Lochinvar Commercial Soiler 400 801 User Manual

KBXII-SER Rev F  
Service Manual  
Models: 400 - 801  
This manual must only be used  
ƽ WARNING  
by a qualified heating installer /  
service technician. Read all  
instructions, including this manual  
and the Knight XL Installation and  
OperationManual, beforeinstalling.  
Perform steps in the order given.  
Failure to comply could result in  
severe personal injury, death, or  
substantial property damage.  
Save this manual for future reference.  
Service Manual  
Please read before proceeding  
Installer  
Read all instructions,  
When calling or writing about the boiler  
– Please have the boiler model and serial  
number from the boiler rating plate.  
ƽ WARNING  
NOTICE  
including this manual and the Knight  
XL Installation and Operation Manual,  
before installing. Perform steps in the  
order given.  
Consider piping and installation when  
determining boiler location (see the Knight  
XL Installation and Operation Manual).  
User – This manual is for use only by  
a
qualified heating installer/service  
Any claims for damage or shortage  
in shipment must be filed immediately  
against the transportation company by the  
consignee.  
technician. Refer to the Knight XL User’s  
Information Manual for your reference.  
Have this boiler serviced/inspected by  
a qualified service technician at least  
annually.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
Handling ceramic fiber materials  
REMOVAL OF COMBUSTION CHAMBER LINING  
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers  
can be converted to cristobalite in very high temperature applications. The International Agency for  
Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite  
from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this  
appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions  
would have to be created to convert the ceramic fibers in this appliance to cristobalite.  
ƽ WARNING  
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic  
materials it is advisable that the installer follow these safety guidelines.  
Avoid breathing dust and contact with skin and eyes.  
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA  
requirements for cristobalite at the time this document was written. Other types of respirators may  
be needed depending on the job site conditions. Current NIOSH recommendations can be found on  
manufacturers, and phone numbers are also listed on this website.  
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.  
Apply enough water to the combustion chamber lining to prevent airborne dust.  
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.  
NIOSH stated First Aid.  
Eye: Irrigate immediately.  
Breathing: Fresh air.  
3
Service Manual  
Please read before proceeding  
When servicing boiler –  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
Boiler operation –  
• Do not block flow of combustion or ventilation air to  
the boiler.  
• Should overheating occur or gas supply fail to shut off,  
do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a location  
external to the appliance.  
• Do not use this boiler if any part has been under water.  
The possible damage to a flooded appliance can be  
extensive and present numerous safety hazards. Any  
appliance that has been under water must be replaced.  
Boiler water –  
• Thoroughly flush the system (without boiler  
connected) to remove sediment. The high-efficiency  
heat exchanger can be damaged by build-up or  
corrosion due to sediment.  
• Do not use petroleum-based cleaning or sealing  
compounds in the boiler system. Gaskets and seals in  
the system may be damaged. This can result in  
substantial property damage.  
• Do not use “homemade cures” or “boiler patent  
medicines”. Serious damage to the boiler, personnel,  
and/or property may result.  
• Continual fresh make-up water will reduce boiler life.  
Mineral buildup in the heat exchanger reduces heat  
transfer, overheats the stainless steel heat exchanger, and  
causes failure. Addition of oxygen carried in by makeup  
water can cause internal corrosion. Leaks in boiler  
piping must be repaired at once to prevent the  
introduction of makeup water.  
Freeze protection fluids –  
• NEVER use automotive antifreeze. Use only inhibited  
propylene glycol solutions which are specifically  
formulated for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used in hydronic  
systems.  
4
Service Manual  
What is in this manual?  
Service  
Maintenance  
• Service and maintenance schedules  
• Address reported problems  
• Inspect boiler area and boiler interior  
• Clean condensate trap  
• Check all piping for leaks  
• Check air openings  
Near boiler piping  
• Typical system components  
The Knight XL display  
• Display panel readout, buttons and their functions  
• Flue vent system and air piping  
• Check water system  
• Check expansion tank  
Control module inputs  
• Control module inputs and options  
• Check boiler relief valve  
• Inspect ignition electrode  
• Check ignition ground wiring  
• Check all boiler wiring  
• Check control settings  
• Perform start-up and checks  
• Check burner flame  
• Check flame signal  
• Check flue gas temperature  
• General maintenance  
Control module outputs  
• Control module outputs and options  
General  
• How the boiler operates  
• How the control module operates  
• Access modes -- user and installer  
• Sequence of operation -- Domestic Hot Water  
(DHW)/space heating  
• Review with owner  
Control panel menu access  
• Cleaning boiler heat exchanger  
• Oiled bearing circulators  
• Accessing programming mode and locating menus  
(See separate guide covering the interface.)  
Troubleshooting  
Control panel parameter access  
• Accessing and changing parameters from the display panel  
• Troubleshooting table - No display  
• Checking temperature sensors  
• Sensor tables  
• Troubleshooting table - Fault messages displayed on  
boiler interface  
Quick start information -- parameter  
table  
• An index of available adjustments and readouts, where to  
access them and where to find detailed information.  
• Combustion analysis procedure  
• Gas valve adjustment procedure  
Knight XL operation  
• A: General  
• B: Temperature Setting  
• C: Data Logging  
• D: Functions  
• E: DHW Settings  
• F: Outdoor Reset  
• G: Anti-cycling  
• H: Control Modes  
• I: Circulation Pumps  
• J: Building Management System (BMS)  
• K: Service Notification  
5
Service Manual  
1 Service  
Near boiler piping  
This piping reference is included to specify the Near Boiler Piping specific to the Knight XL. This piping scheme is important  
for proper operation of the SMART SYSTEM control. See the Knight XL Installation and Operation Manual for more detailed  
piping diagrams.  
DOMESTIC HOT  
WATER PUMP  
DIRT SEPARATOR  
INDIRECT  
SYSTEM SENSOR  
DOMESTIC  
HOT WATER  
TANK  
SYSTEM PUMP  
Y-STRAINER  
(RECOMMENDED)  
BOILER PUMP  
TO FLOOR  
DRAIN  
6
Service Manual  
1 Service  
(continued)  
The Knight XL display  
NAVIGATION DIAL  
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the  
NAVIGATION dial (in the center):  
MENU = Left SELECT Key  
SETPOINTS = NAVIGATION Dial - Pressing Down  
SHDN = Right SELECT Key  
7
Service Manual  
1 Service  
Control inputs  
SYSTEM PUMP SPEED CONTROL  
GAS PRESSURE SWITCH  
DHW THERMOSTAT  
ROOM THERMOSTAT /  
ZONE CONTROL  
LOW VOLTAGE  
CONNECTION  
BOARD  
FLOW SWITCH  
SYSTEM SENSOR  
OUTDOOR SENSOR  
SEQUENCER / BUILDING  
MANAGMENT SYSTEM  
LOW WATER CUTOFF  
O-TEMP  
HEAT EXCHANGER SWITCH  
INLET TEMPERATURE  
SENSOR  
OUTLET TEMPERATURE /  
HI-LIMIT SENSOR  
FLUE GAS SENSOR  
AIR PRESSURE SWITCH  
LOUVER PROVING SWITCH  
FLAME SENSOR  
BLOCKED DRAIN SWITCH  
SMART CONTROL  
MODULE  
DISPLAY PANEL  
PC INTERFACE  
IMG00006  
8
Service Manual  
1 Service  
(continued)  
Control outputs  
ALARM BELL  
LOW VOLTAGE  
CONNECTION  
BOARD  
LOUVER RELAY  
RUN TIME CONTACTS  
BUILDING MANAGEMENT  
SYSTEM  
BOILER PUMP  
SYSTEM PUMP  
DHW PUMP  
IGNITOR  
BLOWER  
SMART CONTROL  
MODULE  
GAS VALVE  
DISPLAY PANEL  
PC INTERFACE  
9
Service Manual  
1 Service  
Access modes  
General Operation  
How the boiler operates  
User  
The user can adjust space heating and tank target temperatures  
by pressing the NAVIGATION dial when “SETPOINTS” is  
flashing at the bottom of the display. The date and time, and  
the temperature units can also be changed.  
The Knight XL uses an advanced stainless steel heat  
exchanger and an electronic control module that allows  
fully condensing operation. The blower pulls in gas and air  
and pushes flue products out of the boiler through the heat  
exchanger and flue piping. The control module regulates  
blower speed to control boiler firing rate. The gas valve  
senses the amount of air flowing into the boiler and allows  
only the right amount of gas to flow.  
Installer  
Most parameters are available only to the installer, accessible  
by entering the installer password (5309).  
How the control module operates  
Saving parameters (reference the Parameter Table -  
Table 1-4 on pages 15 - 18 of this manual)  
The Knight XL control module receives input from boiler  
sensors. The control module activates and controls the  
blower and gas valve to regulate heat input and switches  
boiler, DHW and system pumps on and off as needed.  
The user/installer programs the module to meet system  
needs by adjusting control parameters. These parameters  
set operating temperatures and boiler operating modes.  
Boiler operation can be based on boiler outlet water  
temperature, boiler return water temperature or system  
supply temperature, depending on the parameter setting.  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
To save parameters and exit programming:  
Press the RIGHT SELECT [SAVE] key and then press the  
RIGHT SELECT [HOME] key.  
To enter a parameter and continue programming:  
Press the RIGHT SELECT [SAVE] key 1 time to return to the  
parameter listings; press again to return to the menu listings.  
Remember to press the RIGHT SELECT [HOME] key when  
finished programming in order to save the changes made.  
Sequence of operation  
Table 1-1 shows control module normal sequences of  
operation for space heating and DHW operation. The  
combined operation sequence is for a typical application,  
programmed to provide DHW priority.  
10  
Service Manual  
1 Service  
(continued)  
Table 1-1 Sequence of Operation  
OPERATION  
DISPLAY  
1. Upon a call for heat, the gas pressure switch(es) must be closed.  
2. Once the gas pressure switch(es) are closed, the control turns  
on the appropriate pumps (system and boiler pumps for space  
heating, DHW pump for DHW). The flow switch and/or LWCO  
must close.  
3. The control turns on power to the louver relay. The louver  
proving switch, air pressure switch, and blocked drain switch  
must close.  
4. The control starts a prepurge cycle by initiating the blower.  
5. The control starts a trial for ignition by firing the spark  
electrode and opening the gas valve.  
6. If flame is not detected after the sparking ends, the control will  
perform a postpurge, then start another prepurge cycle and try  
to light the burner again. On the 501 and larger models, the control  
will lock out if this second attempt also fails. On the 400 model,  
the control will perform a total of 4 attempts before locking out.  
7. If flame is detected, it holds the firing rate steady for a few  
seconds to let the flame stabilize, then it begins to modulate the  
firing rate based on a set point or some other command (such  
as a 0-10V BMS signal).  
a
11  
Service Manual  
1 Service  
Table 1-1 (continued from previous page) Sequence of Operation  
OPERATION  
DISPLAY  
8. If the space heating call for heat is active, and the tank thermostat  
or sensor starts a DHW call for heat, the boiler will switch to the  
DHW mode. If programmed for normal DHW operation (not as  
a zone), the DHW pump will turn on first, then the boiler pump  
will turn off (boiler and DHW pump operation briefly overlap to  
ensure flow is maintained through the unit). This will divert the  
boiler’s outlet water from the heating system and send it to the  
tank coil instead. The control will then modulate to maintain the  
outlet temperature to the DHW boiler set point.  
9. If the boiler is not part of a Cascade, and both the space heating  
and DHW calls for heat remain active long enough, the boiler will  
switch back and forth between the two heating modes until one  
of them is satisfied.  
10. Once both calls for heat are satisfied, the control will turn off  
the burner. The blower will continue to run during the postpurge  
period.  
11. Any pumps that are running will continue to run for their  
respective pump delay times before turning off, unless  
programmed to remain on continuously. A 60 second anti-cycle  
period will start, which will delay any new call for heat until it  
times out.  
12. In Standby, ready to start a new cycle.  
12  
Service Manual  
1 Service  
(continued)  
Display panel menu access  
Table 1-2 Use this procedure to access menus from the display panel  
SCREEN  
STATUS  
BUTTON  
OPERATION  
DISPLAY  
[SHDN]  
Press the RIGHT SELECT soft key [SHDN].  
[YES]  
Press the LEFT SELECT soft key [YES].  
Press and hold the LEFT SELECT soft key [MENU]  
for five (5) seconds.  
[MENU]  
Rotate the NAVIGATION dial clockwise until 5 is  
displayed (first digit on the left).  
Press the NAVIGATION dial to select the next digit.  
Rotate the NAVIGATION dial clockwise until 3 is  
shown in the display.  
Press the NAVIGATION dial 2 times to move to the last  
digit. Rotate the NAVIGATION dial counterclockwise  
until 9 is displayed.  
[SAVE]  
Press the RIGHT SELECT soft key [SAVE].  
Rotate the NAVIGATION dial counterclockwise to  
select a category.  
13  
Service Manual  
1 Service  
Display panel parameter access  
Table 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Settings, MIN  
SH Setpt  
SCREEN  
STATUS  
BUTTON  
OPERATION  
DISPLAY  
This example shows how to access parameter Temperature Settings. The first display shown is at the beginning  
of the menu listings, after entering the installer access code.  
Rotate the NAVIGATION dial counterclockwise until  
the arrow (>) is next to TEMPERATURE SETTINGS.  
Press the NAVIGATION dial one time.  
Rotate the NAVIGATION dial counterclockwise until  
the arrow (>) is next to MIN SETPT.  
Press the NAVIGATION dial one time.  
Rotate the NAVIGATION dial to the desired  
temperature.  
[SAVE]  
[EXIT]  
Press the RIGHT SELECT soft key [SAVE] one time.  
Press the LEFT SELECT soft key [EXIT] if all desired  
changes have been made.  
[HOME]  
Press the LEFT SELECT soft key [HOME].  
14  
Service Manual  
1 Service  
(continued)  
Parameter table  
Table 1-4 This table lists SMART SYSTEM control module parameters and where to access them  
User Access  
Installer Access  
See  
Menu  
Description  
Page  
Display Modify Display Modify  
Time and Date  
18  
18  
18  
18  
18  
Yes  
No  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Software Version (read only)  
Temperature Units (ºC/ºF)  
SH Night Setback Offset  
SH Night Setback On Times  
Yes  
No  
Yes  
No  
Yes  
Yes  
Yes  
No  
No  
SH Night Setback Off Times  
DHW Night Setback Offset  
DHW Night Setback On Times  
DHW Night Setback Off Times  
Display Timeout  
18  
18  
18  
18  
19  
19  
19  
19  
No  
No  
No  
No  
No  
Yes  
No  
No  
No  
No  
No  
No  
No  
Yes  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
SH1 Set Point  
Minimum SH Set Point  
Maximum SH Set Point  
Yes  
Yes  
Yes  
Yes  
SH1 Offset  
19  
19  
19  
19  
19  
No  
No  
No  
No  
Yes  
Yes  
No  
Yes  
Yes  
No  
SH1 Differential  
SH2 Set Point  
SH2 Offset  
Yes  
No  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
SH2 Differential  
No  
No  
SH3 Set Point  
SH3 Offset  
19  
19  
19  
19  
Yes  
No  
No  
No  
Yes  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
SH3 Differential  
3-Way Valve Time  
Reset Log Errors  
19  
No  
No  
Yes  
Yes  
Service Mode Delay  
19  
19  
19  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Freeze Protection Pump On  
Freeze Protection Burner On  
Freeze Protection Burner Differential  
20  
No  
No  
Yes  
Yes  
DHW Boiler Set Point  
Tank Set Point  
20  
20  
20  
20  
No  
Yes  
No  
No  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Tank Set Point Differential  
DHW Boiler Offset  
No  
No  
DHW Boiler Differential  
SH/DHW Switching Time  
DHW/SH Switching Time  
Tank Minimum Set Point  
Tank Maximum Set Point  
DHW Type  
20  
20  
20  
20  
20  
20  
20  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Fan Speed Limiting for DHW  
15  
Service Manual  
1 Service  
Parameter table  
Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where  
to access them  
User Access  
Installer Access  
See  
Page  
Menu  
Description  
Display Modify Display Modify  
Outdoor 1 Low  
Outdoor 1 High  
21  
21  
21  
21  
21  
22  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Set Point 1 at Low Outdoor Temp 1  
Set Point 1 at High Outdoor Temp 1  
Outdoor Air Shutdown SH1  
Outdoor Air Shutdown Differential SH1  
Shift Reset Curve SH1  
Outdoor 2 Low  
22  
21  
21  
21  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Outdoor 2 High  
Set Point 2 at Low Outdoor Temp 2  
Set Point 2 at High Outdoor Temp 2  
Outdoor Air Shutdown SH2  
Outdoor Air Shutdown Differential SH2  
Shift Reset Curve SH2  
21  
21  
22  
22  
21  
21  
21  
21  
21  
22  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Outdoor 3 Low  
Outdoor 3 High  
Set Point 3 at Low Outdoor Temp 3  
Set Point 3 at High Outdoor Temp 3  
Outdoor Air Shutdown SH3  
Outdoor Air Shutdown Differential SH3  
Shift Reset Curve SH3  
Boost Temperature  
Boost Time  
22  
22  
22  
22  
22  
22  
23  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Anti-Cycling Time  
Anti-Cycling Override Differential  
Ramp Delay  
Ramp Settings  
16  
Service Manual  
1 Service  
(continued)  
Parameter table  
Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where  
to access them  
User Access  
Installer Access  
See  
Page  
Menu  
Description  
Display Modify Display Modify  
Controlling Sensor  
BMS Tstat Input  
BMS  
23  
23  
23  
23  
23  
23  
23  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
ModBus  
ModBus T/O  
Cascade Address  
Cascade Type  
Max Cascade Set Point  
Cascade Offset  
24  
24  
24  
24  
24  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Cascade Differential  
Min On/Off Time  
Min Next On Time  
Boiler Size  
24  
24  
25  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
System Pump Delay  
Boiler Pump Delay  
DHW Pump Delay  
25  
25  
25  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Boiler Pump Anti-Seize Delay  
Boiler Pump Min Voltage  
System Pump Type  
DHW Pump Anti-Seize Delay  
DHW Blocks Sys Pump  
DHW Forces Sys Pump  
System Pump Anti-Seize Delay  
BMS Type  
25  
25  
25  
25  
25  
25  
25  
25  
25  
25  
26  
26  
26  
26  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Volts at Min  
Volts at Max  
Rate at Min Volts  
Rate at Max Volts  
Set Point at Min Volts  
Set Point at Max Volts  
On Volts  
Off Differential Volts  
Service Notification Months  
26  
No  
No  
Yes  
Yes  
Service Notification Running Time  
Service Notification Cycles  
26  
26  
26  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Reset Maintenance Reminder  
Service Name and Phone Number  
26  
No  
No  
Yes  
Yes  
17  
Service Manual  
1 Service  
Viewable and changeable control parameters  
Space Heating (SH) and Domestic Hot Water (DHW)  
Night Setback On Times  
Before changing parameters, note the  
settings so that the unit can be returned to  
its original operating parameters.  
CAUTION  
This is the time in which the SH Night Setback Offset becomes  
active. There are 7 start times and 7 stop times each for the  
space heating and DHW night setback features. Both may be  
set to any time within a 7-day week. These settings are referred  
to as triggers. Multiple start or stop triggers may be set within a  
single day, if desired. When a start trigger and a stop trigger are  
set to the same time, the stop trigger has priority. The installer  
may adjust the space heating night setback start triggers by  
accessing the SH Night Setback On Times parameter. The DHW  
start triggers in the DHW Night Setback On Times parameter.  
This screen shows the start trigger number, the day of the week,  
and the time of day.  
General  
Time and Date  
The control uses an internal clock for the night setback  
feature and for logging of events. For these features to  
work correctly, the clock must be set when the boiler is first  
installed or anytime the boiler has been powered off for more  
than four (4) hours. This parameter must be accessed to set  
the clock.  
The internal clock does not adjust for  
Daylight Savings Time and therefore,  
will require a manual adjustment.  
NOTICE  
Please note that the brackets ([]) denote  
NOTICE  
screen status.  
The clock is automatically updated whenever a PC is  
connected and the Win_Pro-Installer program is started.  
1. When the screen is first accessed, start trigger number 1  
is shown. If a different trigger number is desired, the  
installer can rotate the NAVIGATION dial until the  
desired trigger number is displayed. Once the desired trigger  
number is selected, the installer can press the NAVIGATION  
dial and the day of the week will start to flash.  
2. The installer can adjust the day of the week to the one he  
wishes to set. Once the day is set, the installer can press the  
NAVIGATION dial and the hour will begin to flash.  
3. After setting the hour, the installer can press the  
NAVIGATION dial and the minutes will flash. Once all  
settings have been made, the installer can press the RIGHT  
SELECT [SAVE] key. The installer can now select a  
different trigger and adjust the settings for that trigger.  
4. Once all adjustments are made, the installer can press the  
RIGHT SELECT [SAVE] key to save all of the new settings  
and return to the General menu, or press the LEFT SELECT  
[EXIT] key to return to the General menu without saving the  
changes.  
Software Version  
The software version allows the user to view the software  
version in use by the control. This software controls the  
operation of the boiler. When a new software version  
becomes available, the existing control can be replaced with a  
new control to update the software.  
Software version is read only.  
Temperature units (°C / °F)  
The control can be configured to display temperature in  
either °C or °F. This parameter can be changed by the user  
or the installer by accessing the Temperature Units parameter.  
The default is °F.  
Space Heating (SH) and Domestic Hot Water (DHW)  
Night Setback Offset  
Once the unit’s internal clock has been set correctly, the  
Night Setback feature can be used to program a lower set  
point during unoccupied times. Both the space heating and  
DHW can be programmed for night setback. When in night  
setback, the control reduces the set point by a fixed amount.  
For space heating, it subtracts the space heating night setback  
offset from each of the SH user set points (SH1, 2, and 3 Set  
point parameters), or the calculated outdoor reset set point (if  
lower). For DHW, it subtracts the DHW night setback offset  
from the tank set point (Tank Set point parameter).  
Space Heating (SH) and Domestic Hot Water (DHW)  
Night Setback Off Times  
The corresponding space heating night setback stop triggers are  
set by accessing the SH Night Setback Off Times parameter. The  
stop triggers for the DHW night setback feature can be adjusted  
by accessing the DHW Night Setback Off Times parameter. The  
adjustment procedure for these parameters is identical to the  
space heating start triggers described above.  
Night Setback Override  
NOTE: The DHW night setback will not work without a tank  
sensor installed.  
Any Night Setback On trigger currently active or scheduled  
within the next seven (7) days can be skipped. To skip a trigger,  
rotate the NAVIGATION dial until the arrow (>) is next to the  
trigger you wish to skip. Press the NAVIGATION dial once.  
“SK” will appear next to that trigger to indicate that it will be  
skipped. You can restore an upcoming trigger by selecting that  
trigger, and pressing the NAVIGATION dial again. The “SK”  
next to that trigger will disappear.  
The installer may adjust the space heating night setback  
offset by accessing the SH Night Setback Offset parameter and  
the DHW night setback offset by accessing the DHW Night  
Setback Offset parameter. The minimum setting is 0°F (0°C)  
and the maximum setting is 90°F (50°C).  
18  
Service Manual  
1 Service  
(continued)  
To save any changes and return to the Home Screen, press  
the RIGHT SELECT [HOME] key. To return to the Status  
Screen without saving the changes, press the LEFT SELECT  
[EXIT] key.  
3-Way Valve Time  
The optional Lochinvar Multi-Temperature Loop Control  
Board(MTLCB)canbeusedtocontrolthesupplytemperature  
up to three (3) sub-loops, corresponding to each of the three  
(3) SH set points, through the use of 3-way mixing valves. To  
ensure the MTLCB will control these temperature properly,  
it is necessary to let the control know how much time these  
mixing valves require to fully open and close. Program  
this time into the 3-Way Valve Time parameter. Since this  
parameter applies to all of the mixing valves used, the actual  
open/close time must be approximately the same for each  
one. The minimum setting is 1 second, and the maximum  
setting is 255 seconds. The default setting is 20 seconds.  
Display Timeout  
This is the time in which the display remains illuminated.  
The range is 10 seconds to 10 minutes. The default is 3  
minutes.  
Temperature Settings  
Space Heating (SH1, SH2, SH3) Set Point  
Mixing valves are required for the  
protection of any low temperature loops.  
CAUTION  
Data Logging  
Reset log errors  
The reset log errors function clears the last 10 errors log.  
There are three (3) individual user set points for better zone  
control. These are listed as SH1 Set Point through SH3 Set  
Point. If multiple set points are calling for heat the highest set  
point has priority. The range is SH Minimum Set point to SH  
Maximum Set point. The default is 125°F (52°C).  
Functions  
Service Mode Delay  
By pressing the pin button on the front of the display for  
five (5) seconds, the control will be placed in Service Mode.  
This will override all other heat demands. The Service Mode  
allows the installer to set the unit to any firing rate for the  
purpose of combustion analysis. The delay sets the length of  
time the boiler will stay in the Service Mode if no keys have  
been pressed before going back to its original state. This  
parameter can only be changed by the installer by accessing  
the Service Mode Delay parameter. The time range of this  
parameter is 1 to 10 minutes. The default value is 10 minutes.  
Space Heating (SH) Minimum Set Point  
The SH minimum set point sets the minimum water  
temperature set point that can be used for space heating  
operation. The user or installer will not be able to program  
the control with a lower SH set point. This parameter can  
only be changed by the installer by accessing Minimum SH  
Set point parameter. The temperature range of this parameter  
is 32°F (0°C) to the space heating maximum set point. The  
default value is 32°F (21°C).  
Freeze Protection Pump On  
The SMART SYSTEM control will turn on the boiler and  
system pump outputs whenever the inlet temperature drops  
below this setting. This is done to prevent the water in the  
heat exchanger from freezing. Certain low-temperature  
applications (such as snow melt) can operate at temperatures  
around freezing, so this setting needs to be lowered in these  
cases. The installer can adjust the temperature at which the  
pump outputs are turned on by accessing Freeze Protection  
Pump On parameter. The minimum setting is -3°F (-19°C),  
and the maximum setting is 45°F (7.2°C). The default setting  
is 45°F (7.2°C).  
Space Heating (SH) Maximum Set Point  
The SH maximum set point sets the maximum water  
temperature set point that can be used for space heating. The  
user or installer will not be able to program the control with a  
higher SH set point. This parameter can only be changed by  
the installer by accessing Maximum SH Set point parameter.  
The temperature range of this parameter is the space heating  
minimum set point to 180°F (82°C). The default value is  
180°F (82°C).  
SH1 - SH3 Offset Set Point  
Never put the Freeze Protection Pump  
on a setting lower than the Freeze  
Protection Burner On setting.  
The SH offset sets how many degrees above set point the  
temperature has to go before the boiler will shut off. This  
parameter can only be changed by the installer by accessing  
parameters SH1, 2 and 3 Offset Set point parameters. The  
temperature range of these parameters is 0°F to 20°F. The  
default value is 10°F.  
NOTICE  
Freeze Protection Burner On  
If running the pumps does not prevent the inlet temperature  
from falling closer to freezing, the SMART SYSTEM control  
will fire the burner at low fire. The installer can adjust the  
temperature at which the burner fires by adjusting the Freeze  
Protection Burner On parameter. The minimum setting is  
-3°F (-19°C), and the maximum setting is 45°F (7.2°C). The  
default setting is 37°F (2.8°C).  
SH1 - SH3 Differential Set Point  
The SH differential sets how many degrees below the offset  
the temperature has to drop before the boiler turns back  
on. This parameter can only be changed by the installer by  
accessing the SH1, 2 and 3 Differential Set point parameters.  
The range is 0°F to 60°F. The default is 20°F.  
Never put the Freeze Protection Pump  
on a setting lower than the Freeze  
Protection Burner On setting.  
NOTICE  
19  
Service Manual  
1 Service  
Freeze Protection Burner Differential  
Once this timer expires, it will switch back to the DHW demand.  
The installer can adjust the length of time the boiler will service  
the space heating demand by accessing SH/DHW Switching  
Time parameter. The minimum setting is 0 minutes and the  
maximum setting is 50 minutes. The default time is 30 minutes.  
Once the burner has started firing due to a low inlet  
temperature, the inlet temperature must increase by this  
amount before the burner turns back off. The installer can  
adjust this differential by accessing the Freeze Protection  
Burner Differential parameter. The minimum setting is 0°F,  
and the maximum is 20°F. The default setting is 5°F (2.8°C).  
DHW/SH Switching Time  
When a boiler has a DHW demand and it receives a space  
heating demand, the SMART SYSTEM control will start a  
timer. Once the timer expires, it will stop the DHW demand  
and service the space heating demand. The installer can adjust  
the length of time the boiler will service the DHW demand  
by accessing the DHW/SW Switching Time parameter. The  
minimum setting is 0 minutes and the maximum setting is 50  
minutes. The default setting is 30 minutes.  
DHW Settings  
DHW Boiler Set Point  
When a DHW call for heat becomes active, the control will  
use the DHW boiler set point to determine the firing rate of  
the boiler based on the boiler outlet water temperature, or  
system temperature when DHW is programmed as a zone.  
This parameter can be changed by the installer by accessing  
the DHW Boiler Set point parameter. The temperature range  
of this parameter is 68°F (20°C) to 180°F (82°C). The default  
value is 180°F (82°C).  
Tank Minimum Set Point  
This setting controls the minimum tank set point for the tank  
temperature. The installer can adjust this by accessing the Tank  
Minimum Set point parameter. The minimum setting is 60°F  
(16°C) and the maximum setting is the maximum tank set point  
(Tank Maximum Set point parameter). The default value is 60°  
(16°C).  
DHW Tank Set Point  
By installing a tank sensor, the SMART SYSTEM control can  
perform the tank thermostat function. The SMART SYSTEM  
control automatically detects the presence of this sensor, and  
generates a DHW call for heat when the tank temperature  
drops below the tank set point differential (Tank Set point  
Differential parameter), and finishes the call for heat when  
the tank temperature reaches tank set point + offset. This  
parameter can be changed by the installer by accessing the  
DHW Tank Set point parameter. The temperature range of  
this parameter tank minimum set point to tank maximum set  
point. The default value is 125°F (52°C).  
Tank Maximum Set Point  
This setting controls the maximum tank set point for the tank  
temperature. The installer can adjust this by accessing the Tank  
Maximum Set point parameter. The minimum setting is the  
minimum tank set point (Tank Minimum Set point parameter)  
and the maximum setting is 190°F (88°C). The default value is  
140°F (60°C).  
DHW Type  
Tank Set Point Differential  
This parameter determines whether the Knight XL boiler treats  
the indirect DHW tank as a separate load, or as a zone on the  
primary loop. When programmed as a separate load, the boiler  
will turn on the DHW pump and then turn off the boiler pump  
when an indirect DHW demand begins. When programmed as  
a zone, the boiler will turn on the DHW pump, leave the boiler  
pump on and change the system set point to the DHW boiler set  
point (DHW Boiler Set point parameter).  
When a tank sensor is installed, the tank temperature must  
drop this amount below the tank set point (DHW Tank  
Set point parameter) before the boiler turns back on. The  
installer can adjust this setting by accessing the Tank Set point  
Differential parameter. The minimum setting is 0° (0°C), and  
the maximum is 40°F (22°C). The default setting is 6°F (3°C).  
DHW Boiler Offset  
This parameter reflects the degrees above DHW boiler set  
point the temperature has to go before the boiler will shut off.  
The range is 0°F (0°C) to 40°F (22°C). The default setting is  
10°F (6°C).  
This setting may be changed by the installer by accessing the  
DHW Type parameter. The choices are NORMAL and ZONE.  
The default setting is NORMAL.  
Fan Speed Limiting for Indirect DHW Tank  
DHW Boiler Differential  
This parameter determines the maximum fan speed (and  
therefore the maximum rate) to be used when heating an  
indirect DHW tank when the DHW Type is set to Normal.  
This setting may be used when the tank is unable to accept all  
of the BTU’s available from the boiler. This parameter may be  
adjusted by the installer by accessing the Fan Speed Limiting  
for Indirect DHW Tank parameter. The default value is the  
maximum fan speed for that model.  
This parameter reflects the degrees below DHW boiler set  
point the temperature has to go before the boiler turns back  
on. The range is 0°F (0°C) to 60°F (33°C). The default setting  
is 20°F (13°C).  
SH/DHW Switching Time  
When a boiler has a space heating demand and it receives  
a DHW demand, it will immediately switch to the DHW  
demand and start a timer. Once the timer has expired, the  
boiler will switch back to the space heating demand and start  
another timer.  
20  
Service Manual  
1 Service  
(continued)  
Set Point (1 - 3) at Low Outdoor Temperature  
Outdoor Reset  
When the outdoor air temperature drops to the Outdoor  
(1 - 3) Low parameters, the calculated set point will be at  
this setting (FIG. 1-1). If the outdoor air temperature drops  
further, the set point will continue to increase above this  
setting. However, if SH1, SH2, and SH3 are set lower, the  
water temperature will be limited by these set points instead.  
These parameters can be changed by the installer by accessing  
the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low  
Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3  
parameters. The temperature range of this parameter is 68°F  
(20°C) to 180°F (82°C). The default value is 180°C (82°C).  
The option of controlling up to three (3) different outdoor  
resets for low outdoor temperatures is available.  
Outdoor (1 - 3) Low  
When the outdoor air temperature drops to this point, the  
water temperature will be at the Set point 1 at Low Outdoor  
Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point  
3 at Low Outdoor Temp 3 parameters (FIG. 1-1). If the  
outdoor air temperature drops further, the set point will  
continue to increase above this setting. This parameter can  
be changed by the installer by accessing the Outdoor (1-3)  
Low parameter. The temperature range of this parameter is  
-39°F (-39°C) to high outdoor temperature set point. The  
default value is 25°F (-4°C).  
Set Point (1 - 3) at High Outdoor Temperature  
When the outdoor air temperature rises to or above Outdoor  
(1 - 3) High parameters, the calculated set point will be at this  
setting (FIG. 1-1). These parameters can be changed by the  
installer by accessing the Set point 1 at High Outdoor Temp 1,  
Set point 2 at High Outdoor Temp 2 and Set point 3 at High  
Outdoor Temp 3 parameters. The temperature range of this  
parameter is 68°F (20°C) to 190°F (88°C). The default value  
is 70°F (21°C).  
Outdoor (1 - 3) High  
When the outdoor air temperature rises to or above this  
point, the water temperature will be at the Set point 1 at High  
Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and  
Set point 3 at High Outdoor Temp 3 parameters (FIG. 1-1).  
This parameter can be changed by the installer by accessing  
the Outdoor (1-3) High parameter. The temperature range  
of this parameter is low outdoor temperature set point to  
104°F (40°C). The default value is 70°F (21°C).  
Outdoor Air Shutdown (SH1 - SH3)  
When the outdoor temperature rises above this point, the  
control will block all SH demands (DHW demands will still  
be active). These parameters can be changed by the installer  
by accessing the Outdoor Air Shutdown SH1, SH2, and SH3  
parameters. The temperature range of this parameter is 32°F  
(0°C) to 104°F (40°C). The default value is 70°F (21°C).  
Figure 1-1 Outdoor Air Reset Curve  
SET POINT AT  
LOW OUTDOOR  
TEMPERATURE  
(SH)  
SET POINT  
SET POINT AT  
HIGH OUTDOOR  
TEMPERATURE  
HIGH OUTDOOR  
TEMPERATURE  
LOW OUTDOOR  
TEMPERATURE  
21  
Service Manual  
1 Service  
Outdoor Air Shutdown Differential (SH1 - SH3)  
Boost Time  
The outdoor air shutdown differential parameter is the  
number of degrees below Outdoor Air Shutdown SH1, SH2,  
and SH3 parameters the outdoor air temperature must go  
before the boiler will respond to a SH demand. These  
parameters can be changed by the installer by accessing  
the Outdoor Air Shutdown Differential SH1, SH2, and SH3  
parameters The temperature range of this parameter is 0°F  
(0°C) to 54°F (30°C). The default value is 10°F (6°C).  
The boost time parameter sets the amount of time that must  
elapse with a SH demand before the water temperature calculated  
set point will be increased. This parameter can be changed by  
the installer by accessing the Boost Time parameter. The time  
range for this parameter is 0 minute to 50 minutes. The default  
value is 0 minutes.  
Anti-Cycling  
Anti-Cycling Time  
Shift Reset Curve (SH1 - SH3)  
Once a SH demand has been satisfied, a set amount of time must  
elapse before the control will respond to a new SH demand. The  
control will block the new heat demand and anti-cycling will  
be shown in the display until the time has elapsed or the water  
temperature drops below the Anti-Cycling Override Differential  
parameter. This parameter can be changed by the installer by  
accessing the Anti-Cycling Time parameter. The time range for  
this parameter is 1 minute to 10 minutes. The default value is  
1 minute.  
There is a shift reset curve for each outdoor reset. The shift  
reset curve parameter shifts the actual set point above or  
below the calculated set point by the number of degrees in  
this parameter. These parameters can be changed by the  
installer by accessing the Shift Reset Curve SH1, SH2, and  
SH3 parameters. The temperature range of this parameter  
is -17°F (-10°C) to 18°F (10°C). The default value is 0°F  
(0°C). This feature will be active if this parameter is set to  
anything other than 0°F (0°C).  
Anti-Cycling Override Differential  
Boost Temperature  
The control will bypass the anti-cycling time if the inlet  
water temperature drops too much. The control will use the  
inlet water temperature the boiler was at when it shut off as  
the starting point. If the inlet temperature drops below the  
temperature parameter the control will abort anti-cycling and  
allow the boiler to fire. This parameter can be changed by  
the installer by accessing the Anti-Cycling Override Differential  
parameter. The temperature range of this parameter is 0°F (0°C)  
to 54°F (30°C). The default value is 10°F (6°C).  
If a SH demand lasts longer than the programmed time  
delay setting and there have been no DHW demands, the  
control will increase the water temperature set point by the  
amount in this parameter. If the SH demand continues  
through another time period, the set point will be increased  
again. This will continue until either the SH demand ends,  
a maximum of 20 increases has occurred, or SH1, SH2,  
SH3 maximum set point has been reached. Once the SH  
demand has been satisfied the set point will revert back  
to its calculated setting. The boost temperature can be  
changed by the installer by accessing the Boost Temperature  
parameter. The temperature range of this parameter is 0°F  
(0°C) to 25°F (14°C). The default value is 0°F (0°C). This  
feature will be active if this parameter is set to anything  
other than 0°F (0°C).  
Ramp Delay (Enable / Disable)  
This parameter allows the installer to enable or disable the SH  
ramp delay. The default setting is disabled.  
Figure 1-2 Ramp Delay Interval  
22  
Service Manual  
1 Service  
(continued)  
BMS  
Ramp Settings  
The set point or modulation of the boiler may be controlled  
through the 0 - 10V BMS input or through ModBus. When the  
BMS parameter is set to INACTIVE, the 0 - 10V input will be  
ignored. When set to ACTIVE, the set point or modulation will  
be controlled by the voltage on the 0 - 10V input (in the case  
of 0 - 10V BMS control), or the 0 - 10V input value received  
through ModBus. The default value is INACTIVE.  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The SMART SYSTEM control can be programmed to limit the  
firing rate for a fixed period of time at the start of a space heating  
demand. There are six (6) possible limits, each with their own  
time delay. The first limit applies as soon as the burner starts.  
Once its time delay expires, the second limit is applied and its  
timer begins. The control steps through these limits until the  
6th (sixth) limit expires. Note, however, that the 6th limit will  
also limit the rate for the rest of that heat demand. The installer  
can adjust the firing limits and time delays by accessing the  
Ramp Settings parameter. Once this parameter is selected, the  
screen will show the step number, the time delay for that step  
and the limit value corresponding with that step. If the installer  
wishes to adjust one of the values in that step, he can press  
the NAVIGATION dial until the value he wishes to change is  
flashing. The installer can then rotate the NAVIGATION dial  
to adjust that value. If the installer presses the RIGHT SELECT  
[SAVE] key while the limit value is flashing, the step value will  
flash again. The installer can then select the next step and adjust  
the delay and limit values corresponding with that step.  
ModBus  
When BMS is set to ACTIVE (see BMS Active / Inactive) and  
the boiler is being controlled through ModBus, set ModBus  
parameter to ACTIVE. Otherwise, set the ModBus parameter  
to INACTIVE. Note that the boiler can still be monitored by  
ModBus with this parameter set to INACTIVE. The default  
value is INACTIVE.  
ModBus T/O  
The amount of time the unit controls will wait to receive  
a communication string from the BMS controller before  
reverting back to its own internal parameters. This parameter  
is adjustable by the installer by accessing the ModBus T/O  
parameter. The adjustment range of this parameter is 5 seconds  
to 2 minutes. The default value is 10 seconds.  
When finished, the installer can press the RIGHT SELECT  
[SAVE] key to store the new settings, or the LEFT SELECT  
[EXIT] key to return to the Anti-Cycling parameter list  
without saving the changes. The delay value can be set between  
0 minutes and 20 minutes. The limit value can be set between  
0% and 100%.  
Cascade Address  
The boiler designated as the Leader needs to be programmed  
with address 0. All the Member boilers require addresses from  
1 to 7, and the addresses must be different for each Member.  
The addresses can be in any order, regardless of the order in  
which the units are wired together. This parameter is adjustable  
by the installer by accessing the Cascade Address parameter.  
The outdoor air (if used) and system supply sensor must be  
connected to the Leader boiler. The default address is 1.  
Control modes  
Controlling Sensor  
The SH controlling sensor parameter selects the sensor the  
control will use to regulate the boiler firing rate. This parameter  
is adjustable by the installer by accessing the Controlling Sensor  
parameter. The sensor selections are as follows: The outlet  
sensor regulates the firing rate based on the outlet water  
temperature of the boiler and the inlet sensor regulates the  
firing rate based on the inlet water temperature of the boiler.  
If the outlet sensor is selected, and the optional system supply  
sensor is connected, the control will regulate the firing rate  
based on the system supply sensor temperature. The default  
sensor is the Outlet Sensor.  
If installing the boilers in an existing system, the new boilers  
should be programmed as the Leader and/or the higher number  
addresses.  
Cascade Type (L/L / EFF)  
There are two (2) options for the way a Cascade divides the load  
between its heaters. The first is Lead/Lag, designated as L/L in  
the menu. This method is used when it is desired to have the  
least amount of total flow through the boilers. This method  
will modulate the last two (2) boilers. This provides for smooth  
transitions when a boiler turns on or off. When the last boiler  
reaches 100% and the calculated load is still increasing, it will  
start the next boiler at 20% and reduce the previous boiler  
to 80%, thus eliminating the sudden jump in total output  
of the Cascade. When the calculated load is decreasing and  
the last boiler gets down to 20% fire, it will hold it there and  
start lowering the firing rate on the next-to-last boiler. When  
the next-to-last boiler reaches 20%, it will turn the last boiler  
off and raise the rate of the next-to-last boiler to 40%, thus  
eliminating the sudden drop in total output of the Cascade.  
BMS Thermostat Input  
When controlling the boiler through the 0 - 10V BMS input or  
through ModBus, the boiler can be enabled one of two ways.  
With the BMS Thermostat Input parameter set to ACTIVE,  
the boiler will be enabled by closing the Heat/Loop Demand 1  
input. When set to INACTIVE, the boiler will be enabled by  
the voltage level on the 0 - 10V input (in the case of 0 - 10V  
BMS control), or the 0 - 10V input value received through  
ModBus. The default value is INACTIVE.  
23  
Service Manual  
1 Service  
The other Cascade divider method is Efficiency  
Optimization, designated as EFF in the menu. This  
method is used, as the name implies, when it is desired  
to have the most efficient system. When the first boiler  
reaches a certain rate (default = 90%), it lowers its rate  
to 45% and turns on the next boiler at 45%. The two (2)  
boilers then modulate at the same rate.  
Minimum On/Off Time  
In order to prevent units in a Cascade from short cycling,  
this parameter defines the minimum ON and OFF time for  
each unit. The installer can adjust this time by accessing the  
Minimum On/Off Time parameter. The minimum setting is 0  
seconds and the maximum setting is 10 minutes. The default  
is 30 seconds.  
Minimum Next On Time  
As the calculated load increases further and both boilers  
ramp up to 90%, it lowers the rate of the first two (2)  
boilers to 60% and brings the next boiler on at 60%.  
The three (3) boilers then modulate together. As the  
calculated load decreases, the boilers will reach a lower  
threshold (default = 30%), at which time the last boiler  
(the third in our example) will turn off and the Cascade  
will increase the rates of the remaining boilers to provide  
the equivalent total output as before ((3 x 30%) / 2 = 45%  
in our example).  
In order to reduce the risk of temperature overshoot with  
a Cascade, this parameter defines the minimum time delay  
from starting one unit until the next unit may be started. The  
installer can adjust this time delay by accessing the Minimum  
Next On Time parameter. The minimum setting is 0 minutes  
and the maximum setting is 10 minutes. The default is 60  
seconds.  
Boiler Size  
When boilers of different sizes are connected together in a  
Cascade, the Leader boiler has to know the size of each boiler  
in that Cascade. The Boiler Size parameters allow the installer  
to program the size based on the Cascade address. This screen  
shows the Cascade address and the size of the boiler with that  
address (in BTU/hr):  
Efficiency optimization is automatically selected when  
boilers of different sizes are programmed into the Leader  
control (see Boiler Size on this page).  
Maximum Cascade Set Point  
This parameter determines the set point used by the  
individual boilers in a Cascade when a system sensor  
is connected to the Leader boiler. When a boiler is  
commanded to fire by the Leader boiler, it will attempt to  
achieve this temperature at its outlet. The Leader boiler  
will limit the modulation of the last boiler to fire in order  
to hold the temperature at the system supply sensor to  
the user set point. If any of the boiler outlet temperatures  
reach the maximum cascade set point, the boiler will  
then modulate down on its own in order to keep its  
outlet temperature within the maximum cascade set point.  
Therefore, this parameter can be used to limit the outlet  
temperatures of all the boilers in a Cascade. Note that  
this parameter does not apply when the boiler is heating  
an indirect DHW tank. This parameter is adjustable by  
the installer by accessing the Maximum Cascade Set Point  
parameter. The temperature range of this parameter is 32°  
(0°C) to 190°F (88°C). The default maximum cascade set  
point is 185°F (85°C).  
1. When the Boiler Size screen is first accessed, Cascade  
Address 0 (Leader) is shown.  
2. Press the NAVIGATION dial to access the first digit of the  
boiler size. Rotate the NAVIGATION dial to adjust the  
first digit. To access the next digit, press the NAVIGATION  
dial again. Continue this process until the correct boiler  
size (to the nearest 1000 BTU/hr) is shown. Press the  
RIGHT SELECT [SAVE] key.  
3. Rotate the NAVIGATION dial to select the address of the  
next boiler in the Cascade. Repeat Step 2.  
4. Once the size of the last boiler in the Cascade has been  
entered and saved, press the LEFT SELECT [EXIT] key to  
return to the Control Modes menu.  
5. If no other parameters are to be adjusted, press the RIGHT  
SELECT [HOME] key to save the new settings and return  
to the Status screens.  
The SMART SYSTEM control automatically uses the Efficiency  
Optimization Cascade type when controlling boilers of different  
sizes.  
Cascade Offset  
This parameter determines how much the temperature  
must go above set point before the lead boiler will turn off.  
This parameter can be adjusted by the installer by accessing  
the Cascade Offset parameter. The temperature range of  
this parameter is 0° to 20°F (11°C) The default value is  
10°F (6°C).  
Circulation pumps  
System Pump Delay  
The system pump delay parameter sets the length of time the  
system pump (if connected) will run after a SH demand has  
been satisfied. This parameter is adjustable by the installer by  
accessing the System Pump Delay parameter. The time range  
for this parameter is 1 second to 40 minutes. The default time  
is 30 seconds.  
Cascade Differential  
This parameter determines how much the temperature  
must go below the turn off temperature (Set point +  
Offset) before the lead boiler turns on. This parameter  
can be adjusted by the installer by accessing the Cascade  
Differential parameter. The temperature range of this  
parameter is 0°F to 60°F (33°C) The default value is 20°F  
(11°C).  
24  
Service Manual  
1 Service  
The SH pump delay parameter sets the length of time the  
boiler pump will run after a SH demand has been satisfied.  
Setting the delay time to 0 will disable the pump. This  
parameter is adjustable by the installer by accessing the Boiler  
Pump Delay parameter. The time range for this parameter is  
1 second to 40 minutes. The default time is 30 seconds.  
(continued)  
DHW Blocks Sys Pump  
Boiler Pump Delay  
When the indirect DHW tank is connected as a zone on the  
primary loop, the DHW Blocks Sys Pump parameter tells the  
system pump if it is allowed to run during a DHW demand.  
To force the system pump to turn off during a DHW demand,  
set the DHW Blocks Sys Pump parameter to YES. The default  
setting is NO.  
DHW Pump Anti-Seize Delay  
DHW Pump Delay  
If the boiler pump does not run for 24 hours, it will be turned  
on briefly to prevent it from seizing. The length of time it runs  
is determined by the DHW Pump Anti-Seize Delay parameter.  
The range of this setting is 0 seconds to 50 minutes. The default  
setting is 20 seconds.  
The DHW pump delay parameter sets the length of time the  
DHW pump (if connected) will run after a DHW demand has  
been satisfied. This parameter is adjustable by the installer by  
accessing the DHW Pump Delay parameter. The time range  
for this parameter is 10 seconds to 40 minutes. The default  
time is 1 minute.  
System Pump Anti-Seize Delay  
If the boiler pump does not run for 24 hours, it will be turned  
on briefly to prevent it from seizing. The length of time it runs  
is determined by the System Pump Anti-Seize Delay parameter.  
The range of this setting is 0 seconds to 50 minutes. The default  
setting is 20 seconds.  
Boiler Pump Anti-Seize Delay  
If the boiler pump does not run for 24 hours, it will be  
turned on briefly to prevent it from seizing. The length of  
time it runs is determined by the Boiler Pump Anti-Seize  
Delay parameter. The range of this setting is 0 seconds to 50  
minutes. The default setting is 20 seconds.  
BMS  
BMS Type  
Boiler Pump Minimum Voltage  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus, the 0 - 10V signal can be interpreted  
as either a modulation command or a set point. When the BMS  
Type parameter is set to POWER, the 0 - 10V signal will control  
the modulation. When set to SETPOINT, the 0 - 10V signal  
will control the SH set point. The default setting is SETPOINT.  
The speed of the boiler pump can be controlled by the  
SMART SYSTEM control in order to maintain a minimum  
T through the heat exchanger. Thus, as the firing rate  
decreases, the speed of the boiler pump can decrease as well.  
The SMART SYSTEM control outputs a 0 - 10V signal to the  
boiler pump to control its speed. The Boiler Pump Minimum  
Voltage parameter determines the minimum voltage given to  
the boiler pump, thereby setting its minimum speed. The  
range of this setting is 2.5V to 10V. The default setting is  
3.5V.  
Volts at Minimum  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus, the Volts at Minimum parameter  
should be set to the minimum voltage signal sent to the  
SMART SYSTEM control. The range of this parameter is 0.0V  
to the Volts at Maximum value. The default setting is 2.0V.  
System Pump Type  
The system pump can be programmed to operate in response  
to any of the Room Thermostat inputs, or to run continuously  
until the boiler goes into Outdoor Shutdown. To program  
the system pump to operate only with a space heating call  
for heat, set the System Pump Type parameter to CFH. To  
program the system pump to run continuously until outdoor  
shutdown starts, set the System Pump Type parameter to  
WWSD. The default setting is CFH.  
Volts at Maximum  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus, the Volts at Maximum parameter  
should be set to the maximum voltage signal sent to the  
SMART SYSTEM control. The range of this parameter is the  
Volts at Minimum value to 10.0V. The default value is 10.0V.  
Rate at Minimum Volts  
DHW Forces Sys Pump  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Type is programmed as  
POWER, the modulation percentage represented by the Volts  
at Minimum parameter is set by the Rate at Minimum Volts  
parameter. The minimum value is 0% and the maximum is  
the Rate at Maximum Volts setting. The default value is 20%.  
When the indirect DHW tank is connected as a zone on the  
primary loop, the DHW Forces Sys Pump parameter tells the  
system pump if it must run when there is a DHW demand.  
To have the system pump constantly running during a DHW  
demand, set the DHW Forces Sys Pump parameter to YES (the  
parameter DHW Blocks Sys Pump must be set to NO). If this  
parameter and the DHW Blocks Sys Pump parameter are both  
set to NO, the system pump operation will be based strictly on  
the System Pump Type parameter setting. The default setting  
of this parameter is YES.  
Rate at Maximum Volts  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Type is programmed as  
POWER, the modulation percentage represented by the Volts  
at Maximum parameter is set by the Rate at Maximum Volts  
parameter. The minimum value is the Rate at Minimum Volts  
setting and the maximum is 100%. The default value is 100%.  
25  
Service Manual  
1 Service  
Set Point at Minimum Volts  
Service Notification Cycles  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Type is programmed as  
SETPOINT, the set point represented by the Volts at Minimum  
parameter is set by the Set Point at Maximum Volts parameter.  
The minimum value is 32°F (0°C) and the maximum is the  
Set Point at Maximum Volts setting. The default value is 70°F  
(21°C).  
When the boiler control determines that a scheduled  
service is due based on the number of boiler cycles, the  
boiler display will alternate the standard boiler display  
text with the message SERVICE DUE every 5 seconds.  
This parameter is adjustable by the installer by accessing  
the Service Notification Cycles parameter. The range for  
this parameter is 0 cycles to 100,000 cycles. The default is  
50,000 cycles.  
Set Point at Maximum Volts  
Reset Maintenance Reminder  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Type is programmed as  
SETPOINT, the set point represented by the Volts at Maximum  
parameter is set by the Set Point at Maximum Volts parameter.  
The minimum value is the Set Point at Minimum Volts setting  
and the maximum is 190°F (88°C). The default value is 180°F  
(82°C).  
Once servicing has been completed, the service notification  
counter should be reset. This parameter can be reset by  
the installer by accessing the Reset Maintenance Reminder  
parameter. Once accessed, press the RESET key to reset the  
service notification counter.  
Service Name and Phone Number  
On Volts  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Thermostat Input is set  
to INACTIVE, the On Volts parameter determines the 0 - 10V  
BMS input voltage at which the boiler is enabled. The minimum  
value is 0.5V and the maximum is 10.0V. The default value is  
2.0V.  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
When a Maintenance Reminder timer or counter has  
expired, a Maintenance Reminder screen will appear on the  
display. By programming the installer’s name and phone  
number, this information will appear on the Maintenance  
Reminder Screen at that time. This can be programmed by  
accessing the Service Name and Phone Number parameter.  
When selected, another menu will appear with PHONE  
and NAME.  
Off Differential Volts  
When programmed for BMS control through the 0 - 10V BMS  
input or through ModBus and the BMS Thermostat Input is set  
to INACTIVE, the Off Differential Volts parameter determines  
how far below the On Volts setting the 0 - 10V BMS input  
voltage must be in order to disable the boiler. The minimum  
value is 0.2V and the maximum is the On Volts setting. The  
default value is 1.0V.  
1. Rotate the NAVIGATION dial to point to the  
name/phone number to program and press the  
NAVIGATION dial. The screen will now display the  
selected item (either PHONE or NAME).  
Service Notification  
Service Notification in Months  
2. Press the NAVIGATION dial again. A cursor will  
appear at the bottom of the screen. By rotating the  
NAVIGATION dial, various numbers and characters  
will appear. When the desired number/character is  
found, press the NAVIGATION dial. The cursor will  
move to the next position.  
When the boiler control determines that a scheduled service is  
due based on days of installation, the boiler display will alternate  
the standard boiler display text with the message SERVICE DUE  
every 5 seconds. This parameter is adjustable by the installer by  
accessing the Service Notification in Months parameter. The time  
range for this parameter is 0 months to 100 months. The default  
time is 12 months.  
3. Repeat this procedure until the entire message is  
entered. If you make a mistake and wish to back up  
one character, rotate the NAVIGATION dial until  
the back arrow () character is displayed and press the  
NAVIGATION dial.  
This feature has been disabled by the manufacturer. To enable  
this feature change parameter K1 to the desired time range.  
4. When finished, press the RIGHT SELECT [SAVE] key  
to return to the previous menu.  
Service Notification Running Time  
When the boiler control determines that a scheduled service is  
due based on the hours of actual operation, the boiler display  
will turn yellow and a new status screen will appear informing  
the installer that maintenance is required. This parameter is  
adjustable by the installer by accessing the Service Notification  
Running Time parameter. The time range for this parameter is  
0 hours to 17,500 hours. The default time is 8,760 hours.  
26  
Service Manual  
2 Maintenance  
Maintenance and annual startup  
Table 2-1 Service and Maintenance Schedules  
Owner maintenance  
Service technician  
(see the Knight XL User’s Information Manual for  
instructions)  
(see the following pages for instructions)  
General:  
• Address reported problems  
• Check boiler area  
• Inspect interior; clean and vacuum if  
necessary;  
• Check pressure/temperature  
gauge  
Daily  
• Clean condensate trap and fill with fresh  
water  
• Check for leaks (water, gas, flue,  
condensate)  
• Verify flue and air lines in good condition  
and sealed tight  
• Check vent piping  
• Check air piping  
• Check system water pressure/system  
piping/expansion tank  
Monthly  
• Check air and vent termination  
screens  
• Check control settings  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check relief valve  
• Check condensate drain system  
• Check air vents  
• Check wiring and connections  
Perform start-up checkout and  
performance verification per Section 10  
in the Knight XL Installation and  
Operation Manual.  
Test low water cutoff (if used)  
Periodically  
• Reset button (low water cutoff)  
• Flame inspection (stable, uniform)  
• Flame signal (at least 10 microamps at  
high fire)  
• Check boiler piping (gas and  
water) for leaks  
Every  
6 months  
• Clean the heat exchanger if flue  
temperature is more than 54°F (30°C)  
above return water temperature.  
• Operate relief valve  
If combustion or performance  
indicate need:  
Shut boiler down (unless boiler  
used for domestic hot water)  
End  
of season  
• Clean heat exchanger  
• Remove and clean burner using  
compressed air only  
months  
• Clean the blower wheel  
27  
Service Manual  
2 Maintenance  
Follow the Service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 2-1 and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except  
as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical  
shock, causing severe personal injury or death.  
ƽ WARNING  
Address reported problems  
Figure 2-1 Condensate Trap  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
RETAINING  
SCREW  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
Inspect boiler area  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of the Knight XL Installation and  
Operation Manual. If any of these are present in the  
boiler intake air vicinity, they must be removed. If  
they cannot be removed, reinstall the air and vent lines  
per this manual and the Knight XL Installation and  
Operation Manual.  
CONDENSATE FROM  
HEAT EXCHANGER  
TO FLOOR  
DRAIN  
Inspect boiler interior  
The condensate trap must be filled with  
water during all times of boiler operation  
to avoid flue gas emission from the  
condensate drain line. Failure to fill the  
trap could result in severe personal injury  
or death.  
1. Remove the front access cover and inspect the interior of  
the boiler.  
ƽ WARNING  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
Clean condensate trap  
Check all piping for leaks  
1. Inspect the condensate drain line, condensate PVC  
fittings, and condensate trap.  
Eliminate all system or boiler leaks.  
ƽ WARNING  
Continual fresh makeup water will  
reduce boiler life. Minerals can build  
up in sections, reducing heat transfer,  
overheating heat exchanger, and causing  
heat exchanger failure. Leaking water may  
also cause severe property damage.  
2. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 2-1).  
3. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 2-1).  
4. Remove any sediment in the trap.  
1. Inspect all water and gas piping and verify to be leak free.  
5. Fill with fresh water until the water begins to pour out of  
the drain.  
2. Look for signs of leaking lines and correct any problems  
found.  
6. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
3. Check gas line using the procedure found in Section 7  
-
Gas Connections of the Knight XL Installation and  
Operation Manual.  
7. Replace the retaining screw.  
28  
Service Manual  
2 Maintenance  
(continued)  
Safety relief valves should be re-inspected  
AT LEAST ONCE EVERY THREE YEARS,  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions  
may corrode the valve or its components  
over time, rendering the valve inoperative.  
Such conditions are not detectable unless  
the valve and its components are physically  
removed and inspected. This inspection  
must only be conducted by a plumbing  
contractor or authorized inspection  
agency – not by the owner. Failure to  
re-inspect the boiler relief valve as directed  
could result in unsafe pressure buildup,  
which can result in severe personal injury,  
death, or substantial property damage.  
Flue vent system and air piping  
ƽ WARNING  
1. Visually inspect the entire flue gas venting system and air  
piping for blockage, deterioration or leakage. Repair any  
joints that show signs of leakage. Verify that air inlet pipe  
is connected and properly sealed.  
2. Verify that boiler vent discharge and air intake are clean  
and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in  
severe personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi (82.7 kPa)).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
Following installation, the valve lever  
must be operated AT LEAST ONCE  
A YEAR to ensure that waterways are  
clear. Certain naturally occurring  
mineral deposits may adhere to the valve,  
rendering it inoperative. When manually  
operating the lever, water will discharge  
and precautions must be taken to avoid  
contact with hot water and to avoid water  
damage. Before operating lever, check  
to see that a discharge line is connected  
to this valve directing the flow of hot  
water from the valve to a proper place of  
disposal. Otherwise severe personal injury  
may result. If no water flows, valve is  
inoperative. Shut down the boiler until a  
new relief valve has been installed.  
ƽ WARNING  
4. Inspect automatic air vents and air separators. Remove  
air vent caps and briefly press push valve to flush vent.  
Replace caps. Make sure vents do not leak. Replace any  
leaking vents.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed or diaphragm or bladder  
type. See Section 6 - Hydronic Piping of the Knight XL  
Installation and Operation Manual for suggested best  
location of expansion tanks and air eliminators.  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief  
valve. Ensure that the reason for relief valve weeping is  
the valve and not over-pressurization of the system due  
to expansion tank waterlogging or undersizing.  
Check boiler relief valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 6 - Hydronic Piping of the  
Knight XL Installation and Operation Manual before  
proceeding further.  
29  
Service Manual  
2 Maintenance  
Inspect ignition and flame sense  
electrodes  
Figure 2-2 Burner Assembly - Model 400  
1. Remove the ignition and flame sense electrodes from the  
boiler heat exchanger access cover.  
2. Remove any deposits accumulated on the ignition/flame  
sense electrode using sandpaper. If the electrodes cannot  
be cleaned satisfactorily, replace with new ones.  
AIR / GAS ARM  
3. Replace ignition/flame sense electrode, making sure  
gasket is in good condition and correctly positioned.  
Check ignition ground wiring  
1. Inspect boiler ground wire from the heat exchanger  
BURNER  
GASKET  
access cover to ground terminal strip.  
2. Verify all wiring is in good condition and securely  
attached.  
SCREWS  
(QTY. 5)  
3. Check ground continuity of wiring using continuity  
meter.  
Figure 2-3 Burner Assembly - Model 501  
4. Replace ground wires if ground continuity is not  
satisfactory.  
Check all boiler wiring  
1. Inspect all boiler wiring, making sure wires are in good  
AIR / GAS ARM  
condition and securely attached.  
Check control settings  
1. Set the SMART SYSTEM control module display to  
Parameter Mode and check all settings. See Section 1 of  
this manual. Adjust settings if necessary. See Section 1 of  
this manual for adjustment procedures.  
BURNER  
GASKET  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
SCREWS  
(QTY. 5)  
Perform start-up and checks  
Figure 2-4 Burner Assembly - Models 601 - 801  
1. Start boiler and perform checks and tests specified in  
Section 10 - Start-up of the Knight XL Installation and  
Operation Manual.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
AIR ARM  
Check burner flame  
1. Inspect flame through observation window.  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove the  
burner and clean it thoroughly using a vacuum cleaner  
or compressed air. Do not use compressed air to clean  
burner if performed inside a building.  
BURNER  
GASKET  
SCREWS  
(QTY. 5)  
3. Remove the burner, reference FIG.’s 2-2 thru 2-4.  
4. When replacing the burner, ensure gasket is in good  
condition and positioned correctly (FIG.’s 2-2 thru 2-4).  
30  
Service Manual  
2 Maintenance  
(continued)  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Caution: DO NOT use a metal brush. Re-vacuum  
the heat exchanger.  
Check flame signal  
1. At high fire the flame signal shown on the display should  
be at least 10 microamps.  
8. Finish cleaning using a clean cloth dampened with warm  
water. Rinse out debris with a low pressure water supply.  
2. A lower flame signal may indicate a fouled or damaged  
flame sense electrode. If cleaning the flame sense electrode  
does not improve, ground wiring is in good condition,  
and ground continuity is satisfactory, replace the flame  
sense electrode.  
9. Allow the heat exchanger to thoroughly dry.  
10. Remove the field supplied rear refractory cover from the  
back of the combustion chamber of the heat exchanger and  
reassemble.  
3. See Section 3 - Troubleshooting in this manual for other  
procedures to deal with low flame signal.  
11. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to  
allow water to flow through the water make-up line to the  
boiler.  
Review with owner  
1. Review the Knight XL User’s Information Manual with  
the owner.  
2. Emphasize the need to perform the maintenance schedule  
specified in the Knight XL User’s Information Manual  
(and in this manual as well).  
12. Perform start-up and check-out procedures in the Check  
Flame and Combustion - Section 10 - Startup of the  
Installation and Operation Manual.  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
13. Replace the access cover and restore boiler to operation.  
4. Remind the owner to follow the proper shutdown  
procedure and to schedule an annual start-up at the  
beginning of the next heating season.  
Table 2-2 Heat Exchanger Cleaning Kits  
Kit  
Part  
Component  
Description  
Model  
Cleaning boiler heat exchanger  
Number Number  
For recommended materials; including brush, appropriate  
extension(s), refractory cover, and detailed instructions see  
Table 2-2 - Heat Exchanger Cleaning Kits.  
CTN20005  
Rear Refractory Cover  
Nylon 4" Wheel Brush*  
MSC20083*  
400  
KIT30063  
MSC20084  
3mm Allen Wrench  
1/4" x 24" Drill Extension  
Rear Refractory Cover  
Nylon 4" Wheel Brush*  
1/4" x 12" Drill Extension  
1/4" x 24" Drill Extension  
1. Shut down boiler:  
MSC20086  
CTN20005  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in Section 10 - Startup of the Installation  
and Operation Manual.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
MSC20083*  
KIT30064  
501 - 801  
MSC20085  
MSC20086  
* Do NOT use a metal brush. Only use  
the kit provided brush or an equivalent  
replacement nylon brush.  
ƽ CAUTION  
2. Allow time for the boiler to cool to room temperature if  
it has been firing.  
3. Remove the nuts securing the heat exchanger access cover  
to the heat exchanger and set aside.  
Figure 2-5 Rope Gasket - Heat Exchanger Door  
4. Remove the heat exchanger access cover, burner, and  
gas/air arm assembly.  
ROPE GASKET  
The boiler contains ceramic fiber  
ƽ WARNING  
materials. Use care when handling these  
materials per instructions on page 3 of  
this manual. Failure to comply could  
result in severe personal injury.  
5. Remove the condensate hose from the heat exchanger  
end. Connect a field supplied 3/4” diameter hose to  
a drain pan. Using field supplied means, cover the  
refractory in the back of the combustion chamber of the  
heat exchanger.  
CAUTION: IF GASKET IS DAMAGED  
DO NOT REUSE, THE HEAT EXCHANGER DOOR  
MUST BE REPLACED.  
Rope gasket is intended for sealing combustion  
(FIG. 2-5). If damaged DO NOT reuse, the  
heat exchanger door must be replaced. Consult  
factory for replacement heat exchanger door  
(kit WTR3080 and WTR3086).  
31  
NOTICE  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
Service Manual  
2 Maintenance  
Test low water flow conditions  
9. When the T reaches 60°F, the control module will turn  
off the burner. If the control module shuts down, the test  
was successful.  
This test is to be carried out once the  
NOTICE  
Knight XL boiler is completely piped  
10. Disconnect the jumper wire from the low voltage terminal  
strip connected in Step 2.  
in with adequate gas and water flow.  
Once the test is completed, ensure  
that the isolation valve is opened up to  
allow full water flow.  
11. Completely open the isolation valve on the outlet piping of  
the boiler.  
12. Resume operation.  
Test procedure  
NOTE: This lockout is a soft lockout. Once the T has  
decreased to an acceptable level and there is a call for heat,  
the unit will fire again to meet the demand.  
1. Set the [SH1 SETPOINT:] set point to the max user set  
point (reference Section 10 of the Knight XL Installation  
and Operation Manual). Max user set point will allow  
the boiler to operate without reaching this set point. The  
boiler will require a load large enough to dissipate a large  
portion of the heat it is generating.  
Figure 2-6 Low voltage terminal strip and enable contacts  
LOW VOLTAGE CONNECTION BOARD  
2. Simulate a call for heat by placing a jumper wire across  
the enable contacts #19 and 20 on the low voltage  
terminal strip located at the rear of the unit (FIG. 2-6).  
3. Allow the unit to progress through its normal diagnostics  
and pre-purge programming.  
4. Locate the pinhole button below the RESET button on  
the display board (see page 7). Insert a thin wire (such as  
a paper clip) into the hole and press the button once and  
hold for 5 seconds to place the boiler into Service Mode.  
In Service Mode the boiler will fire at ignition speed and  
will then modulate up to full fire.  
ENABLE  
CONTACTS  
IMG00103  
5. Allow the unit to fire and operate until the temperatures  
stabilize. This occurs when the inlet and outlet  
temperatures are rising together and the Delta T (T)  
is maintained.  
Figure 2-7 Adjust outlet isolation valve  
ADJUST OUTLET  
ISOLATION VALVE  
ONLY  
6. When the unit stabilizes, begin to slowly shut off the  
isolation valve on the outlet piping of the boiler (see  
FIG. 2-7). This will begin to restrict the flow and  
simulate a low flow condition.  
7. While slowly shutting off the isolation valve, refer to the  
Status Screens to watch the behavior of the boiler. These  
screens allow you to monitor the inlet temperature,  
outlet temperature, and T.  
8. When the T reaches 55˚F, the control will attempt to  
modulate the firing rate down to protect it from low flow  
conditions.  
IMG00098  
32  
Service Manual  
3 Troubleshooting  
Label all wires prior to disconnection  
Check control module fuses  
ƽ WARNING  
when servicing controls. Wiring errors  
can cause improper and dangerous  
operation. Always disconnect power  
to the boiler before servicing. Failure  
to comply could result in severe  
personal injury, death, or substantial  
property damage.  
ALWAYS check control module fuses before  
NOTICE  
replacing control module or any major  
components (blower, etc.). If one of these  
fuses is blown, it can prevent the control  
module or other components from operating.  
1. Turn OFF the power to the boiler at the external line  
switch.  
Never jumper (bypass) any device  
except for momentary testing as  
outlined in the Troubleshooting  
chart. Severe personal injury, death,  
or substantial property damage can  
result.  
ƽ WARNING  
2. Remove top access cover.  
3. Remove the control module cover.  
4. Inspect fuses F1, F2, and F3, see FIG 3-1 below.  
Figure 3-1 Control Module Fuses  
Before troubleshooting:  
1. Have the following items:  
a. Voltmeter that can check 120 VAC, 24 VAC, and  
12 VDC.  
b. Continuity checker.  
c. Contact thermometer.  
F3 - .80 AMP FUSE  
24V DC POWER SUPPLY  
2. Check for 120 VAC (minimum 102 VAC to maximum  
132 VAC) to boiler.  
F1 - 5 AMP FUSE  
PUMPS  
F2 - 3.15 AMP FUSE  
BLOWER  
3. Make sure thermostat is calling for heat and contacts  
(including appropriate zone controls) are closed.  
Check for 24 VAC between thermostat wire nuts and  
ground.  
5. The boiler is shipped with three (3) spare fuses in a plastic  
bag attached to the control module cover.  
4. Make sure all external limit controls are installed and  
operating.  
6. If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15  
amps and F1 is 5 amps).  
Check the following:  
Note: Fuses F1, F2, and F3 are all slow blow fuses.  
1. Wire connectors to control module are securely  
plugged in at the module and originating control.  
Do not jumper fuse or replace with any fuse  
ƽ WARNING  
except as specified. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
2. Gas pressures:  
• Maximum: 14 inches w.c. (3.5 kPa) (natural and  
LP) with no flow (lockup) or with boiler on  
• Minimum: 4 inches w.c. (1.0 kPa) (natural),  
8 inches w.c. (2.0 kPa) (LP) with gas flowing (verify  
during boiler startup)  
7. Install control module cover and top access cover after fuse  
inspection.  
8. Restore power to the boiler at the external line switch and  
verify boiler operation (Section 10 - Start-up in the Knight  
XL Installation and Operation Manual) after completing  
boiler service.  
33  
Service Manual  
3 Troubleshooting  
Table 3-1 Troubleshooting Chart - No Display  
FAULT  
CAUSE  
CORRECTIVE ACTION  
• Check external line switch, fuse, or breaker.  
- No 120 vac supplied to unit.  
• Check position of ON/OFF switch. Turn switch to the  
ON position.  
• Check 120 vac through the ON/OFF switch.  
• Check wiring harness connection between display  
board and main control board. Connect  
harness at both points.  
No Display  
- No voltage through the switch.  
- Bad display board.  
• Replace switch.  
• Replace board.  
- Bad main control board.  
• Replace the main control board.  
• Replace fuse F3 on the main control board, see  
page 33 of this manual.  
- Blown fuse.  
- Main control board temperature set point  
satisfied.  
• Review temperature setting.  
- Remote thermostat satisfied.  
• Review remote thermostat setting.  
- Outside air temperature above Warm • Check location of outside air sensor.  
Check  
No Burner  
Operation  
Weather Shutdown (WWSD) set point for  
main control board.  
resistance of outdoor air sensor and compare to Table  
3-2B on page 35 of this manual.  
• Consult display for specific fault. Refer to fault  
descriptions on page 37 of this manual for corrective  
actions.  
- Unit locked out on fault.  
- Unit in Shutdown Mode.  
• Take unit out of Shutdown Mode.  
• Check ramp delay parameter settings. Optional PC  
software required.  
- Ramp delay active.  
• Turn ramp delay feature off. See page 22 of this  
manual for instructions on how to turn this feature off.  
Unit Does  
• Check BMS parameter settings.  
software required.  
Optional PC  
Not Modulate - Boiler controlled by BMS.  
Above 50%  
• Verify that the flue sensor is located in the flue outlet.  
• Check wiring connections at the flue sensor.  
- Flue sensor open.  
• Check the resistance of the flue sensor and compare  
to Table 3-2D on page 35 of this manual.  
34  
Service Manual  
3 Troubleshooting  
(continued)  
Checking temperature sensors  
The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The  
following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the  
sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor  
It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These  
devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL  
Installation and Operation Manual for correct terminal location.  
Table 3-2A - Inlet Water/System Sensor Resistance vs.  
Table 3-2B - Outdoor Air Sensor Resistance vs.  
Temperature  
Temperature  
Temperature Resistance Temperature Resistance  
Temperature Resistance Temperature Resistance  
-50  
-40  
-30  
-20  
10  
490,813  
336,606  
234,196  
165,180  
118,018  
85,362  
20  
30  
40  
50  
60  
70  
80  
46,218  
34,558  
26,099  
19,900  
15,311  
11,883  
9,299  
50  
68  
18,780  
12,263  
8,194  
5,592  
3,893  
2,760  
158  
176  
194  
212  
1,990  
1,458  
1,084  
817  
86  
104  
122  
140  
0
10  
62,465  
Table 3-2C - Outlet Water Sensor Resistance vs. Temperature  
S1a  
S1b  
(Wire Color - R/BK and Y)  
(Wire Color - G and Y)  
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance  
50  
68  
19,553  
12,690  
8,406  
5,715  
3,958  
2,786  
158  
176  
194  
212  
2,004  
1,464  
1,084  
816  
50  
68  
40,030  
25,030  
16,090  
10,610  
7,166  
158  
176  
194  
212  
3,478  
2,492  
1,816  
1,344  
86  
86  
104  
122  
140  
104  
122  
140  
4,943  
Table 3-2D - Flue Sensor Resistance vs. Temperature  
S3a  
S3b  
(Wire Color - W/B and Y)  
(Wire Color - PR and Y)  
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance  
50  
68  
40,030  
25,030  
16,090  
10,610  
7,166  
158  
176  
194  
212  
3,478  
2,492  
1,816  
1,344  
50  
68  
258,500  
125,500  
80,220  
52,590  
35,270  
24,160  
158  
176  
194  
212  
16,870  
12,000  
8,674  
86  
86  
104  
122  
140  
104  
122  
140  
6,369  
4,943  
35  
Service Manual  
3 Troubleshooting  
Table 3-3 Troubleshooting Chart - Noisy System  
FAULT  
CAUSE  
CORRECTIVE ACTION  
-
Supply gas problem. Natural gas • Refer to Section 7 - Gas Connections of the Knight  
pressures should be between 4 inches XL Installation and Operation Manual for detailed  
w.c. and 14 inches w.c. LP gas pressures information concerning the gas supply.  
should be between 8 inches w.c. and 14  
inches w.c.  
- Gas/air mixture problem.  
• Refer to the Gas Valve Adjustment Procedure on  
page 47 of this manual for the proper gas valve setting.  
Verify that the vent/air intake lengths do not exceed the  
maximum listed in the General Venting section of the  
Knight XL Installation and Operation Manual.  
- Dirty/damaged burner.  
• Refer to page 31 in this manual for the burner removal  
and inspection procedure. Clean or replace the burner  
as necessary.  
Noisy  
Operation  
- Low water flow through the heat exchanger. • Refer to Section  
6
-
Hydronic Piping of the  
Knight XL Installation and Operation Manual for  
minimum flow rates. Verify that the boiler is piped in a  
primary/secondary fashion and that the boiler and  
system pump are running on a call for heat.  
- Air in the piping system.  
• Properly purge all air from the piping system.  
• Verify system pressure is a minimum of 12 psi.  
- Low system water pressure.  
- Blown fuse.  
No Pump  
Operation -  
Boiler Pump  
System Pump  
or  
• Replace fuse F1 on the control board, see page 33 of  
this manual.  
Note: Make sure pump amperage does not exceed  
1.8 amps.  
DHW Pump  
• Replace pump.  
- Faulty pump.  
- Internal fault on control board.  
• Replace main control board.  
- System pressure exceeds relief valve • Lower the system pressure below the 30 psi rating of  
setting.  
the supplied relief valve or replace the standard relief  
valve with a higher rated valve up to the maximum  
pressure of the heat exchanger.  
Relief Valve  
Opening  
• Improperly sized expansion tank.  
36  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Reset the pressure switches.  
• Measure the supply gas pressure to determine cause  
of failure. Natural gas pressures should be between  
4
-
14 inches w.c. and LP gas pressures  
should be between 8 - 14 inches w.c.  
- Either the optional manual reset low gas  
pressure switch or the optional manual reset • Refer to Section 7 - Gas Connections of the Knight  
Gas Pressure SW  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
high gas pressure switch tripped.  
XL Installation and Operation Manual for detailed  
information concerning the gas supply.  
• Correct the supply gas pressure if necessary.  
• Check for a loose or misplaced jumper if pressure  
switches are not installed.  
• Check for a loose or misplaced jumper on the Low  
Voltage Connection Board.  
- The gas pressure switch contacts on the  
Low Voltage Connection Board are open.  
• Check for the addition of a device wired across the  
gas pressure switch terminals on the Low Voltage  
Connection Board.  
• Check boiler pump operation on a call for heat.  
• Check for closed valves or obstructions in the boiler  
piping.  
Flow Switch/  
LWCO  
- Either the optional flow switch or the optional  
low water cutoff is not making.  
• Verify system is full of water and all air has been  
purged from the system.  
(will require a manual  
reset once condition has  
been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• Check for loose or misplaced jumpers if flow switch or  
LWCO is not installed.  
• Replace fuse F3 on the control board, see page 33  
of this manual.  
- Blown fuse.  
• Check condensate tube from unit to floor drain for  
proper installation and obstructions.  
Blocked Drain SW  
(will require a manual  
reset once condition has  
been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• Inspect condensate trap for blockage. Clean if  
necessary.  
The blocked drain switch has detected  
excessive condensate build up inside the  
unit.  
• Check for loose wiring connection at wire harness  
plug.  
• Bad blocked drain switch. Replace switch.  
37  
Service Manual  
3 Troubleshooting  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
APS:  
• Check the wiring connections to switch. Wires should  
be connected to the common and normally closed  
terminals.  
• Air intake lengths exceed the maximum allowed  
lengths. Refer to Section 3 - General Venting of the  
Knight XL Installation and Operation Manual for  
proper lengths.  
• Check for obstruction or blockage in the air  
intake pipes or at terminations.  
APS / HEX  
Temp Sw  
• Check reference hoses connected to the air pressure  
switch for blockage or obstruction.  
Open  
• Inspect the burner. Reference page 31 of this manual  
for removal and cleaning procedures. Replace if  
necessary.  
Either the air pressure switch contacts are  
open, or the O-temp heat exchanger switch  
has opened.  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the SMART SYSTEM  
display to reset.)  
• Inspect the heat exchanger. Reference page 32 of  
this manual for removal and cleaning procedures.  
Replace if necessary.  
• Faulty air pressure switch. Replace switch.  
O-TEMP HEX SWITCH  
• Inspect the back of the inner combustion chamber at  
burner level for refractory breakdown / missing.  
Replace heat exchanger if refractory is broken and unit  
has fired.  
• Check continuity across two contacts. Wires should be  
connected at both poles of the normally closed switch.  
• Faulty O-Temp HEX Switch. Replace switch.  
• The control board will release the call for heat after a  
set time period.  
The main control board has received a call  
for heat too quickly after the previous call for  
heat has ended.  
Anti-cycling  
• The control board will release the call for heat if the  
outlet temperature drops too quickly.  
• Inspect spark electrode and associated wiring for  
damage and connection. Reference page 31 of this  
manual for removal and cleaning procedures.  
Replace if necessary.  
Flame Fail Ign  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the SMART SYSTEM  
display to reset.)  
• Check for proper electrical grounding of the unit.  
The unit has failed to prove main burner  
ignition after four (4) attempts.  
• Check incoming supply gas pressure. Natural gas  
pressures should be between 4 - 14 inches w.c. and  
LP gas pressures should be between 8 - 14 inches w.c.  
Refer to Section 7 - Gas Connections of the Knight  
XL Installation and Operation Manual for detailed  
information concerning the gas supply.  
38  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
The unit has failed to prove main burner • Verify that the plastic hose from the gas valve to the air  
ignition after four (4) attempts.  
inlet is connected and is not damaged.  
• Verify that the vent/air intake pipes are correctly  
installed and that there are no obstructions.  
• Check for 24 vac to the gas valve at the 2-pin  
connection on the side of the main control board during  
the ignition attempt. If no voltage is present, replace  
the main control board.  
• If 24 vac is present at the main control board, check  
the wiring between the main control board and the gas  
valve. Replace the wiring if necessary. Do not  
disconnect the wiring from the gas valve and attempt to  
measure voltage at that point. The main control board  
can detect if the gas valve is not connected and will  
display the Gas Valve or Gas Valve Fail fault.  
Flame Fail Ign  
(cont’d)  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the SMART SYSTEM  
display to reset.)  
• If 24 vac is present, check the outlet of the valve to  
ensure the valve is flowing gas. With a manometer  
connected to the outlet tap of the gas valve, when the  
unit is in the prepurge period, there should be a  
negative pressure present.  
When the valve is  
energized a change in pressure should occur. If the  
pressure change does not occur, the gas valve is not  
opening. Replace the gas valve.  
• Inspect flame sensor and associated wiring.  
Reference page 31 of this manual for removal and  
cleaning procedures. Replace if necessary.  
• Inspect and clean the heat exchanger as necessary.  
Reference page 32 of this manual for cleaning  
procedures.  
• Inspect the burner. Reference page 31 of this manual  
for removal and cleaning procedures. Replace if  
necessary.  
• Replace the main control board.  
Flame Sequence  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the SMART SYSTEM  
display to reset.)  
• Check supply voltage for proper polarity.  
• Check external wiring for voltage feedback.  
• Check the flame rod and make sure it is clean.  
• Check the internal wiring for bad connections.  
• Replace main control board.  
The flame detector circuit is seeing a flame  
signal while no flame is present.  
39  
Service Manual  
3 Troubleshooting  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Adjust the set point of the auto reset limit to a higher  
setting up to a maximum of 200°F. Reference the  
Knight XL Installation and Operation Manual for  
adjusting procedures.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
Knight XL Installation and Operation Manual  
for the proper piping methods for the Knight XL boiler.  
• Check 120 vac to boiler pump motor on a call for  
heat. If voltage is not present, check wiring back to  
the main control board.  
The outlet water temperature has exceeded  
the setting of the automatic reset high limit.  
• Replace the main control board if necessary.  
Outlet ARHL  
• If 120 vac is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
• If the system pump is a variable speed pump, ensure  
that the system flow is not less than the boiler flow.  
• If operating on something other than an outlet sensor,  
check temperature setting of the main control board.  
• If the optional manual reset high limit has tripped,  
check setting of the device.  
• Check resistance of water sensors and compare to  
Table 3-2A on page 35 of this manual. Replace  
sensor if necessary.  
• Replace high limit.  
• Adjust the set point of the manual reset limit to a higher  
setting up to a maximum of 210°F. Reference the  
Knight XL Installation and Operation Manual for  
adjusting procedures.  
Outlet MRHL  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET  
button on the SMART  
SYSTEM display to  
reset.)  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
The outlet water temperature has exceeded  
the setting of the manual reset high limit.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
Knight XL Installation and Operation Manual  
for the proper piping methods for the Knight XL boiler.  
• Check 120 vac to boiler pump motor on a call for  
heat. If voltage is not present, check wiring back to  
the main control board.  
40  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Replace the main control board if necessary.  
• If 120 vac is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
Outlet MRHL  
(cont’d)  
• If the system pump is a variable speed pump, ensure  
that the system flow is not less than the boiler flow.  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• If operating on something other than an outlet sensor,  
check temperature setting of the main control board.  
The outlet water temperature has exceeded  
the setting of the manual reset high limit.  
• If the optional manual reset high limit has tripped,  
check setting of the device.  
• Check resistance of water sensors and compare to  
Table 3-2A on page 35 of this manual. Replace  
sensor if necessary.  
• Replace high limit.  
• Vent/air intake lengths exceed the maximum allowed  
lengths. Refer to Section 3 - General Venting of the  
Knight XL Installation and Operation Manual for  
proper lengths.  
Fan Low/High  
OR  
• Check for obstruction or blockage in the vent/air  
intake pipes or at terminations.  
Fan Speed Low/ The actual fan RPM is 30% lower than what  
is being called for.  
High  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• Check the wiring connections at the fan and at the  
main control board.  
• Replace the fan.  
• Replace the main control board.  
• Replace fuse F2 on the control board, see page 33  
of this manual.  
Blown fuse.  
• Check wiring harness connection at the gas valve and  
at the main control board.  
GV/Relay  
Fail  
(will require a manual  
• Replace the gas valve wire harness.  
• Replace the gas valve.  
The main control board did not detect the  
gas valve.  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• Replace the main control board.  
• Check the sensors and their associated wiring.  
Repair or replace the sensor or wiring if damaged.  
Sensor Open  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
Either the inlet water or outlet water • Measure the resistance of the sensors and compare  
temperature sensor has been disconnected.  
the resistance to the tables on page 35 of this  
manual.  
• Replace the sensor if necessary.  
41  
Service Manual  
3 Troubleshooting  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Check the sensors and their associated wiring.  
Repair or replace the sensor or wiring if damaged.  
Sensor Shorted  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
Either the inlet water or outlet water • Measure the resistance of the sensors and compare  
temperature sensor has been shorted.  
the resistance to the tables on page 35 of this  
manual.  
SYSTEM display to reset.)  
• Replace the sensor if necessary.  
Louver Proving  
Sw  
• Check function of remote devices.  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
SYSTEM display to reset.)  
An optional remote proving switch is not  
making.  
• Check for loose or misplaced jumper if auxiliary  
proving switch is not installed.  
• Check wiring to sensor.  
connected and not damaged. Reconnect / repair  
wiring if necessary.  
Make sure wiring is  
Inlet Sensor  
Fault  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
SYSTEM display to reset.)  
The control reads the inlet sensor as open  
or shorted.  
• Measure the resistance of the sensor and compare to  
the resistance in Table 3-2A on page 35 of this manual.  
Replace sensor if necessary.  
• Replace control module.  
• Check wiring to sensor.  
connected and not damaged. Reconnect / repair  
wiring if necessary.  
Make sure wiring is  
Outlet Sensor  
Fault  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
SYSTEM display to reset.)  
The control reads the inlet sensor as open  
or shorted.  
• Measure the resistance of the sensor and compare to  
the resistance in Table 3-2C on page 35 of this manual.  
Replace sensor if necessary.  
• Replace control module.  
• Check wiring to sensor.  
Make sure wiring is  
connected and not damaged. Reconnect / repair  
wiring if necessary.  
Outlet Temp Diff  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
• Measure the resistance of the sensor and compare to  
the resistance in Table 3-2C on page 35 of this manual.  
Replace sensor if necessary.  
The control module reads an excessive  
temperature difference between the two  
sensors.  
• Restore control parameter defaults from optional PC  
software.  
SYSTEM display to reset.)  
• Replace control module.  
42  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Check wiring to sensor. Make sure wiring is  
connected and not damaged. Reconnect / repair  
wiring if necessary.  
Flue Sensor Fault  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
The control reads the flue sensor as open  
or shorted.  
• Measure the resistance of the sensor and compare  
to the resistance in Table 3-2D on page 35 of this  
manual. Replace the sensor if necessary.  
SYSTEM display to reset.)  
• Replace control module.  
• Check wiring to sensor. Make sure wiring is  
connected and not damaged. Reconnect / repair  
wiring if necessary.  
Flue Temp Diff  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
• Measure the resistance of the sensor and compare to  
the resistance in Table 3-2D on page 35 of this  
manual. Replace sensor if necessary.  
The control module reads an excessive  
temperature difference between the two  
sensors.  
• Restore control parameter defaults from optional PC  
software.  
SYSTEM display to reset.)  
• Replace control module.  
• Inspect the heat exchanger. Reference page 32 of  
this manual for the procedure on how to clean the flue  
side of the heat exchanger.  
Flue Temp Limit  
(will require a manual reset  
once the condition has been  
corrected. Press the RESET  
button on the SMART  
• Inspect the flue sensor and associated wiring.  
Measure the resistance of the flue sensor and  
compare to Table 3-2D on page 35 of this manual.  
Replace the sensor if necessary.  
The stack temperature has exceeded the  
Flue Temp Limit set parameters.  
SYSTEM display to reset.)  
• Verify that the vent/air intake pipes are properly  
installed and that there are no obstructions.  
• Replace the main control board.  
• Restore the parameter defaults from the optional PC  
software.  
The control module has detected parameter  
settings that are out of range.  
Fatal Error  
• Replace control module.  
A lockout occurs at the same time as a  
power outage.  
• Reset control module.  
Memory Error  
43  
Service Manual  
3 Troubleshooting  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Inspect the heat exchanger. Reference page 32 of  
this manual for the procedure on how to clean the flue  
side of the heat exchanger.  
• Inspect the flue sensor and associated wiring.  
Measure the resistance of the flue sensor and  
compare to Table 3-2D on page 35 of this manual.  
Replace the sensor if necessary.  
The stack temperature has exceeded the set  
parameters for the boiler.  
Flue Temp High  
• Verify that the vent/air intake pipes are properly  
installed and that there are no obstructions.  
• Replace the main control board.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
Knight XL Installation and Operation Manual  
for the proper piping methods for the Knight XL boiler.  
• Check for 120 vac to the boiler pump motor on a call  
for heat. If voltage is not present, check the wiring  
back to the main control board. Replace the main  
control board if necessary.  
Delta T High  
The temperature rise across the heat  
exchanger has exceeded the set parameters  
for the boiler.  
• If 120 vac is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
• Verify that the boiler pump is set to the proper speed  
or that the pump is the proper size. Reference  
Section  
6
-
Hydronic Piping of the Knight  
XL Installation and Operation Manual for boiler  
pump specifications.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
Knight XL Installation and Operation Manual  
for the proper piping methods for the Knight XL boiler.  
• Check for 120 vac to the boiler pump motor on a call  
for heat. If voltage is not present, check wiring back  
to the main control board. Replace the main control  
board if necessary.  
Outlet Temp  
High  
Outlet water temperature has exceeded the  
maximum outlet water temperature.  
• If 120 vac is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
• Verify that the boiler pump is set to the proper speed  
or that the boiler pump is the proper size. Reference  
Section 6 - Hydronic Piping of the Knight XL  
Installation and Operation Manual for boiler pump  
specifications.  
• Replace the main control board.  
44  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Check set point of the external control.  
• Check the wiring between the external control and the  
unit.  
Rem Ctrl Flt  
External control is cycling too often.  
• Replace the control.  
Parameters  
Progr  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
SMART SYSTEM display  
to reset.)  
• Press the ENTER/RESET button on the SMART  
SYSTEM display panel.  
After downloading parameters from a laptop,  
the main control board must be reset.  
• Establish a heating load to remove the heat from the  
boiler loop.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
Knight  
XL  
Installation  
and  
Operation  
Manual for the proper piping methods for the Knight  
XL boiler.  
While the unit is in Service Mode, the outlet  
temperature has exceeded 185°F.  
• Check 120 vac to the boiler pump motor on a call for  
heat. If voltage is not present, check the wiring back  
to the main control board. Replace the main control  
board if necessary.  
Service Blk  
• If 120 vac is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
• Verify that the boiler pump is set to the proper speed  
or that the boiler pump is the proper size. Reference  
Section  
6
-
Hydronic Piping of the Knight  
XL Installation and Operation Manual for boiler  
pump specifications.  
• Check 120 vac supply to the transformer.  
• Check wiring connections at the low voltage  
terminal strip.  
120 vac input to the main control board has  
dropped below 80 vac.  
Low 24 vac  
• Check the wire size/length to remote devices.  
• Replace the transformer.  
The main control board has detected an  
internal fault.  
• Replace the main control board.  
• Replace the main control board.  
Watch Dog Error  
The main control board has detected an  
internal fault.  
Write EEProm  
The main control board has detected an  
internal fault.  
• Replace the main control board.  
CRC Parameters  
The main control board has detected an  
internal fault.  
• Replace the main control board.  
No Error Stored  
45  
Service Manual  
3 Troubleshooting  
Combustion Analysis Procedure  
Table 3-5 Flue Products  
Natural Gas  
CO2 O2  
8.0% - 10% 3.0% - 6.5% 9.0% - 11%  
1. Turn the main power off to the boiler by placing the “On/  
Off” switch in the OFF position.  
Propane  
CO2  
O2  
2. Remove the flue temperature sensor from the flue pipe  
connection. Note: Combustion measurements will be  
made at this point.  
4.1% - 6.9%  
8. Once the combustion analysis is complete, test the safety  
shutoff device by turning the manual shutoff valve to the  
OFF position and ensuring that the boiler shuts down  
and registers an alarm. Open the manual shutoff valve,  
reset the control, and return to Service Mode.  
3. Turn the main power on to the boiler by placing the  
“On/Off” switch in the ON position.  
4. Place the boiler into the active position by pressing the  
RIGHT SELECT [ON] key (see page 7).  
9. Turn the main power off to the boiler and replace the flue  
temperature sensor into the flue pipe connection.  
5. Locate the pinhole button below the RESET button on  
the display board (see page 7). Insert a thin wire (such as  
a paper clip) into the hole and press the button once and  
hold for 5 seconds to place the boiler into Service Mode.  
In Service Mode the boiler will fire at ignition speed and  
will then modulate up to full fire.  
10. Place the boiler back into normal operation.  
You must replace the flue gas temperature  
ƽ WARNING  
sensor to prevent flue gas spillage into  
the room. Failure to comply could result  
in severe personal injury, death, or  
substantial property damage.  
6. Remove the flue temperature sensor. Insert the probe  
from a combustion analyzer into the hole left by the  
removal of the flue temperature sensor.  
7. Once the boiler has modulated up to full fire, measure  
the combustion. The values should be in the range listed  
in Table 3-5 above. The CO levels should be less than  
150 ppm for a properly installed unit.  
If the combustion is not within the specified range,  
reference the chart below for possible causes and  
corrective actions.  
Table 3-6 Troubleshooting Chart - Combustion Levels  
POSSIBLE CAUSE  
CORRECTIVE ACTION  
• Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual  
for the proper venting and air intake methods for the Knight XL boiler.  
Vent/Air Intake Length  
or Obstruction  
• Check for obstructions at the vent/air intake terminals.  
• Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation  
Manual for the proper gas supply for the Knight XL boiler.  
Gas Supply Pressure  
• Refer to page 31 of this manual for burner removal and cleaning procedures.  
• Replace burner if necessary.  
Dirty/Damaged Burner  
Gas Valve Adjustment  
• Refer to page 47 of this manual for the gas valve adjustment procedure.  
46  
Service Manual  
3 Troubleshooting  
(continued)  
Gas valve adjustment procedure  
Figure 3-3 Gas Valve Adjustment: Model 501  
If adjustment of the gas valve is deemed necessary, use the  
following procedures: (Note: The procedures below are  
model specific.)  
Under normal operating conditions this  
valve should not need adjusting.  
CAUTION  
Model 400  
Locate the throttle adjustment screw on the top of the gas  
valve, see FIG. 3-2. Using a screwdriver, turn the screw 1/8  
turn counterclockwise to increase CO2 levels or 1/8 turn  
clockwise to decrease CO2 levels. After one adjustment on  
the valve, follow the Combustion Analysis Procedure on  
page 46 of this manual to measure the combustion.  
If combustion is still not within the specified range,  
repeat the procedure. This procedure SHOULD NOT  
be performed more than four (4) times. If after four (4)  
adjustments and the combustion is still not within the  
specified range, revisit the possible causes in Table 3-6 on  
page 46 or replace the gas valve.  
Models 601 - 801  
Locate the throttle adjustment screw on top of the gas valve,  
see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4  
turn counterclockwise to increase CO2 levels or a 1/4 turn  
clockwise to decrease CO2 levels. After one adjustment on the  
valve, follow the Combustion Analysis Procedure on page 46  
of this manual to measure the combustion.  
Figure 3-2 Gas Valve Adjustment: Model 400  
THROTTLE ADJUSTMENT  
SCREW  
If combustion is still not within the specified range, repeat  
the procedure. This procedure SHOULD NOT be performed  
more than four (4) times. If after four (4) adjustments and  
the combustion is still not within the specified range, revisit  
the possible causes in Table 3-6 on page 46 or replace the gas  
valve.  
Figure 3-4 Gas Valve Adjustment: Models 601 - 801  
Model 501  
THROTTLE  
ADJUSTMENT  
SCREW  
Locate the throttle adjustment screw on top of the gas valve,  
see FIG. 3-3. Using a screwdriver, turn the screw a 1/4 turn  
counterclockwise to increase CO2 levels or a 1/4 turn  
clockwise to decrease CO2 levels. After one adjustment on  
the valve, follow the Combustion Analysis Procedure on  
page 46 of this manual to measure the combustion.  
(REMOVE BLUE CAP)  
If combustion is still not within the specified range,  
repeat the procedure. This procedure SHOULD NOT  
be performed more than four (4) times. If after four (4)  
adjustments and the combustion is still not within the  
specified range, revisit the possible causes in Table 3-6 on  
page 46 or replace the gas valve.  
47  
Revision Notes: Revision A (ECO #C05747) initial release. Reflects  
the new model numbers for the Knight XL upgrade.  
Revision B (ECO #C06234) reflects changes made to the Service  
Notification parameter.  
Revision C (ECO #C07981) reflects changes made to the parameter  
table, parameter descriptions, updates to the troubleshooting chart, and  
the addition of the O-temp HEX switch.  
Revision D (ECO #C09197) reflects updates made to the SMART  
SYSTEM control (ECR #R04523).  
Revision E (ECO #C09840) reflects the addition of the Test Procedure  
for low water flow conditions on page 32.  
Revision F (ECO #C10143) reflects updates made to the ignition timing  
information.  
KBXII-SER Rev F  
04/12  

RCA Car Speaker RTD396 User Manual
Profile MP6600 User Manual
Plantronics 655 User Manual
Phoenix Gold Coaxial Loudspeaker V65 User Manual
Panasonic AJ YAC965E User Manual
Oster Blender Oster Digital Blender User Manual
Orion Car Audio 250R 275R User Manual
Nikon AF S NIKKOR 50mmf18G User Manual
Kenwood Car Stereo System TS 130V User Manual
JVC GZ MG20AA User Manual