Price - $3.00
INSTALLATION, OPERATING
AND
SERVICE INSTRUCTIONS
SERIES 2 (model B)
GAS BOILERS
For service or repairs to boiler, call your heating contractor. When seeking information on boiler,
provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
Boiler Serial Number
Installation Date
2 ____-_______
6_ _ _ _ _ _ _
Heating Contractor
Phone Number
Address
PartNo.81417032R10-11/99
Figure 1
Gas
Approx.
Shipping
Weight
(lb.)
Dimensions [inches]
Boiler
Model
Connection Water
Recommended
Vent Size
[1] [2]
For
Content
Number
Automatic [gallons]
Gas Valve
A
B
C
D
E
F
G
202
202X
203
204
205
206
207
208
209
210
18-3/4 10-3/4 6-3/8
4
4
4
5
6
6
7
7
8
8
45-5/8
45-5/8
45-5/8
47-1/8
48-1/2
48-1/2
8-1/2
8-1/2
8-1/2
9-1/8
9-3/4
9-3/4
10 [3]
4-3/4
4-3/4
4-3/4
5-1/4
5-1/4
1/2
1/2
1/2
1/2
1/2
1/2
3/4
3/4
3/4
3/4
2.5
3.2
3.2
4
3" dia. x 15 ft.
4" dia. x 15 ft.
4" dia. x 15 ft.
5" dia. x 15 ft.
6" dia. x 15 ft.
6" dia. x 15 ft.
7" dia. x 15 ft.
7" dia. x 15 ft.
8" dia. x 15 ft.
8" dia. x 15 ft.
212
262
262
306
354
414
458
514
550
608
20
20
12
12
6
6
23-1/4 15-1/4 7-5/8
26-1/2 18-1/2 9-1/4
29-3/4 21-3/4 10-7/8
4.7
5.5
6.2
7
33
25
12-1/2
50-1/8 10-3/8 6-5/8
50-1/8 10-3/8 6-5/8
36-1/4 28-1/4 14-1/8
39-1/2 31-1/2 15-3/4
42-3/4 34-3/4 17-3/8
52
52
11
11
7-1/4
7-1/4
7.7
8.5
[1] 15' chimney height is from bottom of draft hood opening to top of chimney.
[2] Refer to the National Fuel Gas Code, Apendix G for equivalent areas of circular and rectangular flue linings.
Maximum Allowable Working Pressure - 30 PSI (Water Only)
[3] 202 only. Dimension 'G' includes allowance for 4" x 3" reducer furnished with boiler. See Figure 8.
3
SECTION I - INSTALLATION INSTRUCTIONS
F. Slide the boiler forward or backward off the skid using
1. INSPECTSHIPMENT carefullyforanysignsofdamage.
the two wooden slats as runners.
All equipment is carefully manufactured, inspected and
packed. Our responsibility ceases upon delivery of Boiler to
the carrier in good condition. Any claims for damage or
shortage in shipment must be filed immediately against the
carrier by the consignee. No claims for variances or short-
ages will be allowed by Boiler Manufacturer unless pre-
sented within sixty (60) days after receipt of equipment.
6. Move boiler to permanent position.
7. PROVIDE CLEARANCE and AIR for COMBUS-
TIONandVENTILATION.
2. BOILERINSTALLATIONmustconformtotherequire-
ments of the authority having jurisdiction, or in the absence
of such requirements, to:
U.S.A.-
National Fuel Gas Code, ANSI Z223.1,
obtainable from the American Gas Association,
1515 Wilson Blvd., Arlington (Rosslyn), VA
22209.
A. CLEARANCES
1.ALL INSTALLATIONS - Practical service clearances
must be considered (see Figure 1). A minimum of
24" from the left side and front jacket panels is
recommended for servicing but may be reduced to
minimum shown in Figure 2. Subject to boiler and
system piping, left side clearance may be reduced to
1" if right side clearance is increased to 9".
2.ALCOVE INSTALLATIONS - An alcove is consid-
ered a closet as shown in Figure 2 less front. Height
clearance may be reduced to 27".
When required by the authority having juris-
diction, the installation must conform to
ANSI/ASME No. CSD-1.
CANADA - "Installation Codes for Natural and LP Gas
Burning Appliances and Equipment, CAN/
CGA-B149.1 or .2-latest edition obtainable
from the Canadian Gas Association, 55 Scars-
dale Road, Don Mills, Ontario, Canada M3B
2R3.
3. UNCONFINEDSPACE(seedefinition,Paragraph(B)
below) - Height clearance may be reduced to 27".
3. TheseGasBoilersareDESIGNCERTIFIEDFOR
INSTALLATIONONCOMBUSTIBLEFLOORING.DONOT
INSTALLTHESEBOILERSONCARPETING.
4. LOCATEBOILERinfrontoforbehindinstallation
position before removing Crate. Locate on a level floor as
close to chimney as possible. For basement installations,
provide a solid base such as concrete, if floor is not level or
if water may be encountered on floor around Boiler.
The boiler shall be installed such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during boiler operation and service
(circulator replacement, control replacement, etc.).
5. REMOVE CRATE-
A. Remove all crate fasteners. Lift off outside container.
B. Remove all screws and brackets securing boiler to
skid.
C. Save two of the wooden slats from the container sleeve
for use in Steps D & E.
D. Tilt the boiler to one side and slide a wooden slat
under the two raised feet.
E. Tilt the boiler to the other side and slide another
wooden slat under the two raised feet.
Figure 2: Minimum Clearances
4
B. PROVIDECOMBUSTIONANDVENTILATIONAIRin
accordance with applicable provisions of local building
codes, or: U.S.A. - National Fuel Gas Code, NFPA 54/
ANSI Z223.1, Section5.3, Air for Combustionand
Ventilation; Canada - Natural Gas Installation Code,
CAN/CGA-B149.1, or Propane Installation Code,
CAN/CGA-B149.2,Part5,VentingSystemsandAir
Supply for Appliances.
1.CLOSET INSTALLATIONS (confined space) in a
building of other than unusually tight construction
(see definition below), provide combustion and
ventilation air as shown in Figure 2.
2.Installations other than Paragraph (1) above:
a. Determine volume of space (boiler room). Rooms
communicating directly with space (through
openings not furnished with doors) are considered
part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
b. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
c. Determine type of space. Divide Volume by Total
Input.
per 4,000 Btu per hour input of all equipment in
space. Duct cross-sectional area shall be same as
opening free area.
iii.Horizontal ducts. Minimum free area of 1 square
inch per 2,000 Btu per hour input of all equipment in
space. Duct cross-sectional area shall be same as
opening free area.
g.Ventilation Duct Louvers and Grilles. Equip
outside openings with louvers to prevent entrance
of rain and snow, and screens to prevent entrance of
insects and rodents. Louvers and grilles must be
fixed in open position or interlocked with
equipment to open automatically before burner
operation. Screens must not be smaller than ¼ inch
mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to
provide the required free area. If free area of louver
or grille is not known, assume wood louvers have
20-25 percent free area and metal louvers and
grilles have 60-75 percent free area.
i. If result is greater than or equal to 50 ft³ per 1,000
Btuh, space is considered an unconfined space.
ii.If result is less than 50 ft³ per 1,000 Btuh, space is
considered a confined space.
d.Determine building type. A building of unusually
tight construction has the following characteristics:
i. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
rating of 1 perm or less with openings gasketed
and sealed, and
8. CONNECT GAS SERVICE from Meter to gas control
assembly in accordance with Local Piping Codes and
requirements of Gas Company, see Figure 1. They may
require piping of larger size than Control Assembly
Connection, especially if run from meter is long or includes
several elbows. (See Figure 1 for size of Gas Connection to
gas control assembly).
This piping is to be supplied by the installer and must
include a trap, a ground joint union and a manual shutoff
valve upstream of the gas control assembly outside of the
jacket when codes require, see Figure 1. A pipe thread
compound resistant to the action of liquefied petroleum
gases should be applied to all threaded joints in the gas
piping. Pressure testing of the Gas Supply Piping Boiler
and its connections is required before placing the boiler in
operation.
The boiler and shutoff valve must be disconnected
from the gas supply piping system during any pressure
testing at pressures greater than ½ psig.
The boiler must be isolated from the gas supply piping
system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system
at pressures equal to or less than ½ psig.
ii. Weather-stripping has been added on openable
windows and doors, and
iii.Caulking or sealants applied in joints around
window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations,
and at other openings.
e. For boiler located in a building of other than
unusually tight construction, adequate combustion
and ventilation air is normally provided by fresh air
infiltration through cracks around windows and
doors.
f. For boiler located in building of unusually tight
construction, provide outdoor air through two
permanent openings which communicate directly or
by duct with the outdoors or spaces (crawl or attic)
freely communicating with the outdoors. Locate one
opening within 12 inches of top of space. Locate
remaining opening within 12 inches of bottom of
space. Minimum dimension of air opening is 3
inches. Size each opening per following:
i. Directcommunicationwithoutdoors. Minimumfree
area of 1 square inch per 4,000 Btu per hour input of
all equipment in space.
RECOMMENDED SIZING OF GAS SUPPLY
PIPING TO BOILER FOR NATURAL GAS - shall be such
as to provide the required supply of gas without undue loss
of pressure between meter and the boiler. Gas supply piping
should be sized in accordance with the Tables 1, 2 and 3.
The following shall be taken into account:
A. Allowable loss of pressure to assure a burner manifold
pressure of 3½" water.
B. Supply of gas to be provided in cubic feet.
C. Length of piping and number of fittings.
D. Specific gravity of gas.
E. Correction factor for specific gravity.
ii. Vertical ducts. Minimum free area of 1 square inch
5
entering the boiler, see Figure 4. Also consult I=B=R
Installation and Piping Guides.
9. BOILERPIPING
If this Boiler is connected to heating coils located in
air handling units where they may be exposed to
refrigerated air, the boiler piping must be equipped
with flow control valves to prevent gravity circulation
of boiler water during the operation of the cooling
system.
CAUTION
Failure to properly pipe boiler may result in
improper operation and damage to boiler or
building.
H. Use a boiler bypass if the boiler is to be operated in a
system which has a large volume or excessive radia-
tion where low boiler water temperatures may be
encountered (i.e. converted gravity circulation system,
etc.).
A. CLEARANCES - Hot water pipes do not require
clearance from combustible construction.
B. Install drain cock and safety relief valve as shown in
Figure 4. Note - Safety relief valve must be in vertical
position.
Remove the circulator and install a pipe tee between the
circulator and boiler return along with a second tee in
the supply piping as shown in Figure 5. The bypass
should be the same size as the supply and return lines
with valves located in the bypass and supply outlet as
illustrated in Figure 5 in order to regulate water flow
to maintain higher boiler water temperatures.
Set the by-pass and boiler supply valves to a half
throttle position to start. Operate boiler until the
system water temperature is at a normal operating
range.
C. Pipe safety relief valve discharge to floor.
WARNING
Safety relief valve discharge piping must
be piped near floor to eliminate potential
of severe burns. Do not pipe in any area
where freezing could occur. Do not install
any shut-off valves.
Adjust the valves to provide 180° to 200°F supply
water temperature. Opening the boiler supply valve
will raise the system temperature, while opening the
by-pass valve will lower the system supply tempera-
ture.
D. Install circulator with flanges, gaskets and bolts
provided. Five foot long circulator harness allows
circulator to be mounted on supply or return. Connect
harness to circulator and secure any excess conduit.
E. For heating only system piping, see Figure 3. Consult
alsoI=B=RInstallationGuides.
F. Space heating and domestic water heating with Alliance
water heater (intermittent circulation only). Install
Alliance water heater as a separate heating zone. Refer
to Alliance Installation, Operating and Service Instruc-
tions for additional information.
I. A hot water boiler installed above radiation level must
be provided with a low water cutoff device as part of
the installation.
J. OXYGEN CORROSION:
Oxygen contamination of the boiler water will cause
corrosion of the iron and steel boiler components,
which can lead to failure. As such, any system must be
designed to prevent oxygen absorption in the first
place or prevent it from reaching the boiler. Problems
caused by oxygen contamination of boiler water are not
G. If this boiler is used in connection with refrigeration
systems, the boiler must be installed so that the chilled
medium is piped in parallel with the heating boiler using
appropriate valves to prevent the chilled medium from
0.3 inch w.c. Pressure Drop
Length
0.5 inch w.c. Pressure Drop
[Feet]
½
¾
1
1¼
½
¾
1
1¼
10
20
30
40
50
60
70
80
90
100
132
92
73
63
56
50
46
43
40
38
278
190
152
130
115
105
96
520
350
285
245
215
195
180
170
160
150
1,050
730
590
500
440
400
370
350
320
305
175
120
97
360
250
200
170
151
138
125
118
110
103
680
465
375
320
285
260
240
220
205
195
1,400
950
770
660
580
530
490
460
430
400
82
73
66
61
57
53
50
90
84
79
6
Table 2: Equivalent Length of Fittings
Nominal Pipe Size
Fitting
Table 3: Specific Gravity Correction Factors
Specific
Gravity
Correction
Factor
Specific
Gravity
Correction
Factor
½
¾
1
1
1¼
1.6
3.5
6.9
0.50
0.55
0.60
0.65
0.7
1.10
1.04
1.00
0.96
0.93
0.9
1.30
1.40
1.50
1.6
1.07
1.04
1.00
0.97
0.94
45° Ell
90° Ell
0.7
1.6
3.1
1.2
2.6
5.2
2.1
4.1
Tee (As Elbow)
covered by Burnham's standard warranty.
There are many possible causes of oxygen contamina-
tion such as:
1.Addition of excessive make-up water as a result of
system leaks.
1.7
0.75
0.8
0.87
2. Absorption through open tanks and fittings.
3. Oxygen permeable materials in the distribution system.
In order to insure long product life, oxygen sources
should be eliminated. This can be accomplished by
taking the following measures:
C. Position the mounting bracket (with switch attached)
onto the lower edge of the draft hood skirt by locating
the center tooth (with the #10 sheet metal screw) on the
outside and the other two teeth inside the draft hood
skirt. SeeFig. 6.
1.Repairing system leaks to eliminate the need for
addition of make-up water.
2.Eliminating open tanks from the system.
3.Eliminating and/or repairing fittings which allow
oxygen absorption.
4.Use of non-permeable materials in the distribution
system.
5. Isolating the boiler from the system water by installing
a heat exchanger.
D. Slide the mounting bracket up tight against the lower
edge of the draft hood skirt, so that the #10 sheet metal
screw is above the skirt's stiffening rib.
E. Secure the bracket in this position by tightening the
#10 sheet metal screw against the outer surface of the
draft hood skirt.
F. Reinsert the excess power cord through the jacket side
panel hole to take the slack out of the power cord
running up to the blocked vent switch.
G. Reposition the strain relief bushing around the power
cord at the jacket side panel, pinch the two halves of
the bushing together, and snap it back into the hole in
10. INSTALLDRAFTHOODwithoutmodificationonoutlet
of flue collector (See Figure 1). Secure with sheet metal
screws.
11. INSTALLBLOCKEDVENTSWITCH
The blocked vent switch assembly shipped taped to the top
of the boiler includes a power cord and a switch attached to
a mounting bracket. The mounting bracket has a three
tooth staggered comb stamping at one end with a #10 sheet
metal screw in the center tooth.
A. Untape the blocked vent switch assembly from the top
of the boiler and uncoil the power cord.
B. Pinch the black strain relief bushing installed in the
jacket right side panel to dislodge it from the jacket
and pull just enough of the black power cord out so the
blocked vent switch will reach the near side of the draft
hood skirt. Do not pull out more power cord than
necessary.
Figure 3: Boiler Piping
7
Figure 4: Recommended Piping for Combination
Heating & Cooling (Refrigeration) Systems
the jacket side panel to secure the power cord to the
jacket.
H. Be sure the power cord, mounting bracket, and switch
are secure and located as shown in Figure 6.
WARNING
Failure to properly install and use this
Blocked Vent Switch may result in property
damage, personal injury or loss of life.
Figure 6
A. The vent damper should be the same size as the outlet
of the Draft Hood. (See Figure 1) Unpack the damper
carefully-DONOTFORCEITCLOSED!Forcingthe
damper may damage the gear train and void the
warranty. The damper assembly includes a prewired
connection harness for use on all 24V Standing Pilot or
intermittent ignition control systems.
12. TOMEETFEDERALLYMANDATEDEFFICIENCIES,
THISBOILERMUSTBEEQUIPPEDWITHAVENT
DAMPER.
OPENTHEVENTDAMPERCARTONandremovethe
InstallationInstructions.READTHEINSTALLATION
INSTRUCTIONSTHOROUGHLYbeforeproceeding.
The automatic gas control valve supplied on each
Series 2 boiler provides the reduncancy referenced in the
vent damper Installation Instructions.
B. Refer to Figure 7 in this manual.
C. Mount the vent damper assembly on the draft hood
without modification to either. (Refer to instructions
packed with the vent damper for specific instructions).
This is a must for the wiring harness to fit and the
damper position indicator to be visible to the users.
NOTICE
Please refer to the specifications,
installation instructions and troubleshooting
guide packed in the vent damper carton for
complete detailed installation instructions.
Also refer to Figure 7 in this manual.
D. Install the 90° BX connector attached to the flexible
conduit in the 7/8" knockout on the left side of the
jacket. Plug the factory wired Vent Damper Harness
into the polarized receptacle. Install a cable clamp
around the flexible conduit and attach to the Jacket top
panel. (SeeFigure7).
Figure 5
8
installed above the bottom of chimney to prevent
blockage.
E. Continuous Ignition (Standing Pilot) Only. Remove
knockout from vent damper blade.
G. Vent pipe should slope upward from draft hood to
chimney not less than one inch in four feet. No portion
of vent pipe should run downward or have dips or
sags. Vent pipe must be securely supported.
H. Vent pipe must be inserted into but not beyond inside
wall of chimney liner. Seal tight between vent pipe
and chimney.
F. Size 202 Only. Install 4" x 3" reducing fitting on vent
damper outlet (or draft hood outlet for Canadian boiler
not equipped with vent damper).
13. INSTALL VENT CONNECTOR from reducing fitting
(202 Only), draft hood or damper to chimney, see Fig. 8.
I. Do not install non-listed (AGA, CGA, ETL or UL) vent
damper or other obstruction in vent pipe.
14. IFANEXISTINGBOILERISREMOVED-
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too
large for proper venting of the appliances remaining to it.
At the time of removal of an existing boiler, the follow-
ing steps shall be followed with each appliance remaining
connected to the common venting system placed in operation,
while the other appliances remaining connected to the
common venting system are not in operation:
A. Seal any unused openings in the common venting
system.
B. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, and other deficiencies
which could cause an unsafe condition.
C. Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range-hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
A. Vent installation shall be in accordance with local
building codes; or the local authority having jurisdic-
tion; or the National Fuel Gas Code, ANSI Z223.1/
NFPA 54; or the Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel Burning Appliances, ANSI/NFPA
211. Both of the aforementioned standards, ANSI
Z223.1 and ANSI/NFPA 211, specify Type B and Type
L double wall metal vents and fire clay tile lined
masonry chimneys as suitable chimney constructions
for Category I, draft hood equipped appliances, such as
this Series 2 boiler. Both standards prohibit the use of
unlined masonry construction as a chimney, with the
exception in ANSI Z223.1/NFPA 54 that "Where
permitted by the authority having jurisdiction, existing
chimneys shall be permitted to have their use continued
when an appliance is replaced by an appliance of similar
type, input rating, and efficiency." ANSI/NFPA 211
prohibits the use of single wall metal vent as a chimney,
while ANSI Z223.1 allows it under very restrictive
conditions. In Canada refer to the Natural Gas Installa-
tionCode,CAN/CGA-B149.1ortheLPGasInstallation
Code,CAN/CGA-B149.2-latestedition.
B. Do not connect into same leg of chimney serving an
open fireplace.
C. Inspect chimney for obstructions or restrictions and
remove. Clean chimney if necessary.
D. Place in operation the appliance being inspected. Follow
the Lighting (or Operating) Instructions. Adjust
thermostat so appliance will operate continuously.
E. Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or
pipe.
F. After it has been determined that each appliance remain-
ing connected to the common venting system properly
vents when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any other
gas burning appliance to their previous conditions of use.
G. Any improper operation of the common venting system
should be corrected so the installation conforms with the
National Fuel Gas Code, NFPA 54/ANSI Z223.1. When
resizing any portion of the common venting system, the
common venting system should be resized to approach
the minimum size as determined using the appropriate
tables in Part 11 in the National Fuel Gas Code, NFPA
D. Vent pipe to chimney must not be smaller than outlet
on draft hood or damper. Although single wall vent
pipe may be used, Type B is recommended. The
venting system must be arranged so that only the
boiler is served by the damper device. Installation per
paragraph 12 complies with this provision.
E. Where two or more appliances vent into a common
vent, the area of the common vent should at least
equal the area of the largest vent plus 50% of the area
in the additional vents. Do not connect the vent of this
appliance into any portion of mechanical draft system
operating under positive pressure.
F. Vent pipe should have the greatest possible initial rise
above the draft hood consistent with the head room
available and the required clearance from adjacent
combustible building structure. Vent Pipe should be
9
Figure 7: Plug-in Damper Installation
10
54/ANSIZ223.1.
16. INSTALLELECTRICWIRINGinaccordancewith
National Electric Code or the Canadian Electrical Code and
local regulations. See Figures 11 through 14 for applicable
wiring diagram. A separate Electrical Circuit should be run
from meter with a Fused Disconnect Switch in this Circuit.
When installed, the boiler must be electrically grounded in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70,
and/ortheCSAC22.1ElectricalCode, ifanexternalelectrical
source is utilized.
15. INSTALLAROOMTHERMOSTATonaninsidewall
about four feet above floor. Never install thermostat on an
outside wall or where it will be influenced by drafts, hot or cold
water pipes, lighting fixtures, television, rays of the sun or near
a fireplace. Keep large furniture away from thermostat so there
will be free movement of room air around this control.
Heat Anticipator in Thermostat should be set to match the
requirements of the control to which it is connected. See Table
4. If system tends to overheat above the thermostat's
temperature setting, reduce heat anticipator setting by .1 or.2
amps. If system tends to short cycle without reaching desired
room temperature, increase heat anticipator setting by .1 or .2
amps.
For zone valve wiring, a separate 24V transformer is
required rather than attempting to use the boiler mounted
control. Consult zone valve manufacturer for assistance.
17. VENTDAMPERSEQUENCEOFOPERATION
Effikal and Johnson Damper
Figure 8: Typical Vent Installation
Table 4: Wiring Diagrams and Heat Anticipator Settings
Wiring Diagram
Thermostat Heat
Ignition Type
Circulation Method
Anticipator Setting [Amps]
Figure Number
11
Page Number
13
Continuous
Intermittent
0.6
1.0
(Standing Pilot)
Constant/Gravity
14
18
Intermittent
0.6
1.0
12
13
14
16
Intermittent
Constant/Gravity
If system tends to overheat above thermostat's temperature setting, reduce heat anticipator setting by 0.1
or 0.2 amps. If system tends to shortcycle without reaching desired room temperature, increase heat
anticipator setting by 0.1 or 0.2 amps.
11
is deenergized - closing contacts which energize the
damper motor. This causes the damper to close. When
the damper blade reaches the fully closed position, the
damper motor is de-energized.
A. The Vent Damper is continuously powered at Terminal
1.
B. When there is a call for heat, the damper relay coil is
energized through Terminal 5 if all limits ahead of the
damper are satisfied.
C. The relay coil closes contacts which energize the
damper motor, causing the damper to open.
D. When the damper blade reaches the fully open posi-
tion, power is sent back to the ignition circuit through
Terminal 2 and the damper motor is de-energized.
E. When the call for heat is satisfied, the damper relay coil
POWER FAILURE- The damper blade will stop in the
position it was in when power failed. (Combustion can
never take place unless the damper blade is in the fully
open position.)
Figure 9: Vent Damper Schematic Wiring Diagram
12
Figure 11: Wiring Diagram, 24 Volt Standing Pilot and Intermittent Circulation
SEQUENCE OF OPERATION
2. Blocked Vent Switch
In the event excessive blockage in the vent system is
developed the blocked vent switch will open interrupt-
ing power to the gas valve. The main burners will be
extinguished immediately, the circulator will continue
to operate, and the vent damper will remain open until
the thermostat is turned off. The source of blockage
must be corrected by trained and skilled personnel
from a qualified service agency before resetting
switch.
NORMAL OPERATION
1. When the thermostat call for heat, the vent damper
will open (see paragraphs 17A through 17D). The
circulator is started through a relay and at the same
time the gas valve is energized allowing main gas flow
and ignition of main burners.
2. Where condensation of flue gas is encountered in
boiler flues a reverse acting circulator control should
be installed to stop the circulator before the boiler
water temperature drops to that which flue gas
condensation may occur.
3. Flame Rollout Switch
In the event excessive blockage in the boiler section
flue passageways is developed the flame rollout switch
will open interrupting power to the gas valve. The
main burners will be extinguished immediately, the
circulator will continue to operate and the vent
damper will remain open until the thermostat is
turned off. If the flame rollout switch is activated do
not attempt to place the boiler in operation. The source
of blockage must be corrected and the flame rollout
switch replaced by trained and skilled personnel from
a qualified service agency.
3. After the thermostat is satisfied the main valve will
close and main burner flames will be extinguished.
The vent damper will close (see paragraph 17E).
SAFETY SHUTDOWN
1. High Limit Switch
In the event excessive boiler water temperature is
developed the high limit switch will open interrupting
power to the gas valve. The main burners will be
extinguished immediately, and the vent damper will
close at the same time, but the circulator will continue
to operated. Normal operation will be resumed when
the boiler water temperature drops to a point where
the high limit switch closes.
4. Pilot
The thermocouple proves pilot flame and in the
absence of such within 45-90 seconds causes the
combination gas valve, which is equipped with a
100% shut-off provision, to be de-energized, thus,
preventing main gas or pilot gas flow.
13
Figure 12: Wiring Diagram, Intermittent Ignition and Intermittent Circulation
14
SEQUENCE OF OPERATION
NORMAL OPERATION
developed the blocked vent switch will open interrupt-
ing power to the VENT DAMPER and GAS VALVE.
Main burners and pilot burner will be extinguished
immediately, the VENT DAMPER will close and the
CIRCULATOR will continue to operate. The source
of blockage must be corrected by trained and skilled
personnel from a qualified service agency before
resetting switch.
1. When the THERMOSTAT calls for heat, the RELAY
is energized. The CIRCULATOR starts and the
VENT DAMPER is opened (see Paragraphs 17A
through 17D). When the damper blade reaches the
fully open position, the GAS VALVE powers the
igniter circuit and opens the pilot valve.
3. Flame Rollout Switch
In the event excessive blockage in the boiler section
flue passageways is developed the flame rollout switch
will open interrupting power to the VENT DAMPER
and the GAS VALVE. Main burners and pilot burner
will be extinguished immediately. The VENT
DAMPER will close and the CIRCULATOR will
continue to operate. If the flame rollout switch is
activated do not attempt to place the boiler in opera-
tion. The source of blockage must be corrected and the
flame rollout switch replaced by trained and skilled
personnel from a qualified service agency.
2. The sensing circuit between the Q3450 or Q3480 pilot
and the GAS VALVE proves presence of pilot flame.*
3. The GAS VALVE de-energizes the igniter and opens
the main valve, allowing main gas to flow and
ignition of main burners.
4. Where condensation of flue gas is encountered in
boiler flues, a REVERSE ACTING CIRCULATOR
CONTROL should be installed to stop the CIRCULA-
TOR before the boiler water temperature drops to that
at which flue gas condensation may occur.
5. The burners and CIRCULATOR will operate simulta-
neously until the THERMOSTAT is satisfied.
4. Pilot
A. Any pilot failure on the Q3450 or Q3480 Pilot will
close the main gas valve and energize the igniter.
6. After the THERMOSTAT is satisfied the main valve,
pilot valve and the circulator will be de-energized and
main burner and pilot flames will be extinguished.
The VENT DAMPER will close (see Paragraph 17E).
B. If the igniter breaks or becomes disconnected, the pilot
valve coil loses power, closing the pilot valve.
5. For TROUBLE SHOOTING GUIDE, see Figure 28.
SAFETY SHUTDOWN
* · SV9500 and SV9600 Gas Valves:
1. High Limit Switch
The igniter and pilot gas valve will stay energized
until either the pilot lights or the call for heat ends.
In the event excessive boiler water temperature is
developed the High Limit Switch will open, interrupt-
ing power to the VENT DAMPER and the GAS
VALVE. Main Burners and Pilot Burner will be
extinguished immediately. Normal operation will be
resumed when the boiler water temperature drops to a
point where the High Limit Switch closes.
·
SV9501 and SV9601 Gas Valves:
If the pilot fails to light after a 90 second trial for
ignition, the igniter will be de-energized and the pilot
gas valve will close. After a 5 minute delay, the
igniter will be re-energized and the pilot gas valve will
re-open. This continuous retry cycle will end either
when the pilot lights or the call for heat ends.
2. Blocked Vent Switch
In the event excessive blockage in the vent system is
15
Figure 13: Wiring Diagram, Intermittent Ignition and Continuous or Gravity Circulation
16
SEQUENCE OF OPERATION
NORMAL OPERATION
2. Blocked Vent Switch
In the event excessive blockage in the vent system is
developed the blocked vent switch will open interrupt-
ing power to the ignition module and dual combina-
tion gas valve. Main burners and pilot burner will be
extinguished immediately and the vent damper will
close. The source of blockage must be corrected by
trained and skilled personnel from a qualified service
agency before resetting switch.
1. When THERMOSTAT calls for heat, the VENT
DAMPER is opened (see Paragraphs 17A through
17D). When the damper blade reaches the fully open
position, the GAS VALVE powers the igniter circuit
and opens the pilot valve.
2. The sensing circuit between the Q3450 or Q3480 pilot
and the GAS VALVE proves presence of pilot flame.*
3. Flame Rollout Switch
In the event excessive blockage in the boiler section
flue passageways is developed the flame rollout switch
will open interrupting power to the ignition module
and the dual combination gas valve. Main burners and
pilot burner will be extinguished immediately and the
vent damper will close. If the flame rollout switch is
activated do not attempt to place the boiler in opera-
tion. The source of blockage must be corrected and the
flame rollout switch replaced by trained and skilled
personnel from a qualified service agency.
3. The GAS VALVE de-energizes the igniter and opens
the main valve, allowing main gas to flow and
ignition of main burners.
4. On Boilers equipped with Circulators that are wired to
run continuously and, where condensation of flue gas
is encountered in boiler flues, a REVERSE ACTING
CIRCULATOR CONTROL should be installed to stop
the Circulator before the Boiler Water Temperature
drops to that at which flue gas condensation may
occur.
4. Pilot
5. The Burners will operate until the THERMOSTAT is
satisfied.
A. Any pilot failure on the Q3450 or Q3480 pilot will
close the main gas valve and energize the igniter.
6. After the THERMOSTAT is satisfied the GAS
VALVE will be de-energized. The Main Burners and
Pilot Burner will be extinguished. If Boiler is
equipped with circulator, Circulator will continue to
run. The VENT DAMPER will close (see Paragraph
17E).
B. If the igniter breaks or becomes disconnected, the pilot
valve coil loses power, closing the pilot valve.
5. For TROUBLE SHOOTING GUIDE, see Figure 28.
* · SV9500 and SV9600 Gas Valves:
SAFETY SHUTDOWN
1. High Limit Switch
The igniter and pilot gas valve will stay energized
until either the pilot lights or the call for heat ends.
·
SV9501 and SV9601 Gas Valves:
In the event excessive boiler water temperature is
developed, the High Limit will open, interrupting
power to the IGNITION MODULE and the DUAL
COMBINATION GAS VALVE. Main Burners and
Pilot Burner will be extinguished immediately and the
vent damper will close. Normal operation will be
resumed when the Boiler Water Temperature drops to
a point where the High Limit Switch closes.
If the pilot fails to light after a 90 second trial for
ignition, the igniter will be de-energized and the pilot
gas valve will close. After a 5 minute delay, the
igniter will be re-energized and the pilot gas valve will
re-open. This continuous retry cycle will end either
when the pilot lights or the call for heat ends.
17
Figure 14: Wiring Diagram, 24 Volt Standing Pilot with Continuous or Gravity Circulation
SEQUENCE OF OPERATION
2. Blocked Vent Switch
In the event excessive blockage in the vent system is
developed the blocked vent switch will open interrupt-
ing power to the gas valve. The main burners will be
extinguished immediately and the vent damper will
remain open until the thermostat is turned off. The
source of blockage must be corrected by trained and
skilled personnel from a qualified service agency
before resetting switch.
NORMAL OPERATION
1. When the thermostat call for heat, the vent damper
will open (see paragraphs 17A through 17D). The gas
valve is energized allowing main gas to flow and
operation of the main burners.
2. Where condensation of flue gas is encountered in
boiler flues a reverse acting circulator control should
be installed to stop the circulator before the boiler
water temperature drops to that which flue gas
condensation may occur.
3. Flame Rollout Switch
In the event excessive blockage in the boiler section
flue passageways is developed the flame rollout switch
will open interrupting power to the gas valve. The
main burners will be extinguished immediately and
the vent damper will remain open until the thermostat
is turned off. If the flame rollout switch is activated do
not attempt to place the boiler in operation. The source
of the blockage must be corrected and the flame
rollout switch replaced by trained and skilled person-
nel from a qualified service agency.
3. After the thermostat is satisfied the main valve will
close and main burner flames will be extinguished.
The vent damper will close (see paragraph 17E). If the
boiler is so equipped, circulator will continue to run.
SAFETY SHUTDOWN
1. High Limit Switch
In the event excessive boiler water temperature is
developed the high limit switch will open interrupting
power to the gas valve. The main burners will be
extinguished immediately. Normal operation will be
resumed when the boiler water temperature drops to a
point where the high limit switch closes.
4. Pilot
The thermocouple proves pilot flame and in the
absence of such within 45-90 seconds causes the
combination gas valve, which is equipped with a
100% shut-off provision, to be de-energized, thus,
preventing main gas or pilot gas flow.
18
Figure 15: Wiring Schematic, Zone Valves
Figure 16: Wiring Schematic, Zone Circulators
19
SECTION II - OPERATING INSTRUCTIONS
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when
the boiler underwent tests specified in American National Standard for Gas-Fired Low-Pressure Steam and Hot Water Boilers,
ANSI Z21.13b-1994.
1. MAIN BURNER CHECK - Check main burners to see
that they were not dislodged during shipment. Rear of burners
should be in the slots in the rear of burner tray and the front
of the burners should be seated completely on the orifices.
2. INITIAL START -
A. FILL ENTIRE HEATING SYSTEM WITH WATER
and vent air from system. Use the following procedure
onaSeriesLoopSystemequippedwithzonevalves. (See
Figure 3).
1.Close isolation valve in boiler supply piping.
2.Isolate all circuits by closing zone valves or balancing
valves.
3.Attach a hose to bib cock located just below isolation
valve in boiler supply piping. (Note - Terminate hose in
five gallon bucket at a suitable floor drain or outdoor
area).
4. Starting with one circuit, open zone valve.
5.Open bib cock.
6.Open fill valve (Make-up water line should be located
directly above isolation valve in boiler supply piping).
7. Allow water to overflow from bucket until discharge
Figure 17: Schematic Pilot and Gas Piping
Continuous Ignition (Standing Pilot)
from hose is bubble free for 30 seconds.
8. Open zone valve to the second zone to be purged, then
close the first. Repeat this step until all zones have been
purged, but always have one zone open. At completion,
open all zone valves.
9.Close bib cock, continue filling the system until the
pressure gauge reads 12 psi. Close fill valve. (Note - If
make-up water line is equipped with pressure reducing
valve, system will automatically fill to 12 psi. Leave
globe valve open).
10. Open isolation valve in boiler supply piping.
11. Remove hose from bib cock.
B. Turn ROOM THERMOSTAT to lowest setting.
C. Be sure that gas to pilot and main burners has been off
for at least five minutes and vent damper (if used) has
been in the open position.
D. Turn "OFF" the electric switch serving boiler.
E. Open valve on main gas line at meter.
F. PURGE AIR FROM GAS PIPING. This procedure will
vary with equipment furnished butin all cases adequate
ventilation must be provided and no smoking or open
flame permitted. To determine which of the procedures
outlined in succeeding paragraphs is applicable, match
Figure 18: Schematic Pilot and Gas Piping
Intermittent Ignition (HSP)
"Pilot" Position. Depress and hold in this position
until purging is complete. Turn Main Gas Knob to
suffix of boiler model found on Rating Plate with
"off" position.
paragraph heading:
e. Reconnect pilot tubing and check pipe and fittings
from meter to combination Gas Valve for leaks using
soap solution or other approved method.
1.Standing Pilot Models (Suffix V):
a. Keep electric switch "OFF".
b. OpenManualShut-offValveupstreamofCombination
2.Intermittent Ignition Models (Suffix S):
Gas Valve.
a. Turn "ON" electric switch serving boiler.
b. Open Manual Shut-off Valve upstream of
Combination Gas Valve.
c. Disconnect Pilot Tubing at gas valve (Purge must not
be into combustion chamber).
d.Turn Main Gas Knob on Combination Gas Valve to
20
c. Loosen or remove Inlet Pressure Tap Plug in
Combination Gas Valve and when purging is
complete, tighten or replace plug. (See Figure 19).
d.Check pipe and fittings from meter to Combination
Gas Valve using soap solution or other approved
methods.
e. Test gas piping and connections between
Combination Gas Valve and manifold, orifices,
and pilot piping for leaks after boiler is operating.
Use soap solution or other approved method.
3. INSTRUCTIONS TO PUT THE BOILER IN OPERA-
TION. See Figure 20 for intermittent ignition. See Figure
21 for continuous ignition system (standing pilot).
Figure 19a: Top View of SV9500, SV9600 and
VR Gas Valves
21460147
Figure 20a: Operating Instructions, SV9500 and SV9600 Gas Valves
21
Honeywell
Figure 19b: Top View of Honeywell SV9501 and SV9601 Gas Valves
FOR YOUR SAFETY READ BEFORE OPERATING
WHAT TO DO IF YOU SMELL GAS:
WARNING
Do not try to light any appliance.
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Do not touch any electric switch other than the
gas valve; do not use any phone in your
building.
Force or attempted repair may result in a fire or
explosion.
Follow these instructions exactly.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
fire department.
1. This appliance is equipped with an ignition device
which automatically lights the pilot. DO NOT try to
light the pilot by hand.
3. Use only your hand to slide the gas control switch to
"ON". Never use tools. If the switch does not move
by hand, DO NOT try to repair it; call a qualified
service technician. Force or attemped repair may
result in a fire or explosion.
2. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and settles
on the floor.
4. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance. Replace any
part of the control system and any gas control
that has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this
label.
Follow step 2 in the "FOR YOUR SAFETY" section
above on this label. If you do not smell gas, go to
the next step.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
8. Slide gas control switch to "ON".
9. Replace front door.
4. This appliance is equipped with an ignition device
that automatically lights the pilot. DO NOT try to
light the pilot by hand.
10. Turn on all electric power to the appliance.
11. Set the thermostat to desired setting.
5. Remove front door.
12. If the appliance does not operate, follow the
instructions "TO TURN OFF GAS TO APPLIANCE"
and call your service technician or gas supplier.
6. Slide gas control switch to "OFF".
7. Wait five (5) minutes to clear out any gas. Then smell
for gas, including near floor. If you smell gas, STOP!
GAS
INLET
OUTLET
IGNITION SYSTEM
CONTROL SWITCH
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
4. Slide gas control switch to "OFF". DO NOT force.
5. Replace front door.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Remove front door.
Figure 20b: Operating Instructions, SV9501 and SV9601 Gas Valves
22
81460177
Figure 21: Lighting Instructions
23
4. CHECK GAS INPUT RATE TO BOILER
USA boilers built for installation at altitudes greater than
2,000 feet above sea level have been specially orificed to
reduce gas input rate 4 percent per 1,000 feet above sea level
per the National Fuel Gas Code, NFPA 54/ANSI Z223.1,
Section 8.1.2 and Appendix F. Canadian boilers' orifice
sizing is indicated on the rating label. High altitude boiler
models are identifiable by the fourth digit after the dash in the
model number. 2: 0-2000', 4 or 5: above 2000'.
5. MAIN BURNER FLAMES should have a clearly
defined inner cone (see Figure 22 or 23) with no yellow
tipping. Orange-yellow streaks caused by dust should
not be confused with true yellow tipping.
The main burners in this boiler will not operate
cleanly or efficiently if they are contaminated with dirt
and/or construction dust. Burners should be cleaned and
the combustion chamber vacuumed following instruc-
tions in Section III - Service.
A. Input Rate and Maximum Inlet Pressure shown on
Rating Label must not be exceeded. Inlet pressure
must not be lower than minimum inlet pressure shown
on Rating Label.
6. CHECK PILOT BURNER FLAME.
A. Continuous Ignition (Standing Pilot)
Models 202 and 202X with 1" diameter burners. See
Figure 24.
B. All Rate checks and all adjustments are to be made
while boiler is firing - all other appliances connected
to the same meter as the boiler must be off.
C. With boiler off, water Manometer or water column
gauge should be connected to a shut-off cock installed
in the 1/8" outlet pressure tap in the gas valve (See
Figure 19). By installing gas cock upstream of
manometer, gas pressure can be introduced gradually -
without shut-off cock, surge of pressure when boiler is
turned on, could blow liquid out of manometer.
Replace plug in gas valve when rate check is finished.
D. LP Gas Input:
Models 202 and 202X with 40mm (1-9/16") diameter
burners. See Figure 25.
Natural gas Models 203 through 206 and 207 with 1"
diameter burners. See Figure 25.
The pilot produces a single flame. The flame should
be steady, medium hard blue enveloping 3/8 to a 1/2
inch of thermocouple.
Adjust Regulator on Gas Valve so that manifold
pressure is 10 inches water column. Turning Regula-
tor Adjusting Screw Clockwise increases pressure.
Counterclockwise rotation decreases pressure.
E. Natural Gas Input
1.Appx. Input - Adjust regulator on Gas Valve so that
manifold pressure is three and a half (3½) inches
water column (three inches water column for high
altitude with 1" main burners). Turning Regulator
Adjusting Screw Clockwise increases pressure,
Counterclockwise rotation decreases pressure. If
more accurate check on input is necessary see (2)
below.
Figure 22: 40mm and 50mm Main Burner Flame
For minor input changes readjust Regulator Gas
Valve to increase or decrease manifold pressure to
obtain corresponding increase or decrease in gas
input. If it is necessary to increase manifold pressure
more than 0.3" of water to obtain rated input, remove
orifices and drill one size larger. Reinstall and
recheck input rate.
2.Additional Check on Input - Since input is a function
of heating value, specific gravity, and volume of gas
flow contact your utility for the first two items in
order to utilize the formula below. The gas meter
should then be clocked for three (3) minutes with
stop watch and substituting the appropriate values in
the formula below, determine what the gas flow
should be in this 3 minute period to give the input
shown on the Rating Label:
Figure 23: 1 Inch Main Burner Flame
24
B. Continuous Ignition (Standing Pilot)
Natural gas Models 207 with 40mm (1-9/16") diam-
eter burners and 208 through 210. See Figure 26
LP gas Models 203 through 210. See Figure 26.
The pilot produces three (3) flames. The center flame
should be steady, medium hard blue enveloping 3/8 to
a 1/2 inch of thermocouple.
8. CHECK HIGH LIMIT CONTROL. Jumper Thermo-
stat Terminals or Thermostat connections in Limit Control.
Allow burners to operate until shutdown by limit. RE-
MOVE JUMPER.
9. CHECK DAMPER OPERATION if Boiler is equipped
with Vent Damper. Vent Damper must be open when
boiler is running. Start boiler, refer to instructions on
damper to determine if damper is in the full open position.
C. Intermittent Ignition
Models 202 with 1" diameter burners and 202X
through 210. See Figure 27.
The pilot produces three (3) flames. The center flame
should be steady, medium hard blue enveloping 3/8 to
a ½ inch of sensing probe.
10. CHECK IGNITION SYSTEM SAFETY SHUT-OFF
DEVICE.
A. 24 volt-loosen thermocouple at gas valve.
B. Intermittent Ignition - Remove pilot lead wires from
gas valve.
D. Intermittent Ignition
Model 202 with a 40mm (1-9/16") diameter burner.
See Figure 27a.
The pilot produces a single flame. The flame should
be steady, medium hard blue enveloping 3/8 to a ½
inch of sensing probe.
If burners do not shut down determine cause of
malfunction. Replace necessary items and check
operation.
11. COMBUSTION CHAMBER BURN-OFF
A. The mineral wool combustion chamber panels contain
a cornstarch based binder that must be burned out at
installation to prevent odors during subsequent boiler
operation.
7. CHECK THERMOSTAT OPERATION. Raise and
lower temperature setting as required to start and stop
burners.
Figure 24: Typical Pilot Flame, Robertshaw 7CL-6
Figure 26: Typical Pilot Flame, Honeywell Q327
Figure 25: Typical Pilot Flame, Honeywell Q350
Figure 27: Typical Pilot Flame, Honeywell Q3480
25
B. Ventilate the boiler room, set the high limit to its
maximum setting, set the thermostat to call for heat.
Allow the boiler to fire for at least an hour or until the
odor from the cornstarch has dissipated.
C. Return the high limit and thermostat to their desired
settings.
Figure 27a: Typical Pilot Flame, Honeywell Q3450
26
Figure 28: Troubleshooting Guide, Honeywell Intermittent Ignition
27
SECTION III - SERVICE
1. Inspection should be conducted annually. Service as
NOTICE
frequently as specified in paragraphs below. While service
or maintenance is being done, Electrical Power and all Gas
Supply to the Boiler must be "off".
4. BURNERS AND FIREBOX SHOULD BE CLEANED
ANNUALLY, AND IF NECESSARY ADJUSTED ONCE
A YEAR BY A QUALIFIED SERVICE AGENCY.
A. TO REMOVE BURNERS FOR CLEANING,
CHANGING ORIFICE PLUGS, OR REPAIRS.
1.Remove the jacket front panel.
2.Disconnect pilot tubing at the gas valve.
(See Figures 17 and 18)..
3.Disconnect thermocouple (standing pilot) or pilot lead
wires (intermittent ignition) at the gas valve.
4.40mm and 50 mm burners only. Remove injection
shield assembly, where used. (See Figure 30).
5.Remove wires to flame roll-out switch.
6.Remove the burner access panel.
2. VENT SYSTEM. Vent system (see Figure 8 for typical
installation) should be checked annually for:
A. Obstructions.
B. Accumulations of soot.
C. Deterioration of vent pipe or vent accessories due to
condensation or other reasons.
7.50mm dia. burners only. Remove orifice hitch pin
clips.
D. Proper support - no sags, particularly in horizontal
runs.
E. Tightness of joints.
F. Proper vent damper operation - see Section II, para-
graph 9.
G. Remove all accumulations of soot with wire brush and
vacuum, see Fig. 29. Remove all obstructions. Replace
all deteriorated parts and support properly. Seal all
joints.
3. CLEANING BOILER FLUES, see Fig. 29.
Flue passageways in the boiler sections should be
checked annually for any blockage or accumulation of soot.
To obtain access to flueways:
A. Remove vent pipe, damper (if boiler is so equipped),
blocked vent switch, and draft hood.
B. Remove sheet metal screws securing Jacket Top Panel,
lift panel and rotate about relief valve piping until top
of boiler is exposed.
C. Remove bolts securing Canopy to Boiler Sections.
Remove Canopy - flueways are now exposed.
D. Models with flue gas baffles only: Remove baffles by
lifting out of flueways.
Using flashlight, examine all flue passageways. If
passageways are free of soot and obstruction, replace
canopy (and flue gas baffles, if applicable), and seal.
Reinstall Jacket Top Panel, draft hood, blocked vent
switch, damper (if boiler is so equipped), and vent
pipe.
If the flue passageways need cleaning, remove burners
as described in paragraph 4 below. Using long handle
wire or bristle flue brush and vacuum, brush flueways
thoroughly from top of boiler as illustrated in Fig. 29.
Replace canopy and seal with boiler putty. Reinstall
Jacket Top Panel, draft hood, blocked vent switch,
damper (if boiler is so equipped), and vent pipe.
Figure 29: Cleaning of Vent System and
Boiler Flues
28
8.Mark the location of the pilot main burner on the
manifold if the marking on manifold is missing or
obliterated.
C. INSTALL BURNERS by reversing procedure used to
remove burners. Make sure burner with pilot assembly is
in same location as original installation - see Table 5
Check burners to see that they are located properly in
slot at rear of burner tray, see Fig. 30. Reinstall
injection shield assembly (40mm and 50mm burners
only, where used) and burner access panel. Reconnect
flame roll-out switch wires, pilot gas supply, thermo-
couple lead or pilot lead.
9.Hold burner at throat,
a. 1 inch and 40mm diameter burners. Lift front of
burner to clear orifice. Burner which holds pilot
can only be removed by lifting the burner adjacent
to its right first.
b. 50 mm dia. burners only. Push toward the rear until
the burner face plate clears the orifice. Lift burner
out.
D. CHECK MAIN BURNER and PILOT FLAMES, see
procedure Section II, paragraphs 5 and 6.
10.Brush top of burners with a soft bristle brush, see
Fig. 30. Vacuum burners. Check orifices to see
that drilled passageways are free of lint or dirt.
11.Vacuum tip of Pilot Burner.
5. CHECK ALL CONTROL AND DAMPER OPERA-
TION ANNUALLY see procedure in Section II, paragraphs
7 through 10.
B. CLEAN FIREBOX by vacuuming. Exercise care not
to disturb insulation inside the base.
6. REMOVAL OR REPLACEMENT OF PILOT AS-
SEMBLY OR PILOT ASSEMBLY PARTS
1" Burner
If pilot assembly, thermocouple or pilot orifice need
replacing, remove main burner with pilot using procedure
described in Paragraph 4.
A. To replace orifice:
1.Disconnect pilot tubing. The Robertshaw 7CL-6,
Honeywell Q350 and Q3450 pilot orifices are insert
type retained by the compression fitting. The Honey-
well Q327 and Q3480 pilot orifice is a spud type
screwed into pilot burner. Replace with desired
orifice. See Key No. 5B.
50mm Burner
2.Reconnect pilot tubing and check for leaks.
B. To replace Honeywell Q309A thermocouple in Q327
or Q350 pilot:
1.Loosen attachment nut securing thermocouple to
barrel of pilot burner. Disconnect other end at
combination gas valve.
2.Remove thermocouple and replace with equal.
C. To replace Q3450 or Q3480 igniter-sensor rod
assembly:
1.Remove spring clip by pulling it away from the pilot
burner.
2.Remove assembly from pilot burner and disconnect
harness from gas valve.
40mm Burner
3.Replace with equal.
D. To replace complete pilot assembly.
1.Remove machine screws holding pilot burner to pilot
bracket.
2.Disconnect pilot piping.
3.Disconnect all other leads to pilot.
4.Select pilot assembly with identical model number,
reconnect leads and pilot tubing - resecure to pilot
bracket.
E. Reinstall main burner following procedure described
in Paragraph 4.
Figure 30: Burner Cleaning and Installation
29
the service technician or the User. Circulator bearings are
water lubricated.
7. LUBRICATION
There are no parts requiring lubrication on the part of
Table 5: Pilot Burner Location
Main Burner with
Pilot Burner Located Between Main Burners*
Pilot Bracket *
Boiler Model
1 Inch
50mm
40mm
1 Inch
1 & 2
1 & 2
1 & 2
2 & 3
3 & 4
4 & 5
6 & 7
7 & 8
8 & 9
9 & 10
50 mm
---
40mm
---
202
202X
203
204
205
206
207
208
209
210
1
1
1
2
3
4
6
7
8
9
---
---
1
1
1
1
2
2
3
3
4
4
5
---
1 & 2
1 & 2
2 & 3
2 & 3
3 & 4
3 & 4
4 & 5
4 & 5
5 & 6
1 & 2
2 & 3
2 & 3
3 & 4
3 & 4
4 & 5
4 & 5
5 & 6
2
2
3
3
4
4
5
* Main burners numbered left to right as viewed from front of boiler.
SECTION IV REPAIR PARTS
Section Assembly and Canopy Group .................................. 32
Base Assembly ...................................................................... 34
Manifold and Main Burners
1 Inch Main Burners ..................................................... 36
50mm Main Burners ..................................................... 38
40mm Main burners ...................................................... 40
Pilot Burner and Gas Valve
Continuous Ignition (Standing Pilot)............................ 42
Intermittent Ignition ...................................................... 44
Jacket Assembly .................................................................... 46
Water Trim ........................................................................... 48
Controls................................................................................. 50
Draft Hood and Vent Damper .............................................. 51
30
All Series 2 repair parts may be obtained through your local Burnham Wholesale Distributor. Should you require assistance in
locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts,
please contact your Burnham Regional Sales Office as listed below.
Burnham Corporation Regional Offices
A. Burnham Corporation - Central & Western Regions
P.O. Box 3079
C. Burnham Corporation - Metropolitan Region
P.O. Box 3079
Lancaster, PA 17604-3079
Phone: (717) 481-8400
Lancaster, PA 17604-3079
Phone: (717) 481-8400
FAX: (717) 481-8408
FAX: (717) 481-8409
B. Burnham Sales Corporation - Northeast Region
19-27 Mystic Avenue
D. Burnham Corporation - Mid-Atlantic Region
P.O. Box 3079
Somerville, MA 02145
Lancaster, PA 17604-3079
Phone: (717) 481-8400
Phone: (617) 625-9735
FAX: (617) 625-9736
FAX: (717) 481-8409
Contact Regional Office Indicated for your State
Alabama
Alaska
A
A
A
A
A
A
B
D
A
A
A
A
A
A
A
A
A
A
B
D
B
A
A
A
A
A
Nebraska
A
A
B
Oregon
A
D
B
A
A
A
A
A
B
Nevada
Pennsylvania
Rhode Island
South Carolina
South Dakota
Tennessee
Te xas
Arizona
New Hampshire
New Jersey
Arkansas
California
Colorado
Connecticut
Delaware
Florida
Atlantic, Burlington, Camden,
Cape May, Cumberland,
Gloucester, Mercer,
Monmouth, Ocean, Salem
Counties
D
Utah
Ve rm ont
Georgia
Hawaii
All other Counties
C
A
Virginia
New Mexico
Arlington,Accomack,Clarke,
Idaho
New York
Albany, Fulton, Montgomery,
Fairfax,Frederick,Fauquier,
Loudoun,Northampton and
Prince William Counties
All other Counties
D
Illinois
Indiana
Rensselaer, Saratoga,
Schenectady, Schoharie,
Warren, Washington Counties
All Other Counties
B
Iowa
A
A
D
D
A
A
Kansas
Washington
Kentucky
Louisiana
Maine
C
A
A
Washington, D.C.
West Virginia
Wisconsin
North Carolina
North Dakota
Ohio
Maryland
Massachusetts
Michigan
Minnesota
Mississippi
Missouri
Montana
Wyoming
Athens, Belmont, Gallia,
D
Jefferson, Lawrence, Meigs,
Monroe, and Washington
Counties
All other Counties
A
A
Oklahoma
Canada
A
31
Figure 33: Section Assembly and Canopy Group
Quantity
Key
No.
De scrip tio n
Part No.
202 202X 203 204 205 206 207 208 209 210
1. Section Assembly (Intermittent and Continuous Circulation Only)
617170221
617170321
617170421
617170521
617170621
617170721
617170821
617170921
617171021
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
Section Assembly, Complete
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1. Section Assembly (Gravity circulation Only)
617170231
617170331
617170431
617170531
617170631
617170731
617170831
617170931
617171031
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
Section Assembly, Complete
---
---
---
---
---
---
---
---
---
---
32
Quantity
Key
No.
Description
Part No.
202 202X 203 204 205 206 207 208 209 210
2. Canopy Group
61117022
611170300
611170302
611170402
611170502
611170602
611170702
611170802
611170902
611171002
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
1
---
---
----
---
---
---
---
---
----
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Canopy Assembly
(except for 206H)
2A
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Canopy Assembly 206H
6111706010
---
2
---
2
---
2
---
2
---
2
1
2
---
2
---
2
---
2
---
2
Common
Hardware
2B Carriage Bolt, ¼-20 x 1"
2C Flat Washer, ¼"
Common
Hardware
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
Common
Hardware
2D Nut, Hex, ¼-20
Cerafelt Sealing Strip, ½" x 1" x 10'
2E
6206001
(Canopy to Section Assy)
Flue Gas Baffle (*Standing Pilot 1"
and 50mm Burners Only)
(** LP Standing Pilot 1" and 50mm
Burners Only) (+2H Models Only)
(*** Standing Pilot Models Only)
71106001
1***
---
2**+ 3**+ 4**+ 5**+ 6**
7*
8*
9*
2F
33
Figure 34: Base Assembly
Key
Boiler
Size
Key
No.
Boiler
Size
Description
No.
3. Base Assembly Continued
Part No. Qty.
Description
Part No. Qty.
3. Base Assembly
202 718600211
1
1
1
1
1
1
1
1
1
202 618600291
202X 618600391
203 618600391
204 618600491
205 618600591
206 618600691
207 618600791
208 618600891
209 618600991
210 618601091
202 718600291
202X 718600391
203 718600391
204 718600491
205 718600591
206 718600691
207 718600791
208 718600891
209 718600991
210 718601091
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
202X 718600311
203 718600311
204 718600411
205 718600511
206 718600611
207 718600711
208 718600811
209 718600911
210 718601011
Base Assembly
(Complete)
3B Base Wrapper
3
Available for 1 Inch
Burners Only
1
2
1
1
3B1 Base End Insulation
All
720601
202
72060025
202X 72060035
203
204
205
206
207
208
209
210
72060035
72060045
72060055
72060065
72060075
72060085
72060095
72060105
1
1
1
1
1
1
1
1
3A Base Tray
3B2 Base Rear Insulation
34
Key
No.
Boiler
Size
Key
No.
Boiler
Size
Description
Part No. Qty.
Description
Part No. Qty.
3. Base Assembly Continued
3. Base Assembly Continued
202
618600241
618600341
1
1
All
6186001
71860021
8186006
4
4
4
1
1
1
1
1
1
1
1
1
1
3E Base Leg Assembly
3E1 Base Leg
202X
203
All
All
618600341
618600441
618600541
1
1
1
3E2 Nylon Glide
204
202
202X
203
204
205
206
207
208
209
210
718600261
718600361
718600361
718600461
718600561
718600661
718600761
718600861
718600961
718601061
205
Base Front Panel
Assembly
3C
206
207
208
618600641
618600741
618600841
1
1
1
3F Burner Access Panel
209
618600941
1
210
202
618601041
718600205
718600305
1
1
1
202X
203
204
718600305
718600405
1
1
Cerafelt Sealing Strip,
3G
1" x 2" x 10' (Section
All
6206002
1
Assembly to Base)
Burner Tray
205
206
207
208
209
210
203
204
718600505
718600605
718600705
718600805
718600905
718601005
7817038
1
1
1
1
1
1
1
1
(1" Main Burners)
202
thru
206
80860700
20
3H Self-Tapping Screw,
¼" - 20 x ½"
207
thru
210
80860700
80860717
21
4
Self-Tapping Screw,
3J
5/16" - 18 x 1-1/4"
All
7817048
Flat Washer, 5/16",
Common
Hardware
All
All
All
4
4
4
3K
205
206
207
208
209
210
202
202X
203
204
205
206
207
208
209
210
7817058
7817068
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
USS
Burner Tray
Common
Hardware
3D
3L Lock Washer, 5/16"
3M Hex Nut, 5-16,
(50 mm Main Burners)
7817078
Common
Hardware
7817088
7817098
7817108
718600206
71806037
71806037
71806047
71806057
71806067
71806077
718600806
718600906
718601006
Burner Tray
(40mm Main Burners)
35
Figure 35: Manifold and Main Burners
(1 Inch Main Burners)
36
Quantity
Key
No.
Description
Part No.
202
202X
203
2
204
4
205
206
207
11
208
13
209
15
210
17
4. Manifold and Main Burners (1 Inch Main Burners Only)
4A
4B
Main Burner
8236099
----
1
2
6
8
Main Burner with Pilot Bracket
See Table Below
82260023
82260033
1
----
1
----
1
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
82260043
82260053
82260063
82260073
82260083
82260093
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1
----
1
----
----
1
----
----
----
1
----
----
----
----
1
----
----
----
----
----
1
----
----
----
----
----
----
1
----
----
----
----
----
----
----
----
----
----
----
4C
Manifold
----
----
----
----
----
----
----
----
----
82260103
----
----
4D
4E
Main Burner Orifice
See Table Below
Screw, Machine, Slotted Round Head,
10-32 x 3/16" (Standing Pilot)
80860800
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
Screw, Machine, Philips Head
w/Captive Lockwasher, #10-32 x ¼"
(Intermittent Ignition)
80860874
80860700
Screw, Self Tapping, Phillips Pan
Head, ¼-20 x ½"
4F
4B. 1 Inch Main Burner with Pilot Bracket, 24-volt Continuous Ignition (Standing Pilot) Natural Gas Only
Main Burner with 70° 7CL-6 Pilot
Bracket and Offset Lancings
8231706
1
1
---
---
---
---
---
---
---
---
4B
Main Burner with 70° Q350 Pilot
Bracket and Offset Lancings
8236097
8236098
---
---
---
---
1
1
1
1
1
---
1
---
1
---
1
Main Burner with 60° Pilot Bracket
---
---
---
---
---
4B. 1 Inch Main Burner with Pilot Bracket, 24-volt Continuous Ignition (Standing Pilot) LP Gas Only
Main Burner with 70° 7CL-6 Pilot
Bracket and Offset Lancings
8231706
8236111
1
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
4B
Main Burner with 45° Pilot Bracket
---
---
4B. 1 Inch Main Burner with Pilot Bracket, Intermittent Ignition Only
4B
Main Burner with 60° Pilot Bracket
8236098
1
1
1
1
1
1
1
1
1
1
4D. 1 Inch Main Burner Orifices, Natural Gas, Normal Altitude, U.S.A. and Canada
Main Burner Orifice, #47 (White)
Main Burner Orifice, #44 (Orange)
Main Burner Orifice, #45 (Pink)
822710
822712
822711
2
3
---
---
---
5
---
---
7
---
---
9
12
---
---
14
---
---
16
---
---
18
---
---
4D
---
---
---
---
3
---
4D. 1 Inch Main Burner Orifices, LP/Propane, Normal Altitude, U.S.A. and Canada
Main Burner Orifice, 1.25 mm
(Purple)
822705
2
---
---
5
7
9
---
---
---
---
4D
Main Burner Orifice, #55 (Green)
Main Burner Orifice, 3/64" (Blue)
822708
822704
---
---
---
3
3
---
---
---
---
---
---
---
---
---
---
---
12
14
16
18
37
*
Continuous Pilot Ignition:
- Q327A Only
- Not suitable for use with Q350A 24V Continuous
Pilot Ignition
Intermittent Ignition: Q3480C
Figure 36: Manifold and Main Burners
(50 mm Main Burners)
38
Quantity
Key
No.
Description
Part No.
202
202X
203
204
205
206
207
208
209
210
4. Manifold and Main Burners (50 mm Main Burners Only)
4A
4B
Main Burner
8236091
8236092
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
2
3
4
5
6
7
8
Main Burner with 45° Pilot Bracket
1
1
1
1
1
1
1
1
82260034
82260044
82260054
82260064
82260074
82260084
82260094
82260104
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4C
Manifold
---
---
---
---
---
---
---
---
---
---
50 mm Main Burner Orifices, Natural Gas, High Altitude, U.S.A. and Canada, 2000-5000 Ft. Altitude
Main Burner Orifice, #38
Main Burner Orifice, #37
822680
822601
---
---
---
---
2
---
3
---
4
---
5
---
6
---
7
---
8
---
9
---
4E
50 mm Main Burner Orifices, LP/Propane, High Altitude, U.S.A. and Canada, 2000-5000 Ft. Altitude
Main Burner Orifice, #53
Main Burner Orifice, #52
External Hitch Pin Clip
8226002
822641
822604
---
---
---
---
---
---
2
---
2
---
3
---
4
---
5
---
6
---
7
---
8
---
9
4F
3
4
5
6
7
8
9
Screw, Machine, Philips Head
w/Captive Lockwasher, #10-32 x ¼"
4G
80860874
80860700
---
---
---
---
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
4
Screw, Self Tapping, Phillips Pan
Head, ¼-20 x ½"
4H
618600301
618600401
618600501
618600601
618600701
618600801
618600901
618601001
718600303
718600403
718600503
718600603
718600703
718600803
718600903
718601003
80860900
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
4J
Lower Injection Shield
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
2
---
---
---
---
---
---
2
---
---
---
---
---
2
4K
Upper Injection Shield
---
---
---
---
2
---
---
---
3
---
---
3
---
3
4L
Wing Nut, ¼-20, Size B
3
39
Figure 36a: Manifold and Main Burners
(40mm Main Burners)
Quantity
202 202X 203 204 205 206 207 208 209 210
Key
No.
Description
Part No.
4. 40MM MAIN BURNERS ONLY
4A Main Burner
8236135
---
1
1
1
2
3
4
5
6
7
8
Intermittent Ignition Only
Main Burner with 48° Pilot Bracket
4B
Main Burner with 41° Pilot Bracket
8236143
8236136
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
24-volt Continuous Ignition (Standing Pilot) Natural Gas Only
Main Burner with 48° Pilot Bracket
Main Burner with 41° Pilot Bracket
8236143
8236136
1
1
1
1
1
1
---
1
---
1
---
1
---
1
4B
---
---
---
---
---
---
24-volt Continuous Ignition (Standing Pilot) LP Gas Only
Main Burner with 48° Pilot Bracket
Main Burner with 41° Pilot Bracket
8236143
8236136
1
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
4B
---
---
40
Quantity
Key
No.
Description
Part No.
202 202X 203
204
205
206 207
208
209
210
4. 40MM MAIN B URNERS ONLY(Continued)
82260028
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
82260038
82260048
82260058
82260068
82260078
82260088
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4C
Manifold
---
---
---
82260098
82260108
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
---
1
---
Natural Gas, Sea Level to 2000 Ft.
Main Burner Orifice, 3.00 mm
822780
822729
1
---
2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Main Burner Orifice, #41
---
4D
Main Burner Orifice, #36
822771
822772
---
---
---
---
2
---
3
---
4
---
5
---
6
---
7
---
8
---
9
Main Burner Orifice, 7/64"
---
LP Gas, Sea Level to 2000 Ft.
Main Burner Orifice, #49
822709
822722
1
---
2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
--
Main Burner Orifice, #53
Main Burner Orifice, #51
---
---
4D
822733
---
---
2
3
4
5
6
7
8
9
Natural Gas, High Altitude (2000-5000 Ft.) U.S.A. Only
Main Burner Orifice, #36
Main Burner Orifice, #44
Main Burner Orifice, #41
Main Burner Orifice, #40
822771
822712
822729
822728
1
---
2
---
---
2
---
---
---
3
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4D
---
Main Burner Orifice, #39
822727
---
---
---
---
4
5
6
7
8
9
LP Gas, High Altitude (2000-5000 Ft.) U.S.A. Only
Main Burner Orifice, #52
Main Burner Orifice, #55
Main Burner Orifice, #53
822721
822708
822722
1
---
2
---
---
2
---
---
3
---
---
4
---
---
5
---
---
6
---
---
7
---
---
8
---
---
9
---
---
4D
---
Natural Gas, High Altitude (2000-4500 Ft.) Canada Only
Main Burner Orifice, 7/64"
Main Burner Orifice, #43
Main Burner Orifice, #38
Main Burner Orifice, #37
822772
822713
822720
822719
1
---
2
---
---
2
---
---
---
3
---
---
---
4
---
---
---
5
---
---
---
6
---
---
---
7
---
---
---
8
---
---
---
9
---
---
---
4D
---
---
---
LP Gas, High Altitude (2000-4500 Ft.) Canada Only
Main Burner Orifice, #50
Main Burner Orifice, #54
Main Burner Orifice, #52
822732
822734
822721
1
---
2
---
---
2
---
---
3
---
---
4
---
---
5
---
---
6
---
---
7
---
---
8
---
---
9
---
---
4D
---
Screw, Machine, Slotted Round Head,
#10-32 x 3/16" (Standing Pilot)
80860800
80860874
80860700
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
4E
Screw, Machine, Phillips Head
w/Captive Lockwasher, #10-32 x ¼"
(Intermittent Ignition)
Screw, Self Tapping, Phillips Pan Head,
¼-20 x ½"
4F
4
4
4
4
4
4
4
4
4
4
4G
Injection Shield Assembly
A/R
A/R
A/R
A/R
A/R
A/R
A/R
A/R
A/R
A/R
41
* 1" Burner Only
** 40mm Burner Only
Figure 37
Quantity
205 206
Key
No.
Description
Part No.
202 202X
203
204
207
208
209
210
5. Pilot Burner and Gas Valve, 24-volt Continuous Ignition, Natural Gas (1 Inch and 40mm Main Burners Only)
Pilot Burner, Robertshaw 7CL-6
5A Pilot Burner, Honeywell Q350A1644
Pilot Burner, Honeywell Q327A1949
8231702
8236102
8236103
---
1
---
1
---
1
---
1
---
1*
---
---
---
---
---
---
1*
1*
1** 1**
---
1*
---
1*
---
---
1
---
--
---
---
1
---
---
1
1
---
---
1
1
---
---
1
1
---
---
1
1**
---
Pilot Orifice, Robertshaw 76376-1 .010"
5B Pilot Orifice, Honeywell 390686-22 .012"
Pilot Orifice, Honeywell 388146AG .026"
Included
with 5A
1
1** 1**
1*
1**
---
2
---
2*
---
2*
---
---
2
---
---
2
---
---
2
---
---
2
Adptr, 1/4"OD x 1/4" NPT Included w/5A & 5E
8236109
8236108
8236110
8236100
81660143
81660182
81660183
81660241
81660242
8231704
8236024
8236047
822630
---
2
---
2
---
2
5C
Adptr, 1/8"OD x 1/4" NPT Included w/5A & 5E
2** 2**
1** 1**
Pilot Tubing, 1/8" OD x 30" LG
5D
Pilot Tubing, 1/8" OD x 40" LG
1
1
1
1
1
---
1
---
1
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
Gas Valve, Honeywell VR8200C3005
Gas Valve, Honeywell VR8200C6008
---
---
1
---
---
1
---
---
1
1*
---
---
1*
---
---
1*
---
1*
---
1*
---
1*
---
5E Gas Valve, Honeywell VR8300C4134
1*
---
Gas Valve, Honeywell VR8200C6032
Gas Valve, Honeywell VR8300C4183
---
---
---
1** 1**
1** 1** 1** 1**
---
1*
---
1*
---
---
1
---
---
1
---
---
1
---
---
1
1** 1** 1** 1**
Thermocouple, 30", Robertshaw 42930
5F
Thermocouple, 30", Honeywell Q309A
---
1
---
1
---
1
---
1
1** 1**
5G Pilot Tubing, 1/4" OD x 9" LG
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
2*
2*
1*
2*
2*
1*
1*
1*
5H Male Adapter, 1/4" OD x 1/8" NPT
5J Regulator, 3.5" w.c., Maxitrol RV12LT
5K Pilot Tubing, 1/4" OD x 6" LG
8231705
8236094
8236046
1*
5L Compression Coupling, 1/4" x 1/4" x 90°
1*
42
Quantity
Key
No.
Description
Part No.
202 202X 203 204 205 206 207 208 209 210
5. Pilot Burner and Gas Valve, 24-volt Continuous Ignition, LP/Propane (1 Inch and 40mm Main Burners Only)
Pilot Burner, Robertshaw 7CL-6
Pilot Burner, Honeywell Q327A1915
Pilot Burner, Honeywell Q350A2279
8231703
8236106
8236105
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
1*
---
1*
---
5A
5B
---
---
---
---
---
---
---
---
1**
1**
Pilot Orifice, Robertshaw 27270-1 (.008")
Pilot Orifice, Honeywell 388146KR (.014")
Pilot Orifice, HoneywelL 390686-23 (.008")
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
1*
---
1*
---
Included
With 5A
---
---
---
---
---
---
---
1**
2*
1**
2*
Adptr, 1/4"OD x 1/4" NPT Included w/5A & 5E
Adptr, 1/8"OD x 1/4" NPT Included w/5A & 5E
8236109
8236108
---
2
---
2
---
2
---
2
---
2
---
2
---
2
---
2
5C
5D
2**
2**
Pilot Tubing, 1/8" OD x 30" LG
8236110
8236100
81660144
81660243
81660244
8231704
1
1
1
1
1
---
1
---
1
---
1
1**
1**
Pilot Tubing, 1/8" OD x 40" LG
---
---
---
---
---
---
---
---
---
---
---
---
Gas Valve, Honeywell VR8200C3013
Gas Valve, Honeywell VR8200C6040
Gas Valve, Honeywell VR8300C4548
Thermocouple, 30", Robertshaw 42930
---
---
---
1*
1*
5E
1
---
---
1
1
---
---
1
1
---
---
1
1
---
---
1
---
1
---
1
---
1
---
1
1**
1**
---
---
---
1
---
1
---
1
---
1
1*
1**
1*
1*
1**
1*
5F
Thermocouple, 30", Honeywell Q309A
Pilot Tubing, 1/4" OD x 18" LG
8236024
8236048
8236046
8236047
5G
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
5L Compression Coupling, 1/4" x 1/4" x90°
5M Pilot Tubing, 1/4" OD x 9" LG
1*
1*
1*
1*
*
1" Burner Only
** 40mm Burner Only
43
Figure 38
Quantity
Key
No.
Description
Part No.
202
202X 203
204
205
206
207
208
209
210
5. Pilot B urner and Gas Valve, Intermittent Ignition, Natural Gas
Pilot Burner, Honeywell Q3480C1197
Pilot Burner, Honeywell Q3450B1039
Pilot Burner, Honeywell Q3480C1254
8236124
8236144
8236133
1
1
1
1
1
1
1
1
1
1
5A
5B
1**
---
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
Pilot Orifice, Honeywell with NE22
Orifice, 388146NE (.022")
1
1**
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
Included
with 5A
Pilot Orifice, Honeywell with BCR18
Orifice, 390686-4 (.018")
Adapter, 1/4" OD x 1/4" NPT
Included with 5A and 5E
5C
5D
8236109
Pilot Tubing,1/4" OD x 30" LG
8236122
8236123
81660213
81660216
81660237
81660238
1
---
1
1
---
1
1
---
1
1
---
1
1
---
1
1
---
1
1
---
---
1
---
1
---
1
---
1
Pilot Tubing,1/4" OD x 40" LG
Gas Valve, Honeywell SV9501P2004
Gas Valve, Honeywell SV9601P4107
Gas Valve, Honeywell SV9501P2087
Gas Valve, Honeywell SV9601P4172
---
1
---
1
---
1
---
1**
---
---
1**
---
---
1**
---
---
1**
---
---
1**
---
---
1**
---
5E
---
1**
---
1**
---
1**
---
1**
Ignitor/Sensor Assembly with clip
Honeywell Q3400A1024 (Included
with 5A)
5F
8236114
1
1
1
1
1
1
1
1
1
1
5. Pilot Burner and Gas Valve, Intermittent Ignition, LP/Propane
Pilot Burner, Honeywell Q3480C1437
Pilot Burner, Honeywell Q3450B1047
Pilot Burner, Honeywell Q3480C1452
8236125
8236145
8236134
1
1
1
1
1
1
1
1
1
1
5A
5B
1**
---
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
---
1**
Pilot Orifice, Honeywell with KR14
Orifice, 388146KP (.014")
1
1**
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
1
---
2
Included
with 5A
Pilot Orifice, Honeywell with BBR12
Orifice, 390686-25 (.012")
Adapter, 1/4" OD x 1/4" NPT
Included with 5A and 5E
5C
5D
8236109
Pilot Tubing, 1/4" OD x30" LG
8236122
8236123
81660215
81660239
81660240
1
1
1
1
1
1
1
---
1
---
1
---
1
---
1
Pilot Tubing, 1/4" OD x40" LG
---
---
1
---
---
1
---
---
1
---
---
1
---
---
1
---
---
1
Gas Valve, Honeywell SV9601P4115
Gas Valve, Honeywell SV9501P2020
Gas Valve, Honeywell SV9601P4164
1
1
1
5E
5F
---
1**
---
1**
---
1**
---
1**
---
---
---
---
---
---
Ignitor/Sensor Assembly with clip
Honeywell Q3400A1024
(Included with 5A)
8236114
1
1
1
1
1
1
1
1
1
1
** 40mm Burners Only
44
Service Notes
45
Figure 39
Quantity
202 202X 203 204 205 206 207 208 209 210
Key
No.
Description
Part No.
6. Jacket Assembly, Complete
604170254
604170354
604170454
604170554
604170654
604170754
604170854
604170954
604171054
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6
Jacket Assembly, Complete
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6. Jacket Assembly
604170215
604170315
604170415
604170515
604170615
604170715
604170815
604170915
604171015
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6A
Jacket Wrap-Around Panel
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
46
Quantity
Key
No.
Description
Part No.
202 202X 203 204 205 206 207 208 209 210
6. Jacket Assembly (Continued)
604170223
604170323
604170423
604170523
604170623
604170723
604170823
604170923
604171023
604170233
604170333
1
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6B
Jacket Vestibule Panel
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
604170433
604170533
604170633
604170733
604170833
604170933
604171033
604170242
604170342
604170442
604170542
604170642
604170742
604170842
604170942
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
6C
Jacket Top Panel
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6D
Jacket Front Removable Door
---
---
---
---
---
---
604171042
604170216
604170316
---
1
---
---
1
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
---
---
---
604170416
604170516
604170616
604170716
604170816
604170916
604171016
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
6E
Jacket Lower Front Panel
---
---
---
---
---
---
---
---
---
---
Sheet Metal Screw, Type AB,
Phillips Truss Head, #8 x ½"
6F
80860000
26
26
26
26
26
26
26
26
26
26
6G
6H
Snap Bushing, Heyco SB-1093-15
Snap Bushing, Heyco SB-437-5
8136257
8136048
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
47
Figure 40: Water Trim
48
Quantity
Key
No.
Description
Part No.
202 202X 203 204 205 206 207 208 209 210
Safety Relief Valve, 30 psi, ¾ NPT,
Conbraco 10-408-05
7
81660319
1
1
1
1
1
1
1
1
1
1
8. Circulator, Bell & Gossett SLC-30 Option (Intermittent and Continuous Circulation Only)
Circulator with Gaskets,
8A
8056174
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Bell & Gossett NRF-22
8B G asket, Bell & Gossett NRF-22
806602029
8. Circulator, Grundfos Option (Intermittent and Continuous Circulation Only)
Circulator with Gaskets,
8A
8056173
1
1
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Grundfos UP15-42F
8B Ga sket, Grundfos 510179
806602016
2
2
2
8. Circulator, Taco 007 Option (Intermittent and Continuous Circulation Only)
8A Circulator with Gaskets, Taco 007F
8B Gasket, Taco '00' Series
8056170
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
806602006
8. Circulator, Taco 0010 Option (Intermittent and Continuous Circulation Only)
8A Circulator with Gaskets, Taco 0010 8056176
8B Gasket, Taco '00' Series 806602006
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
9. Miscellaneous Circulator Hardware (Intermittent and Continuous Circulation Only)
9A Flange, 1¼ NPT
806602013
80861301
80860406
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
2
4
4
Screw, Cap Hex Head, 7/16-14 x
9B
1½"
9C Nut, Hex, 7/16-14
10. Limit Control
10A Limit, Honeywell L4080D1036
10B Well, ½ NPT (Included w/10A)
80160156
-----
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limit, Honeywell L4080B1212
10C
80160474
80160426
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(Dual Limit Only)
We ll, ¾ NPT, Ho neywell 123870A
10D
(Dual Limit Only)
11. Miscellaneous Trim
11A Drain Cock, Conbraco 31-606-02
11B Temperature-Pressure Gauge,
11C Nipple, 1¼ NPT x 3"
806603011
8056164U
806600005
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
49
Figure 41
Quantity
202 202X 203 204 205 206 207 208 209 210
Key
No.
Description
Part No.
12. Transformer/Relay Assembly (Intermittent Circulation Only)
12A
12B
12C
Junction Box, 4" x 4" x 1½"
8136259
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Transformer/Relay, Honeywell
R8285D5001 (Includes Key No. 80160155U
12C) 50VA
Relay, Honeywell R8222U1006 80160096U
12. Transformer (Continuous and Gravity Circulation Only)
12A
12D
Junction Box, 4" x 4" x 1½"
8136259
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Transformer, 40VA, Honeywell
AT140D1012 or AT72D1188
80160039
13. Flame Rollout Switch
13A
13B
Flame Rollout Switch
80160044
7186018
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Flame Rollout Switch Mounting
Bracket (*40mm Burner Only)
1*
14. Blocked Vent Switch
Blocked Vent Switch
14
6016058
1
1
1
1
1
1
1
1
1
1
Replacement Assembly
50
Figure 42
Quantity
Key
No.
Description
Part No.
202
202X
203
204
205
206
207
208
209
210
16. Draft Hood Carton
8116067
8111702
8111703
8111704
8111705
1
1
1
---
1
---
---
1
---
---
1
---
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
16
Draft Hood
---
---
---
---
---
---
---
---
---
17. Vent Damper Carton (U.S.A. - Standard; Canada - Optional)
Automatic Vent Damper, 4"
Effikal RVGP-KS-4; or
Johnson Y15A
8116143
8116122
1
1
1
---
1
---
---
1
---
---
1
---
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
1
Automatic Vent Damper, 5"
Effikal RVGP-KS-5; or
Johnson Y15B
8116144
8116123
---
---
---
---
---
---
---
---
---
---
---
---
Automatic Vent Damper, 6"
Effikal RVGP-KS-6; or
Johnson Y15C
8116145
8116124
17
---
---
---
Automatic Vent Damper, 7"
Effikal RVGP-KS-7; or
Johnson Y15D
8116146
8116125
---
---
---
---
Automatic Vent Damper, 8"
Effikal RVGP-KS-8; or
Johnson Y15E
8116147
8116126
---
---
18. Vent Reducer
18
Reducer, 4" x 3"
8116164
1
---
---
---
---
---
---
---
---
---
51
52
|