ADCP-50-404 • Issue 2 • November 1998
DMPS-10CE Power Supply
User Manual
Content
Page
Revision History .......................................................................1
Admonishments .......................................................................1
1. GENERAL............................................................................2
2. DETAILED DESCRIPTION .................................................................2
2.1 DMPS-10CE Power Supply (Basic) ......................................................2
3. DMPS-10EXP/CE EXPANSION MODULE ........................................................3
4. SPECIFICATIONS.......................................................................4
5. OUTPUT CABLE ASSIGNMENTS .............................................................5
6. INSTALLATION ........................................................................5
6.1 DMPS-10CE Power Supply Installation ....................................................5
7. DMPS-10EXP/CE EXPANSION MODULE INSTALLATION .............................................6
8. POWER-UP OF THE DMPS-10CE POWER SUPPLY .................................................7
9. REPLACING THE LINE FUSE ...............................................................7
10. CUSTOMER INFORMATION AND ASSISTANCE ...................................................8
Revision History
ISSUE
DATE
REASON FOR CHANGE
Issue 1
Issue 2
06/96
11/98
Original
Update Customer Information and Assistance section.
Admonishments
Important safety admonishments are used throughout this manual to warn of possible hazards
to persons or equipment. An admonishment identifies a possible hazard and then explains
what may happen if the hazard is not avoided. The admonishments — in the form of Dangers,
Warnings, and Cautions — must be followed at all times. These warnings are flagged by use
of the triangular safety icon (seen below), and are listed in descending order of severity of
injury or damage and likelihood of occurrence.
Danger: Danger is used to indicate the presence of a hazard which will cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe
personal injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor
personal injury or property damage if the hazard is not avoided.
2-70000-0344
Page 1
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
3. DMPS-10EXP/CE EXPANSION MODULE
The DMPS-l0EXP/CE Expansion Module, as shown in Figure 2, is designed to be installed
into the DMPS-10CE Basic Power Supply as dc power requirements expand at an installation.
The expansion module receives ac power from the basic shelf and is a completely self-
contained power supply in all other respects.
Up to three expansion modules can be mounted into the DMPS-l0CE Power Supply shelf. The
shelf requires a single ac power source (190 to 240 Vac, 48 to 62 Hz) to deliver up to 4 dc
outputs (via 9-pin cable connectors), each output supplying +5 Vdc, +12 Vdc and –12 Vdc.
Any input voltage between 190 and 240 volts ac can be accommodated without adjustment to
the power supply.
Outputs available from each of the modules (basic plus expansion modules) are +5 Vdc at up
to 4.5 Amps, +12 Vdc at up to 1.0 Amp, and –12 Vdc at up to 0.5 Amp.
Regulation is maintained on the respective voltages, keeping them constant to the tolerances
shown for the given current ranges:
+5 Vdc ± 5.0% for 0 to 4.5 Amps
+12 Vdc ± 10% for 0 to 1.0 Amps
–12 Vdc ± 10% for 0 to 0.5 Amps
J
2
J
3
J
4
E
1
J
1
8258-A
Figure 2. DMPS-10EXP/CE Expansion Module
Page 3
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
Ripple voltage* is held to the following limits:
+5 Vdc, at or below 50 Millivolts, Peak-to-Peak
+12 Vdc, at or below 120 Millivolts, Peak-to-Peak
–12 Vdc, at or below 120 Millivolts, Peak-to-Peak
* Measured with a device having a 50 MHz bandwidth.
4. SPECIFICATIONS
PARAMETER
SPECIFICATION
Input
Voltage
190/240 Vac
Current
2 Amps Maximum (4 Modules)
48 to 62 Hz
Frequency
Fusing (On rear of basic unit)
Output Each Module
Voltage
220 Vac: 4-Amp, Dual, Time Delay
+5 Vdc ± 5%
+12 Vdc ± 10%
–12 Vdc ± 10%
Current
4.5 Amp DC Max. @ +5 V
1.0 Amp DC Max. @ +12 V
0.5 Amp DC Max. @ –12 V
Physical
Chassis
3.5 19 11 inches (8.9 48.3 27.94 cm)
3.5 3.9 9.22 inches (8.9 9.91 23.5 cm)
Expansion Module
Environmental
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Electromagnetic Compatibility
0 to 50 C (32 to 122 F)
–40 to +70 C (–40 to 158 F)
10 to 80% non-condensing
5 to 90% non-condensing
Meets CISPR22 Class B radiated and conducted emissions.
Page 4
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
5. OUTPUT CABLE ASSIGNMENTS
Output from the DMPS-l0CE Power Supply is delivered via a 6 foot, 16 gauge cable,
terminated in a 9-pin connector. Pin assignments on the connector are as follows:
Pin 1 — +5 Volts
Pin 6 — Earth Ground
Pin 2 — +5 Volts
Pin 7 — Common Ground for +5 and ± 12 V
Pin 8 — Common Ground for +5 and ± 12 V
Pin 9 — –12 Volts
Pin 3 — +12 Volts
Pin 4 — No Connection
Pin 5 — No Connection
See Figure 3 for sketch of the 9-pin connector.
6
3
9
2
8
1
7
4
4555-A
Figure 3. 9-Pin Connector
6. INSTALLATION
6.1 DMPS-10CE Power Supply Installation
Remove each item from its shipping container and inspect the units for signs of damage. If
there are any damaged or missing parts, immediately file a claim with the commercial
common carrier or its agent, and notify ADC Telecommunications, Inc.
Normally, the ADC DMPS-10CE Power Supply is shipped with the standard single power
unit installed. Additional DMPS-10EXP/CE expansion modules are shipped in separate
containers. Occasionally, a power supply may be shipped with expansion modules installed. In
either case, installation of the power supply involves positioning the unit in the desired rack
space, near an ac utility outlet, and securing it with the mounting hardware normally used on
the mounting rack.
Note: The DMPS-10CE Power Supply requires air for convection cooling. Air holes in
the top cover and bottom cover allow air to flow through the power supply chassis. For
this reason, be sure to mount the DMPS-10CE Power Supply in such a fashion as to
leave at least half of the top and bottom surfaces open to air movement.
Page 5
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
7. DMPS-10EXP/CE EXPANSION MODULE INSTALLATION
Remove the DMPS-10EXP/CE expansion module from its shipping container and inspect it
for signs of damage or missing parts. If there are any damaged or missing parts, immediately
file a claim with the common carrier or its agent, and notify ADC Telecommunications, Inc.
Notice the connector plug on the front of the expansion module and also notice the one extra-
long pin on the plug. This pin is for chassis ground, and is extra long to assure that the ground
connection is made first and broken last for your protection when installing or removing the unit.
Caution: It is recommended that the expansion module not be installed or removed while
power is connected to the power supply shelf.
Proceed with the installation as follows:
(a) Set the ac switch at the front of the power supply to off (down position), and unplug the
power cord of the supply from its ac utility outlet.
(b) Remove and dispose of one of the four by four inch metal covers on the back of the
power supply by taking off the two screws holding it in place. Save the screws for use in
step (e) below.
(c) Notice the crimped sheet metal slots to the left hand side on the base of the power supply
shelf. The left-hand side of the “U” shaped base of the expansion module must slide into
these slots.
(d) Holding the expansion module with the “U” shaped base down and the 5-pin connector
plug forward, slide the module into the power supply, as shown in Figure 4, until the
connector pins engage the connector socket on the forward edge of the power supply.
Push in firmly to ensure proper connection of all pins in the plug.
CAUTION
ATTTENTION
CAUTION
MODEL
ATTENTION
VOLTS
HERTZ
DATE CODE
OUTPUT
VOLTS
AMPS
PH
CAUTION: DOUBLE POLE
NEUTRAL FUSING
U R
AMPS
CAT
S/N
#
250V 4A
T
MADE
I
N
U
S
A
DATE
CODE
8270-A
Figure 4. DMPS-10 EXP/CE Module Installation
Page 6
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
(e) Install the two screws removed in step (b) above to hold the expansion module in place.
(f) Connect the output power cable to the unit requiring the dc power. Pin assign-ments on
the cable connector are defined earlier in this manual.
Note: It is recommended that the DMPS-10CE Power Supply or the DMPS-10EXP/CE
expansion modules be connected to a load before ac power is applied.
8. POWER-UP OF THE DMPS-10CE POWER SUPPLY
The DMPS-10CE Power Supply has dual panel-mount fuse holders (located on the rear) to
provide over current protection in each leg of the ac input source. As shipped, the power
supply is fused with two 4-amp, time-delay fuses. To power the DMPS-10CE power supply
proceed as follows:
(a) Turn the power switch located on the front panel to the OFF (“0”) position.
(b) Connect the 220 Vac power cord provided to the power supply shelf.
(c) Cut the plug off the other end of the power cord. Replace the plug with a plug that
matches your utility outlet.
(d) Connect the other end of the power cord to the utility outlet.
(e) Set the ac switch at the front of the DMPS-10CE Power Supply to the on (“I”) position.
(f) Verify that power LED is lit on the front of the power supply for the basic power supply
and any expansion modules installed.
9. REPLACING THE LINE FUSE
The line fuses are located in dual panel-mount fuse holders on the back of the unit. To replace
a line fuse/fuses:
(a) Set the ac switch to OFF (“0”) position.
(b) Remove the line cord from its utility outlet.
(c) Disconnect the line cord from the socket in back of the DMPS-10CE Power Supply.
(d) Turn fuse holder carrier in a counter-clockwise direction and remove fuse carrier from
fuse holder. Fuse location is shown in Figure 5.
(e) Use an Ohm meter to check fuses for opens.
(f) Replace the bad fuse/fuses and reinsert the fuse carrier back into its socket. Turn fuse
carrier clockwise until fully seated.
(g) Repeat Steps d – f for the other fuse.
(h) Reconnect the power cord to the Power Supply and its utility outlet.
(i) Set the ac switch to ON (“I”) position.
Page 7
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
UTION
TENTION
CAUTION
MODEL
VOLTS
HERTZ
ATTENTION
DATE CODE
OUTPUT
VOLTS
AMPS
PH
CAUTION: DOUBLE POLE
NEUTRAL FUSING
U R
AMPS
CAT
S/N
#
250V 4A T
MADE
IN USA
DATE
CODE
FUSES
8271-A
Figure 5. DMPS-10CE Fuse Location
10. CUSTOMER INFORMATION AND ASSISTANCE
For customers wanting information on ADC products or help in using them, ADC offers the
services listed below. To obtain any of these services by telephone, first dial the central ADC
telephone number, then dial the extension provided below.
The central number for calls originating in the U.S.A. or Canada is 1-800-366-3891. For calls
originating outside the U.S.A. or Canada, dial country code “1” then dial 612-946-3000.
Sales Assistance
Extension 3000
• Quotation Proposals
• Ordering and Delivery
• General Product Information
Systems Integration
Extension 3000
• Complete Solutions (from Concept to Installation)
• Network Design and Integration Testing
• System Turn-Up and Testing
• Network Monitoring (Upstream or Downstream)
• Power Monitoring and Remote Surveillance
• Service/Maintenance Agreements
• Systems Operation
BBG Technical Assistance Center • Technical Information
Extension 3223
• System/Network Configuration
E-Mail: [email protected]
• Product Specification and Application
• Training (Product-Specific)
• Installation and Operation Assistance
• Troubleshooting and Repair/Field Assistance
Product Return Department
Extension 3748
• ADC Return Authorization number and instructions
must be obtained before returning products.
E-Mail: repair&[email protected]
writing ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
Page 8
© 1998, ADC Telecommunications, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ADCP-50-404 • Issue 2 • November 1998
Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In
no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further
disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of
liability applies to all products, publications and services during and after the warranty period.
This publication may be verified at any time by contacting ADC’s Technical Assistance Center at 1-800-366-3891, extension
3223 (in U.S.A. or Canada) or 612-946-3223 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc.,
Attn: Technical Assistance Center, Mail Station #77, P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
© 1998, ADC Telecommunications, Inc.
All Rights Reserved
Printed in U.S.A.