ADT-LCD40 Series
Remote Fire
Annunciators
for use with Unimode 200
Addressable Fire Alarm Control Panel
FIRE ALARM ANNUNCIATOR
Drill
Ack
Silence
Reset
Hold
2
sec.
Document #50520
D
7/25/00
Rev:
P/N 50520:D ECN 00-325
Download from Www.Somanuals.com. All Manuals Search And Download.
Adherence to the following will aid in problem-free
installation with long-term reliability:
Installation Precautions
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected
to lightning-induced transients. Although no system is
completely immune from lightning transients and inter-
ferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services Department
if any problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reacceptance testing is required
after any change, addition or deletion of system compo-
nents, or after any modification, repair or adjustment to
system hardware or wiring.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system compo-
nents can fail at any time. This system contains static-
sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static-
suppressive packaging to protect electronic assemblies
removed from the unit.
This system meets NFPA requirements for operation
at 0-49° C/32-120° F and at a relative humidity of 85%
RH (non-condensing) at 30°C/86° F. However, the
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore,
it is recommended that this system and all peripherals
be installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must
be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
FCC Warning
Canadian Requirements
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not in-
stalled and used in accordance with the instruction
manual, may cause interference to radio commu-
nications. It has been tested and found to comply
with the limits for class A computing device pursu-
ant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a
residential area is likely to cause interference, in
which case the user will be required to correct the
interference at his own expense.
This digital apparatus does not exceed the
Class A limits for radiation noise emissions from
digital apparatus set out in the Radio Interfer-
ence Regulations of the Canadian Department
of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarSm.p65 01/10/2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Document 50520 Rev D 7/25/00 P/N 50520:D
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Table of Contents
Section 1: ADT-LCD40 Series Annunciators ...........................................6
1.1 ADT-LCD40 and ADT-LCD40L ...................................................7
1.2 ADT-LCD40 Only ..........................................................................7
Figure 1-1: Components .......................................................8
Figure 1-2: Wiring to Terminals ...........................................9
1.3 SW1 DIP Switch Settings ...............................................................10
Figure 1-3: DIP Switch Settings Example ............................11
1.4 Typical Configuration .....................................................................12
Figure 1-4: Typical Configuration ........................................12
Section 2: Operation ...................................................................................13
2.1 Display Patterns ..............................................................................13
2.2 Switch Functions for ADT-LCD40 Only .......................................14
2.2.1 Key-switch ..........................................................................14
2.2.2 Acknowledge .......................................................................14
2.2.3 Silence ..................................................................................15
2.2.4 Drill: Hold 2 Sec. .................................................................15
2.2.5 Reset .....................................................................................15
2.3 LED Indicators (all ADT-LCD40 Series) .......................................16
2.3.1 Power ...................................................................................16
2.3.2 Fire Alarm ............................................................................16
2.3.3 Supervisory ..........................................................................16
2.3.4 Trouble .................................................................................16
Section 3: Mounting ....................................................................................17
3.1 ADT-LCD40 Series Preparation .....................................................17
Figure 3-1: Trim Ring Removal ...........................................17
Figure 3-2: Hardware and Backboxes ..................................18
3.2 Semi-flush Mount Backbox ............................................................19
Figure 3-3: Semi-flush Mounting .........................................19
3.3 Surface Mount Backbox .................................................................20
Figure 3-4: Surface Mounting ...............................................20
Section 4: ADT-LCD40 Series Electrical Connections ............................21
Figure 4-1: Power Connection ..............................................21
Figure 4-2: EIA-485 Connection ..........................................22
Figure 4-3: DIM-485 Connections .......................................23
Figure 4-4: Wiring FACP to ADT-LCD40 Series ................24
Section 5: EIA-485 Shield Termination ....................................................25
5.1 EIA-485 Shield Not in Conduit ......................................................25
Figure 5-1: EIA-485 Without Conduit ..................................26
5.2 EIA-485 Shield in Full Conduit ......................................................27
Figure 5-2: EIA-485 In Conduit ...........................................27
Section 6: Programming the Unimode 200 ...............................................28
Document 50520 Rev D 7/25/00 P/N 50520:D
5
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
Section 1:ADT-LCD40 Series Annunciators
FIRE ALARM ANNUNCIATOR
FIRE ALARM ANNUNCIATOR
Drill
sec.
Ack
Silence
Reset
Hold
2
ADT-LCD40
ADT-LCD40L
Note: Only Model ADT-LCD40L is listed for use in Canada.
The ADT-LCD40 Series Annunciators are compact, attractive,
40-character, backlit LCD fire annunciators designed for use with the
Unimode 200 Addressable Fire Alarm Control Panel. The
ADT-LCD40L operates the same as the ADT-LCD40, except it does not
have function switches or a key-switch. It should be noted that the
ADT-LCD40 Series Annunciator displays will mimic the LCD display
located on the Unimode 200 main circuit board.
If software with Part Number #UNIMODE200V3.0 is installed in the
ADT Unimode 200, the ADT-LCD40 Series Annunciator must have soft-
ware with a Part Number of 73879 to operate with the control panel. If
software with a Part Number of #UNIMODE200V4.0 or higher is
installed in the Unimode 200, the ADT-LCD40 Series Annunciator must
have software with a Part Number of #LCD40V2.0 or higher to operate
with the control panel.
The ADT-LCD40 Series is capable of displaying English-language text
of system point status including device type, independent point alarm,
trouble or supervisory, zone and custom alpha labels programmed into
the control panel. The ADT-LCD40 Series also provide system status
LEDs to display Power, Alarm, Trouble and Supervisory conditions.
The ADT-LCD40 is capable of performing system acknowledge,
silence, drill and reset remotely while the ADT-LCD40L does not have
these features.
Communication between the control panel and the ADT-LCD40 Series
is accomplished over a two-wire serial interface employing the EIA-485
communication standard. Up to 32 annunciators may be connected to
the two-wire EIA-485 circuit. The annunciators may be powered from
the host FACP or remote UL listed, filtered, power supplies.
Document 50520 Rev D 7/25/00 P/N 50520:D
6
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
ADT-LCD40 and ADT-LCD40L
1.1
ADT-LCD40 and ADT-LCD40L
• 40-character LCD display (20 characters x 2 lines) is backlit
under normal and alarm conditions
• System Status LEDs for Power (green), Alarm (red), Trouble
(yellow) and Supervisory (yellow)
• No programming necessary — duplicates messages at control
panel display
• Local piezo sounder with alarm and trouble resound
• Device type identifiers from the control panel
• Device & zone custom alpha labels from the control panel
• Time/date and device address from the control panel
• EIA-485 connects to control panel terminal port (requires
DIM-485 module)
• Plug-in terminal blocks for ease of installation and service
• DIP switches control piezo enable/disable and transmit/receive
mode
• Up to 32 ADT-LCD40 Series Annunciators per Unimode 200
• Mounting options:
ꢀ
Surface mounting in SBB-3 (2.75" depth)
ꢀ
Semi-flush mounting in three-gang electrical box (P/N
10103) with a minimum depth of 2.187"
ꢀ
Can be located up to 3,000 feet (900 m) from the panel
• Backlight turns off during AC loss to conserve battery power but
will turn back on if an alarm condition occurs.
1.2
ADT-LCD40 Only
• Enable/Disable key-switch
• Function switches for:
ꢀ
ꢀ
ꢀ
ꢀ
Acknowledge
Signal Silence
Drill
System Reset
• DIP switches control function switches and key-switch enable/
disable
Document 50520 Rev D 7/25/00 P/N 50520:D
7
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
Components
Figure 1-1: Components
Note: OPEN (Up)
position on SW1
is OFF state (See
“Wiring to Termi-
nals” on page 9.).
OFF = Receive only
OFF = Key-switch Disable on ADT-LCD40 only
(not used on ADT-LCD40L)
ON = Piezo Enable
ROM
Top view
Future use
Membrane Connector
Piezo Sounder
Cable connection to membrane switches
The ADT-LCD40 sounder, if enabled, will
be activated when any new alarm or trouble
is received from the panel. It is silenced by
an Acknowledge switch. Piezo must not be
disabled without approval of the LAHJ
(Local Authority Having Jurisdiction).
for Acknowledge, Silence, Drill and Reset.
Document 50520 Rev D 7/25/00 P/N 50520:D
8
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
Wiring to Terminals
Figure 1-2: Wiring to Terminals
Side view
P2
P1
Ter minal Block
replacement
P/N 02109
Terminal Block replacement
P/N 02108
+ EIA-485 OUT
+ EIA-485 IN
- EIA-485 OUT
- EIA-485 IN
no connection
+24 VDC IN
+24 VDC OUT
-24 VDC IN
-24 VDC OUT
Earth Ground Option
Note: These connections must be power-limited and the +24 VDC
nominal power must be filtered and nonresettable.
Current Consumption @ 24 VDC nominal (filtered and nonresettable)
Normal/Standby (no activity): 64 mA
Trouble Condition: 64 mA
Alarm: 66 mA
AC Fail (not backlit): 28 mA
Document 50520 Rev D 7/25/00 P/N 50520:D
9
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
SW1 DIP Switch Settings
1.3
SW1 DIP Switch Settings
The Up position on DIP switch SW1 is the Off state. Refer to “DIP
Switch Settings Example” on page 11, for an explanation of DIP switch
positions. SW1 switch settings follow:
1 - On (Down) = Receive/Transmit, Off (up) = Receive Only.
Set switch 1 to Off (Up) position for all ADT-LCD40 Series Annun-
ciators except the last (or only) annunciator on the EIA-485 loop.
Set switch to On (Down) position for the last or only annunciator on
the EIA-485 loop to allow transmission of a supervision signal (and
function switch depressions on the ADT-LCD40) back to the FACP.
The last or only annunciator must be set for Receive/Transmit
(switch 1 in the Down position).
A break (open circuit) in the power or EIA-485 connections creates
an ADT-LCD40 Series Annunciator fault at the Unimode 200 panel.
All annunciators before the break will continue to display informa-
tion (but the function switches on the ADT-LCD40 will no longer
operate).
2 - ADT-LCD40 Only (not used on the ADT-LCD40L)
On (Down) = Key-switch enabled, Off (Up) = Key-switch disabled.
Switch 2 set to the On (Down) position enables key-switch
operation. The key-switch may now be used to enable the
ADT-LCD40 membrane switches, allowing remote switch func-
tions, or lockout the switches, preventing remote switch functions
Switch 2 set to the Off (Up) position disables the key-switch
operation. Refer to “Switch Functions for ADT-LCD40 Only” on
page 14, for key-switch function description.
3 - On (Down) = Piezo sounder enabled, Off (Up) = Piezo sounder
disabled.
CAUTION: Piezo sounder must not be disabled without prior
approval of the Local Authority Having Jurisdiction (LAHJ).
4 through 8 = Future use.
Document 50520 Rev D 7/25/00 P/N 50520:D
10
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
DIP Switch Settings Example
.
Figure 1-3: DIP Switch Settings Example
Down Position = On State
Up (OPEN) Position = Off State
Note: SW1 DIP switch settings as illustrated in Figure 1-3 are as
follows:
1. DIP switch 1: On (Down) - Receive/Transmit. This setting is
used for the last or only ADT-LCD40 Series Annunciator on the
EIA-485 line
2. DIP switch 2: Used on ADT-LCD40 only - On (Down) = mem-
brane function switches enabled.
3. DIP switch 3: Off (Up) = piezo sounder disabled (requires
approval of LAHJ)
4. DIP switches 4 through 8: not used
Document 50520 Rev D 7/25/00 P/N 50520:D
11
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Annunciators
Typical Configuration
1.4
Typical Configuration
The ADT-LCD40 Series Annunciators mimic the Unimode 200 display,
have full point-display capacity and require no programming. The
ADT-LCD40 offers multiple annunciator locations with the capability
of remote Acknowledge, Signal Silence, Drill and Reset functions.
Figure 1-4: Typical Configuration
3,000 feet (900 m) to last device on loop
Terminal Mode EIA-485 (2 wires)
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA
T
O
R
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA
T
O
R
F
I
R
E
A
L
A
R
M
A
N
N
U
N
C
IA
T
O
R
Drill
ol s e
Ac
k
Silenc
e
Re
s
et
Drill
ol s e
Drill
ol s e
H
d
2
c
.
Ac
k
Silenc
e
Ac
k
Silenc
e
Re
s
et
Re
s
et
H
d
2
c
.
H
d
2
c
.
24 VDC (2 wires)
Terminal Mode EIA-485 return (2 wires)
3,000 feet (900 m) back from last device on loop
Notes:
1. EIA-485: maximum of 6,000 feet (1,800 m) total cable length
from FACP to annunciator and back to FACP for supervision
(3,000 feet [900 m] maximum to last ADT-LCD40). Circuit is
power-limited.
2. Up to 32 ADT-LCD40 Series Annunciators may be used on the
EIA-485 circuit. The Unimode 200 can power a maximum of
five annunciators. If additional annunciators are connected, the
FCPS-24F may be used to supply additional power. Power
supplies used for this purpose must have their negative terminals
commoned together.
3. Between each ADT-LCD40 Series annunciator are four wires - a
twisted shielded pair for data communications and a pair for 24
VDC power. The return circuit only requires two wires for data
communication supervision, wired from the last or only annunci-
ator on the line.
Document 50520 Rev D 7/25/00 P/N 50520:D
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Display Patterns
Section 2:
Operation
2.1
Display Patterns
The ADT-LCD40 Series Annunciators directly display (mimic) the
information on the Unimode 200 main circuit board LCD display with
the following exceptions:
• Upon Power-up, the ADT-LCD40 Series may display the
following message until a valid message is received from the
Unimode 200
SYSTEM POWER UP
WAITING FOR THE FACP
• If an ADT-LCD40 Series Annunciator fails to receive communi-
cations from the panel for a period of over 30 seconds, it will
activate its local sounder (if so programmed) and display the
following message:
COMMUNICATIONS FAIL
• When placing the host Unimode 200 into some aspects of the
Programming Mode, the annunciator will display the following
message:
PROGRAMMING THE
UNIMODE-200 PANEL
The message shown above will appear at the Level One passcode for
(1) Autoprogram, (2) Point Edit, (3) System Edit, (4) Passcode Entry
and (5) Load. The same message will also appear at the Level Two
passcode for (1) Disable, (2) Clear History and (4) Time.
Document 50520 Rev D 7/25/00 P/N 50520:D
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Switch Functions for ADT-LCD40 Only
2.2
Switch Functions for ADT-LCD40 Only
2.2.1 Key-switch
Key-switch (shown in Off position)
The key-switch is used to enable
and disable the operation of the
function switches if switch 2 on
DIP switch SW1 has been placed
to the On (Down) position.
ATOR
To enable the Acknowledge,
Silence, Drill and Reset function
switches, insert a standard ADT
key into the key-switch located at
the top right corner of the
Reset
ADT-LCD40. Make certain the
key is inserted completely before
attempting to turn it. Turn the key
clockwise until it stops. Leave the key inserted while pressing the
function switches. When finished with the function switches, turn
key-switch counterclockwise to disable function switches.
Note that the key-switch should normally be in the disabled position
(fully counterclockwise), with the key removed and access to the key
restricted to authorized personnel only. Do not leave the key
unattended in the ADT-LCD40.
2.2.2 Acknowledge
When the Acknowledge switch is pressed and released, the
ADT-LCD40 sends an Acknowledge command to the control panel.
Pressing the Acknowledge switch silences the local piezo sounder,
the sounders located in all other system annunciators and the
sounder located on the Fire Alarm Control Panel's main circuit
board. It will also change all flashing system LEDs to steady on.
Only one press is necessary regardless of the number of new alarms,
troubles or supervisory signals.
An acknowledge message is also sent to the printer and the history
files in the Unimode 200. Multiple active events (alarms, troubles,
supervisories) are scrolled on the display at a one second rate, but
may be held for sequential display by pressing and holding the
Acknowledge switch.
When more than one event exists, the first press of the Acknowledge
switch silences system piezo sounders and changes all flashing
Document 50520 Rev D 7/25/00 P/N 50520:D
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Switch Functions for ADT-LCD40 Only
LEDs to steady on. The second press of the switch stops the scroll-
ing and holds the event on the display for one minute. Subsequent
pressing of the switch 'steps' through each active event.
2.2.3 Silence
When the Silence switch is pressed and released, the ADT-LCD40
sends a signal silence command to the control panel. The Silence
switch performs the same functions as the Acknowledge switch. In
addition, if an alarm exists, it turns off all silenceable NACs and
causes the FACP Alarm Silence LED to turn on while the
ADT-LCD40 will display a 'silenced' message. It also sends an
'Alarm Silenced' message to the printer and the history file within the
Unimode 200. A subsequent new alarm will resound the appropriate
NACs (Notification Appliance Circuits) and local sounders.
2.2.4 Drill: Hold 2 Sec.
When the Drill switch is pressed and held for at least two seconds
(time required to prevent accidental activations), the ADT-LCD40
will transmit a drill command to the control panel. This command
causes the FACP to turn on both main panel NAC outputs and all
silenceable circuits (all C304 modules/NACs that are programmed
silenceable). In the event that the system was previously silenced,
the drill command will also turn off the Alarm Silence LED. The
'Manual Evacuate' message is shown on the ADT-LCD40 display.
The same message is sent to the FACP display, printer and history
files. The Silence switch operates on silenceable NAC outputs only.
2.2.5 Reset
When the System Reset switch is pressed and released, the
ADT-LCD40 sends a Reset command to the control panel. This will
turn off all C304 modules and Notification Appliance Circuits, tem-
porarily turns off resettable power to 4-wire detectors, causes a 'Sys-
tem All Normal' message to be displayed on the ADT-LCD40 and
sends a 'System Reset' message to the FACP display, printer and Uni-
mode 200 history files. It also turns on all system LEDs, piezo
sounders and LCD display segments as long as the Reset switch is
held (lamp test). Any alarm or trouble that exists after a Reset will
resound the system.
Document 50520 Rev D 7/25/00 P/N 50520:D
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
LED Indicators (all ADT-LCD40 Series)
2.3
LED Indicators (all ADT-LCD40 Series)
2.3.1 Power
This is a green LED which illuminates if AC power is applied to the
host FACP. The green LED will turn off if AC power to the host
FACP is lost.
2.3.2 Fire Alarm
This is a red LED that flashes when one or more fire alarms occur. It
illuminates steadily when an Acknowledge or Silence switch is
pressed. The Alarm LED turns off when the Reset switch is pressed.
2.3.3 Supervisory
This is a yellow LED that flashes when one or more supervisory
conditions occur, such as a sprinkler valve tamper condition. It
illuminates steadily when an Acknowledge or Silence switch is
pressed. It turns off when the Reset switch is pressed.
2.3.4 Trouble
This is a yellow LED that flashes when one or more trouble condi-
tions occur. It stays on steady when an Acknowledge or Silence
switch is pressed. The LED turns off when all trouble conditions are
cleared. This LED will also illuminate if the microprocessor watch-
dog circuit within the ADT-LCD40 Series is activated.
Document 50520 Rev D 7/25/00 P/N 50520:D
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
ADT-LCD40 Series Preparation
Section 3:
Mounting
3.1
ADT-LCD40 Series Preparation
The ADT-LCD40 Series Annunciators can be surface mounted in a
three-gang electrical box such as the P/N SBB-3 (2.75" depth) or semi-
flush mounted in a three-gang electrical box, P/N 10103 or equivalent,
with a minimum depth of 2 3/16". The ADT-LCD40 Series Annuncia-
tors cannot be mounted in three gangable electrical switch boxes con-
nected together. Select and remove the appropriate knockout(s), pull the
necessary wires through the knockouts and mount the three-gang box in
or on the wall depending on the type of installation desired. Be certain
that power is not applied to the wiring during the installation procedure.
Note: To ensure static protection, all enclosures, including the
ADT-LCD40 Series electrical box, must be connected to earth ground!
Never use the shield for grounding purposes.
To mount the ADT-LCD40 Series Annunciators in an electrical box, the
trim ring must first be removed. The trim ring is held in place by two
screws inserted through the top and bottom edge as illustrated in Figure
3-1. Removal of the trim ring will expose a metal flange with mounting
holes. Refer to “Hardware and Backboxes” on page 18.
Figure 3-1: Trim Ring Removal
Screw
FIRE ALARM ANNUNCIATOR
Drill
sec.
Ack
Silence
Reset
Hold
2
Screw
Document 50520 Rev D 7/25/00 P/N 50520:D
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
Hardware and Backboxes
Figure 3-2: Hardware and Backboxes
FIRE ALARM ANNUNCIATOR
Drill
Hold sec.
Ack
Silence
Reset
2
ADT-LCD40 Series flange
ADT-LCD40 Series Trim Ring
(replacement P/N 23165)
3-Gang Electrical Box P/N 10103
(semi-flush mount)
3-Gang Electrical Box P/N SBB-3
(surface mount)
Document 50520 Rev D 7/25/00 P/N 50520:D
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
Semi-flush Mount Backbox
3.2
Semi-flush Mount Backbox
Remove the plug-in terminal blocks from the ADT-LCD40(L) circuit
board. Connect the EIA-485 and power wiring into the terminal block
positions illustrated in Figure 1-1 on page 8, Figure 4-1 on page 21 and
Figure 4-2 on page 22. Plug the terminal blocks back into the P1 and P2
connectors on the back of the annunciator. Set DIP switch SW1 for the
desired options (refer to Figure 1-2 on page 9).
Carefully insert the ADT-LCD40(L) into the three-gang electrical box
and attach it using the four mounting holes on the ADT-LCD40(L)
flange and the four screws provided for this purpose. Replace the trim
ring and secure with the two screws which were previously removed.
Adjust the plastic trim ring to the surface of the wall before tightening
the screws. Do not overtighten.
Figure 3-3: Semi-flush Mounting
ADT-LCD40 Series flange
Mounting holes (4)
FIRE ALARM ANNUNCIATOR
CAUTION! The ADT-LCD40 Series can
Drill
sec.
Ack
Silence
Reset
Hold
2
be semi-flush mounted in a three-
ONLY
gang electrical box, P/N 10103 or equiva-
lent, with a minimum depth of 2 3/16".
The ADT-LCD40 Series
be
cannot
mounted in three gangable electrical
switch boxes connected together.
Three-gang electrical box
flange
EIA-485 and power wiring
ADT-LCD40(L)
Three-gang electrical box P/N 10103
Document 50520 Rev D 7/25/00 P/N 50520:D
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting
Surface Mount Backbox
3.3
Surface Mount Backbox
Remove the plug-in terminal blocks from the ADT-LCD40(L) circuit
board. Connect the EIA-485 and power wiring into the terminal block
positions illustrated in Figure 1-1 on page 8, Figure 4-1 on page 21 and
Figure 4-3 on page 23. Plug the terminal blocks back into the P1 and P2
connectors on the back of the annunciator circuit board. Set DIP switch
SW1 for the desired options (refer to Figure 1-2 on page 9).
Carefully insert the ADT-LCD40(L) into the three-gang electrical box
and attach it using the four mounting holes on the ADT-LCD40(L)
flange and the four screws provided for this purpose. Replace the trim
ring and secure with the two screws which were previously removed.
Do not overtighten.
Figure 3-4: Surface Mounting
ADT-LCD40 Series flange
Mounting holes (4)
FIRE ALARM ANN UNCIATO R
CAUTION! The ADT-LCD40 Series can
D
rill
sec.
A
ck
S
ilen ce
R
eset
be surface mounted in a three-
ONLY
Hold
2
gang electrical box, P/N SBB-3 or
equivalent, with a minimum depth of
2.75". The ADT-LCD40 Series
cannot
be mounted in three gangable electrical
switch boxes connected together.
Three-gang electrical box P/N SBB-3 or
equivalent with a 2.75" minimum depth.
flange
EIA-485 and power wiring
ADT-LCD40(L)
Three-gang surface box P/N SBB-3
Document 50520 Rev D 7/25/00 P/N 50520:D
20
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Electrical Connections
Power Connection
Section 4:
ADT-LCD40 Series Electrical
Connections
The ADT-LCD40 Series Annunciators can be powered by the Unimode
200 24VDC nominal power or from a remote UL listed, filtered power
supply such as the FCPS-24F. The power run to the annunciator must
be power-limited but need not contain a power supervision relay since
loss of power is inherently supervised through loss of communication
with the annunciator. Maximum ADT-LCD40 Series current draw from
the power supply (under alarm condition) is 66 mA. Maximum current
draw from the control panel's secondary power source (batteries) under
loss of AC power is 28 mA, since the LCD backlight is turned off during
AC loss. Backlighting is turned back on during AC loss only for alarm
conditions in the system.
Figure 4-1: Power Connection
ADT-LCD40 Series
P2
P1
Plug-in Terminal Blocks
no connection
+24 VDC IN from main power supply
+24 VDC OUT to next ADT-LCD40(L)
-24 VDC IN from main power supply
-24 VDC OUT to next ADT-LCD40(L)
Earth Ground Option
1. All connections are power-limited and supervised
2. 12 - 18 AWG (0.75 - 3.25 mm2) wire for 24 VDC circuit is
acceptable
3. Power wire distance limitation is set by 1.2 volt maximum line
drop from source to end of circuit.
Document 50520 Rev D 7/25/00 P/N 50520:D
21
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Electrical Connections
EIA-485 Connection
Figure 4-2: EIA-485 Connection
ADT-LCD40 Series
P1
P2
Ter minal Block
replacement
P/N 02109
Terminal Block replacement
P/N 02108
6,000 feet (1,800 m) maximum wire run
from and back to FACP (3,000 feet to last
ADT-LCD40) @ 18 AWG (0.75 mm )
+ EIA-485 IN from source
- EIA-485 IN from source
2
(+) (-)
EIA-485
Out to next ADT-LCD40 Series
or return to host FACP if last or
only annunciator on line
Notes:
1. All connections are power-limited and supervised
2. A maximum of 32 ADT-LCD40 Series annunciators may be con-
nected to this circuit
3. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm2)
between the panel, annunciators and return to the panel.
4. Use overall foil/braided-shielded twisted pair cable suitable for
EIA-485 applications (refer to “EIA-485 Shield Termination” on
page 25, for shield termination information)
5. The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA
maximum
6. The ADT-LCD40 Series annunciators have resistors built into
the circuit board at the In (Terminals 2 & 4) and the Out (Termi-
nals 1 & 3) for impedance matching. There is no need for the
installer to add impedance matching resistors
Document 50520 Rev D 7/25/00 P/N 50520:D
22
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Electrical Connections
DIM-485 Connections
Figure 4-3: DIM-485 Connections
Circuit Board
1
2
3
4
DIM-485 CONNECTIONS
ADT-LCD40 Series3
DIM-485
Terminal 1 - OUT (+)
Terminal 2 - IN (+)
Terminal 3 - OUT (-)
Terminal 4 - IN (-)
P1 Terminal 2 - IN (+)
P1 Terminal 12 - OUT (+)
P1 Terminal 4 - IN (-)
P1 Terminal 3 2 - OUT (-)
1. Terminal to terminal wiring is shown between the DIM-485 and
one ADT-LCD40 Series Annunciator
2. If more than one ADT-LCD40 Series Annunciator is installed,
the wiring to the DIM-485 In (+) Terminal 2 and In (-) Terminal
4 will be from the last installed annunciator (refer to Figure 4-4
on page 24)
3. The ADT-LCD40 Series Annunciators have resistors built into
the circuit board at the In (Terminals 2 & 4) and the Out (Termi-
nals 1 & 3) for impedance matching. There is no need for the
installer to add impedance matching resistors
4. Connect wiring to DIM-485 terminals before plugging DIM-485
into connector J11 of the Unimode 200 main circuit board.
Document 50520 Rev D 7/25/00 P/N 50520:D
23
Download from Www.Somanuals.com. All Manuals Search And Download.
ADT-LCD40 Series Electrical Connections
Wiring FACP to ADT-LCD40 Series
Dim-485 Installation.
CAUTION! Connect all wiring to the DIM-485 terminals before
plugging it into connector J11 on the Unimode 200 circuit board.
1. Carefully align the DIM-485 connector with the four pins on
connector J11 of the Unimode 200
2. Press firmly on the DIM-485 connector to seat properly on
connector J11 being careful not to bend any pins
3. Be certain to secure the DIM-485 module to the Unimode 200
and keep all wiring from mechanically interfering with module.
Figure 4-4: Wiring FACP to ADT-LCD40 Series
ADT-LCD40 Series in
grounded box
Ferrite Core P/N FBD-1
Required
24 VDC
TB4 Terms
3(+) & 4(-)
EIA-485
ADT-LCD40 Series in
grounded box
DIM-485
Unimode 200
in grounded box
1
2
3
4
Ferrite Core P/N FBD-1
Required
Top
P2
4
P1
1
2
3
5
6
7
1
2
3
4
(+) EIA-485
IN
n/c
(-) EIA-485
Earth
Ground
Optional
Shield
(+)
(-)
Notes:
EIA-485
OUT
Connect
1) Ferrite Core P/N FBD-1 is required to meet
FCC Part 15 requirements if the EIA-485
wiring is not in conduit. Twisted, shielded
wire is recommended for the EIA-485
communications loop.
(+) 24 VDC
IN
2) Six conductor overall shielded wire may be
used for the four EIA-485 wires and the two
power wires. It is, however, strongly
(-) 24 VDC
recommended that the power and communi-
cation wires be separate whenever possible.
(+)
(-)
24 VDC
OUT
Document 50520 Rev D 7/25/00 P/N 50520:D
24
Download from Www.Somanuals.com. All Manuals Search And Download.
EIA-485 Shield Termination
EIA-485 Shield Not in Conduit
Section 5:
EIA-485 Shield Termination
The EIA-485 circuit must be wired using a twisted, shielded pair cable
with a characteristic impedance of 120 ohms (+/- 20%). Do not run
cable adjacent to or in the same conduit as 120 VAC service, noisy
electrical circuits that are powering mechanical bells or horns, audio
circuits above 25 VRMS, motor control circuits or SCR power circuits.
Note: To ensure static (ESD - electrostatic discharge) protection, all
enclosures, including the ADT-LCD40 Series electrical box, must be
connected to earth ground! Never use the EIA-485 shield for this
purpose. The EIA-485 shield is for radiated noise emission protection
(RFI, EMI). Refer to the following figures for details on EIA-485 shield
termination.
5.1
EIA-485 Shield Not in Conduit
The EIA-485 line allows the FACP to communicate with the
ADT-LCD40 Series Annunciators. The shield for the EIA-485 line
must be connected to earth ground at the FACP but must be left floating
(no connection) at the annunciator if it is the first or only device on the
EIA-485 line. If a second annunciator is connected, the shield leaving
the first annunciator must be left floating. The shield entering the sec-
ond annunciator must be connected to the three-gang box or Earth
Ground terminal (P2-7) on the second annunciator. If additional annun-
ciators are connected, the shield leaving each enclosure must be left
floating and the shield entering each must be connected to the three-
gang box or the Earth Ground terminal (P2-7) on the annunciator.
Document 50520 Rev D 7/25/00 P/N 50520:D
25
Download from Www.Somanuals.com. All Manuals Search And Download.
EIA-485 Shield Termination
EIA-485 Without Conduit
Figure 5-1: EIA-485 Without Conduit
Connect the drain wire to the outside
of the Unimode 200 cabinet via a BX-
type connector.
Shield Drain Wire
(+) EIA-485
(-) EIA-485
FACP
FACP Backbox
Document 50520 Rev D 7/25/00 P/N 50520:D
26
Download from Www.Somanuals.com. All Manuals Search And Download.
EIA-485 Shield Termination
EIA-485 Shield in Full Conduit
5.2
EIA-485 Shield in Full Conduit
The EIA-485 line allows the FACP to communicate with the
ADT-LCD40 Series Annunciators. The shield for the EIA-485 line
must be connected to earth ground at the FACP (both exiting and
entering the FACP) but must be left floating (no connection) at the
annunciator if it is the first or only device on the EIA-485 line. If a
second annunciator is connected, the shield leaving the first annunciator
must be floating. The shield entering the second annunciator must be
connected to the Earth Ground terminal (P2-7) on the second annuncia-
tor. If additional annunciators are connected, the shield leaving each
annunciator must be left floating and the shield entering the following
unit must be connected to the Earth Ground terminal (P2-7) on the
annunciator.
Caution! Do not allow the floating (no connection) end of the shield to
contact the conduit. The floating end should be insulated from earth
ground.
Figure 5-2: EIA-485 In Conduit
ADT-LCD40 Series
Connect the shield drain wire to the Earth
Ground Terminal on the ADT-LCD40 Series
Annunciator
P1-2 (+)
EIA-485 (IN)
P1-4 (-)
EIA-485 (IN)
Shield Drain Wire
ADT-LCD40 Series Box
P2-7 Earth
Ground (IN)
Notes:
1) Power-limited 24 VDC power may be run in the same conduit as the EIA-485 wiring
2) Twisted, shielded wire is recommended for the EIA-485 communications loop
3) Each ADT-LCD40 Series electrical backbox is connected to earth ground via the conduit
4) Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP
Document 50520 Rev D 7/25/00 P/N 50520:D
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming the Unimode 200
EIA-485 In Conduit
Section 6:
Programming the Unimode 200
The Unimode 200 must be programmed to allow use of the
ADT-LCD40 Series Annunciators. In order to program the Unimode
200, make certain the main circuit board 'Write Protect' switch (SW1) is
in the down position and then press the ENTER key on the panel key-
pad. After pressing ENTER, the screen shown below is displayed:
1 = PROGRAMMING
2=RD.STATUS 3=AC/BAT
To enter the Programming Mode, press '1'. The display will read:
KEY PASSWORD, ENTER
Enter the Level 1 password. The following screen will appear:
0=CLR 1=AUTO 2=POINT
3=SYS 4=PWORD 5=LOAD
Press '3' to enter System Edit. The system edit screen may appear as
shown (note that previous programming may have altered some N or No
designations to Y or Yes):
V=N I=N A=N P=N C=N
A/U=N L/P=N S=4 R=4
Use the left and right arrow keys to move to the L/P option. Once at the
L/P option, to enable the ADT-LCD40 Series Annunciator option, use
the up and down arrow keys to scroll to the L (for ADT-LCD40 Series
Annunciator) choice. The ADT-LCD40 Series can now communicate
with the Unimode 200.
To leave Programming Mode, press the Backspace (left arrow) key
repeatedly until Program Mode is exited.
Document 50520 Rev D 7/25/00 P/N 50520:D
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
A
Acknowledge switch 6, 7, 12, 14
ADT-LCD40 6, 7, 10, 14, 15
see also ADT-LCD40 Series Annunciators
software version 6
ADT-LCD40 Series Annunciators 6, 12, 13, 16, 17, 19, 20, 21, 22,
23, 28
ADT-LCD40 Series Annunciators display
custom alpha labels 6
device type 6
point alarm 6
supervisory 6
system point status 6
trouble 6
zone labels 6
ADT-LCD40L 6, 7
see also ADT-LCD40 Series Annunciators
Alarm LED 6, 7, 16
Alarm Silence LED 15
annunciators
maximum per EIA-485 circuit 7, 12, 22
B
backboxes 18
backlight 7, 21
C
communication 6
see also EIA-485 circuit 6
communications fault 13
components 8
configuration 12
control switches
ADT-LCD40L only 6
current rating 21
AC fail 9
alarm 9
standby 9
trouble 9
D
DIM-485 23, 24
connections 23
installation 24
Document 50520 Rev D 7/25/00 P/N 50520:D
29
Download from Www.Somanuals.com. All Manuals Search And Download.
wiring 23
DIM-485 module 7
DIP Switch settings 8, 10, 11
function switches 11
piezo sounder 11
Receive/Transmit 10, 11
SW1 10
DIP switches 7
SW1 14, 19, 20
display
scroll 14, 15
step through 15
distance from panel 7, 12, 22
Drill switch 6, 7, 12, 14, 15
E
earth ground 9, 17, 25, 27
EIA-485 circuit 6, 7, 12, 19, 22, 25, 26, 27
fault 10
EIA-485 connection 22
electrical box 17, 18
electrical connections 21
electrostatic discharge 25
F
fault
communication failure 10
FCC Part 15 requirements 24
Ferrite Core 24
filtered 9
flange 18, 20
function switches 6, 7
enable/disable 11, 14
I
impedance matching 22, 23
K
key-switch 6, 14
enable/disable 7, 10
L
lamp test 15
LCD display 7, 13
mimic control panel display 6
see also Liquid Crystal Display 6
Document 50520 Rev D 7/25/00 P/N 50520:D
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Liquid Crystal Display 6
Local Authority Having Jurisdiction 8, 10
M
Manual Evacuate 15
mounting 7, 17, 19
semi-flush 7
surface 7, 20
N
NAC
see also Notification Appliance Circuit 15
nonresettable 9
O
Operation 13
P
piezo sounder 7, 15
alarm resound 7
enable/disable 8, 10, 11
silence 14
trouble resound 7
power connection 21
Power LED 6, 7, 16
power source 6, 9, 12, 21
power-limited 9, 12, 21, 22
power-up 13
programming 7, 12
Unimode 200 13, 28
R
Receive/Transmit 10, 11
Reset switch 6, 12, 14, 15
resettable power 15
resistors
impedance matching 22, 23
ROM 8
S
SBB-3 electrical box 17, 18, 20
semi-flush mounting 7, 19
shield 17, 25, 27
Signal Silence switch 7, 12
silence
NAC 15
piezo sounder 14, 15
Document 50520 Rev D 7/25/00 P/N 50520:D
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Silence switch 6, 14, 15
software version
ADT-LCD40 6
Unimode 200 6
static 25
static protection 17
supervised 21, 22
Supervisory LED 6, 7, 16
surface mount 7, 20
SW1 DIP Switch 10
switch functions 14
System LEDs 14, 15, 16
System Reset switch 7
System Status LEDs 6, 7
T
terminal block 7, 9, 19, 20
three-gang electrical box 17, 19, 20
trim ring 17, 18, 19, 20
Trouble LED 6, 7, 16
U
Unimode 200 6, 7, 12, 13, 15, 21, 23, 24, 26
programming 28
software version 6
Unimode 200 programming 13
W
wire
distance 21
requirements 12
size 21, 22
type 22, 25
wiring 12, 19, 23, 24, 25
wiring connections 9
Document 50520 Rev D 7/25/00 P/N 50520:D
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Document 50520 Rev D 7/25/00 P/N 50520:D
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Document 50520 Rev D 7/25/00 P/N 50520:D
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
Document 50520 Rev D 7/25/00 P/N 50520:D
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|