Lifebreath 195ecm User Manual

Model 195ECM  
ENGINEERING DATA  
Performance  
Net supply air flow in cfm (L/s) against external static pressure  
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE  
The cross-flow heat recovery core transfers heat between the two airstreams. The two  
cores are arranged for highly efficient counter current airflow.  
E.S.P  
(external static pressure)  
[cfm (L/s)]  
MOTORS AND BLOWERS  
Each air stream has one centrifugal blower driven by a common ECM motor. 5 speed  
fan operation. 120 VAC, 1.4 Amps.  
@ 0.1" (25 Pa)  
@ 0.2" (50 Pa)  
@ 0.3" (75 Pa)  
@ 0.4" (100 Pa)  
@ 0.5" (125 Pa)  
@ 0.6" (150 Pa)  
@ 0.7" (175 Pa)  
171 (81)  
164 (77)  
156 (74)  
143 (67)  
134 (63)  
126 (59)  
119 (56)  
FILTERS  
Washable air filters in exhaust and supply air streams.  
MOUNTING THE HRV  
Four threaded inserts at corners of case designed to accept four reinforced polyester  
straps that are supplied with the unit.  
DEFROST  
Damper defrost system.  
Max. Temperature Recovery  
88%  
DEHUMIDISTAT  
Adjustable Internal Dehumidistat.  
Sensible Effectiveness  
@ 114 cfm (54 L/s)  
32°F (0°C)  
32°F (0°C)  
88%  
81%  
CASE  
*Sensible Efficiency  
@ 114 cfm (54 L/s)  
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.  
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.  
*Sensible Efficiency  
@ 119 cfm (56 L/s)  
CONTROLS  
-13°F (-25°C)  
77%  
120  
34  
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).  
Control pad can be removed from HRV and remotely mounted.  
VAC @ 60HZ  
WATTS / Low speed  
WATTS / High speed  
Amp rating  
Weight 106 lbs. (48 kg) Shipping Weight 108 lbs. (49 kg)  
95  
OPTIONAL MAIN CONTROLS  
99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20  
gauge wire (min.) 100’ length  
1.4  
*Sensible Efficiency – thermal **Latent Efficiency – moisture  
Note: Effectiveness - based on temp. differential between the 2 airstreams  
Efficiency – takes into account all power inputs  
99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted  
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length  
99-250 Ventilation Dehumidistat designed to accept remotely mounted Control  
Pad, (4 wire) 20 gauge wire (min.) 100’ length  
OPTIONAL TIMERS  
99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60  
minutes, (3 wire) 20 gauge wire (min.) 100’ length  
99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire)  
20 gauge wire (min.) 100’ length  
OPTIONAL ACCESSORIES  
220  
200  
180  
160  
140  
120  
100  
80  
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)  
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)  
99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen  
60  
WARRANTY  
40  
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement  
parts warranty.  
20  
0
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
Static Pressure (in w.g.)  
DIMENSIONS 195ECM inches (mm)  
All units conform to  
CSA and UL standards.  
METAL CLASPS  
FILTER  
MOTOR  
STALE AIR  
FROM INSIDE  
STALE AIR  
TO OUTSIDE  
ATTENTION  
Ports  
Ports  
6" (150 mm)  
7" (178 mm)  
The ECM motor produces a tone that some may  
find objectionable. We recommend the  
FILTER  
BLOWERS  
installation of the optional 99-SILENCER6 on the  
‘Stale Air from Insideand ‘Fresh Air to Inside’  
ducts.  
FRESH AIR  
FRESH AIR  
TO INSIDE  
FROM OUTSIDE  
49"  
(1245)  
DEFROST  
DAMPER  
14 3/4"  
(375)  
CONDENSATE  
DRAINS  
DEFROST AIR  
FROM INSIDE  
*NOTE: Front clearance of 25 inches (635 mm)  
is recommended for servicing unit.  
Date: ___________________________________________  
Tag: _____________________Qty:___________________  
Project: _________________________________________  
Engineer: _______________________________________  
Contractor: ______________________________________  
Supplier: ________________________________________  
Quote#: _________________________________________  
Submitted by: ____________________________________  
TI-195ECM  

Xerox Workcentre Pro 575 User Manual
Xerox Workcentre Pro 232 User Manual
Trane Air Conditioner 4ttx5049e1 User Manual
Soleus Air Air Conditioner Hp1 15 50 User Manual
Sharp Mx B401 User Manual
Panasonic Cu E15gkr User Manual
Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Msz Fdna User Manual
GE A835 User Manual
BROTHER FAX 2825 User Manual
ASUS VA24DQLB User Manual