Burnham LE L7248 User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
LE™ SERIES  
OIL - FIRED BOILER  
As an ENERGY STAR® Partner, U.S. Boiler Co., Inc. has determined that the LE1 fired at the  
0.60 GPH rate meets the ENERGY STAR guidelines for Energy efficiency established by the  
United States Environmental Protection Agency (EPA).  
For service or repairs to boiler, call your heating contractor. When seeking information on boiler,  
provide Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Serial Number  
Installation Date  
Boiler Model Number  
LE  
Phone Number  
Heating Contractor  
Address  
Price - $3.00  
81433010R18-1/08  
IMPORTANT  
Before starting to install this oil boiler, read these instructions carefully. Keep instructions in  
legible condition and posted near oil boiler for reference by owner and service technician.  
TAbLE OF CONTENTS  
I. General Information..................................3  
II. Installation Instructions ............................5  
III. Operating and Service Instructions..........12  
IV. Boiler Cleaning........................................20  
V. Repair Parts .............................................21  
VI. Appendix  
Low Water Cut Off...................................27  
I. General Information  
Water Content: 6.1 Gallons  
Figure 1: LE™ Packaged Boiler  
1. INSPECT SHIPMENT carefully for any signs of  
2. LOCATE BOILER in front of final position before  
damage.  
removing crate. See Figure 1.  
A. ALL EQUIPMENT is carefully manufactured,  
inspected and packed. Our responsibility ceases  
upon delivery of crated Boiler to the carrier in good  
condition.  
A. LOCATE so that smoke pipe connection to chimney  
will be short and direct. BOILER IS SUITABLE  
FOR INSTALLATION ON COMBUSTIBLE  
FLOOR. Boiler can not be installed on carpeting.  
B. ANY CLAIMS for damage or shortage in shipment  
must be filed immediately against the carrier by the  
consignee. No claims for variances from, or  
shortage in orders, will be allowed by the manufac-  
turer unless presented within sixty (60) days after  
receipt of goods.  
B. FOR BASEMENT INSTALLATION, provide a  
solid base, such as concrete, if floor is not level or  
if water may be encountered on floor around Boiler.  
C. PROVIDE SERVICE CLEARANCE of at least 24”  
clearance in front for servicing.  
D. For minimum clearances to combustible materials  
See Figure 2.  
Approximate shipping weight: 325 pounds  
Water content: 6.1 gallons  
3
D. For boiler located in an unconfined space of a  
conventionally constructed building, the fresh air  
infiltration through cracks around windows and  
doors normally provides adequate air for combus-  
tion and ventilation.  
E. For boiler located in a confined space or an uncon-  
fined space in a building of unusually tight con-  
struction, provide outdoor air with the use of two  
permanent openings which communicate directly or  
by duct with the outdoors or spaces (crawl or attic)  
freely communicating with the outdoors. Locate  
one opening within 12 inches of top of space.  
Locate remaining opening within 12 inches of  
bottom of space. Minimum dimension of air  
opening is 3 inches. Size each opening per  
following:  
Figure ꢀ: Minimum Installation Clearances To  
Combustible Materials  
NOTE 1: Listed clearances comply with American  
National Standard ANSI/NFPA 31, Installation of oil  
burning equipment.  
NOTE 2: LE Series boilers can be installed in rooms  
with clearances from combustible material as listed  
above. Listed clearances can not be reduced for  
alcove or closet installations.  
NOTE 3: For reduced clearances to combustible  
material, protection must be provided as described in  
the above ANSI/NFPA 31 standard.  
(1) Direct communication with outdoors.  
Minimum free area of 1 square inch per 4,000  
BTU per hour input of all equipment in space.  
(2) Vertical ducts. Minimum free area of 1 square  
inch per 4,000 BTU per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
(3) Horizontal ducts. Minimum free area of 1  
square inch per 2,000 BTU per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
3. PROVIDE COMBUSTION AND VENTILATION  
AIR. Local code provisions may apply and should be  
referenced.  
Alternate method for boiler located within  
confined space. Use indoor air if two perma-  
nent openings communicate directly with  
additional space(s) of sufficient volume such  
that combined volume of all spaces meet  
criteria for unconfined space. Size each  
opening for minimum free area of 1 square  
inch per 1,000 BTU per hour input of all  
equipment in spaces, but not less than 100  
square inches.  
WARNING  
Adequate combustion and ventilation air  
must be provided to assure proper  
combustion.  
A. Determine volume of space (boiler room). Rooms  
communicating directly with the space in which the  
appliances are installed, through openings not  
furnished with doors, are considered a part of the  
space.  
F. Louvers and Grilles of Ventilation Ducts  
(1) All outside openings should be screened and  
louvered. Screens used should not be smaller  
than 1/4 inch mesh. Louvers will prevent the  
entrance of rain and snow.  
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)  
B. Determine total input of all appliances in the space.  
Add inputs of all appliances in the space and round  
the result to the nearest 1000 BTU per hour.  
(2) Free area requirements need to consider the  
blocking effect of louvers, grilles, or screens  
protecting the openings. If the free area of the  
louver or grille is not known, assume wood  
louvers have 20-25 percent free area and metal  
louvers and grilles have 60-75 percent free  
area.  
C. Determine type of space. Divide Volume by total  
input of all appliances in space. If the result is  
greater than or equal to 50 ft3/1000 BTU per hour,  
then it is considered an unconfined space. If the  
result is less than 50 ft3/1000 BTU per hour then the  
space is considered a confined space.  
4
II. Installation Instructions  
D. Remove 2 (two) 5/16" - 18 x 3" long hex head cap  
1. REMOVE CRATE  
screws and flatwashers from right side of door.  
Remove 2 hairpin cotter pins and 2 hinge pins from  
hinges on left side of door and remove Door  
Assembly from boiler. Inspect Front and Rear  
Door Insulation Pieces and Combustion Chamber  
Liner, see Step 6.  
A. Remove all fasteners at crate skid.  
B. Lift outside container and remove all other inside  
protective spacers and bracing. Remove container  
containing Safety Relief Valve, Boiler Drain Valve  
and Pipe Fittings.  
2. REMOVAL OF BOILER FROM SKID  
E. Remove 4 hex nuts from bolts that attach hinges and  
hinge spacers to left side of Tubesheet. Remove 4  
hex head cap screws that attach hinges to door.  
A. Tilt boiler, "walk" boiler backward, and set rear legs  
down on floor. Tilt boiler backward, pull skid  
forward and set front legs down on edge of skid.  
Install close coupling, tee, and plug in return  
coupling, see Step 7 and Figure 1. Point tee toward  
permanent return location.  
F. Attach 2 hinge brackets & spacers to Tubesheet and  
2 hinge brackets to Door on right side of boiler. 3  
Holes in each Hinge Bracket must line up with 3  
matching holes in Spacer, Tubesheet or Door. See  
Figure 3. Tighten hex nuts, bolts and screws by  
hand only.  
B. Tilt boiler backward and remove skid. Be careful not  
to damage Burner and Jacket.  
G. Replace door assembly. Hinge brackets attached to  
door must rest on top of hinge brackets attached to  
tubesheet. See Figure 3. Slide hinge pins through  
hinges from top and install cotter pins. Close door  
and install 5/16" - 18 x 3" long hex head cap screws  
through flatwashers and left side of door and into  
tapped holes in tubesheet. Tighten all hex nuts,  
bolts and screws. When door is installed properly,  
it is parallel to Tubesheet when viewed from top  
and sides.  
3. CHANGE HINGE POSITION if necessary.  
A. Look at the area where boiler will be installed. If  
left side of boiler will be less than 12 inches from a  
wall, move hinges to right side of boiler. See B  
through I below.  
B. Pull 2 halves of Burner Swing Door Interlock apart.  
Swing Door Interlock is connected to T-T terminals  
on R7184A Control. Lift Honeywell R7184A  
Control off of Burner Junction Box, open Burner  
Ignition Transformer and disconnect wiring harness  
from left side of burner. Find round plastic cover  
inside Junction Box and install in hole in left side  
of burner.  
H. Bend sides of Jacket Wrapper down and attach 2  
Jacket Straps to 4 slots at bottom of Jacket Wrapper  
sides with sheet metal screws. Install Rear Jacket  
Box with 4 sheet metal screws. See Figure 19.  
C. Remove 8 sheet metal screws from jacket. Remove  
rear jacket box and bend both sides of Jacket  
Wrapper up, see Figure 19.  
I. Connect wiring harness to a knockout on right side  
of Junction Box and install Honeywell R7184A  
Control, see Wiring Diagram, Figures 11A and 11B.  
Reconnect Swing Door Interlock.  
Figure 3: Hinge Installation & Assembly, LE Boiler  
Figure 4: Recommended Water Piping for Zone Valve Zoned Heating Systems  
Figure ꢁ: Recommended Water Piping for Circulator Zoned Heating Systems  
4. INSTALL BOILER CONTROL.  
A. Pull bulb and capillary tube out of hole in back of  
control. Insert bulb in immersion well on top of  
boiler and secure control with set screw in control.  
B. Secure flexible conduit to Jacket Wrapper side with  
conduit clamp and sheet metal screw. Conduit must  
be on same side of boiler as Swing Door hinges.  
5. MOVE BOILER TO PERMANENT POSITION by  
sliding or walking.  
6. INSPECT FRONT AND REAR DOOR INSULATION  
PIECES AND COMBUSTION CHAMBER LINER  
A. OPEN SWING DOOR on front of boiler. Use  
flashlight to inspect insulation pieces secured to  
front and rear doors. Inspect Ceramic Fiber Blanket  
secured to bottom of combustion chamber with  
water glass adhesive. Replace any damaged pieces.  
Figure ꢂ: Recommended Piping for  
Combination Heating & Cooling  
(Refrigeration) Systems  
7. CONNECT SUPPLY AND RETURN PIPING TO  
E. A hot water boiler installed above radiation level  
must be provided with a low water cutoff device as  
part of the installation.  
HEATING SYSTEM  
A. Hot water pipes shall have clearances of at least ½”  
from all combustible construction.  
If a low water cut-off is required, it must be mount-  
ed in the system piping above the boiler.  
B. Use a system by-pass if the boiler is to be operated  
in a system which has a large volume or excessive  
radiation where low boiler water temperatures may  
be encountered (i.e. converted gravity circulation  
system, etc.).  
The minimum safe water level of a hot water boiler  
is just above the highest water containing cavity of  
the boiler; that is, a hot water boiler must be full of  
water to operate safely.  
Valves should be located in the by-pass and return  
line as illustrated in Figures 4 and 5 in order to  
regulate water flow for maintenance of higher  
boiler water temperature.  
F. There are many possible causes of oxygen contami-  
nation such as:  
(1) Addition of excessive make-up water as a  
result of system leaks.  
Set the by-pass and return valves to a half throttle  
position to start. Operate boiler until the system  
water temperature reaches its normal operating  
range.  
(2) Absorption through open tanks and fittings.  
(3) Oxygen permeable materials in the distribution  
system.  
Adjust the valves to maintain 180°F to 200°F boiler  
water temperature and greater than 120°F return  
temperature. Adjust both valves simultaneously.  
Closing the boiler return valve while opening the  
by-pass valve will raise the boiler return tempera-  
ture. Opening the boiler return valve while closing  
the by-pass valve will lower the boiler return  
temperature.  
In order to insure long product life, oxygen sources  
should be eliminated. This can be accomplished by  
taking the following measures:  
(1) Repairing system leaks to eliminate the need  
for addition of make-up water.  
(2) Eliminating open tanks from the system.  
(3) Eliminating and/or repairing fittings which  
allow oxygen absorption.  
C. If this boiler is used in connection with refrigeration  
systems, the boiler must be installed so that the  
chilled medium is piped in parallel with the heating  
boiler using appropriate valves to prevent the  
chilled medium from entering the boiler, see Figure  
6. Also consult I=B=R Installation and Piping  
Guides.  
(4) Use of non-permeable materials in the distribu-  
tion system.  
(5) Isolating the boiler from the system water by  
installing a heat exchanger.  
CAUTION  
D. If this boiler is connected to heating coils located in  
air handling units where they may be exposed to  
refrigerated air the boiler piping must be equipped  
with flow control valves to prevent gravity circula-  
tion of boiler water during the operation of the  
cooling system.  
Oxygen contamination of boiler water will  
cause corrosion of iron and steel boiler  
components, and can lead to boiler failure.  
Burnham's standard warranty does not  
cover problems caused by oxygen  
contamination of boiler water.  
a home without insulation or storm windows. With  
increasing fuel prices that home probably has been  
insulated and fitted with storm windows so that the  
heat loss of the home has been reduced. This  
requires less fuel to be burned and sends less heat  
up the chimney.  
8. INSTALL SMOKEPIPE — The LE should be vented  
into a fireclay tile-lined masonry chimney or a chimney  
constructed from Type L Vent or a factory built  
chimney that complies with the Type HT requirement,  
of UL103. The chimney and vent pipe shall have a  
sufficient draft at all times, to assure safe proper  
operation of the boiler. See Figure 7 for recommended  
installation.  
A new boiler probably has a higher efficiency than  
the boiler being replaced. That probably means that  
the stack temperature from the new boiler will be  
lower than that from the old boiler and with less  
room air being drawn up the chimney to dilute the  
stack gases. The combination of a large uninsulated  
chimney, reduced firing rate, reduced firing time,  
lower stack temperature and less dilution air can, in  
some cases, contribute to the condensing of small  
amounts of water vapor in the chimney. Such  
condensation, when it occurs, can cause chimney  
deterioration. In extreme cases, condensed water  
may be visible on the outside of the breeching or  
chimney. In those extreme cases, the chimney may  
have to be lined to insulate the chimney and thus  
prevent the condensation. The addition of dilution  
air into the chimney may assist in drying the  
chimney interior surfaces.  
C. Heat extractors mounted into the breeching are not  
recommended.  
9. INSTALL ELECTRIC WIRING  
A. Follow the National Electrical Code and local  
regulations. A separate electrical circuit must be run  
from the main electrical service with an over-  
current device/disconnect in the circuit. A service  
switch is recommended and may be required by  
some local jurisdictions. Wiring should conform to  
Figures 11A, 11B and 11C.  
Figure ꢃ  
A. Install the draft regulator following the instructions  
furnished with the regulator. See Figure 8 for  
alternate draft regulator locations.  
B. CANADA — Refer to CSA standard C22.2 Part 1,  
1990, Electrical Features of Fuel Burning Equip-  
ment (Gas and Oil).  
C. If boiler is installed in Canada, a blocked vent safety  
switch must be installed. Refer to Blocked Vent  
Safety Switch Instruction Supplement provided  
with boiler (Canada only).  
10. FUEL UNITS AND OIL LINES  
Use flexible oil line(s) so that Swing Door can be  
opened without disconnecting oil supply.  
A supply line fuel oil filter is recommended as a  
minimum for all firing rates but a pleated paper fuel oil  
filter is recommended for the lowest (.6 GPH) firing  
rate application to prevent nozzle fouling.  
Figure 8  
SINGLE-PIPE OIL LINES — Standard burners are  
provided with single-stage 3450 rpm fuel units with the  
by-pass plug removed for single-pipe installations.  
B. Consider the chimney overall. Chimneys that have a  
high heat loss may become less suitable as the heat  
loss of the home goes down and the efficiency of  
the boiler installed goes up. Most homes have a  
chimney appropriate for the fuel and the era in  
which the home was built. That may have been a  
coal fired or an inefficient oil fired boiler built into  
The single-stage fuel unit may be installed single-pipe  
with gravity feed or lift. Maximum allowable lift is 8  
feet. See Figure 9.  
8
TABLE 2: SINGLE-STAGE UNITS (3450 RPM)  
TWO-PIPE SYSTEMS  
Maximum Length of Tubing  
"H" + "R"  
Lift "H"  
3/8" OD  
1/2" OD  
Tubing (3 GPH) Tubing (3 GPH)  
0'  
1'  
84'  
78'  
73'  
68'  
63'  
57'  
52'  
47'  
42'  
36'  
31'  
26'  
21'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
83'  
2'  
3'  
Figure ꢄ  
4'  
IMPORTANT  
5'  
6'  
Single-pipe installations must be absolutely  
airtight or leaks or loss of prime may result.  
Bleed line and fuel unit completely.  
7'  
8'  
TWO-PIPE OIL LINES - For two-pipe systems where  
more lift is required, the two-stage fuel unit is  
recommended. Tables 2 (single-stage) and 3 (two-stage)  
show allowable lift and lengths of 3/8-inch and ½-inch  
OD tubing for both suction and return lines. Refer to  
Figure 10.  
9'  
10'  
11'  
12'  
13'  
14'  
62'  
---  
41'  
TABLE 3: TWO-STAGE UNITS (3450 RPM)  
TWO-PIPE SYTEMS  
Maximum Length of Tubing  
"H" + "R"  
Lift "H"  
3/8" OD  
1/2" OD  
Tubing (3 GPH) Tubing (3 GPH)  
0'  
2'  
93'  
85'  
77'  
69'  
60'  
52'  
44'  
36'  
27'  
---  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
100'  
76'  
Figure 10  
4'  
Be sure that all oil line connections are absolutely  
airtight.  
6'  
8'  
Check all connections and joints. Flared fittings are  
recommended. Do not use compression fittings.  
10'  
12'  
14'  
16'  
18'  
Open the air-bleed valve and start the burner. For clean  
bleed, slip a 3/16” ID hose over the end of the bleed  
valve and bleed into a container. Continue to bleed for  
15 seconds after oil is free of air bubbles. Stop burner  
and close valve.  
Figure 11A: Wiring Diagram for LE Boilers with Beckett AFG Burner and Split Controls  
SEQUENCE OF OPERATION  
A call for heat by the thermostat energizes the L7248C control which in turn energizes the R7184B primary control. The burner  
will initiate ignition after completing a 10 second pre-purge cycle. If burner ignites within approximately 45 seconds and the cad  
cell sees flame, the burner will continue to operate until the call for heat is satisfied or the setting of the high limit is reached. The  
circulator will operate as long as the thermostat is calling for heat. If the thermostat is not satisfied and the high limit is reached, the  
circulator will continue to operate, and the burner will stop until the high limit is closed by a drop in boiler water temperature.  
Figure 11B: Wiring Diagram for LE Boilers with Beckett AFG Burner, ECꢁ000 Control,  
and Honeywell L4080B High Limit  
SEQUENCE OF OPERATION  
Refer to EC5000 Manual for wiring and operation details.  
10  
Figure 11C: Wiring Diagram for LE Boilers with Riello Burner  
11  
III. Operating and Service Instructions  
WARNING  
All boilers equipped with burner swing door have a potential hazard which can cause severe  
property damage, personal injury or loss of life if ignored. Before opening swing door, turn off  
service switch to boiler and disconnect two halves of Burner Swing Door Interlock wiring  
harness to prevent accidental firing of burner outside the combustion chamber. Be sure to  
tighten swing door fastener completely and reconnect two halves of Burner Swing Door  
Interlock when service is completed.  
that all electrical connections have been completed and  
fuses installed, and that oil tank is filled and oil lines  
have been tested.  
1. ALWAYS INSPECT INSTALLATION BEFORE  
STARTING BURNER.  
2. FILL HEATING SYSTEM WITH WATER.  
NOTE: It is important to properly remove the oil and  
dirt from the system.  
4. LUBRICATION — Follow instruction on burner and  
circulator label to lubricate, if oil lubricated. Most  
motors currently used on residential type burners  
employ permanently lubricated bearings and thus do  
not require any field lubrication. Water lubricated  
circulators do not need field lubrication.  
CLEAN HEATING SYSTEM If boiler water is dirty,  
refer to step 13 for proper cleaning instructions.  
A. Fill entire Heating System with water and vent air  
from system. Use the following procedure on a  
Series Loop or Multi-Zoned System installed as per  
Figures 4 and 5, to remove air from system when  
filling:  
Do not over-lubricate. This can cause as much trouble as no  
lubrication at all.  
5. ADJUST CONTROLS SETTINGS with burner service  
switch turned “ON”.  
(1) Close isolation valve in boiler supply piping.  
A. SET ROOM THERMOSTAT about 10° above  
room temperature.  
(2) Isolate all circuits by closing zone valves or  
balancing valves.  
B. PRESS RED RESET BUTTON.  
(3) Attach a hose to hose bib located just below  
isolation valve in boiler supply piping.  
C. On WATER BOILERS WITHOUT TANKLESS  
HEATERS equipped with L7248 electronic  
aquastat controller, set High Limit (HL) at 180°F.  
This temperature can be varied to suit installation  
requirements. L7248 controller has the High Limit  
adjustment range from 180°F to 240°F (82°C to  
116°C). High Limit Differential is fixed at 15°F  
(8°C).  
(Note - Terminate hose in five gallon bucket at a  
suitable floor drain or outdoor area).  
(4) Starting with one circuit, open zone valve.  
(5) Open hose bib.  
(6) Open fill valve (Make-up water line should be  
located directly above isolation valve in boiler  
supply piping).  
D. ADJUSTING AQUASTAT CONTROLLER  
SETTINGS. To discourage unauthorized changing  
of Aquastat settings, a procedure to enter the  
ADJUSTMENT mode is required. To enter the  
ADJUSTMENT mode, press the UP, DOWN, and  
I buttons (refer to Figure 12) simultaneously for  
three seconds. Press the I button until the feature  
requiring adjustment is displayed:  
(7) Allow water to overflow from bucket until dis  
charge from hose is bubble free for 30 seconds.  
(8) Open zone valve to the second zone to be  
purged, then close the first. Repeat this step  
until all zones have been purged, but always  
have one zone open. At completion, open all  
zone valves.  
(9) Close hose bib, continue filling the system until  
the pressure gauge reads 12 psi. Close fill  
valve.  
• HL_ High Limit.  
• °F °C.  
Then, press the UP and/or DOWN buttons to move  
the set point to the desired value. After 60 seconds  
without any button inputs, the control will auto-  
matically return to the RUN mode.  
(Note - If make-up water line is equipped with  
pressure reducing valve, system will automati-  
cally fill to 12 psi. Leave globe valve open).  
(10) Open isolation valve in boiler supply piping.  
(11) Remove hose from hose bib.  
L7248 Aquastat Controller will not display Low  
Limit and Low Limit Differential adjustment  
features.  
3. CHECK CONTROLS, WIRING AND BURNER to be  
sure that all connections are tight and burner is rigid,  
1ꢀ  
setting and has not gone below the Low Limit  
setting (minus the Differential).  
(2) High Limit: Boiler temperature went above the  
High Limit setting and has not dropped below  
the High Limit setting (minus the Differential).  
TABLE 4: LED ERROR CODES  
Error  
Cause / Action  
Code  
Err1  
Err2  
Err3  
Err4  
Err5  
Err6  
Sensor fault; check sensor.  
ECOM fault; check EnviraCOM™ wiring.  
Hardware fault; replace control.  
B1 fault; check B1 wiring/voltage.  
Low Line; check L1-L2, 110 Vac.  
Fuse; check ECOM wires, replace fuse.  
Figure 1ꢀ: Lꢃꢀ48 Circuit Board Layout -  
Horizontal Mount  
EEPROM, HL, Hdf; reset to default values.  
Restore desired settings.  
Err7  
Err8  
E. DISPLAY READOUT  
In the RUN mode, the Aquastat will flash "bt"  
(boiler temp) followed by the temperature (i.e.,  
220), followed by °F or °C.  
Repeated B1 fault (voltage present at B1 when  
output is turned off); check B1 wiring/voltage.  
(3) Error: The controller has detected an error  
condition (e.g., open sensor) and has shut down  
To read boiler settings, press the I key to read the  
parameter of interest. For example, press I High  
Limit (HL) is displayed, followed by a three-digit  
number, i.e., 220, followed by °F or °C. See  
Display Readout, Figure 13.  
TABLE ꢁ: Lꢃꢀ48 CONTROLLER OPERATING  
SEQUENCE  
Action  
System Response  
Thermostat  
Circulator starts when water temperature  
calls for heat. is above Low Limit setting (if applicable).  
Boiler temperature is checked. Burner  
starts when water temperature is below  
High Limit setting.  
Boiler  
exceeds the  
High Limit.  
Burner is turned off. Burner restarts when  
the water temperature drops below the  
High Limit setting minus the Differential.  
Thermostat is Circulator and burner turn off.  
satisfied.  
Error  
If an error condition is detected, all outputs  
condition 1-5. except ZC are shut down. Burner is off.  
Control continues to function and restarts  
when error is corrected.  
Figure 13: Display Readout Definitions  
After approximately 60 seconds without any key  
presses, the display will enter a dim display mode.  
To return to the bright display mode, simply press  
any key.  
During the error check sequence, the  
system checks for drift in the sensor and  
corrosion in the connections.  
Error  
EnviraCOM communication is not  
F. OPERATION  
condition 6.  
available.  
The L7248 model is restricted to three operational  
states - Normal, High Limit and Error. The  
controller moves back and forth from High Limit to  
Normal state as part of normal operation.  
The controller will enter the Error state when there  
is an abnormal condition. The operating states are:  
Error  
condition 7.  
The control has reset the High Limit  
setting to a default setting and will  
continue to run at those settings.  
Performance of the system will be  
degraded.  
Error  
condition 8.  
If the error condition is detected, all  
outputs except ZC are shut down. Burner  
is off. Control continues to function and  
restarts when all three user keys have  
been pressed longer than 60 seconds.  
(1) Normal: Boiler temperature went below the  
High Limit setting (minus the Differential) and  
has not exceeded the High Limit setting; or the  
boiler temperature went above the Low Limit  
13  
the burner output. The ZC output is energized.  
The controller continues to monitor the system  
and automatically restarts if the error condition  
clears. Refer to Table 4.  
G. HIGH LIMIT CONTROLLER  
The High Limit opens and turns off the burner when  
the water temperature reaches the setpoint. The  
High Limit automatically resets after the water  
temperature drops past the setpoint and through the  
Differential. The L7248 models have High Limit  
Differential presets of 15°F (8°C). See Figure 14.  
The operating sequence for the L7248 is shown in  
Table 5.  
6. REMOVE GUN ASSEMBLY  
LE Boilers equipped with Beckett AFG burners. Items  
to be checked are nozzle size, type, and angle; head  
size, (and setting on MD(V1) head); gun setting; and  
positioning of electrodes. This information is shown in  
Figure 15, and Table 6. If the desired boiler firing rate  
is 0.6 GPH, the nozzle must be changed out, the low  
firing rate baffle must be installed and the factory  
settings must be changed according to Table 6. These  
parts are in the bag attached to the burner. Reinstall  
gun assembly.  
LE Boilers equipped with Riello 40 F3 and 40 F5  
burners: Items to be checked are nozzle size, type and  
angle: settings (air gate, turbulator and pump pressure).  
This information is shown in Table 6A. Reinstall gun  
assembly.  
7. ADJUST OIL BURNER BEFORE STARTING  
A. SET BURNER SETTINGS, see Tables 6 and 6A.  
B. OPEN ALL OIL LINE VALVES.  
Figure 14: Setpoints and Differentials  
Figure 1ꢁ: "L1" and "V1" Head Electrode Positioning and Gun Setting (Beckett AFG)  
14  
TABLE ꢂ: BECkETT AFG BURNER  
Nozzle  
Settings  
Firing  
Rate  
(GPH)  
Boiler  
Model  
Static  
Disc  
Pump  
Head  
Air  
Air  
Manufacturer GPH Angle Type  
Head Pressure  
(PSIG)  
Shutter Band  
LE1  
LE2  
LE3  
0.60 *  
1.00  
0.50  
0.85  
1.10  
70°  
60°  
45°  
B
B
B
5
0
0
N/A  
N/A  
0
140  
140  
140  
Hago or  
Delavan  
MB(L1) 3-3/8U  
10  
10  
1.25 + MD(V1) 2-3/4U  
Delavan  
1.5  
Settings are approximate and must be verified by Smoke and Carbon Dioxide measurement. Readjust where necessary.  
See Text of the Manual.  
* Install low firing rate baffle for 0.60 GPH firing rate.  
+ Do not change the firing rate of the 1.25 GPH burner.  
TABLE ꢂA: RIELLO BURNER SPECIFICATIONS  
Settings  
Boiler  
Model  
Firing Rate  
(GPH)  
Burner  
Model  
Nozzle  
Air Gate  
2.8  
Pump Pressure  
Turbulator  
LE1  
LE2  
LE3  
0.60  
1.00  
1.25  
F3  
F5  
F5  
Delavan 0.50 x 60°A  
Delavan 0.85 x 60°A  
Delavan 1.00 x 60°A  
0.5  
1.0  
3.0  
3.0  
145  
3.5  
C. Attach a plastic hose to fuel pump vent fitting and  
B. ADJUST DRAFT REGULATOR for a draft of 0 to  
maximum of -.03" (water gauge) in the breeching  
after chimney has reached operating temperature  
and while burner is running. Burner will operate  
with a positive draft over fire and zero draft in the  
breeching. Adjust Draft Regulator such that  
maximum draft of -.03" is reached in coldest  
weather.  
provide a pan to catch the oil.  
D. REMOVE GAUGE PORT PLUG from fuel pump  
and install pressure gauge.  
E. REMOVE FLAME PLUG IN SWING DOOR.  
8. START OIL BURNER  
A. Open vent fitting on fuel pump.  
C. READJUST AIR BANDS on burner for a light  
orange colored flame. Use a smoke tester and adjust  
air for minimum smoke (not to exceed #1) with a  
minimum of excess air. Make final check using  
suitable instrumentation to obtain a CO2 of 11.5 to  
12.5%. These settings will assure a safe and  
B. TURN ‘ON’ BURNER service switch and allow  
burner to run until oil flows from vent fitting in a  
SOLID stream without air bubbles for approximate-  
ly 10 seconds.  
C. Close vent fitting and burner flame should start  
immediately after pre-purge is complete. Pre-purge  
prevents burner flame until 10 seconds has elapsed  
after initial power is applied to burner. During pre-  
purge, the motor and ignitor will operate but the oil  
valve will remain closed. Refer to Oil Primary  
Control Instructions for more details.  
efficient operating condition. If the flame appears  
stringy instead of a solid fire, try another nozzle of  
the same type. Flame should be solid and compact.  
After all adjustments are made recheck for a draft  
of zero to -.03" (water gauge) in breeching.  
D. TURN “OFF” BURNER and remove pressure  
gauge. Install gauge port plug and tighten. Start  
burner again.  
9. ADJUST OIL PRESSURE  
A. Locate oil pressure adjusting screw and turn screw  
to obtain the oil pressure indicated in Tables 6 and  
6A.  
E. CAD CELL LOCATION AND SERVICE  
The burner is supplied with a cadmium sulfide flame  
detector mounted at the factory, mounted on the  
bottom of the transformer. See Figure 16. To  
service cad cell or to replace the plug in portion,  
swing open the transformer. After service is  
complete, be sure to fasten down the transformer.  
B. DO NOT REMOVE PRESSURE GAUGE until  
later.  
10. OTHER ADJUSTMENTS  
A. ADJUST THE AIR BAND AND/OR AIR SHUT-  
TER  
F. FLAME FAILURE  
Beckett Burners:  
The LE boiler controls operate the burner automati-  
cally. If for unknown reasons the burner ceases to  
fire and the reset button on the primary control has  
tripped, the burner has experienced ignition failure.  
Adjust air supply by loosening lock screws and  
moving the air shutter and if necessary the air band.  
Refer to Table 6 for preliminary settings.  
1ꢁ  
(1) Safe Start  
i. Jumper the yellow cad cell leads.  
ii. Follow procedure to turn on burner.  
Burner must not start, indictor light turns  
on and control remains in Idle Mode.  
(2) Simulate Flame Failure.  
i. Follow procedure to turn on burner.  
ii. Close hand valve in oil supply line.  
iii. Device enters recycle mode.  
iv. Device tries to restart system after  
approximately 60 seconds.  
v. Safety switch locks out approximately in  
safety switch timing indicated on label.  
Indicator light flashes at 1 Hz rate.  
Ignition and motor stop and oil valve  
closes.  
Figure 1ꢂ: Cad Cell  
Before pressing the reset button call your service-  
man immediately.  
CAUTION  
(3) Simulate Ignition Failure.  
i. Follow procedure to turn on burner, but do  
Do not attempt to start the burner when  
excess oil has accumulated, when the unit  
is full of vapor, or when the combustion  
chamber is very hot.  
not open oil supply hand valve.  
ii. Observe that safety switch locks out  
approximately within safety switch timing  
as indicated on the label. Indicator light  
flashes at 1 Hz rate. Ignition and motor  
stop and oil valve closes.  
11. CHECK FOR CLEAN CUT OFF OF BURNER  
A. AIR IN THE OIL LINE between fuel unit and  
nozzle will compress when burner is on and will  
expand when burner stops, causing oil to squirt  
from nozzle at low pressure as burner slows down  
and causing nozzle to drip after burner stops.  
Usually cycling the burner operation about 5 to 10  
times will rid oil line of this air.  
(4) The indicator light on the oil primary control  
provides lockout, recycle and cad cell indica-  
tions as follows:  
i. Flashing at 1 Hz (½ second on, ½ second  
off): system is locked out or in restricted  
mode.  
ii. Flashing at ¼ Hz (2 seconds on, 2 seconds  
B. IF NOZZLE CONTINUES TO DRIP, repeat step  
(11A). If this does not stop the dripping, remove  
cutoff valve and seat, and wipe both with a clean  
cloth until clean, then replace and re-adjust oil  
pressure.  
off): control is in recycle mode.  
iii. On: cad cell is sensing flame.  
iv. Off: cad cell is not sensing flame.  
C. CHECK HIGH LIMIT CONTROL. Jumper  
thermostat terminals. Allow burner to operate until  
shut-down by limit. Installation is not considered  
complete until this check has been made.  
12. TEST CONTROLS.  
WARNING  
REMOVE JUMPER.  
Before installation of the boiler is  
considered complete, the operation of the  
boiler controls should be checked,  
particularly the primary control and high  
limit control.  
IF CONTROLS DO NOT MEET REQUIREMENTS  
OUTLINED IN PARAGRAPH 12, REPLACE  
CONTROL AND REPEAT CHECK-OUT  
PROCEDURES.  
13. BOILER AND SYSTEM CLEANING INSTRUC-  
A. CHECK THERMOSTAT OPERATION. Raise and  
lower thermostat setting as required to start and  
stop burner.  
TIONS FOR TROUBLE FREE OPERATION  
A. Filling of Boiler and System — General —-In a hot  
water heating system, the boiler and entire system  
(other than the expansion tank) must be full of  
water for satisfactory operation. Water should be  
added to the system until the boiler pressure gauge  
registers 12 psi. To insure that the system is full,  
water should come out of all air vents when  
B. VERIFY PRIMARY CONTROL SAFETY FEA-  
TURES using procedures outlined in instructions  
furnished with control or instructions below:  
CAUTION  
opened. The LE boiler holds 6.1 gallons of water.  
FOR HEATING SERVICEMAN ONLY  
1ꢂ  
B. Boiling Out of Boiler and System. The oil and grease  
which accumulate in a new hot water boiler can be  
washed out in the following manner.  
shorten the life of the boiler. Entrained in make-up  
water are dissolved minerals and oxygen. When the  
fresh, cool make-up water is heated in the boiler the  
minerals fall out as sediment and the oxygen  
escapes as a gas. Both can result in reduced boiler  
life. The accumulation of sediment can eventually  
isolate the water from contacting the steel. When  
this happens the steel in that area gets extremely hot  
and eventually cracks. The presence of free oxygen  
in the boiler creates a corrosive atmosphere which,  
if the concentration becomes high enough, can  
corrode the steel through from the inside. Since  
neither of these failure types are the result of a  
manufacturing defect the warranty does not apply.  
Clearly it is in everyone’s best interest to prevent  
this type of failure. The maintenance of system  
integrity is the best method to achieve this.  
(1) Remove Safety Relief Valve using extreme care  
to avoid damaging it.  
(2) Partially fill boiler and add caustic soda or triso-  
dium phosphate. Add an appropriate amount of  
recommended boil out compound.  
(3) Replace Safety Relief Valve.  
(4) Fill the entire system with water.  
(5) Start firing the boiler.  
(6) Circulate the water through the entire system.  
(7) Vent the system, including the radiation.  
(8) Allow boiler water to reach operating tempera-  
ture, if possible.  
(9) Continue to Circulate the water for a few hours.  
(10) Stop firing the boiler.  
14. HINTS ON COMBUSTION  
(11) Drain the system in a manner and to a location  
that hot water can be discharged with safety.  
A. NOZZLES — Although the nozzle is a relatively  
inexpensive device, its function is critical to the  
successful operation of the oil burner. The selection  
of the nozzle supplied with the LE boiler is the  
result of extensive testing to obtain the best flame  
shape and efficient combustion. Other brands of the  
same spray angle and spray pattern may be used but  
may not perform at the expected level of CO2 and  
smoke. Nozzles are delicate and should be protect-  
ed from dirt and abuse. Nozzles are mass-produced  
and can vary from sample to sample. For all of  
those reasons a spare nozzle is a desirable item for  
a serviceman to have.  
(12) Remove plugs from all available returns and  
wash the water side of the boiler as thoroughly  
as possible, using a high-pressure water stream.  
(13) Refill the system with fresh water.  
C. Add appropriate boiler water treatment compounds  
as recommended by your qualified water treatment  
company.  
D. Make pH or Alkalinity Test.  
After boiler and system have been cleaned and  
refilled as previously described, test the pH of the  
water in the system. This can easily be done by  
drawing a small sample of boiler water and testing  
with hydrion paper which is used in the same  
manner as litmus paper, except it gives specific  
readings. A color chart on the side of the small  
hydrion dispenser gives the reading pH. Hydrion  
paper is inexpensive and obtainable from any  
chemical supply house or thru your local druggist.  
The pH should be higher than 7 but lower than 11.  
Add appropriate water treatment chemicals, if  
necessary, to bring the pH within the specified  
range. With this lower level of protection, care must  
be exercised to eliminate all of the free oxygen in  
the system.  
B. FLAME SHAPE — Looking into the combustion  
chamber through the flame plug hole, the flame  
should appear straight with no sparklers rolling up  
toward the top of the chamber. If the flame drags to  
the right or left, sends sparklers upward or makes  
wet spots on the rear door insulation piece, the  
nozzle should be replaced. If the condition persists  
look for fuel leaks, air leaks, water or dirt in the  
fuel as described below.  
C. FUEL LEAKS — Any fuel leak between the pump  
and the nozzle will be detrimental to good combus-  
tion results. Look for wet surfaces in the air tube,  
under the transformer, and around the air inlet. Any  
such leaks should be repaired as they may cause  
erratic burning of the fuel and in the extreme case  
may become a fire hazard.  
E. Boiler is now ready to be put into service.  
IMPORTANT  
D. AIR LEAKS — Any such leaks should be repaired,  
as they may cause erratic burning of the fuel and in  
extreme cases may become a fire hazard.  
IF, DURING NORMAL OPERATION, IT IS  
NECESSARY TO ADD WATER MORE  
FREQUENTLY THAN ONCE A MONTH,  
CONSULT A QUALIFIED SERVICE  
TECHNICIAN TO CHECK YOUR SYSTEM  
FOR LEAKS.  
There are many possible causes of air leaks in oil  
lines such as:  
(1) Fitting leaks due to mis-flared tubing or  
damaged fitting.  
(2) Fuel line leak due to crushed or bent tubing.  
(3) Filter connection leaks.  
A leaky system will increase the volume of make-up  
water supplied to the boiler which can significantly  
1ꢃ  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
The Repair Parts list designates parts that contain refractory ceramic fibers  
(RCF). RCF has been classified as a possible human carcinogen. When  
exposed to temperatures about 1805°F, such as during direct flame contact,  
RCF changes into crystalline silica, a known carcinogen. When disturbed as a  
result of servicing or repair, these substances become airborne and, if inhaled,  
may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace RCF parts or attempt any service or repair work  
involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
• Take steps to assure adequate ventilation.  
• Wash all exposed body areas gently with soap and water after contact.  
• Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
• Discard used RCF components by sealing in an airtight plastic bag. RCF  
and crystalline silica are not classified as hazardous wastes in the United  
States and Canada.  
First Aid Procedures:  
• If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
• If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
• If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
18  
(4) Tank connection leaks.  
H. COLD OIL — If the oil temperature approaching  
the fuel pump is 40°F or lower poor combustion or  
delayed ignition may result. Cold oil is harder to  
atomize at the nozzle. Thus, the spray droplets get  
larger and the flame shape gets longer. An outside  
fuel tank that is above grade or has fuel lines in a  
shallow bury is a good candidate for cold oil. The  
best solution is to bury the tank and lines deep  
enough to keep the oil above 40°F.  
There are various test kits available to trace air  
leaks, such as electronic sight glasses. Follow the  
manufacturers' instructions to find air leaks.  
The following actions can eliminate air leaks:  
(1) Bleed pump as detailed previously.  
(2) Replace flare fittings.  
(3) Replace oil supply line.  
(4) Repair oil filter leaks.  
I. HIGH ALTITUDE INSTALLATIONS  
(5) Replace or repair tank fittings.  
Air settings must be increased at higher altitudes.  
Use instruments and set for 11.5 to 12.5% CO2.  
IMPORTANT  
J. START-UP NOISE — Late ignition is the cause of  
start-up noises. If it occurs recheck for electrode  
settings, flame shape, air or water in the fuel lines.  
CHECK TEST PROCEDURE. A very good  
test for isolating fuel side problems is to  
disconnect the fuel system and with a 2'  
length of tubing, fire out of an auxiliary five  
gallon pail of clean, fresh, warm #2 oil from  
another source. If the burner runs  
successfully when drawing out of the  
auxiliary pail then the problem is isolated to  
the fuel or fuel lines being used on the  
jobsite.  
K. SHUT DOWN NOISE — If the flame runs out of air  
before it runs out of fuel, an after burn with noise  
may occur. That may be the result of a faulty cut-  
off valve in the fuel pump, or it may be air trapped  
in the nozzle line. It may take several firing cycles  
for that air to be fully vented through the nozzle.  
Water in the fuel or poor flame shape can also cause  
shut down noises.  
E. GASKET LEAKS — If 11.5 to 12.5% CO2 with a  
#1 smoke or less cannot be obtained in the  
15. ATTENTION TO BOILER WHILE NOT IN  
OPERATION.  
breeching, look for air leaks around the flue collar.  
Such air leaks will cause a lower CO2 reading in the  
breeching. The smaller the firing rate the greater  
effect an air leak can have on CO2 readings.  
IMPORTANT  
IF BOILER IS NOT USED DURING WINTER  
TIME, IT MUST BE FULLY DRAINED TO  
PREVENT FREEZE DAMAGE.  
F. DIRT — A fuel filter is a good investment. Acci-  
dental accumulation of dirt in the fuel system can  
clog the nozzle or nozzle strainer and produce a  
poor spray pattern from the nozzle. The smaller the  
firing rate, the smaller the slots become in the  
nozzle and the more prone to plugging it becomes  
with the same amount of dirt.  
A. Spray inside surfaces with light lubricating or  
crankcase oil using gun with extended stem so as to  
reach all corners.  
B. Always keep the manual fuel supply valve shut off  
if the burner is shut down for an extended period of  
time.  
G. WATER — Water in the fuel in large amounts will  
stall the fuel pump. Water in the fuel in smaller  
amounts will cause excessive wear on the pump,  
but more importantly water doesn’t burn. It chills  
the flame and causes smoke and unburned fuel to  
pass out of the combustion chamber and clog the  
flueways of the boiler.  
C. To recondition the heating system in the fall season  
after a prolonged shut down, follow the instructions  
outlined in Section III — Operating and Service  
Instructions, Items 1 through 8.  
1ꢄ  
IV. Boiler Cleaning  
WARNING  
All boiler cleaning must be completed with burner service switch turned off. Boilers equipped  
with burner swing door have a potential hazard which can cause severe property damage,  
personal injury or loss of life if ignored. Before opening swing door, turn off service switch to  
boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten  
swing door fastener completely when service is completed.  
1. CLEAN THE FIRETUBES  
4. CLOSE BOILER  
A. For access to fireside of boiler, pull two halves of  
Burner Swing Door Interlock wiring harness apart,  
remove hex nuts holding door closed and open  
swing door.  
CAUTION: Do not start burner unless burner swing door is  
securely closed. Close door, install hex nuts, and tighten  
securely. Door should be parallel to tubesheet when  
viewed from top and sides. Reconnect two halves of  
Swing Door Interlock.  
B. Prior to cleaning boiler, lay a protective cloth or  
plastic over combustion chamber liner.  
C. Using a 1 1/2" diameter wire brush (30" handle),  
clean firetubes. Measure 15" from end of brush  
opposite handle, and mark handle. DO NOT allow  
this mark to go past front end of firetube during  
cleaning, or brush will hit rear door insulation  
piece.  
WARNING  
The boiler must be connected to an  
approved chimney in good condition.  
Serious property damage could result if the  
boiler is connected to a dirty or inadequate  
chimney. The interior of the chimney flue  
must be inspected and cleaned before the  
start of the heating season and should be  
inspected periodically throughout the  
heating season for any obstructions. A  
clean and unobstructed chimney flue is  
necessary to allow noxious fumes that  
could cause injury or loss of life to vent  
safely and will contribute toward  
2. CLEAN THE COMBUSTION CHAMBER  
Using wire or fiber bristle brush, clean inside of  
combustion chamber. DO NOT let brush hit rear door  
insulation piece or combustion chamber liner.  
3. AFTER CLEANING  
Vacuum debris inside bottom of rear door, remove  
protective cloth, and vacuum remaining fireside of  
boiler as necessary. BE CAREFUL not to damage liner  
or rear door insulation piece. Inspect front and rear door  
insulation pieces, front door gaskets and combustion  
chamber liner for damage. Replace any damaged  
pieces.  
maintaining the boiler's efficiency.  
ꢀ0  
V. Repair Parts  
All LE™ Series Repair Parts may be obtained through your local Burnham Wholesale distribu-  
tor. Should you require assistance in locating a Burnham Distributor in your area, or have questions  
regarding the availability of Burnham products or repair parts, please contact Burnham Customer  
Service at (717) 481-8400 or Fax (717) 481-8408.  
Item  
1
Description  
Qty.  
1
Part Number  
Honeywell L7248C1014 High Limit & Circulator Relay  
--OR--  
100059-01  
Honeywell L4080B1261 High Limit  
80160402  
80160452  
81660319  
8056164U  
806603061  
80160847  
8133302  
2
3
4
5
6
7
8
Honeywell 123871A, 3/4 NPT x 3  
1
1
1
1
1
1
1
Conbraco 10-408-05, 3/4 FPT, 30 PSI Relief Valve  
Temperature/Pressure Gauge 1-1/2 DIA (Long Shank)  
Conbraco 35-302-03, 3/4 FPT Drain Valve  
Beckett R7184 Oil Primary Control  
Burner Disconnect Harness  
Strain Relief Bushing (Not Shown)  
8136029  
Figure 18: LE Boiler Trim & Controls  
ꢀ1  
Figure 1ꢄ: LE Boiler Jacket & Insulation  
ꢀꢀ  
ꢀ3  
ꢀ4  
MODEL  
LE1  
LE2  
1.25  
Firing Rate (gph)  
0.60  
1.00  
Spec No. Beckett  
BCB4611  
AFG50MB  
L1  
BCB4612  
AFG50MD  
V1  
Air Tube Combination  
Combustion Head Type  
Air Band  
3492BKA  
Air Shutter  
3709BK  
2999  
N/A  
Blower  
Low Firing Rate Baffle Kit  
Knurled Nut Kit  
5880  
N/A  
51400  
5636  
2454  
149  
Connector Tube Assembly  
Coupling  
Electrode Clamp  
Electrode Clamp Screw  
Electrode Insulator Assembly  
Spider Spacer Assembly  
Escutcheon Plate  
Gasket  
4219  
5940  
5655  
3493  
5873  
5941  
31498  
Combustion Head  
Hole Plug  
5912U  
5913U  
2139  
5877  
2456  
213U  
Housing Ass'y w/Inlet Bell  
Motor  
Nozzle Adapter  
Nozzle Line Electrode  
Assembly  
NL50MB  
3384  
NL50MD  
3383P  
Pump (Includes Valve)  
Static Plate  
21844  
Ignitor  
7440  
5878U  
51304  
5770  
Transformer  
Ignitor/Transformer Gasket  
Junction Box  
Flame Detector  
7006U  
ꢀꢁ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢀꢂ  
VI. Low Water Cut Off (LWCO)  
WARNING  
DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off (LWCO).  
Only use connections specifically identified for Low Water Cut Off.  
In all cases, follow the Low Water Cut Off (LWCO) manufacturer's instructions.  
When  
draining the heating system. Many probe LWCO  
manufacturers recommend an annual inspection of the  
probe.  
A low water cutoff is required to protect a hot water  
boiler when any connected heat distributor (radiation) is  
installed below the top of the hot water boiler (i.e.  
baseboard on the same floor level as the boiler). In  
addition, some jurisdictions require the use of a LWCO  
with a hot water boiler.  
How to Wire  
LWCO’s are available in either 120 VAC or 24 VAC  
configurations. The 120 VAC configuration can be  
universally applied to both gas and oil boilers by wiring  
it in the line voltage service to the boiler (after the  
service switch, if so equipped).  
The presence of water in a properly installed LWCO  
will cause the normally open contact of the LWCO to  
close, thus providing continuity of the 120 VAC service  
to the boiler.  
Where  
The universal location for a LWCO on both gas and oil  
hot water boilers is above the boiler, in either the supply  
or return piping. The minimum safe water level of a  
water boiler is at the uppermost top of the boiler; that is,  
it must be full of water to operate safely.  
It is recommended to supply power to the probe LWCO  
with the same line voltage boiler service as shown  
below.  
What Kind  
Typically, in residential applications, a probe type  
LWCO is used instead of a float type, due to their  
relative costs and the simplicity of piping for a probe  
LWCO.  
How to Pipe  
A “tee” is commonly used to connect the probe LWCO  
to the supply or return piping, as shown below.  
Wiring of Typical LWCO  
A 24 VAC LWCO is used primarily for gas fired boilers  
where a 24 volt control circuit exists within the boiler.  
However, a 24 VAC LWCO can only be used if the  
boiler manufacturer has provided piping and wiring  
connections and instructions to allow for this  
application.  
LWCO Location  
Select the appropriate size tee using the LWCO  
manufacturer’s instructions. Often, the branch  
connection must have a minimum diameter to  
prevent bridging between the probe and the tee. Also,  
the run of the tee must have a minimum diameter to  
prevent the end of the probe from touching or being  
located too close to the inside wall of the run of the tee.  
How to Test  
Shut off fuel supply. Lower water level until water  
level is BELOW the LWCO. Generate a boiler demand  
by turning up thermostat. Boiler should not attempt to  
operate. Increase the water level by filling the system.  
The boiler should attempt to operate once the water  
level is above the LWCO.  
Ideally, manual shutoff valves should be located above  
the LWCO and the boiler to allow for servicing. This  
will allow probe removal for inspection without  
ꢀꢃ  
Limited Warranty  
FOR RESIDENTIAL GRADE WATER BOILERS  
Subject to the terms and conditions set forth below, U.S. Boiler™  
if the residential grade water boiler is used or operated over its rated  
capacity, is subjected to unauthorized modification, or is damaged  
as a result of being otherwise improperly operated or serviced  
including, but not limited to, damage from any of the following:  
operation with insufficient water, allowing the boiler to freeze,  
subjecting the boiler to flood conditions, and operation with  
unapproved water or fuel additives which cause deposits or  
corrosion.  
Co., Inc. Lancaster, Pennsylvania hereby extends the following limited  
warranties to the original owner of a residential grade water boiler  
manufactured and shipped on or after July 1,1991:  
ONE YEAR LIMITED WARRANTY  
ON RESIDENTIAL GRADE WATER BOILERS  
U.S. Boiler Co., Inc. warrants to the original owner that its residential  
grade water boilers comply at the time of manufacture with recognized  
hydronic industry standards and requirements then in effect and will be  
free of defects in material and workmanship under normal usage for a  
period of one year from the date of original installation. If any part of  
a water boiler is found to be defective in material or workmanship during  
this one year period, U.S. Boiler Co., Inc. will, at its option, repair or  
replace the defective part.  
5.Removal and Installation: These warranties do not cover  
expenses of removal or reinstallation. The owner is responsible for  
the cost of removing and reinstalling any defective part and its  
replacements and all labor and material connected therewith.  
6.Exclusive Remedy: U.S. Boiler Co., Inc. obligation for any breach  
of these warranties is limited to the repair or replacement of its  
parts in accordance with the terms and conditions of these  
warranties.  
LIFETIME LIMITED WARRANTY  
ON HEAT EXCHANGER  
7.Limitation of Damages: Under no circumstances shall U.S. Boiler  
Co., Inc. be liable for incidental, indirect, special or consequential  
damages of any kind whatsoever under these warranties, including,  
but not limited to, injury or damage to persons or property and  
damages for loss of use, inconvenience or loss of time. U.S. Boiler  
Co., Inc. liability under these warranties shall under no circum-  
stances exceed the purchase price paid by the owner for the  
residential grade water boiler involved. Some states do not allow the  
exclusion or limitation of incidental or consequential damages, so  
the above limitation or exclusion may not apply to you.  
U.S. Boiler Co., Inc. warrants to the original owner that the heat  
exchanger of its residential grade water boilers will remain free from  
defects in material and workmanship under normal usage for the  
lifetime of the original owner at the original place of installation. If a  
claim is made under this warranty during the first ten years from the  
date of original installation, U.S. Boiler Co., Inc. will, at its option, repair  
or replace the heat exchanger. If a claim is made under this warranty  
after the expiration of ten years from the date of original installation,  
U.S. Boiler Co., Inc. will, at its option and upon payment of the pro-rated  
service charge set forth below, repair or replace the heat exchanger.  
The service charge applicable to a heat exchanger warranty claim is  
based upon the number of years the heat exchanger has been in  
service and will be determined as a percentage of the retail price of the  
heat exchanger model involved at the time the warranty claim is made  
as follows:  
8.Limitation of Warranties: These warranties set forth the entire  
obligation of U.S. Boiler Co., Inc. with respect to any defect in a  
residential grade water boiler and U.S. Boiler Co., Inc. shall have no  
express obligations, responsibilities or liabilities of any kind whatso-  
ever other than those set forth herein. These warranties are given in  
lieu of all other express warranties.  
Years  
In Service  
1-10  
11  
12  
13  
14  
15  
16  
17  
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING  
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A  
PARTICULAR PURPOSE ARE EXPRESSLY LIMITED IN  
DURATION TO A PERIOD OF ONE YEAR EXCEPT THAT  
IMPLIED WARRANTIES, IF ANY, APPLICABLE TO THE HEAT  
EXCHANGER IN A RESIDENTIAL GRADE WATER BOILER SHALL  
EXTEND TO THE ORIGINAL OWNER FOR THE LIFETIME OF  
THE ORIGINAL OWNER AT THE ORIGINAL PLACE OF  
INSTALLATION. SOME STATES DO NO ALLOW LIMITATION ON  
HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE  
LIMITATION MAY NOT APPLY TO YOU.  
Service Charge  
as % of  
Retail Price  
No  
Charge  
5
10  
15  
20  
25  
30  
35  
Years  
In Service  
25 and  
above  
18  
19  
20  
21  
22  
23  
24  
Service Charge  
as % of  
40  
45  
50  
55  
60  
65  
70  
75  
Retail Price  
NOTE: If the heat exchanger model involved is no longer available  
due to product obsolescence or redesign, the value used to  
establish the retail price will be the published price as shown in the  
Burnham Hydronics Repair Parts Price Sheet where the heat  
exchanger last appeared or the current retail price of the then  
nearest equivalent heat exchanger.  
PROCEDURE FOR OBTAINING WARRANTY SERVICE  
In order to assure prompt warranty service, the owner is  
requested to complete and mail the attached Warranty Card within  
ten days after the installation of the boiler, although failure to comply  
with this request will not void the owner’s rights under these  
warranties.  
ADDITIONAL TERMS AND CONDITIONS  
Upon discovery of a condition believed to be related to a defect in  
material or workmanship covered by these warranties, the owner  
should notify the installer, who will in turn notify the distributor. If  
this action is not possible or does not produce a prompt response,  
the owner should write to U.S. Boiler Co., Inc., Burnham Hydronics,  
at P.O. Box 3079, Lancaster, PA 17604, giving full particulars in  
support of the claim.  
1.Applicability: The limited warranties set forth above are extended  
only to the original owner at the original place of installation within  
the United States and Canada. These warranties are applicable  
only to water boilers designated as residential grade by U.S. Boiler  
Co., Inc. and installed in a single or two-family residence and do not  
apply to steam boilers of any kind or to commercial grade boilers.  
2. Components Manufactured by Others: Upon expiration of the one  
year limited warranty on residential grade water boilers, all boiler  
components manufactured by others but furnished by U.S. Boiler  
Co., Inc. (such as oil burner, circulator and controls) will be subject  
only to the manufacturer’s warranty, if any.  
The owner is required to make available for inspection by U.S.  
Boiler Co., Inc. or its representative the parts claimed to be  
defective and, if requested by U.S. Boiler Co., Inc. to ship these  
parts prepaid to U.S. Boiler Co., Inc. at the above address for  
inspection or repair. In addition, the owner agrees to make all  
reasonable efforts to settle any disagreement arising in connection  
with a claim before resorting to legal remedies in the courts.  
3. Proper Installation: The warranties extended by U.S. Boiler Co.,  
Inc. are conditioned upon the installation of the residential grade  
water boiler in strict compliance with U.S. Boiler Co., Inc. installation  
instructions. U.S. Boiler Co., Inc. specifically disclaims liability of  
any kind caused by or relating to improper installation.  
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND  
YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM  
STATE TO STATE.  
4. Proper Use and Maintenance: The warranties extended by U.S.  
Boiler Co., Inc. conditioned upon the use of the residential grade  
water boiler for its intended purposes and its maintenance  
accordance with U. S. Boiler Co., Inc. recommendations and  
hydronics industry standards. These warranties will be inapplicable  
03/03  

AudioBahn Natural Sound Subwoofer AW1571T User Manual
Bang Olufsen BEOCENTER 26 Jun User Manual
Blaupunkt IVMR 1042 User Manual
Bushnell Instant Replay 18 18 0832 User Manual
DB Link DB Research Car Speaker K1 10D4 User Manual
Dual XDVDN8290 User Manual
HANNspree LCD Monitor HF289 User Manual
Hobie 38584001 User Manual
JVC BN V856 User Manual
JVC GR SXM930 User Manual