WALL-MOUNTED CONDENSING BOILERS
WH 46
WH 65
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
GB
IE
0085
1. INSTRUCTIONS PRIOR TO INSTALLATION
This boiler is designed to heat water at a lower than boiling temperature at atmospheric pressure. The boiler
must be connected to a central heating system and/or to a domestic hot water supply system in compliance
with its performances and output power.
The boiler must be installed by a Qualified Service Engineer ensuring that the following operations are carried
out:
a) Careful checking that the boiler is fit for operation with the type of gas available. For more details see the
notice on the packaging and the label on the appliance itself.
b) Careful checking that the flue terminal draft is appropriate; that the terminal is not obstructed and that no
other appliance exhaust gases are expelled through the same flue duct, unless the flue is especially desi-
gned to collect the exhaust gas coming from more than one appliance, in conformity with the standards
and regulations in force.
c) Careful checking that, in case the flue has been connected to pre-existing flue ducts, thorough cleaning
has been carried out in that residual combustion products may come off during operation of the boiler and
obstruct the flue duct.
d) To ensure correct operation of the appliance and avoid invalidating the warranty, observe the following
precautions:
1. Hot water circuit:
If the water hardness is greater than 20 °F (1 °F = 10 mg calcium carbonate per litre of water) a
polyphosphate or comparable treatment must be used in response to current regulations.
2. Heating circuit
2.1.New system
Before proceeding with installation of the boiler, the system must be cleaned and flushed out thoroughly
to eliminate residual thread-cutting swarf, solder and solvents if any, using suitable proprietary
products.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non
alkaline. The recommended products for cleaning are:
SENTINEL X300 or X400 and FERNOX heating circuit restore. The use of this product must be strictly
in accordance with the maker’s directions. Finally the system must be dosed with a suitable inhibitor
at 1% system volume.
2.2. Existing system
Before proceeding with installation of the boiler, the system must be cleaned and flushed out to remove
sludge and contaminants, using suitable proprietary products as described in section 2.1.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-
alkaline such as SENTINEL X100 and FERNOX heating circuit protective.
Remember that the presence of foreign matter in the heating system can adversely affect the operation
of the boiler (e.g. overheating, noisy operation, or failure of the heat exchanger may occur).
Failure to observe the above will render the warranty null and void.
2. INSTRUCTIONS PRIOR TO COMMISSIONING
Initial lighting of the boiler must be carried out by a qualified service engineer. Ensure the following operations
are carried out:
a) Compliance of boiler parameters with (electricity, water, gas) supply systems settings.
b) Compliance of installation with the standards and regulations in force.
c) Appropriate connection to the power supply and earthing of the appliance.
Failure to observe the above will render the warranty null and void.
Prior to commissioning remove the protective plastic coating from the unit. Do not use any tools or abrasive
detergents as you may damage the painted surfaces.
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
3
3. COMMISSIONING OF THE BOILER
To correctly light the burner proceed as follows:
1) Provide power supply to the boiler;
2) Open the gas cock;
3) Follow the directions given below regarding the adjustments to be made at the boiler control panel.
Figure 1
IMPORTANT: The instructions contained in this manual relating to the operation of the hot water circuit
are relevant only if the appliance is actually connected to a hot water system.
KEYS
Hot water on/off key
DISPLAY SYMBOLS
Operation in hot water mode
Operation in central heating mode
Operation in automatic mode
Central heating water temperature setting key
Hot water temperature setting key
Operation in manual mode at the maximum
temperature set
Reset key
Operation in manual mode at minimum tem-
perature
Program access and scroll keys
Standby (off)
Program access and scroll key
Outdoor temperature
Flame present (on)
Parameter setting key (decrease value)
Parameter setting key (increase value)
Data display reset key
Resettable alarm warning
Central heating mode setting key
MAIN display
SECONDARY display
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
4
3.1 DESCRIPTION OF KEYS
(2) This key can be pressed to set the central heating water output temperature as described in point
3-3.
(3) This key can be pressed to set the hot water temperature as described in point 3-4.
(10) Central heating mode operating key
The
key can be pressed to activate four boiler central heating operating modes; these modes are
identified by a black cursor line underneath the relative symbol on the display, and are as follows:
Dash
“Automatic mode”
active
Figure 2
a)
Automatic operation. Operation of the boiler is controlled by the timed program as described in point
3-5.1 “Daily timed program for operation of the central heating system”;
b)
c)
Manual operation at the maximum temperature set. The boiler comes into operation regardless of
the timed program set. The operating temperature is that set using the
the maximum central heating temperature”);
key (point 3-3: “Setting
Manual operation at minimum temperature. The operating temperature is that set in point 3-6:
“setting the minimum central heating temperature”.
The manual transition from positions a) and b) to position c) involves shut-down of the burner and
disconnection of the pump after the post-circulation delay interval (the factory setting for this parameter
is 3 minutes).
d)
standby. The boiler does not work in central heating mode, although the frost protection function is
still enabled.
(1) Hot water on/off key: Press this key to activate or inhibit this function, which is identified by the
appearance on the display of two black dashes under the
symbol.
(4) Reset key. In case of a fault, referred to in point 3-7 “Faults and resetting the boiler”, the boiler
can be restarted by pressing this key for at least two seconds.
If this key is pressed with no fault present, the display will show the message “E153”, and the same
key has to be pressed again (for at least two seconds) to restart the boiler.
(9) Data key. This key can be pressed repeatedly to display the following information:
- Temperature (°C) of the hot water ( );
- outdoor temperature (°C) ( ); only provided with the outdoor temperature sensor probe
connected.
Press either of the
keys to return to the main menu.
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
5
3.2 SETTING THE TIME
a) Press either of the
keys to access the programming function;
the display will show the letter P followed by a number (program line);
Figure 3
b) Press the
keys until the display shows P1, referring to the time to be set;
c) Press the
keys to set the time; on the display, the letter P will start to flash;
key to save and exit the programming function;
d) Press the
3.3 SETTING THE MAXIMUM CENTRAL HEATING TEMPERATURE
- Press the
- Press the
key (2-figure 1) to set the central heating water temperature;
keys to set the temperature required;
- Press either of the
keys (1 or 10 - figure 1) to save and return to the main menu.
N.B – With the outdoor sensor connected, the
key (2 - figure 1) can be used to shift the central heating
curve. Press the keys to decrease or increase the room temperature in the premises to be heated.
3.4 SETTING THE MAXIMUM HOT WATER TEMPERATURE
- Press the
- Press the
key (3-figure 1) to set the maximum hot water temperature;
keys to set the temperature required;
- Press either of the
keys (1 or 10 - figure 1) to save and return to the main menu.
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
6
3.5 SETTING THE DAILY PROGRAM FOR OPERATION IN CENTRAL HEATING AND DOMESTIC HOT WATER MODES
3.5.1 Setting the daily times for central heating mode operation
- Press either of the
keys to access the programming function;
a) Press these keys until the display shows P11, referring to the program start time;
b) Press the
keys to set the time;
- Press the
key; the display will show P12, referring to the program end time;
- Repeat the operations described in points a and b until the third and last cycle is reached (program line
P16);
- Press the
key to save and exit from the programming function.
3.5.2 Setting the daily times for domestic hot water mode operation
- As supplied by the factory the appliance is set up with the hot water function always enabled and the do-
mestic hot water programming function disabled.
The instructions for enabling this program are given in chapter 17, which is addressed specifically to installers
(parameter H91).
If the program is enabled program lines from 31 to 36 must be set up as described in heading 3-5.1.
3.6 SETTING THE MINIMUM CENTRAL HEATING TEMPERATURE
- Press either of the
keys to access the programming function;
- Press these keys until the display shows p5, referring to the temperature to be set;
- Press the keys to set the temperature required.
This operating mode is enabled when minimum temperature central heating mode “ ” is activated or when
the daily central heating program does not require heat.
N.B – With the outdoor sensor connected, parameter P5 can be used to set the minimum room tempe-
rature in the premises to be heated (night setback).
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
7
3.7 TABLE FOR USER-SETTABLE PARAMETERS
Parameter
N.
Factory
setting
Parameter description
Range
P1
Time of day setting
———-
25
0…23:59
P5
Minimum central heating temperature setting (°C)
Start of first daily period of automatic central heating
End of first daily period of automatic central heating
Start of second daily period of automatic central heating
End of second daily period of automatic central heating
Start of third daily period of automatic heating
End of third daily period of automatic central heating
Start of first daily period of hot water production (*)
End of first daily period of hot water production (*)
Start of second daily period of hot water production (*)
End of second daily period of hot water production (*)
Start of third daily period of hot water production (*)
End of third daily period of hot water production (*)
25..80
P11
P12
P13
P14
P15
P16
P31
P32
P33
P34
P35
P36
6:00
22:00
0:00
0:00
0:00
0:00
0:00
24:00
0:00
0:00
0:00
0:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
Reset of daily central heating and domestic hot water production programs (factory
settings). Press the - + keys together for about 3 seconds; the number 1 appears on the
P45
0
0...1
display. Confirm by pressing either of the
keys
Note: Parameters from P31 to P36 can be displayed only if the domestic hot water program has been enabled
as described in chapter 17 for the attention of the installer (parameter H91).
3.8 FAULT WARNINGS AND RESETTING THE BOILER
If a fault occurs, a flashing warning code appears
on the display.
The fault warnings appear on the main display (figure
1 a) together with the
symbol (Figure 4).
To reset, press the reset
seconds.
button for at least two
Figure 4
Fault warnings appear on the secondary display
(figure 1 b) alternating with the time, both of them
flashing (figure 4.1). It is not possible to reset mal-
function warnings which appear on the secondary
display as the cause of the alarm has first to be
removed.
Fi
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
8
3.9 FAULT WARNINGS TABLE
Fault code
E10
Fault description
action required
outdoor temperature probe sensor failure
ntc output sensor failure
call the authorised service centre.
call the authorised service centre
call the authorised service centre
call the authorised service centre
E20
E40
NTC return heating probe faulty
domestic hot water ntc sensor failure
E50
Safety or fumes thermostat or heating return
temperature probe tripped
press the reset key (for about 2 seconds: if this device is triggered
repeatedly, call the authorised service centre)
E110
E111
E128
Delivery temperature higher than 95°C
If this fault persists, call the authorised service centre
Loss of flame during operation (the ionization current
has fallen below the limit)
Call an authorised service centre.
E129
E132
Minimum fan speed limit is hurt
floor thermostat tripped
Call an authorised service centre.
call the authorised service centre
press the reset key (for about 2 seconds); if the fault persists,
call the authorised service centre)
E133
no gas
Press the reset button if the display presents the (
) symbol,
otherwise switch off the boiler at the mains and switch it on again
after 10 seconds. If the fault persists, call an authorised service
centre. Check the position of the ignition electrodes (chapter 17).
E151
boiler circuit board error
E153
E154
E160
the reset key has been pressed inappropriately
No circulation or reverse flow
press the key again (about 2 seconds)
call the authorised service centre
call the authorised service centre.
fan speed threshold not reached
check that the system is at the rated pressure. (refer to the
section on filling the system). if the fault persists, call the
authorised service centre.
E164
no hydraulic pressure switch enabling signal
All the faults are displayed in order of importance; if several faults occur simultaneously, the first to be displa-
yed is the one with highest priority. After the cause of the first fault has been removed, the second one will
be displayed, and so on.
If any given fault occurs frequently, contact the authorised Service Centre.
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
9
4. FILLING THE BOILER
Important: Regularly check that the pressure displayed by the pressure gauge is between 1 to 4 bar, with the
boiler not operating.
In case the pressure is lower open the boiler filling tap.
We recommend you open the tap very slowly in order to let off the air.
In case pressure drops occur frequently have the boiler checked by a Qualified Service Engineer.
5. TURNING OFF THE BOILER
To shut down the boiler switch off the electrical supply to the appliance.
6. PROLONGED STANDSTILL OF THE SYSTEM. FROST PROTECTION
We recommend you avoid draining the whole system as raw water makeup will lead to harmful limestone
deposits inside the boiler and on the heating elements.
In case the boiler is not operated during wintertime and is therefore exposed to danger of frost we suggest you
add some specific-purpose anti-freeze to the water contained in the system (e.g.: propylene glycole coupled
with corrosion and scaling inhibitors).
The electronic management of the boilers includes a ‘frost protection’ function which operates the burner to
reach a heating flow temperature of 30° C when the system heating flow temperature drops below 5°C.
The frost protection function is enabled if:
* electrical supply to the boiler is on;
* the gas service cock is open;
* the system pressure is as required;
* the boiler is not isolated.
7. SERVICING INSTRUCTIONS AND GAS CHANGE
To maintain efficient and safe operation of your boiler have it checked by a Qualified Service Engineer at the
end of every heating season. Careful servicing will ensure economical operation of the system.
Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily flammable cleaners
(i.e.: gasoline, alcohol, and so on). Always isolate the electrical supply to the appliance before cleaning it (see
section 5 Turning off the boiler).
These boilers are produced for natural gas and can be converted to work with LPG (G 31).
Any gas change must be effected by a Qualified Service Engineer.
INSTRUCTIONS PERTAINING TO THE USER
926.772.1 - GB/IE
10
8. GENERAL INFORMATION
The following remarks and instructions are addressed to Service Engineers to help them carry out a faultless
installation. Instructions regarding lighting and operation of the boiler are contained in the ‘Instructions per-
taining to the user’ section.
Note that installation, maintenance and operation of the gas appliances must be performed exclusively by
qualified personnel in compliance with current standards.
Please note the following:
* This boiler can be connected to any type of double- or single feeding pipe convector plates, radiators,
thermoconvectors. Design the system sections as usual though taking into account the available output /
pump head performances.
* Do not leave any packaging components (plastic bags, polystyrene, etc.) within children’s reach as they are
a potential source of danger.
* Initial lighting of the boiler must be effected by a Qualified Service Engineer.
Failure to observe the above will render the warranty null and void.
9. INSTRUCTIONS PRIOR TO INSTALLATION
This boiler is designed to heat water at a lower than boiling temperature at atmospheric pressure. The boiler
must be connected to a central heating system and, on models with this option, to a domestic hot water supply
system in compliance with its performances and output criteria.
IMPORTANT! The gas boiler is supplied without the following components which must be provided exclusively
by qualified personnel:
• Expansion vessel;
• Pressure relief valve;
• Circulating pump;
• Boiler filling tap.
Before connecting the boiler ensure the following operations have been completed:
a) Check that the boiler is fit for operation with the type of gas available. For more details see the notice on
the packaging and the label on the appliance itself.
b) Check that the flue terminal draft is appropriate; that the terminal is not obstructed and that no other applian-
ce exhaust gases are expelled through the same flue duct, unless the flue is especially designed to collect
the exhaust gas coming from more than one appliance, in conformity with the standards and regulations in
force.
c) Check that, in case the flue has been connected to pre-existing flue ducts, thorough cleaning has been
carried out in that residual combustion products may be created during operation of the boiler and obstruct
the flue duct.
To ensure correct operation of the appliance and avoid invalidating the warranty, observe the following
precautions:
1. Hot water circuit:
If the water hardness is greater than 20 °F (1 °F = 10 mg calcium carbonate per litre of water) a
polyphosphate or comparable treatment system responding to current regulations must be used.
2. Heating circuit
2.1.New system
Before proceeding with installation of the boiler, the system must be cleaned and flushed out thoroughly
to eliminate residual thread-cutting swarf, solder and solvents if any, using suitable proprietary products.
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
11
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non
alkaline. The recommended products for cleaning are:
SENTINEL X300 or X400 and FERNOX heating circuit restore. Please ensure to use this product
proceeding strictly in accordance with the manufacturers instructions. Finally fill the system with the
correct strength of central heating inhibitor.
2.2. Existing system
Before proceeding with installation of the boiler, the system must be cleaned and flushed out to remove
sludge and contaminants, using suitable proprietary products as described in section 2.1.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-
alkaline such us SENTINEL X100 and FERNOX heating circuit protective. To use this product proceeding
strictly in accordance with the maker’s directions.
Remember that the presence of foreign matter in the heating system can adversely affect the operation
of the boiler (e.g. overheating and noisy operation of the heat exchanger). Dose with inhibitor.
Failure to observe the above will render the guarantee null and void.
10. BOILER INSTALLATION
Decide upon the boiler location, then tape the template on the wall.
Connect the pipework to the gas and water inlets prearranged on the template lower bar.
If you are either installing the boiler on a pre-existing system or replacing it, we suggest you also fit strainers
on the system return pipework to the boiler to collect the deposits and scaling which may remain and be
circulated in the system after the initial filling.
When the boiler is fixed on the template connect the flue and air ducts (fittings supplied by the manufacturer)
according to the instructions given in the following relevant sections.
Connect the condensate outlet to the siphon supplied with the boiler. Connect the siphon to a drain, making
sure there is a continuous slope. Horizontal sections must be avoided.
DRILL HOLES WITH A Ø12 BIT, FIT THE MASONRY
PLUGS AND THE SCREWS PROVIDED
N.B. INCLUDE CONDENSATE DRAIN POINT
BOILER WIDTH 600
MR: G 1” heating flow
GAS: G 3/4” gas inlet to the boiler
RR: G 1” heating return
SC: condensation drain 22 mm
Figure 5
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
12
11. BOILER SIZE
Figure 6
12. INSTALLATION OF FLUE AND AIR DUCTS
We guarantee ease and flexibility of installation for the boiler thanks to the fittings and fixtures supplied (de-
scribed below).
The boiler is especially designed for connection to an exhaust flue / air ducting, with either concentric, vertical
or horizontal terminal.
Where exhaust and intake flues not
supplied by POTTERTON GOLD HIGH
OUTPUT have been installed, these
must be certified for the type of use
and must have a maximum pressure
drop of 100 Pa for the complete flue
installation.
C33
C13
0709_1001
Figure 7
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
13
HORIZONTAL CONCENTRIC FLUES
Number of Bends 90°
Boiler
Flue Size
1
2
3
4
WH46
WH65
Ø80/125
Ø80/125
9 m
9 m
8 m
8 m
7 m
7 m
6 m
6 m
VERTICAL CONCENTRIC FLUES
Number of Bends 90°
Boiler
Flue Size
1
2
3
4
WH46
WH65
Ø80/125
Ø80/125
9 m
9 m
8 m
8 m
7 m
7 m
6 m
6 m
CONVENTIONAL FLUE
Number of Bends 90°
Boiler
Flue Size
1
2
3
4
WH46
WH65
Ø80
Ø80
59,5 m
59,5 m
59 m
59 m
58,5 m
58,5 m
58 m
58 m
Concentric flue
This type of duct allows to emit exhaust gases and to draw combustion air from outside the building.
The 87° coaxial bend allows to connect the boiler to a flue-air duct in any direction as it can rotate through
360°.
If the flue outlet is placed outside, the flue-air ducting must protrude at least 18mm out of the wall to allow
alluminium weathering tile to be fitted and sealed to avoid water leakages. If the terminal is below 2m then a
terminal gaurd is required.
Ensure a minimum downward slope of 3° towards the boiler.
A 87° bend reduces the total flue length by 1 metre.
A 45° bend reduces the total flue length by 0.5 metre.
Concentric o
Figure 8
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
14
12.1 HORIZONTAL FLUE TERMINAL Ø 80/125 INSTALLATION OPTIONS
L = refer to table
12.2 VERTICAL FLUE TERMINAL Ø 80/125 mm INSTALLATION OPTIONS
This type of installation can be carried out both on a flat or pitched roof by fitting a terminal, an appropriate
weathering tile and sleeve, (supplementary fittings supplied as options).
L = refer also the table
L max = 10 m
L max = 10 m
L max = 8 m
L max = 9 m
12.5 FAN RPM UPDATING DEPENDING ON FLUE LENGTH (e.g. figure 7)
To ensure the correct rated heat output to the maximum and minimum heat input, it is necessary to update
the speed (rpm) of the fan, it depends on the length of the flue (par. 12), in accordance with the installation of
flue and air pipes as indicated in the tables below. The factory-set value is referred to the minimum length of
flue pipe (0÷4 m for concentric, 0÷20 m for twin). To carry such updating, changing the speed of the fan (rpm)
at the maximum and minimum heat input, refer to par. 16.
WH 65
WH 46
CONCENTRIC PIPE Ø 80/125
(C13-C33-C43)
CONCENTRIC PIPE Ø 80/125
(C13-C33-C43)
Parametres
H536-H613
Parametres
H612
Parametres
H536-H613
Parametres
H612
Pipes length (m)
Pipes length (m)
Max heat output (rpm) Min heat output (rpm)
Max heat output (rpm) Min heat output (rpm)
(*) 0 - 4
5 - 10
(*) 0 - 4
5 - 10
5500
5900
1900
2100
6000
6500
1850
2100
(*) Default setting parameters
(*) Default setting parameters
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
15
13. HYDRAULIC DIAGRAM
Applications and Installation Details
13.1 HYDRAULIC SYSTEM 1
(Pumped heating circuits with remote control QAA73 or Room Thermostat, including hot-water tank, without
and with primary loop)
(*)
(*) optional extra
without low loss header
Figure 9a
(*)
(*)
(*)
(*) optional extra
(*)
with low loss header and primary loop
Figure 9b
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
16
•
•
•
•
•
•
•
TS: Tank Sensor (QAZ36)*
B3: Room Control Module (QAA73)*
B1: Room Thermostat
B9: Outdoor Temperature Sensor (QAC34)*
P1: Heating Pump
PDHW: Hot Water pump
PLP: Primary Pump (only for figure 9b)
(*) Available Optional Extra
•
•
•
•
•
•
Pumps (Not Supplied)
Isolating Valve (Not Supplied)
Installer Wiring --------------
Hot Water Cylinder (Not Supplied)
Low Loss Header (Not Supplied)
Non return valve (Not supplied)
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 14):
WITH QAA73
WITH
REMOTE CONTROL
ROOM THERMOSTAT
APPLICATION
TERMINAL BOARD
M1: A – B
TERMINAL BOARD
M1: A – B
M3: 13 – 14
M3: 11 – 12
M2: 7 – 8
PRIMARY PUMP PLP (only for figure 9b)
DHW PUMP PDHW
M3: 13 – 14
M3: 11 – 12
M2: 7 – 8
HEATING PUMP P1
DHW SENSOR TS
REMOTE CONTROL QAA73
ROOM THERMOSTAT
M2: 1 – 2
NO
M2: 3 – 4 OPEN
M2: 3 – 4
Parameter changes requires (see also section 16):
PCB
Description
PARAMETER
Setting Parameter
H552
H553
H615
H632
Hydraulic system
KonfigHKS
H552 = 2
H553 = 21
KonfigAusgang
Wanfo Q8
H615 = 9
H632 = 00001100
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
17
13.2 HYDRAULIC SYSTEM 2
(Pumped heating circuits with Room Thermostat and compensated circuit with remote control QAA73, inclu-
ding hot-water tank, with primary loop)
• TS:Tank Sensor (QAZ36)*
• B3: Room Control Module (QAA73)*
• B1: Room Thermostat
• B9: Temperature Sensor (QAC34)*
• Zone Controller (Clip-in AGU2.500)*
• FS: Flow Sensor (QAD36: supplied with AGU2.500)*
• P1: Heating Pump
• P DHW: Hot Water pump
• PLP: Primary Pump
• 3WV: 3-way Valve (power open / power close)
(*) Available Optional Extra
• Pumps (Not Supplied)
• Isolating Valve (Not Supplied)
• Installer Wiring --------------
• Hot Water Cylinder (Not Supplied)
• Low Loss Header (Not Supplied)
• Non Return Valve (Not supplied)
*
*
*
HEATING CIRCUIT
COSTANT TEMP.
HEATING CIRCUIT
VARIABLE TEMP.
AGU 2.500*
*
Figure 10
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
18
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 14):
APPLICATION
TERMINAL BOARD
M1: A – B
PRIMARY PUMP PLP
DHW PUMP PDHW
M3: 13 – 14
HEATING PUMP P1
DHW SENSOR TS
M3: 11 – 12
M2: 7 – 8
REMOTE CONTROL QAA73 (LOW TEMPERATURE)
ROOM THERMOSTAT
HEATING PUMP P2
3 WAY VALVE
M2: 1 – 2
M2: 3 – 4
CLIP IN AGU 2.500
CLIP IN AGU 2.500
CLIP IN AGU 2.500
FLOW SENSOR
Parameter changes requires (see also section 16):
PCB
Description
PARAMETER
Setting Parameter
H552
H553
H615
H632
Hydraulic system
KonfigHKS
H552 = 50
H553 = 12
KonfigAusgang
Wanfo Q8
H615 = 9
H632 = 00001111
13.3 HEAT EXCHANGER PRESSURE DROP
Hydraulic Resistance and Water Flow Rates
Boiler
11°C ∆T
kPa
15°C ∆T
kPa
20°C ∆T
kPa
30°C ∆T
kPa
Lit/sec
0,98
Lit/sec
0,72
Lit/sec
0,54
Lit/sec
0,36
WH46
WH65
70,61
56,88
31,38
34,32
11,77
20,59
10,79
11,77
1,41
1,04
0,78
0,52
Minimum Water Flow Rates
Boiler
Lit/sec
0,28
WH46
WH65
0,35
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
19
14. CONNECTING THE MAINS SUPPLY
Electrical safety of the appliance is only guaranteed by correct earthing, in compliance with the applicable
standards and regulations.
Connect the boiler to a 230V earthed power supply by means of the three-pin cable supplied ensure that the
polarity is correct.
Use a double-pole switch isolator with a contact separation of at least 3mm in both poles.
In case you replace the power supply cable fit a HAR H05 VV-F’ 3x0.75mm2 cable with an 8mm diameter
maximum outer sheath.
The fuse, a fast-acting type rated 2A, is incorporated into the power supply terminals (remove the black fuse
holder to enable inspection and/or replacement).
IMPORTANT: Check that the overall current drawn by accessories connected to the appliance is less than 1
amp. If the value is greater, a relay must be wired between the boiler control circuit board and the accessories
drawing the higher current.
Terminal board M1
Terminal board M2
Cover
Cover
Figure 11
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
20
14.1 CONNECTING THE PUMPS
Turn the control box downward to access terminal boards M1 and M3 used for the electrical connections by
removing the protective covers (see figure 12).
Terminals M1 a – b: connection of the primary loop pump for the heating system (PLP)
Check the correct size and rating of the pump by referring to its hydraulic resistance table.
Terminals M3 11 – 12: connection for heating pump (P1)
Terminals M3 13 – 14: connection for hot water tank pump (PDHW)
The electrical specifications of the pump must be as follows:
230 V AC; 50 Hz; 1 A max; cos f > 0.8.
If the specifications of the installed pump are different, a relay must be wired between the boiler control circuit
board and the pump.
It is advisable not to adopt any electrical connection other than those described.
Connect
Figure 12
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
21
14.2 CONNECTING THE HOT WATER TANK SENSOR
Remove the resistor from terminals 9-10 of terminal strip M2 (figure 13), and connect the hot water priority
NTC sensor, which is supplied as an accessory.
The sensing element of the NTC device must be located in the recess provided on the storage tank (figure 13).
The temperature and on-off programming of the domestic hot water supply are selected directly from the
boiler control panel, as described in this manual under the user instruction headings.
SAFETY
CONTACT
ROOM THERMOSTAT
Figure 13
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
22
14.3 DESCRIPTION OF THE ELECTRICAL CONNECTIONS TO THE BOILER
Turn the control box downward to access terminal board M2 used for the electrical connections by removing
the protective cover (see figure 13).
Terminals 1-2: connection of SIEMENS model QAA73 room temperature regulator supplied as optional extra.
Connection polarity is irrelevant.
The link fitted across the “TA” terminals 3-4 must be removed.
Read the instructions supplied with this accessory for correct installation and programming procedures.
Terminals 3-4: “TA” room temperature thermostat connection. Thermostats with integral accelerator resistor
must not be used. Check that there is no voltage across the ends of the two thermostat connection wires.
Terminals 5-6: external safety contact (low voltage).
Terminals 7-8: connection of SIEMENS model QAC34 outdoor temperature sensor supplied as optional extra.
Read the instructions supplied with this accessory for correct installation procedures.
Terminals 9-10: connection of hot water temperature sensor supplied as optional extra for connecting hea-
ting-only boilers to an external water heater.
CLIP-IN AGU 2.511
Terminals 3-4 L-N OUT: connection to signal lamp (230 V - 0,5 A max) for lockout alarm.
Terminals 5-6 L-N OUT: connection to signal lamp (230 V - 0,5 A max) for run mode.
For low voltage signal lamp remove the internal wiring and feed with an external low voltage power supply.
(OPTIONAL EXTRA)
Figure 14
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
23
14.4 CONNECTING THE QAA73 TEMPERATURE REGULATOR
The SIEMENS model QAA73 room temperature regulator, if required (optional extra) must be connected to
terminals 1-2 of terminal board M2 in figure 13.
The link across terminals 3-4, provided for connection of a room temperature thermostat, must be removed.
The settings of the domestic hot water temperature and domestic hot water production schedule must be
made using this device.
The timed program of the central heating circuit must be set on the QAA73 if there is a single zone, or in relation
to the zone controlled by the QAA73 device.
The timed program for the central heating circuit of the other zones can be set directly on the boiler control
panel.
See the instructions provided with the QAA73 room temperature regulator for the user parameter programming
procedure.
IMPORTANT: For systems divided into zones, parameter 80 “HC2 curve”, which can be set on the QAA73
temperature regulator, must be set as _ _ . _ “not active”.
QAA73: parameters which can be set by the installation engineer (service)
By pressing the two PROG buttons together for at least three seconds it is possible to access the list of pa-
rameters that the installer can display and/or set.
Press either of these buttons to change the parameter to display or change.
Press the [+] or [-] key to change the value displayed.
Press either of the PROG buttons again to save the change.
Press the information button (i) to quit programming.
Here follows a list of the most commonly used parameters:
Line no. Parameter
Range
Default value
15
70
HC1 curve
2.5…40
Selection of central heating circuit temperature curve “kt”
72
HC1 max. output
25…85
85
Central heating system maximum output temperature
74
75
Type of building
Light, Heavy
on HC1
Light
Room compensation
On HC1
Activation/deactivation of the influence of the room temperature. If it is deactivated, the outdoor on HC2
temperature sensor must be installed.
on HC1+HC2
nil
77
78
Automatic adaptation of the temperature curve “kt” in relation to the room temperature.
On - off
0…360 min
On
0
Opt Start Max
Maximum time the boiler is switched on ahead of the timed program to optimise the temperature
in the premises.
79
Opt Stop Max
0…360 min
0
Maximum time the boiler is switched off ahead of the timed program to optimise the temperature
in the premises.
80
90
91
HC2 curve
2.5…40
—.- = not active
—.-
DHW Red Setp
Minimum temperature of the domestic hot water
10 or 35…58
10
DHW program
24 h/day
24 h/day
Selection of the type of timed program for domestic hot water.
TSP HC-1h
TSP HC
TSP DHW
24 h/day
= always on
PROG HC-1h
PROG HC
PROG DHW
= as HC1 central heating program less one hour
= as central heating program
= specific domestic hot water program (see also program lines 30-36)
- fault messages
In the event of fault, the display panel on the QAA73 shows the flashing symbol . Press the information key
( ) to display the error code and a description of the fault (see Fault warning tables on paragraph 3.9).
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
24
14.5 CONNECTING THE OUTDOOR TEMPERATURE SENSOR
The SIEMENS model QAC34 outdoor temperature sensor (optional extra) for weather compensation must be
connected to terminals 7-8 of terminal board M2 in figure 13.
The procedures for setting the gradient of the temperature curve “kt” vary depending on the accessories
connected to the boiler.
a) Without QAA73 room temperature regulator:
The temperature curve “kt” must be selected by setting parameter H532 as described in section 16 “setting
the boiler parameters”.
See graph 2 for selecting the curve referred to a room temperature of 20°C.
The chosen curve can be shifted by pressing the
(2), button (2) on the boiler control panel, and modifying
keys. See graph 3 for curve selection. (The example show
the value displayed by pressing the
in graph 3 refers to the curve Kt=15).
and
Increase the value displayed if the room temperature required is not reached inside the premises for central
heating.
TM = Flow temperature
Te = Composite outside temperature
Sth = Kt Curve
Graph 2
Graph 3
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
25
b) With QAA73 room temperature regulator:
The temperature curve “kt” must be selected by setting parameter 70 “HC1 curve” of the QAA73 room tem-
perature control device as described in section 14.4 “QAA73: parameters which can be set by the installation
engineer (service)”.
See graph 4 for selecting the curve referred to a room temperature of 20°C.
The curve is shifted automatically on the basis of the room temperature set using the QAA73 climate con-
trol.
If the system is divided into zones, the temperature curve “kt” relating to the part of the system not control-
led by the QAA73 must be selected by setting parameter H532 as described in section 16 “setting the boiler
parameters”.
IMPORTANT: For systems divided into zones, parameter 80 “HC2 curve”, which can be set on the QAA73
room temperature regulator, must be set as _ _ . _ “not active” (see section 14.4).
TM = Flow temperature
Te = Composite outside temperature
Graph 4
c) With AGU2.500 for control of a low temperature system:
Refer to the instructions provided with the AGU2.500 accessories for connection and control of a low tem-
perature zone.
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
26
15. GAS VALVE ADJUSTMENT
Carry out the following operations in the given sequence:
1) Calibration of the maximum heat output. Check that the CO2 measured on the flue, with the boiler operating
at the maximum heat output, is the same as that shown in table 1. Otherwise, turn the regulation screw (V) on
the gas valve. Turn the screw clockwise to reduce the concentration of CO2 and anticlockwise to increase it.
2) Calibration of reduced heat output. Check that the CO2 measured on the flue, with the boiler operating at the
minimum heat output, is the same as that shown in table 1. Otherwise, turn the offset regulation screw (K) on
the gas valve. Turn the screw clockwise to increase the concentration of CO2 and anticlockwise to reduce it.
Pi:
Gas supply pressure connection point
P out: Gas pressure to burner connection point
P:
Pressure connection point
for measurement of the OFFSET
Air signal input from fan
Pl:
V:
Gas flow adjuster screw max fire
OFFSET adjuster screw min fire
K:
Figure 15
To simplify calibration of the gas valve, the “calibration function” can be set directly on the boiler control panel
by proceeding as follows:
1) Press the
keys (2-3) together until the display shows the pointer “ ” alongside the and symbols
(about 6 seconds) (see fig. 16).
2) Press the
keys to set the fan speed at the minimum and maximum heat output (%PWM);
N.b - to set the minimum and maximum heat output quickly, press the
keys respectively;
3) press either of the two
keys to exit the function.
Figure 16
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
27
IMPORTANT: in the case of conversion from natural gas to propane (LPG), the following operations must be
performed before calibrating the gas valve as illustrated previously:
• Turn adjuster screw (V) on the gas valve through the number of complete revolutions specified in table 3.
G20 - 2H - 20 mbar
8.7 %
G31 - 3P - 37 mbar
10 %
CO2 max. heat output
CO2 min. heat output
8.4 %
9.8 %
Table 1
Gas consumption at 15 °C
1013 mbar
WH 46
WH 65
gas G20 - 2H - 20 mbar
PCI (MJ/Kg) NET
34.02
34.02
7.08
2.11
---
Consumption at max. heat output (Kg/h)
Consumption at min. heat output (Kg/h)
Gas nozzle (mm)
4.91
1.58
8.5
Table 2
Gas consumption at 15 °C
1013 mbar
WH 46
WH 65
gas G31 - 3P - 37 mbar
PCI (MJ/Kg) NET
46.34
3.60
1.16
8.5
46.34
5.20
1.55
---
Consumption at max. heat output (Kg/h)
Consumption at min. heat output (Kg/h)
Gas nozzle (mm)
Table 2.1
Model
Counter clockwise
turns of screw
(V)
WH 46
WH 65
3
4 3/4
Table 3
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
28
16. SETTING THE BOILER PARAMETERS
The boiler parameters may only be modified by professionally qualified staff proceeding as follows:
a) Press the
the display;
b) Press the
, keys on the boiler’s front panel together for about 3 s until the parameter H90 appears on
keys to select the parameter for modification;
c) Press the and keys to modify the parameter;
d) Press the key to exit the programming function.
The following are the parameters generally used:
N° parametro
H90
Description
Factory setting
Setting for domestic hot water reduced temperature (°C)
10
D.H.W. (Domestic Hot Water) program
(0 = enabled; 1 = disabled)
H91
1
Maximum temperature (°C) of the central heating circuit HC1 corresponding to:
-
-
the main circuit in systems with just one zone;
the circuit of the zone where the QAA73 temperature control device is installed in case of
systems with more than one high-temperature zone;
the high temperature zone circuit in mixed systems and if the SIEMENS AGU2.500 accessory
is used.
H505
80
-
Maximum temperature (°C) of the central heating circuit HC2 of a system with more than one
zone, corresponding to the circuit of the low-temperature zone if the SIEMENS AGU2.500
accessory is used.
H507
80
H516
H532
Automatic Summer / Winter switching temperature (°C).
20
15
15
Selection of temperature curve of central heating circuit HC1 (see Graph 1)
Selection of temperature curve of central heating circuit HC2 (see Graph 1)
Maximum speed at maximum output in heating mode (rpm - maximum speed limitation)
Setting value of required speed (rpm) at low-fire
H533
H536
H612
Refer to
paragraph 12.1
H536-H613
H541-H610
H544
Setting value of required speed (rpm) at high-fire heating / domestic hot water mode
PWM (%) setting: maximum output in heating / domestic hot water mode
Pump post-circulation time in central heating mode (min)
10
H545
Burner operating pause time between two start-ups (s)
180
Hydraulic system setting (see instructions provided with the SIEMENS AGU2.500 accessory).
H552 = 50 with AGU2.500
H552 = 80 with RVA 47
H552
2
Configuration of heating circuits
H553 = 12 with AGU2.500
H553
H615
21
9
Programmable function
Configuration of system with low loss header P1
H632 = 00001111 with AGU2.500
H632 = 00001000 with storage tank without low loss header
H632
00001100
The value of Bit could be 1 or 0.
Press the keys 5 and 6 to select the bit to modify (b0 is the bit on the right, b7 is the last bit
on the left).
To modify the Bit value press on the keys 7 and 8
H641
H657
Fan post-purge interval (s)
10
0
Setpoint of autonomous ANTILEGIONELLA function
60...80 °C = setting temperature range
0 = function inactive
Table 4
If the electronic circuit board is replaced, make sure that the parameters set are those specific to the boiler
model, as indicated in the documentation available from the authorised Service Centre.
(*) For these parameters see section 13 (hydraulic system).
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
29
17. CONTROL AND OPERATION DEVICES
The boiler has been designed in full compliance with European reference standards and in particular is equip-
ped with the following
• Overheat thermostat
This thermostat interrupts the gas flow to the main burner in case the water contained in the circuit has ove-
rheated. Under these conditions the boiler locks out and can only repeat the ignition procedure by pressing
of the reset button on the boiler after the cause of the trip has been rectified.
It is forbidden to disable this safety device
• Boiler circuit circulation test
The boiler electronic management unit is fitted with a “boiler circulation test” function which involves con-
tinuously checking the primary circuit delivery and return temperatures. In case of an irregular increase in
the delivery and return temperature or a temperature reversal, the boiler stops and signals the error on the
display (see error table).
• Flue thermostat
This device, positioned on the flue inside the boiler, interrupts the flow of gas to the burner if the temperature
exceeds 90 °C. After verifying the cause of the trip, press the reset button positioned on the thermostat
itself, then press the reset button on the boiler.
It is forbidden to disable this safety device
• Flame ionization detector
The flame sensing electrode guarantees safety of operation in case of gas failure or incomplete interlighting
of the main burner.
Under such conditions the boiler is locked out.
You must press the reset button on the boiler to restore the normal operating conditions.
• Supplementary pump overrun
After the burner has switched off due to a room thermostat intervention the preset pump overrun of the
pump lasts 10 minutes, when the boiler is in the central heating mode.
• Frost protection device
The boilers electronic management includes a “frost protection” function in the central heating system which
operates the burner to reach a heating flow temperature of 30°C when the system heating flow temperature
drops below 5 °C.
This function is enabled as long as the boiler is connected to the a.c. power supply gas supplies and the
pressure in the system is as specified.
• Pump-blocking prevention
In case there is no call for heat either from the central heating system or from the DHW system for 24 hours
on end the pump will automatically switch on for 10 seconds.
• Gas pressure switch
This device enables the main burner only to be switched on if the gas pressure is over 12 mbar.
• Hydraulic pressure sensor
This device enables the main burner only to be switched on if the system pressure is over 0.5 bar.
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
30
18. POSITIONING OF THE IGNITION AND FLAME SENSING ELECTRODE
Figure 17
19. CHECK OF COMBUSTION PARAMETERS
To measure the performance of combustion products, the forced draught boiler models are equipped with two
test points on the tapered coupling specifically designed for this purpose.
One of the two test points is connected to the exhaust flue duct to allow measurements of the combustion
products and efficiency.
The second test point is connected to the comburant air inlet duct to check possible combustion products
circulation in case of coaxial ducts.
The exhaust flue duct test point allows measurements of the following:
• combustion products temperature;
• concentration of oxygen (O2) or, alternatively, of carbon dioxide (CO2);
• concentration of carbon monoxide (CO).
The comburant air temperature must be measured at the test point connected to the air inlet duct.
flue gas
combustion air
gasket
Figure 18
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
31
20. ACTIVATING THE CHIMNEY-SWEEP FUNCTION
To facilitate measurement of the combustion efficiency and improve the cleanliness of the production products,
the chimney sweep function can be activated by proceeding as described below:
1) Press the
(2-3) together until the pointer “ ” appears on the display alongside the symbol (about 3
seconds but no more than 6 seconds). In these conditions, the boiler operates at the maximum heat output
set for central heating.
2) Press either of the
buttons to exit the function.
Figure 19
21. ANNUAL SERVICE
To ensure the boiler operates at peak efficiency, the following checks must be performed every year:
• Check on the appearance and tightness of the gas and combustion circuit gaskets;
• Check on the condition and position of the ignition and flame sensing electrodes (see section 18);
• Check on the condition of the burner and its fixing to the aluminium flange;
• Check for any dirt in the combustion chamber. Use a vacuum-cleaner for this cleaning operation,
• Check if the syphon trap is dirty;
• Check that the gas valve is calibrated correctly (see section 15);
• Check on the central heating system pressure.
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
32
22. BOILER SCHEMATIC
Figure 20
Legend:
1
2
Boiler drain point
Manometer (water pressure gauge)
3
4
5
6
Siphon (condensate)
NTC delivery heating probe
105°C overheat thermostat
Gas valve
7
Heat exchanger
8
9
Flame detector electrode (ionisation probe)
Main burner
10
11
12
13
14
15
16
17
18
19
20
21
Ignition electrode
Air/gas mixture header
Mixer with venturi
Injector
Fan
Flue thermostat
Flue spigot
Automatic air vent
Flue joint
Hydraulic pressure sensor
Pressure gas switch
NTC return heating probe
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
33
23. ILLUSTRATED WIRING DIAGRAM
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
34
24. TECHNICAL DATA
Boiler model WH
WH 46
WH 65
II2H3P
Category
II2H3P
46,4 - 51,5
15 - 16,6
45,0
Nominal heat input (net/gross)
Reduced heat input (net/gross)
kW
kW
67,0 - 74,4
20,0 - 22,2
65,0
kW
Rated heat output 75/60°C
Rated heat output 50/30°C
Reduced heat output 75/60°C
kcal/h
kW
38.700
48,7
55.900
70,3
kcal/h
kW
41.880
14,5
60.460
19,3
kcal/h
kW
12.470
15,8
15.820
21,0
Reduced heat output 50/30°C
kcal/h
—
13.588
★★★★
97,3 / 87,3
105,1 / 94,5
107,6
18.060
★★★★
97,4 / 87,4
105,2 / 94,5
107,6
Useful efficiency according to 92/42/CEE directive
Useful efficiency max heat output 75/60 °C net/gross
Useful efficiency max heat output 50/30 °C net/gross
Useful efficiency 30% heat output
Central heating system max. pressure
Heating circuit temperature range
Type
%
%
%
bar
4
4
°C
25÷80
25÷80
—
C13 - C33 - C43 - C53 - C63 - C83 - B23
Concentric flue duct diameter
Concentric air duct diameter
Twin-pipe flue duct diameter
Twin-pipe air duct diameter
Max. flue mass flow rate
Min. flue mass flow rate
mm
mm
mm
mm
kg/s
kg/s
°C
80
125
80
80
125
80
80
80
0,022
0,007
74
0,032
0,010
75
Max. flue temperature
NOx class
—
5
5
NOx
mg/kWh
—
38,4
G20/G31
20
37,7
G20/G31
20
Type of gas used
Natural gas pressure 2H
Propane gas pressure 3P
Gas Consumption (NG)
mbar
mbar
m3/hr
m3/hr
Bar
cm2
cm2
lit/sec
kPa
mm
mm
lit
37
37
4,91
1,89
1
7,08
2,74
1
Gas Consumption (LPG)
Minimum Operating Pressure
High Level Ventilation to BS6644 boiler room
Low Level Ventilation to BS6644 boiler room
Water Flow at 20°C ∆t
92,8
185,6
0,54
11,7
19
134
268
0,78
20,6
25
Hydraulic Resistance at 20°C ∆t
Cold Feed Size to BS6644
Safety valve size to BS6644 (open vent system)
Water Content
19
19
5,1
6,5
Maximum Flow Temperature
Ventilation to BS5440
°C
85
85
cm2
V
Power supply voltage
230
50
230
50
Power supply frequency
Rated power supply
Hz
W
75
125
72
Net weight
kg
64
Dimensions
height
width
depth
mm
mm
mm
950
600
466
IPX5D
950
600
466
IPX5D
Protection-limit against humidity and water leakages (**)
(**) according to EN 60529
INSTRUCTIONS PERTAINING TO THE INSTALLER
926.772.1 - GB/IE
35
POTTERTON GOLD HIGH OUTPUT, in its commitment to constantly improve its products, reserves the right to alter the
specifications contained herein at any time and without previous warning. These Instructions are only meant to provide
consumers with use information and under no circumstance should they be construed as a contract with a third party.
Wood Lane
Erdington
Birmingham
B24 9QP
TELEPHONE
FAX
0845 0701058
0845 0701059
WEB
POTTERTON GOLD HIGH OUTPUT
Ed. 2 - 07/11
code 926.772.1
|