Weil McLain GOLD CGt SERIES User Manual

CGt SERIES BOILER  
SUGGESTED SPECIFICATIONS  
I. General Requirements  
A. Furnish and install ( ) low pressure packaged cast iron sectional boiler(s) that  
operate under induced draft.  
B. Install boiler-burner unit(s) in compliance with manufacturers installation instructions.  
All work must be done in a neat and workman like manner.  
C. Weil-McLain qty.( ) CGt ( ) PIN boiler(s) capable of burning natural gas at 5 to  
13”w.c.  
1. Packaged boiler (standard).  
2. Natural or propane gas fired.  
3. Water.  
4. Minimum 82% efficiency.  
5. Induced draft.  
6. Built-in Tankless Domestic Water Heater  
D. Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate –  
108 MBH per boiler.  
E. Boiler(s) shall be manufactured by ISO 9001 registered company to conform to  
Section IV of  
the ASME Boiler and Pressure Vessel Code.  
1. Individual sections (and section assembly) to be hydrostatically pressure tested  
at factory in accordance with ASME requirements.  
2. Maximum allowable working pressure 50 PSIG water and cast as part of  
section with ASME symbol.  
F. Regulatory Requirements  
1. Boiler(s) and controls to comply with applicable regulations.  
G. Submittals  
1. Submit shop drawings and product data.  
2. Submittal packet to include boiler (and burner) manufacturer descriptive  
literature, installation instructions, operating instructions, and maintenance  
instructions.  
II.  
Product  
1
a) Water boiler(s) controls furnished:  
1) High temperature limit setting to be 140 – 240 degrees.  
2) Combination pressure-temperature gauge with dial clearly marked  
and easy to read, installed with well for removal without draining the  
boiler.  
3) ASME certified pressure relief valve, set to relieve at 30 PSIG.  
Optional relief valves available up to and including maximum  
allowable pressure. Side outlet discharge type; contractor to pipe  
outlet to floor drain or near floor, avoiding any area where freezing  
could occur.  
4) Integrated spark module for blower control with indicator lights for  
easy troubleshooting.  
E. Boiler Manuals:  
1. Boiler, gas control and user’s information manual.  
2. Venting supplements and instructions.  
Weil-McLain  
500 Blaine Street  
Michigan City, IN 46360-2388  
3
C-879 (0700)  

Weil McLain ULTRA 310 User Manual
Wagan Bluetooth wireless handsfree car kit 2444 User Manual
Vista Davis & Sanford PRO12 User Manual
Victor 1240 3A User Manual
Toshiba TEC EO 11024 User Manual
Sylvania NB531SLX User Manual00000000#
Sony VCL HG0872 User Manual
Sony DSR 370 User Manual
Sony DCR DVD115E User Manual
SimpleTech Digital Camera Memory Card User Manual