GEH-5101 INSTALLATION INSTRUCTIONS  
300- Line Lighting Contractors CR360L  
For 100 Amperes Continuous Rating  
Caution: Before instaꢀꢁꢂg in nuclꢭar applicatin, dꢍterminꢍ  
that thꢭ prdct ls intendd fr sch usꢍ.  
Warning: Discnect pꢫwꢭr beforꢭ ꢃꢄꢅꢆꢇꢈꢉꢊꢋ ꢫr ꢌꢍꢎꢏꢐꢑꢒꢓꢔ  
Ratings Open And Enclosed  
Continuous-100 Amperes Per Pole Maximum  
Features  
Horizontal straighꢃ-line motion makes contactor compacꢃ, easy  
to mainꢃain.  
• Strongbox coil.  
Straight-through wiring.  
Large combination knockouts.  
Figure 1. 100 ampere lighting contactor, CA360L  
Oversized power terminals will accomodate p ꢃo 1/0 wire.  
Maintenance  
1. Keep magnet mating surfaces free of any accumulated dirt or  
Installation  
dust.  
Before connecting contactor to power supply:  
1. Remove all packing.  
2. DO NOT OIL OR GREASE the magnemaꢃing surfaces.  
3. The silver-cadmium oxide contacts need only be replaced when  
nearly al! tip maꢃerial is gone and contact tip support material is  
exposed. DO NOT ꢕꢖE the contacts. Filing or otherwise dressing  
he conꢃacts reslts in lost tip maꢃerial and reduces contact liꢀe.  
4. Terminal tightness should be checked period!ca!!y as part of  
preventive mainenance. Many users wih average conditions find  
an annual check is satisfactory. Any point showing evidence of  
heaing shold immediaely be checked for tightness.  
2. Clean magnemating surfaces.  
3. Operate movable magneꢃ and operating arm by pressing on the  
nameplate to assure free movement.  
4. Mouncontactor on a strdy vertical support.  
5. Be certain wiring connections are tight.  
6. Give installation a final check for conformance with codes, branch  
circuiprotection and remove any foreign material from enclosꢁre.  
A!so check to see hat no tools have been leꢀꢃ in panel during in·  
.stallation. Review diagrams for intended operation and ꢀꢁꢂcꢃꢄoꢅꢆ  
7. Before energizing, make final check to see that all power lines  
and terminals, are free of metal or pieces of wire ꢃhat could  
cause shorts to other pars or ground and additionally thaꢃ wiring  
and equipmenon load side of contacor is free from grounds  
and shorts. An ohmmeter or oher means, as appropriate, is  
recommended.  
Operation  
When energizing, be certain -all equipmenis ready for power and  
that al! personnel are clear. Always observe all safety rules when  
operating this equipmen.  
ꢗꢘꢙꢚ: The pꢍnig f the ꢛꢜꢝꢞꢟ circit protꢽctive dvice may  
ban indꢨcatin tht ꢇ ꢠꢡꢢꢣ has been interrptd. Fꢤꢥꢦꢧꢨꢩꢪ this r  
any thr vidnce f faut or unintrrptd ꢫꢬꢭꢮꢯꢰꢱꢲꢒꢳ cꢦꢒditin,  
the ꢴꢵꢶꢦꢷꢸꢒꢹ mst ꢛꢭ dnꢍ ꢺꢍꢻꢼꢽ ꢮꢍenrizintprvidcntinued  
prtectin ginst ꢾꢿ ꢦr shck hazard.  
Disconnect All Power  
1. Examine all curren-carrying parts and other components of he  
Before Servicing.  
controller and replace if damaged.  
Read Instructions  
For This  
Equipment.  
2. Examine al! conacts to make certain hey are not welded.  
Separate or isolated control circuis must be examined in the  
same manner.  

Nokia 3586i User Manual
LG Electronics P990HN User Manual
Krups Coffeemaker KM4055 User Manual
IBM 19K4260 User Manual
Hitachi Travelstar HTS722016K9SA00 User Manual
Hamilton Beach 840069400 User Manual
Freud Tools SD500 Series User Manual
Creek Audio Destiny User Manual
Bunn AXIOM BREWWISE 391310004B User Manual
Antec Quiet Computing 0761345 02220 0 User Manual