ABB ATS022 User Manual

Doc. No. 1SDH000760R0002 - L5785  
Automatic transfer switch ATS022  
Installation and operating instructions  
Contents  
Installation and operating instructions, ATS022  
Contents  
1.  
Safety notes....................................................................................................................... 4  
2.  
2.1.  
2.2.  
Explanation of abbreviations and terms ......................................................................... 5  
General information.......................................................................................................................5  
Times.............................................................................................................................................5  
3.  
3.1  
3.2  
Introduction........................................................................................................................ 6  
Product overview...........................................................................................................................6  
Application scenarios....................................................................................................................6  
4.  
Applications of device ATS022......................................................................................... 8  
Switching Main Line – Emergency Line (2CBs).............................................................................8  
Switching Main Line – Emergency generator (2CBs) ....................................................................9  
Non priority loads control (NPL) ..................................................................................................10  
Control of two independent power supply lines separated by Tie (3CBs Bus Tie).....................14  
Automatic switching without inverse procedure .........................................................................15  
Line Priority Selection..................................................................................................................16  
4.1  
4.2  
4.3  
4.4  
4.5  
4.6  
5.  
Using the automatic transfer switch ............................................................................. 17  
Interface.......................................................................................................................................17  
LED indicators.............................................................................................................................18  
Keypad keys................................................................................................................................19  
Setting the operating modes.......................................................................................................20  
Manual mode...............................................................................................................................20  
Automatic mode..........................................................................................................................20  
Graphic Display...........................................................................................................................21  
LN1 and LN2 lines status indication............................................................................................22  
Browsing through the Menu........................................................................................................22  
Using pushbuttons in manual mode ...........................................................................................26  
Test Modes..................................................................................................................................26  
5.1  
5.2  
5.3  
5.4  
5.4.1  
5.4.2  
5.5  
5.5.1  
5.5.2  
5.6  
5.7  
6.  
6.1  
6.2  
Input and output signals................................................................................................. 28  
Output signals (DO1…DO12) ......................................................................................................28  
Input signals ................................................................................................................................29  
7.  
Technical data.................................................................................................................. 36  
8.  
8.1.  
8.2.  
Installation of device ATS022 ......................................................................................... 37  
Door-mounted Automatic Transfer Switch ATS022....................................................................37  
DIN rail-mounted Automatic Transfer Switch ATS022.................................................................38  
9.  
Regulatory standards...................................................................................................... 39  
Troubleshooting............................................................................................................... 40  
10.  
1SDH000760R0002  
3
Installation and operating instructions, ATS022  
1. Safety notes  
1. Safety notes  
Before using the ATS022 unit, read the following “Safety notes”:  
using the unit without following the indications can lead to malfunctioning and, in  
some cases, hazardous conditions.  
If there are doubts about safe use, the unit must be put out of service.  
The automatic transfer switch ATS022 must be prevented from operating the circuit breakers before:  
accessing the circuit breakers  
performing maintenance on circuit breakers or any electrical circuits powered by them  
performing any operation where opening/closing the circuit breaker could be dangerous  
During maintenance:  
set the "Manual" mode.  
lock the circuit breaker mechanically in the open position.  
Safe use is not guaranteed if:  
the device has been damaged during transport  
the device shows visible signs of damage  
the device does not work  
the device has been stored for a long period  
Even if the device seems to be in stand-by status switch it off from the control circuit, as there is risk of it  
operating the circuits without warning.  
1SDH000760R0002  
4
Installation and operating instructions, ATS022  
2. Explanation of abbreviations and terms  
2. Explanation of abbreviations and terms  
2.1. General information  
ATS:  
Automatic Transfer Switch; automatic switching device  
ATS of the ATS02x series, version with display and Modbus communication.  
Circuit Breaker; low voltage automatic Circuit Breaker.  
CB on line LN1.  
ATS022:  
CB:  
CB1:  
CB2:  
CB3:  
LN1:  
CB on line LN2.  
CB for Bus Tie, NPL and NPL BUS TIE operating modes.  
Power supply line No.1.  
LN2:  
Power supply line No.2.  
Bus Tie:  
NPL:  
Operating mode with busbar tie circuit breaker.  
Operating mode with non priority control circuit breaker  
NPL BUS TIE: Operating mode with non priority control circuit breaker for non priority loads control  
Modbus RTU: Communication protocol.  
2.2. Times  
NOTE: All the details of the times and switching logics are described in the Chapters concerned.  
TS:  
-
-
Opening delay of main line CB, after detection of fault in mains (generator is not in  
use)  
Generator start delay, after detection of fault in mains (generator in use).  
TCE:  
TBS:  
TCN:  
TGOFF:  
TC:  
Closing delay of CB2 of line LN2  
Opening delay of emergency line CB, after detection of stabilised voltage on main line.  
Closing delay of CB1 of line LN1  
Generator switching off delay, after closure of main line CB.  
Delay in opening and closing of CB3 in Bus Tie application.  
1SDH000760R0002  
5
Installation and operating instructions, ATS022  
3.  
Introduction  
3. Introduction  
3.1 Product overview  
The automatic transfer switch ATS022 is used in all installations where switching is required between two  
lines to ensure the supply of loads in case of a fault on one line.  
ATS022 selects the power supply line by acting directly on the CBs provided on the lines: ATS022 can be  
used with automatic CBs and ABB SACE switch-disconnectors.  
The device monitors the voltage of the main line and emergency line and records the following faults:  
Maximum and minimum voltage  
Maximum and minimum Frequency  
Phase balance  
Voltage imbalance  
Frequency imbalance  
ATS022 does not require an auxiliary safety power supply since it is powered directly by the line  
voltages.  
If both lines are absent, ATS022 enters Powersave mode (maximum duration 1 minute) in which the  
device is active and in stand-by for one of the power supply lines to be restored. When the Powersave  
period ends, the LED switches off and the device awaits a line voltage. The moment the main or the  
emergency line is restored, the unit analyses the conditions of the lines monitored and the status of the  
circuit breakers and proceeds with the switching operation in accordance with the situation concerned.  
The safety auxiliary supply is obligatory in the following cases:  
utilisation of Modbus RS485 communication  
utilisation in systems with rated frequency 16 2/3Hz  
utilisation in single-phase systems with Un 57,5…109VAC  
A 24VDC ….110VDC auxiliary safety power supply can be used (-10%, +15%).  
ATS022 can be used in systems with rated frequency 50Hz, 60Hz, 400Hz, 16 2/3 Hz that can be set from  
the menu.  
The device can be used in systems with single-phase, three-phase with Neutral and three-phase  
without neutral, setting can be done from the menu. ATS022 makes it possible to select from the display  
a different distribution system between Line LN1 and Line LN2. ATS022 can be used in manual or  
automatic mode. In the first case the circuit breakers must be controlled by means of the pushbuttons  
present on the front panel of the device, while in automatic mode, the switching logic is controlled  
directly by the device  
The device is equipped with a front graphic display by means of which the user can check the settings  
and display the status of the unit and the circuit breakers connected to it.  
It is also possible to integrate the ATS022 device inside a communication network which uses the  
Modbus RS485 protocol.  
3.2 Application scenarios  
The ATS022 device can be used in the following applications:  
Main line – Emergency line switching  
Main line – Emergency generator switching  
ATS022 makes it possible to operate a thrid circuit breaker CB3 and can therefore also be used in the  
following applications which can be set on the menu:  
non priority loads control with CB3 on starting line (3CBs NPL)  
non priority loads control with CB3 Bus Tie (3CBs NPL Bus Tie)  
control of two independent power supply lines separated by Bus Tie (3CBs Bus Tie)  
1SDH000760R0002  
6
Installation and operating instructions, ATS022  
3. Introduction  
The ATS022 also makes it possible to select which of the lines is the main one and which one is  
secondary, also with the system running.  
The following selections are possible, set from the menu:  
Main line: Line LN1  
Main line: Line LN2  
No priority line  
In automatic mode, it is possible to select whether or not the switching procedure must include inverse  
switching.  
The following selections are possible:  
with inverse procedure  
without inverse procedure  
1SDH000760R0002  
7
Installation and operating instructions, ATS022  
4.  
Applications of device ATS022  
4. Applications of device ATS022  
The ATS022 device controls all the switching sequences by applying the time delays that can be set:  
Time delays  
Description  
Value  
Opening delay of main line CB after detection of a fault in the  
mains (Generator is not in use)  
TS Delay  
0…30s  
Generator start delay after detection of a fault in the mains  
(Generator in use).  
TBS Delay  
TCE Delay  
TCN Delay  
Opening delay of emergency line CB.  
Closing delay of line LN2 CB2  
0…59s, 1,2,3…30min  
0…60s  
Closing delay of CB1 of line LN1.  
0…60s  
Opening and closing delay of CB3 if used in Bus Tie  
application.  
TC Delay  
0…60s  
TGOFF Delay  
Table 4.1:  
Generator switching off delay after closure of line LN1 CB1.  
0…59s, 1,2,3…30min  
Description of time delays  
4.1 Switching Main Line – Emergency Line (2CBs)  
Description  
Both lines are normally present; in cause of anomaly on the main line,  
ATS022 switches to the emergency line used as the reserve line.  
Figure 4.1:  
2CBs application layout – generator not in use  
1SDH000760R0002  
8
Installation and operating instructions, ATS022  
4. Applications of device ATS022  
Time diagrams  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
TS  
TCE  
TBS  
TCN  
Figure 4.2:  
2CBs application time diagram - main line LN1  
4.2 Switching Main Line – Emergency generator (2CBs)  
Description  
In case of main line failure ATS022 automatically starts up an emergency generator and, as soon as  
power on the generator side is available, ATS022 starts the automatic switching procedure.  
Figure 4.3:  
2CBs application layout – generator in use  
1SDH000760R0002  
9
Installation and operating instructions, ATS022  
4.  
Applications of device ATS022  
Time diagrams  
Line 1 ok  
CB1 CLOSED  
Gen start  
Line 2 ok  
CB2 CLOSED  
TS  
TCE  
TBS  
TCN  
TGOFF  
Figure 4.4:  
2CBs application time diagram - generator in use  
4.3 Non priority loads control (NPL)  
Description  
In case of main line failure the ATS022 starts the switching procedure and controls the non priority loads  
by opening closing circuit breaker CB3.  
ATS022 acquires the CB3 open/close status from the dedicated input DI11 and commands the opening  
and closing by activating output DO11.  
The application of non priority loads requires the use of two CT-AWE typed timed relays for operating the  
opening and closing of CB3.  
Two configurations are possible for utilisation depending on the position of circuit breaker CB3:  
CB3 in Bus Tie position (3CBs NPL – BUS TIE)  
CB3 on starting line (3CBs NPL).  
It is possible to select from two options from the menu on the display:  
only disconnection of non priority loads by opening CB3 (manual re-closure). In this case timed relays  
CT-AWE are not necessary  
disconnection and re-connection of non priority loads by opening and closing of CB3  
For more details refer to the wiring diagrams of the product.  
1SDH000760R0002  
10  
Installation and operating instructions, ATS022  
4. Applications of device ATS022  
CB1  
CB2  
CB3  
NPL  
Figure 4.5:  
Application layout 3CBs NPL BUSTIE  
CB1  
CB3  
CB2  
NPL  
Figure 4.6:  
Application layout 3CBs NPL  
1SDH000760R0002  
11  
Installation and operating instructions, ATS022  
4.  
Applications of device ATS022  
Time diagrams  
Line 1 ok  
CB1 CLOSED  
Gen start  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TCE  
TBS  
TCN  
TGOFF  
Figure 4.7:  
Application time diagram 3CBs NPL BUS TIE - generator in use  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TCE  
TBS  
TCN  
Figure 4.8:  
Application time diagram 3CBs NPL BUS TIE - generator not in use - main line LN1  
1SDH000760R0002  
12  
Installation and operating instructions, ATS022  
4. Applications of device ATS022  
Line 1 ok  
CB1 CLOSED  
Gen start  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TCE  
TBS  
TCN  
TGOFF  
Figure 4.9:  
Application time diagram 3CBs NPL- generator in use  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TCE  
TBS  
TCN  
Figure 4.10: Application time diagram 3CBs NPL - generator not in use - main line LN1  
1SDH000760R0002  
13  
Installation and operating instructions, ATS022  
4.  
Applications of device ATS022  
4.4 Control of two independent power supply lines  
separated by Tie (3CBs Bus Tie)  
Description  
Lines LN1 and LN2 supply two different sections of the plant separated by a bus tie circuit breaker CB3,  
normally open.  
In case of failure of one of the two supply lines, ATS022 closes CB3; the available line thus powers both  
the sections downline. When the line is restored ATS022 restores the normal plant conditions by opening  
CB3.  
ATS022 acquires the open/close status of the device by means of dedicated input DI11 and commands  
the opening and closing by activating output DO11.  
The Bus Tie application requires the use of two CT-AWE type timed relays for operating the opening and  
closing of CB3.  
The three circuit breakers CB1 – CB2 – CB3 must be interlocked mechanically for reasons of safety  
(Emax circuit breakers – C type interlock).  
CB1  
CB2  
CB3  
Figure 4.11: Application layout 3CBs BUS TIE  
Time diagrams  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TC  
TBS  
TCN  
Figure 4.12: Application time diagram 3CBs BUS TIE – line LN1 failure  
1SDH000760R0002  
14  
Installation and operating instructions, ATS022  
4. Applications of device ATS022  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
CB3 CLOSED  
TS  
TC  
TBS  
TCN  
Figure 4.13: Application time diagram 3CBs BUS TIE – line LN2 failure  
4.5 Automatic switching without inverse procedure  
Description  
Following an anomaly of the main line, ATS022 switches on an emergency line (1). If the mains supply  
is restored, the inverse switching procedure is not started up (2). If there is a fault in the reserve line,  
ATS022 must open the emergency switch (3) and wait for restoration of the emergency line to reclose (4),  
without in any case providing for switching on the main line. This operating mode is also applicable if the  
generator is present: in this case, after time Ts the generator is started up and as soon as the emergency  
line is available CB1 is opened.  
ATTENTION If ATS022 is not powered by the auxiliary supply and by any of the two lines the device  
waits for at least one of the two lines (5) to return before proceeding with the switching procedure (6).  
The option is not available in case of 3CBs Bus Tie application and in case of selection of the no priority  
line option.  
Time diagrams  
(1)  
(2)  
(3)  
(4)  
(5)  
(6)  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
TS  
TCE  
TBS  
TBS  
TCE  
Figure 4.14: 2CBs application time diagram - generator not in use – without inverse switching  
procedure  
1SDH000760R0002  
15  
Installation and operating instructions, ATS022  
4.  
Applications of device ATS022  
4.6 Line Priority Selection  
Description  
ATS022 allows selection of the main line by means of the menu on the display. The following selections  
are possible:  
-
-
-
main line: Line LN1  
main line: Line LN2 (selection possible only if generator is not in use)  
no line priority: ATS022 ensures power supply to the load from any of the two lines without  
considering either of these as priority, therefore, for example, following switching on line LN2 due  
to failure of line LN1, ATS022 remains on line LN2 even if LN1 is restored.  
Time diagrams  
Line 1 ok  
CB1 CLOSED  
Line 2 ok  
CB2 CLOSED  
TS  
TCE  
TBS  
TCN  
Figure 4.16: Time Diagram no line priority – generator non in use  
Line 1 ok  
CB1 CLOSED  
Gen start  
Line 2 ok  
CB2 CLOSED  
TS  
TCE  
Figure 4.17: Time diagram no line priority – generator in use  
1SDH000760R0002  
16  
Installation and operating instructions, ATS022  
4. Applications of device ATS022  
5. Using the automatic transfer switch  
5.1 Interface  
ATS022  
M3010004A  
Status of the line  
Code  
16  
1
2
3
4
5
6
7
No voltage  
Undervoltage  
Overvoltage  
Phase missing  
Voltage unbalance  
Incorrect phase sequence  
Invalid frequency  
15  
14  
2
5
1
10  
11  
12  
13  
R E S E T  
4
7
6
3
9
8
Figure 5.1:  
Description of ATS022 front panel interface  
Ref. Description  
1
2
3
CB1: pushbutton for opening/closing circuit breaker CB1  
CB2: pushbutton for opening/closing circuit breaker CB2  
CB3: CB3 opening/closure procedure graphic indication (combination of UP-DOWN keys for at  
least 2sec)  
4
RESET: pushbutton for automatic/manual mode selection and alarms reset  
TEST: test modes selection pushbutton  
5
6
ENTER: pushbutton for confirming an action  
7
ESC: pushbutton for returning to the previous step  
UP: pushbutton for moving up on the menu  
8
9
DOWN: pushbutton for moving down on the menu  
LED POWER: indicates presence of power supply  
LED AUTO: indicates automatic or manual mode  
10  
11  
1SDH000760R0002  
17  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
Ref. Description  
12  
13  
14  
15  
16  
LED ALARM: indicates active alarm  
Tx/Rx LED: indicates bus communication status  
GRAPHIC DISPLAY  
PLATE SHOWING LINES STATUS CODES  
Serial No.  
Table 5.1:  
Description of ATS022 interface  
5.2 LED indicators  
Alarm  
The steady red Alarm LED may indicate the switching logic disabled condition or one of the following  
events:  
circuit breakers command failed  
protection releases tripped  
removal of circuit breakers  
generator alarm  
logic disabling from input DI3  
both CBs closed  
The alarm LED switches Off indicating that the switching logic is enabled and no alarms are present  
Auto  
The Auto LED indicates the operating mode:  
manual: LED Off  
automatic: steady green LED  
test: flashing green LED  
Power  
LED Power LED indicates the presence of power supply:  
power supply present: steady green LED indicates power supply from line voltage or from auxiliary  
source present  
no power supply: LED Off indicates that both lines are not present and that the Powersave condition  
has ended. The switching logic is in stand-by for return of one of the line voltages  
Powersave: green flashing LED indicates, if both lines are absent and if no auxiliary power supply is  
present, that the device is active and is in stand-by for return of one of the line voltages (maximum  
duration 1 minute). When the Powersave period ends, the LED switches off and the device awaits  
a line voltage. The moment the normal or the emergency line is restored, with ATS022 in automatic,  
the unit analyses the conditions of the lines monitored and the status of the circuit breakers and  
proceeds with the switching operation in accordance with the situation concerned.  
TX/RX  
The TX/RX LED indicates the bus communication status.  
Communication via bus under way: green LED flashing at variable frequency  
Communication via bus not active: LED Off  
1SDH000760R0002  
18  
5. Using the automatic transfer switch  
Installation and operating instructions, ATS022  
5.3 Keypad keys  
CB1 key  
In manual mode, press the CB1 key for Opening/Closure of circuit breaker CB1.  
CB2 key  
In manual mode, press the CB2 key for Opening/Closure of circuit breaker CB2.  
RESET  
Press RESET to select the Manual or Automatic operating mode.  
In case of alarm, press RESET to reset the alarm and the device returns to manual mode. Press RESET  
again to bring the device to automatic mode.  
TEST key  
Press the TEST key to set the test modes of the  
direct and inverse switching sequences.  
ATS022 must be in the manual position. To exit TEST mode press  
RESET.  
Enter key  
Used for confirming the action or entry to the menu.  
ESC key  
Used for cancelling an action and returning to previous menu.  
UP key  
Used for moving up on the menu.  
DOWN key  
Used for moving down on the menu.  
1SDH000760R0002  
19  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
5.4 Setting the operating modes  
5.4.1 Manual mode  
To select the Manual operating mode of unit ATS022:  
a. Make sure the Power LED is On, see Figure 5.2/1  
b. If the Auto LED is OFF, see Figure 5.2/2, the automatic transfer switch is in Manual mode.  
c. If the AUTO LED is ON, press RESET, see Figure 5.2/3 . The Auto LED switches to OFF and the  
device is in Manual Mode, see Figure 5.2/4 .  
Manual mode  
1
2
!
OR  
Manual mode  
2
3
4
CB2  
TEST  
!
CB1  
Figure 5.2:  
Description of manual mode selection procedure for ATS022  
5.4.2 Automatic mode  
To select the Automatic operating mode of unit ATS022:  
a. Make sure the Power LED is On, see Figure 5.3/1  
b. Press RESET once, see Figure 5.3/2. If the Auto LED is ON, the automatic transfer switch ATS022 is  
in Automatic mode, see Figure 5.3/3  
c. If the Auto LED is OFF, press RESET again, see Figure 5.3/3; the Auto LED switches to ON and the  
device is in Automatic mode/ Figure 5.3/4  
Automatic Mode  
1
2
3
CB2  
TEST  
!
CB1  
OR  
Automatic Mode  
3
4
5
CB2  
TEST  
CB1  
!
Figure 5.3:  
Description of automatic mode selection procedure for ATS022  
1SDH000760R0002  
20  
Installation and operating instructions, ATS022  
5. Using the automatic transfer switch  
5.5 Graphic Display  
1
14  
7
2
15  
19 10  
17  
LN1: 1 GT  
LN1  
LN2  
6
20  
TBS..  
0,0  
V
11  
0,0  
LN2:  
0,0  
Hz  
G
1
3
5
12  
V
Hz  
M
9
NPL  
L
0,0  
21  
8
4
13 16 18  
Figure 5.4:  
Description of ATS022 display  
Ref.  
1
Description  
LN1: line 1  
2
LN2: line 2  
3
CB1 status graphic indicator  
CB2 status graphic indicator  
CB3 status graphic indicator  
LN1 power presence icon  
LN2 power presence icon  
application type indicator  
manual mode indicator  
test mode indicator  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
generator presence indicator  
generator start (UP arrow)/stop (DOWN arrow) indicator  
open/close command execution indicator  
timing indicator  
LN1 power measurement  
LN2 power measurement  
LN1 frequency measurement  
LN2 frequency measurement  
LN1 line status code  
LN2 line status code  
local/remote mode indicator  
Table 5.2:  
Description of ATS022 display  
1SDH000760R0002  
21  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
5.5.1 LN1 and LN2 lines status indication  
The presence/absence of lines LN1 and LN2 is shown graphically on the display by means of filled/  
empty icons, see Figure 5.4/6 – 5.4/7, and a specific status code  
If there is an anomaly on the line voltage, the icon concerned is empty and the error code is displayed as  
defined by the following Table:  
Line status  
Code  
No power  
1
2
3
4
5
6
7
Minimum voltage  
Maximum voltage  
Phase missing  
Phase imbalance  
Inverted sequence  
Frequency out of range  
Table 5.3:  
Description of line status codes ATS022  
5.5.2 Browsing through the Menu  
Press Enter to access the main Menu. Three different levels of configuration of the unit can be accessed  
from the main menu:  
Figure 5.5:  
Description of main menu ATS022  
Access to the configuration pages requires a 4-digit password which must be entered using the UP,  
DOWN and ENTER keys.  
The password is valid for one minute after the last pressing of a key.  
For the first access to the system the password is 0001; subsequently change the password as desired.  
If the password is lost or forgotten, contact the service centre.  
1SDH000760R0002  
22  
5. Using the automatic transfer switch  
Installation and operating instructions, ATS022  
Configuration of the System  
The system configuration section makes it possible to set:  
- The parameters of the two lines  
Parameters of lines LN1 - LN2 Value  
Factory settings  
100V/57V– 115V/66V - 120V/70V - 208V/120V  
- 220V/127V - 230V/132V -  
Rated voltage  
240V/138V - 277V/160V - 347V/200V -  
380V/220V - 400V/230V - 415V/240V -  
440V/254V - 480V/277V  
400V/230V  
Rated frequency  
50Hz - 60 Hz, 16 2/3 Hz, 400 Hz  
50Hz  
Number of phases LN1  
Number of phases LN2  
1 phase / 3 phases with N / 3 phases without N 3 phases with N  
1 phase / 3 phases with N / 3 phases without N 3 phases with N  
Presence of external voltage  
transformer  
absent/present  
(for voltages greater than 480VAC)  
absent  
100V/57V– 115V/66V - 120V/70V - 208V/120V  
- 220V/127V - 230V/132V -  
240V/138V - 277V/160V - 347V/200V -  
380V/220V - 400V/230V - 415V/240V -  
440V/254V - 480V/277V - 500V/288V -  
Primary voltage TV  
690V/400 V  
550V/317V - 600V/347V - 660V/380V -  
690V/400V - 910V/525V - 950V/550V -  
1000V/577V - 1150V/660V  
100V/57V– 115V/66V - 120V/70V - 208V/120V  
- 220V/127V - 230V/132V -  
Secondary voltage TV  
240V/138V - 277V/160V - 347V/200V -  
380V/220V - 400V/230V - 415V/240V -  
440V/254V - 480V/277V  
400V/230 V  
Table 5.4:  
Description of parameters of lines ATS022  
- Type of application  
Type of application  
Value  
Factory settings  
2CBs / 3CBs NPL opening only / 3CBs NPL  
opening&closing / 3CBs NPL BusTie / 3CBs Bus Tie  
Protection devices  
2CBs  
Utilisation of generator Generator not in use / Generator in use  
Generator not in use  
Line LN1  
Priority Line  
Switching  
Line LN1 / Line LN2 / No priority Line  
With inverse procedure/Without inverse procedure  
With inverse procedure  
Table 5.5:  
Description of types of application ATS022  
Device configuration  
The device configuration section makes it possible to set:  
- Limit thresholds  
Limit thresholds  
Value  
Factory settings  
Min/max voltage  
threshold  
-30% …-5%, +5% … +30%, step 1%  
(Imbalance of voltage set at same threshold)  
-15%; +15%  
Min/max frequency  
threshold  
-10% …-1%, +1% … +10%, step 1%  
-1%; +1%  
Table 5.6:  
Description of limit thresholds ATS022  
1SDH000760R0002  
23  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
- Time delays  
Time delays  
TS Delay  
Value  
Factory settings  
0…30s, step 1s  
0s  
0s  
3s  
3s  
3s  
5s  
TBS Delay  
TCE Delay  
TCN Delay  
TC Delay  
0…59s, , step 1s, 1,2,3…30min, step 1min  
0…60s, step 1s  
0…60s, step 1s  
0…60s, step 1s  
TGOFF Delay  
0…59s, , step 1s, 1,2,3…30min, step 1min  
Table 5.7:  
Description of time delays ATS022  
- Digital inputs  
Digital Input  
Value  
Factory settings  
disabled/generator start/logic enabling/remote  
reset/EMERGENCY BLOCK  
Digital Input DI10 - function  
Generator Start  
Digital Input DI10 - type  
Digital Input DI8 - type  
NO/NC  
NO/NC  
NO  
NO  
Table 5.8:  
Description of inputs ATS022  
- Modbus parameters  
Modbus  
Value  
Factory settings  
Modbus Address  
Modbus Baud Rate  
Modbus Stop Bits  
Modbus Parity  
mode  
1…247  
1
9600/19200/38400 bps  
0,1  
9600  
1
even, odd, absent  
local, remote  
absent  
local  
Table 5.9:  
Description of Modbus parameters ATS022  
- Language and backlit display  
Function  
Value  
Factory settings  
Backlighting duration  
Always On, 0…59s, step 1s, 1,2,3…30min, step 1min Always On  
English/Italian/German/French/Spanish/Finnish/  
Russian/Chinese  
Language  
English  
Table 5.10:  
Description of language and backlighting ATS022  
1SDH000760R0002  
24  
Installation and operating instructions, ATS022  
5. Using the automatic transfer switch  
Diagnostics  
The diagnostics section makes it possible to access the following pages:  
Values Measured: the voltage and frequency values measured on lines LN1 and LN2 can be consulted  
on the display.  
Alarms Log: the latest alarms/events are displayed, up to a maximum of 20. The number of alarms is  
shown at the top of the page and the latest alarm is always at the top of the list. The log is cleared by  
selecting Clear Log and pressing Enter.  
2/2  
Diagnostics  
Measured Values  
Alarm Log  
SW: 1A  
Figure 5.5:  
SN: 12345678  
Description of diagnostics menu ATS022  
Figure 5.6:  
diagnostics – values measured page ATS022  
Figure 5.7:  
diagnostics – Alarms Log page ATS022  
1SDH000760R0002  
25  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
5.6 Using pushbuttons in manual mode  
Opening/Closing circuit breakers CB1, CB2  
In manual mode the circuit breakers can be controlled by means of pushbuttons CB1 and CB2. In case  
of a fault, the alarms are activated by the same methods as those for the automatic switching sequence.  
Pressing the CB1 key:  
If CB1 is closed, the opening command is sent to CB1  
If CB1 and CB2 are both open, the closing command is sent to CB1  
If CB1 is open and CB2 is closed, no operation is carried out  
Pressing CB2 key:  
If CB2 is closed, the opening command is sent to CB2  
If CB2 and CB1 are both open, the closing command is sent to CB2  
If CB2 is open and CB1 is closed, no operation is carried out  
Opening/Closing circuit breaker CB3  
In manual mode, combination of the UP and DOWN keys allows Opening/Closing of circuit breaker CB3.  
CB3 opening: press the UP and DOWN keys simultaneously for at least 2 seconds.  
CB3 closing: press the UP and DOWN keys simultaneously for at least 2 seconds.  
Manual Start/Stop of generator  
In manual mode, the combination of the RESET, CB1 and CB2 keys allows Start/Stop of the generator.  
Generator Start: keeping RESET pressed, press CB1  
Generator Stop: keeping RESET pressed, press CB2  
5.7 Test Modes  
ATS022 makes it possible to select two different test modes:  
testing the entire switching procedure (complete Test)  
generator start/stop test (gen set test)  
WARNING: when the test procedure ends, the user must make sure the device is not left accidentally in  
TEST mode  
Complete Test  
With ATS022 in manual mode, press TEST: all the LEDs, except Tx/Rx, flash twice simultaneously and  
then the Auto LED Auto flashes every 0.5 sec.; the graphic display shows the icon T.  
The test procedure varies according to the application selected:  
1SDH000760R0002  
26  
Installation and operating instructions, ATS022  
5. Using the automatic transfer switch  
2 CBs  
3CBs NPL  
1. Press TEST; start generator  
(not performed if generator is NOT in use)  
1. Press TEST; start generator  
(not performed if generator is NOT in use)  
2. Press TEST; CB1 Opening  
4. Press TEST; CB2 Closure  
5. Press TEST; CB2 Opening  
6. Press TEST; CB1 Closure  
2. Press TEST; CB1 Opening  
3. Press TEST; CB3 Opening  
4. Press TEST; CB2 Closure  
5. Press TEST; CB2 Opening  
6. Press TEST; CB1 Closure  
8. Press TEST; stop generator  
(not performed if generator is NOT in use)  
7. Press TEST; CB3 Closure  
(not performed if ATS022 has activated the  
DISCONNECTION ONLY function)  
8. Press TEST; stop generator  
(not performed if generator is NOT in use)  
3CBs NPL Bus Tie  
3CBs Bus Tie  
1. Press TEST; start generator  
1. Press TEST; CB1 Opening  
(not performed if generator is NOT in use)  
2. Press TEST; CB3 Closure  
3. Press TEST; CB3 Opening  
4. Press TEST; CB1 Closure  
5. Press TEST; CB2 Opening  
6. Press TEST; CB3 Closure  
7. Press TEST; CB3 Opening  
8. Press TEST; CB2 Closure  
2. Press TEST; CB1 Opening  
3. Press TEST; CB3 Opening  
4. Press TEST; CB2 Closure  
5. Press TEST; CB2 Opening  
6. Press TEST; CB3 Closure  
7. Press TEST; CB1 Closure  
8. Press TEST; stop generator  
(not performed if generator is NOT in use)  
Table 5.11:  
Description of complete TEST mode ATS022  
At the end of the procedure, press TEST again to resume the sequence.  
Alarms, if any, on the protection devices control are activated in the same manner as the automatic and  
manual operating modes.  
The user can stop the TEST sequence by pressing the RESET.  
Gen Set Test  
This test mode makes it possible to test only the generator start and stop with the plant running without  
opreating the circuit breakers on the line in any manner whatsoever, only if the ATS022 is set with the  
generator in use, otherwise the Gen Set Test is not performed.  
1SDH000760R0002  
27  
Installation and operating instructions, ATS022  
5.  
Using the automatic transfer switch  
With ATS022 in manual mode, keep the TEST key pressed for at least 3 seconds, on releasing the TEST  
key, all the LEDs, except Tx/Rx, flash simultaneously four times and then the Auto LED flashes at 0.5Hz;  
the graphic display shows the GT icon.  
The test procedure is as follows:  
1. Press TEST; start generator  
2. Press TEST; stop generator  
Table 5.12:  
Description of test method GEN SET ATS022  
1SDH000760R0002  
28  
Installation and operating instructions, ATS022  
6. Input and output signals  
6. Input and output signals  
6.1 Output signals (DO1…DO12)  
DO1, DO2, DO3, DO4: Circuit breakers open/close command  
Output signals DO1, DO2, D03, DO4 control the opening and closure of circuit breakers CB1 and CB2  
connected to ATS022.  
The control logic integrated in the device punctually checks the correct operation of the circuit breakers  
following the command.  
If the change in status of the circuit breaker is not received within 5 seconds of sending the command,  
the device considers the command as failed and operates as below:  
alarm LED lights up.  
DO6 alarm output activation  
DO9 alarm output activation  
The alarm relative to the failed operation is recorded in the section concerned of the "Alarms Log".  
To reset the alarm press RESET:  
the alarm is reset and ATS022 goes into manual mode.  
Press RESET again to bring ATS022 to automatic mode.  
DO5 Emergency generator start/stop command  
Start and stop of the Emergency generator are controlled by means of a bistable relay, making it possible  
to maintain the generator start command even when the powersave mode runs out.  
contact DO5 (X23:1 ; X23:2 - NO):  
-
-
stop unit = contact open  
start unit = contact closed  
contact DO5 (X23:2 ; X23:3 - NC):  
-
-
stop unit = contact closed  
start unit = contact open  
DO6 Alarm signal  
When an alarm is generated, contact DO6 switches, the switching logic is disabled and the alarm LED  
lights up.  
To reset the alarm press RESET:  
the alarm is reset, the Alarm LED turns Off and the ATS022 enters manual mode.  
Press RESET again to bring ATS022 to automatic mode.  
DO7-DO8 Not available  
DO9 Circuit breaker operation failed alarm indication  
When the opening or closing command of a circuit breaker fails, contact DO9 closes; the switching logic  
is disabled and the Alarm LED lights up.  
To reset the alarm press RESET:  
the alarm is reset, the Alarm LED turns Off and the ATS022 enters manual mode.  
Press RESET again to bring ATS022 to automatic mode.  
DO10 Automatic/Manual mode indication  
Contact DO10 indicates the operating mode of the device:  
DO10 open: ATS022 operates in automatic mode  
DO10 closed: ATS022 operates in manual mode  
DO11 CB3 circuit breaker control  
Depending on the operating mode set, contact DO11 allows control of only opening or opening/closing  
of circuit breaker CB3:  
Protection Devices selection  
DO11  
NOTES  
2 CBs  
not used  
1SDH000760R0002  
29  
Installation and operating instructions, ATS022  
3CBs NPL  
6.  
Input and output signals  
CT-AWE type timed relays required if  
used  
selected opening&closing option  
CT-AWE* type timed relays required  
CT-AWE* type timed relays required  
3CBs NPL Bus Tie  
3CBs Bus Tie  
used  
used  
*The CT-AWE must be adjusted with a time between 200ms and 300ms.  
Table 6.1: Description of DO11 functions - ATS022  
DO12 Logic enabled/disabled indication  
Contact DO12 indicates whether switching logic is enabled or disabled:  
DO12 open: logic enabled  
DO12 closed: logic disabled  
6.2 Input signals  
DI1, DI2 Status signals of circuit breakers CB1, CB2  
Inputs DI1, DI2 must be connected to auxiliary contacts of the status of the circuit breakers of the normal  
and emergency lines  
DI1, DI2 open: CB open  
DI1, DI2 closed: CB closed  
DI3 Switching Logic Activation/Deactivation  
Input DI3 is used for enabling/disabling the switching logic. The function may be used for integrating  
generic alarms coming from the plant the presence of which leads to disabling of ATS022 automatic  
switching logic.  
DI3 open: logic disabled  
DI3 closed: logic enabled  
DI4, DI5 Circuit breakers activation indication  
The auxiliary opening contacts of the normal and emergency lines must be connected to contacts DI4,  
DI5 for activation of the trip.  
DI4, DI5 open: CB tripped  
DI4, DI5 closed: CB not tripped  
In case of trip of a circuit breaker (CB1 or CB2):  
the trip indication contact opens  
the switching logic is disabled  
Alartm contact DO6 is closed  
contact DO12 is closed  
the Alarm LED lights up  
the Auto LED switches Off  
To reset the TRIP indication press RESET.  
The TRIP indication is reset  
Alarm LED switches Off  
ATS022 operates in manual mode  
contact DO10 is closed  
Press RESET again to bring ATS022 to Automatic mode  
contact DO10 is opened  
the Auto LED lights up  
DI6, DI7 Circuit breakers CB1, CB2 removed/inserted position indication  
The auxiliary position contacts of the circuit breakers of the normal and emergency lines must be  
1SDH000760R0002  
30  
Installation and operating instructions, ATS022  
6. Input and output signals  
connected to inputs DI6 and DI7 in removable execution.  
DI6, DI7 open: CB removed  
DI6, DI7 closed: CB inserted  
If the circuit breaker is removed:  
the position indication contact opens  
the switching logic is disabled  
Alartm contact DO6 is closed  
contact DO12 is closed  
the Alarm LED lights up  
the Auto LED switches Off  
When the circuit breaker is inserted:  
the position indication contact closes  
the switching logic is re-enabled  
Alarm LED switches Off  
ATS022 operates in manual mode  
contact DO10 is closed  
Alarm contact DO6 is opened  
contact DO12 is opened  
the Auto LED switches Off  
To set the device in automatic mode press RESET  
contact DO10 is Opened  
the Auto LED lights up  
DI8 Generator Alarm  
Input DI8 is used for connecting various alarms coming from the emergency generator: drop in oil  
pressure, Over Temperature, etc.  
Input DI8 may be set as normally open (NO) or normally closed (NC) by means of the menu on the  
graphic display.  
In case of an active generator alarm  
the switching logic is disabled  
Alartm contact DO6 is closed  
contact DO12 is closed  
the Alarm LED lights up  
the Auto LED switches Off  
contact DO10 is closed  
the display shows "generator alarm"  
When the DI8 signal is deactivated:  
Alarm LED switches Off  
Alarm contact DO6 is opened  
contact DO12 is opened  
ATS022 operates in manual mode  
the "generator alarm" message disappears from the display  
To set the device in automatic mode press RESET  
contact DO10 is Opened  
the Auto LED lights up  
DI9 Forced switching on emergency power supply line  
In certain industrial processes, supply of power from the emergency generator may be required instead  
of from the normal power supply line, for brief moments, in order to avoid possible operating anomalies  
of the supply and ensure high levels of reliability.  
1SDH000760R0002  
31  
Installation and operating instructions, ATS022  
6.  
Input and output signals  
In automatic mode, by activating input DI9 the forced switching procedure is started up on the  
emergency line:  
Generator Start  
opening of circuit breaker on normal line  
closure of circuit breaker on emergency line  
The power supply from the emergency line persists as long as the command remains active. When the  
command is deactivated, the unit proceeds with the switching procedure on the normal line.  
2 CBs:  
If DI9 is closed:  
Generator Start  
Opening of circuit breaker CB1  
closure of circuit breaker CB2  
If DI9 is open:  
opening of circuit breaker CB2  
closure of circuit breaker CB1  
generator stop  
3CBs NPL:  
If DI9 is closed:  
Generator Start  
Opening of circuit breakers CB1 and CB3  
closure of circuit breaker CB2  
If DI9 is open:  
opening of circuit breaker CB2  
closure of circuit breakers CB1 and CB3  
generator stop  
3CBs NPL BUS TIE:  
If DI9 is closed:  
Generator Start  
Opening of circuit breakers CB1 and CB3  
closure of circuit breaker CB2  
1SDH000760R0002  
32  
Installation and operating instructions, ATS022  
6. Input and output signals  
If DI9 is open:  
opening of circuit breaker CB2  
closure of circuit breakers CB3 and CB1  
generator stop  
DI10 Programmable input  
The function associated with input DI10 can be selected from the menu on the display, from among the  
following options:  
forced generator start: this function makes it possible to test the correct switching ON/OFF of the  
generator with the plant running  
Contact type set  
Description of function  
NC  
NO  
Open =gen start; Closed = gen stop  
Closed =gen start; Open = gen stop  
Enabling automatic switching logic: this function makes it possible to inhibit the automatic  
switching logic of the device following an alarm present in the field.  
The logic can, however, be disabled if one of the conditions involving the disabling exist  
Contact type set  
Description of function  
Closed = switching enabled;  
Open switching disabled  
NC  
Open = switching enabled;  
Closed switching disabled  
NO  
Reset from Remote: this function allows reset of the device logic in remote by means of remote  
actuator.  
Contact type set  
Description of function  
Closed = remote reset not active;  
Open = remote reset active  
NC  
Closed = remote reset active;  
Open = remote reset not active  
NO  
Emergency Block: this function allows prior opening of both circuit breakers of the power supply  
and emergency lines and permanent disabling of the switching logic. This function can be used, for  
example, in case of an alarm coming from a fire-fighting system which requires immediate opening of  
the circuit breakers and disabling of the switching logic.  
Contact type set  
Description of function  
Closed = emergency block not active;  
Open = emergency block active  
NC  
Closed = emergency block active;  
Open = emergency block not active  
NO  
Input DI10 may be set as normally open (NO) or normally closed (NC) by means of the menu on the  
graphic display.  
Linea 2  
DI11 CB3 circuit breaker
Line 2  
ATS022  
Linea 1  
Linea 2  
Ligne 2  
Leitung 2  
Line 1  
Ined to tcontac
Linea 1  
Ligne 1  
en  
Leitung 1  
Uscita per controllo Gen Start/Stop  
Output to control Gen Start/Stop  
Salida para control Gen Start/Stop  
Sortie pour controle Gen Start/Stop  
Ausgang zur steuerung Gen Start/Stop  
DI11 closed: CB closed  
Uscita per controllo CB1  
Output to control CB1  
Uscita per controllo CB3  
Output to control CB3  
Salida para control CB3  
Sortie pour controle CB3  
Ausgang zur steuerung CB3  
Salida para control CB1  
Sortie pour controle CB1  
Ausgang zur steuerung CB1  
Uscita per controllo CB2  
Output to control CB2  
Salida para control CB2  
Sortie pour controle CB2  
1AusgangzursteuerungCB2  
Installation and operating instructions, ATS022  
6.  
Input and output signals  
Figure 6.1:  
Control circuit diagram ATS022  
Connectors Description  
Normal Line LN1: L1  
DI/DO  
Type  
X11:1  
X11:2  
X11:3  
X11:4  
X12:1  
X12:2  
X12:3  
X12:4  
X41:1  
X41:2  
X21:1  
X21:2  
X21:3  
X22:1  
X22:2  
X22:3  
X23:1  
X23:2  
X23:3  
X24:1  
X24:2  
X24:3  
-
-
Normal Line LN1: L2  
Normal Line LN1: L3  
Normal Line LN1: N  
Emergency Line LN2: L1  
Emergency Line LN2: L2  
Emergency Line LN2: L3  
Emergency Line LN2: N  
+ Auxiliary power supply  
- Auxiliary power supply  
Com  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CB1 opening command  
CB1 closure command  
Com  
DO1  
DO2  
-
NO  
NO  
-
CB2 opening command  
CB2 closure command  
generator start/stop command  
Com  
DO3  
DO4  
D05  
-
NO  
NO  
Open =gen stop; Closed = gen start  
-
generator start/stop command  
CB3 opening command  
Com  
D05  
D011  
-
Closed =gen stop; Open = gen start  
NO  
-
CB3 closure command  
D011  
NC  
Open = no alarm;  
Closed = alarm  
X29:1  
ATS022 unit alarm indication  
DO6  
X29.2  
X29:3  
not used  
not used  
DO7  
DO8  
-
-
circuit breakers command alarm  
indication  
Open = no alarm;  
Closed = alarm  
X29:4  
X29.5  
DO9  
Open = Automatic;  
Closed = Manual  
automatic/manual mode indication DO10  
logic enabled/disabled indication DO12  
Open = logic enabled;  
Closed = logic disabled  
X29:6  
X29:7  
X31:1  
Com  
-
-
Open = logic disabled;  
Closed = logic enabled  
logic enabling input  
DI3  
X31:2  
X31:3  
X31:4  
X32:1  
X32.2  
CB1 status input  
CB2 status input  
Com  
DI1  
DI2  
-
0=CB open; I=CB closed  
0=CB open; I=CB closed  
-
CB3 status input  
programmable input  
DI11  
DI10  
0=CB open; I=CB closed  
NO/NC  
1SDH000760R0002  
34  
Installation and operating instructions, ATS022  
6. Input and output signals  
Connectors Description  
DI/DO  
DI9  
DI8  
DI7  
DI6  
DI5  
DI4  
-
Type  
X32:3  
X32:4  
X32.5  
X32:6  
X32:7  
X32:8  
X32.9  
X51:1  
X51:2  
X52:3  
X61  
switching forcing input  
NO  
generator alarm input  
CB1 position input  
CB2 position input  
CB1 trip input  
NO/NC  
0=CB removed; I=CB inserted  
0=CB removed; I=CB inserted  
0=no CB trip; I=CB trip  
CB2 trip input  
0=no CB trip; I=CB trip  
Com  
-
-
-
-
-
Modbus DATA B  
Modbus DATA A  
Modbus GND  
-
-
-
Earth connection  
-
Table 6.2:  
Description of function and type connector ATS022  
1SDH000760R0002  
35  
Installation and operating instructions, ATS022  
7.  
Technical data  
7. Technical data  
ATS022  
Value  
Three-phase voltage used  
Connected voltage  
Phase voltage  
100Vac - 480Vac (+/-20%)  
57,7Vac - 277Vac (+/-20%)  
24Vdc - 110 Vdc (-10% / +15%)  
50-60-400-16 2/3 Hz  
Safety auxiliary voltage  
Frequency  
Single-phase voltage used  
Phase voltage  
57,7Vac - 277Vac (+/-20%) (1  
24Vdc - 110 Vdc (-10% / +15%) (2  
50-60-400-16 2/3 Hz (3  
Safety auxiliary voltage  
Frequency  
Measurement precision  
Voltage  
1%  
Frequency  
1%  
Relay utilization category  
Relay/connectors utilization category  
Over voltage category  
Power consumption  
IP rating  
8 A, AC1, 250 V  
6 A, AC1, 250 V  
III, Uimp 6 kV  
Max 12W  
IP20  
Device weight  
1314g  
Operating temperature  
Storage temperature  
Humidity  
-20 / +60 °C (4  
-25 / +80°C  
r.h=95% T=25…60°C  
Max. 2000m  
Altitude  
NOTES  
(1 In single-phase system it is not possible to select Un 100 V, 115 V, 120 V.  
(2 In single-phase system, if Un is between 57.7 - 109 V an auxiliary safety power supply is necessary  
(3 In case of rated frequency 16 2/3 Hz, an auxiliary safety power supply must be used. If the rated  
voltage is greater than 100 VAC external transformers must be used.  
(4 If the ATS022 is used in environments with extremely low temperatures (less than - 10°C) it is  
advisable to use a safety auxiliary power supply to avoid display problems of the graphic display.  
Table 7.1:  
Technical data ATS022  
1SDH000760R0002  
36  
Installation and operating instructions, ATS022  
8. Installation of device ATS022  
8. Installation of device ATS022  
The automatic transfer switch ATS022 can be mounted on the front of the panel door or on DIN rail.  
8.1. Door-mounted Automatic Transfer Switch ATS022  
The Automatic Transfer Switch ATS022 can be door-mounted as shown in Figure 8.1.  
2
139  
1
91  
160  
2a  
2b  
Figure 8.1:  
Door-mounted ATS022  
1SDH000760R0002  
37  
Installation and operating instructions, ATS022  
8.  
Installation of device ATS022  
8.2. DIN rail-mounted Automatic Transfer Switch ATS022  
The automatic transfer switch ATS022 can be mounted on a 35mm DIN rail as shown in Figure 8.2.  
3
35mm  
1
EN 50022  
2
145  
97  
Togliere  
3
1
2
Figure 8.2:  
DIN rail-mounted ATS022  
1SDH000760R0002  
38  
Installation and operating instructions, ATS022  
9. Regulatory standards  
9. Regulatory standards  
ATS022 conforms to the following regulatory standards:  
European Directive 73/23 “LVD – Low Voltage Directive”  
EN 50178 electronic equipment for use in power Installations  
EN-IEC 62103 electronic equipment for use in power Installations  
EN-IEC 60947-5-1 low voltage switchgear and control gear: control circuit devices and switching  
elements  
Electromagnetic compatibility EN 50081-2, EN 50082-2  
Environmental conditions IEC 68-2-1, IEC 68-2-2, and IEC 68-2-3  
EN-IEC 61000-4-2: Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques Section 2: Electrostatic discharge immunity test Basic EMC Publication (IEC 61000-4-2  
[8KV air, 4KV cont])  
EN-IEC 61000-4-3, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques Section 3: Radiated, radio-frequency, electromagnetic field immunity test (IEC 61000-4-3  
[level 3])  
EN-IEC 61000-4-4, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques Section 4: Electrical fast transient/burst immunity test Basic EMC Publication (IEC 61000-  
4-4 [level 2/3])  
EN-IEC 61000-4-5, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques Section 5: Surge immunity test (IEC 61000-4-5 [level 1/2])  
EN-IEC 61000-4-6: Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques (IEC 61000-4-6 [level 3])  
EN-IEC 61000-4-8: Electromagnetic compatibility (EMC) - Part 4: Testing and measurement  
techniques (IEC 61000-4-8 [level 5])  
EN 50093, Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques  
Section 11: Voltage dips, short interruptions and voltage variations immunity test (IEC 61000-4-11,  
[100ms/5s] B, C criterion)  
CISPR11 (30MHz...1GHz): Emission (Generic Standard, Industrial) – Radiated  
CISPR11 (0.15MHz…30MHz): Emission (Generic Standard, Industrial) – Conducted  
CISPR/CEI 1000-6-3: Part 6: Generic standards – Section 3: Emission standard for residential,  
commercial and light-industrial environments  
IEC 60068-2-2: Environmental testing. Part 2: Tests. Test B: Dry heat  
IEC 60068-2-6: Environmental testing. Part 2: Tests. Test Fc: vibration (sinusoidal)  
IEC 60068-2-27: Environmental testing. Part 2: Tests. Test Ea and guidance: shock  
IEC 60068-2-30: Environmental testing. Part 2: Tests. Test Db and guidance: Damp heat, cyclic  
IEC 60068-2-1: Environmental testing. Part 2: Tests. Test A: cold (-20 °C 3 °C, 16 hours)  
1SDH000760R0002  
39  
Installation and operating instructions, ATS022  
10. Troubleshooting  
10. Troubleshooting  
The alarms are shown by means of a message on the ATS022 display. The  
Alarm messages are shown in the Table below:  
Table 10.1: Alarms ATS022  
Alarm  
Fault  
Action  
circuit breaker CB1 on normal line  
does not open within 5s  
the alarm can be reset by means of the  
RESET button.  
CB1 opening failed  
circuit breaker CB2 on emergency  
line does not open within 5s  
the alarm can be reset by means of the  
RESET button.  
CB2 opening failed  
CB3 Opening failed  
CB1 closure failed  
CB2 closing failed  
circuit breaker CB3 bus-tie does not the alarm can be reset by means of the  
open within 5s  
RESET button.  
circuit breaker CB1 on normal line  
does not close within 5s  
the alarm can be reset by means of the  
RESET button.  
circuit breaker CB2 on emergency  
line does not close within 5s  
the alarm can be reset by means of the  
RESET button.  
The logic is blocked and ATS enters manual  
mode.  
Reset by inserting CB1.  
CB1 removed  
CB2 removed  
circuit breaker CB2 is removed  
circuit breaker CB2 is removed  
The logic is blocked and ATS enters manual  
mode.  
Reset by inserting CB2.  
Enabled/disabled logic input DI3  
inactive  
Logic block  
External fault  
Trip CB1  
The logic is blocked. Reset by activating DI3  
Check wiring  
Both circuit breakers are closed (DI1  
and DI2 active)  
The logic is blocked as long as input DI4 is  
deactivated  
Circuit breaker CB1 has tripped  
Circuit breaker CB2 has tripped  
Generator alarm input DI8 active  
The logic is blocked as long as input DI5 is  
deactivated  
Trip CB2  
The logic is blocked as long as input DI8 is  
activated  
Generator alarm  
Table 10.1:  
Alarms ATS022  
1SDH000760R0002  
40  
Installation and operating instructions, ATS022  
1SDH000760R0002  
41  
For more information please contact:  
ABB S.p.A.  
ABB SACE Division  
Via Baioni, 35  
24123 Bergamo - Italy  
Phone: +39 035 395 111  
Fax:  
+39 035 395 306 - 433  
Due to possible development of Standards as  
well as of materials, the characteristics and  
dimensions specified in this Installation and  
operating instructions may be considered as  
binding only after confirmation by ABB SACE  
Division.  
© Copyright 2011 ABB. All rights reserved.  

Mr Coffee PR26 User Manual
Meridian Audio G08 User Manual
Melitta ME2TMB User Manual
Lindy GMBH User Manual
KTI Networks Computer Accessories KS 124 User Manual
Jwin JL 355 User Manual
IBM 09N4076 User Manual
Fujitsu MPA3017AT User Manual
Cary Audio Design CD 306 User Manual
Alpine CDE 9841 User Manual