Delta PROFIBUS DP Module for VFD Series Drives PD 01 User Manual

PD-01 USER MANUAL  
PROFIBUS-DP Module for  
VFD Series Drives  
ASIA  
NORTH/SOUTH AMERICA  
DELTA PRODUCTS  
CORPORATION  
EUROPE  
DELTRONICS (Netherlands)  
B.V.  
DELTA ELECTRONICS, INC.  
TAOYUAN Plant/  
31-1, SHIEN PAN ROAD,  
Sales Office/  
Sales Office/  
KUEI SAN INDUSTRIAL ZONE P.O. BOX 12173  
Industriegebied Venlo Nr. 9031  
Columbusweg 20  
NL-5928 LC Venlo  
The Netherlands  
TEL: 31-77-324-1930  
TAOYUAN 333, TAIWAN  
TEL: 886-3-362-6301  
FAX: 886-3-362-7267  
5101 DAVIS DRIVE  
RTP, NC 27709 U. S. A.  
TEL: 1-919-767-3813  
PD-01 PROFIBUS-DP Module  
IND................................................................................................16  
Parameter value (PWE) 3rd and 4th word ....................................16  
Examples for PKW mechanism.....................................................17  
Response time about PD-01 ........................................................................19  
Chapter 5 User Parameters Setting in GSD file .........................................21  
GSD file ........................................................................................................21  
User parameters in GSD file.........................................................................25  
Chapter 6 Troubleshooting..........................................................................29  
Troubleshooting via LED displays ................................................................29  
Troubleshooting via diagnostic data .............................................................30  
Troubleshooting via error codes ...................................................................31  
Chapter 7 Dimensions..................................................................................33  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
PD-01 PROFIBUS-DP Module  
Preface  
Thanks for using DELTA PD-01 PROFIBUS-DP Module. Please read this manual carefully  
prior to use the PD-01 to ensure its operation properly. Please keep this manual in handy  
place for quick reference.  
Getting Start  
This manual is intended be used as an instruction manual and a reference guide.  
Detailed description of PROFIBUS and DP protocol will not be covered here. If you are  
interested in understanding and learning more about the PROFIBUS and DP protocol, we  
recommend you study the related comprehensive literatures.  
The content in this manual is based upon the most updated hardware and software  
information that are published recently. Therefore, please understand no guarantee will  
be given that no any discrepancy in this manual. Moreover, We reserve the right to modify  
this manual without any written notice, or any obligation to notify the end users for  
revision changes.  
Copying or reproducing any part of this manual, without written consent of Delta  
Electronics Inc. is prohibited.  
WARNING  
Failure to read, fully understand and implement the instructions contained in  
this manual may result in damage the equipment, the drive or a possible of plant  
personnel injury.  
This equipment operates under higher voltages, to control of a running machine.  
Only suitable qualified personnel familiar with the operation and construction of  
the equipment are allowed for equipment operation, to prevent any damage or  
hazard of this equipment.  
A successful and safe operation of this equipment depends upon the proper  
handling, storage, installation, operation and maintenance.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
1
PD-01 PROFIBUS-DP Module  
Receiving and Inspection  
All Delta PD-01 have gone through rigorous quality control tests at the factory prior to the  
shipment. Upon the receive of PD-01, please check that the package includes:  
1pcs PD-01,  
1pcs 8cm disc (mini size compact disc),  
1pcs communication cable (for RJ11, 6 pins),  
1 instruction sheet  
Using this Manual  
This is the User Manual for PD-01.  
Chapter 1 describes the overview of PD-01  
Chapter 2 briefly describes the introduction to PROFIBUS and PROFIBUS-DP  
Chapter 3 introduces how to install and remove the PD-01  
Chapter 4 describes the communication with PROFIBUS-DP system  
Chapter 5 introduces GSD file and parameter settings in GSD file of PD-01  
Chapter 6 provides LEDs information, and corrective actions for problem  
solving.  
Chapter 7 provides the dimensions of the PD-01  
Firmware version should conform with VFD Drives as table below:  
Delta AC Drive  
VFD-B  
Firmware Version  
Version 4.00 and above  
Version 3.00and above  
Version 1.09 and above  
VFD-M  
VFD-F  
VFD-L  
115V/200~400W  
230V/200W~2HP  
VFD-S  
All Version  
All Version  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
2
PD-01 PROFIBUS-DP Module  
Chapter 1 Overview  
PD-01, defined as a communication module for PROFIBUS-DP, is used to link VFD series  
Drives and PROFIBUS-DP system.  
Screw Mounting Hole  
SP LED  
NET LED  
Extended Socket  
Address Switches  
Profibus DP Interface (DB9)  
RS-485 Interface (RJ11)  
Screw Mounting Hole  
SP LED: Indicating the connection status between Drives and PD-01  
NET LED: Indicating the connection status between PD-01 and PROFIBUS-DP  
Address Switches: Setting the address of PD-01 on PROFIBUS-DP network  
RS-485 Interface (RJ11): Connecting to VFD Drives, and supply power to PD-01  
PROFIBUS-DP Interface (DB9): 9-PIN connector that connects PD-01 to  
PROFIBUS-DP network  
Extended Socket: 4-PIN socket that connects PD-01 to PROFIBUS-DP network  
Screw Mounting Hole: Used to mount PD-01  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
3
PD-01 PROFIBUS-DP Module  
Technical information  
Two LEDs on PD-01 used to display the connection status of PD-01:  
SP LED: indicating the connection status between PD-01 and VFD series Drives  
NET LED: indicating the connection status between PD-01 and PROFIBUS-DP  
% For more information of LEDs display, refer to Chapter 6. Troubleshooting.  
The address in PROFIBUS-DP can be set via two rotary address switches, ADDH  
and ADDL, on PD-01:  
ADDH used as a high 4 bits of address, ADDL used as a low 4 bits of address.  
% For more information of address switches, refer to Chapter 4. Communication.  
A specific 6-PIN communication cable for RJ11, is used to connect the PD-01 to  
VFD series Drives via RS-485 interface. VFD series Drives supply the 15V DC  
power to PD-01 through this cable.  
PROFIBUS-DP interface (DB9) uses a standard PROFIBUS-DP system interface.  
We recommend users use the standard connector to connect PD-01 to  
PROFIBUS-DP system. Besides, the PD-01 also provides a 4-PIN extended socket  
for users to connect it to PROFIBUS-DP system based upon the requirements.  
However, please pay attention to the assignment of A1, B1, and A2, B2 on the  
4-PIN extended socket.  
PD-01 supports baud rates of 9.6kbaud to 12Mbaud.  
Functionality  
Cyclical process data exchange (PZD).  
Parameter accessing: cyclical accessing of parameters (PKW).  
PROFIBUS supports the control commands SYNC and FREEZE for data  
synchronization between master and slaves.  
Support the configuration of data structure for data exchange with VFD series  
Drives.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
4
PD-01 PROFIBUS-DP Module  
Chapter 2 Introduction  
PROFIBUS  
PROFIBUS is an international, vendor- independent, opening filed bus standard for a wide  
range of applications in the fields of manufacturing, production, process and building  
automation, and other automation control field.  
The PROFIBUS family comprises three types of protocol, PROFIBUS-DP, PROFIBUS-PA and  
PROFIBUS-FMS, each of them is used for different tasks:  
PROFIBUS-DP (Decentralized Periphery): PROFIBUS-DP is a rapid and low cost  
communication connection designed for high-speed data transmission at field level.  
PROFIBUS-DP has widespread usage for such items as remote I/O systems, motor  
control centers, and variable speed drives. It is designed and optimized especially for  
communication between automation systems and decentralized peripheral devices.  
PROFIBUS-PA (Process Automation): PROFIBUS-PA is the PROFIBUS solution for  
process automation, typically with MBP-IS transmission technology. Based upon  
PROFIBUS-DP, PROFIBUS-PA is an extension of the PROFIBUS-DP protocol for data  
transmission. It is designed to support intrinsically safe applications and can be used  
within hazardous areas, with high explosion risk using intrinsic safe MBP-IS interface.  
PROFIBUS-PA is used to connect sensor and controller to the bus.  
PROFIBUS-FMS (Fieldbus Message Specification): PROFIBUS-FMS is multiple  
master communications designed for communication at the cell level. It is designed for  
acyclic or cyclic data transfers at medium speed between control equipment and  
cell-level controllers. FMS services open up a wide range of applications and offer a  
wide range of functionality and flexibility.  
The Maximum cable length in a segment depends on the transmission speed. PROFIBUS-DP  
communicates at speeds from 9.6 Kbps to 12 Mbps over distances from 100 to 1,200 meters.  
Baud Rate  
9.6K  
1200  
19.2K  
1200  
93.75K  
1200  
187.5K  
1000  
500K  
400  
1.5M  
200  
12M  
100  
(bps)  
Length (m)  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
5
PD-01 PROFIBUS-DP Module  
PROFIBUS-DP  
PROFIBUS-DP is a PROFIBUS communication profile optimized for high-speed, time-critical  
data transmission at field level using low-cost connections. PROFIBUS-DP is a suitable  
substitute for conventional, costly parallel wiring of 24 V measurement signals in production  
and manufacturing automation, as well as for analog 4(0) to 20mA measurement signals in  
process automation.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
6
PD-01 PROFIBUS-DP Module  
Chapter 3 Installation  
IMPORTANT NOTE:  
Prior to the installation or remove the PD-01 from network, make sure the power of VFD  
series Drives is switched off (not-energized).  
Installing the PD-01  
Improper installation of the PD-01 will cost its life usage. Please follow the instructions to  
install your PD-01 carefully.  
DIN Rail Installation  
PD-01 can be secured by mounting to DIN rail. There is a small retaining clip locates at  
the bottom of PD-01, place the PD-01 onto the DIN rail and gently push up on the clip to  
ensure the PD-01 is mounted to the DIN rail.  
Direct Mounting  
Please use the specified M4 screws to install the PD-01. Also please ensure to tighten  
them properly.  
DIN RAIL  
Screw  
Mounting  
Hole  
CLIP  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
7
PD-01 PROFIBUS-DP Module  
Insert the connector into the PROFIBUS-DP Interface (DB9), and tighten screws to  
secure the connector in place.  
Power Supply  
The power of PD-01 is supplied from VFD series Drive. Firmware version should  
conform the VFD series Drives as table listed in the page 2. No external power  
needed. The +15VDC power is applied to PD-01 directly via a specific 6-PIN  
communication cable (This 6-PIN cable is packed together with PD-01).  
NOTE:  
Though the PD-01 power is supplied from VFD series Drives, it will energized till power to  
VFD series Drives is applied  
RJ11  
+15V  
GND  
6
1
1: +15V  
3: SG-  
2: GND  
4: SG+  
5: not used 6: not used  
SG-  
Not used  
SG+  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
8
PD-01 PROFIBUS-DP Module  
If the connection of PD-01 to VFD drives does not conform the table listed in page 2, users  
need to provide external 15VDC supply the power to PD-01 (not through the communication  
cable). Refer to the pin assignment of RJ11, it is allowed to supply power to PD-01 via RJ11.  
PD-01 is energized while the power is applied to the VFD series Drives, then the SP  
LED will be steady green.  
Removing the PD-01  
To remove the PD-01, users shall:  
Remove the connection cable between PD-01 and VFD series Drives.  
Loose the PD-01 screws and remove DP connector from PD-01.  
Pull down on the retaining clip and pull out the PD-01 from DIN rail gently.  
Pin assignment of PROFIBUS-DP interface (DB9)  
Use PROFIBUS-DP interface (DB9) of PD-01 connecting PD-01 to PROFIBUS DP system.  
The terminals are short-circuit-proof and isolated.  
Pin  
1
2
Designation  
-
-
Meaning  
Not assigned  
Not assigned  
9
5
3
4
Rxd/TxD-P  
-
Receive/send data P (B)  
Not assigned  
5
6
7
DGND  
VP  
-
Data reference potential (C)  
Supply voltage positive  
Not assigned  
6
8
9
RxD/TxD-N  
-
Receive/send data N (A)  
Not assigned  
1
Terminator  
Bus terminator is important when connects PD-01 to PROFIBUS-DP system. This terminator  
can be switched in and out via switches when the recommended bus connectors have been  
used.  
If extended 4-PIN socket for the connection is used, user may use the internal terminator  
provided by PD-01 via setting the switch. If the switch is turned to "S" (Short), the internal  
terminator is disabled, then A1 and A2, B1 and B2 are all normally close. If the switch is  
turned to "R" (Resistor), the internal terminator between A1 and B1 is enabled, but A2 and B2  
are disconnected from bus.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
9
PD-01 PROFIBUS-DP Module  
Terminator  
switch for A1/B1  
A2  
A1  
B2  
B1  
S
R
121ohm  
When user uses the extend socket, the bus topology is as follows:  
PLC  
(master)  
Green  
Red  
Green  
Red  
A1  
B1  
A1  
B1  
A1  
B1  
Green  
Red  
A2  
B2  
A2  
B2  
A2  
B2  
PD-01  
PD-01  
PD-01  
VFD  
series  
Drive  
VFD  
series  
Drive  
VFD  
series  
Drive  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
10  
PD-01 PROFIBUS-DP Module  
Chapter 4 Communication  
NOTE:  
Before reading this chapter, make sure you read chapter 3 and understand the installation of  
PD-01.  
PROFIBUS address  
PD-01 has two rotary switches to set the PROFIBUS address, the only way  
for user to set the address.  
The address switches, ADDH and ADDL, allow user to set the address in a  
HEX format. ADDH is used to set high 4 bits of address, and ADDL is used  
to set low 4 bits of address. If both ADDH and ADDL are set to F, and PD-01  
is power ON or re-power ON, then PD-01 will enter the TEST mode, the SP  
LED and NET LED will be in steady orange.  
Address  
1..0x7D  
0 or  
0x7E..0xFE  
0xFF  
Meaning  
Valid PROFIBUS address  
Invalid PROFIBUS address  
Enter TEST mode  
NOTE:  
Setting changes via address switches will not effective when PD-01 is operating. This means  
the setting changes will effective after PD-01 power re-boot. Please understand this cold  
restart must be initiated by toggling the power to OFF and then ON.  
Parameters setting in VFD series Drives  
PD-01 is designed to communicate with VFD series Drives via MODBUS communication port.  
Prior to the connection, users have to set parameters below in VFD series Drives:  
Set the communication protocol of VFD series Drives to RTU 8, N, 2.  
Set the baud rate of VFD series Drives to 9600bps.  
Set the frequency source for VFD series Drives to operate via RS485.  
Set the operation source of VFD series Drives via MODBUS communication.  
Refer to the following table for the above settings when connecting to VFD series Drives:  
VFD-L type  
VFD-B / VFD-S  
VFD-M type  
VFD-F type  
115V/200~400W  
230V/200W~2HP  
P09-01=1  
P09-04=2, P09-05=0  
P02-00=4  
type  
Baud Rate 9600  
RTU 8,N,2  
Freq. Source  
Command Source  
P89=01  
P92=03  
P00=04  
P01=03  
P09-01=1  
P09-04=3  
P02-00=4  
P02-01=3  
P09-01=1  
P09-04=6  
P02-00=4  
P02-01=3  
P02-01=3  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
11  
PD-01 PROFIBUS-DP Module  
After these settings completed, connecting PD-01 and VFD series Drives via communication  
cable mentioned earlier, PD-01 is then energized. Two LED will be firstly in orange because  
PD-01 is initialized and test itself. SP LED will be then in steady green since that the  
connection is established between PD-01 and VFD series Drives.  
Cyclical data of PD-01 via PROFIBUS-DP  
PD-01 is controlled via cyclical PROFIBUS-DP channel. This channel can be used to access  
the parameters of VFD series Drives.  
Useful data structure as defined in PROFIDrive Profile 2.0  
The structure of useful data for the cyclical channel is defined in the PROFIDrive Profile,  
version 2.0. Please refer to the Parameter Process data Object (PPO).  
PKW  
PZD  
PZD1 PZD2  
PKE  
1st  
IND  
PWE  
STW  
ZSW  
HSW PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10  
HIW  
2nd  
3rd 4th  
1st  
2nd  
3rd  
4th  
5th  
6th  
7th  
8th  
9th  
10th  
word word word word  
word  
word  
word  
word  
word  
word  
word  
word  
word  
word  
PPO1  
PPO2  
PPO3  
PPO4  
PPO5  
PKW: Parameter ID/value  
PZD: Process data  
PKE: Parameter ID  
IND: Sub-index  
STW: Control word  
ZSW: Status word  
HSW: Main setpoint  
HIW: Main actual value  
PWE: Parameter value  
NOTE:  
PD-01 supports PPO1 and PPO3 structure only.  
Extended configuration  
In addition to the PPO types, cyclical data can also be configured to EXT CONF 1 or EXT  
CONF 2 (see table below). These two extended configuration both have four process  
data words. The areas of consistency can be set flexibly.  
PKW  
PZD  
PZD1 PZD2  
PKE  
1st  
IND  
PWE  
STW  
ZSW  
1st  
HSW PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10  
HIW  
2nd  
3rd  
4th  
2nd  
3rd  
4th  
5th  
6th  
7th  
8th  
9th  
10th  
word word word word  
EXT CONF 1  
word  
word  
word  
word  
word  
word  
word  
word  
word  
word  
EXT CONF 2  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
12  
PD-01 PROFIBUS-DP Module  
Default settings of PZD structure  
PD-01 must receive the user parameters from master that configured via GSD file. The  
default settings of PZD structure are as follows:  
STW1: Control Word, mapping to MODBUS address 0x2000 of VFD series Drives.  
HSW: Main set point, mapping to MODBUS address 0x2001 of VFD series Drives.  
ZSW: Drives status, mapping to MODBUS address 0x2101 of VFD series Drives.  
HIW: Main command frequency, mapping to MODBUS address 0x2102 of VFD series  
Drives.  
DP master -> VFD series Drives:  
PZD3: No default assignment  
PZD4: No default assignment  
VFD series Drives-> DP master:  
PZD3: Output frequency, mapping to MODBUS address 0x2103 of VFD series Drives.  
PZD4: Output current, mapping to MODBUS address 0x2104 of VFD series Drives.  
Control and Status words  
PD-01 supports the PPO1 and PPO3 data structure. However, it does not support the bit  
assignments of control and status words in PROFIDRV. It only supports the DELTA VFD  
series Drives control and status words.  
Control word (data from DP to VFD series Drives)  
00: No function  
01: Stop  
10: Run  
b1-b0  
11: JOG+Run  
b3-b2  
b5-b4  
Not used  
00: No function  
01: FWD  
10: REV  
11: Change direction  
00: 1st Accel / Decel time  
01: 2nd Accel / Decel time  
10: 3rd Accel / Decel time  
11: 4th Accel / Decel time  
0000: Main speed  
0001: 1st speed  
b7-b6  
b11-b8  
0010: 2nd speed  
0011: 3rd speed  
0100: 4th speed  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
13  
PD-01 PROFIBUS-DP Module  
0101: 5th speed  
0110: 6th speed  
0111: 7th speed  
1000: 8th speed  
1001: 9th speed  
b11-b8  
1010: 10th speed  
1011: 11th speed  
1100: 12th speed  
1101: 13th speed  
1110: 14th speed  
1111: 15th speed  
b12  
1: Enable b11-b6  
00: No function  
01:Operation command controlled by PU  
10:Operation command by Pr. setting  
11:Switch between PU and Pr. setting  
Not used  
b14-b13  
b15  
NOTE:  
Table above is for reference only, please check VFD series Drives user manual for  
details. The control word that is mapping to the address of VFD series Drives can be  
carried out by PD-01, so the bit assignments in the user manual of VFD series Drives is valid.  
Status word (data from VFD series Drives to DP)  
00: RUN LED light off, STOP LED light up (Drive Stop)  
01: RUN LED blink, STOP LED light up (Drive Decelerate  
b1-b0  
during the drive stopping)  
10: RUN LED light up, STOP LED blink (Drive standby)  
11: RUN LED light up, STOP LED light off (Drive Run)  
1: JOG is active  
b2  
00: REV LED light off, FWD LED light up (Forward)  
01: REV LED blink, FWD LED light up (Reverse to Forward)  
10: REV LED light up, FWD LED blink (Forward to Reverse)  
11: REV LED light up, FWD LED light off (Reverse)  
1: Reserved parameters opened  
b4-b3  
b5  
b6  
Reserved  
b7  
Reserved  
b8  
b9  
b10  
b11  
b12  
b15-b13  
1: Main frequency controlled by communication  
1: Main frequency controlled by external terminal (EXT)  
1: Operation command controlled by communication (PU)  
1: Parameters have been locked  
Copy command enable  
Reserved  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
14  
PD-01 PROFIBUS-DP Module  
NOTE:  
Table above is for reference only, please check VFD series Drives user manual for  
details. PD-01 will get the status word from VFD series Drives, so the bit assignments in  
the user manual of VFD series Drives is valid.  
Accessing parameters via PKW area  
In cyclical data, PD-01 can provide request and response (read / write) message to  
access the parameters of VFD series Drives. Due to the request and response  
mechanism, the master must send the request until it receives a corresponding  
response.  
PKW have at least 4 words:  
Word 1 Parameter ID (PKE)  
15  
12  
11  
SPM  
10  
0
0
AK  
Parameter number (PNU)  
Word 2 Parameter sub-index (IND)  
15  
8
7
Word 3 PWE1  
Word 4 PWE2  
reserved in PD-01  
parameter value of read/write  
PKE  
Bits 0 to 10 (PNU) contain the number of the relevant parameter.  
Bit 11 is reserved.  
Bits 12 to 15 (AK) contain the request or the response identifier.  
Request identifier (master PD-01)  
Request Identifier  
Meaning  
0
1
2
No request  
Request parameter value  
Modify parameter value (word)  
Response identifier (PD-01 master)  
Response Identifier  
Meaning  
0
1
7
No response  
Transfer parameter value (word)  
Cannot process request (with error number)  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
15  
PD-01 PROFIBUS-DP Module  
Fault numbers for "Cannot process request" response  
NO.  
Meaning  
0
Illegal Parameter number  
Parameter does not exist  
Parameter value cannot Parameter is a read-only parameter  
1
be modified  
or can not change in current state  
Minimum/maximum not  
reached / exceeded  
2
18  
Other error  
IND  
Structure of IND for cyclical communication via PPOs  
PKE  
HIGH  
IND  
HIGH  
PWE1  
HIGH LOW  
PWE2  
LOW  
LOW  
HIGH LOW  
15 14 13 12 11-8 7  
Para Page selection Not used  
20 23 22 21  
0
0
Function of Parameter Page Selection  
Basic PNU  
(B.PNU bit 10-0 of PKE)  
Page selection  
(P.PNU)  
Total PNU  
(B.PNU+P.PNU*2000)  
0…1999  
0…1999  
0…1999  
0
0…1999  
1
2000…3999  
4000…4999  
2
15  
0…1999  
30000…31999  
NOTE:  
In IND, Bit 15 uses a multiplier of 20, so the value of Bit 15 for the access P2000-  
P3999 must be set to 1.  
Parameter value (PWE) 3rd and 4th word  
All parameters in VFD series Drives are 16-bit. A 16-bit parameter value is transferred  
in PWE2 (4th word). PWE1 (3rd word) must be set to 0 on the PROFIBUS-DP master  
in this case.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
16  
PD-01 PROFIBUS-DP Module  
Examples for PKW mechanism  
Example 1: Read data of parameter P0003  
To read value of P0003, set the request ID to 1 (request parameter value - word).  
Because P0003 is less than 2000, the Para Page Select is 0, thus, the data sequence  
are as follows:  
Master PD-01 : 1003 0000 0000 0000  
request value of P0003  
PD-01 Master : 1003 0000 0000 1770  
Request  
Response  
Word 1 (PKE)  
Word 2 (IND)  
1003  
0000  
Word 1 (PKE)  
Word 2 (IND)  
Word 3 (PWE1)  
Word 4 (PWE2)  
1003  
0000  
0000  
1770  
Word 3 (PWE1) 0000  
Word 4 (PWE2) 0000  
PD-01 responds the value of P0003. All parameters in VFD series Drives are 16-bit  
value, so the value is transferred in PWE2 (4th word). The value of P0003 is 0x1770  
(6000 decimal), in VFD-M series Drives, it is “Maximum Output Frequency”.  
Example 2: Read command frequency in VFD series Drives (0x2102)  
To read value of command frequency, set the request ID to1, we should set the Para  
Page Select because the parameter address is greater than 2000. The address  
0x2102 is 8450 in decimal, if set Page Select to 4, then the Basic PNU is 8450 –  
4*2000 = 450 (0x1c2), thus, the data sequence are as follows:  
Master PD-01 : 11C2 2000 0000 0000  
request value of address  
0x2102  
PD-01 Master : 11C2 2000 0000 0868  
Request  
Response  
Word 1 (PKE)  
Word 2 (IND)  
11C2  
2000  
Word 1 (PKE)  
Word 2 (IND)  
Word 3 (PWE1)  
Word 4 (PWE2)  
11C2  
2000  
0000  
0868  
Word 3 (PWE1) 0000  
Word 4 (PWE2) 0000  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
17  
PD-01 PROFIBUS-DP Module  
Example 3: Write data 2 to parameter P0804  
To write data to P0804, request ID is set to 2 (Modify parameter value - word), Para  
Page Select should be set because the parameter address is greater than 2000. The  
address of P0804 is 0x0804, which is 2052 in decimal, if set Page Select to 1 (bit 15  
of IND is 1), then the Basic PNU is 2052 – 1*2000 = 052 (0x34), thus, the data  
sequence are as follows:  
Master PD-01 : 2034800000000002  
write data to P0804  
PD-01 Master : 1034800000000002  
Request  
Response  
Word 1 (PKE)  
Word 2 (IND)  
2034  
8000  
Word 1 (PKE)  
Word 2 (IND)  
1034  
8000  
0000  
0002  
Word 3 (PWE1) 0000  
Word 4 (PWE2) 0002  
Word 3 (PWE1)  
Word 4 (PWE2)  
All parameters values in VFD series Drives are 16-bit, so the data may be transferred  
in PWE2 (4th word).  
NOTE:  
VFD series Drives will write the data to EEPROM. When using PKW to change the  
value of parameter, the data will be written to EEPROM directly. However, if this  
action is too often, the EEPROM will have no capability of directly saving data.  
So please pay close attention on it.  
Example 4: Read diagnostic data  
User can use the special address to read the current diagnostic data. Please refer to  
Section 6.2 for details. The diagnostic address starts from 0x7500 to 0x7504 (5  
words). To read diagnostic data in these addresses, request ID is set to 1, Para Page  
Select should be set because the parameter address is greater than 2000. The  
address 0x7500, which is 29952 in decimal, if set Page Select to 14, then the Basic  
PNU is 29952-14*2000=1952(0x7A0), thus, the data sequence are as follows:  
Master - > PD-01 : 17A0700000000000  
PD-01 - > Master : 17A0700000000300  
read data from 0x7500  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
18  
PD-01 PROFIBUS-DP Module  
Request  
Response  
Word 1 (PKE)  
Word 2 (IND)  
Word 3 (PWE1)  
Word 4 (PWE2)  
17A0  
7000  
0000  
0000  
Word 1 (PKE)  
Word 2 (IND)  
Word 3 (PWE1)  
Word 4 (PWE2)  
17A0  
7000  
0000  
0300  
If PD-01 returns the data 0x0300, it indicates that Scan port is disconnected. Please  
refer to Section 6.2 for details.  
Example 5: Access error  
If take any action using PKW to access parameter in AC Drives and it fails, PD-01 will  
response error information. Suppose that Master send data sequence is 202D 8000  
0000 0002, if VFD series Drives does not find this address (0x07FD), it will respond  
the data sequence 702D 8000 0000 0000, response ID is 7 which means cannot  
process request (with error number), and error number is 0 (Illegal Parameter  
Number).  
Request  
Response  
Word 1 (PKE)  
Word 2 (IND)  
202D  
8000  
Word 1 (PKE)  
Word 2 (IND)  
Word 3 (PWE1)  
Word 4 (PWE2)  
702D  
8000  
0000  
0000  
Word 3 (PWE1) 0000  
Word 4 (PWE2) 0002  
Response time about PD-01  
The update time via PROFIBUS connection can be divided in 3 parts:  
T1: Communication time in transmit data from the master to PD-01, and  
T2: Wait processing in data buffer of PD-01, and  
T3: Communication time in transmit data from PD-01 to VFD Drives.  
Timer  
PD-01  
T1  
T3  
VFD  
series  
Drives  
Master  
Data Buffer  
T2  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
19  
PD-01 PROFIBUS-DP Module  
T1 depends on the actual transmission speed and the type of master in use.  
T2 depends on the internal timer of PD-01. Data is transmitted to VFD series Drives per  
70ms triggered by a timer. User cannot change the time-out interval.  
T3 depends on the Modbus communication between PD-01 and VFD series Drives.  
So the update time is,  
Max update time = T1 + T2 (70ms) + T3  
In fact, the actual update time is less than the Max update time. If the timer time-out  
when the data arrive PD-01, PD-01 will save the data to data buffer, and transmit the data  
to VFD series Drives immediately.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
20  
PD-01 PROFIBUS-DP Module  
Chapter 5 User Parameters Setting in GSD file  
GSD file  
A GSD file is a text file used to identify PROFIBUS-DP device (Master or Slave), which  
contains the necessary data for the configuration of DP slaves within a standard DP master.  
Typical information in a GSD file are Vendor information, Baud rates supported, Timing  
information, Options/features supported and Available I/O signals. The GSD file is the  
fundamental building block for the master parameter record.  
GSD-File for Delta VFD series Drives  
File: DELT08DB.GSD  
File start: ===========================================================  
#Profibus_DP  
; Unit-Definition-List:  
GSD_Revision  
Vendor_Name  
Model_Name  
Revision  
= 1  
= "Delta Electronics"  
= "VFD DRIVES"  
= "Rev. 1"  
Ident_Number  
Protocol_Ident  
Station_Type  
FMS_supp  
= 0x08DB  
= 0  
= 0  
= 0  
Hardware_Release  
Software_Release  
Redundancy  
= "V1.0"  
= "V1.0"  
= 0  
Repeater_Ctrl_Sig  
24V_Pins  
= 2  
= 0  
Implementation_Type  
Bitmap_Device  
Bitmap_Diag  
= "SPC3"  
= "VFDDRV"  
= "VFDDRV"  
= "VFDDRV"  
= 1@TdF@Delta VFD Drives  
Bitmap_SF  
Slave_Family  
Auto_Baud_supp  
= 1  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
21  
PD-01 PROFIBUS-DP Module  
9.6_supp  
= 1  
= 1  
= 1  
= 1  
= 1  
= 1  
= 1  
= 1  
= 1  
19.2_supp  
93.75_supp  
187.5_supp  
500_supp  
1.5M_supp  
3M_supp  
6M_supp  
12M_supp  
MaxTsdr_9.6  
MaxTsdr_19.2  
MaxTsdr_93.75  
MaxTsdr_187.5  
MaxTsdr_500  
MaxTsdr_1.5M  
MaxTsdr_3M  
MaxTsdr_6M  
MaxTsdr_12M  
= 60  
= 60  
= 60  
= 60  
= 100  
= 150  
= 250  
= 450  
= 800  
Freeze_Mode_supp  
Sync_Mode_supp  
= 1  
= 1  
= 0  
= 1  
Set_Slave_Add_supp  
Min_Slave_Intervall  
Modular_Station  
Max_Module  
= 1  
= 1  
Max_Input_Len  
Max_Output_Len  
Max_Data_Len  
Modul_Offset  
= 32  
= 32  
= 64  
= 0  
Fail_Safe  
= 0  
Max_Diag_Data_Len  
ORDERNUMBER  
= 16  
= "PD-01"  
Max_User_Prm_Data_Len = 26  
User_Prm_Data_Len  
User_Prm_Data  
= 26  
= 0x20,0x00,\  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
22  
PD-01 PROFIBUS-DP Module  
0x20,0x01,\  
0x00,0x00,\  
0x00,0x00,\  
0x21,0x01,\  
0x21,0x02,\  
0x21,0x03,\  
0x21,0x04,\  
0x00,0x01,\  
0x00,0x02,\  
0x00,0x02,\  
0x00,0x01,\  
0x00,0x00  
Module = "4 PKW, 2 PZD (PPO 1)  
" 0xF3, 0xF1  
" 0x00, 0xF1  
" 0xF3, 0xF3  
" 0x00, 0xF3  
EndModule  
Module = "0 PKW, 2 PZD (PPO 3)  
EndModule  
Module = "4 PKW, 4 PZD  
EndModule  
Module = "0 PKW, 4 PZD  
EndModule  
PrmText = 1  
Text(0) = "Address discontinuous"  
Text(1) = "Address continue"  
EndPrmText  
PrmText = 2  
Text(0) = "Ignore and Continue"  
Text(1) = "Stop accord to Pr.STOP METHOD"  
EndPrmText  
PrmText = 3  
Text(0) = "Stop DataExchange & Report Fault"  
Text(1) = "Continue & Report Alarm"  
Text(2) = "Ignore & Continue DataExchange"  
EndPrmText  
ExtUserPrmData = 1 "Data Input 1(PD-01 -> VFD)"  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
23  
PD-01 PROFIBUS-DP Module  
Unsigned16 0x2000 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 2 "Data Input 2"  
Unsigned16 0x2001 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 3 "Data Input 3"  
Unsigned16 0x0000 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 4 "Data Input 4"  
Unsigned16 0x0000 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 5 "Data Output 1(VFD -> PD-01)"  
Unsigned16 0x2101 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 6 "Data Output 2"  
Unsigned16 0x2102 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 7 "Data Output 3"  
Unsigned16 0x2103 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 8 "Data Output 4"  
Unsigned16 0x2104 0-65535  
EndExtUserPrmData  
ExtUserPrmData = 9 "d_state"  
Unsigned16 1 0-1  
Prm_Text_Ref = 1  
EndExtUserPrmData  
ExtUserPrmData = 10 "din_len"  
Unsigned16 2 0-4  
EndExtUserPrmData  
ExtUserPrmData = 11 "dout_len"  
Unsigned16 2 0-4  
EndExtUserPrmData  
ExtUserPrmData = 12 "LossDPComTreat"  
Unsigned16 1 0-1  
Prm_Text_Ref = 2  
EndExtUserPrmData  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
24  
PD-01 PROFIBUS-DP Module  
ExtUserPrmData = 13 "LossSPComTreat"  
Unsigned16 0 0-2  
Prm_Text_Ref = 3  
EndExtUserPrmData  
Ext_User_Prm_Data_Ref(0) = 1  
Ext_User_Prm_Data_Ref(2) = 2  
Ext_User_Prm_Data_Ref(4) = 3  
Ext_User_Prm_Data_Ref(6) = 4  
Ext_User_Prm_Data_Ref(8) = 5  
Ext_User_Prm_Data_Ref(10) = 6  
Ext_User_Prm_Data_Ref(12) = 7  
Ext_User_Prm_Data_Ref(14) = 8  
Ext_User_Prm_Data_Ref(16) = 9  
Ext_User_Prm_Data_Ref(18) = 10  
Ext_User_Prm_Data_Ref(20) = 11  
Ext_User_Prm_Data_Ref(22) = 12  
Ext_User_Prm_Data_Ref(24) = 13  
File END: ==========================================================  
NOTE:  
The required GSD file is available and can be downloaded from the DELTA web site  
save it as a GSD file named “DELT08DB.GSD”. Please make sure to specify the file name  
extension as “.GSD”, PLEASE DO NOT SAVE IT extension “.GSD.TXT”.  
User parameters in GSD file  
The user parameters in GSD file are used for the configuration of the PROFIBUS network.  
The description of the user parameters are shown in the following table:  
Item  
1
Name  
Data Input 1  
Type  
UINT  
Description  
Default  
0x2000  
This is a MODBUS address. The 1st word in  
PZD of cyclic output data will be sent to this  
address.  
2
Data Input 2  
UINT  
0x2001  
This is a MODBUS address. The 2nd word in  
PZD of cyclic output data will be sent to this  
address.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
25  
PD-01 PROFIBUS-DP Module  
Item  
3
Name  
Data Input 3  
Type  
Description  
Default  
0x0000  
UINT  
UINT  
UINT  
This is a MODBUS address. The 3rd word in  
PZD of cyclic output data will be sent to this  
address if select Module = "4 PKW, 4 PZD".  
This is a MODBUS address. The 4th word in  
PZD of cyclic output data will be sent to this  
address if select Module = "4 PKW, 4 PZD".  
This is a MODBUS address. PD-01 will  
monitor this address, and copy the return  
data to the 1st word in PZD of cyclic input  
data.  
4
5
Data Input 4  
0x0000  
0x2101  
Data Output 1  
6
7
8
9
Data Output 2  
Data Output 3  
Data Output 4  
d_state  
UINT  
UINT  
UINT  
0x2102  
0x2103  
0x2104  
This is a MODBUS address. PD-01 will  
monitor this address, and copy the return  
data to the 2nd word in PZD of cyclic input  
data.  
This is a MODBUS address. PD-01 will  
monitor this address, and copy the return  
data to the 3rd word in PZD of cyclic input  
data if select Module = "4 PKW, 4 PZD".  
This is a MODBUS address. PD-01 will  
monitor this address, and copy the return  
data to the 4th word in PZD of cyclic input  
data if select Module = "4 PKW, 4 PZD".  
This is a flag. If address in Data Output 1 ~  
Data Output 4 is continuous, set it to 1, and  
set the others to 0.  
This is a length, and unit is word. It specifies  
the length of PD-01 to process data in PZD, if  
user select the Module = "4 PKW, 4 PZD", but  
din_len is 3, PD-01 will process 3 word and  
ignore the 4th word.  
UINT  
UINT  
0x0001  
0x0002  
10 din_len  
11 dout_len  
UINT  
0x0002  
0x0001  
This is a length, and unit is word. It specifies  
the length of PD-01 to monitor data from AC  
Drive, if user select Module = "4 PKW, 4  
PZD", but dout_len is 3, PD-01 will monitor 3  
word and ignore the 4th address.  
This variable indicates that the PD-01 will  
take action when communication with  
Profibus network is lost, the value can be  
assigned as follows:  
12 LossDPComTreat UINT  
00 – Ignore event and continue;  
01 – Stop according to Pr “Stop Method” in  
VFD series Drives.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
26  
PD-01 PROFIBUS-DP Module  
Item  
Name  
Type  
Description  
Default  
13 LossSPComTreat UINT  
0x0000  
This variable indicates that the PD-01 will  
take action when the SP communication  
(SCANport communication) is lost, the value  
can be assigned as follows:  
00 – Stop data exchange and report fault;  
01 – Continue data exchange and report  
alarm;  
02 – Ignore and continue data exchange.  
If the address in Data Output 1 ~ Data Output 4 is continuous, then set d_state to 1, PD-01  
will get starting address from Data Output 1. The next data will be got from the address next  
to the starting address, and the reading length is determined by dout_len. If the MODBUS  
address for reading is discontinuous, please set d_state to 0, PD-01 will also get starting  
address from Data Output 1, but the difference is the other data will be got from the address  
saved in Data Output 2, Data Output 3 and Data Output 4 in order.  
Example, if  
Data Output 1  
Data Output 2  
Data Output 3  
Data Output 4  
= 0x2100;  
= 0x2101;  
= 0x2102;  
= 0x2103;  
dout_len  
= 0x0003;  
The MODBUS address in Data Output 1~Data Output 4 is continuous, so you can set the  
d_state to 1, then PD-01 will monitor the address starting from Data Output 1, and monitor 3  
words from VFD series Drives one time. When the dout_len is 3, PD-01 will ignore the  
address in Data Output 4. If d_state is set to 0, PD-01 will read data from the address in Data  
Output 1, and read data from the address in Data Output 2, and so forth.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
27  
PD-01 PROFIBUS-DP Module  
Edit the user parameters in S7 Step hardware configuration tools shown below:  
NOTE:  
Please do not set d_state to 1 when the address in Data Output 1 ~ Data Output 4 is  
non-continuous to avoid Parameterization error and IO disconnect. The PD-01 just check the  
address starting from Data Output 1 to Data Output [dout_len-1], in other words, if the  
address in Data Output 1 ~ Data Output 3 is continuous, but the address in Data Output 4 is  
not, and dout_len is 0x0003, then the check still can pass.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
28  
PD-01 PROFIBUS-DP Module  
Chapter 6 Troubleshooting  
Troubleshooting via LED displays  
Two LEDs, SP and NET LED, are used to monitor the PD-01 communication status.  
Possible LED displays of NET LED:  
LED  
Indication  
Corrective Actions  
OFF  
No Power Supply  
Verify that the power supply of PD-01.  
Check whether the power supply is  
connected and that power is applied to  
the PD-01 through the connector.  
Red, flickering (rapid Invalid PROFIBUS address Check whether the switch value is  
blinking)  
set via switch  
valid, valid value of slave is within  
1-125. Set the valid value and re-power  
User parameter are sent by master  
Red, blinking  
Communication link to  
PROFIBUS, but No cyclical (from GSD file), for example, if d_state  
data exchanged, or  
Extended user parameter  
error  
is set 1, ensure the data in Data Output  
1 ~ Data Output 1 + dout_len are  
continuous addresses. Otherwise,  
PD-01 will not be able to pass the  
Parameterization check.  
Red ON  
No connection to  
PROFIBUS  
1. Verify that network installation is OK.  
2. Verify that PLC is working.  
3. Verify that switch address setting is  
correct.  
Green, blinking  
“Master” is in “Stop” mode, Turn the KEY of PLC to RUN mode,  
and cyclical process data and send the control command to  
exchange in progress, but PD-01.  
set-points invalid (control  
word = 0)  
Green ON  
Cyclic data exchange in  
progress and OK  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
29  
PD-01 PROFIBUS-DP Module  
Possible LED displays of SP LED:  
LED  
Indication  
Corrective Actions  
OFF  
No Power Supply  
Verify that the power supply of PD-01.  
Check whether the power supply is  
connected and that power is applied to  
the PD-01 through the connector.  
Check your communication setting in  
AC Drive (9600, <8,N,2>, RTU)  
Red, blinking  
Red ON  
CRC check fault  
Connection failure, or  
No connection  
1. Check whether the connections  
between AC Drive and RS485 of  
PD-01 are all correct  
2. Re-wire the connections between AC  
Drive and ensure that the wire  
specification is correct.  
Green, blinking  
AC Drive returns error code 1. Check the AC Drive type and version.  
Not all Delta VFD series Drive are  
supported.  
2. Check the PLC program, and ensure  
the operating address in PD-01 is  
correct.  
Green ON  
Normal  
NOTE:  
If both SP LED and NET LED are in steady orange, it indicates that PD-01 has entered into  
the “test mode”. Please do not set the value of address switch of PD-01 to 0XFF at this time.  
Be sure to set other value and energize PD-01 again.  
Troubleshooting via diagnostic data  
PD-01 provides 16 bytes diagnostic data when the alarm occurs and when user parameter  
setting “LossSPComTreat” is set to “Continue data exchange and report alarm”. It includes 6  
bytes standard diagnostic data and 10 bytes device related diagnostic data. The following  
table shows the meanings of the 16 bytes:  
Byte 1-6  
Byte 7  
Byte 8  
Byte 9  
Byte 10  
Byte 16  
Standard  
diagnostic data  
Length in bytes SP communication  
status  
Error code  
Reserved  
Byte 7 indicates the length of device related diagnostic data including itself, so if byte 7 is 10  
(0Ahex), it indicate device related to diagnostic data have 10 bytes (including byte 7).  
Byte 8 indicates the SP communication status when the alarm occurs, and the valid value  
should be as follows:  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
30  
PD-01 PROFIBUS-DP Module  
00 – Normal  
01 – CRC check failure  
02 – VFD series Drive returns error code  
03 – Communication is time out and disconnected  
Byte 9 indicates the error code when byte 8 is 02 (VFD series Drive returns error code). Refer  
to the Section 6.3 for the meanings of invalid code.  
Other word, user can get the diagnostic data via PZD area any time. PD-01 provides some  
special MODBUS addresses to indicate the diagnostic status, the address assignments are  
as following:  
0x7500  
0x7501  
0x7502  
0x7503  
0x7504  
Address  
High  
byte  
Low  
byte  
High Low High Low High Low High Low  
byte byte byte byte byte byte byte byte  
SP  
Error  
code  
Meaning comm  
status  
Reserved, read to 0  
User can get these data through “Data Output 1”, or 2, or 3, or 4 in user parameters. For  
example, if set the “Data Output 1” to 0x7500 means get the diagnostic data from 0x7500,  
and get the return data from address 0x7500 in 1st word of PZD area.  
NOTE:  
These special addresses are read-only, it will fail if user tries to write data to it.  
Troubleshooting via error codes  
If there is a communication error detected between PD-01 and VFD series Drives, the error  
code will be displayed on the digital keypad of VFD series Drives.  
VFD series Drives can process the message from PD-01 if the communication setting is valid.  
But if the command of message is invalid, the VFD series Drives will respond a report  
message that has error codes listed in table below, to PD-01.  
Code  
Meaning  
Corrective actives  
01 Illegal command code  
The command code received in the  
command message is not available  
for the drives.  
1. Check the Request Identifier in PKW area.  
PD-01 just supports ID 0, 1, 2.  
2. Re-supply power to PD-01.  
02 Illegal data address  
1. Check the Parameter number in PKW area,  
and refer the user manual of VFD Drives.  
The data address received in the  
command message is not available 2. Check the settings of user parameters “Data  
for the drives.  
Input 1” to “Data Input 4” and “Data Output  
1” to “Data Output 4”, and refer to the user  
manual of VFD series Drives.  
3. Re-supply power to PD-01.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
31  
PD-01 PROFIBUS-DP Module  
Code  
03 Illegal data value  
Meaning  
Corrective actives  
1. Check the parameter data (PWE2) in PKW  
area, and refer the user manual of VFD series  
Drives.  
2. Check the PLC program to confirm the data  
that transmitted to PD-01 from master is valid.  
3. Re-supply power to PD-01.  
The data value received in the  
command message is not  
available for the drives.  
04 Slave device failure  
The drive is unable to perform the  
requested action.  
1. Check all data in PKW.  
2. Re-supply power to PD-01.  
VFD series Drives will not respond message to PD-01 if it receives an invalid message from  
PD-01, but error code shown in the table below will be displayed on the digital keypad.  
Code  
05 Reserved  
Meaning  
Corrective actives  
06 AC Drive is busy  
07 Reserved  
08 Reserved  
09 Check sum is error  
10 Time out  
11 Baud rate or protocol is invalid  
12 Message is too short  
13 Message is too long  
14 Message contain invalid character  
1. Please refer to section 4.2 in this manual  
and check the setting of VFD series Drives.  
2. If the error still exists, return it to factory.  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
32  
PD-01 PROFIBUS-DP Module  
Chapter 7 Dimensions  
PD-01  
SP  
A1  
NET  
B1  
A2  
ADDH  
B2  
ADDL  
RS-485  
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED  
33  

HP Hewlett Packard HP LCD Monitor LE2201W User Manual
GE ZHU30RBM User Manual
GE 55911620 User Manual
Frymaster GSMS User Manual
Frigidaire FFGC3005LW User Manual
Frigidaire 318200658 User Manual
Dell Computer Hardware 9150 User Manual
ClearOne comm CHAT 170 User Manual
Atlantis Land A04 WI2202 User Manual
Asus P5K VM User Manual