Fyrnetics Hd135f User Manual

For model: HD135F  
HD135F  
Heat Alarm User’s Guide  
AC Wire-in Single and/or Multiple Station (up to 24 Devices) Heat Alarm  
with 9 Volt Battery Back Up, 135ºF fixed temperature.  
Thank you for purchasing this heat alarm. It is an important part of your familys  
home safety plan. You can trust this product to provide the highest quality safe-  
ty protection. We know you expect nothing less when the lives of your family  
are at stake. Kidde alarms and accessories CAN ONLY BE interconnected with  
other Kidde alarms and accessories as well as specified brands and models of  
interconnect compatible alarms. Connection of Kidde products to a non-speci-  
fied manufacturers interconnect system, or connection with non-specified  
equipment from another manufacturer into an existing Kidde system could result  
in nuisance alarming, failure to alarm, or damage to one or all of the devices in  
the interconnect system. Refer to the Users Guide supplied with each Kidde  
product for interconnect compatible models, brands, and devices. Refer to the  
wiring instructions in section 3 for NFPA initiating device limits  
For your convenience, write down the following information. If you call  
our Consumer Hotline, these are the first questions you will be asked.  
Heat Alarm Model Number  
(located on back of alarm):  
Date Code (located on back of alarm): The  
National Fire Protection Association (NFPA)  
and the manufacturer recommend replacing  
this alarm ten years from the date code.  
Date of Purchase:  
Where Purchased:  
820-0917-EN Rev. C  
1000-7211-00  
Note A: Maximum coverage established by U.L. is based on providing equal  
response time as sprinkler devices spaced at 10-Ft intervals (100 Sq/Ft) on a  
smooth ceiling approximately 15 feet high. Higher ceilings may adversely affect  
response time and earlier response time may be obtained by reducing the spac-  
ing between alarms.  
Note B: Maximum distance is from any wall or ceiling projection extending  
down more than 12 inches.  
2. RECOMMENDED LOCATION OF ALARMS  
• The most favorable mounting location  
for a heat alarm is on the ceiling in the  
center of the room. At this location the  
alarm is closest to all areas of the room  
(see figure 3).  
EXCEPTION: When the mounting surface  
might become considerably warmer or  
cooler than the room, such as a poorly  
insulated ceiling, below an unfinished attic,  
or an exterior wall. In these cases the alarm  
should be mounted on an inside wall.  
• If the alarm cannot be located in the  
center of the room, an off-center location  
can be used on the ceiling. When off cen-  
FIGURE 1  
ter mounting an alarm on the ceiling,  
locate it at a minimum of 4" (10 cm) from  
the side wall (see figure 3).  
If a ceiling mounting location is not fea-  
sible the next logical location for mounting  
heat alarms is on the side wall. When  
mounting the alarm on the wall, use an  
inside wall with the top edge of the alarm  
at a minimum of 4" (10 cm) and a maxi-  
mum of 12" (30.5 cm) below the ceiling  
(see figure 1).  
FIGURE 2  
• Install Heat Alarms on sloped, peaked or cathedral ceilings at or within 3 ft  
(0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke  
alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4m) hori-  
zontally shall be located on the high side of the room.” NFPA 72 states: “A row  
of alarms shall be spaced and located  
within 3 ft (0.9m) of the peak of the  
ceiling measured horizontally” (see  
figure 3).  
• In rooms with open joists or  
beams, all ceiling mounted alarms  
shall be located on the bottom of  
such beams (see figure 2).  
• Alarms installed on an open-joisted  
ceiling shall have their smooth ceiling  
spacing reduced to no more than half  
of the listed spacing when measured  
at right angles to the solid joist (See  
figure 2).  
MOBILE HOME INSTALLATION  
FIGURE 3  
Modern mobile homes have been  
designed and built to be energy effi-  
cient. Install heat alarms as recom-  
mended above (refer to RECOMMENDED LOCATIONS and FIGURE 1).  
In older mobile homes that are not well insulated compared to present stan-  
dards, extreme heat or cold can be transferred from the outside to the inside  
through poorly insulated walls and roof. This may create a thermal barrier  
which can prevent the heat from reaching an alarm mounted on the ceiling. In  
such units, install the heat alarm on an inside wall with the top edge of the  
alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the  
ceiling (see figure 1).  
If you are not sure about the insulation in your mobile home, or if you notice  
that the outer walls and ceiling are either hot or cold, install the alarm on an  
inside wall.  
WARNING: TEST YOUR HEAT ALARM OPERATION AFTER RV OR MOBILE  
HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT  
LEAST ONCE A WEEK DURING USE.  
3. LOCATIONS TO AVOID  
• In front of forced air supply ducts used for heating and air conditioning, near  
ceiling fans, or other high air flow areas.  
• In an area where the temperature may fall below -20ºF or rise above 100ºF.  
• Near fluorescent lights – electronic "noise" may cause nuisance alarms.  
• Heat alarms are not to be used with detector guards unless the combination  
(alarm and guard) have been evaluated and found suitable for that purpose.  
4. INSTALLATION INSTRUCTIONS  
WIRING REQUIREMENTS  
• This smoke alarm should be installed on a U.L. listed or recognized junction  
box. All connections should be made by a qualified electrician and all wiring  
used shall be in accordance with articles 210 and 300.3(B) of the U.S. National  
Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic-  
tion in your area. The multiple station interconnect wiring to the alarms must  
be run in the same raceway or cable as the AC power wiring. In addition, the  
resistance of the interconnect wiring shall be a maximum of 10 ohms.  
• The appropriate power source is 120 Volt AC Single Phase supplied from a  
non-switchable circuit which is not protected by a ground fault interrupter.  
• WARNING:This alarm cannot be operated from power derived from a square  
wave or modified square wave inverter. These type of inverters are sometimes  
used to supply power to the structure in off grid installations, such as solar or  
wind derived power sources. These power sources produce high peak voltages  
that will damage the alarm.  
WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS  
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING  
THE ALARM.  
• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE  
TO ANYTHING. Leave the red wire insulating cap in place to make certain that  
the red wire cannot contact any metal parts or the electrical box.  
• When alarms are interconnected, all interconnected units must be powered  
from a single circuit.  
• A maximum of 24 Kidde/Lifesaver devices may be interconnected in a multiple  
station arrangement. The interconnect system should not exceed the NFPA  
interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat,  
carbon monoxide, etc.). With 18 alarms interconnected, it is still possible to  
interconnect up to a total of 6 remote signaling devices and/or relay modules.  
• When mixing models which have battery backup (1275, 1276, 1285, 1296,  
i12040, i12060, i12080, PE120, PI2000, KN-COSM-IB, HD135F, KN-COB-IC,  
KN-COP-IC) with models without battery backup, (1235, i12020, KN-COSM-I,  
120X, SM120X, CO120X, SL177i) be advised that the models without battery  
backup will not respond during an AC power failure.  
• The maximum wire run distance between the first and last unit in an intercon-  
nected system is 1000 feet.  
• Figure 4 illustrates interconnection wiring. Improper connection will result in  
damage to the alarm, failure to operate, or a shock hazard.  
• Make certain alarms are wired to a continuous (non-switched) power line.  
NOTE: Use standard UL listed household wire (as required by local codes) avail-  
able at all electrical supply stores and most hardware stores.  
FUSE OR CIRCUIT BREAKER  
BLACK  
WHITE  
BLACK  
WHITE  
RED  
RED  
CONNECTOR  
CONNECTOR  
Kidde  
Relay Module  
SM120X  
HD135F  
Smoke  
Smoke  
Heat  
Optional  
Alarm  
Alarm  
Alarm  
Accessory  
FIGURE 4 INTERCONNECT WIRING DIAGRAM  
WIRES ON ALARM HARNESS  
CONNECTED TO  
Black  
White  
Red  
Hot Side of AC Line  
Neutral Side of AC Line  
Interconnect Lines (Red Wires) of Other  
Units in the Multiple Station Set up  
BATTERY INSTALLATION  
See MAINTENANCE (section 7) for battery installation.  
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN  
THE BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR  
WILL NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE  
ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING (SEE  
SECTION 7, FIGURE 9).  
MOUNTING INSTRUCTIONS  
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!  
1.Remove the trim ring from the back of the alarm by holding the trim ring and  
twisting the alarm in the direction indicated by the “OFF” arrow on the alarm  
cover.  
2.After selecting the proper smoke alarm location as described in Section 2 and  
wiring the AC QUICK CONNECT harness as described in the WIRING INSTRUC-  
TIONS, attach the trim ring to the electrical box (see figure 5).  
3.Use a screwdriver to punch out only the pair of holes in the trim ring that  
match your type of electrical box or plaster ring. Mount the trim ring to the  
electrical box, using the appropriate holes. NOTE: Use the circle, square and  
octagon markings near each mounting hole in the trim ring to help you select  
the correct mounting holes (see figure 5).  
Rectangular  
Plaster Ring  
Circular  
Plaster Ring  
Octagonal  
Electrical Box  
Figure 5 SELECT CORRECT MOUNTING HOLES ON TRIM RING  
4.Pull the AC QUICK CONNECTOR through the center hole in the trim ring and  
mount the ring, making sure that the mounting screws are positioned in the  
small ends of the keyholes before tightening the screws (see figure 5).  
5.Plug the AC QUICK CONNECTOR into the back of the alarm (see figure 6),  
making sure that the locks on the connector snap into place. Then push the  
excess wire back into the electrical box through the hole in the center of the  
trim ring.  
6.If you have finished all the WIRING, BATTERY INSTALLATION AND TRIM RING  
MOUNTING STEPS, you can install the alarm on the trim ring. Alignment marks  
are provided on the side of the alarm and on the trim ring (see figure 7).  
7.Install the alarm on the trim ring with the indicating marks aligned and rotate  
the alarm in the direction of the “ON” arrow on the cover until the alarm  
snaps in place (see figure 7).  
8.Turn on the AC power. The green AC Power On Indicator should be lit when  
the alarm is operating from AC power.  
TAMPER RESIST LOCKING PIN: To make your heat alarm tamper resistant, a  
locking pin has been provided with your alarm. Using this pin will help deter  
children and others from removing the alarm from trim ring. To use the pin,  
insert it into the hole in the side of the alarm after the alarm has been installed  
on the trim ring (see figure 8).  
NOTE: The tamper resist pin will have to be removed in order to change the bat-  
teries. Use long nose pliers to pull the pin out of the hole. It is now possible to  
remove the alarm from the trim ring.  
Alignment Marks  
To remove AC  
connector,  
squeeze  
locking  
arms and  
pull.  
Tamper resistant  
locking pin  
Remove  
Install  
FIGURE 6  
FIGURE 7  
FIGURE 8  
After installation, TEST your alarm by pressing and holding the test button for  
several seconds. You can also use a hand held hair dryer to test your heat alarm.  
Complete details on this procedure are outlined in section 5.  
CAUTION! Early warning fire detection is best achieved by the installation of  
fire detection equipment in all rooms and areas of the household as follows: A  
smoke alarm installed in each separate sleeping area (in the vicinity of - but out-  
side of the bedroom) and heat or smoke alarms in the living rooms, dining  
rooms, kitchens, hallways, attics, furnace rooms, closets, utility storage rooms,  
basements, and attached garages.  
5. OPERATION AND TESTING  
OPERATION: The heat alarm is operating once AC power is applied, fresh batter-  
ies are installed and testing is complete. When the heat alarm senses tempera-  
tures above 135ºF (plus or minus a few degrees), the horn will sound a loud (85  
db) pulsating alarm until the temperature drops below 135ºF.  
LED INDICATORS: This heat alarm is equipped with red and green LED indicators.  
The red LED is located under the test button and has two modes of operation.  
Standby Condition: The red LED will flash every 30-40 seconds to indicate that  
the smoke alarm is operating properly.  
Alarm Condition:  
When the unit detects heat and goes into alarm, the red  
LED will flash rapidly (one flash per second). The rapid  
flashing LED and pulsating alarm will continue until the  
temperature drops below 135 ºF.  
WHEN UNITS ARE INTERCONNECTED, only the red LED of the originating alarm  
or alarm being tested will flash rapidly. All other units in the interconnect sys-  
tem will sound an alarm but their red LEDs will NOT flash rapidly.  
The green LED is located under the other button.  
Standby Condition: The green LED will be steady on, indicating the presence  
of AC power.  
TESTING: Test by pushing the test button on the cover and hold it down for a  
minimum of 5 seconds. This will sound the alarm if all the electronic circuitry,  
horn, and battery are working. THE TEST SWITCH MAY NOT CAUSE A TEST SIG-  
NAL IF THE AMBIENT TEMPERATURE IS BELOW 32ºF, IN THIS CASE TEST THE  
UNIT BY BLOWING HOT AIR AT THE ALARM SENSING ELEMENT WITH A HAIR  
DRYER HELD ABOUT 1 FOOT FROM THE UNIT.  
If no alarm sounds, check the fuse or circuit breaker supplying power to the  
alarm circuit, if the alarm still does not sound the unit may have defective bat-  
teries or other failure.  
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION.  
Erratic or low sound coming from your alarm may indicate a defective alarm,  
and it should be returned for service (see section 12).  
6. FALSE ALARMS  
To avoid false alarms,DO NOT USE WHERE ROOM TEMPERATURES WILL EXCEED  
100º F.  
Heat alarms respond only to heat. They do not detect smoke. If the unit does  
alarm, check for fires first. If a fire is discovered, get out of the house and call  
the fire department. If no fire is present check to see if one of the reasons listed  
in section 3 may have caused the alarm.  
7. MAINTENANCE  
ALARM REMOVAL  
IF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCK-  
ING PIN IN SECTION 4 FOR PIN REMOVAL INSTRUCTIONS.  
To replace the battery, remove the alarm from the trim ring by rotating the alarm  
in the direction of the “OFF” arrow on the cover (see section 4, figure 7). To dis-  
connect the AC power harness, squeeze the locking arms on the sides of the  
Quick Connector while pulling the connector away from the bottom of the  
alarm (see section 4, figure 6).  
BATTERY INSTALLATION AND REMOVAL  
To replace or install the batteries, you must  
first remove the alarm from the trim ring  
by following the ALARM REMOVAL instruc-  
tions at the beginning of this section. After  
alarm has been removed, you can open the  
battery door and install or replace the bat-  
tery. Battery installation instructions are  
provided on the inside of the battery door.  
When installing the battery, press the bat-  
tery reminder finger down into the battery  
compartment and install the battery (see  
FIGURE 9  
figure 9).  
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE  
BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR WILL  
NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE  
ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING.  
This smoke alarm uses a 9V carbon backup battery (alkaline and lithium batteries  
may also be used). A fresh battery should last for one year under normal operat-  
ing conditions.  
This alarm has a low/missing battery monitor circuit which will cause the alarm  
to “chirp” approximately every 30-40 seconds for a minimum of seven (7) days  
when the battery gets low. Replace the battery when this condition occurs.  
USE ONLY THE FOLLOWING 9 VOLT BATTERIES FOR SMOKE ALARM  
REPLACEMENT.  
Carbon-zinc type  
Alkaline type  
EVEREADY 216 OR 1222; GOLD PEAK 1604P OR 1604S  
ENERGIZER 522; DURACELL MN1604, MX1604; GOLD  
PEAK 1604A; PANASONIC 6AM6, 6AM-6, 6AM-6PI,  
6AM6X, and 6LR61(GA)  
Lithium type  
ULTRALIFE U9VL-J  
NOTE: WEEKLY TESTING IS REQUIRED!  
WARNING! BE SURE TO FOLLOW BATTERY INSTALLATION INSTRUCTIONS  
PRINTED ON THE INSIDE OF THE BATTERY DOOR AND USE ONLY THE  
BATTERIES SPECIFIED. USE OF DIFFERENT BATTERIES MAY HAVE A DETRI-  
MENTAL EFFECT ON THE SMOKE ALARM.  
CLEANING YOUR ALARM  
YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR  
To clean your alarm, remove it from the mounting bracket as outlined in the  
beginning of this section. You can clean the interior of your alarm (sensing  
chamber) by using compressed air or a vacuum cleaner hose and blowing or vac-  
uuming through the openings around the temperature sensor located on the  
top of the alarm. The outside of the alarm can be wiped with a damp cloth.  
After cleaning, reinstall your alarm and test your alarm by using the test button.  
If cleaning does not restore the alarm to normal operation the alarm should be  
replaced.  
After cleaning, reinstall your alarm. Test your alarm by using the test button and  
check that the green LED is on.  
8. LIMITATIONS OF HEAT ALARMS  
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY  
• HEAT ALARMS ARE NOT DESIGNED TO PROTECT LIFE SAFETY AGAINST  
FIRE AND SMOKE. IN MOST FIRES, HAZARDOUS LEVELS OF TOXIC  
GASES, SMOKE AND HEAT CAN BUILD UP BEFORE A HEAT ALARM WILL  
OPERATE. IN CASES WHERE LIFE SAFETY IS AN ISSUE, HEAT ALARMS  
SHOULD ONLY BE USED TO PROVIDE AN ADDED SOURCE OF INFORMA-  
TION AND AS A SUPPLEMENT TO THE SMOKE ALARM INSTALLATION.  
HEAT ALARMS DO NOT ALWAYS DETECT FIRES, THE FIRE MAY BE A  
SLOW SMOLDERING (SMOKE PRODUCING) LOW HEAT PRODUCING  
TYPE, THE FIRE MAY BE IN A DIFFERENT ROOM THAN THE ALARM, OR  
THE HEAT FROM THE FIRE MAY BYPASS THE ALARM. THIS ALARM WILL  
NOT DETECT SMOKE, GASES OR FLAMES.  
• HOME FIRES DEVELOP IN DIFFERENT WAYS AND ARE OFTEN UNPREDICTABLE.  
NO ONE TYPE OF ALARM (HEAT, PHOTOELECTRIC OR IONIZATION) IS  
ALWAYS BEST, AND A GIVEN ALARM MAY NOT ALWAYS PROVIDE WARNING  
OF A FIRE. ALSO ALARMS DO HAVE LIMITATIONS. FOR A BATTERY POWERED  
ALARM THE BATTERY MUST BE OF THE SPECIFIED TYPE, IN GOOD CONDI-  
TION AND INSTALLED PROPERLY. AC POWERED ALARMS WILL NOT OPERATE  
IF AC POWER HAS BEEN CUT OFF SUCH AS BY AN ELECTRICAL FIRE OR AN  
OPEN FUSE. ALARMS MUST BE TESTED REGULARLY TO MAKE SURE THE BAT-  
TERIES AND THE ALARM CIRCUITS ARE IN GOOD OPERATING CONDITION.  
• HEAT ALARMS CANNOT PROVIDE AN ALARM IF HEAT DOES NOT REACH THE  
ALARM. THEREFORE, HEAT ALARMS MAY NOT SENSE FIRES STARTING IN  
CHIMNEYS, WALLS, ON ROOFS, ON THE OTHER SIDE OF A CLOSED DOOR OR  
ON A DIFFERENT FLOOR. IF THE ALARM IS LOCATED OUTSIDE THE BEDROOM  
OR ON A DIFFERENT FLOOR, IT MAY NOT WAKE UP A SOUND SLEEPER. THE  
USE OF ALCOHOL OR DRUGS MAY ALSO IMPAIR ONES ABILITY TO HEAR THE  
ALARM. FOR MAXIMUM PROTECTION HEAT ALARMS SHOULD ONLY BE USED  
AS A SUPPLEMENT TO SMOKE ALARMS. SMOKE ALARMS SHOULD BE  
INSTALLED IN EACH SLEEPING AREA ON EVERY LEVEL OF A HOME AND BE  
INTERCONNECTE WITH EACH OTHER AND THE HEAT ALARMS.  
• ALTHOUGH HEAT ALARMS WHEN COMBINED WITH SMOKE ALARMS, CAN  
HELP SAVE LIVES BY PROVIDING AN EARLY WARNING OF A FIRE, THEY ARE  
NOT A SUBSTITUTE FOR AN INSURANCE POLICY. HOME OWNERS AND  
RENTERS SHOULD HAVE ADEQUATE INSURANCE TO PROTECT THEIR LIVES  
AND PROPERTY.  
9. GOOD SAFETY HABITS  
DEVELOP AND PRACTICE A PLAN OF ESCAPE  
• Install and maintain Fire extinguishers on every level of the home and in the  
kitchen, basement and garage. Know how to use a fire extinguisher prior to  
an emergency.  
• Make a floor plan indicating all doors and windows and at least two (2)  
escape routes from each room. Second story windows may need a rope or  
chain ladder.  
• Have a family meeting and discuss your escape plan, showing everyone what  
to do in case of fire.  
• Determine a place outside your home where you all can meet if a fire occurs.  
• Familiarize everyone with the sound of the smoke alarm and train them to  
leave your home when they hear it.  
• Practice a fire drill at least every six months, including fire drills at night.  
Ensure that small children hear the alarm and wake when it sounds. They  
must wake up in order to execute the escape plan. Practice allows all occu-  
pants to test your plan before an emergency. You may not be able to reach  
your children. It is important they know what to do.  
• Current studies have shown smoke alarms may not awaken all sleeping  
individuals, and that it is the responsibility of individuals in the household that  
are capable of assisting others to provide assistance to those who may not be  
awakened by the alarm sound, or to those who may be incapable of safely  
evacuating the area unassisted.  
WHAT TO DO WHEN THE ALARM SOUNDS  
• Leave immediately by your escape plan. Every second counts, so don’t waste  
time getting dressed or picking up valuables.  
• In leaving, don’t open any inside door without first feeling its surface. If hot, or  
if you see smoke seeping through cracks, don’t open that door! Instead, use  
your alternate exit. If the inside of the door is cool, place your shoulder against  
it, open it slightly and be ready to slam it shut if heat and smoke rush in.  
• Stay close to the floor if the air is smoky. Breathe shallowly through a cloth,  
wet if possible.  
• Once outside, go to your selected meeting place and make sure everyone is  
there.  
• Call the fire department from your neighbors home - not from yours!  
• Don’t return to your home until the fire officials say that it is all right to do so.  
There are situations where a smoke alarm may not be effective to protect  
against fire as stated in the NFPA Standard 72. For instance:  
a) smoking in bed  
b) leaving children home alone  
c) cleaning with flammable liquids, such as gasoline  
10. NFPA REQUIRED PROTECTION  
The National Fire Protection Associations Standard 72 provides the following  
information:  
Smoke Detection - Where required by applicable laws, codes, or standards for  
the specified occupancy, approved single- and multiple-station smoke alarms  
shall be installed as follows: (1) In all sleeping rooms Exception: Smoke alarms  
shall not be required in sleeping rooms in existing one- and two-family dwelling  
units. (2) Outside of each separate sleeping area, in immediate vicinity of the  
sleeping rooms. (3) On each level of the dwelling unit, including basements  
Exception: In existing one- and two-family dwelling units, approved smoke  
alarms powered by batteries are permitted.  
Smoke Detection - Are More Smoke Alarms Desirable? The required number of  
smoke alarms might not provide reliable early warning protection for those areas  
separated by a door from the areas protected by the required smoke alarms. For  
this reason, it is recommended that the householder consider the use of addi-  
tional smoke alarms for those areas for increased protection. The additional  
areas include the basement, bedrooms, dining room, furnace room, utility room,  
and hallways not protected by the required smoke alarms. The installation of  
the smoke alarms in the kitchen, attic (finished or unfinished), or garage is nor-  
mally not recommended, as these locations occasionally experience conditions  
that can result in improper operation.  
This equipment should be installed in accordance with the National Fire  
Protection Associations Standard 72 (NFPA, Batterymarch Park, Quincy, MA  
02269).  
11. CAUTION (AS REQUIRED BY THE CALIFORNIA STATE FIRE  
MARSHAL)  
“Early warning fire detection is best achieved by the installation of fire detection  
equipment in all rooms and areas of the household as follows. A smoke alarm  
installed in each separate sleeping area (in the vicinity of, but outside of the bed-  
rooms), and heat or smoke alarms in the living rooms, dining rooms, bedrooms,  
kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, base-  
ments and attached garages.”  
12. SERVICE AND WARRANTY  
If after reviewing this manual you feel that your smoke alarm is defective in any  
way, do not tamper with the unit. Return it for servicing to: KIDDE Safety, 1016  
Corporate Park Dr., Mebane, NC 27302.  
1-800-880-6788 (See Warranty for in-warranty returns).  
FIVE YEAR LIMITED WARRANTY  
KIDDE Safety warrants to the original purchaser that the enclosed heat alarm (but not  
the battery) will be free from defects in material and workmanship or design under nor-  
mal use and service for a period of five years from the date of purchase. The obligation  
of KIDDE Safety under this warranty is limited to repairing or replacing the heat alarm or  
any part which we find to be defective in material, workmanship or design, free of  
charge to the customer, upon sending the heat alarm with proof of date of purchase,  
postage and return postage prepaid, to Warranty Service Department, KIDDE Safety,  
1016 Corporate Park Dr., Mebane, NC 27302.  
This warranty shall not apply to the heat alarm if it has been damaged, modified,  
abused or altered after the date of purchase or if it fails to operate due to improper  
maintenance or inadequate AC or DC electrical power.  
THE LIABILITY OF KIDDE SAFETY OR ANY OF ITS PARENT OR SUBSIDIARY CORPORA-  
TIONS ARISING FROM THE SALE OF THIS HEAT ALARM OR UNDER THE TERMS OF THIS  
LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT  
OF THE HEAT ALARM AND, IN NO CASE, SHALL KIDDE SAFETY OR ANY OF ITS PARENT  
OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES  
RESULTING FROM THE FAILURE OF THE HEAT ALARM OR FOR BREACH OF THIS OR ANY  
OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED  
BY THE COMPANY’S NEGLIGENCE OR FAULT.  
Since some states do not allow limitations on the duration of an implied warranty or do  
not allow the exclusion or limitation of incidental or consequential damages, the above  
limitations or exclusions may not apply to you. While this warranty gives you specific  
legal rights, you may also have other rights which vary from state to state.  
Also, KIDDE Safety makes no warranty, express or implied, written or oral, including that  
of merchantability or fitness for any particular purpose, with respect to the battery.  
The above warranty may not be altered except in writing signed by both parties hereto.  
QUESTIONS OR FOR MORE INFORMATION  
Call our Consumer Hotline at 1-800-880-6788 or contact  
us at our website at www.kidde.com  
Kidde, 1016 Corporate Park Drive, Mebane, NC 27302  

York Air Conditioner D2cg300 User Manual
Webasto Automobile Parts Transit Model Engine Front User Manual
Sanyo Ths3632 User Manual
Sanyo Kr 1400ae User Manual
Lanier 5222 User Manual
HANSGROHE AXOR TERRANO 37379XX1 User Manual
GE ADTS552F User Manual
CYBERPOWER PDU41405 User Manual
CRAFTSMAN 358.796200 User Manual
CRAFTSMAN 113.177060 User Manual