Burnham LEDV SERIES User Manual

Price - $3.00  
INSTALLATION,OPERATINGAND  
SERVICE INSTRUCTIONS FOR  
LEDV SERIES DIRECT VENT  
OIL FIRED BOILER  
As an ENERGY STAR Partner, Burnham Corporation has determined that the LEDV-1, fired at the 0.60 GPH rate,  
meets the ENERGY STAR guidelines for Energy efficiency established by the United States Environmental Protection  
Agency (EPA).  
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide  
Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
Boiler Serial Number  
Installation Date  
LEDV__ - _______  
6 _ _ _ _ _ _ _  
Heating Contractor  
Phone Number  
Address  
81433101R3-3/00  
WARNING  
Boiler materials of construction, products of combustion and the fuel contain alumina, silica,  
heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful  
substances which can cause death or serious injury and which are known to the state of California  
to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing,  
respirators and equipment when servicing or working nearby the boiler.  
This boiler contains very hot water under high pressures. Do not unscrew any pipe fittings nor  
attempt to disconnect any components of this boiler without positively assuring the water is cool  
and has no pressure. Always wear protective clothing and equipment when installing, starting  
up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature  
gauges to determine the temperature and pressure of the boiler. This boiler contains components  
which become very hot when the boiler is operating. Do not touch any components unless they  
are cool.  
This boiler must be properly vented and connected to an approved vent system in good condition.  
Serious property damage could result if the boiler is connected to an unapproved vent system .  
This boiler needs fresh air for safe operation and must be installed so there are provisions for  
adequate combustion and ventilation air.  
The interior of the venting and air intake systems must be inspected and cleaned before the start  
of the heating season and should be inspected periodically throughout the heating season for  
any obstructions. Clean and unobstructed venting and air intake systems are necessary to allow  
noxious fumes that could cause injury or loss of life to vent safely and will contribute toward  
maintaining the boiler's efficiency.  
This boiler is supplied with controls which may cause the boiler to shut down and not re-start  
without service - If damage due to frozen pipes is a possibility, the heating system should  
not be left unatttended in cold weather; or appropriate safeguards and alarms should be installed  
on the heating system to prevent damage if the boiler is inoperative.  
This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or  
any oil containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any  
solid fuel (i. e. wood, coal) or gaseous fuel (i. e. natural gas, LP/propane). All flammable debris,  
rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area  
clean and free of fire hazards.  
All boilers equipped with Burner Swing Door have a potential hazard which can cause severe  
property damage, personal injury or loss of life if ignored. Before opening swing door, turn off  
service switch to boiler and disconnect two halves of Burner Swing Door Interlock wiring harness  
to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing  
door fastener completely and reconnect two halves of Burner Swing Door Interlock when service  
is completed.  
NOTICE  
This boiler has a limited warranty, a copy of which is printed on the back of this manual.  
It is the responsibility of the installing contractor to see that all controls are correctly installed  
and are operating properly when the installation is complete. The warranty for this boiler is valid  
only if the boiler has been installed, maintained and operated in accordance with these  
instructions.  
3
NOTICE  
All boilers must be installed in accordance with National, State and Local Plumbing, Heating  
and Electrical Codes and the regulations of the serving utilities which may differ from this  
manual. Authorities having jurisdiction should be consulted before installations are made.  
In all cases, reference should be made to the following Standards:  
USA BOILERS  
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning  
Equipment”, for recommended installation practices.  
B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces,  
Vents, and Solid Fuel Burning Appliances”, For Venting requirements.  
C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, "Controls and  
Safety Devices for Automatically Fired Boilers", for assembly and operations of controls  
and safety devices.  
CANADIAN BOILERS  
A. Current Edition of Canadian Standards Association CSA B139, "Installation Code for Oil  
Burning Equipment", for recommended Installation Practices.  
This boiler is suitable for installation on combustible flooring. Boiler cannot be installed on  
carpeting.  
For optimum performance a nd serviceability from this unit adhere to the following  
recommendations:  
A. Do not tamper with or alter the unit or controls. Retain your contractor or a competent  
serviceman to assure that the unit is properly adjusted and maintained.  
B. Clean firetubes at least once a year - preferably at the start of the heating season to remove  
soot and scale. Inside of Combustion Chamber should also be cleaned at the same time.  
C. Have Oil Burner and Controls checked at least once a year or as may be necessitated.  
D. Do not operate unit with jumpered or absent controls or devices.  
E. Do not operate unit if any control, switch, component, or device has been subject to water.  
4
Table of Contents  
I. Pre-Installation ......................................... 6  
II. Unpack Boiler ........................................... 7  
III. Water Piping and Trim ............................ 9  
IV. Venting/Air Intake Piping ..................... 12  
V. Electrical and Sequence of Operations .. 18  
VI. Oil Piping ............................................... 20  
VII. System Start-up ...................................... 22  
VIII. Service and Cleaning.............................. 26  
IX. Repair Parts ............................................ 29  
Figure 1: LEDV Packaged Boiler  
5
I. Pre-Installation  
A. INSPECT SHIPMENT carefully for any signs of  
C. PROVIDECOMBUSTIONAIRSUPPLYto  
accommodate proper combustion of oil. Local and  
national codes may apply and should be referenced.  
damage.  
1. ALL EQUIPMENT is carefully manufactured,  
inspected and packed. Our responsibility ceases  
upon delivery of crated boiler to the carrier in good  
condition.  
1. In unconfined spaces (basement) in buildings of  
conventional frame, brick, or stone construction,  
infiltration normally is adequate to provide air for  
combustion. An unconfined space is a space whose  
volume is greater than or equal to 50 cubic feet per  
1000 BTUH of the combined input of all air  
consuming appliances in the space.  
2. ANY CLAIMS for damage or shortage in shipment  
must be filed immediately against the carrier by the  
consignee. No claims for variances from, or  
shortage in orders, will be allowed by the  
manufacturer unless presented within sixty (60)  
days after receipt of goods.  
2. In a confined space, combustion air may be ducted  
directly from the outdoors to the burner. Refer to  
Section IV for installation of air intake duct to the  
burner.  
B. LOCATE BOILER in front of final position before  
removingcrate. SeeFigure1. Boiler'sapproximate  
shipping weight is 325 pounds.  
D. VENTILATION AIR must be provided to maintain the  
ambient temperature at safe limits. Local and national  
codes may apply and should be referenced.  
1. LOCATE so that vent pipe will be short and direct.  
Refer to Section V. A., General Venting  
Guidelines.  
1. In unconfined spaces (basement) in buildings of  
conventional frame, brick, or stone construction,  
infiltration normally is adequate to provide air for  
ventilation.  
2. BOILERISSUITABLEFORINSTALLATIONON  
COMBUSTIBLEFLOOR.Boilercannotbeinstalled  
on carpeting.  
2. In confined spaces (closet, etc.) two permanent  
openings, one near the top of the enclosure and one  
near the bottom, shall be provided. Each opening  
shall have a free area of not less than 1 sq. inch per  
1000 BTUH of the total input of all appliances in  
the space.  
3. FORBASEMENTINSTALLATION,provideasolid  
base, such as concrete, if floor is not level, or if water  
may be encountered on floor around boiler.  
4. PROVIDESERVICECLEARANCEofatleast24at  
front of boiler for servicing.  
E. Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners, chemicals,  
sprays, paint removers, fabric softeners, etc.) are used  
or stored.  
5. For minimum clearances to combustible materials,  
see Figure 2.  
6
II. Unpack Boiler  
4. Remove 4 hex nuts from bolts that attach hinges  
and hinge spacers to left side of Tubesheet. Remove  
4 hex head cap screws that attach hinges to door.  
CAUTION  
Do not drop boiler. Do not bump boiler jacket  
against floor.  
5. Attach 2 hinge brackets & spacers to Tubesheet and  
2 hinge brackets to Door on right side of boiler. 3  
Holes in each Hinge Bracket must line up with 3  
matching holes in Spacer, Tubesheet or Door. See  
Figure 3. Tighten hex nuts, bolts and screws by  
hand only.  
A. REMOVE CRATE  
1. Remove all fasteners at crate skid.  
2. Lift outside container and remove all other inside  
protective spacers and bracing. Remove vacuum  
relief valve and miscellaneous trim bag containing  
safety/relief valve, and pipe fittings.  
6. Replace door assembly. Hinge brackets attached to  
door must rest on top of hinge brackets attached to  
tubesheet. See Figure 4. Slide hinge pins through  
hinges from top and install cotter pins. Close door  
and install 5/16" - 18 x 3" long hex head cap  
screws through flat washers and left side of door  
and into tapped holes in tubesheet. Tighten all hex  
nuts, bolts and screws. When door is installed  
properly, it is parallel to Tubesheet when viewed  
from top and sides.  
B. REMOVAL OF BOILER FROM SKID  
1. Boiler is secured to base with 2 bolts, 1 at left front  
and 1 at right rear. Remove both bolts.  
2. Tilt boiler, "walk" boiler backward, and set rear  
legs down on floor. Tilt boiler backward, pull skid  
forward and set front legs down on edge of skid.  
Install close nipple, tee, and plug in return  
coupling. See Section III and Figure 5. Point tee  
toward permanent return location.  
7. Bend sides of Jacket Wrapper down and attach 2  
Jacket Straps to 4 slots at bottom of Jacket Wrapper  
sides with sheet metal screws. Install Rear Jacket  
Box with 4 sheet metal screws. See Figure 20.  
3. Tilt boiler backward and remove skid. Be careful  
not to damage Burner or Jacket.  
8. Connect wiring harness to burner Junction Box and  
install Honeywell R8184P Control, see Wiring  
Diagram, Figure 15.  
C. DETERMINE PROPER HINGE LOCATION FOR  
BURNER SWING DOOR. Boiler is shipped with  
hinges on left side. Approximately 12 inches are  
required on the hinge side for burner clearance. If  
there will be less than 12 inches from left side of boiler  
to wall, move hinges to right side (refer to Paragraph  
D).  
Reconnect Swing Door Interlock.  
E. INSTALL BOILER CONTROL.  
1. Pull bulb and capillary tube out of hole in back of  
control. Insert bulb in immersion well on top of  
boiler and secure control with set screw in control.  
D. HINGE LOCATION CHANGE (if required).  
2. Secure flexible conduit to Jacket Wrapper side with  
conduit clamp and sheet metal screw. Conduit  
must be on same side of boiler as Swing Door  
hinges.  
1. Pull 2 halves of Burner Swing Door Interlock apart.  
Swing Door Interlock is connected to R-W  
terminals on R8184P Control. Lift Honeywell  
R8184P Control off of Burner Junction Box and  
disconnect wiring harness from burner.  
F. MOVE BOILER TO PERMANENT POSITION by  
sliding or walking.  
2. Remove 8 sheet metal screws from jacket. Remove  
rear jacket box and bend both sides of Jacket  
Wrapper up, see Figure 20.  
G. INSPECT FRONT AND REAR DOOR INSULATION  
AND COMBUSTION CHAMBER LINER  
3. Remove 2 (two) 5/16" - 18 x 3" long hex head cap  
screws and flat washers from right side of door.  
Remove 2 hairpin cotter pins and 2 hinge pins from  
hinges on left side of door and remove Door  
Assembly from boiler. Inspect Front and Rear Door  
Insulation Pieces and Combustion Chamber Liner,  
see Paragraph G.  
1. OPEN BURNER SWING DOOR on front of boiler.  
Use flashlight to inspect insulation secured to front  
and rear doors. Inspect ceramic fiber blanket  
secured to bottom of combustion chamber. Inspect  
inner and outer door gaskets. Replace any damaged  
pieces.  
7
Figure 3: Proper Hinge Bracket Installation  
Figure 4: Hinge Assembly  
Figure 2: Minimum Clearances to Combustible Materials  
8
III. Water Piping and Trim  
refrigerated air, the boiler piping must be equipped  
with flow control valves to prevent gravity  
circulation of boiler water during the operation of the  
cooling system.  
3. If boiler is used with an Alliance Indirect-Fired  
Domestic Water Heater, install the Alliance as a  
separate heating zone. Refer to the Alliance  
Installation, Operating, and Service Instructions for  
additionalinformation.  
A. Design and install boiler and system piping to  
prevent oxygen contamination of boiler water.  
4. Use a system bypass if the boiler is to be operated in  
a system which has a large volume or excessive  
radiation where low boiler water temperatures may  
be encountered (i.e. converted gravity circulation  
system, etc.).  
There are many possible causes of oxygen  
contamination such as:  
The bypass should be the same size as the supply  
and return lines with valves located in the bypass  
and return line as illustrated in Figures 5 and 7 in  
order to regulate water flow for maintenance of  
higherboilerwatertemperature.  
1. Addition of excessive make-up water as a result of  
system leaks.  
2. Absorption through open tanks and fittings.  
3. Oxygen permeable materials in the distribution  
system.  
Set the by-pass and return valves to a half throttle  
position to start. Operate boiler until the system  
water temperature reaches its normal operating  
range.  
Adjust the valves to maintain 180°F to 200°F boiler  
water temperature and greater than 120°F return  
temperature. Adjust both valves simultaneously.  
Closing the boiler return valve while opening the by-  
pass valve will raise the boiler return temperature.  
Opening the boiler return valve while closing the by-  
pass valve will lower the boiler return temperature.  
In order to insure long product life, oxygen sources  
should be eliminated. This can be accomplished by  
taking the following measures:  
1. Repairing system leaks to eliminate the need for  
addition of make-up water.  
2. Eliminating open tanks from the system.  
3. Eliminating and/or repairing fittings which allow  
oxygen absorption.  
4. Use of non-permeable materials in the distribution  
system.  
5. A hot water boiler installed above radiation level  
must be provided with a low water cutoff device as  
part of the installation.  
5. Isolating the boiler from the system water by  
installing a heat exchanger.  
C. Install Safety Relief Valve. See Figures 5 and 7. Safety  
Relief Valve must be installed with spindle in vertical  
position. Installation of the relief valve must be  
consistent with the ANSI/ASME Boiler and Pressure  
VesselCode,SectionIV.  
B. Connect System supply and return piping to boiler. See  
Figures 5 and 7. Also consult I=B=R Installation and  
PipingGuides. Maintainminimum½inchclearancefrom  
hot water piping to combustible materials.  
1. If this boiler is used in connection with refrigeration  
systems, the boiler must be installed so that the  
chilled medium is piped in parallel with the heating  
boiler using appropriate valves to prevent the chilled  
medium from entering the boiler, see Figure 6. Also  
consult I=B=R Installation and Piping Guides.  
WARNING  
Safety (relief) valve discharge piping must  
be piped near floor to eliminate potential of  
severe burns. Do not pipe in any area where  
freezing could occur. Do not install any shut-  
off valves, plugs or caps.  
2. If this boiler is connected to heating coils located in  
air handling units where they may be exposed to  
9
Figure 5: Recommended Boiler Piping for Zoning with Valves  
isolation valve in boiler supply piping. (Note -  
Terminate hose in five gallon bucket at a suitable  
floor drain or outdoor area).  
D. InstallDrainValveinreturnpiping. Seefigure5.  
E. Oil, grease, and other foreign materials which  
accumulate in new hot water boilers and a new or  
reworked system should be boiled out, and then  
thoroughly flushed. A qualified water treatment  
chemical specialist should be consulted for  
4. Starting with one circuit, open zone valve.  
5. Open bib cock.  
6. Open fill valve (Make-up water line should be  
located directly above isolation valve in boiler  
supply piping).  
recommendations regarding appropriate chemical  
compounds and concentrations which are compatible  
with local environmental regulations.  
7. Allow water to overflow from bucket until dis charge  
from hose is bubble free for 30 seconds.  
F. After the boiler and system have been cleaned and  
flushed, and before refilling the entire system add  
appropriate water treatment chemicals, if necessary, to  
bring the pH between 7 and 11.  
8. Open zone valve to the second zone to be purged,  
then close the first. Repeat this step until all zones  
have been purged, but always have one zone open.  
At completion, open all zone valves.  
G. Fill entire heating system with water and vent air  
from system. Use the following procedure on a Series  
Loop System equipped with zone valves. (See Figure  
5).  
9. Close bib cock, continue filling the system until  
the pressure gauge reads 12 psi. Close fill valve.  
(Note - If make-up water line is equipped with  
pressure reducing valve, system will automatically  
fill to 12 psi.  
1. Close isolation valve in boiler supply piping.  
2. Isolate all circuits by closing zone valves or  
balancing valves.  
10. Open isolation valve in boiler supply piping.  
11. Remove hose from bib cock.  
3. Attach a hose to bib cock located just below  
10  
Figure 6: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems  
Figure 7: Recommended Boiler Piping for Zoning with Circulators  
11  
IV. Venting / Air Intake Piping  
A. GeneralGuidelines  
1. Vent system installation must be in accordance with  
these instructions and applicable provisions of local  
building codes. Contact local building or fire officials  
about restrictions and installation inspection in your  
area.  
2. The LEDV Series is designed as a Direct Vent boiler.  
In this configuration, all air for combustion is  
supplied directly to the burner from outdoors and  
flue gases are vented directly outdoors (through  
wall). See Figures 10 and 11. The LEDV may be  
side-wall vented with combustion air supplied from  
indoors. This configuration may be used in  
5. Vent Terminal Location (see Figure 8). Locate vent  
terminal so vent pipe is short and direct. The vent  
terminal must be located:  
a. Not less than 12 inches above grade plus snow  
accumulation.  
installations where infiltration provides adequate air  
for combustion and ventilation. Flue gases are still  
vented directly outdoors (through wall).  
b. Not less than 4 feet below, 4 feet horizontally, or  
1 foot above any door, window, or gravity air  
inlet.  
3. Forminimumclearancestocombustiblematerials  
refer to Figure 2.  
c. Not less than 3 feet above any forced air inlet  
located within 10 feet.  
4. Maximum wall thickness that vent terminal may be  
installed through is 10 inches.  
d. Not less than 2 feet from an adjacent building.  
e. Not less than 7 feet above a public walkway.  
Figure 8: Vent Terminal Location  
12  
Components of this kit are listed in the Repair Parts  
Section of this manual.  
6. IntakeTerminalLocation(DirectVentonly)-Locate  
Air Intake Terminal not less than 12 inches to the  
left, right, or bottom of the vent terminal. Do not  
locate air intake terminal above vent terminal. Intake  
terminal must be at least 12 inches above grade plus  
snow accumulation. See Figure 9.  
7. The LEDV must be vented with 4" Z-Flex Direct  
OilVent. 20feetisthemaximumventlength  
allowed. The vent pipe is available in 5, 10, 15, and  
20 foot lengths. Table 1 lists vent part numbers.  
B. VentInstallation(DirectVentandSide-WallVent)  
1. Install Vent Terminal. See Figure 10.  
a. After determining the location from previous  
Section, cut an opening in the wall for the vent  
terminal.  
Table 1: Vent Pipe Part Numbers  
4" Direct Oil™ Vent Pipe  
Combustible wall: 8 inches diameter hole is  
required to maintain a 1 inch clearance to  
combustiblematerials.  
Pipe Length  
5 Ft.  
Burnham Part No.  
8113302  
Non-combustible wall: 6½ inches diameter  
hole is required.  
10 Ft.  
8113303  
15 Ft.  
8113304  
b. Secure trim plate to outside wall.  
c. Insert the vent terminal through the opening  
until the stop bead rest against the trim plate.  
20 Ft.  
8113305  
8. The vent system must be completed with the Direct  
Oil™ Vent Kit, which is shipped with the boiler.  
d. Slide the inside trim plate assembly (fitted with  
gear clamp) onto the terminal pipe.  
Figure 9: Intake Terminal Location  
13  
Figure 10: Vent Installation  
Figure 11: Vent Connector, Un-Assembled  
14  
Figure 12: Vent Connector, Assembled  
Figure 13: Air Intake Installation  
15  
e. Secure the inside trim plate to inside wall.  
f. Tighten the gear clamp to the terminal pipe.  
g. Seal all external joints with a weatherproof caulk.  
2. Cut vent pipe to length with a hack saw.  
a. All horizontal runs must rise at least ¼ inch per  
foot toward vent terminal.  
b. Avoid any sags or dips in vent pipe.  
C. Air Intake Installation (Direct Vent only)  
See Figure 13.  
3. Install Vent Connector/Appliance Adaptor. See  
Figures 11 and 12.  
a. Apply a continuous bead of high temperature  
adhesive/sealant (supplied with boiler) around  
outside of corrugated pipe of vent connector.  
b. Twist vent connector into end of vent pipe.  
Turn the connector counter-clockwise until it is  
engaged approximately 4 inches into the inner  
vent pipe and the outer collar of the connector  
overlaps the outside of the vent pipe.  
1. General  
a. Use 4 inch diameter single wall metal pipe and  
fittings available at most heating distributors.  
Maximum allowable air intake length is 40  
equivalent feet. Each elbow is equal to 6  
equivalent feet.  
c. Tighten the gear clamp on the outer collar of the  
connector.  
d. Repeat steps a. through c. with the appliance  
adapter.  
4. Connect vent pipe to boiler.  
b. Start at Burner. Work toward air intake terminal.  
a. Apply a continuous bead of high temperature  
adhesive/sealant (supplied with boiler) to inside  
of appliance adapter (approximately ½ inch  
from end).  
c. Maintain minimum of ¼ inch per foot slope in  
horizontal run to air intake terminal. Slope  
down toward air intake terminal.  
d. Seal all joints gas-tight, using silicone caulk or  
self-adhesive aluminum tape.  
b. Slip appliance adapter over boiler flue collar and  
tighten gear clamp.  
2. After determining location, cut a hole in the wall to  
accept 4 inch air intake pipe.  
5. Connect vent pipe to terminal.  
a. Carefully slide insulation sleeve over vent  
connector and vent pipe until gear clamp on  
small end of connector can be accessed.  
3. Remove the black plastic inlet cover from the right  
side of the Beckett AFII burner.  
4. Mount the vacuum relief valve tee assembly or 90°  
elbow into the burner inlet ring. See Figure 13.  
a. Secure with at least three (3) sheet metal screws  
evenly spaced around the burner inlet ring.  
b. Assemble the vacuum relief valve balance  
weight onto the gate. Refer to the vacuum relief  
valve manufacturer's instructions.  
b. Apply a continuous bead of high temperature  
adhesive/sealant (supplied with boiler) on inside  
of cent connector (approximately ½ inch from  
end).  
c. Mount the vacuum relief valve into the tee and  
fasten with a screw and nut in collar tabs. To  
ensure proper operation, the gate must be level  
across the pivot point and plumb. Refer to  
vacuum relief valve manufacturer's instructions.  
c. Clip connector over vent terminal until it is fully  
engaged. Then tighten gear clamp.  
d. Slide insulation sleeve over terminal connection  
so that connector is completely covered.  
5. Install remainder of air intake, securing each joint  
with at least three (3) sheet metal screws evenly  
spaced.  
e. Secure each end of insulation sleeve with the  
gear clamps provided.  
6. Secure vent pipe in position with pipe straps.  
16  
D. AirIntakeInstallation (IndoorAirforCombustion)  
1. Remove the black plastic inlet cover from the right  
side of the Beckett AFII burner.  
2. Attach the Air Intake Terminal directly to the burner  
intakecollar.  
3. DiscardtheVacuumReliefValve.  
6. Install air intake terminal. See Figure 13.  
Alternate to 1., 2. and 3.:  
Keep the black plastic inlet cover in place and  
discard the Air Intake Terminal and the Vacuum  
ReliefValve.  
7. Seal all external joints with weatherproof caulk.  
17  
V. Electrical and Sequence of Operations  
and ignition transformer.  
A. ELECTRICAL  
b. After a 15 second pre-purge period, in which  
time a draft is established in the flueways, the  
oil valve is opened.  
1. Install wiring and ground boiler in accordance with  
requirements of authority having jurisdiction, or in  
absence of such requirements the National  
Electrical Code, ANSI/NFPA 70, and/or the CSA  
C22.1 Electric Code.  
c. If the burner ignites within 15 seconds from the  
time the oil valve opens and the CAD cell senses  
a flame, the burner will operate until the call for  
heat is satisfied or the setting of the high limit is  
reached.  
2. A separate electrical circuit should be run from the  
main electrical service with a fused disconnect  
switch in the circuit.  
d. A manual reset button is provided to reset the  
safety switch after lockout.  
3. Wiring should conform to Figure 15.  
B. SEQUENCE OF OPERATIONS  
e. When the call for heat ends, or the CAD cell  
fails to sense a flame, the oil valve will close.  
The combustion blower will continue to operate  
for a postpurge period of approximately two (2)  
minutes.  
1. General. A call for heat by the thermostat  
energizes the L8148A limit control which in turn  
energizes the R8184P primary control to turn on  
the burner. The circulator will operate as long as  
there is a call for heat. If the call for heat is not  
satisfied and the high limit setting is reached, the  
circulator will continue to operate, and the burner  
will stop until the high limit circuit is closed by a  
drop in boiler water temperature.  
4. CAD Cell.  
The Beckett AFII burners used on the LEDV Series  
are supplied with a C554A Cadmium Sulfide (cad  
cell) Flame Detector to monitor the burner flame  
and shut down the burner on ignition failure or on  
flame failure during the run cycle. On either  
failure, the manual reset button on the R8184P will  
be tripped.  
2. L8148A Combination Limit control.  
The switching action within the L8148A control  
has one setting, the high limit. The switching relay  
is controlled by the low voltage room thermostat.  
On a call for heat, the relay contacts close to  
complete the line voltage circulator circuit and also  
the burner circuit if the boiler water temperature is  
below the high limit setting. The high limit switch  
shuts off the burner if boiler water temperature  
exceeds the high limit setting. See Figure 14.  
3. R8184P Oil Primary Control.  
The R8184P operates the oil burner motor, solenoid  
oil valve, and the ignition transformer in response  
to a call for heat from the L8148A limit control.  
a. A call for heat will energize the burner motor  
Figure 14: Control Differential  
18  
Figure 15: Schematic Wiring Diagram  
VI. Oil Piping  
A. General  
TABLE 2: SINGLE-STAGE UNITS (3450 RPM)  
TWO-PIPE SYSTEMS  
1. Use flexible oil line(s) so that Swing Door can be  
opened without disconnecting oil supply.  
Maximum Length of Tubing  
"H" + "R" (See Figure 16)  
Lift "H"  
2. A supply line fuel oil filter is recommended as a  
minimum for all firing rates but a pleated paper  
fuel oil filter is recommended for the lowest (.6  
GPH) firing rate application to prevent nozzle  
fouling.  
(See Fig. 16)  
3/8" OD  
1/2" OD  
Tubing (3 GPH)  
Tubing (3 GPH)  
0'  
1'  
84'  
78'  
73'  
68'  
63'  
57'  
52'  
47'  
42'  
36'  
31'  
26'  
21'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
83'  
3. Use Flared fittings only. Do not use compression  
fittings.  
2'  
4. Use of a high efficiency micron oil filter (Garber or  
equivalent) in addition to conventional filter is  
highly recommended.  
3'  
4'  
5'  
B. Single-pipe Oil Lines.  
6'  
1. Standard burners are provided with single-stage  
3450 rpm fuel units with the bypass plug removed  
for single-pipe installations.  
7'  
8'  
9'  
2. The single-stage fuel unit may be installed single-  
pipe with gravity feed or lift. Maximum allowable  
lift is 8 feet. See Figure 16.  
10'  
11'  
12'  
13'  
14'  
62'  
---  
41'  
Figure 16: Single-Pipe Installation  
20  
Figure 17: Two-Pipe Installation  
C. Two-Pipe Oil Lines.  
TABLE 3: TWO-STAGE UNITS (3450 RPM)  
TWO-PIPE SYTEMS  
1. For two-pipe systems where more lift is required,  
the two-stage fuel unit is recommended. Table 2  
(single-stage) and Table 3 (two-stage) show  
allowable lift and lengths of 3/8-inch and ½-inch  
OD tubing for both suction and return lines. Refer  
to Figure 17.  
Maximum Length of Tubing  
"H" + "R" (See Figure)  
Lift "H"  
(See Fig. )  
3/8" OD  
1/2" OD  
Tubing (3 GPH) Tubing (3 GPH)  
0'  
2'  
93'  
85'  
77'  
69'  
60'  
52'  
44'  
36'  
27'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
76'  
4'  
6'  
8'  
10'  
12'  
14'  
16'  
18'  
21  
VII. System Start-up  
WARNING  
All boilers equipped with burner swing door have a potential hazard which can cause severe  
property damage, personal injury or loss of life if ignored. Before opening swing door, turn off  
service switch to boiler to prevent accidental firing of burner outside the combustion chamber.  
Be sure to tighten swing door fastener completely when service is completed.  
A. ALWAYSINSPECTINSTALLATIONBEFORE  
F. BURNERSTART-UP  
STARTING BURNER.  
B. FILL HEATING SYSTEM WITH WATER. Refer to  
Section III, G.  
C. CHECK CONTROLS, WIRING AND BURNER to be  
sure that all connections are tight and burner is rigid,  
that all electrical connections have been completed and  
fuses installed, and that oil tank is filled and oil lines  
have been tested.  
1. VERIFYburnersettings.  
a. Refer to Table 4.  
2. Open all shut-off valves in the oil supply line to the  
burner.  
D. LUBRICATION — Follow instruction on burner and  
circulator label to lubricate, if oil lubricated. Most  
motors currently used on residential type burners  
employ permanently lubricated bearings and thus do  
not require any field lubrication. Water lubricated  
circulators do not need field lubrication.  
3. Attach a plastic hose to fuel pump vent fitting and  
provide a container to catch the oil.  
4. REMOVE GAUGE PORT PLUG from fuel pump  
and install pressure gauge.  
Do not over-lubricate. This can cause as much trouble  
as no lubrication at all.  
5. REMOVE TEST PLUG IN FLUE COLLAR.  
E. SET CONTROLS with burner service switch turned  
6. Close the service switch to start the burner. If the  
burner does not start immediately, check the  
manual overload switch on the motor, if so  
equipped, and the safety switch of the burner  
primary control.  
“OFF”.  
1. SET ROOM THERMOSTAT about 10° above  
room temperature.  
2. PRESS RED RESET BUTTON on R8184P Oil  
Primary Control and release.  
3. Set high limit dial on L8148 at temperature to suit  
requirements of installation.  
TABLE 4: BECKETT AFII BURNER  
Settings  
Boiler  
Model  
Firing Rate  
(GPH)  
Air Tube  
Burner  
Delavan Nozzle  
Air  
Head  
Pump Pressure  
(PSIG)  
Combination  
(stop screw)  
LEDV-1  
LEDV-2  
LEDV-3  
0.60  
1.00  
1.25  
AFII 85  
AFII 150  
AFII 150  
HLX50HD  
HLX50HE  
HLX50HE  
0.50 x 70°B  
0.85 x 60°B  
1.00 x 60°B  
2.5  
3.5  
4.0  
#2  
#3  
#5  
140  
140  
140  
22  
Figure 18: Electrode / Head Setting  
7. Bleed the fuel unit when the burner motor starts  
with the microTEKDV boiler is the result of  
extensive testing to obtain the best flame shape  
and efficient combustion. Other brands of the  
same spray angle and spray pattern may be used  
but may not perform at the expected level of  
CO2 and smoke. Nozzles are delicate and should  
be protected from dirt and abuse. Nozzles are  
mass-produced and can vary from sample to  
sample. For all of those reasons a spare nozzle is  
a desirable item for a serviceman to have.  
rotating. To bleed, loosen the vent fitting (with  
plastic hose attached) and catch the oil in an empty  
container. Continue to bleed for 15 seconds after  
oil is free of air bubbles. Tighten the vent fitting  
when all the air is purged. NOTE: Bleeding might  
not be necessary with a two pipe system. When  
vent fitting is closed, burner flame should start  
immediately.  
8. ADJUST OIL PRESSURE  
b. FLAME SHAPE — Looking into the  
combustion chamber through the flame plug  
hole, the flame should appear straight with no  
sparklers rolling up toward the top of the  
chamber. If the flame drags to the right or left,  
sends sparklers upward or makes wet spots on  
the rear door insulation piece, the nozzle should  
be replaced. If the condition persists look for  
fuel leaks, air leaks, water or dirt in the fuel as  
described below.  
a. Locate oil pressure adjusting screw and turn  
screw to obtain 140 PSIG pressure.  
b. DO NOT REMOVE PRESSURE GAUGE until  
later.  
9. ADJUST AIR SETTING on burner for a light  
orange colored flame. Use a smoke tester and  
adjust air for minimum smoke (not to exceed  
#1) with a minimum of excess air. Make final  
check using suitable instrumentation to obtain a  
CO2 of 11.5 to 12.5%. These settings will assure a  
safe and efficient operating condition. If the flame  
appears stringy instead of a solid fire, try another  
nozzle of the same type. Flame should be solid and  
compact.  
c. FUEL LEAKS — Any fuel leak between the  
pump and the nozzle will be detrimental to good  
combustion results. Look for wet surfaces in the  
air tube, under the transformer, and around the  
air inlet. Any such leaks should be repaired as  
they may cause erratic burning of the fuel and in  
the extreme case may become a fire hazard.  
10. TURN "OFF" BURNER BY OPENING SERVICE  
SWITCH. Remove pressure gauge. Install gauge  
port plug and tighten. Re-start burner.  
d. AIR LEAKS — Any such leaks should be  
repaired, as they may cause erratic burning of  
the fuel and in extreme cases may become a fire  
hazard.  
11. HINTS ON COMBUSTION  
a. NOZZLES — Although the nozzle is a  
relatively inexpensive device, its function is  
critical to the successful operation of the oil  
burner. The selection of the nozzle supplied  
There are many possible causes of air leaks in  
oil lines such as:  
23  
i. Fitting leaks due to mis-flared tubing or  
is to bury the tank and lines deep enough to  
keep the oil above 40°F.  
damaged fitting.  
ii. Fuel line leak due to crushed or bent tubing.  
iii. Filter connection leaks.  
i. HIGH ALTITUDE INSTALLATIONS — Air  
settings must be increased at higher altitudes.  
Use instruments and set for 11.5 to 12.5% CO2.  
iv. Tank connection leaks.  
There are various test kits available to trace  
air leaks, such as electronic sight glasses.  
Follow the manufacturers' instructions to  
find air leaks.  
j. START-UP NOISE — Late ignition is the cause  
of start-up noises. If it occurs recheck for  
electrode settings, flame shape, air or water in  
the fuel lines.  
The following actions can eliminate air leaks:  
k. SHUT DOWN NOISE — If the flame runs out  
of air before it runs out of fuel, an after burn  
with noise may occur. That may be the result of  
a faulty cut-off valve in the fuel pump, or it may  
be air trapped in the nozzle line. It may take  
several firing cycles for that air to be fully  
vented through the nozzle. Water in the fuel or  
poor flame shape can also cause shut down  
noises.  
i. Bleed pump as detailed in System Start-Up  
Section of this manual.  
ii. Replace flare fittings.  
iii. Replace oil supply line.  
iv. Repair oil filter leaks.  
v. Replace or repair tank fittings.  
e. GASKET LEAKS — If 11.5 to 12.5% CO2 with  
a #1 smoke cannot be obtained in the breeching,  
look for air leaks around the flue collar. Such air  
leaks will cause a lower CO2 reading in the  
breeching. The smaller the firing rate the  
greater effect an air leak can have on CO2  
readings.  
f. DIRT — A fuel filter is a good investment.  
Accidental accumulation of dirt in the fuel  
system can clog the nozzle or nozzle strainer  
and produce a poor spray pattern from the  
nozzle. The smaller the firing rate, the smaller  
the slots become in the nozzle and the more  
prone to plugging it becomes with the same  
amount of dirt.  
G. TEST CONTROLS  
g. WATER — Water in the fuel in large amounts  
will stall the fuel pump. Water in the fuel in  
smaller amounts will cause excessive wear on  
the pump, but more importantly water doesn’t  
burn. It chills the flame and causes smoke and  
unburned fuel to pass out of the combustion  
chamber and clog the flueways of the boiler.  
WARNING  
Before installation of the boiler is considered  
complete, the operation of the boiler controls  
should be checked, particularly the primary  
control and high limit control.  
h. COLD OIL — If the oil temperature  
1. CHECK THERMOSTAT OPERATION. Raise and  
lower thermostat setting as required to start and  
stop burner.  
approaching the fuel pump is 40°F or lower  
poor combustion or delayed ignition may result.  
Cold oil is harder to atomize at the nozzle.  
Thus, the spray droplets get larger and the flame  
shape gets longer. An outside fuel tank that is  
above grade or has fuel lines in a shallow bury is  
a good candidate for cold oil. The best solution  
2. VERIFY PRIMARY CONTROL SAFETY  
FEATURES using procedures outlined in  
Instructions furnished with control (See back of  
Control Cover) or Instructions as follows:  
24  
temperature. Burner should start.  
FOR HEATING SERVICEMAN ONLY  
a. Simulate flame failure:  
d. Adjust thermostat to lowest setting. Adjust limit  
to desired setting.  
Follow the starting procedure to turn on the  
burner.  
Close the hand valve in the oil supply line.  
4. CHECK LOW WATER CUTOFF (if so equipped).  
a. Adjust thermostat to highest setting.  
Safety switch should lock out in  
b. With boiler operating, open drain valve and  
slowly drain boiler.  
approximately 15 seconds. Ignition should  
stop and oil valve should close. Blower will  
stop after postpurge period.  
c. Burner should stop when water level drops  
below low water cutoff probe. Verify limit,  
thermostat or other controls have not shut off  
boiler.  
Push red reset button to reset safety switch.  
b. Simulate ignition failure:  
Follow the starting procedure to turn on the  
burner, but do not open the oil supply hand  
valve.  
d. Adjust thermostat to lowest setting. Refill  
boiler.  
Safety switch should lock out in  
approximately 15 seconds. Ignition and  
motor should stop and oil valve should  
close.  
H. Boiler is now ready to be put into service.  
Push red reset button to reset safety switch.  
c. Simulate power failure:  
Follow the starting procedure to turn on the  
burner.  
With the burner running, turn off the power  
to the system by tripping the circuit breaker  
or removing the fuse.  
A leaky system will increase the volume of make-up  
water supplied to the boiler which can significantly  
shorten the life of the boiler. Entrained in make-up  
water are dissolved minerals and oxygen. When the  
fresh, cool make-up water is heated in the boiler the  
minerals fall out as sediment and the oxygen escapes  
as a gas. Both can result in reduced boiler life. The  
accumulation of sediment can eventually isolate the  
water from contacting the steel. When this happens  
the steel in that area gets extremely hot and eventually  
cracks. The presence of free oxygen in the boiler  
creates a corrosive atmosphere which, if the concen-  
tration becomes high enough, can corrode the steel  
through from the inside. Since neither of these failure  
types are the result of a manufacturing defect the  
warranty does not apply. Clearly it is in everyone’s  
best interest to prevent this type of failure. The  
maintenance of system integrity is the best method to  
achieve this.  
Burner should stop.  
Restore power. Burner should start.  
d. If system does not operate as described, go to the  
TROUBLESHOOTING AND MAINTENANCE  
section.  
3. VERIFY HIGH LIMIT OPERATION.  
a. Adjust thermostat to highest setting.  
b. Observe temperature gauge. When temperature  
is indicated, adjust limit to setting below  
observed temperature. Burner should stop.  
c. Adjust limit to setting above observed  
25  
Section VIII: Service and Cleaning  
WARNING  
All boiler service and cleaning must be completed with burner service switch turned off. Boilers  
equipped with burner swing door have a potential hazard which can cause severe property  
damage, personal injury or loss of life if ignored. Before opening swing door, turn off service  
switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to  
tighten swing door fasteners completely when service is completed.  
piece. Inspect front and rear door insulation  
pieces, front door gaskets and combustion  
chamber liner for damage. Replace any damaged  
pieces.  
4. CLOSE BOILER  
CAUTION: Do not start burner unless burner swing  
door is securely closed. Close door, install fasteners,  
and tighten securely. Door should be parallel to  
tubesheet when viewed from top and sides.  
Reconnect two halves of Swing Door Interlock.  
C. Vent/Air Intake System. Inspect for obstructions,  
soot accumulation, proper support, and deterioration of  
pipe, fittings, and joints.  
A. General. Inspection, service and cleaning should be  
conducted annually. Turn off electric power and close  
oil supply valve while conducting service or  
maintenance.  
1. Inspect inside of vent pipe.  
B. Firetubes and Combustion Chamber.  
a. Disconnect appliance adapter from boiler flue  
collar.  
1. CLEAN THE FIRETUBES  
b. Remove any obstructions and clean with a wire  
brush as required.  
a. For access to fireside of boiler, pull two halves  
of Burner Swing Door Interlock wiring harness  
apart, remove fasteners holding door closed and  
open swing door.  
c. Reconnect appliance adapter to boiler flue collar  
as detailed in Section IV: Venting/Air Intake  
Piping.  
b. Prior to cleaning boiler, lay a protective cloth or  
plastic over combustion chamber liner.  
2. Clean terminal screens. Terminals must be free of  
obstruction, undamaged, with screens securely in  
place.  
c. Using a 1 1/2" diameter wire brush (30"  
handle), clean firetubes. Measure 15" from end  
of brush opposite handle, and mark handle. DO  
NOT allow this mark to go past front end of  
firetube during cleaning, or brush will hit rear  
door insulation piece.  
3. Terminal and wall thimbles (if used) must be  
weather-tight.  
4. Pipe must be full round shape, and show no damage  
from impact or excessive temperature.  
2. CLEAN THE COMBUSTION CHAMBER  
5. Pipe must be supported at minimum 5 foot intervals  
and must not sag.  
Using wire or fiber bristle brush, clean inside of  
combustion chamber. DO NOT let brush hit rear  
door insulation piece or combustion chamber liner.  
6. All vent joints must be secure and watertight.  
7. All air intake joints must be secure and airtight.  
3. AFTER CLEANING  
a. Vacuum debris inside bottom of rear door,  
remove protective cloth, and vacuum remaining  
fireside of boiler as necessary. BE CAREFUL  
not to damage liner or rear door insulation  
D. Burner.  
1. Replace the oil supply line filter.  
26  
an external float type low water cutoff is on the  
boiler, the blow off valve should be opened once  
a month (use greater frequency where conditions  
warrant), to flush out the sediment chamber so  
the device will be free to function properly.  
2. Remove and clean the pump strainer (if applicable).  
3. Replace the nozzle with an equivalent nozzle. See  
Table 4.  
4. Clean and inspect the electrodes for damage,  
replacing any that are cracked or chipped.  
b. Annual Service. Float type low water cutoffs  
should be dismantled annually by qualified  
personnel, to the extent necessary to insure  
freedom from obstructions and proper  
5. Clean the combustion head of all lint and soot.  
6. Inspect the transformer cables and connectors.  
7. Remove and clean the cad cell.  
functioning of the working parts. Inspect  
connecting lines to boiler for accumulation of  
mud, scale, etc., and clean as required.  
Examine all visible wiring for brittle or worn  
insulation and make sure electrical contacts are  
clean and that they function properly. Give  
special attention to solder joints on bellows and  
float when this type of control is used. Check  
float for evidence of collapse and check mercury  
bulb (where applicable) for mercury separation  
or discoloration.  
8. Clean the blower wheel and the air control of any  
lint.  
9. Check all wiring for secure connections or  
insulation breaks.  
10.Re-adjust the burner as detailed in Section VII:  
System Start-up, Paragraph F.  
E. Controls. Test Controls for proper operation as  
2. Probe Type (Annual Service). Probe type LWCO  
should be removed once a year, examined and  
cleaned of any dirt accumulations to assure proper  
operations. Do not attempt to repair mechanisms in  
the field. Complete replacement mechanisms,  
including necessary gaskets and installation  
detailed in Section VII: System Start-up, Paragraph G.  
F. Low water cutoff (if so equipped).  
1. Float Type  
instructions, are available from the manufacturer.  
a. Monthly Blowoff. During the heating season, if  
27  
Service Notes  
28  
IX. Repair Parts  
All LEDV Series Repair Parts may be obtained through your local Burnham Wholesale Distributor. Should  
you require assistance in locating a Burnham Distributor in your area, or have questions regarding the avail-  
ability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed  
below.  
Burnham Corporation Regional Offices  
A. Burnham Corporation - Central & Western Regions C. Burnham Corporation - Metropolitan Region  
P.O. Box 3079  
P.O. Box 3079  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (717) 481-8408  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (717) 481-8409  
B. Burnham Sales Corporation - Northeast Region  
19-27 Mystic Avenue  
D. Burnham Corporation - Mid-Atlantic Region  
P.O. Box 3079  
Somerville, MA 02145  
Phone: (617) 625-9735  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (617) 625-9736  
FAX: (717) 481-8409  
29  
Figure 19: LEDV Boiler Trim & Controls  
30  
Figure 20: LEDV Boiler Jacket & Insulation  
31  
Figure 21: LEDV Bare Boiler Assembly  
33  
Figure 23: Beckett AFII Oil Burner Repair Part  
For replacement oil burner parts, contact your wholesaler or the burner manufacturer: R.W. Beckett Co., P.O. Box 1289, Elyria, OH 44036  
(216) 327-1060 or (800) OIL BURN(645-2876)  
BECKETT AFII BURNER REPLACEMENT PARTS  
LEDV1  
LEDV2  
Beckett Part Number  
BCB5407  
LEDV3  
Part Description  
Complete Burner (without Primary Control)  
Air Tube Combination  
Air Tube Screws  
BCB5406  
HLX50HD  
BCB5408  
HLX50HE  
4352  
Blower Wheel  
21439  
21438  
Coupling (Motor to Pump)  
Electrodes (Replacement Kit)  
Escutcheon Plate  
21437  
51484U  
31623  
Stop Screw  
3166502  
3166503  
5394  
3166505  
Fuel Line  
Fuel Pump (Single Stage, with Solenoid  
Valve)  
21757  
Fuel Pump (Two Stage, with Solenoid  
Valve)  
2583  
Gasket, Flange  
Head Assembly (AFII 6 Slot)  
Hole Plug  
31658  
51671  
51584  
51672  
51476  
2139  
51485  
3666  
Inlet Air Scoop  
Splined Nut  
Main Housing Assembly  
Motor  
21444  
213  
Nozzle Adapter  
Nozzle Line Heater  
Rear Access Door  
Transformer  
51621  
51424GY  
51402  
4 x 4 Electrical Box  
31613BK  
35  

Bazooka BA260 User Manual
Burnham V9A User Manual
Clarion VMA 6491 VMA6491 User Manual
Crown Boiler AWI095 User Manual
Dual L8SW User Manual
Eclipse Fujitsu Ten AVN5495 User Manual
Hitachi Camcorder E521A User Manual
JBL GTO1220 User Manual
JVC GET0642 002A User Manual
JVC GR DV500 User Manual