DeviceNet Network Scanner DVPDNET-SL  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
1 Introduction  
1) Thank you for choosing Delta DVPDNET-SL. To ensure correct installation and operation of DVPDNET-SL,  
please read this chapter carefully before using your DVPDNET-SL.  
2) DVPDNET-SL running on the left side of PLC can serve as the DeviceNet master or slave with PLC MPU  
together. It can be configured through DeviceNet software.  
1.1 Features  
z
Serves as DeviceNet master by connecting to PLC MPU and Supports standard DeviceNet protocol.  
z DeviceNet Builder provides convenient graphic configuration interface; automatically scans and  
recognizes all slaves in the bus.  
z
z
Supports DeviceNet Master mode and Slave mode.  
Supports eight types of baud rates: 10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800kbps,  
1M kbps  
1.2 Basic Functions of DVPDNET-SL  
¾
DVPDNET-SL DeviceNet Network Scanner can be used both as a master or a slave in DeviceNet. When  
being used as a master, it supports the following functions:  
z
Automatically carrying out the data exchange with PLC MPU. User needs only to operate the special  
register in PLC to realize the monitoring of all slaves.  
z
z
z
Supports client function of explicit message.  
Supports slave to establish all kinds of I/O connections: polled, bit-strobed, change of state and cyclic.  
As the connection medium between DeviceNet Builder configuration software and DeviceNet network.  
The configuration software is able to directly configure the network through DVPDNET-SL.  
Sending explicit messages for reading/writing the data in slave through PLC ladder diagrams.  
Max length for output data and input data are both 380 bytes.  
z
z
¾
When being used as a slave, it supports the following functions:  
z
z
z
z
Explicit message serve and Group 2 only serve connection mode.  
Polling  
Offering 256 bytes for input data and 256 bytes for output data in data exchange with master.  
Automatically exchanging data with PLC MPU. The user needs only to edit the D register in the PLC  
without using FROM/TO instruction.  
z Max length for output data and input data are both 255 bytes.  
1
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
1.3 Specifications  
PLC that DVPDNET-SL supports  
Item  
Specification  
DVPDNET-SL supports PLC MPU which can be extendable in its left side  
g. DVP-SV, DVP-EH2_L, DVP-SX2, DVP-SA2, DVP10MC11T etc.  
PLC Model  
DeviceNet Interface  
Item  
Specification  
Transmission  
CAN  
method  
Electrical  
500V DC  
isolation  
Interface  
Removable connector (5.08mm)  
Transmission TAP-CB01 cable and TAP-CB02 cable are recommended. (The shielded wire  
cable  
must be grounded and the cable should be away from power line)  
DeviceNet network provides direct current: 11~25V, 28mAtypical value,  
125mA impulse current24 VDC)  
Voltage  
DeviceNet Communication  
Item  
Specification  
Explicit connection, IO polled connection, bit-strobe connection, COS/CC  
connection  
Message type  
Baud rate  
Standard mode: 125 kbps; 250 kbps; 500 kbps  
Extended mode: 10 kbps; 20 kbps; 50 kbps; 125 kbps; 250 kbps; 500 kbps;  
800kbps; 1M kbps  
Environment  
Item  
Specification  
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge  
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV  
Noise immunity Analog & Communication I/O: 1KV  
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV  
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m  
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2  
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)  
Operation  
Storage  
Vibration/shock Standard: IEC 61131-2IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27  
resistance  
(TEST Ea)  
Certificates  
IEC 61131-2, UL508  
2
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
2 Product Profile & Outline  
2.1 Dimension  
DVPDNET  
MS  
NS  
5
1
x10  
0
5
x100  
0
DR  
DR  
1
0
IN 1  
IN 0  
2.2 Product Profiles  
1. Model name  
2. Extension port  
3. Power, MS, NS LED  
4. DIN rail clip  
5. Digital indicator  
6. Extension clip  
7. Address switch  
8. Function switch  
9. DeviceNet connection port  
2.3 DeviceNet Connection Port  
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with  
DVPDNET-SL.  
PIN  
1
Signal  
V-  
Color  
Black  
Blue  
-
Content  
0V DC  
5
4
2
CAN_L  
SHIELD  
CAN_H  
Signal-  
Shielded  
Signal+  
3
2
3
4
White  
1
5
V+  
Red  
24V DC  
Note: Either end of the communication cable should be connected with the terminal resistor of  
121and the resistors should be connected between “Signal+” and “Signal-”.  
3
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
2.4 Address Switch  
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99  
are forbidden).  
Switch setting  
0 … 63  
Content  
5
0
0
5
Valid DeviceNet node address  
Invalid DeviceNet node address  
64…99  
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding  
switch of x101 to 2 and the corresponding switch of x100 to 6.  
Note:  
z
Please set up the node address when the power is switched off. After the setup is completed, re-power  
DVPDNET-SL.  
z
z
When DVPDNET-SL is operating, changing the setting of node address will be invalid.  
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.  
2.5 Function Switch  
The function switches are for:  
Setting up the work mode (IN0)  
Setting up the baud rate of DeviceNet (DR0 ~ DR1)  
DR1  
DR0  
Baud rate  
OFF  
OFF  
ON  
OFF  
ON  
125kbps  
250kbps  
500kbps  
OFF  
Entering the mode of extended baud rate  
( see Chapter 9)  
ON  
ON  
ON  
When the slave is off-line, the I/O data in  
the buffer area will be held.  
IN0  
IN1  
When the slave is off-line, the I/O data in  
the buffer area will be cleared.  
OFF  
Reserved  
Note:  
z Please set up the function switch when the power is switched off. After the setup is completed, re-power  
DVPDNET-SL.  
z When DVPDNET-SL is operating, changing the setting of the function switch will be invalid.  
z Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.  
4
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
2.6 Digital Indicator  
The digital indicator provides the following two functions:  
DVPDNET  
POWER  
MS  
NS  
1) Displaying the node address and error messages of DVPDNET-SL .  
2) Displaying the error message of slave.  
Note:  
z
z
When the module works normally, the digital displayer will show its own node ID.  
When "E1" and "03" are on display continuously, it indicates that the error that "E1" refers to  
occurs in the slave of node 03.  
z
When the error codes such as "E7" and "E1" are on display, please refer to section 11.2 for the  
correction.  
2.7 Extension Port  
The extension port is mainly used on connecting DVPDNET-SL to the left-side extension port on DVP-SV PLC  
MPU.  
5
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
3 Installation  
3.1 Connecting DVPDNET-SL to DVP-SV MPU  
Adjust the extension clip on the left side of DVP-SV.  
Meet the extension port of the MPU with DVPDNET-SL as shown in the figure below.  
Fasten the extension clip.  
DVPDNET  
DVP28SV  
RUN  
STOP  
3.2 Installing DVPDNET-SL and DVP-SV MPU on DIN Rail  
Use 35mm DIN rail.  
Open the DIN rail clip on DVP-SV and DVPDNET-SL. Insert DVP-SV and DVPDNET-SL onto the DIN  
rail.  
Clip up the DIN rail clips on DVP-SV and DVPDNET-SL to fix DVP-SV and DVPDNET-SL on the DIN rail,  
as shown below.  
DVPDNET  
DVP28SV  
35mm DIN rail  
RUN  
STOP  
6
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
3.3 Connecting to DeviceNet Connection Port  
The colors on the PINs on the DeviceNet connection port match the colors of the connection cables.  
Make sure you connect the cable to the right PIN.  
We recommend you also apply Delta’s power module in the connection.  
7
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4 Configuration of DVPDNET-SL  
4.1 Configuration through DeviceNet Builder Software  
Before DVPDNET-SL starts to work normally, it must be configured through DeviceNet Builder  
software.  
4.1.1 Selection of Communication Channel  
Max 8 DVPDNET-SL modules can be connected to the left side of PLC and every DVPDNET-SL is a  
communication channel. When there are three DVPDNET-SL modules connected to PLC’s left side and  
DeviceNet Builder software is on line, the following dialog box will pop up for selecting the current channel.  
Parameter  
Unit No.  
Explanation  
The unit No. of the first DVPDNET-SLDNET Scanneron the left side of PLC is 1.  
PLC’s left side can be connected with max 8 DVPDNET_SL. The further  
DVPDNET-S is from PLC MPU, the larger its unit No is.  
Name  
Code  
DVPDNET-SL’s name in DeviceNet Builder software.  
For displaying the current mode of DVPDNET-SL: master mode or slave mode.  
The register areas which PLC MPU distributes to DVPDNET-SL.The areas are  
mainly used to receive the message from DeviceNet Slave and the data from  
slave in the bus will be automatically updated to these registers.  
Input  
mapping  
The register areas which PLC MPU distributes to DVPDNET-SL. The areas are  
mainly used to control DeviceNet slave and the control data in these registers will  
be automatically sent to DeviceNet slave in the bus. Slave will take some action  
accordingly after receiving the data.  
Output  
mapping  
8
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4.1.2 Setup of Scan Module  
The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.  
Parameter  
Explanation  
For setting DVPDNET-SL as master mode.  
Master  
mode  
Scan  
interval  
time  
The cycle time for master to send and receive the real time data after real-time  
data connection is successful.  
The result value of the parameter multiplied by 4. (Unit:ms)  
Master assumes that the slave is offline if it receives no response from slave after  
timeout.  
Timeouts  
EPR)  
The parameter gets effective only in master mode.  
Selecting “Startup” activates the function of extended baud rate.  
Select the appropriate baud rate according to actual demand then.  
Extended  
baud rate  
Slave mode  
Bit-strobe  
For setting DVPDNET-SL as slave mode  
Reserved; no actual purpose now.  
The parameters get effective only in slave mode.  
The filled byte number corresponds to the data length for output and input as  
DVPDNET-S is taken as slave. “Sending data length” corresponds to “Output  
length” and “Receiving data length” corresponds to “Input length”.  
Polled  
COS/CC  
Reserved; no actual purpose now.  
Device  
mapping  
address  
For AH modes specially; no actual purpose now.  
Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.  
9
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4.1.3 Setup of Scan List  
Double click the existing icon of DVPDNET-SL in the DeviceNet Builder interface and then the following  
dialog box appears for configuring the scan module.  
Parameter  
Explanation  
All already scanned slaves appear in “Available list”.  
After the configuration information is downloaded to DVPDNET-SL, the slave in  
“Available node” will not conduct the real-time data exchange with DVPDNET-SL.  
Available  
node  
After the configuration information is downloaded to DVPDNET-SL, the slave in  
“Scan list” will conduct the real-time data exchange with DVPDNET-SL.  
Scan list  
Node  
address  
The station No. for the slave in DeviceNet bus.  
The name that “Node address” corresponds to.  
Node name  
10  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4.1.4 Input Table and Output Table  
Select the device in “Scan list” and then the data length of input and output of the device will be displayed  
respectively in the lower part of the following dialog box.  
Parameter  
Explanation  
PLC MPU’s registers and the corresponding output data are shown in “Output list”.  
The values in PLC’s registers will be sent to slave in real time as the control data  
of slave.  
Output  
Table  
PLC MPU’s registers and the corresponding input data are shown in “input list”.  
The data that slave sends to master will be updated in PLC’s registers in real time.  
Input Table  
Register  
The number of the register of PLC MPU; “D6289_H” indicates the high byte of  
register D6289; “D6289_L” indicates the low byte of register D6289.  
Device  
mapping  
For displaying the data type and the name of current slave; “Poll” means the polled  
data.  
11  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4.2 Data Mapping Areas  
The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The  
mapping relation is unchanged and user has no right to revise this area.  
Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected  
to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.  
DVPDNET  
DVPDNET  
DVPDNET  
DVPDNET  
DVPDNET  
DVPDNET  
DVPDNET  
DVPDNET  
DVP28SV  
RUN  
STOP  
The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1,  
the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on.  
Mapped D registers  
Output mapping  
DVPDNET-SL  
index  
Input mapping  
D6000 ~ D6247  
D6500 ~ D6747  
D7000 ~ D7247  
D7500 ~ D7747  
D8000 ~ D8247  
D8500 ~ D8747  
D9000 ~ D9247  
D9500 ~ D9747  
1
2
3
4
5
6
7
8
D6250 ~ D6497  
D6750 ~ D6997  
D7250 ~ D7497  
D7750 ~ D7997  
D8250 ~ D8497  
D8750 ~ D8997  
D9250 ~ D9497  
D9750 ~ D9997  
4.3 I/O Mapping Table (as master mode)  
As DVPDNET-SL of unit No. 1 serves as master mode, the data mapping areas are distributed as below table.  
Output mapping area  
Mapping area  
Input mapping area  
Mapping area  
D register  
Data length  
D register  
Data length  
32 words  
Explicit message  
Explicit message  
program response  
D6250 ~ D6281  
D6282 ~ D6285  
D6286  
32 words D6000 ~ D6031  
program request  
Bit-strobe  
command  
Status of nodes in  
the scan list  
D6032 ~ D6035  
D6036  
4 words  
1 word  
4 words  
1word  
DVPDNET-SL  
status  
Reserved  
DeviceNet output  
data  
DeviceNet input  
data  
D6287 ~ D6476  
190 words D6037 ~ D6226  
D6227 ~ D6247  
190 words  
21 words  
D6477 ~ D6497 Reserved  
Reserved  
21 words  
12  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
Note: If the unit No. is 2, the number of the registers above will all be added by 500 respectively; if the unit No.  
is 3, the number of the registers above will all be added by 1000 respectively; if the unit No. is 4, the number of  
the registers above will all be added by 1500 respectively and so on.  
4.4 I/O Mapping Table (as slave mode)  
As DVPDNET-SL serves as slave mode, the data mapping areas are distributed as below table and these  
registers are applied for real-time data exchange.  
Input mapping area  
Initial register  
Output mapping area  
Initial register  
Unit No.  
Max data length  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
Max data length  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
255Bytes  
1
2
3
4
5
6
7
8
D6000  
D6500  
D7000  
D7500  
D8000  
D8500  
D9000  
D9500  
D6250  
D6750  
D7250  
D7750  
D8250  
D8750  
D9250  
D9750  
When the unit No. of DVPDNET_SL is 1, the control data which DeviceNet sends out will be updated in real  
time in the registers of PLC MPU with D6000 as the initial register. In the meanwhile, the value in the registers  
of PLC MPU with D6250 as the initial register will be automatically sent back to DeviceNet master so as to  
realize the real-time data exchange.  
13  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
5 Sending Explicit Message from Ladder Diagram  
DVPDNET-SL supports the sending of explicit messages through WPL programs.  
5.1 The Principle of Explicit Message Sending  
1
Explicit request message  
(PLC  
DVPDNET-SL)  
4
Explicit response message  
(DVPDNET-SL  
PLC)  
DVPDNET  
DVP28SV  
RUN  
STOP  
Explicit request message  
from master  
2
DeviceNet  
DNA02  
RJ12  
VFD-B  
Explicit response message  
from slave  
3
: DVP-SV MPU sends out explicit request message to DVPDNET-SL according to WPL program.  
: DVPDNET-SL sends out request message to the target equipment.  
: The target equipment processes the request message and responds DVPDNET-SL.  
: DVP-SV MPU stores the response message from DVPDNET-SL to D register. One explicit message  
transmission is therefore completed.  
14  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
5.2 Structure of Explicit Message  
You can edit explicit messages in “explicit request message editing area” and “explicit response message  
editing area”. See the table below for the corresponding relation between the two areas and PLC devices. If  
you transmit the request message to be sent out to D6250 ~ D6281, DVPDNET-SL will fill the response  
message to D6000 ~ D6031.  
PLC device  
Mapping area  
Mapping length  
64 bytes  
D6000 ~ D6031  
D6250 ~ D6281  
Explicit response message editing area  
Explicit request message editing area  
64 bytes  
1)  
Structure of request message  
See the table below:  
Request Message  
15 14 13 12 11 10 9  
PLC device  
D6250  
8
7
6
5
4
3
2
1
0
ReqID  
Command  
Size  
Message Header  
D6251  
D6252  
Port  
Service Code  
High byte of Class ID  
High byte of Instance ID  
Reserved  
MAC ID  
D6253  
Low byte of Class ID  
Low byte of Instance ID  
Attribute ID (optional)  
Message Data  
D6254  
D6255  
D6256 ~ D6281  
Service Data  
Command: Fixed to “01Hex”.  
ReqID: The request ID. Whenever an explicit message is sent out, the message will be given a ReqID  
for DVPDNET-SL to identify. For the next explicit message to be sent out, you have to change the ID  
number. ReqID = 0 indicates that DVPDNET-SL will not send out explicit message. Range of ReqID:  
00Hex ~ FFHex.  
Size: The length of the message, starting from D6253. The high bytes of D6255 are reserved. When  
the data length is being calculated, D6255 is counted as 1 byte. The maximum data length is 58 bytes.  
Errors will occur when the length is longer than 58 bytes. Unit: byte.  
Port: The communication port. Fixed to “00Hex".  
MAC ID: The node address of the target equipment on DeviceNet.  
Service Code: The service code of the explicit message. See the meanings of the codes in the table  
below:  
Service Code  
01Hex  
Explanation  
Read all attributes (Get_Attribute_All)  
Set up all attributes (Set_Attribute_All)  
Read a single attribute (Get_Attribute_Single)  
Set up a single attribute (Set_Attribute_Single)  
02Hex  
0EHex  
10Hex  
15  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
2)  
Structure of response message  
See the table below:  
Response Message  
PLC device  
D6000  
15 14 13 12 11 10 9  
ReqID  
8
7
6
5
4
3
2
1
0
Status  
Size  
Message Header  
D6001  
Port  
D6002  
Service Code  
Service Response Data  
MAC ID  
D6003 ~ 6031  
Message Data  
The definitions of ReqID, Port, Service Code and MAC ID are the same as their definitions in request  
message.  
Size: The length of the message, starting from D6003. Max. 58 bytes. Errors will occur when the  
length is longer than 58 bytes. Unit: byte.  
See the table below for the meanings of Status (status codes):  
Status  
Explanation  
No explicit message is sent out.  
0
1
The communication of explicit message is successful.  
The explicit message is being sent out.  
Error: No response from the target equipment.  
Error: Command is invalid.  
2
3
4
5
Error: Size of request message is invalid.  
Error: Size of response message is invalid.  
Error: Failing to establish a connection to the target equipment.  
Reserved  
6
7
8 ~ 255  
3)  
Notes:  
DVPDNET-SL can only send out 1 explicit message at a time.  
Before sending explicit message by using WPL program, we suggest you clear the request message  
editing area and response message editing area to 0.  
If the slave responds with standard error code, and DVPDNET-SL also consider the communication  
being successful, “The communication of explicit message is successful.” will indicate that the  
communication has been completed successfully.  
16  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
4)  
Application example (I)  
Target  
When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502  
1> The connection  
DVPDNET  
DVP28SV  
RUN  
STOP  
Node Address:00  
DeviceNet  
Node Address:02  
RJ12  
Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network.  
2> Compulsory settings and explanations on devices  
Compulsory settings in DVPDNET-SL  
Parameter  
Set value  
00  
Explanation  
Node address  
Set the node address of DVPDNET-SL to “00”.  
Set the communication speed of DVPDNET-SL and bus to  
“500kbps”.  
Baud rate  
500kbps  
Compulsory settings in DNA02  
Parameter  
Set value  
02  
Explanation  
Node address  
Set the node address of DNA02 to “02".  
Set the communication speed of DNA02 and bus to  
“500kbps”.  
Baud rate  
500kbps  
Compulsory settings in VFD-B  
Parameter  
02-00  
Set value  
04  
Explanation  
The main frequency is operated on RS-485 interface.  
The operation commands are operated on the  
communication interface. Operation by keys is valid.  
02-01  
03  
09-00  
09-01  
09-04  
01  
03  
03  
Communication address of VFD-B: 01  
Baud rate: 38,400  
Modbus RTU mode. Data format <8, N, 2>  
17  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
Explanations on devices  
Explanation  
15 14 13 12 11 10 9  
PLC device  
Content  
8
7
6
5
4
3
2
1
0
D6250 0101Hex ReqID = 01Hex  
D6251 0005Hex Port = 00Hex  
Command = 01Hex  
Size = 05Hex  
D6252 0E02Hex Service Code = 0EHex  
MAC ID = 02Hex  
Request  
message  
editing area  
D6253 0001Hex High bye of Class ID =00Hex Low byte of Class ID = 01Hex  
High byte of Instance ID =  
00Hex  
Low byte of Instance ID =  
01Hex  
D6254 0001Hex  
D6255 0001Hex N/A  
Attribute ID = 01Hex  
Status = 01Hex  
Size = 02Hex  
D6000 0101Hex ReqID = 01Hex  
D6001 0002Hex Port = 00Hex  
D6002 8E02Hex Service Code = 8EHex  
Response  
message  
MAC ID = 02Hex  
editing area  
High byte of Service Data = Low byte of Service Data =  
D6003 031FHex  
03Hex  
1FHex  
3> PLC program  
M1002  
ZRST  
ZRST  
D6000 D6031  
D6250 D6281  
Reset response message editing area  
& request message editing area  
M0  
MOV  
MOV  
MOV  
H0101 D6250  
ReqID = 01, Command = 01  
H0005 D6251 Port = 00, Size = 05  
Service Code = 0E, MAC ID = 02  
H0E02 D6252  
MOV  
MOV  
MOV  
H0100 D6253 Class ID to be read = 01  
H0100 D6254  
H0100 D6255  
Instance ID to be read = 01  
Attribute ID to be read = 01  
4> Program explanations:  
In the beginning of the program, clear the response message editing area and request message  
editing area to 0.  
When M0 = On, DVPDNET-SL will send out request message, reading Class 1>>Instance 1>>  
Attribute 1 of the target equipment (node address: 02). If the communication of explicit message is  
successful, the slave will return with a response message.  
When M0 = On, DVPDNET-SL will only send out request message once. If you would like it to send out  
request message again, you will have to change ReqID.  
When the reading is successful, the message responded from the target equipment will be stored in  
D6000 ~ D6003.  
18  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
5)  
Application example (II)  
Target  
M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.  
1> The connection  
Note: IFD9502, a Delta DeviceNet slave module can connect the temperature controller to DeviceNet  
network.  
2> Compulsory settings and explanations on devices  
Compulsory settings in DVPDNET-SL  
Parameter  
Set value  
00  
Explanation  
Node address  
Set the node address of DVPDNET-SL to “00”.  
Set the communication speed of DVPDNET-SL and bus to  
“500kbps”.  
Baud rate  
500kbps  
Compulsory settings in DNA02  
Parameter  
Set value  
02  
Explanation  
Node address  
Set the node address of DNA02 to “02”.  
Set the communication speed of DNA02 and bus to  
“500kbps”.  
Baud rate  
500kbps  
Compulsory settings in VFD-B  
Parameter  
02-00  
Set value  
04  
Explanation  
The main frequency is operated on RS-485 interface.  
The operation commands are operated on the  
communication interface. Operation by keys is valid.  
02-01  
03  
09-00  
09-01  
09-04  
01  
03  
03  
Communication address of VFD-B: 01  
Baud rate: 38,400  
Modbus RTU mode. Data format <8, N, 2>  
19  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
Explanations on devices  
Explanation  
15 14 13 12 11 10 9  
PLC device  
Content  
8
7
6
5
4
3
2
1
0
D6250 0101Hex ReqID = 01Hex  
D6251 0005Hex Port = 00Hex  
Command = 01Hex  
Size = 07Hex  
D6252 0E02Hex Service Code = 10Hex  
MAC ID = 02Hex  
Request  
message  
D6253 0099Hex High byte of Class ID = 00Hex Low byte of Class ID = 99Hex  
High byte of Instance ID =  
00Hex  
Low byte of Instance ID =  
01Hex  
editing area  
D6254 0001Hex  
D6255 0002Hex N/A  
Attribute ID = 02Hex  
Low byte of data = 04Hex  
Status = 01Hex  
D6256 0004Hex High byte of data = 00Hex  
D6000 0101Hex ReqID = 01Hex  
D6001 0002Hex Port = 00Hex  
D6002 9002Hex Service Code = 90EHex  
Size = 02Hex  
Response  
message  
MAC ID = 02Hex  
editing area  
High byte of Service Data =  
Low byte of Service Data =  
04Hex  
D6003 0004Hex  
00Hex  
3> PLC program  
M1002  
ZRST  
ZRST  
D6000 D6031  
D6250 D6281  
Reset response message editing area  
& request message editing area  
M1  
MOV  
MOV  
MOV  
H0101 D6250 ReqID = 01, Command = 01  
H0008 D6251  
Port = 00, Size = 08  
H0E02 D6252 Service Code = 0E, MAC ID = 02  
H0099 D6253 Class ID to be write= 99  
MOV  
MOV  
MOV  
MOV  
Instance ID to be written = 01  
Attribute ID to be written = 02  
Data to be written = 0004  
H0001 D6254  
H0002  
H0004  
D6255  
D6256  
4> Program explanations  
In the beginning of the program, clear the response message editing area and request message  
editing area to 0.  
When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>  
Instance 1 >> Attribute 2 of the target equipment (node address: 02). If the communication of  
explicit message is successful, the slave will return with a response message.  
20  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to  
send out request message again, you will have to change ReqID.  
When the writing is successfully done, the message responded from the target equipment will be  
stored in D6000 ~ D6003.  
21  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
6 Bit-Strobe Command  
6.1 Principle of Bit-Strobe  
Bit-strobe is one of the standard I/O transmission methods for DeviceNet. The length of command is fixed to 8  
bytes (i.e. 64 bits), and every bit corresponds to a slave.  
Corresponding nodes on the network  
PLC  
device  
b15  
b14  
b13  
b1  
b0  
D6282  
D6283  
D6284  
D6285  
Node 15  
Node 31  
Node 47  
Node 63  
Node 14  
Node 30  
Node 46  
Node 62  
Node 13  
Node 29  
Node 45  
Node 61  
Node 1  
Node 17  
Node 33  
Node 49  
Node 0  
Node 16  
Node 32  
Node 48  
When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to  
the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will be  
to respond with a message to the master.  
D6282  
D8283  
b31 b30  
b18 b17 b16 b15 b14  
b2 b1 b0  
Node 0  
Node 1  
Node 2  
Node 14  
In the bit-strobe mode, the master will not send control data to the slave node. However, when its  
corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its  
corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.  
22  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
7 Display of Node Status on Network  
7.1 Display of Node Status in Scan List  
This function is to monitor if DeviceNet slave is offline or not. DVPDNET-SL does read-time monitoring to the  
nodes in the scan list and maps the status of every node to a bit. You can acquire the node status by  
monitoring D6032 ~ D6035. See the table below for the corresponding relation between PLC devices and the  
nodes on the network:  
Corresponding nodes on the network  
PLC  
device  
b15  
b14  
b13  
b1  
b0  
D6032  
D6033  
D6034  
D6035  
Node 15  
Node 31  
Node 47  
Node 63  
Node 14  
Node 30  
Node 46  
Node 62  
Node 13  
Node 29  
Node 45  
Node 61  
Node 1  
Node 17  
Node 33  
Node 49  
Node 0  
Node 16  
Node 32  
Node 48  
When the node in the scan list is normal, the corresponding bit will be off. If the node occurs with abnormality,  
its corresponding bit will be On.  
7.2 Status of DVPDNET-SL  
You can acquire the real-time status of DVPDNET-SL by monitoring D6036. When DVPDNET-SL runs  
normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0.  
When error occurs in DVPDNET-SL, the high byte of D6036 = 2. For detailed error information, please refer  
to the error codes, i.e. the low byte of D6036.  
Explanation  
PLC  
device  
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0  
Status of DVPDNET-SL  
Error codes of DVPDNET-SL  
(0: normal, 1: initializing, 2: error)  
D6036  
23  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
8 Setup of Slave Mode  
DVPDNET-SL can serve as slave through modifying of the mode by software. As DVPDNET-SL serves as slave,  
the default input / output data length is 8 bytes and max input / output data length is 255 bytes.  
DVPDNET-SL can be set as slave mode in the following method.  
1) Connect the devices according to below figure. PC accesses PLC MPU via RS232 or RS485.  
DVPDNET-SL  
DVP28SV  
DeviceNet Builder  
2) Open DeviceNet Builder software, and select “Setup” => “Communication Setting” => “System Channel”,  
and the “Serial Port Setting” dialog box will appear as below.  
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud  
rate and communication format. Click on “OK” after configuration is finished.  
Item  
Function  
Default  
COM1  
COM port on the PC to be used to communicate  
with DVP-SV  
COM Port  
Address  
Baud rate  
01  
Communication address of DVP-SV  
Communication speed between the PC and  
DVP-SV  
9,600 (bps)  
Data Bits  
Parity  
7
Communication protocol between the PC and  
DVP-SV  
Even Parity  
1
Stop Bit  
Communication mode between the PC and  
DVP-SV  
Mode  
ASCII  
24  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”  
to start scanning the DeviceNet network after selecting “analog online” in the following window.  
5) Select “Network” >> “Scan module” and then “Scan module setting” dialog box appears. After “Slave mode”  
is selected there, fill the appropriate slave data length. Finally click on “OK” to finish the setting.  
6) Select “Network” >> “Download” and then below dialog box appears. Click on “Y” to download the  
configuration data to DVPDNET-SL.  
7) After download is finished, power PLC off and then repower it. At this time, DVPDNET-SL has been set as  
slave mode.  
25  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
9 Setup of Extended Baud Rate  
9.1 Setup of Extended Baud Rate (as master mode)  
1) Connect the device to the Devicenet network according to the following figure. PC accesses PLC MPU via  
RS232 or RS485.  
DVPDNET-SL  
DVP28SV  
DeviceNet Builder  
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”. And  
then the following dialog box appears.  
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud  
rate and communication format. Click on “OK” after configuration is finished.  
Item  
Function  
Default  
COM1  
COM port on the PC to be used to communicate  
with DVP-SV  
COM Port  
Address  
Baud rate  
01  
Communication address of DVP-SV  
Communication speed between the PC and  
DVP-SV  
9,600 (bps)  
Data Bits  
Parity  
7
Communication protocol between the PC and  
DVP-SV  
Even Parity  
1
Stop Bit  
Communication mode between the PC and  
DVP-SV  
Mode  
ASCII  
4) Select “Network” => "Online” and the following “Select Communication Channel” dialog box will appear. Click  
on “OK”.  
26  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
5) Select “Network” => "Setup of scan module” and the following "Setup of scan module” dialog box appears.  
Select “Master mode” and “Startup” to activate the function of extended baud rate. In the meanwhile, select  
the appropriate baud rate according to the actual demand. Click “OK” to finish setting.  
6) Select “Network” => “Download” and the following dialog box appears. Click “OK” to download the  
configuration information to DVPDNET-SL.  
7) After download is completed, set DVPDNET-SL’s function switch DR0 and DR1 as ON and then repower  
PLC to finish the setting of the extended baud rate.  
27  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
9.2 Setup of Extended Baud Rate (as slave mode)  
1) Connect the relevant devices to the DeviceNet network according to the following figure.  
DVPDNET-SL(Master)  
DVP28SV  
DeviceNet Builder  
DeviceNet  
DVP28SV  
DVPDNET-SL(Slave)  
Note:  
a. DVPDNET-SL at the bottom of the above figure has been set as slave mode.  
b. The node addresses of two DVPDNET-SLs must not be repeated. (See section 2.4).  
c. The baud rates of two DVPDNET-SLs are both 500K bps (See section 2.5.  
2) Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”,  
In result, you can see the following dialog box.  
28  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud  
rate and communication format. Click on “OK” after configuration is finished.  
Item  
Function  
Default  
COM1  
COM port on the PC to be used to communicate  
with DVP-SV  
COM Port  
Address  
Baud rate  
01  
Communication address of DVP-SV  
Communication speed between the PC and  
DVP-SV  
9,600 (bps)  
Data Bits  
Parity  
7
Communication protocol between the PC and  
DVP-SV  
Even Parity  
1
Stop Bit  
Communication mode between the PC and  
DVP-SV  
Mode  
ASCII  
4) Select “Network” => "Online” and the “Select Communication Channel” dialog box will appear. Click on “OK”  
to start scanning the entire DeviceNet network.  
5) After scanning is successful, right click DNET (Slave) to select “Parameter editing”.  
29  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
6) Set parameter 5 as “Enable” and select the baud rate in parameter 6 in the following page. Click on  
“Download” to download the newly set parameter value to DVPDNET-SLSlave.  
7) After download is completed, set DVPDNET-SLSlave’s function switch: DR0 and DR1 as ON. And then  
repower PLC to finish the setting of the extended baud rate.  
30  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
10 Application Example on Constructing DeviceNet Network  
In this section, we will present an application example, illustrating how to construct a DeviceNet network and the  
configuration of the network.  
Target  
Using an X point of DVP28SV to control RUN/STOP of the remote VFD-L AC motor drive.  
10.1 How to Construct a DeviceNet Network  
1) The connection  
DVPDNET-SL  
DVP28SV  
START  
STOP  
X0  
X1  
DeviceNet Builder  
RS232  
DeviceNet  
RTU-DNET  
VFD-L  
VFD-L  
RS485  
Note:  
RTU-DNET, a Delta DeviceNet remote IO communication module supports the MODBUS communication  
function.  
2) Set up DVPDNET-SL, RTU-DNET and VFD-L according to the table below.  
Module  
Node address  
Baud rate  
DVPDNET-SL  
RTU-DNET  
01  
02  
500kbps  
500kbps  
31  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
VFD-L  
Set value  
Explanation  
parameter  
02-00  
02-01  
4
3
Transmit the frequency of VFD-L via RS485  
communication.  
Control operation of VFD-L via RS485  
communication.  
09-00  
09-01  
09-04  
1
1
1
Set the node address of VFD-L in Modbus to 1.  
Set the communication rate of VFD-L in Modbus 9600  
Set the communication format of VFD-L in Modbus to  
7, E, 1, ASCII.  
10.2 How to Configure Network by DeviceNet Network Configuration Tool  
1) Configuration of DeviceNet slave  
1> Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System  
Channel”, and the “Serial Port Setting” dialog box will appear as below.  
2> Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address,  
baud rate and communication format. Click on “OK” after configuration is finished.  
Item  
Function  
Default  
COM1  
COM port on the PC to be used to  
communicate with DVP-SV  
COM Port  
Address  
Baud rate  
Communication address of DVP-SV  
01  
Communication speed between the PC and  
DVP-SV  
9,600 (bps)  
Data Bits  
Parity  
7
Communication protocol between the PC  
and DVP-SV  
Even Parity  
1
Stop Bit  
Communication mode between the PC and  
DVP-SV  
Mode  
ASCII  
32  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
3> Select “Network” => "Online”, and the “Select Communication Channel” dialog box will appear.  
Clicking on “OK” starts scanning the DeviceNet network.  
4> If the bar on the dialog box does not progress, it means the connection between the PC and DVP-SV  
is abnormal, or there are other programs also using the COM port on the PC. After the scan is  
completed, the dialog box will tell you that the scan is completed, and the icons and device names of  
all the nodes scanned on the network will be shown on the screen. See the figure below, in which the  
node address of DVPDNET-SL and RTU-DNET are 01 and 02 respectively.  
33  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
5> Double click on RTU-DNET (node 02), and the "Node Configuration…” dialog box will appear.  
6> Click on “IO Configure…” button in “Node Configuration” dialog box, and you will then see “RTU  
Configuration” page where you click on “Scan IO” button and “Warning” dialog box will appear. Click  
“OK” then DeviceNet Builder will detect the devices connected to RTU-DNET as below.  
7> Because no special module is connected to the right side of RTU-DNET, “None” will show in the  
location of the special module in the following window. The point number for X and Y are both 0.Then  
click on “Gateway setting”.  
34  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
8> In the interface of “Modbus gateway setting”, use the parameters of one slave and fill the relevant  
values there. You can refer to the user manual of RTU-DNET.  
Note: The slave here is the slave in Modbus network without direct relation with DeviceNet network.  
9> Click on “OK” in the above window and then click on “Download” in the following window to  
download the configuration data to RTU-DNET. After download is finished, the configuration  
of RTU-DNET is completed.  
35  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
2) Configuration of DeviceNet Master  
1> Double click on DNET Scanner (node 01), and the “Scan Module Configuration..." dialog box will  
appear. You can find the currently available nodes, RTU-DNET and VFD-B Drives 230V 3HP, in  
the list on the left side. On the right side, there is an empty “Scan List”.  
2> (2) Move the slave devices on DeviceNet in the "Available Nodes” list on the left side to the "Scan  
>
List” on the right side. Select a node and click on . Follow the steps to move all the nodes to the  
scan list.  
36  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
3> Confirm all the settings and click on “OK”. Next, download the configuration to DVPDNET-SL. If  
DVP-SV is in RUN mode while you are downloading the configuration, a “Warning” dialog box will  
appear.  
4> Click on “OK” to continue the download. Make sure DVP-SV is in RUN mode.  
The mapping relation between DVPDNET-SL and slave device is shown as below after  
configuration of the DeviceNet network following the above steps is completed.  
DVP28SV DVPDNET-SL slave device  
DVP28SV  
D6287  
DVPDNET-SL  
RTU-DNET & VFD-L  
Control word of VFD-L  
2000H)  
Control frequency of VFD-L  
D6288  
(2001H)  
DVP28SV DVPDNET-SL slave device  
DVP28SV  
D6037  
DVPDNET-SL  
RTU-DNET & VFD-L  
Output frequency of VFD-L  
2103H)  
37  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DeviceNet Network Scanner DVPDNET-SL  
10.3 Ladder Diagram Program  
This section introduces how to edit the ladder diagram program to meet the control request of DeviceNet network.  
When X0=ON, VFD-L AC motor drive runs;  
Control  
request  
When X1=ON, VFD-L AC motor drive stops;  
After VFD-L has run for 6 seconds and at this time the running frequency still has not  
reached the designated frequency, Y0 of DVP28SV=ON.  
Explanation of PLC Program  
X0  
MOV  
MOV  
H12  
D6287  
When X0=ON, VFD-L starts up and  
its target frequency is 20Hz.  
K2000 D6288  
X1  
X0  
T0  
MOV  
TMR  
H1  
T0  
D6287  
K60  
When X1=ON, VFD-L stops running.  
Y0 will be ON in DVP28SV if the  
frequency of VFD-L has not reached  
20Hz after starting up for 6 seconds  
LD<> K2000 D6037  
(
Y0  
)
38  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
11 LED Indicator & Trouble-shooting  
DVPDNET-SL supports two diagnostic methods: indicator diagnosis and digital displayer diagnosis.  
DVPDNET  
POWER  
MS  
NS  
11.1 LED Indicator Diagnosis  
POWER LED  
LED status  
Off  
Indication  
Power is abnormal.  
Power is normal.  
How to correct  
Make sure DVPDNET-SL is powered.  
Green light on  
--  
NS LED  
LED status  
Indication  
How to correct  
1. Make sure DVPDNET-SL is powered.  
2. Make sure at least 1 node or more are  
communicating on the network.  
No power or duplicate ID  
check has not completed  
Off  
Green light  
blinking  
No correction is needed; check the digital indicator for  
the error.  
No communication  
Normal operation  
Green light on  
--  
Red light  
blinking  
Error in communication  
Check the digital indicator and eliminate the error.  
1. Make sure all the devices have their unique node  
address.  
2. Check the network for correcting media installation  
and baud rate.  
3. Check if the node address of DVPDNET-SL is valid.  
4. Check if the network power is normal.  
Network error; cannot check  
duplicate ID; bus-off (check  
the digital indicator)  
Red light on  
MS LED  
LED status  
Off  
Indication  
No power  
How to correct  
Make sure DVPDNET-SL is powered.  
Green light  
blinking  
The master is not  
configured.  
Configure the scan list and re-download it to  
DVPDNET-SL.  
Green light on  
Normal operation  
--  
Check the digital indicator and make sure the salve  
information in the scan list is consistent with the salve  
actually connected.  
Red light  
blinking  
Some slaves encounter  
communication error.  
1. Check if the configuration is valid.  
2. Re-power it. If the error still exists, send it back to  
the factory for repair.  
Red light on  
Internal error  
39  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
MS & NS LED  
LED status  
Indication  
How to correct  
NS LED  
Off  
MS LED  
Off  
No power  
Make sure DVPDNET-SL is powered.  
Make sure at least 1 node or more are  
Green light  
on  
Duplicate ID check has not communicating in the network, and the baud  
Off  
completed.  
rate is the same as the setting in  
DVPDNET-SL.  
Green light  
on  
Change the MAC ID setting and re-power  
DVPDNET-SL.  
MAC ID detection failure  
or bus-off  
Red light on  
Red light on  
1. Check if the network cable is correctly  
connected to DVPDNET-SL.  
2. Check the 24V DC network power.  
Red light  
blinking  
No 24V DC power from  
DeviceNet network  
Go to your manufacturer or distributor for  
problem-solving.  
Red light on Red light on Hardware error  
11.2 Digital displayer diagnosis  
Code  
Indication  
How to correct  
Node address of  
DVPDNET-SL (in normal  
operation)  
0 ~ 63  
--  
DVPDNET-SL is in STOP  
status.  
Turn the PLC MPU to RUN and start I/O data  
exchange.  
80  
F0  
F1  
F2  
F3  
Duplicate MAC ID check  
failure  
Check the node address and re-power DVPDNET-SL.  
No slave device in the scan Configure the scan list and download it to  
list.  
DVPDNET-SL.  
Check if the power of DVPDNET-SL and PLC MPU is  
normal.  
Low voltage is detected.  
Switch IN1 from On to Off and re-power  
DVPDNET-SL.  
Entering test mode  
Bus-off  
1. Check if the network cable is normal.  
2. Check if the baud rate is correct.  
3. Re-power DVPDNET-SL.  
F4  
Make sure the cable is correctly connected and check  
if the network power is normal.  
F5  
F6  
F7  
F8  
F9  
No network power  
Internal error; Flash or RAM If the error still exists after re-power, send your  
check error  
DVPDNET-SL back to the factory for repair.  
Internal error; GPIO check  
error  
If the error still exists after re-power, send your  
DVPDNET-SL back to the factory for repair.  
Error produced in factory  
manufacturing  
If the error still exists after re-power, send your  
DVPDNET-SL back to the factory for repair.  
Internal error; EEPROM  
access failure  
If the error still exists after re-power, send your  
DVPDNET-SL back to the factory for repair.  
1. Configure the network correctly and re-download it  
to DVPDNET-SL.  
FA  
Invalid configuration data  
2. Check if the node address of the slave in the scan  
list is the same as the node address of  
DVPDNET-SL.  
Device key parameter does Make sure that the device parameter in the scan list  
E0  
E1  
not match the scan list  
table.  
matches the desired key parameter, including vendor  
ID, product code, device type and version.  
Data size returned does not  
match the scan list.  
Re-configure the scan list using correct data size.  
40  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
DeviceNet Network Scanner DVPDNET-SL  
Code  
E2  
Indication  
How to correct  
1. Check if there is any change for the node address of  
the slave.  
Slave device in the scan list  
does not exist or is offline.  
2. Check if the communication cable is disconnected  
or connected loosely.  
DVPDNET-SL fails to  
transmit a message.  
Make sure that the connection is valid and check if the  
baud rate is correct.  
E3  
E4  
Error detected in sequence  
of fragmented I/O  
Check if the slave is operating normally.  
messages from device  
Slave device returns error  
when DVPDNET-SL  
attempts to communicate  
with it.  
E5  
E6  
Check if the slave is operating normally.  
Data size returned is bigger  
than expected.  
Check the configuration of slave device and scan list.  
If the code is displayed long, do the troubleshooting  
according to the following steps.  
1. Make sure that at least two nodes work normally in  
the network.  
2. Check if either end of the network is connected with  
the terminal resistor of 121.  
DVPDNET-SL is checking  
MAC ID.  
E7  
3. Check if the baud rates of the node devices in the  
network are consistent with each other.  
4. Check if the communication cable is normal so as to  
avoid that the cable is disconnected or connected  
loosely.  
5. Re-power 10DNET scanner module.  
41  
DVP-PLC Operation Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  

AEG Dishwasher 40730 User Manual
AEG Washer 2252 F User Manual
Agilent Technologies Water Dispenser 856290216 User Manual
Aiphone Stereo System IS WBCA User Manual
Aiwa Stereo System XR MG9 User Manual
Aleratec Computer Accessories 350117 User Manual
Altinex Network Card VA6835FC User Manual
Amana Ice Maker IA 52204 0001 User Manual
Axis Communications Security Camera P1353 User Manual
BB Electronics Switch EIR618 User Manual