EMERSON VILTER 02 User Manual

VilterMotor Starter  
Refrigeration HMI Operation Manual  
Table of Contents  
Section Title  
Section Number  
Section 1 • General Information  
History .................................................................................................................................................. 1-1  
Vilter Engineered Motor Starters................................................................................................ 1-1  
Safety Features .......................................................................................................................... 1-1  
Hardware Components - Exterior ........................................................................................................... 1-2  
Main Breaker Enclosure.......................................................................................................................... 1-3  
Control Circuit and Components Enclosure ............................................................................................ 1-4  
Permanent Electrical Safety Devices....................................................................................................... 1-5  
Door Interlocks ...................................................................................................................................... 1-8  
Human Machine Interface (HMI) Touch Screen....................................................................................... 1-9  
Section 2 • HMI Power Up  
Splash Screen......................................................................................................................................... 2-1  
Section 3 • Main Menu/Architecture Screen  
Main Menu/Architecture Screen............................................................................................................. 3-1  
Show Menu Button .................................................................................................................... 3-1  
Component Navigation Touch Screen ........................................................................................ 3-1  
Previous Panel Button ................................................................................................................ 3-1  
Lengua Button (Optional) .......................................................................................................... 3-1  
Menu Popup Window ................................................................................................................ 3-2  
Section 4 • Log In/Out Screen  
Log In/Out Screen .................................................................................................................................. 4-1  
Section 5 • HMI Configuration Screen  
HMI Configuration Screen...................................................................................................................... 5-1  
Section 6 • HMI Information Screen  
HMI Information Screen ......................................................................................................................... 6-1  
XBTGT HMI Information Button.................................................................................................. 6-1  
Section 7 • Network Interface/Advantys STB Screen  
Network Interface / Advantys STB Screen............................................................................................... 7-1  
Advantys STB Button ................................................................................................................. 7-1  
Advantys STB Technical Data Screen .......................................................................................... 7-2  
Section 8 • Soft Starter Screen  
Soft Starter (RVSS) Screen...................................................................................................................... 8-1  
RVSS Configuration Button ........................................................................................................ 8-1  
Last Fault Display ....................................................................................................................... 8-1  
Fault Code Button ...................................................................................................................... 8-2  
Reset Faults Button .................................................................................................................... 8-2  
RVSS Information Button ........................................................................................................... 8-2  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
TOC - 1  
Table of Contents  
Section Title  
Section Number  
Section 8 • Soft Starter Screen (Continued)  
State of Logic I/O Indicators ....................................................................................................... 8-2  
RVSS Configuration Screen .................................................................................................................... 8-3  
Ready Indicator.......................................................................................................................... 8-3  
Enable / Run / Stop / Off Buttons ................................................................................................ 8-3  
Parameters ................................................................................................................................ 8-4  
Save Changes Button ................................................................................................................. 8-4  
Change Class Button .................................................................................................................. 8-5  
Change Signal Button ................................................................................................................ 8-6  
Section 9 • Oil Pump Starter Screen  
Oil Pump Motor Starter Screen............................................................................................................... 9-1  
Oil Pump Motor Starter (TeSys U) Configuration Button............................................................. 9-1  
Last Fault Display ....................................................................................................................... 9-1  
Fault Code Button ...................................................................................................................... 9-1  
Reset Faults Button .................................................................................................................... 9-1  
TeSys U Information Button ....................................................................................................... 9-1  
State of Logic I/O Indicators ....................................................................................................... 9-2  
Warning (Last Fault) Display....................................................................................................... 9-2  
Reset Warnings Button .............................................................................................................. 9-2  
Oil Pump Motor Starter (TeSys U) Configuration Screen .........................................................................9-3  
Run / Stop Buttons..................................................................................................................... 9-3  
Control Mode Local/Remote - Change Mode Button................................................................... 9-3  
Parameters ................................................................................................................................ 9-4  
Disable Phase Fault Button......................................................................................................... 9-4  
Setting the %FLA Value .............................................................................................................. 9-4  
Section 10 • Power Monitor Screen  
Power Monitor Screen............................................................................................................................ 10-1  
Power Monitor (Tesys T) Configuration Button........................................................................... 10-2  
Power Monitor (TeSys T) Configuration Screen....................................................................................... 10-2  
Parameters ................................................................................................................................ 10-3  
Thermal Overload / Phase Loss / Under Power / Over Current / Under Voltage Fault Buttons ....... 10-3  
Section 11 • Power Monitor Trend Screen  
Power Monitor Trend Screen ................................................................................................................. 11-1  
Calendar Window ...................................................................................................................... 11-1  
Time Span.................................................................................................................................. 11-1  
Range Span................................................................................................................................ 11-1  
Forward and Reverse Buttons..................................................................................................... 11-2  
Play and Pause Buttons .............................................................................................................. 11-2  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
TOC - 2  
Table of Contents  
Section Title  
Section Number  
Section 12 • Compressor Motor Trend Screen  
Compressor Motor Trend Screen............................................................................................................ 12-1  
Calendar Window ...................................................................................................................... 12-1  
Time Span.................................................................................................................................. 12-1  
Data Limit.................................................................................................................................. 12-1  
Normal Run Current................................................................................................................... 12-2  
Run Current Warning ................................................................................................................. 12-2  
Section 13 • Oil Pump Motor Trend Screen  
Oil Pump Motor Trend Screen ................................................................................................................ 13-1  
Calendar Window ...................................................................................................................... 13-1  
Time Span.................................................................................................................................. 13-1  
Data Limit.................................................................................................................................. 13-1  
Section 14 • Alarm & Event Log Screen  
Alarm & Event Log Screen....................................................................................................................... 14-2  
Acknowledge All........................................................................................................................ 14-3  
Acknowledge ............................................................................................................................ 14-3  
Scroll Buttons ............................................................................................................................ 14-3  
Page Buttons ............................................................................................................................. 14-3  
Section 15 • Motor Starter Drawings Screen  
Motor Starter Drawings Screen .............................................................................................................. 15-1  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
TOC - 3  
List of Figures  
Figures  
Section Number  
Figure 1-1. Hardware Components - Exterior.......................................................................................... 1-2  
Figure 1-2. Main Breaker Enclosure - Interior View.................................................................................. 1-3  
Figure 1-3. Control Circuit and Components Enclosure - Interior View .................................................... 1-4  
Figure 1-4. Permanent Electrical Safety Devices ..................................................................................... 1-5  
Figure 1-5. Permanent Electrical Safety Devices (Continued).................................................................. 1-6  
Figure 1-6. Permanent Electrical Safety Devices (Continued).................................................................. 1-7  
Figure 1-7. Door Interlock ...................................................................................................................... 1-8  
Figure 1-8. HMI Touch Screen................................................................................................................. 1-9  
Figure 2-1. Splash Screen ....................................................................................................................... 2-1  
Figure 3-1. Main Menu/Architecture Screen ........................................................................................... 3-1  
Figure 3-2. Main Menu/Architecture Screen - Menu Popup Window....................................................... 3-2  
Figure 4-1. Menu Popup Window........................................................................................................... 4-1  
Figure 4-2. Log In Screen........................................................................................................................ 4-1  
Figure 4-3. Log In Screen - On-Screen Keyboard ..................................................................................... 4-2  
Figure 5-1. HMI Configuration Button .................................................................................................... 5-1  
Figure 5-2. HMI Configuration Screen .................................................................................................... 5-1  
Figure 6-1. HMI Information Screen........................................................................................................ 6-1  
Figure 7-1. Network Interface / Advantys STB......................................................................................... 7-1  
Figure 7-2. Advantys STB Technical Data Screen..................................................................................... 7-2  
Figure 8-1. Soft Starter (RVSS) Screen .................................................................................................... 8-1  
Figure 8-2. RVSS Configuration Button................................................................................................... 8-1  
Figure 8-3. Soft Starter (RVSS) Screen - Fault Code Popup List ................................................................8-2  
Figure 8-4. RVSS Configuration Screen ................................................................................................... 8-3  
Figure 8-5. RVSS Configuration Screen - Nominal Motor Current Numeric Entry Keypad......................... 8-4  
Figure 8-6. RVSS Configuration Screen - Change Class Popup Window ................................................... 8-5  
Figure 8-7. RVSS Configuration Screen - Change Signal Popup Window.................................................. 8-6  
Figure 9-1. Oil Pump Motor Starter Screen ............................................................................................. 9-1  
Figure 9-2. Oil Pump Motor Starter Screen - Warning Fault Code Popup List ........................................... 9-2  
Figure 9-3. Oil Pump Motor Starter Configuration Screen.......................................................................9-3  
Figure 9-4. Oil Pump Motor Starter Configuration Screen - Numeric Entry Keypad.................................. 9-4  
Figure 10-1. Power Monitor Screen ........................................................................................................ 10-1  
Figure 10-2. Power Monitor Configuration Screen.................................................................................. 10-2  
Figure 10-3. Power Monitor Configuration Screen - Numeric Entry Keypad............................................. 10-3  
Figure 11-1. Power Monitor Trend Screen............................................................................................... 11-1  
Figure 11-2. Power Monitor Trend Screen - Reverse/Pause/Play/Forward Buttons................................... 11-2  
Figure 11-3. Power Monitor Trend Screen - Calendar Window (Enlarged) ............................................... 11-2  
Figure 12-1. Compressor Motor Trend Screen ........................................................................................ 12-1  
Figure 12-2. Compressor Motor Trend Screen - Normal Run Current & Run Current Warning .................. 12-2  
Figure 13-1. Oil Pump Motor Trend Screen............................................................................................. 13-1  
Figure 14-1. Alarm & Event Log Screen ................................................................................................... 14-2  
Figure 14-2. Alarm & Event Log Screen - Push Buttons ............................................................................ 14-3  
Figure 15-1. Motor Starter Drawings Screen........................................................................................... 15-1  
Figure 15-2. Drawing Menu.................................................................................................................... 15-2  
Figure 15-3. Zoom In/Out Buttons ......................................................................................................... 15-2  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
TOC - 4  
Section 1 • General Information  
History  
Vilter Manufacturing - providing innovative solutions to  
industrial applications since 1867.  
Safety Features  
Vilter Manufacturing, a business line of Emerson Climate  
Technologies, provides a complete line of compressors  
for industrial refrigeration, industrial heat pumps and  
hydrocarbon gas processing including reciprocating,  
single screw, twin screw, and scroll compressors.  
• The Main Breaker and incoming voltage are seques-  
tered from the main enclosure.  
• HMI provides monitoring and conguration of inter-  
nal starter components.  
• Electrical and Mechanical interlocks to prevent entry  
while enclosure is energized.  
Vilter’s single screw compressors provide the lowest  
life-cycle costs, and highest reliability of all industrial  
refrigeration and gas compressors. Its balanced de-  
sign provides quiet and reliable operation. Dependable  
performance, well beyond 100,000 hours, is typical in  
closed loop refrigeration systems without the need for  
special oil ltration or vibration monitoring and analysis.  
Periodic compressor rebuilds and overhauls are relative-  
ly unheard of with the Vilter single screw compressor.  
• Non-contact voltage indicators to verify power pres-  
ent inside enclosure.  
• External power disconnect devices are provided for  
main and control voltages.  
• Remote monitoring and control with password  
protection.  
• Thermal and Magnetic protection of the loads being  
fed from the starter.  
This manual covers typical motor starter applications  
The form and function of the HMI screens will be the  
same if additional screens are added for your particular  
project.  
Vilter Engineered Motor Starters  
The principle behind our Vilter Engineered Motor  
Starters is to build safe and smart equipment in the  
spirit of the NFPA 70E Standard for Electrical Safety in  
the Workplace. The goal is to provide operators with  
troubleshooting and conguration tools on the outside  
of the motor starter, away from electrical hazards, as  
well as to eliminate and/or reduce the risk of an Arc Flash  
Hazard and electrocution.  
We build our Vilter Engineered Motor Starters according  
to UL 508A, NFPA 79 and NFPA 70 NEC. We incorporate  
the latest proven technology for internal power and con-  
trol components.  
We also custom engineer our Vilter Engineered Motor  
Starters to meet your specic application and load re-  
quirements – starter enclosures can be customized to t  
within existing structures.  
All Vilter Engineered Motor Starters are pre-assembled  
and shipped ready for installation.  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 1  
Section 1 • General Information  
Hardware Components - Exterior  
Vilter Motor Starters may differ depending on application. Below are typical components that can be found in each  
motor starter. For specic motor starter layout, refer to supplied electrical drawings.  
1* - Human Machine Interface (HMI) Touch Screen  
2** - Control Circuit and Components Enclosure  
3 - Electromechanical Door Interlock  
4** - Main Breaker Enclosure - Incoming Feeder  
5 - Main Motor Starter Enclosure  
6 - Permanent Electrical Safety Devices (Voltage  
Indicator and Non-Contact Voltage Detector)  
1*  
2**  
3
6
5
4**  
Figure 1-1. Hardware Components - Exterior  
* Navigating through screens will not start or stop the compressor. Loss of communication between the HMI and com-  
ponents will not impact functionality of the motor starter - it will still protect and start all compressor loads.  
** Main Breaker Enclosure and Control Enclosure can be mounted either top or bottom depending on the incoming  
feeder – in some applications the Main Breaker is mounted in the main enclosure.  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 2  
Section 1 • General Information  
Main Breaker Enclosure  
The Main Breaker is mounted in a separate enclosure;  
therefore, removing the line side voltage from the Main  
Motor Starter Enclosure when the Main Breaker is in  
the off position. Now, a technician can enter the Main  
Motor Starter Enclosure without exposure to any volt-  
age once it is placed in an electrically safe work condition  
per NFPA 70E.  
CAUTION  
Main breaker should only be turned to the off position  
when the compressor is not running. Failure to  
comply may result in damage to equipment.  
NOTICE  
Always follow your employer’s electrical safety  
program and NFPA 70E when working around and in  
energized equipment – this manual is not a substitute  
for NFPA 70E.  
Only the Main Breaker and feeder ground lug reside in  
the Main Breaker Enclosure – a shunt trip is standard on  
all Main Breakers and is wired to terminal blocks in the  
Control Circuit and Components Enclosure for customer  
use.  
Main Motor Starter Enclosure  
Main Breaker external to Main  
Motor Starter Enclosure  
Figure 1-2. Main Breaker Enclosure - Interior View  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 3  
Section 1 • General Information  
Control Circuit and Components Enclosure  
Control components on the secondary of the control  
The 120VAC and 24VDC control circuit and components  
are in a separate enclosure away from the 480V power  
circuit. This greatly reduces the Hazard/Risk category  
per NFPA 70E as well as the possibility of an Arc Flash  
Hazard.  
power transformer reside in the Control Circuit and  
Components Enclosure – in applications where the con-  
trol power transformer is 2kVA or below, the 120VAC  
secondary fusing is mounted on the control power  
transformer.  
NOTICE  
Always follow your employer’s electrical safety  
program and NFPA 70E when working around and in  
energized equipment – this manual is not a substitute  
for NFPA 70E.  
Control Circuit and  
Components Enclosure  
Main Motor Starter Enclosure  
Figure 1-3. Control Circuit and Components Enclosure - Interior View  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 4  
Section 1 • General Information  
Permanent Electrical Safety Devices  
In some applications the Permanent Electrical Safety  
Devices are wired to the line side of the Main Breaker;  
therefore, forcing the technician to de-energize the  
feeder breaker to the motor starter and removing  
power from the Main Motor Starter Enclosure.  
Permanently installed electrical safety devices will alert  
people if the motor starter has power in the Main Motor  
Starter Enclosure. Four separate electrical safety devic-  
es are hard wired to the load side of the Main Breaker.  
When the Main Breaker is in the on position, power ows  
through the Main Breaker and through the Permanent  
Electrical Safety Devices.  
NOTICE  
Always follow your employer’s electrical safety  
program and NFPA 70E when working around and in  
energized equipment – this manual is not a substitute  
for NFPA 70E.  
Wired to Main Breaker  
Main Motor Starter Enclosure  
Device is wired to each  
phase and ground  
Device is wired to each  
phase L1, L2 & L3  
Main Breaker external to  
Main Motor Starter Enclosure  
Figure 1-4. Permanent Electrical Safety Devices  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 5  
Section 1 • General Information  
Permanent Electrical Safety Devices (Continued)  
Permanent Electrical Safety Devices should be used be-  
CAUTION  
fore entering the Main Motor Starter Enclosure. Before  
turning off the main breaker, ensure that the motor  
starter loads are properly interrupted and not energized.  
Check the Visual Voltage Indicator to make sure the red  
LEDs are all blinking – this ensures the indicator is work-  
ing properly. Use your Non-Contact Voltage Detector  
to test for voltage on each phase – ensure your Non-  
Contact Voltage Detector is working properly before  
using it and after using it on the Non-Contact Voltage  
Portal by testing it on a known energy source. Your Non-  
Contact Voltage Detector should illuminate and/or beep  
when voltage is present.  
Main breaker should only be turned to the off position  
when the compressor is not running. Failure to  
comply may result in damage to equipment.  
NOTICE  
Always follow your employer’s electrical safety  
program and NFPA 70E when working around and in  
energized equipment – this manual is not a substitute  
for NFPA 70E.  
Permanent Electrical Safety Devices continuously test  
for voltage and that the device itself is working properly.  
The Visual Voltage Indicator and Non-Contact Voltage  
Portal are used together to provide redundancy and to  
allow an independent voltage detector (non-contact  
voltage detector) to verify the presence or absence of  
voltage in the Main Motor Starter Enclosure.  
Redundant Voltage Verication – Visual  
Indicator and Non-Contact Voltage Portal  
Non-Contact Voltage Detector  
Tests for Voltage on Each Phase  
Main power circuit  
voltage indicator  
Control circuit voltage indi-  
cator wired to load side of  
control power disconnect  
Visual Voltage Indicator Tests Voltage between Phases and  
Ground – L1-L2; L1-L3; L2-L3; L1-GND; L2-GND; L3-GND  
Figure 1-5. Permanent Electrical Safety Devices (Continued)  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 6  
Section 1 • General Information  
Now turn off your main breaker and apply lockout/ta-  
gout devices in accordance with your documented and  
established policy. Return to the Permanent Electrical  
Safety Devices to ensure the Visual Voltage Indicator red  
LEDs are not blinking. Use your Non-Contact Voltage  
Detector on a known source to ensure it is working prop-  
erly then test each phase using the Non-Contact Voltage  
Portals, then test your Non-Contact Voltage Detector  
again on a known source to ensure it is working properly.  
Non-Contact Voltage Detector  
Tests for Voltage on Each Phase  
Before turning off the main breaker and entering the Main  
Motor Starter Enclosure – ensure that the visual voltage in-  
dicator’s red LEDS are blinking – turning off the main break-  
er should turn off the red LEDs – if the red LEDs continue to  
blink, there is still power in the enclosure. If the red LEDs  
are not blinking prior to turning off the main breaker there  
may be a problem with the visual voltage indicator as well  
as voltage in the Main Motor Starter Enclosure.  
Figure 1-6. Permanent Electrical Safety Devices (Continued)  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 7  
Section 1 • General Information  
Door Interlocks  
The Main Motor Starter Enclosure door includes an  
electromechanical door interlock that is energized by  
the Main Breaker. As the load side of the Main Breaker  
(in some applications, the line side) is energized, the  
Door Interlock is energized and locks the enclosure  
door. This prevents deliberate and accidental entry into  
the energized equipment.  
Door Interlock is energized by Main Breaker  
Main Breaker  
Figure 1-7. Door Interlock  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 8  
Section 1 • General Information  
Human Machine Interface (HMI) Touch Screen  
The Human Machine Interface (HMI) Touch Screen  
allows users to interface with intelligent motor starter  
components on the inside of the Main Motor Starter  
Enclosure. Conguration, troubleshooting and data ac-  
quisition tools are brought to the outside of the motor  
starter away from energized components and potential  
electrical hazards on the inside of the motor starter.  
Component Conguration  
Fault Management  
Data Acquisition/Trending  
Figure 1-8. HMI Touch Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 9  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
1 – 10 / Blank  
Section 2 • HMI Power Up  
Splash Screen  
On boot up, this screen will display as the HMI boots and  
runs its diagnostics. Also, other intelligent components  
run their respective diagnostic routines and establish  
communication. Once everything has powered up, the  
touch screen will show the Main Menu/Architecture  
screen.  
Figure 2-1. Splash Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
2 – 1  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
2 – 2 / Blank  
Section 3 • Main Menu/Architecture Screen  
Main Menu/Architecture Screen  
The Main Menu/Architecture screen is the overview  
screen of the motor starter. The darker lines represent  
480V connections and the light gray lines are commu-  
nication connections. This screen allows the operator to  
navigate to all screens, see Figure 3-1.  
Previous Panel Button  
• Returns to previously viewed screen.  
Lengua Button (Optional)  
• Allows the operator to select the language to display  
on the screens.  
Show Menu Button  
• This button opens the Menu button popup window.  
Navigation to the various motor starter components  
can be selected through the Menu button popup  
window.  
Component Navigation Touch Screen  
• Selecting a component on the touch screen will di-  
rectly open to the component screen.  
NOTE  
Not all components are selectable. Only intelligent  
components are selectable.  
Figure 3-1. Main Menu/Architecture Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
3 – 1  
Section 3 • Main Menu/Architecture Screen  
the selected screen will open and the button will disap-  
pear. In Figure 3-2, when on the main menu/architec-  
ture screen the Main Menu button is hidden.  
Menu Popup Window  
Component screens and other additional screens can be  
accessed through the menu popup window.  
When not logged in, the Drawings button and All  
Conguration buttons will be hidden.  
When a button is selected on the menu popup window,  
HMI Conguration Button (Hidden)  
Main Menu Button  
(Hidden)  
Menu Popup Window  
Drawings Button  
(Hidden)  
Figure 3-2. Main Menu/Architecture Screen - Menu Popup Window  
Top Row Buttons (Left to Right)  
• Main Menu (Hidden)  
• Power Monitor  
Bottom Row Buttons (Left to Right)  
• Log In/Out  
• Power Trend  
• Compressor Soft Starter  
• Oil Pump Starter  
• Compressor Trend  
• Oil Pump Trend  
• Network I/O  
• Cooler Fan VFD  
• Fault/Event Log  
• HMI  
• Drawings (Hidden)  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
3 – 2  
Section 4 • Log In/Out Screen  
2. Press the Name text eld to open the on-screen  
Log In/Out Screen  
keyboard, see Figure 4-3.  
NOTE  
The Log In/Out screen can be accessed through the  
menu popup window (see Figure 4-1) or through the  
User Display Field (see Figure 4-2).  
User Name and Password entries are case sensitive.  
The caps lock is on when green. In this case, the caps  
lock should remain on, since the User Name and  
Password are all upper case.  
To log in:  
3. Enter the user name, then hit Enter.  
1. From the menu popup window, Press Log In/Out  
button to open the Log In Screen. Or, from any  
screen, press the User Display Field.  
Log In/Out Button  
Figure 4-1. Menu Popup Window  
Password Text Field  
User Display Field  
Name Text Field  
Lock  
Main Menu/  
Architecture Screen  
Previous Screen  
Unlock  
(Press after typing User  
Name and Password)  
Figure 4-2. Log In Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
4 – 1  
Section 4 • Log In/Out Screen  
4. Press the Password text eld to open the on-screen  
keyboard.  
5. Enter the password, then hit Enter.  
6. Press the Unlock button.  
NOTE  
Log in will end when pressing the Lock button or time  
out with inactivity.  
7. Once logged in, the user name will be displayed in  
the User Display Field.  
Figure 4-3. Log In Screen - On-Screen Keyboard  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
4 – 2  
Section 5 • HMI Configuration Screen  
The HMI Conguration screen, shown in Figure 5-2, is  
the hardware and software setup of the HMI device. This  
screen should only be accessed by qualied personnel.  
HMI Conguration Screen  
When logged in with a high level access, the HMI  
Conguration button can be found on the Main  
Menu/Architecture screen or HMI Information screen,  
see Figure 5-1.  
NOTE  
Set Date/Time through the HMI Conguration Screen.  
Functional details in this screen will not be covered in the  
manual.  
HMI Conguration Button  
Figure 5-1. HMI Conguration Button  
Figure 5-2. HMI Conguration Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
5 – 1  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
5 – 2 / Blank  
Section 6 • HMI Information Screen  
HMI Information Screen  
The HMI Information screen shows the XBTGT HMI info  
button and HMI graphic, see Figure 6-1. This screen does  
not require a login to view.  
NOTE  
The HMI Conguration button is hidden from view until  
logged in with a high level access.  
XBTGT HMI Information Button  
• Navigates to the XBTGT HMI technical data screen.  
HMI Conguration Button (Hidden), High Level Login Required  
XBTGT HMI Information Button  
Figure 6-1. HMI Information Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
6 – 1  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
6 – 2 / Blank  
Section 7 • Network Interface / Advantys STB Screen  
Network Interface/Advantys STB Screen  
The Network Interface/Advantys STB screen shows the  
Advantys STB button and Modbus Hub graphic. This  
screen also shows the Modbus and Ethernet connec-  
tions, see Figure 7-1. This screen does not require a login  
to view.  
Advantys STB Button  
• Navigates to the Advantys STB technical data screen.  
Figure 7-1. Network Interface / Advantys STB  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
7 – 1  
Section 7 • Network Interface / Advantys STB Screen  
Advantys STB Technical Data Screen  
• This screen shows the Advantys STB technical data,  
see Figure 7-2.  
NOTE  
Screens with the information button will navigate to  
the component’s technical data screen in the Help File  
section. In Figure 7-2, is an example of the technical  
data screen that will be similar to all technical data  
screens.  
Figure 7-2. Advantys STB Technical Data Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
7 – 2  
Section 8 • Soft Starter Screen  
Last Fault Display  
Soft Starter (RVSS) Screen  
• Both screen and popup list displays the “last fault”  
address stored in the Soft Start fault register.  
The Soft Starter screen shows information from the  
RVSS (Reduced Voltage Soft Start) via Modbus commu-  
nication. This screen is read only and does not require a  
login to view, see Figure 8-1.  
NOTE  
The RVSS shown and used for the following description  
is an ATS48 Soft Starter.  
RVSS Conguration Button  
• Navigates to the RVSS Conguration screen for  
changing critical soft start parameters. This button,  
shown in Figure 8-2, is visible only when logged in  
with high level access. For RVSS Conguration screen,  
see Figure 8-4.  
Figure 8-2. RVSS Conguration Button  
Figure 8-1. Soft Starter (RVSS) Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 1  
Section 8 • Soft Starter Screen  
Fault Code Button  
RVSS Information Button  
• This button opens the Fault Code popup window, see  
Figure 8-3.  
• Navigates to the RVSS technical data screen, in this  
case, an ATS48 Soft Starter.  
Reset Faults Button  
State of Logic I/O Indicators  
• This button resets some active faults in the  
• These indicators change state (color) depending on  
the status of the description text, see Figure 8-3.  
RVSS. Major faults require  
a
480V power cy-  
cle by turning the main breaker disconnect to  
the OFF position and then back to ON position.  
• Green indicates engaged or running.  
• Red indicates fault.  
• Not illuminated is not in use.  
State of Logic  
I/O Indicators  
Figure 8-3. Soft Starter (RVSS) Screen - Fault Code Popup List  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 2  
Section 8 • Soft Starter Screen  
RVSS Conguration Screen  
Ready Indicator  
• This screen is only viewable when logged in with high  
level access, see Figure 8-4. Each parameter is con-  
gurable except the Motor Current (A) display and  
the Last Fault display.  
• This indicator turns green when the RVSS is ready to  
start only.  
Enable / Run / Stop / Off Buttons  
• These buttons are for Vilter Personnel use only.  
Unauthorized use may result in equipment damage  
or injury.  
WARNING  
Motor must be stopped before making changes. Must  
use motor nameplate data when conguring. Failure  
to comply may result in death, serious injury and/or  
damage to equipment.  
Figure 8-4. RVSS Conguration Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 3  
Section 8 • Soft Starter Screen  
Parameters  
• Pressing one of the numeric entry elds for a param-  
eter (i.e. Nominal Current Motor (FLA)) will open the  
numeric entry keypad. Enter a number within the set  
min/max range for that parameter. For an example,  
see Figure 8-5.  
• Must use motor nameplate data when conguring.  
Save Changes Button  
• After entering the desired parameters, press the save  
button to save the changes to the RVSS.  
Figure 8-5. RVSS Conguration Screen - Nominal Motor Current Numeric  
Entry Keypad  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 4  
Section 8 • Soft Starter Screen  
Change Class Button  
• This button opens a popup window to allow changes  
to the overload class of the RVSS, see Figure 8-6.  
Figure 8-6. RVSS Conguration Screen - Change Class Popup Window  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 5  
Section 8 • Soft Starter Screen  
Change Signal Button  
• This button opens a popup window to allow changes  
to the analog output signal current, see Figure 8-7.  
Figure 8-7. RVSS Conguration Screen - Change Signal Popup Window  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
8 – 6  
Section 9 • Oil Pump Motor Starter Screen  
Last Fault Display  
Oil Pump Motor Starter Screen  
• Both screen and popup, displays the “last fault” ad-  
dress stored in the fault register.  
The Oil Pump Motor Starter screen shows information  
from the TeSys U via Modbus communication. This  
screen is read only and does not require a login to view,  
see Figure 9-1.  
Fault Code Button  
• This button opens the Fault Code popup window.  
NOTE  
The oil pump motor starter shown and used for the  
following description is a Tesys U motor starter.  
Reset Faults Button  
• This button resets simple active faults in the start-  
er. Major faults require resetting the switch on the  
TeSys U motor starter.  
Oil Pump Motor Starter (TeSys U) Conguration  
Button  
• Navigates to Oil Pump Motor Starter Conguration  
screen for changing critical parameters. This but-  
ton, shown in Figure 9-1, is visible only when logged  
in with high level access. For Oil Pump Motor Starter  
Conguration screen, see Figure 9-3.  
TeSys U Information Button  
• Navigates to the oil pump starter technical data  
screen, in this case, a TeSys U motor starter.  
Figure 9-1. Oil Pump Motor Starter Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
9 – 1  
Section 9 • Oil Pump Motor Starter Screen  
State of Logic I/O Indicators  
Warning (Last Fault) Display  
• These indicators change state (color) depending on  
the status of the description text, see Figure 9-2.  
• Both screen and popup list displays the “last fault”  
address stored in the starter fault register, see  
Figure 9-2.  
• Green indicates engaged or running.  
• Red indicates fault.  
Reset Warnings Button  
• Not illuminated is not in use.  
• This button resets active warning faults in the starter.  
State of Logic I/O Indicators  
Figure 9-2. Oil Pump Motor Starter Screen - Warning Fault Code Popup List  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
9 – 2  
Section 9 • Oil Pump Motor Starter Screen  
Oil Pump Motor Starter (TeSys U) Conguration  
Run / Stop Buttons  
Screen  
• These buttons are for Vilter Personnel use only.  
Unauthorized use may result in equipment damage  
or injury.  
• This screen is only viewable when logged in with  
high level access, see Figure 9-3. Each parameter is  
congurable.  
Control Mode Local/Remote - Change Mode  
Button  
WARNING  
• These buttons are for Vilter Personnel use only.  
Unauthorized use may result in equipment damage  
or injury.  
Motor must be stopped before making changes. Must  
use motor nameplate data when conguring. Failure  
to comply may result in death, serious injury and/or  
damage to equipment.  
Type in % of motor over-  
load to equal motor FLA  
Figure 9-3. Oil Pump Motor Starter Conguration Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
9 – 3  
Section 9 • Oil Pump Motor Starter Screen  
Parameters  
Setting the %FLA Value  
• Pressing one of the numeric entry elds for a param-  
eter (i.e. Undercurrent Trip (%FLA)) will open the nu-  
meric entry keypad. Enter a number within the set  
min/max range for that parameter. For an example,  
see Figure 9-4.  
• To set the %FLA value from the motor nameplate  
data, the percentage of the TeSys U overload must be  
entered to equal the motor FLA, see Figure 9-3.  
• For example, if the TeSys U has a 5A maximum over-  
load and the motor FLA is 1.4A. Divide 1.4 by 5 to  
equal 28% (1.4 / 5 = .28). Type in 28 to equal 1.4A (.28  
x 5 = 1.4).  
• Must use motor nameplate data when conguring.  
Disable Phase Fault Button  
• This button allows the operator to shut off the Phase  
Disable. The phase imbalance should be increased to  
allow the motor to keep running until the motor can  
be replaced.  
NOTE  
At this point the motor is going to fail, it’s just a matter  
of when, this action may allow enough time to get a  
new motor installed.  
Figure 9-4. Oil Pump Motor Starter Conguration Screen - Numeric Entry Keypad  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
9 – 4  
Section 10 • Power Monitor Screen  
Power Monitor Screen  
The Power Monitor screen shows information from the  
TeSys T via Modbus communication. This screen is read  
only and does not require a login to view, see Figure  
10-1.  
NOTE  
The Power Monitor shown and used for the following  
description is a TeSys T controller.  
Figure 10-1. Power Monitor Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
10 – 1  
Section 10 • Power Monitor Screen  
Power Monitor (Tesys T) Conguration Button  
Power Monitor (TeSys T) Conguration Screen  
• Navigates to the Power Monitor (TeSys T)  
Conguration screen for changing critical param-  
eters. This button, shown in Figure 10-1, is vis-  
ible only when logged in with high level access.  
For the Power Monitor Conguration screen, see  
Figure 10-2.  
• This screen is only viewable when logged in with  
high level access, see Figure 10-2. Each parameter is  
congurable.  
WARNING  
Motor must be stopped before making changes. Must  
use motor nameplate data when conguring. Failure  
to comply may result in death, serious injury and/or  
damage to equipment.  
Figure 10-2. Power Monitor Conguration Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
10 – 2  
Section 11 • Power Monitor Trend Screen  
Time Span  
Power Monitor Trend Screen  
• This numeric entry display sets the leading to lag-  
ging edge of the trend screen span; notice here the  
span is set to 2 minutes, so the time span is 8:23:50  
to 8:25:50 on this trend. Security is needed to make  
changes to this numeric entry display.  
The Power Monitor Trend screen shows informa-  
tion via Modbus communication. The pens are pre-  
set and listed at the bottom of the screen. This screen  
is read only and does not require a login to view, see  
Figure 11-1.  
NOTE  
Range Span  
The Power Monitor Trend screen shown is for the  
TeSys T controller.  
• This numeric entry display set the upper limit of the  
range. Here the upper limit is set to 600, notice the  
scale on the right of the trend screen shows 0 to 600.  
Security is needed to make changes to this numeric  
entry display.  
Calendar Window  
• Pressing the calendar in the upper left of the trend  
screen enlarges the calendar. From the calendar,  
the operator can select dates of past trends, see  
Figure 11-3.  
Time Range  
Time Span  
Range Span  
Figure 11-1. Power Monitor Trend Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
11 – 1  
Section 11 • Power Monitor Trend Screen  
Forward and Reverse Buttons  
• The forward and reverse buttons allow you to incre-  
ment through the time range, see Figure 11-2.  
Play and Pause Buttons  
• This button allows you to run or pause the trend, see  
Figure 11-2.  
Figure 11-2. Power Monitor Trend Screen - Reverse/Pause/Play/Forward Buttons  
Figure 11-3. Power Monitor Trend Screen - Calendar Window (Enlarged)  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
11 – 2  
Section 11 • Power Monitor Trend Screen  
Time Span  
Power Monitor Trend Screen  
• This numeric entry display sets the leading to lag-  
ging edge of the trend screen span; notice here the  
span is set to 2 minutes, so the time span is 8:23:50  
to 8:25:50 on this trend. Security is needed to make  
changes to this numeric entry display.  
The Power Monitor Trend screen shows informa-  
tion via Modbus communication. The pens are pre-  
set and listed at the bottom of the screen. This screen  
is read only and does not require a login to view, see  
Figure 11-1.  
NOTE  
Range Span  
The Power Monitor Trend screen shown is for the  
TeSys T controller.  
• This numeric entry display set the upper limit of the  
range. Here the upper limit is set to 600, notice the  
scale on the right of the trend screen shows 0 to 600.  
Security is needed to make changes to this numeric  
entry display.  
Calendar Window  
• Pressing the calendar in the upper left of the trend  
screen enlarges the calendar. From the calendar,  
the operator can select dates of past trends, see  
Figure 11-3.  
Time Range  
Time Span  
Range Span  
Figure 11-1. Power Monitor Trend Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
11 – 1  
Section 11 • Power Monitor Trend Screen  
Forward and Reverse Buttons  
• The forward and reverse buttons allow you to incre-  
ment through the time range, see Figure 11-2.  
Play and Pause Buttons  
• This button allows you to run or pause the trend, see  
Figure 11-2.  
Figure 11-2. Power Monitor Trend Screen - Reverse/Pause/Play/Forward Buttons  
Figure 11-3. Power Monitor Trend Screen - Calendar Window (Enlarged)  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
11 – 2  
Section 12 • Compressor Motor Trend Screen  
Time Span  
Compressor Motor Trend Screen  
• This numeric entry eld sets the leading to lagging  
edge of the trend screen span. In Figure 12-1, the  
span is set to 2 minutes, so the time span is 8:23:50  
to 8:25:50 on this trend. High level access login is  
needed to make changes to this eld.  
The Compressor Motor Trend screen shows information  
from the RVSS via Modbus communication. The pens are  
preset and listed at the bottom of the screen. This screen  
does not require a login to view, see Figure 12-1. Both  
setpoints, Normal Run Current and Run Current Warning  
are congurable.  
Data Limit  
• This numeric entry eld set the upper limit of the  
range. In Figure 12-1, the upper limit is set to 500.  
The scale on the right side of the trend screen corre-  
sponds to the upper limit, displaying 0 to 500. High  
level access login is needed to make changes to this  
eld.  
Calendar Window  
• Pressingthecalendarintheupperleftofthetrendscreen  
enlarges the calendar. From the calendar, the opera-  
tor can select dates of past trends. For an example, see  
Figure 11-3 (page 11-2).  
Time Range  
Time Span  
Data Limit  
Figure 12-1. Compressor Motor Trend Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
12 – 1  
Section 12 • Compressor Motor Trend Screen  
Normal Run Current  
• This setpoint sets the pen for the Normal Run Current  
of the motor. The actual motor current should trend  
around this set point; but may vary depending on the  
loading of the motor. This should be adjusted by the  
operator for their application.  
Run Current Warning  
• This setpoint sets the pen for the Run Current  
Warning. If the current reaches this warning limit, the  
HMI will show an Alarm banner and register the event  
in the Alarm Log. The Alarm banner will remain visible  
until the motor current dips below the set point.  
• Typical Run Current Warning is the Full Load Amps  
from the motor nameplate or specic application.  
Normal  
Run  
Current  
Run  
Current  
Warning  
Figure 12-2. Compressor Motor Trend Screen - Normal Run Current & Run Current Warning  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
12 – 2  
Section 13 • Oil Pump Motor Trend Screen  
Time Span  
Oil Pump Motor Trend Screen  
• This numeric entry eld sets the leading to lagging  
edge of the trend screen span. High level access login  
is needed to make changes to this eld.  
The Oil Pump Motor Trend screen shows informa-  
tion from the TeSys U via Modbus communication.  
The pens are preset and listed at the bottom of the  
screen. This screen does not require a login to view, see  
Figure 13-1.  
Data Limit  
• This numeric entry eld set the upper limit of the  
range. High level access login is needed to make  
changes to this eld.  
Calendar Window  
• Pressing the calendar in the upper left of the trend  
screen enlarges the calendar. From the calendar, the  
operator can select dates of past trends. For an ex-  
ample, see Figure 11-3 (page 11-2).  
Time Range  
Time Span  
Data Limit  
Figure 13-1. Oil Pump Motor Trend Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
13 – 1  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
13 – 2 / Blank  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
Blank / 14 – 1  
Section 14 • Alarm & Event Log Screen  
Alarm & Event Log Screen  
The Alarm & Event Log screen shows faults and events  
that either active or inactive, see Figure 14-1. The faults  
and events will populate the lines until they reach the  
maximum, then it will populate in a rst in, rst out se-  
quence. The Alarm & Event Log will also be stored on the  
ash card. Also, when the ash card lls up, it will store  
in a rst in, rst out sequence. The ash card will store  
faults and events for up to 30 days.  
Figure 14-1. Alarm & Event Log Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
14 – 2  
Section 14 • Alarm & Event Log Screen  
Acknowledge All  
Scroll Buttons  
• This button acknowledges the fault and turns the text  
turns yellow as long as the fault is no longer active.  
• These buttons scroll up and down the Fault/Event  
lists.  
Acknowledge  
Page Buttons  
• This button clears the fault and turns the text green  
as long as the fault is no longer active.  
• These buttons page up and down the Fault/Event  
lists.  
Acknowledge All  
Acknowledge  
Scroll Buttons  
Page Buttons  
Figure 14-2. Alarm & Event Log Screen - Push Buttons  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
14 – 3  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
14 – 4 / Blank  
Section 15 • Motor Starter Drawings Screen  
Motor Starter Drawings Screen  
The Motor Starter Drawings screen, shown in Figure  
15-1, show drawings associated with the motor starter  
package. The number of screens depend on the size of  
the drawing set. The drawings shown are as-designed  
drawings.  
Drawing Menu  
• Displays all associated as-designed drawings in a  
popup window, see Figure 15-2.  
Zoom In/Out Buttons  
• Enlarges or reduces image of drawing, see Figure  
15-3.  
Figure 15-1. Motor Starter Drawings Screen  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
15 – 1  
Section 15 • Motor Starter Drawings Screen  
Figure 15-2. Drawing Menu  
Figure 15-3. Zoom In/Out Buttons  
Vilter Motor Starter Refrigeration HMI Operation Manual • Emerson Climate Technologies • 35391MSR  
15 – 2  
35391MSR Rev. 1 (8/14) Emerson and Vilter are trademarks of Emerson Electric Co. or one of its afliated companies. © 2014 Emerson Climate Technologies, Inc. All rights reserved. Printed in the USA.  

Sony Cv P12px User Manual
Smart Ups Apcrbc132 User Manual
Sanyo Xhx2452 User Manual
Sanyo Khs3672r User Manual
Samsung Aqt18wjwb User Manual
HP 8341B User Manual
CRAFTSMAN 921.152100 User Manual
CRAFTSMAN 917.773410 User Manual
CRAFTSMAN 917.274350 User Manual
ASUS X01AD ZB633KL User Manual