BACnet® Option Module
Instruction Manual
TR200
November 2009
BAS-SVX24B-EN
Table of Contents
Safety
1-1
1-1
1-3
1-8
1-8
Copyright, limitation of liability and revision rights
High Voltage Warning
Before Commencing Repair Work
Special Conditions
2-1
2-1
Introduction
Introduction
3-1
3-1
3-5
How to Install
The BACnet Option
System Specifications
4-1
4-1
4-2
4-3
How to Configure the System
Configuring BACnet
BIBBs
Example of a simple set-up of BACnet
5-1
How to Control the Adjustable Frequency Drive
Network Adjustable Frequency Drive Control Inputs and Out-
5-2
puts
5-15
Adjustable Frequency Drive Feedback to Network
6-1
6-1
6-2
Parameters
Parameter Overview
Parameter Description
7-1
7-1
7-2
7-3
Troubleshooting
Alarm, Warning and Extended Status Word
Alarm Words
Warning Words
TR200 BACnet
-1
7-4
LED Status
-2
TR200 BACnet
Safety
Copyright, limitation of liability and revision rights
This publication contains information proprietary to Trane. By accepting and using this manual, the user agrees
that the information contained herein will be used solely for operating equipment from Trane or equipment
from other vendors provided that such equipment is intended for communication with Trane equipment over
a serial communication link. This publication is protected under the copyright laws of most countries.
Trane does not warrant that a software program produced according to the guidelines provided in this manual
will function properly in every physical, hardware or software environment.
Although Trane has tested and reviewed the documentation within this manual, Trane makes no warranty or
representation, neither expressed nor implied, with respect to this documentation, including its quality, per-
formance, or fitness for a particular purpose.
In no event shall Trane be liable for direct, indirect, special, incidental, or consequential damages arising out of
the use, or the inability to use information contained in this manual, even if advised of the possibility of such
damages. In particular, Trane is not responsible for any costs, including but not limited to those incurred as a
result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs
to substitute these, or any claims by third parties.
Trane reserves the right to revise this publication at any time and to make changes to its contents without prior
notice or any obligation to notify former or present users of such revisions or changes.
TR200 BACnet
1-1
Safety
Warnings, Cautions and Notices
Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are
provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions
are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate
a situation that could result in equipment or property damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these
precautions.
Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also
be used to alert against unsafe practices.
NOTE
Indicates a situation that could result in equipment or property damage-only accidents.
Note
Indicates something important to be noted by the reader.
Indicates default setting
✮
1-2
TR200 BACnet
Safety
High Voltage Warning
WARNING
The voltage of the adjustable frequency drive is dangerous whenever it is connected to line power. Incorrect installation
of the motor or adjustable frequency drive could result indeath, serious injury or damage to the equipment. Conse-
quently, it is essential to comply with the instructions in this manual as well as local and national rules and safety
regulations.
Safety Note
WARNING
The voltage of the adjustable frequency drive is dangerous whenever connected to line power. Incorrect installation of
the motor, adjustable frequency drive or serial communication bus could result in death, serious personal injury or
damage to the equipment. Consequently, the instructions in this manual, as well as national and local rules and safety
regulations, must be complied with.
WARNING
Failure to follow instructions below could result in death or serious injury.
Safety Regulations
1. The adjustable frequency drive must be disconnected from line power if repair work is to be carried out.
Make sure that the line power supply has been disconnected and that the necessary time has passed before
removing motor and line power plugs.
2. The [STOP/RESET] key on the keypad of the adjustable frequency drive does not disconnect the equipment
from line power and is thus not to be used as a safety switch.
3. Correct protective grounding of the equipment must be established, the user must be protected against
supply voltage, and the motor must be protected against overload in accordance with applicable national
and local regulations.
4. The ground leakage currents are higher than 3.5 mA.
5. Protection against motor overload is set by par.1-90 Motor Thermal Protection. If this function is desired,
set par.1-90 Motor Thermal Protection to data value [ETR trip] (default value) or data value [ETR warning].
Note: The function is initialized at 1.16 x rated motor current and rated motor frequency. For the North
American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and line power supply while the adjustable frequency drive is con-
nected to line power. Make sure that the line power supply has been disconnected and that the necessary
time has passed before removing motor and line power plugs.
7. Please note that the adjustable frequency drive has more voltage inputs than L1, L2 and L3, when load
sharing (linking of DC intermediate circuit) and external 24 Vdc have been installed. Make sure that all
voltage inputs have been disconnected and that the necessary time has passed before commencing repair
work.
TR200 BACnet
1-3
Safety
Installation at high altitudes
WARNING
Installation at high altitude:
380–500 V, enclosure A, B and C: At altitudes above 6,561 ft [2 km], please contact Trane regarding PELV/Class II.
380–500 V, enclosure D, E and F: At altitudes above 9,842 ft [3 km], please contact Trane regarding PELV/Class II.
If the drive is to be installed over 6,561 ft [2 km] altitude, then the PELV specifications are not fulfilled anymore, i.e.,
the distances between components and critical parts become too small. To maintain the clearance for functional insu-
lation anyway, the risk for overvoltage must be reduced by means of external protective devices or some kind of galvanic
isolation. De-rating should also be taken into consideration, since cooling the drive is more difficult at high altitude.
Please contact Trane in such cases.
Failure to follow recommendations could result in death or serious injury.
WARNING
Warning against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop,
while the adjustable frequency drive is connected to line power. If personal safety considerations make it necessary
to ensure that no unintended start occurs, these stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always
be activated, following which data can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the adjustable frequency drive, or if a
temporary overload or a fault in the supply line power or the motor connection ceases.
Consequently, disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be inadvertently energized. Failure to follow recommendations could
result in death or serious injury.
WARNING
Touching the electrical parts could result in death or serious injury - even after the equipment has been disconnected
from line power.
Also make sure that other voltage inputs have been disconnected, such as external 24 VDC, load sharing (linkage
of DC intermediate circuit), as well as the motor connection for kinetic backup. Refer to the Instruction Manual
for further safety guidelines.
Failure to follow recommendations could result in death or serious injury.
WARNING
The adjustable frequency drive DC link capacitors remain charged after power has been disconnected. To avoid an
electrical shock hazard, disconnect the adjustable frequency drive from line power before carrying out maintenance.
Wait at least as follows before doing service on the adjustable frequency drive:
Failure to follow recommendations could result in death or serious injury.
1-4
TR200 BACnet
Safety
Voltage (V)
200 - 240
380 - 480
525-600
Min. Waiting Time (Minutes)
20
4
15
30
40
1.5–5 hp
7.5–60 hp
[5.5 –45 kW]
15–125 hp
[11–90 kW]
15–125 hp
[11–90 kW]
15–125 hp
[11–90 kW]
[1.1–3.7 kW]
1.5–10 hp
[1.1–7.5 kW]
1.5–10 hp
[1.1–7.5 kW]
150–350 hp
[110–250 kW]
450–1350 hp
[315–1000 kW]
525-690
60–550 hp
[45–400 kW]
600–1875 hp
[450–1400 kW]
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
TR200 BACnet
1-5
Safety
Safety Precautions
WARNING
The voltage of the adjustable frequency drive is dangerous whenever connected to line power. Incorrect installation of
the motor, adjustable frequency drive or serial communication bus could cause death, serious personal injury or damage
to the equipment. Consequently, the instructions in this manual, as well as national and local rules and safety regula-
tions, must be complied with.
WARNING
Safety Regulations
1. The line power supply to the adjustable frequency drive must be disconnected whenever repair work is to be
carried out. Make sure that the line power supply has been disconnected and that the necessary time has elapsed
before removing motor and line power supply plugs.
2. The [OFF] button on the control panel of the adjustable frequency driver does not disconnect the line power supply
and consequently it must not be used as a safety switch.
3. The equipment must be properly grounded, the user must be protected against supply voltage and the motor must
be protected against overload in accordance with applicable national and local regulations.
4. The ground leakage current exceeds 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired, set par.
1-90 Motor Thermal Protection to data value ETR trip 1 [4] or data value ETR warning 1 [3].
6. Do not remove the plugs for the motor and line power supply while the adjustable frequency drive is connected
to line power. Make sure that the line power supply has been disconnected and that the necessary time has elapsed
before removing motor and line power plugs.
7. Please note that the adjustable frequency drive has more voltage sources than L1, L2 and L3, when load sharing
(linking of DC intermediate circuit) or external 24 V DC are installed. Make sure that all voltage sources have been
disconnected and that the necessary time has elapsed before commencing repair work.
Failure to follow recommendations could result in death or serious injury.
WARNING
Warning against unintended start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop,
while the adjustable frequency drive is connected to line power. If personal safety considerations (e.g., risk of
personal injury caused by contact with moving machine parts following an unintentional start) make it necessary
to ensure that no unintended start occurs, these stop functions are not sufficient. In such cases, the line power
supply must be disconnected or the Safe Stop function must be activated.
2. The motor may start while setting the parameters. If this means that personal safety may be compromised (e.g.,
personal injury caused by contact with moving machine parts), motor starting must be prevented, for instance by
use of the Safe Stop function or secure disconnection of the motor connection.
3. A motor that has been stopped with the line power supply connected, may start if faults occur in the electronics
of the adjustable frequency drive, through temporary overload or if a fault in the power supply grid or motor con-
nection is remedied. If unintended start must be prevented for personal safety reasons (e.g., risk of injury caused
by contact with moving machine parts), the normal stop functions of the adjustable frequency drive are not suffi-
cient. In such cases, the line power supply must be disconnected or the Safe Stop function must be activated.
Consequently, disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be inadvertently energized. Failure to follow recommendations could
result in death or serious injury.
1-6
TR200 BACnet
Safety
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout pro-
cedures to ensure the power cannot be inadvertently energized. Failure to follow recommendations could result
in death or serious injury.
1. Control signals from, or internally within, the adjustable frequency drive may in rare cases be activated in
error, be delayed or fail to occur entirely. When used in situations where safety is critical, e.g., when con-
trolling the electromagnetic brake function of a hoist application, these control signals must not be relied
on exclusively.
Note
When using the Safe Stop function, always follow the instructions in the Safe Stop section of the Design Guide.
WARNING
Disconnect all electric power, including remote disconnects. Follow proper lockout/tagout procedures to ensure the
power cannot be inadvertently energized. Use an appropriate voltmeter to verify that the unit is discharged. Failure to
disconnect power and ensure unit is discharged before servicing could result in death or serious injury.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of
DC intermediate circuit), as well as the motor connection for kinetic backup.
Systems where adjustable frequency drives are installed must, if necessary, be equipped with additional monitoring
and protective devices according to the valid safety regulations, e.g., law on mechanical tools, regulations for the
prevention of accidents, etc. Modifications on the adjustable frequency drives by means of the operating software are
allowed.
Failure to follow recommendations could result in death or serious injury.
Hoisting applications:
The adjustable frequency drive functions for controlling mechanical brakes cannot be considered as a primary
safety circuit. There must always be a redundancy for controlling external brakes.
Protection Mode
Once a hardware limit on motor current or DC link voltage is exceeded, the drive will enter “Protection mode”.
“Protection mode” means a change of the PWM modulation strategy and a low switching frequency to minimize
losses. This continues 10 sec after the last fault and increases the reliability and the robustness of the drive while
re-establishing full control of the motor.
In hoist applications, “Protection mode” is not usable because the drive will usually not be able to leave this
mode again, and therefore it will extend the time before activating the brake – which is not recommended.
"Protection mode” can be disabled by setting par.14-26 Trip Delay at Inverter Fault to zero, which means that
the drive will trip immediately if one of the hardware limits is exceeded.
Note
It is recommended to disable protection mode in hoisting applications (par.14-26 Trip Delay at Inverter Fault =
0).
TR200 BACnet
1-7
Safety
Before Commencing Repair Work
WARNING
Hazardous Voltage!
1. Disconnect the adjustable frequency drive from line power.
2. Disconnect DC bus terminals 88 and 89
3. Wait at least the time mentioned above in the section General Warning.
4. Remove motor cable
Failure to follow recommendations could result in death or serious injury.
Special Conditions
Electrical ratings:
The rating indicated on the nameplate of the adjustable frequency drive is based on a typical 3-phase line power
supply within the specified voltage, current and temperature ranges, which are expected to be used in most
applications.
The adjustable frequency drives also support other special applications, which affect the electrical ratings of the
adjustable frequency drive.
Special conditions that affect the electrical ratings might be:
•
•
•
Single phase applications.
High temperature applications that require derating of the electrical ratings.
Marine applications with more severe environmental conditions.
Other applications might also affect the electrical ratings.
Consult the relevant sections in this manual and in the for information about the electrical ratings.
Installation requirements:
The overall electrical safety of the adjustable frequency drive requires special installation considerations re-
garding:
•
•
•
•
Fuses and circuit breakers for overcurrent and short-circuit protection
Selection of power cables (line power, motor, brake, load sharing and relay)
Grid configuration (grounded delta transformer leg, IT,TN, etc.)
Safety of low-voltage ports (PELV conditions).
Consult the relevant clauses in these instructions and in the for information about the installation requirements.
1-8
TR200 BACnet
Introduction
Introduction
About this Manual
First time users can obtain the most essential information for quick installation and set-up in these chapters:
Introduction
How to Install
How to Configure the System
Application Example
For more detailed information including the full range of set-up options and diagnosis tools, refer to the chapters:
How to Control the TR200
How to Access TR200 Parameters
Parameters
Troubleshooting
Technical Overview
BACnet (Building Automation and Control Network) is an open data communications protocol, American Na-
tional Standard (ANSI/ASHRAE 135-1995). BACnet provides a means by which computer-based control equip-
ment from different manufacturers can work together. BACnet is designed to handle many types of building
controls, including HVAC, lighting, security, fire, access control, maintenance and waste management. BACnet
permits flexibility for expansion and different equipment combinations.
Conformance Classes, Function Groups and the PICS: Evaluating the capabilities of a BACnet device is poten-
tially a formidable task, given the great choice of objects, properties and services, which can be implemented,
as well as the fact that it is not necessary for every BACnet device to have a full BACnet implementation in order
to carry out its task. ASHRAE's BACnet Committee recognized this problem and responded with aids to evalu-
ation in the form of "Conformance Classes", "Function Groups" and the "Protocol Implementation Conformance
Statement" (PICS).
The BACnet protocol defines six levels of conformance classes, each of which specifies the minimum subset of
services implemented on the device. The lowest level, Conformance Class 1, requires only that the BACnet
device contain a device object and that it be able to execute (respond to) a ReadProperty service request. Each
successive conformance class level adds service requests that must be executable by the device, as well as the
service requests it must be able to initiate. Conformance Class 6 requires 21 types of service requests (of the 32
overall) to be implemented, of which 20 must be initiable and 17 executable. Conformance class thus provides
a measure of the device's ability to communicate.
Function groups specify a combination of objects and services necessary to carry out certain building automa-
tion functions. They are specified independently of conformance class, though the implementation of some of
the function groups automatically confers some conformance class higher than 1.
TR200 BACnet
2-1
Introduction
Background information
Protocol name:
BACnet
Technology developer:
Year introduced:
ASHRAE
1995
Governing standards:
Openness:
ANSI/ASHRAE Standard 135-2004, ISO 16484-5
Open specification
Physical characteristics
Network topology:
Bus
Physical media:
Max. Distance at low speed:
Shielded twisted pair
3937 ft [1200 m]
Transport mechanism
Communication methods:
Baud Rates Supported:
Termination:
Master/slave
9600, 19200, 38400, 76800
120 ohm
2-2
TR200 BACnet
Introduction
Assumptions
This manual assumes you are using a Trane BACnet Option Card in conjunction with a Trane TR200 series
adjustable frequency drive. It is also assumed that your master is a BMS or PC equipped with a serial commu-
nication card supporting all the BACnet communication services required by your application, and that all
requirements stipulated in the BACnet standard, as well as those pertaining to the Variable Frequency Drive are
strictly observed as well as all limitations therein fully respected.
Background Knowledge
The Trane BACnet Option Card is designed to communicate with any master complying with the BACnet stand-
ard. Familiarity with the PC or PLC used as a master in the system is assumed. Issues regarding hardware or
software produced by other manufacturers are beyond the scope of this manual and are not the responsibility
of Trane.
If you have questions regarding set-up of master-to-master communication or communication to a non-Trane
slave, consult the appropriate manuals.
Available Literature for TR200
-
-
-
The Instruction Manual provides the necessary information for getting the drive up and running.
Instruction Manual TR200 High Power
The Design Guide contains all the technical information about the drive and customer design and applica-
tions.
-
The Programming Guide provides information on how to program and includes complete parameter de-
scriptions.
x = Revision number
yy = Language code
Trane technical literature is available in print from your local Trane Sales Office or online at: www.trane.com/vfd
TR200 BACnet
2-3
Introduction
Abbreviations
ACI
AOC
AV
BMS
BV
CAN
CTW
EE-
Acyclical Control Interval
Application Orientated Controller
Analog Variable
Building Management System
Binary Variable
Controller Area Network
Control Word
PCD
PCA
PCV
PDU
PELV
PLC
Process Data
Parameter Characteristics
Parameter-Characteristics-Value
Protocol Data Unit
Protected Extra Low Voltage
Programmable Logic Control
Parameter Number
PNU
PVA
Electrical Erasable Programmable Read Only
Parameter Value
PROM Memory
EIA
Electronic Industries Association: Specifies of the RC
Request/Response Characteristics
Status Word
EIA Standard RS 485-A
Electromagnetic Compatibility
Serial Communication Bus Data link Layer
Field Device Tool
EMC
FDL
FDT
IND
I/O
STW
Sub index
Input/Output
ISO
LCD
International Standards Organization
Liquid Crystal Display
keypad Local Control Panel
LED
MAV
MOC
MRV
PC
Light Emitting Diode
Main Actual Value
Motion Orientated Controller
Main Reference Value
Personal Computer
2-4
TR200 BACnet
How to Install
The BACnet Option
Installation of the Option
Items required to install a serial communication bus option in the adjustable frequency drive:
-
-
The serial communication bus option
Serial communication bus option adaptor frame for the adjustable frequency drive. This frame is deeper
than the standard frame, to allow space for the serial communication bus option beneath.
-
Cable holders
TR200 BACnet
3-1
How to Install
Instructions:
-
-
-
Remove the keypad panel from the adjustable frequency drive.
Remove the frame located beneath and discard.
Push the option into place. Two positions are possible, with cable terminal facing either up or down. The
cable up position is often most suitable when several adjustable frequency drives are installed side by side
in a rack, as this position permits shorter cable lengths.
-
-
-
-
-
Push the serial communication bus option adaptor frame for the adjustable frequency drive into place.
Remove the plug for the Drive port and connect the plug that is connected to the BACnet option
Replace the keypad panel.
Attach cable.
Fasten the cable in place using cable holders. The adjustable frequency drive top surface has pre-drilled
threaded holes for attaching the cable holders to the unit.
Cabling
Cable lengths and number of nodes
The maximum cable length allowable in one segment is dependent on the transmission speed. The total cable
length includes drop cables if any. A drop cable is the connection from the main bus cable to each node. If a T-
connection is used, permissible cable length and maximum number of nodes/drives are 1, 2, 3 and 4 bus
segments.
Drop cable connection (i.e., T-connection) beyond the cable lengths indicated is not recommended, due to the
increased risk of reflection occurring. Instead, Trane recommends direct connection of the adjustable frequency
drive.
Note that a repeater is a node in both of the two segments it connects. The number of adjustable frequency
drives is based on a single master system. If there are two or more masters (e.g., PC tools, routers), the number
of adjustable frequency drives must be reduced correspondingly.
Network topology
Free topology without repeater
Free topology with one repeater
Free topology maximum device-to-device
Bus topology single terminated
Bus topology double terminated without repeater
Bus topology double terminated with one repeater
Bus topology maximum stub length
Maximum cable length
1640 ft [500 m]
3280 ft [1000 m]
1640 ft [500 m]
1640 ft [500 m]
8858 ft [2700 m]
17716 ft [5400 m]
9.8 ft [3 m]
3-2
TR200 BACnet
How to Install
The length statements in the tables above are valid for bus cable with the following properties:
-
-
-
-
-
Impedance: 135 to 165 Ohm at a measuring frequency from 3 to 20 MHz
Resistance: <110 Ohm/km
Capacitance: <30 pF/m
Damping: max. 9 dB over the whole wire length
2
2
Cross section: max. 0.00053 in [0.34 mm ], corresponding to AWG 22
Cable type: twisted in pairs, 1 x 2, or 2 x 2, or 1 x 4 wires
-
-
Shielding: Copper-braided shield or braided shield and foil shield
Use of the same cable type throughout the entire segment is recommended to avoid impedance mismatch.
TR200 BACnet
3-3
How to Install
Network Termination
Connecting the Bus Line
Connect the BACnet Option Card to the bus line via terminals 62, 63 and 66. Terminal 62 is marked red and
Terminal 63 is marked green. These two are the RS485 lines. Terminal 66 the signal ground for the RS485
transmitter.
Maximum Cable Lengths
Maximum total bus cable length: 4000 ft [1200 m]
3-4
TR200 BACnet
How to Install
Cable Routing
The BACnet communication cable must be kept away from motor and brake resistor cables to avoid coupling
of high frequency noise from one cable to the other. Normally a distance of 7.9 in (200 mm) is sufficient, but
maintaining the greatest possible distance between cables is generally recommended, especially where cables
run in parallel over long distances.
When crossing is unavoidable, the BACnet cable must cross motor and brake resistor cables at an angle of 90
degrees.
System Specifications
EMC Precautions
The following EMC precautions are recommended to achieve interference-free operation of the BACnet network.
Additional EMC information is available in the TR200 Drive Design Guide. Also consult the BACnet master manual
for further installation guidelines.
NOTE
Ensure compliance with relevant national and local regulations, for example in protective ground connection.
Connection of the Cable Shield
It is recommended to connect the shield to ground at both ends of the bus cable. This ensures the optimum
resistance towards EMC noise. The shield of the BACnet cable must always be connected to ground at both
ends, meaning the shield must be connected to ground in all stations connected to the BACnet network. It is
very important to have a low impedance ground connection of the shield, also at high frequencies. This can be
obtained by connecting the surface of the shield to ground, for example by means of a cable clamp or a con-
ductive cable connector. The TR200 Series has various clamps and brackets to enable a proper ground
connection of the BACnet cable shield.
TR200 BACnet
3-5
How to Install
Ground Connection
It is important that all stations connected to the BACnet network are connected to the same ground potential.
The ground connection must have low HF (high frequency) impedance. This can be achieved by connecting a
large surface area of the cabinet to ground, for example by mounting the TR200 series on a conductive rear
plate. Particularly when there are long distances between the stations in a BACnet network, it may be necessary
to use additional potential equalizing cables, connecting the individual stations to the same ground potential.
The use of repeaters with galvanic isolation or fiber optic can improve the EMC performance and reduce ground
loop current.
3-6
TR200 BACnet
How to Configure the System
Configuring BACnet
Initialization Procedure
The Initialization Procedure is explained by the flow chart given below:
Initialization Parameter
General Settings
Name
Control Site
Par. Number
8-01
Default Value
Digital and control word
Drive RS-485
1.0 sec
Setting for BACnet
Digital and control word
Drive RS-485
1.0 sec
Control word source
ControlWord Timeout time
ControlWord Timeout Function
End of Timeout Function
Reset ControlWord Timeout
Diagnosis
8-02
8-03
8-04
8-05
8-06
8-07
Off
Off
Resume set-up
Do not reset
Set-up
Resume set-up
Do not reset
Don’t care
ControlWord Profile
8-10
Drive Profile
Drive Profile
Drive Port Settings
Name
Protocol
Address
Par. Number
8-30
Default Value
Drive
Setting for BACnet
Drive Option
1
8-31
1
Baud Rate
Minimum Response Delay
Max Response Delay
8-32
8-35
8-36
9600 baud
10 ms
5000 ms
9600 baud
10 ms
5000 ms
Table 4. 1: 1) Please see also section: Parameter Overview >Parameter List.
TR200 BACnet
4-1
How to Configure the System
Digital/Bus settings
Name
Par. Number
Default Value
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Setting for BACnet
Logic-or
Coasting Select
Quick Stop Select
DC Brake Select
Start Select
Reversing Select
Set-up Select
8-50
8-51
8-52
8-53
8-54
8-55
8-56
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Logic-or
Preset reference Select
BACnet settings
Name
BACnet device instance
Par. Number
Default Value
Setting for BACnet
1
8-71
1
Depent on the Number of
Masters in the system
At power-up
MS/TP Max Masters
8-73
127
“I am” Service
Initialization Password
8-74
8-75
At power-up
“admin”
“admin”
Control Word Timeout Function
par.8-03 Control Timeout Time and par.8-04 Control Timeout Function are not enabled in this version of the
BACnet option.
BIBBs
Bibb's
ReadProperty Service
ReadPropertyMultiple Service
WriteProperty Service
WritePropertyMultiple Service
ConfirmedEventNotification Service
UnconfirmedEventNotification Service
GetEventInformation Service
AcknowledgeAlarm Service
ReinitializeDevice Service
DeviceCommunicationControl Service
I-Have Service
Who-Has Service
Who-Is Service
I-am Service
TimeSynchronization
4-2
TR200 BACnet
How to Configure the System
Example of a simple set-up of BACnet
This example shows the necessary steps to set up the TR200 BACnet interface with the following system re-
quirements:
•
•
•
•
•
•
•
MS/TP running at 38,400 baud
MAC address 20 for the TR200
BACnet Device Instance 0 1025
Highest number of a master stack is 35
Start/stop of drive from BACnet only
Reference from BACnet
Read status of drive (actual speed)
Set the following parameters:
Name
Protocol
Par. number
8-30
Value
Drive option [9]
20
Address
8-31
Drive Port Baud Rate
Coasting Select
BACnet device instance
MS/TP Max Masters
8-32
8-50
8-70
8-72
38,400 Baud [4]
Bus [1]
1025
35
After the parameters have been set according to the table above, the drive has to be unpowered and repowered
before the changes take effect. When the adjustable frequency drive is detected by the BMS, the drive can be
controlled by BV:1, which will start the motor if set to [1]. Setting AV:0 will set the speed reference of the drive.
The actual speed can be monitored via AV:1. See also Analog Input and Output Objects section.
TR200 BACnet
4-3
How to Configure the System
4-4
TR200 BACnet
How to Control the Adjustable Frequency Drive
Reference Handling
Select the adjustable frequency drive configuration mode in par.1-00 Configuration Mode.
[0] Open-loop
[3] Closed-loop
Open-loop
For open-loop operation, the reference represents the desired output speed of the adjustable frequency drive.
The speed reference value:
Closed-loop
For closed-loop operation, the reference represents the setpoint.
NOTE
In closed-loop operation, par.3-02 Minimum Reference and par.4-12 Motor Speed Low Limit [Hz] must be set to 0 Hz.
Set the par.4-14 Motor Speed High Limit [Hz] to a value greater than the setting in par.3-03 Maximum Reference.
TR200 BACnet
5-1
How to Control the Adjustable Frequency
Drive
Network Adjustable Frequency Drive Control Inputs and Outputs
Analog Input and Output Objects
Control the adjustable frequency drive from the BACnet network using 'objects'. The various types of 'objects'
and their descriptions are shown in the following tables.
Change- Non-vola-
Alarm
notifi-
cation
Object
ID
Read/
Write
Triggers bus
timeout
Object Name
able De-
scription
tile RAM Drive Par.
Store
Analog
Input 53
Analog
Input 54
Analog
In X30/11
Analog
In X30/12
Analog
Input X42/1
Analog
Input X42/3
Analog
AI:0
AI:1
AI:2
AI:3
AI:4
AI:5
AI:6
R
R
R
R
R
R
R
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
16-62
16-64
16-75
16-76
18-30
18-31
18-32
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NO
NO
NO
NO
NO
NO
NO
No
No
No
No
No
No
Input X42/5
Table 5. 1: Analog inputs
Change- Non-vola-
Linked to
TR200Pa-
rameter
Alarm
notifi-
cation
Triggers
Bus Time-
out
Object
Read/
Write
Object Name
ID
able De-
scription
tile RAM
Store
Terminal
AO:0
AO:1
42 Output Bus
Control
W/R
W/R
Yes
Yes
No
No
6-53
5-93
No
No
Yes
Yes
Pulse out
#27 Bus
Control
Pulse out
#29 Bus
Control
AO:2
AO:3
AO:4
W/R
W/R
W/R
Yes
Yes
Yes
No
No
No
5-95
6-63
No
No
No
Yes
Yes
Yes
Analog
Out X30/8 [mA]
Analog
Output
26-43
X42/7[V]
Analog
AO:5
AO:6
Output
X42/9[V]
Analog
W/R
W/R
Yes
Yes
No
No
26-53
26-63
No
No
Yes
Yes
Output
X42/11[V]
Table 5. 2: Analog outputs
5-2
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
No
Yes
No
No
No
Yes
Yes
Object
ID
Read/
Write
TR200Pa-
rameter
Triggers Bus
Timeout
Object Name
able De-
scription
Yes
tile RAM
Store
No
AV:0
AV:1
AV:2
AV:3
AV:4
AV:5
AV:6
AV:7
AV:8
AV:9
Reference
Speed Act. Value
Bus Feedback1
Bus Feedback2
Bus Feedback3
Motor Voltage
Motor Current
Motor Torque %
DC Link Voltage
Motor Thermal
Heatsink Temper-
ature
W/R
W/R
W/R
W/R
W/R
Read
Read
Read
Read
Read
MRV
MAV
8-94
8-95
8-96
16-12
16-14
16-22
16-30
16-18
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
Yes
No
AV:10
Read
Yes
No
16-34
Yes
No
AV:11
AV:12
AV:13
AV:14
AV:15
Inverter Thermal
Operating Hours
Running Hours
KWh Counter
Power [KW]
Read
Read
Read
Read
Read
Yes
No
No
No
No
No
No
No
No
No
16-35
15-00
15-01
15-02
16-10
Yes
No
No
No
No
No
No
No
No
No
PID Start Speed
[Hz]
PID Proportional
Gain
PID Integral Time
(Sec)
PID Differential
Time (Sec)
AV:16
AV:17
AV:18
AV:19
W/R
W/R
W/R
No
No
No
TR200
TR200
TR200
20-83
20-93
20-94
No
No
No
No
No
No
W/R
W/R
W/R
W/R
W/R
No
No
No
No
No
TR200
TR200
TR200
TR200
TR200
20-95
20-96
20-84
21-15
21-17
No
No
No
No
No
No
No
No
No
No
AV:20 PID Dif. Gain Limit
On Reference
Bandwith
Ext. 1 Setpoint
Ext. 1 Reference
[Unit]
AV:21
AV:22
AV:23
Ext. 1 Feedback
[Unit]
Ext. 1 Proportion-
al Gain
AV:24
W/R
No
TR200
21-18
21-21
No
No
No
No
AV:25
AV:26
AV:27
W/R
W/R
W/R
No
No
No
TR200
Na
Reserved
Ext. 1 Integral
Time (Sec)
Ext. 1 Differential
Time (Sec)
Ext. 1 Dif. Gain
Limit
TR200
21-22
21-23
21-24
No
No
No
No
No
No
AV:28
W/R
No
TR200
AV:29
AV:30
W/R
W/R
No
No
TR200
Na
Reserved
Table 5. 3: Analog values
TR200 BACnet
5-3
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
No
Object
ID
Read/
Write
TR200 Pa-
rameter
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
TR200
AV:31
AV:32
Ext. 2 Setpoint
Ext. 2 Reference
[Unit]
Ext. 2 Feedback
[Unit]
Ext. 2 Proportion-
al Gain
Ext. 2 Integral
Time (Sec)
W/R
W/R
21-35
21-37
No
No
No
No
No
No
No
TR200
TR200
TR200
TR200
TR200
No
No
No
No
No
AV:33
AV:34
AV:35
AV:36
W/R
W/R
W/R
W/R
21-38
21-41
21-42
21-43
No
No
No
No
Ext. 2 Differential
Time
AV:37
AV:38
Ext. 2 Dif. Gain
Ext. 3 Setpoint
Ext. 3 Reference
[Unit]
Ext. 3 Feedback
[Unit]
Ext. 3 Proportion-
al Gain
Ext. 3 Integral
Time (Sec)
W/R
W/R
No
No
TR200
TR200
21-44
21-55
No
No
No
No
AV:39
AV:40
AV:41
AV:42
AV:43
W/R
W/R
W/R
W/R
W/R
No
No
No
No
No
TR200
TR200
TR200
TR200
TR200
21-57
21-58
21-61
21-62
21-63
No
No
No
No
No
No
No
No
No
No
Ext. 3 Differential
Time (Sec)
Ext. 3 Dif. Gain
Limit
Running Bypass
AV:44
AV:45
W/R
No
No
TR200
No
21-64
31-11
No
No
No
No
Read
Table 5. 4: Analog values cont.
5-4
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Binary Input and Output Objects
Change-
able De-
scription
No
Non-vola-
tile RAM
Store
No
Alarm
notifi-
cation
No
No
No
No
No
No
No
Triggers
Bus
Timeout
No
Object
ID
Read/
Write
Object Name
Drive Par.
BI:0
BI:1
BI:2
BI:3
BI:4
BI:5
BI:6
Digital Input 33
Digital Input 32
Digital Input 29
Digital Input 27
Digital Input 19
Digital Input 18
Digital Input 37
Digital Input
X30/2
Digital Input
X30/3
Digital Input
X30/4
Digital Input P
1660/10*
Digital Input P
1660/11*
Digital Input P
1660/12*
Digital Input P
1660/13*
Read
Read
Read
Read
Read
Read
Read
16-60/00
16-60/01
16-60/02
16-60/03
16-60/04
16-60/05
16-60/06
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
BI:7
BI:8
Read
Read
Read
Read
Read
Read
Read
Read
Read
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
16-60/07
16-60/08
16-60/09
16-60/10
16-60/11
16-60/12
16-60/13
16-60/14
16-60/15
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
BI:9
BI:10
BI:11
BI:12
BI:13
BI:14
BI:15
Digital Input P
1660/14*
Digital Input P
1660/15*
Table 5. 5: Binary inputs
Bl:7 - Bl:19 values are only available if the option is installed.
*) Reserved for future options!
TR200 BACnet
5-5
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
No
Object
ID
Read/
Write
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
No
Drive Par.
BO:0
BO:1
Digital Output 27
Digital Output 29
GPIO Output
Term X30/6
GPIO Output
Term X30/7
Relay 1 Output
Relay 2 Output
Option B Relay 1
Output
Option B Relay 2
Output
Option B Relay 3
Output
Reserved Output
P 590/9
Reserved Output
P 590/10*
Reserved Output
P 590/11*
Reserved Output
P 590/12*
Reserved output
P 590/13*
Reserved Output
P 590/14*
Reserved Output
P 590/15*
Option C Relay 1
Output
Option C Relay 2
Output
Option C Relay 3
Output
Option C Relay 4
Output
Option C Relay 5
Output
Option C Relay 6
Output
Option C Relay 7
Output
Option C Relay 8
Output
Reserved Output
P 590/24*
Reserved Output
P 590/25*
W/R
W/R
5-90/00
5-90/01
Yes
Yes
No
No
No
BO:2
BO:3
W/R
W/R
No
No
No
No
5-90/02
5-90/03
No
No
Yes
Yes
BO:4
BO:5
W/R
W/R
No
No
No
No
5-90/04
5-90/05
No
No
Yes
Yes
BO:6
BO:7
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
5-90/06
5-90/07
5-90/08
5-90/09
5-90/10
5-90/11
5-90/12
5-90/13
5-90/14
5-90/15
5-90/16
5-90/17
5-90/18
5-90/19
5-90/20
5-90/21
5-90/22
5-90/23
5-90/24
5-90/25
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
BO:8
BO:9
BO:10
BO:11
BO:12
BO:13
BO:14
BO:15
BO:16
BO:17
BO:18
BO:19
BO:20
BO:21
BO:22
BO:23
BO:24
BO:25
Table 5. 6: Binary outputs
5-6
TR200 BACnet
How to Control the Adjustable Frequency
Drive
*) Reserved for future options!
Change- Non-vola-
Alarm
notifi-
cation
Object
Read/
Write
Triggers Bus
Timeout
Object Name
ID
able De-
scription
tile RAM
Store
Drive Par.
Reserved Output
BO:30
W/R
W/R
W/R
W/R
W/R
W/R
No
No
No
No
No
No
No
No
No
No
No
No
5-90/30
5-90/31
5-90/26
5-90/27
5-90/28
5-90/29
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
P 590/30*
Reserved Output
BO:31
P 590/31*
Reserved Output
BO:36
P 590/26*
Reserved Output
BO:37
P 590/27*
Reserved Output
BO:38
P 590/28*
Reserved Output
BO:39
P 590/29*
Table 5. 7: Binay outputs cont.
*) Reserved for future options!
TR200 BACnet
5-7
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
tile RAM Drive Par.
Store
BACnet op-
tion
CTW
CTW, Bit 3
=0
BV:0
BV:1
BV:2
Com. Fault
Start
R
No
No
No
NA
Yes
No
No
No
Yes
Yes
W/R
W/R
No
Coasting
No
CTW bit
15=1
CTW bit 0
=1
CTW bit 07
= 1
BV:3
BV:4
BV:5
BV:6
BV:7
CW/CCW
Jog
W/R
W/R
W
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
NO
NO
Reset
Reset Kwh Coun-
ter
Reset Running
Hours Counter
Drive Ready
Reverse
W
P15-06
P15-07
W
BV:10
BV:11
R
R
No
No
NA
NA
STW Bit 01
STW Bit 15
No
No
No
No
Speed = Refer-
ence
BV:12
R
No
NA
STW Bit 08
No
No
BV:13
BV:14
BV:15
BV:16 -20
BV:21
BV:22
Bus Control
Tripped
Triplock
R
R
R
R
R
R
No
No
No
No
No
No
NA
NA
NA
STW Bit 09
STW Bit 03
STW Bit 06
No
Yes
Yes
No
No
No
Reserved
ECB Test Mode
ECB Drive mode
ECB Aut. Bypass
Enable
NA
NA
31-10/00
31-10/01
No
No
No
No
BV:23
R
No
NA
31-10/02
No
No
ECB Bypass
Mode
ECB State
ECB Overload
Trip
BV:24
BV:25
BV:26
R
R
R
No
No
No
NA
NA
NA
31-10/03
31-10/05
31-10/06
No
Yes
Yes
No
No
No
BV:27
BV:28
M2 Fault
M3 Fault
R
R
No
No
NA
NA
31-10/07
31-10/08
Yes
Yes
No
No
ECB External In-
terlock
ECB Manual
Override
BV:29
R
No
NA
NA
31-10/09
31-10/10
Yes
No
No
No
BV:30
BV:31
R
R
No
No
Reserved
Table 5. 8: Binary values
5-8
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
NA
Drive Par.
BV:40
BV:41
BV:42
BV:43
BV:44
BV:45
BV:46
BV:47
BV:48
BV:49
BV:50
BV:51
BV:52
Brake Check
Pwr. Card Temp
Ground Fault
Ctrl.Card Temp
Ctrl. Word TO
Overcurrent
Torque Limit
Motor TH Over
Motor TH Over
Inverter Overld.
DC undervolt
DC overvolt
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
16-90/00
16-90/01
16-90/02
16-90/03
16-90/04
16-90/05
16-90/06
16-90/07
16-90/08
16-90/09
16-90/10
16-90/11
16-90/12
16-90/13
16-90/14
16-90/15
16-90/16
16-90/17
16-90/18
16-90/19
16-90/20
16-90/21
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
Short Circuit
No
NA
BV:53 Soft-charge fault
BV:54 Line Power Fault
No
NA
No
NA
BV:55
BV:56
BV:57
BV:58
BV:59
BV:60
BV:61
AMA Not OK
Live Zero Error
Internal Fault
Brake Overload
U Phase Loss
V Phase Loss
W Phase Loss
Serial Communi-
cation Bus Fault
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
No
NA
BV:62
R
No
NA
16-90/22
Yes
BV:63 24 V Supply Low
BV:64 Line Power Fault
BV:65 1.8 V Supply Low
R
R
R
R
R
R
R
R
R
No
No
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
NA
NA
16-90/23
16-90/24
16-90/25
16-90/26
16-90/27
16-90/28
16-90/29
16-90/30
16-90/31
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
BV:66
BV:67
BV:68
BV:69
BV:70
BV:71
Brake Failure
Brake IGBT
Option Changed
Drive Initialized
Safe Stop
Brake Low
Service Trip P
1691/0
BV:72
BV:73
BV:74
BV:75
BV:76
R
R
R
R
R
No
No
No
No
No
NA
NA
NA
NA
NA
16-91/00
16-91/01
16-91/02
16-91/03
16-91/04
Yes
Yes
Yes
Yes
Yes
Service Trip P
1691/1
Service Trip P
1691/2
Service Trip P
1691/3
Service Trip P
1691/4
BV:77
BV:78
BV:79
No Flow
Dry Pump
Curve End
R
R
R
No
No
No
NA
NA
NA
16-91/05
16-91/06
16-91/07
Yes
Yes
Yes
Table 5. 9: Binary values cont.
TR200 BACnet
5-9
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
Yes
Yes
Yes
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
NA
Drive Par.
BV:80
BV:81
BV:82
BV:83
Broken Belt
Discharge High
Start Fault
Speed Limit
State Fault P
1691/12
State Fault P
1691/13
State Fault P
1691/14
R
R
R
R
16-91/08
16-91/08
16-91/10
16-91/11
No
NA
No
NA
No
NA
Yes
BV:84
BV:85
BV:86
BV:87
BV:88
R
R
R
R
R
No
No
No
No
No
NA
NA
NA
NA
NA
16-91/12
16-91/13
16-91/14
16-91/15
16-91/16
Yes
Yes
Yes
Yes
Yes
State Fault P
1691/15
KTY Temperature
Error
BV:89
BV:90
BV:91
BV:92
BV:93
BV:94
BV:95
BV:96
BV:97
BV:98
BV:99
BV:100
BV:101
BV:102
BV:103
BV:104
BV:105 Pwr. Card Temp
BV:106 Ground Fault
BV:107 Ctrl. Card Temp
BV:108
BV:109
BV:110
BV:111
Drive Fan Error
ECB Error
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
16-91/17
16-91/18
16-91/19
16-91/20
16-91/21
16-91/22
16-91/23
16-91/24
16-91/25
16-91/26
16-91/27
16-91/28
16-91/29
16-91/30
16-91/31
16-92/00
16-92/01
16-92/02
16-92/03
16-92/04
16-92/05
16-92/06
16-92/07
16-92/08
16-92/09
16-92/10
16-92/11
16-92/12
16-92/13
16-92/14
16-92/15
16-92/16
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Alarm 1692/19
Alarm 1692/20
Alarm 1692/21
Alarm 1692/22
Alarm 1692/23
Alarm 1692/24
Alarm 1692/25
Alarm 1692/26
Alarm 1692/27
Alarm 1692/28
Alarm 1692/29
Alarm 1692/30
Alarm 1692/31
Brake Check
Crtl. Word TO
Overcurrent
Torque Limit
Motor Th Over
BV:112 Motor ETR Over
BV:113 Inverter Overld.
BV:114
BV:115
BV:116 DC Voltage Low
BV:117 DC Voltage high
BV:118
BV:119
BV:120
DC undervolt
DC overvolt
Line ph. loss
No Motor
Live Zero Error
Table 5. 10: Binary values cont.
5-10
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
Yes
Yes
Yes
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
NA
Drive Par.
BV:121
BV:122
BV:123
BV:124
BV:125
10V low
R
R
R
R
R
16-92/17
16-92/18
16-92/19
16-92/20
16-92/21
Brake Overload
Brake Resistor
Brake IGBT
No
NA
No
NA
No
NA
Yes
Yes
Speed Limit
No
NA
Serial Communi-
cation Bus Fault
BV:126
R
No
NA
16-92/22
Yes
BV:127 24V Supply Low
R
R
R
R
R
R
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
16-92/23
16-92/24
16-92/25
16-92/26
16-92/27
16-92/28
Yes
Yes
Yes
Yes
Yes
Yes
BV:128
BV:129
BV:130
BV:131
BV:132
Line failure
Current Limit
Low Temp
Voltage Limit
Encoder loss
Output Freq. Lim-
it
BV:133
R
No
NA
16-92/29
Yes
BV:134
BV:135
BV:136
BV:137
BV:138
Safe Stop
R
R
R
R
R
No
No
No
No
No
NA
NA
NA
NA
NA
16-92/30
16-92/31
16-93/00
16-93/01
16-93/02
Yes
Yes
Yes
Yes
Yes
Ext. Status
Start Delayed
Stop Delayed
Clock Failure
Fire Mode was
Active
BV:139
BV:140
R
R
No
No
NA
NA
16-93/03
16-93/04
Yes
Yes
Reserved,
P1693/04
BV:141
BV:142
BV:143
BV:144
BV:145
No Flow
R
R
R
R
R
No
No
No
No
No
NA
NA
NA
NA
NA
16-93/05
16-93/06
16-93/07
16-93/08
16-93/09
Yes
Yes
Yes
Yes
Yes
Dry Pump
End of Curve
Belt Broken
Discharge High
Reserved, P
1693/10
Reserved, P
1693/11
Reserved, P
1693/12
Reserved, P
1693/13
Reserved, P
1693/14
Reserved, P
1693/15
Reserved, P
1693/16
BV:146
BV:147
BV:148
BV:149
BV:150
BV:151
BV:152
R
R
R
R
R
R
R
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
16-93/10
16-93/11
16-93/12
16-93/13
16-93/14
16-93/15
16-93/16
Yes
Yes
Yes
Yes
Yes
Yes
Yes
BV:153 KTY Temperature
BV:154 Drive Fan Failure
R
R
R
No
No
No
NA
NA
NA
16-93/17
16-93/18
16-93/19
Yes
Yes
Yes
BV:155
ECB Failure
Table 5. 11: Binary values cont.
TR200 BACnet
5-11
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
tile RAM
Store
Drive Par.
Reserved, P
1693/20
Reserved, P
1693/21
Reserved, P
1693/22
Reserved, P
1693/23
Reserved, P
1693/24
Reserved, P
1693/25
Reserved, P
1693/26
Reserved, P
1693/27
BV:156
BV:157
BV:158
BV:159
BV:160
BV:161
BV:162
BV:163
BV:164
BV:165
R
R
R
R
R
R
R
R
R
No
No
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
NA
NA
16-93/20
16-93/21
16-93/22
16-93/23
16-93/24
16-93/25
16-93/26
16-93/27
16-93/28
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Reserved, P
1693/28
Reserved, P
1693/29
R
R
R
No
No
No
NA
NA
NA
16-93/29
16-93/30
16-93/31
Yes
Yes
Yes
BV:166 PTC Temperature
Reserved, P
1693/31
BV:167
BV:168 Ramping Active
R
R
R
R
R
R
R
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
16-94/00
16-94/01
16-94/02
16-94/03
16-94/04
16-94/05
16-94/06
No
No
No
No
No
No
No
BV:169
BV:170
BV:171
BV:172
BV:173
BV:174
AMA Running
Start CW/CCW
Slowdown
Catch Up
Feedback High
Feedback Low
Output Current
High
BV:175
BV:176
R
R
No
No
NA
NA
16-94/07
16-94/08
No
No
Output Current
Low
BV:177 Output Freq High
BV:178 Output Freq Low
BV:178 Brake Check OK
R
R
R
R
No
No
No
No
NA
NA
NA
NA
16-94/09
16-94/10
16-94/11
16-94/12
No
No
No
No
BV:180
Brake Max
Table 5. 12: Binary values cont.
5-12
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Change- Non-vola-
Alarm
notifi-
cation
No
Object
ID
Read /
Write
Triggers Bus
Timeout
Object Name
able De-
scription
No
tile RAM
Store
NA
Drive Par.
BV:181
BV:182
Braking
Out of Speed
range
R
R
16-94/13
16-94/14
No
NA
No
BV:183
BV:184
OVC Active
AC Brake
R
R
No
No
NA
NA
16-94/15
16-94/16
No
No
Password Time-
lock
BV:185
R
No
NA
16-94/17
No
BV:186 Password Status
R
R
R
R
No
No
No
No
NA
NA
NA
NA
16-94/18
16-94/19
16-94/20
16-94/21
No
No
No
No
BV:187
BV:188
BV:189
Reference High
Reference Low
Reference Site
Reserved,
16-94/22
BV:190
BV:191
BV:192
BV:193
BV:194
BV:195
BV:196
BV:197
BV:198
BV:199
R
R
R
R
R
R
R
R
R
R
No
No
No
No
No
No
No
No
No
No
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
16-94/22
16-94/23
16-94/24
16-94/25
16-94/26
16-94/27
16-94/28
16-94/29
16-94/30
16-94/31
No
No
No
No
No
No
No
No
No
No
Reserved,
16-94/23
Reserved,
16-94/24
Reserved,
16-94/25
Reserved,
16-94/26
Reserved,
16-94/27
Reserved,
16-94/28
Reserved,
16-94/29
Reserved,
16-94/30
Reserved,
16-94/31
Table 5. 13: Binary values cont.
Multi-state Input and Output Objects
Multi-state Variable
Change-
able De-
scription
Non-vola-
tile RAM
Store
Object
ID
Read/
Write
Alarm notifi- Triggers Bus
Object Name
Drive Par.
cation
Timeout
SL LC Controller
State
MSV:0
MSV:1
R
No
No
Non
Non
16-38
No
No
Bit 13 & 14
in CTW
Set-up selection
W/R
No
No
TR200 BACnet
5-13
How to Control the Adjustable Frequency
Drive
Mailbox variable
Change- Non-vola-
Object
ID
Read/
Write
Alarm notifi- Triggers Bus
Object Name
able De-
scription
tile RAM
Store
Drive Par.
cation
Timeout
PCV part of
the send
drive mes-
sage
PCV part of
the receive
drive mes-
sage
MBV:0
MBV:1
Mailbox Write
W/R
R
No
No
Non
Non
No
No
Mailbox Read
No
No
Real Time Clock Variable
The adjustable frequency drive has a built-in real-time clock. The standard real-time clock has no battery backup
function (for real-time clock battery backup, selected TR200 option modules are available), which will lead to a
time stop if the drive is unpowered. Some BACnet Masters can be programmed to send out the date and time
as a broadcast message on a regular basis. The BACnet will update the real-time clock of the drive if it receives
this type of message: “Message”.
5-14
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Adjustable Frequency Drive Feedback to Network
The BACnet option provides several output variables (NVOs) to the network, containing important adjustable
frequency drive, motor and I/O feedback data. The BACnet option transmits bound network variables only and
sends feedback data when there is a change in value.
Influence of the digital input terminals upon the drive control mode, par.8-50 Coasting Select to par.8-56 Preset
The influence of the digital input terminals upon control of the adjustable frequency drive can be programmed
NOTE
par.8-01 Control Site overrules the settings in parameters 8-50 to 8-56 and Terminal 37, Safe Stop overrules any
parameter.
Each of the digital input signals can be programmed to logic AND, logic OR, or to have no relation to the cor-
responding bit in the control word. In this way, a specific control command, i.e., stop / coast, can be initiated by
the serial communication bus only, serial communication bus AND Digital Input, or serial communication bus
OR digital input terminal.
CAUTION
In order to control the adjustable frequency drive via BACnet, par.8-50 Coasting Select must be set to either Bus [1],
or to Logic AND [2] and par.8-01 Control Site must be set to Digital and ctrl. word [0] or Controlword only [2].
More detailed information and examples of logical relationship options are provided in the Troubleshooting
chapter.
TR200 BACnet
5-15
How to Control the Adjustable Frequency
Drive
Object / Property Support Matrix
The following table summarizes the object types and properties supported:
Binary Binary Binary Analog Analog Analog
Event
notifi-
cation
class
Multi-
stage
value
Property
Device
File
input
output
value
input
output value
Object
identifier
Object
Name
Object
Type
System
Status
Vendor
Name
Vendor
Identifier
Model
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Name
Firmware
Revision
Appl. Soft-
ware Revi-
sion
X
Location
Descrip-
tion
X
X
X
X
X
X
X
X
X
X
X
Protocol
Version
Protocol
Revision
Services
Supported
Object
X
X
X
Types Sup-
ported
X
Object List
Max. AP-
DU Length
Segmenta-
tion Sup-
port
X
X
X
Local Time
Local Date
APDU
Timeout
Number
APDU Re-
tries
X
X
X
X
Max Mas-
ter
X
X
Max Info
Frames
Device Ad-
dress Bind-
ing
X
X
Database
Revision
5-16
TR200 BACnet
How to Control the Adjustable Frequency
Drive
Object / Property Support Matrix, continued..
Event
Multi-
Binary Binary Binary Analog Analog Analog
notifi-
cation
class
Property
Device
stage
value
File
input output value input
output value
Present Value
Status Flags
Event State
Reliability
Out-of-Serv-
ice
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Number of
States
State Text
Units
Time Delay
Notification
Class
X
X
X
X
X
X
X
X
X
High Limit
Low Limit
Deadband
Limit Enable
Event Enable
Acked Transi-
tions
Notify Type
Event Time
Stamp
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Priority Array
Priority
X
X
X*
X*
X
X
??
X
X
X
X
X
ACk Required
Recipient List
# of Notifica-
tion Class
Relinquish De-
fault
X
??
Polarity
X
X
X
X
X
X
Active Text
Inactive Text
File type
X
X
X
X
File size
Modification
Date
X
Archive
X
X
Read Only
File Access
Method
X
*For commandable values only
TR200 BACnet
5-17
How to Control the Adjustable Frequency
Drive
5-18
TR200 BACnet
Parameters
Parameter Overview
Parameter List
Conver-
sion index type
Data
Nr.
8-01
Title
Default value
Range
[0 - 2]
Control Site
Dig. and ctrl. word [0]
Drive RS485 [0]
1 s
-
-
5
5
7
5
5
5
5
5
8-02
8-03
8-04
8-05
8-06
8-07
8-10
8-30
8-31
8-32
8-33
8-35
8-36
8-37
8-50
8-52
8-53
8-54
8-55
8-56
8-70
8-72
8-73
8-74
8-75
Control Source
[0 - 4]
Control Timeout Time
Control Timeout Function
End-of-timeout Function
Reset Control Timeout
Diagnosis Trigger
Control Profile
0.1–18000
[0 - 10]
[0 - 1]
[0 - 1]
[0 - 3]
- 1
-
Off [0]
Hold set-up [0]
Do not reset [0]
Disable [0]
Drive profile [0]
Drive
-
-
-
-
[0 - x]
Protocol
Address
Baudrate
1
[0 – 255]
[0 – 7]
38,400
No Parity, 1 Stop Bit
10mS
5000mS
25.00mS
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
1
Parity/Stop Bits
Minimum Response Delay
Max Response Delay
Max Inter-Char Delay
Coasting Select
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[0 - 3]
[1-4194304]
[1-127]
-
-
-
-
-
-
-
-
5
5
5
5
5
5
DC Brake Select
Start Select
Reversing Select
Set-up Select
Preset Reference Select
BACnet Device Instance
MS/TP Max Masters
MS/TP Max Info Frames
“I am” Service
127
Once at power-up [0]
“admin”
[0-1]
String[19]
-
Initialization Password
Table 6. 1: BACnet specific parameter list
Please refer to the TR200 Drive Instruction Manual, MG.12.HX.YY for a comprehensive parameter list or to the
TR200 Drive Programming Guide, MG.12.JX.YY for detailed descriptions of parameters.
TR200 BACnet
6-1
Parameters
Parameter Description
8-** Comm. and Options
Parameter group for configuring communications and options.
8-01 Control Site
Option:
Function:
[0] *
[1]
Digital and ctrl. word
Digital only
Control by using both digital input and control word.
Control by using digital inputs only.
[2]
Control word only
Control by using control word only.
8-02 Control Source
Option:
Function:
Select the source of the control word: one of two serial interfaces or four
installed options. During initial power-up, the adjustable frequency drive
automatically sets this parameter to Option A [3] if it detects a valid serial
communication bus option installed in slot A. If the option is removed,
the adjustable frequency drive detects a change in the configuration, sets
Drive Port, and the adjustable frequency drive then trips. If an option is
not change but the adjustable frequency drive will trip and display: Alarm
67 Option Changed.
[0]
None
[1]
FC RS-485
FC USB
[2]
[3] *
[4]
Option A
Option B
Option C0
Option C1
External Can
[5]
[6]
[30]
NOTE: This parameter cannot be adjusted while the motor is running.
8-03 Control Timeout Time
Range:
Function:
60.0 s* [1.0 - 18000.0 s]
Enter the maximum time expected to pass between the reception of two
consecutive messages. If this time is exceeded, it indicates that the serial
In LonWorks, the following variables will trigger the Control Word Time
parameter:
nviStartStop
nviReset Fault
6-2
TR200 BACnet
Parameters
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option:
Function:
Select the timeout function. The timeout function is activated when the
control word fails to be updated within the time period specified in par.
Metasys N2 protocol.
[0] *
[1]
Off
Freeze output
Stop
[2]
[3]
Jogging
[4]
Max. speed
Stop and trip
Select setup 1
Select setup 2
Select setup 3
Select setup 4
N2 Override Release
[5]
[7]
[8]
[9]
[10]
[20]
In LonWorks, the timeout function is also activated when the following SNVTs fail to be updated within the time
nviStartStop
nviDrvSpeedStpt
nviRefPcnt
nviReset Fault
nviControlWord
nviRefHz
8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control word following a timeout.
set to [Set-up 1-4].
[0]
Hold set-up
the adjustable frequency drive resumes its original set-up.
[1] *
Resume set-up
Resumes the set-up active prior to the timeout.
TR200 BACnet
6-3
Parameters
8-06 Reset Control Timeout
Option:
Function:
This parameter is active only when the choice Hold set-up [0] has been
[0] *
[1]
Do not reset
Do reset
set-up 1-4] following a control timeout.
Returns the adjustable frequency drive to the original set-up following a
control word timeout. When the value is set to Do reset [1], the adjustable
frequency drive performs the reset and then immediately reverts to the
Do not reset [0] setting.
8-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for LonWorks.
[0] *
[1]
Disable
Trigger on alarms
Trigger alarm/warn.
[2]
8-10 Control Profile
Option:
Function:
Select the interpretation of the control and status words corresponding
to the installed serial communication bus. Only the selections valid for
the serial communication bus installed in slot A will be visible in the
keypad display.
[0] *
[1]
FC profile
PROFIdrive profile
ODVA
[5]
[7]
CANopen DSP 402
8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the
control card.
Parameter group 8-7* is only visible when Adjustable Frequency Drive
Option [9] is chosen.
[0] *
[1]
FC
Communication according to the FC protocol as described in the TR200
Design Guide, RS 485 Installation and Set-up .
FC MC
Same as FC [0] but to be used when downloading SW to the adjustable
frequency drive or uploading dll file (covering information regarding pa-
rameters available in the adjustable frequency drive and their inter-
dependencies) to Trane Drive Utility, TDU.
[2]
[3]
Modbus RTU
Metasys N2
Communication according to the Modbus RTU protocol as described in
the TR200 Design Guide, RS 485 Installation and Set-up .
Communication protocol. The N2 software protocol is designed to be
general in nature in order to accommodate the unique properties each
6-4
TR200 BACnet
Parameters
device may have. Please see separate manual TR200 MetasysMG.
12.NX.YY.
[4]
[9]
FC Option
To be used when a gateway is connected to the integrated RS 485 port,
e.g., the BACnet gateway.
The following changes will take place:
-The address for the adjustable frequency drive port will be set to 1 and
network, e.g., BACnet.
-Baud rate for the Drive port will be set to a fixed value (115,200 Baud)
and par.8-32 Baud Rate is now used to set the baud rate for the network
port (e.g., BACnet) on the gateway.
[20]
NOTE: Further details can be found in the Metasys manual.
8-31 Address
Range:
Function:
1. N/A* [1. - 126. N/A]
Enter the address for the adjustable frequency drive (standard) port.
Valid range: 1–126.
8-32 Baud Rate
Option:
Function:
[0]
[1]
[2]
[3]
[4] *
[5]
[6]
[7]
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud
76800 Baud
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
able Frequency Drive Port. For some of the protocols, not all options will
be visible. Default depends on the protocol selected.
[0] *
[1]
Even Parity, 1 Stop Bit
Odd Parity, 1 Stop Bit
No Parity, 1 Stop Bit
No Parity, 2 Stop Bits
[2]
[3]
TR200 BACnet
6-5
Parameters
8-35 Minimum Response Delay
Range:
Function:
10. ms* [5. - 10000. ms]
Specify the minimum delay time between receiving a request and trans-
mitting a response. This is used for overcoming modem turnaround
delays.
8-36 Max Response Delay
Range:
Function:
10001. [11. - 10001. ms]
ms*
Specify the maximum permissible delay time between transmitting a re-
quest and receiving a response. Exceeding this delay time will cause
control word timeout.
8-37 Max Inter-Char Delay
Range:
Function:
25.00
ms*
[0.00 - 35.00 ms]
Specify the maximum permissible time interval between receiving two
bytes. This parameter activates timeout if transmission is interrupted.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the terminals (digital input)
and/or via the bus.
[0]
[1]
Digital input
Bus
Activates Start command via a digital input.
Activates Start command via the serial communication port or serial
communication option.
[2]
Logic AND
Logic OR
Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] *
Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals (digital input) and/or via
the serial communication bus.
[0]
[1]
Digital input
Bus
Activates Start command via a digital input.
Activates Start command via the serial communication port or serial
communication option.
[2]
Logic AND
Logic OR
Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] *
Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
6-6
TR200 BACnet
Parameters
8-53 Start Select
Option:
Function:
Select control of the adjustable frequency drive start function via the ter-
minals (digital input) and/or via the serial communication bus.
[0]
[1]
Digital input
Bus
Activates Start command via a digital input.
Activates Start command via the serial communication port or serial
communication option.
[2]
Logic AND
Logic OR
Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] *
Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
8-54 Reverse Select
Option:
Function:
Select control of the adjustable frequency drive reverse function via the
terminals (digital input) and/or via the serial communication bus.
[0] *
[1]
Digital input
Bus
Activates Reverse command via a digital input.
Activates Reverse command via the serial communication port or serial
communication option.
[2]
[3]
Logic AND
Logic OR
Activates Reverse command via the serial communication bus/serial
communication port, AND additionally via one of the digital inputs.
Activates Reverse command via the serial communication bus/serial
communication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
8-55 Set-up Select
Option:
Function:
Select control of the adjustable frequency drive set-up selection via the
terminals (digital input) and/or via the serial communication bus.
[0]
[1]
Digital input
Bus
Activates the set-up selection via a digital input.
Activates the set-up selection via the serial communication port or serial
communication option.
[2]
Logic AND
Logic OR
Activates the set-up selection via the serial communication bus/serial
communication port, AND additionally via one of the digital inputs.
[3] *
Activate the set-up selection via the serial communication bus/serial
communication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
TR200 BACnet
6-7
Parameters
8-56 Preset Reference Select
Option:
Function:
Select control of the adjustable frequency drive Preset Reference selec-
tion via the terminals (digital input) and/or via the serial communication
bus.
[0]
[1]
Digital input
Bus
Activates Preset Reference selection via a digital input.
Activates Preset Reference selection via the serial communication port
or serial communication option.
[2]
Logic AND
Logic OR
Activates Preset Reference selection via the serial communication bus/
serial communication port, AND additionally via one of the digital inputs.
[3] *
Activates the Preset Reference selection via the serial communication
bus/serial communication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01 Control Site is set to [0] Digital and control word.
8-70 BACnet Device Instance
Range:
Function:
1 N/A* [0 - 4194304 N/A]
Enter a unique ID number for the BACnet device.
8-72 MS/TP Max Masters
Range:
Function:
127 N/ [0 - 127 N/A]
A*
Define the address of the master which holds the highest address in this
network. Decreasing this value optimizes polling for the token.
8-73 MS/TP Max Info Frames
Range:
Function:
1 N/A* [1 - 65534 N/A]
Define how many info/data frames the device is allowed to send while
holding the token.
8-74 "Startup I am"
Option:
Function:
[0] *
[1]
Choose whether the device should send the "I-Am" service message only
at power-up or continuously with an interval of approx. 1 min.
8-75 Initialization Password
Range:
Function:
0 N/A* [0 - 0 N/A]
Enter the password needed for execution of Drive Re-initialization from
BACnet.
6-8
TR200 BACnet
Troubleshooting
Alarm, Warning and Extended Status Word
Alarm and Warning Messages
General
There is a clear distinction between alarms and warnings. In the event of an alarm, the adjustable frequency
drive will enter a fault condition. After the cause for the alarm has been cleared, the master must acknowledge
the alarm message in order to start operation of the adjustable frequency drive again. A warning, on the other
hand, may appear when a warning condition arises, then disappear when conditions return to normal without
interfering with the process.
Alarm Word and Warning Word are shown on the display in Hex format. If there is more than one warning or
alarm, a sum of all warnings or alarms will be shown. Warning Word and Alarm Word are displayed in par.
16-90 to 16-95. For more information on the individual alarms and warnings, please refer to: TR200 Design
Guide.
Warnings
All warnings within the adjustable frequency drive are represented by a single bit within a warning word. A
warning word is always an action parameter. Bit status FALSE [0] means no warning, while bit status TRUE [1]
means warning. Each bit status has a corresponding text string message. In addition to the Warning Word
message, the master will also be notified via a change to bit 7 in the status word.
Alarms
Following an alarm message the adjustable frequency drive will enter a fault condition. Only after the fault has
been rectified and the master has acknowledged the alarm message by setting bit 3 in the Control Word, can
the adjustable frequency drive resume operation. All alarms within the TR200 are represented by a single bit
within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no alarm, while
bit status TRUE [1] means alarm.
TR200 BACnet
7-1
Troubleshooting
Alarm Words
Alarm word, par.16-90 Alarm Word
Alarm word 2, par.16-91 Alarm word 2
Bit
(Hex)
Alarm Word
(par.16-90 Alarm Word)
Brake check
Power card overtemperature
Ground fault
Ctrl. card overtemperature
Control word timeout
Overcurrent
Bit
(Hex)
00000001
00000002
Alarm Word 2
(par.16-91 Alarm word 2)
Service Trip, read / Write
Reserved
Service Trip, Typecode /
Spare part
Reserved
Reserved
No Flow
Dry Pump
End of Curve
Broken Belt
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Fans error
ECB error
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Torque limit
Motor thermistor overtemp.
Motor ETR overtemperature
Inverter overloaded
DC link undervoltage
DC link overvoltage
Short circuit
Soft-charge fault
Line phase loss
AMA not OK
Live zero error
Internal fault
Brake overload
Motor phase U is missing
Motor phase V is missing
Motor phase W is missing
Serial communication bus
fault
24 V supply fault
Line failure
1.8 V supply fault
Brake resistor short circuit
Brake chopper fault
Option change
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Drive initialized
Safe Stop
Not used
7-2
TR200 BACnet
Troubleshooting
Warning Words
Warning word , par.16-92 Warning Word
Warning word 2, par.16-93 Warning word 2
Bit
(Hex)
Warning Word
(par.16-92 Warning Word)
Brake check
Warning Word 2
(par.16-93 Warning word
2)
Bit
(Hex)
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
Power card overtemperature
Ground fault
Ctrl. card overtemperature
Control word timeout
Overcurrent
00000001
00000002
00000004
00000008
00000010
00000020
00000040
00000080
00000100
00000200
00000400
00000800
00001000
00002000
00004000
00008000
00010000
00020000
00040000
00080000
00100000
00200000
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
Start Delayed
Stop Delayed
Clock Failure
Reserved
Reserved
No Flow
Dry Pump
End of Curve
Broken Belt
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Fans warning
ECB warning
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Torque limit
Motor thermistor overtemp.
Motor ETR overtemperature
Inverter overloaded
DC link undervoltage
DC link overvoltage
DC link voltage low
DC link voltage high
Line phase loss
No motor
Live zero error
10 V low
Brake resistor power limit
Brake resistor short circuit
Brake chopper fault
Speed limit
Serial Communication Bus
comm. fault
24 V supply fault
Line failure
Current limit
Low temperature
Voltage limit
Encoder loss
Output frequency limit
Not used
Not used
00400000
00800000
01000000
02000000
04000000
08000000
10000000
20000000
40000000
80000000
TR200 BACnet
7-3
Troubleshooting
LED Status
Check the LEDs. The two bi-color LEDs on the BACnet card indicate the status of BACnet communication.
LED 1: Net Status
Phases
Status
Bi-color LED
Power On. Hardware Not OK
Red
Self test
Gree
n
Gree
n
Red
▂█▂█▂█▂█▂█
Running Module OK
Recoverable fault
Data ex-
change
Device communicating.
Gree
n
LED 2: Module Status
Phases
Power
On.
Status
Bi-color LED
Unrecoverable fault drive is not re- Red
sponding on internal bus
Self test configuration takes place Gree
n
Running Module OK
Gree
n
Red
Recoverable fault
• Configuration not OK, e.g, P830
• Drive tripped
7-4
TR200 BACnet
|