Bryan Boilers HE CLM300 W FDG User Manual

Form No. 6700  
(Rev. 5/07)  
Bryan “Flexible Water Tube”  
HE-CLM Series Water Boilers  
900,000 to 3,000,000 BTUH  
Forced draft gas fired  
Quality Construction Features  
A. Heavy steel boiler frame, built and stamped in accordance  
with the ASME Boiler Code, Section IV.  
B. Large volume water leg downcomers promote rapid internal  
circulation, temperature equalization and efficient heat transfer.  
C. Bryanbentwatertubesareexible,individuallyreplaceablewith-  
out welding or rolling. Never more than two tube configurations.  
D. Boiler tube and furnace area access panel: heavy gauge  
steelcasingwith2"hightemperatureceramic fiberandinsulation,  
bolted and tightly sealed to boiler frame.  
E. Jacket access panels make the interior of the boiler easily  
accessible for service and inspection.  
F. Steel boiler jacket with 16 gauge rust-resistant zinc coating  
andattractiveenamelnish, insulatedwith1½"berglasstoinsure  
exceptionally cool outer surface.  
G. Minimum sized flue vent.  
H. Forced draft, flame retention head type burner. Efficient  
combustion and quiet operation.  
I. All controls, gauges, relief valve(s) are factory installed and  
wired and easily accessible for servicing.  
J. Electrical box: all controls installed and connected to terminal  
strip.  
K. Water side interior accessible for cleanout and inspection,  
front and rear openings, upper and lower drums.  
Model HE-CLM300-W-FDG  
L. Steel plate boiler base with lightweight, high temperature  
insulating firebrick combustion chamber, designed for maximum  
combustion efficiency.  
Guaranteed 85%  
efficiency  
• With HE-CLM Series Boilers,  
Bryan HE-CLM Series Boiler Specifications  
you get a guaranteed 85%  
OUTPUT @ 85% EFFICIENCY(1) HTG.SURFACE APPROX. SHIP  
MBH (KW)  
combustion efficiency result-  
ing from a uniquely designed  
integrated extended surface  
heat extractor.  
BOILER  
MODEL  
INPUT  
MBH (KW)  
HP (KW)  
23 (224)  
30 (299)  
38 (374)  
46 (448)  
53 (523)  
61 (598)  
69 (672)  
76 (747)  
SQ.FT.(M2)  
171 (15.9)  
227 (21.1)  
282 (26.2)  
338 (31.4)  
394 (36.6)  
451 (41.9)  
506 (47.0)  
564 (52.4)  
LBS. (KG)  
HE-CLM90  
HE-CLM120  
HE-CLM150  
HE-CLM180  
HE-CLM210  
HE-CLM240  
HE-CLM270  
HE-CLM300  
900 (264)  
1,200 (352)  
1,500 (440)  
1,800 (527)  
2,100 (615)  
2,400 (703)  
2,700 (791)  
3,000 (879)  
765 (224)  
2,110 (957)  
1,020 (299)  
1,275 (374)  
1,530 (448)  
1,785 (523)  
2,040 (598)  
2,295 (672)  
2,550 (747)  
2,400 (1,089)  
2,860 (1,297)  
3,200 (1,452)  
3,740 (1,697)  
4,200 (1,905)  
4,740 (2,150)  
5,175 (2,348)  
• What's more, HE-CLM Boilers  
offer high operating  
efficiency—at all normal  
operation temperatures—  
without the complications  
of condensation concerns.  
NOTES : (1) Output and horsepower based on an average natural gas combustion efficiency of 85%.  
®
BRYAN BOILERS  
Originators of the “Flexible Water Tube” design  

Audiovox Mobile Video VOD128 User Manual
Blaupunkt DM2000 User Manual
Brunton NOMAD V2 PRO User Manual
Canon Camcorder GL1 User Manual
Canon RE 450X User Manual
Casio Camcorder EX Z30 User Manual
Directed Electronics OHD900 User Manual
FujiFilm FinePix Z85 User Manual
Hasselblad CF22 CF39 User Manual
iSimple IPOD PXAMG User Manual