Ariston E COMBI 24 30 38 User Manual

,QVWDOODWLRQꢀDQGꢀ6HUYLFLQJꢀLQVWUXFWLRQV  
E-Combi  
E-System  
24/30/38  
24/30  
CONDENSING WALL HUNG  
COMBINATION BOILER  
G.C.N : 47 - 116 - 62 (24 kW)  
G.C.N : 47 - 116 - 63 (30 kW)  
G.C.N : 47 - 116 - 64 (38 kW)  
CONDENSING WALL HUNG  
O.H. BOILER  
G.C.N : 41 - 116 - 34 (24 kW)  
G.C.N : 41 - 116 - 35 (30 kW)  
Country of destination GB, IE  
overview  
These instructions are suitable for E-COMBI and E-SYSTEM boilers :  
Do not forget to complete the Benchmark Commisioning Checklist.  
The Benchmark Scheme  
Benchmark places responsibilities on both manufacturers and installers.  
The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned  
and serviced in accordance with the manufacturers instructions by competent persons and that it meets the requirements of the  
appropriate Building Regulations.  
The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer  
for future reference.  
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of  
Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.  
To the Installer  
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that  
your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.  
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.  
ARISTON recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.  
CUSTOMER CARE  
ARISTON, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products  
and a high quality after sales service.  
Advice on installation or servicing can also be obtained by contacting the ARISTON Technical and Customer Service Departments at High  
Wycombe.  
TECHNICAL DEPARTMENT  
Tel: 0870 241 8180  
Fax: 01494 459775  
CUSTOMER SERVICE DEPARTMENT  
Tel:  
0870 600 9888  
01494 459775  
Fax:  
GUARANTEE  
The manufacturer’s guarantee is for 2 years from the date of installation or 18 months from the date of production. The  
guarantee is invalidated if the appliance is not installed in accordance with the recommendations made herein or in a manner  
not approved by the manufacturer.  
without delay.  
CAUTION  
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person only,  
in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.  
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person in  
accordance with the current edition of I.S.813 “Domestic Gas Installations, the current Building Regulations, reference should  
also be made to the current ETCI rules for electrical installation.  
All Gas Safe registered installers carry an ID card, and have a registration number. Both should be recorded in your  
direct on 0800 408 5500.  
Improper installation may cause damage or injury to individuals, animals and personal property for which the manufacturer  
will not be held liable.  
To ensure efficient and safe operation it is recommended that the boiler is serviced annually by a competent person.  
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent person.  
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland  
3
overview  
Advice for the installer  
Symbols used on the data plate  
The installation and first ignition of the boiler must be  
performedbyqualifiedpersonnelincompliancewithcurrent  
national regulations regarding installation, and in conformity  
with any requirements established by local authorities and public  
health organisations.  
After the boiler has been installed, the installer must ensure  
that the end user receives the declaration of conformity and the  
operating manual, and should provide all necessary information  
as to how the boiler and the safety devices should be handled.  
2
1
4
3
5
6
7
This appliance is designed to produce central heating hot water for  
domestic use only.  
It should be connected to a heating system and a distribution network  
for domestic hot water, both of which must be compatible with its  
performance and power levels.  
The use of the appliance for purposes other than those specified is  
strictly forbidden. The manufacturer cannot be held responsible for  
any damage caused by improper, incorrect and unreasonable use of  
the appliance or by the failure to comply with the instructions given  
in this manual.  
8
MAX  
MIN  
Q
P
9
12  
13  
60/80°C  
15  
16  
18  
17  
10  
11  
20  
21  
22  
19  
Installation, maintenance and all other interventions must be carried  
out in full conformity with the governing legal regulations and the  
instructions provided by the manufacturer. Incorrect installation  
can harm persons, animals and possessions; the manufacturing  
company shall not be held responsible for any damage caused as a  
result. The boiler is delivered in a carton. Once you have removed all  
the packaging, make sure the appliance is intact and that no parts are  
missing. If this is not the case, please contact your supplier.  
Keep all packaging material (clips, plastic bags, polystyrene foam, etc.)  
out of reach of children as it may present a potential hazard.  
In the event of a fault and/or malfunction, turn the appliance off, turn  
off the gas cock and do not attempt to repair it yourself. Contact a  
qualified professional instead.  
Before any maintenance or repair work is performed on the boiler,  
make sure you have disconnected it from the electricity supply  
by switching the external bipolar switch to the “OFF” position and  
removing the fuse.  
All repairs, which should only be performed using original spare parts,  
should be carried out by a qualified professional. Failure to comply  
with the above instructions could compromise the safety of the  
appliance and invalidate all liability on the part of the manufacturer.  
In the event of any maintenance or other structural work in the  
immediate vicinity of the flue or flue gas exhaust devices and their  
accessories, switch the appliance off by switching the external bipolar  
switch to the “OFF” position and shutting off the gas control valve.  
When the work has been completed, a qualified technician must  
check the efficiency of the flue and the devices.  
Legend :  
1. Brand  
2. Manufacturer  
3. Boiler model - Serial number  
4. Commercial reference  
5. Certification number  
6. Destination country - gas category  
7. Gas setting  
8. Installation type  
9. Electrical data  
10. Maximum domestic hot water pressure  
11. Maximum heating pressure  
12. Boiler type  
13. NOx class / Efficiency  
14. Input rating nominal heating  
15. Power ouput heating  
16. DHW specific flow rate  
17. Boiler output efficiency  
18. Input rating nominal DHW  
19. Gases which may be used  
20. Minimum ambient temperature for use  
21. Max. central heating temperature  
22. Max. domestic hot water temperature  
Turn the boiler off and turn the external switch “OFF” to clean the  
exterior parts of the appliance.  
Clean using a cloth dampened with soapy water. Do not use  
aggressive detergents, insecticides or toxic products. If the appliance  
is used in full compliance with current legislation, it will operate in a  
safe, environmentally-friendly and cost-efficient manner.  
If using kits or optional extras, make sure they are authentic.  
CE labelling  
The CE mark guarantees that the appliance conforms to the following  
directives:  
-
-
-
-
90/396/CEE  
relating to gas appliances  
2004/108/CEE  
relating to electromagnetic compatibility  
92/42/CEE  
relating to energy efficiency  
2006/95/CEE  
relating to electrical safety  
4
overview  
Safety regulations  
Key to symbols:  
Failure to comply with this warning implies the risk of personal  
injury, in some circumstances even fatal.  
Failure to comply with this warning implies the risk of damage, in  
some circumstances even serious, to property, plants or animals.  
During all work carried out at a certain height (generally  
with a difference in height of more than two metres), make  
sure that parapets are used to surround the work area or  
that individual harnesses are used to prevent falls. The space  
where any accidental fall may occur should be free from  
dangerous obstacles, and any impact upon falling should be  
cushioned by semi-rigid or deformable surfaces.  
Personal injury caused by falling from a height.  
Install the appliance on a solid wall which is not subject to  
vibration.  
Noisiness during operation.  
When drilling holes in the wall for installation purposes, take  
care not to damage any electrical wiring or existing piping.  
Electrocution caused by contact with live wires. Explosions, fires  
or asphyxiation caused by gas leaking from damaged piping.  
Damage to existing installations. Flooding caused by water  
leaking from damaged piping.  
Make sure the workplace has suitable hygiene and sanitary  
conditions in terms of lighting, ventilation and solidity of the  
structures.  
Perform all electrical connections using wires which have a  
suitable section.  
Personal injury caused by knocks, stumbling etc.  
Protect the appliance and all areas in the vicinity of the work  
place using suitable material.  
Damage to the appliance or surrounding objects caused by  
falling splinters, knocks and incisions.  
Handle the appliance with suitable protection and with care.  
Damage to the appliance or surrounding objects from shocks,  
knocks, incisions and squashing.  
Fire caused by overheating due to electrical current passing  
through undersized cables.  
Protect all connection pipes and wires in order to prevent  
them from being damaged.  
Electrocution caused by contact with live wires. Explosions, fires  
or asphyxiation caused by gas leaking from damaged piping.  
Flooding caused by water leaking from damaged piping.  
Make sure the installation site and any systems to which the  
appliance must be connected comply with the applicable  
norms in force.  
During all work procedures, wear individual protective  
clothing and equipment.  
Personal injury caused by electrocution, falling splinters or  
fragments, inhalation of dust, shocks, cuts, puncture wounds,  
abrasions, noise and vibration.  
Place all debris and equipment in such a way as to make  
movement easy and safe, avoiding the formation of any piles  
which could yield or collapse.  
Damage to the appliance or surrounding objects from shocks,  
knocks, incisions and squashing.  
All operations inside the appliance must be performed with  
the necessary caution in order to avoid abrupt contact with  
sharp parts.  
Electrocution caused by contact with live wires which have been  
installed incorrectly.  
Damage to the appliance caused by improper operating  
conditions.  
Use suitable manual tools and equipment (make sure in  
particular that the tool is not worn out and that its handle  
is fixed properly); use them correctly and make sure they do  
not fall from a height. Replace them once you have finished  
using them.  
Personal injury from falling splinters or fragments, inhalation of  
dust, shocks, cuts, pricks and abrasions.  
Personal injury caused by cuts, puncture wounds and abrasions.  
Reset all the safety and control functions affected by any  
work performed on the appliance and make sure they  
operate correctly before restarting the appliance.  
Explosions, fires or asphyxiation caused by gas leaks or an  
incorrect flue gas exhaust.  
Damage or shutdown of the appliance caused by out-of-control  
operation.  
Before handling, empty all components that may contain hot  
Damage to the appliance or surrounding objects caused by  
falling splinters, knocks and incisions.  
Use electrical equipment suitable for its intended use  
(in particular, make sure that the power supply cable  
and plug are intact and that the parts featuring rotary or  
reciprocating motions are fastened correctly); use this  
equipment correctly; do not obstruct passageways with the  
power supply cable, make sure no equipment could fall from  
a height. Disconnect it and replace it safely after use.  
Personal injury caused by falling splinters or fragments,  
inhalation of dust, knocks, cuts, puncture wounds, abrasions,  
noise and vibration.  
Damage to the appliance or surrounding objects caused by  
falling splinters, knocks and incisions.  
Make sure any portable ladders are positioned securely, that  
they are suitably strong and that the steps are intact and not  
slippery and do not wobble when someone climbs them.  
Ensure someone provides supervision at all times.  
water, carrying out any bleeding if necessary.  
Personal injury caused by burns.  
Descale the components, in accordance with the instructions  
provided on the safety data sheet of the product used,  
airing the room, wearing protective clothing, avoid  
mixing different products, and protect the appliance and  
surrounding objects.  
Personal injury caused by acidic substances coming into contact  
with skin or eyes; inhaling or swallowing harmful chemical  
agents.  
Damage to the appliance or surrounding objects due to  
corrosion caused by acidic substances.  
If you detect a smell of burning or smoke, keep clear of the  
appliance, disconnect it from the electricity supply, open all  
windows and contact the technician.  
Personal injury caused by falling from  
(stepladders shutting accidentally).  
a
height or cuts  
Make sure any rolling ladders are positioned securely, that  
they are suitably strong, that the steps are intact and not  
slippery and that the ladders are fitted with handrails on  
either side of the ladder and parapets on the landing.  
Personal injury caused by falling from a height.  
Personal injury caused by burns, smoke inhalation, asphyxiation  
5
product description  
Control panel  
E-COMBI  
1
60°  
70°  
50°  
80°  
40°  
90°  
10  
2
3
9
8
on/off  
ꢂꢃ  
ꢂꢁ  
7
6
ꢂꢀ  
ꢂꢉ  
I
ꢀꢂ  
4
5
ꢀ ꢆ  
O
ꢀ ꢄ  
ꢀ ꢀ  
ꢀ ꢃ  
ꢀ ꢁ  
E-SYSTEM  
1
60°  
70°  
50°  
80°  
40°  
90°  
10  
2
3
9
8
on/off  
4
5
Legend :  
1. Green indicator : CH temperature and error indicator  
2. ON/OFF button  
3. Green indicator : ON/OFF  
4. Pressure gauge  
5. Winter / Summer switch - Heating temperature regulation knob  
6. Domestic Hot Water adjustment knob (E-Combi models)  
7. Time clock (E-Combi models)  
8. Green indicator : flame ON  
Red indicator : lockout light  
9. Yellow indicator : flashing error light  
10. RESET button  
6
product description  
Overall view  
E-COMBI  
E-SYSTEM  
1
22  
21  
1
2
22  
21  
2
3
3
4
20  
19  
20  
19  
4
18  
17  
18  
17  
5
6
5
6
7
7
8
16  
14  
12  
16  
15  
14  
9
9
10  
13  
12  
10  
11  
11  
1. Flue connector  
2. Manual air vent  
3. Burner  
13. D.H.W. Flow switch  
14. Circulation pump with auto air vent  
15. Diverter valve  
4. Detection electrode  
5. C.H. Return temperature probe  
6. C.H. Flow temperature probe  
7. Gas valve  
8. Secondary heat exchanger  
9. Trap  
16. Low water pressure switch  
17. Silencer (according to model)  
18. Modulating fan  
19. Ignition electrodes  
20. Ignitor  
21. Thermal fuse  
10. C.H. pressure relief valve  
11. Electrical box  
22. Combustion analysis test point  
12. C.H. circuit filter  
7
product description  
Minimum clearances  
Overall Dimensions  
In order to allow easy access to the boiler for maintenance operations,  
the boiler must be installed in accordance with the clearances stated  
to the left (opposite).  
E-COMBI  
200  
120  
200  
120  
180  
5
5
450  
150  
315 mod. 24  
385 mod. 30/35  
65 67 67 65  
E-SYSTEM  
200  
120  
200  
120  
180  
150  
315 mod. 24  
385 mod. 30  
132  
132  
A. Central Heating Flow  
B. Domestic Hot Water Outlet  
C. Gas Inlet  
D. Domestic Cold Water Inlet  
E. Central Heating Return  
8
product description  
Technical Data  
Model E-COMBI  
24  
30  
38  
CE Certification (pin)  
0085BR0347  
Boiler type  
B23-B33-C13-C33-C43-C53-C83  
Max/min nominal calorific flow rate (Pci)  
Max/min nominal calorific flow rate (Pcs)  
Qn  
Qn  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
%
22.0/5.5  
28.0/6.5  
31.1/7.2  
30.0/6.5  
33.3/7.2  
27.4/6.2  
29.5/6.9  
30.0/6.0  
97.9  
31.0/7.5  
24.4/6.1  
25.0/5.5  
27.8/6.1  
21.6/5.2  
23.5/5.8  
25.0/5.0  
97.9  
34.4/8.3  
38.0/7.5  
42.2/8.3  
30.3/7.3  
33.1/8.0  
38.9/7.1  
98.0  
Domestic hot water max/min nominal calorific flow rate (Pci)  
Domestic hot water max/min nominal calorific flow rate (Pcs)  
Qn  
Qn  
Max/min power output (80°C-60°C)  
Pn  
Pn  
Pn  
Max/min power output (50°C-30°C)  
Domestic hot water max/min power output  
Combustion efficiency (of flue gas)  
Nominal calorific flow rate efficiency (60/80°C) Hi/Hs  
%
98.0/88.2  
107.0/96.4  
108.0/97.3  
101.0/90.9  
95.0/85.5  
98.0/88.2  
105.3/94.8  
110.3/99.3  
98.2/88.4  
95.6/86.1  
97.6/87.9  
106.9/96.3  
107.2/96.5  
103.1/92.8  
96.8/87.2  
Nominal calorific flow rate efficiency (30/50°C) (condensation) Hi/Hs  
Efficiency at 30% at 30°C (condensation) Hi/Hs  
Efficiency at 30% at 47°C Hi/Hs  
%
%
%
Minimum calorific flow rate efficiency (60/80°C) Hi/Hs  
Efficiency rating (dir. 92/42/EEC)  
Sedbuk Band Rating  
%
stars  
band  
%
****  
A / 90.3  
0.2  
****  
A / 90.1  
0.1  
****  
A / 90,1  
0.1  
Loss when stopped (ΔT = 50°C)  
Loss of burner gas when operating  
Available air pressure  
%
2.1  
2.1  
2.0  
Pa  
137  
5
141  
5
132  
5
NoX class  
class  
°C  
Flue gas temperature (G20) (80°C-60°C)  
CO2 content (G20) (80°C-60°C)  
63  
63  
63  
%
9.0  
9.0  
9.6  
CO content (0%O2) (80°C-60°C)  
ppm  
%
< 100  
4.5  
< 100  
4.5  
< 125  
3,5  
O2 content (G20) (80°C-60°C)  
Maximum flue gas flow (G20) (80°C-60°C)  
Excess air (80°C-60°C)  
Kg/h  
%
41.2  
27  
49.4  
27  
59.2  
20  
Expansion vessel inflation pressure  
Maximum heating pressure  
bar  
bar  
L
1
1
1
3
3
3
Expansion vessel capacity  
6.5  
6.5  
6.5  
Maximum water capacity with in the appliance (75°C-35°C)  
Min/max heating temperature (high temperature range)  
Domestic hot water max/min temperature  
Specific flow rate of domestic hot water (ΔT=30°C)  
Quantity of hot water ΔT=25°C  
L
100/300  
35/82  
36/60  
12.0  
14.4  
10.3  
***  
100/300  
35/82  
36/60  
15.0  
18.0  
12.9  
***  
100/300  
35/82  
36/60  
18.2  
21.8  
15.6  
***  
°C  
°C  
l/mn  
l/mn  
l/mn  
stars  
l/mn  
bar  
V/Hz  
W
Quantity of hot water ΔT=35°C  
Hot water comfort rating (EN13203)  
Hot water minimum flow rate  
< 2  
< 2  
< 2  
Domestic hot water max/min pressure  
Power supply frequency/voltage  
Total electrical power absorbed  
7/0.3  
230/50  
114  
+5  
7/0.3  
230/50  
115  
+5  
7/0.3  
230/50  
150  
+5  
Minimum ambient temperature for use  
Protection level for the electrical appliance  
Weight  
°C  
PI  
X5D  
32  
X5D  
35  
X5D  
35,5  
kg  
9
product description  
Model E-SYSTEM  
CE Certification (pin)  
Boiler type  
24  
30  
0085BR0347  
B23-B33-C13-C33-C43-C53-C83  
Max/min nominal calorific flow rate (Pci)  
Qn  
Qn  
kW  
kW  
22.0/5.5  
24.4/6.1  
28.0/6.5  
31.1/7.2  
Max/min nominal calorific flow rate (Pcs)  
Max/min power output (80°C-60°C)  
Max/min power output (50°C-30°C)  
Pn  
Pn  
kW  
kW  
21.6/5.2  
23.5/5.8  
27.4/6.2  
29.5/6.9  
Combustion efficiency (of flue gas)  
%
%
97.9  
97.9  
Nominal calorific flow rate efficiency (60/80°C) Hi/Hs  
98.0/88.2  
107.0/96.4  
108.0/97.3  
101.0/90.9  
95.0/85.5  
98.0/88.2  
105.3/94.8  
110.3/99.3  
98.2/88.4  
95.6/86.1  
Nominal calorific flow rate efficiency (30/50°C) (condensation) Hi/Hs  
Efficiency at 30% at 30°C (condensation) Hi/Hs  
Efficiency at 30% at 47°C Hi/Hs  
%
%
%
Minimum calorific flow rate efficiency (60/80°C) Hi/Hs  
Efficiency rating (dir. 92/42/EEC)  
%
stars  
band  
%
****  
A / 90.3  
0.2  
****  
A / 90.1  
0.1  
Sedbuk Band Rating  
Loss when stopped (ΔT = 50°C)  
Loss of burner gas when operating  
Available air pressure  
%
2.1  
2.1  
Pa  
137  
5
141  
5
NoX class  
class  
°C  
Flue gas temperature (G20) (80°C-60°C)  
CO2 content (G20) (80°C-60°C)  
63  
63  
%
9.0  
9.0  
CO content (0%O2) (80°C-60°C)  
ppm  
%
< 100  
4.5  
< 100  
4.5  
O2 content (G20) (80°C-60°C)  
Maximum flue gas flow (G20) (80°C-60°C)  
Excess air (80°C-60°C)  
Kg/h  
%
41.2  
27  
49.4  
27  
Expansion vessel inflation pressure  
Maximum heating pressure  
bar  
bar  
L
1
1
3
3
Expansion vessel capacity  
6.5  
6.5  
Maximum water capacity with in the appliance (75°C-35°C)  
Min/max heating temperature (high temperature range)  
Domestic hot water max/min temperature  
L
100/300  
35/82  
36/60  
100/300  
35/82  
36/60  
°C  
°C  
Power supply frequency/voltage  
Total electrical power absorbed  
Minimum ambient temperature for use  
Protection level for the electrical appliance  
Weight  
V/Hz  
W
230/50  
114  
+5  
230/50  
115  
+5  
°C  
PI  
X5D  
32  
X5D  
35  
kg  
10  
installation  
Flue  
Reference Standards  
Detailed information on flue assembly can be found in the  
Connecting the Flue” section.  
In the United Kingdom, the installation and initial start-up of the  
boiler must be by a Gas Safe registered installer in accordance with  
the installation standards currently in effect, as well as with any and  
all local health and safety standards i.e. Gas Safe.  
In the Republic of Ireland the installation and initial start-up of the  
appliance must be carried out by a Competent Person in accordance  
with the current edition of I.S.813Domestic Gas Installationsand the  
current Building Regulations, reference should also be made to the  
current ETCI rules for electrical installation.  
The installation of this appliance must be in accordance with the  
relevant requirements of the Local Building Regulations, the current  
I.E.E. Wiring Regulations, the by-laws of the local authority, in Scotland,  
in accordance with the Building Standards (Scotland) Regulation and  
Health and Safety document No. 635, “Electricity at Work Regulations  
1989and in the Republic of Ireland with the current edition of I.S. 813  
and the Local Building Regulations (IE).  
The boiler must be installed so that the flue terminal is exposed to the  
free passage of external air at all times and must not be installed in  
a place likely to cause nuisance. It must not be allowed to discharge  
into another room or space such as an outhouse or closed lean-to.  
Condensing boilers have a tendency to form a plume of water vapour  
from the flue terminal due to the low temperature of the flue gasses.  
The terminal should therefore be located with due regard for the  
damage or discolouration that may occur to building within the  
vicinity and consideration must also be given to adjacent boundaries,  
openable windows the min acceptable clearances are shown  
opposite.  
NOTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY TO CAUSE A NUISANCE AND  
POSITIONED TO ENSURE THAT PRODUCTS OF COMBUSTION DO NOT DISCHARGE ACROSS  
A BOUNDARY  
C.O.S.H.H.  
Materials used in the manufacture of this appliance are non-hazardous  
and no special precautions are required when servicing.  
It may be necessary to protect the terminal with a guard, if this is the  
case it will be necessary to purchase a stainless steel terminal guard.  
Reference should be made to the Building Regulations for guidance.  
Codes of Practice  
Installation should also comply with the following British Standards  
Code of Practice:  
BS 7593:1992 Treatment of water in domestic hot water central  
heating systems  
Ventilation  
The room in which the boiler is installed does not require specific  
ventilation. If the boiler is installed in a cupboard or compartment  
ventilation is not required for cooling purposes.  
BS 5546:1990 Installation of hot water supplies for domestic  
purposes  
BS 5440-1:2008 Flues  
Gas Supply  
The gas installation and tightness testing must be in accordance with  
the requirements of BS6891. Ensure that the pipe size is adequate for  
demand including other gas appliances on the same supply.  
Electrical Supply  
BS 5440-2:2009 Air supply  
BS 5449:1990 Forced ciculation hot water systems  
BS 6798:2009 Installation of gas fired hot water boilers of rated  
input not exceeding 70kW  
BS 6891:1989 Installation of low pressure gas pipes up to 28mm  
BS 7671:2001 IEE Wiring Regulations  
BS 4814:1990 Specification for expansion vessels  
BS 5482:1994 Installation of L.P.G.  
Domestic heating compliance guide  
and in the Republic of Ireland in accordancce with the following  
codes of practice:  
The appliance requires an earthed 230V - 50 Hz supply and must be in  
accordance with current I.E.E. regulations.  
It must also be possible to be able to completely isolate the appliance  
electrically.  
Connection should be via a 3 amp double pole fused isolating switch  
with contact separation of at least 3mm on both poles.  
Alternatively, a fused 3 amp, 3 pin plug and unswitched socket may be  
used, provided it is not used in a room containing a bath or shower, it.  
It should only supply the appliance.  
I.S. 813  
Domestic Gas Installations  
Water Supply  
The boiler is suitable for sealed systems only. The maximum working  
pressure for the appliance is 6 bar. All fittings and pipework for the  
appliance should be of the same standard. If there is a possibility of  
the incoming mains pressure exceeding 6 bar, particularly at night,  
then a suitable pressure limiting valve must be fitted.  
The boiler is designed to provide hot water on demand to multiple  
outlets within the property. If there is a requirement for greater  
demands, for example if the boiler has several bathrooms and  
cloakrooms, a vented or unvented hot water storage system may be  
used.  
Avoid installing the boiler where the air inlet can be polluted by  
chemical products such as chlorine (swimming pool area), or ammonia  
(hair dresser), or alkalin products (launderette).  
Showers  
Any shower valves used with the appliance should be of a thermostatic  
or pressure balanced type.  
Refer to the shower manufacturer for performance guidance and  
suitability.  
11  
installation  
Flushing and Water Treatment  
Location  
The boiler is equipped with a stainless steel heat exchanger.  
The detailed recommendations for water treatment are given in BS  
7593:1992 (Treatment of water in domestic hot water central heating  
systems); the following notes are given for general guidance.  
If the boiler is installed on an existing system, any unsuitable additives  
must be removed.  
The boiler can be installed on any suitable internal wall (suitable  
sound proofing may be required when installing onto a stud partition  
wall). Provision must be made to allow for the correct routing of the  
flue and siting of the terminal to allow the safe and efficient removal  
of the flue products.  
A compartment or cupboard may be used provided that it has been  
built or modified for this purpose.  
It is not necessary to provide permanent ventilation for cooling  
purposes. Detailed recommendations are given in BS 5440 Part 2.  
If it is proposed that it is to be installed in a timber framed building  
then reference should be made to British Gas Document DM2, IGE/  
UP/7 or advice sought from Gas Safe.  
Under no circumstances should the boiler be fired before the system  
has been thoroughly flushed; the flushing procedure must be in line  
with BS 7593:1992.  
We highly recommend the use of a flushing detergent appropriate for  
the metals used in the circuit. These include cleansers produced by  
Fernox BetzDearbon, whose function is to disolve any foreign matter  
that may be in the system.  
In hard water areas or where large quantities of water are in the  
system the treatment of water to prevent premature scaling of the  
main exchanger is necessary.  
The formation of scale heat compromises the efficiency of the thermic  
exchanger because small areas of scale cause a high increase of the  
temperature of the metallic walls and therefore add to the thermal  
stress of the heat exchanger.  
Where a room sealed appliance is installed in a room containing  
a bath or shower, the appliance and any electrical switch or  
appliance control, utilising mains electricity should be situated  
specifically in accordance with current IEE Wiring Regulations.  
For unusual locations, special procedures may be necessary. BS  
6798:2009 gives detailed guidance on this aspect.  
Demineralised water is more aggressive so in this situation it is  
necessary to treat the water with an appropriate corrosion inhibitor.  
Any treatment of water by additives in the system for frost protection  
or for corrosion inhibition has to be absolutely suitable for all metals  
used in the circuit.  
The use of a corrosion inhibitor in the sysem such as Fernox MB-  
1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is  
recommended to prevent corrosion (sludge) damaging the boiler and  
system.  
If anti-freeze substances are to be used in the system, check carefully  
that they are compatible with the metals used in the circuit.  
ARISTON suggests the use of suitable anti-freeze products such as  
Fernox ALPHI 11, which will prevent rust and incrustation taking place.  
Periodicaly check the pH balance of the water/anti-freeze mixture of  
the boiler circuit and replace it when the amount measured is out of  
the range stipulated by the manufacturer (7 < pH < 8).  
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE  
In under-floor systems, the use of plastic pipes without protection  
against penetration of oxygen through the walls can cause corrosion  
of the systems metal parts (metal piping, boiler etc), through the  
formation of oxides and bacterial agents.  
To prevent this problem it is necessary to use pipes with an “oxygen  
proof barrier, in accordance with standards DIN 4726/4729.  
If pipes of this kind are not used, keep the system separate by  
installing heat exchangers of those with a specific system water  
treatment.  
IMPORTANT  
Failure carry out the water treatment procedure will invalidate  
the appliance guarantee.  
System Controls  
The boiler is electrically controlled and is suitable for most modern  
electronic time and temperature controls. The addition of such  
external controls can be beneficial to the efficient operation of the  
system. The boiler connections for external controls are 12V DC and  
so only controls of 12V DC that have voltage free contacts should be  
used. (page 25).  
ARISTON supply a range of wired and wireless system controls.  
Contact your supplier for more details.  
12  
installation  
Condensate Discharge  
2. External termination of condensate drainage pipe via internal  
discharge branch (e.g. sink waste) and condensate trap.  
The condensate discharge hose from the boiler must have a  
continuous fall of 2.5o and must be inserted by at least 50mm into  
a suitable acid resistant pipe - e.g. plastic waste or overflow pipe.  
The condensate discharge pipe must have a minimum diameter of  
22mm, must have a continuous fall and preferably be installed and  
terminated to prevent freezing.  
The discharge pipe must be terminated in a suitable position:  
i) Connecting into an internal soil stack (at least 450mm above the  
invert of the stack). A trap giving a water seal of at least 75mm  
must be incorporated into the pipe run, there also must be an air  
beak upstream of the trap.  
trap  
ii) Connecting into the waste system of the building such as a  
washing maching or sink trap. The connection must be upstream  
of the washing machine/sink. If the connection is downstream of  
the waste trap then an additional trap giving a minimum water  
seal of 75mm and an air break must be incorporated in the pipe  
run, as above.  
iii) Terminating into a gully, below the grid level but above the water  
level  
iv) Into a soakaway  
Note: If any condensate pipework is to be installed externally then  
it should be kept to a minimum and be insulated with a waterproof  
insulation and have a continuous fall. The total length of external  
pipe used should not exceed 3 metres.  
3. External termination of condensate drainage pipe via internal  
discharge branch (e.g. sink waste - proprietary fitting).  
Some examples of the type of condensate terminations can be found  
below.  
1. Internal termination of condensate drainage pipe to internal  
stack.  
trap  
4. External termination of condensate drainage pipe via condensate  
trap  
13  
installation  
Installing the Boiler  
Connecting the boiler to the system  
- Remove the boiler casing as described on page 16  
- Remove the caps and connect the valves to the boiler using the  
washers provided  
- 4 x fibre washers for the CH flow and return, cold water inlet and hot  
water outlet connections  
Please check that you are familiar with the installation requirement  
before commencing work (pages 7 - 13).  
The installation accessories described in the following list are included  
in the boiler packaging:  
-
-
Hanging bracket  
A paper template (showing the dimensions of the boiler with 5  
mm side clearances)  
Connection valves (compression)  
Washers  
Filling loop  
Installation, Servicing and Operating Instructions  
Flue gasket  
E-COMBI  
-
-
-
-
-
Note: Connections viewed from behind boiler  
E-SYSTEM  
Method of positioning the boiler on the wall  
The paper template can be used to ensure the correct positioning of  
kitchen cabinets etc.  
The paper template has to be fixed to the wall and used to locate the  
position of the hanging bracket and the centre for the flue hole.  
Drill and plug the wall and secure the hanging bracket using the  
screws provided ensure the hanging bracket is level. Remove the  
boiler from its packaging and remove the front casing panel.  
Place the boiler on the hanging bracket.  
Note: Connections viewed from behind boiler  
NOTE: THE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE WALL SURFACE.  
14  
installation  
Safety Valve Discharge and Condense Outlet  
Gas connection  
The pressure relief valve pipe is made of copper. It should terminate  
below the boiler safely outside the premises. Care should be taken  
that it does not terminate over an entrance or window or where a  
discharge of heated water could endanger occupants or passers by.  
Make sure, using the labels on the packaging and the data plate on  
the appliance itself, that the boiler is in the correct country and that  
the gas category for which the boiler was designed corresponds to  
one of the categories available in the country where it will be used.  
The gas supply piping must be created and measured out in  
compliance with specific legal requirements and in accordance with  
the maximum power of the boiler; you should also make sure that the  
shut-off valve is the right size and that it is connected correctly.  
Check that the supplied gas corresponds to the type of gas for which  
the boiler was designed (see the data plate located on the appliance  
itself).  
Warning !  
Do not apply heat to the copper safety valve outlet pipe whilst it  
is connected to the 3 bar safety relief valve.  
Fill the central heating and DHW system and bleed air from the system  
as described in the Commissioning instructions (page 30).  
The system should be carefully checked for leaks, as frequent refilling  
could cause premature system corrosion or unnecessary scaling of  
the heat exchanger. The pipe from the trap should be connected to a  
drain as described in the relevant regulations.  
It is also important to check that the pressure of the gas (methane  
or LPG) you will be using to feed the boiler is suitable, because if it  
is insufficient the power may be reduced, causing inconvenience for  
the user.  
Pay special attention not to bend the condensate drain pipe in such  
a way as to interrupt the flow. Please only use drain pipe material  
compatible with condensate products (refer to BS 6798:2009).  
The condensate flow can reach 2 litres/hour because of the acidity of  
the condensate products (Ph close to 2), take care before operation.  
See page 13 for condensate discharge options.  
Water connection  
The illustration below shows the connections for the water and gas  
attachments of the boiler. See valves configuration on page 14.  
Check that the maximum water mains pressure does not exceed 6 bar;  
if it does, a pressure reducing valve must be installed.  
For the measuring of the pipes and of the heating bodies in the  
heating system, the residual head value should be calculated as a  
function of the requested flow rate, in accordance with the values  
shown in the circulation pump graph (page 16).  
A
A
E-COMBI  
(ꢀ  
'ꢀ  
-
-
remove the 2 screws A from the  
transport bar  
dispose of the transport bar and  
reassemble the fixing screws.  
&ꢀ  
)ꢀ  
%ꢀ  
+ꢀ  
$ꢀ  
,ꢀ  
A. Central heating Flow  
B. Domestic Hot Water Outlet  
C. Gas Inlet  
D. Domestic Cold Water Inlet  
E. Central Heating Return  
F. Safety Valve Discharge  
H. Drain Valve  
I. Drain condensate  
E-SYSTEM  
(ꢀ  
*
&ꢀ  
)ꢀ  
,ꢀ  
+ꢀ  
$ꢀ  
* - Connection for Filling Loop  
15  
installation  
Instructions for opening the casing and performing an  
internal inspection  
Before performing any work on the boiler, first disconnect it from the  
electrical power supply using the external bipolar switch; removing  
the fuse and shutting off the gas cock.  
To access the inside of the boiler, the following is necessary:  
1. Remove the casing by unhooking it from the control panel (a)  
2. Loosen the two screws on the front casing (b), pull it forwards and  
unhook it from the upper pins (c)  
To calculate the size of the heating installation, refer to the "Available  
pressure" graph below.  
Graph representing the available circulation pump  
pressure ΔT20oC  
mbar  
500  
450  
400  
350  
3. Lower the control panel (d)  
30-38 kW  
300  
250  
200  
150  
100  
50  
4. Unhook the two clips on the combustion chamber panel and lift  
off (e).  
24 kW  
(a)  
0
0
100  
200  
300  
400  
500  
600  
700  
800  
900  
1000  
1100 1200  
l/h  
Before the equipment is used, for the first time the trap must  
(b)  
be filled with water. To do this, add approximately 1/4 litre of  
water via the flue outlet before fitting the flue system, or uns-  
crew the cap on the trap positioned underneath the boiler, fill  
it with water and refit it.  
Warning!  
Insufficient water in the trap can temporarily cause the flue  
gas to be expelled into the surrounding ambient air.  
(c)  
(d)  
G
E
D
C
F
(e)  
B
H
A
16  
installation  
Water circuit diagram  
E-SYSTEM  
E-COMBI  
1
1
19  
18  
19  
18  
2
3
2
3
17  
16  
17  
16  
15  
14  
15  
14  
6
7
7
13  
8
9
8
9
12  
11  
10  
11  
10  
$ꢀ  
&ꢀ  
(ꢀ  
$ꢀ  
%ꢀ  
&ꢀ  
'ꢀ (ꢀ  
1. Manual air vent  
2. Burner  
3. Detection electrode  
4. C.H. flow temperature probe  
5. C.H. return temperature probe  
6. Secondary heat exchanger  
7. C.H. pressure relief valve  
8. By-pass  
9. Drain valve  
10. Condensate trap  
11. C.H. circuit filter  
12. D.H.W. Flow switch  
13. Diverter valve  
14. Low water pres switch  
15. Circulation pump  
16. Expansion vessel  
17. Modulating fan  
18. Ignition electrodes  
19. Thermal fuse  
17  
installation  
Connecting the Flue  
Flue System  
The provision for satisfactory flue termination must be made as  
described in BS 5440-1.  
The appliance must be installed so that the flue terminal is exposed  
to outdoor air.  
The terminal must not discharge into another room or space such as  
an outhouse or lean-to.  
It is important that the position of the terminal allows a free passage  
of air across it at all times.  
The terminal should be located with due regard for the damage or  
discolouration that might occur on buildings in the vicinity, it must  
also be located in a place not likely to cause nuisance.  
In cold or humid weather water vapour may condense on leaving the  
flue terminal.  
The effect of such “steamingmust be considered.  
If the terminal is less than 2 metres above a balcony, above ground or  
above a flat roof to which people have access, then a suitable stainless  
steel terminal guard must be fitted.  
Fig. 1  
The minimum acceptable spacing from the terminal to obstructions  
and ventilation openings are specified in Fig. 1.  
- A Directly below an opening, window, etc  
- B Horizontally to an opening, window, etc  
- C Below gutters, soils pipes or drain pipes  
- D Below eaves  
- E From vertical drain pipe or soil pipe  
- F From internal or external corner  
- G Above ground, roof or balcony level  
- H From a surface facing the terminal  
- I From a terminal facing a terminal  
- J Vertically from a terminal on the same wall  
- K Horizontally from an terminal on the same wall  
- L Fixed by vertical flue terminal  
300 mm  
300 mm  
75 mm  
200 mm  
75 mm  
300 mm  
300 mm  
600 mm  
1200 mm  
1500 mm  
300 mm  
Where 2 or more vertical fanned draught chimney configurations  
teminate in close proximity at the same height they shall be separated  
by at least 300mm. Where any 1 vertical outlet is more than 300mm  
above the other, then they shall be separated by at least 1500mm.  
See table  
180  
118 mm  
See table on page 22  
Fig. 2  
Warning  
Important  
Ensure that the flue is not blocked.  
Ensure that the flue is supported and assembled in accordance with  
these instructions.  
The exhaust gas ducts must not be in contact with or close to  
inflammable material and must not pass through building structures  
or walls made of inflammable material.  
When replacing an old appliance, the flue system must be changed.  
18  
installation  
Fitting the Coaxial Flue  
(Ø 60 / 100 Horizontal)  
Fig. 3  
Contents:  
1x Silicone O-Ring (60mm)  
1x Elbow (90°)  
2x Wall Seals (Internal & External)  
1x Flue Pipe including Terminal (1 metre - 60/100)  
2x Flue Clamps  
Installation without extension  
4x Screws  
2x Seals  
Level  
Once the boiler has been positioned on the wall, fit the rubber flue  
seal into the internal flue turret (see diagram opposite),  
insert the elbow into the socket and rotate to the required position.  
Note: It is possible to rotate the elbow 360° on its vertical axis.  
150 mm  
Using the flue clamp, seals and screws supplied (Fig 4) secure the  
elbow to the boiler.  
Installation with extension  
The 1 metre horizontal flue kit (3318073) supplied is suitable for an  
exact X dimension of 753mm.  
slope
Level  
Measure the distance from the face of the external wall to the face  
of the flue elbow (X - Fig 2), this figure must now be subtracted from  
753mm, you now have the total amount to be cut from the plain end  
of the flue.  
Slope min 1° per metre  
max 3° per metre (1° = 17mm)  
Draw a circle around the outer flue and cut the flue to the required  
length taking care not to cut the inner flue, next cut the inner  
flue ensuring that the length between the inner and outer flue is  
maintained. (Fig 4).  
Clamp  
Fig. 4  
e.g.  
X = 555mm  
753-555 = 198mm (Length to be cut from the plain end of the flue).  
Once cut to the required length, ensure that the flue is free from burrs  
and reassemble the flue. If fitting the flue from inside of the building  
attach the grey outer wall seal to the flue terminal and push the flue  
through the hole, once the wall seal has passed through the hole, pull  
the flue back until the seal is flush with the wall. Alternatively, the  
flue can be installed from outside of the building, the grey outer seal  
being fitted last.  
Screws  
Seal  
Should the flue require extending, the flue connections are push fit,  
however, one flue bracket should be used to secure each metre of flue.  
Note: See table for maximum and minimum flue runs.  
In the event that extension pieces need to be shortened, they must  
only be cut at the male end and it must be ensured that the inner and  
outer flue remain flush.  
19  
installation  
Fitting the 5” Flue (Ø 80 / 125 Horizontal/vertical)  
Once the boiler has been positioned on the wall, it is necessary to in-  
sert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical flue  
runs into the boiler flue socket (not supplied with flue kit - Part No  
3318095).  
Push the adaptor onto the boiler’s flue connection, grease the seals  
then add extensions or elbows as required, secure the adaptor, using  
the clamp and screws provided.  
Useable length of  
vertical flue 575 mm*  
Total length of  
vertical kit 1240 mm  
To fit extensions or elbows it is first necessary to ensure that the lip  
seal is fitted correctly into the inner flue, once verified, it is simply ne-  
cessary to push them together, no clamps are necessary to secure the  
flue components.  
180 mm  
Before proceeding to fit the flue, ensure that the maximum flue leng-  
th has not been exceeded (see the tables) and that all elbows and  
bends have been taken into consideration. For each additional 90° el-  
bow 1 metre must be subtracted from the maximum flue length, and  
for each 45° 0.5 metres must be subtracted from the maximum flue  
length (the height of the vertical adaptor and a 45° bend can be seen  
in Fig.6 and a 90° bend in Fig. 7).  
Note: DO NOT cut the vertical flue kit.  
Fig. 5  
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)  
Note: See table for maximum and minimum flue runs.  
Contents:  
1x Silicone O-Ring (60mm)  
1x Conical Adaptor (60/100mm)  
1x Vertical Flue Kit (80/125mm)  
3x Screws  
The vertical flue kit is supplied with a specially designed weather  
proof terminal fitted, which can be used either with a flat roof or a  
pitched roof.  
The vertical flue kits useable lengths with the pitched roof flashings  
are indicated in Fig. 7.  
Total length  
of Vertical Kit  
1355 mm  
Useable length  
of Vertical flue  
690 mm*  
180 mm  
Fig. 6  
Fig. 7  
20  
installation  
Before proceeding to fit the flue, ensure that the maximum flue  
length has not been exceeded (see the tables) and that all elbows and  
bends have been taken into consideration. For each additional 90°  
elbow 1 metre must be subtracted from the maximum flue length,  
and for each 45° 0.5 metres must be subtracted from the maximum  
flue length (the height of the vertical adaptor and a 45° bend can be  
seen in Fig. 8).  
Fitting the Twin Pipe (Ø80 / 80)  
Fig. 8a  
Note: See table for maximum and minimum flue runs.  
Fig. 8  
Where it is not possible to terminate the flue within the distance  
permitted for coaxial flues, the twin flue pipe can be used by fitting a  
special adaptor to the flue connector and using the aperture for the  
air intake located on top of the combustion chamber.  
Mark the position of the flue hole in the ceiling and/or roof (see Fig. 7  
for distance from wall to the centre of the flue).  
Cut a 130mm diameter hole through the ceiling and/or roof and fit  
the flashing plate to the roof.  
Always ensure that the flue is adequately supported, using one flue  
bracket per extension and avoiding low points. (ARISTON supply  
suitable clamps as Part No. 3318015).  
DO NOT cut the vertical flue kit.  
To connect the vertical flue kit directly to the boiler, place the vertical  
starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold  
and secure with the clamp, fit the vertical adaptor onto the vertical  
starter kit (Note: there is no need to use a clamp to secure this as it  
is a push fit connection), the vertical flue kit must then be inserted  
through the roof flashing, this will ensure that the correct clearance  
above the roof is provided as the terminal is a fixed height.  
To utilise the air intake it is necessary to:  
1) Take the air intake cover off the top of the appliance  
2) Assemble the air inlet adaptor - see fig. 8a  
The twin flue pipes can be fitted with or without additional elbows  
and need no clamps, simply ensure that the red o-ring is inserted in  
the female end of the flue pipe and push the extension piece fully  
into the previous section of flue pipe or elbow. Check that the o-ring  
is not dislodged when assembling the flue (greasing the seal will aid  
assembly).  
Should extensions be required, they are available in 1 metre (Part  
No. 3318077) and 500mm (Part No. 3318078) lengths. They must be  
connected directly to the vertical starter kit before connecting the  
adaptor to allow the vertical flue kit to be fitted. In the event that  
extension pieces need to be shortened, they must only be cut at the  
male end and it must be ensured that the inner and outer flue remain  
flush.  
When running the twin flue pipe vertically it can be converted back to  
coaxial flue to enable vertical termination with a coaxial kit by use the  
pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089).  
When using the vertical flue system, action must be taken to ensure  
that the flue is supported adequately to prevent the weight being  
transferred to the appliance. Use 1 flue bracket per extension.  
It is not possible to terminate concentrically horizontally. Termination  
is only possible with separate air and exhaust terminals.  
When the flue passes through a ceiling or wooden floor, there must  
be an air gap of 25mm between any part of the flue system and any  
combustible material. The use of a ceiling plate will facilitate this.  
Also when the flue passes from one room to another a fire stop must  
be fitted to prevent the passage of smoke or fire, irrespective of the  
structural material through which the flue passes.  
When siting the twin flue pipe, the air intake and exhaust terminals  
must terminate on the same wall, the centres of the terminals must  
be a minimum of 280 mm apart and the air intake must not be sited  
above the exhaust terminal (refer to Fig. 10). The air intake pipe can  
be run horizontally, however, the terminal and the final 1 metre of flue  
must be installed either horizontally or with a slight fall away from the  
boiler to avoid rain ingress.  
It is also strongly recommended that the air intake pipe run be  
constructed of insulated pipe to prevent condense forming on the  
outside of the tube.  
21  
installation  
The maximum permissible flue length for twin flue is  
dependent on the type of run used (see table below).  
180  
120  
Fig. 9  
For further information relating to flue runs not illustrated,  
please contact the Technical Department on 0870 241 8180.  
For coaxial systems, the maximum flue lengths listed in the  
table below take into account an elbow.  
For twin flue systems the maximum flue lengths listed in the  
table below includes the exhaust gas/air intake terminal.  
Type 5 outlets should respect the following instructions:  
1- Use the same ø 80 mm flue pipes for the air intakes and  
exhaust gas ducts.  
2- If you need to insert elbows in the air intake and exhaust  
gas ducts, you should consider for each one the equivalent  
length to be included in the calculation of developed  
length.  
Fig. 10  
AIR INTAKE MUST NOT BE  
FITTED ABOVE THE EXHAUST  
AIR INTAKE  
EXHAUST  
3- The exhaust gas duct should jut above the roof by at least  
0.5 m.  
4- The intake and exhaust gas ducts in Type C13 and C53  
must be installed on the same wall, or where the exhaust  
is vertical and the air intake horizontal, the terminals must  
be on the same side of the building.  
AIR INTAKE  
22  
installation  
Table of flue gas exhaust duct lengths  
Maximum Extension Exhaust-air (m)  
Diameter of pipe  
Type  
E-COMBI 24  
E-SYSTEM 24  
E-COMBI 30  
E-SYSTEM 30  
(mm)  
E-COMBI 38  
MIN  
MAX  
MIN  
MAX  
MIN  
MAX  
C13  
C33  
0,5  
12  
0,5  
12  
0,5  
0,5  
6
ø 60/100  
ø 80/125  
Coaxial System  
C13  
C33  
0,5  
36  
0,5  
36  
18  
S1 = S2  
0,5/0,5  
1 + S2  
S1 = S2  
0,5/0,5  
1 + S2  
S1 = S2  
0,5/0,5  
1 + S2  
C13  
C33  
ø 80/80  
ø 80/80  
36/36  
1/83  
48/48  
1/70  
18/18  
1/42  
Twin-pipe System  
C53  
1/0,5  
1/0,5  
1/0,5  
S1 = Air intake S2 = Flue gas exhaust  
S1 = S2 - Air intake and flue gas exhaust equal lengths  
S1 + S2 - Air intake and flue gas exhaust unequal lengths  
Type of air suction/flue gas exhaust ducting  
Combustion air intake from outside  
C13 Flue gas exhaust and air suction  
duct through external wall in  
the same range of pressure  
C33 Flue gas exhaust andair suction  
duct from outsidewithroof  
terminalin the same range of  
pressure  
C53 Flue gas exhaust leading  
outside and air suction duct  
through external wall not in the  
same range of pressure  
23  
installation  
WARNING  
Peripheral unit connection  
To access peripheral unit connections carry out the following steps:  
Before performing any work on the boiler, first disconnect it  
from the electrical power supply using the external bipolar  
switch and remove the fuse.  
-
-
-
-
Disconnect the boiler from the power supply  
Remove the casing by unhooking it from the instrument panel  
Rotate the control panel while pulling it forwards  
Unscrew the three screws on the back cover of the instrument  
panel  
Electrical connections  
For increased safety, ask a qualified technician to perform a thorough  
check of the electrical system.  
-
Unhook the right side clip and the right front clip; then lift the flap  
The manufacturer is not responsible for any damage caused by the  
lack of a suitable earthing system or by the malfunctioning of the  
electricity mains supply.  
Make sure that the system is able to withstand the maximum power  
used by the boiler (this is indicated on the appliance data plate).  
Check that the section of the wires is suitable and is not less 0.75 mm2  
The appliance must be connected to an efficient earthing system if it  
is to operate correctly.  
The following connections are located here:  
- the room thermostat 1.  
Caution!  
For the connection and positioning of the wires belonging  
to optional peripheral units, please refer to the installation  
manuals of these units.  
The power supply cable must be connected to a 230V-50Hz network,  
where the L-N poles and the earth connection are all respected.  
Important!  
In the event that the power supply cable has to be changed, replace it  
with one with the same specification.  
Power supply cable  
120  
H05V2V2-F  
140  
Important!  
The appliance is supplied with a fly-lead already connected,  
this must be connected to a 240V supply fused at 3 amp it  
must give complete electrical isolation of the appliance,  
by use of a fused double pole isolator having a contact  
separation of at least 3mm in all poles or alternatively  
by means of a 3A fused three pin plug and unswitched  
shuttered socket outlet both complying with BS1363.  
Theuseofmultiplugs, extensionleadsoradaptorsisstrictlyprohibited.  
It is strictly forbidden to use the piping from the hydraulic, heating  
and gas systems for the appliance earthing connection.  
The boiler is not protected against the effects caused by lightning. If  
the boiler fuses need to be replaced, use 2A rapid fuses.  
24  
installation  
Room Thermostat / Remote Clock Connection  
The boiler connections for external controls are 12V DC and so only  
controls of 12V DC that have voltage free contacts should be used.  
The boiler connections for external controls are 12V DC and so only  
controls of 12V DC that have voltage free contacts should be used.  
To connect a room thermostat, it is necessary to:  
1. Open the control panel  
2. Loosen the cable clamp using a screwdriver and insert the wires  
leading from the room thermostat  
3. Connect the wires to the terminals as indicated in the figure below,  
removing the link  
4. If a remote time clock is to be fitted, (using a volt free switching time  
clock) connect the switching wires from the time clock following  
points 1 - 3 above (Disconnect internal time clock)  
5. If using an external time clock and room thermostat, these must be  
connected in series as shown in diagram C, (Disconnect internal  
time clock)  
6. Ensure that they are well connected and not subject to stress when  
the control panel is closed  
NOTE: WHEN CONNECTING THE BOILER TO EXTERNAL CONTROLS, DO NOT RUN 240V  
CABLES FOR SWITCHING CIRCUITS (WHICH ARE LOW VOLTAGE) TOGETHER USE  
SEPERATE CABLES TO PREVENT INDUCED VOLTAGE ON THE LOW VOLTAGE CIRCUITS.  
Connector TA on Terminal block  
(low voltage switching)  
Connector TA on Terminal block  
(low voltage switching)  
Connector TA on Terminal block  
(low voltage switching)  
Note: y plan system switch 240v and are therefore not suitable  
system control systems unless a suitable relay is used to switch the  
low voltage control circuit.  
Do not connect 240v to the TA1 switching circuit. Connectiong 240v  
to the TA1 switching circuit will damage th P.C.B. and invalidate  
appliance warranty.  
25  
installation  
Electrical diagram  
For increased safety, ask a qualified technician to perform a thorough  
check of the electrical system.  
The manufacturer is not responsible for any damage caused by the  
lack of a suitable earthing system or by the malfunctioning of the  
electricity mains supply.  
2
3
4
1
C N 1 1  
1 6 C N  
2 4 C N  
1 2 C N  
Bk= Black  
Rd = Red  
Gr = Green  
Bl = Blue  
Br = Brown  
Wh = White  
Gry = Grey  
26  
commissioning  
S Plan Wiring Diagram  
Note: Y plan system not suitable. See notes on page 25  
27  
commissioning  
Initial preparation  
Filling of the DHW System (Combi only):  
Close all hot water draw off taps;  
Open the cold water inlet cock supplied with the connection kit;  
Slowly open each draw off tap and close them only when clear water,  
free of bubbles, is visible.  
At the time of commissioning, complete all relevant sections of  
the Benchmark Checklist located on the inside back pages of this  
document.  
ARISTON Thermo UK LTD Limited support the Benchmark  
initiative. On pages pages 53 and 54 of this manual the Benchmark  
Commissioning Checklist and Service interval Record can be  
found. It is important that this is completed in the presence of your  
customer, they are shown how to use it, and it is signed by them.  
Please instruct your customer that they must have this manual with  
them whenever they contact a service engineer or us.  
Preliminary electrical system checks to ensure electrical safety must  
be carried out by a competent person i.e. polarity, earth continuity,  
resistance to earth and short circuit.  
Gas Supply:  
Inspect the entire installation including the gas meter and test for  
tightness. The entire installation should be in accordance with the  
relevant standards. In GB this is BS 6891 and in IE this is the current  
edition of I.S.813.  
The connection on the the appliance is a 15 mm nut and olive  
located at the rear of the gas service cock.  
If the gas supply serves other appliances, ensure that an adequate  
supply is available both to the boiler and the other appliances when  
they are in use at the same time.  
Electricity supply  
- Check that the voltage and frequency of the electricity supply  
correspond to the data shown on the boiler data plate;  
- Make sure that the earthing connection is efficient.  
Pipe work must be of an adequate size.  
Pipes of less than 22 mm should not be used, final being 15 mm.  
Open the gas cock (supplied with the connection kit) to the  
appliance and check the gas connection on the appliance for leaks.  
Filling the Heating System:  
Water Treatment:  
Remove the front casing panel and lower the control panel as  
described on page 16).  
The boiler is equipped with a stainless steel heat exchanger.  
The detailed recommendations for water treatment are given in BS  
7593:1992 (Treatment of water in domestic hot water central heating  
systems); the following notes are given for general guidance;  
Open the central heating flow and return cocks supplied with the  
connection kit;  
Lift the cap on the automatic air release valve and leave open  
permanently;  
Close all air release valves on the central heating system;  
Gradually open the valves at the filling point (filling loop) until water  
is heard to flow, do not open fully;  
Open each air release tap starting with the lowest point and close  
them only when clear water free of air is visible;  
Purge the air from the pump by unscrewing the pump plug anti-  
clockwise, also manually rotate the pump shaft in the direction  
indicated by the pump label to ensure the pump is free;  
Refit the pump plug;  
If the boiler is installed on an existing system, any unsuitable  
additives must be removed;  
Under no circumstances should the boiler be fired before the system  
has been thoroughly flushed; the flushing procedure must be in line  
with BS7593:1992.  
Firstly fill the central heating system with the power off, and flush  
through cold, fill the central heating system again, adding a flushing  
detergent, run the boiler on central heating until it reaches its  
operating temperature and flush the system, refill the system with a  
suitable corrosion inhibitor,  
Continue filling the system until at least 1.5 bar registers on the  
pressure gauge;  
Inspect the system for water tightness and remedy any leaks  
discovered.  
NOTE: FAILURE TO CARRY OUT THE FLUSHING PROCEDURE WILL RESULT IN THE WARRANTY  
BECOMING VOID.  
IMPORTANT!  
MANUALLY VENT THE HEAT EXCHANGER AT THE MANUAL AIR VENT. FAILURE TO VENT  
ADEQUATELY MAY DAMAGE THE HEAT EXCHANGER (PAGE 7, LEGEND 2).  
28  
commissioning  
First ignition operation  
Date . . . . . . . . . . . .  
Installer . . . . . . . . . .  
1. Check the electrical supply.  
Complete . . . . . .  
2. Check the type of gas and  
change the gas if necessary.  
3. Check the gas tightness.  
Complete . . . . . .  
Complete . . . . . .  
6. Measure the gas inlet pressure.  
standing + warming pressure  
5. Check the exhaust flue.  
See page 18  
6. Fill the installation.  
See page 30  
Complete . . . . . .  
Complete . . . . . .  
Complete . . . . . .  
9. Set the heating power.  
See page 31  
7. Check the hydraulic water  
tightness.  
8. Spin the pump.  
Complete . . . . . .  
Complete . . . . . .  
Complete . . . . . .  
10. Set up heating controls  
Complete . . . . . .  
11. Balance the central heating  
circuit.  
12. Check the boiler in DHW mode  
(combi only)  
Complete . . . . . .  
Complete . . . . . .  
13. Adjust DHW flow rate on the  
boiler (if necessary).  
14. Analyse the combustion  
(see page 33)  
Complete . . . . . .  
15. Check the ionisation current.  
Complete . . . . . .  
Complete . . . . . .  
16. Explain to the end user the the  
boiler operation.  
17. At the time of commissioning, complete all relevant sections of the  
Benchmark Checklist located on the inside back pages of this document.  
Complete . . . . . .  
Complete . . . . . .  
29  
commissioning  
irst ignition  
1. Make sure that:  
60°  
70°  
50°  
80°  
40°  
90°  
-
-
The gas valve is closed;  
The electrical connection has been properly carried out. Make sure  
that the green/yellow earthing wire is connected to an efficient  
earthing system;  
2
8
-
-
Use a screwdriver to lift the cap on the automatic air relief valve;  
Switch on the boiler (by pressing the ON/OFF button), the green  
led 3 will illuminate indicating that the boiler is ready to operate.  
Turn the CH button 5 between min. and max position. The pump  
will start and the burner will attempt to light, after 7 seconds  
the boiler will lock out because there is no gas; the red Led 8  
illuminates.  
MIN  
MIN  
5
6
MAX  
Adjust maximum C.H. power  
MAX  
Adjust Soft Ignition  
60°  
70°  
50°  
80°  
40°  
90°  
Regulating the maximum central heating power & soft  
ignition  
on/off  
ꢂꢁ  
ꢂꢀ  
I
ꢀꢂ  
Regulate the maximum central heating power (between minimum  
and maximum) to adjust the central heating power and the soft  
ignition :  
ꢀ ꢇ  
ꢀ ꢆ  
O
ꢀ ꢄ  
ꢀ ꢀ  
ꢀ ꢃ  
ꢀ ꢂ  
ꢀ ꢁ  
Adjust the setting on the front panel  
1. Push ON/OFF button for 10 seconds, the red reset led blinks.  
2. Adjusting with the CH knob the maximum CH power between 0  
and 99 % (see table).  
3. Combi only adjusting with the DHW knob the soft ignition  
between 0 to 99% (see table). The percentage level is visualized  
by the green led.  
-
-
Bleed the air from the radiators;  
The flue should be suitable and free from any obstructions;  
2. Open the gas cock and check the connection seals, including the  
boiler connection joints, making sure that the meter does not  
detect any passage of gas. Eliminate any leaks.  
3. Unlock the boiler by pushing the reset button. The burner will  
light, if the first start fails repeat the operation until the burner  
lights.  
4. To store the new values of settings, it is enough to push ON/OFF  
button.  
IMPORTANT!!  
For E-SYSTEM boiler  
To adjust the Soft Ignition it is necessary remove the cover using a  
screwdriver, see fig. a, and alter the soft ignition by adjusting the  
potentiometer, see fig. b.  
Setting  
Regulating the central heating ignition delay  
fig. a  
fig. b  
on/off  
on/off  
Adjust the central heating ignition delay  
1. Push ON/OFF button for 10 seconds, the red reset led  
blinks.  
2. Pressing the RESET button, the green led blinks.  
3. Adjusting with the CH knob (Temporisation 0, 1, 2, 3, 4, 5, 6  
minutes see table).  
Green Leds  
Temperature indicator  
40 50 60 70 80 90 *  
= no led lit  
= lit  
TAC  
0 min  
1 min  
2 min  
3 min  
4 min  
5 min  
6 min  
Green Leds  
Temperature indicator  
40 50 60 70 80 90 *  
Max adjustable  
power and soft  
ignition  
= no led lit  
= lit  
0 to 39 %  
40 to 49 %  
50 to 59 %  
60 to 69 %  
70 to 79 %  
80 to 89 %  
90 to 99 %  
* This LED is red  
* This LED is red  
30  
commissioning  
Test function and combustion analysis  
The boiler has two pressure taps to measure the combustion gas  
temperature, the combustive air and the concentrations of O2 and CO2  
on the outside of the flue gas header.  
To access these pressure taps, unscrew the screw which holds the  
blanking cover and its seal together.  
50  
Only a 2.5 key  
must be used  
Minimum gas flow combustion analysis  
Activate the test function at minimum power in either heating or  
domestic hot water production.  
Wait for the boiler to stabilise before carrying out the combustion  
analyses. Check the CO2 value according to the table above.  
Important: do not remove silencer 17  
N.B. When the combustion chamber is open, the CO2 value drops  
by 0.3%.  
If the values taken differ from the table, adjust the gas valve following  
the procedure described below.  
Checking the gas setting  
To carry out analyses of combustion, the test function must be  
activated.  
To adjust the CO2 value, remove cap, adjust the CO2 content to 0.2 by  
turning setting screw 51 (4 mm allen key)  
Maximum gas flow combustion analysis  
Activate the test function at the maximum heating power, pushing  
for 5 seconds the RESET until the yellow led 9 blinks (also 60°C led is  
lit to indicate that Chimney is at max. CH absolute) The rotate the CH  
knob to the min., intermediate position or max position it’s possible  
to switch between min, max CH absolute and max DHW power  
(respectively the 40°C, 60°C and 80°C are lit to indicate the power  
level.  
- unscrew to lower the CO2 value  
- tighten to increase the CO2 value  
Set the content by turning the screw about a 1/4 of a turn then wait  
after each change for approximately 1 minute for the CO2 value to  
stabilise, then repeat.  
Once the settings and analyses are complete, exit test mode by  
pressing Reset and reposition the blanking cover and its seal correctly.  
The function is automatically deactivated after 10 minutes or by  
pressing the RESET button.  
Wait for the boiler to stabilise before carrying out the combustion  
analyses. Check the CO2 value according to the table below.  
Important: do not remove silencer 17  
N.B. When the front combustion chamber panel is open, the CO2  
value drops by 0.3%.  
CO2  
24  
30  
38  
maximum  
minimum  
CO2 (%)  
G20  
G31  
9.0 0.2  
10.7 0.2  
9.0 0.2  
10.0 0.2  
9.4 0.2  
10.6 0.2  
Only a 4 key must be used  
If the values taken differ from the table, adjust  
the gas valve following the procedure described  
below.  
24  
30  
38  
Adjust the CO2 content to  
0.2 by turning  
Gas setting  
G20  
G31  
G20  
G31  
G20  
G31  
setting screw 50 (2.5 mm allen key)  
lower Wobbe index  
15°C, 1013 mbar) (MJ/m3)  
gas valve restrictor(ø)  
- tighten to lower the CO2 value  
45.67 70.69 45.67 70.69 45.67 70.69  
- unscrew to increase the CO2 value  
Set the content by turning the screw about a  
1/4 of a turn then wait after each change for  
approximately 1 minute for the CO2 value to  
stabilise, then repeat.  
NO  
2.65  
2.33  
0.58  
3.80  
1.94  
1.71  
0.43  
NO  
3.17  
2.96  
0.69  
4.50  
2.33  
2.17  
0.50  
NO  
4.02  
3.28  
0.79  
5.25  
2.95  
2.41  
0.58  
max D.H.W  
max C.H.  
min  
gas flow max/min  
(15°C, 1013 mbar)  
(nat - m3/h) (GPL - kg/h)  
31  
boiler protection devices  
Boiler protection devices  
Important  
The boiler is protected from malfunctioning by means of internal  
checks performed by the electronic microprocessor P.C.B., which  
stops the boiler from operating if necessary.  
If this shutdown occurs frequently, contact an authorised  
Technical Service Centre for assistance. For safety reasons, the  
boiler will permit a maximum of 5 resets in 15 minutes (5 presses  
In the event of the boiler being shut off in this manner, the led code  
shows the type of shut-off and the reason behind it.  
There are two types of shut-off:  
of the  
button).  
Anti-frost Device.  
When the electrical supply is turned on the anti-frost function acts  
on the central heating flow temperature probe, independently from  
other safety devices.  
Safety shut-off  
This type of error is “volatile, which means that the boiler starts up  
again automatically as soon as the problem which caused the shut-off  
is removed; the yellow led 9 blinks and green CH temperature leds 1  
indicate the error code- see table below.  
If the primary circuit temperature is between 3°C and 8°C the  
pump will run (with the diverter valve switching between central  
heating and hot water every 1 minute) until the temperature  
reaches > 9°C.  
If the flow temperature remains between 3°C and 8°C the pump will  
continue to run for a maximum of 20 minutes unless a temperature  
above > 9°C is detected in the central heating flow, after this the  
burner will fire (heating position) until a temperature of > 30°C is  
detected.  
If the central heating flow temperature is < 3°C, the burner will fire  
(heating position) at minimum power until the temperature reaches  
> 30°C, the burner will go out.  
If lockout is caused by overheat the burner will not fire but the pump  
will continue to run (heating position).  
As soon as the cause of the shut-off disappears, the boiler starts up  
again and continues to operate normally.  
Note : In the event of insufficient water pressure inside the heating  
circuit, the boiler will perform a safety shut-o(yellow led 9 blinks - leds  
50-60 blink – see table). To re-pressurise the boiler, it will be necessary  
to connect the silver flexible hose supplied to the two isolating points  
underneath the boiler, once the hose is connected, open up both of  
the black quarter turn handles until the pressure reads 1.5 bar on the  
pressure gauge. If the pressure drops very frequently, there may be a  
water leak at some point in the system.  
The anti-frost device activates only when the boiler operating  
correctly :  
- the system pressure is correct;  
- the boiler is electrically powered;  
- there is a supply of gas.  
Shutdown  
This type of error is “non-volatile, which means that it is not removed  
automatically.  
The red led 8 light and green leds 1 indicate the error code- see table  
below.  
To restore normal operation press the  
panel.  
button on the control  
Table summarising error codes  
Green Leds  
Temperature indicator  
40 50 60 70 80 90 yellow red  
Note  
= flashing light  
= lit  
Reset  
Description  
Overheat  
X
X
Insufficient circulation  
Insufficient water pressure (request filling)  
C.H. Flow temp. probe circuit open / short circuit  
C.H. Return temp. probe circuit open / short circuit  
External sensor circuit open / short circuit  
Floor thermostat contact open  
Heating delivery probe problem  
Insufficient circulation  
X
EEPROM error  
Communication error  
Too many (> 5) resets in 15 minutes  
Main P.C.B. error  
Room sensor circuit open / short circuit  
No flame detected  
Flame detected with gas valve closed  
Flame lift  
X
X
X
1st Ignition Failed  
2nd Ignition Failed  
Flame cut-off  
Thermofuse open  
X
X
Fan speed error  
32  
maintenance  
Important  
liquid is added to the water in the heating system in order to avoid  
the need for repeated draining; when this liquid is used make sure it is  
compatible with the stainless steel used for the bodywork of the boiler.  
We recommend the use of anti-freeze products which contain  
PROPYLENE GLYCOLS as these inhibit corrosion and that they are  
used in conjunction with the anti-scaling and anti-corrosion function,  
in the quantities suggested by the manufacturer, at the mimimum  
temperature.  
Maintenance is an essential part of the safe and efficient operation of  
the boiler and ensures its durability. It should be performed according  
to the instructions given in current legislation. Perform combustion  
analysis regularly in order to check the operating efficiency of the  
boiler and to make sure the combustion is within the boundaries set  
by current legislation.  
Before beginning maintenance work:  
-
Disconnect the appliance from the electricity supply by turning  
the external bipolar switch to the “OFFposition;  
Remove the fuse;  
Close the gas valve and the central heating and domestic hot  
water system valves.  
Regularly check the pH level of the water/anti-freeze mix in the boiler  
circuit and replace it when the value measured is lower than the limit  
prescribed by the manufacturer.  
-
-
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE.  
The manufacturer will not be held liable for any damage caused by  
the appliance or the system due to the use of inappropriate anti-freeze  
substances or additives.  
After the work has been completed the initial settings will be restored.  
General comments  
It is recommended that the following inspections be carried out on the  
boiler at least once a year:  
Draining the domestic hot water system (E-COMBI)  
Every time there is a danger of freezing, the domestic hot water system  
must be drained as follows:  
1. Check the seals in the water part and, if necessary, replace the  
gaskets and restore the seal to perfect working order.  
2. Check the seals in the gas part and, if necessary, replace the  
gaskets and restore the seal to perfect working order.  
3. Visually check the overall condition of the boiler.  
4. Visually check the combustion and, if necessary, disassemble and  
clean the burner.  
-
-
-
Shut off the water mains inlet valve;  
Open all the hot and cold water taps;  
Empty the water from the lowest points of the system (where  
applicable).  
WARNING  
5. Following the inspection detailed in point “3, disassemble and  
clean the combustion chamber, if necessary.  
6. Following the inspection detailed in point “4, disassemble and  
clean the burner and injector, if necessary.  
7. Cleaning the primary heat exchanger  
8. Make sure the following heating safety devices are operating  
correctly:  
Before handling, empty all components which may contain hot water,  
performing bleeding where necessary.  
Descale the components in accordance with the instructions provided  
on the safety data leaflet supplied with the product used, make sure  
the room is well ventilated, wear protective clothing, avoid mixing  
different products, and protect the appliance and surrounding objects.  
Seal all openings used to take a gas pressure reading or to make any  
gas adjustments.  
- temperature limit safety device.  
9. Make sure that the following gas part safety devices are operating  
correctly:  
- absence of gas or flame safety device (ionisation).  
10. Check the efficiency of the domestic hot water production process  
(test the flow rate and temperature).  
Make sure that the nozzle is compatible with the supplied gas.  
If a smell of burning is detected or smoke is seen leaking from the  
appliance, or there is a smell of gas, disconnect it from the electricity  
supply, shut off the gas valve, open the windows and call for technical  
assistance.  
11. Perform a general inspection of the boiler operation.  
12. Remove oxide from the detection electrode using an emery cloth.  
13. After servicing, complete the relevant Service Interval Record  
section of the Benchmark Checklist located on page 54 of this  
manual.  
Cleaning the primary exchanger  
The inside of the primary exchanger is accessed by removing the  
burner. Wash with water and detergent using a non-metallic rifle-type  
brush, rinse with water.  
14. These checks are not exhaustive. Further mechanical, electrical  
and combustion maintenance checks may be required.  
15. Analyse combustion, see page 33.  
The trap is accessed by emptying the condensate bowl located in the  
bottom section. Wash with water and detergent.  
Replace the condensate collection bowl in its housing.  
NB: In the event of prolonged of the appliance, the trap must be filled  
before being used again.  
A lack of water in the siphon is dangerous and may cause exhaust  
gases to be released into the atmosphere.  
Operational test  
After having carried out the maintenance operations, fill the heating  
circuit at a pressure of approximately 1.5 bar and release the air from  
the system.  
Fill the domestic hot water system at the same time.  
-
-
-
Begin operating the boiler.  
If necessary, release the air from the heating system again.  
Check the settings and make sure all the command, adjustment and  
monitoring parts are working correctly.  
Combustion Analyses  
Details for flue gas analyses can be found on page 33.  
Using a suitable calibrated combustion analyser, perform a combus-  
tion check. The CO2 valus can be found on page 33.  
-
Check the flue system is sealed and operating correctly.  
if the vlues are correct the CO/CO2 ratio must be less than 0.004.  
Where combustion readings cannot be achieved carrefully check items  
such as the burner, heat exchanger, flue system for defect.  
Once satisfactors readings hane been achieved complete the relevant  
service interval record selection of the Benchmark Commissioning  
Checklist at the rear of this publication.  
Draining procedures  
The heating system must be drained using the following procedure:  
- Switch off the boiler, make sure the external bipolar switch is in the  
OFF position;  
- Loosen the automatic air relief valve;  
- Open the system drain off cock and collect the escaping water in a  
container;  
- Empty the water from the lowest points of the system (where  
applicable).  
If the system is to be left inactive in areas where the room temperature  
may fall below 0°C during winter, we recommend that anti-freeze  
33  
maintenance guide  
General access  
Tools  
Time  
3 min  
1
Unclip the cover to remove  
Remove the two screws  
Remove the front panel  
2
Lower the electrical box  
Remove the combustion chamber front panel by releasing the  
clips  
34  
maintenance guide  
Electrical unit  
Control box access  
Tools  
Time  
4 min  
1
Remove the front panel as above and pivot  
Remove the two screws and unlock the  
four clamps to gain access to the control  
box  
the electrical box  
Fuse  
Tools  
Time  
5 min  
1
Open the control box as above  
Remove the fuse  
35  
maintenance guide  
Main P.C.B.  
Tools  
Time  
7 min  
1
After opening the control boz, disconnect  
the electrical plug connectors  
Unscrew the two screwa and remove the  
PCB  
Display P.C.B.  
Tools  
Time  
7 min  
1
Unclip the cover to remove  
Remove the two control knobs  
Unscrew the four screws and pull the  
assembly towards you  
2
Disconnect the electrical plug connectors,  
unlock the two clamps, and remove the  
PCB  
36  
maintenance guide  
Hydraulic Unit  
Right hand hydraulic block assembly  
Legend:  
1. Diverter valve motor  
1
2
3
2. Diverter valve  
4
3. Auto air vent  
4. Primary water pressure switch  
5. Pump  
6. Central heating filter  
7. Non return valve  
5
8. Non return valve assembly  
9. DHW flow switch assembly  
10. Drain valve  
6
7
10  
8
11. Central heating return  
9
12. Domestic cold water intlet  
11  
12  
13. Domestic hot water outlet  
13  
14  
14. Central heating flow  
37  
maintenance guide  
3 Way valve unit  
Tools  
Time  
5 min  
1
Unplug the diverter valve cable  
Remove the clip and lift the motor from the diverter valve body  
2
Drain the boiler (see 3.3).  
aligned correctly  
Remove the clip and lift the diverter valve from the assembly  
Draining  
Tools  
Time  
5 min  
Turn the drain valve anti-clockwise to open and drain the water from  
the boiler.  
1
38  
maintenance guide  
Automatic air vent  
Tools  
Time  
5 min  
1
Drain boiler (see 3.3). Remove the clip and lift the AAV from the assembly  
Primary water pressure sensor  
Tools  
Time  
5 min  
1
Drain boiler (see 3.3). Remove the xing clip, unplug the electrical connector and lift the sensor from the assembly  
39  
maintenance guide  
Pump  
Tools  
Time  
10 min  
1
Drain boiler (see 3.3). Remove the clip and the two screws  
Disconnect the pipe and then move the pump to the right  
disengage  
2
Remove the pump  
Remove the sensor (see 3.5)  
3
Remove the AAV (see 3.4)  
40  
maintenance guide  
C.H. Filter  
Tools  
Time  
5 min  
1
After opening the control boz, disconnect  
Unscrew the two screwa and remove the  
PCB  
the electrical plug connectors  
D.H.W. Flow Switch assembly (E-COMBI)  
Tools  
Time  
5 min  
1
Drain boiler (see 3.3). Remove the clip and pull the ow  
Twist the ow switch assembly to disengage  
switch assembly towards you  
41  
maintenance guide  
Left hand Hydraulic block assembly  
Legend  
1. Left hand hydraulic block  
2. By-pass assembly  
3. Safety valve  
4. Central heating flow  
5. Domestic hot water outlet  
1
2
3
4
5
Secondary Heat Exchanger (E-COMBI)  
Tools  
Time  
10 min  
1
Drain primary and domestic hot water circuits.  
Remove the two screws and remove the heat exchanger  
42  
maintenance guide  
Condensate Trap  
Tools  
Time  
5 min  
Unscrew the condense trap from the condense body  
1
Safety valve  
Tools  
Time  
5 min  
1
Drain boiler (see 3.3). Disconnect the  
discharge pipe  
Remove the first clip on the left and pull  
the safety valve towards you  
43  
maintenance guide  
By-Pass Assembly  
Tools  
Time  
5 min  
1
Drain boiler (see 3.3). Remove the second  
clip and pull the assembly toward you  
Push on the by-pass to disengage it  
Temperature Sensor  
Tools  
Time  
5 min  
NTC1  
NTC2  
1
NTC1 : Black wires  
NTC2 : Grey wires  
Unplug the electrical connectors  
Remove the clip and the temperature sensor  
RESISTANCE (kOmh)  
TEMPERATURE (°C)  
0
27  
17  
12  
10  
8
5
4
3
2
10  
20  
25  
30  
40  
50  
60  
70  
80  
1,5  
44  
maintenance guide  
Manual Air vent  
Tools  
Time  
5 min  
1
Remove the clip and lift the manual air vent from the exchanger  
Main Heat Exchanger  
Tools  
Time  
20 min  
1
Drain boiler (see 3.3). Remove the four clips Isolate the gas supply. Remove the four Remove the four screws to free the heat ex-  
and disconnect the two pipes between the screws and disconnect the gas pipe from changer  
exchanger and pump and between the ex- the gas valve  
changer and left hand hydraulic block  
2
Pull the heat exchanger towards you  
Remove the clip and lift the manual air vent Twist the thermal fuse to remove  
45  
maintenance  
Burner unit  
Legend  
1. Burner  
2. Fan  
3. Silencer  
4. Gas inlet  
5. Air inlet  
6. Gas valve  
7. Mixing tube  
8. Detection electrode  
9. Ignition electrode  
10. Spark generator  
46  
maintenance guide  
Spark generator  
Tools  
Time  
5 min  
1
Unplug the ignition electrode from the  
spark generator  
Remove the screw and the spark generator  
Electrodes  
Tools  
Time  
5 min  
1
Unplug the electrodes  
Remove the screws and pull the electrodes  
towards you.  
47  
maintenance guide  
Burner  
Tools  
Time  
15 min  
1
Remove the silencer  
Isolate the gas supply. Remove the four Pull the assembly towards you  
screws and disconnect the gas pipe from  
the gas valve  
Note: Any work carried out on the  
combustion assembly requires  
a combustion analysis check on  
completion of work  
2
Remove the three screws to free the burner Pull the burner toward you  
door  
2
1
3
Power  
Length  
Venturi  
1.Stainless Steel Burner  
24 KW  
104.6 mm  
Ø 42 mm  
2. Ignition electrode  
3.Detection electrode  
30 KW  
38 KW  
135.8 mm  
167 mm  
/
/
48  
maintenance guide  
Fan  
Tools  
Time  
15 min  
1
Remove the combustion assembly  
(see 4.3)  
Remove the three screws to free the fan.  
Twist the gas valve anti-clockwise to disengage it from  
the fan  
Legend:  
1. Venturi  
2. Gasket  
3. Fan  
Fan & Mixer venturi according to the model  
Power Fan Venturi diameter  
Model 24 EBM RG 128 45 W Ø 17 mm  
Model 30  
Model 38  
EBM RG 128 45 W  
EBM RG 128 45 W  
Ø 21 mm  
Ø 25 mm  
49  
maintenance guide  
Gas valve  
Tools  
Time  
15 min  
1
Remove the combustion assembly  
(see 4.3)  
Twist the gas valve anti-clockwise to disconnect it from the  
fan  
Replacement gas valves are not  
factory set and will need to be set  
up (see page 33)  
Legend  
1. Venturi  
Bayonet  
connection  
2. Gas valve  
3. Solenoids  
4. Inlet test nipple  
5. Offset adjustment  
6.Throttle adjustment  
Note: When changing the gas valve, the new gas valve is not  
preset. Ensure the maximum + minimum CO2 valves are set  
up in accordance whit the commissioning procedure.  
50  
maintenance guide  
Annual Maintenance  
Plate heat exchanger  
Primary Heat  
exchanger  
Maintenance Interval: As  
necessary  
How: To measure specifi-  
cation of DHW perfor-  
mance.  
Maintenance Interval:  
Annually  
How : Visual inspection /  
Clean as necessary  
By-pass & Safety valve  
Maintenance Interval:  
Annually  
How: Visual inspection /  
Clean as necessary  
Condensate trap  
Maintenance Interval:  
Annually  
Central heating filter  
or after cleaning primary  
heat exchanger  
Maintenance Interval:  
Annually  
How: Visual inspection /  
Clean as necessary /  
Add water before  
replacing  
How: Visual inspection /  
Clean as necessary  
Flow switch operation  
Maintenance Interval:  
Annually  
How: Visual inspection /  
Clean as necessary  
/ Check flow rate  
Expansion vessel  
Maintenance Interval:  
Annually  
How: Check air pressu-  
re is at 1 bar (System  
drained)  
Pump  
Ignition & detection  
electrodes  
Maintenance Interval:  
At the first ignition and  
annually  
Maintenance Interval:  
Annually  
How: Visual inspection /  
Clean as necessary / Di-  
stance from the burner /  
Ionisation current more  
than 1 μA  
How: Check that the  
AAV is open /  
Visual inspection / Clean  
as necessary  
Burner  
Maintenance Interval:  
Annually  
How: Visual inspection /  
Clean as necessary  
Fan  
Maintenance Interval:  
Annually  
How : Visual inspection /  
Clean as necessary  
51  
maintenance guide  
Fault finding  
Overheat  
Flame detected  
with gas valve  
closed  
Ignition electrode/wiring connectors  
Insufficient  
circulation  
Water pressure  
Ignition electrode wiring connection onto  
main pcb  
Bleed heat exchanger  
Pump operation  
CH return filter for blockages  
Circulation around boiler (blockages)  
ntc temperature sensors  
Flame lift  
Insufficient working gas pressure  
Check flue system for correct assembly/  
termination  
CO2 settings  
Insufficient water  
(request filling)  
Water pressure gauge for correct pressure  
Check for waterleaks on the entire system  
Thermofuse open  
Fan speed error  
Check wiring and connections to  
thermofuse  
Check integriry of main heat exchanger  
CH Flow temp.  
Check connections and wiring to temp  
probe circuit open/ sensors  
Check fan  
short circuit  
Check wiring connections from fan to pcb  
CH Flow temp.  
probe circuit open/  
short circuit  
Resistance values of temp sensors  
Heating delivery  
probe problem  
Details in maintenance guide in installation  
manual  
Floor thermostat  
contact open  
Check terminals TA2 for presence of link  
wire  
EEPROM Error  
Check the EEPROM connection onto the  
pcb  
Communication  
error  
Check connection and wiring onto all  
devices, main and display pcb  
Main PCB error  
Too many (>5)  
Identify reason for lockout from table and  
resets in 5 minutes check for relevant faults  
No Flame detected Insufficient working gas pressure  
1st Ignition failed  
Spark electrode/wiring connectors  
2nd Ignition failed Ignition electrode/wiring connectors  
Flame cut-off  
Spark generator/wiring connectors  
Check flue system for correct assembly/  
termination  
Check earth  
Gas valve  
CO2 settings  
Soft light rate  
52  
GAS BOILER SYSTEM COMMISSIONING CHECKLIST  
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating  
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.  
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.  
Customer Name  
Address  
Telephone Number  
Boiler Make and Model  
Boiler Serial Number  
Commissioned by (print name)  
Company Name  
CORGI ID Number  
Telephone Number  
Company Address  
Commissioning Date  
To be completed by the customer on receipt of a Building Regulations Compliance Certificate :  
*
Building Regulations Notification Number (if applicable)  
CONTROLS Tick the appropriate boxes  
Time and Temperature Control to Heating  
Room Thermostat and  
Programmer/Timer  
Programmable  
Room Thermostat  
Load/Weather  
Compensation  
Optimum Start  
Control  
Time and Temperature Control to Hot Water  
Heating Zone Valves  
Cylinder Thermostat and Programmer/Timer  
Combination Boiler  
Not Required  
Not Required  
Not Required  
Not Required  
Provided  
Fitted  
Fitted  
Fitted  
Fitted  
Hot Water Zone Valves  
Thermostatic Radiator Valves  
Automatic Bypass to System  
Boiler Interlock  
ALL SYSTEMS  
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions  
Yes  
What system cleaner was used?  
What inhibitor was used?  
Quantity  
litres  
ft3/hr  
CENTRAL HEATING MODE Measure and Record:  
m3/hr  
mbar  
OR  
OR  
Gas Rate  
Burner Operating Pressure (if applicable)  
Central Heating Flow Temperature  
Central Heating Return Temperature  
Gas Inlet Pressure  
mbar  
°C  
°C  
COMBINATION BOILERS ONLY  
Is the installation in a hard water area (above 200ppm)?  
If yes, has a water scale reducer been fitted?  
What type of scale reducer has been fitted?  
DOMESTIC HOT WATER MODE Measure and Record:  
Gas Rate  
Yes  
Yes  
No  
No  
ft3/hr  
m3/hr OR  
mbar OR  
Burner Operating Pressure (at maximum rate)  
Cold Water Inlet Temperature  
Gas Inlet Pressure (at maximum rate)  
mbar  
°C  
Hot water has been checked at all outlets  
Water Flow Rate  
Yes  
Temperature  
°C  
l/min  
CONDENSING BOILERS ONLY  
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798  
Yes  
ALL INSTALLATIONS  
If required by the manufacturer, record the following  
CO2  
%
OR CO  
ppm OR CO/CO2 Ratio  
The heating and hot water system complies with the appropriate Building Regulations  
Yes  
Yes  
Yes  
Yes  
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions  
The operation of the boiler and system controls have been demonstrated to and understood by the customer  
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer  
Commissioning Engineer’s Signature  
Customer’s Signature  
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)  
All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.  
A Building Regulations Compliance Certificate will then be issued to the customer.  
*
©Heating and Hotwater Industry Council (HHIC)  
SERVICE RECORD  
It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.  
Service Provider  
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s  
instructions.  
Always use the manufacturer’s specified spare part when replacing controls.  
SERVICE 1 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 2 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 3 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 4 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 5 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 6 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 7 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 8 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SERVICE 9 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 10 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
CORGI ID Number  
Comments  
Telephone Number  
CORGI ID Number  
Comments  
Signature  
Signature  
SHORT LIST  
407  
401  
537  
543  
530  
538  
136  
135  
589  
590  
517  
112  
134  
111  
625  
615  
607  
616  
502  
506  
110  
(ꢇ&20%, (ꢇ6<67(0  
0DQIꢀꢁGDWH  
.H\ 1  
'HVFULSWLRQ  
7\SH  
0DQIꢀꢁ3Wꢀ 1  
ꢅꢆ ꢃꢀ ꢃꢇ ꢅꢆ ꢃꢀ  
IURP  
WR  
ꢂꢃꢂꢂ %851(5ꢁ$66(0%/<  
ꢀꢁꢁꢀ ,*1,7,21ꢈ(/(&752'(  
ꢀꢁꢁꢁ ,21,=$7,21ꢈ(/(&752'(  
ꢀꢁꢁꢅ *$6.(7ꢈ'ꢋꢇꢌꢂꢉꢉꢍꢌꢂꢅꢍꢌ  
ꢀꢁꢃꢆ (/(&752'(ꢈ*$6.(7  
.....  
.....  
.....  
.....  
.....  
.....  
ꢉꢁꢃꢁꢊꢆꢃꢅ  
ꢉꢁꢃꢁꢊꢆꢃꢃ  
ꢉꢁꢃꢁꢆꢊꢌꢃ  
ꢉꢀꢀꢀꢀꢅꢇꢉ  
ꢉꢀꢀꢀꢀꢅꢎꢊ  
ꢉꢀꢀꢀꢀꢉꢅꢃ  
ꢀꢁꢃꢌ &20%867,21ꢈ&+$0%(5ꢈ/,1,1*ꢈ.,7  
ꢀꢁꢃꢉ '225ꢈ*$6.(7  
ꢂꢄꢂꢂ *$6ꢁ6(&7,21  
ꢀꢆꢀꢁ *$6ꢈ9$/9(  
ꢀꢆꢀꢊ )$1ꢈ$66<  
.....  
.....  
ꢉꢀꢀꢀꢀꢌꢃꢊ  
ꢉꢀꢀꢀꢀꢉꢅꢅ  
ꢂꢅꢂꢂ +<'5$8/,&ꢁ%/2&.  
...  
ꢀꢌꢀꢅ 02725ꢈꢂꢈ7+5((ꢂ:$<ꢈ9$/9(  
ꢀꢌꢀꢉ ꢃꢂ:$<ꢈ635,1*ꢈ.,7ꢈꢏ'ꢍ+ꢍ:ꢍꢐ  
ꢀꢌꢁꢊ /2:ꢈ35(6685(ꢈ6:,7&+  
ꢀꢌꢃꢀ $872ꢈ$,5ꢈ9(17ꢈ:,7+ꢈ2ꢂ5,1*  
ꢀꢌꢃꢊ 35(6685(ꢈ5(/,()ꢈ9$/9(  
ꢀꢌꢃꢇ 3803ꢈꢌ0ꢈꢅ9  
ꢉꢁꢃꢀꢅꢆꢇꢃ  
ꢉꢌꢁꢀꢆꢃꢁꢆ  
ꢉꢌꢁꢀꢌꢀꢎꢀ  
ꢉꢌꢁꢀꢆꢊꢀꢃ  
ꢉꢁꢃꢁꢅꢉꢉꢇ  
ꢉꢌꢁꢀꢆꢃꢁꢎ  
ꢉꢌꢁꢀꢆꢃꢅꢃ  
ꢉꢌꢁꢀꢆꢃꢃꢃ  
ꢉꢁꢀꢀꢅꢅꢆꢎ  
...  
.....  
.....  
.....  
.....  
...  
ꢀꢌꢆꢃ 6(1625ꢈꢏ5(('ꢐ  
...  
ꢀꢌꢇꢎ 6(&21'$5<ꢈ(;&+$1*(5  
ꢀꢌꢎꢀ /,3 6($/ꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈꢈ  
...  
ꢂꢆꢂꢂ (/(&75,&$/ꢁ%2;  
.....  
.....  
.....  
.....  
ꢀꢉꢀꢊ ,*1,7(5  
ꢉꢁꢀꢀꢅꢁꢀꢌꢂꢅꢀ  
ꢉꢀꢀꢀꢁꢁꢅꢎ  
ꢉꢀꢀꢀꢁꢁꢃꢀ  
ꢉꢌꢁꢀꢆꢅꢃꢆ  
ꢀꢉꢁꢌ 35,17('ꢈ&,5&8,7ꢈ%2$5'  
ꢀꢉꢁꢉ 35,17('ꢈ&,5&8,7ꢈ%2$5'ꢈꢏ',63/$<ꢐ  
ꢀꢉꢅꢌ 35(6685(ꢈ*$8*(  
Professional Team Limited  
Suites 9 & 10, Plaza 256  
Blanchardstown Corporate Park 2  
Ballycoolin  
Dublin 15  
Telephone: (01) 810 3723  
Fax: (01) 810 3727  
Ariston Thermo UK Ltd  
Hughenden Avenue  
High Wycombe  
Bucks HP13 5FT  
Telephone: (01494) 755600  
Fax: (01494) 459775  
Technical Advice: 0870 241 8180  
Customer Service: 0870 600 9888  
Technical Advice: (01) 437 0121  
Customer Service: (01) 437 0121  

A O Smith NW 37 670 User Manual
ATN Aries 6900 User Manual
Blaupunkt 7 644 820 310 User Manual
Blaupunkt San Remo CD31 User Manual
Braun MULTIQUICK 5 MR 530 BABY User Manual
Bushnell Binoculars 190125 User Manual
Dynex DX DA100502 User Manual
Grindmaster CRATHCO 5311 User Manual
Havis Shields S UMM XPT 104 User Manual
Jensen PowerPlus 652 User Manual