| 
		 Vermont Casting Cfm Specialty Air Conditioner Msy D36na User Manual  | 
	
| 	
		 INDOOR UNIT   
					No. OBH501   
					SERVICE MANUAL   
					Wireless type   
					Models   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Outdoor unit service manual   
					MUZ-D•NA Series (OBH502)   
					MUY-D•NA Series (OBH502)   
					CONTENTS   
					·······································   
					1. TECHNICAL CHANGES   
					3 
					2. PART NAMES AND FUNCTIONS····················· 4   
					3. SPECIFICATION················································ 5   
					4. OUTLINES AND DIMENSIONS ························ 7   
					5. WIRING DIAGRAM············································ 8   
					6. REFRIGERANT SYSTEM DIAGRAM··············· 9   
					7. SERVICE FUNCTIONS ··································· 10   
					8. MICROPROCESSOR CONTROL ··················· 12   
					9. TROUBLESHOOTING····································· 19   
					10. DISASSEMBLY INSTRUCTIONS···················· 31   
					PARTS CATALOG (OBB501)   
					NOTE:   
					RoHS compliant products have <G> mark on the spec name plate.   
				TECHNICAL CHANGES   
					1 
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					1. New model   
					3 
				2 
					PART NAMES AND FUNCTIONS   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Air cleaning filter   
					(Anti-Allergy Enzyme Filter)   
					Front panel   
					Air filter   
					(Catechin air filter)   
					Air inlet   
					Emergency operation   
					switch   
					Air outlet   
					Operation indicator   
					lamp   
					Horizontal vane   
					Remote control   
					receiving section   
					Remote controller   
					MSZ-D30NA   
					ACCESSORIES   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Installation plate   
					1 
					7 
					1 
					2 
					2 
					1 
					2 
					1 
					1 
					2 
					Installation plate screw 4 × 25 mm   
					Remote controller holder   
					Screw for × 3.5 × 1.6 mm (Black)   
					Battery (AAA) for remote controller   
					Wireless remote controller   
					Felt tape (Used for left or left-rear piping)   
					L-Joint pipe   
					Conduit plate   
					Air cleaning filter   
					4 
				3 
					SPECIFICATION   
					Model   
					MSZ-D30NA   
					MSY-D30NA   
					MSZ-D36NA   
					MSY-D36NA   
					External finish   
					White   
					Power supply   
					V, phase, Hz   
					208 / 230 , 1 , 60   
					Max. fuse size (time delay)/ Disconnect switch   
					Min. circuit ampacity   
					Fan motor   
					A 
					A 
					F.L.A   
					CFM   
					15   
					1.0   
					0.76   
					HEAT Dry   
					COOL Dry   
					445-639-848   
					— 
					445-639-848   
					— 
					Airflow   
					Low-Med.-High   
					CFM   
					389(350)-639(576)-848(763)   
					389(350)-639(576)-848(763)   
					(Wet)   
					Moisture removal   
					pt./h   
					dB(A)   
					dB(A)   
					in.   
					in.   
					in.   
					9.9   
					11.3   
					32-42-49   
					34-42-49   
					11.9   
					32-42-49   
					— 
					Cooling   
					Heating   
					32-42-49   
					34-42-49   
					32-42-49   
					— 
					Sound level   
					Low-Med.-High   
					Cond. drain connection O.D.   
					W 
					Dimensions   
					5/8   
					46-1/16   
					11-5/8   
					D 
					H 
					in.   
					14-3/8   
					Weight   
					Ib.   
					40   
					Remote controller   
					Control voltage (by built-in transformer)   
					Wireless type   
					12-24 VDC   
					NOTE : Test conditions are based on ARI 210/240.   
					5 
				3-1. OPERATING RANGE   
					(1) POWER SUPPLY   
					Rated voltage   
					Guaranteed Voltage   
					208/230 V   
					1 phase   
					60 Hz   
					Min.187 V 208 V 230 V Max.253 V   
					Indoor unit   
					(2) OPERATION   
					Intake air temperature (°F)   
					Mode   
					Condition   
					Standard temperature   
					Maximum temperature   
					Minimum temperature   
					Maximum humidity   
					Indoor   
					78 %   
					Outdoor   
					DB   
					80   
					90   
					67   
					WB   
					67   
					73   
					DB   
					95   
					115   
					14   
					WB   
					— 
					— 
					Cooling   
					57   
					— 
					— 
					Standard temperature   
					Heating Maximum temperature   
					Minimum temperature   
					70   
					80   
					70   
					60   
					67   
					60   
					47   
					75   
					14   
					43   
					65   
					13   
					3-2. OUTLET AIR SPEED AND COVERAGE RANGE   
					Airlow   
					(CFM)   
					Air speed   
					(ft./sec.)   
					Coverage   
					range (ft.)   
					The air coverage range is the figure up   
					to the position where the air speed is 1   
					ft./sec., when air is blown out horizon-   
					tally from the unit properly at the High   
					speed position.   
					The coverage range should be used   
					only as a general guideline since it var-   
					ies according to the size of the room   
					and furniture arranged inside the room.   
					Model   
					Mode   
					HEAT   
					Function   
					Dry   
					MSZ-D30NA   
					MSZ-D36NA   
					848   
					848   
					763   
					23.6   
					45.0   
					45.0   
					40.7   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Dry   
					23.6   
					21.3   
					COOL   
					Wet   
					6 
				4 
					OUTLINES AND DIMENSIONS   
					Unit : inch   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Indoor unit   
					2-11/16   
					4-11/16   
					45-1/2   
					20-7/8   
					17-11/16   
					5-3/8   
					2-3/16   
					11-5/8   
					1/4   
					Wall hole ø3   
					Air in   
					46-1/16   
					Installation plate   
					Piping   
					Drain hose   
					2-15/16   
					33-11/16   
					9-1/2   
					2-5/8   
					5-7/8   
					Air out   
					2-5/16   
					3/4   
					Piping   
					Insulation   
					ø1-1/4 O.D   
					ø9/16 I.D   
					ø3/8 19-11/16   
					Liquid line   
					(Flared connection ø3/8)   
					ø5/8 16-7/8   
					(Joint connection ø5/8)   
					ø5/8   
					ø1-15/16 O.D   
					ø1-1/4 I.D   
					ø1-15/16 O.D   
					ø1-1/4 I.D   
					Gas line   
					Joint   
					Wireless remote controller   
					(Flared connection ø5/8)   
					Inslation ø1-1/8 Connected part ø9/16 O.D   
					Drain hose   
					Required Space (Indoor Unit)   
					4-11/16 or more   
					8-11/16 or more   
					9-3/8 or more   
					4-3/16 or more   
					In case of left,left back,   
					or left under piping (using spacer) 5-1/8 or more   
					7 
				5 
					WIRING DIAGRAM   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					8 
				6 
					REFRIGERANT SYSTEM DIAGRAM   
					Unit:inch   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Refrigerant pipe ø5/8   
					(with heat insulator)   
					Indoor coil   
					thermistor   
					RT12(main)   
					Indoor   
					heat   
					exchanger   
					Flared connection   
					Joint   
					Indoor coil   
					thermistor   
					RT13(sub)   
					Distributor   
					Joint connection   
					Room temperature   
					thermistor   
					RT11   
					Flared connection   
					Strainer   
					Refrigerant flow in cooling   
					Refrigerant flow in heating   
					Refrigerant pipe ø3/8   
					(with heat insulator)   
					9 
				7 
					SERVICE FUNCTIONS   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					7-1. TIMER SHORT MODE   
					For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board.   
					The time will be shortened as follows. (Refer to 9-7.)   
					Set time : 1-minute 1-second   
					Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is   
					shortened by short circuit-of JPG and JPS.)   
					7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION   
					A maximum of 4 indoor units with wireless remote controllers can be used in a room.   
					In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be   
					modified according to the number of the indoor unit.   
					How to modify the remote controller P.C. board   
					Remove batteries before modification.   
					The board has a print as shown below :   
					NOTE : For modification, take out   
					the batteries and press   
					the OPERATE/STOP (ON/   
					OFF) button twice or 3   
					times at first.   
					After finish modification,   
					put back the batteries then   
					J1   
					press the RESET button.   
					J2   
					The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.   
					After modification, press the RESET button.   
					Table 1   
					1 unit operation   
					No modification   
					2 units operation   
					Same as at left   
					3 units operation   
					Same as at left   
					Same as at left   
					Solder J2   
					4 units operation   
					Same as at left   
					Same as at left   
					No. 1 unit   
					No. 2 unit   
					No. 3 unit   
					No. 4 unit   
					— 
					— 
					— 
					Solder J1   
					— 
					— 
					Same as at left   
					Solder both J1 and J2   
					— 
					How to set the remote controller exclusively for particular indoor unit   
					After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote   
					controller for the indoor unit.   
					The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are   
					set.   
					The setting will be cancelled if the breaker has turned off, or the power supply has shut down.   
					Please conduct the above setting once again after the power has restored.   
					10   
				7-3. AUTO RESTART FUNCTION   
					When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed   
					are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment   
					power has restored after power failure. Then, the unit will restart automatically.   
					Operation   
					If the main power has been cut, the operation settings remain.   
					After the power is restored, the unit restarts automatically according to the memory.   
					(However, it takes at least 3 minutes for the compressor to start running.)   
					How to release “AUTO RESTART FUNCTION”   
					Turn off the main power of the unit.   
					Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)   
					CN152   
					JR07   
					BZ   
					NOTE:   
					• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the   
					remote controller.   
					• If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is   
					cancelled.   
					• If the unit has been off with the remote controller before power failure, the auto restart function does not work as the   
					power button of the remote controller is off.   
					• To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the   
					same time.   
					• When some air conditioners are connected to the same supply system, if they are operated before power failure, the   
					starting current of all the compressors may flow simultaneously at restart.   
					Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting   
					current by adding to the system that allows the units to start one by one.   
					11   
				8 
					MICROPROCESSOR CONTROL   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					WIRELESS REMOTE CONTROLLER   
					+ These pictures show MSZ type.   
					Signal transmitting section   
					Operation display section   
					OPERATE/STOP   
					(ON/OFF) button   
					VANE CONTROL button   
					(Horizontal vane button)   
					FAN SPEED   
					CONTROL button   
					Temperature buttons   
					OFF TIMER button   
					ON TIMER button   
					OPERATION SELECT button   
					ECONO COOL button   
					TIME SET buttons   
					FORWARD button   
					BACKWARD button   
					WIDE VANE button (Vertical vane button)   
					Indication of   
					remote controller   
					model is on back   
					POWERFUL button   
					RESET button   
					CLOCK SET button   
					NOTE   
					Use the remote controller   
					provided with the unit only.   
					Do not use other remote   
					controller.   
					NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the   
					remote controller with beeps.   
					INDOOR UNIT DISPLAY SECTION   
					Operation Indicator lamp   
					The operation indicator at the right side of the indoor unit indicates the operation state.   
					•The following indication applies regardless of shape of shape of the indication.   
					Lighted   
					Indication   
					Operation state   
					Room temperature   
					Blinking   
					Not lighted   
					About 4 °F (2 °C) or   
					more away from set   
					temperature   
					The unit is operating to   
					reach the set temperature   
					The room temperature   
					is approaching the set   
					temperature   
					About 2 °F (1 °C) to   
					4 °F (2 °C) from set   
					temperature   
					12   
				8-1. COOL ( ) OPERATION   
					(1) Press OPERATE/STOP (ON/OFF) button.   
					OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.   
					(2) Select COOL mode with OPERATION SELECT button.   
					(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.   
					The setting range is 61 ~ 88 °F (16 ~ 31 °C).   
					1. Coil frost prevention   
					When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.   
					The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor   
					heat exchanger rises.   
					2. Low outside temperature operation   
					When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.   
					8-2. DRY ( ) OPERATION   
					(1) Press OPERATE/STOP (ON/OFF) button.   
					OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.   
					(2) Select DRY mode with OPERATION SELECT button.   
					(3) The set temperature is determined from the initial room temperature.   
					1. Coil frost prevention   
					Coil frost prevention is as same as COOL mode. (8-1.1.)   
					2. Low outside temperature operation   
					Low outside temperature operation is as same as COOL mode. (8-1.2.)   
					8-3. HEAT ( ) OPERATION (MSZ)   
					(1) Press OPERATE/STOP (ON/OFF) button.   
					OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.   
					(2) Select HEAT mode with OPERATION SELECT button.   
					(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.   
					The setting range is 61 ~ 88 °F (16 ~ 31 °C).   
					1. Cold air prevention control   
					When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-   
					perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.   
					2. High pressure protection   
					The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-   
					densing pressure from increasing excessively.   
					When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.   
					The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat   
					exchanger falls.   
					3. Defrosting   
					Defrosting starts when the temperature of outdoor heat exchanger becomes too low.   
					The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses and the compressor re-starts.   
					This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.   
					8-4. FAN(   
					)OPERATION (MSY)   
					(1) Press OPERATE/STOP (ON/OFF) button.   
					OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.   
					(2) Select FAN mode with OPERATION SELECT button.   
					(3) Select the desired fan speed. When AUTO, it becomes Low.   
					Only indoor fan operates. Outdoor unit does not operate.   
					8-5. “I FEEL CONTROL” ( ) OPERATION (MSY)   
					(1) Press OPERATE/STOP (ON/OFF) button on the remote   
					Initial room temperature   
					Mode   
					controller. OPERATION INDICATOR lamp of the indoor   
					unit turns on with a beep tone.   
					(2) Select “I FEEL CONTROL” mode with OPERATION   
					SELECT button.   
					(3) The operation mode is determined by the room tempera-   
					ture at start-up of the operation.   
					COOL mode of   
					"I FEEL CONTROL"   
					77 °F (25 °C) or more   
					more than 55 °F (13 °C),   
					less than 77 °F (25 °C) "I FEEL CONTROL"   
					DRY mode of   
					• 
					• 
					Once the mode is fixed, the mode does not change by room temperature afterwards.   
					Under the ON TIMER (   
					operation starts.   
					) operation, mode is determined according to the room temperature at the set time the   
					13   
				(4) The initial set temperature is decided by the initial room temperature.   
					Model   
					Initial room temperature   
					79 °F (26 °C) or more   
					Initial set temperature   
					75°F (24 °C)   
					COOL mode of "I FEEL   
					CONTROL"   
					1 
					77 °F (25 °C) to 79 °F (26 °C) Initial room temperature minus 4 °F (2 °C)   
					DRY mode of "I FEEL   
					CONTROL"   
					more than 55 °F (13 °C),   
					Initial room temperature minus 4 °F (2 °C)   
					less than 77 °F (25 °C)   
					1 When the system is restarted with the remote controller, the system operates with the previous set temperature   
					regardless of room temperature at restart.   
					The set temperature is calculated by the previous set temperature.   
					(5) TEMPERATURE buttons   
					In “I FEEL CONTROL” (   
					) mode, set temperature is decided by the microprocessor based on the room temperature.   
					In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too   
					warm.   
					Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.   
					• Fuzzy control   
					When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering   
					the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or   
					cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.   
					In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.   
					··· To raise the set temperature 2 ~ 4 °F (1 ~ 2 °C)   
					··· To lower the set temperature 2 ~ 4 °F (1 ~ 2 °C)   
					8-6. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ)   
					Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.   
					Mode selection   
					(1) Initial mode   
					When unit starts the operation with AUTO operation from off;   
					• If the room temperature is higher than the set temperature, operation starts in COOL mode.   
					• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.   
					(2) Mode change   
					COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 4 °F (2 °C) below   
					the set temperature.   
					HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 4 °F (2 °C) above   
					the set temperature.   
					14   
				8-7. AUTO VANE OPERATION   
					1. Horizontal vane   
					(1) Vane motor drive   
					These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of   
					the motor are controlled by pulse signals (approx. 12 V) transmitted from indoor microprocessor.   
					(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.   
					(3) Positioning   
					To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the selected   
					angle.   
					(a) The operation starts or finishes (including timer operation).   
					(b) The test run starts.   
					(4) VANE AUTO (   
					) mode   
					The microprocessor automatically determines the horizontal vane angle and operation to make the optimum room tem-   
					perature distribution.   
					COOL and DRY operation   
					FAN operation (MSY)   
					HEAT operation (MSZ)   
					Vane angle is fixed to Angle 4.   
					Vane angle is fixed to Angle 1.   
					1 
					(5) STOP (operation OFF) and ON TIMER standby   
					In the following cases, the horizontal vane returns to the closed position.   
					(a) OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).   
					(b) The operation is stopped by the emergency operation.   
					(c) ON TIMER is ON standby.   
					(6) Dew prevention   
					During COOL or DRY operation with the vane angle at Angle 4 ~ 5 when the compressor cumulative operation time   
					exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.   
					(7) SWING (   
					) mode   
					By selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically.   
					(8) Cold air prevention in HEAT operation (MSZ)   
					The horizontal vane position is set to Upward.   
					(9) ECONO COOL (   
					) operation (ECONOmical operation)   
					When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6 °F (2 °C) higher.   
					Also the horizontal vane swings in various cycle.   
					SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air   
					conditioner can keep comfort. As a result, energy can be saved.   
					ECONO COOL operation is cancelled when ECONO COOL button is pressed once again, when the VANE CONTROL   
					or POWERFUL button is pressed, or operation mode is changed.   
					( 
					10) POWERFUL (   
					) operation.   
					The air conditioner automatically adjusts the fan speed and the set temperature, and operates the POWERFUL mode.   
					The POWERFUL mode is cancelled automatically 15 minutes after operation starts, or when POWERFUL but-   
					ton is pressed once again within 15 minutes after operation starts. The operation mode returns to the mode prior to   
					POWERFUL operation. POWERFUL mode also is cancelled, when the ECONO COOL or FAN SPEED SELECT button   
					is pressed within 15 minutes after operation starts, or operation mode is changed.   
					15   
				2. Vertical vane   
					(1) Vane motor drive   
					These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the   
					motor are controlled by pulse signals (approx. 12 V) transmitted from microprocessor.   
					(2) The vertical vane angle and mode change as follows by pressing WIDE VANE button.   
					1 
					4 
					SWING   
					5 
					6 
					2 
					3 
					(3) Positioning   
					The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle.   
					Confirming of standard position is performed in the following cases.   
					(a) OPERATE/STOP (ON/OFF) button is pressed (POWER ON/OFF).   
					(b) SWING is started or finished.   
					(c) The power supply turns ON.   
					(4) SWING MODE (   
					) 
					By selecting SWING mode with WIDE VANE button, the vertical vane swings horizontally.   
					The remote controller displays “ ”.   
					(5) WIDE MODE (   
					) 
					By selecting WIDE mode with WIDE VANE button, indoor fan speed becomes faster than setting fan speed on the   
					remote controller ( ). The remote controller displays “ ”.   
					NOTE : The position of vane angle 3, angle 4 and angle 5 are different in COOL operation and HEAT operation.   
					Indoor fan speed becomes faster than setting fan speed on the remote controller even when   
					ed.   
					or   
					is select-   
					16   
				8-8. TIMER OPERATION   
					1. How to set the time   
					(1) Check that the current time is set correctly.   
					NOTE : Timer operation will not work without setting the current time. Initially “0:00” blinks at the current time display   
					of TIME MONITOR, so set the current time correctly with CLOCK SET button.   
					How to set the current time   
					(a) Press the CLOCK set button.   
					(b) Press the TIME SET buttons (   
					• Each time FORWARD button (   
					) to set the current time.   
					and   
					) is pressed, the set time increases by 1 minute, and each time   
					BACKWARD button (   
					) is pressed, the set time decreases by 1 minute.   
					• Pressing those buttons longer, the set time increases / decreases by 10 minutes.   
					(c) Press the CLOCK set button.   
					(2) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.   
					(3) Set the time of timer.   
					ON timer setting   
					(a) Press ON TIMER button(   
					) during operation.   
					(b) Set the time of the timer using TIME SET buttons (   
					OFF timer setting   
					) .   
					).   
					and   
					and   
					(a) Press OFF TIMER button   
					during operation.   
					( 
					) 
					(b) Set the time of the timer using TIME SET buttons (   
					Each time FORWARD button (   
					) is pressed, the set time decreases by 10 minutes.   
					2. To release the timer   
					To release ON timer, press ON TIMER button (   
					To release OFF timer, press OFF TIMER button (   
					) is pressed, the set time increases by 10 minutes; each time BACKWARD button (   
					).   
					).   
					TIMER is cancelled and the display of set time disappears.   
					PROGRAM TIMER   
					• OFF timer and ON timer can be used in combination. The timer of the set time that is reached first will operate first.   
					• “ ” and “ ” display shows the order of OFF timer and ON timer operation.   
					(Example 1) The current time is 8:00 PM.   
					The unit turns off at 11:00 PM, and on at 6:00 AM.   
					(Example 2) The current time is 11:00 AM.   
					The unit turns on at 5:00 PM, and off at 9:00 PM.   
					PM   
					PM   
					PM   
					AM   
					NOTE : If the main power is turned OFF or a power failure occurs while ON/OFF timer is active, the timer setting is can-   
					celled. As these models are equipped with an auto restart function, the air conditioner starts operating with timer   
					cancelled when power is restored.   
					17   
				8-9. EMERGENCY/TEST OPERATION   
					In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor   
					unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote   
					controller run down. The unit will start and OPERATION INDICATOR lamp will light.   
					The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at   
					High speed and the system is in continuous operation (with thermostat ON).   
					After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of   
					75 °F (24 °C). The fan speed shifts to Med.   
					All protective operations such as the coil frost prevention works even in emergency operation.   
					In the test run or emergency operation, the horizontal vane operates in VANE AUTO (   
					) mode.   
					Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any   
					signal from the remote controller. In case of latter normal operation will start.   
					NOTE : Do not press EMERGENCY OPERATION switch during normal operation.   
					HEAT   
					Operation mode   
					COOL   
					(MUZ)   
					75 °F (24 °C) 75 °F (24 °C)   
					Set temperature   
					Fan speed   
					Med.   
					Auto   
					Med.   
					Auto   
					Horizontal vane   
					The operation mode is indicated by the Operation   
					Indicator lamp as following   
					Operation Indicator lamp   
					(MSZ type)   
					E.O.   
					SW   
					EMERGENCY COOL   
					E.O.   
					SW   
					Lighted   
					Not lighted   
					↓ 
					EMERGENCY HEAT   
					STOP   
					EMERGENCY OPERATION switch   
					↓ 
					(MSY type)   
					EMERGENCY COOL   
					↓ 
					STOP   
					8-10. 3-MINUTE TIME DELAY OPERATION   
					When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect   
					compressor from overload.   
					8-11. CHANGING TEMPERATURE INDICATION (°F /°C)   
					• The preset unit is °F.   
					• °F→°C : Press RESET button while the   
					temperature buttons are pressed.   
					• °C→°F : Press RESET button or remove   
					the batteries .   
					Press RESET button gently using   
					a thin stick.   
					18   
				9 
					TROUBLESHOOTING   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					9-1. CAUTIONS ON TROUBLESHOOTING   
					1. Before troubleshooting, check the following   
					1) Check the power supply voltage.   
					2) Check the indoor/outdoor connecting wire for miswiring.   
					2. Take care of the following during servicing   
					1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirm-   
					ing the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.   
					2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic   
					control P.C. board.   
					3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the   
					components.   
					4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.   
					Lead wiring   
					Housing point   
					3. Troubleshooting procedure   
					1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.   
					To make sure, check how many times the abnormality indication is flashing on and off before starting service work.   
					2) Before servicing check that the connector and terminal are connected properly.   
					3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the   
					components for bursting and discoloration.   
					4) When troubleshooting, refer to 9-2., 9-3. and 9-4.   
					4. How to replace batteries   
					Weak batteries may cause the remote controller malfunction.   
					In this case, replace the batteries to operate the remote controller normally.   
					Remove the front lid and insert batteries.   
					Then reattach the front lid.   
					Press RESET button with tip end of ball point pen   
					or the like, and then use the remote controller.   
					Insert the negative pole of the   
					batteries first. Check if the polarity   
					of the batteries is correct.   
					RESET button   
					NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.   
					2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced.   
					This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the   
					battery replacement.   
					19   
				9-2. FAILURE MODE RECALL FUNCTION   
					Outline of the function   
					This air conditioner can memorize the abnormal condition which has occurred once.   
					Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can   
					be recalled.   
					This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   
					1. Flow chart of failure mode recall function for the indoor/outdoor unit   
					Operational procedure   
					The cause of abnormality cannot be found because the abnormality doesn't recur.   
					Setting up the failure mode recall function   
					Turn ON the power supply.   
					<Preparation of the remote controller>   
					While pressing both OPERATION SELECT button and TOO COOL button on the   
					remote controller at the same time, press RESET button.   
					First, release RESET button.   
					And release the other two buttons after all LCD in operation display section of the   
					remote controller is displayed after 3 seconds.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is   
					displayed) with the remote controller headed towards the indoor unit.   
					1 
					1. Regardless of normal or abnormal condition, a short   
					beep is emitted once the signal is received.   
					Does the left lamp of OPERATION INDICATOR   
					lamp on the indoor unit blink at the interval of 0.5   
					seconds?   
					Indoor unit is normal.   
					But the outdoor unit might be abnormal because there are some abnor-   
					malities that can't be recalled with this way.   
					Confirm if outdoor unit is abnormal according to the detailed outdoor unit   
					failure mode recall function.   
					Blinks: Either indoor or outdoor unit is abnormal.   
					No   
					(OFF)   
					Beep is emitted at the same timing as the   
					blinking of the left lamp of OPERATION   
					INDICATOR lamp.   
					Yes   
					(Blinks)   
					2 
					Judgment of indoor/outdoor abnormality   
					Before blinking, does the left lamp of OP-   
					ERATION INDICATOR lamp stay ON for 3   
					seconds?   
					Stays ON for 3 seconds (without beep):   
					The outdoor unit is abnormal.   
					No   
					Yes   
					The outdoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the   
					outdoor unit failure mode table. (Refer to outdoor unit service manual.)   
					The indoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the indoor unit   
					failure mode table. (Refer to 9-2.2)   
					Make sure to check at least two consecutive blinking cycles.   
					Make sure to check at least two consecutive blinking cycles.   
					3 
					2 
					Releasing the failure mode recall function   
					Release the failure mode recall function by the following procedures.   
					•Turn OFF the power supply and turn it ON again.   
					•Press RESET button of the remote controller.   
					Repair the defective parts.   
					Deleting the memorized abnormal condition   
					After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   
					function" mentioned above.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   
					with the remote controller headed towards the indoor unit.   
					Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   
					Release the failure mode recall function according to "Releasing the failure mode recall function"   
					mentioned above.   
					NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   
					2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   
					2. Blinking pattern when the indoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					2.5-second OFF   
					ON   
					OFF   
					Beeps   
					Beeps   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					3.Blinking pattern when the outdoor unit is abnormal:   
					Blinking at 0.5-   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					3-second ON   
					second interval   
					2.5-second OFF   
					3-second ON   
					ON   
					OFF   
					No beep   
					Beeps   
					No beep   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					20   
				2. Indoor unit failure mode table   
					Left lamp of OP-   
					Abnormal point   
					ERATION INDICA-   
					(Failure mode)   
					TOR lamp   
					Condition   
					— 
					Correspondence   
					— 
					Not lighted   
					Normal   
					The room temperature thermistor short or open   
					circuit is detected every 8 seconds during op-   
					eration.   
					1-time flash every Room temperature   
					Refer to the characteristics of the room temperature   
					thermistor (9-7.).   
					0.5-second   
					thermistor   
					2-time flash   
					Indoor coil thermis- The indoor coil thermistor short or open circuit Refer to the characteristics of the main indoor coil   
					2.5-second OFF   
					tor   
					is detected every 8 seconds during operation.   
					thermistor, the sub indoor coil thermistor (9-7.).   
					3-time flash   
					2.5-second OFF   
					The serial signal from outdoor unit is not re-   
					ceived for a maximum of 6 minutes.   
					Refer to 9-6. "How to check miswiring and serial   
					signal error".   
					Serial signal   
					The rotational frequency feedback signal is   
					not emit during the 12 seconds the indoor fan   
					operation.   
					11-time flash   
					2.5-second OFF   
					Indoor fan motor   
					Refer to 9-6. "Check of indoor fan motor".   
					It cannot properly read data in the nonvolatile   
					memory of the indoor electronic control P.C.   
					board.   
					12-time flash   
					2.5-second OFF   
					Indoor control   
					system   
					Replace the indoor electronic control P.C. board.   
					NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-4.).   
					21   
				9-3. INSTRUCTION OF TROUBLESHOOTING   
					Start   
					Indoor unit operates.   
					Indoor unit oper-   
					Indoor unit   
					OPERATION INDICATOR   
					lamp on the indoor unit is   
					flashing on and off.   
					Outdoor unit doesn't   
					ates.   
					doesn't receive   
					the signal from   
					remote controller.   
					operate normally.   
					Outdoor unit   
					doesn't operate.   
					If blinking of OPERATION INDI-   
					Indoor unit   
					Indoor unit   
					Outdoor unit   
					operates only   
					in Test Run   
					operation.   
					Outdoor   
					Unit doesn't   
					operate normal   
					operation in   
					COOL or HEAT   
					mode.   
					CATOR lamp cannot be checked,   
					it can be checked with failure   
					mode recall function.   
					operates, when   
					EMERGENCY   
					OPERATION   
					doesn't operate,   
					when EMERGEN-   
					CY OPERATION   
					switch is pressed.   
					unit doesn't   
					operate even   
					in Test Run   
					operation.   
					switch is pressed.   
					"Test Run operation" means the   
					operation within 30 minutes after   
					EMERGENCY OPERATION   
					switch is pressed.   
					1.Check indoor / out-   
					door connecting wire.   
					(Check if the power is   
					supplied to the indoor   
					unit.)   
					2.Refer to 9-6. "Check   
					of indoor electronic   
					control P.C. board and   
					indoor fan motor".   
					Check room   
					temperature   
					thermistor.   
					Refer to 8-7.   
					"Test point   
					diagram and   
					voltage".   
					Refer to   
					Refer to 9-6.   
					Refer to "How   
					to check   
					inverter/   
					"Check of R.V. "Check of remote   
					coil".   
					controller and   
					receiver P.C.   
					board".   
					Refer to outdoor unit service manual.   
					compressor".   
					Left lamp   
					7-time flash 14-time flash   
					Cause: Cause:   
					Outdoor unit Outdoor unit   
					• Trouble of • Other ab-   
					outdoor con- normality   
					trol system   
					Left lamp   
					Left lamp   
					Left lamp   
					Left lamp   
					Left lamp   
					Left lamp   
					Left lamp   
					6-time flash   
					Cause:   
					Flash on and   
					2-time flash   
					3-time flash 4-time flash 5-time flash   
					off at 0.5-sec- Cause:   
					Cause:   
					Cause:   
					Cause:   
					Outdoor unit   
					• Trouble of   
					thermistor in   
					outdoor unit   
					ond intervals   
					Cause:   
					Indoor unit   
					Indoor unit Indoor unit   
					• Trouble of • Trouble   
					Outdoor unit   
					• Outdoor   
					power   
					• Trouble of   
					room tem-   
					perature /   
					indoor coil   
					thermistor   
					Indoor/ Out-   
					door unit   
					indoor fan   
					motor   
					of indoor   
					unit control   
					system   
					system   
					abnormality   
					• Miswiring or   
					trouble of   
					serial signal   
					Refer to 9-6. Check room Refer to 9-6. Replace the Refer to "How Refer to   
					Replace the Check "Flow   
					inverter P.C. chart of the   
					board or the detailed   
					"How to   
					temperature   
					"Check of indoor elec-   
					to check   
					"Check of   
					check miswir- thermistor   
					ing and serial and indoor   
					signal error". coil thermis-   
					tor.Refer to   
					indoor fan   
					motor".   
					tronic control inverter/ com- outdoor   
					P.C. board.   
					pressor".   
					thermistors". outdoor elec- outdoor unit   
					tronic control failure mode   
					P.C. board.   
					recall func-   
					tion."   
					9-7."Test   
					point diagram   
					and voltage".   
					22   
				9-4. TROUBLESHOOTING CHECK TABLE   
					Before taking measures, make sure that the symptom reappears for accurate troubleshooting.   
					When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection   
					after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR   
					lamp flashing.   
					Lighted   
					OPERATION INDICATOR   
					Blinking   
					Not lighted   
					Abnormal   
					No.   
					1 
					Operation indicator lamp   
					Left lamp flashes.   
					Symptom   
					Condition   
					Correspondence   
					point   
					Indoor unit   
					0.5-second ON   
					Miswiring or   
					serial signal   
					and outdoor The serial signal from the outdoor unit is not   
					• Refer to 9-6. "How to check miswiring   
					and serial signal error".   
					unit do not   
					operate.   
					received for a maximum of 6 minutes.   
					0.5-second OFF   
					Left lamp flashes.   
					Indoor coil   
					thermistor   
					2-time flash   
					Indoor unit   
					• Refer to 9-7.the characteristics of indoor   
					coil thermistor, and the room tempera-   
					ture thermistor.   
					and outdoor The indoor coil or the room temperature   
					2 
					unit do not   
					operate.   
					thermistor is short or open circuit.   
					2.5-second OFF   
					Room   
					temperature   
					thermistor   
					Left lamp flashes.   
					Indoor unit   
					3-time flash   
					Indoor fan   
					motor   
					and outdoor The rotational frequency feedback signal is not • Refer to 9-6. "Check of indoor fan mo-   
					3 
					4 
					unit do not   
					operate.   
					emitted during the indoor fan operation.   
					tor".   
					2.5-second OFF   
					Left lamp flashes.   
					4-time flash   
					Indoor unit   
					and outdoor   
					unit do not   
					operate.   
					It cannot properly read data in the nonvolatile   
					memory of the indoor electronic control P.C.   
					board.   
					Indoor con-   
					trol system   
					• Replace the indoor electronic control   
					P.C. board.   
					2.5-second OFF   
					Left lamp flashes.   
					Indoor unit   
					It consecutively occurs 3 times that the   
					• Refer to "How to check of inverter/   
					5-time flash   
					Outdoor   
					power sys-   
					tem   
					and outdoor compressor stops for overcurrent protection or compressor".   
					5 
					unit do not   
					operate.   
					start-up failure protection within 1 minute after Refer to outdoor unit service manual.   
					start-up. • Check the stop valve.   
					2.5-second OFF   
					Left lamp flashes.   
					6-time flash   
					Indoor unit   
					Outdoor   
					and outdoor The outdoor thermistors short or open circuit • Refer to "Check of outdoor thermistor".   
					6 
					7 
					thermistors   
					unit do not   
					operate.   
					during the compressor operation.   
					Refer to outdoor unit service manual.   
					2.5-second OFF   
					Left lamp flashes.   
					7-time flash   
					Indoor unit   
					and outdoor   
					unit do not   
					operate.   
					It cannot properly read data in the nonvola-   
					tile memory of the inverter P.C. board or the   
					outdoor electronic control P.C. board.   
					• Replace the inverter P.C. board or the   
					outdoor electronic control P.C. board.   
					Refer to outdoor unit service manual.   
					Outdoor con-   
					trol system   
					2.5-second OFF   
					Left lamp flashes.   
					14-time flash   
					Indoor unit   
					• Confirm the abnormality in detail using   
					the failure mode recall function for   
					outdoor unit.   
					Other abnor-   
					mality   
					and outdoor An abnormality other than above mentioned is   
					8 
					unit do not   
					operate.   
					detected.   
					2.5-second OFF   
					23   
				9-5. TROUBLE CRITERION OF MAIN PARTS   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA   
					MSY-D36NA   
					Part name   
					Check method and criterion   
					Figure   
					Room temperature   
					thermistor(RT11)   
					Measure the resistance with a tester.   
					Refer to 9-7. "Test point diagram and voltage", "Indoor electronic control P.C.   
					board", the chart of thermistor.   
					Indoor coil thermistor   
					(RT12(MAIN), RT13(SUB))   
					Indoor fan motor(MF)   
					Check 9-6.   
					. 
					Measure the resistance between the terminals with a tester.   
					(Part temperature 50 ~ 86 °F)   
					Horizontal vane motor (MV1)   
					RED   
					Horizontal vane motor   
					(MV1)   
					Vertical vane motor   
					(MV2)   
					ROTOR   
					Color of the lead wire   
					BRN - other one   
					Normal   
					YLW   
					BRN   
					240 ~ 260 Ω   
					Vertical vane motor (MV2)   
					GRN   
					ORN   
					Color of the lead wire   
					BRN - other one   
					Normal   
					282 ~ 306 Ω   
					24   
				9-6. TROUBLESHOOTING FLOW   
					OPERATION INDICATOR lamp flashes 3-time.   
					Indoor fan does not operate.   
					A Check of indoor fan motor   
					The indoor fan motor error has occurred, and the indoor fan doesn't operate.   
					Turn OFF the power supply.   
					Pay careful attention to the high voltage on the fan motor connector CN211.   
					Turn ON the power supply, wait 5 seconds or more, and then press   
					EMERGENCY OPERATION switch.   
					Measure the supply voltage as follows within 12 seconds after EMER-   
					GENCY OPERATION switch is pressed.   
					If more than 12 seconds passes by, turn OFF the power supply and   
					turn ON it again, then measure the voltage.   
					Is there any foreign matter that   
					interferes the rotation of the line   
					flow fan?   
					No   
					1.Measure the voltage between CN211 (+) and (-).   
					2.Measure the voltage between CN211 (+) and (-).   
					Yes   
					If more than 12 seconds or more passes after EMERGENCY OPERATION   
					switch is pressed, the voltage mentioned above 2 goes 0 VDC although   
					the indoor electronic control P.C. board is normal   
					Remove the foreign matter and   
					adjust the line flow fan.   
					Is there 294/325 VDC between   
					CN211   
					CN211 (+) and (-), and does the   
					voltage between CN211 (+) and   
					(-) rise to the range of 3 to 6 VDC   
					within 12 seconds after EMERGEN-   
					CY OPERATION switch is pressed?   
					Indoor electronic   
					control P.C. board   
					Replace the indoor fan motor.   
					Yes   
					No   
					Replace the indoor electronic control P.C. board.   
					The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.   
					Measure the voltage between CN211   
					Is it unchanged holding   
					(+) and (-) while the fan motor is   
					rotating.   
					Replace the indoor electronic control P.C. board.   
					0 or 15 VDC?   
					No   
					(Changed)   
					Yes   
					(Unchanged)   
					Replace the indoor fan motor.   
					25   
				Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.   
					B Check of remote controller and receiver P.C. board   
					Check if the remote controller is exclusive for this air conditioner.   
					Switch ON the remote controller.   
					Is LCD display on the remote controller   
					Replace the batteries. (Refer to 9-1.4.)   
					visible?   
					No   
					(not clear)   
					Yes   
					Remove the batteries, then set them back   
					and press RESET button. (Refer to 9-1.4.)   
					Check if the unit operates with the remote   
					controller.   
					Does the unit operate with the remote   
					controller?   
					Turn ON a radio to AM and press switch   
					ON the remote controller.   
					No   
					Yes   
					OK   
					Is noise heard from radio?   
					Yes   
					Replace the remote controller.   
					No   
					Are there any fluorescent lights of   
					inverter or rapid-start type within the   
					range of 3.28 ft.?   
					•Reinstall the unit away from lights.   
					•Attach a filter on receiving part.   
					Yes   
					No   
					Measure the voltage between receiver P.C. board   
					connector CN301 No.2(+) and No.3(-) when the   
					remote controller button is pressed.   
					Replace the remote controller.   
					Is the voltage approx. 4VDC?   
					No (5 or 0 VDC)   
					Yes   
					Replace the receiver P.C. board.   
					26   
				The unit does not operate with the remote controller.   
					Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.   
					C Check of indoor electronic control P.C. board and indoor fan motor   
					Turn OFF the power supply.   
					Remove indoor fan motor connector CN211   
					and vane motor connector CN151 from the   
					indoor electronic control P.C. board and turn   
					ON the power supply.   
					Measure the resistance between   
					CN211 and of the indoor fan motor   
					connector.   
					Short/open circuit:   
					Replace the indoor fan motor.   
					Does the unit operate with the remote   
					controller?   
					Does OPERATION INDICATOR lamp light   
					up by pressing EMERGENCY OPERATION   
					switch?   
					Measure the resistance of the horizon-   
					tal vane motor coil.   
					Refer to 9-5.   
					Short/open circuit:   
					Replace the horizontal vane motor and the   
					indoor electronic control P.C. board.   
					Yes   
					No   
					Replace the indoor elec-   
					tronic control P.C. board.   
					Yes   
					Are the varistor(NR11)   
					burnt and the fuse(F11)   
					blown?   
					No   
					Turn OFF the power supply.   
					Check both “parts side” and “pattern   
					side” of the indoor electronic control   
					P.C. board visually.   
					Be sure to check both the fuse   
					and the varistor in any case.   
					Is the fuse(F11) blown   
					only?   
					No   
					Yes   
					1.The fan motor connector's lead wire is red, whereas is   
					black.   
					2.Connect "+" of the tester to fan motor connector's lead   
					wire, and "-" to lead wire, otherwise the resistance cannot   
					be measured properly.   
					Measure the resistance between   
					(+) and (-) of the indoor fan motor   
					connector (to CN211 on the indoor   
					electronic control P.C. board) . 1,   
					2 
					Replace the indoor electronic control   
					P.C. board and the indoor fan motor.   
					Is the resistance 1 MΩ   
					or more?   
					No   
					Yes   
					Replace the indoor electronic   
					control P.C. board   
					Measure the resistance of cement   
					resistor(R111) on the indoor elec-   
					tronic control P.C. board.   
					Is the resistance approx.   
					4 Ω?   
					Replace the indoor electronic control P.C.   
					board and the indoor fan motor.   
					No   
					Yes   
					Replace the indoor electronic control P.C. board.   
					Indoor electronic   
					control P.C. board   
					Varistor(NR11)   
					Fuse(F11)   
					CN211   
					27   
				• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.   
					Indoor unit does not operate.   
					• OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second.   
					Outdoor unit does not operate.   
					D How to check miswiring and serial signal error   
					Turn OFF the power supply.   
					Is there rated voltage AC in   
					Check the power supply.   
					the power supply?   
					No   
					Yes   
					Turn ON the power supply.   
					Is there rated voltage between   
					outdoor terminal block S1 and   
					S2?   
					Check the wiring.   
					No   
					Yes   
					Press EMERGENCY OPERATION switch once.   
					Does the left lamp of OPERATION INDICATOR   
					lamp light up? <Confirmation of the power to   
					the indoor unit>   
					No   
					No   
					Yes   
					Is there any miswiring, poor   
					contact, or wire disconnec-   
					tion of the indoor/outdoor   
					connecting wire?   
					Is serial signal error indicated 6 minutes later?   
					Yes   
					Correct them.   
					Yes   
					Is fuse (F65) broken?   
					No   
					A 
					Turn OFF the power supply.   
					Check once more if the indoor/outdoor   
					connecting wire is not miswiring.   
					B 
					1. Miswiring may damage indoor electronic control   
					P.C. board during the operation.   
					Be sure to confirm the wiring is correct before   
					the operation starts.   
					Short-circuit outdoor terminal block S2   
					and S3.   
					1 
					Turn ON the power supply.   
					Does the LED on the inverter P.C. board or   
					the outdoor electronic control P.C. board   
					repeat "3.6-second-OFF and 0.8-second-   
					ON quick blinking"?   
					Replace the inverter P.C. board or the   
					outdoor electronic control P.C. board.   
					2 
					No   
					(Lighted   
					or not   
					2. Be careful to the residual   
					voltage of smoothing capacitor.   
					Yes   
					lighted)   
					Turn OFF the power supply.   
					Remove the short-circuit between out-   
					door terminal block S2 and S3.   
					Turn ON the power supply.   
					Is there amplitude of 10 to 20 VDC   
					between outdoor terminal block S2 and   
					S3? <Confirmation of serial signal>   
					Yes   
					Is there any error of the in-   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					Replace the indoor/out-   
					door connecting wire.   
					A 
					No   
					Yes   
					• Turn OFF inverter-controlled lighting   
					equipment.   
					• Turn OFF the power supply and then   
					turn ON again.   
					No   
					• Press EMERGENCY OPERATION   
					switch.   
					Is there any error of the in-   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					No   
					Is there rated voltage between   
					indoor terminal block S1 and S2?   
					<Confirmation of power voltage>   
					Replace the indoor/out-   
					Yes door connecting wire.   
					• Reinstall   
					No   
					either the unit   
					or the light   
					each other   
					Yes   
					away.   
					Is serial signal   
					error indicated 6   
					minutes later?   
					• Attach a filter   
					on remote   
					control receiv-   
					ing section   
					of the indoor   
					unit.   
					No   
					Replace the indoor electronic control P.C. board.   
					Yes   
					Be sure to release the failure-mode recall function   
					after checking.   
					B 
					28   
				E Electromagnetic noise enters into TV sets or radios   
					Is the unit grounded?   
					Yes   
					Ground the unit.   
					No   
					Is the distance between the antennas   
					and the indoor unit within 9.91 ft., or is   
					the distance between the antennas and   
					the outdoor unit within 9.91 ft.?   
					Extend the distance between the antennas and   
					the indoor unit, and/or the antennas and the   
					outdoor unit.   
					Yes   
					No   
					Is the distance between the TV sets or   
					radios and the indoor unit within 3.28   
					ft., or is the distance between the TV   
					sets or radios and the outdoor unit   
					within 9.91 ft.?   
					Extend the distance between the TV sets and/or   
					radios and the indoor unit, or the TV sets or   
					radios and the outdoor unit.   
					Yes   
					No   
					Are the antennas damaged?   
					Is the coaxial cable damaged?   
					Is there any poor contact in the anten-   
					na wiring?   
					Replace or repair the antenna.   
					Replace or repair the coaxial cable.   
					Yes   
					Yes   
					No   
					Is the indoor/outdoor connecting wire of   
					the air conditioner and the wiring of the   
					antennas close?   
					Extend the distance between the indoor/outdoor   
					connecting wire of the air conditioner and the wir-   
					ing of the antennas.   
					No   
					Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength   
					or the installation condition (combination of specific conditions such as antennas or wiring).   
					Check the followings before asking for service.   
					1. Devices affected by the electromagnetic noise   
					TV sets, radios (FM/AM broadcast, shortwave)   
					2. Channel, frequency, broadcast station affected by the electromagnetic noise   
					3. Channel, frequency, broadcast station unaffected by the electromagnetic noise   
					4. Layout of ;   
					indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver   
					5. Electric field intensity of the broadcast station affected by the electromagnetic noise   
					6. Presence or absence of amplifier such as booster   
					7. Operation condition of air conditioner when the electromagnetic noise enters in   
					1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic   
					noise.   
					2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller   
					for power ON, and check for the electromagnetic noise.   
					3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the   
					electromagnetic noise.   
					4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the   
					indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.   
					29   
				9-7. TEST POINT DIAGRAM AND VOLTAGE   
					MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA   
					Indoor electronic control P.C. board   
					Power supply input   
					208 / 230 VAC   
					Cement resistor (R111)   
					Varistor (NR11)   
					Fuse (F11)   
					250 V 3.15 A   
					Indoor fan motor   
					(CN211)   
					Release of Auto restart function   
					Solder the Jumper wire JR07   
					(Refer to 7-3.)   
					294 / 325 VDC   
					(-) Fiducial terminal of   
					cathode side on measur-   
					ing high-voltage DC   
					15 VDC   
					(+)3-6 VDC   
					(+)0 VDC or 15 VDC   
					5 VDC   
					Power monitor   
					receiver P.C. board   
					Indoor coil thermis-   
					tor RT12(MAIN)   
					RT13(SUB)   
					(CN112)   
					Horizontal vane   
					motor(CN151)   
					Room temperature   
					thermistor(RT11)   
					(CN111)   
					Timer short   
					mode point   
					} 
					JPG, JPS   
					(Refer to 7-1.)   
					Vertical vane motor (CN152)   
					12 VDC   
					Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)]   
					Room temperature thermistor (RT11)   
					40   
					SW P.C. board   
					30   
					20   
					10   
					0 
					32 50 68 86 104 122 140   
					Temperature (°F)   
					30   
				10   
					DISASSEMBLY INSTRUCTIONS   
					<"Terminal with locking mechanism" Detaching points>   
					The terminal which has the locking mechanism can be detached as shown below.   
					There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.   
					The terminal without locking mechanism can be detached by pulling it out.   
					Check the shape of the terminal before detaching.   
					(1) Slide the sleeve and check if there is a locking lever or not.   
					(2) The terminal with this connector has the   
					locking mechanism.   
					Sleeve   
					ꢀSlide the sleeve.   
					ꢀHold the sleeve, and   
					ꢁPull the terminal while   
					pushing the locking   
					pull out the terminal   
					slowly.   
					Locking lever   
					lever.   
					Connector   
					10-1. MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA   
					OPERATING PROCEDURE   
					PHOTOS   
					1. Removing the panel   
					Photo 1   
					Front panel   
					(1) Press and unlock the knobs on both sides of the front   
					panel and lift the front panel until it is level, and then pull   
					the hinges forward to remove the front panel.   
					(2) Remove the screw caps of the panel.   
					Remove the screws of the panel.   
					(3) Hold the lower part of both ends on the panel and pull it   
					slightly toward you, and then remove the panel by pushing   
					it upward.   
					(4) Remove the screw of the corner box. Remove the corner   
					box.   
					Screw of the   
					corner box   
					Screws   
					Photo 2   
					2. Removing the electrical box, the electronic control P.C.   
					board, the power monitor receiver P.C. board and the SW   
					P.C. board   
					Ground wire to indoor   
					heat exchanger   
					Water cut   
					Screw of   
					electrical side   
					cover   
					(1) Remove the panel and corner box. (Refer to 1.)   
					(2) Remove the screw of the electrical cover. Remove the elec-   
					trical cover.   
					(3) Remove the screw of the V.A. clamp.   
					(4) Remove the V.A. clamp, then remove the indoor/outdoor   
					connecting wire.   
					Screw of elec-   
					trical cover   
					Screw of V.A.   
					clamp   
					(5) Disconnect TAB of the ground wire connected to the indoor   
					heat exchanger.   
					(6) Remove the screw of the electrical side cover. Remove the   
					electrical side cover.   
					SW holder   
					(7) Disconnect all the connectors, TAB and TAB4 on the indoor   
					electronic control P.C. board.   
					(8) Remove the screw on lower side of the electrical box. (See   
					photo 3) Remove the electrical box.   
					(9) Remove the indoor electronic control P.C. board.   
					( 
					( 
					( 
					10   
					) Remove the SW holder from the electrical box.   
					Power monitor   
					receiver holder   
					11   
					) Open the SW holder and pull out the SW P.C. board.   
					12   
					) Remove the power monitor receiver holder from the electri-   
					cal box.   
					( 
					13   
					) Open the power monitor receiver holder and pull out the   
					power monitor receiver P.C. board.   
					31   
				OPERATING PROCEDURE   
					PHOTOS   
					Photo 3   
					3. Removing the nozzle assembly   
					(1) Remove the panel and the corner box. (Refer to 1.)   
					(2) Remove the electrical cover. (Refer to 2.)   
					(3) Remove the electrical side cover, disconnect the vane   
					motor connector.   
					(4) Pull out the drain hose from the nozzle assembly, and   
					remove the nozzle assembly.   
					Screw of electrical   
					box   
					4. Removing the vertical vane motor   
					(1) Remove the nozzle assembly. (Refer to 3.)   
					(2) Remove the crank of the vertical vane motor unit from the   
					vertical vane.   
					Photo 4   
					Screws of the vertical   
					vane motor unit   
					(3) Remove the screw of the vertical vane motor unit, and pull   
					the vertical vane motor unit.   
					(4) Remove the screws of the vertical vane motor unit cover.   
					(5) Remove the crank of the vertical vane motor unit from the   
					shaft of the vertical vane motor.   
					Crank of the vertical   
					vane motor unit   
					(6) Remove the vertical vane motor from the vertical vane   
					motor unit.   
					(7) Disconnect the connector of vertical vane motor from the   
					vertical vane motor.   
					Screws of the vertical vane motor unit cover   
					Photo 5   
					Crank of the vertical   
					vane motor unit   
					5. Removing the horizontal vane motor   
					(1) Remove the nozzle assembly. (Refer to 3.)   
					(2) Remove the screws of the horizontal vane motor unit, and   
					pull out the horizontal vane motor unit.   
					(3) Disconnect the connector from the horizontal vane motor.   
					(4) Remove the screws of the horizontal vane motor.   
					(5) Remove the horizontal vane motor.   
					Screws of the vertical   
					vane motor unit   
					Screws of the vertical vane motor unit cover   
					Photo 6   
					Screws of the   
					horizontal vane   
					motor   
					Screws of the horizontal vane motor unit   
					32   
				OPERATING PROCEDURE   
					PHOTOS   
					Photo 7   
					6. Removing the line flow fan and the indoor fan motor   
					(1) Remove the panel and the corner box. (Refer to 1.)   
					(2) Remove the electrical box. (Refer to 2.)   
					(3) Remove the nozzle assembly. (Refer to 3.)   
					(4) Remove the water cover.   
					Screw of the motor band   
					(5) Loosen the screw of the line flow fan.   
					(6) Remove the screws of the motor bed.   
					(7) Remove the lead wire of the indoor coil thermistor from the   
					hooks of the motor bed.   
					(8) Remove the motor band and the motor bed together with   
					indoor fan motor. (Be careful not to drop the indoor fan   
					motor because it is heavy.)   
					Screws of the motor bed   
					(9) Remove the screw of the motor band, and remove the   
					motor band then pull out the indoor fan motor.   
					(10) Remove the screws of the left side of the heat exchanger.   
					(11) Lift the left side of the heat exchanger.   
					Lead wire of the indoor   
					coil thermistor   
					(12) Remove the line flow fan to the lower-left.   
					Photo 8   
					Photo 9   
					Screws of the left   
					side of the heat   
					exchanger   
					Screw of the line   
					flow fan   
					33   
				34   
				35   
				TM   
					HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   
					Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   
					Distributed in Feb. 2008. No. OBH501 7   
					Made in Japan   
					New publication, effective Feb. 2008   
					Specifications subject to change without notice.   
				 |