ADT Security Services Smoke Alarm ADT LCD40 User Manual

ADT Security Services, Inc.  
One Town Center Road  
Boca Raton, FL 33431  
Phone: (561) 988-3600  
FAX: (561) 988-3675  
ADT-LCD40 Series  
Remote Fire  
Annunciators  
for use with Unimode 200  
Addressable Fire Alarm Control Panel  
FIRE ALARM ANNUNCIATOR  
Drill  
Ack  
Silence  
Reset  
Hold  
2
sec.  
Document #50520  
D
7/25/00  
Rev:  
P/N 50520:D ECN 00-325  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adherence to the following will aid in problem-free  
installation with long-term reliability:  
Installation Precautions  
WARNING - Several different sources of power can be  
connected to the fire alarm control panel. Disconnect all  
sources of power before servicing. Control unit and  
associated equipment may be damaged by removing  
and/or inserting cards, modules, or interconnecting  
cables while the unit is energized. Do not attempt to  
install, service, or operate this unit until this manual is  
read and understood.  
Like all solid state electronic devices, this system may  
operate erratically or can be damaged when subjected  
to lightning-induced transients. Although no system is  
completely immune from lightning transients and inter-  
ferences, proper grounding will reduce susceptibility.  
Overhead or outside aerial wiring is not recommended,  
due to an increased susceptibility to nearby lightning  
strikes. Consult with the Technical Services Department  
if any problems are anticipated or encountered.  
CAUTION - System Reacceptance Test after Software  
Changes. To ensure proper system operation, this  
product must be tested in accordance with NFPA 72  
Chapter 7 after any programming operation or change in  
site-specific software. Reacceptance testing is required  
after any change, addition or deletion of system compo-  
nents, or after any modification, repair or adjustment to  
system hardware or wiring.  
Disconnect AC power and batteries prior to removing  
or inserting circuit boards. Failure to do so can damage  
circuits.  
Remove all electronic assemblies prior to any drilling,  
filing, reaming, or punching of the enclosure. When  
possible, make all cable entries from the sides or rear.  
Before making modifications, verify that they will not  
interfere with battery, transformer, and printed circuit  
board location.  
All components, circuits, system operations, or software  
functions known to be affected by a change must be  
100% tested. In addition, to ensure that other operations  
are not inadvertently affected, at least 10% of initiating  
devices that are not directly affected by the change, up  
to a maximum of 50 devices, must also be tested and  
proper system operation verified.  
Do not tighten screw terminals more than 9 in-lbs.  
Over-tightening may damage threads, resulting in  
reduced terminal contact pressure and difficulty with  
screw terminal removal.  
Though designed to last many years, system compo-  
nents can fail at any time. This system contains static-  
sensitive components. Always ground yourself with a  
proper wrist strap before handling any circuits so that  
static charges are removed from the body. Use static-  
suppressive packaging to protect electronic assemblies  
removed from the unit.  
This system meets NFPA requirements for operation  
at 0-49° C/32-120° F and at a relative humidity of 85%  
RH (non-condensing) at 30°C/86° F. However, the  
useful life of the system's standby batteries and the  
electronic components may be adversely affected by  
extreme temperature ranges and humidity. Therefore,  
it is recommended that this system and all peripherals  
be installed in an environment with a nominal room  
temperature of 15-27° C/60-80° F.  
Follow the instructions in the installation, operating,  
and programming manuals. These instructions must  
be followed to avoid damage to the control panel and  
associated equipment. FACP operation and reliability  
depend upon proper installation by authorized personnel.  
Verify that wire sizes are adequate for all initiating and  
indicating device loops. Most devices cannot tolerate  
more than a 10% I.R. drop from the specified device  
voltage.  
FCC Warning  
Canadian Requirements  
WARNING: This equipment generates, uses, and  
can radiate radio frequency energy and if not in-  
stalled and used in accordance with the instruction  
manual, may cause interference to radio commu-  
nications. It has been tested and found to comply  
with the limits for class A computing device pursu-  
ant to Subpart B of Part 15 of FCC Rules, which is  
designed to provide reasonable protection against  
such interference when operated in a commercial  
environment. Operation of this equipment in a  
residential area is likely to cause interference, in  
which case the user will be required to correct the  
interference at his own expense.  
This digital apparatus does not exceed the  
Class A limits for radiation noise emissions from  
digital apparatus set out in the Radio Interfer-  
ence Regulations of the Canadian Department  
of Communications.  
Le present appareil numerique n'emet pas de  
bruits radioelectriques depassant les limites  
applicables aux appareils numeriques de la  
classe A prescrites dans le Reglement sur le  
brouillage radioelectrique edicte par le  
ministere des Communications du Canada.  
LimWarSm.p65 01/10/2000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Document 50520 Rev D 7/25/00 P/N 50520:D  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Table of Contents  
Section 1: ADT-LCD40 Series Annunciators ...........................................6  
1.1 ADT-LCD40 and ADT-LCD40L ...................................................7  
1.2 ADT-LCD40 Only ..........................................................................7  
Figure 1-1: Components .......................................................8  
Figure 1-2: Wiring to Terminals ...........................................9  
1.3 SW1 DIP Switch Settings ...............................................................10  
Figure 1-3: DIP Switch Settings Example ............................11  
1.4 Typical Configuration .....................................................................12  
Figure 1-4: Typical Configuration ........................................12  
Section 2: Operation ...................................................................................13  
2.1 Display Patterns ..............................................................................13  
2.2 Switch Functions for ADT-LCD40 Only .......................................14  
2.2.1 Key-switch ..........................................................................14  
2.2.2 Acknowledge .......................................................................14  
2.2.3 Silence ..................................................................................15  
2.2.4 Drill: Hold 2 Sec. .................................................................15  
2.2.5 Reset .....................................................................................15  
2.3 LED Indicators (all ADT-LCD40 Series) .......................................16  
2.3.1 Power ...................................................................................16  
2.3.2 Fire Alarm ............................................................................16  
2.3.3 Supervisory ..........................................................................16  
2.3.4 Trouble .................................................................................16  
Section 3: Mounting ....................................................................................17  
3.1 ADT-LCD40 Series Preparation .....................................................17  
Figure 3-1: Trim Ring Removal ...........................................17  
Figure 3-2: Hardware and Backboxes ..................................18  
3.2 Semi-flush Mount Backbox ............................................................19  
Figure 3-3: Semi-flush Mounting .........................................19  
3.3 Surface Mount Backbox .................................................................20  
Figure 3-4: Surface Mounting ...............................................20  
Section 4: ADT-LCD40 Series Electrical Connections ............................21  
Figure 4-1: Power Connection ..............................................21  
Figure 4-2: EIA-485 Connection ..........................................22  
Figure 4-3: DIM-485 Connections .......................................23  
Figure 4-4: Wiring FACP to ADT-LCD40 Series ................24  
Section 5: EIA-485 Shield Termination ....................................................25  
5.1 EIA-485 Shield Not in Conduit ......................................................25  
Figure 5-1: EIA-485 Without Conduit ..................................26  
5.2 EIA-485 Shield in Full Conduit ......................................................27  
Figure 5-2: EIA-485 In Conduit ...........................................27  
Section 6: Programming the Unimode 200 ...............................................28  
Document 50520 Rev D 7/25/00 P/N 50520:D  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
Section 1:ADT-LCD40 Series Annunciators  
FIRE ALARM ANNUNCIATOR  
FIRE ALARM ANNUNCIATOR  
Drill  
sec.  
Ack  
Silence  
Reset  
Hold  
2
ADT-LCD40  
ADT-LCD40L  
Note: Only Model ADT-LCD40L is listed for use in Canada.  
The ADT-LCD40 Series Annunciators are compact, attractive,  
40-character, backlit LCD fire annunciators designed for use with the  
Unimode 200 Addressable Fire Alarm Control Panel. The  
ADT-LCD40L operates the same as the ADT-LCD40, except it does not  
have function switches or a key-switch. It should be noted that the  
ADT-LCD40 Series Annunciator displays will mimic the LCD display  
located on the Unimode 200 main circuit board.  
If software with Part Number #UNIMODE200V3.0 is installed in the  
ADT Unimode 200, the ADT-LCD40 Series Annunciator must have soft-  
ware with a Part Number of 73879 to operate with the control panel. If  
software with a Part Number of #UNIMODE200V4.0 or higher is  
installed in the Unimode 200, the ADT-LCD40 Series Annunciator must  
have software with a Part Number of #LCD40V2.0 or higher to operate  
with the control panel.  
The ADT-LCD40 Series is capable of displaying English-language text  
of system point status including device type, independent point alarm,  
trouble or supervisory, zone and custom alpha labels programmed into  
the control panel. The ADT-LCD40 Series also provide system status  
LEDs to display Power, Alarm, Trouble and Supervisory conditions.  
The ADT-LCD40 is capable of performing system acknowledge,  
silence, drill and reset remotely while the ADT-LCD40L does not have  
these features.  
Communication between the control panel and the ADT-LCD40 Series  
is accomplished over a two-wire serial interface employing the EIA-485  
communication standard. Up to 32 annunciators may be connected to  
the two-wire EIA-485 circuit. The annunciators may be powered from  
the host FACP or remote UL listed, filtered, power supplies.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
ADT-LCD40 and ADT-LCD40L  
1.1  
ADT-LCD40 and ADT-LCD40L  
• 40-character LCD display (20 characters x 2 lines) is backlit  
under normal and alarm conditions  
• System Status LEDs for Power (green), Alarm (red), Trouble  
(yellow) and Supervisory (yellow)  
• No programming necessary — duplicates messages at control  
panel display  
• Local piezo sounder with alarm and trouble resound  
• Device type identifiers from the control panel  
• Device & zone custom alpha labels from the control panel  
• Time/date and device address from the control panel  
• EIA-485 connects to control panel terminal port (requires  
DIM-485 module)  
• Plug-in terminal blocks for ease of installation and service  
• DIP switches control piezo enable/disable and transmit/receive  
mode  
• Up to 32 ADT-LCD40 Series Annunciators per Unimode 200  
• Mounting options:  
Surface mounting in SBB-3 (2.75" depth)  
Semi-flush mounting in three-gang electrical box (P/N  
10103) with a minimum depth of 2.187"  
Can be located up to 3,000 feet (900 m) from the panel  
• Backlight turns off during AC loss to conserve battery power but  
will turn back on if an alarm condition occurs.  
1.2  
ADT-LCD40 Only  
• Enable/Disable key-switch  
• Function switches for:  
Acknowledge  
Signal Silence  
Drill  
System Reset  
• DIP switches control function switches and key-switch enable/  
disable  
Document 50520 Rev D 7/25/00 P/N 50520:D  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
Components  
Figure 1-1: Components  
Note: OPEN (Up)  
position on SW1  
is OFF state (See  
“Wiring to Termi-  
nals” on page 9.).  
OFF = Receive only  
OFF = Key-switch Disable on ADT-LCD40 only  
(not used on ADT-LCD40L)  
ON = Piezo Enable  
ROM  
Top view  
Future use  
Membrane Connector  
Piezo Sounder  
Cable connection to membrane switches  
The ADT-LCD40 sounder, if enabled, will  
be activated when any new alarm or trouble  
is received from the panel. It is silenced by  
an Acknowledge switch. Piezo must not be  
disabled without approval of the LAHJ  
(Local Authority Having Jurisdiction).  
for Acknowledge, Silence, Drill and Reset.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
Wiring to Terminals  
Figure 1-2: Wiring to Terminals  
Side view  
P2  
P1  
Ter minal Block  
replacement  
P/N 02109  
Terminal Block replacement  
P/N 02108  
+ EIA-485 OUT  
+ EIA-485 IN  
- EIA-485 OUT  
- EIA-485 IN  
no connection  
+24 VDC IN  
+24 VDC OUT  
-24 VDC IN  
-24 VDC OUT  
Earth Ground Option  
Note: These connections must be power-limited and the +24 VDC  
nominal power must be filtered and nonresettable.  
Current Consumption @ 24 VDC nominal (filtered and nonresettable)  
Normal/Standby (no activity): 64 mA  
Trouble Condition: 64 mA  
Alarm: 66 mA  
AC Fail (not backlit): 28 mA  
Document 50520 Rev D 7/25/00 P/N 50520:D  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
SW1 DIP Switch Settings  
1.3  
SW1 DIP Switch Settings  
The Up position on DIP switch SW1 is the Off state. Refer to “DIP  
Switch Settings Example” on page 11, for an explanation of DIP switch  
positions. SW1 switch settings follow:  
1 - On (Down) = Receive/Transmit, Off (up) = Receive Only.  
Set switch 1 to Off (Up) position for all ADT-LCD40 Series Annun-  
ciators except the last (or only) annunciator on the EIA-485 loop.  
Set switch to On (Down) position for the last or only annunciator on  
the EIA-485 loop to allow transmission of a supervision signal (and  
function switch depressions on the ADT-LCD40) back to the FACP.  
The last or only annunciator must be set for Receive/Transmit  
(switch 1 in the Down position).  
A break (open circuit) in the power or EIA-485 connections creates  
an ADT-LCD40 Series Annunciator fault at the Unimode 200 panel.  
All annunciators before the break will continue to display informa-  
tion (but the function switches on the ADT-LCD40 will no longer  
operate).  
2 - ADT-LCD40 Only (not used on the ADT-LCD40L)  
On (Down) = Key-switch enabled, Off (Up) = Key-switch disabled.  
Switch 2 set to the On (Down) position enables key-switch  
operation. The key-switch may now be used to enable the  
ADT-LCD40 membrane switches, allowing remote switch func-  
tions, or lockout the switches, preventing remote switch functions  
Switch 2 set to the Off (Up) position disables the key-switch  
operation. Refer to “Switch Functions for ADT-LCD40 Only” on  
page 14, for key-switch function description.  
3 - On (Down) = Piezo sounder enabled, Off (Up) = Piezo sounder  
disabled.  
CAUTION: Piezo sounder must not be disabled without prior  
approval of the Local Authority Having Jurisdiction (LAHJ).  
4 through 8 = Future use.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
DIP Switch Settings Example  
.
Figure 1-3: DIP Switch Settings Example  
Down Position = On State  
Up (OPEN) Position = Off State  
Note: SW1 DIP switch settings as illustrated in Figure 1-3 are as  
follows:  
1. DIP switch 1: On (Down) - Receive/Transmit. This setting is  
used for the last or only ADT-LCD40 Series Annunciator on the  
EIA-485 line  
2. DIP switch 2: Used on ADT-LCD40 only - On (Down) = mem-  
brane function switches enabled.  
3. DIP switch 3: Off (Up) = piezo sounder disabled (requires  
approval of LAHJ)  
4. DIP switches 4 through 8: not used  
Document 50520 Rev D 7/25/00 P/N 50520:D  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Annunciators  
Typical Configuration  
1.4  
Typical Configuration  
The ADT-LCD40 Series Annunciators mimic the Unimode 200 display,  
have full point-display capacity and require no programming. The  
ADT-LCD40 offers multiple annunciator locations with the capability  
of remote Acknowledge, Signal Silence, Drill and Reset functions.  
Figure 1-4: Typical Configuration  
3,000 feet (900 m) to last device on loop  
Terminal Mode EIA-485 (2 wires)  
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA  
T
O
R
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA  
T
O
R
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA  
T
O
R
Drill  
ol s e  
Ac  
k
Silenc  
e
Re  
s
et  
Drill  
ol s e  
Drill  
ol s e  
H
d
2
c
.
Ac  
k
Silenc  
e
Ac  
k
Silenc  
e
Re  
s
et  
Re  
s
et  
H
d
2
c
.
H
d
2
c
.
24 VDC (2 wires)  
Terminal Mode EIA-485 return (2 wires)  
3,000 feet (900 m) back from last device on loop  
Notes:  
1. EIA-485: maximum of 6,000 feet (1,800 m) total cable length  
from FACP to annunciator and back to FACP for supervision  
(3,000 feet [900 m] maximum to last ADT-LCD40). Circuit is  
power-limited.  
2. Up to 32 ADT-LCD40 Series Annunciators may be used on the  
EIA-485 circuit. The Unimode 200 can power a maximum of  
five annunciators. If additional annunciators are connected, the  
FCPS-24F may be used to supply additional power. Power  
supplies used for this purpose must have their negative terminals  
commoned together.  
3. Between each ADT-LCD40 Series annunciator are four wires - a  
twisted shielded pair for data communications and a pair for 24  
VDC power. The return circuit only requires two wires for data  
communication supervision, wired from the last or only annunci-  
ator on the line.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Display Patterns  
Section 2:  
Operation  
2.1  
Display Patterns  
The ADT-LCD40 Series Annunciators directly display (mimic) the  
information on the Unimode 200 main circuit board LCD display with  
the following exceptions:  
• Upon Power-up, the ADT-LCD40 Series may display the  
following message until a valid message is received from the  
Unimode 200  
SYSTEM POWER UP  
WAITING FOR THE FACP  
• If an ADT-LCD40 Series Annunciator fails to receive communi-  
cations from the panel for a period of over 30 seconds, it will  
activate its local sounder (if so programmed) and display the  
following message:  
COMMUNICATIONS FAIL  
• When placing the host Unimode 200 into some aspects of the  
Programming Mode, the annunciator will display the following  
message:  
PROGRAMMING THE  
UNIMODE-200 PANEL  
The message shown above will appear at the Level One passcode for  
(1) Autoprogram, (2) Point Edit, (3) System Edit, (4) Passcode Entry  
and (5) Load. The same message will also appear at the Level Two  
passcode for (1) Disable, (2) Clear History and (4) Time.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Switch Functions for ADT-LCD40 Only  
2.2  
Switch Functions for ADT-LCD40 Only  
2.2.1 Key-switch  
Key-switch (shown in Off position)  
The key-switch is used to enable  
and disable the operation of the  
function switches if switch 2 on  
DIP switch SW1 has been placed  
to the On (Down) position.  
ATOR  
To enable the Acknowledge,  
Silence, Drill and Reset function  
switches, insert a standard ADT  
key into the key-switch located at  
the top right corner of the  
Reset  
ADT-LCD40. Make certain the  
key is inserted completely before  
attempting to turn it. Turn the key  
clockwise until it stops. Leave the key inserted while pressing the  
function switches. When finished with the function switches, turn  
key-switch counterclockwise to disable function switches.  
Note that the key-switch should normally be in the disabled position  
(fully counterclockwise), with the key removed and access to the key  
restricted to authorized personnel only. Do not leave the key  
unattended in the ADT-LCD40.  
2.2.2 Acknowledge  
When the Acknowledge switch is pressed and released, the  
ADT-LCD40 sends an Acknowledge command to the control panel.  
Pressing the Acknowledge switch silences the local piezo sounder,  
the sounders located in all other system annunciators and the  
sounder located on the Fire Alarm Control Panel's main circuit  
board. It will also change all flashing system LEDs to steady on.  
Only one press is necessary regardless of the number of new alarms,  
troubles or supervisory signals.  
An acknowledge message is also sent to the printer and the history  
files in the Unimode 200. Multiple active events (alarms, troubles,  
supervisories) are scrolled on the display at a one second rate, but  
may be held for sequential display by pressing and holding the  
Acknowledge switch.  
When more than one event exists, the first press of the Acknowledge  
switch silences system piezo sounders and changes all flashing  
Document 50520 Rev D 7/25/00 P/N 50520:D  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Switch Functions for ADT-LCD40 Only  
LEDs to steady on. The second press of the switch stops the scroll-  
ing and holds the event on the display for one minute. Subsequent  
pressing of the switch 'steps' through each active event.  
2.2.3 Silence  
When the Silence switch is pressed and released, the ADT-LCD40  
sends a signal silence command to the control panel. The Silence  
switch performs the same functions as the Acknowledge switch. In  
addition, if an alarm exists, it turns off all silenceable NACs and  
causes the FACP Alarm Silence LED to turn on while the  
ADT-LCD40 will display a 'silenced' message. It also sends an  
'Alarm Silenced' message to the printer and the history file within the  
Unimode 200. A subsequent new alarm will resound the appropriate  
NACs (Notification Appliance Circuits) and local sounders.  
2.2.4 Drill: Hold 2 Sec.  
When the Drill switch is pressed and held for at least two seconds  
(time required to prevent accidental activations), the ADT-LCD40  
will transmit a drill command to the control panel. This command  
causes the FACP to turn on both main panel NAC outputs and all  
silenceable circuits (all C304 modules/NACs that are programmed  
silenceable). In the event that the system was previously silenced,  
the drill command will also turn off the Alarm Silence LED. The  
'Manual Evacuate' message is shown on the ADT-LCD40 display.  
The same message is sent to the FACP display, printer and history  
files. The Silence switch operates on silenceable NAC outputs only.  
2.2.5 Reset  
When the System Reset switch is pressed and released, the  
ADT-LCD40 sends a Reset command to the control panel. This will  
turn off all C304 modules and Notification Appliance Circuits, tem-  
porarily turns off resettable power to 4-wire detectors, causes a 'Sys-  
tem All Normal' message to be displayed on the ADT-LCD40 and  
sends a 'System Reset' message to the FACP display, printer and Uni-  
mode 200 history files. It also turns on all system LEDs, piezo  
sounders and LCD display segments as long as the Reset switch is  
held (lamp test). Any alarm or trouble that exists after a Reset will  
resound the system.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
LED Indicators (all ADT-LCD40 Series)  
2.3  
LED Indicators (all ADT-LCD40 Series)  
2.3.1 Power  
This is a green LED which illuminates if AC power is applied to the  
host FACP. The green LED will turn off if AC power to the host  
FACP is lost.  
2.3.2 Fire Alarm  
This is a red LED that flashes when one or more fire alarms occur. It  
illuminates steadily when an Acknowledge or Silence switch is  
pressed. The Alarm LED turns off when the Reset switch is pressed.  
2.3.3 Supervisory  
This is a yellow LED that flashes when one or more supervisory  
conditions occur, such as a sprinkler valve tamper condition. It  
illuminates steadily when an Acknowledge or Silence switch is  
pressed. It turns off when the Reset switch is pressed.  
2.3.4 Trouble  
This is a yellow LED that flashes when one or more trouble condi-  
tions occur. It stays on steady when an Acknowledge or Silence  
switch is pressed. The LED turns off when all trouble conditions are  
cleared. This LED will also illuminate if the microprocessor watch-  
dog circuit within the ADT-LCD40 Series is activated.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
ADT-LCD40 Series Preparation  
Section 3:  
Mounting  
3.1  
ADT-LCD40 Series Preparation  
The ADT-LCD40 Series Annunciators can be surface mounted in a  
three-gang electrical box such as the P/N SBB-3 (2.75" depth) or semi-  
flush mounted in a three-gang electrical box, P/N 10103 or equivalent,  
with a minimum depth of 2 3/16". The ADT-LCD40 Series Annuncia-  
tors cannot be mounted in three gangable electrical switch boxes con-  
nected together. Select and remove the appropriate knockout(s), pull the  
necessary wires through the knockouts and mount the three-gang box in  
or on the wall depending on the type of installation desired. Be certain  
that power is not applied to the wiring during the installation procedure.  
Note: To ensure static protection, all enclosures, including the  
ADT-LCD40 Series electrical box, must be connected to earth ground!  
Never use the shield for grounding purposes.  
To mount the ADT-LCD40 Series Annunciators in an electrical box, the  
trim ring must first be removed. The trim ring is held in place by two  
screws inserted through the top and bottom edge as illustrated in Figure  
3-1. Removal of the trim ring will expose a metal flange with mounting  
holes. Refer to “Hardware and Backboxes” on page 18.  
Figure 3-1: Trim Ring Removal  
Screw  
FIRE ALARM ANNUNCIATOR  
Drill  
sec.  
Ack  
Silence  
Reset  
Hold  
2
Screw  
Document 50520 Rev D 7/25/00 P/N 50520:D  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Hardware and Backboxes  
Figure 3-2: Hardware and Backboxes  
FIRE ALARM ANNUNCIATOR  
Drill  
Hold sec.  
Ack  
Silence  
Reset  
2
ADT-LCD40 Series flange  
ADT-LCD40 Series Trim Ring  
(replacement P/N 23165)  
3-Gang Electrical Box P/N 10103  
(semi-flush mount)  
3-Gang Electrical Box P/N SBB-3  
(surface mount)  
Document 50520 Rev D 7/25/00 P/N 50520:D  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Semi-flush Mount Backbox  
3.2  
Semi-flush Mount Backbox  
Remove the plug-in terminal blocks from the ADT-LCD40(L) circuit  
board. Connect the EIA-485 and power wiring into the terminal block  
positions illustrated in Figure 1-1 on page 8, Figure 4-1 on page 21 and  
Figure 4-2 on page 22. Plug the terminal blocks back into the P1 and P2  
connectors on the back of the annunciator. Set DIP switch SW1 for the  
desired options (refer to Figure 1-2 on page 9).  
Carefully insert the ADT-LCD40(L) into the three-gang electrical box  
and attach it using the four mounting holes on the ADT-LCD40(L)  
flange and the four screws provided for this purpose. Replace the trim  
ring and secure with the two screws which were previously removed.  
Adjust the plastic trim ring to the surface of the wall before tightening  
the screws. Do not overtighten.  
Figure 3-3: Semi-flush Mounting  
ADT-LCD40 Series flange  
Mounting holes (4)  
FIRE ALARM ANNUNCIATOR  
CAUTION! The ADT-LCD40 Series can  
Drill  
sec.  
Ack  
Silence  
Reset  
Hold  
2
be semi-flush mounted in a three-  
ONLY  
gang electrical box, P/N 10103 or equiva-  
lent, with a minimum depth of 2 3/16".  
The ADT-LCD40 Series  
be  
cannot  
mounted in three gangable electrical  
switch boxes connected together.  
Three-gang electrical box  
flange  
EIA-485 and power wiring  
ADT-LCD40(L)  
Three-gang electrical box P/N 10103  
Document 50520 Rev D 7/25/00 P/N 50520:D  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Surface Mount Backbox  
3.3  
Surface Mount Backbox  
Remove the plug-in terminal blocks from the ADT-LCD40(L) circuit  
board. Connect the EIA-485 and power wiring into the terminal block  
positions illustrated in Figure 1-1 on page 8, Figure 4-1 on page 21 and  
Figure 4-3 on page 23. Plug the terminal blocks back into the P1 and P2  
connectors on the back of the annunciator circuit board. Set DIP switch  
SW1 for the desired options (refer to Figure 1-2 on page 9).  
Carefully insert the ADT-LCD40(L) into the three-gang electrical box  
and attach it using the four mounting holes on the ADT-LCD40(L)  
flange and the four screws provided for this purpose. Replace the trim  
ring and secure with the two screws which were previously removed.  
Do not overtighten.  
Figure 3-4: Surface Mounting  
ADT-LCD40 Series flange  
Mounting holes (4)  
FIRE ALARM ANN UNCIATO R  
CAUTION! The ADT-LCD40 Series can  
D
rill  
sec.  
A
ck  
S
ilen ce  
R
eset  
be surface mounted in a three-  
ONLY  
Hold  
2
gang electrical box, P/N SBB-3 or  
equivalent, with a minimum depth of  
2.75". The ADT-LCD40 Series  
cannot  
be mounted in three gangable electrical  
switch boxes connected together.  
Three-gang electrical box P/N SBB-3 or  
equivalent with a 2.75" minimum depth.  
flange  
EIA-485 and power wiring  
ADT-LCD40(L)  
Three-gang surface box P/N SBB-3  
Document 50520 Rev D 7/25/00 P/N 50520:D  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Electrical Connections  
Power Connection  
Section 4:  
ADT-LCD40 Series Electrical  
Connections  
The ADT-LCD40 Series Annunciators can be powered by the Unimode  
200 24VDC nominal power or from a remote UL listed, filtered power  
supply such as the FCPS-24F. The power run to the annunciator must  
be power-limited but need not contain a power supervision relay since  
loss of power is inherently supervised through loss of communication  
with the annunciator. Maximum ADT-LCD40 Series current draw from  
the power supply (under alarm condition) is 66 mA. Maximum current  
draw from the control panel's secondary power source (batteries) under  
loss of AC power is 28 mA, since the LCD backlight is turned off during  
AC loss. Backlighting is turned back on during AC loss only for alarm  
conditions in the system.  
Figure 4-1: Power Connection  
ADT-LCD40 Series  
P2  
P1  
Plug-in Terminal Blocks  
no connection  
+24 VDC IN from main power supply  
+24 VDC OUT to next ADT-LCD40(L)  
-24 VDC IN from main power supply  
-24 VDC OUT to next ADT-LCD40(L)  
Earth Ground Option  
1. All connections are power-limited and supervised  
2. 12 - 18 AWG (0.75 - 3.25 mm2) wire for 24 VDC circuit is  
acceptable  
3. Power wire distance limitation is set by 1.2 volt maximum line  
drop from source to end of circuit.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Electrical Connections  
EIA-485 Connection  
Figure 4-2: EIA-485 Connection  
ADT-LCD40 Series  
P1  
P2  
Ter minal Block  
replacement  
P/N 02109  
Terminal Block replacement  
P/N 02108  
6,000 feet (1,800 m) maximum wire run  
from and back to FACP (3,000 feet to last  
ADT-LCD40) @ 18 AWG (0.75 mm )  
+ EIA-485 IN from source  
- EIA-485 IN from source  
2
(+) (-)  
EIA-485  
Out to next ADT-LCD40 Series  
or return to host FACP if last or  
only annunciator on line  
Notes:  
1. All connections are power-limited and supervised  
2. A maximum of 32 ADT-LCD40 Series annunciators may be con-  
nected to this circuit  
3. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm2)  
between the panel, annunciators and return to the panel.  
4. Use overall foil/braided-shielded twisted pair cable suitable for  
EIA-485 applications (refer to “EIA-485 Shield Termination” on  
page 25, for shield termination information)  
5. The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA  
maximum  
6. The ADT-LCD40 Series annunciators have resistors built into  
the circuit board at the In (Terminals 2 & 4) and the Out (Termi-  
nals 1 & 3) for impedance matching. There is no need for the  
installer to add impedance matching resistors  
Document 50520 Rev D 7/25/00 P/N 50520:D  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Electrical Connections  
DIM-485 Connections  
Figure 4-3: DIM-485 Connections  
Circuit Board  
1
2
3
4
DIM-485 CONNECTIONS  
ADT-LCD40 Series3  
DIM-485  
Terminal 1 - OUT (+)  
Terminal 2 - IN (+)  
Terminal 3 - OUT (-)  
Terminal 4 - IN (-)  
P1 Terminal 2 - IN (+)  
P1 Terminal 12 - OUT (+)  
P1 Terminal 4 - IN (-)  
P1 Terminal 3 2 - OUT (-)  
1. Terminal to terminal wiring is shown between the DIM-485 and  
one ADT-LCD40 Series Annunciator  
2. If more than one ADT-LCD40 Series Annunciator is installed,  
the wiring to the DIM-485 In (+) Terminal 2 and In (-) Terminal  
4 will be from the last installed annunciator (refer to Figure 4-4  
on page 24)  
3. The ADT-LCD40 Series Annunciators have resistors built into  
the circuit board at the In (Terminals 2 & 4) and the Out (Termi-  
nals 1 & 3) for impedance matching. There is no need for the  
installer to add impedance matching resistors  
4. Connect wiring to DIM-485 terminals before plugging DIM-485  
into connector J11 of the Unimode 200 main circuit board.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-LCD40 Series Electrical Connections  
Wiring FACP to ADT-LCD40 Series  
Dim-485 Installation.  
CAUTION! Connect all wiring to the DIM-485 terminals before  
plugging it into connector J11 on the Unimode 200 circuit board.  
1. Carefully align the DIM-485 connector with the four pins on  
connector J11 of the Unimode 200  
2. Press firmly on the DIM-485 connector to seat properly on  
connector J11 being careful not to bend any pins  
3. Be certain to secure the DIM-485 module to the Unimode 200  
and keep all wiring from mechanically interfering with module.  
Figure 4-4: Wiring FACP to ADT-LCD40 Series  
ADT-LCD40 Series in  
grounded box  
Ferrite Core P/N FBD-1  
Required  
24 VDC  
TB4 Terms  
3(+) & 4(-)  
EIA-485  
ADT-LCD40 Series in  
grounded box  
DIM-485  
Unimode 200  
in grounded box  
1
2
3
4
Ferrite Core P/N FBD-1  
Required  
Top  
P2  
4
P1  
1
2
3
5
6
7
1
2
3
4
(+) EIA-485  
IN  
n/c  
(-) EIA-485  
Earth  
Ground  
Optional  
Shield  
(+)  
(-)  
Notes:  
EIA-485  
OUT  
Connect  
1) Ferrite Core P/N FBD-1 is required to meet  
FCC Part 15 requirements if the EIA-485  
wiring is not in conduit. Twisted, shielded  
wire is recommended for the EIA-485  
communications loop.  
(+) 24 VDC  
IN  
2) Six conductor overall shielded wire may be  
used for the four EIA-485 wires and the two  
power wires. It is, however, strongly  
(-) 24 VDC  
recommended that the power and communi-  
cation wires be separate whenever possible.  
(+)  
(-)  
24 VDC  
OUT  
Document 50520 Rev D 7/25/00 P/N 50520:D  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EIA-485 Shield Termination  
EIA-485 Shield Not in Conduit  
Section 5:  
EIA-485 Shield Termination  
The EIA-485 circuit must be wired using a twisted, shielded pair cable  
with a characteristic impedance of 120 ohms (+/- 20%). Do not run  
cable adjacent to or in the same conduit as 120 VAC service, noisy  
electrical circuits that are powering mechanical bells or horns, audio  
circuits above 25 VRMS, motor control circuits or SCR power circuits.  
Note: To ensure static (ESD - electrostatic discharge) protection, all  
enclosures, including the ADT-LCD40 Series electrical box, must be  
connected to earth ground! Never use the EIA-485 shield for this  
purpose. The EIA-485 shield is for radiated noise emission protection  
(RFI, EMI). Refer to the following figures for details on EIA-485 shield  
termination.  
5.1  
EIA-485 Shield Not in Conduit  
The EIA-485 line allows the FACP to communicate with the  
ADT-LCD40 Series Annunciators. The shield for the EIA-485 line  
must be connected to earth ground at the FACP but must be left floating  
(no connection) at the annunciator if it is the first or only device on the  
EIA-485 line. If a second annunciator is connected, the shield leaving  
the first annunciator must be left floating. The shield entering the sec-  
ond annunciator must be connected to the three-gang box or Earth  
Ground terminal (P2-7) on the second annunciator. If additional annun-  
ciators are connected, the shield leaving each enclosure must be left  
floating and the shield entering each must be connected to the three-  
gang box or the Earth Ground terminal (P2-7) on the annunciator.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EIA-485 Shield Termination  
EIA-485 Without Conduit  
Figure 5-1: EIA-485 Without Conduit  
Connect the drain wire to the outside  
of the Unimode 200 cabinet via a BX-  
type connector.  
Shield Drain Wire  
(+) EIA-485  
(-) EIA-485  
FACP  
FACP Backbox  
Document 50520 Rev D 7/25/00 P/N 50520:D  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EIA-485 Shield Termination  
EIA-485 Shield in Full Conduit  
5.2  
EIA-485 Shield in Full Conduit  
The EIA-485 line allows the FACP to communicate with the  
ADT-LCD40 Series Annunciators. The shield for the EIA-485 line  
must be connected to earth ground at the FACP (both exiting and  
entering the FACP) but must be left floating (no connection) at the  
annunciator if it is the first or only device on the EIA-485 line. If a  
second annunciator is connected, the shield leaving the first annunciator  
must be floating. The shield entering the second annunciator must be  
connected to the Earth Ground terminal (P2-7) on the second annuncia-  
tor. If additional annunciators are connected, the shield leaving each  
annunciator must be left floating and the shield entering the following  
unit must be connected to the Earth Ground terminal (P2-7) on the  
annunciator.  
Caution! Do not allow the floating (no connection) end of the shield to  
contact the conduit. The floating end should be insulated from earth  
ground.  
Figure 5-2: EIA-485 In Conduit  
ADT-LCD40 Series  
Connect the shield drain wire to the Earth  
Ground Terminal on the ADT-LCD40 Series  
Annunciator  
P1-2 (+)  
EIA-485 (IN)  
P1-4 (-)  
EIA-485 (IN)  
Shield Drain Wire  
ADT-LCD40 Series Box  
P2-7 Earth  
Ground (IN)  
Notes:  
1) Power-limited 24 VDC power may be run in the same conduit as the EIA-485 wiring  
2) Twisted, shielded wire is recommended for the EIA-485 communications loop  
3) Each ADT-LCD40 Series electrical backbox is connected to earth ground via the conduit  
4) Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP  
Document 50520 Rev D 7/25/00 P/N 50520:D  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming the Unimode 200  
EIA-485 In Conduit  
Section 6:  
Programming the Unimode 200  
The Unimode 200 must be programmed to allow use of the  
ADT-LCD40 Series Annunciators. In order to program the Unimode  
200, make certain the main circuit board 'Write Protect' switch (SW1) is  
in the down position and then press the ENTER key on the panel key-  
pad. After pressing ENTER, the screen shown below is displayed:  
1 = PROGRAMMING  
2=RD.STATUS 3=AC/BAT  
To enter the Programming Mode, press '1'. The display will read:  
KEY PASSWORD, ENTER  
Enter the Level 1 password. The following screen will appear:  
0=CLR 1=AUTO 2=POINT  
3=SYS 4=PWORD 5=LOAD  
Press '3' to enter System Edit. The system edit screen may appear as  
shown (note that previous programming may have altered some N or No  
designations to Y or Yes):  
V=N I=N A=N P=N C=N  
A/U=N L/P=N S=4 R=4  
Use the left and right arrow keys to move to the L/P option. Once at the  
L/P option, to enable the ADT-LCD40 Series Annunciator option, use  
the up and down arrow keys to scroll to the L (for ADT-LCD40 Series  
Annunciator) choice. The ADT-LCD40 Series can now communicate  
with the Unimode 200.  
To leave Programming Mode, press the Backspace (left arrow) key  
repeatedly until Program Mode is exited.  
Document 50520 Rev D 7/25/00 P/N 50520:D  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
Acknowledge switch 6, 7, 12, 14  
ADT-LCD40 6, 7, 10, 14, 15  
see also ADT-LCD40 Series Annunciators  
software version 6  
ADT-LCD40 Series Annunciators 6, 12, 13, 16, 17, 19, 20, 21, 22,  
23, 28  
ADT-LCD40 Series Annunciators display  
custom alpha labels 6  
device type 6  
point alarm 6  
supervisory 6  
system point status 6  
trouble 6  
zone labels 6  
ADT-LCD40L 6, 7  
see also ADT-LCD40 Series Annunciators  
Alarm LED 6, 7, 16  
Alarm Silence LED 15  
annunciators  
maximum per EIA-485 circuit 7, 12, 22  
B
backboxes 18  
backlight 7, 21  
C
communication 6  
see also EIA-485 circuit 6  
communications fault 13  
components 8  
configuration 12  
control switches  
ADT-LCD40L only 6  
current rating 21  
AC fail 9  
alarm 9  
standby 9  
trouble 9  
D
DIM-485 23, 24  
connections 23  
installation 24  
Document 50520 Rev D 7/25/00 P/N 50520:D  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
wiring 23  
DIM-485 module 7  
DIP Switch settings 8, 10, 11  
function switches 11  
piezo sounder 11  
Receive/Transmit 10, 11  
SW1 10  
DIP switches 7  
SW1 14, 19, 20  
display  
scroll 14, 15  
step through 15  
distance from panel 7, 12, 22  
Drill switch 6, 7, 12, 14, 15  
E
earth ground 9, 17, 25, 27  
EIA-485 circuit 6, 7, 12, 19, 22, 25, 26, 27  
fault 10  
EIA-485 connection 22  
electrical box 17, 18  
electrical connections 21  
electrostatic discharge 25  
F
fault  
communication failure 10  
FCC Part 15 requirements 24  
Ferrite Core 24  
filtered 9  
flange 18, 20  
function switches 6, 7  
enable/disable 11, 14  
I
impedance matching 22, 23  
K
key-switch 6, 14  
enable/disable 7, 10  
L
lamp test 15  
LCD display 7, 13  
mimic control panel display 6  
see also Liquid Crystal Display 6  
Document 50520 Rev D 7/25/00 P/N 50520:D  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liquid Crystal Display 6  
Local Authority Having Jurisdiction 8, 10  
M
Manual Evacuate 15  
mounting 7, 17, 19  
semi-flush 7  
surface 7, 20  
N
NAC  
see also Notification Appliance Circuit 15  
nonresettable 9  
O
Operation 13  
P
piezo sounder 7, 15  
alarm resound 7  
enable/disable 8, 10, 11  
silence 14  
trouble resound 7  
power connection 21  
Power LED 6, 7, 16  
power source 6, 9, 12, 21  
power-limited 9, 12, 21, 22  
power-up 13  
programming 7, 12  
Unimode 200 13, 28  
R
Receive/Transmit 10, 11  
Reset switch 6, 12, 14, 15  
resettable power 15  
resistors  
impedance matching 22, 23  
ROM 8  
S
SBB-3 electrical box 17, 18, 20  
semi-flush mounting 7, 19  
shield 17, 25, 27  
Signal Silence switch 7, 12  
silence  
NAC 15  
piezo sounder 14, 15  
Document 50520 Rev D 7/25/00 P/N 50520:D  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Silence switch 6, 14, 15  
software version  
ADT-LCD40 6  
Unimode 200 6  
static 25  
static protection 17  
supervised 21, 22  
Supervisory LED 6, 7, 16  
surface mount 7, 20  
SW1 DIP Switch 10  
switch functions 14  
System LEDs 14, 15, 16  
System Reset switch 7  
System Status LEDs 6, 7  
T
terminal block 7, 9, 19, 20  
three-gang electrical box 17, 19, 20  
trim ring 17, 18, 19, 20  
Trouble LED 6, 7, 16  
U
Unimode 200 6, 7, 12, 13, 15, 21, 23, 24, 26  
programming 28  
software version 6  
Unimode 200 programming 13  
W
wire  
distance 21  
requirements 12  
size 21, 22  
type 22, 25  
wiring 12, 19, 23, 24, 25  
wiring connections 9  
Document 50520 Rev D 7/25/00 P/N 50520:D  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Document 50520 Rev D 7/25/00 P/N 50520:D  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Document 50520 Rev D 7/25/00 P/N 50520:D  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Document 50520 Rev D 7/25/00 P/N 50520:D  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

2Wire Network Router 100S User Manual
ADIC Tool Storage Version 27 User Manual
Aiphone Intercom System HM 7 User Manual
Aiphone Intercom System IE DL1 User Manual
Alacritech Video Gaming Accessories Scalable Networking Accelerator User Manual
Algolith Stereo Receiver FRS 1002 MD
AllTrade Food Warmer BAR916HG User Manual
Atlona Switch AT HDMI 22M User Manual
Axor Plumbing Product 42033000 User Manual
Bakers Pride Oven Kitchen Entertainment Center CA34 CV9 User Manual