3Com Power Supply Prestige Series User Manual

®
p o w e r w a r e  
Pr e s t i g e Se r i e s  
3000 VA, 200-240V  
Installation and Operator’s Manual for IBM Applications  
Download from Www.Somanuals.com. All Manuals Search And Download.  
QUICK INSTALL  
UPS with PPDM Quick Installation  
1
If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS  
Monitoring feature should be set. See “UPS Monitoring” on page 52 for instructions.  
2
UPS  
Cabinet  
Battery  
Cabinet  
PowerPass  
Distribution  
Module  
(PPDM,)  
3
Bypass Switch  
(NORMAL Position)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Install  
4
I
ON  
I
ON  
Battery  
Breaker  
OFF  
OFF  
O
O
5
6
7
The UPS output voltage is factory-configured for 230V. If you need to change the output  
voltage, see “UPS with PPDM Startup” on page 42.  
For the AS/400 interface, plug the AS/400 communications cable into the serial port on the  
UPS rear panel. Plug the other end of the cable into the J14 connector or the connector  
labeled “UPS” on your AS/400.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
UPS Model and Battery Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Load Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Approximate Battery Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Special Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2
2
3
5
2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
UPS and Battery Cabinet Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
UPS with PowerPass Distribution Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
UPS with PPDM Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
REPO Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Troubleshooting Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
4 UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
UPS Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Battery Test on Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Battery Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
Changing the Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
UPS Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Using the PPDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Disconnecting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
Reconnecting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55  
5 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Initial Communications Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
Front Panel Communications Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
UPS Serial Communications Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60  
Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
UPS Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Communications Mode Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67  
3000 VA Model Specification with PPDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67  
Prestige 3000 UPS Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67  
Prestige 3000 UPS Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69  
Base Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69  
Standard Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69  
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71  
Resetting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73  
Silencing the Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73  
8 AS/400 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75  
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 1  
INTRODUCTION  
Congratulations on the purchase of your Powerware Prestige Series  
uninterruptible power system (UPS). The Prestige UPS meets the  
toughest measures of superior design and manufacturing, including  
ISO 9001. You now own the most reliable power protection available.  
The Prestige 3000 provides a steady, well-regulated power supply for  
your computing and communications equipment, while protecting it  
from the frequent irregularities that are inherent in commercially  
available power. Voltage spikes, power surges, brownouts, and power  
failures have the potential to corrupt critical data, destroy unsaved work  
sessions, and in some instances, damage expensive hardware.  
With the Prestige 3000, you can safely eliminate the effects of electrical  
line disturbances and guard the integrity of your systems and  
equipment. The PowerPass Distribution Module (PPDM) has a  
Maintenance Bypass feature that supplies power to your equipment even  
when the UPS electronics are removed for maintenance or upgrades.  
Figure 1 shows the Prestige 3000 UPS.  
Figure 1. Prestige 3000 UPS  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
UPS Model and Battery Configurations  
This UPS is designed to work with single-phase, three-wire, AC power  
sources. There are two important considerations when selecting the UPS  
model and battery configuration to properly safeguard your equipment:  
Load requirements  
Battery times  
Load Requirements  
The load is the equipment to be protected by the UPS. Select the UPS  
model that meets the power consumption requirements of the load in  
volt-amperes (VA). The total load VA should not exceed the UPS VA  
rating. To determine the total load requirements:  
1. Obtain the load ratings from either the nameplate or operators  
manual of the equipment to be protected by the UPS. The  
ratings are listed in either watts (W), amperes or amperes  
max (A), or volt-amperes.  
2. If the rating is in watts, multiply by 1.4 to obtain the VA  
requirement (this is the typical relationship between watts and  
volt-ampere ratings in most computing equipment). However,  
in some new computing equipment, the power supply is  
power-factor corrected and the watts rating equals the VA  
requirement. Check with the manufacturer to determine  
applicability.  
If the rating is in amperes or amperes max, multiply by the  
input voltage to obtain the VA requirement.  
NOTE For the load ratings of AS/400 models and attachable devices, see Chapter 9 of  
AS/400 Physical Planning Reference,” SC41-5109.  
3. Add all of the resultant VA ratings together to obtain the total  
load requirements of the equipment to be protected (see  
Figure 2). If the load consists of the power-factor corrected  
supplies, it is recommended to use total watts for the load  
requirements.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
3 COMPUTERS  
3 MONITORS  
EXTERNAL  
MODEM  
200 WATTS  
EACH  
1 AMP  
EACH AT 240V  
50 VA  
3 x 200 WATTS x 1.4 = 840 VA  
3 x 1 AMP x 240 = 720 VA  
50 VA  
840 VA + 720 VA + 50 VA = 1610 VA (Total Load Requirements)  
Figure 2. Volt-Amperes Calculation Example  
If the total load requirements of the equipment exceeds the capacity of  
the UPS, you must either reduce the number of pieces of equipment, or  
use a UPS with a larger load capacity.  
When deciding on which pieces of equipment to remove from the UPS,  
select equipment that has a lower priority for power protection.  
Computers, monitors, and modems typically have a higher priority  
because they could be processing or transmitting data when a power  
outage occurs.  
Approximate Battery Times  
During a power failure, the UPS battery supplies power to your  
equipment, providing time to complete computing activities prior to  
UPS shutdown. The duration of this time period is directly related to the  
UPS battery configuration. By adding battery cabinets, you can  
customize the UPS to provide enough battery time for normal processing  
activities.  
To prepare for a power outage at your installation, ensure that you have  
sufficient battery time available. To do this, take a few minutes to  
determine your approximate battery time by completing the following  
steps:  
Battery Time  
Load  
Requirements  
(VA)  
UPS Model  
Battery Cabinets  
Total Battery Time  
Minutes (Approximate)  
Prestige 3000 (9910 EP5)  
Figure 3. Determining Approximate Battery Time  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1. See “Load Requirements” on page 2 for assistance in  
determining the total load requirements for your UPS. Round  
this number up to the next Load (VA) entry in the following  
table, “Prestige 3000 with PPDM,” and enter the number in  
Figure 3.  
2. In Figure 3, enter the number of battery cabinets that you  
have installed. Find the intersection point of the appropriate  
Load (VA) and number of battery cabinets in the following  
table, “Prestige 3000 with PPDM.” Enter this number in  
Figure 3, Total Battery Time Minutes.  
If changes take place in your installation, such as different load  
parameters or changes to battery cabinet configuration, take time to  
reevaluate your approximate battery time availability.  
NOTE For detailed information regarding calculation of 9910 UPS battery capacityand  
run time for your load, reference: AS/400 Physical Planning,” SA41-5109, “AS/400  
Advanced Series Backup and Recovery - Advanced,” SC41-4305 (see Chapter 10), or  
AS/400e series Backup and Recovery,” SC41-5304 (see Chapter 37).  
Prestige 3000 with PPDM  
Approximate Battery Time (in Minutes)  
Load (VA)  
Load (W)  
1 Cabinet  
36.8  
2 Cabinets  
3 Cabinets  
600  
800  
420  
533  
88  
66  
44  
33  
26  
20  
16  
146  
110  
73  
27.6  
1200  
1600  
2000  
2500  
3000  
800  
18.4  
1067  
1333  
1667  
2000  
13.7  
54  
10.7  
42  
8.3  
33  
6.5  
27  
NOTE For AS/400 usage, see “Base Equipment” on page 69.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Special Symbols  
The following common symbols may be found on the UPS:  
LOAD ON - Press the button with this symbol to energize the  
output receptacles (Output On).  
LOAD OFF - Press the button with this symbol to de-energize  
the output receptacles (Output Off).  
SAFETY EARTHING TERMINAL - Indicates the primary safety  
ground.  
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric  
shock is present and the associated warning should be  
observed.  
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your  
operators manual for additional information.  
BYPASS - Indicates bypass control switches.  
INPUT BREAKER - Indicates the input breaker, which shuts  
off utility power to the UPS electronics.  
BATTERY BREAKER - Indicates the battery breaker, which  
shuts off battery power (power transmission through the  
battery cord).  
BATTERY CONNECTOR - Indicates the battery connector,  
which remains electrically “hot” even with the battery  
breaker off. Keep covered when not in use.  
OUTPUT BREAKER - Indicates an output breaker.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
This page intentionally left blank.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 2  
SAFETY WARNINGS  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you  
should follow during installation of the UPS. Please read all instructions before  
operating the equipment and save this manual for future reference.  
DANGER  
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed  
by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER  
SERVICEABLE PARTS inside the UPS.  
CAUTION  
Batteries can present a risk of electrical shock or burn from high short circuit  
current. Observe proper precautions.  
Proper disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
This UPS contains its own energy source (batteries). The output receptacles may  
carry live voltage even when the UPS is not connected to an AC supply.  
Never dispose of batteries in a fire. Batteries mayexplode when exposed to flame.  
Never open or mutilate batteries. Released electrolyte is harmful to the skin and  
eyes, and may be extremely toxic.  
Use only the power supply cord provided with this UPS. The power cord is wired in  
accordance with National Electrical Code (NEC) specifications. Be sure the wall  
outlet to be used with the UPS is wired in accordance with these same  
specifications in order to avoid damage to your equipment. Be sure that  
overcurrent protection for the AC outlet is provided at the time of installation. Be  
sure the input plug is completely inserted into the wall outlet. Use a single-phase,  
three-wire, grounded AC outlet only.  
To reduce the risk of fire or electric shock, install this UPS in a temperature and  
humidity controlled, indoor environment, free ofconductive contaminants.Ambient  
temperature must not exceed 104 F(40 C). Do not operate near water or  
excessive humidity (95% max).  
Do not remove or unplug the input cord when the UPS is turned on. This removes  
the safety ground from the UPS and the equipment connected to the UPS.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
To comply with internationalstandards and wiring regulations, the total equipment  
connected to the output of this UPS must not have an earth leakage current  
greater than 2.75 milliamperes.  
The wall outlet must be within 2 meters of the equipment and accessible to the  
operator. The on/off switch on the UPS does not electrically isolate the internal  
parts. Unplug the input cord from the wall outlet when disconnecting the unit for  
long periods of time.  
Please note that the output sockets on the UPS are electrically live whenever the  
UPS Output On button is pressed, even if the input cord is disconnected.  
For PowerPass systems with hardwired outputs, overcurrent protection for the  
output AC circuit(s) is to be provided by others.  
For PowerPass systems with hardwired outputs, suitablyrated disconnect switches  
for the output AC circuit(s) are to be provided by others.  
Sikkerhedsanvisninger  
VIGTIGE SIKKERHEDSANVISNINGER  
GEM DISSE ANVISNINGER  
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE  
SIKKERHEDSANVISNINGER  
FARE  
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og  
vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af  
UPS’ens indvendige dele kan repareres af brugeren.  
ADVARSEL  
Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj  
kortslutningsspænding. De korrekte forholdsregler bør overholdes.  
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for  
bortskaffelsesprocedurer.  
Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan  
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.  
Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere  
ved åben ild.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Batterierne bør aldrig åbnes eller skilles ad. Elektrolyt, der slipper ud, er skadelig  
for hud og øjne og kan være overordentlig giftig.  
Brug kun den netledning, som blev leveret med UPS’en. Denne netledning er  
tilsluttet ifølge specifikationerne for NEC (National Electrical Code). Sørg for, at  
stikket, som skal bruges til UPS’en, er tilsluttet ifølge de samme specifikationer for  
at undgå skade på dit udstyr. Sørg for, at der er overstrømsbeskyttelse på  
AC-stikket på monteringstidspunktet. Sørg for, at stikket er sat helt ind i  
stikkontakten. Brug en enfaset, -treledet AC-kilde, som er jordet.  
Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit  
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk  
stød. Rumtemperaturen må ikke overstige 40°C. UPSen bør ikke betjenes nær  
vand eller høj fugtighed (maksimalt 95%).  
Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er  
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.  
Ioverensstemmelse med internationale normer ogbestemmelser forel-installation  
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke  
overskride en jordafdelingsspænding på mere end 2,75 milliampere.  
Stikkontakten må højst være 2 meter fra udstyret og tilgængelig for brugeren.  
UPS’ens afbryderkontakt isolerer ikke elektrisk de indvendige dele. Træk derfor  
stikket ud af kontakten, hvis enheden er slukket i lang tid ad gangen.  
Bemærk venligst, at stikkontakterne på UPS’en er strømførende, når knappen UPS  
Output On” er trykket ned, selvom indgangsnedledningen ikke er tilsluttet.  
Med hensyn til Bypass-systemer med direkte forbundne udgange, skal  
overstrømsbeskyttelsen for AC-kredsen(e) komme andetsteds fra.  
Med hensyn til Bypass-systemer med direkte forbundne udgange, skal  
afbryderkontaktertilAC-kredsløbet medpassende mærkeeffekt kommeandetsteds  
fra.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Belangrijke Veiligheidsinstructies  
BELANGRIJKE VEILIGHEIDSINSTRUCTIES  
BEWAAR DEZE INSTRUCTIES  
DEZE HANDLEIDING BEVAT BELANGRIJKE  
VEILIGHEIDSINSTRUCTIES  
GEVAAR  
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en  
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden  
uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER  
kunnen worden GEREPAREERD.  
OPGELET  
Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als  
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.  
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw  
plaatselijke voorschriften.  
Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen  
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is  
aangesloten.  
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.  
Nooit batterijen openen of beschadigen. Vrijkomend elektrolyt is schadelijk voor de  
huid en ogen, en kan uiterst giftig zijn.  
Uitsluitend het elektriciteitssnoer gebruiken dat bij deze UPS wordt geleverd. Het  
snoer is volgens de specificaties van de IEC (International Electrical Code) bedraad.  
Controleer of wandcontactdoos waarop de UPS wordt aangesloten, volgens deze  
zelfde specificaties is bedraad teneinde schade aan uw apparatuur te voorkomen.  
Controleer of het wandcontactdoos voldoende is afgezeherd. Controleer of de  
voedingsstekker goed in het stopcontact is gestoken. Gebruik uitsluitend een  
enkelfasig geaard wandcontactdoos met randaarde.  
Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in  
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd,  
waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur  
mag 40 C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge  
vochtigheid (max. 95%).  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit  
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen  
aardebeveiliging meer hebben.  
Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de  
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen  
aardlekstroom van meer dan 2,75 milliampère hebben.  
De hoofdvoedingcontactdoos moet zich op minder dan 2 meter van de apparatuur  
bevinden en makkelijk bereikbaar zijn voor de gebruiker. De aan/uit-schakelaar op  
de UPS biedt geen elektrische isolatie voor de inwendige onderdelen. De stekker  
uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt  
gebruikt.  
Neem er nota van dat de uitgangaansluit punten op de UPS altijd onder stroom  
staan wanneer de belastingschakelaar ( ) wordt ingedrukt, ongeacht de  
aanwezigheid van de voeding.  
Voor Bypass systemen met vast-bedrade uitgangen, moet de  
overstroombeveiliging voor wisselstroom uitgangcircuit(s) door derden worden  
geleverd.  
Voor Bypass Module systemen met vast-bedrade uitgangen, moeten de juiste  
hoofdschakelaars voor wisselstroom uitgangcircuit(s) door derden worden  
geleverd.  
Tärkeitä turvaohjeita  
TÄRKEITÄ TURVAOHJEITA - SUOMI  
SÄILYTÄ NÄMÄ OHJEET  
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA  
VAARA  
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot  
on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä  
MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.  
VARO  
Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään  
oikosulkuun. Noudata asianmukaisia ohjeita.  
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia  
määräyksiä.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla  
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.  
Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.  
Älä avaa tai riko akkuja. Paljastunut elektrolyytti on vahingollinen iholle ja silmille  
ja voi olla erittäin myrkyllistä.  
Käytä vain tämän UPS-laitteen mukana toimitettua virtakaapelia, joka on kytketty  
kansallisten määräysten mukaisesti. Varmista, että UPS-laitteen kanssa käytetty  
pistorasia on johdotettu näiden samojen määritysten mukaisesti, jotta laitteet  
eivät vahingoittuisi. Varmista myös, että asennuksen yhteydessä vaihtovirran  
pistorasia varustetaanylivirtasuojauksella.Työnnä kosketin kokonaanpistorasiaan.  
Käytä pelkästään yksivaihteista, kolmijohtoista, maadoitettua verkkopistorasiaa.  
Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin, joissa  
lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia  
epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 C. Älä käytä lähellä vettä ja  
vältä kosteita tiloja (95 % maksimi).  
Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa  
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.  
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän  
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä  
2,75 milliampeeria (mA).  
Päävirtapistokkeen täytyy olla 2 m:n säteellä laitteistosta ja käyttäjän saatavilla.  
UPS-laitteen virtakytkin ei erota sisäosia verkkojännitteestä. Irrota  
sisääntulopistoke, jos kytket laitteen pois käytöstä pitkähköksi ajaksi.  
Ota myös huomioon, että UPS-laitteen ulostuloliittimissä on jännite aina kun  
painetaan UPSin lähtöteho PÄÄLLÄ -painiketta ( ), riippumatta siitä, onko  
tulokaapeli kytkettynä tai ei.  
Tämän laitteen mukana ei toimiteta lähdön ylivirtasuojausta kiinteän asennuksen  
ohitusjärjestelmissä.  
Tämän laitteen mukana ei toimiteta lähdön johdonsuojakatkaisijoita jakeluja  
varten kiinteän asennuksen ohitusjärjestelmissä.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Consignes de sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ  
IMPORTANTES  
DANGER!  
Cet onduleur contient des TENSIONS MORTELLES. Toute opération dentretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.  
ATTENTION!  
Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par  
des courts-circuits de haute intensité. Prendre les précautions nécessaires.  
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les  
règlements en vigueur dans votre localité.  
Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie  
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le  
secteur.  
Ne jamais jeter les batteries au feu. Lexposition aux flammes risque de les faire  
exploser.  
Ne jamais ouvrir ou mutiler des batteries. Lélectrolyte dégagé est nuisible à la  
peau et aux yeux et peut savérer extmement toxique.  
Utiliser uniquement le cordon d’alimentation fourni avec l’onduleur. Ce cordon est  
câblé conformément aux spécifications du Code électrique international (CEI).  
S’assurer que le câblage de la prise secteur devant être utilisée avec l’onduleur est  
lui aussi conforme à ces spécifications pour éviter d’endommager le matériel.  
S’assurer que la prise secteur est protégée contre les surcharges au moment de  
l’installation. S’assurer que la prise d’entrée est insérée à fond dans la prise  
secteur. Utiliser uniquement une prise secteur à trois fils, monophasée et mise à la  
terre.  
Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne  
doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Ne pas retirer le cordon dalimentation lorsque l’onduleur est sous tension sous  
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.  
Afin d’être conforme aux normes et règlements internationaux de câblage, le  
courant de fuite à la terre de la totalité du matériel branché sur la sortie de  
l’onduleur ne doit pas dépasser 2,75 mA.  
La prise secteur doit se trouver à moins de 2 m du matériel et être accessible à  
l’utilisateur. Linterrupteur de ON/OFF (marche/arrêt) de l’onduleur n’assure pas  
l’isolation électrique des pièces internes. Débrancher le cordon d’alimentation de  
la prise secteur en cas de déconnexion de l’appareil pendant une période  
prolongée.  
Noter que les prises de sortie de l’onduleur sont sous tension lorsque Output On  
buttonest enfoncé, même si le cordon d’alimentation est débranché de la prise  
secteur.  
Pour les systèmes de bypass dotés de sortie à bornier, la protection contre les  
surintensités des circuits de sortie de courant alternatif est à se procurer auprès  
d’un autre fournisseur.  
Pour les systèmes de bypass dotés de sortie à bornier, les interrupteurs adaptés au  
circuit de courant alternatif sont à se procurer auprès d’un autre fournisseur.  
Sicherheitswarnungen  
WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN  
AUFBEWAHREN.DIESES HANDBUCH ENTHÄLT WICHTIGE  
SICHERHEITSANWEISUNGEN.  
WARNUNG  
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten  
sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine  
vom Benutzer zu wartenden Komponente  
VORSICHT!  
Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder  
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind  
unbedingt zu beachten.  
Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen  
Bestimmungen zu beachten.en.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den  
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an  
einer Wechselspannungsquelle angeschlossen ist.  
Batterien niemals verbrennen, da sie explodieren können.  
Batterien nie öffnen oder anderweitig beschädigen. Derdarin enthaltene Elektrolyt  
wirkt ätzend auf Haut und Augen. Es besteht Vergiftungsgefahr!  
Nur das Netzkabel verwenden, das dieser USV beiliegt. Dieses Kabel ist gemäß  
den Spezifikationen des International Electrical Code (IEC) verdrahtet.  
Sicherstellen, daß die Wandsteckdose, die für die USV verwendet wird, gemäß  
den selben Spezifikationen verdrahtet ist, um eine eschädigung der Geräte zu  
vermeiden. Sicherstellen, daß bei Installation ein Überstromschutz für die  
Wechselstromsteckdose vorhanden ist. Sicherstellen, daß der Eingangsstecker  
vollständig in die Wandsteckdose eingesteckt wurde. Nur eine einphasige,  
geerdete Dreileiter-Wechselstromsteckdose verwenden.  
Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden  
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine  
leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40 C  
nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher  
Luftfeuchtigkeit (max. 95 %) betreiben.  
Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet  
ist, weil hierdurch die Sicherheitserdung von der USV und den daran  
angeschlossenen Geräten entfernt wird.  
Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an  
den Ausgang dieser USV angeschlossenen Geräte zusammen einen  
Erdschlußstrom von insgesamt 2,75 Milliampere nicht überschreiten.  
Die Netzsteckdose, die zur Hauptversorgung verwendet wird, darf sich nicht weiter  
als 2 Meter vom Gerät weg befinden und muß für den Bediener erreichbar sein.  
Der Ein-/Aus-Schalter der USV bietet keine elektrische Isolation der internen Teile.  
Wenn das Gerät längere Zeit nicht benutzt wird, sollte es von der Netzsteckdose  
abgezogen werden.  
Beachten, daß die Ausgangssteckdosen auf der USV jedesmal Strom führen, wenn  
der Belastungsschalter ( ) gedrückt wird, ungeachtet dessen, ob die USV mit  
Strom versorgt wird.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Für Bypass-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für  
die Ausgangswechselstromkreise anderweitig bereitgestellt werden.  
Für Bypass-Systeme mit festverdrahteten Ausgängen müssen Trennschalter für die  
AusgangswechselstromkreisemitpassendemNennwert anderweitigbereitgestellt  
werden.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Avvisi di sicurezza  
IMPORTANTI ISTRUZIONI DI SICUREZZA  
CONSERVARE QUESTE ISTRUZIONI  
QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI  
SICUREZZA  
PERICOLO  
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le  
operazioni di riparazione e di manutenzione devono essere effettuate  
ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo  
statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.  
ATTENZIONE  
le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da  
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.  
le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento  
fare riferimento alle disposizioni locali.  
questo gruppo statico di continuità contiene una fonte di energia autonoma (le  
batterie). Le prese di uscita possono condurre tensione energizzata quando il  
gruppo statico di continuità non è collegato con una fonte di alimentazione a  
corrente alternata.  
non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle  
fiamme.  
mai aprire nè mutilare le batterie poichè l’elettrolita da esse rilasciato è nocivo  
alla cute e agli occhi e può essere altamente tossico.  
usare esclusivamente il cavo di alimentazione in dotazione con il gruppo statico di  
continuità. Il cavo di alimentazione è cablato in conformità con le specifiche del  
Codice Elettrico Internazionale (IEC). Assicurarsi che la presa a muro nella quale si  
deve inserire il gruppo statico di continuità sia cablata in conformità con le  
medesime specifiche onde evitare di danneggiare l’apparecchiatura. Accertarsiche  
al momento dell’installazione la presa a corrente alternata sia protetta contro le  
sovracorrenti. Assicurarsi che la spina di ingresso sia completamente inserita nella  
presa a muro. Usare esclusivamente una presa a corrente alternata monofase, a  
tre fili, collegata a terra.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di  
continuità in un ambiente interno a temperatura ed umidità controllata, privo di  
agenti contaminanti conduttivi. La temperatura ambiente non deve superare i  
40 C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità  
eccessiva (95% max).  
non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di  
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di  
sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.  
per conformità con gli standard internazionali e con le norme in merito al  
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di  
continuità non deve avere una corrente di dispersione di terra superiore a  
2,75 milliampere.  
la presa di alimentazione principale non deve trovarsi a oltre 2 metri  
dall’apparecchiatura e deve essere accessibile all’operatore. Linterruttore on/off  
del gruppo statico di continuità non isola elettricamente i componenti interni.  
Scollegare l’unità dalla presa di alimentazione quando rimane in riposo per lunghi  
periodi di tempo.  
si noti che le prese di alimentazione di uscita del gruppo statico di continuità sono  
elettricamente energizzate ogniqualvolta viene premuto l’interruttore azzurro di( )  
attivazione uscita, a prescindere dal fatto che il gruppo statico di continuità sia  
alimentato o meno.  
nei sistemi Bypass provvisti di uscite cablate, i dispositivi di protezione da  
sovracorrente per il/i circuito/i a corrente alternata in uscita devono essere forniti  
da terzi.  
nei sistemi Bypass provvisti di uscite cablate, i sezionatori di corrente nominale  
adeguata per il/i circuito/i a corrente alternata in uscita devono essere forniti da  
terzi.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Viktig Sikkerhetsinformasion  
FARLIG  
Denne UPSen inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må  
kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE  
SERVICE PÅ NOEN AV DELENE i UPSen.  
FORSIKTIG  
Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy  
kortslutningsstrøm. Følg instruksene.  
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om  
fjerning av batterier.  
Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være  
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.  
Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.  
Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadelige for hud  
og øyne og kan være ekstremt giftige.  
Brukkun denstrømforsyningskabelen somfølger meddenne UPS’en.Strømkabelen  
er koblet i overensstemmelse med spesifikasjonene i IECs (International Electrical  
Code) bestemmelser. Sjekk at stikkontakten som anvendes for UPS’en er koblet i  
overensstemmelsen med de samme spesifikasjonene for å unngå skade på utstyr.  
Sjekk også at det finnes overstrømvern for vekselstrømkontakten under  
installeringen. Sjekk at støpselet er ført helt inn i stikkontakten. Bruk kun en  
en-faset, tre-trådet, jordet vekselstrømkontakt.  
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et  
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for  
ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40 C. Den må  
ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.).  
Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at  
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet  
med den.  
Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere  
total lekkasjestrøm enn 2,75 milliampere for å være i overensstemmelse med  
internasjonale standarder og forkablingsbestemmelser.  
Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig for  
operatøren. Av/På-bryteren på UPS’en isolerer ikke de interne delene. Trekk ut  
ledningen fra stikkontakten når utstyret frakoples over lengre tidsrom.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
UPSens stikkontakter for utgangsstrømforsyning er strømførende når lastbryteren  
( ) trykkes, uavhengig av strømforsyningen.  
For PowerPass systemer med fastkoplete uttak, må overstrømvern for  
vekselstrømuttak(ene) stilles til rådighet av andre.  
For PowerPass systemer med fastkoplete uttak, må passende utkoplingsbrytere for  
vekselstrømuttak(ene) stilles til rådighet av andre.  
Regulamentos de Segurança  
INSTRUÇÕES DE SEGURANÇA IMPORTANTES  
GUARDE ESTAS INSTRUÇÕES  
ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA  
IMPORTANTES  
CUIDADO  
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser  
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não  
há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.  
PERIGO  
As baterias podem apresentar o risco de choque elétrico, ou queimaduras  
provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.  
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do  
local para maiores informações sobre os regulamentos de descarte de produtos.  
Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída  
podem conter voltagem ativa quando a UPS não se encontra conectada a uma  
fonte de alimentação de corrente alternada.  
Nunca jogue as baterias no fogo, porque há risco de explosão.  
Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial à pele e  
aos olhos e pode ser extremamente tóxico.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Utilize somente o cabo de alimentação elétrica fornecido com a UPS. Este cabo foi  
fabricado de acordo com as especificações do IEC (International Electrical Code).  
Certifique-se de que a tomada de parede foi montada de acordo com estas  
mesmas especificações a fim de evitar danos ao seu equipamento. Na hora da  
instalação, verifique se foi fornecida uma proteção contra sobrecarga de circuito  
para a tomada de corrente alternada. Verifique se o plugue de entrada está  
completamente inserido na tomada de parede. Utilize somente uma tomada de  
corrente alternada aterrada, trifilar, monofásica.  
Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente  
interno com temperatura e umidade controladas e livres de contaminadores  
condutíveis. A temperatura ambiente não deve exceder 40 C. Não opere próximo  
a água ou em umidade excessiva (máx: 95%).  
Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto  
removerá o aterramento de segurança da UPS e do equipamento conectado.  
Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o  
equipamento totalconectado à saída desta UPS não deve ter uma corrente de fuga  
à terra maior que 2,75 miliampères.  
O soquete de alimentação principal deve estar no máximo dois metros do  
equipamento e acessível ao operador. O interruptor on/off da UPS não isola  
eletricamente as peças internas. Desconecte-o do soquete de alimentação se não  
for usá-lo por um longo período.  
Favor observar que o soquete de alimentação de saída na UPS estará  
eletricamente ativo todas as vezes que o interruptor ( ) estiver pressionado,  
indiferente à presença de energia elétrica na rede de alimentação.  
Para sistemas Bypass com saídas conectadas, a proteção de sobrecarga para  
circuitos de saída de corrente alternada deve ser fornecida por outros.  
Para sistemas Bypass com saídas conectadas, interruptores de desconexão  
devidamente qualificados para circuitos de saída de corrente alternada devem ser  
fornecidos por outros.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Предупреждения по мерам безопасности  
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
СОХРАНИТЕ ЭТИ УКАЗАНИЯ  
ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ  
УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ  
О П А С Н О  
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ.  
Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО  
УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ.  
Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.  
О С Т О Р О Ж Н О  
Аккумуляторы могут вызвать опасность поражения электрическим  
током или ожога от тока короткого замыкания. Соблюдайте  
соответствующие меры предосторожности.  
Необходимо соблюдать правила утилизации аккумуляторов.  
Обратитесь к местным нормативным актам за информацией о  
требованиях к утилизации.  
Данный ИБП содержит собственные источники энергии  
(аккумуляторы). На выходных розетках может иметься напряжение,  
даже когда ИБП не подключен к сети переменного тока.  
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут  
взорваться под воздействием огня.  
Никогда не открывайте и не деформируйте аккумуляторы.  
Вытекающий электролит опасен для кожи и глаз, и может быть  
крайне токсичным.  
Пользуйтесь только сетевым шнуром, поставляемым в комплекте с  
ИБП. Разводка сетевого шнура выполнена в соответствии с  
требованиями Международных электрических норм (IEC). Во  
избежание повреждения Вашего оборудования убедитесь в том, что  
разводка настенной розетки, которая будет использоваться с ИБП,  
выполнена в соответствии с теми же требованиями. Убедитесь во  
время установки в том, что розетка оснащена средствами защиты от  
перегрузки по току. Убедитесь в том, что входная вилка надежно  
вставлена в настенную розетку. Пользуйтесь только однофазной  
трехпроводной заземленной розеткой переменного тока.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Для снижения опасности пожара или поражения электрическим  
током устанавливайте ИБП в закрытом помещении с  
контролируемыми температурой и влажностью, в котором  
отсутствуют проводящие загрязняющие вещества. Температура  
окружающего воздуха не должна превышать 40°С. Не  
эксплуатируйте устройство около воды или в местах с повышенной  
влажностью (макс. 95%).  
Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки  
при включенном ИБП. При этом защитное заземление отключается  
от ИБП и от оборудования, подключенного к ИПБ.  
Для обеспечения соблюдения требований международных  
стандартов и требований к разводке электрических цепей,  
суммарная величина тока утечки на землю всего оборудования,  
подключенного к выходу ИБП, не должна превышать  
2,75 миллиампера.  
Настенная розетка должна находиться в пределах 2 метров от  
оборудования и быть доступной для оператора. Выключатель ИБП  
не отключает внутренние узлы от входного электропитания. При  
отключении оборудования на продолжительные интервалы времени  
отсоедините входной сетевой шнур от настенной розетки.  
Пожалуйста, обратите внимание на то, что выходные розетки ИБП  
находятся под электрическим напряжением, если была нажата  
кнопка включения выхода ( ) ИБП, даже если входной сетевой  
шнур отключен.  
Для блока байпаса с неразъемными выходами защита от перегрузки  
по току выходной(ых) цепи(ей) переменного тока должна  
обеспечиваться сторонними организациями.  
Для блока байпаса с неразъемными выходами сторонними  
организациями должны быть обеспечены выключатели  
выходной(ых) цепи(ей) переменного тока, рассчитанные на  
соответствующий номинал.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD  
IMPORTANTES  
PELIGRO  
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico  
deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO  
AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del  
SIE.  
PRECAUCIÓN  
Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras  
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones  
correspondientes.  
Es necesario desechar las baterías de un modo adecuado. Consulte las normas  
locales para conocer los requisitos pertinentes.  
Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de  
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a  
un suministro de corriente alterna (c.a.).  
Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las  
expone a la llama.  
Nunca abra ni dañe las baterías. El electrolito que se libera es perjudicial para la  
piel y los ojos, y puede ser extremadamente tóxico.  
Utilice solamente el cable de entrada que se suministra con este SIE. El cable está  
instalado según las especificaciones del NEC (Código Eléctrico Nacional).  
Asegúrese de que el tomacorriente de la pared a utilizar con el SIE esté instalado  
según estas mismas especificaciones a fin de evitar daños en sus equipos.  
Asegúrese de que se coloca una protección contra sobreintensidad para el  
tomacorriente de c.a. en el momento de la instalación. Asegúrese de que el  
enchufe de entrada se inserte por completo dentro del tomacorriente de la pared.  
Utilice solamente un tomacorriente monofásico con tres cables de carga en c.a.  
con descarga a tierra.  
Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un  
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes  
conductores. La temperatura ambiente no debe exceder los 40 C. No trabaje cerca  
del agua o con humedad excesiva (95% máximo).  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
No retire o desenchufe el cable de entrada mientras el SIE se encuentre  
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos  
conectados al SIE.  
Para cumplir con los estándares internacionales y las normas de instalación, la  
totalidad de los equipos conectados a la salida de este SIE no debe tener una  
intensidad de pérdida a tierra superior a los 2,75 miliamperios.  
El tomacorriente debe encontrarse a menos de 2 metros del equipo y ser accesible  
para el operador. El interruptor de encendido/apagado del SIE no tiene aislación  
eléctrica de las partes internas. Desenchufe el cable de entrada del tomacorriente  
de la pared cuando desconecte la unidad durante períodos largos.  
Tenga en cuenta que los receptáculos de salida del SIE tienen corriente eléctrica  
siempre que se oprime el botón pulsador de conexión de salida del SIE (Output  
ON), aun cuando el cable de entrada esté desconectado.  
Para los sistemas de bypass con salidas cableadas, la protección por  
sobreintensidad para el (los) circuito(s) de la salida de c.a. se deberá adquirir a un  
tercero.  
Para los sistemas de bypass con salidas cableadas, los interruptores de  
desconexión regulados adecuadamente para el (los) circuito(s) de la salida de c.a.  
deberán ser adquiridos a un tercero.  
Säkerhetsföreskrifter  
VIKTIGA SÄKERHETSFÖRESKRIFTER  
SPARA DESSA FÖRESKRIFTER  
DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA  
SÄKERHETSFÖRESKRIFTER  
FARA  
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD  
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som  
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.  
VIKTIGT  
Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.  
Följ tillämpliga anvisningar.  
Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan  
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.  
Använda batterier får aldrig brännas upp. De kan explodera.  
Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för hud  
och ögon och kan vara mycket giftig.  
Använd endast den nätsladd som medföljer denna UPS-enhet. Nätsladden är  
kompatibel med IEC-specifikationerna (International Electrical Code). Kontrollera  
att det vägguttag som ska användas med UPS-enheten är draget enligt samma  
specifikationer, så att skada på utrustningen undviks. Kontrollera att det finns  
överspänningsskydd för växelströmsuttaget vid installationstillfället. Kontrollera  
att UPS-kontakten är ordentligt inskjuten i vägguttaget. Använd endast ett  
enfasigt, jordat växelströmsuttag.  
Minska risken för brand eller elektriska stötar genom att installera denna  
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga  
ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40 C.  
Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).  
Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort  
kerhetsjordningen från både UPS-enheten och den anslutna utrustningen.  
För att överensstämma med internationell standard och dragningsföreskrifter får  
inte den totala utrustning som anslutits till uttaget på denna UPS-enhet ha  
jordanslutningsström som överstiger 2,75 milliampere.  
Vägguttaget får vara högst 2 meter från utrustningen och måste vara inom räckhåll  
för användaren. UPS-enhetens strömbrytare isolerar inte elektriskt de interna  
delarna. Vid längre avstängning bör nätsladden dras ur vägguttaget.  
Observera att UPS-enhetens uttag är strömförande när laddningsström-  
brytaren (Output On button) trycks ned, oberoende av om spänningskällan är  
tillkopplad eller inte.  
Överströmsskydd för de utgående växelströmkretsarna ska tillhandahållas avandra  
för fast anslutna förbikopplingssystem.  
Strömbrytare för bortkoppling med passande dimensioner för de utgående  
växelströmkretsarna ska tillhandahållas av andra för fast anslutna  
förbikopplingssystem.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Warnings  
This page intentionally left blank.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 3  
INSTALLATION  
The following sections describe UPS storage requirements and the  
installation and startup of the UPS.  
Unpacking and Inspection  
Carefully unpack the UPS and battery cabinets, making sure to retain  
the packaging materials. Examine each unit carefully for any signs of  
damage and immediately notify your distributor if damage is present.  
For assistance with the IBM 9910 UPS, see Chapter 8, “AS/400 Service”  
on page 75.  
UPS and Battery Cabinet Storage  
If you plan to store the UPS or battery cabinets prior to use, store them  
in a cool, dry environment. Storage temperature should not exceed  
35 C (95 F) in order to preserve battery life. For longer term storage,  
energize the UPS and battery cabinet for approximately 8 hours every  
90 days in order to maintain battery charge.  
Whenever the units are not energized, verify the circuit breaker on all  
battery cabinets is returned to the OFF (O) position.  
UPS with PowerPass Distribution Module Installation  
The PPDM is a standard option for the AS/400 systems. The PPDM has a  
Maintenance Bypass feature that supplies power to your equipment even  
when the UPS electronics are removed for maintenance or upgrades.  
There are three PPDM models available: the 5-15R PPDM, the  
5-15R/6-15R PPDM, and the IEC 320-C13 PPDM. The rear panels of  
these models are shown in Figure 5 on page 37, Figure 6 on page 38,  
and Figure 8 on page 41, respectively.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Use the following procedure to install the UPS and battery cabinets with  
the PPDM:  
1. Place the UPS near the equipment to be protected. The UPS  
should be well ventilated and away from direct sunlight or  
other heat source.  
Place the UPS and battery cabinets on top of or beside the  
PPDM as shown in Figure 4.  
NOTE You can install additional battery cabinets while the UPS is operating, but  
confirm the UPS is not in Battery mode (see page 49).  
UPS  
Cabinet  
Air Vents  
Battery  
Cabinet  
PPDM  
Battery  
Cabinet  
UPS  
Cabinet  
PPDM*  
*NOTE: The IEC 320-C13 PPDM should  
be placed on top of the UPS cabinet.  
Figure 4. Cabinet Setup  
2. Verify the circuit breaker on all battery cabinets is in the  
OFF (O) position.  
3. Remove the battery connector guard. Plug the battery cord into  
the external battery connector on the UPS. All battery  
connectors are polarized to prevent incorrect connection.  
4. If additional battery cabinets are to be used, plug the battery  
cord of the second cabinet into the external battery connector  
of the first battery cabinet. Follow this procedure for each  
additional battery cabinet.  
5. Remove the breaker tie from the circuit breaker on all battery  
cabinets.  
6. Switch the circuit breaker on all battery cabinets to the ON ( )  
position.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Serial Port  
Power Input  
Connector  
Tie Wrap  
Mounts  
Battery  
Connector  
Input Circuit  
Protector  
Power Output  
Receptacle  
UPS Cabinet  
REPO  
Receptacle  
(Optional)  
Circuit  
Breaker  
External  
Battery  
Connector  
Breaker Tie  
Battery Cord  
Battery  
Cabinet  
Bypass  
Switch  
Y-Cord  
Load Circuit  
Protectors  
Utility Input  
Connector  
Power Output  
Receptacles  
(5-15R)  
PPDM  
Figure 5. UPS with 5-15R PPDM Rear Panel  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Serial Port  
Power Input  
Connector  
Tie Wrap  
Mounts  
Battery  
Connector  
Input Circuit  
Protector  
Power Output  
Receptacle  
UPS Cabinet  
REPO  
Receptacle  
(Optional)  
Circuit  
Breaker  
External  
Battery  
Connector  
Breaker Tie  
Battery Cord  
Battery  
Cabinet  
PPDM  
Y-Cord  
Bypass  
Switch  
Power Output  
Receptacle  
(IEC 320-C19)  
Output  
Protectors  
Neutral  
Ground Screw  
Power Output  
Receptacles  
(5-15R and  
6-15R)  
Utility Input  
Connector  
(IEC 320-C13)  
Figure 6. UPS with 5-15R/6-15R PPDM Rear Panel  
7. For 5-15R/6-15R PPDM Models Only: The factory default for the  
PPDM output neutral is grounded. In some countries, the  
output neutral should not be grounded. If your application  
requires an ungrounded output neutral, continue with Step 7;  
otherwise, skip to Step 8.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
For ungrounded output neutral applications only. Remove the  
ground screw, rotate the ground cover until it snaps into place,  
and reinstall the ground screw in the ungrounded position (see  
Figure 7).  
Neutral Ground Screw  
Ground Cover  
Neutral Ground Screw  
Ground Cover  
Grounded Position  
(Default)  
Ungrounded Position  
(For certain  
applications only)  
Figure 7. Output Neutral Ground Screw  
8. Two tie wraps are included with the UPS to secure the Y-cord to  
the input and output receptacles on the UPS rear panel. Insert  
the tie wrap through the slot on each tie wrap mount.  
9. Verify the Bypass switch on the PPDM rear panel is in the  
NORMAL position.  
10. Plug the Y-cord of the PPDM into the power connectors on the  
UPS rear panel.  
11. Verify that the plugs are fully seated.  
If power cord locking is required: loop the tie wraps around the  
Y-cord connections and tighten to secure the cord to the rear  
panel. Allow sufficient slack in the cord between the receptacle  
and the tie wrap. At least 12 (30 cm) of slack is recommended.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
12. For the AS/400 interface, plug the AS/400 communications  
cable into the serial port on the UPS rear panel. Plug the other  
end of the cable into the J14 connector or the connector labeled  
“UPS” on your AS/400.  
Specific locations of the J14 serial port are listed below  
according to the AS/400 model:  
AS/400 Models 3xx/5xx - located on the base power supply  
on the back of the system unit  
AS/400 Models 600/S10/620/S20 - on the power supply  
AS/400 Models 640/S30/650/S40/SB1 - on the right side of the  
regulator cage in the back of the tower  
13. The equipment to be protected by the UPS should be powered  
off. Plug the equipment into the power output receptacles on  
the PPDM rear panel.  
NOTES  
Use the IEC 320-C19/C20 output cord provided with the PPDM to connect the  
AS/400 to the PPDM.  
You may have to use the output cord provided with the PPDM for 230V usage.  
The AS/400 line cord should be used from the PPDM input connector to the wall  
outlet (see Step 4 on page 43). Some configurations require the input cord  
provided with PPDM.  
When using the PPDM, it is recommended that the equipment not be plugged  
into the UPS cabinet.  
Do not protect laser printers with the UPS/PPDM because of the exceptionally  
high cyclic power requirements of the heating elements.  
14. If you are using a Remote Emergency Power-Off switch, follow  
the instructions in “REPO Installation” on page 44.  
15. Start the UPS according to the following “UPS with PPDM  
Startup” procedure.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
PPDM  
Bypass Switch  
Utility Input  
Connector  
(IEC 320-C20)  
Power Output  
Receptacle  
(IEC 320-C19)  
Output  
Breakers  
Power Output  
Receptacles  
(IEC 320-C13)  
Serial Port  
Y-Cord  
Power Input  
Connector  
Tie Wrap  
Mounts  
Battery  
Connector  
Input Circuit  
Protector  
Power Output  
Receptacle  
UPS Cabinet  
REPO  
Receptacle  
(Optional)  
Circuit  
Breaker  
External  
Battery  
Connector  
Breaker Tie  
Battery Cord  
Battery  
Cabinet  
Figure 8. UPS with IEC 320-C13 PPDM Rear Panel  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
UPS with PPDM Startup  
To start up the UPS:  
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM  
system value for the UPS Monitoring feature should be set. See  
“UPS Monitoring” on page 52 for instructions.  
2. Confirm the Bypass switch on the PPDM rear panel is in the  
NORMAL position.  
3. Steps 4 through 8 are for changing the output voltage. The  
output voltage is factory-configured for 230V. If you do not  
need to change the output voltage, skip to Step 9.  
Use the following table to select the correct output voltage  
according to your PPDM.  
PPDM Model Number  
5-15R PPDM 208: 120/208  
UPS Voltage Selection*  
208  
208  
5-15R PPDM 208: 120/240  
5-15R PPDM 208: 120  
208  
5-15R PPDM 240: 120/240  
Set to 220V for 110/220V PPDM output  
Set to 230V for 115/230V PPDM output  
Set to 240V for 120/240V PPDM output  
5-15R PPDM 240: 120  
Set to 220V for 110V PPDM output  
Set to 230V for 115V PPDM output  
Set to 240V for 120V PPDM output  
5-15R/6-15R PPDM: 208  
5-15R/6-15R PPDM: 240  
IEC 320-C13 PPDM  
208  
240  
Set to 220V for 220V PPDM output  
Set to 230V for 230V PPDM output  
Set to 240V for 240V PPDM output  
The UPS output voltage should be set according to local mains voltage.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
4. Plug the input power supply cord (use the AS/400 or PPDM  
line cord) into the utility input connector on the PPDM rear  
panel.  
Press and hold the Output  
Off button while plugging the  
other end of the power supply cord into a grounded, three-wire,  
AC receptacle that has been wired in accordance with NEC  
specifications or national wiring rules. Release the  
Output  
Off button when the alarm beeps. All indicators flash  
simultaneously.  
5. Press and hold the Output On button until the alarm beeps  
again.  
Two indicators, corresponding with the current setting, remain  
flashing. The output voltage is factory-configured for 230V.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
240V  
230V  
220V  
208V  
Figure 9. Output Voltage Indicators  
6. Press the Output Off button to scroll through the output  
voltage options, top to bottom. Each time you press the button,  
the UPS beeps and the next two indicators flash.  
NOTE If you do not save a selection within two minutes, the setup automatically  
aborts and switches back to the original configuration.  
7. Press and hold the Output On button until the alarm beeps to  
select and save the output voltage. Failure to release the button  
immediately after the beep will cause the UPS to abort the  
setup.  
8. Continue to Step 10.  
9. Plug the input power supply cord into the utility input  
connector on the PPDM rear panel.  
Plug the other end of the power supply cord into a grounded,  
three-wire, AC receptacle that has been wired in accordance  
with NEC specifications or national wiring rules.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
10. Turn on the equipment that is connected to the UPS.  
11. Press and hold the Output On button until you hear the UPS  
beep (approximately one second).  
The  
indicator remains lit and the Self Test indicator turns  
on. The front panel displays the percentage of full load being  
applied to the UPS. The UPS is now in Normal mode with the  
load online. See “Normal Mode” on page 48 for more  
information.  
REPO Installation  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the  
hardwired installation.  
The REPO switch is a customer-supplied switch that can disconnect UPS  
output voltage from your protected equipment. If you are using a REPO  
switch, you need a junction box, external wiring, and a switch with the  
following specifications:  
The switch should be a wall-mounted, momentary-contact, normally  
open, pushbutton switch.  
Minimum ratings of 240 Vac and 35 mA.  
Wire should be 18 AWG (0.75 mm2) minimum.  
CAUTION  
The black and white REPO wires are at high-voltage potential (240V). Refer to your  
local electrical code for proper installation of the high-voltage REPO wires.  
To ensure the UPS stops supplying power to the load during any mode of  
operation, the input power must be disconnected from the UPS when the  
emergency power-off function is activated.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
1. Place the conduit through the access hole on the junction box  
(see Figure 10). Connect the exposed conduit wires to the  
corresponding compression terminals (see the following table).  
Tighten the compression terminals with a screwdriver.  
2. Pivot the REPO receptacle guard out of the way, plug the REPO  
plug/receptacle UPS connector into the REPO receptacle on the  
UPS rear panel and twist the connector in place (see Figure 5  
on page 37).  
Mounting Holes  
Plug/Receptacle  
UPS Connector  
Access Hole  
for Conduit  
Three Foot Cord  
Terminal Block  
Figure 10. Optional REPO Cord Junction Box  
Power Cable Terminations  
Wire Function Terminal Terminal Wire  
Tightening Torque  
Entrelec Phoenix  
Position  
Size Rating*  
Contact  
REPO  
L1  
TB1-4  
12 - 22 AWG  
(4 - 0 mm )  
L2  
TB1-5  
3.5 - 5.3 lb in 5.6 - 6.8 lb in  
2
Ground  
TB1-6  
2
Suggested wire size is #18-AWG (0.75 mm )75 C copper wire minimum.  
The REPO function activates when L1 and L2 are shorted together.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Troubleshooting Tips  
If you should encounter any problems during startup, see the  
troubleshooting chart on page 71.  
The battery cabinets are shipped with the batteries charged. However,  
batteries may lose some of the charge during shipping and storage. You  
can use the UPS immediately after unpacking, but it may not provide the  
full-rated backup time during a power failure. Upon initial startup, the  
UPS may need to operate for approximately 8 hours before the battery is  
fully charged and full battery-backup time is available. If the Battery  
Fault indicator flashes, operate the UPS for 24 hours to fully charge the  
battery.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 4  
UPS OPERATION  
This chapter covers the operation of the UPS including front panel  
functions, operating modes, using the Battery Start feature, shutting  
down the UPS, and using the PowerPass Distribution Module.  
UPS Front Panel  
The UPS front panel has three distinct functions:  
Displays the UPS operational mode (Normal, Bypass, or Battery).  
Displays any alarm conditions present during operation (the  
indicators flash).  
Displays the loading percentage during Normal mode and the battery  
capacity during Battery mode.  
You can also use the front panel to configure UPS communication  
options and to configure the UPS output voltage. See “Front Panel  
Communications Access” on page 58 or “Changing the Output Voltage”  
on page 51.  
Output On Button  
(UPS on, load online)  
Output Off Button  
(UPS off, load offline)  
Indicator Legend  
Unlit  
Sine Wave Indicator  
Amber  
Green  
Flashing  
Overload Indicator  
Site Fault Indicator  
Overtemp Indicator  
Battery Fault Indicator  
Self Test Indicator  
Battery Online Indicator  
Figure 11. UPS Front Panel  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
Operating Modes  
After you install and apply power to the UPS, the UPS filters and  
regulates incoming AC power, eliminating noise and voltage spikes, and  
provides consistent power to your equipment (see Figure 12). While  
power is applied to the UPS, the maintenance-free battery is  
automatically kept in a fully-charged condition.  
Bypass Line  
Utility  
Power  
Surge  
Inverter  
Rectifier  
Suppression  
EMI/RFI Filters  
UPS Load  
Outlet  
Battery Cabinets  
Battery  
Charger  
Battery  
Battery  
Battery  
Figure 12. UPS Block Diagram  
Normal Mode  
During Normal mode, the  
indicator illuminates and the front panel  
displays the percentage of UPS load capacity being used by the protected  
equipment (see Figure 13).  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
LOAD ON  
LOAD ON  
LOAD ON  
LOAD ON  
LOAD OFF  
APPROX.  
81-100%  
LOAD  
APPROX.  
61-80%  
LOAD  
APPROX.  
41-60%  
LOAD  
APPROX.  
0-40%  
LOAD  
NORMAL  
UTILITY  
Figure 13. Normal Operation Indicators  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
Bypass Mode  
The  
indicator and the  
indicator illuminate simultaneously,  
indicating Bypass mode (see Figure 14). When the UPS is in Bypass  
mode, the load is powered by utility power. However, utility power  
continues to be passively filtered by the UPS.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
LOAD ON  
UNIT ON  
BYPASS  
Figure 14. Bypass Operation Indicators  
Battery Mode  
When the UPS is operating during a power outage, the alarm beeps  
several times initially, and then once every 10 seconds while in Battery  
mode. The  
indicator illuminates. The front panel displays the  
approximate percentage of battery capacity remaining. You can calculate  
the approximate minutes of battery time by multiplying the Total  
Battery Time Minutes” (see Figure 3 on page 3) times the percentage  
indicated by the Battery Operation indicators (see Figure 15). When the  
utility power returns, the UPS switches to Normal mode operation while  
the battery recharges.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
BATTERY  
ONLINE  
BATTERY  
ONLINE  
BATTERY  
ONLINE  
BATTERY  
ONLINE  
BATTERY  
ONLINE  
>50%  
>25%  
>75%  
CAPACITY  
REMAINS  
SHUTDOWN  
IMMINENT  
LOW  
BATTERY  
WARNING  
CAPACITY CAPACITY  
REMAINS  
REMAINS  
Figure 15. Battery Operation Indicators  
If battery capacity becomes low while in Battery mode, the Battery Fault  
indicator begins to flash and the Self Test indicator remains lit,  
indicating approximately two minutes before UPS shutdown. The alarm  
beeps every two seconds.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
When shutdown is imminent, the Self Test indicator flashes. These  
warnings are approximate, and the actual time to shutdown may vary  
significantly. For approximate battery times see the table on page 4.  
Once these warnings are indicated, immediately complete and save your  
work to prevent data loss and similar difficulties. When utility power is  
restored after the UPS shuts down, the UPS automatically connects to  
the load when the startup is complete.  
Diagnostics  
The UPS periodically performs diagnostic tests while the unit is  
operating in Normal mode, ensuring proper operation. These tests  
include:  
Self Test  
Utility Verification Test  
Battery Discharge Test  
Over Temperature Test  
The UPS also runs a series of over 20 internal tests when power is first  
applied. If a diagnostic test fails, see Chapter 7, “Troubleshooting” on  
page 71.  
Battery Test on Demand  
You can perform a battery test on the UPS while it is operating in  
Normal mode by pressing the Output On button. The UPS  
automatically distributes some of the load to the batteries for 30 seconds  
and tests the batterys performance.  
Battery Start  
NOTE Before using this feature, the UPS must have been powered by utility power at  
least once.  
This feature allows you to start the UPS without utility power. After  
utility power has been unavailable for one minute, press and hold the  
Output On button until the alarm beeps.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
The UPS supplies power to your equipment and goes into Battery mode.  
The  
indicator remains lit and the front panel displays the percentage  
of battery capacity remaining to the UPS. This process should take about  
15 seconds.  
UPS Shutdown  
Performing a UPS shutdown turns off the power to your protected  
equipment. Confirm the equipment is prepared for a power-off before  
shutting down the UPS.  
NOTE Do not perform a UPS shutdown if you want to use the Maintenance Bypass  
feature on the PPDM (see Using the PPDM” on page 53).  
To perform a UPS shutdown:  
1. Press and hold the Output  
Off button until the long beep  
ceases (approximately three seconds).  
The  
indicator remains lit indicating Normal mode, load  
offline.  
2. Unplug the UPS.  
The UPS enters Battery mode for several seconds. The  
indicator turns off and the UPS shuts down.  
3. When all LEDs are no longer illuminated on the UPS, switch  
the circuit breaker to the OFF (O) position on each battery  
cabinet.  
Changing the Output Voltage  
To change the operating voltage of the UPS:  
1. Perform a UPS shutdown as described in the previous section.  
2. Follow the instructions in “UPS with PPDM Startup” on  
page 42.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
UPS Monitoring  
UPS monitoring is a standard feature of the AS/400 operating system.  
QUPSDLYTIM is a timer in the AS/400 that tells the system how long to  
run on UPS power before shutting down. Each AS/400 system is initially  
assigned a default value for QUPSDLYTIM.  
To determine the default value for your system or to change the value,  
refer to the Uninterruptible Power Supply section in one of the  
following IBM documents:  
“AS/400 Advanced Series Backup and Recovery - Advanced,”  
SC41-4305 (for AS/400 Models 3xx and 5xx)  
“AS/400e series Backup and Recovery,” SC41-5304  
(for AS/400 6xx and Sxx)  
V4R1 Backup and Recovery information (AS/400 Models 3xx, 5xx, 6xx  
and Sxx) is also available on the Customer Documentation AS/400  
Softcopy Library CD (SK3T-0118) and on the Internet at:  
NOTE *NOMAX tells the AS/400 to use customized shutdown software, and if none  
is available it will begin shutdown immediately when utility power fails. Do not set  
QUPSDLYTIM to “*NOMAX” unless you understand the implications of the “*NOMAX”  
function as described in one of the IBM documents listed above.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
Using the PPDM  
The PPDM provides continuous online power for your equipment. With  
the PPDM, you can replace or upgrade the UPS without losing power to  
your equipment. Figure 16 shows the operation of the UPS with the  
PPDM.  
Utility  
Power  
In  
UPS  
Out  
UPS Load  
PPDM  
Battery  
Battery  
Battery  
Figure 16. UPS and PPDM Block Diagram  
Disconnecting the UPS  
Use the following procedure to transfer the critical load to Maintenance  
Bypass (AC Line operation) and remove the UPS:  
1. Turn the Bypass switch on the PPDM to the BYPASS position  
(see Figure 17). The PPDM is now powering your equipment  
from utility power.  
2. Press and hold the Output  
Off button until the long beep  
ceases (approximately three seconds). The  
remains lit.  
indicator  
3. Remove the Y-cord connections from the UPS rear panel.  
CAUTION  
Do not remove the input power cord or your equipment from the PPDM.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
4. Switch the circuit breaker on all battery cabinets to the  
OFF (O) position.  
5. Disconnect the battery connector on the UPS rear panel.  
6. Remove the UPS.  
Power Input  
Connector  
Battery  
Connector  
Power Output  
Receptacle  
UPS Cabinet  
Battery  
Circuit  
Breaker  
Battery  
Cabinet  
Bypass  
Switch  
Y-Cord  
PPDM  
Figure 17. UPS with 5-15R PPDM Rear Panel  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
Reconnecting the UPS  
Use the following procedure to reinstall the UPS and transfer the critical  
load from Maintenance Bypass (AC Line operation) to the UPS:  
1. Reconnect the battery cabinet to the battery connector on the  
UPS rear panel.  
2. Switch the circuit breaker on all battery cabinets to the ON ( )  
position.  
3. Steps 4 through 8 are for changing the output voltage. The  
output voltage is factory-configured for 230V. If you do not  
need to change the UPS output voltage, skip to Step 9. Use the  
following table to select the correct output voltage according to  
your PPDM.  
PPDM Model Number  
5-15R PPDM 208: 120/208  
UPS Voltage Selection*  
208  
208  
5-15R PPDM 208: 120/240  
5-15R PPDM 208: 120  
208  
5-15R PPDM 240: 120/240  
Set to 220V for 110/220V PPDM output  
Set to 230V for 115/230V PPDM output  
Set to 240V for 120/240V PPDM output  
5-15R PPDM 240: 120  
Set to 220V for 110V PPDM output  
Set to 230V for 115V PPDM output  
Set to 240V for 120V PPDM output  
5-15R/6-15R PPDM: 208  
5-15R/6-15R PPDM: 240  
IEC 320-C13 PPDM  
208  
240  
Set to 220V for 220V PPDM output  
Set to 230V for 230V PPDM output  
Set to 240V for 240V PPDM output  
The UPS output voltage should be set according to local mains voltage.  
4. Press and hold the Output  
Off button while plugging the  
Y-cord of the PPDM into the power connectors on the UPS as  
shown in Figure 17.  
Release the Output Off button when the alarm beeps.  
All indicators flash simultaneously.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS Operation  
5. Press and hold the Output On button until the alarm beeps  
again.  
Two indicators, corresponding with the current setting, remain  
flashing. The output voltage is factory-configured for 230V.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
240V  
230V  
220V  
208V  
Figure 18. Output Voltage Indicators  
6. Press the Output Off button to scroll through the output  
voltage options, top to bottom. Each time you press the button,  
the UPS beeps and the next two indicators flash.  
NOTE If you do not save a selection within two minutes, the setup automatically  
aborts and switches back to the original configuration.  
7. Press and hold the Output On button until the alarm beeps to  
select and save the output voltage. Failure to release the button  
immediately after the beep will cause the UPS to abort the  
setup.  
8. Continue to Step 10.  
9. Plug the Y-cord of the PPDM into the power connectors on the  
UPS as shown in Figure 17.  
10. Press and hold the Output On button until you hear the UPS  
beep (approximately one second).  
The  
indicator remains lit and the Self Test indicator  
turns on.  
11. Turn the Bypass switch on the PPDM to the NORMAL position.  
The front panel displays the percentage of full load being  
applied to the UPS. The UPS is now in Normal mode with the  
load online.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 5  
COMMUNICATION  
The UPS is equipped with a communications interface port that allows  
communication with a wide variety of external devices including:  
Video or dumb terminal  
Serial printer  
Computer with power management or shutdown software  
AS/400 systems  
The serial port enables you to monitor and record diagnostic data with  
the following communication interfaces:  
Serial Communications Interface  
Terminal Mode  
Data Dump Mode  
Printer Mode, 2400 Baud, with Novell Contacts (default)  
Printer Mode, 19200 Baud, with Novell Contacts  
LAN Configuration  
Novell-Style Network Interface  
3Com-Style Network Interface  
AS/400-Style Network Interface  
Custom User-Configurable Interface  
Initial Communications Settings  
The UPS is factory-configured for one of several communication  
interfaces (usually determined by the customer). To determine the initial  
UPS communications configuration, you can:  
Look at the box label with the serial number (communication mode  
is shown in the upper right corner).  
Use the Display Configuration option on the UPS Serial  
Communications Menu (see page 60).  
For assistance with IBM 9910 UPSs, see Chapter 8, “AS/400 Service”  
on page 75.  
If you want to change the UPS configuration settings, use the front panel  
or the UPS Serial Communications Menu.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Front Panel Communications Access  
Before you access the front panel, review the following configurations  
and note the indicator that corresponds with the communication mode.  
NOTE Only the Printer mode front panel options change the baud rate. Use the UPS  
Serial Communications Menu to select other baud rates (see page 60).  
Indicator Legend  
Printer Mode, 2400 Baud, Novell Contacts  
Select this mode for the OnliNet or LanSafe  
software.  
Unlit  
Amber  
Green  
Flashing  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
Novell-Style LAN Contacts  
3Com LAN Manager  
Any baud rate other than 2400 or 19200  
Any communication mode and baud rate  
with Printer mode, or not Printer mode.  
option.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
SELF TEST  
AS/400-Style LAN Contacts, No Serial  
Select this mode for the OnliSafe software.  
Printer Mode, 19200 Baud (network  
devices), Novell Contacts  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
SELF TEST  
SELF TEST  
Figure 19. Front Panel Communication Options  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
To access the front panel communication options, perform the following  
steps:  
1. If the UPS is powered on, prepare your equipment for  
shutdown.  
Press and hold the Output  
Off button until the long beep  
ceases (approximately three seconds).  
Unplug the UPS. Wait until all indicators turn off and then  
continue to the next step.  
2. Plug in the UPS while pressing the Output  
Off button until  
the alarm beeps. All indicators begin flashing.  
3. Press and hold the Output  
Off button a second time until the  
alarm beeps again.  
A single indicator, corresponding with the current setting,  
remains flashing.  
4. Press the Output  
Off button to scroll through the  
communication options, top to bottom. Each time you press the  
button, the UPS beeps and the next indicator flashes.  
NOTE If you do not save a selection within two minutes, the setup automatically  
aborts and switches back to the original configuration.  
5. Press and hold the Output On button until the alarm beeps to  
select and save a communication option. Failure to release the  
button immediately after the beep will cause the UPS to abort  
the setup.  
6. Press the Output On button again to return the UPS to  
Normal mode.  
NOTE Printer mode selections are the only serial communication modes available  
from the front panel.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
UPS Serial Communications Menu  
With the UPS Serial Communications (Main) Menu, you can view or  
select UPS communication modes, baud rates, and LAN configurations.  
To change or display the current communications configuration:  
1. Connect the UPS serial port to a video monitor with a serial  
interface or to your computers serial port. If you are using  
OnliNet or LanSafe software, the UPS should already be  
connected to your computer.  
2. Set your terminal so that it matches the baud rate of the UPS  
(usually 2400 baud, 8 bits, No parity, 1 stop bit). Refer to your  
terminal or operating system documentation for details on  
configuring your terminal communication settings.  
3. At the terminal prompt, press Control-C until the UPS Serial  
Communications Menu appears.  
4. Select a menu option by typing the corresponding letter or  
number key. All menu selections are single keystrokes and are  
not case-sensitive.  
D > Display Configuration displays the current communication  
settings and the new settings that you have selected prior to  
saving them. The new settings are not effective until you select  
save from the Main Menu.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
NOTE Catalog #, Serial #, and Version # are all identification numbers unique to your  
UPS and can also be found on the UPS nameplate.  
1 > Continuous Dump The UPS regularly transmits status  
information to the computer. Baud rates of 1200 to 2400 are  
recommended to reduce host computer overhead when using  
this mode.  
2 > Polled Dump Status information is transmitted only when  
requested by a poll character (Control-E).  
3 > Smart Dump Status information is transmitted when polled, as  
in the previous mode. However, the transmission also occurs  
automatically whenever UPS status changes. For example, if  
there is a power outage, UPS status information changes and is  
therefore, automatically transmitted.  
A > ASCII Terminal The UPS displays the formatted data on the  
attached video terminal.  
B > VT100 Terminal The UPS displays the formatted data on the  
attached video terminal.  
P > Printer Dump The UPS prints the formatted data on the  
attached printer.  
L > LAN Configuration allows you to configure the UPS for a new  
LAN mode and displays the Select LAN Configuration Menu.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Select the AS400 option if you are using OnliSafe software to  
monitor the UPS.  
The Custom Configuration option has two screens: the first screen  
has options available for inverter shutdown, and the second  
screen has options available for the contact configuration.  
Consult your shutdown software documentation for details on  
the required signal states for configuring LAN communications.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Z > Set Baud Rate allows you to select a new baud rate. The Select  
Baud Rate Menu displays a list of baud rate options.  
5. To save the configuration settings, type S at the Main Menu  
prompt. The UPS operates and communicates under the new  
configuration, and defaults to these settings each time it is  
started.  
If you want to abandon the selections you have made, type Q to  
quit.  
NOTE Any changes you make to the UPS communications configuration must  
correspond to the communications equipment you are using. In particular, new baud  
rate selections for the UPS must match your communications equipment.  
Power Management Software  
Power management software allows you to monitor UPS operations  
automatically. To use OnliNet or LanSafe software, the UPS must be  
configured for any one of the Data Dump, Terminal, or Printer modes;  
however, Printer mode is preferred.  
OnliNet provides multiple levels of UPS monitoring and control, as well  
as automatic shutdown for many different operating systems. If you  
have any questions or would like further information, see Chapter 8,  
“AS/400 Service” on page 75 for the number to call in your location.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
UPS Communications Interface Port  
In addition to configuring the UPS for specific communication options,  
you must also ensure proper use of the serial port when connecting the  
UPS to your network or monitoring equipment.  
CAUTION  
The serial port LAN contacts are transistors and are rated at a maximum current of  
50 mA and a maximum of +40 Vdc. Do not exceed these ratings or apply any  
negative voltage or AC voltage to these contacts; otherwise, damage may occur to  
your UPS.  
Use only the pins specified for your communications configuration. The  
use of any additional pins for any of the following interfaces can cause  
interference with system communications.  
Even though your network uses the specified signal lines, the pins  
assigned to these signals at the network end of the cable may vary with  
those of the UPS serial port. The connector body and style may vary as  
well.  
NOTE Standard, pin-for-pin cables may not work correctly. Consult your network  
software or server manuals for system shutdown pin assignments.  
The UPS serial port complies with EIA RS-232 standards. RS-232  
specifies a maximum cable length of 50 ft (15m). See Figure 20 for the  
location of the serial port.  
UPS Rear Panel  
Serial  
Port  
Serial Port Detail  
Figure 20. Serial Port Location  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
Communications Mode Reference Chart  
The following chart defines the UPS serial port contacts. Serial  
communication is not available with 3Com and AS/400 network  
configurations. Use only the applicable pins for the selected  
communication mode; otherwise, interference problems may occur.  
Communication Mode Function  
Signal Name Pin No.  
True Condition  
N/A  
Serial  
Data to UPS  
Data from UPS  
Signal Ground  
Battery On  
RS232 TxD  
RS232 RxD  
2
3
N/A  
7
Novell  
ON.AC  
14/16  
23/24  
7/15/25  
14/16  
23/24  
7/15/25  
2
Open  
(Default)  
Low Battery  
Signal Ground  
Battery On  
TWO.MIN  
Closed  
Novell  
ON.AC  
Closed  
Closed  
(Custom)  
Low Battery  
Signal Ground  
TWO.MIN  
3Com  
Shutdown (Remote) SHUT.DOWN  
Positive Voltage  
Positive Voltage  
Positive Voltage  
(Default)  
Low Battery  
Battery On  
LOW.BATT  
PWR.FAIL  
9
10  
Signal Ground  
UPS Available  
Battery On  
7
AS/400  
UPS Available 11/13  
Utility Failure 14/16  
Closed  
Closed  
Closed  
Closed  
Bypass  
UPS Offline  
Low Battery  
17/19  
Low Battery  
Signal Ground  
23/24  
12/15/18/25  
Pin numbers separated by a forward slash ( / ) are connected together internally.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Communication  
This page intentionally left blank.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 6  
SPECIFICATIONS  
3000 VA Model Specification with PPDM  
Output Current  
(Total not to exceed 2000 Watts, 3000 VA)  
Input  
Voltage In:Out  
Current  
208:120/208  
208:120/240  
240:120/240  
208:120  
13.0A  
13.0A  
11.3A  
13.0A  
11.3A  
12.3A  
11.7A  
11.3A  
12.50A/14.40A  
12.50A  
12.50A  
12.50A (2x5-15R)/25.00A (L5-30R)  
12.50A (2x5-15R)/25.00A (L5-30R)  
13.64A  
240:120  
220:220  
230:230  
13.04A  
240:240  
12.50A  
Prestige 3000 UPS Physical Specifications  
Parameter  
Height  
UPS Cabinet  
252 mm (9.91”)  
142.5 mm (5.61”)  
400 mm (15.75”)  
7.4 kg (16.25 lb)  
Battery Cabinet  
252 mm (9.91”)  
142.5 mm (5.61”)  
400 mm (15.75”)  
23.6 kg (52 lb)  
PowerPass Distribution Module  
252 mm (9.91”)  
Width  
142.5 mm (5.61”)  
Depth  
400 mm (15.75”)  
Weight  
21.4 kg (47 lb)  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Prestige 3000 UPS Technical Specifications  
Input Voltage Range  
Input Power Factor  
Frequency Range  
Surge Protection  
Output Waveform  
160 to 276 Vac  
0.95 Typical  
50/60 Hz ±3 Hz  
IEC 801-4  
Sine wave  
Output Voltage  
(without PPDM)  
200/208/220/230/240 Vac ±3%  
Online (BTUs)  
978  
On Battery (BTUs)  
1468  
Common Mode Noise  
Rejection  
>60 dB @ 100 kHz  
>80 dB @ 100 kHz  
Transverse Mode Noise  
Rejection  
Input Cord  
Detachable 2-meter cord  
IEC 320 (1)  
Outlets (UPS Cabinet)  
Output Voltages and Outlets  
(with PPDM)  
120/208V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)  
120/240V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)  
220/230/240V: IEC 320-C13 (6), IEC 320-C19 (1)  
120/208V: L6-30R (1), 5-15R (4)  
120/240V: L6-30R (1), 5-15R (4)  
Batteries (10) per cabinet  
Battery Cabinet  
12 Vdc, 5 Ah, maintenance-free rechargeable lead acid  
120 Vdc  
Operating Environment  
Temperature: 10 Cto40 C  
(50 F to 104 F)  
Humidity:  
5 to 95%  
(noncondensing)  
Agency Approvals  
Safety: EN50091-1  
UL 1778  
cUL  
EMC: FCC Part 15 Class A  
EN50091-2  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Part Numbers  
Base Equipment  
Machine Model  
Type  
IBM Part  
Number  
VA  
Watts  
Volts  
Frequency  
Description  
Prestige 3000 Model 3000  
9910  
EP5  
21H1572  
3000  
2100  
120/208 or 120/240  
50-60  
All models include electronics module, PPDM (208V or 240V) input line cord, AS/400 communications cable, operators  
manual, and one battery pack.  
Standard Accessories  
IBM Part Number  
N/A  
IBM Type/Model  
9910-6602  
Description  
Prestige 3000 Full Battery Pack  
17G1792  
9910-6561  
Prestige 3000 PowerPass Distribution Module  
(IEC 320-C13 PPDM: 120/208)  
17G1793  
17G1794  
21H8436  
21H8437  
9910-6562  
9910-6563  
9910-6550  
9910-6551  
Prestige 3000 PowerPass Distribution Module  
(5-15R/6-15R PPDM: 120/208)  
Prestige 3000 PowerPass Distribution Module  
(5-15R/6-15R PPDM: 120/240)  
Prestige 3000 PowerPass Distribution Module  
(5-15R PPDM: 120/208)  
Prestige 3000 PowerPass Distribution Module  
(5-15R PPDM: 120/240)  
IBM Part Number  
Powerware Part Number  
124102011-001  
Description  
17G2374  
N/A  
15-ft. AS/400 Communications Cable  
L6-30P Input Line Cord  
152507429-003  
N/A  
152507829-001  
IEC 320-C19/IEC 309 Input Line Cord  
(for 9910-6561 only)  
N/A  
N/A  
N/A  
N/A  
N/A  
152507429-014  
152507429-017  
152600403-001  
152507379-001  
152600358-001  
IEC 320-C19/L6-30P Input Line Cord  
(for 9910-6562 and 9910-6563)  
IEC 320-C19/C20 Output Cord  
(for 9910-6561, 9910-6562, and 9910-6563)  
IEC 320-C13/C14 Output Cord (Qty. 4)  
(for 9910-6561 only)  
IEC 320-C13/5-15P Output Cord  
(for 9910-6562 and 9910-6563)  
IEC 320-C13/6-15P Output Cord (Qty. 2)  
(for 9910-6562 and 9910-6563)  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Optional Accessories  
IBM Part Number  
21H8444  
IBM Type/Model  
Description  
9910-6602  
Prestige 3000 Full Battery Pack  
Manuals  
IBM Order  
Number  
Description  
Powerware Prestige Series Installation and Operators Manual for IBM Applications (3000 VA)  
SC21-8379  
Manuals may be ordered from the IBM Mechanicsburg Distribution Center.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
Download from Www.Somanuals.com. All Manuals Search And Download.  
70  
C H A P T E R 7  
TROUBLESHOOTING  
The Prestige UPS is designed for durable, automatic operation and also  
alerts you whenever potential operating problems may occur. Use the  
following troubleshooting chart to determine the UPS alarm condition.  
Indicator Legend  
Unlit  
Amber  
Green  
Flashing  
Condition  
Possible Cause  
Action  
UPS does not turn on.  
UPS is not plugged in.  
Faulty wall socket.  
Plug UPS into working outlet.  
Test wall socket, repair as required.  
Reduce load, then reset breaker.  
UPS input breaker is tripped.  
UPS has not been activated.  
Load does not turn on.  
UPS beeps occasionally.  
Press the Output On button for one  
second, then release.  
Normal operation.  
None. UPS is protecting your  
equipment.  
UPS input breaker trips. Load fault.  
Check the load.  
Disconnect faulty load equipment.  
Wait several minutes before resetting  
the UPS input breaker.  
Restart the load.  
Utility line is out of  
specification.  
Test wall socket, repair as required.  
indicator remains  
lit, even though line  
voltage is present.  
UPS input breaker is tripped.  
Low battery capacity.  
Reduce load, then reset breaker.  
UPS does not provide  
the expected backup  
time.  
Allow battery to charge for 24 hours,  
then retest.  
Protected equipment power  
requirements exceed UPS  
capacity.  
Reduce load, then retest.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Condition  
Possible Cause  
Action  
Communications do not  
function properly.  
Incorrect communications  
cabling.  
Verify cable integrity (see page 64).  
Incorrect baud rate.  
Select a new baud rate (see page 63).  
Incorrect communication mode. Select a new communication mode  
(see Chapter 5).  
No output load voltage.  
Load plug(s) not fully seated.  
Load circuit protectors tripped.  
Verify load plug(s) are fully seated.  
Reset load protectors.  
Power requirements exceed UPS Your UPS continues to operate.  
OVERLOAD  
SITE FAULT  
OVERTEMP  
BATTERY  
capacity. If overload is greater  
than 105%, the alarm beeps  
every second and the UPS may  
switch to Bypass mode.  
Reduce load.  
SELF TEST  
The UPS switched to Bypass  
mode because the overload  
increased (above 105%). The  
alarm beeps.  
Reduce load.  
OVERLOAD  
If the Overload indicator remains lit,  
reset the UPS by pressing the  
Output On button until the alarm  
beeps.  
You may need to obtain a larger  
capacity UPS.  
The utility line voltage and  
frequency are out of  
specification.  
The inverter remains online, deriving  
power from the utility until it is no  
longer acceptable.  
Check the unit configuration.  
Refer to the product specifications  
(see page 67).  
UPS internal temperature is too  
high. The alarm beeps and the  
Shut down the UPS. Clear vents.  
Remove any heat sources. Wait  
UPS switches to Bypass mode for approximately 5 minutes and retry.  
OVERTEMP  
BATTERY  
approximately 10 minutes,  
Contact your service representative if  
allowing the UPS to cool down.  
condition persists.  
Weak battery while in Normal  
mode. The alarm beeps.  
Allow the battery to charge for  
24 hours, then retest. Have batteries  
replaced if condition persists.  
Battery breaker is open (O).  
Verify that the battery cabinet breaker  
is in the ON ( ) position.  
Battery cabinet is not properly  
connected to the UPS.  
Verify that the battery cords are  
connected.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Condition  
Possible Cause  
Action  
Weak battery while in Bypass  
mode.  
This usually indicates that the  
batteries need replacing or the UPS  
requires service. Contact your service  
representative.  
BATTERY  
Self Test failure. UPS internal  
problem.  
The UPS may switch to Bypass mode,  
depending on the circumstances.  
Reset the UPS by pressing the  
Output On button until the alarm  
beeps.  
SELF TEST  
Contact your service representative if  
condition persists.  
Resetting the UPS  
To reset the UPS while an alarm condition is present, press the  
Output On button until the UPS alarm beeps.  
Silencing the Alarm  
To silence the alarm for an existing fault, press and hold the  
Output On button for one second. The alarm becomes quiet.  
If UPS status changes, the alarm beeps, overriding previous alarm  
silencing. Press the Output On button again to silence the alarm.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
This page intentionally left blank.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C H A P T E R 8  
AS/400 SERVICE  
The following sections describe the methods for obtaining service for  
your UPS and warranty information.  
Warranty  
The warranty service on Powerware UPSs is element exchange. If the  
UPS becomes inoperative, the module that is inoperative will be  
replaced. For 3 kVA UPSs, this would either be the I/O, battery, or  
PowerPass Distribution Module. The process for obtaining a  
replacement module varies by country. Under NO CONDITIONS are  
IBM Customer Engineers authorized to remove the covers.  
The warranty on the replacement unit, should you require one, is for the  
remaining period of warranty of the original unit. See page 79 for a  
detailed description of the warranty.  
Installation Instructions  
Installation instructions are in pictorial form on the Quick Install pages  
in the front of this manual and also in written form beginning on page  
35. Safety instructions are provided in multiple languages and begin on  
page 7. Publications may be ordered from the IBM Mechanicsburg  
Distribution Center.  
Connected Equipment Insurance  
With this program, Powerware Corporation provides a $25,000  
Powerware Protection Guarantee. See page 80 for specific terms and  
conditions of the Powerware Protection Guarantee.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS/400 Service  
Battery Warranty  
If, in Powerware Corporations opinion, the unit fails to meet published  
specifications and the defect is within the terms of the limited warranty  
(attached), the defective part(s) will be repaired or replaced at the  
option of Seller with no charge for replacement parts. The battery is  
warranted to have at least 70% of original full load capacity at the end of  
five years from date of installation or 66 months after manufacture,  
whichever comes first. The warranty is invalid if the battery is subject to  
misuse, abuse, or physical damage.  
Warranty  
Model  
Part Number  
Coverage Area  
AP, Canada, LA, US  
EMEA  
5 Year  
3 Year  
X
EP5  
21H1572  
X
Obtaining Service  
The troubleshooting chart on page 71 covers most of the difficulties you  
may encounter during normal operations.  
For further assistance with IBM 9910 UPSs, see the following section  
that applies to you. For critical applications, expedited replacement may  
be available.  
Please have the following information ready when you call for service:  
Model number  
Serial number  
Version number (if available)  
Date of failure or problem  
Symptoms of failure or problem  
Customer return address and contact information  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS/400 Service  
Customer Responsibilities  
The customer is responsible for the following element exchange items:  
Receiving, unpacking, and exchanging of the defective element.  
Repacking the defective element in the container received with the  
replacement element.  
Following the instructions provided for return of the defective  
element.  
IBM on-site service for the element exchange activities is available for an  
additional charge.  
United States  
Customer Process for Service  
1. Customer calls 1-800-IBMSERV (Field Services Support-FSS).  
2. Customer indicates that the UPS is defective.  
3. The FSS will confirm that the unit is listed in the customer  
profile and notify Powerware.  
4. Powerware will promptly call the customer and ask for the  
serial number. Powerware will also attempt to determine the  
nature of the problem. The problem may be related to improper  
operation as opposed to a defect.  
5. If the unit requires replacement, Powerware will send a  
replacement unit.  
6. The customer is expected to install the replacement unit. To  
return the defective unit see the instructions on the bottom of  
the Return Material Authorization (RMA). The packaging  
material used for the replacement unit can be used for this  
purpose.  
Shipping  
Powerware will pay all shipping costs incurred (both to and from the  
customer site or IBM Designated Location) to replace the defective UPS  
system.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS/400 Service  
Handling of Incomplete, Damaged, or Incorrectly Shipped 9910  
UPSs  
If the customer initially receives a 9910 UPS that is incomplete,  
damaged, or incorrectly shipped:  
1. The customer calls IBM at 1-800-IBMSERV to report the  
problem.  
2. An IBM representative notifies the customer of how the  
problem will be resolved.  
Canada  
Customer Process for Service  
1. Customer calls 1-800-426-7378.  
2. Dispatch takes the information from the customer and notifies  
the IBM Customer Service Representative (CSR).  
3. Problem determination is performed by the CSR.  
4. If a replacement unit is required, the unit is ordered out of  
stock and sent to the customer.  
5. The CSR does the swap and returns the defective unit to the  
IBM parts center.  
Latin America  
Asia Pacific  
Customer Process for Service  
1. Customer calls the local IBM office servicing account.  
2. The IBM CE responds, determines the problem, and resolves  
the problem.  
Customer Process for Service  
1. Customer calls the local IBM office servicing account.  
2. The IBM CE responds, determines the problem, and resolves  
the problem.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS/400 Service  
EMEA  
Customer Process for Service  
1. Customer calls the local IBM office servicing account.  
2. The IBM CE responds, determines the problem, and resolves  
the problem.  
IBM Powercare Five-Year Warranty  
Applies only to electronics (unit) installed in the 50 United States of America, Canada, Latin America, and Asia Pacific:  
Powerware Corporation warrants the unit against defects in material and workmanship for a period of five years from the  
date of startup or sixty-six (66) months from the date of completion of manufacture, whichever period expires first.  
If, in Powerware Corporations opinion, the unit fails to meet published specifications and the defect is within the terms of  
this limited warranty, the defective part(s) will be repaired or replaced at the option of Seller with no charge for  
replacement parts. There will be no charge for replacement equipment installation or defective part repair in connection  
with defects covered by this Limited Warranty. Equipment sold, but not manufactured, by Seller (e.g. batteries, battery  
racks), shall be warranted only by the manufacturer of such equipment, Prestige 3000 Powerware Corporations line up  
and match batteries are warranted for 5 years from start-up or 66 months from manufacture subject to the terms attached  
hereto. Equipment repaired or replaced pursuant to this Limited Warranty will be warranted for the unexpired portion of  
the original warranty subject to all the terms thereof.  
This warranty does not apply to any unit that has been subject to neglect, accident, abuse, misuse, misapplication,  
incorrect connection, or that has been subject to repair or alteration not authorized in writing by Powerware Corporation  
personnel. THIS WARRANTY IS THE PURCHASERS (USERS) SOLE REMEDY AND IS EXPRESSLY IN LIEU OF ANY  
OTHER WARRANTY, AND THERE ARE NO OTHER EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES  
INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OF FITNESS FOR PURPOSE. Powerware  
Corporations liability on any claim of any kind relating to the unit, batteries or otherwise for any loss or damage arising  
out of or in connection with or resulting from this Agreement or from the performance or breach thereof shall in no case  
exceed the price allocable to the goods or services or unit thereof which gives rise to the claim.  
Sellers obligations under this Limited Warranty are conditioned upon receipt by Seller of all payments due (including  
interest charges, if any). During such time as Seller has not received payment of any amount due to Seller in accordance  
with the Contract terms under which the equipment is sold, Seller shall have no obligation under said warranty; also  
during this time the period of said warranty shall continue to run and the expiration of said warranty shall not be  
extended upon payment of the overdue amount. These limitations to said warranty apply even in the event that the  
equipment is sold by Seller for resale to an ultimate user.  
In no event shall Seller be liable for any indirect, incidental, special, or consequential damages. Seller shall not be  
responsible for failure to provide service or parts due to causes beyond Sellers reasonable control.  
Any advice furnished the Purchaser (user) before or after delivery in regard to use or application of Powerware  
Corporation equipment, is furnished without charge and on the basis that it represents Powerware Corporations best  
judgment under the circumstances. The use of any verbal advice by the Purchaser (user) is solely and entirely at its own  
risk.  
Preventive Maintenance (PM) is not required on the product to maintain the warranty.  
This limited warranty applicable only to products purchased from the IBM Corporation.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AS/400 Service  
Powerware Protection Guarantee  
Attached Equipment Protection Program Terms and Conditions  
Program Summary: Powerware Corporation guarantees to repair or replace (at the option of Powerware Corporation)  
any equipment that is damaged by AC power disturbances when said equipment is properly connected to a Powerware  
Corporation uninterruptible power supply (UPS) covered by the Powerware Protection Guarantee. This program provides  
for reimbursement of repair or replacement expenses up to $25,000.00 and applies only to component or physical system  
damage.  
Products Covered: The Powerware Protection Guarantee applies to all Powerware Corporation Prestige 3000 UPS  
systems that are covered under the original IBM AS/400 Powercare Limited warranty during the manufacturers warranty  
period.  
Applicability: The Powerware Protection Guarantee applies only to units installed in the United States of America, Latin  
America, Canada, Asia Pacific and were sold by IBM Corporation with AS/400 systems. Further, this Powerware  
Protection Guarantee applies only to end-users of the UPS product(s) who have returned the warranty registration card  
within 30-days after product delivery. This program does not apply to damage resulting from any cause other than AC  
power disturbances and is independent of the Powerware Corporation manufacturers warranty or service contract. The  
Powerware Protection Guarantee applies to the following AC power disturbances as defined by the American National  
Standards Institute (ANSI): power line transients; electrical spikes; electrical surges; brownout; blackout. UPS products  
must be properly maintained according to the manufacturers’ recommendations set forth in the operators manual and the  
UPS installation must adhere to electrical safety requirements set forth by the National Electrical Code (NEC) or  
applicable local code(s). The UPS must be properly connected to a properly installed electrical outlet or other connection  
per the NEC or applicable local code (s). The equipment covered by this guarantee must be connected directly to the  
output of the Powerware Corporation UPS product with no intervening electrical devices. The Powerware Protection  
Guarantee is null and void if the UPS product has been: misapplied; improperly maintained; mishandled; abused;  
improperly installed; altered in any way subjected to accident or misuse; used in other than normal operating conditions  
described in the UPS product specifications. The Powerware Protection Guarantee is independent of all other warranties  
and there are no other warranties expressed or implied, including warranties of merchantability and fitness for a particular  
purpose. IN NO EVENT SHALL POWERWARE CORPORATION BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL,  
INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF ITS’ PRODUCTS, EVEN IF ADVISED  
OF THE POSSIBILITY OF SUCH DAMAGE. Direct, indirect, special, incidental or consequential damages include, but are  
not limited to, lost profits or revenue, loss of equipment, loss of use of equipment, software loss, loss of data in whole or  
in part, recovery of data in whole or in part, restoration of data in whole or in part, corruption of data in whole or in part,  
cost of substitutes or rental equipment, claims by third parties or otherwise.  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INDEX  
Battery Fault  
alarm, 72  
Numeric  
3Com Network Interface  
indicator, 47  
front panel configuration, 58  
LAN Configuration Menu, 62  
Battery Mode, 49  
Battery Online, indicator, 47  
Battery Start, 50  
A
Battery Test on Demand, 50  
baud rates, 60, 63  
AC Line  
Bypass switch, 53  
operation, 53  
Bypass Mode, 49  
Bypass switch, 37, 38, 41  
alarm  
silencing, 73  
UPS, 72  
C
changing the output voltage, 51  
Alarm Conditions  
Battery Fault, 72  
Overload, 72  
communication  
interface port, 64  
modes, 60  
Overtemperature, 72  
Self Test Failure, 73  
Utility Out of Spec, 72  
UPS, 57  
Communications Mode Reference  
Chart, 65  
AS/400 Network Interface  
front panel configuration, 58  
LAN Configuration Menu, 62  
configuration settings  
abandoning, 63  
displaying, 60  
front panel, 58  
saving, 63  
ASCII Terminal Mode, 61  
contact configuration, serial port, 64  
Continuous Dump Mode, 61  
B
battery  
circuit breaker, 37, 38, 41  
configuration, 2  
extension time, 3  
input connector, 37, 38, 41  
installation, 35  
output connector, 37, 38, 41  
storage, 35  
Control Keys  
Control-C, 60  
Control-E, 61  
cord, power, 43, 68  
Custom LAN Configuration  
Menu, 62  
customer service, 75  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
load  
definition, 2  
D
requirements, 2  
Data Dump Modes, 61  
diagnostics, 50  
LOW_BATT, 62  
M
Display Configuration Screen, 61  
Main Menu, 60  
E
Maintenance Bypass feature  
See also PowerPass Distribution  
Module (PPDM)  
exiting Main Menu, 63  
activating, 53  
deactivating, 55  
F
Menu  
front panel  
Custom LAN Configuration, 62  
LAN Configuration, 62  
Main, 60  
Serial Communications, 60  
Set Baud Rate, 63  
configuring communications, 58  
display functions, 47  
indicators, 47  
front panel configuration  
3Com, 58  
AS/400, 58  
Novell, 58  
printer mode, 58  
Mode  
ASCII Terminal, 61  
Battery, 49  
Bypass, 49  
Communications, 60  
Data Dump, 61  
Normal, 48  
Printer, 59, 61  
Terminal, 61  
I
indicators, front panel, 47  
input cord, 43, 68  
VT100 Terminal, 61  
N
Inverter Shutdown Control, 62  
Normal Mode  
indicator, 47  
operation, 48  
L
LAN Configuration  
Main Menu option, 60  
menu, 62  
Novell Network Interface  
front panel configuration, 58  
LAN Configuration Menu, 62  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Maintenance Bypass feature, 35  
operation, 53  
O
Operating Modes, 48  
power output  
receptacles, 37, 38, 41  
rear panel, 37, 38, 41  
startup, 42  
Operation  
Battery, 49  
Bypass, 49  
Normal, 48  
UPS with PPDM, 53  
utility input connector, 37, 38, 41  
Printer Mode  
front panel configuration, 59  
Main Menu configuration, 61  
Output Off Button, 5, 47  
Output On Button, 5, 47  
R
output voltage  
changing, 51  
Remote Emergency Power-Off  
initial setting, 42  
switch. See REPO switch  
Overload  
REPO switch, plug/receptacle  
condition, 72  
indicator, 47  
UPS, 44  
resetting the UPS, 73  
Overtemperature  
alarm, 72  
indicator, 47  
S
Safety Warnings, 7  
Self Test  
failure, 73  
indicator, 47  
P
plug/receptacle UPS, installation  
optional REPO cord junction  
box, 45  
serial cable, 64  
serial port  
REPO switch, 44  
contact ratings, 64  
description, 64  
Polled Dump Mode, 61  
Power Management Software  
LanSafe, 58, 63  
OnliNet, 58, 63  
service  
for incomplete, damaged, or  
incorrect UPS, 78  
in Asia Pacific, 78  
in Canada, 78  
OnliSafe, 58, 62  
PowerPass Distribution Module  
(PPDM)  
in EMEA, 79  
AC Line operation, 53  
block diagram, 53  
installation, 35  
in Latin America, 78  
in the US, 77  
obtaining, 76  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Service and Support, 75  
Set Baud Rate Menu, 63  
shutdown, 51  
front panel, 47  
input circuit protector, 37, 38, 41  
installation, 35  
operation, 47  
Site Fault, indicator, 47  
Smart Dump Mode, 61  
specifications, 67  
operation with PPDM, 53  
power input connector, 37, 38, 41  
power output receptacle, 37, 38, 41  
rear panel, 37, 38, 41  
resetting, 73  
Startup Tests, 50  
storage temperature, 35  
Switch, Bypass, 37, 38, 41  
system requirements, 2  
Serial Communications Menu, 60  
serial port, 37, 38, 41, 64  
shutdown, 51  
special symbols, 5  
T
storage, 35  
unpacking and inspection, 35  
Terminal Modes, 61  
Tests  
UTIL_FAIL, 62  
Battery (on demand), 50  
Startup, 50  
Utility Out of Spec, 72  
transistors, contact ratings, 64  
troubleshooting  
chart, 71  
tips, 46  
V
U
volt-amperes, 2  
uninterruptible power system, 1  
VT100 Terminal Mode, 61  
UPS  
alarm silencing, 73  
alarms, 72  
block diagram, 48  
changing output voltage, 51  
communication, 57  
Communications Mode Reference  
Chart, 65  
W
warranty  
battery, 76  
external battery  
connector, 37, 38, 41  
IBM five-year, 79  
Powerware® Prestige Series Installation and Operators Manual for IBM Applications (3000 VA) Uncontrolled Copy  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀꢁꢂꢃꢄꢅꢁꢁꢆꢃꢇꢀ  
164201134 C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acer Flat Panel Television AT2001 User Manual
Acnodes Computer Monitor APH 8064 User Manual
Aiwa CD Player NSX MT241 User Manual
Aiwa Stereo System FR TC5000 User Manual
AKG Acoustics Microphone SPC 4 User Manual
Altec Lansing MP3 Docking Station iM510 User Manual
American DJ DJ Equipment Fan 1000 User Manual
American Standard Hot Tub 2425V LHO User Manual
Ask Proxima Projector DP6810 User Manual
Avocent Network Card SST 8P User Manual