Emerson Process Management Emerson Electric Co Computer Monitor MSL600 User Manual

Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
MSL600  
Ultrasonic continuous sludge blanket monitor  
Model Covered:  
MSL600/Z0 with MSL603 transducer  
Page 1  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
5.6  
5.7  
5.8  
5.9  
Relay parameters .............................................................................................................................................. 23  
Alarm.................................................................................................................................................................. 23  
Transducer out-of-water time........................................................................................................................... 23  
Digital input ....................................................................................................................................................... 24  
6.  
Detailed operation.................................................................................................25  
6.1  
6.2  
6.3  
6.4  
The menu structure........................................................................................................................................... 25  
Parameter editing.............................................................................................................................................. 26  
Scrolling............................................................................................................................................................. 26  
Direct access..................................................................................................................................................... 26  
7.  
Application parameters ........................................................................................27  
7.1  
Main menu parameters..................................................................................................................................... 27  
7.1.1  
7.1.2  
7.2  
Cancel password................................................................................................................................................. 27  
Go Online/Offline................................................................................................................................................. 27  
Installation parameters..................................................................................................................................... 27  
7.2.1  
7.2.2  
7.2.3  
7.2.4  
7.3  
Tank Depth – P101 ............................................................................................................................................. 27  
Xdr Tilt Time – P103 ........................................................................................................................................... 27  
Tag No. – P242................................................................................................................................................... 27  
Description – P240.............................................................................................................................................. 28  
De-sludge parameters ...................................................................................................................................... 28  
7.3.1  
7.3.2  
7.3.3  
7.3.4  
7.3.5  
7.3.6  
7.4  
Start On - P250 ................................................................................................................................................... 28  
Stop On - P251 ................................................................................................................................................... 28  
Stop If - P252...................................................................................................................................................... 29  
Start Time - P253................................................................................................................................................ 29  
Interval - P254..................................................................................................................................................... 29  
Max Retries - P257 ............................................................................................................................................. 29  
Cleaning parameters......................................................................................................................................... 30  
7.4.1  
7.4.2  
7.4.3  
7.5  
Start On - P260 ................................................................................................................................................... 30  
Interval - P264..................................................................................................................................................... 30  
Cleaning Time - P444 ......................................................................................................................................... 30  
mA output parameters...................................................................................................................................... 30  
7.5.1  
7.5.2  
7.5.3  
7.5.4  
7.6  
Lower Range Val - P400..................................................................................................................................... 30  
Upper Range Val - P401..................................................................................................................................... 30  
Alarm Action - P402 ............................................................................................................................................ 31  
0/4-20mA - P403................................................................................................................................................. 31  
Relay parameters .............................................................................................................................................. 32  
7.6.1  
7.6.2  
7.6.3  
7.7  
Relay RL1 mode (P410) and RL2 mode (P420).................................................................................................. 32  
Relay On and Off Points ..................................................................................................................................... 34  
Relay overrides (Min ON, Max ON, and Min OFF).............................................................................................. 34  
Display parameters (HMI)................................................................................................................................. 34  
7.7.1  
7.7.2  
7.7.3  
7.7.4  
7.8  
HMI upper, middle, and lower display options..................................................................................................... 34  
Backlight On/Off - P575 ...................................................................................................................................... 35  
Clear Trend......................................................................................................................................................... 35  
Clear Profile ........................................................................................................................................................ 35  
Logging parameters.......................................................................................................................................... 36  
7.8.1  
7.8.2  
7.8.3  
Log Interval - P590.............................................................................................................................................. 36  
Fast log - P591.................................................................................................................................................... 36  
Data Overwrite - P592......................................................................................................................................... 36  
Page 3  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.8.4  
Low Mem Alarm - P593....................................................................................................................................... 36  
7.9  
Engineering parameters................................................................................................................................... 37  
7.9.1  
7.9.2  
7.9.3  
7.9.4  
7.10  
Alg. Select – P620............................................................................................................................................... 37  
Common algorithm parameters P621 to P629 .................................................................................................... 37  
Municipal 1 parameters P630 to P637 ................................................................................................................ 40  
Municipal 2 parameter P640 ............................................................................................................................... 42  
System parameters........................................................................................................................................... 43  
7.10.1 AUTO CYCLE function........................................................................................................................................ 43  
7.10.2 DISPLAY test ...................................................................................................................................................... 43  
7.10.3 Current Output test parameters P700 to P702.................................................................................................... 43  
7.10.4 LOAD DEFAULTS function................................................................................................................................. 43  
7.10.5 COMMS parameters P710 to P716..................................................................................................................... 44  
7.10.6 SETTINGS parameters P730 to P737 and BASE UNITS selection ....................................................................44  
7.10.7 PIN parameter P740 ........................................................................................................................................... 45  
7.10.8 FIXED parameters D750 to D753 ....................................................................................................................... 45  
7.11  
Readings and diagnostics parameters ........................................................................................................... 46  
7.11.1 Readings parameters D800 to D834................................................................................................................... 46  
7.11.2 Diagnostics parameters D835 to D852 ............................................................................................................... 47  
8.  
Technical reference...............................................................................................49  
8.1  
Transmit pulse and echo processing.............................................................................................................. 49  
9.  
Maintenance ..........................................................................................................49  
Troubleshooting....................................................................................................49  
Programming chart ...............................................................................................50  
Specification..........................................................................................................53  
10.  
11.  
12.  
12.1  
MSL600 .............................................................................................................................................................. 53  
12.2  
MSL603 transducer........................................................................................................................................... 54  
13.  
14.  
Dimensional drawings ..........................................................................................55  
MSL603 transducer cable extension ...................................................................57  
Figures and tables  
Figure (1): MSL600 system architecture ..........................................................................................................................9  
Figure (2): Circular clarifiers – Rotating bridge.................................................................................................................10  
Figure (3): Circular clarifiers - Static bridge......................................................................................................................11  
Figure (4): Rectangular clarifiers......................................................................................................................................11  
Figure (5): MSL600 mounting...........................................................................................................................................14  
Figure (6): Transducer cable wiring..................................................................................................................................15  
Figure (7): External connection terminals.........................................................................................................................16  
Figure (8): The LCD display layout...................................................................................................................................18  
Figure (9): Keypad layout.................................................................................................................................................19  
Figure (10): Tank depth parameter .................................................................................................................................21  
Figure (11): Menu structure..............................................................................................................................................26  
Figure (12): MSL600 Bridge mounted unit .......................................................................................................................53  
Figure (13): MSL600 and MSL603 assembly...................................................................................................................54  
Table (A): Connection descriptions reading from left to right (all via M20 cable glands)..................................................16  
Table (B): Relay Parameter numbers...............................................................................................................................32  
Page 4  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
(i)  
Safety precautions  
BEFORE OPERATING THIS DEVICE THE MANUAL SHOULD BE READ FULLY  
The following safety precautions should be observed before using this product or working on the attached cables.  
This MSL600 product is intended for use by qualified personnel who recognize shock hazards and are familiar  
with the safety precautions required to avoid possible injury. Read the operating information carefully before  
using the product.  
The types of product users are:  
Responsible body: This is the individual or group responsible for the use and maintenance of equipment, and  
for ensuring that operators are adequately trained. Operators use the product for its intended function. They  
should not be allowed access to the electrical connections within the control box, and would normally only  
operate the external keypad and monitor the display.  
Maintenance personnel perform routine procedures on the product to keep it operating, for example, checking  
the line voltage or checking electrical connections, replacing mains fuses etc. Otherwise, only service  
personnel should perform them.  
Service personnel are trained to work on live circuits, and perform safe installations and repairs of products.  
Only properly trained service personnel may perform installation and service procedures. There are no user  
serviceable parts on the main PCB section of the MSL600 product.  
Users of this product must be protected from electric shock at all times. The responsible body must ensure  
that users are prevented access and/or insulated from every connection point. Product users must be trained  
to protect themselves from the risk of electric shock.  
Before operating an instrument, make sure the line cord is connected to a properly grounded power  
receptacle. Inspect the connecting cables for possible wear, cracks, or breaks before each use. When fuses  
are used in a product, replace with same type and rating for continued protection against fire hazard.  
Chassis connections must only be used as shield connections for measuring circuits, NOT as safety earth  
ground connections.  
Standard fuses, with applicable national safety approvals, may be used if the rating and type are the same. If  
you are unsure about the applicability of a replacement component, call a MOBREY office for information.  
Only use the MSL600 with the sensor supplied or Mobrey agreed replacement. The unit will not necessarily  
work with apparently equivalent sensor units.  
To clean the instrument, use a damp cloth or mild, water based cleaner. Clean the exterior of the instrument  
only. Do not apply cleaner directly to the inside of the instrument or allow liquids to enter or spill on the  
instrument.  
WARNING - If this equipment is used in a manner not specified by Mobrey, the protection provided may be  
impaired. The MSL600 is regarded as permanently installed equipment and as such a switch or circuit  
breaker must be included in the installation. This should be in close proximity to the equipment, it should be  
marked as the disconnecting device, and it should disconnect both current carrying conductors.  
A protective earth should be used for all applications.  
The normal application of the MSL600 requires it to be mounted on a water handling plant. The installation  
point and power cables associated with the MSL600 must be such that tank overflow, local flooding or pump  
failure do not cause these to be submerged or subject to flows of water. Sensor and sensor cabling can be  
submerged without hazard to equipment operators when correctly connected as described in this manual.  
Explanation of symbols: The IEC Protective Earth Symbol is:  
CHECK THAT THE POWER SUPPLY IS SUITABLE BEFORE SWITCHING POWER ON.  
Internal adjustments can select mains 115 Volts AC power, which makes the equipment unsuitable for 230V AC  
supplies. Check the 2 voltage selection switches compared with the available power supply.  
Page 5  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
1. Introduction  
Before operating this device the manual should be read carefully paying particular attention to the safety  
precautions laid out in section (i).  
This instruction manual provides comprehensive information specific to the Mobrey Measurement continuous  
suspended solids blanket level monitor, the MSL600.  
1.1 About the MSL600  
The basic MSL600 system contains an ultrasonic transducer and a bridge-mounted control unit.  
The control unit is microprocessor-based and is given the designation MSL600. It is intended to be mounted on a  
bridge using a specially designed and easy-to-install mounting bracket that is supplied with the system.  
The system is specially adapted for use with clarifiers and thickeners containing municipal and industrial  
wastewater treatment sludge. The MSL600 provides a means of sensing the presence of the sludge blanket and  
measuring its depth in the clarifier. It also provides a range of current and relay outputs to the user for control and  
alarm purposes.  
The MSL600 uses the sonar principle, with an ultrasonic pulse transmitted under water from a partially  
submerged, IP68-rated transducer (MSL603). The pulse of ultrasound is transmitted vertically down into the  
clarifier tank, and then reflects from the surface of the sludge blanket. The system captures the ultrasonic echoes  
received from the sludge blanket interface and determines the time-of-flight of the echo from the transducer to the  
sludge blanket.  
Knowing the speed of sound in the supernatant (the system has automatic temperature compensation), the  
control unit calculates the distance to the blanket interface. This distance is then subtracted from the  
programmed depth of the tank to give the sludge blanket depth or interface level. This is the system’s  
fundamental process variable.  
1.2 About this Manual  
This section introduces the user to the MSL600 system, its components and key features. The system’s mode of  
operation is explained in this section.  
In section 2, the manual discusses application planning where installation is primarily intended to be on municipal  
and industrial wastewater clarifiers.  
In section 3, the manual discusses the actual physical process of mechanical and electrical installation of the  
system. This section provides a step by step procedure for easy installation of the MSL600 system on site.  
In section 4, the manual introduces the basics of programming the system. This section introduces the human  
machine interface (HMI), keypad and display  
In section 5, the manual discusses the minimum programming steps needed for commissioning the system so  
that a meaningful measurement can be made. This quick start setup section is intended to cater for the needs of  
most users.  
In section 6, the manual discusses in more detail the human machine interface and how the system is  
programmed.  
In section 7, all of the system’s parameters are discussed and their function detailed. Sections 6.0 and 7.0 are  
primarily intended for the more advanced user who needs to tune the system to meet an unusual application.  
In section 8, the manual discusses in detail the mode of operation of some of the key system elements. This  
section is intended for the most advanced user.  
Page 6  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Finally, sections 9 to 13 cover maintenance, troubleshooting, programming chart, technical specifications and  
dimension drawings relevant to using the MSL600 system.  
1.3 Important MSL600 features  
The MSL600 system incorporates several unique design features which are intended to promote trouble free  
operation, give a degree of installation flexibility, and allow ease of installation.  
1.3.1 Human Machine Interface  
In common with other Mobrey Measurement control units, the MSL600 makes use of the Mobrey Measurement  
Human Machine Interface (HMI). The HMI reflects comments and suggestions received about the need to be  
easy and intuitive to use. The intention is that you should be able to program and interrogate the system using the  
integral membrane keypad and Liquid Crystal Display (LCD) without the need for regular reference to this manual.  
For the more experienced user, the HMI also facilitates rapid navigation of the menu structure to system parameters.  
1.3.2 Self-cleaning  
One of the most important features of the MSL600 is its transducer self-cleaning facility.  
In the application for which the system is designed, the transducer is normally mounted in a relatively hostile  
environment. In this environment, the likelihood of the transducer becoming coated or otherwise fouled is  
relatively high. A fouled transducer is far less efficient at transmitting sonar pulses into the supernatant. Without  
the ability to automatically clean itself, the transducer maintenance cycle would need to be more regular, and thus  
increase the life cost of the system.  
Experience suggests that any moving mechanical cleaning devices are themselves prone to fouling. It is for this  
reason that the MSL600 uses an air purge cleaning function. Extensive experimental results show that this  
method is extremely effective in keeping the face of the transducer free from any coating growth or build-up of  
floating debris.  
The cleaning cycle is optimised for maximum efficiency. However, you can manually initiate a cleaning cycle or  
override this feature by turning it off.  
1.3.3 Mounting bracket  
Most clarifier tanks have railings on the walkway, rotating or moving bridge or walkway. It is recommended that  
the MSL600 be mounted on these railings. The MSL600 system is supplied with a purpose designed mounting  
bracket. This bracket design has been optimised to fit most designs of railing. This is intended to provide  
alignment and a stable platform for the transducer and control unit.  
The transducer and mounting bracket, collectively known as an MSL603, are intended to be fitted to the clarifier  
before the MSL600 control unit is attached to them. This allows mechanical adjustment and fitting without the  
need to worry about the electronics in the enclosure.  
The transducer mounting arrangement is hinged so that the transducer can be lifted out of the water, using the  
chain provided, for ease of maintenance (in most cases this will not be necessary because the transducer is self-  
cleaning). When installed, the transducer front face should be continually immersed in water to a depth of  
approximately 75mm (3 inches). The MSL600 mounting bracket should allow sufficient adjustment for this in  
most cases. Extensions and extra tubes are readily available from a number of sources to allow the mounting to  
be modified – contact Mobrey Measurement Sales for assistance (see section 3.3.3 for other sources).  
Note:  
The MSL603 transducer can also be supplied without mounting hardware and is supplied complete with  
10 metres (33 feet) of connecting cable and air hose for the self-cleaning system. This allows the installer to  
provide their own mounting arrangements using suitable 25mm (1 inch) pipe or conduit. This arrangement is  
normally supplied for fixed bridges or enclosed tanks where a pivoting sensor is not required.  
Page 7  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
1.4 As a system  
Figure (1) shows the architecture of the complete MSL600 system and where each component is intended to be  
used. Install the MSL603 transducer and mounting bracket on the rotating bridge or fixed walkway over the  
clarifier tank. Install the MSL600 control unit on the mounting bracket.  
Figure (1): MSL600 system architecture  
Location  
Fixed or rotating bridge  
Location  
Control room  
PLC/SCADA  
3 relay  
outputs  
RS232  
4-20mA  
output  
MSL600 - Standalone Bridge Mount Unit  
PC or  
Laptop  
computer  
MSL603 Transducer  
Page 8  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
2. Application planning  
The following section discusses a few practical considerations when planning an installation.  
2.1 Circular clarifiers  
Circular clarifiers are very common and can come with rotating or static bridges over them.  
2.1.1 Rotating bridge  
If the transducer is mounted on a rotating bridge then it should be positioned on the leading edge of the bridge,  
see Figure (2). This places it ahead of any bow wave in the sludge blanket which may be created by trailing sub  
surface scrappers that would otherwise give rise to a false indication of the blanket level.  
Ideally the transducer should be mounted between 1/3 and 2/3 of the way along from the outer (wall) edge of the  
settlement tank (i.e. 1/3 to 2/3 of the radius from the inside of the tank wall).  
Care should be taken to ensure that the transducer is mounted over an undisturbed section of the tank, i.e. not  
too close to the tank inlet or tank wall, and away from columns of rising gas bubbles. All of these factors can  
result in false sonar echoes being received. It is recommended that the transducer be mounted at least  
1m (3.3 feet) from any such structures.  
If a scum removing skimmer is present then the transducer should be mounted behind this.  
When locating the transducer the user must ensure that there are no permanent underwater obstructions below  
the transducer, as these will give false sonar echoes and disrupt the signal. It is recommended that the  
transducer be mounted at least 1m (3.3 feet) from any such structures.  
Ensure that the transducer does not come into contact or collide with any scum boards, weirs or other surface  
obstructions as the bridge rotates.  
Figure (2): Circular clarifiers – Rotating bridge  
Approximate  
MSL600  
mounting  
position  
Page 9  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
2.1.2 Static bridge  
The transducer mounting arrangement is designed to lift out of the water if it is mounted on a fixed bridge when a  
moving scraper passes underneath (e.g. on a picket fence thickener). Ideally, the transducer should be mounted  
1/3 to 2/3 of the way along from the outer (wall) edge of the settlement tank (i.e. 1/3 to 2/3 of the radius from the  
inside of the tank wall).  
If the transducer is mounted on a static bridge then it should be positioned on the trailing edge of the bridge, see  
Figure (3). This gives the hinge mechanism maximum clearance from the bridge structure.  
Ensure the transducer guard is facing towards the moving sweeper. The guard and hinge mechanism can be  
angled slightly to meet the rotating parts at a normal incidence. This avoids the transducer guard sliding  
sideways along the rotating part as it is lifted.  
Always check that the parts sliding over each other will not become entangled or locked together. The rotating  
mechanism on most bridges is strong enough to bend the mounting bracket if this should happen.  
It is strongly recommended that a few uneventful rotations be observed before installation is completed.  
Figure (3): Circular clarifiers - Static bridge  
2.2 Rectangular clarifiers  
As with a rotating bridge and a circular tank, the transducer should be mounted from the leading edge of the  
bridge to avoid false level readings from the disturbed bow wave in the sludge blanket as the bridge scrapes  
sludge into the hopper at the end of the clarifier.  
The considerations detailed in section 2.1 for rotating clarifiers should all be considered as appropriate for a  
rectangular clarifier.  
Figure (4): Rectangular clarifiers  
Page 10  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
3. Installation  
The following section discusses installation considerations in more detail.  
3.1 Preliminary checks  
Carefully unpack the MSL600 control unit, transducer, and mounting bracket arrangement from their packaging.  
Check that there is no visible damage to any of the packed parts, paying particular attention to the transducer and  
transducer cables, and the membrane keypad and display area on the MSL600.  
Contained in the packaging should be the following:  
Pack one  
1 x MSL600 bridge mounted unit, with compressor housing containing the air compressor for self-cleaning on  
a metal mounting plate (pre-assembled).  
1 x MSL600 manual.  
Pack two  
1 x transducer assembly, and bridge mounting kit (including tool kit).  
(Optional – MSL603 transducer only with 10 metres of cable and air hose)  
3.2 Location  
Determine the optimum location for installation of the MSL600 following the hints and tips given in section 2,  
Application planning.  
3.3 Mounting bracket attachment  
The mounting bracket is specifically designed for mounting on the centre rail of the safety railing on the bridge of  
any settling tank, see Figure (5). The rail can be any diameter up to 52mm (2 inches).  
The bracket is also clamped to the bridge kicking board or similar supporting frame.  
Adjustments can be made for different bridge heights, and the bracket can be angled to miss obstructions.  
An extension arm can be added to the main support tube to extend the adjustment of the bracket further, if required.  
Most adjustments are made by hexagon key and spanner, included in the supplied bridge mounting kit.  
The transducer arm hangs vertically from a pivot and can be swung out of the water for cleaning and inspection.  
WARNING!  
The transducer is a sensitive instrument and care must be taken to prevent unnecessary impact or strain on it during installation.  
3.3.1 Bridge preparation  
The bracket should be prepared and initial adjustments made off the bridge. If any obstructions are present in the  
installation area, the unit should be set up accordingly. This will greatly simplify any adjustments required during  
mounting of the unit on the bridge. The cable and hose from the transducer should be handled with care to  
prevent any sharp bending, especially in the area where they exit the transducer arm.  
Check there is sufficient room between the top rail, centre rail, and any other structure for the control box to be  
fitted. The space required is 430mm (17 inches) high and 360mm (14 inches) wide [see Figure (5)].  
Measure the distance from the water surface to the centre rail of the safety railing (dimension A).  
Measure the distance from the centre rail to the kicking board (dimension B) or similar structure.  
Page 11  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
With the bracket on the ground adjust the pivot tube up or down the main support tube until the distance between  
the angle bracket and midpoint of the transducer is dimension A. Adjust the clamping bracket up or down the  
main support tube to dimension B so it will be just clear of the final clamping position.  
If the clamp is higher than the pivot tube this will need to be removed and reassembled in reverse order (view X).  
If dimension A is too large and cannot be achieved, remove the pivot tube assembly, screw on the extension tube  
and refit the pivot tube (view Y). If the pivot arm is to be set at an angle or set to the opposite hand, this should  
be done at this stage.  
Adjust the transducer guard so that it is at 90° to the pivot arm, projecting under the pivot arm and approximately  
25mm (1 inch) below the bottom of the transducer.  
If necessary move the chain attachment clamps to positions convenient for swinging the transducer out of the  
water. Adjust the chain so that it is slightly slack with the unit fully extended and any excess chain is hanging on  
the main support tube and not the transducer arm.  
The cable and air hose can now be attached to the bottom of the main support tube with the cable ties provided.  
The cable and hose must make a 360° loop between transducer tube and main support tube to allow for flexing  
when the arm is lifted. Move the transducer arm up and down and check that the cable and hose move freely  
without excessive strain.  
Before installing the unit on the bridge check that all the fittings associated with pivot tube are securely tightened,  
including those which have not been adjusted, as these are often difficult to reach later.  
3.3.2 Installing the bracket on the bridge  
Before carrying the unit on to the bridge, swing the transducer arm into the up position and attach it to the main  
support tube with the chain. This makes the unit more compact and easier to manage. Lift the unit over the  
handrail and hook it on to the horizontal centre tube of the rail. Release the rail clamp and push it up firmly under  
the rail. While pushing on the barrel of the rail clamp (not the lug) retighten the clamping screw. This will  
ensure a tight fit against the rail.  
Loosen the clamping bracket assembly, attach it to the kicking board or similar structure and retighten. The  
studding allows the main support tube to be adjusted approximately to the vertical position. In some instances  
one or both nuts between the clamps will need to be removed. Tighten all fixings.  
Lower the transducer arm carefully into the water and check the water surface is approximately in line with the top  
of the parallel portion of the transducer and it is clear of obstructions. Adjust the pivot arm height and angle as  
necessary. It is recommended the unit be removed from the bridge to make these fine adjustments. Ensure the  
cable and air hose still move freely without excessive strain when the transducer is raised and lowered.  
Check that the transducer arm is hanging vertically. The transducer guard also functions as a balance arm.  
To adjust, swing the arm up and loosen the transducer guard. Move the guard backwards or forwards as  
appropriate and retighten. Repeat until the arm hangs vertically.  
When the unit is installed and functioning correctly check all fittings are securely tightened, including those which  
have not been adjusted.  
3.3.3 Attaching the MSL600  
The MSL600 and compressor box come attached to a back plate complete with mounting lug. Check the  
clamping screw of the mounting lug is clear of the inside face and slide the complete unit onto the top of the main  
support tube. Orientate the unit to the correct position and tighten the clamping screw.  
Run the cable and hose up to the control unit avoiding sharp bends and flattening of the hose. Plug the air hose  
onto the air connector on the bottom of the compressor box. The unit is now ready for wiring.  
Additional fittings for MSL bracket (UK only) can be obtained from:  
Alvin Products Limited, Knight Works, 10-12 Hampton Street, London, SE1 6SN  
Tel. 020 7708 2004, Fax. 020 7708 3044, Web site: www.alvin.net  
Fittings are ALVIN ‘KEY’ CLAMPS (Size 5 - 26.9mm dia.) Similar fittings are also available from other manufacturers.  
Note: Socket head screws require 1/4” A/F Hex key clamp bracket screws require 17mm A/F spanner.  
Page 12  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Figure (5): MSL600 mounting  
Page 13  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
3.4 Transducer connections  
The MSL600 is housed in an ABS enclosure rated to IP66. The lower section of the housing is for cable  
connections and the upper part has the LCD and keypad controls.  
It is not necessary, or advisable, to remove the lid of the upper part of the enclosure. There are no user  
serviceable parts inside.  
All field wiring connections are accessible by removing the lower lid, which is secured by four screws. Inside the  
terminal area, all connections are made using screw terminals. All terminal blocks are suitable for wires 0.5mm2 to  
2.5mm2 (26 to 12 AWG). Insulation should be stripped back 7.0mm (0.25 inches).  
The transducer cable comprises of five wires, see Figure (6), the connections for which are as follows:  
• White wire  
• Black wire  
• Yellow wire  
• Red wire  
-
-
-
-
-
Transducer signal wire. This should be connected to the terminal  
block marked ‘SENSOR’ and ‘SIG’.  
Transducer 0V wire. This should be connected to the terminal block  
marked ‘SENSOR’ and ‘0V’.  
Transducer screen wire. This should be connected to the terminal  
block marked ‘SENSOR’ and ‘SCN’.  
Temperature compensation positive wire. This should be connected  
to the terminal block marked ‘TEMP’ and ‘IN’  
• Brown wire  
Temperature compensation 0V wire. This should be connected to  
the terminal block marked ‘TEMP’ and ‘0V’.  
Figure (6): Transducer cable wiring  
All connections to the transducer are intended to be made via the first M20 cable gland (fitted) on the left-hand  
side, at the bottom of the MSL600 enclosure.  
3.5 Power and other electrical connections  
(See also section (i), safety precautions)  
It is the responsibility of the installer to observe all local regulations and approval requirements, and to use cable  
to suit the environmental requirements of the particular application.  
Prior to applying power to the unit ensure that the two voltage selection switches are set to the appropriate  
voltage for the installation.  
In the event of a fuse needing replacement the user must ensure that the mains input fuse (F1) has a rating of  
200mA (F) and the cleaning compressor (F2) has a rating of 1A(T).  
Page 14  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
The diagram below, Figure (7) shows the layout of external connection terminals of the MSL600 with the lower  
terminal housing cover removed. Table (A) gives a description of each.  
Note:  
When wiring of the unit is finished, ensure that the terminal housing cover is replaced the correct way up, i.e. with  
the bevelled edge uppermost otherwise the IP rating of the enclosure may be compromised.  
Figure (7): External connection terminals  
SENSOR TEMP  
(see note 1)  
SIG  
0V  
SCN  
IN  
Transducer sonar signal (white)  
Transducer zero volts (black)  
Transducer screen (yellow)  
Temperature compensation signal (red)  
Temperature zero volts (brown)  
0V  
DIGITAL INPUT (see note 2)  
1
Digital input signal  
0V  
Digital input zero volts  
CURRENT OUT ISOLATED  
0V  
Current output zero  
Io  
Current out  
24V  
24V source for current output (Not normally used)  
RELAY 1 (de-energised state)  
NO  
C
Normally open  
Common  
NC  
Normally closed  
RELAY 2 (de-energised state)  
NO  
C
Normally open  
Common  
NC  
Normally closed  
RELAY 3 (de-energised state)  
NO  
C
Normally open  
Common  
NC  
Normally closed  
COMPRESSOR (Factory wired)  
115V  
C
230V  
(White)  
(Purple)  
(Orange)  
115V supply for the cleaning compressor  
Common for the cleaning compressor  
230V supply for the cleaning compressor  
MAINS  
L
N
E
Live terminal for mains supply  
Neutral terminal for mains supply  
Earth terminal for mains supply  
Table (A): Connection descriptions reading from left to right (all via M20 cable glands)  
Page 15  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
3.6 Cable extension  
The transducer is connected using ALPHA XTRA-GUARD4 P/N45272. The standard cable length is 10 metres.  
This cable comprises of two twisted pairs with an overall screen and drain. The brown and red wires from the  
transducer should be connected to one twisted pair. The black and white wire from the transducer should be  
connected to the other twisted pair. The yellow from the transducer should be connected to the drain wire which  
must be terminated at the screen (SCN) terminal on the PCB.  
Fitting instructions for extending the MSL603 transducer cable are in section 14.  
Note 1:  
The standard 10 metres of cable should be sufficient for most installations. The maximum recommended  
additional extension is 20m. Use only cable conforming to the specification given above and ensure any  
connections are made using high grade screened connectors. For suitable specification connectors refer to  
Mobrey Measurement customer support. It is the responsibility of the installer to ensure that any extension to the  
cable must be suitable for its working environment.  
Note 2:  
The digital input, if used must be connected to switch relay contacts which are insulated to IEC6010 category III  
(4kV impulse) with no exposed live parts.  
Page 16  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
4. Programming  
The following sections introduce the main display and use of the keypad (MSL600 only) for programming the  
MSL600. Password protection to prevent unauthorized access is also discussed.  
4.1 Display  
The display is a 240 x 128 dot matrix LCD module with full graphics capability and LED back light. The LCD is  
split into four parts, see Figure (8).  
Figure (8): The LCD display layout  
Upper left  
In the upper left of the display is an icon representing the transducer and the unit tag  
number. The tag number is user programmable via the HMI.  
Upper right  
The HMI information is displayed in the upper right of the display. The HMI uses 4 lines  
x 20 characters with each character 7 x 5 dots. In normal operation, the actual blanket  
level is displayed here.  
Lower left  
The lower left of the display shows the sonar echo profile from which the blanket position  
is determined.  
Lower right  
The lower right of the display shows the blanket level trend at minute intervals over the  
last hour.  
When the display is in the normal mode, trending is active and the  
and keys enable the user to view the last  
12 hours of data, an hour at a time backwards and forwards respectively. The views are labelled with their start  
and finish times. The sonar echo profile recorded at the corresponding start time is also displayed.  
After reaching the oldest data the key is inoperative. Where no data has been recorded there is a gap in the  
trend line. A zero value is represented by a line a single-pixel thick. Pressing Esc returns to the real time normal  
display.  
Note: Do not confuse this trending with data logging which is discussed in more detail later.  
The LCD has a back light for operator convenience. This has one of 3 modes selectable using the HMI:  
On permanently unless internal temperature too high, in which case automatically off.  
Off permanently unless internal temperature is too low, in which case automatically on.  
Auto - i.e. off until keypad is actuated, in which case on and stay on for, typically, 5 minutes - on for only 10  
seconds if internal temperature too high.  
The LCD on the MSL600 is supplemented by a single red LED which indicates the health of the unit. The LED  
flashes every 2 seconds (½Hz) to indicate normal operation, whilst a steady illumination or no illumination  
indicates a problem.  
Page 17  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
4.2 Contrast (viewing angle) control  
When the system is making measurements in normal mode the screen contrast or viewing angle can be adjusted.  
Whilst holding down the Esc key press either the or key  
Esc and - increases (darkens) the contrast and Esc and decreases (lightens) the contrast.  
4.3 Keypad and Menu Navigation  
Data entry and interrogation is normally achieved using the integral membrane keypad on the MSL600 front  
panel, see Figure (9).  
Figure (9): Keypad layout  
The keypad comprises 6 keys:  
Cursor keys (ꢂꢄꢃꢄ ꢄꢁ)  
Enter key ()  
Escape key (Esc)  
The four arrow keys allow navigation around the HMI menu structure and the Esc and keys allow movement  
from one menu level to the next. Each time a key is pressed an audible “beep” is heard. This “beep” can be  
turned off via the HMI if required.  
To access the main menu (from the normal display, see section 4.1) press .  
To access a menu option, highlight the option using the ꢂꢄꢃ keys and press .  
To change a parameter the padlock in the on line/off line menu must be open. This is done by highlighting “Go off  
Line” in the main menu and pressing . Press again and the padlock will open. Press again and the padlock  
will close.  
By pressing Esc repeatedly, the screen will always return to the normal display. Alternatively, pressing and  
holding Esc for a few seconds will result in jumping straight back to the Main Menu screen.  
If any key other than Esc is held pressed for more than 1 second then it auto repeats. This is particularly useful for  
fast scrolling through parameters. Although the display does not show every parameter whilst fast scrolling (it is  
only refreshed every 500ms), the key beep (if enabled) is actuated for each parameter.  
Movement through the menu structure using the arrows is shown by the titles being highlighted and flashing, i.e.  
reversed to showing clear letters on a black background and vice versa. Pressing with the title highlighted  
enters that part of the menu.  
Page 18  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
4.4 Security  
The HMI includes a password system which may be used to protect parameters from unauthorised changes and  
also to prevent the system from being switched between On and Off-line mode.  
The password is in the form of a 4-digit code (or PIN). When the user has entered the correct PIN then the  
password is said to be open (else closed). The PIN is a 4-digit code, value 0000 to 9999.  
Once the password is open then all parameters may be edited.  
A PIN of 0000 means that the password is disabled, i.e. no password is required to edit parameters.  
Examining the PIN locally shows “- - - -” unless set to 0000.  
When prompting for entering of PIN, the display shows “- - - -”.  
A PIN is set or entered by scrolling each of the 4 digits using the  
arrows to select the value for each digit.  
and arrows to select the digit and and ꢃ  
No PIN is required to navigate the menus or to simply examine parameter values.  
Attempting to change a parameter value prompts for the entering of the PIN (if it is not already open). If the  
parameter affects outputs, and if On-line, then after entering the PIN the user is offered go Off-line.  
If the password is open then the main menu offers the option “Cancel Password” as the default (highest priority)  
option. Closing the password does not affect the On line/Off-line status.  
The password is automatically closed after 5 minutes without any key press; this does not affect the  
On line/Off-line status.  
4.5 On-line/Off-line  
This feature allows the MSL600 outputs, i.e. its relays and current output to be frozen. Also, when On-line, the  
editing of all parameters which may affect these outputs is inhibited.  
Off-line inhibits relays and current output.  
On-line inhibits the editing of all parameters that may affect the outputs. These include relay, current output and  
alarm parameters.  
The On line/Off-line state is shown by the padlock symbol at the top left-hand corner of the HMI display (padlock  
closed represents On-line).  
Go On line/Off-line by selecting the appropriate item in the main menu. As the mode is toggled, a large image of  
the Padlock symbol opens and closes. Attempting to edit any parameter can only be performed with the unit  
Off-line.  
If the system password is closed then the system will prompt for a password, once correctly entered then it  
changes as requested.  
NOTE: There is no time-out on On-line or Off-line.  
Page 19  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
5. Quick start parameters  
The system leaves the factory with default values in all the parameters. These values, after installation, allow  
immediate operation without any further programming. However, it is recommended for best operation that the  
following parameters should be programmed.  
In order to get meaningful measurements from the MSL600 in the minimum time only the following parameters  
need to be adjusted.  
5.1 Tank depth - Bottom reference  
An accurate knowledge of the tank depth is a key parameter for the system.  
The tank depth is the distance from the front face of the transducer to the bottom of the tank directly under the  
transducer [see Figure (10)]. Where the tank bottom slopes, as is often the case, the sludge blanket level, Xm  
indicated by the system is therefore relative to this zero reference level.  
Tank depth  
Sludge blanket interface Xm  
0m tank depth  
Figure (10): Tank depth parameter  
The maximum tank depth that the system will measure is 7.000m (23.00 feet), the minimum is 1.000m (3.3 feet),  
do not confuse this with the transducer blanking distance which is discussed elsewhere and is 0.3m (1 foot) by  
default.  
The tank depth value is stored in the system and used in subsequent calculations. The factory default is 7.000m  
(23.00 feet), corresponding to the maximum depth of tank for which the system is specified.  
When the unit is powered on for the first time the system makes measurements using this default. It will be  
obvious that until the user enters a measured value certain functions, such as current output and displayed  
blanket level will not be correct for the installation.  
Page 20  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
5.2 Determination of tank depth  
The ultimate blanket level measurement accuracy depends upon the accuracy of the value entered for the tank  
depth. It is always recommended that this be determined for every installation by the user using a measuring rod  
or similar. Alternatively, the user can obtain a workable estimate of the tank depth by adjusting the tank depth  
value Off line using the HMI and positioning the bottom echo at the bottom of the profile display.  
This only works if a bottom echo is visible and the user must be sure that the echo he is positioning does actually  
correspond to the tank bottom. To do this, follow the procedure below:  
1.  
From the normal display, press .  
2.  
3.  
4.  
The main menu will appear on the upper right of the display.  
Highlight the Go Off line menu option and press . The padlock will open.  
Press Esc to return to the main menu.  
5.  
6.  
Use the and keys highlight the INSTALLATION menu option and press .  
Highlight the Tank depth option and press .  
7.  
To edit the depth press .  
8.  
Use the and keys to increment and decrement the highlighted digit.  
9.  
Use the  
and keys to move from one digit to the next.  
10.  
11.  
When editing has finished press to save the value.  
The large echo (in most cases this represents the bottom of the tank that the transducer is positioned over)  
on the lower left display will move.  
12.  
13.  
14.  
Repeat steps 7 to 11 as necessary.  
When this echo appears at the bottom of the display the tank depth is set.  
ESC to return to main menu.  
Please note that to avoid confusing echoes this procedure should be carried out when there is no significant  
sludge blanket in the tank.  
5.3 Transducer self-cleaning  
The transducer self-cleaning is pre-programmed for optimal performance. However, the cleaning cycle can be  
changed by following the procedure set out below.  
In order to access the transducer cleaning parameters follow the following programming sequence:  
1. Press to access the main menu.  
2. The main menu will appear on the upper right of the display.  
3. Highlight the Go Off line menu option and press . The padlock will open.  
4. Press Esc to return to the main menu.  
5. Use the and keys to highlight the SETUP menu option and press .  
6. Highlight the DUTY (mode) menu option and press .  
7. Highlight the CLEANING menu option and press .  
8. Highlight the Start On menu option and press .  
9. Use the and keys to highlight the required option and press .  
Three options are available;  
Auto Clean - This is the default option and means that the MSL600 will automatically carry out a cleaning  
cycle for 10 seconds on the hour every hour.  
Manual 5s - This allows the user to manually activate a 5 second cleaning cycle at any time after which the  
cycle returns to its previous setting (note, the unit must be on line to carry out this process).  
Off - The unit will not perform any cleaning cycles.  
Page 21  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
5.4 mA current output parameters  
The operation of the current output is programmed by four parameters and is always controlled by the sludge  
blanket level.  
The current output parameters are found in SETUP – OUTPUT – CURRENT OUTPUT.  
The parameters are as follows:  
Low range val (Lower range value)  
This parameter allows the user to reference the programmed minimum current output (0 or 4mA) to any point  
in the programmed blanket level measurement range.  
The default condition is that the programmed minimum current corresponds to 0m (0 feet), the tank bottom.  
Up range val (Upper range value)  
This parameter allows the user to reference the maximum 20mA current output to any point in the  
programmed blanket level measurement range.  
The default condition is that 20mA corresponds automatically to the programmed tank depth parameter less  
the top blanking distance. This level is programmed by the tank depth parameter which by default is set to be  
7.000m (23.00 feet). The 20mA level for default settings therefore corresponds to a sludge blanket level of  
6.7m (22.1 feet)  
Alarm action  
This parameter is selectable from a list and determines the action to be taken by the current output under  
alarm conditions.  
The allowed actions are:  
Go to 3.6mA  
Go to 21mA  
Hold last reading  
0/4-20mA (0-20mA or 4-20mA setting)  
This parameter sets the current output range from a list to be either 0-20 or 4-20mA.  
5.5 Current output adjust  
The current output is calibrated in the factory and should not require any adjustment.  
However, if required, it is possible to adjust the 4mA and 20mA points using a calibrated meter. This is done by  
following the procedure detailed below:  
1. Connect a milliammeter to the terminal block marked CURRENT OUT ISOLATED between the 0V and the IO  
connections.  
2. Put the system off line so that the ‘Go Off line?’ padlock is open.  
3. Access the SETUP – SYSTEM – TEST – CURRENT OUTPUT menu.  
4. Select either the “4mA out adjust” or the “20mA out adjust” and press .  
5. Read the actual current on the calibrated meter.  
6. Enter this value in the chosen parameter and press .  
7. Check that the actual current is now exactly 4mA or 20mA.  
For diagnostic purposes the current output can be driven to any value between 4mA and 20mA by accessing  
SETUP – SYSTEM – TEST – CURRENT OUTPUT – Set current.  
With a suitable meter connected to the current output terminals a value can programmed on the control unit and  
the same value will appear on the meter.  
This programmed current will remain until the ‘Go On line?’ padlock is closed.  
Page 22  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
5.6 Relay parameters  
The MSL600 offers various options for operating its relays. There are 2 relays that are programmable to different  
modes, these modes are:  
Alarm  
Set point operation  
De-sludge  
On  
Off  
None  
Fault  
Slg Lev Limits (Sludge Level Limits)  
The mode of operation is selected through the SETUP – OUTPUT – RELAY – Relay Mode menu.  
The default mode for Relay 1 is set point operation and for Relay 2 default mode is alarm. Relay 3 is permanently  
assigned to fault mode (see section 7.6 for further details).  
5.7 Alarm  
There are six different alarm conditions in the SETUP - OUTPUT - ALARM menu. Each alarm condition can be  
set to operate a relay, or drive the current output, or both, or neither to the following states:  
Current output – 3.6mA, 21mA or Hold as defined in “Alarm action” in the CURRENT OUTPUT menu.  
Relay outputs – The relays energise in the alarm condition if they are programmed in Alarm mode.  
The relays or current output must be set up for alarm action for this function to operate. The available alarm  
actions are shown in the list below:  
Out of limits  
Current saturated  
Memory filling  
Digital Input  
Max Retries  
Xdr tilted  
Dirty supernatant  
Noise Alarm  
5.8 Transducer out-of-water time  
Certain installations make use of a picket fence thickener or a variety of rotating scrappers and scum boards.  
These rotating arms at the surface of the liquid will periodically lift the articulated transducer out of the liquid as  
they sweep by.  
The transducer includes a (non-mercury) mechanical tilt switch. This is used to indicate when the transducer is  
being tilted and lifted out of the water. The MSL600 uses this information to determine whether valid sonar echo  
profile data is being received. If not then measurement will pause and outputs will be held until the arm is vertical  
again.  
When the transducer is tilted a timer is started. The time for which the transducer has been tilted is compared to  
a maximum allowed value, programmed by the user. If this time is exceeded then an alarm condition can be  
flagged. It is possible to program an alarm relay to respond to this flag. This is intended to detect problems if the  
fence should stop under the transducer, etc. The time for which the transducer has been tilted is available as a  
Monitor readings parameter (D833).  
When the arm returns to the vertical the timer is re-set to zero and if allocated the alarm cancelled.  
If the transducer has been out of water for greater than the time allowed then its temperature may be significantly  
different to that of the supernatant.  
Page 23  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
The transducer may take up to 1 hour to reach thermal equilibrium. Therefore, it may take some time to restore  
accurate blanket level readings. When the arm tilts out of the supernatant the MSL600 holds the last supernatant  
temperature reading from the transducer. When the transducer falls back into the supernatant the MSL600 starts  
to make measurements again.  
When the MSL600 measures the supernatant temperature at the transducer, as long as the temperature is within  
the programmed normal limits for a supernatant then the system uses this measured temperature for speed of  
sound compensation.  
If the measured temperature is outside of these limits then the MSL600 uses the last held temperature reading.  
This state will continue until a valid temperature reading is again obtained from the transducer in the supernatant.  
The upper and lower temperature points are programmable as HMI Engineering parameters. The default values  
are -5 to +40°C (23 to 104 deg F). The lower temperature should always be less than the upper and valid entries  
should be limited to temperatures between -40°C and +85°C (-40 to 185 deg F).  
Because the tilt switch is sensitive to vibration as well as angle it is de-bounced in software. An engineering  
parameter exists in the HMI to allow this function to be turned on and off, in the case of for example a particularly  
vibration prone bridge.  
5.9 Digital input  
Parameter P340 is used to assign the status of the digital input to an alarm relay if desired. This allows the user  
to stop measurement whilst the blanket is known to be disturbed and meaningful results would not be obtained.  
E.g. during high in-flow or when top water level falls below the transducer face and normal measurements can’t  
be performed.  
When the digital input is active all measurements continue as normal and the LED still flashes. The sonar pulse  
echo display continues to update with live data. However, the blanket level is held at its last value. The trend  
graph continues to update, relays and current output remain active, and logging continues using the held blanket  
level.  
Digital input active means either a short across the terminals, i.e. from a contact closure or a PLC driving low, i.e.  
going to ‘0’.  
Page 24  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
6. Detailed operation  
The following sections go into programming the system in more detail.  
6.1 The menu structure  
From the normal display, pressing the key will enter the menu system, see Figure (11). A full menu structure is  
shown in section 11.  
Main menu item  
Go On line ?  
INSTALLATION  
SETUP  
Tank Depth  
Xdr Tilt Time  
Tag No.  
Description  
DUTY (Mode)  
CLEANING  
DE-SLUDGE  
Digital i/p action  
OUTPUT  
CURRENT OUTPUT  
RELAY  
ALARM  
FAULT  
DISPLAY  
LOGGING  
ENGINEERING  
SYSTEM  
TEST  
COMMS  
SETTINGS  
PIN  
FIXED  
MONITOR  
DIRECT  
READINGS  
DIAGNOSTICS  
Pxxx  
Dxxx  
Figure (11): Menu structure  
The top-level menu contains the list of available menu items:  
Menu Item  
Description  
Go On-line (Go off-line)  
INSTALLATION  
SETUP  
Allows programming when off line  
Installation parameters  
Setup parameters  
Diagnostic and performance type parameters  
Allows direct access to parameters  
MONITOR  
DIRECT  
Page 25  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
To move up and down the list, use the and arrows until the required menu item is highlighted, then use the ꢅ  
key to enter that menu option.  
The presence of additional menu items off the screen is indicated by up and down arrows on the right hand side  
of the display.  
The next level of the menu is then displayed and the required option can again be selected as above.  
6.2 Parameter editing  
Once the required parameter is displayed, select it and press the key (note that menu groups are in upper case  
letters, parameters are in upper and lower case).  
Note also that there are two parameter types:  
Read/Write - these parameters are normally preceded by a “P” - e.g. P200. They may be modified by the user.  
Read Only - these parameters are normally preceded by a “D” - e.g. D800. They are either fixed within the  
MSL600 or produced by data processing and thus may not be modified by the user. Examples are Software  
Revision and Serial Number.  
The desired parameter may now be modified. Numeric values are edited one digit at a time, the  
select each digit by highlighting them and the and keys increment and decrement each digit.  
and keys  
Alternatively, some parameters are in the form of a list. These are edited in a similar way, selecting with the ꢅ  
key and using the and keys to scroll through the list.  
When the displayed value is correct, press the key to store the value.  
6.3 Scrolling  
When a parameter is displayed but no digit is highlighted, the and keys will scroll to the next parameter in  
numeric order. This provides an alternative method of accessing parameters without using the menu facility.  
6.4 Direct access  
It is possible to access the parameters directly from the main menu if the parameter number is known.  
From the normal display press the key to display the main menu on the top right hand side of the display.  
Use the arrow keys to scroll down until the menu option DIRECT is highlighted and press the key.  
Highlight either Pxxx or Dxxx  
(Pxxx are user configurable parameters and Dxxx are non-configurable diagnostic parameters).  
Enter the parameter number to be edited and press .  
If an invalid number is entered then the next lowest parameter is displayed.  
Page 26  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7. Application parameters  
The following section details each parameter.  
7.1 Main menu parameters  
The following functions are available at the top level of the menu structure.  
Note: A full menu structure is shown in section 11.  
7.1.1 Cancel password  
This is a dynamic parameter; it only appears when password has been opened. This parameter allows the user  
to cancel the need for password entry before access to parameter editing is allowed.  
7.1.2 Go Online/Offline  
This is a dynamic parameter; it changes according to whether the system is online or offline. The padlock icon  
will be displayed in a corresponding open or closed state.  
7.2 Installation parameters  
The following parameters are intended primarily for use during system installation.  
7.2.1 Tank Depth – P101  
The tank depth is the distance from the front face of the transducer to the bottom of the tank directly under the  
transducer and is the user programmable range for zero blanket level.  
Parameter values (Metric)  
Parameter values (Imperial)  
Default  
7.000m  
Min  
1.000m  
Max  
7.000m  
Default  
23.00 ft  
Min  
3.30 ft  
Max  
23.00 ft  
7.2.2 Xdr Tilt Time – P103  
This is the maximum time for which transducer can be out of the water before the system registers a fault.  
The parameter is either disabled by entering a value of zero or programmed with a value in minutes.  
The default is a value of 0 minutes, disabled.  
Parameter values:  
Default  
0 (Disabled)  
Min  
1
Max  
15  
7.2.3 Tag No. – P242  
This is a user defined alpha-numeric parameter. Any string up to 8 characters long may be entered using the keypad.  
This will usually correspond to the instrument’s asset number or some other such identifier on the user’s schedule.  
The following characters are allowed:  
!”#$%&’()*+,-./0123456789:;<=>?@ABCDEFGHIJKLMNOPQRSTUVWXYZ[\]^_  
Parameter values:  
Default  
MSL600  
Min  
-
Max  
-
Page 27  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.2.4 Description – P240  
This is a user defined alpha-numeric parameter. Any string up to 12 characters long may be entered using the  
keypad. This will usually be a description of the application.  
The following characters are allowed:  
!”#$%&’()*+,-./0123456789:;<=>?@ABCDEFGHIJKLMNOPQRSTUVWXYZ[\]^_  
Parameter values:  
Default  
CLARIFIER1  
Min  
-
Max  
-
7.3 De-sludge parameters  
The following parameters relate to the de-sludge function and are found in the setup menu.  
Note that minimum and maximum parameters relating to time are 00:00 and 23:59 respectively. Minimum and  
maximum parameters relating to sludge level are 0.000 to 7.000m (0.00 to 23.00 feet)  
Note: A full menu structure is shown in section 11.  
7.3.1 Start On - P250  
Use this parameter to select how the de-sludge cycle starts.  
The selectable options are:  
None  
Time  
Sludge Level  
The parameter defaults to “None” which means it is not used.  
Parameter values:  
Default  
None  
Min  
-
Max  
-
7.3.2 Stop On - P251  
Use this parameter to select how the de-sludge cycle stops.  
The selectable options are:  
None  
Time  
Sludge Level  
The parameter defaults to "None" which means it is not used.  
Parameter values:  
Default  
None  
Min  
-
Max  
-
Page 28  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.3.3 Stop If - P252  
Use this parameter to select if it is necessary to override the “Stop on” condition.  
The selectable options are:  
Not used  
Sludge Level  
The parameter defaults to none which means it is not used.  
Parameter values:  
Default  
None  
Min  
-
Max  
-
7.3.4 Start Time - P253  
This is the time of the day at which the first de-sludge operation starts. The time is programmed in hours and  
minutes. This parameter is set up in conjunction with the de-sludge Interval P254.  
Parameter values:  
Default  
07:00  
Min  
-
Max  
-
7.3.5 Interval - P254  
The parameter is the interval between de-sludge events.  
After a start time has been programmed, the interval between each de-sludge needs to be programmed.  
For example, if it is required that the de-sludge cycle starts at 7:00am each morning then 07:00 is entered in P253.  
If it is then required that a de-sludge cycle is carried out every hour thereafter, 01:00 is entered in P254.  
Parameter values:  
Default  
01:00  
Min  
-
Max  
-
7.3.6 Max Retries - P257  
This parameter is the maximum number of retries allowed following an unsuccessful de-sludge cycle. If the  
maximum retries is exceeded, and a relay is programmed, and allocated in alarm mode, it can be used to signal  
this fact.  
A retry occurs if the start condition is still present when the stop condition occurs or if a relay maximum run time is  
exceeded and the stop condition has not been reached.  
To prevent a relay from remaining on, the relay minimum off time must be programmed (see P415).  
Parameter values:  
Default  
10  
Min  
0
Max  
250  
Page 29  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.4 Cleaning parameters  
The following parameter relates to the cleaning function.  
Note: A full menu structure is shown in section 11.  
7.4.1 Start On - P260  
Use this parameter to select how the cleaning cycle starts.  
The selectable options are:  
AutoClean  
Manual 5s  
Off  
The default is “AutoClean”.  
7.4.2 Interval - P264  
Use this parameter to programme the interval between cleaning cycles (see also P444 - cleaning duration).  
This parameter is programmed in hours and minutes.  
Default  
1:00  
Min  
0:10  
Max  
1:39  
7.4.3 Cleaning Time - P444  
The duration of the cleaning cycle can be programmed in seconds  
Default  
0:10  
Min  
0:10  
Max  
0:20  
7.5 mA output parameters  
The following parameters are used to program the mA current output.  
7.5.1 Lower Range Val - P400  
This is the sludge blanket level in metres (or feet if Imperial version) for the minimum mA output, either 0 or 4mA  
as programmed using P403.  
Parameter values (Metric)  
Parameter values (Imperial)  
Default  
0.000m  
Min  
0.000m  
Max  
7.000m  
Default  
0.00 ft  
Min  
0.00 ft  
Max  
23.00 ft  
7.5.2 Upper Range Val - P401  
This is the sludge blanket level in metres (or feet if Imperial version) for the maximum mA output.  
This value is by default set to "Auto".  
Parameter values (Metric)  
Parameter values (Imperial)  
Default  
Auto  
Min  
0.000m  
Max  
7.000m  
Default  
Auto  
Min  
0.00 ft  
Max  
23.00 ft  
Note: In the case of the default setting the upper limit is defined as being at the programmed transducer blanking  
distance P623 from the front of the transducer face.  
Page 30  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.5.3 Alarm Action - P402  
This parameter is used to select the desired action which is taken by the mA output when the system is in an  
alarm condition.  
The allowed options are:  
Go to 3.6mA  
Go to 21mA  
Hold (last reading)  
The default action is to go to 3.6mA.  
7.5.4 0/4-20mA - P403  
This parameter is used to select the desired range of the mA output from a list.  
The allowed options are:  
0-20mA  
4-20mA  
The default is 4-20mA.  
Page 31  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.6 Relay parameters  
The following parameters are used to program the 2 available relays RL1 and RL2, which are controlled by the  
sludge blanket level. The mode of relay RL3 is fixed to fault indication.  
Note: A full menu structure is shown in section 11.  
P
RL1  
410  
411  
412  
413  
414  
415  
RL2  
420  
421  
422  
423  
424  
425  
Mode  
On Point  
Off Point  
Min ON  
Max ON  
Min OFF  
Table (B): Relay Parameter numbers  
7.6.1 Relay RL1 mode (P410) and RL2 mode (P420)  
The mode of operation, or function, of the relay can be selected from a list:  
A) Alarm............................................................see page 32  
B) Fault .............................................................see page 33  
C) Set Point.......................................................see page 33  
D) De-sludge.....................................................see page 33  
E) On.................................................................see page 33  
F) Off.................................................................see page 33  
G) None.............................................................see page 33  
H) Slg lev limits (Sludge Level Limits) ...............see page 33  
i) Temp OL (Temperature Over Limits)............see page 33  
7.6.1.1 Alarm mode (relay RL1 and RL2 parameters P540 to 552)  
There are several alarms which can be assigned to a relay. When an alarm condition occurs it may be signalled  
by relay, current, both relay and current, or not at all. Alarm conditions are listed below:  
Out of Limits - P540  
The sludge blanket level is outside the limits set in the relay on and off point parameters  
mA o/p Sat. (Current Saturated) - P541  
The current output is outside the limits set in the current output parameters.  
Memory Filling - P542  
The logging memory is filling. This alarm condition is activated when the remaining memory is less than the  
percentage programmed by the user in ‘Low Mem Alarm’ P593.  
Digital Input - P543  
If the digital input is active then the relay indicates alarms.  
Max Retries - P544  
If at the end of a de-sludge operation the start condition is still present for a programmed number of retries  
then the relay alarms.  
Xdr Tilted - P550  
An alarm can be activated after the transducer has been out of water for a user-programmed length of time.  
Dirty S-nat - P551  
If the supernatant gives a high degree of returned echo (indicating a significant number of suspended  
particles) then an alarm can be activated.  
Noise Alarm - P552  
An alarm is activated if the background noise exceeds the pre-set limit set in parameter P622.  
Page 32  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.6.1.2 Fault mode (relay RL1 and RL2 parameters P560 to P570)  
There are several fault conditions which can be assigned to a relay. Fault conditions may be selected to be  
signalled by relay, current, both relay and current, or not at all.  
Messages describing active faults are automatically written to the lower HMI display.  
When a fault condition occurs, a relay configured in fault mode will de-energise. Fault conditions are listed  
below:  
Memory Fault - P560  
A memory fault occurs if system memory has been corrupted. On occasion the control unit may indicate a  
memory fault when first powered up. This is normal because the unit is automatically loading default  
settings in to the memory. After the first power up this fault message should not occur again. All control  
units are first powered up prior to leaving the factory. If the memory fault message appears after the unit  
has been switched on and off at least once then consult the factory.  
CU Temp Fault - P561  
A fault is indicated if the temperature within the control unit exceeds pre-set limits.  
Xdr Temp Fault - P563  
A fault is indicated if the temperature within the transducer unit exceeds pre-set limits.  
7.6.1.3 Set point mode (relay RL1 and RL2)  
The relays can be operated in set point mode. See also section 7.6.2.  
For example:  
If it is required to turn a pump on using relay 1 when the sludge blanket reaches a depth of 3.5m (11.5 ft), then  
3.5 (11.5) is programmed in to P411 (RL1 on point).  
Note:  
It is advisable that the "On" and "Off" points are always set to different values, nominally 50mm (2 in/0.16ft)  
apart.  
7.6.1.4 De-sludge mode (relay RL1 and RL2)  
The relay can be programmed to operate in de-sludge mode. The de-sludge parameters are described in  
section 7.3 of the manual.  
7.6.1.5 On mode (relay RL1 and RL2)  
The relays can be switched permanently on if required.  
7.6.1.6 Off mode (relay RL1 and RL2)  
The relays can be switched permanently off if required.  
7.6.1.7 None mode (relay RL1 and RL2)  
If the relay mode is set to "None" then the relay remains in its last valid state i.e. if the relay is "On" and the  
mode is changed to "None", the relay remains "On".  
7.6.1.8 Sludge Level Limits mode (relay RL1 and RL2)  
If the relay mode is set to Slg Lev Limits, the relay is energised above the Relay On point. It is also energised  
below the Relay Off point. However, the relay is de-energised in between the "On" and "Off" points.  
7.6.1.9 Temperature Over Limits mode (relay RL1 and RL2)  
If the relay mode is set to Temp OL, the relay is energised above the minimum and maximum control unit  
operating temperatures. The relay is de-energised while temperatures are within the normal operating range.  
Page 33  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.6.2 Relay On and Off Points  
Relay On Point for RL1 (P411) and RL2 (P421)  
This is the sludge blanket level at which the Set Point mode relay turns on i.e. between 0.000 and 7.000m  
(0.00 to 23.00 ft). See also section 7.6.1.3 for related information.  
Relay OFF Point for RL1 (P412) and RL2 (P422)  
This is the sludge blanket level at which the Set Point mode relay turns off i.e. between 0.000 and 7.000m  
(0.00 to 23.00 ft). See also section 7.6.1.3 for related information.  
7.6.3 Relay overrides (Min ON, Max ON, and Min OFF)  
Relay minimum on time (Min ON) for RL1 (P413) and RL2 (P423)  
This is the minimum time for which the relay will remain on in non-alarm or fault modes. This takes priority over  
the maximum on time. It is important to note that this function only operates when the minimum off time is set to a  
non-zero value. This parameter can be set between 00:00 and 99.59 in mm:ss.  
Relay maximum on time Max ON for RL1 (P414) and RL2 (P424)  
This is the maximum time for which the relay will remain on in non-alarm or fault modes. It is important to note  
that this function only operates when the minimum off time is set to a non-zero value. This parameter can be set  
between 00:00 and 99.59 in mm:ss.  
Relay minimum off time Min OFF for RL1 (P415) and RL2 (P425)  
Once the relay has turned off this is the minimum time before the relay will turn on again. If both minimum and  
maximum on times are set to zero (default) then they are not used. This parameter can be set between 00:00 and  
99.59 in mm:ss.  
7.7 Display parameters (HMI)  
7.7.1 HMI upper, middle, and lower display options  
The top right hand section of the main display, the HMI, can be adjusted to suit your requirements.  
The HMI display is split into three regions:  
1. Display Upper - P570 (Default – Time)  
2. Display Middle - P571 (Default – Sludge level)  
3. Display Lower - P572 (default – Date)  
What is displayed in these sections is selected from a list as follows:  
Time  
Rad msg count  
None  
Sludge Level  
Range  
% mA Output  
mA Output  
RL1 run-time  
RL2 run-time  
Clean run-time  
Internal Temp  
Xducer Temp  
Noise level  
% Free Lg Mem  
Description  
Tag  
Date  
Note: The current output and relays are always controlled by sludge level regardless of display selection.  
Page 34  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.7.2 Backlight On/Off - P575  
The default for the display back light is "Auto". It can be switched to "Off" or "On". If set to Auto it is on when a key  
is pressed. The back light will automatically turn off after 5 minutes or if the internal temperature is too high and  
exceeds its programmed limits. It will turn on if the internal controller temperature is too low and is less than the  
programmed limit.  
7.7.3 Clear Trend  
The lower right of the display shows a trend of the sludge blanket position over the last 12 hours. Pressing ꢅ  
when in the Clear Trend menu will clear this trend information. When the data is cleared the unit indicates this by  
displaying ‘Done’. This does NOT clear logged data.  
7.7.4 Clear Profile  
The lower left of the display shows a profile of the sludge blanket. Pressing when in the Clear Profile menu will  
clear this information. When the data is cleared the unit indicates this by displaying ‘Done’  
Page 35  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.8 Logging parameters  
Logged data can be downloaded and analysed via the RS232 port and Mobrey Measurement Log View Software  
(via a PC). For copies of this software, please contact Mobrey Measurement Sales.  
Note: A full menu structure is shown in section 11.  
7.8.1 Log Interval - P590  
The MSL600 can log the value (not the units) of the parameter that is shown on the middle of the HMI Display.  
The MSL600 can store up to 4800 records. The interval between each record being stored is programmed in  
minutes in P590, the Logging interval. The unit takes a reading every 5 seconds and averages the readings over  
the programmed logging interval.  
The unit automatically stores the maximum recorded value that occurred in the previous 24-hour period (from 12  
midnight to 12 midnight).  
Parameter values:  
Default  
5
Min  
0
Max  
99  
7.8.2 Fast log - P591  
The control unit will automatically override the logging interval and log at a rate of one record per minute when the  
sludge blanket level is above the level in metres (Feet – Imperial) set in the fast Log parameter. If the parameter  
is set to zero then fast log is not used.  
Parameter values (Metric)  
Parameter values (Imperial)  
Default  
0.000  
Min  
0.000  
Max  
7.000  
Default  
0.000  
Min  
0.000  
Max  
23.00  
7.8.3 Data Overwrite - P592  
If this parameter is set to "On" then old data will be over written when the memory is full. If it is set to "Off" then old  
data is not over written and the unit stops logging when the memory is full.  
Parameter values:  
Default  
On  
Min  
Off  
Max  
-
7.8.4 Low Mem Alarm - P593  
An alarm can be activated if the memory reaches this level when set as a % of full memory.  
Parameter Values:  
Default  
0
Min  
0
Max  
99  
Page 36  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9  
Engineering parameters  
The MSL600 blanket echo processing algorithm has been optimised for use on various types of municipal and  
industrial sludge. The user can select from either of two municipal sludge types depending on the application.  
The following parameters have been extensively tested and, once MUNICIPAL 1 or MUNICIPAL 2 sludge types  
have been chosen, the user should not need to adjust them. However, different sludge types have widely  
varying ultrasonic properties and settling characteristics, therefore the following parameters are adjustable in  
order that the MSL600 can be set up for different types of sludge.  
Note:  
It is strongly recommended that if the default parameters do not give reliable operation, or if use on industrial  
sludge is required, then advice is sought from Mobrey Measurement Customer Support.  
7.9.1 Alg. Select – P620  
Use this parameter to select an algorithm which is optimised for municipal or industrial sludge.  
The allowed options are:  
Municipal 1 (This covers most Municipal Wastewater applications e.g. Primary and Secondary settlement  
tanks, Picket fence thickeners)  
Municipal 2 (This covers Industrial applications such as Industrial effluent final settlement, clarifiers, slurry  
settlement etc.)  
The default is Municipal 1. After selecting the algorithm to use, there are a number of common algorithm  
parameters which can be adjusted using the HMI.  
7.9.2 Common algorithm parameters P621 to P629  
Common algorithm parameters affect the way in which both Municipal 1 and Municipal 2 algorithms work.  
7.9.2.1 Ave. Cyc Count – P621  
The number of cycles, in powers of 2 over which the unit will average raw sonar echo profiles to remove any  
spurious reflections from such things as air bubbles and floating solids.  
Since a complete measurement cycle takes 2 seconds then the averaging cycle count can effectively damp the  
noise over a period between 4 seconds and 2048 seconds(or 34 minutes, which is a substantial proportion of a  
rotation of most bridges).  
The default value is 128 cycles. The minimum is 2 and the maximum is 1024.  
Parameter values:  
Default  
128  
Min  
2
Max  
1024  
Page 37  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9.2.2 Noise Alrm Lev – P622  
The unit automatically monitors the background electronic noise floor as a % of display width, see parameter  
D834. If this level exceeds the Noise Alarm Lev value, programmed as a % of display width then an alarm can  
be indicated by allocating an output in P552, Noise Alarm.  
The default value is 25%.  
Parameter values:  
Default  
25  
Min  
0
Max  
100  
7.9.2.3 Top Blanking – P623  
This is the minimum operating range for the transducer in metres (feet – imperial). This parameter allows the  
user to program a region in front of the transducer which is not used by the system.  
This is useful if there are any fixed obstructions in front of the transducer which cannot be moved or otherwise  
avoided.  
This parameter is also useful when programming the industrial algorithm for avoiding floating or settling debris in  
front of the transducer.  
The default value is 0.3 metres / 1 foot.  
Parameter values (metric)  
Parameter values (imperial)  
Default  
0.300  
Min  
0.100  
Max  
7.000  
Default  
1.00  
Min  
0.33  
Max  
23.00  
7.9.2.4 Damping – P624  
It is unlikely that the blanket level will change by a large amount on a short time scale. The settling process is  
typically fairly slow. If the system should want to respond to noise or stray echoes from bubbles or debris this  
parameter, which is programmed as a time measured in seconds damps out rapid fluctuations in the measured  
sludge blanket level.  
The default value is 60 seconds.  
Parameter values:  
Default  
60  
Min  
0
Max  
9999  
7.9.2.5 Upr S-nat Temp – P625  
This is the value used for temperature compensation if the measured supernatant temperature should exceed  
this value. Valid entries are between –35 and +85°C (-30 to 185 deg F).  
The default is +40°C (105 deg F)  
Parameter values (metric)  
Parameter values (imperial)  
Default  
40  
Min  
-35  
Max  
+85  
Default  
105  
Min  
-30  
Max  
185  
Page 38  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9.2.6 Lwr S-nat Temp – P626  
This value is used for temperature compensation if the measured supernatant temperature is below this value.  
The lower temperature (P626) must always be less than the upper (P625).  
Valid entries are between –40 and +85°C (-40 to 185 deg F).  
The default is -5°C (25 deg F)  
Parameter values (metric)  
Parameter values (imperial)  
Default  
-5  
Min  
-40  
Max  
+85  
Default  
25  
Min  
-40  
Max  
185  
7.9.2.7 SoS constant - P627  
The speed of sound at 0 C (32 deg F) for a particular supernatant can be programmed in m/s (ft/s imperial).  
o
Default (metric m/s)  
1402.0  
Default (imperial ft/s)  
4599.7  
7.9.2.8 Bottom Blanking – P628  
This parameter allows the user to program a region close to the bottom of the tank which is not used by the  
system for normal blanket level measurement.  
This is useful if there are any fixed obstructions in front of the transducer close to the bottom of the tank which  
cannot be moved or otherwise avoided.  
The default value is 0.0 metres / 0 foot  
Parameter values (metric)  
Parameter values (imperial)  
Default  
0.000  
Min  
0.000  
Max  
9.999  
Default  
0.00  
Min  
0.00  
Max  
33.00  
7.9.2.9 Level Offset – P629  
This parameter is used to provide an offset to the normal displayed sludge blanket level (D800). The value may  
be entered as a positive or negative value to provide the required offset to the normal displayed sludge blanket  
level.  
Default is 0.0.  
Parameter values (metric)  
Parameter values (imperial)  
Default  
0.0  
Min  
-0.99  
Max  
0.99  
Default  
0.0  
Min  
-3.0  
Max  
3.0  
Page 39  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9.3 Municipal 1 parameters P630 to P637  
When the Municipal 1 algorithm is selected using parameter P620 (page 37), only the following specific  
parameters need to be adjusted.  
7.9.3.1 Significance – P630  
This parameter is used to select which echo in the echo profile that the Municipal 1 algorithm chooses as the  
most likely to correspond to the real sludge blanket level.  
The algorithm scans the echo profile for echoes. It calculates the mean and standard deviation of amplitudes  
for these echoes. Depending on the P630 setting, the algorithm can be programmed to select the first significant  
echo it comes to, measured from the surface of the supernatant or the most significant echo it detects in the  
entire profile.  
The allowed options are:  
First  
Most (default)  
7.9.3.2 Sharp Echo Reject – P631  
Electrical noise and other types of false echo are characteristically shorter in duration than the real echo from a  
sludge blanket. This parameter allows fine tuning of the value which the municipal algorithm uses as a window  
width to separate out these echoes.  
Note:  
This is a key system parameter and should not be adjusted without asking for advice from Mobrey Measurement.  
Parameter values:  
Default  
8
Min  
5
Max  
30  
7.9.3.3 Lost Echo Rnge - P633  
The lost echo range is the distance, split equally above and below, that the device will still look for an echo  
before going to hold last reading as set in lost echo delay (P637).  
The parameter P633 is set in number of samples. However, each sample equates to approximately 25mm (1”).  
Therefore when set with the default value of 24, the device will look for a valid echo in a window 300mm (12”)  
above and 300mm (12”) below its last valid value. If no valid echo is present, it will hold its last reading for the  
programmed amount as set in P637.  
Parameter values:  
Default  
24  
Min  
1
Max  
410  
7.9.3.4 Threshold – P634  
The Municipal 1 algorithm scans the echo profile for echoes. It calculates the mean and standard deviation of  
amplitudes for these echoes. In order to be significant, the echoes must exceed a threshold value determined in  
terms of the standard deviation of the echo amplitudes.  
The default value is 0.5 standard deviations.  
Parameter values:  
Default  
0.5  
Min  
0.00  
Max  
9.99  
Page 40  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9.3.5 Noise SD Mult – P635  
The Municipal 1 algorithm scans the echo profile for echoes. Prior to sending pulses to the transducer, the  
noise floor is measured. It calculates the mean and standard deviation of fluctuations in the noise floor.  
In order to be significant, the echo from a blanket must not only exceed a threshold value determined in terms of  
the standard deviation of the echo amplitudes (P634) but it must also exceed a threshold value determined in  
terms of the standard deviation of the noise floor (P635).  
The default value is 2.75 standard deviations.  
Parameter values:  
Default  
2.75  
Min  
0.00  
Max  
9.99  
7.9.3.6 Dirty Mult – P636  
It is often the case that the supernatant becomes dirty. In this case, large echoes can be seen directly in front of  
the transducer that should not necessarily be ignored or blanked out. If the amplitude of these signals is typically  
above 50% of the screen width, it is likely the supernatant was dirty and an alarm would be helpful in this  
situation. This can be achieved by programming a relay to operate in alarm mode and setting the alarm  
condition to Dirty S-nat.  
Parameter P636 is used to linearly scale the default threshold of 50%. The default value is a multiplier of 0.5,  
which represents 50% of the maximum displayable amplitude.  
Parameter values:  
Default  
0.5  
Min  
0.00  
Max  
2.00  
7.9.3.7 Lost Echo Time - P637  
The Municipal 1 algorithm has a facility such that if the echo is lost from a set range (see P633) then the last  
reading is held for the programmed time. This allows the unit to accommodate any false echoes from targets  
other than the sludge blanket. In other words, the device is able to recognise that the sludge level does not  
change rapidly.  
The parameter can be set between 1 to 255 minutes  
Parameter values:  
Default  
30  
Min  
1
Max  
255  
Page 41  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.9.4 Municipal 2 parameter P640  
Only one specific parameter, P640, needs to be adjusted when the Municipal 2 algorithm is selected.  
Industrial blankets are typically much denser and more substantial than municipal sludge found in a  
conventional wastewater plant. For this reason, the echo profile from an industrial sludge typically only displays  
one distinct echo.  
7.9.4.1 Threshld Offset – P640  
The echo from the blanket will produce a signal which is visible above the electronic noise floor on the echo  
profile display.  
The threshold offset parameter is the offset of the threshold which the user wishes to set above the noise floor.  
Both the noise level, D834 and the threshold offset are expressed as a % of full screen.  
The noise level can be viewed as a diagnostic parameter from the monitor menu. The first point in the echo  
profile which exceeds the threshold level is determined by the algorithm to be at the blanket level.  
Remember that;  
Threshold level = Threshld Offset (P640) + Noise Level (D834)  
When setting this parameter, remember that the echo amplitude can get larger or smaller over a period of time  
during normal operation of the system. This is because the consistency of the sludge varies with time and  
position in the settling tank as the bridge rotates over it.  
Floating debris close to the transducer can give echoes which will exceed the threshold level. It is suggested  
that in this case the blanking distance, P623 be extended to include this region in the echo profile.  
The default value is 30%.  
Parameter values:  
Default  
30  
Min  
0
Max  
100  
Page 42  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.10 System parameters  
These parameters can be used to test the MSL600 hardware.  
Note: A full menu structure is shown in section 11.  
7.10.1 AUTO CYCLE function  
The Auto Cycle or Self-Test function has the effect of automatically ramping up the sludge blanket level value  
between its minimum and maximum values so as to exercise the current output and relays without the actual  
blanket level changing.  
With the unit On-line, this parameter is accessed via SETUP-SYSTEM-TEST-AUTOCYCLE. Once the menu item  
AUTOCYCLE is entered press . The on screen display prompts you to press to start the AUTOCYCLE.  
AUTOCYCLE is stopped by pressing . Press ESC to return to main menu.  
A complete cycle is executed in about 100 seconds. It may be paused and re-started using the arrow key.  
During Auto Cycle mode, the MSL600 system continues to measure the blanket level in the background.  
On exiting the Auto Cycle mode the sludge blanket level immediately takes on the value based on the MSL600  
sensor inputs.  
7.10.2 DISPLAY test  
This function allows the user to test all the pixels in the MSL600 display.  
The Display Test function displays the product name, full software version number, and exercises all pixels.  
The MSL600 remains in Display Test mode until the Esc key is pressed. The same data, excluding the test  
pattern, is displayed at power-up.  
7.10.3 Current Output test parameters P700 to P702  
This function allows the user to test the current output on the MSL600.  
7.10.3.1 4mA Out Adjust - P700  
The current output is calibrated in the factory and should not require any adjustment. However, if required, it is  
possible to adjust the 4mA point using a calibrated meter (see section 5.5).  
7.10.3.2 20mA Out adjust - P701  
The current output is calibrated in the factory and should not require any adjustment. However, if required, it is  
possible to adjust the 20mA point using a calibrated meter (see section 5.5).  
7.10.3.3 Set Current - P702  
It is possible to force the current output to a value to check loop equipment. Any value between 0 and 20mA  
can be programmed (see section 5.5). When the unit is returned to On Line mode the current output reverts to  
normal.  
7.10.4 LOAD DEFAULTS function  
The unit can be reset to its factory-default configuration at any time by selecting the Load Defaults menu option.  
Pressing loads the default values when in this menu. This action does not change the language setting or the  
base units selected (metric or imperial).  
Page 43  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.10.5 COMMS parameters P710 to P716  
These parameters are used for serial RS232 communications.  
7.10.5.1 Address - P710  
Poll Address. The default value of this parameter should not be changed. The parameter is included in the  
menu system for future software updates. Default = 0  
7.10.5.2 Interface - P711  
The type of serial interface. The default value of this parameter should not be changed. The parameter is  
included in the menu system for future software updates. Default = log download  
7.10.5.3 Baud Rate - P712  
The speed of transfer of the interface in bit/s. The default value of this parameter should not be changed. The  
parameter is included in the menu system for future software updates. Default = 9600  
7.10.5.4 Start Bits - P713  
The number of start bits. The default value of this parameter should not be changed. The parameter is included  
in the menu system for future software updates. Default = 1  
7.10.5.5 Data Bits - P714  
The number of data bits between start and parity bit. The default value of this parameter should not be changed.  
The parameter is included in the menu system for future software updates. Default = 8  
7.10.5.6 Parity - P715  
Whether an even or odd parity check bit has been added. The default value of this parameter should not be  
changed. The parameter is included in the menu system for future software updates. Default = even  
7.10.5.7 Stop Bits - P716  
The number of stop bits. The default value of this parameter should not be changed. The parameter is included  
in the menu system for future software updates. Default = 1  
7.10.6 SETTINGS parameters P730 to P737 and BASE UNITS selection  
7.10.6.1 Base units  
The user can select either metric units (metres, deg C) or imperial units (Feet, degrees F)  
7.10.6.2 Date - P730  
The current date is entered here.  
7.10.6.3 Time - P731  
The current time is entered here.  
Page 44  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.10.6.4 Date format - P734  
The format for the date can be chosen from a list:  
yy/mm/dd  
dd/mm/yy (Default metric)  
mm/dd/yy (Default imperial)  
7.10.6.5 Keypad Sound - P735  
Each time a key is pressed, a beep sounds as confirmation of the key being pressed. This audio feedback can  
be turned off. The default is on.  
7.10.6.6 Language - P737  
The HMI default language is English. The user can chose from a list of English, Francais, Deutsch, or Svenska.  
7.10.7 PIN parameter P740  
7.10.7.1 PIN - Personal Identification Code - P740  
The unit can be protected from unauthorised use by programming a PIN. Access is via SETUP – SYSTEM –  
PIN – PIN. Any four digit numeric characters can be programmed as a PIN. In the PIN menu enter 0000 to  
remove the password.  
Please ensure that the PIN is not forgotten. If the password is forgotten, the factory must be consulted.  
Please provide the full serial number of the unit which can normally be found on the external label.  
7.10.8 FIXED parameters D750 to D753  
7.10.8.1 Model Code - D750  
The model code of the control unit.  
7.10.8.2 Serial No. - D751  
The serial number of the control unit.  
7.10.8.3 H/W Revision - D752  
The hardware revision of the control unit.  
7.10.8.4 S/W Version - D753  
The software revision. This is displayed to one decimal place. Performing the Display test function (section Error!  
Reference source not found.) will show the full software version.  
Page 45  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.11 Readings and diagnostics parameters  
The user can not alter the value of readings or diagnostics parameters within the MONITOR menu.  
Note: A full menu structure is shown in section 11.  
7.11.1 Readings parameters D800 to D834  
7.11.1.1 Sludge Level - D800  
The main process variable, the sludge blanket level in metres (feet – imperial).  
Note:  
If P629 Level offset is being used, this value will be added or subtracted from the normal sludge blanket level  
and displayed as D800.  
7.11.1.2 Target Range - D801  
The actual distance from the transducer to the sludge blanket interface in metres (feet – imperial).  
7.11.1.3 % Current Output - D805  
Indicates % of current output  
7.11.1.4 Current Output - D806  
The actual current output in mA.  
7.11.1.5 Relay Status - D820  
This diagnostic parameter indicates the status of all the relays including relay three, the fault relay and relay  
four, the compressor relay.  
The relay status is indicated by a 1 or a 0. A 1 indicates the relay is energised, a 0 indicates the relay is de-  
energised.  
The display shows the state in the following format: 0000  
Reading from left to right the first 0 is relay 1, the second 0 is relay 2, the third 0 is relay 3 and the fourth 0 is  
relay 4.  
7.11.1.6 RL * Runtime – (RL 1-D821, RL 2-D822, Cleaning time-824)  
The total length of time in hours and minutes that a relay has been energised is monitored from this parameter.  
Entering zero for the hours and minutes will reset the parameter.  
7.11.1.7 Alarm Report - D830  
When an alarm is detected then it can be viewed by accessing this parameter.  
Press to highlight the first alarm report item. The user can step through the current active alarms using the ꢂ  
and keys.  
7.11.1.8 Fault Report - D831  
When a fault is detected then it can be viewed by accessing this parameter. In normal operation, the highest  
priority active fault condition is also displayed in the lower display. Press to highlight the first fault report item.  
The user can scroll through the current active faults using the and keys.  
Page 46  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.11.1.9 Xdr Tilt Time - D833  
A diagnostic parameter indicating the time for which the transducer has been out of the water in min:secs.  
7.11.1.10 Noise Level - D834  
A diagnostic parameter indicating the noise level in the tank as a % of full screen.  
7.11.2 Diagnostics parameters D835 to D852  
7.11.2.1 Input Status - D835  
A diagnostic parameter indicating the status of the digital input, 1 indicating active, 0 indicating not active.  
7.11.2.2 LE Count – D836  
This gives an indication as to reliability of signal.  
7.11.2.3 Radio Channel - D842  
This parameter is not used with this version of the MSL600.  
7.11.2.4 Radio Address - D843  
This parameter is not used with this version of the MSL600.  
7.11.2.5 CU Temperature (Temperature of Control Unit) - D844  
View this parameter to see the current temperature in °C (imperial – degrees F) inside the MSL600 control unit.  
This temperature is used for control of the LCD back light, turning it on to generate a degree of internal heating  
in cold weather and off when hot to avoid overheating.  
7.11.2.6 Xducer Temp (Temperature of Transducer) - D845  
View this parameter to see the current temperature in °C (imperial - degrees F) of the transducer. This  
temperature is used in the compensation of the speed of sound in the supernatant.  
7.11.2.7 Free Memory (Logging Memory Free) - D846  
View this parameter to see the amount of MSL600 logging memory remaining as a % before the end of the  
buffer is reached and over writing at the start begins. This parameter is compatible with Mobrey Measurement  
Log View software.  
7.11.2.8 Date of Change (Last date of Change) - D848  
View this parameter to see the date of the last change to the configuration of the MSL600. This parameter can  
be used to detect unauthorised access.  
7.11.2.9 Echo Sharpness – D849  
View this parameter to estimate the size of the echo. A typical reading would be between 20 and 30.  
Page 47  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
7.11.2.10 Speed of Sound - D850  
View this parameter to see the temperature compensated speed of sound in the supernatant which the  
MSL600 is using in its calculation of sludge blanket level in m/s (imperial – ft/s).  
7.11.2.11 Max Xdr Temp - D851  
View this parameter to see the maximum temperature in °C (imperial – degrees F) which has been  
experienced by the transducer.  
This log is reset by direct entry of a nominal ambient value of 20°C (68 degrees F).  
7.11.2.12 Min Xdr Temp - D852  
View this parameter to see the minimum temperature in °C (imperial degrees F) that has been experienced by  
the transducer. This log is reset by direct entry of a nominal ambient value of 20°C (68 degrees F).  
Page 48  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
8. Technical reference  
8.1 Transmit pulse and echo processing  
The transducer and it’s transmit and receive circuitry is optimized to work at 1.0MHz.  
Some sludge blankets are indistinct.  
The algorithm has been optimised to average out and ignore unwanted signals produced by particles in the  
supernatant, whilst detecting and measuring the wanted signals from the sludge blanket.  
Although the algorithm is designed to largely ignore particles in the supernatant, the information (size and  
distance) is retained allowing a warning of this condition to be indicated.  
9. Maintenance  
The MSL600 should require no maintenance. It has no user serviceable parts inside.  
Although the MSL603 transducer should keep its front face clean by self-cleaning the transducer should be  
inspected periodically to ensure that algae or floating debris is not collecting on its side or transducer face.  
10. Troubleshooting  
Refer to factory  
Page 49  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
11. Programming chart  
Main Menu Option  
Sub-menu Level 1  
Sub-menu Level 2  
Sub-menu Level 3  
Parameter Title  
-
Par No.  
-
Cancel Password (only seen if the password is active)  
Go Offline ?  
INSTALLATION  
-
-
Tank Depth  
Xdr Tilt Time  
Tag No.  
Description  
Start On  
P101  
P103  
P242  
P240  
P250  
P251  
P252  
P253  
P254  
P257  
P260  
P264  
P444  
P340  
P400  
P401  
P402  
P403  
P410  
P411  
P412  
P413  
P414  
P415  
P420  
P421  
P422  
P423  
P424  
P425  
P430  
P540  
P541  
P542  
P543  
P544  
P550  
P551  
P552  
P560  
P561  
P563  
P570  
P571  
P572  
P575  
-
SETUP  
DUTY(Mode)  
DESLUDGE  
Stop On  
Stop If  
Start Time  
Interval  
Max Retries  
Start On  
CLEANING  
Interval  
Cleaning Time  
Digital i/p action  
Low Range Val  
Up Range Val  
Alarm Action  
0/4-20mA  
OUTPUT  
CURRENT OUTPUT  
RELAY  
RELAY 1  
Relay 1 Mode  
RL1 On Point  
RL1 Off Point  
RL1 Min ON  
RL1 Max ON  
RL1 Min OFF  
Relay 2 Mode  
RL2 On Point  
RL2 Off Point  
RL2 Min ON  
RL2 Max ON  
RL2 Min OFF  
Relay 3 Mode  
Out of Limits  
mA o/p Sat.  
Memory Filling  
Digital Input  
Max Retries  
Xdr Tilted  
Dirty S-nat  
Noise Alarm  
Memory Fault  
CU Temp Fault  
Xdr Temp Fault  
Display Upper  
Display Middle  
Display Lower  
Backlight On/Off  
-
RELAY 2  
RELAY 3  
ALARM  
FAULT  
DISPLAY  
Clear Trend  
Clear Profile  
-
-
LOGGING  
Log Interval  
Fast Log  
Data Overwrite  
Low Mem Alarm  
P590  
P591  
P592  
P593  
Page 50  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Programming chart continued…  
ENGINEERING  
Alg. Select  
P620  
CONFIG ALGORITHM COMMON  
Ave. Cyc Count  
Noise Alrm Lev  
Top Blanking  
Bottom Blanking  
Damping  
Upr S-nat Temp  
Lwr S-nat Temp  
SoS constant  
Level Offset  
Significance  
Sharp Echo Reject  
Lost Echo Rnge  
Threshold  
P621  
P622  
P623  
P628  
P624  
P625  
P626  
P627  
P629  
P630  
P631  
P633  
P634  
P635  
P636  
P637  
P640  
-
MUNICIPAL 1  
Noise SD Mult  
Dirty Mult  
Lost Echo Time  
Thrshld Offset  
-
MUNICIPAL 2  
AUTO-CYCLE  
DISPLAY  
SYSTEM  
TEST  
-
-
CURRENT OUTPUT  
4mA Out Adjust  
20mA Out Adjust  
Set Current  
-
P700  
P701  
P702  
-
LOAD DEFAULTS  
COMMS  
Address  
Interface  
Baud Rate  
Start Bits  
Data Bits  
Parity  
Stop Bits  
Radio Timeout  
Radio On/Off  
Base Units  
Date  
P710  
P711  
P712  
P713  
P714  
P715  
P716  
P722  
P723  
-
P730  
P731  
P734  
P735  
P737  
P740  
D750  
D751  
D752  
D753  
RADIO  
SETTINGS  
FIXED  
Time  
Date Format  
Keypad Sound  
Language  
PIN  
Model Code  
Serial No.  
H/W Revision  
S/W Version  
Page 51  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Programming chart continued…  
Sludge Level  
Target Range  
% Current Out  
Current Output  
Relay Status  
D800  
D801  
D805  
D806  
D820  
D821  
D822  
D824  
D830  
MONITOR  
READINGS  
Relay  
RL1 Run-Time  
Relay Run-time  
RL2 Run-Time  
Cleaning Time  
Alarm Report  
Fault Report  
Xdr Tilt Time  
Noise Level  
Input Status  
CU Temperature  
Xducer Temp  
Free Memory  
Date of Change  
Echo Sharpness  
Speed of Sound  
Max Xdr Temp  
Min Xdr Temp  
Radio Msg Count  
Radio STX Count  
Radio Channel  
Radio Address  
-
D831  
D833  
D834  
D835  
D844  
D845  
D846  
D848  
D849  
D850  
D851  
D852  
D853  
D854  
D842  
D843  
DIAGNOSTICS  
RADIO  
Pxxx  
Dxxx  
DIRECT  
-
Note: The Radio parameters are not used with this version of the MSL600.  
Page 52  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
12. Specification  
12.1 MSL600  
Model No.  
Operating principle  
Range  
MSL600  
Ultrasonic sonar  
7.0m (23 feet)  
0.3m (1 foot)  
Dead band  
Accuracy  
+/-35mm (+/- 1.4”)  
25mm (1”)  
Resolution  
o
Temperature limits C - Sensor  
-40 to +65 (-40 to 150 degrees F)  
o
Temperature limits C - Control unit  
-20 to +55 (-4 to 130 degrees F)  
Temperature compensation  
Power Supply – AC  
Power Supply – Hz  
Power rating  
Integral  
Switch selected 115 or 230Vac  
50/60Hz  
140VA  
Outputs  
Relays  
2 programmable relays  
1 fault relay  
Analogue  
0/4-20mA  
Display  
LCD 240 x 128 pixels with back light  
RS232  
Communications  
Enclosure  
IP rating  
IP66  
Material  
ABS  
Dimensions W x H x D  
355 x 237 x 95mm (14 x 9.3 x 3.75 INS)  
Without compressor housing. See dimensional drawing  
for full details.  
Programming  
Via integral membrane keypad  
Compressor driven air cleaning  
Transducer cleaning method  
Page 53  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Weight  
Enclosure & compressor housing  
Transducer & mounting bracket  
Approvals  
7.0 Kg / 15.4 lbs  
12.0 Kg / 26.4 lbs  
CE, LVD, EMC  
Max Altitude  
2000m  
Max Humidity  
95% RH  
2-1EC664  
Pollution Degree  
Additional specification notes:  
Programming menu using Mobrey HMI.  
Sludge blanket level from bottom of the clarifier.  
Icon enunciators display the relay status.  
The display gives a graphical presentation of sludge profile through the clarifier.  
A trend graph indicates the sludge level for the last 12 hour(s).  
The MSL600 has a single red LED to indicate power on. This LED flashes on as the transducer pulses.  
Continuous On = fault  
12.2 MSL603 transducer  
IP Rating  
Material  
Cable  
IP68 / Type 6P  
Ceramic face, PTFE nozzle, UPVC body  
Alpha xtra-guard 4 P/N 45272, 10 metres  
Page 54  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
13. Dimensional drawings  
Figure (12): MSL600 Bridge mounted unit  
Page 55  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Figure (13): MSL600 and MSL603 assembly  
Page 56  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
14. MSL603 transducer cable extension  
Parts required:  
ITT Cannon TNM connectors (Cannon part no.) [R.S. stock no.]  
1 off Reversed receptacle (192993-0071) [265-9727]  
1 off Reversed plug  
2 off Shielded endbell  
4 off Solder cup pin  
4 off Solder cup socket  
(192993-0051) [265-9812]  
(192993-0081) [265-9777]  
(192900-0634) [329-8660] to fit in the receptacle  
(192900-0632) [329-8676] to fit in the plug  
Fitting instructions:  
PLEASE NOTE - THIS CABLE CARRIES LOW LEVEL SIGNALS WHICH ARE VULNERABLE TO ELECTRO-  
MAGNETIC INTERFERENCE. IT IS IMPORTANT FOR THE CORRECT OPERATION OF THE MSL600 THAT THE  
BRAIDED SCREEN, AS WELL AS THE INTERNAL CORES ARE CONNECTED AS SPECIFIED.  
The cable comprises a brown and white twisted pair, and a black and white twisted pair. During the following  
procedure, care should be taken to ensure that the two white wires are connected correctly.  
The Shielded Endbell is supplied with assembly instructions, which includes an exploded drawing. In the following  
description, the part references [in square brackets] refer this drawing.  
Terminate the new length of cable to look like the existing transducer cable as follows: The drain wire has a yellow  
sleeve, the white wire, that is twisted with the brown wire, has a red sleeve. All conductors should preferably have  
crimped ferrules for insertion in the terminal blocks.  
Cut off the terminations on the existing transducer cable  
The following instructions refer to both plug and receptacle assemblies:  
Slide the endbell components [parts 1 to 5] on to the cable.  
Strip the outer insulation back 38mm  
Pull the exposed braid back over the outer insulation and remove the inner foils to expose the twisted cores for the  
full 38mm.  
Using an indelible marker, mark the white wire in the white/black twisted pair.  
Untwist the wires and strip the insulation back 4mm.  
Solder pins/sockets to wires.  
Fit the 'O' ring from the endbell kit in the groove of the connector.  
Push the support sleeve [part 6] onto the cable, and over the braid.  
Insert the pins/sockets into the back of the connector as follows: position A - marked white, B - black, C - white, D -  
brown. The pins/sockets must be pressed well into the housing, using a narrow implement, to snap into place.  
Pull the support sleeve [part 6] forwards towards the connector, and draw the braid over the spring elements [of part 6].  
Pull the grounding ring [part 5] forwards and snap it onto the support sleeve [part 6] trapping the braid.  
Screw together the remaining elements of the endbell. Note that ITT Cannon recommend a torque setting for the  
housing [part 4].  
The air hose is extended using the nozzle (RS stock no. 795-348) and a hose (RS-stock no, 721-4013, 20m, black).  
Page 57  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Page 58  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
Page 59  
Installation, Operation & Maintenance Manual  
IP262/Z0, Rev. AB  
February 2012  
MSL600  
The Emerson logo is a trade mark and service mark of Emerson Electric Co.  
Rosemount is a registered trademark of Rosemount Inc.  
Mobrey is a registered trademark of Mobrey Ltd.  
All other marks are the property of their respective owners.  
We reserve the right to modify or improve the designs or specifications of product and services at any time without notice.  
© 2012 Mobrey Ltd. All rights reserved.  
International:  
Americas:  
Emerson Process Management  
Mobrey Ltd.  
Emerson Process Management  
Rosemount Measurement  
8200 Market Boulevard  
Chanhassen, MN 55317 USA  
Tel (USA) 1 800 999 9307  
Tel (International) +1 952 906 8888  
Fax +1 952 906 8889  
158 Edinburgh Avenue,  
Slough, Berks, SL1 4UE, UK  
T +44 (0) 1753 756600  
F +44 (0) 1753 823589  

Fisher Price W3131 User Manual
Emerson EWR10D4 User Manual
Eizo FlexScan T550 User Manual
Dell Computer Monitor SX2210T User Manual
Cypress CY7C1917CV18 User Manual
Curtis TV2710B User Manual
Creda JACKSON J151E User Manual
Cisco Systems 7961G GE User Manual
Carrier Access Computer Hardware 600 User Manual
ADTRAN Polycom SoundPoint IP 430 User Manual