DVPDNET-SL
DeviceNet Network Scanner
Operation Manual
DVP-0204520-03
2012-3-27
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4.1 Configuration through DeviceNet Builder Software ........................................................................... 8
4.1.1 Selection of Communication Channel......................................................................................... 8
4.1.2 Setup of Scan Module ................................................................................................................ 9
4.1.3 Setup of Scan List..................................................................................................................... 10
4.1.4 Input List and Output List...........................................................................................................11
4.2 Data Mapping Areas ........................................................................................................................ 12
4.3 I/O Mapping Table (as master mode) .............................................................................................. 12
4.4 I/O Mapping Table (as slave mode)................................................................................................. 13
5.1 The Principle of Explicit Message Sending...................................................................................... 14
5.2 Structure of Explicit Message .......................................................................................................... 15
6.1 Principle of Bit-Strobe ...................................................................................................................... 22
DISPLAY OF NODE STATUS ON NETWORK.................................................................................... 23
7.1 Display of Node Status in Scan List................................................................................................. 23
7.2 Status of DVPDNET-SL ................................................................................................................... 23
SETUP OF SLAVE MODE................................................................................................................... 24
SETUP OF EXTENDED BAUD RATE................................................................................................. 26
9.1 Setup of Extended Baud Rate (as master mode)............................................................................ 26
9.2 Setup of Extended Baud Rate (as slave mode)............................................................................... 28
10.1 How to Construct a DeviceNet Network ........................................................................................ 31
10.2 How to Configure Network by DeviceNet Network Configuration Tool .......................................... 32
10.3 Ladder Diagram Program .............................................................................................................. 38
11 LED INDICATOR & TROUBLE-SHOOTING ....................................................................................... 39
11.1 LED Indicator Diagnosis ................................................................................................................ 39
11.2 Digital displayer diagnosis ............................................................................................................. 40
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
1 Introduction
1) Thank you for choosing Delta DVPDNET-SL. To ensure correct installation and operation of DVPDNET-SL,
please read this chapter carefully before using your DVPDNET-SL.
2) DVPDNET-SL running on the left side of PLC can serve as the DeviceNet master or slave with PLC MPU
together. It can be configured through DeviceNet software.
1.1 Features
z
Serves as DeviceNet master by connecting to PLC MPU and Supports standard DeviceNet protocol.
z DeviceNet Builder provides convenient graphic configuration interface; automatically scans and
recognizes all slaves in the bus.
z
z
Supports DeviceNet Master mode and Slave mode.
Supports eight types of baud rates: 10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800kbps,
1M kbps
1.2 Basic Functions of DVPDNET-SL
¾
DVPDNET-SL DeviceNet Network Scanner can be used both as a master or a slave in DeviceNet. When
being used as a master, it supports the following functions:
z
Automatically carrying out the data exchange with PLC MPU. User needs only to operate the special
register in PLC to realize the monitoring of all slaves.
z
z
z
Supports client function of explicit message.
Supports slave to establish all kinds of I/O connections: polled, bit-strobed, change of state and cyclic.
As the connection medium between DeviceNet Builder configuration software and DeviceNet network.
The configuration software is able to directly configure the network through DVPDNET-SL.
Sending explicit messages for reading/writing the data in slave through PLC ladder diagrams.
Max length for output data and input data are both 380 bytes.
z
z
¾
When being used as a slave, it supports the following functions:
z
z
z
z
Explicit message serve and Group 2 only serve connection mode.
Polling
Offering 256 bytes for input data and 256 bytes for output data in data exchange with master.
Automatically exchanging data with PLC MPU. The user needs only to edit the D register in the PLC
without using FROM/TO instruction.
z Max length for output data and input data are both 255 bytes.
1
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
1.3 Specifications
PLC that DVPDNET-SL supports
Item
Specification
DVPDNET-SL supports PLC MPU which can be extendable in its left side
g. DVP-SV, DVP-EH2_L, DVP-SX2, DVP-SA2, DVP10MC11T etc.)
PLC Model
DeviceNet Interface
Item
Specification
Transmission
CAN
method
Electrical
500V DC
isolation
Interface
Removable connector (5.08mm)
Transmission TAP-CB01 cable and TAP-CB02 cable are recommended. (The shielded wire
cable
must be grounded and the cable should be away from power line)
DeviceNet network provides direct current: 11~25V, 28mA(typical value),
125mA impulse current(24 VDC)
Voltage
DeviceNet Communication
Item
Specification
Explicit connection, IO polled connection, bit-strobe connection, COS/CC
connection
Message type
Baud rate
Standard mode: 125 kbps; 250 kbps; 500 kbps
Extended mode: 10 kbps; 20 kbps; 50 kbps; 125 kbps; 250 kbps; 500 kbps;
800kbps; 1M kbps
Environment
Item
Specification
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Noise immunity Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Operation
Storage
Vibration/shock Standard: IEC 61131-2、IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
resistance
(TEST Ea)
Certificates
IEC 61131-2, UL508
2
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
2 Product Profile & Outline
2.1 Dimension
DVPDNET
MS
NS
5
1
x10
0
5
x100
0
DR
DR
1
0
IN 1
IN 0
2.2 Product Profiles
1. Model name
2. Extension port
3. Power, MS, NS LED
4. DIN rail clip
5. Digital indicator
6. Extension clip
7. Address switch
8. Function switch
9. DeviceNet connection port
2.3 DeviceNet Connection Port
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with
DVPDNET-SL.
PIN
1
Signal
V-
Color
Black
Blue
-
Content
0V DC
5
4
2
CAN_L
SHIELD
CAN_H
Signal-
Shielded
Signal+
3
2
3
4
White
1
5
V+
Red
24V DC
Note: Either end of the communication cable should be connected with the terminal resistor of
121Ω and the resistors should be connected between “Signal+” and “Signal-”.
3
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
2.4 Address Switch
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99
are forbidden).
Switch setting
0 … 63
Content
5
0
0
5
Valid DeviceNet node address
Invalid DeviceNet node address
64…99
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding
switch of x101 to 2 and the corresponding switch of x100 to 6.
Note:
z
Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z
z
When DVPDNET-SL is operating, changing the setting of node address will be invalid.
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5 Function Switch
The function switches are for:
Setting up the work mode (IN0)
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1
DR0
Baud rate
OFF
OFF
ON
OFF
ON
125kbps
250kbps
500kbps
OFF
Entering the mode of extended baud rate
( see Chapter 9)
ON
ON
ON
When the slave is off-line, the I/O data in
the buffer area will be held.
IN0
IN1
When the slave is off-line, the I/O data in
the buffer area will be cleared.
OFF
Reserved
Note:
z Please set up the function switch when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z When DVPDNET-SL is operating, changing the setting of the function switch will be invalid.
z Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.
4
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
2.6 Digital Indicator
The digital indicator provides the following two functions:
DVPDNET
POWER
MS
NS
1) Displaying the node address and error messages of DVPDNET-SL .
2) Displaying the error message of slave.
Note:
z
z
When the module works normally, the digital displayer will show its own node ID.
When "E1" and "03" are on display continuously, it indicates that the error that "E1" refers to
occurs in the slave of node 03.
z
When the error codes such as "E7" and "E1" are on display, please refer to section 11.2 for the
correction.
2.7 Extension Port
The extension port is mainly used on connecting DVPDNET-SL to the left-side extension port on DVP-SV PLC
MPU.
5
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
3 Installation
3.1 Connecting DVPDNET-SL to DVP-SV MPU
Adjust the extension clip on the left side of DVP-SV.
Meet the extension port of the MPU with DVPDNET-SL as shown in the figure below.
Fasten the extension clip.
DVPDNET
DVP28SV
RUN
STOP
3.2 Installing DVPDNET-SL and DVP-SV MPU on DIN Rail
Use 35mm DIN rail.
Open the DIN rail clip on DVP-SV and DVPDNET-SL. Insert DVP-SV and DVPDNET-SL onto the DIN
rail.
Clip up the DIN rail clips on DVP-SV and DVPDNET-SL to fix DVP-SV and DVPDNET-SL on the DIN rail,
as shown below.
DVPDNET
DVP28SV
35mm DIN rail
RUN
STOP
6
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
3.3 Connecting to DeviceNet Connection Port
The colors on the PINs on the DeviceNet connection port match the colors of the connection cables.
Make sure you connect the cable to the right PIN.
We recommend you also apply Delta’s power module in the connection.
7
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4 Configuration of DVPDNET-SL
4.1 Configuration through DeviceNet Builder Software
Before DVPDNET-SL starts to work normally, it must be configured through DeviceNet Builder
software.
4.1.1 Selection of Communication Channel
Max 8 DVPDNET-SL modules can be connected to the left side of PLC and every DVPDNET-SL is a
communication channel. When there are three DVPDNET-SL modules connected to PLC’s left side and
DeviceNet Builder software is on line, the following dialog box will pop up for selecting the current channel.
Parameter
Unit No.
Explanation
The unit No. of the first DVPDNET-SL(DNET Scanner)on the left side of PLC is 1.
PLC’s left side can be connected with max 8 DVPDNET_SL. The further
DVPDNET-S is from PLC MPU, the larger its unit No is.
Name
Code
DVPDNET-SL’s name in DeviceNet Builder software.
For displaying the current mode of DVPDNET-SL: master mode or slave mode.
The register areas which PLC MPU distributes to DVPDNET-SL.The areas are
mainly used to receive the message from DeviceNet Slave and the data from
slave in the bus will be automatically updated to these registers.
Input
mapping
The register areas which PLC MPU distributes to DVPDNET-SL. The areas are
mainly used to control DeviceNet slave and the control data in these registers will
be automatically sent to DeviceNet slave in the bus. Slave will take some action
accordingly after receiving the data.
Output
mapping
8
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4.1.2 Setup of Scan Module
The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.
Parameter
Explanation
For setting DVPDNET-SL as master mode.
Master
mode
Scan
interval
time
The cycle time for master to send and receive the real time data after real-time
data connection is successful.
The result value of the parameter multiplied by 4. (Unit:ms)
Master assumes that the slave is offline if it receives no response from slave after
timeout.
Timeouts
(EPR)
The parameter gets effective only in master mode.
Selecting “Startup” activates the function of extended baud rate.
Select the appropriate baud rate according to actual demand then.
Extended
baud rate
Slave mode
Bit-strobe
For setting DVPDNET-SL as slave mode
Reserved; no actual purpose now.
The parameters get effective only in slave mode.
The filled byte number corresponds to the data length for output and input as
DVPDNET-S is taken as slave. “Sending data length” corresponds to “Output
length” and “Receiving data length” corresponds to “Input length”.
Polled
COS/CC
Reserved; no actual purpose now.
Device
mapping
address
For AH modes specially; no actual purpose now.
Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.
9
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4.1.3 Setup of Scan List
Double click the existing icon of DVPDNET-SL in the DeviceNet Builder interface and then the following
dialog box appears for configuring the scan module.
Parameter
Explanation
All already scanned slaves appear in “Available list”.
After the configuration information is downloaded to DVPDNET-SL, the slave in
“Available node” will not conduct the real-time data exchange with DVPDNET-SL.
Available
node
After the configuration information is downloaded to DVPDNET-SL, the slave in
“Scan list” will conduct the real-time data exchange with DVPDNET-SL.
Scan list
Node
address
The station No. for the slave in DeviceNet bus.
The name that “Node address” corresponds to.
Node name
10
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4.1.4 Input Table and Output Table
Select the device in “Scan list” and then the data length of input and output of the device will be displayed
respectively in the lower part of the following dialog box.
Parameter
Explanation
PLC MPU’s registers and the corresponding output data are shown in “Output list”.
The values in PLC’s registers will be sent to slave in real time as the control data
of slave.
Output
Table
PLC MPU’s registers and the corresponding input data are shown in “input list”.
The data that slave sends to master will be updated in PLC’s registers in real time.
Input Table
Register
The number of the register of PLC MPU; “D6289_H” indicates the high byte of
register D6289; “D6289_L” indicates the low byte of register D6289.
Device
mapping
For displaying the data type and the name of current slave; “Poll” means the polled
data.
11
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4.2 Data Mapping Areas
The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The
mapping relation is unchanged and user has no right to revise this area.
Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected
to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVP28SV
RUN
STOP
The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1,
the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on.
Mapped D registers
Output mapping
DVPDNET-SL
index
Input mapping
D6000 ~ D6247
D6500 ~ D6747
D7000 ~ D7247
D7500 ~ D7747
D8000 ~ D8247
D8500 ~ D8747
D9000 ~ D9247
D9500 ~ D9747
1
2
3
4
5
6
7
8
D6250 ~ D6497
D6750 ~ D6997
D7250 ~ D7497
D7750 ~ D7997
D8250 ~ D8497
D8750 ~ D8997
D9250 ~ D9497
D9750 ~ D9997
4.3 I/O Mapping Table (as master mode)
As DVPDNET-SL of unit No. 1 serves as master mode, the data mapping areas are distributed as below table.
Output mapping area
Mapping area
Input mapping area
Mapping area
D register
Data length
D register
Data length
32 words
Explicit message
Explicit message
program response
D6250 ~ D6281
D6282 ~ D6285
D6286
32 words D6000 ~ D6031
program request
Bit-strobe
command
Status of nodes in
the scan list
D6032 ~ D6035
D6036
4 words
1 word
4 words
1word
DVPDNET-SL
status
Reserved
DeviceNet output
data
DeviceNet input
data
D6287 ~ D6476
190 words D6037 ~ D6226
D6227 ~ D6247
190 words
21 words
D6477 ~ D6497 Reserved
Reserved
21 words
12
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
Note: If the unit No. is 2, the number of the registers above will all be added by 500 respectively; if the unit No.
is 3, the number of the registers above will all be added by 1000 respectively; if the unit No. is 4, the number of
the registers above will all be added by 1500 respectively and so on.
4.4 I/O Mapping Table (as slave mode)
As DVPDNET-SL serves as slave mode, the data mapping areas are distributed as below table and these
registers are applied for real-time data exchange.
Input mapping area
Initial register
Output mapping area
Initial register
Unit No.
Max data length
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
Max data length
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
255Bytes
1
2
3
4
5
6
7
8
D6000
D6500
D7000
D7500
D8000
D8500
D9000
D9500
D6250
D6750
D7250
D7750
D8250
D8750
D9250
D9750
When the unit No. of DVPDNET_SL is 1, the control data which DeviceNet sends out will be updated in real
time in the registers of PLC MPU with D6000 as the initial register. In the meanwhile, the value in the registers
of PLC MPU with D6250 as the initial register will be automatically sent back to DeviceNet master so as to
realize the real-time data exchange.
13
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
5 Sending Explicit Message from Ladder Diagram
DVPDNET-SL supports the sending of explicit messages through WPL programs.
5.1 The Principle of Explicit Message Sending
1
Explicit request message
(PLC
ꢀ
DVPDNET-SL)
4
Explicit response message
(DVPDNET-SL
ꢀ
PLC)
DVPDNET
DVP28SV
RUN
STOP
Explicit request message
from master
2
DeviceNet
DNA02
RJ12
VFD-B
Explicit response message
from slave
3
①: DVP-SV MPU sends out explicit request message to DVPDNET-SL according to WPL program.
②: DVPDNET-SL sends out request message to the target equipment.
③: The target equipment processes the request message and responds DVPDNET-SL.
④: DVP-SV MPU stores the response message from DVPDNET-SL to D register. One explicit message
transmission is therefore completed.
14
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
5.2 Structure of Explicit Message
You can edit explicit messages in “explicit request message editing area” and “explicit response message
editing area”. See the table below for the corresponding relation between the two areas and PLC devices. If
you transmit the request message to be sent out to D6250 ~ D6281, DVPDNET-SL will fill the response
message to D6000 ~ D6031.
PLC device
Mapping area
Mapping length
64 bytes
D6000 ~ D6031
D6250 ~ D6281
Explicit response message editing area
Explicit request message editing area
64 bytes
1)
Structure of request message
See the table below:
Request Message
15 14 13 12 11 10 9
PLC device
D6250
8
7
6
5
4
3
2
1
0
ReqID
Command
Size
Message Header
D6251
D6252
Port
Service Code
High byte of Class ID
High byte of Instance ID
Reserved
MAC ID
D6253
Low byte of Class ID
Low byte of Instance ID
Attribute ID (optional)
Message Data
D6254
D6255
D6256 ~ D6281
Service Data
Command: Fixed to “01Hex”.
ReqID: The request ID. Whenever an explicit message is sent out, the message will be given a ReqID
for DVPDNET-SL to identify. For the next explicit message to be sent out, you have to change the ID
number. ReqID = 0 indicates that DVPDNET-SL will not send out explicit message. Range of ReqID:
00Hex ~ FFHex.
Size: The length of the message, starting from D6253. The high bytes of D6255 are reserved. When
the data length is being calculated, D6255 is counted as 1 byte. The maximum data length is 58 bytes.
Errors will occur when the length is longer than 58 bytes. Unit: byte.
Port: The communication port. Fixed to “00Hex".
MAC ID: The node address of the target equipment on DeviceNet.
Service Code: The service code of the explicit message. See the meanings of the codes in the table
below:
Service Code
01Hex
Explanation
Read all attributes (Get_Attribute_All)
Set up all attributes (Set_Attribute_All)
Read a single attribute (Get_Attribute_Single)
Set up a single attribute (Set_Attribute_Single)
02Hex
0EHex
10Hex
15
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
2)
Structure of response message
See the table below:
Response Message
PLC device
D6000
15 14 13 12 11 10 9
ReqID
8
7
6
5
4
3
2
1
0
Status
Size
Message Header
D6001
Port
D6002
Service Code
Service Response Data
MAC ID
D6003 ~ 6031
Message Data
The definitions of ReqID, Port, Service Code and MAC ID are the same as their definitions in request
message.
Size: The length of the message, starting from D6003. Max. 58 bytes. Errors will occur when the
length is longer than 58 bytes. Unit: byte.
See the table below for the meanings of Status (status codes):
Status
Explanation
No explicit message is sent out.
0
1
The communication of explicit message is successful.
The explicit message is being sent out.
Error: No response from the target equipment.
Error: Command is invalid.
2
3
4
5
Error: Size of request message is invalid.
Error: Size of response message is invalid.
Error: Failing to establish a connection to the target equipment.
Reserved
6
7
8 ~ 255
3)
Notes:
DVPDNET-SL can only send out 1 explicit message at a time.
Before sending explicit message by using WPL program, we suggest you clear the request message
editing area and response message editing area to 0.
If the slave responds with standard error code, and DVPDNET-SL also consider the communication
being successful, “The communication of explicit message is successful.” will indicate that the
communication has been completed successfully.
16
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4)
Application example (I)
Target
When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502
1> The connection
DVPDNET
DVP28SV
RUN
STOP
Node Address:00
DeviceNet
Node Address:02
RJ12
Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter
Set value
00
Explanation
Node address
Set the node address of DVPDNET-SL to “00”.
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in DNA02
Parameter
Set value
02
Explanation
Node address
Set the node address of DNA02 to “02".
Set the communication speed of DNA02 and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in VFD-B
Parameter
02-00
Set value
04
Explanation
The main frequency is operated on RS-485 interface.
The operation commands are operated on the
communication interface. Operation by keys is valid.
02-01
03
09-00
09-01
09-04
01
03
03
Communication address of VFD-B: 01
Baud rate: 38,400
Modbus RTU mode. Data format <8, N, 2>
17
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
Explanations on devices
Explanation
15 14 13 12 11 10 9
PLC device
Content
8
7
6
5
4
3
2
1
0
D6250 0101Hex ReqID = 01Hex
D6251 0005Hex Port = 00Hex
Command = 01Hex
Size = 05Hex
D6252 0E02Hex Service Code = 0EHex
MAC ID = 02Hex
Request
message
editing area
D6253 0001Hex High bye of Class ID =00Hex Low byte of Class ID = 01Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
D6254 0001Hex
D6255 0001Hex N/A
Attribute ID = 01Hex
Status = 01Hex
Size = 02Hex
D6000 0101Hex ReqID = 01Hex
D6001 0002Hex Port = 00Hex
D6002 8E02Hex Service Code = 8EHex
Response
message
MAC ID = 02Hex
editing area
High byte of Service Data = Low byte of Service Data =
D6003 031FHex
03Hex
1FHex
3> PLC program
M1002
ZRST
ZRST
D6000 D6031
D6250 D6281
Reset response message editing area
& request message editing area
M0
MOV
MOV
MOV
H0101 D6250
ReqID = 01, Command = 01
H0005 D6251 Port = 00, Size = 05
Service Code = 0E, MAC ID = 02
H0E02 D6252
MOV
MOV
MOV
H0100 D6253 Class ID to be read = 01
H0100 D6254
H0100 D6255
Instance ID to be read = 01
Attribute ID to be read = 01
4> Program explanations:
In the beginning of the program, clear the response message editing area and request message
editing area to 0.
When M0 = On, DVPDNET-SL will send out request message, reading Class 1>>Instance 1>>
Attribute 1 of the target equipment (node address: 02). If the communication of explicit message is
successful, the slave will return with a response message.
When M0 = On, DVPDNET-SL will only send out request message once. If you would like it to send out
request message again, you will have to change ReqID.
When the reading is successful, the message responded from the target equipment will be stored in
D6000 ~ D6003.
18
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
5)
Application example (II)
Target
M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.
1> The connection
Note: IFD9502, a Delta DeviceNet slave module can connect the temperature controller to DeviceNet
network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter
Set value
00
Explanation
Node address
Set the node address of DVPDNET-SL to “00”.
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in DNA02
Parameter
Set value
02
Explanation
Node address
Set the node address of DNA02 to “02”.
Set the communication speed of DNA02 and bus to
“500kbps”.
Baud rate
500kbps
Compulsory settings in VFD-B
Parameter
02-00
Set value
04
Explanation
The main frequency is operated on RS-485 interface.
The operation commands are operated on the
communication interface. Operation by keys is valid.
02-01
03
09-00
09-01
09-04
01
03
03
Communication address of VFD-B: 01
Baud rate: 38,400
Modbus RTU mode. Data format <8, N, 2>
19
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
Explanations on devices
Explanation
15 14 13 12 11 10 9
PLC device
Content
8
7
6
5
4
3
2
1
0
D6250 0101Hex ReqID = 01Hex
D6251 0005Hex Port = 00Hex
Command = 01Hex
Size = 07Hex
D6252 0E02Hex Service Code = 10Hex
MAC ID = 02Hex
Request
message
D6253 0099Hex High byte of Class ID = 00Hex Low byte of Class ID = 99Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
editing area
D6254 0001Hex
D6255 0002Hex N/A
Attribute ID = 02Hex
Low byte of data = 04Hex
Status = 01Hex
D6256 0004Hex High byte of data = 00Hex
D6000 0101Hex ReqID = 01Hex
D6001 0002Hex Port = 00Hex
D6002 9002Hex Service Code = 90EHex
Size = 02Hex
Response
message
MAC ID = 02Hex
editing area
High byte of Service Data =
Low byte of Service Data =
04Hex
D6003 0004Hex
00Hex
3> PLC program
M1002
ZRST
ZRST
D6000 D6031
D6250 D6281
Reset response message editing area
& request message editing area
M1
MOV
MOV
MOV
H0101 D6250 ReqID = 01, Command = 01
H0008 D6251
Port = 00, Size = 08
H0E02 D6252 Service Code = 0E, MAC ID = 02
H0099 D6253 Class ID to be write= 99
MOV
MOV
MOV
MOV
Instance ID to be written = 01
Attribute ID to be written = 02
Data to be written = 0004
H0001 D6254
H0002
H0004
D6255
D6256
4> Program explanations
In the beginning of the program, clear the response message editing area and request message
editing area to 0.
When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>
Instance 1 >> Attribute 2 of the target equipment (node address: 02). If the communication of
explicit message is successful, the slave will return with a response message.
20
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to
send out request message again, you will have to change ReqID.
When the writing is successfully done, the message responded from the target equipment will be
stored in D6000 ~ D6003.
21
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
6 Bit-Strobe Command
6.1 Principle of Bit-Strobe
Bit-strobe is one of the standard I/O transmission methods for DeviceNet. The length of command is fixed to 8
bytes (i.e. 64 bits), and every bit corresponds to a slave.
Corresponding nodes on the network
PLC
device
b15
b14
b13
…
…
…
…
…
b1
b0
D6282
D6283
D6284
D6285
Node 15
Node 31
Node 47
Node 63
Node 14
Node 30
Node 46
Node 62
Node 13
Node 29
Node 45
Node 61
Node 1
Node 17
Node 33
Node 49
Node 0
Node 16
Node 32
Node 48
When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to
the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will be
to respond with a message to the master.
D6282
D8283
b31 b30
b18 b17 b16 b15 b14
b2 b1 b0
Node 0
Node 1
Node 2
Node 14
In the bit-strobe mode, the master will not send control data to the slave node. However, when its
corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its
corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.
22
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
7 Display of Node Status on Network
7.1 Display of Node Status in Scan List
This function is to monitor if DeviceNet slave is offline or not. DVPDNET-SL does read-time monitoring to the
nodes in the scan list and maps the status of every node to a bit. You can acquire the node status by
monitoring D6032 ~ D6035. See the table below for the corresponding relation between PLC devices and the
nodes on the network:
Corresponding nodes on the network
PLC
device
b15
b14
b13
…
…
…
…
…
b1
b0
D6032
D6033
D6034
D6035
Node 15
Node 31
Node 47
Node 63
Node 14
Node 30
Node 46
Node 62
Node 13
Node 29
Node 45
Node 61
Node 1
Node 17
Node 33
Node 49
Node 0
Node 16
Node 32
Node 48
When the node in the scan list is normal, the corresponding bit will be off. If the node occurs with abnormality,
its corresponding bit will be On.
7.2 Status of DVPDNET-SL
You can acquire the real-time status of DVPDNET-SL by monitoring D6036. When DVPDNET-SL runs
normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0.
When error occurs in DVPDNET-SL, the high byte of D6036 = 2. For detailed error information, please refer
to the error codes, i.e. the low byte of D6036.
Explanation
PLC
device
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Status of DVPDNET-SL
Error codes of DVPDNET-SL
(0: normal, 1: initializing, 2: error)
D6036
23
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
8 Setup of Slave Mode
DVPDNET-SL can serve as slave through modifying of the mode by software. As DVPDNET-SL serves as slave,
the default input / output data length is 8 bytes and max input / output data length is 255 bytes.
DVPDNET-SL can be set as slave mode in the following method.
1) Connect the devices according to below figure. PC accesses PLC MPU via RS232 or RS485.
DVPDNET-SL
DVP28SV
DeviceNet Builder
2) Open DeviceNet Builder software, and select “Setup” => “Communication Setting” => “System Channel”,
and the “Serial Port Setting” dialog box will appear as below.
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
Item
Function
Default
COM1
COM port on the PC to be used to communicate
with DVP-SV
COM Port
Address
Baud rate
01
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
9,600 (bps)
Data Bits
Parity
7
Communication protocol between the PC and
DVP-SV
Even Parity
1
Stop Bit
Communication mode between the PC and
DVP-SV
Mode
ASCII
24
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”
to start scanning the DeviceNet network after selecting “analog online” in the following window.
5) Select “Network” >> “Scan module” and then “Scan module setting” dialog box appears. After “Slave mode”
is selected there, fill the appropriate slave data length. Finally click on “OK” to finish the setting.
6) Select “Network” >> “Download” and then below dialog box appears. Click on “Y” to download the
configuration data to DVPDNET-SL.
7) After download is finished, power PLC off and then repower it. At this time, DVPDNET-SL has been set as
slave mode.
25
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
9 Setup of Extended Baud Rate
9.1 Setup of Extended Baud Rate (as master mode)
1) Connect the device to the Devicenet network according to the following figure. PC accesses PLC MPU via
RS232 or RS485.
DVPDNET-SL
DVP28SV
DeviceNet Builder
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”. And
then the following dialog box appears.
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
Item
Function
Default
COM1
COM port on the PC to be used to communicate
with DVP-SV
COM Port
Address
Baud rate
01
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
9,600 (bps)
Data Bits
Parity
7
Communication protocol between the PC and
DVP-SV
Even Parity
1
Stop Bit
Communication mode between the PC and
DVP-SV
Mode
ASCII
4) Select “Network” => "Online” and the following “Select Communication Channel” dialog box will appear. Click
on “OK”.
26
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
5) Select “Network” => "Setup of scan module” and the following "Setup of scan module” dialog box appears.
Select “Master mode” and “Startup” to activate the function of extended baud rate. In the meanwhile, select
the appropriate baud rate according to the actual demand. Click “OK” to finish setting.
6) Select “Network” => “Download” and the following dialog box appears. Click “OK” to download the
configuration information to DVPDNET-SL.
7) After download is completed, set DVPDNET-SL’s function switch DR0 and DR1 as ON and then repower
PLC to finish the setting of the extended baud rate.
27
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
9.2 Setup of Extended Baud Rate (as slave mode)
1) Connect the relevant devices to the DeviceNet network according to the following figure.
DVPDNET-SL(Master)
DVP28SV
DeviceNet Builder
DeviceNet
DVP28SV
DVPDNET-SL(Slave)
Note:
a. DVPDNET-SL at the bottom of the above figure has been set as slave mode.
b. The node addresses of two DVPDNET-SLs must not be repeated. (See section 2.4).
c. The baud rates of two DVPDNET-SLs are both 500K bps (See section 2.5).
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”,
In result, you can see the following dialog box.
28
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud
rate and communication format. Click on “OK” after configuration is finished.
Item
Function
Default
COM1
COM port on the PC to be used to communicate
with DVP-SV
COM Port
Address
Baud rate
01
Communication address of DVP-SV
Communication speed between the PC and
DVP-SV
9,600 (bps)
Data Bits
Parity
7
Communication protocol between the PC and
DVP-SV
Even Parity
1
Stop Bit
Communication mode between the PC and
DVP-SV
Mode
ASCII
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”
to start scanning the entire DeviceNet network.
5) After scanning is successful, right click DNET (Slave) to select “Parameter editing”.
29
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
6) Set parameter 5 as “Enable” and select the baud rate in parameter 6 in the following page. Click on
“Download” to download the newly set parameter value to DVPDNET-SL(Slave).
7) After download is completed, set DVPDNET-SL(Slave)’s function switch: DR0 and DR1 as ON. And then
repower PLC to finish the setting of the extended baud rate.
30
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
10 Application Example on Constructing DeviceNet Network
In this section, we will present an application example, illustrating how to construct a DeviceNet network and the
configuration of the network.
Target
Using an X point of DVP28SV to control RUN/STOP of the remote VFD-L AC motor drive.
10.1 How to Construct a DeviceNet Network
1) The connection
DVPDNET-SL
DVP28SV
START
STOP
X0
X1
DeviceNet Builder
RS232
DeviceNet
RTU-DNET
VFD-L
VFD-L
RS485
Note:
RTU-DNET, a Delta DeviceNet remote IO communication module supports the MODBUS communication
function.
2) Set up DVPDNET-SL, RTU-DNET and VFD-L according to the table below.
Module
Node address
Baud rate
DVPDNET-SL
RTU-DNET
01
02
500kbps
500kbps
31
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
VFD-L
Set value
Explanation
parameter
02-00
02-01
4
3
Transmit the frequency of VFD-L via RS485
communication.
Control operation of VFD-L via RS485
communication.
09-00
09-01
09-04
1
1
1
Set the node address of VFD-L in Modbus to 1.
Set the communication rate of VFD-L in Modbus 9600
Set the communication format of VFD-L in Modbus to
7, E, 1, ASCII.
10.2 How to Configure Network by DeviceNet Network Configuration Tool
1) Configuration of DeviceNet slave
1> Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System
Channel”, and the “Serial Port Setting” dialog box will appear as below.
2> Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address,
baud rate and communication format. Click on “OK” after configuration is finished.
Item
Function
Default
COM1
COM port on the PC to be used to
communicate with DVP-SV
COM Port
Address
Baud rate
Communication address of DVP-SV
01
Communication speed between the PC and
DVP-SV
9,600 (bps)
Data Bits
Parity
7
Communication protocol between the PC
and DVP-SV
Even Parity
1
Stop Bit
Communication mode between the PC and
DVP-SV
Mode
ASCII
32
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
3> Select “Network” => "Online”, and the “Select Communication Channel” dialog box will appear.
Clicking on “OK” starts scanning the DeviceNet network.
4> If the bar on the dialog box does not progress, it means the connection between the PC and DVP-SV
is abnormal, or there are other programs also using the COM port on the PC. After the scan is
completed, the dialog box will tell you that the scan is completed, and the icons and device names of
all the nodes scanned on the network will be shown on the screen. See the figure below, in which the
node address of DVPDNET-SL and RTU-DNET are 01 and 02 respectively.
33
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
5> Double click on RTU-DNET (node 02), and the "Node Configuration…” dialog box will appear.
6> Click on “IO Configure…” button in “Node Configuration” dialog box, and you will then see “RTU
Configuration” page where you click on “Scan IO” button and “Warning” dialog box will appear. Click
“OK” then DeviceNet Builder will detect the devices connected to RTU-DNET as below.
7> Because no special module is connected to the right side of RTU-DNET, “None” will show in the
location of the special module in the following window. The point number for X and Y are both 0.Then
click on “Gateway setting”.
34
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
8> In the interface of “Modbus gateway setting”, use the parameters of one slave and fill the relevant
values there. You can refer to the user manual of RTU-DNET.
Note: The slave here is the slave in Modbus network without direct relation with DeviceNet network.
9> Click on “OK” in the above window and then click on “Download” in the following window to
download the configuration data to RTU-DNET. After download is finished, the configuration
of RTU-DNET is completed.
35
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
2) Configuration of DeviceNet Master
1> Double click on DNET Scanner (node 01), and the “Scan Module Configuration..." dialog box will
appear. You can find the currently available nodes, RTU-DNET and VFD-B Drives 230V 3HP, in
the list on the left side. On the right side, there is an empty “Scan List”.
2> (2) Move the slave devices on DeviceNet in the "Available Nodes” list on the left side to the "Scan
>
List” on the right side. Select a node and click on . Follow the steps to move all the nodes to the
scan list.
36
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
3> Confirm all the settings and click on “OK”. Next, download the configuration to DVPDNET-SL. If
DVP-SV is in RUN mode while you are downloading the configuration, a “Warning” dialog box will
appear.
4> Click on “OK” to continue the download. Make sure DVP-SV is in RUN mode.
The mapping relation between DVPDNET-SL and slave device is shown as below after
configuration of the DeviceNet network following the above steps is completed.
DVP28SV → DVPDNET-SL → slave device
DVP28SV
D6287
DVPDNET-SL
RTU-DNET & VFD-L
Control word of VFD-L
(2000H)
Control frequency of VFD-L
D6288
(2001H)
DVP28SV ← DVPDNET-SL ←slave device
DVP28SV
D6037
DVPDNET-SL
RTU-DNET & VFD-L
Output frequency of VFD-L
(2103H)
37
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
10.3 Ladder Diagram Program
This section introduces how to edit the ladder diagram program to meet the control request of DeviceNet network.
When X0=ON, VFD-L AC motor drive runs;
Control
request
When X1=ON, VFD-L AC motor drive stops;
After VFD-L has run for 6 seconds and at this time the running frequency still has not
reached the designated frequency, Y0 of DVP28SV=ON.
Explanation of PLC Program
X0
MOV
MOV
H12
D6287
When X0=ON, VFD-L starts up and
its target frequency is 20Hz.
K2000 D6288
X1
X0
T0
MOV
TMR
H1
T0
D6287
K60
When X1=ON, VFD-L stops running.
Y0 will be ON in DVP28SV if the
frequency of VFD-L has not reached
20Hz after starting up for 6 seconds
LD<> K2000 D6037
(
Y0
)
38
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
11 LED Indicator & Trouble-shooting
DVPDNET-SL supports two diagnostic methods: indicator diagnosis and digital displayer diagnosis.
DVPDNET
POWER
MS
NS
11.1 LED Indicator Diagnosis
POWER LED
LED status
Off
Indication
Power is abnormal.
Power is normal.
How to correct
Make sure DVPDNET-SL is powered.
Green light on
--
NS LED
LED status
Indication
How to correct
1. Make sure DVPDNET-SL is powered.
2. Make sure at least 1 node or more are
communicating on the network.
No power or duplicate ID
check has not completed
Off
Green light
blinking
No correction is needed; check the digital indicator for
the error.
No communication
Normal operation
Green light on
--
Red light
blinking
Error in communication
Check the digital indicator and eliminate the error.
1. Make sure all the devices have their unique node
address.
2. Check the network for correcting media installation
and baud rate.
3. Check if the node address of DVPDNET-SL is valid.
4. Check if the network power is normal.
Network error; cannot check
duplicate ID; bus-off (check
the digital indicator)
Red light on
MS LED
LED status
Off
Indication
No power
How to correct
Make sure DVPDNET-SL is powered.
Green light
blinking
The master is not
configured.
Configure the scan list and re-download it to
DVPDNET-SL.
Green light on
Normal operation
--
Check the digital indicator and make sure the salve
information in the scan list is consistent with the salve
actually connected.
Red light
blinking
Some slaves encounter
communication error.
1. Check if the configuration is valid.
2. Re-power it. If the error still exists, send it back to
the factory for repair.
Red light on
Internal error
39
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
MS & NS LED
LED status
Indication
How to correct
NS LED
Off
MS LED
Off
No power
Make sure DVPDNET-SL is powered.
Make sure at least 1 node or more are
Green light
on
Duplicate ID check has not communicating in the network, and the baud
Off
completed.
rate is the same as the setting in
DVPDNET-SL.
Green light
on
Change the MAC ID setting and re-power
DVPDNET-SL.
MAC ID detection failure
or bus-off
Red light on
Red light on
1. Check if the network cable is correctly
connected to DVPDNET-SL.
2. Check the 24V DC network power.
Red light
blinking
No 24V DC power from
DeviceNet network
Go to your manufacturer or distributor for
problem-solving.
Red light on Red light on Hardware error
11.2 Digital displayer diagnosis
Code
Indication
How to correct
Node address of
DVPDNET-SL (in normal
operation)
0 ~ 63
--
DVPDNET-SL is in STOP
status.
Turn the PLC MPU to RUN and start I/O data
exchange.
80
F0
F1
F2
F3
Duplicate MAC ID check
failure
Check the node address and re-power DVPDNET-SL.
No slave device in the scan Configure the scan list and download it to
list.
DVPDNET-SL.
Check if the power of DVPDNET-SL and PLC MPU is
normal.
Low voltage is detected.
Switch IN1 from On to Off and re-power
DVPDNET-SL.
Entering test mode
Bus-off
1. Check if the network cable is normal.
2. Check if the baud rate is correct.
3. Re-power DVPDNET-SL.
F4
Make sure the cable is correctly connected and check
if the network power is normal.
F5
F6
F7
F8
F9
No network power
Internal error; Flash or RAM If the error still exists after re-power, send your
check error
DVPDNET-SL back to the factory for repair.
Internal error; GPIO check
error
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
Error produced in factory
manufacturing
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
Internal error; EEPROM
access failure
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
1. Configure the network correctly and re-download it
to DVPDNET-SL.
FA
Invalid configuration data
2. Check if the node address of the slave in the scan
list is the same as the node address of
DVPDNET-SL.
Device key parameter does Make sure that the device parameter in the scan list
E0
E1
not match the scan list
table.
matches the desired key parameter, including vendor
ID, product code, device type and version.
Data size returned does not
match the scan list.
Re-configure the scan list using correct data size.
40
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
DeviceNet Network Scanner DVPDNET-SL
Code
E2
Indication
How to correct
1. Check if there is any change for the node address of
the slave.
Slave device in the scan list
does not exist or is offline.
2. Check if the communication cable is disconnected
or connected loosely.
DVPDNET-SL fails to
transmit a message.
Make sure that the connection is valid and check if the
baud rate is correct.
E3
E4
Error detected in sequence
of fragmented I/O
Check if the slave is operating normally.
messages from device
Slave device returns error
when DVPDNET-SL
attempts to communicate
with it.
E5
E6
Check if the slave is operating normally.
Data size returned is bigger
than expected.
Check the configuration of slave device and scan list.
If the code is displayed long, do the troubleshooting
according to the following steps.
1. Make sure that at least two nodes work normally in
the network.
2. Check if either end of the network is connected with
the terminal resistor of 121Ω.
DVPDNET-SL is checking
MAC ID.
E7
3. Check if the baud rates of the node devices in the
network are consistent with each other.
4. Check if the communication cable is normal so as to
avoid that the cable is disconnected or connected
loosely.
5. Re-power 10DNET scanner module.
41
DVP-PLC Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
|