Weil McLain Gold GV 3 Series User Manual

GOLD G V  
W a t e r b o ile r — S e rie s 3  
Us e r ’s  
in fo r m a t io n  
m a n u a l  
If the information in this manual is not followed exactly, a fire or  
explosion may result, causing property damage, personal injury or  
loss of life.  
Do not store or use gasoline or other flammable vapors and liquids in the  
vicinity of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any phone in your  
building.  
Immediately call your gas supplier from a neighbor’s phone. Follow  
the gas supplier’s instructions.  
If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified installer, service agency  
or the gas supplier.  
Part No. 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
S TOP !! Re a d b e fo re p ro c e e d in g  
Failure to adhere to the guidelines on this page can result in  
severe personal injury, death or substantial property damage.  
Bo ile r s e rvic e a n d m a in t e n a n c e —  
To avoid electric shock, disconnect electrical supply before  
performing maintenance.  
To avoid severe burns, allow boiler to cool before performing  
maintenance.  
You must maintain the boiler as outlined in the manual and have the  
boiler started up and serviced at least annually by a qualified  
service technician to ensure boiler/system reliability.  
Bo ile r o p e ra t io n —  
Do not block flow of combustion or ventilation air to boiler.This boiler  
is equipped with a control which will automatically shut down the boiler  
should air or vent be blocked. If vent or air blockage is easily accessible  
and removable, remove it. The boiler should attempt to restart within an  
hour. If blockage is not obvious or cannot be removed, have the boiler  
and system checked by a qualified service technician.  
Should overheating occur or gas supply fail to shut off, do not  
turn off or disconnect electrical supply to pump. Instead, shut off the  
gas supply at a location external to the appliance.  
Do not use this boiler if any part has been under water.  
Immediately call a qualified service technician to inspect the boiler and to  
replace any part of the control system and any gas control, which has  
been under water.  
Bo ile r w a t e r —  
DO NOT use petroleum-based cleaning or sealing compounds in  
boiler system.Water seal deterioration will occur,causing leakage between  
sections and damage to heating system components. This can result in  
substantial property damage.  
DO NOT use "homemade cures" or "boiler patent medicines".  
Serious damage to boiler, personnel and/or property may result.  
Continual fresh makeup water will reduce boiler life. Mineral  
build-up in sections reduces heat transfer, overheats cast iron,and causes  
section failure. Addition of oxygen and other gases can cause internal  
corrosion. Leaks in boiler or piping must be repaired at once to prevent  
makeup water.  
Do not add cold water to hot boiler. Thermal shock can cause  
sections to crack.  
Part number 550-141-812/0699  
3
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Pre ve n t c o m b u s t io n a ir c o n t a m in a t io n —  
Air contamination  
Common household and hobby products often contain possible threat of flue gas spillage into the building.  
fluorine or chlorine compounds. When these chemicals  
pass through the boiler, they can form strong acids in the Please read the information below.If the contaminating  
vent system or boiler. The acid can eat through the vent chemicals will be present, have your installer pipe the  
or boiler wall, causing serious damage and presenting a boiler air from outside per the Boiler manual.  
If the boiler is installed in any area likely to cause contamination, or if products which  
would contaminate the air cannot be removed, you must pipe combustion air to the boiler  
air intake. Contaminated combustion air will damage the boiler and vent system, resulting in  
possible severe personal injury, death or substantial property damage.  
Do not operate a GV boiler in a laundry room or pool facility, for example, without  
using ducted outside air.These areas will always contain contaminants.  
Products to avoid  
Areas likely to have contaminants  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
Dry cleaning/laundry areas and establishments  
Swimming pools  
Chlorinated waxes/cleaners  
Metal fabrication plants  
Beauty shops  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
Paint or varnish removers  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
Hydrochloric acid/muriatic acid  
Cements and glues  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning  
solvents found in household laundry rooms  
Garages with workshops  
Adhesives used to fasten building products and  
other similar products  
4
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Pe rfo rm m a in t e n a n c e p e r s c h e d u le b e lo w  
Service technician  
(see following pages for instructions)  
Owner maintenance  
(see following pages for instructions)  
• Check boiler area  
Inspect:  
• Any problems reported by owner  
• Boiler area  
Daily  
• Check air openings  
• Check pressure gauge  
• Air openings  
• Flue gas vent  
• Boiler heating surfaces  
• Water piping  
• Check boiler interior piping  
• Check venting system  
• Check air vents  
• Condensate drain system  
Monthly  
Service:  
• Check condensate drain system  
• Check relief valve  
• Lubricate blower motor  
• Lubricate any circulators requiring oil  
Start-up:  
• Perform start-up per manual  
• Test low water cutoff (if used)  
Check/test:  
Periodically  
• Clean vent termination/air intake  
screens  
• Check gas piping for leaks  
• Check cold fill & operating pressures  
• Check temperature mixing system  
• Check/maintain components - vents,  
limits, expansion tank, gauges, igniter  
• Inspect & operate relief valve  
• Oil blower motor  
Every 6 months  
End of season  
• Operate relief valve  
Review:  
• Review maintenance procedures with  
owner  
• Shut down procedure  
Part number 550-141-812/0699  
5
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Us e r m a in t e n a n c e p ro c e d u re s  
The boiler should be inspected and started annually, at  
Boiler must be serviced and  
the beginning of the heating season, only by a qualified  
service technician. In addition, the maintenance and care  
of the boiler designated on page 5 and explained on the  
following pages must be performed to assure maximum  
boiler efficiency and reliability. Failure to service and  
maintain the boiler and system could result in equipment  
failure,causing possible severe personal injury,death or  
substantial property damage.  
maintained  
The following information provides detailed instructions  
for completing the maintenance items listed in the  
maintenance schedule, page 5. In addition to this  
maintenance, the boiler must be serviced and started up  
at the beginning of each heating season by a qualified  
service technician.  
—— D A ILY ——  
Ch e c k b o ile r a re a  
To prevent potential of severe personal injury,death or substantial property  
damage, eliminate all materials discussed below from the boiler vicinity. If  
contaminants are found:  
Remove products immediately from the area. If they have been there for an  
extended period, call a qualified service technician to inspect the boiler and  
vent system for possible damage from acid corrosion.  
If products cannot be removed, immediately call a qualified service technician  
to install an outside combustion air source for the boiler (if not already  
installed).  
1. Combustible/flammable materials Do not store combustible materials, gasoline or any  
other flammable vapors or liquids near the boiler. Remove immediately if found.  
2. Air contaminants Products containing chlorine or fluorine, if allowed to contaminate the  
boiler intake air,will cause acidic condensate in the vent and boiler.This will cause significant  
damage to the vent and/or boiler if allowed to continue. Read the list of potential materials  
listed on page 4 of this manual. If any of these products are in the room from which the boiler  
takes its combustion air, they must be removed immediately or the boiler combustion air  
must be supplied from outside.SeeWARNING above.  
Ch e c k a ir o p e n in g s  
1. Verify that combustion and ventilation air openings to the boiler room and/or building are  
open and unobstructed.  
2. Verify that boiler vent discharge and air intake are clean and free of obstructions. Remove any  
debris on the air intake or flue exhaust openings.  
Ch e c k b o ile r p re s s u re /t e m p e ra t u re g a u g e  
1. Make sure the pressure reading on the boiler pressure/temperature gauge does not exceed 24  
psig. Higher pressure may indicate a problem with the expansion tank.  
Contact a qualified service technician if problem persists.  
6
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Us e r m a in t e n a n c e p ro c e d u re s (cont.)  
M O N T H LY Ch e c k b o ile r in t e rio r p ip in g  
1. Remove boiler jacket top.  
2. Visually inspect for leaks around internal piping, circulators, relief valve and other fittings.  
Immediately call a qualified service technician to repair any leaks.  
Have leaks fixed at once by a qualifed service technician. Continual fresh  
makeupwater willreduceboiler life. Mineralscan buildupin sections, reducing  
heat transfer,overheating cast iron, and causing section failure.  
Do not usepetroleum-based cleaningor sealingcompounds in boiler system.  
Severe damage to boiler and system components can occur, resulting in  
possible severe personal injury, death or substantial property damage.  
Ch e c k ve n t in g s ys t e m  
1. Visually inspect the flue gas vent piping for any signs of blockage, leakage or joints or  
deterioration of the piping. Notify your qualified service technician at once if you find any  
problem.  
Failure to inspect the vent system as noted above and have them repaired by  
a qualifed service technician can result in vent system failure, causing severe  
personal injury or death.  
Ch e c k a u t o m a t ic a ir ve n t s (if u s e d )  
1. See Figure 1.  
2. Remove the cap from any automatic air vent in the system and check operation by depressing  
valve B slightly with the tip of a screwdriver.  
3. If the air vent valve appears to be working freely and not leaking, replace cap A, twisting all the  
way on.  
4. Loosen cap A one turn to allow vent to operate.  
5. Have vent replaced if it does not operate correctly.  
A
Figure 1 Automatic air vent  
B
85036  
Part number 550-141-812/0699  
7
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Us e r m a in t e n a n c e p ro c e d u re s (cont.)  
M O N T H LY Ch e c k c o n d e n s a t e d ra in s ys t e m  
1. While the boiler is running check the discharge end of the condensate drain tubing.  
2. Make sure no flue gas is escaping from the condensate drain tubing by holding your fingers  
in front of the tubing discharge.  
3. If you do notice flue gas escaping from the drain tubing, this indicates a dry drain trap. Call  
your qualified service technician to install a condensate drain line check valve kit.  
Under some circumstances a GV vent system may not produce enough  
condensate to keep the condensate trap full of liquid. If the trap is not full,  
small amounts of flue products can be emitted into the boiler room through  
the condensate drain line. Contact a qualified service technician to install a  
condensate drain line check valve kit.  
4. Verify that the condensate drain tubing is unobstructed by squeezing it. Check the entire  
length of the condensate drain tubing, including the corrugated tube between the boiler vent  
outlet tee and the boiler jacket side.  
Ch e c k b o ile r re lie f va lve  
1. Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.  
2. If the relief valve often weeps, the expansion tank may not be working properly. Immediately  
contact your qualified service technician to inspect the boiler and system.  
P E R IO D IC A LLY  
Te s t lo w w a t e r c u t o ff (if in s t a lle d )  
1. If the system is equipped with a low water cutoff, test the low water cutoff periodically during  
the heating season,following the low water cutoff manufacturers instructions.  
Cle a n ve n t t e rm in a t io n & a ir in t a ke s c re e n s  
1. Remove all lint and debris from both the boiler air intake screen and the flue discharge screen.  
2. The boiler control module will sense blockage of the air intake or flue and lockout if the  
blockage is excessive. It will signal the failure by flashing the appropriate indicator lights on  
the control board.  
3. If removing the debris does not allow the boiler to operate correctly afterwards, contact your  
qualifed service technician to inspect the boiler and vent/air systems.  
8
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Us e r m a in t e n a n c e p ro c e d u re s (cont.)  
Oil b lo w e r m o t o r  
Figure 2 Blower motor  
EVER Y  
6 M O N T H S  
1. Remove the jacket top panel to access the blower  
motor.  
2. Use only S.A.E. 20 motor oil. DO NOT use household  
universal oils.  
Oil  
cup  
Use only S.A.E. 20 motor oil to  
lubricate the blower motor. Do not  
usecommon universalhouseholdoils.  
3. See Figure 2.  
4. Place a few drops of oil in each of the two oiler cups  
on the side of the blower motor.  
Oil cup  
85037  
Op e ra t e b o ile r re lie f va lve  
1. Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge,  
avoiding any possibility of scalding from hot water.  
To avoid water damage or scalding due to valve operation,a metal discharge  
line must be connected to relief valve outlet and run to a safe place of disposal.  
This discharge line must be installed by a qualifed heating installer or service  
technician in accordance with the instructions in the Boiler manual. The  
discharge line must be terminated so as to eliminate possibility of severe  
burns should the valve discharge.  
2. Read the boiler pressure/temperature gauge to make sure the system is pressurized.  
3. Lift the relief valve top lever slightly,allowing water to relieve through the valve and discharge  
piping.  
4. If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief  
valve discharge pipe to ensure that the valve does not weep after the line has had time to drain.  
If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to  
weep afterwards, contact your qualified service technician to inspect the valve and system.  
5. If water does not flow from the valve when you lift the lever completely, the valve or discharge  
line may be blocked. Immediately shutdown the boiler, following the instructions on the  
inside jacket top Lighting Instructions. Call your qualified service technician to inspect the  
boiler and system.  
E N D  
Fo llo w b o ile r s h u t d o w n p ro c e d u re  
O F S EA S O N  
1. Follow TO TURN OFF GAS TO APPLIANCEon the Lighting instructions on the  
inside of the jacket top panel.You will also find these instructions on pages 12 and 13 of this  
manual. Use the Lighting instruction for the gas valve model installed on the boiler.  
2. Do not drain system unless exposure to freezing temperatures will occur.  
3. Do not drain the system if it is filled with an antifreeze solution.  
4. Do not shut down boilers used for domestic water heating. They must operate year-round.  
Part number 550-141-812/0699  
9
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Ho w t h e b o ile r w o rks . . .  
Co n t ro l m o d u le  
x
The GCM control module responds to signals from the room thermostat, air pressure switch, inlet  
water sensor and boiler limit circuit to operate the circulators, gas valve,igniter and blower.When  
a room thermostat calls for heat, the GCM starts the system circulator and blower.  
The GCM runs the blower long enough to purge the boiler flue passages, then turns on the igniter  
and lets it warm up.  
After a 15-second warmup, the GCM opens the gas valve, turns the igniter off, and checks for  
flame. The flame must come on within 4 seconds or the GCM will shut down and try the full cycle  
again.  
When the room thermostat is satisfied, the GCM turns off the boiler components and waits for the  
next heat call.  
The GCM indicator lights show normal sequence when the lights are on steady. When a problem  
occurs, the GCM flashes combinations of lights which indicate the most likely reason for the  
problem.  
Tra n s fo rm e r  
x
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.  
Blo w e r  
x
The blower pulls in air and mixes it with gas from the gas valve. The blower forces this mixture into  
the burner for combustion inside the boiler chamber.  
Air p re s s u re s w it c h  
The air pressure switch signals the control module, telling the control module whether air is  
moving through the blower.  
x
Wa t e r t e m p e ra t u re lim it s w it c h  
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes  
above its setting. (The circulators will continue to run as long as there is a call for heat.)  
x
S ys t e m c irc u la t o r  
The system circulator circulates water through the external (system) piping. The flow rate of the  
circulator is controlled by the GCM, depending on the temperature of the water entering the boiler  
sections.  
x
Byp a s s c irc u la t o r  
The GCM operates the bypass circulator to mix hot water from the boiler outlet with colder return  
water from the system when needed to prevent condensation of flue gases in the boiler.  
x
When the water returning to the boiler is below 140 °F, the GCM regulates the bypass circulator  
and system circulator flow rates to raise the water temperature up to 140 °F before it enters the  
boiler sections. By balancing these flow rates, the GCM can protect against condensation even if  
return water is as low as 60 °F.  
Wa t e r t e m p e ra t u re s e n s o r  
x
The water temperature sensor monitors the temperature of the water entering the boiler sections.  
The sensor sends this information to the GCM, telling the GCM how much to adjust the circulator  
flow rates to provide at least 140 °F entering water.  
10  
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
GOLD GV Water boiler — Series 3  
j
i
b
a
f
e
h
g
d
c
a
supply to system  
b return from system  
combustion air inlet fitting  
d flue outlet  
gas valve (see warning, right)  
f
pressure/temperature gauge  
g flueway inspection port cover  
c
h sensor hose trap  
i
manual air vent  
relief valve  
j
e
85001U  
Part number 550-141-812/0699  
11  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Lig h t in g in s t ru c t io n s 7 2 0 0 DERN g a s va lve  
Before attempting to start the boiler, check the boiler pressure temperature gauge. If boiler and system are  
full of water and properly pressurized, the gauge should read at least 12 psig on most systems. Operating the boiler  
without proper water content will damage boiler and controls and could result in severe personal injury, death or  
substantial property damage.  
FOR YOUR SAFETY READ BEFORE OPERATING  
If you do not follow these instructions exactly, a fire or explosion may result  
causing property damage, personal injury or loss of life.  
A. Thisappliancedoesnot haveapilot. It isequipped  
with an ignition devicewhich automatically lights  
the burner. Do not try to light the burner by  
hand.  
C. Use only your hand to depress and move Selector arm on gas  
valve. Never use tools. If the arm will not depress or move by  
hand, don't try to repair it, call a qualified service technician.  
Force or attempted repair may result in a fire or explosion.  
B. Before OPERATING, smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.See below.  
D. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and any  
gas control, which has been under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
Do not touch any electric switch; do not use any  
phone in your building.  
If you cannot reach your gas supplier, call the fire department.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above on this label.  
2. Set the thermostat to lowest setting.  
Robertshaw gas valve  
model 7200DERN  
Selector arm  
3. Turn off all electrical power to the appliance.  
4. Remove jacket top panel.  
5. This appliance is equipped with an ignition device which automatically lights the burner.Do  
not try to light the burner by hand.  
6. Depress Selector arm slightly and move left  
to OFF.  
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor.If you  
smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to  
the next step.  
8. Depress Selector arm slightly and move right  
9. Turn on all electric power to the appliance.  
10. Set thermostat to desired setting.  
to ON.  
85020  
NOTE: Selector arm cannot be  
moved to OFF unless arm is  
pushed in slightly. DO NOT force.  
11. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO  
APPLIANCE" below and call your service technician or gas supplier.  
12. Replace jacket top panel.  
TO TURN OFF GAS TO THE APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to be performed.  
3. Remove jacket top panel.  
4. Depress Selector arm slightly and move left  
to OFF.Do not force.  
5. Replace jacket top panel.  
12  
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Lig h t in g in s t ru c t io n s 36E ga s va lve  
Before attempting to start the boiler, check the boiler pressure temperature gauge. If boiler and system are  
full of water and properly pressurized, the gauge should read at least 12 psig on most systems. Operating the boiler  
without proper water content will damage boiler and controls and could result in severe personal injury, death or  
substantial property damage.  
FOR YOUR SAFETY READ BEFORE OPERATING  
If you do not follow these instructions exactly, a fire or explosion may result  
causing property damage, personal injury or loss of life.  
A. Thisappliancedoesnot haveapilot. It isequipped  
with an ignition device which automatically lights  
the burner. Do not try to light the burner by  
hand.  
C. Use only your hand to turn the Control knob on gas valve.  
Never use tools. If the knob will not turn by hand, don't try to  
repair it. Call a qualified service technician. Force or attempted  
repair may result in a fire or explosion.  
B. Before OPERATING, smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.See below.  
D. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and any  
gas control, which has been under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
Do not touch any electric switch; do not use any  
phone in your building.  
If you cannot reach your gas supplier, call the fire department.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above on this label.  
2. Set the thermostat to lowest setting.  
White-Rodgers gas valve  
model 36E  
Gas control knob  
3. Turn off all electrical power to the appliance.  
4. Remove jacket top panel.  
5. This appliance is equipped with an ignition device which automatically lights the burner.Do  
not try to light the burner by hand.  
6. Turn Gas control knob to OFF.  
7. Wait five (5) minutes to clear out any gas.Then smell for gas,including near the floor.If you  
smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to  
the next step.  
8. Turn Gas control knob to ON.  
9. Turn on all electric power to the appliance.  
10. Set thermostat to desired setting.  
Position  
indicator  
85022  
11. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO  
APPLIANCE" below and call your service technician or gas supplier.  
12. Replace jacket top panel.  
TO TURN OFF GAS TO THE APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to be performed.  
3. Remove jacket top panel.  
4. Turn Gas control knob to OFF.  
5. Replace jacket top panel.  
Part number 550-141-812/0699  
13  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Co m m o n p ro b le m s a n d s o lu t io n s  
Symptom  
Common Causes  
Possible Corrections  
Thermostat installed where drafts Locate thermostat on inner wall away from  
Rapid cycling boiler  
or heat affect reading  
heat sources or cool drafts.  
turns on and off frequently  
Heat anticipator in thermostat  
adjusted incorrectly  
Adjust thermostat per manufacturers  
instructions.  
Incorrect limit setting  
Set limit according to system needs.  
Maximum setting is 220˚F. Increase limit  
setting to decrease cycling.  
Insufficient water flow through  
boiler  
Check all valves to and from boiler. Return  
to proper setting.  
Confirm circulator size.  
Expansion tank sized too small  
Flooded expansion tank  
Inoperative limit control  
Call qualified service technician to check  
expansion tank operation and size.  
Frequent release of water  
through relief valve  
Call qualified service technician to check  
expansion tank operation.  
Call qualified service technician to replace  
limit control.  
Leaks in boiler or piping  
Have qualified service technician repair  
leaks at once to avoid constant use of  
makeup water. Makeup water can cause  
mineral deposits which, in turn, can cause  
boiler section failure. Do not use petroleum-  
base stop-leak compounds.  
Need to frequently add  
makeup water  
Oxygen corrosion due to leaks in Have qualified service technician repair at  
Black water condition  
boiler and piping  
once. Keep pH of water between 7.0 to 8.5.  
14  
Part number 550-141-812/0699  
G O LD G V S e r. 3 Us e r s in fo rm a t io n m a n u a l  
Co m m o n p ro b le m s a n d s o lu t io n s (continued)  
Symptom  
Common Causes  
Possible Corrections  
Mineral deposits in sections due to Call qualified service technician to de-lime  
Popping or percolating  
noise heard in boiler  
constant use of makeup water  
boiler, if necessary. In some cases,  
deposits will be too heavy to remove with  
de-liming procedures.  
Have qualified service technician repair  
leaks to eliminate need for constant  
makeup water.  
Incorrect pH of boiler water  
Call qualified service technician to check  
pH level and correct. pH should be  
maintained between 7.0 to 8.5.  
Insufficient water flow through  
boiler  
Check all valves to and from boiler. Return  
to proper setting.  
Confirm circulator size.  
Contaminated combustion air  
supply See page 4 in this  
manual.  
Remove any contaminating products. See  
page 4 in this manual.  
Metal flakes found in vent  
outlet or vent starter tee —  
flueway corrosion  
Provide outside air for combustion. Kit  
available through Weil-McLain distributor.  
Have qualified service technician pipe-up  
kit.  
Condensation of combustion  
gases in boiler sections  
Have qualified service technician check  
operation of mixing system. Repair/replace  
if necessary.  
Air in system  
Bleed air from system through air vents in  
radiators or baseboard units.  
Some radiators or  
baseboard units do not  
heat or are noisy  
Low system pressure  
Fill to correct pressure.  
Check for leaks in boiler or piping. Have  
qualified service technician repair at once.  
High limit set too low  
Adjust high limit to higher setting.  
Part number 550-141-812/0699  
15  
Weil-McLain Limited Warranty for  
Residential & Commercial Cast Iron Boilers  
xxRESIDENTIALWATERWARRANTYLimited Lifetime  
xxRESIDENTIAL STEAMWARRANTYLimited 10Year  
xxCOMMERCIAL WARRANTYLimited 10-Year  
These warranties do not cover:  
1. Components that are part of the heating systems, but  
were not furnished by Weil-McLain as a part of the  
boiler.  
NOTE: The residential steam and water warranties do not  
cover residential boilers installed in buildings other than one  
or two family dwelling units, unless they are buildings with  
individual boilers for each dwelling unit.  
2. The workmanship of any installer of Weil-McLains  
boilers. In addition, this warranty does not assume any  
liability of any nature for unsatisfactory performance  
caused by improper installation.  
First Year-(All Residential & Commercial Cast Iron  
Boilers)  
3. Any costs for labor for removal and reinstallation of the  
alleged defective part, transportation to Weil-McLain, if  
necessary, and any other materials necessary to  
perform the exchange.  
Limited Warranty for Cast Iron Boilers:  
Weil-McLain warrants that its cast iron boilers are free from  
defects in material and workmanship for one year from the  
date of installation. If any parts are found to be defective in  
manufacture, Weil-McLain will provide replacement of such  
defective parts.  
4. Improper burner adjustments, control settings,care or  
maintenance. Information is included in the installation  
Instructions, Owners Information Manual and/or Start-  
up, Service and Maintenance Instructions, and other  
printed technical material furnished by Weil-McLain with  
the boiler.  
Second Through Tenth Year-(Residential Water/Steam)  
Second Through Tenth Year-(Commercial Water/Steam)  
Limited Warranty for cast iron sections:  
Weil-McLain warrants that the cast iron sections of its water  
and steam boilers are free from defects in material and  
workmanship from the date of installation for the second  
through the tenth year. If, during such time period, any section  
is found to be defective, Weil-McLain will provide replacement  
for the original cast iron section(s).  
5. Boilers operated with combustion air contaminated  
externally by chemical vapors or with improper fuel  
additives, or with water conditions which may have  
caused unusual deposits in the cast iron sections.  
These warranties extend only to the first retail purchaser of the boiler  
and only to a boiler that has not been moved from its original  
installation site.  
Eleventh Year and Beyond - (Residential Water Only)  
Limited Warranty for Cast Iron Sections:  
Weil-McLain warrants that the cast iron sections of its  
residential water boilers are free from defects in material and  
workmanship for the eleventh year and beyond from the date  
of installation.If, during such time period, any section(s) is  
found to be defective, Weil-McLain will provide replacement  
for the original cast iron section(s) upon the payment of a  
proportionate charge based on the time the boiler has been  
in service. The proportionate charge will be equal to the  
appropriate percentage of the list price of such section(s) at  
the time the warranty claim is made, and will be determined  
as follows:  
THE WARRANTIES DESCRIBED ABOVE ARE IN LIEU OF ALL  
OTHERWARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT  
NOT LIMITEDTO ANY IMPLIEDWARRANTIES OF FITNESS FOR  
A PARTICULAR PURPOSE AND MERCHANTABILITY. WEIL-  
McLAIN EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY  
FOR CONSEQUENTIAL, INCIDENTAL, INDIRECT OR PUNITIVE  
DAMAGES FOR BREACH OF ANY EXPRESS OR IMPLIED  
WARRANTY.  
For prompt product warranty claims, notify the installer who, in turn,  
will notify the Weil-McLain distributor from whom he purchased the  
boiler. If this action does not result in warranty resolution, contact  
Weil-McLain Consumer Relations Department, 500 Blaine Street,  
Michigan City, Indiana 46360-2388, with details in support of the  
warranty claim. Alleged defective part or parts must be returned  
through trade channels in accordance with the Weil-McLain  
procedure currently in force for handling returned goods for the  
purpose of inspection to determine cause of failure. Weil-McLain  
will furnish new part(s) to an authorized Weil-McLain distributor who,  
in turn will furnish the new part(s) to the heating contractor who  
installed the boiler. If you have any questions about the coverage of  
this warranty, contact Weil-McLain at the address above.  
11th year - 5%; 12th year - 10%; 13th year - 15%;  
14th year - 20%; 15th year - 25%; 16th year - 30%;  
17th year - 35%; 18th year - 40%; 19th year - 45%;  
20th year - 50%; 21st year - 55%; 22nd year - 60%;  
23rd year - 65%; 24th year - 70%; 25th year and  
beyond - 75%.  
All Residential & Commercial Cast Iron Boilers  
These warranties are subject to the condition that the boiler  
must have been installed by a heating contractor whose  
principal occupation is the sale and installation of plumbing,  
heating and/or air conditioning equipment.  
Weil-McLain  
500 Blaine Street  
Michigan City, IN 46360-2388  
16  
Part number 550-141-812/0699  

Vita Mix XL VM0141 User Manual
Tokina MOTORIZED ZOOM LENS TM10Z0614N User Manual
Sony HANDYCAM DCR SX20EK User Manual
Sony CARL ZEISS PLANNER T 50MM F1.4 SAL50F14Z User Manual
Sony Car Amplifier User Manual
Sony Camera Accessories BRU H700 User Manual
Sirius Satellite Radio Stratus 6 SDSV6 User Manual
Sharp Viewcam VL NZ50U User Manual
Sanyo VCC ZM300 User Manual
Samsung BD C6800 User Manual