Burnham V7 SERIES User Manual

Price - $3.00  
INSTALLATION,  
OPERATING AND SERVICE  
INSTRUCTIONS FOR  
V7 SERIES OIL FIRED BOILER  
KNOCKDOWN & PACKAGED  
HEATING UNITS  
Theseinstructionshavebeen  
reviewedbyULCandfound  
suitable for use in the  
installationofULClabeled  
V-7SeriesBoilers.  
As an  
ENERGY  
STAR® Partner,  
Burnham Corporation  
has determined that the  
V73WR (0.60 GPH),  
V74WR (0.80 GPH),  
V75WR (0.90 GPH),  
and V76WR (1.15 GPH)  
meet the ENERGY STAR®  
guidelines for Energy  
efficiency established by the  
United States Environmental  
Protection Agency (EPA).  
The ULC label or listed  
marking on a product is the  
onlyevidenceprovidedby  
Underwriters'Laboratoriesof  
Canadatoidentifyproducts  
whichhavebeenproduced  
underthelistingandfollow-up  
service.  
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide  
Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
Boiler Serial Number  
Installation Date  
_V7 ____-____  
6_ _ _ _ _ _ _  
Heating Contractor  
Phone Number  
Address  
8142711R24-7/99  
IMPORTANT  
Before starting to install this oil boiler, read these instructions carefully. Keep instructions in legible condition and  
posted near oil boiler for reference by owner and service technician.  
TABLE OF CONTENTS  
I. General Information ............................. 3  
II. Knockdown Boiler Assembly ............... 7  
III. Installation Instructions...................... 12  
IV. Operating Instructions........................ 21  
V. Boiler Cleaning .................................. 29  
VI. Repair Parts ........................................ 31  
Burner Specifications ......................... 46  
SECTION I: GENERAL INFORMATION  
Figure 1A: V72 thru V79 Water Boiler Without Tankless Heater (WB)  
TABLE 1: DIMENSIONAL DATA (SEE FIGURES 1A THRU 1E)  
Heat Transfer  
Dimensions  
Water Content -  
Gallons  
Surface Area -  
Sq. Ft.  
Boiler  
Model  
No.  
Approximate  
Shipping Weight  
(LB.)  
Minimum  
Chimney Size  
Steam Water  
Boiler Boiler  
"A"  
"B"  
"C"  
Steam Boiler  
V72  
V713  
V73  
V714  
V74  
V75  
V76  
V77  
V78  
V79  
11-3/8" 6-3/8"  
16" 8-3/4"  
15-3/8" 8-3/8"  
20" 10-3/4"  
5"  
6"  
6"  
6"  
6"  
7"  
7"  
8"  
8"  
8"  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 8" x 15'  
8" x 12" x 15'  
8" x 12" x 15'  
8" x 12" x 15'  
----  
----  
10.6  
13.5  
13.2  
15.9  
15.9  
18.5  
21  
----  
----  
381  
524  
478  
580  
575  
674  
773  
872  
971  
1070  
10.8  
----  
13.8  
----  
19-3/8" 10-3/8"  
23-3/8" 12-3/8"  
27-3/8" 14-3/8"  
31-3/8" 16-3/8"  
35-3/8" 18-3/8"  
39-3/8" 20-3/8"  
13.5  
16.1  
18.6  
21.2  
23.8  
26.4  
19.7  
25.6  
31.4  
37.3  
43.1  
49.0  
23.6  
26.2  
28.8  
NOTE: 1. Maximum Working Pressure 15 PSI (Steam) and 30 PSI (Water)  
2. The V72, V713 and V714 Boilers are available as packaged water boilers only  
3. The V713 and V714 are not ULC listed Models  
3
Figure 1B: V73 thru V79 Water Boiler with Tankless Heater (WBT)  
Figure 1C: V73 thru V79 Steam Boiler with or without Tankless Heater ("SBT" or "SB")  
4
Β υρνηαµ  
Figure 1D: V713 and V714 Packaged Water Boiler Less Tankless Heater (WB)  
Burnham  
Figure 1E: V713 and V714 Packaged Water Boiler with Tankless Heater (WBT)  
5
A. INSPECT SHIPMENT carefully for any signs of  
2. FOR BASEMENT INSTALLATION, provide a  
solid base, such as concrete, if floor is not level, or  
if water may be encountered on floor around boiler.  
damage.  
1. ALL EQUIPMENT is carefully manufactured,  
inspected and packed. Our responsibility ceases  
upon delivery of crated boiler to the carrier in good  
condition.  
3. PROVIDE SERVICE CLEARANCE of at least 24”  
on right side of boiler for removal of rear tankless  
heater. Provide at least 24” clearance from front  
jacket panel for servicing and removal of front  
tankless heater (increase to 30" for #A54 heater).  
Provide at least 24" clearance from right side of  
boiler or top of boiler for cleaning flueways. Boiler  
flueways may be cleaned either from the top or  
from the side.  
2. ANY CLAIMS for damage or shortage in shipment  
must be filed immediately against the carrier by the  
consignee. No claims for variances from, or  
shortage in orders, will be allowed by the  
manufacturer unless presented within sixty (60)  
days after receipt of goods.  
4. For minimum clearances to combustible materials.  
See Table 2.  
B. LOCATE BOILER in front of final position before  
removing crate. See Figures 1A thru 1E.  
C. PROVIDE AIR SUPPLY AND VENTILATION to  
accommodate proper combustion. If natural ventilation  
is inadequate, provide a screened opening or duct from  
the boiler room to the outside. The opening or duct  
must be sized so the boiler input will not exceed 4,000  
BTUH/Sq. In. of free area. If other air consuming  
appliances are near the boiler, the air inlet should be  
larger. Consult respective manufacturers.  
1. LOCATE so that smoke pipe connection to  
chimney will be short and direct. BOILER IS  
SUITABLE FOR INSTALLATION ON  
COMBUSTIBLE FLOOR. Boiler cannot be  
installed on carpeting.  
NOTE 1: Listed clearances comply with American  
National Standard ANSI/NFPA 31, Installation of Oil  
Burning Equipment.  
TABLE 2: Minimum Installation Clearances To  
Combustible Materials (Inches)  
NOTE 2: V7 Series boilers can be installed in rooms  
with clearances from combustible material as listed  
above. Listed clearances cannot be reduced for  
alcove or closet installations.  
C
A
B
Chimney  
D
E
Boiler Above Front  
Connector  
Rear Sides  
NOTE 3: For reduced clearances to combustible  
material, protection must be provided as described in  
the above ANSI/NFPA 31 standard.  
V7 24  
6
18  
6
6
6
SECTION II: KNOCKDOWN BOILER ASSEMBLY  
Note: If Boiler is Packaged Go To Section III  
section as shown in Fig. 3. Place gaskets so as not  
to allow any flueway blockage.  
A. REMOVAL OF BARE BOILER FROM SKID  
1. Boiler is secured to base with 4 bolts, 2 on front and  
2 on rear, see Figure 2. Remove all bolts.  
2. Cut the remainder of the roll into two (2) equal  
pieces. Place each piece along the sides, allowing  
the ends to overlap the front and rear pieces.  
2. Tilt boiler to right and to rear. Using right rear leg  
as pivot, rotate boiler 90° in a clockwise direction,  
and lower left side of boiler to floor. Tilt boiler and  
remove crate skid.  
Do not allow any flueway blockage.  
3. Position canopy body within the retaining bar  
which borders the flueway openings on top of the  
bare boiler block assembly.  
Figure 2  
B. MOVE BOILER TO PERMANENT POSITION by  
sliding or walking.  
C. TEST BOILER FOR LEAKS before installing  
controls, trim, and jacket, and before connecting to  
heating system.  
1. Loosen nuts on tie rods until only finger tight.  
2. Install pressure gauge (at least 30 P.S.I. capacity), a  
hose to the city water and a valve in the supply  
tapping. Plug remainder of tappings.  
Figure 3  
3. Fill boiler with water and apply a pressure of at  
least 10 pounds but no more than 30 pounds gauge  
pressure.  
IMPORTANT: Jacket support bracket must be  
facing left side of boiler — see Figure 3.  
4. Secure canopy to boiler with two (2) 1/4" - 20 x 3"  
lg. carriage bolts, 1/4" flat washers and 1/4" - 20  
wing nuts provided.  
4. Examine Boiler carefully inside and outside for  
leaks or damage due to shipment or handling.  
D. DRAIN WATER FROM BOILER. Remove gauge,  
valve and plugs from those tappings to be used. Leave  
other tappings plugged or bushed according to Figure  
4.  
H. INSTALL the following steam or water trim that  
would be concealed or inaccessible after flush jacket is  
installed, see Figure 4 for boiler tapping locations and  
usage.  
E. INSPECT JOINTS BETWEEN SECTIONS. All joints  
are factory sealed. If there are any spaces due to  
shipment or handling, seal them with boiler putty.  
1. STEAM BOILER — Top tappings:  
a. Tapping "L" — Install 2" plug in rear section  
top supply tapping on boiler sizes V73 thru  
V75.  
F. INSPECT FLUE COVER PLATES for tightness. If  
loose, retighten mounting hardware. If flue plate or  
sealing insulation is damaged repair or replace as  
needed.  
b. Tapping “M” — Install ¾” coupling and ¾” x  
8” long nipple into ¾” tapping located next to  
front section top supply tapping — all boiler  
sizes.  
G. INSTALL AND SECURE CANOPY with cerafelt  
gasket and hardware provided to ensure gas tight seal  
— see Figure 3.  
2. WATER BOILER — Top tappings:  
a. Tapping “L” — Install 2” plug in rear section  
top supply tapping on boiler sizes V73 thru  
V79.  
1. Cut two (2) strips 13 ¾” lg. from the roll of cerafelt  
gasket insulation. Place one (1) strip across the top  
of the front section and the other across the rear  
7
Figure 4: Boiler Tapping Locations and Usage (Knockdown Boilers Only)  
PU RP OSE OF TA PP INGS  
Tapping  
Location  
S team B oiler  
Water B oiler  
S ize  
Non-Heater  
w/Heater  
Non-Heater  
L81 48A  
Front Heater  
L81 24C  
R ear Heater  
Flush Plug  
PA4 04A Pressuretrol (P robe LW CO )  
Plugg ed (Flo at LW CO )  
A
B
¾"  
¼"  
¾ "  
¾"  
½ "  
Op erating C on trol Op erating C on trol  
Pressure/Va cuum G auge  
Temp era ture/Pre ssure G auge  
Flush Plug  
Pro be LWC O Std.  
C
Plugged (Flo at LW CO )  
C-C  
D
Flush Plug  
Flush Plug  
Flush Plug  
Water Gau ge Glass (Probe LW CO )  
Flush Plug  
Water G auge G lass, Pre ssuretrol, a nd LW CO (Flo at)  
L4006A Op era tin g  
L81 24C  
Op erating C on trol  
F
¾"  
-----  
-----  
Disre gard  
C on trol  
G
H
J
1½"  
1½"  
1½"  
2"  
Bushe d to ¾ " for Draincock (O ptiona l Re tu rn )  
R eturn  
R eturn  
Bushe d to ¾ " for Draincock (O ptiona l Re tu rn )  
Flush Plug  
Su rface Blow off - Plugged  
Front Su pply (3 thru 9 Section)  
K
Front Su pply (3 thru 9 Section)  
Plugged , Optional Se co nd Su pply (3 thru 5 Section)  
R equire d S eco nd Supply (6 thru 9 Se ction )  
L
M
P
2"  
Plu gge d (3 thru 9 Section)  
Re lief Valve  
¾"  
¾"  
¾"  
Safety Valve  
Aux. Ta pping -  
Plu gged  
Aux. Ta pping -  
Plu gged  
Au xiliary Tapp ing - Plugge d  
Disre gard  
R
Au xiliary Tapp ing - Plugge d  
Au xiliary Tapp ing - Plugge d  
8
Figure 5: Knockdown Boiler Jacket Assembly  
b. Tapping “M” —Install ¾” x 8” long nipple into  
side panel mounting holes with the front and rear  
panel holes. Secure with #8 x ½” long sheet metal  
screws.  
¾” tapping located next to front section top  
supply tapping — all boiler sizes.  
I. INSTALL FLUSH JACKET (See Figure 5).  
5. Install jacket top panel. Place jacket top panel on  
boiler and secure to front, rear and left side panels  
with #8 x ½” long sheet metal screws.  
1. Remove burner swing door mounting plate. Loosen  
the bottom bolt three full turns. Remove (5)  
remaining 5/16” bolts securing mounting plate to  
boiler sections.  
6. Install jacket lower right side panel. Align right  
side panel mounting holes with front and rear panel  
holes. Secure with #8 x ½” long sheet metal screws.  
Lift up and remove plate.  
7. Install jacket upper right side access panel. Using  
the thumb holes, hold access panel 1” above lower  
right side panel. Engage flanges on access panel  
with surrounding panels and lower into position  
until access panel is resting flush with top panel  
and bottom flange is properly locked into position  
with lower right side panel.  
2. Install rear jacket panel. Align two dimpled holes  
on jacket panel with the cast iron lugs. Secure with  
two #10 x 3/8” long self tapping screws.  
3. JACKET FRONT PANEL  
a. Install black plastic collar extension to jacket  
front panels with 7-13/16" dia. heater opening.  
Engage two (2) retaining tabs over raw edge of  
opening. Provide support behind the panel with  
one hand while applying pressure on collar to  
snap each tab over edge of opening until all  
eight (8) tabs are securing collar.  
8. Attach the data labels shipped in the instruction  
envelope as follows: (see Figure 5).  
a. Place the Rating Label (serialized)  
approximately 1/4" below the top edge and  
3-1/2" from the right edge of the jacket front  
panel as shown. Mark outline of label on jacket  
with a pencil. Remove paper backing from  
label, realign label with pencil marks and apply  
label to jacket by using backing paper to rub  
across face of label.  
b. Install front jacket panel. Locate two 3/16”  
diameter holes on front panel approximately 16”  
up from the bottom of the panel and 4½” in  
from each side. Align these holes with the  
similarly located cast iron lugs on the front  
section. Secure with two #10 x 3/8” long self-  
tapping screws.  
b. Locate the Combination Label (P/N 8142756)  
on the front right corner of top panel,  
4. Install jacket left side panel. Fold panel at  
perforation keeping insulation inward. Align left  
approximately 3/8" from each edge as shown.  
Mark the location and apply label in the same  
9
Figure 6  
manner as rating label.  
burner to the left. Install two remaining 5/16” x ½”  
long bolts in horizontal sets of holes. Level burner  
and fully tighten all bolts.  
c. On steam boilers, install the Lowest Permissible  
Water Level Plate, Form No. 1204 (shipped in  
Steam Trim Carton), on the jacket right side  
panel. Align the two holes in the plate with the  
two 1/8” dia. holes located near the front edge,  
in line with the lower sight glass tapping, and  
secure with #8 x ½” lg. sheet metal screws.  
K. INSTALL STEAM BOILER TRIM AND CONTROLS  
(See Figures 1C & 4).  
1. Thread the combination pressure/vacuum gauge  
into the ¼” tapping. Tighten with wrench applied  
to the square shank of the gauge. Do not apply  
pressure to the gauge case — this might destroy the  
calibration of the gauge.  
J. INSTALL OIL BURNER (See Figure 6).  
1. Check target wall and cerafelt blanket in  
combustion chamber. If any damage or movement  
occurred during shipment, repair or replace as  
needed.  
2. Thread 1½” x ¾” bushing and a ¾” drain cock into  
the 1½” tapping located in the lower right corner of  
the front casting. Tighten with wrench.  
2. Check the burner mounting plate and swing door  
insulation pieces for damage and adhesion. If  
damaged, replace insulation. If loose, re-attach with  
RTV 732 or 736 silicone caulk.  
NOTE: Lower rear section tapping “H” is used for  
standard condensate return on steam boilers.  
3. Thread safety relief valve, as shown in Figure 1C,  
into 3/4" coupling and 3/4” x 8” nipple previously  
installed in step H. Tighten with wrench.  
3. Engage bottom slot on burner mounting plate with  
matching bolt in bottom tapping of front section.  
Align mounting holes and fasten the mounting  
plate to the boiler sections with (5) five 5/16” bolts  
and washers removed in step 8a. Fully tighten all  
bolts.  
NOTE: Pipe discharge as shown in Figure 8.  
4. Install probe type LWCO if so equipped. Thread  
probe into ¾” tapping located on the front section  
directly above the protectorelay on the oil burner.  
Read the manufacturer’s instructions packed with  
the probe LWCO for proper pipe dope application.  
DO NOT use Teflon tape on probe threads. Use of  
teflon can render the probe LWCO inoperational.  
Slip the LWCO control over the probe and clamp in  
place. Connect the wire(s) between the probe and  
control per the manufacturer’s instructions. Install  
4. Place burner flange gasket on burner swing door  
and thread two 5/16” x ½” long bolts into vertical  
set of holes approximately three full turns.  
5. Insert oil burner air tube into the opening of the  
burner swing door. Align keyhole slot with vertical  
set of bolts, engage hex head of bolts and rotate  
10  
the sight glass using the two ½” tappings to the  
right of the probe LWCO.  
4. Screw drain valve into 1½” tapping in lower rear  
section using 1½” x ¾” bushing (note - lower front  
section tapping “G” (see Figure 4) is used for  
standard return on water boilers).  
5. Install float-type Low Water Cutoff, if so equipped.  
See Figure below.  
5. If CIRCULATOR (not supplied with boiler) is to be  
mounted directly to 1½" boiler return tapping "G",  
use the piping arrangements outlined in steps a. thru  
e. as follows:  
a. Install nipples and unions in Tappings D.  
b. Mount hardware to low water cutoff body. Install  
assembly.  
c. Install water gage glass on low water cutoff  
assembly's tee fittings.  
a. Thread 1½” x 3” long nipple and 1½” x 90°  
elbow into the return tapping and tighten with a  
pipe wrench.  
6. Install Limit Control.  
a. Probe LWCO: Install Limit in Tapping A using  
¾ NPT x 2" nipple, ¾ NPT elbow, ¾ NPT x ¼  
NPT bushing, and syphon. See Figure below  
right.  
b. Float LWCO: Remove ¼ NPT plug from top of  
Low Water Cutoff. Install Syphon and Limit into  
this tapping. See Figure below.  
b. Thread 1½” NPT x 15” long pipe nipple into the  
90° elbow and tighten with a pipe wrench.  
c. Thread one of the circulator flange onto the pipe  
nipple and tighten with a pipe wrench. Position  
flange so that the bolt slots are perpendicular to  
the boiler front.  
7. On units equipped with a tankless heater, install the  
aquastat controller well in the ¾” tapping in tankless  
heater plate. Slip the bulb of the aquastat into the well  
and secure the control in place with the set screw.  
d. Place a flange gasket in the flange groove on the  
circulator and mount the circulator on the flange  
installed in step 3. Note that this is the return  
piping and the flow arrow on the circulator should  
point down ê. Fasten circulator with 7/16” nuts  
and bolts.  
8. Connect the field wiring to the pressure limit, the  
LWCO, the burner J-box, and from the aquastat  
control (if equipped with tankless heater) to the oil  
burner primary control's "T-T" terminals. Make the  
wiring connections as shown in Figures 17 thru 20.  
e. Bolt second circulator flange and gasket to the  
circulator with 7/16” nuts and bolts.  
6. Install pressure relief valve, as shown in Figure 1B,  
onto ¾” x 8” nipple previously installed in Step H.  
Tighten with wrench.  
L. INSTALL WATER TRIM AND CONTROLS  
(See Figures 1B and 4).  
1. Thread ½” pipe plugs into gauge glass tappings in  
the upper right side of front section.  
NOTE: Pipe discharge as shown in Figure 9.  
7. On units without a tankless heater, install the control  
well into the ¾” tapping located on the front of the  
boiler in the upper left corner. Tighten the well and  
insert the control’s bulb into the well. Secure the  
control with set screw on the control.  
2. Thread ¾” pipe plug in probe low water cut off  
tapping (just left of gauge glass tappings).  
3. Thread combination pressure/temperature gauge into  
¼” tapping. Tighten with wrench applied to the  
square shank of the gauge. Do not apply pressure to  
the gauge case - this might destroy the calibration of  
the gauge.  
8. On units with a tankless heater, install the control  
well in the ¾” tapping on the tankless heater plate.  
Tighten the well and insert the control’s bulb into the  
well. Secure the control with set screw on the control.  
9. Connect the field wiring from the circulator to the  
control and from the control to the burner J-Box.  
Make the wiring connections as shown on Figures 21  
and 22.  
NOTE: Proceed to Installation Instructions Section  
III, step E, to continue.  
Limit Installation for Probe LWCO Equipped  
Boilers  
Float-type Low Water Cutoff Installation  
11  
SECTION III: INSTALLATION INSTRUCTIONS  
4. Packaged boilers with Probe style LWCO. Install  
A. REMOVE CRATE — (Packaged Boilers)  
Limit in Tapping A using ¾ NPT x 2" nipple, ¾  
NPT elbow, ¾ NPT x ¼ NPT bushing, and syphon  
included in trim bag. See Figure on previous page.  
Connect wiring harness from Low Water Cutoff.  
See Figure below.  
1. Remove all fasteners at crate skid.  
2. Lift outside container and remove all other inside  
protective spacers and bracing. Remove draft  
regulator box and miscellaneous trim bag  
containing safety/relief valve, and pipe fittings.  
B. REMOVAL OF BOILER FROM SKID  
TS-39-126-A  
5. If this boiler is used in connection with  
refrigeration systems, the boiler must be installed so  
that the chilled medium is piped in parallel with the  
heating boiler using appropriate valves to prevent  
the chilled medium from entering the boiler, see  
Figure 10. Also consult I = B = R Installation and  
Piping Guides.  
TS-39-26-A  
Fig. 7  
6. If this boiler is connected to heating coils located in  
air handling units where they may be exposed to  
refrigerated air, the boiler piping must be equipped  
with flow control valves to prevent gravity  
circulation of boiler water during the operation of  
the cooling system.  
1. Boiler is secured to base with 4 bolts, 2 on left side  
and 2 on right side, see Figure 7. Remove all bolts.  
2. Tilt boiler to right and to rear. Using right rear leg  
as pivot, rotate boiler 90° in a clockwise direction,  
and lower left side of boiler to floor. Tilt boiler and  
remove crate skid. Care should be exercised to  
prevent damage to jacket or burner.  
7. Use a boiler bypass if the boiler is to be operated in  
a system which has a large volume or excessive  
radiation where low boiler water temperatures may  
be encountered (i.e. converted gravity circulation  
system, etc.).  
C. MOVE BOILER TO PERMANENT POSITION by  
sliding or walking.  
D. INSPECT COMBUSTION TARGET WALL AND  
COMBUSTION CHAMBER LINER  
Remove the circulator and install a pipe tee  
between the circulator and boiler return along with  
a second tee in the supply piping as shown in  
Figure 11. The bypass should be the same size as  
the supply and return lines with valves located in  
the bypass and supply outlet as illustrated in Figure  
11 in order to regulate water flow for maintenance  
of higher boiler water temperature.  
1. OPEN FLAME OBSERVATION DOOR AND/OR  
BURNER SWING DOOR on front of boiler. Use  
flashlight to inspect target wall secured to rear  
section with silastic sealant. Inspect ceramic fiber  
blanket secured to floor of boiler with water glass  
adhesive. If either is damaged they must be  
replaced.  
E. CONNECT SUPPLY AND RETURN PIPING TO  
Set the by-pass and boiler supply valves to a half  
throttle position to start. Operate boiler until the  
system water temperature reaches its normal  
operating range.  
Adjust the valves to maintain 180°F boiler water  
temperature. Adjust both valves simultaneously.  
Closing the boiler supply valve and opening the by-  
pass valve will raise the boiler water temperature  
and lower the supply temperature. Opening the  
boiler supply valve while closing the by-pass valve  
will lower the boiler water temperature and raise  
the supply temperature.  
HEATING SYSTEM.  
CLEARANCES — Steam and hot water pipes shall  
have clearances of at least ½” from all combustible  
construction.  
1. With STEAM HEATING, see Figure 8. Consult I =  
B = R Installation and Piping Guide No. 200.  
2. With Forced Circulation HOT WATER HEATING,  
see Figure 9. Consult I = B = R Installation and  
Piping Guide No. 200.  
3. Packaged boilers. Install Safety Valve in Tapping  
M. Use ¾ NPT x 8" nipple and ¾ NPT coupling  
included in trim bag. Safety Valve must be  
installed with spindle in vertical position.  
8. A hot water boiler installed above radiation level  
must be provided with a low water cutoff device as  
part of the installation.  
12  
TS-39-17-D  
Fig 8: V73 Thru V79 Recommended Boiler Piping For Gravity Return Steam Boiler  
TS-39-4-C  
Fig. 9: V72 thru V79, V713 and V714 Recommended Boiler Piping for Series Loop Forced Hot Water System  
13  
In order to insure long product life, oxygen sources  
should be eliminated. This can be accomplished by taking  
the following measures:  
1. Repairing system leaks to eliminate the need for  
addition of make-up water.  
2. Eliminating open tanks from the system.  
3. Eliminating and/or repairing fittings which allow  
oxygen absorption.  
TS-O-62-B  
4. Use of non-permeable materials in the distribution  
system.  
5. Isolating the boiler from the system water by installing  
a heat exchanger.  
F. CONNECT TANKLESS HEATER PIPING AS  
SHOWN IN Figure 12. See Tables 3 and 3A for  
Tankless Heater Ratings.  
Fig. 10: Recommended Piping for Combination  
Heating & Cooling (Refrigeration) Systems  
Water Boilers  
TS-0-63-B  
TS-39-7-A  
Fig. 12: Schematic Tankless Heater Piping  
Fig. 11: Recommended Bypass Piping  
Water Boilers  
THE FOLLOWING GUIDELINES SHOULD BE FOL-  
LOWED WHEN PIPING THE TANKLESS HEATER:  
1. FLOW REGULATION — If flow through the  
heater is greater than its rating, the supply of  
adequate hot water may not be able to keep up with  
the demand. For this reason a flow regulator  
matching the heater rating should be installed in  
the cold water line to the heater. The flow regulator  
should preferably be located below the inlet to the  
heater and a minimum of 3’ away from the inlet so  
that the regulator is not subjected to excess  
CAUTION  
Oxygen contamination of boiler water will cause  
corrosion of iron and steel boiler components,  
and can lead to boiler failure. Burnham's  
standard warranty does not cover problems  
caused by oxygen contamination of boiler water.  
temperatures that may occur during “off” periods  
when it is possible for heat to be conducted back  
through the supply line. The flow regulator also  
limits the flow of supply water regardless of inlet  
pressure variations in the range of 20 to 125 psi.  
There are many possible causes of oxygen contamina-  
tion such as:  
1. Addition of excessive make-up water as a result of  
system leaks.  
2. Absorption through open tanks and fittings.  
2. TEMPERING OF HOT WATER — Installation of  
an automatic mixing valve will lengthen the  
3. Oxygen permeable materials in the distribution  
system.  
delivery of the available hot water by mixing some  
14  
TABLE 3: TANKLESS HEATER DATA: Rear  
Mounted Heater on Steam and Water  
Boilers  
WARNING  
Install an automatic mixing valve at the tankless  
heater outlet to avoid risk of burns or scalding  
due to excessively hot water at the fixtures.  
Adjust and maintain the mixing valve in  
Pressure Drop  
thru Heater  
(PSI)  
Heater Rating  
(GPM)  
Boiler Heater  
Model  
No.  
accordance with the manufacturer's instructions.  
Steam Water Steam Water  
3. FLUSHING OF HEATER — All water contains  
some sediment which settles on the inside of the  
coil. Consequently, the heater should be  
V713  
V73  
V1-2  
V1-2  
V1-1  
V1-2  
V1-2  
V1-2  
V1-2  
V1-2  
V1-2  
V1-2  
---  
2.75  
---  
3.25  
3
---  
3.9  
---  
---  
4.7  
5.6  
7.2  
7.2  
8
5.6  
4.7  
4.4  
8
periodically backwashed. This is accomplished by  
installing hose bibs as illustrated and allowing  
water at city pressure to run into hose bib A,  
through the heater, and out hose bib B until the  
discharge is clear. The tees in which the hose bibs  
are located should be the same size as heater  
connections to minimize pressure drop.  
3.5  
4
V714  
---  
V74  
V75  
V76  
V77  
V78  
V79  
3
3.25  
3.5  
3.75  
4
5.6  
6.4  
7.2  
8
3.25  
3.75  
3.75  
4
4. HARD WATER — A water analysis is necessary  
to determine the hardness of your potable water.  
This is applicable to some city water and  
particularly to well water. An appropriate water  
softener should be installed based on the analysis  
and dealer’s recommendation. This is not only  
beneficial to the tankless heater but to piping and  
fixtures plus the many other benefits derived from  
soft water.  
4.5  
4.5  
9.8  
9.8  
4
8
TABLE 3A: TANKLESS HEATER DATA: Front  
Mounted Heater on Water Boilers  
Boiler  
Model  
Heater Heater Rating  
Pressure Drop  
Thru Heater (PSI)  
NOTE: STEAM BOILERS  
No.  
222  
222  
222  
222  
222  
A54  
222  
A54  
222  
A54  
(GPM)  
a. During summertime operation, the normal water  
line should be raised 1”, from 22-5/8” to  
23-5/8” (see Figure 1C) for improved tankless  
heater performance.  
V73  
V74  
V75  
V76  
3
22  
22  
3.5  
4
30.5  
33  
G. INSTALL SMOKEPIPE — The V7 should be vented  
into a fireclay tile-lined masonry chimney or chimney  
constructed from type L vent or a factory built chimney  
that complies with the type HT requirements of  
UL103. The chimney and vent pipe shall have a  
sufficient draft at all times, to assure safe proper  
operation of the boiler. See Figure 13 for recommended  
installation.  
4.5  
4.6  
5.5  
4.75  
6
33  
V77  
V78  
V79  
36  
40  
39.5  
40  
4.75  
6
1. Install a draft regulator (supplied with boiler)  
following the instructions furnished with the  
regulator. See Figure 14 for alternate draft regulator  
locations.  
39.5  
cold water with the hot. This prevents excessive  
and possibly scalding hot water at the fixtures. In  
addition, savings of hot water will be achieved  
since the user will not waste as much hot water  
while seeking water temperature to his liking.  
Higher temperature hot water required by  
dishwashers and automatic washers is possible by  
piping the hot water from the heater prior to  
entering the mixing valve. The mixing valve should  
be “trapped” by installing it below the cold water  
inlet to heater to prevent lime formation in the  
valve.  
2. Consider the chimney overall. Chimneys that have  
a high heat loss may become less suitable as the  
heat loss of the home goes down and the efficiency  
of the boiler installed goes up. Most homes have a  
chimney appropriate for the fuel and the era in  
which the home was built. That may have been a  
coal fired or an inefficient oil fired boiler built into  
a home without insulation or storm windows. With  
increasing fuel prices that home probably has been  
insulated and fitted with storm windows so that the  
heat loss of the home has been reduced. This  
15  
Fig. 14: Proper and Improper Locations  
of Draft Regulator  
Fig. 13: Recommended Smokepipe Arrangement  
and Chimney Requirements  
3. For the same reasons as in (2.) above, heat  
extractors mounted into the breeching are not  
recommended.  
requires less fuel to be burned and sends less heat  
up the chimney.  
H. INSTALL ELECTRIC WIRING in accordance with  
National Electrical Code and local regulations. A  
separate ELECTRICAL CIRCUIT should be run from  
meter with a Fused Disconnect Switch in the Circuit.  
Wiring should conform to Figures 17 thru 23.  
A new boiler probably has a higher efficiency than  
the boiler being replaced. That probably means that  
the stack temperature from the new boiler will be  
lower than that from the old boiler and with less  
room air being drawn up the chimney to dilute the  
stack gases. The combination of a large uninsulated  
chimney, reduced firing rate, reduced firing time,  
lower stack temperature and less dilution air can, in  
some cases, contribute to the condensing of small  
amounts of water vapor in the chimney. Such  
condensation, when it occurs, can cause chimney  
deterioration. In extreme cases, condensed water  
may be visible on the outside of the breeching or  
chimney. In those extreme cases, the chimney may  
have to be lined to insulate the chimney and thus  
prevent the condensation. The addition of dilution  
air into the chimney may assist in drying the  
chimney interior surfaces.  
CANADA- Refer to CSA standard C22.2 Part 1, 1990,  
Electrical Features of Fuel Burning Equipment (Gas  
and Oil).  
I. FUEL UNITS AND OIL LINES  
SINGLE-PIPE OIL LINES - Standard burners are  
provided with single-stage 3450 rpm fuel units with  
the by-pass plug removed for single-pipe installations.  
The single-stage fuel unit may be installed single-pipe  
with gravity feed or lift. Maximum allowable lift is 8  
feet. See Figure 15.  
TWO-PIPE OIL LINES - For two-pipe systems where  
more lift is required, the two-stage fuel unit is  
recommended. Table 4 (single-stage) and Table 5  
(two-stage) show allowable lift and lengths of 3/8-inch  
and 1/2-inch OD tubing for both suction and return  
lines. Refer to Figure 16.  
A massive chimney on a cold, or exposed outside  
wall may have produced adequate draft when it was  
fired with a higher input and greater volumes of  
heated gases. With reduced input and volume, the  
draft may be severely affected. In one instance our  
research showed a new chimney of adequate sizing  
produced only -.035" W.C. after 30 minutes of  
continuous firing at 13.0% CO2. Outside wall  
chimneys take longer to heat up and can have .00"  
W.C. draft at burner startup. You may have to  
consider a special alloy chimney flue liner with  
insulation around it and a stabilizing draft cap or  
even a draft inducing fan in severe cases.  
Be sure that all oil line connections are absolutely  
airtight. Check all connections and joints. Flared  
fittings are recommended. Do not use compression  
fittings or PTFE ("Teflon®") tape.  
Open the air-bleed valve and start the burner. For  
clean bleed, slip a 3/16" ID hose over the end of the  
bleed valve and bleed into a container. Continue to  
bleed for 15 seconds after oil is free of air bubbles.  
Stop burner and close valve.  
16  
TABLE 4: SINGLE-STAGE UNITS (3450 RPM) -  
TWO-PIPE SYSTEMS  
Manimum Length of Tubing  
"H" + "R" (See Figure 16)  
Lift "H"  
(See Fig. 16)  
3/8" OD  
1/2" OD  
Tubing (3 GPH) Tubing (3 GPH)  
0'  
1'  
84'  
78'  
73'  
68'  
63'  
57'  
52'  
47'  
42'  
36'  
31'  
26'  
21'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
83'  
2'  
3'  
4'  
5'  
6'  
7'  
Figure 15  
8'  
9'  
10'  
11'  
12'  
13'  
14'  
IMPORTANT  
Single-pipe installations must be absolutely  
airtight or leaks or loss of prime may result.  
Bleed line and fuel unit completely.  
62'  
---  
41'  
TABLE 5: TWO-STAGE UNITS (3450 RPM) -  
TWO-PIPE SYSTEMS  
Maximum Length of Tubing  
"H" + "R" (See Figure 16)  
Lift "H"  
(See Fig. 16)  
3/8" OD  
1/2" OD  
Tubing (3 GPH) Tubing (3 GPH)  
0'  
2'  
93'  
85'  
77'  
69'  
60'  
52'  
44'  
36'  
27'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
76'  
4'  
6'  
8'  
10'  
12'  
14'  
16'  
18'  
Figure 16  
17  
Fig. 17: Wiring Diagram for Steam Boilers with Standard Hydrolevel CG-450 Probe LWCO,  
Beckett AFG Burner and Controls, with or without Tankless Heater  
Fig. 18: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-801 Probe LWCO,  
Beckett AFG Burner and Controls, with or without Tankless Heater  
BOILER SEQUENCE OF OPERATION WITH PROBE LWCO  
When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner. The burner will operate until the  
thermostat is satisfied or the limit setting on the high limit is reached. When the high limit control restores the circuit on a drop in  
pressure, the burner will start if the thermostat is still calling for heat.  
Any of the probe low water cutoffs will shut down the burner after a 10-15 second delay, if the water level in the boiler drops too low.  
The Hydrolevel CG-450 and the McDonnell & Miller PS-804-120 low water cutoffs will shut down the burner for 90 seconds every 10  
minutes of firing time to allow water level to stabilize. If the water level is too low the burner will not be allowed to restart.  
Any of the probe low water cutoffs reset and restart the burner with a call for heat a few seconds after the water is returned to its  
normallevel.  
On burner start, if the cad cell does not see flame within approximately 45 seconds, primary control will lock out on safety and must be  
reset before burner can be restarted.  
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected setting for proper  
operation of the domestic water heater, if equipped with optional tankless heater.  
18  
Fig. 19: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-804-120 Probe LWCO,  
Beckett AFG Burner and Controls, with or without Tankless Heater  
NOTE: The McDonnell Miller low water cut off incorporates a 10 second delay to prevent nuisance burner cut-off due to rapid  
water level fluctuations. The LWCO also has a time delay of 15 seconds which allows additional fill time after water touches the  
probe. Red LED indicates a low water condition.  
Fig. 20: Wiring Diagram for Steam Boilers with McDonnell & Miller #67 LWCO,  
Beckett AFG Burner and Controls, with or without Tankless Heater  
BOILER SEQUENCE OF OPERATION WITH FLOAT LWCO  
When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner. The burner will operate until  
the thermostat is satisfied or the limit setting on the high limit is reached. When the high limit control restores the circuit on a  
drop in pressure, the burner will start if the thermostat is still calling for heat. The low water cut off will shut down the burner if the  
water level in the boiler drops too low. The control resets and restarts the burner with a call for heat a few seconds after the water  
is returned to its normal level.  
On burner start, if the cad cell does not see flame within approximately 45 seconds, primary control will lock out on safety and  
must be reset before burner can be restarted.  
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected setting for  
proper operation of the domestic water heater, if equipped with optional tankless heater.  
19  
Fig. 21: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, without Tankless Heater  
SEQUENCE OF OPERATION  
A call for heat by the thermostat energizes the L8148A control which in turn energizes the R4184D primary control to turn on the  
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame, the burner will continue to operate until the call  
for heat is satisfied or the setting of the high limit is reached. The circulator will operate as long as the thermostat is calling for heat. If  
the thermostat is not satisfied and the high limit is reached, the circulator will continue to operate, and the burner will stop until the high  
limit is closed by a drop in boiler water temperature.  
Fig. 22: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, with Tankless Heater  
SEQUENCE OF OPERATION  
A call for heat by the thermostat energizes the L8124C control which in turn energizes the R4184D primary control to turn on the  
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame the burner will continue to operate until the call  
for heat is satisfied. The circulator will also operate when the thermostat calls for heat if the boiler water temperature is up to the setting  
of the low limit in the L8124C control. If boiler water temperature is below the low limit setting the burner will operate but the circulator  
will not, giving preference to the domestic hot water demand.  
On call for heat by the thermostat the burner will continue to operate until the thermostat is satisfied or the setting of the high limit is  
reached. If the thermostat is not satisfied when the high limit is reached the burner will stop but the circulator will continue to operate  
until the thermostat is satisfied. Any time the boiler water temperature drops below the setting of the low limit the burner will be  
energized in order to maintain domestic water temperature.  
20  
SECTION IV: OPERATING AND SERVICE INSTRUCTIONS  
WARNING  
All boilers equipped with burner swing door have a potential hazard which can cause severe property  
damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to  
boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door  
fastener completely when service is completed.  
A. ALWAYS INSPECT INSTALLATION BEFORE  
(Note - If make-up water line is equipped with  
pressure reducing valve, system will  
automatically fill to 12 psi. Leave globe valve  
open).  
STARTING BURNER.  
B. FILL HEATING SYSTEM WITH WATER.  
NOTE: It is important, especially in a steam system,  
to properly remove the oil and dirt from the system.  
Failure to clean the system can result in erratic water  
lines and surging.  
j. Open isolation valve in boiler supply piping.  
k. Remove hose from bib cock.  
C. CHECK CONTROLS, WIRING AND BURNER to be  
sure that all connections are tight and burner is rigid,  
that all electrical connections have been completed and  
fuses installed, and that oil tank is filled and oil lines  
have been tested.  
CLEAN HEATING SYSTEM IF boiler water or  
condensate return water is dirty or if erratic water lines  
or surging exist after a few days of boiler operation.  
Refer to step "N" for proper cleaning instructions for  
steam and water boilers.  
D. LUBRICATION Follow instruction on burner and  
circulator label to lubricate, if oil lubricated. Most  
motors currently used on residential type burners  
employ permanently lubricated bearings and thus do  
not require any field lubrication. Water lubricated  
circulators do not need field lubrication.  
1. STEAM BOILERS Fill boiler to normal water  
line. Refer to Figure No. 1C.  
2. HOT WATER BOILERS. Fill entire heating system  
with water and vent air from system. Use the  
following procedure on a series loop or multi-zoned  
system installed as per Figure 9, to remove air from  
system when filling:  
Do not over-lubricate. This can cause as much trouble  
as no lubrication at all.  
E. SET CONTROLS with burner service switch turned  
a. Close isolation valve in boiler supply piping.  
OFF.  
b. Isolate all circuits by closing zone valves or  
balancing valves.  
1. SET ROOM THERMOSTAT about 10° above  
room temperature.  
c. Attach a hose to bib cock located just below  
isolation valve in boiler supply piping.  
2. PRESS RED RESET BUTTON on primary control  
(R4184D/R8184G) and release.  
(Note - Terminate hose in five gallon bucket at a  
suitable floor drain or outdoor area).  
3. On STEAM BOILERS, set cut-in pressure on  
PA404 pressuretrol for three (3) pounds and  
differential pressure for two (2) pounds. These  
pressures may be varied to suit individual  
requirements of installation.  
d. Starting with one circuit, open zone valve.  
e. Open bib cock.  
f. Open fill valve (make-up water line should be  
located directly above isolation valve in boiler  
supply piping).  
4. On STEAM BOILERS WITH TANKLESS  
DOMESTIC WATER HEATERS, set boiler water  
temperature dial on L4006 operating control at  
190°F (max.). Set differential at 10°.  
g. Allow water to overflow from bucket until  
discharge from hose is bubble free for 30  
seconds.  
5. On WATER BOILERS WITHOUT TANKLESS  
HEATERS, set high limit dial on L8148 at 210°F.  
This temperature may be varied to suit  
requirements of installation.  
h. Open zone valve to the second zone to be  
purged, then close the first. Repeat this step  
until all zones have been purged, but always  
have one zone open. At completion, open all  
zone valves.  
6. On WATER BOILERS WITH TANKLESS  
HEATERS, set operating control dial (low limit) on  
L8124 at 190°F and high limit dial at 210°F.  
Operating control (low limit) must be a minimum  
of 20° below high limit setting. Set differential at  
25°.  
i. Close bib cock, continue filling the system until  
the pressure gauge reads 12 psi. Close fill valve.  
21  
NOTICE  
Burner-specific references in the following instructions pertain to the Beckett AFG, supplied as  
standard equipment. For optional burners, Riello R40 and Carlin EZ-1HP and 102CRD-3, consult  
Table 6 at the rear of this manual for specifications, the instruction booklet shipped with the  
burner, and the appropriate Supplemental Instructions shipped with the boiler:  
Burnham Part Number  
Supplemental Instructions for:  
Riello R40  
8142761  
8142759  
8142760  
Carlin EZ-1HP  
Carlin 102CRD-3  
V72 thru V77; V713 and V714:  
F. REMOVE GUN ASSEMBLY  
"L1" and "F" head burners have a fixed head which  
is non-adjustable. To check combustion head  
location refer to Figure 24.  
1. Items to be checked are nozzle size, type, and  
angle; head size (and setting on MD(V1)head); gun  
setting; and positioning of electrodes. This  
informations is shown in Figures 23 and 24 and  
Table 6 (at rear of manual).  
V78 & V79:  
V1(variable) head burners have the ability to  
control air by moving the head either forward or  
back.  
2. Reinstall gun assembly.  
G. ADJUST OIL BURNER BEFORE STARTING.  
Loosen the adjusting plate assembly hold down  
screw. Slide the head and plate to the required  
firing rate setting as shown in Figure 24. Tighten  
the screw and knurled nut.  
1. SET BURNER AIR BAND AND AIR SHUTTER,  
see Table 6 at rear of manual..  
2. OPEN ALL OIL LINE VALVES.  
3. Attach a plastic hose to fuel pump vent fitting and  
provide a pan to catch the oil.  
It might be necessary to move the head forward or  
back one position at a time to optimize the smoke  
and CO2 readings. See Figure 24.  
4. REMOVE GAUGE PORT PLUG from fuel pump  
and install pressure gauge capable of reading at  
least 150 PSI.  
3. ADJUST DRAFT REGULATOR for a draft  
of .02(water gauge) over the fire after chimney  
has reached operating temperature and while  
burner is running.  
5. OPEN FLAME OBSERVATION DOOR on front  
of boiler.  
4. READJUST AIR BANDS on burner for a light  
orange colored flame while the draft over the fire is  
.02. Use a smoke tester and adjust air for  
minimum smoke (not to exceed #1) with a  
minimum of excess air. Make final check using  
suitable instrumentation to obtain a CO2 of 11.5 to  
12.5% with draft of .02(water gauge) in fire  
box. These settings will assure a safe and efficient  
operating condition. If the flame appears stringy  
instead of a solid fire, try another nozzle of the  
same type. Flame should be solid and compact.  
After all adjustments are made recheck for a draft  
of .02over the fire.  
H. START OIL BURNER.  
1. Open vent fitting on fuel pump.  
2. TURN ONBURNER service switch and allow  
burner to run until oil flows from vent fitting in a  
SOLID stream without air bubbles for  
approximately 10 seconds.  
3. Close vent fitting and burner flame should start  
immediately.  
I. ADJUST OIL PRESSURE.  
1. Locate oil pressure adjusting screw and turn screw  
to obtain 140 PSI pressure (100 PSI for V74R  
only).  
2. DO NOT REMOVE PRESSURE GAUGE until  
later.  
J. OTHER ADJUSTMENTS  
1. ADJUST THE AIR BAND AND/OR AIR  
SHUTTER.  
(Non-Burnham Drawing  
Copy from other Manual)  
Adjust air supply by loosening lock screws and  
moving the air shutter and if necessary the air band.  
Refer to Table 6 for preliminary settings.  
2. ADJUST THE COMBUSTION HEAD.  
Fig. 23: "F" Head Electrode Positioning and Gun  
Setting (Beckett AFG)  
22  
(Non-Burnham Drawing,  
Copy from LE Manual, 81433010R4, Page 13, without  
"Figure 12A, 12B, 12C and 12D"; sample enclosed)  
Fig. 24: "L1" and "V1" Head Electrode Positioning and Gun Setting (Beckett AFG)  
5. TURN OFFBURNER and remove pressure  
gauge. Install gauge port plug and tighten. Start  
burner again.  
6. CAD CELL LOCATION AND SERVICE  
The burner is supplied with a cadmium sulfide  
flame detector mounted at the factory, mounted on  
the bottom of the ignitor. See Figure 25. To service  
cad cell or to replace the plug in portion, swing  
open the ignitor. After service is complete, be sure  
to fasten down the ignitor.  
7. FLAME FAILURE  
The V7 boiler controls operate the burner  
automatically. If for unknown reasons the burner  
ceases to fire and the reset button on the primary  
control has tripped, the burner has experienced  
ignition failure. Before pressing the reset button  
call your serviceman immediately.  
Figure 25: Cad Cell Location  
23  
CAD CELL TEST  
g. Open line switch. Clean cell face and see that  
cell is securely in socket. Reconnect leads. Reset  
safety switch.  
h. Close line switch. If burner starts and runs  
beyond safety switch cut-out time, cell is good.  
If not, install new cell.  
K. CHECK FOR CLEAN CUT OFF OF BURNER.  
3. WARNING Check High Limit Control —  
Jumper Thermostat Terminals. Allow burner to  
operate until shut-down by limit. Installation is not  
considered complete until this check has been  
made.  
1. AIR IN THE OIL LINE between fuel unit and  
nozzle will compress when burner is on and will  
expand when burner stops, causing oil to squirt  
from nozzle at low pressure as burner slows down  
and causing nozzle to drip after burner stops.  
Usually cycling the burner operation about 5 to 10  
times will rid oil line of this air.  
REMOVE JUMPER.  
4. Check low water cut off control with water level at  
normal water line (see Figure 1C). Raise thermostat  
setting to allow burner to operate. Open boiler drain  
to allow water level to drop to bottom of sight glass  
until burner operation is shut-down by low water  
cutoff.  
2. IF NOZZLE CONTINUES TO DRIP, repeat step  
K.1.. If this does not stop the dripping, remove  
cutoff valve and seat, and wipe both with a clean  
cloth until clean, then replace and readjust oil  
pressure. If dripping or after burn persist replace  
fuel pump.  
Close boiler drain and refill to normal water line.  
Burner should automatically restart during fill.  
Lower thermostat setting.  
L. TEST CONTROLS.  
5. Check operating control on boiler equipped with  
tankless heaters. With burner off, draw hot water  
until burner starts, then turn off hot water and  
check burner shut-down.  
WARNING  
Before installation of the boiler is considered  
complete, the operation of the boiler controls  
should be checked, particularly the primary  
control and high limit control.  
IF CONTROLS DO NOT MEET REQUIREMENTS  
OUTLINED IN PARAGRAPH L., REPLACE  
CONTROL AND REPEAT CHECK-OUT  
PROCEDURES.  
1. Check thermostat operation. Raise and lower  
thermostat setting as required to start and stop  
burner.  
M. MAINTENANCE OF LOW WATER CUTOFF  
DEVICES  
2. VERIFY PRIMARY CONTROL SAFETY  
FEATURES using procedures outlined in  
Instructions furnished with control (See back of  
control cover) or instructions as follows:  
IMPORTANT  
Probe and float type low water cut-off devices  
require annual inspection and maintenance.  
CHECKOUT PROCEDURE  
1. PROBE TYPE LOW WATER CUT-OFF  
FOR SERVICEMAN ONLY  
Although these devices are solid state in their  
operation, the probe is exposed to possible  
contamination in the boiler water and subject to  
fouling.  
a. Check wiring connections. Close line switch.  
Check power at control.  
PRIMARY RELAY TEST  
It is important to physically remove the probe from  
the boiler tapping annually and inspect that probe  
for accumulation of scale or sediment.  
b. Disconnect cad cell leads (f-f). Reset safety  
switch.  
c. Set controller to call for heat. Burner should  
start.  
Follow these steps to inspect, clean and/or replace  
the probe:  
d. Jumper F-F terminal within 15 to 30 seconds.  
Burner should run.  
a. Turn off electric service to the boiler.  
b. Drain boiler water to a level below the tapping  
for the probe.  
e. Remove F-F Jumper. Burner shuts down in  
approximately 15 to 60 seconds.  
c. Disconnect wiring connections between the low  
water cutoff control and the probe.  
f. If burner operates as described, relay is good. If  
not, install new relay.  
24  
d. Dismount the low water cutoff control from the  
probe.  
required. Examine all visible wiring for brittle or  
worn insulation and make sure electrical contacts  
are clean and that they function properly. Give  
special attention to solder joints on bellows and  
float when this type of control is used. Check float  
for evidence of collapse and check mercury bulb  
(where applicable) for mercury separation or  
discoloration. Do not attempt to repair mechanisms  
in the field. Complete replacement mechanisms,  
including necessary gaskets and installation  
instructions are available from the manufacturer.  
e. Unscrew the probe from the boiler tapping.  
f. Inspect that portion of the probe that is exposed  
to the boiler water for a scale or sediment  
buildup.  
g. Light deposits may be removed by wiping the  
probe with a damp cloth. Wiping the probe with  
a cloth soaked in vinegar will remove more  
tenacious lime deposits. The most stubborn  
deposits may be removed from the probe by  
using a diluted amount, 3 parts of water to 1  
part of phosphoric acid (H2PO4).  
N. BOILER AND SYSTEM CLEANING  
INSTRUCTIONS FOR TROUBLE FREE  
OPERATION.  
1. STEAM BOILERS  
CAUTION  
a. Oil, greases & sediments which accumulate in a  
new boiler and piping must be removed from the  
system in order to prevent an unsteady water  
line and carry over of the water into the supply  
main above boiler.  
Exercise caution when handling phosphoric acid  
and follow the instruction label on its container.  
h. Clean the pipe threads of the probe to remove  
old, hardened pipe dope and other foreign  
matter.  
Operate the boiler with steam in the entire  
system for a few days allowing the condensate to  
return to the boiler. If the condensate can  
temporarily be wasted, operate boiler only for  
the length of time it takes for condensate to run  
clear. If the latter cannot be achieved or if the  
condensate is returned to the boiler, boil out the  
boiler using the SURFACE BLOWOFF  
connection, see Figure 4.  
i. Apply a moderate amount of good quality pipe  
dope to the pipe threads on the probe, leaving  
the two end threads bare. Do not use PTFE  
(Teflon) tape.  
j. Screw the probe into the boiler tapping.  
k. Mount the low water cutoff control on the probe.  
l. Reconnect the control to probe wiring.  
m. Fill the boiler to its normal waterline.  
i. Drain boiler until 1of water is visible in  
gauge glass. Run temporary 1½” pipe line  
from the surface blowoff connection to an  
open drain or some other location where hot  
water may be discharged safely. Do not  
install valve in this line.  
n. Add boiler water treatment compound as needed  
(refer to paragraph N.).  
o. Restore electric service to the boiler.  
p. Fire burner to bring the water in the boiler to a  
boil to drive off free oxygen.  
ii. Drain about 5 gallons of hot water from  
boiler into a container and dissolve into it  
an appropriate amount of recommended  
boil out compound. Remove safety valve &  
add solution to boiler water thru exposed  
tapping using a funnel.  
q. WARNING BEFORE RETURNING  
BOILER TO SERVICE: Follow the low water  
cutoff check out procedure in step L.4..  
2. FLOAT TYPE LOW WATER CUT-OFF  
During the heating season, if an external low water  
cutoff is on the boiler, the blow off valve should be  
opened once a month (use greater frequency where  
conditions warrant), to flush out the sediment  
chamber so the device will be free to function  
properly.  
NOTICE  
Check with local authorities or consult local  
water treatment services for acceptable chemical  
cleaning compounds.  
Low-water cutoffs and water feeders should be  
dismantled annually by qualified personnel, to the  
extent necessary to insure freedom from  
obstructions and proper functioning of the working  
parts. Inspect connecting lines to boiler for  
accumulation of mud, scale, etc., and clean as  
iii. Start burner and operate sufficiently to boil  
the water without producing steam pressure.  
Boil for about 5 hours. Open boiler feed  
pipe sufficiently to permit a steady trickle of  
water from the surface blowoff pipe.  
25  
Continue this slow boiling and trickle of  
overflow for several hours until the water  
coming from the overflow is clear.  
v. When boiler has cooled down sufficiently  
(crown sheet of sections are not too hot to  
touch), close the drain cocks at boiler and in  
return main and feed water slowly up to  
normal level in boiler. Turn on oil burner  
and allow boiler to steam for 10 minutes,  
then turn off burner. Draw off one quart of  
water from bottom gauge glass fitting and  
discard. Draw off another quart sample and  
if this sample is not clear, repeat the cycle  
of draining the boiler and return main and  
refilling the boiler until sample is clear.  
iv. Stop burner and drain boiler in a manner  
and to a location that hot water can be  
discharged with safety.  
v. Refill boiler to normal water line. If water  
in gauge glass does not appear to be clear,  
repeat steps (i. thru iii.) and boil out the  
boiler for a longer time.  
b. Low pressure steam boilers such as the V7  
Series should be maintained with appropriate  
water treatment compounds. Add suitable water  
treatment compounds as recommended by your  
qualified water treatment company.  
vi. If the boiler water becomes dirty again at a  
later date due to additional sediment  
loosened up in the piping, close gate valve  
in Hartford Loop, open drain cock in return  
main, turn on oil burner and allow  
c. Remove temporary surface blowoff piping, plug  
tapping and reinstall safety valve. Boil or bring  
water temperature to 180°F promptly in order to  
drive off the dissolved gases in the fresh water.  
Condensate to flow to drain until it has run  
clear for at least 30 minutes while feeding  
water to boiler so as to maintain normal  
water level. Turn off oil burner, drain  
boiler, open gate valve in Hartford Loop,  
then repeat step 1 above.  
d. If unsteady water line, foaming or priming  
persist, install gate valve in Hartford Loop and  
drain valves in return main and at boiler as  
shown in Figure 8 and proceed as follows:  
e. Make pH or Alkalinity Test.  
i
Connect hoses from drain cocks to floor  
drain. Close gate valve in Hartford Loop  
and open drain cock in return main. Fill  
boiler to normal water level, turn on oil  
burner and operate boiler at this water level  
for at least 30 minutes after the condensate  
begins to run hot, then turn off burner.  
After boiler and system have been cleaned and  
refilled as previously described, test the pH of  
the water in the system. This can easily be done  
by drawing a small sample of boiler water and  
testing with hydrion paper which is used in the  
same manner as litmus paper, except it gives  
specific readings. A color chart on the side of  
the small hydrion dispenser gives the reading in  
pH. Hydrion paper is inexpensive and  
obtainable from any chemical supply house or  
through your local druggist. The pH should be  
higher than 7, but lower than 11. Add some of  
the washout chemical (caustic soda), if  
Close all radiator valves. Remove all supply  
main air valves and plug the openings in  
supply main.  
ii. Draw about 5 gallons of hot water from  
boiler into a container and dissolve into it  
the appropriate amount of a recommended  
boilout compound. Remove safety valve  
from boiler and pour this solution into  
boiler, then reinstall safety valve.  
necessary, to bring the pH within the specified  
range.  
f. Boiler is now ready to be put into service.  
2. WATER BOILERS  
iii. Turn on oil burner and keep operating  
while feeding water to boiler slowly. This  
will raise water level in boiler slowly so that  
water will be boiling hot and will rise  
slowly into supply main and back through  
return main, flowing from drain hose at  
about 180°F. Continue until water runs  
clear from drain hose for at least 30  
minutes.  
a. Filling of Boiler and System — General —-In a  
hot water heating system, the boiler and entire  
system (other than the expansion tank) must be  
full of water for satisfactory operation. Water  
should be added to the system until the boiler  
pressure gauge registers 12 psi. To insure that  
the system is full, water should come out of all  
air vents when opened.  
iv. Stop feeding water to boiler but continue  
operating oil burner until excess water in  
boiler flows out through supply main and  
water lowers (by steaming) until it reaches  
normal level in boiler. Turn off oil burner.  
Drain boiler. Open all radiator valves.  
Reinstall all supply main air valves. Open  
gate valve in Hartford Loop.  
b. Boiling Out of Boiler and System. The oil and  
grease which accumulate in a new hot water  
boiler can be washed out in the following  
manner.  
i. Remove safety relief valve using extreme  
care to avoid damaging it.  
ii. Add an appropriate amount of  
26  
recommended boil out compound.  
iii. Replace safety relief valve.  
iv. Fill the entire system with water.  
v. Start firing the boiler.  
and can vary from sample to sample. For all of  
those reasons a spare nozzle is a desirable item for  
a serviceman to have.  
2. FLAME SHAPE Looking into the combustion  
chamber through the observation door, the flame  
should appear straight with no sparklers rolling up  
toward the crown of the chamber. If the flame drags  
to the right or left, sends sparklers upward or makes  
wet spots on the target wall, the nozzle should be  
replaced. If the condition persists look for fuel  
leaks, air leaks, water or dirt in the fuel as  
described above.  
vi. Circulate the water through the entire  
system.  
vii. Vent the system, including the radiation.  
viii. Allow boiler water to reach operating  
temperature, if possible.  
ix. Continue to circulate the water for a few  
hours.  
3. FUEL LEAKS Any fuel leak between the pump  
and the nozzle will be detrimental to good  
combustion results. Look for wet surfaces in the air  
tube, under the ignitor, and around the air inlet.  
Any such leaks should be repaired as they may  
cause erratic burning of the fuel and in the extreme  
case may become a fire hazard.  
x. Stop firing the boiler.  
xi. Drain the system in a manner and to a  
location that hot water can be discharged  
with safety.  
xii. Remove plugs from all available returns and  
wash the water side of the boiler as  
thoroughly as possible, using a high-  
pressure water stream.  
4. AIR LEAKS Any such leaks should be repaired,  
as they may cause erratic burning of the fuel and in  
extreme cases may become a fire hazard.  
xiii. Refill the system with fresh water.  
c. Add appropriate boiler water treatment  
compounds as recommended by your qualified  
water treatment company.  
5. GASKET LEAKS If 11.5 to 12.5% CO2 with a  
#1 smoke cannot be obtained in the breeching, look  
for air leaks around the burner mounting gasket,  
observation door, and canopy gasket. Such air leaks  
will cause a lower CO2 reading in the breeching.  
The smaller the firing rate the greater effect an air  
leak can have on CO2 readings.  
d. Make pH or Alkalinity Test.  
After boiler and system have been cleaned and  
refilled as previously described, test the pH of  
the water in the system. This can easily be done  
by drawing a small sample of boiler water and  
testing with hydrion paper which is used in the  
same manner as litmus paper, except it gives  
specific readings. A color chart on the side of  
the small hydrion dispenser gives the reading  
pH. Hydrion paper is inexpensive and  
obtainable from any chemical supply house or  
thru your local druggist. The pH should be  
higher than 7 but lower than 11. Add  
appropriate water treatment chemicals, if  
necessary, to bring the pH within the specified  
range. With this lower level of protection, care  
must be exercised to eliminate all of the free  
oxygen in the system.  
6. DIRT A fuel filter is a good investment.  
Accidental accumulation of dirt in the fuel system  
can clog the nozzle or nozzle strainer and produce a  
poor spray pattern from the nozzle. The smaller the  
firing rate, the smaller the slots become in the  
nozzle and the more prone to plugging it becomes  
with the same amount of dirt.  
7. WATER Water in the fuel in large amounts will  
stall the fuel pump. Water in the fuel in smaller  
amounts will cause excessive wear on the pump, but  
more importantly water doesnt burn. It chills the  
flame and causes smoke and unburned fuel to pass  
out of the combustion chamber and clog the  
flueways of the boiler.  
e. Boiler is now ready to be put into service.  
8. COLD OIL If the oil temperature approaching  
the fuel pump is 40°F or lower poor combustion or  
delayed ignition may result. Cold oil is harder to  
atomize at the nozzle. Thus, the spray droplets get  
larger and the flame shape gets longer. An outside  
fuel tank that is above grade or has fuel lines in a  
shallow bury is a good candidate for cold oil. The  
best solution is to bury the tank and lines deep  
enough to keep the oil above 40°F.  
O. HINTS ON COMBUSTION  
1. NOZZLES Although the nozzle is a relatively  
inexpensive device, its function is critical to the  
successful operation of the oil burner. The selection  
of the nozzle supplied with the V7 boiler is the  
result of extensive testing to obtain the best flame  
shape and efficient combustion. Other brands of the  
same spray angle and spray pattern may be used but  
may not perform at the expected level of CO2 and  
smoke. Nozzles are delicate and should be protected  
from dirt and abuse. Nozzles are mass-produced  
9. HIGH ALTITUDE INSTALLATIONS  
Air openings must be increased at higher altitudes.  
Use instruments and set for 11.5 to 12.5% CO2.  
27  
clean water to prescribed water level.  
IMPORTANT  
4. Always keep the manual fuel supply valve shut off  
if the burner is shut down for an extended period of  
time.  
SUCTION LINE LEAKS - THE OIL MUST BE  
FREE OF AIR. Try bleeding the pump  
through a clear tube. There must be no froth  
visible. There are various test kits available  
to enable you to look at the oil through clear  
tubing adapted to the supply line at the  
pump fitting. Air eliminators are on the  
market that have potential. Also, electronic  
sight glasses are being used with good  
success. At times, new tubing must be run  
to the tank or new fittings put on. Just make  
sure you get the air out.  
5. To recondition the heating system in the fall season  
after a prolonged shut down, follow the instructions  
outlined in Section IV, Items A through M.  
CAUTION  
This boiler contains controls which may  
cause the boiler to shut down and not  
restart without service. If damage due to  
frozen pipes is a possibility, the heating  
system should not be left unattended in  
cold weather; or appropriate safeguards  
and alarms should be installed on the  
heating system to prevent damage if the  
boiler is inoperative.  
Any air leaks in the fuel line will cause an  
unstable flame and may cause delayed  
ignition noises. Use only flare fittings in the  
fuel lines.  
10. START-UP NOISE Late ignition is the cause of  
start-up noises. If it occurs recheck for electrode  
settings, flame shape, air or water in the fuel lines.  
11. SHUT DOWN NOISE If the flame runs out of  
air before it runs out of fuel, an after burn with  
noise may occur. That may be the result of a faulty  
cut-off valve in the fuel pump, or it may be air  
trapped in the nozzle line. It may take several firing  
cycles for that air to be fully vented through the  
nozzle. Water in the fuel or poor flame shape can  
also cause shut down noises.  
Q. FREQUENT WATER ADDITION  
IMPORTANT  
CHECK TEST PROCEDURE. A very good test for  
isolating fuel side problems is to disconnect the  
fuel system and with a 24" length of tubing, fire  
out of an auxiliary five gallon pail of clean, fresh,  
warm #2 oil from another source. If the burner  
runs successfully when drawing out of the  
auxiliary pail then the problem is isolated to the  
fuel or fuel lines being used on the jobsite.  
A leaky system will increase the volume of make-up  
water supplied to the boiler which can significantly  
shorten the life of the boiler. Entrained in make-up  
water are dissolved minerals and oxygen. When the  
fresh, cool make-up water is heated in the boiler the  
minerals fall out as sediment and the oxygen  
P. ATTENTION TO BOILER WHILE NOT IN  
OPERATION.  
escapes as a gas. Both can result in reduced boiler  
life. The accumulation of sediment can eventually  
isolate the water from contacting the cast iron.  
When this happens the cast iron in that area gets  
extremely hot and eventually cracks. The presence  
of free oxygen in the boiler creates a corrosive  
atmosphere which, if the concentration becomes  
high enough, can corrode the cast iron through  
from the inside. Since neither of these failure types  
are the result of a casting defect the warranty does  
not apply. Clearly it is in everyones best interest to  
prevent this type of failure. The maintenance of  
system integrity is the best method to achieve this.  
1. IMPORTANT  
IF BOILER IS NOT USED DURING WINTER  
TIME, IT MUST BE FULLY DRAINED TO  
PREVENT FREEZE DAMAGE.  
2. Spray inside surfaces with light lubricating or  
crankcase oil using gun with extended stem so as to  
reach all corners.  
3. With steam boilers, at end of season add sufficient  
water to fill boiler to top of water column and leave  
it that way until fall when water should be drained  
again to proper level. If at this time boiler water is  
dirty, drain water, flush out boiler, and refill with  
28  
(Non-Burnham Drawing  
Copy from other Manual)  
AQUASTAT SWITCHING ACTION WITHIN L8124C  
CONTROL  
The switching action within the L8124C control has  
EXAMPLE: Set point of 140°F; differential set at 25°F.  
On a temperature rise, R-B will break and R-W will make  
at 155°F. On a temperature fall, R-B will make and R-W  
will break at 130°F.  
three settings:  
1. high limit  
2. low limit  
3. adjustable differential  
Set low limit indicator at the minimum temperature  
recommended for domestic hot water supply. This setting  
must be at least 20°F below high limit setting to prevent  
one switch from locking out the other.  
HIGH LIMIT OPERATION -  
The high limit opens and turns off the burner when the  
water temperature reaches the set point. The high limit  
automatically resets after the water temperature drops past  
the set point and through the 10°F differential.  
Set the indicator at desired shutoff temperature.  
Set the differential the desired number of degrees.  
25°F differential gives longest burner cycles.  
AQUASTAT SWITCHING ACTION WITHIN L8148A  
CONTROLS  
LOW LIMIT OPERATION -  
On a temperature rise, with the adjustable differential  
at the minimum setting of 10°F, the burner circuit (R-B)  
breaks and the circulator circuit (R-W) makes at the low  
limit set point. On a temperature drop of 10°F below the set  
point, the R-B circuit makes and the R-W circuit breaks.  
The switching action in the L8148A control has one  
setting, the high limit. The switching relay is controlled by  
the low voltage room thermostat. On a call for heat, the  
relay contacts make to complete the line voltage circulator  
circuit and also the burner circuit if the boiler water  
temperature is below the high limit setting. The high limit  
switch shuts off the burner if boiler water temperature  
exceeds the high limit setting.  
ADJUSTABLE DIFFERENTIAL -  
At any differential setting greater than 10°F, the R-B  
make temperature and R-W break temperature will remain  
the same-control setting minus 10°F. The R-B break and R-  
W make temperature will be the set point temperature plus  
the difference between the differential setting and 10°F.  
Set the indicator at the desired shutoff temperature.  
SECTION V: BOILER CLEANING  
WARNING  
All boiler cleaning must be completed with burner service switch turned off. Boilers  
equipped with burner swing door have a potential hazard which can cause severe property  
damage, personal injury or loss of life if ignored. Before opening swing door, turn off  
service switch to boiler to prevent accidental firing of burner outside the combustion  
chamber. Be sure to tighten swing door fastener completely when service is completed.  
29  
smokepipe, burner mounting plate, burner swing door  
and all flue plates are secured in place.  
A. CLEAN THE FLUEWAYS (See Figure 26).  
1. Prior to cleaning boiler, lay a protective cloth or  
plastic over combustion chamber blanket to collect  
debris falling from flueways.  
1. Install the canopy taking care to align the gaskets  
without blocking the flueways. If gasket is  
damaged, replace as needed.  
2. For access to firebox  
2. Reinstall flue plates, making sure gasket on each  
plate is in place and forms gas tight seal. If  
damaged replace as needed.  
On boilers with burner swing door and flexible fuel  
line(s), remove fastener securing door and swing  
door open. For full access to firebox, remove burner  
and swing door from mounting plate by pulling  
hairpin cotter from bottom of hinge pin and  
removing pin from hinge. Set burner aside. Remove  
swing door mounting plate, see Figure 6.  
3. Reinstall jacket top panel and secure with sheet  
metal screws. Replace jacket upper right side access  
panel.  
4. Reinstall smokepipe on canopy and secure to collar  
with sheet metal screws.  
5. Install swing door mounting plate to front section  
with fasteners, see Figure 6.  
6. Reinstall burner in reverse order of disassembly  
outlined in paragraph A.2 above. For details, see  
Figure 6.  
3. For cleaning from the side:  
a. Lift the jacket's upper right side access panel off  
to expose the flue cleanout plates.  
b. Loosen nuts securing the flue cleanout plates  
and remove the plates. The insulation should be  
removed with the plates taking care not to  
damage the insulation.  
4. For cleaning from the top:  
a. Lift the jacket's upper right side access panel off  
to allow removal of the jacket top panel.  
b. Remove as much smokepipe as necessary to  
allow removal of the jacket top panel and  
canopy (smokebox).  
c. Remove the jacket top panel.  
d. Remove the canopy, being careful not to damage  
the ceramic fiber gasket.  
5. Using a 1¼” diameter wire or fibre bristle brush  
(30handle) clean the flueways. Brush from the top  
and/or side using horizontal and diagonal strokes  
for best results. DO NOT allow brush to strike the  
target wall or liner in the chamber.  
B. CLEAN TOP OF BOILER SECTIONS (if cleaning  
from the top).  
Figure 26: Cleaning of Boiler Flueways  
Brush and vacuum the tops of the boiler sections.  
C. CLEAN THE FIREBOX.  
WARNING  
Using wire or fibre bristle brush, clean crown of boiler  
and inside of water legs. DO NOT allow brush to strike  
target wall or blanket in the combustion chamber.  
The boiler must be connected to an approved  
chimney in good condition. Serious property damage  
could result if the boiler is connected to a dirty or  
inadequate chimney. The interior of the chimney flue  
must be inspected and cleaned before the start of the  
heating season and should be inspected periodically  
throughout the heating season for any obstructions.  
A clean and unobstructed chimney flue is necessary  
to allow noxious fumes that could cause injury or loss  
of life to vent safely and will contribute toward  
maintaining the boiler's efficiency.  
D. AFTER CLEANING, remove protective cloth with  
debris and vacuum as necessary, but be careful not to  
damage blanket. Inspect target wall, combustion  
chamber blanket, burner mounting plate insulation and  
burner swing door insulation for signs of damage. If  
damaged, replace as needed.  
E. REASSEMBLE BOILER.  
CAUTION: Do not start the burner unless canopy,  
30  
SECTION VI: REPAIR PARTS  
All V7 Series Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance  
in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair  
parts, please contact your Burnham Regional Sales Office as listed below.  
Burnham Corporation Regional Offices  
A. Burnham Corporation - Central & Western Regions  
P.O. Box 3079  
C. Burnham Corporation - Metropolitan Region  
P.O. Box 3079  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (717) 481-8408  
FAX: (717) 481-8409  
B. Burnham Sales Corporation - Northeast Region  
19-27 Mystic Avenue  
D. Burnham Corporation - Mid-Atlantic Region  
P.O. Box 3079  
Somerville, MA 02145  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
Phone: (617) 625-9735  
FAX: (617) 625-9736  
FAX: (717) 481-8409  
Contact Regional Office Indicated for your State  
Alabama  
Alaska  
A
A
A
A
A
A
B
D
A
A
A
A
A
A
A
A
A
A
B
D
B
A
A
A
A
A
Nebraska  
A
A
B
Oregon  
A
D
B
A
A
A
A
A
B
Nevada  
Pennsylvania  
Rhode Island  
South Carolina  
South Dakota  
Tennessee  
Texas  
Arizona  
New Hampshire  
New Jersey  
Arkansas  
California  
Colorado  
Connecticut  
Delaware  
Florida  
Atlantic, Burlington, Camden,  
Cape May, Cumberland,  
Gloucester, Mercer,  
Monmouth, Ocean, Salem  
Counties  
D
Utah  
Vermont  
Georgia  
Hawaii  
All other Counties  
C
A
Virginia  
New Mexico  
New York  
Albany, Fulton, Montgomery,  
Arlington,Accomack,Clarke,  
Idaho  
Fairfax,Frederick,Fauquier,  
Loudoun,Northampton and  
Prince William Counties  
All other Counties  
D
Illinois  
Indiana  
Rensselaer, Saratoga,  
Schenectady, Schoharie,  
Warren, Washington Counties  
All Other Counties  
B
Iowa  
A
A
D
D
A
A
Kansas  
Washington  
Kentucky  
Louisiana  
Maine  
C
A
A
Washington, D.C.  
West Virginia  
Wisconsin  
North Carolina  
North Dakota  
Ohio  
Maryland  
Massachusetts  
Michigan  
Minnesota  
Mississippi  
Missouri  
Montana  
Wyoming  
Athens, Belmont, Gallia,  
Jefferson, Lawrence, Meigs,  
Monroe, and Washington  
Counties  
D
All other Counties  
A
A
Oklahoma  
Canada  
A
31  
BARE BOILER ASSEMBLY  
Item  
No.  
Description  
Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79  
BARE BOILER ASSEMBLY (See Page 32 for Illustration)  
Front Section (Non-Htr.), Machined Water 71727019  
Front Section (Non-Htr.), Machined Water 71727015  
Front Section (Non-Htr.), Machined Steam 71727018  
1
---  
1
1
---  
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
---  
1A  
2
---  
---  
Front Section w/Htr. Opening, Machined  
Water  
71727016  
---  
---  
---  
---  
1
1
---  
---  
1
1
1
1
1
1
1
1
1
1
1
1
Front Section w/Htr. Opening, Machined  
Steam  
2A  
3
71727017  
Center Section  
Center Section  
7172202  
---  
---  
---  
1
---  
1
---  
1
2
---  
1
---  
2
---  
3
---  
4
---  
5
---  
6
---  
7
71727021  
4
Narrow Back Section (Non-Htr.), Machined 7172204  
---  
---  
---  
---  
---  
---  
---  
Wide Back Section (Non-Htr.), Machined  
Water  
4A  
71727033  
1
---  
---  
1
1
---  
---  
1
1
1
1
1
1
1
1
1
1
1
1
Wide Back Section (Non-Htr.), Machined  
Steam  
4B  
5
71727034  
---  
Rear Section w/Htr. Opening, Machined  
Rear Section w/Htr. Opening, Machined  
5" Cast Iron Slip Nipple  
7172203  
71727036  
7066003  
7066001  
8202701  
82027023  
82022033  
82027031  
82022043  
---  
---  
1
1
---  
---  
4
---  
1
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
---  
6
6
7
8
2
3
4
5
6
7
8
2½" Cast Iron Slip Nipple  
1
2
3
4
5
6
7
8
Rear Target Wall Insulation  
1
1
1
1
1
1
1
1
1
1
Combustion Chamber Liner, ½" x 23" x 4"  
Combustion Chamber Liner, ½" x 24" x 5"  
Combustion Chamber Liner, ½" x 23" x 8"  
Combustion Chamber Liner, ½" x 24" x 9"  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
---  
2
Combustion Chamber Liner, ½" x 23" x 12" 82027041  
Combustion Chamber Liner, ½" x 23" x 16" 82027051  
Combustion Chamber Liner, ½" x 23" x 20" 82027061  
Combustion Chamber Liner, ½" x 23" x 24" 82027071  
Combustion Chamber Liner, ½" x 23" x 28" 82027081  
Combustion Chamber Liner, ½" x 23" x 32" 82027091  
---  
---  
---  
---  
---  
---  
---  
---  
2
8A  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
2
Tie Rod, 3/8"-16 x 7¾" Lg.  
Tie Rod, 3/8"-16 x 12½" Lg.  
Tie Rod, 3/8"-16 x 17" Lg.  
Tie Rod, 3/8"-16 x 20¾" Lg.  
Tie Rod, 3/8"-16 x 25¼" Lg.  
Tie Rod, 3/8"-16 x 27½" Lg.  
Tie Rod, 3/8"-16 x 31½" Lg.  
Tie Rod, 3/8"-16 x 36½" Lg.  
80861072  
80861010  
80861011  
80861012  
80861013  
80861014  
80861015  
80861036  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
---  
---  
----  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
9
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
CONTINUED ON PAGES 34 AND 35  
33  
BARE BOILER ASSEMBLY (CONTINUED)  
CONTINUED FROM PAGE 33  
Item  
No.  
Description  
Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79  
BARE BOILER ASSEMBLY (See Page 34 for Illustration)  
10  
11  
Flue Cover Plate Assembly  
6112214  
8036068  
8036058  
7036002  
1
2
---  
1
2
1
1
1
3
---  
1
3
1
1
1
4
1
1
1
5
1
1
1
6
1
1
1
7
1
1
1
8
1
1
1
Heater Cover Plate Gasket - Front Heater  
---  
---  
---  
11A Heater Cover Plate Gasket - Rear Heater  
12  
Blank Heater Cover Plate (WB) - Front Heater  
---  
---  
Tapped Heater Cover Plate (WBTL) - Front  
Heater  
12A  
7036001  
7036020  
---  
---  
---  
---  
1
1
---  
---  
1
1
1
1
1
1
1
1
1
1
1
1
1
Blank Heater Cover Plate (SB & WB) - Rear  
Heater  
12B  
12C  
Tapped Heater Cover Plate (WBTL) - Rear  
Heater  
7036021  
6036036  
6031204  
6036031  
---  
---  
---  
---  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
---  
---  
222A Heater Carton Assy. - (WBT) Front Heater  
---OR---  
A54 Heater Carton Assy. - (WBT) Front Heater  
13  
---  
1
---  
1
---  
1
---  
1
---  
1
---  
---  
V1-2 Heater Assy. - (SBT & WBT) - Rear  
Heater  
13A  
1
13B V1-1 Heater Carton Assy. - (WBT) Rear Heater  
14 Burner Swing Door Mounting Plate  
14A Burner Swing Door Mounting Plate Insulation  
6036030  
7172705  
82027021  
72027014  
7172706  
82027022  
72027015  
7022701  
80861614  
80861667  
7026001  
8026015  
7202710  
611270211  
---  
1
1
1
1
1
1
2
1
1
1
1
1
1
---  
1
---  
1
1
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
1
1
1
1
1
1
1
1
1
15  
16  
Rope Gasket - Burner Mounting Plate - 53" Lg.  
Burner Swing Door  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16A Burner Swing Door Insulation  
16B Rope Gasket (Burner Swing Door) - 28" Lg.  
16C Hinge  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
16D Hinge Pin  
1
1
1
1
1
1
1
1
1
16E Hairpin Cotter  
1
1
1
1
1
1
1
1
1
17  
18  
19  
Observation Port Cover  
1
1
1
1
1
1
1
1
1
Spring 3/8" I.D. x ½" Lg.  
1
1
1
1
1
1
1
1
1
Canopy Sealing Strip (½" x 1" x 98")  
V72 Canopy Assembly, Type II  
V713 Canopy Assembly  
1
1
1
1
1
1
1
1
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
611270313 ---  
611270311 ---  
611270413 ---  
611270411 ---  
611270511 ---  
611270611 ---  
611270711 ---  
611270811 ---  
611270911 ---  
20  
V73 Canopy Assembly, Type II  
V714 Canopy Assembly  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
V74 Canopy Assembly, Type II  
V75 Canopy Assembly, Type II  
V76 Canopy Assembly, Type II  
V77 Canopy Assembly, Type II  
V78 Canopy Assembly, Type II  
V79 Canopy Assembly, Type II  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
35  
TS-39-112-D  
V713 and V714 FLUSH JACKET  
Item No. Description  
Part No.  
V713  
V714  
V713 and V714 Flush Jacket Components - Items 1 thru 6 Include Insulation As Part of Assembly  
1
2
Jacket Front Panel Assembly  
Jacket Rear Panel Assembly  
60427097  
60427096  
604270314  
604270414  
604270322  
604270422  
604270337  
604270437  
604270336  
604270436  
604270335  
604270435  
7042715  
1
1
1
1
1
---  
1
3
4
5
Jacket Left Side/Top Panel Assembly  
Jacket Top Panel Assembly  
---  
1
---  
1
---  
1
---  
1
Jacket Lower Right Side Panel Assembly  
---  
1
---  
1
Jacket Upper Right Side Access Panel Assembly without Heater Opening (WB  
Only)  
---  
1
6
7
---  
1
Jacket Upper Right Side Access Panel Assembly with Heater Opening (WBT Only)  
---  
Jacket Bracket (WB Only)  
Jacket Bracket (WBT Only)  
1
1
7042714  
37  
TS-39-109-D  
V72 Thru V79 FLUSH JACKET  
Item  
No.  
Description  
Part No.  
V72  
V73  
V74 V75 V76 V77 V78 V79  
V72 Thru V79 Flush Jacket Components - Items 1 thru 7 Include Insulation As Part of Ass'y  
Jacket Front Panel Ass'y w/o Htr. Opg. (Wtr. Blr.)  
Jacket Front Panel Ass'y w/o Htr. Opg. (Stm. Blr.)  
Jacket Front Panel Ass'y w/Htr. Opg. (Wtr. Blr.)  
Jacket Front Panel Ass'y w/Htr. Opg. (Stm. Blr.)  
Plastic Collar Extension-Jkt. Frt. Panel w/Htr. Opg.  
Jacket Rear Panel Assembly  
60427090  
60427091  
1
---  
---  
---  
---  
1
1
1
1
1
1
1
1
1
60427092  
60427094  
2
3
8032704  
1
1
1
1
1
1
60427093  
1
1
1
1
1
1
1
604270241  
604270341  
604270441  
604270541  
604270641  
604270741  
604270841  
604270941  
604270221  
604270321  
604270421  
604270521  
604270621  
604270721  
604270821  
604270921  
604270234  
604270334  
604270434  
604270534  
604270634  
604270734  
604270834  
604270934  
604270233  
604270333  
604270433  
604270533  
604270633  
604270733  
604270833  
604270933  
604270332  
604270432  
604270532  
604270632  
604270732  
604270832  
604270932  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
4
5
6
Jacket Left Side/Top Panel Assembly  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
Jacket Top Panel Assembly  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
Jacket Lower Right Side Panel Assembly  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
Jacket Upper Right Side Access Panel Assembly  
without Heater Opening  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
7
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
Jacket Upper Right Side Access Panel Assembly  
with Heater Opening  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
39  
V73 Thru V79 STEAM BOILERS - TRIM AND CONTROLS  
Item  
No.  
Description  
Part No.  
V73 V74 V75 V76 V77 V78 V79  
V73 Thru V79 STEAM BOILERS - TRIM AND CONTROLS (See Page 40 for Illustration)  
1. Draft Regulator  
1A  
1B  
DR-6 Draft Regulator  
DR-7 Draft Regulator  
8116029  
8116001  
1
1
1
1
---  
1
---  
1
---  
1
---  
---  
---  
---  
2. Instruction Envelope Containing:  
2A  
2B  
2C  
Installation and Operating Instructions  
10 Year Limited Warranty Mailer (Steam Boilers)  
I=B=R Pamphlet  
8142711  
81460121  
81460061  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3. Probe Low Water Cutoff  
Low Water Cutoff, Hydrolevel CG450 (less probe)  
80160628  
80160624  
3A  
Low Water Cutoff, McDonnell & Miller PS-801-120  
1
1
1
1
1
1
1
Low Water Cutoff, McDonnell & Miller PS-804-120  
Probe, Hydrolevel EL-1214 (Hydrolevel CG450)  
Limit, Honeywell PA404A1009  
80160662  
80160629  
80160300  
806603030  
806600508  
806601520  
806600003  
8056091  
3B  
3C  
3D  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Syphon, ¼ NPT x 4" x 180°  
3D1 Bushing, ¾ NPT x ¼ NPT  
3D2 Elbow, ¾ NPT  
3D3 Nipple, ¾ NPT x 2"  
3E  
Gage Glass Set, 6", ConBraCo 20-104-10  
4. Float Low Water Cutoff  
4A  
4B  
4C  
4D  
Low Water Cutoff, McDonnell & Miller 67  
80160597  
80160300  
806603030  
8056091  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limit, Honeywell PA404A1009  
Syphon, ¼ NPT x 4" x 180°  
Gage Glass Set, 6", ConBraCo 20-104-10  
5. Miscellaneous Trim and Controls  
5A  
5B  
Oil Primary Control, Honeywell R8184G1286  
80160416  
81660530  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Safety Valve, ¾ NPT, 15 psi, ConBraCo 13-511-  
08  
5B1 Coupling, ¾ NPT  
806602561  
806600221  
806603011  
806600507  
80160400  
80160426  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5B2 Nipple, ¾ NPT x 8"  
5C  
Drain Valve, ¾ NPT, ConBraCo 31-606-02  
5C1 Bushing, 1½ NPT x ¾ NPT  
5D  
5E  
Limit, Honeywell L4006A2015 (SBPT & SBFT)  
Well, ¾ NPT x 1½", Honeywell 123890A  
41  
V72 Thru V79, V713 and V714 WATER BOILERS - TRIM AND CONTROLS  
ITEM  
NO.  
DESCRIPTION  
Part No.  
V72 V713 V73 V714 V74 V75 V76 V77 V78 V79  
V72 Thru V79, V713 and V714 WATER BOILERS - TRIM AND CONTROLS (See Page 42 for Illustration)  
1. DRAFT REGULATOR  
1A  
1B  
DR-6 Draft Regulator  
DR-7 Draft Regulator  
8116029  
8116001  
1
1
1
1
1
1
1
---- ---- ----  
---- ---- ---- ---- ---- ---- ----  
1
1
1
2. INSTRUCTION ENVELOPE CONTAINING:  
2A  
2B  
Installation and Operating Instructions  
8142711  
81460135  
81460061  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limited Warranty Mailer (Water  
Boilers)  
2C I=B=R Pamphlet  
3. CONTROLS  
Honeywell L8148A1090 Hi Limit, Circ. 80160449U  
1
1
1
1
1
1
1
1
1
1
Relay (WB)  
3A  
--OR --  
Honeywell L8124C1102 Hi & Lo Limit, 80160406U  
Circ. Relay (WBT)  
----  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Honeywell #123870A Immersion Well,  
80160426  
¾NPT x 1½ Insulation (WB)  
3B  
-- OR --  
Honeywell #123872A Immersion Well,  
80160497 ----  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
½NPT x 3" Insulation (WBT)  
Honeywell R4184D (1027/1001)  
Protectorelay  
3C  
80160473  
1
4. CIRCULATOR & PIPING (Packaged Boiler Only)  
4A  
4B  
Circulator, Taco 007F (position 2)  
Gasket, Taco "00" Series Circulator  
8056007  
806602006  
806602014  
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
4C Circulator Flange, 1½"NPT  
Cap Screw, Hex Head, 7/16" -14 x  
4D  
80861301  
4
4
4
4
4
4
4
4
4
4
1½"  
4E  
4F  
Hex Nut, 7/16" - 14  
80860406  
806600011  
806601003  
806600006  
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
Nipple, 1½"NPT x18"  
4G Tee, 1½" x ¾" x 1½"NPT, Black  
4H Nipple, 1½"NPT x 3"  
5. MISCELLANEOUS WATER TRIM  
Relief Valve, ¾"NPT, F/F 30 LB,  
5A  
81660319  
806600221  
8056169U  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Conbraco 10-408-05  
5B  
Nipple, ¾"NPT x 8"  
Te m p/ Pr es su re Gau ge, 2½" Dia.,  
5C  
ENFM #41042.5210  
Drain Cock, ¾"NPT Short Shank  
5D  
5E  
806603011  
806603515  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(WB and WBT), Conbraco #31-606-02  
Plug, Square Head, 1½"NPT  
(Packaged)  
Reducing Bushing, 1½" x ¾"NPT  
80660507  
(Knockdown)  
43  
Beckett AFG Burner  
BECKETT OIL BURNER PART NOS. FOR V7 SERIES BOILERS  
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also  
provide the name of the part(s) and part number as listed below.  
Boiler Model  
V72  
V713  
V73  
V714  
V74  
V75  
V76  
V77  
V78  
V79  
Air Tube Combination  
Beckett's Spec No.  
Air Band  
AFG70MB AF72YH  
AF44XN  
AF72YY  
AF44WH  
AF44RA  
AF44XO AF72WK AFG50MD AFG50MD  
BCB6111 BCB6119 BCB6112 BCB6120 BCB6113 BCB6114 BCB6115 BCB6116 BCB6117 BCB6118  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
5880  
3666  
5636  
149  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
5880  
3666  
5636  
149  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
[1]  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
[1]  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
3492  
4150  
4198  
3709  
4198  
2999  
2454  
---  
Air Band Nut  
Air Band Screw  
Air Shutter  
Air Shutter Screw  
Blower  
Coupling  
Low Firing Rate Baffle  
Bulkhead Knurled Locknut  
Connector Tube Assembly  
Electrode Clamp  
Electrode Clamp Screw  
Electrode Insulator Assembly  
Spider Spacer Assembly  
Escutcheon Plate  
Adjusting Plate Assembly  
Head  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
3666  
5636  
149  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
3493  
---  
4219  
5780  
5503  
---  
4219  
5780  
5503  
---  
5941  
5913  
4221  
31498  
5877  
2456  
213  
5941  
5913  
4221  
31498  
5877  
2456  
213  
5912  
4221  
31498  
5877  
2456  
213  
360003 [4] 360004 360006 [5] 360004 [6] 360006 [7] 360012 360016  
Head Screws  
4221  
31498  
5877  
4221  
31498  
5877  
4221  
31498  
5877  
4221  
31498  
5877  
4221  
31498  
5877  
4221  
31498  
5877  
2456  
213  
4221  
31498  
5877  
2456  
213  
Flange Gasket  
AFG Housing  
Motor  
2456  
2456  
2456  
2456  
2456  
Nozzle Adapter  
213  
213  
213  
213  
213  
Nozzle Line Electrode Assembly NL72BN  
NL72YH  
2460  
NL44YH  
2460  
NL72YY  
2460  
NL44WP  
2460  
NL44YB  
2460  
NL44X0 NL72WK NL50MD  
NL50MD  
2460  
3383P  
51771  
4217  
4292  
51304  
10251  
5770  
7006  
21789  
Pump  
2460  
3384  
2460  
3383P  
51771  
4217  
2460  
None  
51771  
4217  
2460  
3383P  
51771  
4217  
Static Plate  
3384  
[2] 3384  
51771  
4217  
3384  
[3] 3383P  
51771  
4217  
3384  
Ignitor  
51771  
4217  
51771  
4217  
51771  
4217  
51771  
4217  
Ignitor Hinge Screw  
Ignitor Holding Screw  
Ignitor Gasket Kit  
Wire Guard  
4292  
4292  
4292  
4292  
4292  
4292  
4292  
4292  
4292  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
51304  
10251  
5770  
Junction Box  
Flame Detector  
Oil Solenoid Valve  
7006  
7006  
7006  
7006  
7006  
7006  
7006  
7006  
7006  
21789  
21789  
21789  
21789  
21789  
21789  
21789  
21789  
21789  
[1] 5880 in V73R, V73M and V74R [2] 3912 in V73M and V73R [3] 3384 in V74M and V74R [4]360000 in V73R; 360003 in V73M  
[5] 360003 in V74R and V74M [6] 360003 in V75R; 360006 in V75M [7] 360006 in V76R; 360012 in V76M  
45  
Print word document  
46  
47  

Blaupunkt LAS VEGAS 7 645 650 310 User Manual
Bushnell Binoculars 190125 User Manual
Canon Camcorder VIXIA HF630 User Manual
Casio Fx 115esplus Scientific Calculator fx115ESPlus User Manual
Directed Audio 6550 User Manual
Earthquake Sound DBXI 15 User Manual
HP (Hewlett Packard) Hewlett Packard Car Amplifier 8447F User Manual
Infinity Systems Inc Car Speaker BU 2 User Manual
Jensen Phase Linear SD1413 User Manual
Jensen POWER 880 User Manual