PB Heat Gas Boiler User Manual

®
®
Peerless Pinnacle  
Stainless Steel Gas Boilers  
WARNING  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
– Do not store or use gasoline or other  
flammable vapors and liquids in the vicinity  
of this or any other appliance.  
– WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electrical switch;  
do not use any phone in your building.  
Immediately call your gas supplier from  
a neighbor’s phone. Follow the gas  
supplier’s instructions.  
If you cannot reach your gas supplier,  
call the fire department.  
– Installation and service must be performed  
by a qualified installer, service agency or  
the gas supplier.  
As an ENERGY STAR® Partner, PB Heat, LLC has  
determined that this product meets the ENERGY STAR®  
guidelines for energy efficiency.  
Installation,  
Operation &  
Maintenance  
Manual  
USING THIS MANUAL  
USING THIS MANUAL  
A. INSTALLATION SEQUENCE  
DANGER  
Indicates a condition or hazard which will cause  
severe personal injury, death or major property  
damage.  
Follow the installation instructions provided in this  
manual in the order shown. The order of these  
instructions has been set in order to provide the installer  
with a logical sequence of steps that will minimize  
potential interferences and maximize safety during  
boiler installation.  
WARNING  
B. SPECIAL ATTENTION BOXES  
Indicates a condition or hazard which may cause  
severe personal injury, death or major property  
damage.  
Throughout this manual you will see special attention  
boxes intended to supplement the instructions and make  
special notice of potential hazards. These categories  
mean, in the judgment of PB Heat, LLC:  
CAUTION  
Indicates a condition or hazard which will or can  
cause minor personal injury or property damage.  
NOTICE  
Indicates special attention is needed, but not directly  
related to potential personal injury or property  
damage.  
1
PREINSTALLATION  
1. PREINSTALLATION  
A. GENERAL  
C. ACCESSIBILITY CLEARANCES  
1. Pinnacle boilers are supplied completely assembled  
as packaged boilers. The package should be  
inspected for damage upon receipt and any damage  
to the unit should be reported to the shipping  
company and wholesaler. This boiler should be  
stored in a clean, dry area.  
1. The Pinnacle boiler is certified for closet installations  
with zero clearance to combustible construction. In  
addition, it is design certified for use on combustible  
floors.  
2. Refer to Figure 1.1 and Figure 1.2 for the  
recommended clearance to allow for reasonable  
access to the boiler. Local codes or special  
conditions may require greater clearances.  
2. Carefully read these instructions and be sure to  
understand the function of all connections prior to  
beginning installation. Contact your PB Heat, LLC  
Representative for help in answering questions.  
D. COMBUSTION AND VENTILATION AIR  
3. This boiler must be installed by a qualified  
contractor. The boiler warranty may be voided if the  
boiler is not installed correctly.  
1. The Pinnacle boiler is designed only for operation  
with combustion air piped from outside (sealed  
combustion). PVC pipe must be supplied between  
the air inlet connection at the rear of the boiler  
through an outside wall.  
4. A hot water boiler installed above radiation or as  
required by the Authority having jurisdiction, must be  
provided with a low water fuel cut-off device either as  
part of the boiler or at the time of installation.  
2. No additional combustion or ventilation air is  
required for this appliance.  
5. This boiler can be installed at high altitudes above  
5,000 feet elevation with no burner adjustments. For  
boilers equipped for firing liquefied petroleum (LP)  
gas at elevations above 7,000 feet contact the factory.  
DANGER  
Do not install this boiler on carpeting.  
B. CODES & REGULATIONS  
1. Installation and repairs are to be performed in strict  
accordance with the requirements of state and local  
regulating agencies and codes dealing with boiler  
and gas appliance installation.  
3. Refer to Section 5 of this manual, Venting, for  
specific instructions for piping combustion air.  
E. PLANNING THE LAYOUT  
2. In the absence of local requirements the following  
should be followed.  
1. Prepare sketches and notes showing the layout of the  
boiler installation to minimize the possibility of  
interferences with new or existing equipment, piping,  
venting and wiring.  
a. ASME Boiler and Pressure Vessel Code, Section  
IV - "Heating Boilers"  
b. ASME Boiler and Pressure Vessel Code, Section  
VI - Recommended Rules for the Care and  
Operation of Heating Boilers"  
2. The following sections of this manual should be  
reviewed for consideration of limitations with  
respect to:  
a. Water Piping: Section 3  
b. Fuel Piping: Section 4  
c. Venting: Section 5  
d. Air Intake Piping: Section 5  
e. Condensate Removal: Section 5  
f. Electrical Wiring: Section 6  
WARNING  
Liquefied Petroleum (LP) Gas or Propane is heavier  
than air and, in the event of a leak, may collect in low  
areas such as basements or floor drains. The gas  
may then ignite resulting in a fire or explosion.  
c. ANSI Z223.1/NFPA 54 - "National Fuel Gas Code"  
d. ANSI/NFPA 70 - "National Electrical Code"  
e. ANSI/NFPA 211 - "Chimneys, Fireplaces, Vents  
and Solid Fuel Burning Appliances"  
3. Where required by the authority having jurisdiction,  
the installation must conform to the Standard for  
Controls and Safety Devices for Automatically Fired  
Boilers, ANSI/ASME CSD-1.  
2
PREINSTALLATION  
WARNING  
WARNING  
This boiler is certified as an indoor appliance. Do not  
install this boiler outdoors or locate where it will be  
exposed to freezing temperatures.  
Do not install this boiler where gasoline or other  
flammable liquids or vapors are stored or are in use.  
Figure 1.1: Accessibility Clearances – Floor Standing Units  
Figure 1.2: Accessibility Clearances – Wall Hung Units  
3
BOILER SET-UP  
2. BOILER SET-UP  
3. Use a minimum of 1/4" threaded fasteners for  
supporting the boiler. Do not mount the boiler to  
wall board only.  
A. GENERAL  
1. Pinnacle boilers are to be installed in an area with a  
floor drain or in a suitable drain pan. Do not install  
any boiler where leaks or relief valve discharge will  
cause property damage.  
WARNING  
Make sure the boiler is adequately supported. Do not  
install this boiler on drywall unless adequately  
supported by wall studs.  
2. This boiler is not intended to support external piping.  
All venting and other piping should be supported  
independently of the boiler.  
4. Be sure to adequately support the boiler while  
installing external piping. Be sure to pipe condensate  
to a suitable drain or condensate pump.  
3. Install this boiler level to prevent condensate from  
backing up inside the boiler.  
CAUTION  
C. FLOOR MOUNTED BOILERS  
This boiler is must be installed level to prevent  
condensate from backing up inside the boiler.  
1. PI-80, PI-140, and PI-199 boilers are designed for  
floor mounting. The PI-80 can be wall mounted  
using the optional boiler stand available through  
your PB Heat, LLC distributor (Part Number 91439).  
B. WALL HUNG BOILERS  
2. The boiler stand may used for floor mounting of the  
PI-140 and PI-199 boilers.  
1. The PI-T50 and PI-T80 Boilers are provided with  
slots for wall mounting and feet for floor mounting.  
Refer to Figure 10.1 in this manual for dimensions &  
locations.  
2. If wall mounted, the boiler must be attached to a  
wall that provides adequate support for the boiler.  
4
WATER PIPING AND CONTROLS  
3. WATER PIPING AND CONTROLS  
4. Expansion Tank: An expansion tank (such as a Bell &  
Gossett Series HFT) is required to provide room for  
expansion of the heating medium (water or glycol  
solution). Consult the expansion tank manufacturer's  
instructions for specific information regarding  
A. GENERAL  
1. The water supply and return piping of this appliance  
are to be sized according to system requirements. Do  
not use piping smaller than the boiler connections.  
installation. The expansion tank is to be sized for the  
required system volume and capacity. In addition, be  
sure that the expansion tank is sized based on the  
proper heating medium. Glycol solutions may expand  
more than water for a similar temperature rise.  
2. In hydronic systems where sediment may exist,  
install a strainer device in the boiler return piping to  
prevent large particles and pipe scale from entering  
the boiler heat exchanger coil. Use a large mesh  
screen in the strainer.  
CAUTION  
3. Install this boiler so that the gas ignition system  
components are protected from water (dripping,  
spraying, etc.) during appliance operation and  
service (circulator replacement, condensate trap  
cleaning, control replacement, etc.).  
Use only inhibited propylene glycol solutions which  
are specifically formulated for hydronic systems.  
Unlike automotive antifreeze, solutions for hydronic  
applications contain corrosion inhibitors that will  
protect system components from premature failure  
due to corrosion.  
B. OPERATING PARAMETERS  
1. The Pinnacle boiler is designed to operate in a closed  
loop hydronic system at approximately 15 psi. A  
pressure limit in the boiler header will prevent the  
unit from operating if the pressure drops below 10  
psi. This is to keep the appliance from operating in  
the event of a system leak or other condition in which  
water is not flowing through the heat exchanger.  
WARNING  
Use only inhibited propylene glycol solutions which  
are specifically formulated for hydronic systems.  
Ethylene glycol is toxic and may cause an  
environmental hazard if a leak or spill occurs.  
2. Table 3.1 shows minimum water flow rates for  
Pinnacle boilers. If a glycol solution is to be used,  
contact the factory for minimum flow rates.  
5. Y-Type Strainer: In older systems where a significant  
amount of sediment may be present, it may be  
necessary to install a Y-type strainer. The strainer  
should be checked often and cleaned during the first  
few months of operation to assure that sediment  
does not reach the heat exchanger and clog the  
passages. Use a large mesh screen in the strainer.  
Table 3.1 – Minimum Flow Rate and Water Volume  
Boiler  
Model  
Total Water  
Minimum Flow  
Volume-Gallon (Liter) Rate-GPM (LPM)  
PI-T50  
PI-T80  
PI-80  
0.50 (1.89)  
0.63 (2.40)  
0.63 (2.40)  
0.93 (3.50)  
1.13 (4.26)  
2 (7.6)  
4 (15.2)  
4 (15.2)  
6 (22.7)  
8 (30.3)  
6. Flow Control Valve: Flow control valves such as the  
TACO Flo-Chek or Bell & Gossett Flo-Control™ are  
used to prevent gravity circulation by incorporating a  
check valve with a weighted disc.  
PI-140  
PI-199  
7. Pressure Reducing Valve: A pressure reducing valve,  
such as the Bell & Gossett B-38 or a TACO #329, is  
used in a hydronic system to automatically feed  
water to the system whenever pressure in the system  
drops below the pressure setting of the valve. These  
valves should not be used on glycol systems unless  
close supervision of the glycol solution is practiced.  
C. SYSTEM COMPONENTS  
1. Figure 3.1 shows the symbol key for piping diagrams  
in this section. The following are brief descriptions of  
system components.  
2. Pressure/Temperature Gauge: A combination  
pressure/temperature gauge is provided with each  
Pinnacle boiler to be mounted in the piping from the  
boiler supply to the system. Most local codes require  
this gauge.  
8. Back Flow Preventer: A back flow preventer (check  
valve) is required by some jurisdictions to prevent  
the hydronic system water from backing up into the  
city water supply. This is especially important on  
systems in which glycol solution is used as the  
heating medium.  
3. Air Elimination: Any closed loop hydronic system in  
which the Pinnacle boiler is installed must have an  
air elimination device. As the system water is heated,  
dissolved oxygen and carbon dioxide will separate  
from the liquid. An air elimination device (such as a  
TACO 430 Series Air Scoop with automatic air vent)  
is required to remove the dissolved gasses from the  
system preventing corrosion in the piping system and  
eliminating system noise.  
5
WATER PIPING AND CONTROLS  
Figure 3.1: Piping Symbol Key  
9. Pressure Relief Valve: The boiler pressure relief valve  
is factory installed into the right side boiler manifold  
(inside the jacket). Pipe the discharge of the relief  
valve to within 12" of the floor and close to a floor  
drain. Provide piping that is the same size or larger  
than the relief valve outlet.  
b. The circulator should be sized based on the net  
output of the boiler. The Table 3.2 shows the  
Boiler Output as reported to the Hydronics  
Institute division of GAMA. These values are  
based on a pickup factor of 1.15.  
Table 3.2 – Boiler Inputs and Outputs  
CAUTION  
Boiler  
Model  
Boiler Input  
(Btu/hr [kW])  
Net I=B=R Output  
(Btu/hr [kW])  
Pipe the discharge of the relief valve as close as  
possible to the floor and away from high traffic areas.  
Pipe the discharge to a floor drain. Failure to do so  
may result in personal injury and/or property damage.  
PI-T50  
PI-T80  
PI-80  
50,000 (14.7)  
80,000 (23.4)  
80,000 (23.4)  
140,000 (41.0)  
199,000 (58.3)  
40,000 (11.7)  
64,000 (18.8)  
64,000 (18.8)  
112,000 (32.8)  
159,000 (46.6)  
PI-140  
PI-199  
10. Circulator: The boiler circulator is to be sized to  
overcome the pressure drop of the system while  
providing the flow required by the boiler.  
a. If the boiler is piped in a secondary loop of a  
primary/secondary heating system, the circulator  
will need only to overcome the resistance of the  
boiler and any fittings in that loop.  
6
WATER PIPING AND CONTROLS  
c. The required flow rate can be calculated based  
on the design temperature difference from the  
return to the supply of the boiler. For a PI-T80  
with a design temperature difference of 20°F the  
calculation is as follows:  
g. Special consideration must be given if anti-freeze is  
to be used as a heating medium. Propylene glycol  
has a higher viscosity than water therefore the  
system pressure drop will be higher.  
Output  
64,000  
10. Indirect Water Heater: An indirect water heater  
should be piped in a dedicated zone. It consists of a  
water tank that is heated by boiler water passing  
through an internal coil. Examples of indirect water  
heating are shown in the System Piping subsection  
of this Section.  
Required Flow =  
=
= 6.4 GPM  
T x 500  
20 x 500  
d. Table 3.3 shows the pressure drop (in feet of  
water) for a flow rate which gives a 20°F  
temperature difference for each boiler model.  
Table 3.3 – Flow Rate and Pressure Drop  
Boiler  
Model  
Flow Rate  
(GPM [LPM])  
Pressure Drop  
(Feet [meters])  
PI-T50  
PI-T80  
PI-80  
4.0 (15.1)  
6.4 (24.2)  
6.4 (24.2)  
11.2 (42.4)  
15.9 (60.2)  
4.5 (1.22)  
5.0 (1.52)  
5.0 (1.52)  
8.0 (2.44)  
13.0 (4.02)  
PI-140  
PI-199  
e. The boiler pressure drop for various flow rates  
can be determined by using Figure 3.2, the  
Pinnacle Circulator Sizing Graph.  
f. Table 3.4 gives the recommended circulators for  
a boiler on a secondary loop with water as the  
heating medium.  
Table 3.4 – Recommended Circulators  
Boiler  
Model  
TACO  
Circulator  
Grundfos Circulator  
PI-T50  
PI-T80  
PI-80  
006  
007  
UPS 15-58FC SPD-1  
UPS 15-58FC SPD-2  
UPS 15-58FC SPD-2  
UPS 15-58FC SPD-3  
UP 26-64F  
007  
PI-140  
PI-199  
0010  
0011  
NOTICE  
The circulator sizing given is for primary/secondary  
installations only. The system circulators must be  
sized based on the flow and pressure drop  
requirements of the system.  
7
WATER PIPING AND CONTROLS  
Figure 3.2: Pinnacle Circulator Sizing Graph  
21  
20  
19  
18  
17  
16  
15  
14  
13  
12  
11  
10  
9
PI-T50  
8
7
PI-T80/80  
PI-140  
6
5
4
3
PI-199  
2
1
0
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Flow Rate (GPM)  
D. SYSTEM PIPING  
E. FREEZE PROTECTION  
1. Figure 3.3 shows a single boiler with two zones. In  
this application, the Peerless Partner indirect water  
heater and the single heating zone require similar  
water temperature.  
1. Glycol for hydronic applications is specially  
formulated for this purpose. It includes inhibitors  
which prevent the glycol from attacking metallic  
system components. Make certain that the system  
fluid is checked for the correct glycol concentration  
and inhibitor level.  
2. Figure 3.4 shows an additional zone in which  
baseboard radiation is the heat load. This zone also  
requires water temperatures similar to the indirect  
water heater.  
2. Use only inhibited propylene glycol solutions of up  
to 50% by volume. Ethylene glycol is toxic and can  
chemically attack gaskets and seals used in hydronic  
systems.  
3. Figure 3.5 shows diverter tees used in combination  
with conventional hydronic radiators on an  
additional zone. A second boiler is also added to the  
system. Notice that the boilers are piped in parallel  
on the secondary loop. It is important that the  
common headers are sized to match the system  
piping. Smaller headers may result in flow  
fluctuations through the boilers.  
3. The antifreeze solution should be tested at least once  
per year and as recommended by the antifreeze  
manufacturer.  
4. Figure 3.6 shows a system in which several different  
types of loads and multiple boilers are shown. This  
system illustrates how different temperature zones  
can be supplied from the same source by mixing  
down the temperature using a three way mixing  
valve. Radiant flooring typically requires much lower  
temperatures than baseboard radiation and indirect  
water heating. Notice that a third boiler is included in  
this system.  
5. Figure 3.7 shows zone valves used in place of zone  
circulators. Notice that this system utilizes reverse  
return piping which makes it easier to balance the  
system. If the heating zones are very different in  
length, the balancing valves on the return side of  
each loop are required.  
8
WATER PIPING AND CONTROLS  
9
WATER PIPING AND CONTROLS  
10  
WATER PIPING AND CONTROLS  
11  
WATER PIPING AND CONTROLS  
12  
WATER PIPING AND CONTROLS  
13  
WATER PIPING AND CONTROLS  
Antifreeze solutions expand more than water. For example, a  
50% by volume solution expands 4.8% for a 148°F  
temperature rise while water expands about 3% for the same  
temperature increase. Allowance for this expansion must be  
considered in sizing expansion tanks and related components.  
9. Do not use galvanized pipe in glycol systems.  
10. Use water that is low in mineral content and make  
sure there are no petroleum products in the solution.  
11. Mix solution at room temperature.  
12. Do not use a chromate treatment.  
4. The flow rate in systems utilizing glycol solution  
should be increased compared with a water system  
to compensate for increased heating capacity.  
13. Do not use glycol solution in a system that may  
reach temperatures above 250°F.  
5. Due to increased flow rate and fluid viscosity the  
circulator head requirement will increase. Contact the  
pump manufacturer to correctly size the circulator for  
a particular application based on the glycol  
14. Refer to Technical Topics, #2a published by the  
Hydronics Institute Division of GAMA for further  
glycol system considerations.  
concentration and heating requirements.  
F. SPECIAL APPLICATIONS  
6. A strainer, sediment trap, or some other means for  
cleaning the piping system must be provided. It  
should be located in the return line upstream of the  
boiler and must be cleaned frequently during the  
initial operation of the system. Glycol solution is  
likely to remove mill scale from new pipe in new  
installations.  
1. If the boiler is used in conjunction with a chilled  
medium system, pipe the chiller in a separate  
secondary loop.  
a. Assure that the boiler circulator is disabled during  
chiller operation so chilled water does not enter  
the boiler.  
7. Glycol solution is expensive and leaks should be  
avoided. Weld or solder joints should be used where  
possible and threaded joints should be avoided.  
Make up water should not be added to the system  
automatically when a glycol solution is used. Adding  
make-up water may significantly dilute the system.  
b. Install a flow control valve (spring check valve) to  
prevent gravity flow through the boiler.  
c. See figure 3.8 for recommended system piping.  
2. For boilers connected to heating coils in a forced air  
system where they may be exposed to chilled air  
circulation, install flow control valves or other  
automatic means to prevent gravity circulation of the  
boiler water during cooling cycles. See figure 3.9 for  
illustration.  
8. Check local regulations to see if systems containing  
glycol solutions must include a back-flow preventer  
or require that the glycol system be isolated from the  
water supply.  
14  
WATER PIPING AND CONTROLS  
Figure 3.8: Boiler in conjunction with a Chilled Water System  
Figure 3.9: Boiler Connected to a Heating Coil in a Forced Air System  
15  
GAS PIPING  
4. GAS PIPING  
Table 4.2: Maximum Capacity of Pipe (CFH) for a  
Pressure Drop of 0.3" of Water  
A . GENERAL  
1. All fuel piping to the boiler is to be in accordance  
with local codes. In the absence of local regulations  
refer to the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54.  
Pipe  
Length  
(Feet)  
1-1/4"  
NPT  
1-1/2"  
NPT  
3/4" NPT  
Pipe  
1" NPT  
Pipe  
Pipe  
Pipe  
10  
20  
30  
40  
50  
60  
278  
190  
152  
130  
115  
105  
520  
350  
285  
245  
215  
195  
1,050  
730  
590  
500  
440  
400  
1,600  
1,100  
890  
2. Size and install piping to provide a supply of gas  
sufficient to meet the maximum demand of all  
appliances supplied by the piping.  
760  
B. FUEL LINE SIZING  
670  
1. The rate of gas to be provided to the boiler can be  
determined by the following:  
610  
The values are based on a specific gravity of 0.60 (typical  
for natural gas). See Table 4.3 for capacity correction  
factors for gases with other specific gravities.  
Btu  
( )  
/
Boiler Input Rate  
Gas Heating Value  
hr  
³
ft  
Input Rate  
=
( )  
/
hr  
Btu  
( )  
/ft³  
Obtain the gas heating value from the gas supplier.  
Table 4.3: Maximum Capacity Correction Factors  
for Specific Gravity other than 0.60  
2. As an alternative use Table 4.1 which uses typical  
heating values for natural gas and liquefied  
petroleum (LP) gas.  
Specific  
0.50 0.55 0.60 0.65 0.70 0.75  
Gravity  
Correction  
Factor  
1.10  
1.04  
1.00  
0.96  
0.93  
0.90  
Table 4.1: Gas Input Rates  
Specific  
Gravity  
³
0.80 0.85 0.90 1.00 1.10 1.20  
Gas Input Rate* (ft /hr)  
Natural Gas  
Boiler  
LP Gas  
20  
Model  
PI-T50  
PI-T80  
PI-80  
Correction  
Factor  
0.87  
0.84  
0.82  
0.78  
0.74  
0.71  
50  
80  
32  
Specific  
Gravity  
1.30 1.40 1.50 1.60 1.70 1.80  
80  
32  
Correction  
Factor  
PI-140  
PI-199  
140  
199  
56  
0.68  
0.66  
0.63  
0.61  
0.59  
0.58  
79  
³
*Natural gas input rates are based on 1000 Btu/ft , LP  
4. The gas piping to the boiler must be a minimum of  
3/4" pipe. The boiler is supplied with a 3/4" NPT x  
1/2" NPT bell reducer. Do not remove the reducer.  
³
input rates are based on 2500 Btu/ft .  
5. Size and install the gas supply piping for no more  
than 0.5 inches of water pressure drop between the  
gas regulator and the boiler.  
3. Table 4.2 shows the maximum flow capacity of  
several pipe sizes based on 0.3" of pressure drop.  
a. The values shown are based on a gas specific  
gravity of 0.60 (Typical for natural gas).  
C. GAS SUPPLY PIPING INSTALLATION  
b. Multiply the capacities listed by the factors  
indicated in Table 5.3 for gas with a specific  
gravity other than 0.60 to obtain the corrected  
capacity.  
1. Do not install any piping directly over or in front of  
the boiler. Locate the drop pipe adjacent to the  
boiler.  
16  
GAS PIPING  
2. Install a sediment trap as shown in Figure 4.1. Be  
sure to allow clearance from the floor for removal of  
the pipe cap.  
5. Maintain a minimum distance of 10 feet between the  
gas pressure regulator and the boiler.  
6. Check all gas piping for leaks prior to placing the  
boiler in operation. Use an approved gas detector,  
non-corrosive leak detection fluid, or other leak  
detection method. If leaks are found, turn off all gas  
flow and repair as necessary.  
WARNING  
Use a pipe joint sealing compound that is resistant to  
liquefied petroleum gas. A non-resistant compound  
may lose sealing ability in the presence of this gas,  
resulting in a gas leak. Gas leaks may potentially  
cause an explosion or fire.  
WARNING  
When checking for leaks, do not use matches,  
candles, open flames or other methods that provide  
an ignition source. This may ignite a gas leak  
resulting in a fire or explosion.  
3. Install a ground joint union between the sediment  
trap and the boiler to allow service of the appliance.  
4. Install a service valve as shown in Figure 4.1 to allow  
the gas supply to be interrupted for service.  
7. Figure 4.2 and 4.3 are illustrations of the gas shutoff  
valve for the Pinnacle Boiler. This valve is to be used  
in addition to the gas service valve shown  
in Figure 4.1.  
D. GAS SUPPLY PIPING - OPERATION  
1. The gas line must be properly purged of air to allow  
boiler to operate. Failure to do so may result in  
burner ignition problems.  
2. Table 4.4 shows the maximum and minimum supply  
pressure to the boiler.  
a. Gas pressure below the minimum pressure may  
result in burner ignition problems.  
b. Gas pressure above the maximum may result in  
damage to the gas valve.  
CAUTION  
Do not subject the gas valve to more than 1/2 psi  
(13.5" W.C.) of pressure. Doing so may damage the  
gas valve.  
Figure 4.1: Gas Supply Piping – Sediment Trap  
Figure 4.2: PI-80/PI-140/PI-199  
Gas Valve Shut Off  
Figure 4.3: PI-T50/PI-T80 Gas Valve Shut Off  
17  
GAS PIPING  
Table 4.4: Maximum and Minimum Fuel Pressure  
WARNING  
Pressure (inches of water)  
Gas  
Do not adjust the throttle screw without monitoring  
Type  
Minimum  
3.7  
Maximum  
13.5  
the carbon dioxide (CO ) and carbon monoxide (CO)  
²
Natural  
LP  
in the vent pipe. Vent CO emissions above 400 ppm  
are in excess of most safety standards.  
3.7  
13.5  
3. To check the gas supply pressure on the gas valve:  
a. Turn off the power at the service switch.  
b. For both gas valve arrangements, turning the  
throttle screw clockwise will decrease the gas flow  
(decreasing CO ) and turning it counterclockwise  
²
b. Turn off the gas shutoff valve.  
will increase the gas flow (increasing CO ).  
²
c. The recommended CO settings are given in  
²
c. Using a flat screwdriver, turn the screw inside the  
inlet pressure tap fitting (see figure 4.4 and 4.5)  
one turn counterclockwise.  
Table 4.5. In no case should the boiler be  
allowed to operate with CO emissions in excess  
of 150 ppm.  
d. Attach the manometer tube to the pressure tap  
fitting.  
2. Refer to Section 5, Venting for information on  
obtaining vent samples from this boiler.  
e. Open the gas shutoff valve and start the boiler.  
Table 4.5: Recommended Vent CO Settings  
²
f. Read and record the gas pressure while the boiler  
is firing.  
Firing  
Rate  
Gas Type  
Vent CO  
Vent CO  
²
g. Turn off the boiler and gas shutoff valve  
Low  
High  
Low  
High  
8-1/2% to 9-1/2%  
8-1/2% to 9-1/2%  
9-1/2% to 10-1/2%  
9-1/2% to 10-1/2%  
< 50 ppm  
< 100 ppm  
< 50 ppm  
< 100 ppm  
Natural  
h. Remove the manometer tube from the pressure  
tap fitting and turn the screw to close the internal  
valve.  
LP  
i. Turn on the gas shutoff valve and boiler service  
switch.  
4. All gas piping must be leak tested prior to placing the  
boiler in operation.  
a. If the leak test pressure requirement is higher  
than the maximum inlet pressure noted in Table  
4.4, the boiler must be isolated from the gas  
supply piping system.  
b. If the gas valve is exposed to pressures exceeding  
13.5" of water, the gas valve must be replaced.  
5. Install the boiler such that the gas ignition system  
components are protected from water (dripping,  
spraying, rain, etc) during operation and service  
(circulator replacement, condensate trap cleanout,  
and control replacement, etc).  
Figure 4.4: Gas Valve/Venturi PI-T50/PI-T80  
E. MAIN GAS VALVE - OPERATION  
1. Figure 4.4 shows an illustration of the gas valve/venturi  
assembly for the Pinnacle PI-T50 and PI-T80 and  
Figure 4.5 shows an illustration of the gas valve/venturi  
assembly for the PI-80, PI-140, and PI-199.  
a. The throttle screw on either of these valves  
should not be adjusted without a means to  
measure carbon monoxide (CO) and carbon  
dioxide (CO ) emissions.  
²
Figure 4.5: Gas Valve/Venturi PI-80, PI-140, PI-199  
18  
VENTING, INLET AIR AND CONDENSATE  
5. VENTING, INLET AIR AND CONDENSATE  
A. GENERAL  
C. EXHAUST VENT / AIR INTAKE PIPE  
LOCATION  
1. Install the boiler venting system in accordance with  
these instructions and with the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54, CAN/CGA B149,  
and/or applicable provisions of local building codes.  
1. Determine exhaust vent location:  
a. The vent piping for this boiler is approved for  
zero clearance to combustible construction.  
2. This boiler is a direct vent appliance and is listed as a  
Category IV appliance with Underwriters  
Laboratories, Inc.  
b. See Figure 5.1 for an illustration of clearances for  
location of exit terminals of direct-vent venting  
systems.  
c. This boiler vent system shall terminate at least 3  
feet (0.9 m) above any forced air intake located  
within 10 ft (3 m). Note: this does not apply to  
the combustion air intake of a direct-vent  
appliance.  
WARNING  
This vent system will operate with a positive  
pressure in the pipe. Do not connect vent connectors  
serving appliances vented by natural draft into any  
portion of mechanical draft systems operating under  
positive pressure.  
d. Provide a minimum of 1 foot distance from any  
door, operable window, or gravity intake into any  
building.  
e. Provide a minimum of 1 foot clearance from the  
bottom of the exit terminal above the expected  
snow accumulation level. Snow removal may be  
necessary to maintain clearance.  
WARNING  
Follow these venting instructions carefully. Failure to  
do so may result in severe personal injury, death, or  
substantial property damage.  
f. Provide 4 feet horizontal clearance from electrical  
meters, gas meters, gas regulators, and relief  
equipment. In no case shall the exit terminal be  
above or below the aforementioned equipment  
unless the 4 foot horizontal distance is  
maintained.  
B. APPROVED MATERIALS FOR EXHAUST  
VENT AND INTAKE AIR PIPE  
1. Use only Non Foam Core venting material. The  
following materials are approved for use as vent pipe  
for this boiler:  
g. Do not locate the exit terminal over public  
walkways where condensate could drip and/or  
freeze and create a nuisance or hazard.  
a. Non Foam Core PVC (Polyvinyl Chloride) Pipe  
conforming to ASTM D-1784 Class 12454-B  
(formerly designated Type 1, Grade 1).  
h. When adjacent to a public walkway, locate exit  
terminal at least 7 feet above grade.  
b. Non Foam Core CPVC (Chlorinated Polyvinyl  
Chloride) Pipe conforming to ASTM D-1784  
Class 23447-B (formerly designated Type IV,  
Grade 1).  
i. Do not locate the exit termination directly under  
roof overhangs to prevent icicles from forming.  
j. Provide 3 feet clearance from the inside corner  
of adjacent walls.  
c. Non Foam Core ABS (Acrylonitrile-Butadiene-  
Styrene) Pipe conforming to ASTM D3965  
Class 3-2-2-2-2.  
2. Determine air intake pipe location.  
a. Provide 1 foot clearance from the bottom of the  
air inlet pipe and the level of maximum snow  
accumulation. Snow removal may be necessary  
to maintain clearances.  
WARNING  
Do not use Foam Core Pipe in any portion of the  
exhaust piping from this boiler. Use of Foam Core  
Pipe may result in severe personal injury, death, or  
substantial property damage.  
b. Do not locate air intake pipe in a parking area  
where machinery may damage the pipe.  
c. Maximum distance between air intake and  
exhaust vent is 6 feet (1.8 m). Minimum distance  
between exhaust vent and air intake on single  
Pinnacle is 8" (0.2 m) center-to-center. Minimum  
distance between vents and intakes on multiple  
Pinnacles is 8" (0.2 m) center-to-center. See  
Figure 5.2.  
2. Cellular foam core piping may be used on air inlet  
piping only. Never use cellular foam core material for  
exhaust piping.  
19  
VENTING, INLET AIR AND CONDENSATE  
Figure 5.1: Location of exit terminals of mechanical draft and direct-vent venting systems.  
(Reference: National Fuel Gas Code ANSI Z223.1/NFPA 54 2002).  
Table 5.1: Fitting Equivalent Length Table  
Fitting Description  
Elbow, 90°, Short Radius  
Elbow, 45°, Short Radius  
Coupling  
Equivalent Length  
5
3
0
0
3
0
Air Intake Tee  
Concentric Vent Kit  
V1000 & V500 Vent Kit  
Exhaust Vent Pipe Equivalent Length = (2x5)+10=20 feet  
Figure 5.2: Multiple Pinnacle Vent Spacing  
Further, if the intake air pipe has two 90° elbows,  
one 45° elbow and 10 feet of PVC pipe, the  
following calculation applies:  
D. EXHAUST VENT AND INTAKE AIR PIPE  
SIZING  
Air Intake Pipe Equivalent Length = (2x5)+3+10=23 feet  
1. For the PI-T50 and PI-T80 Boilers the exhaust vent  
and air intake pipes should be 2" Schedule 40 or 80.  
Finally, if a concentric vent kit is used we find:  
Total Combined Equivalent Length = 20+23+3=46 feet  
2. For the PI-80, PI-140, PI-199 the exhaust vent and  
air intake pipes should be 3" Schedule 40 or 80.  
Therefore, the total combined equivalent length  
is 46 feet which is well below the maximum of  
85 feet.  
3. The total combined equivalent length of exhaust  
vent and intake air pipe should not exceed 85 feet.  
c. The intake air pipe and the exhaust vent are  
intended to penetrate the same wall or roof of  
the building.  
a. The equivalent length of elbows, tees, and other  
fittings are listed in Table 5.1.  
b. For example: If the exhaust vent has two 90°  
elbows and 10 feet of PVC pipe we will  
calculate:  
d. Effort should be made to keep a minimum  
difference in equivalent length between the air  
intake pipe and the exhaust vent.  
20  
VENTING, INLET AIR AND CONDENSATE  
4. The minimum combined equivalent length is 16  
equivalent feet.  
4. Remove all burrs and debris from joints and fittings.  
5. All joints must be properly cleaned, primed, and  
cemented. Use only cement and primer approved for  
use with the pipe material. Cement must conform to  
ASTM D2564 for PVC or CPVC pipe and ASTM  
D2235 for ABS pipe.  
5. The maximum combined equivalent length can be  
extended by increasing the diameter of the vent  
pipe. However, the transitions should begin a  
minimum of 15 equivalent feet from the boiler.  
a. Transitions should always be made in vertical  
sections of pipe to prevent the condensate from  
pooling in the vent pipe.  
WARNING  
All joints of positive pressure vent systems must be  
sealed completely to prevent leakage of flue products  
into the living space.  
b. Use a 3" x 2" reducing coupling to transition from  
the PI-T50 and PI-T80 boiler connections to a 3"  
vent.  
6. Horizontal lengths of exhaust vent must slope back  
towards the boiler not less than ¼" per foot to allow  
condensate to drain from the vent pipe. If the vent  
pipe must be piped around an obstacle that causes a  
low point in the pipe, a drain pipe must be  
c. Use a 4" x 3" reducing coupling to transition from  
the PI-80, PI-140, and PI-199 boiler connections  
to 4" vent.  
d. The maximum equivalent length for the  
increased diameter vent pipes is 125 feet.  
connected to allow condensate to drain.  
7. All piping must be fully supported. Use pipe hangers  
at a minimum of 4 foot intervals to prevent sagging  
of the pipe where condensate may form.  
e. If the transition occurs at a distance greater than  
15 equivalent feet from the boiler, the maximum  
equivalent length will be reduced. See Table 5.2.  
Standard Vent Pipe is 2” and Oversized Vent  
Pipe is 3” for PI-T50 and PI-T80. Standard Vent  
Pipe is 3” and Oversized Vent Pipe is 4” for PI-  
80 through PI-199.  
8. Do not use the boiler to support any piping.  
9. A screened straight coupling is provided with the  
boiler for use as an outside exhaust termination.  
10. A screened inlet air tee is provided with the boiler to  
be used as an outside intake termination.  
Table 5.2: Maximum Equivalent Vent Length for  
Oversized Vent Pipe  
11. The following are optional intake air/exhaust vent  
terminations available from your PB Heat, LLC  
distributor for use with Pinnacle boilers.  
TEL of  
TEL of  
Transition  
Point  
(ft from  
boiler)  
Maximum  
TEL of all  
Vent Pipe (ft)  
Standard 2” Oversized 3”  
or 3” Vent  
Pipe (ft)  
or 4” Vent  
Pipe (ft)  
Table 5.3: Vent Termination Kits  
15  
20  
30  
40  
50  
60  
70  
80  
85  
95  
77-1/2  
60-1/2  
43  
125  
117-1/2  
110-1/2  
103  
Stock  
Description  
Code  
25  
2" PVC Concentric Vent Termination Kit  
91469  
30  
3" PVC Concentric Vent Termination Kit  
2" Stainless Steel Vent Termination Kit  
3" Stainless Steel Vent Termination Kit  
4" Stainless Steel Vent Termination Kit  
91403  
91465  
91402  
91401  
35  
26  
96  
40  
8-1/2  
0
88-1/2  
85  
None  
TEL = Total Equivalent Length  
E. EXHAUST VENT AND AIR INTAKE PIPE  
INSTALLATION  
12. Refer to Figure 5.3 to 5.10 for sidewall venting and  
Figures 5.11 to 5.14 for vertical venting.  
1. On the PI-T50 and PI-T80 the 2" exhaust vent  
connection is located on the top, right side of the  
boiler and the air intake is on the top, left side. See  
Figure 10.1. The air intake connection is intended  
for a slip fit. No sealant or adhesive is required.  
2. On the PI-80, PI-140, and PI-199 Boilers the 3”  
exhaust vent connection is located on the rear of the  
boiler and the air intake is higher and toward the left  
side when the boiler is viewed from the front. See  
Figure 10.2. The air intake connection is intended for  
a slip fit. No sealant or adhesive is required.  
3. Use only solid PVC, CPVC, or ABS schedule 40 or  
80 pipe. FOAM CORE PIPING IS NOT APPROVED.  
21  
VENTING, INLET AIR AND CONDENSATE  
Figure 5.3: PI-80, PI-140, and PI-199 Sidewall  
Venting with 3" Pipe (Exhaust  
Termination at Higher Elevation than  
Air Intake).  
Figure 5.5: PI-80, PI-140, PI-199 Sidewall Venting  
with 3" Pipe (Air Intake and Exhaust on  
the same Elevation).  
Figure 5.4: PI-T50 & PI-T80 Sidewall Venting with  
2" Pipe (Exhaust Termination at Higher  
Elevation than Air Intake).  
Figure 5.6: PI-T50 & PI-T80 Sidewall Venting with  
2" Pipe (Air Intake and Exhaust on the  
same Elevation).  
WARNING  
All exhaust vent pipes must be glued, properly  
supported, and pitched at a minimum of ¼" per foot  
back to the boiler. Failure to do so may result in severe  
personal injury, death, or substantial property damage.  
22  
VENTING, INLET AIR AND CONDENSATE  
Figure 5.7: PI-80, PI-140, PI-199 Sidewall Venting  
with 3" Pipe (3" Vent Kit).  
Figure 5.9: PI-80, PI-140, PI-199 Sidewall Venting  
with 3" Pipe (Concentric Vent Kit).  
Figure 5.8: PI-T50 & PI-T80 Sidewall Venting with  
2" Pipe (2" Vent Kit).  
Figure 5.10: PI-T50 & PI-T80 Sidewall Venting with  
2" Pipe (Concentric Vent Kit).  
WARNING  
All exhaust vent pipes must be glued, properly  
supported, and pitched at a minimum of ¼" per foot  
back to the boiler. Failure to do so may result in  
severe personal injury, death, or substantial property  
damage.  
23  
VENTING, INLET AIR AND CONDENSATE  
Figure 5.11:  
PI-80, PI-140, PI-199 Vertical  
Venting with 3" Pipe.  
Figure 5.13:  
PI-80, PI-140, PI-199 Vertical  
Venting with 3" Pipe (Concentric  
Vent Kit).  
Figure 5.12:  
PI-T50 & PI-T80 Vertical Venting  
with 2" Pipe.  
Figure 5.14:  
PI-T50 & PI-T80 Vertical Venting  
with 2" Pipe (Concentric Vent Kit).  
24  
VENTING, INLET AIR AND CONDENSATE  
F. EXHAUST TAPPING FOR VENT SAMPLE  
H. BOILER REMOVAL FROM COMMON  
VENTING SYSTEM  
To obtain a combustion sample a hole must be drilled in  
the exhaust vent pipe just above the first elbow at the  
outlet of the boiler.  
1. At the time of removal of an existing boiler from a  
common venting system, follow these steps with  
each appliance that remains connected. These steps  
are to be completed while all components which  
remain connected to the common venting system are  
not in operation.  
a. Drill a 21/64" diameter hole in the vent pipe just  
above the first elbow.  
b. Tap the hole with a 1/8" NPT Pipe Tap.  
a. Seal any unused openings in the common  
venting system.  
c. Take combustion samples through the tapped  
hole.  
b. Visually inspect the venting system for proper size  
and horizontal pitch. Verify there is no blockage  
or restriction, leakage, corrosion, and other  
deficiencies which could cause an unsafe  
condition.  
d. Thread a standard 1/8" NPT Pipe Plug into the  
hole.  
G. CONDENSATE DRAIN INSTALLATION  
1. This boiler is a high efficiency unit that produces  
condensate. The condensate must be drained from  
the unit.  
c. Where practical, close all building doors and  
windows, including interior doors between the  
space in which the appliances that remain  
connected to the common venting system are  
located and other areas of the building.  
2. The white hose under the unit is a condensate trap  
which prevents products of combustion from exiting  
the boiler through the condensate drain.  
d. Turn on any clothes dryers and any appliance  
not connected to the common venting system.  
Turn on any exhaust fans, such as range hoods  
and bathroom exhaust fans, at their maximum  
speed. (Do not operate a summer exhaust fan).  
3. The black plastic 3/4" NPT fitting at the left rear  
corner of the boiler is intended for connection to  
plastic piping. Do not block vent hole at the top of  
the fitting.  
e. Close fireplace dampers.  
4. Slope the condensate drain piping down away from  
the unit into a floor drain or condensate pump.  
Check with local codes or ordinances to  
determine if the condensate must first be  
neutralized before running it to a drain.  
f. Place the appliance being inspected in operation.  
Follow the lighting instructions and adjust the  
thermostat so that the appliance operates  
continuously.  
g. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use  
the flame of a match or candle, or smoke from a  
cigarette, cigar, or pipe.  
CAUTION  
Make sure the condensate drain piping is below the  
level of the boiler to prevent condensate from filling  
up the combustion chamber and damaging the boiler.  
h. After it has been determined that each appliance  
remaining connected to the common venting  
system properly vents when tested as outlined  
above, return doors, windows, exhaust fans,  
fireplace dampers and any other gas-burning  
appliance to their previous condition of use.  
5. Do not route the condensate piping through  
unheated spaces that may reach freezing  
temperatures.  
i. Any improper operation of the common venting  
system should be corrected so that the  
installation conforms with the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA  
B149.  
6. Use only plastic piping for the condensate drain line.  
Metal pipes will corrode and cause blockage of the  
condensate drain.  
7. To allow for proper drainage on large horizontal  
runs, a second line vent may be required and the  
required tubing size may increase to 1" I.D.  
j. The common venting system should be resized to  
approach the minimum size determined by using  
the appropriate tables located in the National  
Fuel Gas Code, ANSI Z223.1/NFPA 54, "Sizing  
of Category I Venting."  
8. A condensate removal pump is required if the boiler  
is below the drain.  
25  
ELECTRICAL  
6. ELECTRICAL  
Install all electrical wiring in accordance with the National  
Electrical Code, ANSI/NFPA 70, and local requirements.  
c) An example of this wiring using a Honeywell R845A  
relay is shown in Figure 6.2  
NOTICE  
This unit when installed must be electrically  
grounded in accordance with the requirements of the  
authority having jurisdiction or, in the absence of  
such requirements, with the current edition of the  
National Electrical Code, ANSI/NFPA 70.  
A. WIRING  
1. Refer to Figures 6.1 for connecting the power supply  
to the boiler.  
Figure 6.2: Wiring Circulator with R845A  
Switching Relay  
8. The thermostat connections are shown in Figure 6.1  
or 6.2. The setting for the thermostat anticipator is  
0.56 amps.  
9. The boiler control board and factory wiring are  
shown in figure 6.3.  
B. SEQUENCE OF OPERATION  
1. System Power-Up:  
Figure 6.1: Wiring Connections to Boiler  
Junction Box  
a) When power is first applied to the boiler, the  
control will initially run through a self-diagnostic  
routine. The interface unit shows the system  
supply temperature.  
2. Connect boiler to a 110 volt, single phase, 60 hertz  
electrical supply line with a fused disconnect switch.  
The boiler is fused for a load of 6.3 amperes.  
b) Next, it will power the combustion air fan for a 10  
second purge cycle.  
3. The boiler electrical connection is located on the left  
side of the boiler in the junction box which houses  
the service switch.  
c) Finally the combustion air shuts down and if there  
is no call for heat the control board enters a  
standby mode.  
4. Wire the burner service switch in the hot line to the  
boiler as shown in Figure 6.1.  
2. Heating Cycle:  
a) When the thermostat calls for heat (closing the  
contact between the two gray [TT] wires) and the  
boiler control senses a supply temperature lower  
than the set point by more than the differential,  
the boiler initiates a heating cycle.  
5. Make sure to maintain correct polarity on the  
incoming power supply wires. If polarity is reversed,  
the boiler control will not sense the main burner  
flame.  
6. Connect the ground wire from the incoming power  
supply to the green ground screw in the junction  
box. Also, the boiler ground should be connected to  
this screw.  
b) The control then powers the combustion air fan  
at the speed prescribed for the particular boiler  
model and performs a 6 second pre-purge of the  
combustion chamber.  
7. Figure 6.1 shows connections to system circulator.  
c) 0.5 second before the pre-purge is complete  
power is applied to the spark igniter.  
a) The maximum current load for the circulator  
circuit is 4.0 amperes.  
d) Once the pre-purge cycle is complete, the fan  
speed decreases to the programmed ignition  
speed.  
b) For loads greater than 4.0 amps, isolate the  
circulator using a switching relay.  
26  
ELECTRICAL  
e) The main gas valve is then energized to allow  
gas to mix with the combustion air.  
h) As the supply temperature approaches the set  
point, the combustion control will reduce the  
input rate. The supply temperature will continue  
to climb to about 7°F above the boiler set point  
before it cycles off.  
f) If the main flame is not detected in 5 seconds,  
the gas valve closes and the combustion fan goes  
into post-purge. Otherwise, the combustion fan  
stays at the ignition speed for the length of the  
flame stabilization period. (10 to 25 seconds).  
i) The differential is applied from this point. For  
example if the boiler set point is at 180°F with a  
10°F differential, the supply temperature will  
reach 187°F before shutting down. It will not  
re-start until the supply temperature drops below  
177°F.  
g) After the flame stabilization period is complete,  
the combustion air fan ramps down to its low fire  
setting. Then the boiler will begin to modulate  
depending on the supply temperature to  
maintain the set point temperature.  
Figure 6.3: Boiler Control Board Wiring Schematic  
27  
ELECTRICAL  
Table 6.1: Program Functions  
C. SAFETY INTERLOCKS  
Alternating  
Display  
1. Low Water Pressure Limit Switch: This boiler is  
intended to operate at pressures exceeding 10 psig. If  
the water pressure drops to below 10 psig, there is a  
water pressure limit switch that interrupts boiler  
operation and displays the message "PR0" on the  
interface unit. The combustion air fan completes a  
post-purge in this event. Once the low water pressure  
condition is corrected the boiler will reinitiate a  
heating cycle if there remains a call for heat.  
Description  
Character  
Allowable Range  
50°F to 201°F  
(10°C to 94°C)  
Supply Set Point  
C
5°F to 30°F  
(3°C to 17°C)  
Set Point Differential  
Ch  
Not Applicable  
de  
t
Measurement Units  
C or F  
2. High Water Temperature Limit Switch: The boiler is  
equipped with a limit switch that will interrupt the  
heating cycle and execute a post-purge if the water  
temperature increases to above the limit set point of  
225°F.  
i. The display will alternately show "C" and  
then the current set point temperature.  
ii. The set point may be adjusted by using the  
S1/- (to decrease) or S2/+ (to increase) keys  
on the display module.  
3. High Flue Temperature Limit Switch: The high flue  
temperature limit switch will interrupt the heating  
cycle if it senses flue gas temperatures above 210°F.  
c. Pressing the S3 "Program" key again will advance  
to the next adjustable value, Set Point  
4. Blocked Vent Pressure Limit Switch: This switch  
prevents the boiler from operating if the vent  
pressure exceeds 2 inches of water column. This will  
prevent the boiler from operating if the vent pipe is  
blocked.  
Differential, and the display will alternate  
between: "Ch" and the programmed value:  
i. The differential adjustment is the difference  
between the temperature that the boiler shuts  
down (high) and the temperature at which it  
re-starts (low).  
D. CONTROL FUNCTIONS  
1. This Pinnacle boiler is equipped with a P125 Control  
Board. This control board with display module has  
the following functions:  
ii. The differential may be set to values between  
5°F (3°C) and 30°F (17°C) in 1°F increments.  
a. Shows the boiler supply (outlet) water  
temperature on the LED Display as default.  
iii. The boiler will always shut down at a  
temperature 7°F (4°C) above the set point.  
The differential temperature is then applied to  
this value.  
b. Allows user to adjust the supply water set point,  
the set point differential, and change the display  
mode between Fahrenheit and Celsius.  
iv. The set point differential may be adjusted by  
using the S1/- (to decrease) or S2/+ (to  
increase) keys on the display module.  
c. Provides Error and Fault Codes on the LED  
Display.  
d. Shows the actual supply and return  
temperatures, fan speed, flame signal (µA), boiler  
circulator status, boiler set point, total power on  
hours, boiler on hours, and the number of cycles.  
d. Pressing the S3 "Program" key again will advance  
to the next adjustable value. The display will read  
"de" and alternate with numerical value. This  
value is not applicable to the Pinnacle boiler.  
e. Allows manual control of the firing rate using the  
Service Mode.  
e. Finally, by pressing the S3 "Program" key again,  
the display will advance to the Measurement  
Units selection. The display will alternate  
between "t" and either "F" or "C" depending on  
the units selected. This value may be changed by  
using the S1/- or S2/+ keys on the display  
module.  
2. Default Display: Under normal operating conditions  
the default display shows the temperature of the  
water supply (boiler outlet) to the system. This may  
be displayed in Fahrenheit or Celsius according to  
user preferences.  
f. Pressing the S3 "Program" key once more will  
exit the program mode and again display the  
supply temperature.  
3. Program Functions: By using the S3 "Program" key,  
the settings shown in Table 6.1 may be programmed.  
a. To access the menu, press and hold the S3  
"Program" key on the display module.  
b. The control will enter the Supply Set Point  
selection.  
28  
ELECTRICAL  
4. Error Codes: The LED Display will display error codes  
if the boiler is in a temporary fault condition. Table 8.1  
shows Error Codes and descriptions. In some cases, if  
the temporary fault is not corrected within 60 seconds  
the controller will go into a Fault Code.  
e. To exit the Service Mode, press the S1/- or S2/+  
keys simultaneously.  
8. Installer Menu: The Pinnacle boiler can be  
programmed to be controlled by an external  
analog input controlling set point temperature or  
fan speed. In addition, it can be programmed for  
a 6 minute step modulation sequence.  
5. Fault Codes: A Fault Code indicates the controller is  
locked-out. Press the S4 "Reset" button to resume  
operation after repairing the problem. Table 8.2  
shows Fault Codes for this control.  
a. To enter the installer menu, press and hold the  
S3 "Program" key and S4 "Reset" key  
simultaneously for 3 seconds. The display will  
show a blinking "000."  
6. Status Menu: The status menu, as shown in Table  
6.3, allows the installer to display the current boiler  
supply (outlet) temperature, return (inlet  
Table 6.4: Installer Menu  
temperature), fan speed, flame signal (µA), boiler  
circulator status, boiler set point, total power on  
hours, boiler on hours, and the number of cycles.  
a. To access this menu press and hold the S4  
"Reset" key on the display module for 3 seconds.  
Parameter  
No.  
Function  
0 = Internal Control  
1
2
3
1 = External Input from 0-10 volt adapter  
b. The display will alternate between "d1" and the  
value of the supply temperature.  
0 = External Temperature Input  
1 = External Fan Speed Input  
0 = Step Modulation Disabled  
1 = Step Modulation Enabled  
c. To scroll through the other status codes, simply  
press S4 "Reset", again.  
b. Use the S1/- and S2/+ keys to change the display  
to read 125. Press the S3 "Program" key to enter  
the installer menu. (The control will shut down  
the boiler if it is in operation.) The display will  
alternate between 1 and a value of either 0 or 1.  
d. To exit this menu, press the S3 "Program" key.  
Table 6.3: Status Menu  
Status  
Description  
Code  
c. Table 6.4 shows the Parameter numbers and  
Functions. Press S3 "Program" to advance  
through the parameters and use the S1/- and  
S2/+keys to change the function values. Do not  
change to external input without external  
input device installed!  
d1  
d2  
d3  
d4  
d5  
d6  
d7  
d8  
d9  
Supply (Outlet) Temperature (F or C)  
Return (Inlet) Temperature (F or C)  
Fan Speed (rpm ÷ 10) [ex. 200 = 2000 rpm]  
Flame Signal (µA)  
d. To exit the Installer Menu, press and hold the S4  
“Reset” key for 3 seconds.  
Boiler Circulator Status (0 = Off, 1 = On)  
Boiler Set Point (F or C)  
Power On Time (Hrs ÷ 1000) [ex. 0.1 = 100 hrs]  
Boiler On Time (Hrs ÷ 1000)  
Boiler Cycles (n ÷ 1000)  
7. Service Mode: The Pinnacle boiler can be operated  
in Service Mode to allow the installer to manually set  
the fan speed/input rate of the boiler.  
a. To enter service mode, press and hold the S2/+  
key and the S3 "Program" key simultaneously.  
b. The display will alternately display "SER" and the  
fan speed in RPMs ÷ 10. As default, the fan  
speed will start at the ignition fan speed (this  
value is listed in Section 10, Dimensions and  
Ratings, for each boiler size).  
c. The fan speed can be adjusted by using the S1/-  
key (to decrease speed) or S2/+ key (to increase  
speed) on the display module.  
d. The fan speed will stay in this mode for 10  
minutes or until the boiler reaches 7 degrees  
above the set point temperature.  
Figure 6.4: Display Module  
29  
START-UP PROCEDURES  
7. START-UP PROCEDURES  
c) The set point may be adjusted by using the S1/-  
A. COMPLETING THE INSTALLATION  
(to decrease) or S2/+ (to increase) keys on the  
display module.  
1. Confirm that all water, gas and electricity are  
turned off.  
d) Pressing the S3 "Program" key again will advance  
to the next adjustable value, Set Point Differential  
and the display will alternate between.  
2. Verify that water piping, venting, gas piping and  
electrical wiring and components are installed  
properly and where applicable in accordance with  
manufacturers' instructions. Be sure that the boiler is  
installed in accordance with this manual and good  
engineering practice.  
e) The differential adjustment is the difference  
between the temperature at which the boiler  
shuts down (high) and the temperature at which  
it re-starts (low).  
3. Fill the boiler and system with water, making certain  
to vent all air from each high point in the system.  
Open each vent in the system until all air is released  
and water begins to be discharged, and then close  
the vent.  
f) The differential may be set to values between 5°F  
(3°C) and 30°F (17°C) in 1°F increments.  
g) The boiler will always shut down at a  
temperature 7°F (4°C) above the set point. The  
differential temperature is then applied to this  
value.  
4. The pressure reducing valve on the fill line will  
typically allow the system to be filled and pressurized  
to 12 PSI. Consult the manufacturer's instructions for  
operation of the valve and expansion tank.  
h) The set point differential may be adjusted by  
using the S1/- (to decrease) or S2/+ (to increase)  
keys on the display module.  
5. Check joints and fittings throughout the system and  
repair as required.  
i) Pressing the S3 "Program" key again will advance  
to the next adjustable value. The display will read  
"de" and alternate with numerical value. This  
value is not applicable to the Pinnacle boiler.  
6. Connect a manometer at or near the service valve to  
the boiler.  
7. Confirm that the gas supply pressure to the boiler is  
between the minimum and maximum values for the  
gas being used. These values can be found in Table  
4.4 of Section 4.  
j) Finally, by pressing the S3 "Program" key again,  
the display will advance to the Measurement  
Units selection. The display will alternate  
between "t" and either "F" or "C" depending on  
the units selected. This value may be changed by  
using the S1/- or S2/+ keys on the display  
module.  
8. If a full supply pressure test is required, isolate the  
boiler and gas valve before performing the pressure  
test. If the supply pressure is too high or too low,  
contact the fuel gas supplier.  
11. Light the boiler by following the Lighting/Operating  
instructions in this section. The initial ignition may  
fail several times before the gas piping is completely  
purged of air.  
9. Turn on electricity and gas to the boiler. Check to see  
if the LED display is lit. The combustion air fan will  
begin a 5 second purge cycle and then the control  
will go into Standby Mode.  
12. Use the sequence of operation description and  
Figure 6.3, Control Board Wiring Schematic to  
follow light off and shutdown sequences and to assist  
in diagnosing problems. If the boiler does not  
function properly, consult Section 8,  
10. Adjust set point temperatures and differential  
temperatures by pressing and holding the S3,  
"Program" key for 3 seconds.  
a) The control will enter the Supply Set Point  
selection.  
Troubleshooting.  
b) The display will alternately show "C" and then  
the current set point temperature.  
30  
START-UP PROCEDURES  
B. LIGHTING AND OPERATING  
PROCEDURES  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion may  
result, causing property damage, personal injury or loss of life.  
A. This appliance does not have a pilot. It is equipped  
with an ignition device which automatically lights the  
burner. Do not try to light the burner by hand.  
If you cannot reach your gas supplier, call the  
fire department.  
C. Use only your hand to turn the gas control knob. Never  
use tools. If the handle will not turn by hand, don’t try  
to repair it, call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
B. BEFORE OPERATING smell all around the appliance  
area for gas. Be sure to smell next to the floor  
because some gas is heavier than air and will settle  
on the floor.  
D. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the  
control system and any gas control which has been  
under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch; do not use any  
phone in your building.  
Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas suppliers’ instructions.  
OPERATING INSTRUCTIONS  
11. STOP! Read the safety information above.  
15. Remove front cover.  
12. Set the thermostat to lowest setting.  
16. Turn gas shutoff valve clockwise to “off”. Handle will be  
vertical, do not force.  
13. Turn off all electric power to the appliance.  
17. Wait five (5) minutes to clear out any gas. If you then  
smell gas, STOP! Follow “B” in the safety information  
above on this label. If you don’t smell gas, go to next  
step.  
14. This appliance is equipped with an ignition device  
which automatically lights the burner. Do not try to light  
the burner by hand.  
18. Turn gas shutoff valve counterclockwise to “on”.  
Handle will be horizontal  
19. Install Front Cover.  
10. Turn on all electric power to appliance.  
11. Set thermostat to desired setting.  
12. If the appliance will not operate, follow the instructions  
To Turn Off Gas To Appliance” and call your service  
technician or gas supplier.  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
4. Turn gas shutoff valve clockwise to “off”. Handle will be  
vertical. Do not force.  
2. Turn off all electric power to the appliance if service is  
to be performed.  
5. Install front cover.  
3. Remove front cover.  
31  
START-UP PROCEDURES  
C. CHECK-OUT PROCEDURE  
4. Low Water Cut-Off (if used) - Consult the  
manufacturer's instructions for the low water cut-off  
operational check procedure.  
1. After starting the boiler, be certain that all controls  
are working properly. Check to be sure that the  
boiler will shut down when the water temperature  
reaches the control board set point.  
5. Check the system to assure that there are no leaks or  
overfilling problems which may cause excessive  
make up water to be added. Make up water may  
cause liming in the boiler and corrosion in ferrous  
system parts.  
2. To check operation of the ignition system safety shut-  
off features:  
a) Turn off gas supply.  
6. Check the expansion tank and automatic fill valve (if  
used) to confirm that they are operating correctly. If  
either of these components causes high pressure in  
the system, the boiler relief valve will weep or open,  
allowing fresh water to enter the system.  
b) Set thermostat or controller above room  
temperature to call for heat.  
c) The boiler should perform 3 attempts at ignition  
before going into lock-out.  
7. Check the condensate drain hose (and pump if  
installed) and make sure all condensate is being  
removed from heat exchanger.  
d) Turn gas supply on.  
e) Reset by pushing S4 "Reset" key.  
8. Review operation with end-user.  
f) Observe boiler operation through one complete  
cycle.  
9. Complete the Warranty Card and submit it to PB  
Heat.  
3. Turn off the automatic fill to the boiler and drain  
some water to drop the system pressure below 10  
psig. Verify that the display module reads "PRO"  
after 5 seconds and does not allow the boiler to  
operate. Close the boiler drain and turn on the  
automatic fill valve.  
10. Hang the Installation, Operation, and Maintenance  
Manual in an accessible position near the boiler.  
32  
TROUBLESHOOTING  
8. TROUBLESHOOTING  
A. BOILER ERROR  
DANGER  
1. When an error condition occurs the controller will  
display an error code on the display module.  
When servicing or replacing components that are in  
direct contact with the boiler water, be certain that:  
There is no pressure in the boiler. (Pull the  
release on the relief valve. Do not depend on  
the pressure gauge reading).  
2. These error codes and several suggested corrective  
actions are included in Table 8.1.  
3. In the case of E00, E13, and E14 this error, if  
uncorrected, will go into a fault condition as  
described is Paragraph B.  
The boiler water is not hot  
The electrical power is off  
B. BOILER FAULT  
WARNING  
1. When a fault condition occurs the controller will  
illuminate the red "fault" indication light and display  
a fault code in the format "F##" on the display  
module.  
Do not use this appliance if any part has been under  
water. Improper or dangerous operation may result.  
Contact a qualified service technician immediately to  
inspect the boiler and to repair or replace any part of  
the boiler which has been under water.  
2. Note the fault code and refer to Table 8.2 for an  
explanation of the fault code along with several  
suggestions for corrective actions.  
CAUTION  
3. Press the reset key to clear the fault and resume  
operation. Be sure to observe the operation of the  
unit to prevent a recurrence of the fault.  
This appliance has wire function labels on all internal  
wiring. Observe the position of each wire before  
removing it. Wiring errors may cause improper and  
dangerous operation. Verify proper operation after  
servicing.  
WARNING  
When servicing or replacing any components of this  
boiler be certain that:  
CAUTION  
The gas is off.  
All electrical power is disconnected  
If overheating occurs or the gas supply fails to shut  
off, do not turn off electrical power to the circulating  
pump. This may aggravate the problem and increase  
the likelihood of boiler damage. Instead, shut off the  
gas supply to the boiler at the gas service valve.  
Table 8.1: P125 Control Board Error Codes  
Code  
Description  
Duration  
Corrective Action  
1. Check circulation pump operation.  
2. Assure that there is adequate flow through the boiler by  
accessing the status menu and assuring that there is less  
than a 50°F rise from the return thermistor to the supply  
thermistor.  
E00  
High Limit Exceeded  
50 Sec.  
3. Replace switch if faulty.  
Combustion Fan Speed Low.  
The boiler combustion air fan speed  
less than 70% of expected.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
E13  
E14  
60 Sec.  
60 Sec.  
Combustion Fan Speed High.  
The boiler combustion air fan speed  
is more than 130% of expected.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
1. Assure that the system pressure is above 10 psig.  
2. Check for leaks in the system piping.  
3. Check the switch operation by applying a jumper. (If the  
switch is not functioning properly replace it.)  
PRO Water Pressure Switch Open  
Until Corrected  
1. Assure that the vent is not blocked.  
Until Corrected 2. Check the switch operation by applying a jumper. (If the  
switch is not functioning properly replace it.)  
FLu  
Blocked Vent Pressure Switch Open  
33  
TROUBLESHOOTING  
Table 8.2: P125 Control Board Fault Codes  
Fault  
Code  
Description  
Corrective Action  
1. Check circulation pump operation.  
2. Assure that there is adequate flow through the boiler by accessing the status menu  
and confirming that there is less than a 50°F rise from the return thermistor to the  
supply thermistor.  
3. If gray thermostat wires are being used, disconnect them and jump them together.  
If F00 code can be reset check thermostat circuit for short circuit or stray voltage.  
4. Check supply temperature reading on LED display. Replace High Limit Switch if  
supply temperature is below 210°F.  
F00  
High Limit Exceeded.  
5. Temporarily jump out Water Pressure Switch. If F00 code can be reset check wiring  
harness and connections. If wiring harness is okay replace Water Pressure Switch.  
1. Push the red reset button on the switch.  
F01  
Vent Temperature Limit Exceeded.  
2. Check the flue temperature during operation using a combustion analyzer.  
3. Replace the switch if faulty.  
Interrupted or Shorted  
Supply (Outlet) Thermistor.  
1. Check the electrical connection to the thermistor on the outlet manifold.  
2. Replace thermistor if necessary.  
F02  
F03  
Interrupted or Shorted  
Return (Inlet) Thermistor.  
1. Check the electrical connection to the thermistor on the inlet manifold.  
2. Replace thermistor if necessary.  
1. Check circulation pump operation.  
Supply (Outlet)  
Temperature exceeded 230°F.  
2. Assure that there is adequate flow through the boiler by accessing the status menu  
and confirming that there is less than a 50°F rise from the return thermistor to the  
supply thermistor.  
F05  
F06  
1. Check circulation pump operation.  
Return (Inlet) Temperature  
exceeded 230°F.  
2. Assure that there is adequate flow through the boiler by accessing the status menu  
and confirming that there is less than a 50°F rise from the return thermistor to the  
supply thermistor.  
1. Watch the igniter through the observation window provided.  
No flame detected – The boiler will make three 2. If there is no spark, check the spark electrode for the proper ¼" gap.  
attempts at ignition before the control goes into 3. Remove any corrosion from the spark electrode.  
F09  
F10  
this lockout condition.  
4. If there is a spark but no flame, check the gas supply to the boiler.  
5. If there is a flame, check the flame sensor.  
1. Check the gas pressure to the gas valve while the unit is in operation.  
2. Assure that the flame is stable when lit.  
3. Check to see if the green light on the display module is out while the boiler  
Loss of Flame Signal – The boiler will relight 4  
times before the control goes into this lockout  
condition.  
is running.  
4. If the green light doesn't come on or goes off during operation check the flame  
signal on the status menu.  
5. If the signal reads less than 1 microampere, clean the flame sensor.  
6. If the sensor continues to read low, replace it.  
1. Turn the gas off to the unit at the service valve.  
2. If the flame signal is still present replace the flame rod.  
3. If the flame signal is not present after turning off the gas supply, check  
the gas valve electrical connection.  
False Flame Signal – The boiler will lock out if  
it senses a flame signal when there should be  
none present.  
F11  
4. If there is no power to the gas valve, remove the valve and check for obstruction  
in the valve seat or replace the gas valve.  
5. Turn the gas on at the service valve after corrective action is taken.  
Combustion Fan Speed Low – The boiler will  
1. Check the combustion air fan wiring.  
lock out if it senses that the fan speed is less than 2. Replace the combustion air fan.  
F13  
F14  
70% of expected for more than 60 seconds.  
3. Replace the control board.  
Combustion Fan Speed High – The boiler will  
lock out if the fan speed is more than 130% of  
expected for more than 60 seconds.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
1. Make sure the connector is correctly connected to the gas valve.  
2. Check the electrical wiring from the valve to the control board.  
3. Replace the gas valve.  
Gas Valve Error  
F18  
4. Replace control board.  
Watchdog  
Call factory for further assistance.  
Call factory for further assistance.  
Call factory for further assistance.  
Call factory for further assistance.  
F30  
F31  
F32  
F33  
Parameter Memory  
Parameter Memory Write Error  
Programming Error  
Neutral Fault – Boiler locks out if it senses  
a voltage drop or power feedback on the  
neutral wire.  
1. Check for adequate supply voltage.  
2. Check for power feedback on the neutral wire.  
NC  
34  
MAINTENANCE  
9. MAINTENANCE  
d. Release the try lever and allow the valve to close.  
If the valve leaks, operate the lever two or three  
times to clear the valve seat of foreign matter. It  
may take some time to determine if the valve has  
shut completely.  
A. GENERAL (WITH BOILER IN USE)  
General boiler observation can be performed by the  
owner. If any potential problems are found, a qualified  
installer or service technician/agency must be notified.  
1. Remove any combustible materials, gasoline and  
other flammable liquids and substances that generate  
flammable vapors from the area where the boiler is  
contained.  
e. If the valve continues to leak, it must be replaced  
before the boiler is returned to operation.  
f. Check that operating pressure and temperature  
have returned to normal.  
2. Observe general boiler conditions (unusual noises,  
vibrations, etc.)  
g. Check again to confirm that valve has closed  
completely and is not leaking.  
3. Observe operating temperature and pressure on the  
combination gauge located in the supply piping on  
the left side of the boiler. Boiler pressure should  
never be higher than 5 psi below the rating shown  
on the safety relief valve (25 psig maximum for a 30  
psig rating). Boiler temperature should never be  
higher than 240° F.  
3. Test low-water cut-off (if used) as described by the  
manufacturer.  
4. Test limit as described in Section 7, Part C, “Check-  
Out Procedure”.  
5. Test function of ignition system safety shut-off  
features as described in Section 7, Part C, “Check-  
Out Procedure”.  
4. Check for water leaks in boiler and system piping.  
5. Smell around the appliance area for gas. If you smell  
gas, follow the procedure listed in the Lighting  
Operating Instructions to shut down appliance in  
Section 7, Start-Up Procedure Part B.  
DANGER  
When servicing or replacing components, be  
absolutely certain that the following conditions are  
met:  
B. WEEKLY (WITH BOILER IN USE)  
1. Flush float-type low-water cut-off (if used) to remove  
sediment from the float bowl as stated in the  
manufacturer’s instructions.  
Water, gas and electricity are off.  
The boiler is at room temperature.  
There is no pressure in the boiler.  
C. ANNUALLY (BEFORE START OF  
HEATING SEASON)  
6. Remove the top/front jacket panel and inspect for  
any foreign debris that may have entered through air  
inlet vent.  
CAUTION  
7. Inspect burner for deterioration. Replace if necessary.  
The following annual inspection must be performed  
by a qualified service technician.  
8. With boiler in operation check that condensate is  
dripping from drain hose. Check for any restriction in  
condensate drain line.  
a. CONDENSATE CLEANING INSTRUCTIONS:  
1. Check boiler room floor drains for proper  
functioning.  
1. Turn the thermostat down or off so the  
Pinnacle will not cycle and then follow the  
steps below.  
2. Check function of the safety relief valve by  
performing the following test:  
a. Check valve piping to determine that it is  
properly installed and supported.  
a. Close manual gas shutoff valve.  
b. Disconnect the condensate piping from the  
outside connection (not from the Pinnacle)  
so flow can be observed.  
b. Check boiler operating temperature and pressure.  
c. Lift the try lever on the safety relief valve to the  
full open position and hold it for at least five  
seconds or until clean water is discharged.  
c. Block the air flow in the exhaust by  
temporarily plugging the exhaust from the  
outside vent.  
35  
MAINTENANCE  
d. Disconnect the white, red, blue, and black  
1. Shut the Pinnacle down by using the  
following steps:  
connection from the Molex on the  
combustion blower. (Refer to Control  
Wiring Schematic, Figure 6.3.) This will  
cause the fan to run at 100% which will  
then blow out any sediment that has  
accumulated in the condensate line. (This  
process should only take a few minutes.)  
a. Close the manual gas shutoff valve, shut  
down the unit and wait for the unit to be  
cool to the touch.  
b. Disconnect the condensate piping from the  
outside connections (not from the Pinnacle  
side) so the flow can be observed.  
e. The unit should now be ready to restart.  
2. Before restarting the Pinnacle follow the  
steps below:  
c. Remove the (4) screws on the 1/2" NPT  
connector on the gas valve.  
a. Reconnect the Molex connection and  
unblock the vent. (IMPORTANT: MAKE  
SURE EXHAUST VENT IS NO  
LONGER BLOCKED!)  
d. Remove the (6) 10mm nuts from the  
burner plate assembly to access the coils.  
e. Pull the entire burner plate assembly  
towards you, while removing or pushing  
aside any wiring to allow the removal of  
the assembly.  
b. Open the manual gas shutoff valve and  
reset the thermostats.  
c. Observe the boiler function to make sure  
you see a condensate flow.  
2. Using a spray bottle filled with the  
recommended product "Rydlyme" or "CLR",  
spray liberally on the coils, making sure the  
solution penetrates and funnels down through  
the condensate hose. If the condensate hose  
is blocked, let the chemical penetrate for at  
least 15 minutes or until it drains.  
d. If you do not observe a condensate flow,  
repeat the above procedure.  
3. If the problem is not corrected at this point, it  
is possible that there is a material deposit  
problem. Follow the Coil Cleaning instructions  
(Section b) included in this section to dissolve  
deposits and clean condensate line.  
3. Use the nylon or brass brush (do not use  
steel) and scrub coils to remove any buildup,  
then vacuum the derbis from the coils.  
DANGER  
4. Spray the coils with clear water, making sure  
to confine the spray to the area being cleaned  
(try to avoid betting the back ceramic wall of  
the unit wet). Flush the combustion chamber  
with fresh water. At this point, the Pinnacle  
should be ready to power back up.  
It is extremely important to make sure the exhaust  
vent is not longer blocked. Failure to do so may  
result in personal injury or death.  
b. COMBUSTION CHAMBER COIL CLEANING  
INSTRUCTIONS  
5. Before powering up the Pinnacle follow the  
steps below:  
Before beginning this procedure, you must have  
on hand the following items:  
a. Reinstall the burner assembly.  
b. Replace the (6) 10mm nuts to the burner  
plate.  
a nylon or brass brush (not steel)  
"Rydlyme" (recommended for best results)  
"CLR" (available at most hardware stores)  
c. Reconnect the wiring.  
d. Replace the (4) screws on the 1/2" NPT  
connector on the gas valve. Turn the gas  
back on. (IMPORTANT: CHECK FOR  
GAS LEAKS)  
36  
MAINTENANCE  
e. Reset thermostats (IMPORTANT: MAKE  
SURE EXHAUST VENT IS NO  
LONGER BLOCKED!)  
f. Turn the Pinnacle back on** and observe  
condensate flow.  
g. Reconnect the condensate piping to the  
outside connection.  
DANGER  
It is extremely important that you check for leaks  
when reconnecting the gas valve and make sure the  
exhaust vent is no longer blocked. Failure to do so  
may result in severe personal injury or death.  
**NOTE: When firing the boiler the first few times you  
may experience some fluttering of the gas  
burner that may result in a flame lockout.  
This is normal and will require you to re-cycle  
the unit until this clears up. This is caused  
by water still present in the combustion  
chamber.  
9. Inspect exhaust vent and air inlet vents for proper  
support and joint integrity. Repair as necessary. Refer  
to Section 5, VENTING.  
10. Inspect exhaust vent and air inlet vent terminations  
for obstructions.  
WARNING  
Leaks in the vent system will cause products of  
combustion to enter structure (vent system operates  
under positive pressure).  
37  
BOILER DIMENSIONS & RATINGS  
10. BOILER DIMENSIONS & RATINGS  
A. BOILER DIMENSIONS  
1. Figure 10.1 shows the dimensions of the PI-T50 and  
PI-T80.  
Figure 10.1: PI-T50/PI-T80 Dimensions  
38  
BOILER DIMENSIONS & RATINGS  
2. Figure 10.2 shows the dimensions of the PI-80,  
PI-140 and PI-199.  
Figure 10.2: PI-80/PI-140/PI-199 Dimensions  
39  
BOILER DIMENSIONS & RATINGS  
Table 10.1: Boiler Ratings  
DOE Heating  
Capacity³  
Btu/hr  
Net I=B=R  
Seasonal  
Efficiency³  
AFUE %  
Shipping  
Weight  
Lbs.  
Boiler  
Model  
Input Btu/hr  
Rating¹ ²  
Btu/hr  
PI-T50  
PI-T80  
PI-80  
18,000 to 50,000  
19,000 to 80,000  
27,000 to 80,000  
16,000 to 46,000  
17,000 to 74,000  
25,000 to 74,000  
40,000  
92  
92  
92  
92  
92  
58  
58  
64,000  
64,000  
75  
PI-140  
PI-199  
46,000 to 140,000 43,000 to 129,000  
66,000 to 199,000 61,000 to 183,000  
112,000  
159,000  
101  
111  
1.  
2.  
Net I=B=R ratings are based on an allowance of 1.15.  
Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as  
intermittent system operation, extensive piping systems, etc.  
3.  
Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government Testing.  
Table 10.2: Combustion Air Fan Speed  
Fan Speed – RPM  
Boiler  
Model  
High Fire  
Ignition  
Low Fire  
PI-T50  
PI-T80  
PI-80  
3200  
4700  
4600  
4300  
6000  
3000  
3000  
4600  
2000  
3745  
1250  
1200  
2000  
1400  
2100  
PI-140  
PI-199  
Note: These values are subject to change without notice.  
Table 10.3: Connection Sizes  
Supply &  
Return Conn.  
(NPT)  
Relief Valve Gas Supply  
Air Inlet &  
Vent Conn.  
(Sch 40 PVC)  
Condensate  
Drain Pipe  
(NPT)  
Boiler  
Model  
Outlet  
(NPT)  
Conn.  
(NPT)  
PI-T50  
PI-T80  
PI-80  
1-1/4"  
1-1/4"  
1-1/4"  
1-1/4"  
1-1/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
2"  
2"  
3"  
3"  
3"  
3/4"  
3/4"  
3/4"  
3/4"  
3/4"  
PI-140  
PI-199  
40  
REPAIR PARTS  
11. REPAIR PARTS  
41  
REPAIR PARTS  
42  
WHAT’S NEW WITH THE P125 CONTROL BOARD  
APPENDIX A. WHAT’S NEW WITH THE  
P125 CONTROL BOARD  
A. ADVANTAGES OF THE P125 CONTROL  
BOARD  
B. P125 CONTROL BOARD QUICK  
REFERENCE  
1. Temperature displays in Fahrenheit or Celsius.  
1. Press and hold the S3 “Program” key to make  
changes to:  
2. Improved troubleshooting by status display of:  
a. Actual Supply and Return Temperatures  
a. Set Point Temperature  
b. Set Point Differential  
c. Temperature Display Units  
Scroll through to Exit  
b. Flame Signal  
c. Fan Speed  
3. Service Mode allows installers to manually control  
the firing rate for easy set up.  
2. Press and hold S4 "Reset" key to display the status of:  
a. Supply Temperature  
4. Available Software that allows the installer to access  
status information and fault history from a PC.  
b. Return Temperature  
c. Fan Speed  
5. Optional Interface Module that allows the boiler to  
be operated with a 0-10 volt analog input signal  
from a modulating controller (such as Tekmar 265,  
263, and BTC MPA) for features such as:  
d. Flame Signal  
e. Boiler Circulator Status  
f. Boiler Set Point  
a. Outdoor Reset Control.  
b. Dual temperature set points for space heating  
and indirect hot water demands.  
g. Power On Time  
c. Modulating Sequencing for up to three boilers.  
h. Number of Cycles  
Press the S3 “Program” key to exit.  
The Pavilion 410 is an external control that allows  
the boiler to be controlled with a 0-5 volt analog  
input signal. An interface module is not necessary.  
The Pavilion 410 provides features a. and b. (above).  
3. Press and hold the S2/+ and the S3 “Program” keys  
simultaneously to enter “Service Mode.” Press S1/-  
or S2/+ to change the fan speed. (Note: The service  
mode will cause the boiler to run even if there is no  
call for heat. The limits will, however, shut down the  
unit if the temperature exceeds the set point.  
Figure A.1:Pinnacle P125 Board Display Module  
43  
WHAT’S NEW WITH THE P125 CONTROL BOARD  
C. P125 CONTROL BOARD VS. WHA  
CONTROL BOARD COMPARISON  
Figure A.2:Comparative Control Board Sequence of Operation  
44  
®
®
Peerless Pinnacle  
Stainless Steel Gas Boilers  
Installation,  
Operation &  
Maintenance  
Manual  
TO THE INSTALLER:  
This manual is the property of the owner and must  
be affixed near the boiler for future reference.  
TO THE OWNER:  
This boiler should be inspected annually by  
Qualified Service Agency.  
a
CONTROLS  
MH27745  
ASME  
HI Division  
of gama  
PB HEAT, LLC  
P.O. BOX 447 • NEW BERLINVILLE, PA 19545-0447  
PeerlessBoilers.com  
©2006 WEB-3  
PI8008 R11 (9/06-5M)  
Printed in U.S.A.  

Polar Bicycle Accessories CS600X User Manual
Pioneer Car Stereo System DEH 4400BT User Manual
Philips VKR 9300 User Manual
Philips CED370 User Manual
Panasonic Cordless Phone With Answering Machine KXTG7645M User Manual
Panasonic Camcorder HC V700M User Manual
Panasonic AJ HDX900P User Manual
Nokia BH 301 User Manual
Learning Resources Inc Calculator 2284 User Manual
JVC KD Lh401 User Manual