Firex 46184 User Manual

Item 46184  
120V AC Direct Wire with  
Battery Back-up Smoke Alarm  
with Moisture Resistant Coating  
Smoke Alarm  
Features  
Description  
®
The FireX 46184 Smoke Alarm is an ionization 120V AC  
Moisture Resistant — A conformal coating has  
been applied to the alarm electronics allowing it to  
be used in conditions where humidity and  
condensation can be an issue.  
smoke alarm with battery back-up for single or multiple  
station use. It has a conformal coating which allows it to be  
used in conditions where humidity and condensation can be  
an issue. The 46184 includes a Quick Quiet™ False Alarm  
Control feature which allows the user to quiet an unwanted  
alarm for up to 15 minutes. The 46184 has a front loading  
Alarm Locator — Red LED flashes until reset for  
quick, clear identification of the initiating alarm in  
an interconnected system.  
Front Loading Battery Door — Eliminates  
battery handling during installation and allows for  
safe and convenient battery replacement.  
battery door with PowerLink™ Tab, 85 decibel horn, ramp-up test horn, and multi-purpose LED  
indicators. The Latching LED feature clearly identifies the smoke alarm that initiated an alarm in  
an interconnected system with a flashing red LED.  
PowerLink™ Tab — Makes installation faster  
and easier, reducing callbacks due to battery  
failure. Simply pull tab, close door and press  
test button.  
Installation of Smoke Alarm  
This smoke alarm should be installed in accordance with the NFPA’s Standard 72 (National Fire  
Protection Association, Batterymarch Park, Quincy, MA 02269) and any local codes that apply.  
Use #18 AWG minimum solid or stranded wire. When interconnecting, maximum wire length  
between any two is 1,500 feet for #18 AWG or 4,000 feet for #14 AWG (20 OHMS loop resistance).  
DO NOT connect to any other type or model  
of heat or smoke alarm. Connect smoke or  
heat alarms to a single AC branch circuit. If  
local codes do not permit, be sure the  
neutral wire is common to both phases.  
Quick Quiet™ False Alarm Control — Quiets  
unwanted alarms for up to 15 minutes  
Visable Low Battery Indicator — Helps locate  
chirping unit.  
9 Volt Battery Back-up (battery included) —  
Provides added protection in the event of a  
power failure  
Ramp-Up Horn — Allows you to test the unit  
without the ear-piercing horn.  
Technical Information  
Architectural  
Specifications  
Item/Model  
46184 / FADC  
Product Weight  
Operating Temp.  
Interconnect Qty.  
8 ounces  
40˚ to 100˚F  
The smoke alarm shall be a Styleline design (1-5/8” high,  
5” wide), powered by a 120 VAC, 60 Hz source with a 9  
volt battery back-up. The alarm shall have a “quick  
connect” molded harness and front loading battery door.  
The alarm shall have a dual chamber ionization sensor.  
The alarm shall be rated at no greater than .5W in  
standby. Nominal sensitivity shall be measured by U.L. at  
obs. 1.35 0.7%/ft. Temperature operating range shall  
be between 40° and 100°F (4°-38°C); humidity range  
between 10%-93% relative humidity; 100% solid state  
alarm circuits over an input range of 100-130 VAC. A  
green continuous power-on indicator shall be a built-in  
light emitting diode in the standby condition; a second  
red flashing LED shall indicate that a sufficient 9-volt  
battery back-up is present; when activated the initiating  
alarm red LED shall remain illuminated while the  
interconnected alarm LEDs are extinguished. The Quick  
Quiet™ False Alarm Control feature shall desensitize the  
alarm for 15 minutes. The red LED shall blink once every  
10 seconds when in Quick Quiet™ False Alarm Control  
and the alarm shall produce two short chirps 2 seconds  
apart at the conclusion of the desensitized period. The  
test switch shall electronically activate the chamber to  
simulate smoke and check for proper operation. The  
electronic horn shall have a level of 85 decibels at 10  
feet. The alarm shall mount to a single gang box, 4”  
octagon junction box, or a square to round drywall ring  
without screw removal. It shall have a pigtail wiring,  
separate mounting bracket. The 46184 shall meet the  
requirements of U.L. Standard 217.  
Up to 18 FireX devices maximum: 12 smoke alarm or smoke and  
carbon monoxide combination alarms, items 4418 (model AD), 4518 (model ADC), 4671 (model  
TCPI), 5000 and 4618 (model FADC), 4480 (model PAD), and FireX smoke and carbon monoxide  
combination alarm 12000 (model FADCM). Up to 6 heat or carbon monoxide alarms maximum;  
FireX heat alarm item 5700 (model ADH), FireX carbon monoxide alarm items 6045 (model  
COQ8) or 10000 (model COE).  
Electrical Rating  
Alarm Point  
Horn Output  
Listing  
120V AC, 60Hz, 50mA max, 9 Volt Battery Back-up  
1.35 +/- 0.7% / ft. obscuration  
85 decibels at 10 feet  
UL 217  
Detection Type  
Humidity Range  
Dual ionization chamber  
10% to 93% Relative Humidity  
Shipping Specifications  
Individual Carton Dim.  
Master Carton Quantity  
5-1/8” x 5-1/8” x 1-11/16” 13cm x 13cm x 4.3cm  
24  
Master Carton Dimensions 21-1/2” x 11” x 5-7/8”  
54.6cm x 28cm x 14.9cm  
5.9 kg  
Master Carton Weight  
Pallet Quantity  
Pallet Dimensions  
13 lbs  
1008  
48”L x 40”W x 46”H  
122cm x 102cm x 117cm  
Technical Service Telephone +1 800 445 8299  
Technical Service Facsimile +1 630 260 7243  
©2006 invensys Controls 11/06 - #150-2023  
191 E. North Avenue  
Carol Stream Illinois 60188 USA  
Telephone +1 800 951 5526 Facsimile +1 630 260 7299  
Year  
Limited  
E
5Warranty  

Hotpoint GW38X User Manual
Hotpoint 6500 User Manual
Glen Dimplex Home Appliances Ltd 110 GT User Manual
Daewoo DTQ 13V1FC User Manual
Cypress 001 07160 User Manual
BenQ Computer Monitor GL2240AM User Manual
Asus LCD Monitor VW226TTAA User Manual
Asus Computer Monitor VH236 User Manual
AOC LM929 User Manual
AMD GA M61PM S2 User Manual