 22AWG, Shielded wire
(Available in 500’ and 1000’ boxes)
Install two separate runs of this cable, one for the intercom and one for
the door release.
DAK-2S
(2 component modules per kit)
DOOR RELEASE WIRES MUST BE IN A SEPARATELY JACKETED CABLE FROM THE INTERCOM WIRING.
LEM-1DL
LEM-1DLS Set contains:
1 LEM-1DL, 1 LE-D, 1 PT-1210N.
Door strike not included.
LE-D
2 cond. shielded for intercom
PT-1210N
Power
Source
for Strike
Separate 2 conductor for door release
If using a non-Aiphone door strike, use separate power
source for door release mechanism.
!
LEM-1DL Supplement
Pg. 1
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAM: LEM-1DL System with External Signaling using RY-AC Relay
Component
Module
LE-D
LEM-1DL
1
1
Output of RY-AC (Yellow
wires) provide a momentary
dry contact closure while
the call button on the door
station is being pressed.
E
-
E
NOTE: Intercom must be
powered with a 12VDC
power suplly when RY-AC
is connected.
PS-1225UL
Leave
E/- jumper
attached
White
Red
BELL
+
-
+
-
RY-AC
Black
Power source
for bell
Normally Open Dry
Contact to door
strike and power
EL
EL
Component Module
If a DAK-2S is not available, install components as shown below.
Capacitor: 25V, 15-33ufd Non-polarized
Diode: 1N4148
To 1 of LE-D and
WHITE wire of RY-AC
To 1 of LEM-1DL
SYSTEM CONFIGURATION:
LEM-1DL with Door Release contact activating a Normally Closed relay for a Magentic Lock
Note: For applications requiring a Normally Closed (N/C) contact (Magnetic locks, etc.), an external
relay should be chosen based on the lock’s power source.
- When using a 12-18V DC magnetic lock, Aiphone’s RY-18L relay may be used.
- For 24V DC magnetic locks, Aiphone’s RY-24L relay may be used.
- A 3rd party relay of similar specifications may also be used. Refer to manufacturer’s
documentation for connection details.
LE Series Sub
LEM-1DL
1
1
E
-
E
Leave
E/- jumper
attached
+
-
LOCK
POWER
EL
EL
+
-
RY-18L / RY-24L
MAGNETIC LOCK WIRING METHOD:
(Normally Closed Contact)
Lock Power: Power source for Magnetic Lock
When using 12-18V DC, use the RY-18L
When using 24-36V DC, use the RY-24L
Red
Blk
Magnetic Lock
Brn
Org
COM
N/C
Yel
Use Brown & Yellow wires
when connecting to a Maglock.
LEM-1DL Supplement
Pg. 3
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION TIPS:
1. Use shielded wire for the communication path, and ground one end of the shield to an earth ground.
2. Run intercom wire at least 20” away from AC wiring, fluorescent lights or dimmer switches.
3. Keep intercom cable away from alarm, data, phone, and video cables.
4. Door release wires must be in a separately jacketed cable from the intercom wires. Use two separate
cables; one for audio and one for door release.
5. When installing a second master station, wire must be run from the first master station, not from the
door station. See diagram on page 2.
6. Do not install master station near light switches, dimmer switches, or other devices that may cause
interference with the intercom system.
7. Do not install the master station on the opposite wall from the door station. If the units are too close,
acoustical feedback may result.
TROUBLESHOOTING GUIDE:
PROBLEM
POSSIBLE CAUSE
SOLUTION
(A) Press OFF button on master. If call tone still doesn’t come
through, read solution (B).
(B) Make sure jumper is attached to E/- terminals on door
(A) OFF button on master not pressed. station (or proper wires jumpered on LS-NVP, LE-SS subs).
No call tone from door to master station.
No communication from door station.
(B) E/- jumper not attached.
Wire from E/- should be connected to E of master.
Ensure that the jumper at the door station is attached between
E and - terminals
E/- jumper not attached
No call tone, no communication. Chirping
sound when volume control is turned all the
way up.
Check power supply. If it’s a model SKK-620, remove and
replace with model PT-1210N. Verify that voltage on +/-
terminals is between 12-16V AC or 12-24V DC.
Wrong voltage on LEM-1DL
In a system with RY-AC and external signaling
device connected, the external device is
activated every time TALK button is pressed.
Make sure the component module is installed with the bare
DAK-2S component module missing or wire under the 1 terminal and the white wire of the RY-AC
installed incorrectly.
spliced to the colored wire.
In a dual master system, call tone is heard
at the second master when pushing the talk
button on one master.
Install 1 component module from the DAK-2S at each master.
See Pg. 2. If DAK-2S is not available, connect specified diode
and capacitor in parallel and install as shown on PG. 3.
Missing DAK-2S dual master adaptor
kit.
Ensure that each master has its own power supply. Use any
power supply with output between 12-16V AC or 12-24V DC.
Aiphone recommends the PT-1210N.
In a dual master system, feedback occurs
when pressing the talk button.
One power supply is used for both
masters.
Ensure that the intercom wire is run at least 20” from any AC
electircal wire, or crossed at 90 degrees. Intercom wire should
be shielded, with the drain wire connected to an earth ground
Intercom wiring run close to AC wiring. at the master end.
AC noise when listening to the door station
AC noise when talking to the door station
Ensure that power wires coming from the PT-1210N are not
Power wires run with communication
wires.
run in the same jacket cable with the communication wires run
to the door.
Aiphone Communcation Systems
1700 130th AVE N.E.
Bellevue, WA 98005
(425) 455-0510
LEM-1DL Supplement
Pg. 4
Toll Free Technical Support:
1-800-692-0200
E-mail [email protected]
#90111
1109JD
FAX (425) 455-0071