| TRIAD Boiler Systems, Inc.   Series 8900 SH   Space Heating Control Panel   Operation and Installation Manual   TRIAD Boiler Systems, Inc.   West Chicago, IL 60185   Phone: 630-562-2700   Fax: 630-562-2800   Printed in USA. 1/12/04   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 1: INTRODUCTION   This manual explains the operation, installation and control of TRIAD Boilers using the   Series 8900 Microprocessor Control Panel. This manual provides information needed to   operate the panel and to fine-tune the boiler system depending on the requirements of the   structure that requires heating.   We have taken care to make this manual as easy to understand as possible, and to   anticipate common questions that might be asked. If we missed something along the way,   please feel free to call us or your TRIAD Manufacturer’s Representative with ideas and   suggestions.   INSTALLATION PROCEDURES:   The Series 8900SH Control Panel requires 120V A.C., 5 AMP, 60 Hz single phase to   operate. Service wiring should be run in an approved manner using black and white wire.   Minimum wire size shold be 14 guage or as local code requires.   After running the service wire to the panel, connect to the fuse block and neutral terminal,   which is marked. Be carefull that the panel is not mounted in an area that could experience   temperatures above 125°F.   Mounting the Outside Sensor:   The outdoor sensor is to be mounet on the North or Northwest outside wall of the building.   The sensor should be mounted no less than twelve feet above the ground. In a high-rise   installation, when the equipment room is on the top floor, install the sensor as close as   possible to the panel with it still on a North wall. Caution – Do not mount the sensor near a   heat source such as an air handler or lighting fixture.   Mounting the Return Line Sensor:   The immersion sensor is to be installed in the return side on the Primary Main of the boiler   system, at least 12 inches away from the nearest boiler.   Use 18 gauge solid copper wire between the senors and the control panel.   Use 18 gauge or heavier coded thermostat wire to connect the low voltage terminals   between the boiler and the control panel.   TRIAD recommends that the boilers be numbered. The terminal strip in the panel is   prenumbered at the factory. Direction of flow through the Primary Main should be noted.   The #1 boiler is at the “Supply End” of the Primary Main. The last boiler in the series is on   the “Return Side”.   Connect each boiler to the control panel ensuring that each boiler number is connected to   the corresponding number in the control panel. Maintain polarity! This means all first   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   terminals of each pair should be connected to the same terminal in each boiler control   center. Follow the drawing and wiring information carefully!   KEYPAD WITH ENTRY PROCEDURES   All functions of the Control Panel are activated through the use of two-digit Entry Codes via   a simple keypad, which operates as follows:   1 4 7 * 2 5 8 0 3 6 9 # 1. Press the appropriate two digit Entry Code.   2. Wait for the Entry Code in the display to begin flashing.   3. Enter the desired temperature, value code, etc.   4. Press the pound sign # to save the displayed entry.   Press the star sign * to abort an unwanted entry to prevent it from being saved and to revert   back to the last display code viewed. To discontinue the entry procedure, press the star sign   to start over.   STARTUP PROCEDURES:   To bring the Series 8900SH Control Panel online, the following three steps must be   completed:   1. Unlock the keypad using code 61. (See Section 8)   2. Enter the code settings through the keypad. (See sections 3 and 8.)   3. Calibrate the sensors. (See Section 4).   System shut down and start-up should be done through the keypad only, (by using Code   62) and NOT by shutting off power to the control panel. If the power to the panel is off for   more than 30 days, all control settings will be lost. In the event of temporary power loss the   panel has two built-in rechargeable batteries that will maintain the settings for up to 30   days. THE FIRST TIME THE PANEL IS TURNED ON THE BATTERIES WILL REQUIRE 48   HOURS TO TRICKLE CHARGE.   Code 61 is used to lock or unlock the system. Lock the system when you are completed   with the initial settings, or any time you change the settings. The system display readings   are always available, even with the keypad locked.   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   In the event of power loss or damage to the control panel the boilers will revert to self   control. At that point each boiler will cycle on and off according to its high limit control.   TRIAD recommends that in this situation the high limits be set at approximately 180°F.   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   WIRING DIAGRAM   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   OUTDOOR AND RETURN WATER LINE SENSORS:   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   SERIES 8900SH SPECIFICATIONS:   9.8 vac, 50/60 Hz, max input 35 vac with transient/surge protection   Input Voltage   3VA   Avg. Power Consumption   Battery Protected Memory   CPU   8K RAM   Industry standard Z80, 4MHz   Internal crystal based clock   8K EPROM   Time Clock   Operating System Memory   Serial Interface   1200 Baud standard TTL signal level. Can be interfaced with modem   or direct connect to IBM compatible PC   Sensor Input Channels   Sensor input Range   Six   Voltage input of 1.9VDC is read at a value of –55 by the controller.   Voltage input of 3.1VDC is read as a value of 200. If an input is   shorted to common, the controller will read –40 at the input. If input   is open, the controller will read 230.   Within + or – 1 degree Fahrenheit   Sensor Accuracy   Sensor Type   Solid-state linear sensing   Up to 24   Output Channels   Output Capacity   Relay Type   30VA, 24VAC   Coil 12VDC / “Dry Contact”   5VDC   All Other Components   Wiring   Multiconductor 18 AWG thermostat wire is recommended to wire   sensor inputs and control outputs. Maximum length of wire from   control panel to sensor is 300 feet.   Two 1.2V sealed nickel-cadmium rated at 720 hrs. Standard charge   15 hrs at 18mA.   Light Emitting Diodes   Batteries   Display   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   GLOSSARY:   Entry Codes: The set of two digit numbers that allow the operator to interact with the   control panel.   Error Code: A code shown on the display that indicates a problem exists either in the   sensors or in the computer itself.   Fine Tuning: Utilizing certain codes concerned with the boiler run time and the boiler   staging to carefully "size" the output to the building to obtain the highest efficiency possible.   High Limit: A control mounted near the top of the boiler that shuts down the main flame of   the burner if the boiler temperature exceeds the high limit setting.   Manual Override: When Code 63 is used to manually override the control panel.   Potentiometer: An electronic device used to adjust the sensor temperatures.   Program: A set of commands that tells the computer which calculations to carry out.   Ratio Control: The control that allows the operator to vary the Return Water Line   temperature in relation to the drop in outside temperature.   Relay: An electromechanical device that opens or closes a current path on demand.   Sensor: A device used with the control panel to measure relative heat and cold.   Outside Temperature Shutdown: The pre-selected temperature that, when reached, shuts   the boiler system off.   Stage: The position of a boiler in the firing sequence.   Supply Water Line: The supply water line is the line that provides heated water from the   boilers to the building.   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   LIMITED FIVE -YEAR FULL TERM WARRANTY   The Manufacturer warrants the equipment described as the Series 8900 Control Panel to   be free from defects in material or workmanship under normal use and service. The   Manufacturer's obligation under this warranty shall be limited to repairing or replacing any   part of said panel, which the Manufacturer’s examination shall disclose to its satisfaction to   be thus defective, for a period of One (1) Year after date of original installation provided   proper evidence of such installation is recorded at the factory and installation is in   accordance with TRIAD design.   The Manufacturer further agrees that if the Series 8900 Circuit Board(s) shall be   disclosed to the manufacturer's satisfaction to be defective under normal use and service   during a period of Five (5) Years after date of original installation, a replacement Circuit   Board will be furnished the owner free of charge, exclusive of any applicable federal, state   or local taxes.   All repairs and/or replacements furnished shall be F.O.B. TRIAD's factory. The   Manufacturer shall not be liable for freight, drayages installation and/or other labor costs   and any other costs or expenses involved with direct replacement of the defective parts.   Defective part failures covered by this warranty should be promptly reported to the   Manufacturer. This Warranty voided if Panel sustains an excessive surge in primary or   secondary voltage.   This Warranty is in lieu of all other warranties expressed or implied and of all other   obligations or liabilities on the part of the Manufacturer, and the Manufacturer neither   assumes nor authorizes any other person(s) to assume for it any obligation or liability in   connection with the sale of said equipment or any part thereof. This Warranty will not apply   to said equipment or any part thereof which has been subject to any accident, negligence.   misapplication, alteration, abuse or misuse. Nor does it apply outside the boundaries of the   United States.   Section 1   Introduction And Specifications   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 2: SEQUENCE OF OPERATION   All functions of the Control Panel are activated through the use of two-digit Entry Codes that   provide instruction to the panel. These codes are explained in more detail in Sections 3 and 8.   The sequence of operation is best explained through the following example:   Assume a six boiler TRIAD system heating an office building that is empty at night and on   weekends, an average outside temperature of 70°F, with an expected night temperature of   35°F.   The control panel is on and controling the building heat. Through Entry Codes it has been   instructed as follows:   Turn the heat on when the outdoor temperature drops below 60°F and off when it rises above   60° F.   Maintain a minimum Return Water Line temperature of 100°F, with a starting outdoor   temperature of 60° F.   The manual Reset Ratio is set on Automatic.   The rate of system change factor is set at .10.   The boilers will fire in a sequence of 1, 2, 3, 4, 5, 6, and boiler number 1 is the lead boiler.   At 6:00 pm the temperature will automatically be set back by 5°F, with a return to normal   temperature occuring 6:00 am.   As the outside temperature gradually drops from 70°F to 60°F, the control panel prepares to   bring on heat. The decision has been made for the boilers to fire in a sequence of 1 through 6,   so as the outdoor air temperature drops below 60°F, the control panel calls for the number 1,   or lead boiler, to fire. As boiler 1 fires it begins to add heat to the return main. Because it is the   designated lead boiler, number 1 will continue to fire intermittently while heat is called for. The   lead boiler shuts off when the required Return Water Line temperature is reached (determined   with code 14) and fires again when the Return Water Line temperature has dropped 2°F. This   allows all the cycle time and the attendant wear and tear to be confined to the lead boiler. Any   boiler can be designated the lead at any time.   As the temperature outside continues to drop, the control panel notes that the Return Water   Line temperature has not reached the 100°F it must maintain, so it calls for the number 2 boiler   to fire. However, before it can bring on the number 2 boiler it checks to make sure that the   other instructions entered into the control panel are being satisfied. These are (i) the rate of   system change factor, (ii) the required Return Water Line temperature, and (iii) the calculated   Reset Ratio. With this information the panel can fire the other boilers in a way that will most   efficiently satisfy the heating needs.   Section 2   Sequence of Operations   Series 8900SH Control Panel   Operation And Installation Manual   If the outside temperature continues to drop, then the calculated Reset Ratio (code 23) will be   activated. More heat will be required to maintain the building temperature. To determine how   much more, the control panel monitors (when in Automatic mode) the outdoor air temperature,   the current Return Water Line temperature, the design return water temperature, and the   design outdoor temperature. It then determines the Reset Ratio, which is simply a way of   calculating how much heat to add to the system to make up for heat loss. If the Reset Ratio is   set at 1:1.5 then for every 1°F the outdoor temperature drops, the Return Water Line   temperature will be increased by 1.5°F. It is possible to override the automatic mode and enter   your own Reset Ratio in code 23.   The next code that is monitored is the Rate of Change Factor (code 24) which sets the speed   at which boilers are brought on line and off line. This rate of change factor has a range of .01   to 2.00. The rate of change factor is a timer that counts from 0.00 to 99.00. When 99.00 is   reached, a boiler is brought on line or taken off line. The rate of change factor is important   because it allows for a balancing of how much heat is increased against how much heat the   building naturally loses. The rate of change factor also allows you to determine how long each   boiler will run before firing the next boiler in line.   Assume it is now 7:00 pm, the building is empty and dark, and three of the boilers have been   used to maintain the building heat. Because the control panel was set to lower the   temperature in the Return Water Line at 7:00 pm, it directs one boiler to go off line, allowing   the Return Water Line temperature to fall the required 5 degrees. At 6:00 am the panel will   increase the Return Water Line temperature back to normal so the building will be warm when   the employees arrive.   An important feature of the Series 8900SH control panel is its ability to handle setback   recovery. The control panel starts monitoring the Return Water Line temperature and outdoor   temperatures 2 hours prior to the 6:00 am set point so it can calculate the most efficient way to   fire the boilers. Instead of all the boilers firing simultaneously, the panel may only fire one   boiler, but allow it to run longer to save on fuel.   If heat was needed in the building after 7:00 pm a simple keypad entry (code 81) will override   the setback. This set back override can be done in advance, or at the time the heat is needed.   Assume it is now early afternoon and the outdoor temperature continues to rise. Only two   boilers are needed to maintain the building temperature. When the outdoor temperature rises   above 60° F, the control panel shuts the system down until the next time it's needed.   Section 2   Sequence of Operations   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 3: ENTRY CODES   The control panel is operated by Entry Codes, which are simple two digit numbers that provide   the panel instructions. However, before entering any codes, you should become familiar with   the features of the control panel.   The 8900SH has a keypad and a set of 6 display LED’s. A code is entered by simply pressing   any of the two digits on the keypad, which will then cause two LED’s on the far left to light up   in the order of the keys pressed. You must wait for the Entry Code in the display to begin   flashing before entering the desired temperature, value, code, etc.   The (*) star key on the lower left of the keypad cancels any code you have entered. If the   wrong code is entered, simply press the (*) key and start over.   IF THE PANEL DOES NOT POWER UP, OR THE RED DISPLAY LED’S ARE NOT ON,   REFER TO THE WIRING DIAGRAM AND INSTALLATION INSTRUCTIONS. ALSO, REFER   TO “SENSOR TROUBLESHOOTING” IN SECTION 5.   Below is a quick reference table showing the codes used to set up the control panel’s basic   operation. Do not be concerned that the codes are not listed in numerical order.   YOU MUST ENTER THE CODES IN THE ORDER SHOWN BELOW, THEN CALIBRATE ALL   SENSORS CONNECTED TO THE CONTROL PANEL. MORE DETAIL ON EACH CODE IS   AVAILABLE IN SECTION 8.   CODE   60   FUNCTION   This code starts the sequence for the “60” codes.   This code displays the System Mode, which tells us that the boiler system is either ready to   heat or is shut off. Press 62 then press 0 (for System Off) or 1 (for System On).   62   63   65   This code manually overrides the control panel to control the boilers directly. Press Code 62   first, and enter 0, then press Code 63 and enter the number of the boiler you want to fire.   This code allows for the panel to control the system primary pump. After entering code 65,   entering 0 shuts the pump off, entering 1 starts the pump, and entering 2 automatically   cycles the pump. In the automatic cycle mode, the pump starts and stops along with the   boilers according to the system shutdown outdoor temperature chosen in code 21. Please   note that the pump starter must be an Automatic Reset type.   This code controls the temperature setback feature. When 66 is entered, the display will   show 0 or 1. Press 0 to turn it off, or press 1 to turn it automatically on.   66   67   68   This code displays the 24 hour (military) clock. Press 67, enter the hour and minutes, and   press # to save.   This code displays the day of the week and the day of the month. Press 68, enter the day of   the week and press #, then enter the day of the month, 01 to 31, and press #.   Section 3   Entry Codes   Series 8900SH Control Panel   Operation And Installation Manual   This code displays the month and year. Press 69, then enter Month, 1 to 12, and the year,   01, 02, 03, etc. Then press #.   69   This code starts the sequence for the 20 codes.   20   This code stores the outside air temperature at which the heating system cycles off and on.   While the system can be set anywhere between 0° F and 120° F, TRIAD recommends a   setting of around 60° F. Press 21, enter the desired temperature, and the display will show   the setting. The system will now shut down if the outside temperature rises above 60° F and   turn back on when it drops below 60° F.   21   This code sets the Minimum Return Water Temperature. TRIAD recommends a setting of   100° F, even though the system can handle a range of between 50° F to 190° F.   22   23   This code allows you to override the computer to manually set the Outdoor Reset Ratio. The   available range is from .10 to 2.50° F. Press 23, enter your desired Reset Ratio, and then   press #. Control of the Outdoor Reset Ratio can be returned to the computer by entering “0"   in code 23 and then pressing # .   This controls the Rate Of Change Factor, which determines how quickly the boilers are   brought on line or dropped off line. The Rate Of Change Factor simply indicates the speed   of the counter in code 17 (which counts to 100 and is described in Section 6). The range of   code 24 is between .01 to 2.00 seconds. For example, a setting of 1.00 will be a 100 second   delay, a setting of 2.00 will only be a 50 second delay, because the timer is counting up to   100 by two’s (twice as fast). TRIAD recomends starting with setting at .10.   24   This code tells the panel how many boilers it will control, up to a maximum of 24.   26   27   This code sets the Design Return Water Line Temperature, which is determined by the   Outdoor Design Temperature for your geographic region. The range of this code is 100° F to   225 ° F. To activate, press 27, input the desired Design Return Water Line Temperature,   and then press #.   This code sets the Design Outdoor Temperature. The range can be from -20 to 50. To   enter, press 28, input the correct Design Outdoor Temperature, and then press #. To enter a   number below 0° F just press any two (2) keys side by side at the some time to obtain a   negative number, then enter your temperature.   28   Stage/Relay/Boiler Activation (On). Please read section 8 for a complete explanation of this   function before setting the control panel.   40-42   Not used at this time. Zero Out this code by pressing 50, then 9999, then #.   50-57   30-37   This code allows for temperature set-back when the building is empty.   DO NOT ENTER SETTINGS IN THIS CODE NOW. ZERO IT OUT AT THIS TIME BY   ENTERING 30, THEN 9999, THEN (#).   Code 30 sets back the temperature for all 7 days of the week, and codes 31 through 37 will   set back the temperature on a specific day or days.   Zero this out by entering 9999 in Code 91 and pressing the # sign.   90   Section 3   Entry Codes   Series 8900SH Control Panel   Operation And Installation Manual   Record your settings the following worksheet and keep for future reference.   Date of Entries _________   Worksheet For Code Settings   CODE   62   FUNCTION   SETTINGS   System Mode   65   System Primary Pump (When Used)   Setback – On/Off   66   67   Hours and Minutes – 24 Hour Clock   Day of the Week – Day of the Month   Month and Year   68   69   21   Outside Temperature Shutdown Setting   Minimum Return Water Temperature Setting   Reset Ratio Setting (Manual Setting When Used)   Rate of Change Factor   22   23   24   26   Total Number of Boilers   27   Design Return Water Temperature Setting   Design Outdoor Temperature Setting   28   Section 3   Entry Codes   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 4: SENSOR CALIBRATION   This section will deal with the calibration of the sensors that measure both outside air   temperatures and water system temperatures. Correct calibration is very important so the   control panel receives the accurate information necessary to properly control the building   temperature.   The TRIAD system uses a minimum of two sensors, one which is placed outside, on the north   or northwest side of a building, and the second which is placed in the Return Water Line   coming back to the boilers.   The panel moniters temperature by passing a very weak electrical current through the sensor   and back to the control panel. The resistance to this current changes when the temperature   around the sensor changes, which is interpreted by the panel as an increase or decrease in   temperature.   CALIBRATION:   To calibrate the sensors you will need an accurate digital thermometer, a small non-magnetic   flat screwdriver, a medium non-magnetic flat screwdriver, and a small crescent wrench.   PLEASE NOTE THAT THE SERIES 8900SH CONTROL PANEL MUST BE TURNED ON FOR AT   LEAST 15 MINUTES BEFORE ATTEMPTING TO CALIBRATE THE SENSORS.   Press the function CODE for the sensor to display the current reading.   CODE xx = Potentiometer # = Sensor #   CODE 11 = R26 = Outdoor Sensor = S1   CODE 12 = R27 = Return Temp. Sensor = S3   Take off the cover of the main circuit board by loosening the two screws on either side of the   cover and pulling it straight off.   The sensors should be wired up to the sensor terminal strip. If they are not, skip to   “Troubleshoooting The Sensors” in Section 5.   Then, locate the outside sensor and take a reading with your digital thermometer as close as   possible to the sensor. Now, go directly back to the control panel and enter 11. The display   light will indicate what the panel thinks is the temperature at the outside sensor; (S1). Carefully   Section 4   Sensor Calibration   Series 8900SH Control Panel   Operation And Installation Manual   rotate the screwdriver slot on the potentiometer R26 until the temperature shown on the   display matches the outside temperature. The sensor is now calibrated.   Now locate the Return Water Line sensor and measure the temperature as close as possible.   Then, at the control panel enter 12. The display will show what the panel believes is the Return   Water Line temperature. Correct as before, turning the screwdrive slot on potentiometer R27.   There are three ways to determine accurate Return Water Line temperature.   1. Clean the copper surface of the return line next to the sensor well and tape the   thermometer probe to the clean copper. Wait until the temperature shown on your digital   thermometer stabilizes, and accept that as the correct temperature.   2. Remove the sensor from the well and let it hang in the air as far away from the hot   return line as possible. Place your thermometer probe next to the sensor in the air. Wait for   your digital thermometer to stabilize: Take that temperature and use it to calibrate your sensor.   When you return the sensor to the well on the return line, the sensor will show an accurate   temperature.   3. Insert the probe of your digital thermometer next to the sensor in the sensor well on the   Return Water Line.   Section 4   Sensor Calibration   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 5: SENSOR TROUBLESHOOTING   The wiring within the control panel from the Terminal Strip For Field Connections to the sensor   input terminals on the circuit board are completed at the factory.   Inside the panel is a second set of wires from each sensor to the “Terminal Strip For Field   Connections” that is generally completed by the electrical contractor.   Each pair of wires from a sensor is connected to the terminal strip inside the panel (for field   wiring) and from there to the sensor input terminals on the circuit board. Below is a list of   where the wires for each sensor are attached and the code that allows you to read the   temperature.   SENSOR LOCATION   Outside Sensor   Return Sensor   INPUT TERMINALS   ENTER CODE   S1   S2   11   12   GENERAL TROUBLESHOOTING   If the display is showing Error Code 230, either the sensor is bad or a wire is broken. To   check the wire between the input terminals on the circuit board and the sensor itself remove   the circuit board cover and, using the chart above, identify the correct sensor. With a small   screwdriver, loosen the two terminals and gently remove both wires. With an Ohm metor,   check the resistance (continuity) between the two wires. No resistance (continuity) indicates a   wire is broken. The second test is to attach a good sensor to the terminal strip in place of the   one removed. If the display now reads a temperature then the old sensor is probably bad and   should be replaced.   If the display is showing Error Code -40, the wires either have a short or the wires are   reversed at the sensor input terminals. Each sensor has a positive wire and a negative wire   that could have been reversed during installation. To test for this, remove the cover and   reverse the wires. If the display now reads a temperature the problem is solved.   If the display still reads Error Code -40 the wiring between the sensor terminal input and the   sensor itself must be checked for shorts. Remove the wires from the terminal strip and, using   an Ohm meter set at 1K, touch the Ohm motor leads together and adjust the needle to 1. Now   touch the Ohm meter leads to the wires from the sensor. If the needle again goes to 1, or the   and of the scale, the wires are shorted. If the needle only moves part way up the scale, the   sensor is bad and must be replaced.   If you are adjusting a sensor potentiometer R26 through R31, and the display is not changing,   make sure the correct monitor code for the sensor being adjusted has been entered. If the   code is correct and the display still will not change, replace the sensor.   If the sensor has been replaced and the display continues to show the incorrect temperature,   the control panel may be bad. Try a different sensor by switching them around on the terninal   strip. If this still does not work, send the the board back to TRIAD for recalibration.   Section 5   Sensor Troubleshooting   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 6: MONITORING CODES   Monitoring codes display the information programmed into the control panel, such as what   temperatures it was asked to maintain, what temperature setbacks it was instructed to use,   and any other customized settings.   The difference between Monitoring Codes and Entry Codes is that Entry Codes allow us to   enter items such as the time, dates, setback, etc. through the keypad, while Monitoring Codes   allow us to display what was entered.   CODE   DISPLAY   This code begins the automatic monitoring of the first nine codes. When code 10 is entered,   the control panel will sequence through codes 11 to 19, displaying each for 3 seconds before   moving to the next one.   10   This code displays the Outside Air Temperature.   11   12   13   This code displays the current Return Water Line temperature.   This code displays the day of the week and the 24 hour military time clock, alternating   between the two.   This code calculates the required Return Water Line Temperature using the Outside   Temperature, the Ratio that was entered, and other information within the processor. Codes   12 and 14 are usually very close.   14   In this code, the panel checks the values of Codes 11, 12, 27, and 28, to calculate the   Outdoor Reset Ratio. This automatic function can be overridden via code 23.   15   16   This displays the heating system status by using twelve horizontal display LED’s that   indicate which functions are operating. Each light correlates to a function, as shown below:   BOILER ON   NA   SYSTEM PUMP   SYSTEM MODE   NA   SYSTEM ON   AUTO SETBACK   NA   NA   NA   NA   SETBACK OVERRIDE   --   --   --   --   --   --   --   This code allows you to monitor the computer. The control panel is continually reviewing the   Return Water Line temperature (Code 12) and comparing it to what the temperature should   be in Code 14. When viewed, this code will be counting up to 99.00. When 99.00 is   reached a boiler is either brought on line or dropped off line. The speed at which the   computer counts up to 99. 00 is based on the Rate Of Change Factor entered in code 24.   17   This shows the last boiler that has come on, and for how many minutes it has been running.   18   19   This indicates which boiler(s) are currently running. It rotates as you watch, showing each   boiler number.   Section 6   Monitoring Codes   Series 8900SH Control Panel   Operation And Installation Manual   This code, and the ones that follow, are all time clocks, providing elapsed running time since   the boilers were originally installed. Press Code 90 to start the display.   90   91   92   This code allows you to pick which boiler to check the elapsed time on. To view boiler # 5   enter 91, and then 5. Then the panel will automatically go to code 92.   This code shows the total number of hours and minutes that a boiler has run since it was   installed up to a maximum of 23 hours, 59 minutes. When 24 hours have accumulated one   day is automatically added to code 93. Press # to view code 93.   This code shows the total number of days a boiler has run since it was installed up to a   maximum of 9999.   93   You can clear the accumulated time for all boilers and start over at time zero by entering code   91, then entering 99, and pressing the # sign. This is useful when boiler maintenance is   planned. By zeroing out the elapsed time after a maintenance procedure, you now have a   timer that can count upwards to the point when maintenance must be done again.   NOTE: WHEN THE KEYBOARD LOCKED, ALL CODES CAN STILL BE VIEWED.   OTHER IMPORTANT ITEMS:   The panel has two rechargeable batteries that will reain all stored information for 30 days if the   power goes out for any reason.   If the control panel fails for any reason, or is accidentally unplugged, the boilers automatically   come on and are then controlled by their own high limit switches. Thus, the system will never   be out of heat because of panel failure.   Section 6   Monitoring Codes   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 7: ERROR CODES   Error codes are the way the control panel indicates if there are any system problems or faults.   DISPLAY   EXPLANATION   If this is displayed after entering any of codes 11, 12, 73, 74, 75, or 76, then you have   an Open Sensor, which means the sensor is bad, or the wire connected to the sensor   input terminal is broken. See Section No. 5, Sensor Troubelshooting to test.   230   If this is displayed after entering any of codes 11, 12, 73, 74, 75, or 76 then you have   either a bad sensor, or the polarity at the sensor input terminals is reversed. See Section   No. 5. Sensor Troubelshooting to test.   -40   This will display if you attempt to enter a code the panel does not recognize. Make sure   you are using a valid code.   CODE N.A.   Some codes have limits. For example, code 26 tells the panel the number of boilers in   the system. The maximum number it can operate is 24, so if 25 was entered the display   would read “out of range”.   OUT OF   RANGE   This display, which means program lost, could be an indication of any of the following:   PROG   LOSE   1. The first time the control panel is powered up PROG LOSE may flash. Press * (star)   to reset the computer and then proceed with entering the codes.   2. If pressing * (star) does not clear the display, the E- PROM chip may be bad. Contact   your TRIAD service representative or TRIAD Boiler Systems for a replacement.   3. If the replacement of the E-PROM chip does not solve the problem. the batteries may   have gone bad. In this case the computer will have to be returned to the factory for   service.   Replacement of E-PROM Chip:   The E-PROM Chip can be replaced if (i) it fails or (ii) to update the program and keep it tailored   to the heating system.   THE E-PROM CHIP HAS A NOTCH ON ONE END. WHEN THE CHIP IS INSERTED INTO   THE SOCKET IT IS CRITICAL THAT THIS NOTCH LINES UP WITH A MATCHING NOTCH   ON THE RIGHT SIDE OF THE SOCKET. INSERTING THE CHIP WITH THE NOTCH TO THE   LEFT WILL PERMANENTLY DISABLE THE E-PROM.   To insert the chip in the socket, gently rest the upper pins in the upper sockets without   applying any downward pressure, and then insert the lower pins into the lower sockets. DO   NOT FULLY INSERT THE PINS! With all pins properly alligned, place your fingers behind the   circuit board to prevent it from bending, and your thumbs on the top of the EPROM. Apply slow   and even downward pressure with your thumbs until the pins are snugly seated.   Section 7   Error Codes   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 8: ENTRY CODE DETAILS   This section provides more detail to better understand the control panel Entry Codes.   The Keypad is used to (i) provide instructions to the computer (ii) read, via the display LED’s,   what current settings are stored in memory, and (iii) aid in monitoring the system after the   settings are complete.   KEYPAD WITH ENTRY PROCEDURES   1 4 7 * 2 5 8 0 3 6 9 # 1. Press the appropriate two digit Entry Code.   2. Wait for the Entry Code in the display to begin flashing.   3. Enter the desired temperature, value code, etc.   4. Press the pound sign # to save the displayed entry.   Press the star sign * to abort an unwanted entry to prevent it from being saved and to revert   back to the last display code viewed. To discontinue the entry procedure, press the star sign to   start over.   ENTRY CODE 21: OUTSIDE TEMPERATURE SHUTDOWN SETTING   PRESS   ENTER YOUR CHOICE   PRESS = SAVE KEY   + = ENTRY CODE   2 1 6 0 # FOR AN OUTSIDE TEMPERATURE SHUTDOWN SETTING OF 60°F.   THE AVAILABLE RANGE IS + 0°F to + 120°F   This code shuts down all boilers when the outside temperature reaches or goes above a   specified point and turns on the boilers when the outside temperature drops below the   specified point. A common setting is around 60°F degrees.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 22: MINIMUM RETURN WATER TEMPERATURE SETTING   PRESS = ENTRY CODE   ENTER YOUR CHOICE   PRESS = SAVE KEY   + 2 2 1 0 0 # FOR A MINIMUM RETURN WATER TEMPERATURE SETTING OF 100°F.   THE AVAILABLE RANGE IS + 50°F to + 190°F   This code allows the panel to set and monitor a minimum allowable boiler system Return   Water Line temperature. When the outside temperature drops below the setting in code 21,   the control panel will maintain a minimum of 100°F in the boiler system return line.   ENTRY CODE 23: OUTDOOR RESET RATIO SETTING   (AUTOMATIC CALCULATION)   PRESS   ENTER YOUR CHOICE   PRESS = SAVE KEY   + = ENTRY CODE   2 3 0 # The above setting of "0” is entered when you want the computer to automatically calculate the   outdoor Reset Ratio setting. This calculation will be displayed in monitor code No. 15.   ENTRY CODE 23: OUTDOOR RESET RATIO SETTING   (MANUAL CALCULATION)   PRESS   ENTER YOUR CHOICE   PRESS = SAVE KEY, FOR A RESET RATIO OF 1.00.   + = ENTRY CODE   2 3 1.   0 0 # THE AVAILABLE RESET RATIO DEGREE RANGE IS -.10 TO 2.50   This code allows for manual fine tuning of the boiler system to the requirements of the   building’s host system. As an example, assume it is 60°F degrees outside and that 100°F   water is needed in the system Return Water Line. As night approaches and the temperature   begins to drop, the 100°F Return Water will not keep the building warm. So, as the outside   temperature drops one degree, the control panel senses this and increases the Return Water   Line temperature by the ratio amount. If the ratio is set at 1.00, as in the example above, for   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   every 1°F the outside temperature drops, the Return Water Line temperature is increased 1°F.   If the ratio is set at 1.50, the Return Water Line will increase 1.5°F for every 1°F drop in   outside temperature.   THE FORMULA BELOW WILL HELP YOU DETERMINE THE INITIAL RATIO SETTING.   Outdoor Reset Ratio Formula:   Design Return Water Temperature – Minimum Return Water Temperature = Outdoor Reset   Outside Shutdown Temperature – Outside Design Temperature   Ratio   Example:   180°F - 100°F =   60°F - (-10°F)   80°F = 1.14 Reset Ratio   70°F   ENTRY CODE 24: RATE OF CHANGE FACTOR   PRESS   ENTER YOUR CHOICE   PRESS   THE AVAILABLE RANGE IS FROM .01 TO 2.00   + = ENTRY CODE   2 4 .1   0 = SAVE KEY, FOR A RATE OF CHANGE FACTOR OF .10.   # This code allows you to set the speed of the counter that was explained in code 17. The Rate   of Change Factor directly influences how fast or slow boilers are brought on line when heat is   called for. If boilers are brought on line too quickly, a waste of fuel can result due to too many   boilers running and short-cycling. Too long a count between boilers may result in   unsatisfactory heat to the building. TRIAD recommends an initial setting of .10. The lower the   factor, the longer (slower) the response time of the boilers, and the higher the factor, the   shorter (faster) the response time.   ENTRY CODE 26: NUMBER OF BOILERS TO BE CONTROLLED   PRESS   ENTER YOUR CHOICE   PRESS   + = ENTRY CODE   2 6 2 4 = SAVE KEY, TO CONTROL 24 BOILERS.   # THE AVAILABLE RANGE IS FROM 1 TO 24   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 27: DESIGN RETURN WATER TEMPERATURE SETTING   PRESS = ENTRY CODE   ENTER YOUR CHOICE   PRESS = SAVE KEY, TO SET DESIGN RETURN WATER TEMPERATURE.   + 2 7 1 8 0 # THE AVAILABLE TEMPERATURE RANGE IS +100°F TO +225°F   This sets the Design Return Water Temperature. It is important to set it correctly because   many of the panel’s calculations are based on this figure. Usually the system design engineer   will have already calculated this. However, if you do not know the proper temperature simply   use 180°F.   ENTRY CODE 28: OUTSIDE DESIGN TEMPERATURE SETTING   PRESS   ENTER YOUR CHOICE   PRESS   + = ENTRY CODE   2 8 1 0 = SAVE KEY, TO SET OUTSIDE DESIGN TEMPERATURE.   # THE AVAILABLE TEMPERATURE RANGE IS - 20°F TO +50°F   This code sets the Design Outside Temperature, which is the average coldest temperature   your geographic area is expected to experience. The correct figure can be found by calling a   local heating contractor or your mechanical engineer.   To enter a number below 0°F degrees, press any two keys side by side at the same time to set   the display to a negative number, then enter the temperature.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 30 – 37: WATER TEMPERATURE SETBACK SCHEDULES   PRESS   + = ENTRY CODE FOR ALL 7 DAYS OF THE WEEK   3 0 30   34   ALL 7 DAYS   MONDAY   THURSDAY   31   32   33   35   FRIDAY   36   TUESDAY   SATURDAY   37   WEDNESDAY   SUNDAY   SETBACK TIME ON AND   TEMPERATURE SETBACK   1 8 6 0 0 5 0 = 6:00 AM, 5°F SETBACK   = 6:00 AM, 0°F SETBACK   FIRST SETBACK OFF-TIME   PRESS   = SAVE KEY   # This code programs water temperature setback schedules for either the entire week or for   each day of the week. This feature is primarily used for night, or whenever the building is   empty.   The control panel uses 24 hour military time. Choose the hour (on the hour) for setback to   begin, say 6 p.m., or 1800 hours in the example above. Then enter the amount to set back,   which can be anywhere from 1°F to 99°F. The example above assumes 5°F. After entering   the “on time", and the degrees to be setback, press the enter key (#). When # is pressed at   the end of each entry, it not only enters the values into program memory, the display is   advanced to the next slot.   Next, input the time to turn the setback off to return to normal running conditions, 6:00 am in   this example. The panel now knows to lower the water temperature by 5 degrees at 6 p.m.   and return to the original temperature at 6 a.m.   An important feature of the panel is that it begins the warming process two hours prior to the   programmed time. Thus, the panel will begin monitoring both the outside and Return Line   Temperatures at 4:00 a.m to determine the most fuel efficient way to reach the desired water   temperature by 6:00 a.m..   Each of the codes 30 through 37 can handle four complete on and off setback schedules   every 24 hours. Remember that code 30 sets the time for all seven days of the week, and 31   through 37 sets each individual day for its own setback. A simple way to customize certain   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   days is to input the times and temperatures that will be the same for the most of the days into   the 30 code, and then enter the times and temperatures that will be different into the   appropriate Entry Code(s) 31 through 37. The values entered into the 30 code are saved in   program memory, but a specific entry into a specific day will override the 30 code entry for that   day.   To eliminate the entries in codes 30 through 37 simply enter 9999, then press #.   Please note that codes 30 through 37 are used for scheduling purposes only. In order to   activate the automatic operation of the setback times and temperatures, another entry must be   made into Entry Code 66.   ENTRY CODE 40 – 42: STAGE /RELAY /BOILER ACTIVATION (ON)   These codes determine the boiler firing sequence.   The control panel has 24 stages, and thus can control up to 24 boilers. Inside the control   panel enclosure is a terminal strip that is connected to the boiler wiring and sensor wiring. For   each boiler there is one on/off relay (mounted under the panel cover or on the inside of the   enclosure) which closes to fire a boiler and opens to shut down a boiler.   Your mechanical contractor should have numbered the boilers to correspond with the numbers   on the terminal strip. If not, use Code 63 to manually activate boiler No. 1. If it won't fire, rewire   the terminal strip so relay 1 fires boiler 1, relay 2 fires boiler 2, etc. The sequence in which the   boilers fire is important for both efficiency and maintenance reasons.   Now, assume a system has 12 boilers. To sequence them, use Code 40 to enter a 1 to   represent the first stage to fire when there is a call for heat. (See example No. 1).   Then enter a “blank” or zero (0) to separate the stage number from the boiler number.   Then enter a 1 so the first stage called on will fire boiler number one. If you make a mistake,   enter 9999 and # to start over.   When # is pressed, the display will clear and show you 40 0000. This means that the   information related to stage 1 was saved and you have been bumped to the second slot.   There are eight slots in each code 40 through 42. If you forget where you were or get   confused, simply press *, which will take you out of the 40 codes and back to the last code   monitered. Enter Code 40 again, and then repeatedly press # until you find your place. Each   pressing of # moves you to the next slot in whatever code you are in.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   Example 1:   ENTER CODE “40”   DISPLAY WILL SHOW   4 4 0 0 0 0.   . 0 0 1 ENTER STAGE “1”   ENTER A BLANK “0”   ENTER BOILER NO. 1   4 4 0 0 . 0 0 1 1 1.   PRESS   = SAVE KEY, TO HAVE BOILER #1 OPERATE AS THE FIRST STAGE.   # To set firing of the second boiler, enter 2 for the stage, then a 0, then a 2 for the second boiler.   The display should read 40 2.02. Now press # to save that slot to memory. Again, the display   will automatically bump you to the next slot with the display showing 40 0000, indicating you   are in slot 3. The control panel will automatically go into the next slot.   Once the eighth boiler has been entered, all of the slots available in Code 40 have been used.   Because there are still 4 more boilers remaining, simply press Code 41 and continue entering   the last 4 stages.   Example 2:   4 4 1 1 9.   0.   0 1 9 0 1 4 4 1 1 1 1 1.   2.   1 1 1 2 PRESS   = SAVE KEY, TO HAVE BOILERS 9 THROUGH 12 ENTERED.   # Changing The Lead Boiler Firing Sequence:   After a boiler has been in the number 1 position for a year, it will have accumulated more firing   time because it is always first to fire and last to go off, so it is recommended that the lead   boiler be changed. Generally, the position of the lead boiler is moved to the next boiler down   the line. So, in Code 40, simply change boiler 2 to be in stage 1, boiler 3 to be stage 2, boiler   4, stage 3, etc., until finally, in Code 41, boiler 1 will be in stage 12.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 61: KEYBOARD LOCK - UNLOCK   PRESS   PRESS   + + = ENTRY CODE   6 6 1 6 + + = LOCK OR UNLOCK   8 u l 2 DISPLAY SHOWS   OR   n l o c PRESS   = SAVE KEY   # Code 61 prevents tampering with the entries by locking the panel. When code 61 is entered,   the display will show either “loc” or “unl”. If loc is displayed, the keypad can only be used to   view the settings. If the display shows unl, the settings can be changed. It is recommended   that the keypad be locked after each entry session.   ENTRY CODE 62: SYSTEM MODE   PRESS   + = ENTRY CODE   6 2 DISPLAY SHOWS   OR   = OFF   = ON   0 1 PRESS   = SAVE KEY   # The system mode turns the boiler system off and on, and is commonly used to shut it down at   the end of the heating season and turn it on again in the Fall. When turning the system on, the   panel takes over control of the boilers, and in some cases the primary system pump. To use   this code, enter 62, and the display will show either 0 or 1, for off or on, respectively. Enter   your choice and press # to save.   ENTRY CODE 63: MANUAL OVERRIDE OF BOILER STAGES   PRESS   + = ENTRY CODE   6 3 DISPLAY SHOWS   0 2 ENTER YOUR CHOICE   1 # PRESS   = SAVE KEY, TO SET CONTROL STAGE 12.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   The code allows for manual control of up to 24 stages. During normal operation, the panel   controls all the boilers. Code 63 will override that to control any boiler you choose. To use this   code, you must first enter 0 in code 62, then enter code 63, and then enter the boiler/stage you   want to run. Remember to always press # after each entry.   This code turns off when a zero is entered and turns on when the number of boilers you want   is entered. Thus, to give control of the boilers back to the panel, enter 0 to turn code 63 off,   and enter a 1 to turn code 62 on. Code 63 is commonly used during maintenance or testing.   ENTRY CODE 65: MANUAL OVERRIDE OF THE SYSTEM PRIMARY PUMP   PRESS   + = ENTRY CODE   6 5 DISPLAY SHOWS   = OFF   0 1 2 OR   OR   = MANUAL ON   = AUTOMATIC   PRESS   = SAVE KEY   # This code allows the system primary pump to be turned on, off, or put on automatic. The   system primary pump circulates water from the boilers through the building. To use this code,   enter 65, and then enter 0 or 1 to turn it off or on, respectively, which takes control of the purnp   away from the panel. Enter 2 to have the panel control the system pump. Please note that the   pump must have an auto-reset feature to work with setting number 2.   ENTRY CODE 66: SETBACK - ON / OFF   PRESS   + = ENTRY CODE   6 6 DISPLAY SHOWS   OR   = OFF   = ON   0 1 PRESS   = SAVE KEY   # This code turns the system setback feature off and on. Once this is turned on, then refer to   codes 30 through 37 to actually set when and how much you want the temperature to   decrease.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 67: 24 HOUR CLOCK - HOUR AND MINUTE   PRESS = ENTRY CODE   DISPLAY SHOWS   + 6 7 = 6:30 PM   1 8 3 0 This code allows you to set or observe the 24 hour military time clock. To set the clock, enter   67, then the hour, then the minute, then press #.   ENTRY CODE 68: DAY OF THE WEEK AND DATE OF THE MONTH   PRESS   PRESS   + = ENTRY CODE   6 8 = SEVENTH DAY OF THE WEEK   = TWENTY-NINTH DAY OF THE MONTH   = SAVE KEY   7 PRESS   PRESS   29   # This code allows you to set, or observe, the day of the week and month. To set the proper day   of the week, enter a single digit of 1 through 7 to represent Monday through Sunday, then   enter two digits to represent the calendar day of the month and then press # to save.   ENTRY CODE 69: MONTH AND YEAR   PRESS   PRESS   + = ENTRY CODE   6 9 = JUNE   06   PRESS   PRESS   = YEAR 2001   = SAVE KEY   01   # This code allows you to set, or observe, the month and year.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   ENTRY CODE 81: SETBACK OVERRIDE   PRESS   + = ENTRY CODE   6 6 ENTER CHOICE   = MINUTES OF SETBACK   0 RANGE IS FROM 1 TO 240 MINUTES   PRESS = SAVE KEY   # This provides flexibility to the setback schedule. For example, a school might set back every   night of the week, but occasionally have a special activity in the evenings. To warm the   building, you could re-enter the code for that night and change the settings. However, it is   much easier to enter Code 81, the number of minutes of override, and then press #.   Section 8   Entry Code Details   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 9: FINE TUNING THE HEATING SYSTEM   The key to fine tuning any boiler system is to understand the building use. A hospital, an office   building, a school, and an apartment all have very different hosting needs.   The following codes are used to fine tune a system’s heating output:   Codes 30 to 37 - Setback Temperature.   Code 21 - Outside Air Temperature Shut Down.   Code 22 - Minimum Return Water Line Temperature.   Code 23 - Outdoor Reset Ratio Setting.   Code 24 - Rate of Change Factor.   The goal of fine tuning a system is to find a balance between the comfort of the occupants and   the cost of operation. Boiler staging is a function of building needs, not outside temperature or   Return Water Line temperature. The following provides a step-by-step way to improve the   settings.   Codes 30 to 37:   First, determine the times each day that the heat can be set back using Codes 30 – 37. Some   buildings, such as hospitals, are always occupied, and thus do not allow for much, if any,   setback. However, in a normal office building temperatures can be reduced by 20°F overnight   and on weekends (the maximum recornrnended by TRIAD). Setback can be as much as 20°F   because the control panel begins determining the most fuel efficient way to reheat the building   two hours prior to the end of the setback period instead of just firing all the boilers   simultaneously. While watching both the outside temperature and the system Return Line   Temperature, the panel will fire the boiler(s) only enough to bring the heat back normal. So the   energy savings realized during setback are not wasted by firing all the boilers at the last   minute.   Remember that the panel is capable of 4 setbacks every 24 hours, so setback can also be   scheduled, for example, in the afternoon when the sun and body heat from the occupants, can   naturally contribute to warming the building.   Code 21:   The setback function in codes 30-37 are now operating and the building cools off when vacant   and warms back up when occupied. The next step is to use Code 21 to slowly reduce the   outside air shutoff temperature degree by degree. If the current setting is 60°F, once a week   reduce the setting by 1°F. The goal is to reduce the heat to the lowest temperature the   occupants will comfortably allow. If it becomes too cold increase the set point by 1°F.   Code 22:   Next, begin reducing the minimum system Return Line Temperature by 1°F each week using   Code 22. If the starting temperature is 100°F, reduce it to 99°F for a week, and every week   thereafter, until the building is comfortable. If it becomes too cold, then increase the set point   by 1°F.   Section 9   Fine Tuning The Heating System   Series 8900SH Control Panel   Operation And Installation Manual   Code 23:   The next step is to use Code 23 to ensure the panel has automatic control of the Reset Ratio.   Enter code 23 and input 0 to have it automatically calculated.   Code 24:   The next step is to use Code 24 to set the Rate of Change Factor. As explained in Section 8,   the rate of change factor controls the speed at which the timer counts from 00 to 99. When 99   is reached, the panel either fires a boiler or shuts a boiler off. The Rate of Change Factor is   important to the system’s efficiency because if the count is too fast the boilers will short cycle,   and if the count is too slow there is a lag between the need for heat and the firing of the   boilers. TRIAD recommends an initial setting of .10.   By viewing Code 18 you can get a feel for how long the boilers have been running in each   cycle. For maximum efficiency, the boilers should fire for a minimum of 30 minutes. If they   aren’t, reduce Code 24 by .01, for a setting of .09. Check daily and continue to reduce your   entry by .01 until a run time of 30 minutes is achieved.   Once you feel the building is being heated as efficiently as possible, record the settings and   keep in a safe place.   TRIAD has a system available that can remotely monitor the control panel that is designed to   be used with an IBM-compatible PC and consists of a modem, an interface, and software.   This allows the control panel settings to be monitored or changed from a remote station. It is   possible to operate several buildings from one central location. More information is available   from TRIAD.   Section 9   Fine Tuning The Heating System   Series 8900SH Control Panel   Operation And Installation Manual   SECTION 10: TROUBLESHOOTING   THE BUILDING EXPERIENCES A POWER OUTAGE   In the case of a power outage, the control panel has two built-in rechargable batteries that will   power the memory for 30 days, allowing the panel to continue where it left off when power is   restored. However, the boilers will not run without electricity, and the building has lost the   hosting system until power is restored. Please note that the batteries require 48 hours to trickle   charge the first time the panel is turned on.   THE RED DISPLAY LED’S ARE OUT   First check the breaker that feeds the control panel.   Next, make sure the switch in the panel is "on”, and there is a good fuse in the fusestat. If   there is a spare fuse in the panel enclosure, replace the fuse.   Pull the cover off the panel circuit board, and with a volt meter, check that there is between 9.8   and 10.5 VAC to the two “WALL XFMR” terminals (transformer terminals) on the control relay   output terminal strip. If there is insufficient voltage, the power from the transformer to the circuit   board has been lost. If you do have proper voltage, the control panel may be bad. Turn the   panel off so the boilers will automatically revert to self control via their high limit controls and   continue to supply the building with heat. Contact your TRIAD Service contractor or your   TRIAD representative.   THE CONTROL PANEL IS RUNNING, AND THE BOILERS ARE RUNNING, BUT THE   BUILDING IS TOO COLD   Use Code 23 to reset the Ratio Control slightly upwards.   THE CONTROL PANEL IS RUNNING, AND THE BOILERS ARE RUNNING, BUT THE   BUILDING IS TOO HOT   Use Code 23 to reset the Ratio Control slightly downwards.   THE BUILDING IS TOO COLD AND YOU CANNOT IDENTIFY THE PROBLEM   Turn off the control panel by flipping the power switch off, allowing control of the system to be   returned to the boilers. Then, set the boilers high limit controls at 160°F and increase or   decrease as necessary. Call your TRIAD representative.   THE BOILERS ARE NOT OPERATING   First decide if the problem is with the boilers or the control panel by flipping the power switch   off. The boilers should fire and maintain temperature through their own high limit controls. If   not, the problem is with the boiler equipment. First check the power supply to the boilers at the   breaker box. Next check the boiler fuel supply. If the problem is still not resolved, contact your   TRIAD representative.   Section 10   Troubleshooting   Series 8900SH Control Panel   Operation And Installation Manual   THE CONTROL PANEL IS DAMAGED   Turn off the control panel and contact your TRIAD service contractor or TRIAD representative.   THE BURNER WILL NOT COME ON DURING TESTING OF THE SYSTEM (CODE 63) _   Be sure that the control panel is calling for the boilers by:   1. Making sure that 0 has been entered in code 62   2. Making sure that 1 has been entered in code 63   3. Making sure the high limit set points on the boilers have not been exceeded   THE CONTROL PANEL WILL NOT ACCEPT ENTRIES   Make sure the Keypad is unlocked in code 61   Section 10   Troubleshooting   |