DIXELL EMERSON XR35CH User Manual

b. Auxiliary thermostat  
I.E.. anti condensing heater) with the possibility of switching it on and off also by keyboard  
Parameters involved:  
Digital controller for medium temperature  
refrigeration applications  
- ACH Kind of regulation for the auxiliary relay: Ht: heating; cL: cooling;  
- SAA Set point for auxiliary relay  
- SHy Differential for auxiliary relay  
- ArP Probe for auxiliary relay  
- Sdd Auxiliary output off during defrost  
XR35CH  
-Manual for the SW rel. 2.6-  
By means of these 5 parameters the functioning of the auxiliary relay can be set.. The differential is  
given by the SHy parameter.  
NOTE: Set oA1 =AUS and ArP= nP (no probe for auxiliary output).  
In this case the relay 1-7 can be activated only by digital input with i1F or i2F = AUS.  
3.3.4 On/off relay oA1 = onF  
In this case the relay is activated when the controller is turned on and de-activated when the controller  
is turned off.  
1. GENERAL WARNING  
1.1 PLEASE READ BEFORE USING THIS MANUAL  
3.3.5 Neutral zone regulation  
With oA1 = db the relay 1-7 can control a heater element to perform a neutral zone action.  
oA1 cut in = SET-HY  
oA1 cut out = SET  
This manual is part of the product and should be kept near the instrument for easy and quick  
reference.  
The instrument shall not be used for purposes different from those described hereunder. It cannot be  
used as a safety device.  
Check the application limits before proceeding.  
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring  
the same and unchanged functionality.  
3.3.6 Alarm relay  
With oA1 = ALr the relay 1-7 operates as alarm relay. It is activated every time an alarm happens. Its  
status depends on the tbA parameter: if “tbA = y”, the relay is silenced by pressing any key.  
If “tbA = n”, the alarm relay remains on until the alarm condition recovers.  
1.2  
SAFETY PRECAUTIONS  
Check the supply voltage is correct before connecting the instrument.  
3.3.7 Night blind management during energy saving cycles  
With oA1 = HES, the relay 1-7 operates to manage the night blind: the relay is energised when the  
energy saving cycle is activated , by digital input, frontal button or RTC (optional)  
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden  
temperature changes with high atmospheric humidity to prevent formation of condensation  
Warning: disconnect all electrical connections before any kind of maintenance.  
Fit the probe where it is not accessible by the End User. The instrument must not be opened.  
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see  
address) with a detailed description of the fault.  
4. FRONT PANEL COMMANDS  
Consider the maximum current which can be applied to each relay (see Technical Data).  
Ensure that the wires for probes, loads and the power supply are separated and far enough from each  
other, without crossing or intertwining.  
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel  
with inductive loads could be useful.  
2. GENERAL DESCRIPTION  
Model XR35CH, format 32 x 74 mm, is a digital thermostat with off cycle defrost designed for  
refrigeration applications at normal temperature. It provides two relay outputs, one for the compressor,  
the other one can be used as light, for alarm signalling or as auxiliary output.. It could be provided with  
a Real Time Clock which allows programming of up to 6 daily defrost cycles, divided into holidays and  
workdays. A “Day and Night” function with two different set points is fitted for energy saving. It is also  
provided with up to four NTC or PT1000 probe inputs, the first one for temperature control, the second  
one, to be located onto the evaporator, to control the defrost termination temperature. One of the 2  
digital inputs can operate as third temperature probe. The fourth probe is used to signal the condenser  
temperature alarm or to display a temperature.  
: To display target set point; in programming mode it selects a parameter or confirm an  
operation.  
(DEF) To start a manual defrost  
(UP): To see the max. stored temperature; in programming mode it browses the parameter  
codes or increases the displayed value.  
(DOWN) To see the min stored temperature; in programming mode it browses the parameter  
codes or decreases the displayed value.  
The RS485 serial output allows to connect the unit to a network line ModBUS-RTU compatible such  
as the dIXEL monitoring units of X-WEB family. The HOT key receptacle allows to program the  
controller by means the HOT KEY programming keyboard.  
To switch the instrument off, if onF = oFF.  
The instrument is fully configurable through special parameters that can be easily programmed  
through the keyboard.  
To switch the light, if oA1 = Lig.  
KEY COMBINATIONS:  
3. CONTROLLING LOADS  
+
To lock & unlock the keyboard.  
  
+
+
To enter in programming mode.  
3.1 COMPRESSOR  
The regulation is performed according to  
the temperature measured by the  
Temper.  
To return to the room temperature display.  
thermostat probe with  
a
positive  
4.1 USE OF LEDS  
SET  
differential from the set point: if the  
temperature increases and reaches set  
point plus differential the compressor is  
started and then turned off when the  
temperature reaches the set point value  
again.  
Each LED function is described in the following table.  
Time  
LED MODE  
FUNCTION  
Compr.  
ON  
ON  
Flashing Anti-short cycle delay enabled  
ON Defrost enabled  
Flashing Drip time in progress  
Compressor enabled  
In case of fault in the thermostat probe the start and stop of the compressor are timed through  
parameters “COn” and “COF”.  
ON  
ON  
An alarm is occurring  
3.2 DEFROST  
With oA1 different from dEF and tdF = EL the controller performs timed defrost, simply stopping the  
compressor.  
With oA1 = dEF two defrost modes are available through the “tdF” parameter: defrost through  
electrical heater (tdF = EL) and hot gas defrost (tdF = in), in this case the second relay has to set ase  
The defrost interval depends on the presence of the RTC (optional). If the RTC is present is controlled  
by means of parameter “EdF”:  
Continuous cycle is running  
ON  
ON  
Energy saving enabled  
Light on  
ECO  
ON  
°C/°F ON  
°C/°F Flashing Programming phase  
Auxiliary relay on  
Measurement unit  
-
-
with EdF=in the defrost is made every “IdF” time – standard way for controller without RTC.  
with EdF = “rtc”, the defrost is made in real time depending on the hours set in the parameters  
Ld1..Ld6 on workdays and in Sd1…Sd6 in holidays;  
5. MAX & MIN TEMPERATURE MEMORIZATION  
5.1 HOW TO SEE THE MIN TEMPERATURE  
Other parameters are used to control defrost cycles: its maximum length (MdF) and two defrost  
modes: timed or controlled by the evaporator’s probe (P2P).  
3.3 SECOND RELAY CONFIGURATION (PAR. OA1; TERM. 1-7)  
1. Press and release the nkey.  
The functioning of the auxiliary relay (terminals. 1-7) can be set by the oA1 parameter, according to  
the kind of application. In the following paragraph the possible setting:  
2. The “Lo” message will be displayed followed by the minimum temperature recorded.  
3. By pressing the nkey again or by waiting 5s the normal display will be restored.  
3.3.1 Defrost relay oA1 = dEF  
With oA1 = dEF the second relay operates as defrost relay. See paragraph 3.2 for more details.  
5.2 HOW TO SEE THE MAX TEMPERATURE  
1. Press and release the okey.  
3.3.2 Light relay  
2. The “Hi” message will be displayed followed by the maximum temperature recorded.  
3. By pressing the okey again or by waiting 5s the normal display will be restored.  
With oA1 = Lig the relay 1-7 operates as a light.  
3.3.3 Auxiliary relay oA1 = AUS  
a. Relay activation by digital input 2 (oA1 = AUS, i2F = AUS)  
With oA1 = AUS and i2F = AUS the relay 1-7 is switched on and off by digital.  
1592038080 XR35CH GB r1.0 17.03.2015  
XR35CH  
1/5  
ArP Probe selection for auxiliary: nP = no probe, the auxiliary relay is switched only by the digital  
input; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display  
probe); P4 = Probe 4.  
Sdd Auxiliary relay off during defrost: n = the auxiliary relay operates during defrost.  
y = the auxiliary relay is switched off during defrost.  
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)  
Ld1÷Ld6 Workday defrost start (0 ÷ 23h 50 min.) These parameters set the beginning of the 6  
programmable defrost cycles during workdays. Ex. When Ld2 = 12.4 the second defrost starts at  
12.40 during workdays.  
Sd1÷Sd6 Holiday defrost start (0 ÷ 23h 50 min.) These parameters set the beginning of the 6  
programmable defrost cycles on holidays. Ex. When Sd2 = 3.4 the second defrost starts at 3.40  
on holidays.  
ALARMS  
ALP Probe selection for alarm: nP = no probe, the temperature alarms are disabled; P1 = Probe 1  
(Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe); P4 = Fourth  
probe.  
N.B. :To disable a defrost cycle set it to “nu”(not used). Ex. If Ld6=nu ; the sixth defrost  
cycle is disabled  
ALC Temperature alarms configuration: (Ab; rE)  
OTHER  
Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =  
temperature alarms are referred to the set point. Temperature alarm is enabled when the  
temperature exceeds the “SET+ALU” or “SET-ALL” values.  
Adr Serial address (1÷244): Identifies the instrument address when connected to a ModBUS  
compatible monitoring system.  
PbC Type of probe: it allows to set the kind of probe used by the instrument: Pt1 = Pt1000 probe,  
ntc = NTC probe.  
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it.  
dP1 Thermostat probe display  
dP2 Evaporator probe display  
dP3 Third probe display- optional.  
dP4 Fourth probe display.  
rSE Real set point: it shows the set point used during the energy saving cycle or during the  
continuous cycle.  
rEL Software release for internal use.  
ALU MAXIMUM temperature alarm: (ALL÷110°C; ALL÷230°F) when this temperature is reached  
the alarm is enabled, after the “ALd” delay time.  
ALL Minimum temperature alarm: (-100°C ÷ ALU; -148÷ALU when this temperature is reached the  
alarm is enabled, after the “ALd” delay time.  
AFH Differential for temperature alarm recovery: (0,1÷25,5°C; 1÷45°F) Intervention differential for  
recovery of temperature alarm.  
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm  
condition and alarm signalling.  
dAO Exclusion of temperature alarm at start-up: (from 0.0 min to 23.5h) time interval between the  
detection of the temperature alarm condition after instrument power on and alarm signalling.  
Ptb Parameter table code: readable only.  
CONDENSER TEMPERATURE ALARM  
AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe;  
P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.  
AL2 Low temperature alarm of condenser: (-100÷150°C; -148÷302°F) when this temperature is  
reached the LA2 alarm is signalled, possibly after the Ad2 delay.  
Au2 High temperature alarm of condenser: (-100÷150°C; -148÷302°F) when this temperature is  
reached the HA2 alarm is signalled, possibly after the Ad2 delay.  
AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F)  
Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the  
condenser alarm condition and alarm signalling.  
dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min)  
bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on  
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation  
restarts after AC time at minimum.  
8. DIGITAL INPUTS  
The first digital input 18-20 is enabled with P3P = n.  
With P3P = n and i1F = i2F the second digital input is disabled  
The free voltage digital inputs are programmable by the “i1Fand i2F parameters.  
8.1 GENERIC ALARM (i2F = EAL)  
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the  
EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is  
de-activated.  
8.2 SERIOUS ALARM MODE (i2F = bAL)  
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm  
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-  
activated.  
AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on  
working; Y = yes, compressor is switched off till the alarm is present, in any case regulation  
restarts after AC time at minimum.  
AUXILIARY RELAY  
8.3 PRESSURE SWITCH (i2F = PAL)  
tbA Alarm relay silencing (with oA1 =ALr):  
If during the interval time set by “did” parameter, the pressure switch has reached the number of  
activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The  
compressor and the regulation are stopped. When the digital input is ON the compressor is always  
OFF. If the nPS activation in the did time is reached, switch off and on the instrument to restart  
normal regulation.  
n= silencing disabled: alarm relay stays on till alarm condition lasts,  
y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm  
oA1 Second relay configuration (1-7): dEF = defrost, FAn: do not select it!. ALr: alarm; Lig: light;  
AuS: Auxiliary relay; onF: always on with instrument on; db= neutral zone; cP2 = do not select  
it!; dEF2: do not select it!;. HES:. night blind  
AoP Alarm relay polarity: it set if the alarm relay is open or closed when an alarm happens. CL=  
terminals 1-7 closed during an alarm; oP = terminals 1-7 open during an alarm  
8.4 DOOR SWITCH INPUT (i1F or i2F = dor)  
It signals the door status and the corresponding relay output status through the “odc” parameter: no,  
Fan = normal (any change); CPr; F_C = Compressor OFF.  
Since the door is opened, after the delay time set through parameter “doA”, the door alarm is enabled,  
the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as  
soon as the external digital input is disabled again. With the door open, the high and low temperature  
alarms are disabled.  
DIGITAL INPUTS  
i1P Digital input polarity (18-20): oP: the digital input is activated by opening the contact; CL: the  
digital input is activated by closing the contact.  
i1F Digital input configuration (18-20): dor= door switch function; dEF= activation of a defrost cycle;  
i2P 2nd digital input polarity (18-19): oP: the digital input is activated by opening the contact; CL:  
the digital input is activated by closing the contact.  
i2F 2nd digital input configuration (18-19): EAL= external alarm: “EA” message is displayed; bAL=  
serious alarm “CA” message is displayed. PAL= pressure switch alarm, “CA” message is  
displayed; dor= door switch function; dEF= activation of a defrost cycle; ES = energy saving;  
AUS=auxiliary relay activation with 0A3 = AUS; Htr= kind of action inversion (cooling heating);  
FAn= fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the controller off.  
did (0255 min) with i2F= EAL or i2F = bAL digital input alarm delay (18-20): delay between the  
detection of the external alarm condition and its signalling.  
8.5 START DEFROST (i1F or i2F = dEF)  
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will  
restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time  
is expired.  
8.6 SWITCH THE AUXILIARY RELAY (i2F = AUS)  
With oA1 = AUS the digital input switched the status of the auxiliary relay  
with i2F= PAL: time for pressure switch function: time interval to calculate the number of the  
pressure switch activation.  
doA Door open signalling delay (0255 min):  
nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the “did”  
interval, before signalling the alarm event (I2F= PAL).  
8.7 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i2F=Htr)  
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.  
If the nPS activation in the did time is reached, switch off and on the instrument to restart  
normal regulation.  
odc Compressor status when open door: no; FAn = normal; CPr, F_C = Compressor OFF.  
rrd Outputs restart after doA alarm: no= outputs not affected by the doA alarm; yES = outputs  
restart with the doA alarm.  
8.8 ENERGY SAVING (i2F = ES)  
The Energy Saving function allows to change the set point value as the result of the SET+ HES  
(parameter) sum. This function is enabled until the digital input is activated.  
8.9 HOLIDAY DEFROST (i2F = HDF) ONLY FOR MODELS WITH RTC  
This function enabled the holiday defrost setting.  
HES Temperature increase during the Energy Saving cycle:  
(-30,0°C30,0°C) it sets the increasing value of the set point during the Energy Saving cycle.  
TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)  
8.10 ON OFF FUNCTION (i2F = onF)  
To switch the controller on and off.  
Hur  
Min  
Current hour (0 ÷ 23 h)  
Current minute (0 ÷ 59min)  
dAY Current day (Sun ÷ SAt)  
8.11 DIGITAL INPUTS POLARITY  
The digital input polarity depends on the “i1Pand “i2P” parameters.  
i1P or i2P =CL: the input is activated by closing the contact.  
i1P or i2P=OP: the input is activated by opening the contact  
Hd1  
Hd2  
First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times.  
Second weekly holiday (Sun ÷ nu) Set the second day of the week which follows the holiday  
times.  
N.B. Hd1,Hd2 can be set also as “nu” value (Not Used).  
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)  
9. RS485 SERIAL LINE FOR MONITORING SYSTEMS  
The RS485 serial line, allows to connect the instrument to a monitoring system ModBUS-RTU  
compatible such as the X-WEB500/3000/300.  
ILE  
Energy Saving cycle start during workdays: (0 ÷ 23h 50 min.) During the Energy Saving  
cycle the set point is increased by the value in HES so that the operation set point is SET +  
HES.  
dLE  
ISE  
Energy Saving cycle length during workdays: (0 ÷ 24h 00 min.) Sets the duration of the  
Energy Saving cycle on workdays.  
Energy Saving cycle start on holidays. (0 ÷ 23h 50 min.)  
10. X-REP OUTPUT OPTIONAL  
As optional, an X-REP can be connected to the instrument, trough the dedicated  
connector.  
dSE Energy Saving cycle length on holidays (0  
÷
24h 00 min.)  
1592038080 XR35CH GB r1.0 17.03.2015  
XR35CH  
3/5  
To connect the X-REP to the  
instrument the following connectors  
must be used CAB-51F(1m), CAB-  
52F(2m), CAB-55F(5m),  
noP  
In programming mode: none parameter is present in Pr1  
On the display or in dP2, dP3, dP4: the selected probe is nor enabled  
15. TECHNICAL DATA  
Housing: self extinguishing ABS.  
Case: frontal 38x80mm; depth 62mm;  
11. INSTALLATION AND MOUNTING  
Instrument XR35CH shall be mounted on vertical panel, in a 29x71  
mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 060 °C.  
Avoid places subject to strong vibrations, corrosive gases,  
excessive dirt or humidity. The same recommendations apply to  
probes. Let air circulate by the cooling holes.  
Mounting: panel mounting in a 71x29mm panel cut-out  
Protection: IP20; Frontal protection: IP65  
Connections: Screw terminal block 2,5 mm2 wiring.  
Power supply: according to the model 24Vac, ±10%; 230Vac 10%, 50/60Hz, 110Vac 10%,  
50/60Hz  
Power absorption: 3VA max  
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PT1000 probes.  
Digital inputs: free voltage contact  
Relay outputs: compressor SPST 8(3) A, 250Vac or SPST 16A 250Vac  
aux: SPDT 8(3) A, 250Vac  
Data storing: on the non-volatile memory (EEPROM).  
Internal clock back-up: 24 hours  
Kind of action: 1B; Pollution grade: 2;Software class: A.;  
Rated impulsive voltage: 2500V; Overvoltage Category: II  
Operating temperature: 0÷55°C; Storage temperature: -30÷85 °C.  
Relative humidity: 2085% (no condensing)  
12. ELECTRICAL CONNECTIONS  
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5  
mm2. Before connecting cables make sure the power supply complies with the instrument’s  
requirements. Separate the probe cables from the power supply cables, from the outputs and the  
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier  
loads use a suitable external relay.  
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);  
PT1000 probe: -100÷150°C (-148÷302°F)  
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit  
12.1 PROBE CONNECTION  
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid  
infiltration. It is recommended to place the thermostat probe away from air streams to correctly  
measure the average room temperature. Place the defrost termination probe among the evaporator  
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during  
defrost, to prevent premature defrost termination.  
16. CONNECTIONS  
13. HOW TO USE THE HOT KEY  
13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)  
1.  
2.  
Program one controller with the front keypad.  
When the controller is ON, insert the “Hot key” and push okey; the "uPL" message appears  
followed a by flashing “End”  
3.  
4.  
Push “SET” key and the End will stop flashing.  
Turn OFF the instrument remove the “Hot Key”, then turn it ON again.  
NOTE: the “Err” message is displayed for failed programming. In this case push again okey if you  
want to restart the upload again or remove the “Hot key” to abort the operation.  
Supply: 120Vac or 24Vac: connect to terminals 5-6.  
The X-REP output is optional  
13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY  
(DOWNLOAD)  
1.  
2.  
3.  
Turn OFF the instrument.  
17. DEFAULT SETTING VALUES  
Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.  
Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory,  
the “doL” message is blinking followed a by flashing “End”.  
After 10 seconds the instrument will restart working with the new parameters.  
Remove the “Hot Key”..  
Label  
Name  
Range  
LS÷US  
-
Value Level  
Set Set point  
rtc* Real time clock menu  
Hy Differential  
LS Minimum set point  
US Maximum set point  
3.0  
-
- - -  
Pr1  
Pr1  
Pr2  
Pr2  
Pr1  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr1  
Pr2  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr1  
Pr1  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
4.  
5.  
2.0  
-50.0  
110  
0.0  
Y
0,125.5°C/ 1255°F  
-100CSET/-58°FSET  
SET110°C/ SET 230°F  
-1212°C /-120120°F  
n=not present; Y=pres.  
-1212°C /-120120°F  
n=not present; Y=pres.  
-1212°C /-120120°F  
n=not present; Y=pres.  
-1212°C /-120120°F  
0÷255 min  
0 50 min  
0 ÷ 100 (100=P1 , 0=P2)  
0.0÷24.0h  
(-100÷150,0°C) (-67÷302°F)  
0 255 min  
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on  
if you want to restart the download again or remove the “Hot key” to abort the operation.  
Ot Thermostat probe calibration  
P2P Evaporator probe presence  
OE Evaporator probe calibration  
P3P Third probe presence  
14. ALARM SIGNALS  
0.0  
n
0
n
0
Message  
“P1”  
Cause  
Room probe failure  
Outputs  
Compressor output acc. to par. “Con” and “COF”  
Defrost end is timed  
Outputs unchanged  
Outputs unchanged  
Outputs unchanged.  
Outputs unchanged.  
It depends on the “Ac2” parameter  
It depends on the “bLL” parameter  
Compressor restarts  
O3 Third probe calibration  
“P2”  
“P3”  
P4”  
“HA”  
“LA”  
"HA2"  
"LA2"  
“dA”  
“EA”  
“CA”  
“CA”  
“rtc”  
Evaporator probe failure  
Third probe failure  
P4P Fourth probe presence  
O4 Fourth probe calibration  
OdS Outputs delay at start up  
AC Anti-short cycle delay  
rtr P1-P2 percentage for regulation  
CCt Continuous cycle duration  
CCS Set point for continuous cycle  
COn Compressor ON time with faulty probe  
COF Compressor OFF time with faulty probe  
CH Kind of action  
Fourth probe failure  
Maximum temperature alarm  
Minimum temperature alarm  
Condenser high temperature  
Condenser low temperature  
Door open  
External alarm  
Serious external alarm (i1F=bAL) All outputs OFF.  
Pressure switch alarm (i1F=PAL) All outputs OFF  
0
1
100  
0.0  
3
15  
30  
cL  
°C  
dE  
P1  
P1  
0.0  
50  
rtc  
EL  
P2  
8.0  
8
Output unchanged.  
0 255 min  
CL; Ht  
°C °F  
in=integer; dE= dec.point  
CF Temperature measurement unit  
rES Resolution  
Lod Probe displayed  
rEd2 X-REP display  
Real time clock alarm  
Alarm output ON; Other outputs unchanged;  
Defrosts according to par. “IdF” Set real time clock  
has to be set  
Alarm output ON; Other outputs unchanged;  
Defrosts according to par. “IdF” Contact the service  
P1;P2  
P1 P2 P3 P4 SEt dtr  
0 ÷ 20.0 min (10 sec.)  
1 ÷ 99  
rtF  
Real time clock board failure  
dLy Display temperature delay  
dtr P1-P2 percentage for display  
EdF* Kind of interval for defrost  
tdF Defrost type  
dFP Probe selection for defrost termination  
dtE Defrost termination temperature  
IdF Interval between defrost cycles  
MdF (Maximum) length for defrost  
dSd Start defrost delay  
dFd Displaying during defrost  
dAd MAX display delay after defrost  
Fdt Draining time  
dPo First defrost after start-up  
dAF Defrost delay after fast freezing  
ACH Kind of action for auxiliary relay  
SAA Set Point for auxiliary relay  
rtc ÷in  
14.1 SILENCING BUZZER / ALARM RELAY OUTPUT  
If “tbA = y”, the buzzer and the relay are is silenced by pressing any key.  
If “tbA = n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.  
EL=el. heater; in= hot gas  
nP; P1; P2; P3; P4  
-50 50 °C  
1 120 ore  
0 255 min  
0÷99min  
rt, it, SEt, DEF  
0 ÷ 255 min  
0÷120 min  
n=after IdF; y=immed.  
0 ÷ 23h e 50’  
14.2 ALARM RECOVERY  
Probe alarms P1”, “P2”, P3” and “P4” start some seconds after the fault in the related probe; they  
automatically stop some seconds after the probe restarts normal operation. Check connections before  
replacing the probe.  
Temperature alarms “HA, LA” “HA2” and “LA2automatically stop as soon as the temperature  
returns to normal values.  
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.  
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.  
20  
0
it  
30  
0
n
0.0  
cL  
0,0  
2,0  
nP  
n
CL; Ht  
-100÷110°C / -58÷230°F  
0,125.5°C/ 1255°F  
nP / P1 / P2 / P3/P4  
n÷y  
14.3 OTHER MESSAGES  
Differential for auxiliary relay  
SHy  
Pon  
PoF  
Keyboard unlocked.  
Keyboard locked  
ArP Probe selection for auxiliary relay  
Sdd Auxiliary relay operating during defrost  
1592038080 XR35CH GB r1.0 17.03.2015  
XR35CH  
4/5  
Label  
Name  
Range  
Value Level  
ALP Alarm probe selection  
nP; P1; P2; P3; P4  
P1  
Pr2  
ALc Temperat. alarms configuration  
rE= related to set;  
Ab = absolute  
Ab  
Pr2  
ALU MAXIMUM temperature alarm  
ALL Minimum temperature alarm  
110,0  
-50,0  
2,0  
15  
1,3  
P4  
-40  
110  
5
Pr1  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Pr2  
Set110.0°C; Set÷230°F  
-100°CSet/ -58°FSet  
(0,1°C÷25,5°C) (1°F÷45°F)  
0 255 min  
0 23h e 50’  
nP; P1; P2; P3; P4  
(-100 ÷ 150°C) (-67÷ 302°F)  
(-100 ÷ 150°C) (-67÷ 302°F)  
AFH Differential for temperat. alarm recovery  
ALd Temperature alarm delay  
dAO Delay of temperature alarm at start up  
AP2 Probe for temperat. alarm of condenser  
AL2 Condenser for low temperat. alarm  
AU2 Condenser for high temperat. alarm  
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F]  
Ad2 Condenser temperature alarm delay  
dA2 Delay of cond. temper. alarm at start up  
Compr. off for condenser low temperature  
bLL alarm  
0 ÷ 254 (min.) , 255=nU  
15  
1,3  
0.0 ÷ 23h 50’  
n
Pr2  
n(0) - Y(1)  
Compr. off for condenser high  
AC2 temperature alarm  
tbA Alarm relay disabling  
n
y
Pr2  
Pr2  
n(0) - Y(1)  
n=no; y=yes  
oA1 Second relay configuration  
ALr = alarm; dEF = defrost; Lig  
=Light; AUS =AUX; onF=always  
on; Fan= do not select it; db =  
neutral zone; cP2 = second  
compressor; dF2 = do not select  
it; HES = night blind  
oP; cL  
oP=opening;CL=closing  
dor; dEF;  
oP=opening;CL=closing  
EAL - bAL- PAL - dor - dEF - ES  
- AUS - Htr - FAn - HdF - onF  
0÷255min  
0÷255min  
0 ÷15  
no; Fan; CPr; F_C  
n Y  
(-30°C÷30°C) (-54°F÷54°F)  
0 ÷ 23  
Lig  
Pr2  
AoP Alarm relay polarity (oA1=ALr)  
i1P Digital input polarity (18-20)  
i1F Digital input 1 configuration (18-20)  
i2P Digital input polarity (18-19)  
cL  
cL  
dor  
15  
Pr2  
Pr1  
Pr1  
Pr1  
i2F Digital input configuration (18-19)  
cL  
Pr2  
did Digital input alarm delay (18-20)  
doA Door open alarm delay  
Nps Number of activation of pressure switch  
odc Compress status when open door  
rrd Regulation restart with door open alarm  
HES Differential for Energy Saving  
Hur* Current hour  
EAL  
15  
15  
F-c  
y
0
-
-
-
Pr2  
Pr1  
Pr2  
Pr2  
Pr2  
Pr2  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Min* Current minute  
0 ÷ 59  
dAY* Current day  
Sun ÷ SAt  
Hd1* First weekly holiday  
Sun÷ SAt nu  
nu  
nu  
Hd2* Second weekly holiday  
ILE* Energy Saving cycle start during  
workdays  
dLE* Energy Saving cycle length during  
workdays  
Sun÷ SAt nu  
0 ÷ 23h 50 min.  
0.0  
0
Pr1  
Pr1  
0 ÷ 24h 00 min.  
ISE* Energy Saving cycle start on holidays  
dSE* Energy Saving cycle length on holidays  
Ld1* 1st workdays defrost start  
Ld2* 2nd workdays defrost start  
Ld3* 3rd workdays defrost start  
Ld4* 4th workdays defrost start  
Ld5* 5th workdays defrost start  
Ld6* 6th workdays defrost start  
Sd1* 1st holiday defrost start  
Sd2* 2nd holiday defrost start  
Sd3* 3rd holiday defrost start  
Sd4* 4th holiday defrost start  
Sd5* 5th holiday defrost start  
Sd6* 6th holiday defrost start  
Adr Serial address  
PbC Kind of probe  
onF on/off key enabling  
dP1 Room probe display  
dP2 Evaporator probe display  
dP3 Third probe display  
dP4 Fourth probe display  
rSE Real set  
rEL Software release  
Ptb Map code  
0 ÷ 23h 50 min.  
0 ÷ 24h 00 min.  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
0 ÷ 23h 50 min. - nu  
1÷247  
0.0  
0
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr1  
Pr2  
Pr2  
Pr2  
Pr1  
Pr1  
Pr1  
Pr1  
Pr2  
Pr2  
Pr2  
6.0  
13.0  
21.0  
nu  
nu  
nu  
6.0  
13.0  
21.0  
nu  
nu  
nu  
1
Pt1000; ntc  
nu, oFF; ES  
ntc  
nu  
-
-
-
--  
--  
--  
--  
-
-
actual set  
--  
--  
2.6  
-
* Only for model with real time clock  
2 Only for XR35CH with X-REP output  
1592038080 XR35CH GB r1.0 17.03.2015  
XR35CH  
5/5  

York Air Conditioner D2cg300 User Manual
Traxxas Automobile Parts 5304 User Manual
Trane 2ttx4 User Manual
Samsung As09a5 6 Maf User Manual
Oce North America Op1030 User Manual
Manual For Shark Ion Robot User Manual
JBL VENUE SUB12 User Manual
HITACHI CP WX5500 User Manual
ENVIROLITE WA09T35XXB User Manual
ASUS VZ249HE User Manual