AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS
Series
:
COOLING ONLY PR-5,8,10,15,20
:
HEAT PUMP
PRH-5,8,10,15,20
PRH-5,8,10,15,20-L
DATA BOOK
SAFETY FOR USE
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Warning
Erroneous handling may induce serious injury depending on the situation.
Caution
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
Warning
Never repair the unit, remodel or transfer it to
another site by yourself.
If they are performed improperly, water leakage, electric
shock or fire may result. If you need to have the unit
repaired or moved, consult your dealer.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water
leakage, electric shock or fire may be result.
Consult your dealer or specialist subcontractor for
repair and movement.
For installation, conduct the work correctly by
following the Installation Manual.
Improper installation may cause a fire, electrical shock
or water leakage.
Use only the specified refrigerant (R-22) to charge
the refrigerant circuit.
Do not mix it with any other refrigerant and do not allow
air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting
in a rupture and other hazards.
Install the unit on a spot sufficiently durable against
the unit weight.
Insufficient durability can cause an injury by the falling
down of unit.
After completing installation work, make sure that
refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater,
stove, oven and so on, it may generate noxious gases.
All electric work must be performed by licensed
technician, according to local regulations and the
instructions given in this manual.
The units should be powered by dedicated power lines.
Power lines with insufficient capacity or improper
electrical work may result in electric shock or fire.
Take a proper measure to suppress the critical
concentration of refrigerant if leaked when
installing the unit in a small room.
The limit density is made not to be exceeded even if the
refrigerant leaks by any chance.
You are necessary to ventilation measures to prevent
the accident. If the refrigerant leaks, hypoxia accident
may caused.
Use only the specified cables for wiring.
The connections must be made secured without
tension the terminals.
Improper connection or fastening can cause a fire or
electrical shock.
For the countermeasure to be taken, consult your
dealer.
The unit should be installed according to the
instructions in order to minimize the risk of damage
from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the
falling down of the unit.
The terminal block cover of unit must be firmly
attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or
fire.
Use only optional parts authorised by Mitsubishi
Electric.
If the accessories are installed improperly, water
leakage, electric shock or fire may result.
Ask your dealer or an authorised company to install
them.
The unit must be installed on stable, flat surface,
in a place where there is no accumulation of snow,
leaves or rubbish.
The unit should be installed in a location where air
and noise emitted by the unit will not disturb the
neighbors.
If the unit is loosely mounted, it may fall, and cause injury.
- 2 -
Caution
Arrange the configuration of wiring not to bring up
Refrain from installing the unit in an area where
flammable gas can accumulate around the unit.
If the flammable gas can accumulate around the unit, an
explosion can occur.
When the unit is installed at telecommunication
centers or hospitals, take a proper provision
against noise.
The erroneous operation of air conditioner may be
induced by inverter equipment, independent power
device, medical equipment or communication
equipment.
While the erroneous operation of medical equipment or
communication equipment may caused by the air
conditioner.
the panel and terminal cover, and fasten the panel
and terminal cover securely.
The poor mounting of the panel or terminal cover may
cause the heat generation of the terminal connection,
a fire or electrical shock.
Do not wash the unit with water.
If washed with water, electrical shock may be caused.
Do not handle the switch with wet hands.
Otherwise electrical shock can be resulted.
Be very careful on handling the unit.
When carrying in outdoor unit, be sure to support it at
four points.
Carrying in and lifting with 3-point support may make
outdoor unit unstable, resulting in a fall of it.
The unit should not be carried by only one person if it is
more than 20kg.
For special use as for foods, animals/plants,
precision equipment or art objects, the applicability
should be confirmed beforehand.
As the use for the applications other than that
designed originally may result in the deterioration of the
quality. Consult your dealer in this regard.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a
trouble, a place where much machine oil, salt sonnet,
humidity or dust, spa district, a place full of sulfur gas,
volatile gas, or corrosive gas, a place near high
frequency processing machine.
Thermal insulation of the drain pipes is necessary
prevent dew condensation.
If the drain pipes are not properly insulated,
condensation will result and drip on ceiling, floor or other
possessions.
The drain piping must process by surely,and insulate
the drain piping not to be dewy.
Some units use PP bands for packing.
Do not use any PP band for delivery purpose.
Do not touch the heat exchanger fins with your bear
hands.
Doing so may cut your hands.
Be sure to safely dispose the packaging materials.
Packaging materials, such as catches and other metal
or wooden parts, may cause stabs or other injuries.
Tear off and discard plastic packing bags so that
children will not play any of them.
If children play with a plastic bag which was not torn off,
it may cause a risk of suffocation.
The base and attachments of the unit should be
periodically checked for looseness, cracks or other
damage.
If such defects are left uncorrected, the unit may fall and
cause personal injury or property damage.
When the room humidity exceeds 80% or when the
drain pipe is clogged, water may drip from the indoor
unit. The outdoor unit produces condensation during the
heating operation.
Make sure to provide drainage around the outdoor unit if
such condensation is likely to cause damage.
Turn on the main power switch more than 6 hours
before starting operation.
Do not turn the main power switch OFF during seasons
of heavy use, doing so can result In failure.
Do not touch the compressor or refrigerant piping
without wearing glove on your hands.
Touching directly such part can cause a burn or
frostbite as it becomes high or low temperature
according to the refrigerant state.
Do not touch the metal edges inside the unit
without wearing glove on your hands.
Touching directly it may injure your hands.
Do not remove the front panel or the fan guard from
the unit when it is running.
You could be injured if you touch rotating, hot or high-
voltage parts.
Install drain piping according to this Installation
Manual to ensure proper drainage.
Place thermal insulation on the pipes to prevent
condensation.
Improper drain piping may cause water leakage and
damage to furniture or other possessions.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water
pipe, lightning rod or telephone earth wire.
Improper earth connection may cause electrical shock.
When installing at a watery place, provide an
electric leak breaker.
Failure to mount the electric leak breaker may cause
electrical shock.
Use breaker or fuse with proper capacity.
Make sure that there is a main power switch.
Using a wire or a copper wire instead of proper capacity
of fuse can cause fire or trouble.
Other appliances connected to the same line could cause
an overload.
Do not operate the air conditioner without the air
filter set place.
Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop
operation and turn the power source switch off.
Continuing the operation without eliminating the
emergency state may cause a machine trouble, fire, or
electrical shock.
For the power lines, use standard cables of
sufficient current capacity.
Otherwise, current leakage, overheating or fire may
occur.
After stopping operation, be sure to wait for five
minutes before turning off the main power switch.
Otherwise, water leakage or unit failure may occur.
When installing the power lines, do not apply
tension to the cables.
The tighten or loosen the connections may cause generate
heat and cause fire.
- 3 -
A COMPLETE LINE UP
PR-5YC
PRH-5YA
PRH-5YA-L
(PRH ONLY)
Cooling capacity Heatling capacity
14,000 kcal/h
55,600 BTU/h
16.3 kW
13,000 kcal/h
51,600 BTU/h
15.1 kW
PR-8YC
PRH-8YA
PRH-8YA-L
(PRH ONLY)
Heatling capacity
19,800 kcal/h
78,600 BTU/h
23 kW
Cooling capacity
20,500 kcal/h
81,300 BTU/h
23.8 kW
PR-10YC
PRH-10YA
PRH-10YA-L
(PRH ONLY)
Cooling capacity Heatling capacity
25,500 kcal/h
101,200 BTU/h
29.7 kW
27,500 kcal/h
109,100 BTU/h
32 kW
PR-15YC
PRH-15YA
PRH-15YA-L
(PRH ONLY)
Heatling capacity
39,100 kcal/h
155,100 BTU/h
45.5 kW
Cooling capacity
39,800 kcal/h
157,900 BTU/h
46.3 kW
PR-20YC
PRH-20YA
PRH-20YA-L
(PRH ONLY)
Heatling capacity
52,600 kcal/h
208,700 BTU/h
61.2 kW
Cooling capacity
52,300 kcal/h
207,500 BTU/h
60.8 kW
- 4 -
FEATURES
High Sensible Cooling Capacity
Labor Saving Installation
The sensible cooling capacity has been significantly
improved through optimized heat exchanger design.
Because of the single unit configuration, all
refrigeration work can be omitted. The unit operation
can commence immediately after connection to the
power supply, drain piping, ducting and control
system.
Comfort Heating
The PRH series are designed to provide effective heating
even when the outside temperature is down to 0˚C. The
PRH-L series are designed to provide effective heating
even when the outside temperature is down to -10˚C.In
addition, the twin circuit models, PRH-15,20YA,
PRH-15,20YA-L are provided with control features that
prevents both refrigeration circuits defrosting at the same
time. This ensures constant comfort conditions during
defrost and varying loads.
Low Ambient Cooling
In applications with relatively high internal loads,
there may be a requirement for all series to operate
on cooling at low ambient conditions. An optional
accessory is available to maintain the refrigeration
circuit in balance at outdoor temperatures as low as
0˚C (PRH only).In case of PR,PRH-L is -5˚C.
Please consult your local Mitsubishi Electric Sales
office for application advice on this accessory.
Highly Efficient Operation
The EER (Energy Efficiency Ratio) on these models is
greatly improved by revised design specifications and by
being manufactured stringently to Mitsubishi Electric
high quality standards.
Wide Electrical Control Capability
All series may be ordered in either of two control
configurations.
The factory standard is for provision of a 24 volt
terminal block to enable a field wired control of the
contractors choice to be connected.
Flexibility of Supply Air Delivery
Alternatively, for models PR-5-10YC,PRH-5-10YA,
PRH-5-10YA-L the intelligent "K" series remote
control system may be ordered. The K control
utilizes a microprocessor and includes liquid crystal
display with touch pad for adjustment of control
parameters.
These options give the flexibility to enable
connection to Building Management Systems,
smoke spill cycles, economy cycles, remote
monitoring etc.
All series feature belt driven Supply Air fans enabling
accurate matching of actual airflow rates to the specified
quantities. Accurate commissioning is assisted by the
capability to exchange pulleys and belts if necessary to
achieve the desired air balance.
Please consult your local Mitsubishi Electric Sales
office for application advice on these controls.
- 5 -
DESCRIPTIONS
compressors, air-cooled condensers, evaporator
MITSUBISHI ELECTRIC Rooftop Air Conditioners
Series PR,PRH,RPH-L are available in a wide
range of sizes and models to enable the designer
to select the best model for each application.
The complete range has been designed for
outdoor installation, and the units are provided with
the latest technological features to ensure
economical, reliable and comfortable ducted type
air conditioning.
fans, condenser fans and auxiliary and control
equipment, completely packaged in a water-proof
enclosure.
With the development of all series demands for
such features as light weight, compactness,
increased capacity, appropriate static pressure , air
flow control, and having flexibility of inter-facing
energy saving electronic controls Mitsubishi
Electric have met market expectations.
All series units are completely assembled, wired
and strictly tested at the factory. They consist of a
MECHANICAL SPECIFICATIONS
General
Condenser Coils
All units are factory assembled, piped, internally
wired and fully charged with R-22. They are also
tested and checked under a strict quality control
system in the factory. All units are designed for
outdoor rooftop or ground level installation. Exterior
surfaces of all units are phosphatized, zinc-coated
steel with acrylic resin primer and ivory white baked
enamel finish.
Unnecessary power input due to higher
discharge pressure is avoided by high
performance designs of cross-finned coils.
Condenser coils are made of 9.52mm OD,
0.35mm thick seamless copper tubes
mechanically bonded to 0.12mm thick aluminium
plate fins. Each coil is factory pressure and leak
tested at 3.3MPa.
Refrigeration Controls
Evaporator Fans
Refrigeration controls include condenser fan,
evaporator fan and compressor contactor. Each
circuit of the unit has a separate set of refrigeration
controls. PR, PRH,PRH-L-15,20 units have two
independent circuits.
Belt-drive, forward curved, centrifugal type fans
made of galvanized steel are used to deliver an
accurate airflow at low noise level.
Condenser Fan
This direct-drive propeller fan is dynamically
balanced, to ensure smooth airflow. A weather-
proof three-phase squirrel cage induction motor
is used to drive the condenser fan.
Compressors
All units have high efficiency type hermetic line
starting compressors. Compressors are equipped
with thermal overload protector, overcurrent relay
and high pressure protection controls. Crankcase
heaters are standard .
Evaporator Coils
Highly efficient cross-finned coils are applied to
provide a larger cooling capacity with low air speed
on the coil. Coils are made of 9.52mm OD and
0.35mm thick seamless copper tubing
mechanically bonded to 0.12mm thick aluminium
fins and are factory leak tested at a pressure of
3.3MPa. They are provided with strainers attached
to the capillary tubes to further ensure a clean
system.
- 6-
TYPICAL INSTALLATION EXAMPLE
PR
PRH
PRH-L
- 7-
SPECIFICATIONS
PR-5YC
PR-8YC
PR-10YC
PR-15YC
PR-20YC
PRH-5YA
PRH-8YA
PRH-10YA
PRH-15YA PRH-20YA
ITEM
PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L
kW
BTU/h
kcal/h
kW
16.3
55,600
14,000
13
23.8
81,300
20,500
19.7
29.7
101,200
25,500
25.3
46.3
157,900
39,800
38.4
60.8
207,500
52,300
50.2
TOTAL COOLING CAPACITY
(GROSS)
SENSIBLE COOLING CAPACITY
(GROSS)
BTU/h
kcal/h
kW
44,400
11,200
15.1
67,100
16,900
23
86,500
21,800
32
130,900
33,000
45.5
171,400
43,200
61.2
TOTALHEATING CAPACITY
(GROSS)
(PRH-YA,PRH-YA-L ONLY)
BTU/h
kcal/h
%
51,600
13,000
78,600
19,800
0-100
109,100
27,500
155,100
39,100
208,700
52,600
CAPACITY STEPS
REFRIGERANT
0-50-100
R22(FACTORY CHARGED)
CAPILLARY TUBE
REFRIGERANT CONTROL
EXTERNAR FINISH
COLOR(MUNSELL NO.)
HEIGHT
ACRYLIC RESIN COATING
MUNSELL 5Y8/1
mm
mm
mm
kg
1,000
1,200
1,990
1,840
DIMENSION
WIDTH
DEPTH
1,000
299
1,300
1,600
393
NET WEIGHT
COMPRESSOR
MOTOR OUTPUT
INDOOR COIL
FAN
413
698
729
HERMETIC LINE START(RECIPROCATING)
kW
3.73
5.6
7.5
2
X
5.6
2
X
7.5
CROSS FINCOIL
CENTRIFUGAL (GALVANIZED STEEL) - BELT DRIVE
THREE PHASE CAGE INDUCTION MOTOR
FAN MOTOR
FAN MOTOR OUTPUT
kW
CMM
CFM
L/S
0.75
54
1.1
84
1.5
2.2
168
3
100
190
NOMINAL AIR FLOW
1,907
900
10
2,967
1,400
10
3,532
5,934
2,800
20
6,711
3,160
20
1,660
EXTERNAL STATIC
PRESSURE
mmAq
Pa
10
100
100
100
200
200
OUTDOOR COIL
FAN
CROSS FIN COIL
PROPELLER -DIRECT DRIVE
FAN MOTOR
THREE PHASE CAGE INDUCTION MOTOR
X
X
FANMOTOR OUTPUT
kW
CMM
CFM
L/S
0.15
95
0.35
185
0.35
185
2
0.35
185
2
0.35
185
2
X
2
X
NOMINAL AIR FLOW
X
X
3,355
1,583
6,534
3,083
6,534
3,083
25.4
2
6,534
3,083
2
6,534
3,083
2
2
X
X
DRAIN CONNECTION
mm
HIGHPRESSURE SWITCH,FUSE
PROTECTION DEVICES
OVER CURRENT RELAY (COMP.& INDOOR FAN,OUTDOOR FAN)
INTERNAL THERMOSTAT (COMP. & OUTDOOR FAN)
ANTISHORT-CYCLE TIMER,FREEZE & FROST PROTECTOR
NOTE 1. NOMINAL COOLING & HEATING CAPACITIES ARE BASED FOLLOWING CONDITIONS.
COOLING : INDOOR:27˚CDB, 19˚C WB ; OUTDOOR:35˚CDB.
HEATING : INDOOR:21˚CDB ; OUTDOOR:7DB, 6˚C WB.
2. CAPACITIES ARE GROSS CAPACITIES WHICH DO NOT INCLUDE A DEDUCTION FOR EVAPORATOR
FAN MOTOR HEAT.
- 8 -
ELECTRICAL DATA
Cooling
PR-5YC
PR-8YC
PR-10YC
PR-15YC
PR-20YC
PRH-5YA
PRH-8YA
PRH-10YA
PRH-15YA
PRH-20YA
VOLT
ITEM
PRH-5YA-L PRH-8YA-L
PRH-10YA-L PRH-15YA-L PRH-20YA-L
TOTAL INPUT
kW
A
5.4
10.3
73
8.3
15.9
73
11.4
20.2
79
16.8
30.8
76
22.7
39.1
81
TOTAL RUNCURRENT
POWER FACTOR
START CURRENT
%
A
62
87
100
115
135
415V COMPRESSOR INPUT
RUNCURRENT
kW
A
3.92
7.44
1.24
2.26
0.24
0.6
6.46
11.70
1.30
2.90
0.54
1.3
9.22
15.62
1.64
3.28
0.54
1.3
2 X 6.55
2 X 11.74
2.62
2 X9.30
2 X15.22
3.02
I/D FAN INPUT
RUNCURRENT
kW
A
4.72
6.06
O/D FAN INPUT
RUNCURRENT
kW
A
2 X 0.54
2 X 1.3
2 X0.54
2 X 1.3
TOTAL INPUT
kW
A
5.4
11.2
73
8.3
17.3
73
11.4
21.9
79
16.8
33.6
76
22.7
42.6
81
TOTAL RUNCURRENT
POWER FACTOR
START CURRENT
%
A
68
95
109
126
147
380V COMPRESSOR INPUT
RUNCURRENT
kW
A
3.92
8.06
1.24
2.48
0.24
0.66
6.46
12.71
1.30
3.17
0.54
1.42
9.22
16.90
1.64
3.58
0.54
1.42
2 X 6.55
2 X 12.80
2.62
2 X9.30
2 X16.57
3.02
I/D FAN INPUT
RUNCURRENT
kW
A
5.16
6.62
O/D FAN INPUT
RUNCURRENT
kW
A
2 X 0.54
2 X 1.42
2 X0.54
2 X1.42
(PRH,PRH-L Only)
Heating
PRH-5YA
PRH-8YA
PRH-10YA
PRH-15YA
PRH-20YA
VOLT
ITEM
PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L
kW
A
4.8
9.8
68
7.0
14.1
69
9.6
18.2
73
14.4
27.2
74
19.3
34.8
77
TOTAL INPUT
TOTAL RUNCURRENT
POWER FACTOR
%
A
62
87
100
111
131
START CURRENT
415V COMPRESSOR INPUT
RUNCURRENT
kW
A
3.32
6.94
1.24
2.26
0.24
0.6
5.16
9.90
1.30
2.90
0.54
1.3
7.42
13.62
1.64
3.28
0.54
1.3
2 X5.35
2 X9.94
2.62
2 X7.60
2 X13.07
3.02
I/D FAN INPUT
RUNCURRENT
kW
A
4.72
6.06
O/D FAN INPUT
RUNCURRENT
kW
A
2 X0.54
2 X 1.3
2 X0.54
2 X 1.3
kW
A
4.8
10.7
68
7.0
15.4
69
9.6
20.0
73
14.4
29.6
74
19.3
38.1
77
TOTAL INPUT
TOTAL RUNCURRENT
POWER FACTOR
START CURRENT
%
A
68
95
109
121
143
380V COMPRESSOR INPUT
RUNCURRENT
kW
A
3.32
7.56
1.24
2.48
0.24
0.66
5.16
10.81
1.30
3.17
0.54
1.42
7.42
15.00
1.64
3.58
0.54
1.42
2 X5.35
2 X10.8
2.62
2 X7.60
2 X14.32
3.02
I/D FAN INPUT
RUNCURRENT
kW
A
5.16
6.62
O/D FAN INPUT
RUNCURRENT
kW
A
2 X0.54
2 X1.42
2 X0.54
2 X1.42
- 9 -
CAPACITY TABLES
- 10 -
- 11 -
- 12 -
- 13 -
- 14 -
- 15 -
- 16 -
- 17 -
- 18 -
- 19 -
Operation range
PR-YC
Cooling
50
46
40
30
20
10
0
-10
10
15
20 2425
30
Indoor temp.(˚CWB)
PRH-YA
Heating
Cooling
50
46
15
40
10
5
30
20
10
0
- 5
0
-10
10
-10
10
15
20 2425
30
15
20
25 27 30
Indoor temp.(˚CWB)
Indoor temp.(˚CDB)
Heating
Cooling
PRH-YA-L
50
46
15
40
10
5
30
20
10
0
- 5
0
-10
10
-10
10
15
20 2425
30
15
20
25 27 30
Indoor temp.(˚CWB)
Indoor temp.(˚CDB)
- 20-
FAN PERFORMANCE
Airflow
PR-5YC
CMM
45
750
1230
139.7
5.5
165.1
6.5
B39
0.75
1330
139.7
5.5
50
55
60
PRH-5YA
PRH-5YA-L
L/S
830
1320
920
1450
1000
1450
FAN SPEED
rpm
PULLEYSIZE
mm
inch
127
5
139.7
5.5
139.7
5.5
(MOTOR SIDE)
Operation range
100
PULLEYSIZE
(FAN SIDE)
BELT SIZE
mm
inch
inch
kw
139.7
5.5
B36
0.75
1450
139.7
5.5
139.7
5.5
B37
0.75
1580
152.4
6
139.7
5.5
B37
0.75
1580
152.4
6
139.7
5.5
B40
1.1
1610
127
5
139.7
5.5
B39
1.1
1600
139.7
5.5
127
5
B39
1.1
-
-
-
Fan speed
MOTOR
(rpm)
700
600
500
400
300
200
100
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
200
152.4
6
External
static
pressure
(Pa)
1800
1700
B38
0.75
1450
139.7
5.5
139.7
5.5
B37
0.75
1610
127
5.0
114.3
4.5
B35
0.75
MOTOR
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1600
1500
139.7
5.5
B40
1.1
-
114.3
4.5
B37
1.1
-
-
-
-
-
300
1400
MOTOR
1300
1200
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
1100
400
-
-
-
45
750
50
830
60
1000
(CMM)
( / s)
-
-
-
-
-
-
MOTOR
-
-
-
Airflow
Std.
Airflow
CMM
L/S
60
1000
1000
70
1170
1090
80
1330
1310
90
1500
1310
95
1580
1450
PR-8YC
FAN SPEED
rpm
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
mm
inch
mm
114.3
4.5
114.3
4.5
114.3
4.5
114.3
4.5
127
5.0
PRH-8YA
165.1
152.4
127
127
127
100
200
PRH-8YA-L
(FAN SIDE)
BELT SIZE
inch
inch
kw
6.5
B39
1.1
1230
139.7
5.5
165.1
6.5
B41
1.1
1450
127
5.0
127
5.0
B38
1.1
1580
152.4
6.0
139.7
5.5
B40
1.1
1740
152.4
6.0
127
5.0
B39
1.1
6.0
B39
1.1
1320
127
5.0
139.7
5.5
B39
1.1
1450
127
5.0
127
5.0
B38
1.1
1600
139.7
5.5
127
5.0
B39
1.1
1740
152.4
6.0
127
5.0
B36
1.5
5.0
B37
1.1
1450
127
5.0
127
5.0
B38
1.1
1580
152.4
6
139.7
5.5
B37
1.5
1690
177.8
7.0
152.4
6.0
B39
1.5
-
-
-
-
-
-
-
5.0
B37
1.5
1450
127
5.0
127
5.0
B35
1.5
1600
139.7
5.5
127
5.0
B35
1.5
-
-
-
-
-
5.0
B35
1.5
1580
152.4
6.0
139.7
5.5
Operation range
MOTOR
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
Fan speed (rpm)
600
500
400
300
200
100
1800
1700
B37
1.5
External
static
pressure
(Pa)
MOTOR
1600
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.5kW
1500
1400
1.1kW
300
400
500
1300
1200
1100
MOTOR
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1000
60
1000
70
1170
80
1330
90
1500
(CMM)
-
-
-
-
-
-
-
-
(
/ s)
MOTOR
Airflow
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
MOTOR
-
Std.
- 21 -
PR-10YC
Airflow
90
1500
1320
127
CMM
L/S
100
1660
110
1830
120
2000
1550
190.5
7.5
177.8
7.0
B39
2.2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PRH-10YA
PRH-10YA-L
FAN SPEED
rpm
mm
1450
139.7
5.5
1450
139.7
5.5
PULLEYSIZE
(MOTOR SIDE)
Operation range
inch
mm
5.0
139.7
PULLEYSIZE
(FAN SIDE)
BELT SIZE
139.7
139.7
100
200
inch
inch
kw
5.5
B35
1.5
1450
139.7
5.5
139.7
5.5
B36
1.5
1580
152.4
6
139.7
5.5
B37
1.5
1710
165.1
6.5
5.5
B36
1.5
1450
139.7
5.5
139.7
5.5
B36
1.5
1600
139.7
5.5
127
5.0
B33
2.2
1740
152.4
6.0
5.5
B33
2.2
1600
139.7
5.5
127
5.0
B33
2.2
1740
152.4
6.0
127
5.0
B34
2.2
-
Fan speed
MOTOR
(rpm)
600
External
static
pressure
(Pa)
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
500
1800
1700
400
MOTOR
1600
300
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1500
2.2kW
300
200
1400
1.5kW
1300
100
MOTOR
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1200
-
-
-
-
-
-
90
100
1670
110
1830
120
2000
(CMM)
( / s)
400
139.7
5.5
B35
2.2
127
5.0
B34
2.2
1500
Airflow
MOTOR
Std.
Airflow
120
CMM
130
140
2330
690
114.3
4.5
241.3
9.5
150
2500
730
127
5.0
160
170
2830
760
127
5.0
241.3
9.5
180
PR-15YC
L/S
2000
2170
2670
3000
FAN SPEED
rpm
640
101.6
4.0
640
101.6
4.0
730
127
5.0
810
127
5.0
PRH-15YA
PRH-15YA-L
PULLEYSIZE
(MOTOR SIDE)
mm
inch
PULLEYSIZE
(FAN SIDE)
BELT SIZE
mm
inch
inch
kw
228.6
228.6
254
254
228.6
100
200
9.0
9.0
10.0
10.0
9.0
Operation range
B37
2.2
2
B37
2
B39
2.2
2
B41
2
B41
2
B40
2
B39
2
MOTOR
2.2
810
127
5.0
2.2
850
127
5.0
2.2
890
2.2
890
2.2
910
127
5.0
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
760
127
5.0
810
127
5.0
External
static
pressure
(Pa)
Fan speed
139.7
5.5
139.7
5.5
(rpm)
800
241.3
9.5
228.6
9.0
228.6
9.0
215.9
8.5
228.6
9.0
228.6
9.0
203.2
8.0
B40
2
B39
2
B39
2
B38
2
B39
2
B39
2
B37
2
700
MOTOR
2.2
910
127
5.0
2.2
910
127
5.0
2.2
910
127
5.0
2.2
970
127
5.0
2.2
1000
139.7
5.5
2.2
970
127
5.0
3.0
1040
127
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1200
600
5.0
300
400
500
600
203.2
8.0
203.2
8.0
203.2
8.0
190.5
7.5
203.2
8.0
190.5
7.5
177.8
7.0
3.0kW
2.2kW
2
2
2
2
2
2
2
B37
B37
B37
B36
B37
B36
B35
500
MOTOR
2.2
1040
127
2.2
1040
127
2.2
1040
127
2.2
1040
127
3.0
1040
127
3.0
1040
127
3.0
-
1100
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
400
5.0
5.0
5.0
5.0
5.0
5.0
-
1000
177.8
7.0
177.8
7.0
177.8
7.0
177.8
7.0
177.8
7.0
177.8
7.0
-
-
900
300
B35
B35
B35
B35
B35
B35
-
2
2
2
2
2
2
MOTOR
2.2
1120
127
2.2
1140
139.7
5.5
3.0
1120
127
3.0
1120
127
3.0
-
3.0
-
-
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
800
200
-
-
-
5.0
5.0
5.0
-
-
-
700
165.1
6.5
177.8
7.0
165.1
6.5
165.1
6.5
-
-
-
-
-
-
100
600
B34
2
B36
2
B34
2
B34
2
-
-
-
MOTOR
2.2
1210
127
3.0
1230
139.7
5.5
3.0
1230
139.7
5.5
3.0
-
-
-
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
-
-
-
-
-
-
120
2000
140
2330
160
2670
180
3000
(CMM)
/ s)
5.0
-
-
-
(
152.4
6.0
165.1
6.5
165.1
6.5
-
-
-
-
-
-
Airflow
B33
2
B35
2
B35
2
-
-
-
MOTOR
3
3
3
-
-
-
Std.
- 22 -
Airflow
170
2830
730
CMM
L/S
180
3000
810
190
3170
810
200
3330
840
210
3500
910
220
3670
940
FAN SPEED
rpm
PR-20YC
mm
inch
PULLEY SIZE
127
5.0
254
10.0
B43
3.0
127
5.0
228.6
9.0
B41
3.0
910
127
5.0
203.2
8.0
127
5.0
228.6
9.0
B41
3.0
910
127
5.0
203.2
8.0
139.7
5.5
241.3
127
5.0
203.2
8.0
B39
3.0
1000
139.7
5.5
203.2
8.0
139.7
5.5
215.9
(MOTOR SIDE)
PRH-20YA
PRH-20YA-L
PULLEY SIZE
(FAN SIDE)
BELT SIZE
mm
inch
inch
kw
100
200
9.5
8.5
2
2
2
2
2
2
B42
B41
MOTOR
3.0
910
127
5.0
203.2
8.0
4.0
970
127
5.0
190.5
7.5
FAN SPEED
PULLEY SIZE
(MOTOR SIDE)
PULLEY SIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
850
127
5.0
215.9
8.5
B40
3.0
940
139.7
5.5
215.9
8.5
External
static
pressure
(Pa)
Operation range
Fan speed
2
2
B39
2
B39
2
B39
2
B40
2
B38
(rpm)
MOTOR
3.0
1000
139.7
5.5
203.2
8.0
3.0
1040
127
5.0
177.8
7.0
3.0
1040
127
5.0
177.8
7.0
4.0
1040
127
5.0
177.8
7.0
B37
4.0
-
-
4.0
700
FAN SPEED
PULLEY SIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
rpm
mm
inch
mm
inch
-
-
-
-
-
300
400
600
1200
2
2
2
2
2
BELT SIZE
MOTOR
inch
kw
B41
B40
B37
B37
-
-
3.0
1040
127
5.0
177.8
7.0
3.0
1040
127
5.0
177.8
7
4.0
1060
139.7
5.5
190.5
7.5
B39
4.0
-
-
-
-
-
-
-
-
-
-
-
-
-
4.0
1120
127
5.0
165.1
6.5
500
FAN SPEED
PULLEY SIZE
(MOTOR SIDE)
PULLEY SIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1100
-
-
-
-
400
4.0kW
3.0kW
B37
2
B37
2
2
B36
2
1000
300
MOTOR
3.0
1140
139.7
5.5
177.8
7.0
4.0
1120
127
5.0
165.1
6.5
4.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED
PULLEY SIZE
(MOTOR SIDE)
PULLEY SIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
-
-
-
-
-
-
-
900
200
500
800
B38
4
2
B36
2
MOTOR
4
-
-
-
-
-
-
-
100
700
FAN SPEED
PULLEY SIZE
(MOTOR SIDE)
PULLEY SIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1230
139.7
5.5
165.1
6.5
600
170
2830 3000
180
200
3330
220
3670
(CMM)
B37
4.0
2
(
/ s)
MOTOR
-
Airflow
Std.
- 23 -
Pulley outside dimensions are shown below: (Unit : mm)
(1) Shape of belt groove
e
f
Sectional plan of V-belt
w
L0
V-belt
thickness
(Reference)
Shape of Nominal
V-belt Dia. øP.C ( ˚
a
W
L0
K
K0
e
f
r1
r2
r3
16.5mm
)
r1
r3
Over 125
Under 160
34 15.86
a
r2 r2
Over 160
36
38
12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0
1~2
11
16.07
16.29
B
Under 200
40˚
Over 200
B type
(2) Shape of motor pulley boss (Unit : mm)
C
PR-5 10
MOTOR
CAPACITY
A
B
C
PRH-5 10 Pulley for blower & motor
(kW)
+0.009
0
+0.073
+0.040
0.75
19
24
24
28
28
38
15.5
20.0
20.0
23.9
23.9
33.0
6
8
- 0.004
- 0.2
+0.009
- 0.004
0
+0.073
+0.040
1.1
1.5
- 0.2
+0.009
- 0.004
0
+0.073
+0.040
8
- 0.2
+0.009
- 0.004
0
+0.073
+0.040
2.2, 3.0
4.0
8
- 0.2
+0.009
- 0.004
0
+0.073
+0.040
8
- 0.2
+0.018
- 0.002
0
+0.089
+0.050
5.5
10
- 0.2
PR-8 20
PR-5
PRH-5
PR-15,20
PRH-8 20
c
PRH-15, 20 Pulley for blower & motor
MODEL
a
b
c
PR-5
-0.020
0
19
20
20
25
PRH-5
-0.007
- 0.1
PR-8,10
-0.020
-0.007
0
0
- 0.1
16.5
21.0
6
8
PRH-8, 10
- 0.036
-0.020
-0.007
PR-15,20
0
0
- 0.1
- 0.036
PRH-15, 20
(3) Shape of motor (Unit : mm)
L
AC
SHAFT
Diameter
Limits
TBW
AD
AE
+0.009
-0.004
+0.018
-0.002
19 to 28
32 to 48
ED
F
E
øD
Shaft
tapped
DH x EH
deep
Holes
K Dia.
EB
E
AA
AA
LL
A CRS
AB
C
B CRS
BB
BC
Frame Fixing
OUT PUT Size
Shaft
General
ED DH EH AA AB BB BC
A
B
C
H
K
D
E
F
G
L
HA AC AD AE EB LL TBW TBH
0.75
1.1
80
125 100 50
80 10 19
90 10 24
90 10 24
40
50
50
60
60
6
8
8
8
8
15.5 25 M6 16 27 157 127 13.5 295
20 32 M8 19 28 174 152 38.5 320
20 32 M8 19 28 174 152 13.5 320
23.9 40 M10 22 28 184 170 15 371
23.9 40 M10 22 35 218 170 15 377
4
4
4
4
4
5
158 132 102 1.5 75 103 103
178 140 110 1.5 100 103 103
178 140 110 1.5 100 103 103
208 138 120 1.6 23 103 103
215 164 130 1.6 23 131 131
257 189 154 1.6 26 131 131
90SN 140 100 56
90N 140 125 56
1.5
2.2,3.0
4.0
100L 160 140 63 100 12 28
112M 190 140 70 112 12 28
132S 216 140 89 132 12 38
5.5
80 10 33 56 M12 28 38 243 208 53 458
- 24 -
NC CURVES
PR-5YC
PRH-5YA
PRH-5YA-L
50Hz
CONDITION
A scale
62db
63 Hz
67
125 Hz
63
250 Hz
62
500 Hz
61
1000 Hz
57
2000 Hz
50
4000 Hz
45
8000 Hz
43
COOLING &
HEATING
90
80
70
60
50
40
30
20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
10
over
45
63
90
125
180
250
355
500
710
1000
1400
2000
2800
4000
5600
8000
all
octave-band frequency [Hz]
Note. The measuring point is 1m from the comp. service panel.
PR-8YC
PRH-8YA
PRH-8YA-L
50Hz
CONDITION
A scale
64db
63 Hz
70
125 Hz
67
250 Hz
62
500 Hz
60
1000 Hz
58
2000 Hz
56
4000 Hz
52
8000 Hz
50
COOLING &
HEATING
90
80
70
60
50
40
30
20
10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
over
all
45
63
90
125
180
250
355
500
710
1000
1400
2000
2800
4000
5600
8000
octave-band frequency [Hz]
Note. The measuring point is 1m from the comp. service panel.
- 25 -
PR-10YC
PRH-10YA
PRH-10YA-L
50Hz
CONDITION
A scale
64db
63 Hz
71
125 Hz
69
250 Hz
63
500 Hz
61
1000 Hz
59
2000 Hz
57
4000 Hz
49
8000 Hz
44
COOLING &
HEATING
90
80
70
60
50
40
30
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
20
10
over
all
45
63
90
125
180
250
355
500
710
1000
1400
2000
2800
4000
5600
8000
octave-band frequency [Hz]
Note. The measuring point is 1m from the comp. service panel.
PR-15YC
PRH-15YA
PRH-15YA-L
50Hz
CONDITION
A scale 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
COOLING &
HEATING
68db
76
76
68
65
62
59
51
48
90
80
70
60
50
40
30
20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
10
over
45
63
90
125
180
250
355
500
710
1000
1400
2000
2800
4000
5600
8000
all
octave-band frequency [Hz]
Note. The measuring point is 1m from the comp. service panel.
- 26 -
50Hz
PR-20YC
PRH-20YA
PRH-20YA-L
CONDITION
A scale
68db
63 Hz
73.5
125 Hz
77
250 Hz
70
500 Hz
65
1000 Hz 2000 Hz 4000 Hz 8000 Hz
COOLING &
HEATING
60
58
51
48
90
80
70
60
50
40
30
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
20
10
over
all
45
63
90
125
180
250
355
500
710
1000
1400
2000
2800
4000
5600
8000
octave-band frequency [Hz]
Note. The measuring point is 1m from the comp. service panel.
OUTLINE DIMENSIONS
PR-5YC
PRH-5YA
PRH-5YA-L
25
1030
25
16-ø3.5 HOLES
(1030)
25
CONDENSER AIR OUTLET
65
10
25
200
200
850
200
200
25
A
SUPPLY AIR DUCT FLANGE
25
A(DETAIL)
RETURN AIR DUCT FLANGE
6-15X25 MTG HOLES
10
65
900
30
210
210
210
210
30
850
900
75
75
50
40
50
40
1600
16-ø3.5 HOLES
1000
49
607
944
470
SUPPLY AIR
CONDENSER AIR INLET
(2 SIDES)
CONTROL BOX
RETURN AIR
22
22
54.5
80
54.5
971
DRAIN 1B PT
1534
WIRING HOLE
80
4- ø25
SASPENSION HOLES
424
1080
- 27 -
PR-8,10YC
PRH-8, 10YA
PRH-8, 10YA-L
20-ø3.5 HOLES
25
1330
25
(1330)
25
65
10
35
180
180
180
180
180
180
35
CONDENSER AIR
OUTLET
1150
A
SUPPLY AIR DUCT FLANGE
25
A(DETAIL)
RETURN AIR DUCT FLANGE
6-15X25 MTG HOLES
1200
190 190
10
65
30
190
190
190
190
30
75
1150
1200
1300
75
1600
20-ø3.5 HOLES
50
40
50
40
49
607
944
470
SUPPLY AIR
CONTROL BOX
CONDENSER AIR INLET
(2 SIDES)
RETURN AIR
22
54.5
22
54.5
80
80
1271
1380
4-ø25
SASPENSION HOLES
DRAIN 1B PT
1534
WIRING HOLE
424
PR-15,20YC
PRH-15, 20YA
PRH-15, 20YA-L
26-ø3.5 HOLES
25
2010
25
25
2010
62
60 150 200 200 200 200 200 200 200 150
1820
60
10
CONDENSER AIR OUTLET
A
25
SUPPLY AIR DUCT FLANGE
A (DETAIL)
RETURN AIR DUCT FLANGE
1879
6-15X25 MTG HOLES
10
62
39.5
200 200 200 200 200 200 200 200 200 39.5
85
85
1820
1879
1990
26-ø3.5 HOLES
55.5
35
55.5
35
1840
43
717
1080
990
540
SUPPLY AIR
CONTROL BOX
CONDENSER
AIR INLET
(3 SIDES)
RETURN AIR
RETURN AIR
101
131
22
54.5
22
WIRING HOLE
DRAIN 1B PT
1742.7
1951
2060
4-ø25
54.5
556.5
SUSPENSION HOLES
37
- 28 -
WIRING DIAGRAMS
PR-5, 8, 10YC (STANDARD)
Power Supply
3Phase
CIRCUIT BREAKER
(FIELD SUPPLY)
380~415Volt
50Herts
PR- 5YC ···40A
PR- 8YC ···50A
PR-10YC ···60A
TB1
51C
52C
INTERNAL
MC
L1
L2
L3
RED
RED
PROTECTOR
RED
WHITE
WHITE
BLACK
WHITE
BLACK
BLACK
TB2
RED
51F2
TB2
1
RED
R1
RED
R2
S2
T2
MF2
N
BLUE
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
S1
T1
2
3
PE
52F
51F1
RED
RED
WHITE
BLACK
MF1
F
INTERNAL
F
(3.15A)
PROTECTOR
TB3
11
11
TB4
1
SWITCH BOX
(FIELD SUPPLY)
15
51F1
F
SW1
(3.15A)
GL
RL
51F2
63H
FZ1
52C
Tr
23
WA
SW2
51
1
C
AC
AC
24V
220~
240V
3
2
4
5
6
TB4
26L
3
CZ
CZ
CH
52F
CZ
FZ0
FZ1
TM
(3MIN)
52C
8,20YC ONLY
30
CZ
30
CZ
TM
FZ0
FZ1
30
CZ
7
52C
12 TB3
TB3
12
Caution,
Symbol
Name
1.To protect each Fan motors and Compressors from abnormal current,
these Over current relays<51C>,<51F1,2>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is
installed. Therefore,do not change factory set value of this timer.
MC
MF1
MF2
52C
52F
TB1~4
CH
F
Tr
51C
51F1, 2
63H
26L
Compressor motor
Fan motor (in door)
Fan motor (out door)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
Transformer
Over current relay(compressor)
Over current relay (fan I/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Timer (anti short cycle)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (off)
Note:
1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
TM
FZ0·1
CZ
30CZ
<SW1>
<SW2>
<GL>
Switch (on)
Lamp (operation)
<RL>
Lamp (check)
Thermostat (room temp.)
<23WA>
- 29 -
PR-15, 20YC (STANDARD)
CIRCUIT BREAKER
(FIELD SUPPLY)
Power supply
3Phase
380~415Volt
50Hertz
PR -15YC···100A
PR -20YC···125A
MC1
INTERNAL
PROTECTOR
52C1
51C1
TB1
L1
L2
L3
Red
White
Red
Red
White
Black
Black
Black
TB2
R11
51F2
R12
S12
T12
1
2
3
Red
Red
Red
Blue
S11
T11
White
Black
N
White
Black
White
Black
MF2
PE
MC2
51C2
INTERNAL
PROTECTOR
52C2
Red
Red
Red
White
White
Black
Black
INTERNAL
PROTECTOR
Black
TB3
51F3
Red
Red
21
21
21
22
22
22
1
2
3
R
S
T
R
S
T
White
Black
White
Black
MF3
52F
51F1
Red
INTERNAL
PROTECTOR
Red
White
Black
MF1
F
F(3.15A)
TB4 11
TB4 14
51F1
TB5
1
SWITCH BOX
(FIELD SUPPLY)
FZ0
F
30
30
(3.15A)
CZ2-2
CZ1-2
RL1
RL2
SW1
23WA
GL
High
Low
51F2
51F3
SW2
Tr
63
63
AC
H1
H2
CZ1
CZ2
220~
240V
AC
CZ1
CZ2
24V
51C1
1
2
3
4
5
6
7
8
51C2
1
TB5
52 52
C1 C2
52
C2
52
C1
52
TM
TM
CZ1
C2
(3MIN)
(3MIN)
26
L1
26
L2
52
C1
FZ0
CH2
CZ2
52
3
3
F
FZ1
FZ1
TM
CH1
2
52
C1
FZ0
(2SEC)
30
30
30
CZ1-1
30
CZ2-1
CZ1
CZ2
2
FZ1
52
C2
C3Z20-1
C3Z10-1
C3Z10-2
C3Z20-2
9
TB4 12
TB412
Caution,
Symbol
MC1·2
Name
1.To protect each Fan motors and Compressors from abnormal current,
these Over current relays <51C1,2> , <51F1,2,3> are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressors from frequently "ON-OFF" ,timer <TM> is
installed. Therefore,do not change factory set value of this timer.
3.This timer <2> installed so that two compressors may never start at
the same time. The unit stop if the set value of the timer is changed.
Compressor motor
Fan motor (in door)
Fan motor (out door)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
MF1
MF2·3
52C1·2
52F
TB1~5
CH1·2
F
Crankcase heater
Fuse
Note:
Tr
51C1·2
Transformer
1.The dotted lines show field wiring.
Over current relay(compressor)
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
51F1~3 Over current relay (fan I/D,O/D)
63H1·2
26L1·2
TM
2
High-pressure switch
Thermostat(freeze protection)
Timer (anti short cycle)
Timer
5.Specification subject to change without notice.
FZ0·1
Auxiliary relay (fan)
CZ1·2
30CZ1-1,2
30CZ2-1,2
<SW1>
<SW2>
<GL>
Auxiliary relay (compressor)
Auxiliary relay (check)
Auxiliary relay (check)
Switch (off)
Switch (on)
Lamp (power on)
<RL1·2> Lamp (check)
<23WA> Thermostat (room temp.)
- 30 -
PR-5, 8, 10YC
(SPECIAL ORDER : K CONTROL)
Power supply
3Phase
380~415Volt
50Hertz
CIRCUIT BREAKER
(FIELD SUPPLY)
MC
INTERNAL
PR- 5YC ···40A
PR- 8YC ···50A
PR-10YC ···60A
PROTECTOR
TB1
L1
52C
51C
Red
Red
White
Black
Red
L2
L3
White
Black
Black
51F2
TB2
1
2
3
1
2
Red
R
R
N
Blue
White
Black
S1
S 2
MF2
1
2
T
T
PE
52F
51F1
Red
Red
DSA
CN
1
White
Black
MF1
Blue
Green/Yellow
Black
3
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
15
TH2
30
IB
CZ
51F1
51F2
63H
FZ
TB4
A
B
C
D
52F
51C
CZ
FZ
Tr
TH5
CZ
52C
CH
FZ
52C
30
CZ
R/C
30
CZ
8,10YC ONLY
TB3 12
TB3 12
Caution,
Name
Symbol
MC
To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2>are installed.
Therefore,do not change factory set value of these Over current relays.
Compressor motor
Fan motor(indoor)
Fan motor(outdoor)
Contactor(compressor)
Contactor(fan I/D)
Terminal block
Crankcase heater
Fuse
MF1
MF2
52C
52F
TB1~4
CH
F
Tr
51C
51F1,2
63H
FZ
Note:
1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Transformer
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Auxiliary relay(fan)
5.Specification subject to change without notice.
CZ
30CZ
IB
Auxiliary relay(compressor)
Auxiliary relay(check)
Indoor board
TH2
TH5
R/C
DSA
Thermistor(pipe)
Thermistor(room temp.)
Remote controller
Surge absorber circuit board
- 31 -
PR-5, 8, 10YC
(SPECIAL ORDER : LOW TEMPERATURE)
CIRCUIT BREAKER
Power supply
3Phase
380~415Volt
50Hertz
MC
(FIELD SUPPLY)
INTERNAL
PR - 5YC ···40A
PR - 8YC ···50A
PR -10YC ···60A
PROTECTOR
TB1
L1
51C
52C
Red
White
Black
Red
Red
L2
L3
White
Black
Black
51F2
TB2
52F2
TB2
1
2
3
Red
2
2
2
2
2
2
R
1
R
1
R
S
T
R
S
T
Red
Red
White
Black
N
Blue
White
S1
S 1
White
Black
MF2
PE
Black
T
1
T
1
52F1
51F1
51F3
Red
Red
52F3
52F4
White
Black
MF1
Black
Tr1
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
51F3
TB4
1
SWITCH BOX
(FIELD SUPPLY)
15
14
F
51F1
51F2
63H
(3.15A)
RL
SW1
FZ1
GL
23WA
TB4
26D3
SW2
FZ
2
FZ
3
FZ
4
Tr2
FZ
2
AC
220~
AC
51
1
C
240V
24V
2
3
4
5
52
F1
6
26D4
52
F2
52
F4
CZ
FZ2
CZ
26L
3
52
F3
FZ0
TM
52C
CH
52
C
CZ
(3MIN)
FZ3
FZ1
30
CZ
30
FZ
3
CZ
FZ1
52C
FZ0
TM
FZ4
30
CZ
7
8,10YC ONLY
12
TB3 12
Caution,
Symbol
MC
Name
1.To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2,3>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is
installed. Therefore,do not change factory set value of this timer.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
MF1
MF2
52C
52F1
TB1~4
CH
Note:
1.The dotted lines show field wiring.
F
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Tr1·2
51C
51F1,2,3
63H
26L
Transformer
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Timer (anti short cycle)
5.Specification subject to change without notice.
TM
FZ0,1 Auxiliary relay (fan)
CZ
Auxiliary relay (compressor)
30CZ
<SW1>
Auxiliary relay (check)
Switch (off)
<SW2>
<GL>
<RL>
Switch (on)
Lamp (operation)
Lamp (check)
<23WA> Thermostat (room temp.)
52F2~4
FZ2~4
Contactor (fan O/D)
Auxiliary relay (fan O/D)
- 32 -
PR-15, 20YC
(SPECIAL ORDER : LOW TEMPERATURE)
CIRCUIT BREAKER
(FIELD SUPPLY)
Power supply
3Phase
380~415Volt
50Hertz
PR -15YC···100A
PR -20YC···125A
MC1
INTERNAL
PROTECTOR
52C1
51C1
TB1
L1
L2
L3
Red
White
Black
Red
Red
White
Black
Black
TB2
R11 R11
51F2
TB2
52F2
Red
1
2
3
Red
Red
R12
R12
Red
White
Black
Blue
N
White
Black
White
Black
S11 S11
T11 T11
S12 S12
White
Black
MF2
T12
T12
PE
51F4
MC2
51C2
INTERNAL
PROTECTOR
52C2
52F3
Red
Red
Red
White
White
Black
Black
INTERNAL
PROTECTOR
Black
52F4
Tr1
51F3
TB3
TB3
52F5
1
2
3
Red
22
22
22
R
S
T
22
22
22
R
S
T
21
21
R
S
T
21
Red
R
S
T
Red
White
Black
21
White
Black
White
Black
MF3
21
21
51F5
52F6
52F
51F1
Red
INTERNAL
PROTECTOR
52F7
Red
Tr2
White
Black
MF1
F
F(3.15A)
TB4 11
TB5
1
SWITCH BOX
(FIELD SUPPLY)
FZ0
51F1
TB4
11
F
30
30
(3.15A)
CZ1-2
CZ2-2
RL1
RL2
SW1
23WA
51F4
51F2
51F5
High
Low
GL
26D3
26D1
51F3
63
SW
2
FZ
2
FZ
2
FZ
FZ
5
FZ
3
FZ
4
FZ
6
FZ
7
Tr
5
63
AC
H1
H2
51C2
1
CZ1
CZ2
220 ~
240V
AC
CZ1
CZ2
24V
51C1
1
2
3
5
6
8
4
7
TB5
52 52
C1 C2
52
26D4
26D2
C2
52
52
C2
52
F2
52
F4
52
F5
52
F7
TM
TM
FZ2
FZ5
CZ1
C1
(3MIN)
(3MIN)
26
L1
26
L2
52
C1
FZ0
52
F3
52
F6
CZ2
CH2
52
3
3
F
FZ6
FZ3
FZ1
FZ1
TM
CH1
2
FZ
3
FZ
6
52
C1
FZ0
(2SEC)
30
30
30
CZ1-1
30
CZ2-1
CZ1
2
CZ2
FZ1
52
C2
FZ4
FZ7
30
30
C3Z10-1
C3Z10-2
10
CZ2-1
CZ2-2
TB4 12
TB4 12
Symbol
Name
Caution,
1.To protect each Fan motors and Compressors
from abnormal current,these Over current relays<51C1,2>,
<51F1~5>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressors from frequently "ON-OFF",timer<TM>is
installed. Therefore,do not change factory set value of this timer.
3.This timer<2>installed so that two compressors may never start at
the same time. The unit stop if the set value of the timer is changed.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
MC1·2
MF1
MF2·3
52C1·2
52F1
TB1~5
CH1·2
F
Tr1~3
51C1·2
51F1~5
63H1·2
26L1·2
TM
Transformer
Note:
Over current relay(compressor)
Over current relay (fan I/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Timer (anti short cycle)
Timer
1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
2
5.Specification subject to change without notice.
FZ0·1
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Auxiliary relay (check)
Switch (off)
CZ1·2
30CZ1-1, 2
30CZ2-1, 2
<SW1>
<SW2>
<GL>
Switch (on)
Lamp (operation)
<RL1·2>
Lamp (check)
<23WA>
26D1~4
52F2~7
Thermostat (room temp.)
Thermostat (ambiemt temp.)
Contactor (fan O/D)
Auxiliary relay (fan O/D)
FZ2~7
- 33 -
PR-5, 8, 10YC
(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)
CIRCUIT BREAKER
(FIELD SUPPLY)
PR - 5YC ···40A
PR - 8YC ···50A
PR -10YC ···60A
Power supply
3Phase
380~415Volt
50Hertz
MC
INTERNAL
PROTECTOR
TB1
52C
51C
L1
Red
Red
White
Red
L2
L3
White
Black
Black
Black
51F2
TB2
TB2
1
2
3
52F2
R
S
T
R
S
T
R
R2
S 2
T2
1
1
1
1
1
1
2
Red
Red
Red
Blue
N
S 2
T2
White
Black
White
Black
MF2
White
Black
PE
52F1
51F1
51F3
Red
Red
52F3
DSA
CN
1
White
Black
MF1
Blue
Green/Yellow
Black
3
52F4
Tr1
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
TH2
51F3
30
15
14
IB
CZ
51F1
FZ1
51F2
63H
51C
26D3
FZ
2
FZ
2
FZ
3
FZ
4
A
B
C
D
TB4
52
F1
FZ1
CZ
Tr2
26D4
52
F2
52
F4
FZ2
TH5
52
F3
CZ
52C
CH
FZ1
FZ3
52C
30
FZ
3
CZ
R/C
30
CZ
FZ4
8,10YC ONLY
12
TB3 12
Caution,
Symbol
MC
MF1
MF2
52C
52F1
TB1~4
CH
Name
To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2,3>are installed.
Therefore,do not change factory set value of these Over current relays.
Compressor motor
Fan motor(indoor)
Fan motor(outdoor)
Contactor(compressor)
Contactor(fan I/D)
Terminal block
Crankcase heater
Fuse
Note:
1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
F
Tr1·2
51C
51F1,2,3
63H
FZ1
CZ
Transformer
(compressor)
Over current relay
5.Specification subject to change without notice.
Over current relay(fanI/D,O/D)
High-pressure switch
Auxiliary relay(fan)
Auxiliary relay(compressor)
Auxiliary relay(check)
Indoor board
30CZ
IB
TH2
52F2~4
FZ2~4
Thermistor(pipe)
Contactor(fan O/D)
Auxiliary relay(fan O/D)
Thermistor(room temp)
Remote controller
Surge absorber circuit board
TH5
R/C
DSA
- 34 -
PRH-5, 8, 10YA
PRH-5, 8, 10YA-L (STANDARD)
CIRCUIT BREAKER
Power Supply
3Phase
(FIELD SUPPLY)
PRH- 5YA,
PRH- 5YA-L
PRH- 8YA,
···40A
380~415Volt
50Hertz
···50A
···60A
PRH- 8YA-L
PRH-10YA,
TB1
51C
PRH-10YA-L
52C
INTERNAL
MC
L1
L2
L3
RED
RED
PROTECTOR
RED
WHITE
WHITE
BLACK
WHITE
BLACK
BLACK
TB2
RED
51F2
TB2
X1
1
2
3
RED
R1
RED
R2
S2
T2
MF2
N
BLUE
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
S1
T1
PE
52F
51F1
RED
RED
WHITE
BLACK
MF1
F
INTERNAL
F
(3.15A)
PROTECTOR
TB3
11
11
TB4
1
SWITCH BOX
(FIELD SUPPLY)
15
HZ
HZ
13
51F1
F
SW2
14
SW1
(3.15A)
COOL
C
HEAT
GL
RL
51F2
63H
FZ1
52C
Tr
X1
H
SW3
26
D2
23
WA
C
51
1
AC
AC
24V
21
S4
220~
240V
3
2
4
5
6
7
TB4
26L
3
CZ
TM
CZ
CH
52F
CZ
HZ
FZ0
26
D1
X2
FZ1
52C
8,10YA,
YA-L
ONLY
X1
X2
(3MIN)
30
CZ
30
CZ
TM
FZ0
FZ1
30
CZ
8
52C
12 TB3
TB3
12
Caution,
Symbol
Name
1.To protect each Fan motors and Compressors from abnormal current,
these Over current relays<51C>,<51F1,2>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is
installed. Therefore,do not change factory set value of this timer.
MC
MF1
MF2
52C
52F
TB1~4
CH
F
Tr
51C
51F1, 2
63H
Compressor motor
Fan motor (in door)
Fan motor (out door)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
Note:
1.The dotted lines show field wiring.
Transformer
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Over current relay(compressor)
Over current relay (fan I/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Thermostat (defrost)
5.Specification subject to change without notice.
26L
26D1·2
TM
Timer (anti short cycle)
4-Way valve
Auxiliary relay (fan)
21S4
FZ0·1
CZ
HZ
30CZ
X1·2
<SW1>
<SW2>
<SW3>
<GL>
<RL>
Auxiliary relay (compressor)
Auxiliary relay (heater)
Auxiliary relay (check)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (off)
Switch (on)
Lamp (operation)
Lamp (check)
Thermostat (room temp.)
<23WA>
- 35 -
PRH-15, 20YA
PRH-15, 20YA-L (STANDARD)
CIRCUIT BREAKER
(FIELD SUPPLY)
PRH-15YA
PRH-15YA-L
PRH-20YA
Power supply
3Phase
380~415Volt
50Herts
···100A
MC1
···125A
INTERNAL
PRH-20YA-L
PROTECTOR
52C1
51C1
TB1
L1
L2
L3
Red
White
Red
Red
White
Black
Black
Black
TB2
R12
51F2
X1
1
2
3
Red
Red
R11
S11
T11
Red
Blue
N
White
Black
White
Black
S12
T12
White
Black
MF2
MC2
51C2
INTERNAL
PROTECTOR
52C2
Red
Red
Red
White
White
Black
Black
INTERNAL
PROTECTOR
Black
TB3
51F3
X2
1
2
3
21
21
21
22
22
22
R
S
T
R
S
T
Red
Red
White
Black
White
Black
MF3
52F
51F1
Red
INTERNAL
PROTECTOR
Red
White
Black
MF1
F
F(3.15A)
TB4 11
TB5
1
SWITCH BOX
(FIELD SUPPLY)
FZ0
51F1
51F2
HZ
HZ
14
F
30
30
SW1
C
(3.15A)
CZ2-2
CZ1-2
HEAT
COOL
RL1
RL2
SW2
TB4 13
GL
C
H
H
51F3
SW3
High
Low
3
Tr
X1 X2
X2
63
63
23WA
AC
H1
H2
CZ1
CZ2
220~
240V
AC
CZ1
CZ2
24V
51
C1
51
C2
2
4
5
6
7
8
9
26
TB5
52 52
C1 C2
21
52
C2
D4
26
S41
1
1
D3
52
C1
52
TM
TM
21
CZ1
HZ
C2
(3MIN)
(3MIN)
26
L1
26
L2
S42
26
52
C1
FZ0
CH2
CZ2
X4
52
F
26
D2
X3
3
3
D1
FZ1
FZ1
TM
CH1
2
X2
52
C1
FZ0
(2SEC)
30
30
X1
30
CZ1-1
30
CZ2-1
CZ1
CZ2
2
X4
FZ1
X3
52
C2
C3Z20-1
C3Z10-1
C3Z10-2
C3Z20-2
10
TB4 12
TB4 12
Caution,
Symbol
MC1·2
Name
1.To protect each Fan motors and Compressors from abnormal current,
these Over current relays<51C1,2>,<51F1,2,3>are installed.
Compressor motor
Fan motor (in door)
Fan motor (out door)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
MF1
MF2·3
52C1·2
52F
TB1~5
CH1·2
F
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressors from frequently "ON-OFF" ,timer<TM>is
installed. Therefore,do not change factory set value of this timer.
3.This timer<2>installed so that two compressors may never start at
the same time. The unit stop if the set value of the timer is changed.
Note:
Tr
Transformer
1.The dotted lines show field wiring.
51C1·2
51F1~3
63H1·2
26L1·2
26D1~4
TM
Over current relay(compressor)
Over current relay (fan I/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Thermostat (defrost)
Timer (anti short cycle)
Timer
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
2
21S41·42
4-Way valve
FZ0·1
CZ1·2
HZ
30CZ1-1,2
30CZ2-1,2
X1~4
<SW1>
<SW2>
<SW3>
<GL>
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (heater)
Auxiliary relay (check)
Auxiliary relay (check)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (off)
Switch (on)
Lamp (operation)
<RL1·2>
<23WA>
Lamp (check)
Thermostat (room temp.)
- 36 -
PRH-5, 8, 10YA
PRH-5, 8, 10YA-L
(SPECIAL ORDER : K CONTROL)
CIRCUIT BREAKER
(FIELD SUPPLY)
PRH- 5YA,
···40A
Power supply
3Phase
380~415Volt
50Herts
PRH- 5YA-L
PRH- 8YA,
PRH- 8YA-L···50A
PRH-10YA,
PRH-10YA-L···60A
MC
INTERNAL
PROTECTOR
TB1
L1
52C
51C
Red
Red
White
Black
Red
L2
L3
White
Black
Black
51F2
TB2
X1
1
2
3
1
2
Red
R
R
N
Blue
White
Black
S1
S 2
MF2
1
2
T
T
PE
52F
51F1
Red
Red
DSA
White
Black
CN
MF1
Blue
Green/Yellow
Black
1
3
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
15
TH2
HZ
HZ
14
30
IB
CZ
51F1
51F2
13
FZ
X1
63H
51
TB4
A
B
C
D
21
S4
52F
HZ
CZ
FZ
CM
26
D2
Tr
TH5
26
D1
X2
CZ
52C
CH
FZ
X1
52C
30
X2
CZ
R/C
30
CZ
8,10YA,YA-L ONLY
TB3 12
TB3 12
Caution,
Name
Symbol
MC
To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2>are installed.
Therefore,do not change factory set value of these Over current
relays.
Compressor motor
Fan motor(indoor)
Fan motor(outdoor)
Contactor(compressor)
Contactor(fan I/D)
Terminal block
Crankcase heater
Fuse
MF1
MF2
52C
52F
TB1~4
CH
Note:
1.The dotted lines show field wiring.
F
Tr
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Transformer
51C
51F1,2
63H
26D1·2
21S4
FZ
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat(defrost)
5.Specification subject to change without notice.
4-Way valve
Auxiliary relay(fan)
CZ
HZ
30CZ
X1·2
IB
Auxiliary relay(compressor)
Auxiliary relay(heater)
Auxiliary relay(check)
Auxiliary relay(defrost)
Indoor board
TH2
TH5
R/C
DSA
Thermistor(pipe)
Thermistor(room temp.)
Remote controller
Surge absorber circuit board
- 37 -
PRH-5, 8, 10YA
PRH-5, 8, 10YA-L
(SPECIAL ORDER : LOW TEMPERATURE)
CIRCUIT BREAKER
(FIELD SUPPLY)
PRH- 5YA,
···40A
Power supply
3Phase
PRH- 5YA-L
MC
INTERNAL
PRH- 8YA,
PRH- 8YA-L
PRH-10YA,
···50A
380~415Volt
50Herts
PROTECTOR
···60A
TB1
L1
51C
52C
PRH-10YA-L
Red
White
Black
Red
Red
L2
L3
White
Black
Black
51F2
TB2
X1
52F2
TB2
1
2
3
2
2
2
2
2
2
R
1
R
1
R
S
T
R
S
T
Red
Red
Red
White
Black
N
Blue
S1
S 1
White
Black
White
Black
MF2
PE
T
1
T
1
52F1
51F1
51F3
Red
Red
52F3
52F4
White
Black
MF1
Black
Tr1
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
51F3
TB4
1
SWITCH BOX
(FIELD SUPPLY)
HZ
16
15
HZ
14
F
51F1
51F2
63H
SW1
COOL
TB313
(3.15A)
HEAT
RL
SW2
FZ1
GL
C
H
26D3
X1
SW3
23WA
FZ
2
FZ
3
FZ
4
Tr2
FZ
2
AC
21
S4
220~
AC
240V
24V
51
C
26
D2
2
3
4
5
6
7
52
F1
26D4
52
F2
52
F4
CZ
FZ2
TB4
1
CZ
HZ
26
X2
26L
3
52
F3
FZ0
D1
TM
52C
CH
52
C
CZ
(3MIN)
FZ3
X1
FZ1
30
CZ
30
X2
FZ
3
CZ
FZ1
52C
FZ0
TM
FZ4
30
CZ
8
8,10YA,
12
YA-L ONLY
TB3 12
Caution,
Symbol
MC
Name
1.To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2,3>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressor from frequently "ON-OFF",timer<TM>is
installed. Therefore,do not change factory set value of this timer.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
MF1
MF2
52C
52F1
TB1~4
CH
Note:
1.The dotted lines show field wiring.
F
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Tr1·2
51C
51F1,2,3
63H
26L
26D1~4
TM
21S4
Transformer
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Thermostat (defrost)
5.Specification subject to change without notice.
Timer (anti short cycle)
4-Way valve
FZ0,1 Auxiliary relay (fan)
CZ
Auxiliary relay (compressor)
HZ
Auxiliary relay (heater)
Auxiliary relay (check)
Auxiliary relay (defrost)
Switch (operatin mode)
Switch (off)
30CZ
X1·2
<SW1>
<SW2>
<SW3>
<GL>
Switch (on)
Lamp (operation)
<RL>
Lamp (check)
<23WA>
52F2~4
FZ2~4
Thermostat (room temp.)
Contactor (fan O/D)
Auxiliary relay (fan O/D)
- 38 -
PRH-15, 20YA
PRH-15, 20YA-L
(SPECIAL ORDER : LOW TEMPERATURE)
CIRCUIT BREAKER
(FIELD SUPPLY)
PRH-15YA
Power supply
3Phase
380~415Volt
50Herts
···100A
PRH-15YA-L
PRH-20YA
MC1
INTERNAL
···125A
PROTECTOR
PRH-20YA -L
52C1
51C1
TB1
L1
L2
L3
Red
White
Black
Red
Red
White
Black
Black
TB2
R11 R11
51F2
TB2
X1
52F2
1
2
3
Red
R12
S12 S12
T12 T12
R12
Red
Red
Red
Blue
N
White
Black
S11 S11
T11 T11
White
Black
White
Black
White
Black
MF2
PE
51F4
MC2
51C2
INTERNAL
PROTECTOR
52C2
52F3
Red
Red
Red
White
White
Black
Black
INTERNAL
PROTECTOR
Black
52F4
Tr1
51F3
TB3
TB3
52F5
X2
1
2
3
22
22
22
R
S
T
22
22
22
R
S
T
21
21
R
S
T
21
Red
R
S
T
Red
Red
21
White
Black
White
Black
White
Black
MF3
21
21
51F5
52F6
52F
51F1
Red
INTERNAL
PROTECTOR
52F7
Red
Tr2
White
Black
MF1
F
F(3.15A)
TB4 11
TB5
1
SWITCH BOX
(FIELD SUPPLY)
HZ
18
FZ0
51F1
HZ
TB4 14
F
30
30
SW1
C
(3.15A)
CZ1-2
CZ2-2
HEAT
COOL
RL1
RL2
SW2
TB4 13
51F4
51F2
51F5
GL
26D3
FZ
26D1
C
H
H
51F3
63
SW3
FZ
FZ
FZ
5
FZ
3
FZ
4
FZ
6
FZ
7
High
Low
Tr
X1 X2
X2
2
2
5
63
23WA
AC
H1
H2
CZ1
CZ2
220~
240V
AC
CZ1
CZ2
24V
51
51
2
3
4
5
6
7
8
9
C1
C2
26
TB5
52 52
C1 C2
21
52
C2
D4
26
26D4
S41
26D2
1
1
D3
52
52
C2
52
F2
52
F4
52
F5
52
F7
TM
TM
FZ2
FZ5
21
S42
CZ1
HZ
C1
(3MIN)
(3MIN)
26
L1
26
L2
52
C1
FZ0
26
D2
52
F3
52
F6
CH2
CZ2
X4
52
F
26
X3
3
3
D1
FZ6
FZ3
FZ1
FZ1
TM
CH1
2
FZ
FZ
6
X2
52
C1
FZ0
(2SEC)
3
30
30
X1
30
CZ1-1
30
CZ2-1
CZ1
2
CZ2
X4
FZ1
X3
52
C2
FZ4
FZ7
30
30
C3Z10-1
C3Z10-2
10
CZ2-1
CZ2-2
TB4 12
TB4 12
Symbol
Name
Caution,
1.To protect each Fan motors and Compressors
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse
MC1·2
MF1
MF2·3
52C1·2
52F1
TB1~5
CH1·2
F
from abnormal current,these Over current relays<51C1,2>,
<51F1~5>are installed.
Therefore,do not change factory set value of these Over current relays.
2.To protect the compressors from frequently "ON-OFF",timer<TM>is
installed. Therefore,do not change factory set value of this timer.
3.This timer<2>installed so that two compressors may never start at
the same time. The unit stop if the set value of the timer is changed.
Tr1~3
Transformer
Note:
51C1·2
51F1~5
63H1·2
26L1·2
26D1~4
TM
Over current relay(compressor)
Over current relay (fan I/D,O/D)
High-pressure switch
Thermostat(freeze protection)
Thermostat (defrost)
Timer (anti short cycle)
Timer
1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
2
4-Way valve
21S41·42
FZ0·1
CZ1·2
HZ
30CZ1-1, 2
30CZ2-1, 2
X1~4
<SW1>
<SW2>
<SW3>
<GL>
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (heater)
Auxiliary relay (check)
Auxiliary relay (check)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (off)
Switch (on)
Lamp (operation)
<RL1·2>
Lamp (check)
<23WA>
26D1~4
52F2~7
Thermostat (room temp.)
Thermostat (ambiemt temp.)
Contactor (fan O/D)
Auxiliary relay (fan O/D)
- 39 -
PRH-5, 8, 10YA
PRH-5, 8, 10YA-L
(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)
CIRCUIT BREAKER
(FIELD SUPPLY)
PRH- 5YA,
···40A
Power supply
PRH- 5YA-L
3Phase
PRH- 8YA,
···50A
380~415Volt
50Hertz
PRH- 8YA-L
PRH- 10YA
MC
INTERNAL
···60A
PROTECTOR
PRH-10YA-L
TB1
52C
51C
L1
Red
Red
White
Red
L2
L3
White
Black
Black
Black
51F2
TB2
TB2
X1
1
2
3
52F2
R
S
T
R
S
T
R
R2
S 2
T2
1
1
1
1
1
1
2
Red
Red
Red
Blue
N
S 2
T2
White
Black
White
Black
MF2
White
Black
PE
52F1
51F1
51F3
Red
Red
52F3
DSA
White
Black
CN
1
3
MF1
Blue
Green/Yellow
Black
52F4
Tr1
INTERNAL
PROTECTOR
F(3.15A)
TB3 11
11
TH2
51F3
HZ
16
HZ
30
15
14
IB
CZ
TB3 13
51F1
FZ1
51F2
63H
26D3
X1
FZ
2
FZ
FZ
3
FZ
4
A
B
C
D
TB4
2
52
F1
21
S4
FZ1
HZ
CZ
26
D2
Tr2
51
C
26D4
52
F2
52
F4
FZ2
TH5
26
D1
X2
52
F3
CZ
52C
CH
FZ1
FZ3
X1
52C
30
X2
FZ
3
CZ
R/C
30
FZ4
CZ
12
8,10YA,YA-L ONLY
TB3 12
Caution,
Symbol
MC
Name
To protect each Fan motors and Compressor from abnormal current,
these Over current relays<51C>,<51F1,2,3>are installed.
Therefore,do not change factory set value of these Over current relays.
Compressor motor
Fan motor(indoor)
Fan motor(outdoor)
Contactor(compressor)
Contactor(fan I/D)
Terminal block
MF1
MF2
52C
52F1
TB1~4
CH
Note:
1.The dotted lines show field wiring.
Crankcase heater
Fuse
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
F
Tr1·2
51C
51F1,2,3
63H
26D1~4
21S4
FZ1
CZ
HZ
30CZ
X1·2
IB
Transformer
(compressor)
Over current relay
5.Specification subject to change without notice.
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat(defrost)
4-Way valve
Auxiliary relay(fan)
Auxiliary relay(compressor)
Auxiliary relay(heater)
Auxiliary relay(check)
Auxiliary relay(defrost)
Indoor board
TH2
52F2~4
FZ2~4
Thermistor(pipe)
Contactor(fan O/D)
Auxiliary relay(fan O/D)
Thermistor(room temp)
Remote controller
Surge absorber circuit board
TH5
R/C
DSA
- 40 -
ELECTRICAL OPERATION FLOW CHARTS
PR-5, 8, 10YC
START
POWER ON
CH ON
GL ON
30CZ ON (SELF HOLD)
NO
SW2 ON?
YES
FZ0,1 ON (SELF HOLD)
52F ON
MF1 OPERATE
YES
NO
23WA ON?
YES
CZ ON
TM ON
NO
PASS THE 3 MIN.?
YES
52C ON
MC OPERATE
MF2 OPERATE
CH OFF
SAFETY
NO
DEVICE OFF?
YES
30CZ OFF
52C OFF
MC STOP
MF2 STOP
RL ON
CH ON
SERVICE CALL
- 41 -
PRH-5, 8, 10YA
PRH-5, 8, 10YA-L
START
POWER ON
CH ON
GL ON
30CZ ON (SELF HOLD)
NO
SW3 ON?
YES
FZ0,1 ON (SELF HOLD)
52F ON
MF1 OPERATE
NO
NO
SW1 COOL?
HZ ON
YES
21S4 ON
23WA ON?
NO
23WA ON?
YES
CZ ON
YES
CZ ON
TM ON
TM ON
NO
PASS THE 3 MIN.?
YES
NO
PASS THE 3 MIN.?
YES
52C ON
MC OPERATE
MF2 OPERATE
52C ON
MC OPERATE
MF2 OPERATE
CH OFF
CH OFF
SAFETY
NO
DEVICE OFF?
NO
CONDENSING
<
TEMP. -12˚C?
=
YES
30CZ OFF
YES
26D1, 2 ON
52C OFF
MC STOP
MF2 STOP
X1 ON
X2 ON (SELF HOLD)
RL ON
CH ON
21S4 OFF
MF2 STOP
SERVICE CALL
NO
CONDENSING
<
TEMP. 6˚C?
=
YES
26D1, 2 OFF
X1, 2 OFF
21S4 ON
MF2 OPERATE
- 42 -
PR-15, 20YC
START
POWER ON
CH1, 2 ON
GL ON
30CZ1, 30CZ2 ON (SELF HOLD)
NO
SW2 ON?
YES
FZ0, FZ1 ON (SELF HOLD)
52F ON
MF1 OPERATE
YES
NO
23WA No.1 ON?
YES
CZ1 ON
TM1 ON
NO
PASS THE 3 MIN.?
YES
52C1 ON
MC1 OPERATE
MF2 OPERATE
CH1 OFF
NO
23WA No.2 ON?
YES
CZ2 ON
TM2 ON
NO
PASS THE 2 SEC.?
YES
52C2 ON
MC2 OPERATE
MF3 OPERATE
CH2 OFF
NO
No.2 SAFETY
DEVICE OFF?
NO
No.1 SAFETY
DEVICE OFF?
YES
30CZ2 OFF
YES
30CZ1 OFF
52C2 OFF
MC2 STOP
MF3 STOP
52C1 OFF
MC1 STOP
MF2 STOP
RL2 ON
RL1 ON
CH1 ON
CH2 ON
SERVICE CALL
- 43 -
PRH-15, 20YA
PRH-15, 20YA-L
HZ ON
START
POWER ON
21S41, 2 ON
CH1, 2 ON
NO
23WA No.2 ON?
GL ON
YES
CZ1 ON
30CZ1, 30CZ2 ON (SELF HOLD)
TM1 ON
NO
SW3 ON?
NO
NO
YES
PASS THE 3 MIN.?
FZ0, FZ1 ON (SELF HOLD)
YES
52F ON
MF1 OPERATE
TM2 ON
NO
NO
PASS THE 2 SEC.?
YES
SW1 COOL?
YES
52C2 ON
MC2 OPERATE
MF3 OPERATE
23WA No.1 ON?
YES
CH2 OFF
CZ1 ON
TM1 ON
NO
23WA No.1 ON?
YES
NO
PASS THE 3 MIN.?
YES
52C1 ON
MC1 OPERATE
MF2 OPERATE
52C1 ON
MC1 OPERATE
MF2 OPERATE
CH1 OFF
CH1 OFF
NO
No.1 CONDENSING
<
TEMP. -12˚C?
=
NO
23WA No.2 ON?
YES
26D1, 3 ON
YES
CZ2 ON
X1 ON
NO
X3 ON (SELF HOLD)
No.2 CONDENSING
TEMP. -12˚C?
=
TM2 ON
<
21S41 OFF
MF2 STOP
YES
NO
PASS THE 2 SEC.?
YES
26D2, 4 ON
X2 ON
NO
No.1 CONDENSING
<
X4 ON (SELF HOLD)
52C2 ON
MC2 OPERATE
MF3 OPERATE
TEMP. 6˚C?
=
21S42 OFF
MF3 STOP
YES
26D1, 3 OFF
CH2 OFF
No.2 SAFETY
DEVICE OFF?
NO
X1, 3 OFF
NO
No.2 CONDENSING
NO
No.1 SAFETY
DEVICE OFF?
<
TEMP. 6˚C?
=
YES
21S41 ON
MF2 OPERATE
30CZ2 OFF
YES
YES
30CZ1 OFF
52C2 OFF
MC2 STOP
MF3 STOP
YES
No.1 DEFROST
OPERATION?
52C1 OFF
MC1 STOP
MF2 STOP
NO
RL2 ON
21S42 ON
MF2 OPERATE
RL1 ON
CH1 ON
CH2 ON
SERVICE CALL
- 44 -
REFRIGERANT SCHEMATICS
PR-5YC
Condenser
Evaporator
ø19.05
High
Check
pressure
joint
switch
ø19.05
Check
joint
Pressure
gauge
ø12.7
Check
joint
ø22.2
Check
joint
Compressor
Capillary
Tube
ø12.7
ø12.7
Strainer
Dryer
: OPTION
Notes: This schematics shows one refrigerant cycle.
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is
composed of two refrigerant cycles.
PR-8, 10, 15, 20YC
Condenser
Evaporator
ø19.05
High
pressure
switch
Check
joint
ø19.05
Check
joint
Pressure
gauge
ø12.7
Check
joint
ø22.2
Check
joint
Compressor
Capillary
Tube
ø12.7
ø12.7
Strainer
Dryer
: OPTION
- 45 -
PRH-5YA
Condenser
Evaporator
ø19.05
High
pressure
switch
4-Way
valve
Check
joint
Check
joint
ø19.05
Pressure
gauge
ø12.7
Check
joint
ø22.2
Check
joint
Compressor
Capillary
Tube
Capillary
Tube
ø12.7
ø12.7
Strainer
Check Strainer
valve
Dryer
: OPTION
Notes: This schematics shows one refrigerant cycle.
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is
composed of two refrigerant cycles.
PRH-8, 10, 15, 20YA
Condenser
Evaporator
8, 15YA: ø22.0
10, 20YA: ø25.4
High
pressure
switch
4-Way
valve
Check
joint
8, 15YA: ø22.0
10, 20YA: ø25.4
Pressure
gauge
Muffler
ø15.88
ø15.88
Check
joint
Check
joint
ø25.4
Check
joint
Compressor
Capillary
Tube
Capillary
Tube
ø12.7
ø12.7
Strainer
Check Strainer
valve
Dryer
: OPTION
- 46 -
PRH-5YA-L
Condenser
Evaporator
ø19.05
High
pressure
switch
4-Way
valve
Check
joint
Check
joint
ø19.05
Pressure
gauge
ø12.7
Check
joint
ø22.2
Check
joint
Accumulator
Compressor
Capillary
Tube
Capillary
Tube
ø12.7
ø12.7
Strainer
Check Strainer
valve
Dryer
: OPTION
Notes: This schematics shows one refrigerant cycle.
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is
composed of two refrigerant cycles.
PRH-8, 10,15,20YA-L
Condenser
Evaporator
8,15YA-L: ø22.0
10,20YA-L: ø25.4
High
pressure
switch
4-Way
valve
Check
joint
8,15YA-L: ø22.0
10,20YA-L: ø25.4
Pressure
gauge
Muffler
ø15.88
ø15.88
Check
joint
Check
joinøt25.4
Check
joint
Accumulator
Compressor
Capillary
Tube
Capillary
Tube
ø12.7
ø12.7
Strainer
Check Strainer
valve
Dryer
: OPTION
- 47 -
SAFETY & CONTROL DEVICES
PR-5YC
PRH-5YA
PRH-5YA-L
PR-8YC
PRH-8YA
PRH-8YA-L
PR-10YC
PRH-10YA
PRH-10YA-L
ITEM
NO.
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
51C
-
26.0A
27.5A
120˚C OFF
2.94MPa OFF
-2˚C IN
31.0A
110˚C OFF
130˚C OFF
63H
26L
26D1,2
51F1
51F2
-
FREEZE PROTECTOR
FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)
INDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE (CONTROL CIRCUIT)
-12˚C IN, 6˚C OUT
3.2A
2.3A
3.6A
2.0A
150˚C OFF
3.15A
F
FUSE (OPERATION CIRCUIT)
F
3.15A
OUTDOOR FAN MOTOR OVER CURRENT RELAY
(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)
51F3
NO.
2.0A
PR-15YC
PRH-15YA
PRH-15YA-L
PR-20YC
PRH-20YA
PRH-20YA-L
ITEM
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
51C1,2
27.5A
31.0A
-
63H1,2
26L1,2
26D1,2,3,4
51F1
51F2,3
-
120˚C OFF
130˚C OFF
2.94MPa OFF
FREEZE PROTECTOR
-2˚C IN
FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)
INDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE (CONTROL CIRCUIT)
-12˚C IN, 6˚COUT
5.0A
6.6A
2.0A
150˚C OFF
3.15A
F
FUSE (OPERATION CIRCUIT)
F
3.15A
OUTDOOR FAN MOTOR OVER CURRENT RELAY
(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)
51F4,5
2.0A
ACCESSORY AVAILABILITY
PARTS CODE
PRH-8YA
-
MODEL NAME
DESCRIPTION
PR-5YC
PRH-5YA
-
PRH-5YA-L
PR-8YC
PRH-8YA-L
PR-10YC
PRH-10YA
-
PRH-10YA-L
PR- YC-K
PRH- YA-K
PRH- YA-LK
PR- YC
-
-
-
-
-
-
-
-
-
-
-
K-Remote controller
-
-
-
-
-
-
PAC-201LC
-
PAC-202LC
-
PAC-203LC
-
-
PRH- YA
PRH- YA-L
PR- YC
PRH- YA
PRH- YA-L
PR- YC
-
-
PAC-201LC
-
-
-
PAC-202LC
-
-
-
PAC-203LC
-
Lowtemperaturecooling
Pressuregauge
Finguard
-
-
PAC-201LC
-
-
PAC-202LC
-
-
PAC-203LC
PAC001PG
-
-
PAC002PG
-
-
PAC003PG
-
-
-
-
PAC001PG
-
-
PAC002PG
-
-
PAC003PG
-
-
PAC001PG
-
-
PAC002PG
-
-
PAC003PG
PAC101FG
-
-
PAC102FG
-
-
PAC103FG
-
-
PRH- YA
PRH- YA-L
-
-
PAC101FG
-
-
-
PAC102FG
-
-
-
PAC103FG
-
PAC101FG
PAC102FG
PAC103FG
PARTS CODE
DESCRIPTION
MODEL NAME
PR-15YC
PRH-15YA
PRH-15YA-L
PR-20YC
PRH-20YA
PRH-20YA-L
PR- YC
PAC-201LCX2(PCS)
-
-
PAC-201LCX2(PCS)
-
-
Lowtemperaturecooling
PRH- YA
PRH- YA-L
PR- YC
-
-
PAC-201LCX2(PCS)
-
-
-
PAC-201LCX2(PCS)
-
-
-
PAC-201LCX2(PCS)
-
-
PAC-201LCX2(PCS)
PAC001PGX2(PCS)
-
PAC001PGX2(PCS)
-
Pressuregauge
Finguard
PRH- YA
PRH- YA-L
PR- YC
PRH- YA
PRH- YA-L
-
-
PAC001PGX2(PCS)
-
-
-
PAC001PGX2(PCS)
-
-
-
PAC001PGX2(PCS)
-
-
PAC001PGX2(PCS)
PAC104FG
-
-
-
-
PAC105FG
-
-
PAC104FG
-
-
-
PAC105FG
-
PAC104FG
PAC105FG
:Factory install
:Field install
- 48 -
PHYSICAL DATA
[PRODUCT]
ROOFTOP AIR-COOLED HEATPUMP PACKAGED AIR CONDITIONERS
Product type
PR,PRH,PRH-L SERIES
PR-10YC
Product number: Cooling type
PR-5YC
PR-8YC
PR-15YC
PR-20YC
Product number: Heat pump
Product number: Heat pump
PRH-5YA
PRH-5YA-L
PRH-8YA
PRH-10YA
PRH-10YA-L
PRH-15YA
PRH-15YA-L
PRH-20YA
PRH-20YA-L
PRH-8YA-L
28.1
23.8
19.7
8.3
Capacity
kw
kW
kW
kW
17.6
16.3
13
35.2
52.8
46.3
38.4
16.8
0.18
45.5
14.4
70.3
60.8
50.2
22.7
0.11
61.2
19.3
Coolingcapacity(AS1861)
29.7
SensibleCooling capacity(AS1861)
Cooling power consumption(Input)
ByPass Factor
25.3
5.4
11.4
0.19
15.1
4.6
0.24
23
0.18
Heating capacity (AS1861) (Only PRH-YA,PRH-YA-L)
Heating power consumption (Only PRH-YA,PRH-YA-L)
kW
kW
32
7
9.6
[ELECTRICAL]
Design voltage
Cycles
Volts
Hz
415
50
Phases
3
Power supply
Control voltage
Maximum voltage
Minimum voltage
Approx. starting current
Volts
Volts
Volts
Volts
Amps
415
240/24
415
380
100
62
87
115
135
Unit current (Nominal voltage and AS1861
maximum conditions)
Amps
12.8
20.6
25.7
37.9
50.9
Fan motorhp
HP
Amps
rpm
1.0
1.5
2
3
4
Fan motorcurrent
Fan motor speed
[COMPRESSOR]
Make
2.26
1,400
2.90
1,410
3.28
4.72
1,420
6.06
COPELAND
Model
CRNQ-0500-TFD QR90K1-TFD
QR12M1-TFD
QR90K1-TFD
QR12M1-TFD
2
Type
HERMETIC LINE START (RECIPROCATING)
Quantity
1
1
1
2
Nominalmotorhp
Locked rotor current
Normalrun current(AS1861)
Swept volume
HP
Amps
Amps
cc/rev
mm
5
7.5
10
2
✕
7.5
2
✕
10
59.5
7.65
101.92
49.78
26.19
83.4
11.7
177.45
95.2
15.62
221.8
83.4
95.2
2✕
11.74
2
✕
15.22
2
✕
177.45
2
✕221.8
Bore
55.58
4
Stroke
mm
18.29
22.86
2,900
18.29
22.86
Speed
rpm
Numberof cylinders
Oil charge
2
ml
2,070
3,250
2✕3,250
Type of oil
Calumet R015 or Witco 3GS
70
watts
40
2✕70
Crankcase heater
[REFRIGERATION SYSTEM]
Refrigerant
R22
5.8
Refrigerant charge per circuit
Numberof refrigerant controls
Refrigerant control
Reverse cycle valve (Only PRH-YA,PRH-YA-L)
kg
3.6
1
4.6
1
2✕4.6
2✕5.8
1
2
2
Capillary tube
4-Way valve
Reverse cycle defrost
Defrost system (Only PRH-YA,PRH-YA-L)
[EVAPORATOR]
Quantity
1
1
1
2
2
Facearea
sq.m
0.53
3
0.69
4
2✕0.65
Rows deep
3
3
4
Rows high
26
26
26
30
30
Finned length
Face velocity
Fins per meter
Fin materialthickness
Finmaterial
mm
m/s
800
1.7
512
1,046
2.4
2✕850
2.0
2.2
2.4
512
512
0.12
473
2.11
11
512
1.95
15
mm
Aluminium
1.95
Fins pitch
mm
mm
mm
1.95
10
1.95
13
Tube diameter
Gauge of copper tube
Numberof circuits
9.52
0.35
17
- 49 -
[PRODUCT]
ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS
PRH SERIES
Product type
Product number : Heat pump
[INDOOR AIR CIRCUIT]
Number of blowers
PRH-5YA
PRH-8YA
PRH-10YA
PRH-15YA
PRH-20YA
1
2
2
2
2
Diameterof blowers
mm
mm
253
393
282
Width of blowers
Blower drive
182
Beltdrive
1.5
Fan motor output
Normal fan motor run current
Air quantity
kW
A
0.75
2.26
900
1.1
2.2
3.0
2.90
1,400
3.28
4.72
2,800
6.06
3,160
L/s
1,660
Externalstatic pressure
Pa
100
200
Supply air dimensions(h
Return air dimensions(h
[CONDENSER]
Quantity
✕
w)
mm ✕mm
300 ✕850
410 ✕900
300 ✕1,150
410 ✕1,200
428 ✕1,820
464 ✕1,879
✕w)
mm ✕mm
1
1.3
3
1
1.12
3
1
1.46
3
2
2
2✕1.32
3
Facearea
sq.m
2✕1.07
Rows deep
3
Rows high
30
23
30
30
37
Finned length
Face velocity
mm
m/s
1,700
1.2
473
1,920
2✕1,400
2.8
2.1
473
0.12
2.9
2.3
Fins per meter
Fin material thickness
Fin material
473
473
473
mm
Aluminium
Fins pitch
mm
mm
mm
2.11
11
2.11
2.11
9.52
0.35
15
2.11
2.11
Tube diameter
Gauge of copper tube
Numberof circuits
11
1
11
2
14
2
[OUTDOOR AIR CIRCUIT]
Number of fans
1
600
-
1
Diameter of fans
mm
mm
800
645
Pitch of fans
Fan drive
-
-
990
Direct drive
Fan motor output
Quantity
kw
0.15
1
0.35
1
0.35
1
2✕0.35
2
2✕0.35
2
Normal fan motor run current
Fan motor speed
Amps
rpm
0.6
650
1.3
1.3
2✕1.3
2✕1.3
Air quantity
L/s
1,583
3,083
1,300
2✕3,083
[ENCLOSURE AND FRAME]
height
mm
mm
mm
1,000
1,600
1,200
1,990
1,840
Dimension
Color
width
depth
1,000
Munsell 5Y8/1
Panel thickness
mm
mm
1.2
Condensate drain size
25.4
Weight
kg
299
73
393
75
413
75
698
79
729
79
Sound power level
Sound pressure level
dbA
dbA
62
64
64
68
68
- 50 -
INSTALLATION
All series of air conditioners are designed for outdoor installations and are to be placed on a slab or
rooftop, however if the air conditioner is to be installed in a plant room application, please contact your
equipment supplier prior to installation.
Access for both service and installation must be provided to the compressors, control wiring and fans as
shown below.
1.Clearances
(1) Care must be taken to prevent recirculation of
the condenser air. To stabilize compressor
condensing pressures it is recommended that
wherever possible the condenser air inlet side
be faced away from prevailing winds.
(2) For rooftop installation, the type of mounting
base depends on the roof construction. A built-
up roof may not support the weight of the unit
and so it may be necessary to support the unit
by adding structural members below it.
(3) The units are equipped with hoisting
plates for rigging and hoisting of the unit.
The hoisting plates are located in the base
of the unit.
When hoisting the unit with a crane,
spreader bars must be used to prevent
damage to side panels by the supporting
cables.
PR-15,20YC
PRH-15,20YA
PRH-15,20YA-L
PR-5 10YC
PRH-5~10YA
PRH-5~10YA-L
300mm(min. clearance)
300mm(min. clearance)
Condenser inlet
1,000mm(min. clearance)
Evaporator coil service
Condenser inlet
700mm(min. clearance)
Electrical
control circuit
1,000mm(min. clearance)
and compressor
Evaporator coil service
service
Condenser inlet
300mm(min. clearance)
1,000mm(min. clearance)
Evaporator coil service
1,500mm(min. clearance)
Condenser outlet
1,500mm(min. clearance)
Condenser outlet
2.Roof Mounting
(1) The figure shows the use of the roof curb available
for mounting these units.
(2) The curb should be sealed and fixed to the roof by
weather stripping. A suggested means of sealing
the unit and roof curb is shown below.
4-ø15roof mounting holes
6-ø15
Roof curb
Unit mounting holes
Unit
Seal with tar
Roof deck
Roof curb
- 51 -
3.Duct Work
PRH unit
Vertical air
plenum
(1) All series units are equipped with horizontal
supply and return air openings. Duct connection to
the unit should be made with duct flanges and
secured directly to the air openings with flexible
duct connectors to avoid normal noise transmission.
Plenum
divider
Insulation
Roof curb
(2) For vertical air supply, a field supply plenum should
be used.
The figure below shows the recommended method
for duct connection.
Roof curb
Duct
(3) To prevent air leakage, all duct seams should be
taped.
Roof line
Duct
Singleduct
divider
Ducts run in air spaces that are not air-conditioned
must be insulated and provided with a vapor barrier.
Ducts exposed to the outside must be
weatherproofed. For quiet operation, we
recommend that the insulation on the supply duct
be placed inside, lining the duct.
Duct connection with a vertical air plenum
(4) Where ducts from the outside enter a building, the
duct openings in the building should be sealed with
weather stripping to prevent rain, duct, sand,etc.
from entering the building.
(5) Correctly sized filters must be fitted and there is no
provision within the unit, however the filters may be
installed in the return air.
4.Drain piping
(1) A 1 FPT condensate drain fitting is provided. The
drain pipe can be led out at the right or left side.
Under standard specifications, it is led out at the left
side and the right side is covered.
>
A 70mm
=
>
B 2C
Drain piping
=
>
C 2XE.S.P
=
(2) The drain pipe must be provided with a trap on the
outside of the unit and also installed at an incline for
proper drainage, as shown below.
The drain pipe
should extend
below this level.
Drain trap
Note:ESP=External Static Pressure
(3) To prevent condensate formation and leakage,
provide the drain pipe with insulation to safeguard
against sweating.
Drain trap for condensate
(4) Upon completion of the piping work, check that there
is no leakage and that the water drains off properly.
- 52 -
5.Electrical Wiring
Remove the panel on the right side (PR,PRH-5 10) or the rear side (PR,PRH-15,20) of the unit and
connect the units power supply wiring to the proper terminals in the control box, as shown below.
PR-5YC
PRH-5YA
PRH-5YA-L
PR-8YC
PRH-8YA
PRH-8YA-L
PR-10YC
PRH-10YA
PRH-10YA-L
PR-15YC
PRH-15YA
PRH-15YA-L
PR-20YC
PRH-20YA
PRH-20YA-L
MODEL
INDOOR FAN MOTOR OUTPUT <kW>
2
0.75
1.1
1.1
1.5
1.5
2.2
2.2
3.0
3.0
4.0
<mm
mm
>
>
5.5
5.5
40
5.5
5.5
50
8
8
22
22
22
22
POWER SUPPLY
EARTH
WIRING
2
<
< A >
60
100
100
MAIN SWITCH
Std.
Control box
Terminal block
Terminal block
Control box
power supply
power supply
Wiring for PR,PRH-15,20(rear view)
Wiring for PR,PRH-5 10(right side view)
TN-NET SYSTEM (For European models only)
L1
L2
L3
N
PE
Note:
All electrical wiring must be comply with local electrical authority regulations.
6.Final Checks
After having installed the unit, check that:
(1) The unit is fixed securely.
(2) The unit is installed properly.
(3) The drain pipe is provided with a drain trap.
(4) The electrical wiring has been connected correctly and the terminal screws have been properly
tightened.
(5) The duct work has been performed correctly.
7.Trial Operation
(1) Before turning the unit on, measure the resistance between the terminals of the electrical parts and
ground with a 500V megger and check that the value is at least 1MΩ. If the measured value is below 1MΩ,
do not operate the unit.
(2) Check the operation of the high pressure switch by activating it. Operation should stop when the two leads
of the outdoor unit fan motor are removed from the contactor and cooling continues for 5~10min.
(3) Check that the indoor and outdoor fans are rotating in the proper direction.
(4) After having checked the above points, proceed with a trial operation of the unit.
- 53 -
INSTRUCTIONS FOR USE
1.CHECK POINTS FOR OPERATION
Check the following points before you operate your air conditioner.
(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.
Indoor Unit
Outlet grille
Inlet grille
Ceiling
Ceiling
Obstacle blocking air inlet
Obstacle blocking air inlet
Outdoor Unit
Obstacle blocking air inlet
(2) Make sure the air conditioner is properly grounded by checking the ground terminal .
Ground
- 54 -
2.CAUTION FOR USE
Keep the following points in mind to safeguard against failures and breakdowns.
(1) This air conditioner does not restart within 3min.
after shut down.
3 Minutes
(These models have a crankcase heater in the
Shutdown
Operation
compressor. If the air conditioner is shut down
for a short time, please do not turn the power
switch to OFF, but turn the operation switch to OFF.)
(2) If the air conditioner is shut down by a power failure,
set the operation switch to OFF. When the power is
restored, normal air conditioner operation can be
resumed.
(3) Do not stick rods or other objects through the air
outlet during operation since this may result in
equipment damage or personal injury.
3.MAINTENANCE
For superior performance and lasting durability, please do not forget to conduct
proper and regular maintenance.
3.1 Cleaning the Air Filter
Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location. Clean
more regularly if the air filter gets very dirty.
If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate. Failure to
clean the air filter may result in equipment breakdown or malfunctions.
3.2 Cleaning panels
Clean dirt off front panel as follows.
Fingermarks
Use a household neutral cleanser such as for
dishes or vegetables. Moisten a soft cloth with
Neutral
Cleanser
the cleanser, then wipe lightly. Next,wipe three
or four times with another soft cloth moisten
Grease
with water. Finally, wipe off all the remaining
cleanser with a soft cloth.
Moisten a soft cloth with the alcohol, then wipe
off lightly. Isopropyl alcohol is sold at stores as
reagents in small quantities.
Adhesive
Isopropyl
alcohol
Note:
Alcohol is highly combustible. Take extreme
Paste
care when handling. Also, do not use paint or
adhesive thinner.
3.3 Cleaning the Outdoor Unit Heat Exchanger
If you use your air conditioner for prolonged periods,
the outdoor heat exchanger will become dirty, impairing
its function and reducing air conditioners performance.
Consult your equipment supplier or air conditioning
contractor on how to clean the heat exchanger.
Heat exchanger
Heat exchanger
- 55 -
4. PREPARING FOR OPERATION AFTER PROLONGED SHUTDOWN
When the usage season starts, proceed with the following before starting operation:
(1)Clean the air filter.
(2)Do not use the unit immediately. Turn the main power switch on for a period of 3 hours before restarting
cooling / heating operation. This allows the compressors to come up to the correct operation temperatures.
Failure to do this, could cause compressor failure.
5.PREPARING FOR PROLONGED SHUTDOWN
After the usage season is over, prepare the air conditioner for later use by:
(1)Setting the power switch to OFF.
(2)Consulting your Air conditioning specialist for detailed information.
6.TROUBLESHOOTING
If any trouble occurs, turn the operation (start or run) switch off immediately.
Symptom
Possible cause
Power failure.
Remedy
Wait for power supply
recovery.
Both fan and compressor
do not run.
Blown fuse of power
source switch.
Contact your
Air conditioning specialist
.
Excessively low power
source voltage.
Ask your electric power
company.
For temperature control,
• decrease the set
temperature at cooling.
• increase the set
temperature at heating.
The set temperature of
thermostat is
• excessively high for
cooling.
• excessively low for
heating.
Fan runs but compressor
does not run.
Can not be operated as
it is out of temperature
control range.
The room temperature is
• excessively low for
cooling.
• excessively high for
heating.
Air outlet and inlet
are blocked.
Remove blocking matter.
Clean it.
Fan runs but stops
immediately.
The filter installed in
the field is clogged
with dust.
Windows and doors are
being opened.
Close them.
Air outlet and inlet
are blocked.
Remove blocking matter.
Runs but without
cooling/heating.
For temperature control,
• decrease the set
temperature at cooling.
• increase the set
temperature at heating.
The set temperature of
thermostat is
• excessively high for
cooling.
• excessively low for
heating.
Insufficient
refrigerant charge.
Contact your
Air conditioning specialist
.
Note:
If the unit does not operate normally after troubleshooting, please contact your local equipment supplier or
air conditioning contractor.
- 56 -
SPECIFICATION GUIDELINES
Please supply and install a one piece, air to air reverse cycle air conditioning system.
The system shall be completely assembled, tested and have a complete refrigeration charge ready for
installation and operation from the factory.
The system shall operate at outdoor ambient temperatures as high as 46˚C.
The system shall have a total cooling capacity of
L/s at ˚C db and ˚C wb entering indoor coil temperature with a
entering
the outdoor coil.
kW or greater with an indoor air quantity of
˚C temperature
The system shall have a sensible heat capacity of
˚C.
kW or greater with a room db temperature of
The total heating capacity (without electric element heaters) shall be
kW or greater at
˚Cdb,
˚C wb outdoor air conditions, with
˚C of indoor air entering indoor coil at ˚C db. One
kW electric heater element (accessory) shall be furnished.
The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be
equipped with a crankcase heater.
Compressors shall be protected by a factory installed anti-cycle device and provide a 3 minute delay before
compressor can restart.
Coils shall be of non-ferrous construction with mechanically bonded aluminium plate fins. Outdoor coils
shall be made, of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick
aluminium plate fins.
Coils with multiple stage refrigeration systems shall consist of independent circuits. Face area of the coil
2
shall not be less than
M . The coil shall be factory pressure and leak tested at 3,233 kPa pressure.
2
The indoor coil face area shall be not less than
M .
Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure
smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel
cage
kW induction motor.
The system shall be factory wired and all electrical wiring must comply with the Local wiring code. (Controls
and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal
and current sensitive overload devices.
An automatic defrost control shall be included to accomplish defrosting (only if required) every
minutes for a period of
minutes.
A low voltage transformer (24V) shall be factory installed in the unit for an external control circuit.
High pressure switch (pre-set) shall be factory installed.
The enclosure shall be a single, enclosed, weatherproof casing constructed of phosphatised, zinc coated
steel with acrylic resin primer and ivory white baked enamel finish.
The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be
located in the base of the unit.
The unit shall have a 25mm OD male drain connection provided. The drain pipe shall be accessible from
either the left or right side of the unit. A blanking cap shall be provided to cap the drain outlet not being
used.
The duct (field supply) shall be fully insulated with fiber glass insulation to prevent sweating and to minimize
sound.
Each unit shall have a drain pan of 1mm thick steel coated with epoxy resin enamel.
The enclosure shall have openings provided for power connections. Access for both service and installation
shall be provided to compressors, control wiring, filters, electric heaters (when fitted) and fans.
Side panels and top panels shall be removable for easy service access.
The unit maximum dimensions shall be : height:
mm, width:
mm and depth:
mm.
Due to continuous product development, these guidelines are subject to change.
- 57 -
MEMO
- 58 -
DATA BOOK PR,PRH
MITSUBISHI ELECTRIC CORPORATION
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100,TELEX J24532 CABLE MELCO TOKYO
New publication effective Jan. 1999.
Specifications subject to change without notice.
Issuued in January. 1999 MEE98K036
Printed in Japan.
|
Polar Automobile Parts Fin 90440 User Manual
Ohlins 951 6001126 User Manual
Motorola P893 User Manual
Manual Control Universal General Electric 72521 User Manual
GE DDE7206R User Manual
GBC PRO 3600 User Manual
FUJITSU SCANSNAP S1100 02 User Manual
EMERSON SR400 User Manual
CRAFTSMAN 315.212500 User Manual
CRAFTSMAN 172.10855 User Manual