York Dh 180 User Manual

262260-YTG-E-1008  
®
DESCRIPTION  
YORK Sunline Ultra™ units are convertible single package  
high efficiency rooftops. All models have independent dual  
refrigerant circuits for efficient part load operation. Although  
the units are primarily designed for curb mounting on a roof,  
they can also be slab-mounted at ground level or set on steel  
beams above a finished roof.  
TECHNICAL GUIDE  
All units include:  
Powder Paint finish that meets ASTM-B-117 1000 hour  
salt spray standards  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
AND SINGLE PACKAGE  
Two-stage cooling provided by dual independent refriger-  
ation circuits with expansion valves, filter-driers, high and  
low pressure/loss of charge switches and freezestats  
Hermetically sealed scroll compressors with crankcase  
heaters  
AIR CONDITIONERS  
DH 180, 210, 240 & 300  
Two-stage heating provided by dual independent heat  
exchangers with aluminized steel tubes, redundant gas  
valves, spark ignition with induced draft logic  
15, 17.5, 20 & 25 NOMINAL TONS  
10.8 EER (15 TONS), 10.2 EER (17.5 TONS), 9.7 EER (20  
TONS) AND 9.6 EER (25 TONS)  
Permanently lubricated motors  
Bottom or side air discharge configuration capability  
(field convertible)  
Belt drive blower motor with high static drive options  
Constant supply air volume (CV) with optional variable  
air volume (VAV)  
Manufactured under the quality standards of ISO9001  
Twenty-four volt control circuit with compressor lock-out  
Zero-25% fixed air damper with hood  
Copper tube/aluminum fin coils  
Hinged filter access and tool free latched doors optional  
Hinged tool free blower, blower motor, filters and electri-  
cal panel access optional  
Rigging holes in base rails for lifting  
Single point power connection  
Complete factory package - tested, charged and wired  
CSA agency approvals on all units  
WARRANTY  
Factory Limited Parts Warranty  
One-year parts warranty  
A Five-year parts warranty on the compressor and  
electric heat elements.  
Ten-year parts warranty on the gas-fired heat  
exchangers.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
262260-YTG-E-1008  
PRODUCT NOMENCLATURE  
15-25 Ton Sunline Ultra™ Model Number Nomenclature  
D H 180 N24 A 2 A AA 1 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
Product Identifier  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
H = 10.0-11.0 EER A/C  
SS Drain Pan  
CPC Controller, DFS, APS  
Nominal Cooling Capacity  
Johnson Controller UNT 1126 (N2 protocol), DFS, APS  
Honeywell Controller, DFS, APS  
180 = 15 Ton  
210 = 17.5 Ton  
240 = 20 Ton  
300 = 25 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Simplicity IntelliComfort Controller w/ModLinc  
York Commercial Comfort System (YCCS) Rtu Controller  
Hot Gas Bypass (Standard on VAV, Optional on CV)  
Variable Air Volume, VFD (not available with factory installed BAS options)  
Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)  
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)  
Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)  
Variable Air Volume, VFD (BAS ready)  
Heat Type and Nominal Heat Capacity  
C00 = Cooling Only. No field installed  
electric heat  
Gas Heat Options  
N24 = 240 MBH Output Aluminized Steel  
N32 = 320 MBH Output Aluminized Steel  
S24 = 240 MBH Output Stainless Steel  
S32 = 320 MBH Output Stainless Steel  
Variable Air Volume, VFD and Manual Bypass (BAS ready)  
Variable Air Volume, VFD Ready (for customer provided, field installed drive)  
Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)  
2" Pleated filters  
Electric Heat Options  
4" Pleated filters  
E18 = 18 KW  
E36 = 36 KW  
E54 = 54 KW  
E72 = 72 KW  
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)  
Double Wall Construction  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
Product Generation  
Airflow  
1 = First Generation  
2 = Second Generation  
A = Std. Motor  
B = Std. Motor/Economizer  
C = Std. Motor/Economizer/Power Exhaust  
(Downflow Only)  
Additional Options  
Hinged Filter Door & Tool Free Access Cabinet  
D = Std. Motor/Motorized Damper  
E = Std. Motor/Motorized Damper/Barometric Relief  
J = Std. Motor/Economizer/Barometric Relief  
N = Hi Static  
Standard Cabinet  
AA = None  
BA = Hinged Filter Door & Tool Free Access Panels  
BB = Phase Monitor, Hinged Filter Door & Tool Free  
Access Panels  
P = Hi Static/Economizer  
AB = Phase Monitor  
Q = Hi Static/Economizer/Power Exhaust  
(Downflow Only)  
R = Hi Static/Motorized Damper  
K = Hi Static/Motorized Damper/Barometric Relief  
S = Hi Static/Economizer/Barometric Relief  
AC = Coil Guard  
AD = Dirty Filter Switch  
BC = Coil Guard, Hinged Filter Door & Tool Free  
Access Panels  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
RC = Coil Guard & American Flag  
TA = Technicoat Condenser Coil  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator & Condenser Coils  
BD = Dirty Filter Switch, Hinged Filter Door &  
Tool Free Access Panels  
BE = Phase Monitor & Coil Guard, Hinged Filter  
Door & Tool Free Access Panels  
BF = Phase Monitor & Dirty Filter Switch, Hinged  
Filter Door & Tool Free Access Panels  
BG = Coil Guard & Dirty Filter Switch, Hinged Filter  
Door & Tool Free Access Panels  
Voltage  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,  
Hinged Filter Door & Tool Free Access Panels  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
Installation Options  
A = No Options Installed  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
B = Option 1  
C = Option 2  
D = Options 1 & 2  
E = Option 3  
F = Option 4  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
Johnson Controls Unitary Products  
3
 
262260-YTG-E-1008  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0°F outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
FEATURES  
All models are available with a wide variety of factory-  
mounted options such as stainless steel heat exchangers,  
phase monitor, dirty filter switch, and coil guard to make them  
suitable for almost every application.  
All units are self-contained and assembled on full perimeter  
base rails with holes in the four corners for overhead rigging.  
Every unit is completely piped, wired, charged and tested at  
the factory to simplify the field installation and to provide  
years of dependable operation.  
The S implicity® control board used in this product will  
effectively operate the cooling system down to 0°F  
when this product is applied in a comfort cooling  
application for people. An economizer is typically  
included in this type of application. When applying this  
product for process cooling applications (computer  
rooms, switchgear, etc.), please reference applications  
bulletin AE-011-07 or call the applications department  
for Unitary Products @ 1-877-UPG-SERV for  
All models (including those with an economizer) are suitable  
for either bottom or horizontal duct connections. Models with  
factory installed power exhaust are suitable for bottom  
duct connections only. For bottom duct, you remove the  
sheet metal panels from the supply and return air openings  
through the base of the unit. For horizontal duct, you replace  
the supply and return air panels on the rear of the unit with a  
side duct flange accessory.  
guidance. Additional accessories may be needed for  
stable operation at temperatures below 30°F.  
All models are available with these “factory mounted” outdoor  
air damper options:  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti short cycle delay can be temporarily  
overridden with the push of a button.  
Single enthalpy economizer with or without power  
exhaust  
BAS-ready economizer with or without power exhaust  
Motorized outdoor air damper  
Barometric Relief Damper  
Lead-Lag - An integrated Lead-Lag option allows  
equal run time hours on all compressors, thereby  
extending the life of all compressors. This option is  
selectable on the unit control board.  
A fixed outdoor air intake assembly will be shipped in the  
return air compartment of all units ordered without an econo-  
mizer or motorized outdoor air damper option. The assembly  
includes a rain hood with a damper that can be set for 10, 15  
or 25% outdoor air. With bottom duct connections, the intake  
damper assembly should be mounted over the opening in the  
return air panel. With horizontal ductwork, it should be  
mounted on the return air duct.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable. Furthermore, the heating and cooling  
fan delay times are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
All supply air blowers are equipped with a belt drive that can  
be adjusted to meet the exact requirements of the job. A high  
static drive option is available for applications with a higher  
CFM and/or static pressure requirement. A variable air volume  
(VAV) option using a variable frequency drive is available for  
applications requiring a constant supply duct pressure. A dif-  
ferential pressure transducer is used to monitor supply duct  
static pressure and return a speed reference signal to the VFD  
to control the output of the indoor blower motor.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
gas valve, if applicable, and the temperature limit  
switch on gas and electric heat units. The unit con-  
trol board will alarm on ignition failures, compressor  
lockouts and repeated limit switch trips.  
Nuisance Trip Protection and Strikes - To prevent  
nuisance trouble calls, the control board uses a  
“three times, you’re out” philosophy. The high and  
low-pressure switches and the freezestats must trip  
three times within two hours before the unit control  
board will lock out the associated compressor.  
All compressors include scroll compressors and internal pres-  
sure relief. Every refrigerant circuit includes an expansion  
valve, a liquid line filter-drier, a discharge line high pressure  
switch and a suction line with a freezestat and low pressure/  
loss of charge switch to protect all system components. A hot  
gas bypass option, consisting of an adjustable compressor  
discharge bypass valve, is available for low cooling load  
applications.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
®
®
S implicity Controls - S implicity control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
4
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
ELECTRIC HEATER LOCATION  
(OPTIONAL ELECTRIC/ELECTRIC UNITS)  
HIGH EFFICIENCY COMPRESSORS  
WITH CRANKCASE HEATERS  
20 GAUGE ALUMINIZED STEEL  
TUBULAR HEAT EXCHANGERS  
LONG LASTING  
POWDER PAINT FINISH  
COPPER TUBE/ALUMINUM FIN  
CONDENSER COILS  
LOW VOLTAGE RELAY BOARD  
AND TERMINAL STRIP  
ECONOMIZER HOOD  
ELECTRICAL DISCONNECT  
MOUNTING LOCATION  
(Field installed)  
KNOCKOUT FOR  
SIDE CONTROL WIRING ENTRY  
KNOCKOUT FOR  
SIDE POWER WIRING ENTRY SIDE  
2" DISPOSABLE  
FILTERS  
TERMINAL BLOCK  
(For Single Point Power Supply  
with Electric Heat)  
ELECTRIC\ELECTRIC UNITS  
OUTDOOR AIR OPENING  
FOR SLIDE-IN/PLUG-IN  
INTERNAL ECONOMIZER(OPTION)  
BOTTOM POWER & CONTROL  
WIRING ENTRY  
KNOCKOUTS FOR SIDE  
GAS SUPPLY ENTRY  
SIDE AND BOTTOM  
SUPPLY & RETURN AIR  
HOLE FOR BOTTOM  
GAS SUPPLY ENTRY  
DUCT OPENINGS(SIDE X SIDE)  
POWER VENTOR MOTOR  
1" NPTI  
CONDENSATE DRAIN  
GAS/ELECTRIC  
UNIT SHOWN  
WITH POST PURGE CYCLE  
BELT-DRIVE  
BLOWER MOTOR  
LOCATION OF VFD (Optional)  
FULL PERIMETER 14 GAUGE BASE  
RAILS WITH LIFTING HOLES  
LOCATION OF VFD BYPASS (Optional)  
FIGURE 1 - UNIT CUTAWAY  
All units have long lasting powder paint cabinets with 1000  
hour salt spray test approval under ASTM-B117 procedures.  
BAS Controls - York’s Sunline™ series units offer factory  
®
mounted BAS controls such as S implicity Intelli-  
®
Comfort, Novar , Honeywell, Johnson, York Commer-  
All models are CSA approved.  
cial Comfort System (YCCS) and CPC.  
Warranty - All models include a one-year limited parts  
warranty on the complete unit. Compressors and electric  
heater elements carry a five-year warranty. Gas heat  
exchangers carry a 10-year parts warranty.  
FACTORY-INSTALLED OPTIONS  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
Gas Heat Operation - All gas heat units are built with  
two heating sections for two equal stages of capacity  
control. Each section includes a durable heat exchanger  
with aluminized steel or optional stainless steel tubes, a  
redundant gas valve, spark ignition, power venting, an  
ignition module for 100% shut-off and all of the safety  
controls required to meet the latest ANSI standards.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit  
or through a knockout in the piping panel on the front of  
the unit.  
BAS-READY ECONOMIZER - Includes a slide-in / plug-  
in damper assembly with fully modulating spring-return  
motor actuator with zero to 95-degree rotation capable of  
introducing up to 100% outdoor air with nominal 1% leak-  
age type dampers.  
Electric Heat Operation - All electric heat models (fac-  
tory installed only) are wired for a single power source  
and include a bank of nickel chromium elements  
mounted at the discharge of the supply air blower to pro-  
vide a high velocity and uniform distribution of air across  
the heating elements. Every element is fully protected  
against excessive current and temperature by fuses and  
two thermal limit switches.  
Actuator requires 2-10 VDC input from an external  
source, such as a field-installed or factory-installed BAS  
controller. BAS-ready actuators have an adjustable auxil-  
iary end-switch for optional power exhaust control.  
For units with optional VAV or Simplicity® Intelli-Com-  
fort™ control, a factory-installed, dry bulb sensor deter-  
mines if outdoor air temperature is low enough to provide  
free-cooling operation. (Field-installed humidity sensors  
for either outdoor air or outdoor & return air streams are  
The power supply wiring can be routed into the control  
box through a threaded pipe connection in the base pan  
of the unit or through a knockout in the wiring panel on  
the front of the unit.  
Johnson Controls Unitary Products  
5
   
262260-YTG-E-1008  
available for single enthalpy and differential enthalpy  
configurations, respectively).  
Blower Motor Access compartment. The switch can be  
used to either route power to the VFD for modulating  
control of the blower motor, to bypass the drive and oper-  
ate the motor at full speed, or to power the drive (and not  
the motor) for diagnostic purposes.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
POWER EXHAUST - Our economizer options are avail-  
able with power exhaust. Whenever the outdoor air intake  
dampers are opened for free cooling, the exhaust fan will  
be energized to prevent the conditioned space from being  
over-pressurized during economizer operation. BAS-  
ready economizer actuators have an adjustable auxiliary  
end-switch to provide a range of damper positions available  
to energize power exhaust. For units with optional VAV,  
power exhaust is energized by means of a binary output  
signal from the unit's VAV control board.  
Due to space limitations, VAV is not available with any of  
the factory-installed BAS options described below, but is  
available with ‘BAS-ready’ models. Terminal blocks are  
provided in the control box for field wiring of the cus-  
tomer-installed BAS.  
A ‘VFD-ready’ option provides the provisions for a cus-  
tomer-installed drive. The unit comes with a mounting  
bracket installed in the Blower Access compartment  
which may accommodate other vendor’s drives depend-  
ing on their size. In order to utilize the unit’s mounting  
bracket, the maximum recommended drive dimensions  
are as follows:  
The exhaust fan, motor and controls are installed and  
wired at the factory. The rain hood must be assembled  
and installed in the field.  
For 5-hp motor applications ........................10” H x 6” W x 7” D  
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D  
The power exhaust option can only be used on bot-  
tom duct configurations.  
If the drive will not fit in the allotted space, then it will  
have to be mounted elsewhere; either within the building  
on a perpendicular wall which is not subjected to exces-  
sive temperature, vibration, humidity, dust, corrosive  
gas, explosive gas, etc., or within an appropriate enclo-  
sure rated for outside installation to safeguard against  
moisture, dust and excessive heat.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to a  
pre-set position whenever the supply air blower is oper-  
ating and will drive fully closed when the blower unit  
shuts down.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
A terminal block located in the control box is provided for  
field connection of the VFD controls.  
BAROMETRIC RELIEF DAMPER - This damper option  
can be used to relieve internal building air pressure on  
units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
HOT GAS BYPASS - To allow for low cooling load oper-  
ation, a direct-acting pressure-modulating bypass control  
valve installed on the system #1 discharge line is used to  
divert high temperature, high pressure refrigerant around  
the TXV in order to maintain a desired minimum evapo-  
rator pressure. HGBP is standard on all units with VAV  
and optional with CV units.  
FILTER OPTIONS - Standard units are shipped with 2”  
throw-away filters installed. 2” pleated and 4” pleated fil-  
ters are offered as a factory installed option.  
PHENOLIC COATED EVAPORATOR AND CON-  
DENSER COILS - Special coating process that utilizes  
Technicoat 10-1" processes. Coating is applied by total  
immersion of the complete coil for maximum protection.  
CONVENIENCE OUTLET - This 110 volt outlet can be  
“powered” by the unit with a stepdown transformer or  
you may order the unit with a “non-powered” conve-  
nience outlet that can be wired in the field.  
ELECTRIC HEATERS wired for single point power sup-  
ply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
DISCONNECT SWITCH - A HACR breaker sized to the  
unit max fuse size is provided. Factory installed option  
only.  
VARIABLE AIR VOLUME (VAV) - A factory-installed  
variable frequency drive (VFD), mounted in the Blower  
Access compartment, is used to control the speed of the  
indoor blower motor in order to maintain a constant static  
pressure in the supply duct. A pressure transducer and  
VAV control board are mounted inside the control box.  
The drive comes completely wired and pre-programmed  
from the factory.  
BAS - Building Automation System Controls (avail-  
able on two-system cooling product only).  
S implicity® INTELLI-Comfort™ CONTROL - The York®  
S implicity® INTELLI-Comfort™ control is factory  
installed. It includes a supply air sensor, a return air sen-  
sor, and an outside air sensor. There are provisions for a  
field installed dirty filter indicator switch, an air-proving  
An optional, factory-installed manual bypass switch  
available with factory-installed VFD can be found in the  
6
Johnson Controls Unitary Products  
262260-YTG-E-1008  
switch, an Outside Air Humidity sensor, a Return Air  
Humidity sensor, an Inside IAQ sensor, and an Outside  
Air IAQ sensor. Construction mode operation, 365-day  
real time clock with 7 day programming plus holiday  
scheduling is built-in. Two different modes of demand  
ventilation are achieved through the INTELLI-Comfort™  
YORK COMMERCIAL COMFORT SYSTEM (YCCS) -  
Provides rooftop system integration for YCCS single  
zone, change-over bypass and VAV systems.  
SMOKE DETECTORS - (supply air & return air) The  
smoke detectors stop operation of the unit by interrupting  
power to the control board if smoke is detected within the  
air compartment.  
using CO sensors. It uses an inside CO sensor to per-  
2
2
form Demand Ventilation. It can also use an Outside CO  
2
sensor to perform Differential Demand Ventilation. It  
uses a Patented Comfort Ventilation algorithm to provide  
comfortable ventilation air temperature. The patented  
economizer-loading algorithm will protect the equipment  
when harsh operating conditions exist. Humidity in the  
occupied space or return duct can be monitored and  
controlled via humidity sensors and the on-board con-  
nection for hot gas re-heat system. It uses the INTELLI-  
Start™ algorithm to maximize energy savings by recov-  
ering the building from the Unoccupied Setpoints to the  
Occupied Setpoints just in time for the Occupied Time  
Period to begin. The S implicity® INTELLI-Comfort™ bal-  
ances space temperature, ventilation air temperature,  
Factory installed smoke detectors in the return air,  
may be subjected to freezing temperatures during  
“off” times due to out side air infiltration. these smoke  
detectors have an operational limit of 32°F to 131°F.  
smoke detectors installed in areas that could be out  
side those limitations will have to be moved to prevent  
having false alarms.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
CO and humidity for ultimate comfort.  
2
S implicity® INTELLI-Comfort™ with ModLINC CON-  
TROL - The York® S implicity® INTELLI-Comfort™ with  
ModLINC control is factory installed. It includes all the  
features of the INTELLI-Comfort™ control with an addi-  
tional control to translate communications from MOD-  
BUS to the BACnet MSTP protocol.  
STAINLESS STEEL HEAT EXCHANGER - For applica-  
tions in corrosive environments, this option provides a  
full stainless steel heat exchanger assembly.  
STAINLESS STEEL DRAIN PAN- An optional rust-proof  
stainless steel drain pan is available to provide years of  
trouble-free operation in corrosive environments.  
Novar® BAS CONTROL - The Novar® building automa-  
tion system controller is factory installed. Includes supply  
air sensor, return air sensor, dirty filter indicator switch,  
and air proving switch.  
PHASE MONITORS - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of-  
phase condition.  
HIGH STATIC DRIVE - May include a belt, blower pulley,  
motor pulley or a motor change to enhance blower per-  
formance.  
JOHNSON CONTROLS BAS CONTROL - The John-  
son Control YK-UNT-1126 building automation system  
controller is factory installed. Includes supply air sen-  
sor, return air sensor, dirty filter indicator switch, and air  
proving switch.  
DIRTY FILTER SWITCH - This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
CPC BAS CONTROL - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
HINGED FILTER DOOR/”TOOL FREE” BLOWER AND  
ACCESS PANELS (not hinged) - This option allows for  
easy access and maintenance.  
HONEYWELL BAS CONTROL - The Honeywell  
W7750C building automation system controller is factory  
installed. Includes air supply sensor, return air sensor,  
dirty filter indicator switch, and air proving switch.  
NOTE: Knobs are shipped separately within the unit to pre-  
vent shipping damage. These must be field installed  
for tool free operation.  
Johnson Controls Unitary Products  
7
262260-YTG-E-1008  
HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,  
FILTER AND ELECTRIC ACCESS PANELS - This  
option allows for complete hinged and tool free access to  
the unit's blower, blower motor, filters and electrical panel  
sections.  
tudes up to 6,000 feet. This accessory supplements the  
basic propane conversion kit.  
SIDE DUCT FLANGES - One-inch flanges replace the  
supply and return air panels on the rear of the unit to  
accommodate horizontal duct connections. These  
flanges can also be used individually for bottom supply/  
horizontal return or horizontal supply/bottom return. They  
cannot be used on units with power exhaust.  
FIELD-INSTALLED ACCESSORIES  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
BAROMETRIC RELIEF DAMPER - This damper acces-  
sory can be used to relieve internal building air pressure  
on units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
HIGH STATIC DRIVE - May include a belt, blower pulley,  
motor pulley or a motor change to enhance blower per-  
formance.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to  
some pre-set position whenever the supply air blower is  
operating and will drive fully closed when the blower unit  
shuts down.  
ENTHALPY ACCESSORY CONTROL KIT - This kit  
contains the required components to convert a single  
enthalpy economizer to dual enthalpy.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
BURGLAR BARS - Mount in the supply and return  
openings to prevent entry into the duct work.  
ROOF CURBS - Fourteen-inch high roof curbs provide a  
water-tight seal between the unit and the finished roof.  
These full perimeter curbs meet the requirements of the  
National Roofing Contractors Association (NRCA) and  
are shipped knocked-down for field assembly.  
FLUE EXHAUST EXTENSION KIT - In locations with  
wind or weather conditions which may interfere with  
proper exhausting of furnace combustion products, this  
kit can be installed to prevent the flue exhaust from  
entering nearby fresh air intakes.  
They're designed to fit inside the base rails of the unit  
and include both a wood nailing strip and duct hanger  
supports.  
WOOD SKID - Allows unit to be handled with 90” forks.  
CO SENSOR - Senses CO levels and automatically  
2
2
HIGH ALTITUDE NATURAL GAS - Burner orifices and  
pilot orifices are provided for proper furnace operation at  
altitudes up to 6,000 feet.  
overrides the economizer when levels rise above the  
present limits.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
PROPANE - Burner orifices, pilot orifices and gas valve  
parts are provided to convert a natural gas furnace to  
propane.  
PHASE MONITORS - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of-  
phase condition.  
HIGH ALTITUDE PROPANE - Burner orifices and pilot  
orifices are provided for proper furnace operation at alti-  
8
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
1
TABLE 1: INDOOR SOUND POWER RATING  
-12  
SOUND POWER (db 10  
Octave Band Centerline Frequency (Hz)  
Watts)  
ESP  
IWG  
BLOWER  
UNIT  
SIZE  
dB(A)  
CFM  
SWL  
@
dB(A)  
2
RPM  
BHP  
63  
125  
250  
500  
1,000  
2,000  
4,000  
8,000  
10Ft.  
180  
210, 240  
300  
6,000  
8,000  
1.00  
1.00  
1.30  
1,080  
1,120  
1,160  
4.60  
6.65  
12.5  
99  
99  
89  
92  
98  
82  
85  
91  
84  
87  
93  
77  
80  
86  
72  
75  
81  
67  
70  
76  
89  
92  
98  
56  
102  
108  
102  
108  
59  
10,000  
65  
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA val-  
ues provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no  
way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or  
sound data in any other form than sound power level ratings.  
2. At a distance of 10 feet from the blower.  
1
1
TABLE 2: CAPACITY RATINGS - (ARI 360)  
TABLE 3: GAS HEAT RATINGS  
2
3
MODEL  
MBH  
EER  
IPLV  
MODEL  
MBH INPUT  
MBH OUTPUT  
COOLING ONLY  
300  
240  
DH180N/S24  
DH180N/S32  
DH210N/S24  
DH210N/S32  
DH240N/S24  
DH240N/S32  
DH300N/S24  
DH300N/S32  
4
DH180C00  
DH210C00  
DH240C00  
DH300C00  
10.8  
10.2  
9.7  
11.3  
10.8  
10.2  
9.6  
178  
400  
300  
400  
300  
400  
300  
400  
320  
240  
320  
240  
320  
240  
320  
205  
223  
271  
9.6  
COOLING WITH GAS HEAT  
4
DH180N/S  
DH210N/S  
DH240N/S  
DH300N/S  
10.8  
10.2  
9.7  
11.3  
10.8  
10.2  
9.6  
178  
205  
223  
271  
9.6  
COOLING WITH ELECTRIC HEAT  
4
DH180E18  
10.8  
11.3  
11.3  
11.0  
178  
178  
176  
176  
1. All units are two-stage heating. First stage is 50% of total.  
4
4
4
DH180E36  
DH180E54  
10.8  
10.5  
SSE = Steady State Efficiency (80%) - Output divided by Input  
DH180E72  
DH210E18  
DH210E36  
DH210E54  
DH210E72  
DH240E18  
DH240E36  
DH240E54  
DH240E72  
DH300E18  
DH300E36  
DH300E54  
DH300E72  
10.5  
10.2  
10.2  
10.0  
10.0  
9.6  
11.0  
10.8  
10.8  
10.6  
10.6  
10.1  
10.1  
9.7  
205  
205  
203  
203  
223  
223  
221  
219  
271  
271  
269  
269  
For units with VFD and electric or gas heat, the  
speed of the indoor blower motor continues to be  
controlled by duct static pressure via the VAV con-  
trol board.  
9.6  
9.5  
9.5  
9.6  
9.6  
9.7  
9.6  
9.6  
If there are VAV boxes present in the duct system,  
the boxes must be driven to the full-open position  
using a customer-supplied power source to assure  
adequate airflow across electric heating elements or  
gas heat exchanger tubes.  
9.5  
9.5  
9.4  
9.4  
1. 80/67°F Indoor and 95°F outdoor.  
2. EER = Energy Efficiency Ratio at full load - the cooling  
capacity in Btu’s per hour (Btuh) divided by the power  
input in watts, expressed in Btuh per watt (Btuh/watt).  
3. IPLV = Integrated part load value.  
4. Deduct 2 MBH @ 208V.  
Johnson Controls Unitary Products  
9
     
262260-YTG-E-1008  
TABLE 4: DH 180 COOLING CAPACITIES (15 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
75°F  
85°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
223.0  
211.0  
199.0  
181.3  
178.5  
231.5  
219.0  
206.5  
188.1  
185.3  
240.0  
227.0  
214.0  
195.0  
192.0  
226.4  
213.5  
194.5  
191.5  
225.8  
213.0  
194.0  
191.0  
11.3  
11.2  
11.1  
10.8  
10.5  
11.3  
11.2  
11.2  
10.9  
10.6  
11.4  
11.3  
11.2  
10.9  
10.6  
11.2  
11.2  
10.8  
10.5  
11.2  
11.1  
10.8  
10.5  
100.4 79.0  
57.7  
-
-
-
-
-
-
218.1  
203.0  
188.0  
173.0  
170.1  
225.0  
209.5  
194.0  
178.5  
175.6  
232.0  
216.0  
200.0  
184.0  
181.0  
217.6  
201.5  
185.4  
182.4  
219.2  
203.0  
186.8  
183.7  
12.9  
12.6  
12.3  
12.1  
12.1  
12.9  
12.6  
12.4  
12.2  
12.2  
13.0  
12.7  
12.4  
12.2  
12.2  
12.8  
12.5  
12.2  
12.2  
12.8  
12.5  
12.3  
12.3  
99.3 77.9  
56.5  
-
-
-
-
-
-
133.1 111.7 90.3  
68.9  
130.5 109.2 87.8 66.4  
161.8 140.4 119.0 97.6  
4500  
5250  
6000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
165.8 144.4 123.0 101.6 80.2  
76.2  
181.3 178.6 157.3 135.9 114.5 93.1  
178.5 179.1 162.3 140.9 119.6 98.2  
173.0 169.9 148.5 127.2 105.8 84.4  
170.1 170.1 151.1 129.7 108.3 86.9  
107.2 87.6  
62.3  
-
-
-
-
-
-
112.3 87.0  
61.8  
-
-
-
-
-
-
148.2 122.9 97.7  
72.4  
146.4 121.2 95.9 70.6  
189.2 158.3 133.0 107.7 82.5  
180.5 155.3 130.0 104.7 79.5  
188.1 186.8 170.1 144.9 119.6 94.3  
185.3 185.5 175.7 150.4 125.1 99.8  
178.5 177.0 162.3 137.0 111.7 86.5  
175.6 175.6 165.0 139.8 114.5 89.2  
114.0 96.2  
67.0  
-
-
-
-
-
-
125.3 96.2  
67.0  
-
-
-
-
-
-
163.3 134.2 105.0 75.8  
162.3 133.2 104.0 74.8  
212.6 172.2 143.0 113.8 84.7  
199.3 170.2 141.0 111.8 82.7  
195.0 195.0 183.0 153.8 124.7 95.5  
192.0 192.0 189.0 159.8 130.7 101.5  
184.0 184.0 176.0 146.8 117.7 88.5  
181.0 181.0 179.0 149.8 120.7 91.5  
178.0 144.8 111.6 78.4  
-
-
-
176.0 142.7 109.5 76.3  
-
-
-
212.8 185.2 152.0 118.8 85.6  
201.2 181.7 148.5 115.3 82.1  
6750  
7500  
194.5 194.5 188.5 155.3 122.1 88.9  
191.5 191.5 190.0 156.8 123.6 90.4  
185.4 185.4 181.4 148.2 115.0 81.8  
182.4 182.4 181.4 148.1 114.9 81.7  
192.8 155.5 118.2 81.0  
-
-
-
189.6 152.3 115.1 77.8  
-
-
-
213.0 198.3 161.0 123.7 86.5  
203.0 193.3 156.0 118.7 81.5  
194.0 194.0 194.0 156.7 119.5 82.2  
191.0 191.0 191.0 153.8 116.5 79.3  
186.8 186.8 186.8 149.5 112.2 75.0  
183.7 183.7 183.7 146.5 109.2 71.9  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
95°F  
105°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
213.2  
195.1  
177.0  
164.6  
161.8  
218.6  
200.0  
181.5  
168.8  
165.9  
224.0  
205.0  
186.0  
173.0  
170.0  
208.9  
189.5  
176.3  
173.2  
212.7  
193.0  
179.5  
176.4  
14.5  
14.0  
13.5  
13.4  
13.7  
14.5  
14.0  
13.6  
13.5  
13.7  
14.6  
14.1  
13.6  
13.5  
13.8  
14.3  
13.8  
13.6  
14.0  
14.4  
13.9  
13.8  
14.1  
98.2 76.8  
55.4  
-
-
-
-
198.8  
182.7  
166.5  
155.6  
152.2  
203.9  
187.3  
170.8  
159.5  
156.1  
209.0  
192.0  
175.0  
163.5  
160.0  
195.8  
178.5  
166.8  
163.2  
199.7  
182.0  
170.0  
166.4  
16.1  
15.4  
14.8  
14.7  
15.0  
16.2  
15.5  
14.8  
14.8  
15.1  
16.3  
15.6  
14.9  
14.9  
15.2  
15.7  
15.0  
15.0  
15.3  
15.9  
15.2  
15.1  
15.5  
97.0 75.6  
54.2  
-
-
-
-
128.0 106.6 85.2  
63.8  
-
125.1 103.7 82.4 61.0  
153.3 131.9 110.5 89.1  
-
4500  
5250  
6000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
157.8 136.4 115.0 93.6  
72.2  
-
67.7  
-
164.6 161.2 139.8 118.4 97.1  
161.8 161.2 139.8 118.4 97.1  
75.7  
155.6 153.8 135.7 114.3 93.0  
152.2 151.9 134.0 112.6 91.3  
71.6  
75.7  
69.9  
117.4 86.5  
61.2  
-
-
-
-
-
-
117.3 84.6  
59.4  
-
-
-
-
144.7 119.4 94.1  
68.8  
140.7 115.5 90.2 64.9  
164.1 146.3 121.0 95.7  
-
171.9 152.3 127.0 101.7 76.5  
70.5  
-
168.8 167.1 154.4 129.1 103.9 78.6  
165.9 165.6 154.4 129.1 103.9 78.6  
159.5 158.7 148.6 123.3 98.1  
156.1 156.0 146.8 121.5 96.2  
72.8  
70.9  
136.6 96.2  
67.0  
-
-
-
-
-
-
137.6 93.7  
64.5  
-
-
-
-
-
-
161.3 132.2 103.0 73.8  
156.3 127.2 98.0 68.8  
186.0 168.2 139.0 109.8 80.7  
175.0 160.7 131.5 102.3 73.2  
173.0 173.0 169.0 139.8 110.7 81.5  
170.0 170.0 169.0 139.8 110.7 81.5  
163.5 163.5 161.5 132.3 103.2 74.0  
160.0 160.0 159.5 130.3 101.2 72.0  
173.9 140.7 107.4 74.2  
-
-
-
170.2 137.0 103.8 70.6  
-
-
-
189.5 178.2 145.0 111.8 78.6  
178.5 170.1 139.3 106.0 72.8  
166.8 166.8 165.8 132.6 99.4  
163.2 163.2 163.0 129.7 96.5  
6750  
7500  
176.3 176.3 174.3 141.0 107.8 74.6  
173.2 173.2 172.7 139.5 106.3 73.1  
66.1  
63.3  
-
186.4 149.2 111.9 74.6  
-
-
-
184.1 146.8 109.6 72.3  
-
193.0 188.3 151.0 113.7 76.5  
182.0 179.6 147.0 109.7 72.5  
170.0 170.0 170.0 132.8 95.5  
166.4 166.4 166.4 129.1 91.9  
-
179.5 179.5 179.5 142.3 105.0 67.7  
176.4 176.4 176.4 139.1 101.9 64.6  
58.3  
54.6  
10  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 4: DH 180 COOLING CAPACITIES (15 TON) (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
115°F  
SENSIBLE CAPACITY, MBH  
COIL  
TOTAL POWER  
ENTERING DRY BULB, °F  
1
2
CAP.  
INPUT  
KW  
WB  
°F  
MBH  
CFM  
90  
85  
80  
75  
70  
65  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
184.5  
170.3  
156.0  
146.5  
142.7  
189.3  
174.6  
160.0  
150.2  
146.3  
194.0  
179.0  
164.0  
154.0  
150.0  
182.8  
167.5  
157.3  
153.2  
186.6  
171.0  
160.6  
156.4  
17.8  
16.9  
16.0  
16.1  
16.4  
17.9  
17.0  
16.1  
16.2  
16.5  
18.0  
17.1  
16.2  
16.3  
16.6  
17.2  
16.3  
16.4  
16.7  
17.3  
16.4  
16.5  
16.8  
95.8 74.4  
53.0  
-
-
-
-
122.3 100.9 79.5 58.1  
148.8 127.4 106.0 84.6  
-
4500  
63.2  
-
146.5 146.5 131.6 110.3 88.9  
142.7 142.7 128.2 106.8 85.5  
67.5  
64.1  
117.2 82.8  
57.5  
-
-
-
-
136.8 111.5 86.3 61.0  
156.4 140.3 115.0 89.7  
-
5250  
6000  
64.5  
-
150.2 150.2 142.8 117.6 92.3  
146.3 146.3 139.1 113.8 88.6  
67.0  
63.3  
138.6 91.2  
62.0  
-
-
-
-
151.3 122.2 93.0 63.8  
164.0 153.2 124.0 94.8  
-
-
65.7  
154.0 154.0 154.0 124.8 95.7  
150.0 150.0 150.0 120.8 91.7  
66.5  
62.5  
-
166.5 133.3 100.1 66.9  
-
167.5 162.1 133.5 100.3 67.1  
157.3 157.3 157.3 124.1 90.9  
153.2 153.2 153.2 120.0 86.8  
-
6750  
7500  
57.7  
53.6  
-
181.8 144.5 107.3 70.0  
-
171.0 171.0 143.0 105.7 68.5  
160.6 160.6 160.6 123.3 86.1  
156.4 156.4 156.4 119.1 81.9  
-
48.8  
44.6  
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-  
mance Table for the KW of the supply air blower motor.  
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.  
Nominal Rating  
Johnson Controls Unitary Products  
11  
262260-YTG-E-1008  
TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
75°F  
85°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
241.5  
232.2  
223.0  
204.4  
200.4  
250.1  
240.5  
231.0  
211.7  
207.6  
258.7  
248.8  
238.9  
219.0  
214.7  
253.0  
243.0  
222.7  
218.3  
257.2  
247.0  
226.4  
222.0  
13.9  
13.2  
12.6  
12.4  
12.6  
14.5  
13.8  
13.1  
12.9  
13.1  
15.1  
14.4  
13.7  
13.5  
13.7  
14.5  
13.8  
13.6  
13.8  
14.6  
13.9  
13.7  
13.9  
119.5 94.6  
69.6  
-
-
-
-
-
-
240.2  
226.1  
212.0  
193.5  
191.2  
248.8  
234.2  
219.6  
200.5  
198.0  
257.4  
242.3  
227.2  
207.4  
204.9  
246.9  
231.6  
211.4  
208.8  
251.6  
235.9  
215.3  
212.7  
15.6  
15.1  
14.5  
14.3  
14.3  
16.0  
15.4  
14.9  
14.7  
14.7  
16.4  
15.8  
15.2  
15.0  
15.0  
15.9  
15.3  
15.1  
15.1  
16.0  
15.4  
15.2  
15.2  
119.7 94.8  
69.9  
-
-
-
-
-
-
159.7 134.8 109.8 84.9  
156.3 131.4 106.4 81.5  
5250  
6125  
7000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
199.9 174.9 150.0 125.1 100.1  
192.9 167.9 143.0 118.1 93.1  
204.4 204.4 182.1 157.1 132.2 107.2  
200.4 200.4 183.1 158.2 133.2 108.3  
193.5 193.5 170.5 145.5 120.6 95.6  
191.2 191.2 171.8 146.9 121.9 97.0  
136.3 104.8 75.3  
-
-
-
-
-
-
140.3 105.8 76.3  
-
-
-
-
-
-
177.8 148.3 118.9 89.4  
175.2 145.7 116.2 86.7  
219.4 191.9 162.4 132.9 103.4  
210.0 185.6 156.2 126.7 97.2  
211.7 211.7 197.2 167.7 138.2 108.7  
207.6 207.6 198.3 168.8 139.3 109.9  
200.5 200.5 186.1 156.6 127.2 97.7  
198.0 198.0 187.6 158.1 128.6 99.1  
153.0 115.0 81.0  
-
-
-
-
-
-
160.9 116.7 82.7  
-
-
-
-
-
-
195.9 161.9 127.9 93.9  
194.0 160.0 126.0 92.0  
238.9 208.8 174.8 140.8 106.8  
227.2 203.3 169.3 135.3 101.3  
219.0 219.0 212.3 178.3 144.3 110.2  
214.7 214.7 213.5 179.5 145.5 111.4  
207.4 207.4 201.8 167.8 133.8 99.7  
204.9 204.9 203.4 169.4 135.4 101.3  
214.9 176.1 137.4 98.6  
-
-
-
212.6 173.9 135.2 96.4  
-
-
-
243.0 227.9 187.8 149.0 110.3  
231.6 219.6 181.6 142.9 104.1  
7875  
8750  
222.7 222.7 219.4 180.6 141.9 103.1  
218.3 218.3 217.7 179.0 140.2 101.5  
211.4 211.4 208.6 169.8 131.1 92.3  
208.8 208.8 208.1 169.3 130.6 91.8  
233.8 190.3 146.9 103.4  
-
-
-
231.2 187.8 144.3 100.8  
-
-
-
247.0 247.0 200.7 157.2 113.8  
235.9 235.9 193.9 150.4 107.0  
226.4 226.4 226.4 183.0 139.5 96.0  
222.0 222.0 222.0 178.5 135.0 91.6  
215.3 215.3 215.3 171.9 128.4 84.9  
212.7 212.7 212.7 169.3 125.8 82.3  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
95°F  
105°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
238.9  
219.9  
201.0  
182.6  
182.0  
247.5  
235.0  
215.5  
195.8  
195.1  
256.1  
235.8  
215.5  
195.8  
195.1  
240.9  
220.2  
200.0  
199.3  
246.0  
224.8  
204.2  
203.5  
17.4  
16.9  
16.5  
16.3  
16.1  
17.6  
17.2  
16.7  
16.5  
16.3  
17.7  
17.2  
16.7  
16.5  
16.3  
17.3  
16.8  
16.6  
16.4  
17.4  
16.9  
16.7  
16.5  
120.0 95.0  
70.1  
-
-
-
-
-
-
228.3  
209.9  
191.5  
176.2  
176.4  
235.7  
223.4  
203.8  
187.4  
187.8  
243.0  
223.4  
203.8  
187.5  
187.8  
228.3  
208.3  
191.6  
191.9  
233.2  
212.8  
195.7  
196.0  
15.0  
14.6  
14.2  
14.0  
13.9  
17.2  
19.0  
18.5  
18.2  
18.1  
19.5  
19.0  
18.5  
18.2  
18.1  
19.1  
18.6  
18.3  
18.2  
19.2  
18.7  
18.4  
18.3  
116.1 91.2  
66.2  
-
-
-
-
-
-
152.9 128.0 103.0 78.1  
148.0 123.0 98.1 73.1  
5250  
6125  
7000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
185.9 160.9 136.0 111.1 86.1  
179.8 154.8 129.9 105.0 80.0  
182.6 182.6 158.8 133.9 108.9 84.0  
182.0 182.0 160.5 135.5 110.6 85.6  
176.2 176.2 152.7 127.8 102.9 77.9  
176.4 176.4 153.3 128.3 103.4 78.4  
144.4 106.7 77.2  
-
-
-
-
-
-
143.3 102.8 73.3  
-
-
-
-
-
-
172.5 143.1 124.0 84.1  
167.5 138.0 108.6 79.1  
200.7 179.4 163.8 120.4 90.9  
191.8 173.3 143.8 114.3 84.8  
189.2 189.2 191.3 145.6 116.1 86.6  
188.5 188.5 193.3 147.4 117.9 88.4  
181.8 181.8 169.1 139.6 110.1 80.6  
182.1 182.1 169.7 140.2 110.7 81.2  
168.8 118.4 84.4  
-
-
-
-
-
-
170.4 114.4 80.4  
-
-
-
-
-
-
192.1 158.1 124.1 90.1  
187.1 153.1 119.1 85.0  
215.5 197.8 163.8 129.8 95.8  
203.8 191.7 157.7 123.7 89.7  
195.8 195.8 191.3 157.3 123.3 89.2  
195.1 195.1 193.3 159.3 125.3 91.2  
187.5 187.5 185.5 151.4 117.4 83.4  
187.8 187.8 186.1 152.0 118.0 84.0  
210.4 171.7 132.9 94.2  
-
-
-
205.3 166.5 127.8 89.0  
-
-
-
220.2 211.3 175.5 136.7 98.0  
208.3 202.2 169.3 130.5 91.8  
7875  
8750  
200.0 200.0 197.8 159.0 120.3 81.5  
199.3 199.3 198.4 159.7 120.9 82.2  
191.6 191.6 190.6 151.8 113.1 74.3  
191.9 191.9 191.0 152.3 113.5 74.8  
228.7 185.2 141.8 98.3  
-
-
-
223.5 180.0 136.5 93.1  
-
-
-
224.8 224.8 187.1 143.6 100.2  
212.8 212.8 180.9 137.4 93.9  
204.2 204.2 204.2 160.8 117.3 73.8  
203.5 203.5 203.5 160.0 116.6 73.1  
195.7 195.7 195.7 152.2 108.7 65.3  
196.0 196.0 196.0 152.5 109.1 65.6  
12  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
115°F  
125°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
KW  
WB  
MBH  
MBH  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
217.8  
199.9  
182.0  
169.7  
170.9  
223.9  
205.5  
187.1  
174.4  
175.7  
229.9  
211.0  
192.1  
179.1  
180.4  
215.7  
196.4  
183.1  
184.4  
220.4  
200.7  
187.1  
188.5  
12.5  
12.2  
12.0  
11.8  
11.8  
16.9  
16.5  
16.1  
15.8  
15.8  
21.2  
20.7  
20.2  
19.9  
19.9  
20.8  
20.3  
20.0  
20.0  
20.9  
20.4  
20.1  
20.1  
112.3 87.3  
62.4  
-
-
-
-
207.3  
189.9  
172.5  
163.2  
165.4  
212.0  
194.2  
176.5  
167.0  
169.2  
216.8  
198.6  
180.4  
170.8  
173.1  
203.1  
184.5  
174.7  
177.0  
207.7  
188.7  
178.6  
181.0  
10.1  
9.9  
108.4 83.5  
58.5  
-
-
-
-
143.0 118.0 93.1  
68.1  
-
138.0 113.1 88.1  
63.2  
-
5250  
6125  
7000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
173.7 148.7 123.8 98.9  
73.9  
-
9.7  
167.6 142.6 117.7 92.8  
67.8  
-
169.7 169.7 146.7 121.7 96.8  
170.9 170.9 146.0 121.1 96.1  
71.8  
9.5  
163.2 163.2 140.6 115.6 90.7  
165.4 165.4 138.8 113.8 88.9  
65.7  
71.2  
9.6  
63.9  
142.1 98.9  
69.4  
-
-
-
-
-
-
16.5  
16.2  
15.8  
15.6  
15.7  
23.0  
22.5  
22.0  
21.6  
21.7  
22.6  
22.1  
21.7  
21.8  
22.7  
22.2  
21.8  
21.9  
141.0 95.0  
65.5  
-
-
-
-
162.5 133.0 103.5 74.1  
157.5 128.0 98.5  
69.1  
-
182.9 167.2 137.7 108.2 78.7  
174.0 161.1 131.6 102.1 72.6  
167.0 167.0 157.2 127.7 98.2  
169.2 169.2 155.2 125.7 96.2  
-
174.4 174.4 163.1 133.6 104.2 74.7  
175.7 175.7 162.4 132.9 103.4 74.0  
68.7  
66.7  
172.0 110.4 76.4  
-
-
-
-
173.6 106.4 72.4  
-
-
-
-
-
-
182.0 148.0 114.0 80.0  
-
177.0 143.0 109.0 74.9  
192.1 185.6 151.6 117.6 83.6  
179.1 179.1 179.6 145.6 111.6  
180.4 180.4 178.8 144.8 110.8  
-
77.5  
76.7  
-
180.4 179.5 145.5 111.5 77.5  
170.8 170.8 170.8 139.7 105.7 71.7  
173.1 173.1 171.6 137.5 103.5 69.5  
200.1 161.4 122.6 83.9  
-
195.0 156.3 117.5 78.8  
-
-
-
196.4 193.2 163.1 124.4 85.6  
-
184.5 184.1 156.9 118.2 79.4  
174.7 174.7 174.7 137.4 98.7  
177.0 177.0 176.3 137.5 98.8  
7875  
8750  
183.1 183.1 183.4 144.6 105.9 67.1  
184.4 184.4 183.6 144.9 106.1 67.4  
59.9  
60.0  
-
218.2 174.8 131.3 87.8  
-
-
-
207.7 169.5 126.1 82.6  
-
200.7 200.7 174.6 131.1 87.7  
188.7 188.7 168.4 124.9 81.4  
178.6 178.6 178.6 135.1 91.6  
181.0 181.0 181.0 137.5 94.0  
-
187.1 187.1 187.1 143.6 100.2 56.7  
188.5 188.5 188.5 145.0 101.5 58.1  
48.1  
50.5  
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance  
Table for the KW of the supply air blower motor.  
2. These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.  
Nominal Rating  
Johnson Controls Unitary Products  
13  
262260-YTG-E-1008  
TABLE 6: DH 240 COOLING CAPACITIES (20 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
75°F  
85°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
277.0  
263.0  
249.0  
240.6  
237.8  
287.0  
272.5  
258.0  
249.3  
246.4  
297.0  
282.0  
267.0  
258.0  
255.0  
295.2  
279.5  
270.1  
266.9  
308.4  
292.0  
282.2  
278.9  
19.1  
18.6  
18.0  
17.9  
17.7  
17.9  
17.4  
16.9  
16.7  
16.5  
16.7  
16.2  
15.7  
15.6  
15.4  
13.7  
13.3  
13.2  
13.0  
11.2  
10.8  
10.7  
10.6  
159.2 130.7 102.2  
-
-
-
-
-
-
262.0  
249.0  
236.0  
228.6  
226.7  
272.0  
258.5  
245.0  
237.3  
235.4  
282.0  
268.0  
254.0  
246.0  
244.0  
280.7  
266.0  
257.6  
255.5  
293.3  
278.0  
269.2  
267.1  
20.5  
20.1  
19.6  
19.4  
19.1  
19.4  
18.9  
18.5  
18.3  
18.1  
18.2  
17.8  
17.4  
17.2  
17.0  
15.3  
15.0  
14.8  
14.6  
12.8  
12.5  
12.4  
12.2  
153.7 125.2 96.7  
-
-
-
-
-
-
196.1 167.6 139.1 110.6  
190.4 161.8 133.3 104.8  
6000  
7000  
8000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
233.0 204.5 176.0 147.5 119.0  
227.0 198.5 170.0 141.5 113.0  
240.6 240.6 215.3 186.8 158.3 129.8  
237.8 237.8 213.7 185.2 156.7 128.1  
228.6 228.6 204.2 175.7 147.1 118.6  
226.7 226.7 203.3 174.8 146.3 117.8  
189.9 145.8 112.1  
-
-
-
-
-
-
187.6 140.0 106.3  
-
-
-
-
-
-
219.9 186.3 152.6 118.9  
214.1 180.4 146.7 113.0  
250.0 226.7 193.0 159.3 125.6  
240.5 220.7 187.0 153.3 119.6  
249.3 249.3 236.2 202.5 168.8 135.1  
246.4 246.4 234.3 200.6 166.9 133.3  
237.3 237.3 224.6 190.9 157.2 123.5  
235.4 235.4 223.7 190.0 156.3 122.6  
220.5 160.9 122.0  
-
-
-
-
-
-
221.5 154.9 116.0  
-
-
-
-
-
-
243.8 204.9 166.0 127.1  
237.8 198.9 160.0 121.1  
267.0 248.9 210.0 171.1 132.2  
254.0 242.9 204.0 165.1 126.2  
258.0 258.0 257.0 218.1 179.2 140.4  
255.0 255.0 255.0 216.1 177.2 138.4  
246.0 246.0 245.0 206.1 167.2 128.4  
244.0 244.0 244.0 205.1 166.2 127.4  
275.1 228.1 183.8 139.5  
-
-
-
265.0 220.8 176.5 132.2  
-
-
-
279.5 270.4 232.5 188.2 143.9  
266.0 260.4 225.0 180.7 136.4  
9000  
270.1 270.1 269.6 225.3 181.0 136.7  
266.9 266.9 266.9 222.7 178.4 134.1  
257.6 257.6 257.1 212.8 168.6 124.3  
255.5 255.5 255.5 211.2 167.0 122.7  
306.4 251.2 201.5 151.9  
-
-
-
292.3 242.6 192.9 143.3  
-
-
-
292.0 292.0 255.0 205.3 155.6  
278.0 278.0 246.0 196.3 146.6  
10000  
282.2 282.2 282.2 232.5 182.8 133.1  
278.9 278.9 278.9 229.2 179.5 129.8  
269.2 269.2 269.2 219.6 169.9 120.2  
267.1 267.1 267.1 217.4 167.7 118.0  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
95°F  
105°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
247.1  
235.0  
223.0  
216.5  
215.6  
257.0  
244.5  
236.0  
225.3  
224.3  
267.0  
254.0  
241.0  
234.0  
233.0  
266.1  
252.5  
245.2  
244.1  
278.2  
264.0  
256.3  
255.2  
21.9  
21.5  
21.2  
20.9  
20.6  
20.8  
20.5  
20.1  
19.8  
19.6  
19.7  
19.4  
19.1  
18.8  
18.6  
16.9  
16.7  
16.4  
16.2  
14.4  
14.2  
14.0  
13.8  
148.1 119.6 91.1  
-
-
-
-
-
-
232.2  
221.1  
210.0  
205.4  
204.0  
241.6  
230.1  
218.5  
213.7  
212.2  
251.0  
239.0  
227.0  
222.0  
220.5  
251.1  
238.5  
233.3  
231.7  
263.2  
250.0  
244.5  
242.8  
23.3  
22.9  
22.6  
22.2  
21.9  
22.3  
21.9  
21.6  
21.2  
21.0  
21.3  
20.9  
20.6  
20.2  
20.0  
18.4  
18.1  
17.8  
17.6  
16.0  
15.7  
15.4  
15.3  
144.0 115.5 87.0  
-
-
-
-
-
-
184.6 156.1 127.6 99.0  
180.0 151.5 123.0 94.5  
6000  
7000  
8000  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
221.0 192.5 164.0 135.5 107.0  
209.0 187.5 159.0 130.5 102.0  
216.5 216.5 193.0 164.5 136.0 107.5  
215.6 215.6 193.0 164.5 136.0 107.5  
205.4 205.4 183.0 154.5 126.0 97.5  
204.0 204.0 182.6 154.1 125.6 97.1  
185.3 134.3 100.6  
-
-
-
-
-
-
184.7 132.6 96.0  
-
-
-
-
-
-
208.2 174.5 140.8 107.1  
203.1 169.4 135.7 102.0  
231.0 214.7 182.0 147.3 113.6  
218.0 206.2 175.5 141.8 108.1  
225.3 225.3 213.0 179.3 145.6 111.9  
224.3 224.3 213.0 179.3 145.6 111.9  
213.7 213.7 202.0 168.3 134.6 100.9  
212.2 212.2 201.6 167.9 134.2 100.5  
222.5 148.9 110.0  
-
-
-
-
-
-
225.5 149.8 105.0  
-
-
-
-
-
-
231.8 192.9 154.0 115.1  
226.3 187.4 148.5 109.6  
241.0 236.9 198.0 159.1 120.2  
227.0 224.9 192.0 153.1 114.2  
234.0 234.0 233.0 194.1 155.2 116.4  
233.0 233.0 233.0 194.1 155.2 116.4  
222.0 222.0 221.0 182.1 143.2 104.4  
220.5 220.5 220.5 181.6 142.7 103.9  
255.0 213.4 169.2 124.9  
-
-
-
244.7 208.0 163.7 119.4  
-
-
-
252.5 250.4 217.5 173.2 128.9  
238.5 237.5 211.6 167.3 123.1  
9000  
245.2 245.2 244.7 200.4 156.1 111.8  
244.1 244.1 244.1 199.8 155.6 111.3  
233.3 233.3 232.8 188.5 144.2 99.9  
231.7 231.7 231.7 187.4 143.1 98.8  
278.2 234.0 184.3 134.7  
-
-
-
263.2 228.5 178.9 129.2  
-
-
-
264.0 264.0 237.0 187.3 137.6  
250.0 250.0 231.3 181.6 131.9  
10000  
256.3 256.3 256.3 206.7 157.0 107.3  
255.2 255.2 255.2 205.6 155.9 106.2  
244.5 244.5 244.5 194.8 145.1 95.5  
242.8 242.8 242.8 193.2 143.5 93.8  
14  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 6: DH 240 COOLING CAPACITIES (20 TON) (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
115°F  
SENSIBLE CAPACITY, MBH  
COIL  
TOTAL POWER  
ENTERING DRY BULB, °F  
1
2
CAP.  
INPUT  
KW  
WB  
°F  
MBH  
CFM  
90  
85  
80  
75  
70  
65  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
217.3  
207.2  
197.0  
194.2  
192.4  
226.2  
215.6  
205.0  
202.1  
200.2  
235.0  
224.0  
213.0  
210.0  
208.0  
236.1  
224.5  
221.3  
219.2  
248.2  
236.0  
232.7  
230.5  
24.8  
24.3  
23.9  
23.5  
23.2  
23.8  
23.4  
23.0  
22.5  
22.3  
22.8  
22.4  
22.0  
21.6  
21.4  
20.0  
19.6  
19.2  
19.1  
17.5  
17.2  
16.9  
16.7  
139.8 111.3 82.8  
-
-
-
-
-
-
175.4 146.9 118.4 89.9  
6000  
197.0 182.5 154.0 125.5 97.0  
194.2 194.2 173.0 144.5 116.0 87.5  
192.4 192.4 172.2 143.7 115.2 86.7  
184.2 131.0 91.4  
-
-
-
-
-
-
198.1 164.4 130.7 97.0  
7000  
8000  
205.0 197.8 170.0 136.3 102.6  
202.1 202.1 191.0 157.3 123.6 89.9  
200.2 200.2 190.1 156.4 122.7 89.0  
228.5 150.8 100.0  
-
-
-
-
-
-
220.8 181.9 143.0 104.1  
213.0 213.0 186.0 147.1 108.2  
210.0 210.0 209.0 170.1 131.2 92.4  
208.0 208.0 208.0 169.1 130.2 91.4  
234.5 202.5 158.2 113.9  
-
-
-
224.5 224.5 205.8 161.5 117.2  
9000  
221.3 221.3 220.8 176.6 132.3 88.0  
219.2 219.2 219.2 175.0 130.7 86.4  
248.2 223.0 173.4 123.7  
-
-
-
236.0 236.0 225.5 175.8 126.1  
10000  
232.7 232.7 232.7 183.0 133.3 83.6  
230.5 230.5 230.5 180.8 131.1 81.4  
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-  
mance Table for the KW of the supply air blower motor.  
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.  
Nominal Rating  
Johnson Controls Unitary Products  
15  
262260-YTG-E-1008  
TABLE 7: DH 300 COOLING CAPACITIES (25 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
75°F  
85°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
371.3  
334.4  
297.6  
290.9  
281.0  
373.9  
336.8  
299.7  
293.0  
282.9  
376.6  
339.1  
301.7  
295.0  
284.9  
341.5  
303.7  
297.0  
286.8  
343.8  
305.7  
299.1  
288.7  
19.7  
19.3  
18.8  
18.3  
18.2  
19.7  
19.3  
18.9  
18.3  
18.2  
19.8  
19.3  
18.9  
18.4  
18.3  
20.3  
19.8  
19.3  
19.2  
21.3  
20.8  
20.2  
20.1  
191.8 156.2 120.6  
-
-
-
-
-
-
348.9  
318.7  
288.4  
277.6  
272.4  
353.3  
322.7  
292.0  
281.1  
275.8  
357.7  
326.7  
295.7  
284.6  
279.3  
330.7  
299.3  
288.1  
282.7  
334.8  
303.0  
291.6  
286.1  
21.5  
21.1  
20.8  
20.1  
20.1  
21.6  
21.3  
21.0  
20.3  
20.3  
21.8  
21.5  
21.1  
20.5  
20.4  
22.2  
21.8  
21.2  
21.1  
22.9  
22.6  
21.8  
21.8  
185.5 149.8 114.2  
-
-
-
-
-
-
233.0 197.4 161.8 126.1  
226.6 190.9 155.3 119.7  
7500  
8750  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
274.2 238.6 203.0 167.3 131.7  
267.7 232.0 196.4 160.8 125.1  
290.9 284.9 246.4 210.8 175.1 139.5  
281.0 281.0 261.8 226.1 190.5 154.9  
277.6 274.6 238.9 203.3 167.7 132.0  
272.4 272.4 249.6 214.0 178.3 142.7  
219.7 168.5 126.4  
-
-
-
-
-
-
214.0 162.4 120.3  
-
-
-
-
-
-
253.8 211.7 169.6 127.5  
247.8 205.7 163.6 121.5  
288.0 254.9 212.8 170.7 128.5  
281.7 249.0 206.9 164.7 122.6  
293.0 290.0 258.3 216.2 174.1 132.0  
282.9 282.9 274.5 232.4 190.3 148.1  
281.1 279.6 251.7 209.5 167.4 125.3  
275.8 275.8 262.9 220.8 178.7 136.5  
247.6 180.9 132.3  
-
-
-
-
-
-
242.4 175.0 126.4  
-
-
-
-
-
-
274.6 226.0 177.4 128.8  
269.0 220.4 171.8 123.2  
10000  
301.7 271.2 222.6 174.0 125.4  
295.7 265.9 217.3 168.7 120.1  
295.0 295.0 270.2 221.6 173.0 124.4  
284.9 284.9 287.2 238.6 190.0 141.4  
284.6 284.6 264.4 215.8 167.2 118.6  
279.3 279.3 276.2 227.6 179.0 130.4  
290.9 235.5 180.2 124.8  
-
-
-
288.3 232.9 177.6 122.2  
-
-
-
303.7 281.3 226.0 170.6 115.3  
299.3 279.9 224.5 169.2 113.8  
11250  
12500  
297.0 297.0 275.0 219.7 164.3 109.0  
286.8 286.8 287.9 232.6 177.2 121.9  
288.1 288.1 273.2 217.8 162.5 107.1  
282.7 282.7 281.2 225.8 170.5 115.1  
307.1 245.0 182.9 120.8  
-
-
-
307.5 245.4 183.3 121.2  
-
-
-
305.7 291.5 229.4 167.3 105.2  
303.0 293.9 231.8 169.7 107.6  
299.1 299.1 279.8 217.7 155.6 93.5  
288.7 288.7 288.7 226.6 164.5 102.4  
291.6 291.6 282.0 219.9 157.8 95.7  
286.1 286.1 286.1 224.0 161.9 99.8  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
95°F  
105°F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
SENSIBLE CAPACITY, MBH  
ENTERING DRY BULB, °F  
TOTAL POWER  
TOTAL  
POWER  
1
2
1
2
CAP.  
INPUT  
KW  
CAP.  
INPUT  
WB  
MBH  
MBH  
KW  
CFM  
°F  
90  
85  
80  
75  
70  
65  
90  
85  
80  
75  
70  
65  
77  
72  
326.6  
302.9  
279.2  
264.2  
263.7  
332.8  
308.6  
284.4  
269.2  
268.7  
338.9  
314.3  
289.7  
274.2  
273.7  
320.0  
294.9  
279.2  
278.6  
325.7  
300.2  
284.1  
283.6  
23.2  
23.0  
22.8  
22.0  
22.0  
23.5  
23.3  
23.1  
22.3  
22.3  
23.8  
23.6  
23.4  
22.6  
22.6  
24.1  
23.9  
23.0  
23.0  
24.6  
24.3  
23.5  
23.5  
179.1 143.5 107.9  
-
-
-
-
-
-
314.3  
288.7  
263.1  
253.6  
251.0  
319.5  
293.5  
267.5  
257.8  
255.2  
324.6  
298.2  
271.8  
261.9  
259.3  
303.0  
276.2  
266.1  
263.4  
307.8  
280.5  
270.3  
267.6  
26.2  
25.8  
25.3  
24.5  
24.6  
26.4  
25.9  
25.4  
24.7  
24.8  
26.6  
26.1  
25.6  
24.9  
24.9  
26.5  
26.0  
25.2  
25.3  
26.8  
26.3  
25.6  
25.6  
163.3 127.7 92.0  
-
-
-
-
-
-
220.1 184.5 148.8 113.2  
209.2 173.5 137.9 102.2  
7500  
8750  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
261.1 225.5 189.8 154.2 118.5  
254.1 219.4 183.7 148.1 112.5  
264.2 264.2 231.5 195.8 160.2 124.6  
263.7 263.7 237.4 201.8 166.1 130.5  
253.6 253.6 225.7 190.1 154.5 118.8  
251.0 251.0 222.7 187.1 151.4 115.8  
208.2 156.3 114.2  
-
-
-
-
-
-
197.7 139.8 97.6  
-
-
-
-
-
-
241.8 199.7 157.5 115.4  
230.6 188.5 146.3 104.2  
275.4 243.0 200.9 158.8 116.7  
263.0 237.2 195.0 152.9 110.8  
269.2 269.2 245.0 202.9 160.8 118.7  
268.7 268.7 251.3 209.2 167.1 124.9  
257.8 257.8 239.6 197.5 155.4 113.3  
255.2 255.2 236.4 194.2 152.1 110.0  
237.3 169.1 120.5  
-
-
-
-
-
-
232.2 151.9 103.3  
-
-
-
-
-
-
263.5 214.9 166.3 117.7  
252.0 203.4 154.8 106.2  
10000  
289.7 260.6 212.0 163.4 114.8  
271.8 254.9 206.3 157.7 109.1  
274.2 274.2 258.6 210.0 161.4 112.8  
273.7 273.7 265.2 216.6 168.0 119.4  
261.9 261.9 253.5 204.9 156.3 107.7  
259.3 259.3 250.0 201.4 152.8 104.2  
285.6 230.3 174.9 119.6  
-
-
-
271.3 215.9 160.6 105.2  
-
-
-
294.9 278.4 223.1 167.7 112.4  
276.2 266.7 213.9 158.5 103.2  
11250  
12500  
279.2 279.2 271.4 216.0 160.7 105.3  
278.6 278.6 274.4 219.0 163.7 108.3  
266.1 266.1 261.9 206.5 151.2 95.8  
263.4 263.4 257.0 201.6 146.3 90.9  
307.8 245.7 183.6 121.5  
-
-
-
290.5 228.4 166.3 104.2  
-
-
-
300.2 296.2 234.1 172.0 109.9  
280.5 278.5 221.4 159.3 97.2  
284.1 284.1 284.1 222.0 159.9 97.8  
283.6 283.6 283.6 221.5 159.4 97.3  
270.3 270.3 270.3 208.2 146.1 84.0  
267.6 267.6 263.9 201.8 139.7 77.6  
16  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 7: DH 300 COOLING CAPACITIES (25 TON) (CONTINUED)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
115°F  
SENSIBLE CAPACITY, MBH  
COIL  
TOTAL POWER  
ENTERING DRY BULB, °F  
1
2
CAP.  
INPUT  
KW  
WB  
°F  
MBH  
CFM  
90  
85  
80  
75  
70  
65  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
77  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
302.0  
274.5  
247.1  
242.9  
238.3  
306.2  
278.4  
250.5  
246.3  
241.6  
310.4  
282.2  
254.0  
249.7  
244.9  
286.0  
257.4  
253.1  
248.2  
289.8  
260.9  
256.4  
251.5  
29.3  
28.5  
27.7  
27.1  
27.2  
29.3  
28.5  
27.8  
27.1  
27.3  
29.4  
28.6  
27.8  
27.2  
27.3  
28.9  
28.1  
27.4  
27.6  
29.1  
28.3  
27.7  
27.8  
147.5 111.8 76.2  
-
-
-
-
-
-
198.2 162.6 126.9 91.3  
7500  
247.1 213.3 177.7 142.0 106.4  
242.9 242.9 220.0 184.3 148.7 113.1  
238.3 238.3 208.0 172.3 136.7 101.1  
187.3 123.2 81.1  
-
-
-
-
-
-
219.4 177.3 135.1 93.0  
8750  
250.5 231.3 189.2 147.0 104.9  
246.3 246.3 234.2 192.1 150.0 107.8  
241.6 241.6 221.4 179.3 137.2 95.1  
227.1 134.6 86.0  
-
-
-
-
-
-
240.5 191.9 143.3 94.7  
10000  
254.0 249.2 200.6 152.0 103.4  
249.7 249.7 248.4 199.8 151.2 102.6  
244.9 244.9 234.9 186.3 137.7 89.1  
256.9 201.6 146.2 90.9  
-
-
-
257.4 255.1 204.7 149.3 94.0  
11250  
12500  
253.1 253.1 252.4 197.1 141.7 86.4  
248.2 248.2 239.6 184.2 128.9 73.5  
273.3 211.2 149.1 87.0  
-
-
-
260.9 260.9 208.7 146.6 84.5  
256.4 256.4 256.4 194.3 132.2 70.1  
251.5 251.5 244.3 182.2 120.1 58.0  
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-  
mance Table for the KW of the supply air blower motor.  
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.  
Nominal Rating  
Johnson Controls Unitary Products  
17  
262260-YTG-E-1008  
order to use the indoor blower tables for high altitude applica-  
tions, certain corrections are necessary.  
CFM, STATIC PRESSURE, AND POWER - ALTI-  
TUDE AND TEMPERATURE CORRECTIONS  
A centrifugal fan is a "constant volume" device. This means  
that, if the rpm remains constant, the CFM delivered is the  
same regardless of the density of the air. However, since the  
air at high altitude is less dense, less static pressure will be  
generated and less power will be required than a similar  
application at sea level. Air density correction factors are  
shown in Table 8 and Figure 2.  
The information below should be used to assist in application  
of product when being applied at altitudes at or exceeding  
1000 feet above sea level.  
The air flow rates listed in the standard blower performance  
tables are based on standard air at sea level. As the altitude  
or temperature increases, the density of air decreases. In  
TABLE 8: ALTITUDE CORRECTION FACTORS  
ALTITUDE (FEET)  
AIR TEMP  
0
1000  
1.022  
1.002  
0.982  
0.964  
0.947  
0.929  
0.912  
2000  
0.986  
0.966  
0.948  
0.930  
0.913  
0.897  
0.880  
3000  
0.950  
0.931  
0.913  
0.896  
0.880  
0.864  
0.848  
4000  
0.916  
0.898  
0.880  
0.864  
0.848  
0.833  
0.817  
5000  
0.882  
0.864  
0.848  
0.832  
0.817  
0.802  
0.787  
6000  
0.849  
0.832  
0.816  
0.801  
0.787  
0.772  
0.758  
7000  
0.818  
0.802  
0.787  
0.772  
0.758  
0.744  
0.730  
8000  
0.788  
0.772  
0.757  
0.743  
0.730  
0.716  
0.703  
9000  
0.758  
0.743  
0.729  
0.715  
0.702  
0.689  
0.676  
10000  
0.729  
0.715  
0.701  
0.688  
0.676  
0.663  
0.651  
40  
50  
1.060  
1.039  
1.019  
1.000  
0.982  
0.964  
0.946  
60  
70  
80  
90  
100  
The examples below will assist in determining the airflow per-  
formance of the product at altitude.  
blower tables to select the blower speed and the BHP  
requirement.  
Example 1: What are the corrected CFM, static pressure,  
and BHP at an elevation of 5,000 ft. if the blower performance  
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?  
Solution: As in the example above, no temperature informa-  
tion is given so 70°F is assumed.  
The 1.5" static pressure given is at an elevation of 5,000 ft.  
The first step is to convert this static pressure to equivalent  
sea level conditions.  
Solution: At an elevation of 5,000 ft the indoor blower will still  
deliver 6,000 CFM if the rpm is unchanged. However, Table  
8 must be used to determine the static pressure and BHP.  
Since no temperature data is given, we will assume an air  
temperature of 70°F. Table 8 shows the correction factor to be  
0.832.  
Sea level static pressure = 1.5 / .832 = 1.80"  
Enter the blower table at 6000 sCFM and static pressure of  
1.8". The rpm listed will be the same rpm needed at 5,000 ft.  
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC  
Corrected BHP = 4.0 x 0.832 = 3.328  
Suppose that the corresponding BHP listed in the table is 3.2.  
This value must be corrected for elevation.  
Example 2: A system, located at 5,000 feet of elevation, is to  
BHP at 5,000 ft = 3.2 x .832 = 2.66  
deliver 6,000 CFM at a static pressure of 1.5". Use the unit  
18  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR  
Johnson Controls Unitary Products  
19  
 
262260-YTG-E-1008  
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY  
180 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
6000  
BHP  
BLOWER  
SPEED,  
(RPM)  
4500  
BHP  
5250  
BHP  
6750  
BHP  
7200  
BHP  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
208 VOLT AND STANDARD DRIVE  
850  
870  
6.0**  
5.5  
4.5  
3.5  
3.0  
2.0  
1.0  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
2.4  
2.5  
2.6  
2.9  
3.0  
3.1  
3.2  
2.2  
2.3  
2.4  
2.6  
2.7  
2.8  
2.9  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.3  
3.0  
3.1  
3.4  
3.6  
3.7  
3.8  
3.9  
2.7  
2.8  
3.0  
3.2  
3.3  
3.4  
3.5  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
3.2  
3.5  
3.7  
4.0  
4.1  
4.2  
4.5  
2.9  
3.1  
3.3  
3.6  
3.7  
3.8  
4.0  
-
-
-
-
-
-
0.2  
0.3  
0.5  
0.6  
0.7  
0.9  
4.1  
4.4  
4.7  
4.8.  
5.0  
5.2  
3.7  
3.9  
4.2  
4.3  
4.5  
4.7  
-
-
-
915  
0.2  
0.4  
0.5  
0.6  
0.7  
4.5  
4.9  
5.1  
5.4  
5.7  
4.0  
4.4  
4.6  
4.8  
5.1  
965  
980  
1010  
1040  
208 VOLT AND HIGH STATIC DRIVE  
965  
980  
6.0  
5.5  
4.5  
3.5  
3.0  
2.0  
1.0  
1.2  
1.3  
1.5  
1.6  
1.7  
1.9  
2.1  
2.9  
3.0  
3.2  
3.4  
3.5  
3.7  
3.9  
2.6  
2.7  
2.9  
3.0  
3.1  
3.3  
3.5  
1.0  
1.1  
1.3  
1.4  
1.5  
1.7  
2.0  
3.6  
3.7  
3.9  
4.0  
4.2  
4.5  
4.7  
3.2  
3.3  
3.5  
3.6  
3.8  
4.0  
4.2  
0.8  
0.9  
1.1  
1.2  
1.3  
1.5  
1.8  
4.0  
4.1  
4.5  
4.7  
4.9  
5.1  
5.5  
3.6  
3.7  
4.0  
4.2  
4.4  
4.6  
4.9  
0.5  
0.6  
0.8  
1.0  
1.2  
-
4.7  
4.8  
5.1  
5.5  
5.7  
-
4.2  
4.3  
4.6  
4.9  
5.1  
-
0.4  
5.0  
4.4  
0.5  
5.1  
4.6  
1025  
1065  
1095  
1130  
1170  
0.7  
5.6  
5.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE  
870  
915  
6.0**  
5.0  
4.0  
3.5  
2.0  
1.0  
1.0  
1.1  
1.2  
1.3  
1.5  
1.6  
2.4  
2.6  
2.9  
3.0  
3.2  
3.3  
2.2  
2.4  
2.6  
2.7  
2.9  
3.0  
0.8  
0.9  
1.0  
1.1  
1.3  
1.4  
3.1  
3.3  
3.6  
3.7  
3.9  
4.0  
2.8  
3.0  
3.2  
3.3  
3.5  
3.6  
0.6  
0.7  
0.8  
0.9  
1.1  
1.2  
3.5  
3.7  
4.0  
4.1  
4.5  
4.7  
3.1  
3.3  
3.6  
3.7  
4.0  
4.2  
0.2  
0.3  
0.5  
0.6  
0.9  
1.0  
4.1  
4.4  
4.7  
4.8  
5.3  
5.5  
3.7  
3.9  
4.2  
4.3  
4.7  
4.9  
-
-
-
0.2  
0.4  
0.5  
0.7  
-
4.5  
5.0  
5.1  
5.7  
-
4.0  
4.4  
4.6  
5.1  
-
965  
980  
1040  
1065  
230/460/575 VOLT AND HIGH STATIC DRIVE  
980  
6.0  
4.5  
4.0  
3.5  
2.5  
1.5  
1.0  
1.3  
1.5  
1.6  
1.7  
1.9  
2.1  
2.2  
2.9  
3.2  
3.4  
3.5  
3.7  
3.9  
4.0  
2.6  
2.9  
3.0  
3.1  
3.3  
3.5  
3.6  
1.1  
1.3  
1.4  
1.5  
1.7  
2.0  
2.1  
3.7  
3.9  
4.0  
4.2  
4.5  
4.7  
4.8  
3.3  
3.5  
3.6  
3.8  
4.0  
4.2  
4.3  
0.9  
1.1  
1.2  
1.3  
1.5  
1.8  
2.0  
4.1  
4.5  
4.7  
4.9  
5.1  
5.5  
5.7  
3.7  
4.0  
4.2  
4.4  
4.6  
4.9  
5.1  
0.6  
0.9  
1.0  
1.2  
-
4.8  
5.3  
5.5  
5.7  
-
4.3  
4.7  
4.9  
5.1  
-
0.5  
5.1  
4.6  
1040  
1065  
1095  
1130  
1170  
1190  
0.7  
5.7  
5.1  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.  
2. Refer to Table 11 for additional static resistances.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
20  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY  
210 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
BLOWER  
SPEED,  
(RPM)  
6000  
BHP  
7000  
BHP  
8000  
BHP  
9000  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
BHP  
KW  
208 VOLT AND STANDARD DRIVE  
870  
900  
930  
950  
980  
1015  
6.0**  
5.0  
4.0  
3.0  
2.0  
1.0  
0.4  
0.8  
1.1  
1.3  
1.6  
1.9  
2.1  
3.2  
4.1  
4.6  
5.3  
5.9  
1.8  
2.7  
3.4  
3.9  
4.5  
5.0  
0.1  
0.5  
0.9  
1.1  
1.4  
1.7  
2.3  
3.5  
4.5  
5.1  
5.8  
6.5  
2.0  
2.9  
3.8  
4.3  
4.9  
5.5  
-
-
-
-
-
-
0.2  
0.6  
0.8  
1.2  
1.5  
3.8  
4.9  
5.5  
6.3  
7.0  
3.2  
4.1  
4.6  
5.3  
5.9  
-
-
-
0.1  
0.4  
0.7  
1.0  
5.1  
5.9  
6.9  
7.7  
4.3  
5.0  
5.8  
6.5  
208 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.0  
3.5  
3.0  
2.5  
2.0  
1.0  
1.3  
1.6  
1.8  
1.9  
2.0  
2.1  
2.3  
2.4  
4.6  
5.3  
5.8  
6.1  
6.2  
6.4  
6.6  
6.7  
3.9  
4.5  
4.9  
5.1  
5.2  
5.4  
5.5  
5.6  
1.1  
1.4  
1.7  
1.8  
1.9  
2.0  
2.1  
2.2  
5.1  
5.8  
6.3  
6.5  
6.8  
7.0  
7.2  
7.3  
4.3  
4.9  
5.3  
5.5  
5.7  
5.9  
6.0  
6.1  
0.8  
1.2  
1.5  
1.6  
1.7  
1.8  
1.9  
2.1  
5.5  
6.3  
6.9  
7.1  
7.4  
7.6  
7.8  
7.9  
4.6  
5.3  
5.8  
6.0  
6.2  
6.4  
6.6  
6.7  
0.4  
0.7  
1.0  
1.1  
1.2  
1.3  
1.5  
-
5.9  
6.9  
7.5  
7.8  
8.1  
8.3  
8.6  
-
5.0  
5.8  
6.3  
6.6  
6.8  
7.0  
7.2  
-
1010  
1020  
1035  
1050  
1075  
1100  
230/460/575 VOLT AND STANDARD DRIVE  
870  
900  
6.0**  
5.0  
4.0  
3.5  
2.5  
1.5  
1.0  
0.4  
0.8  
1.1  
1.3  
1.6  
1.9  
2.0  
2.1  
3.2  
4.1  
4.6  
5.3  
5.9  
6.1  
1.8  
2.7  
3.4  
3.9  
4.5  
5.0  
5.1  
0.1  
0.5  
0.9  
1.1  
1.4  
1.7  
1.8  
2.3  
3.5  
4.5  
5.1  
5.8  
6.5  
6.6  
2.0  
2.9  
3.8  
4.3  
4.9  
5.5  
5.6  
-
-
-
-
-
-
0.2  
0.6  
0.8  
1.2  
1.5  
1.6  
3.8  
4.9  
5.5  
6.3  
7.0  
7.3  
3.2  
4.1  
4.6  
5.3  
5.9  
6.1  
-
-
-
930  
0.1  
0.4  
0.7  
1.0  
1.1  
5.1  
5.9  
6.9  
7.7  
7.9  
4.3  
5.0  
5.8  
6.5  
6.7  
950  
980  
1015  
1025  
230/460/575 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.0  
3.5  
3.0  
2.0  
1.5  
1.0  
1.3  
1.6  
1.9  
2.0  
2.1  
2.3  
2.4  
2.5  
4.6  
5.3  
5.9  
6.2  
6.4  
6.6  
6.7  
6.8  
3.9  
4.5  
5.0  
5.2  
5.4  
5.5  
5.6  
5.7  
1.1  
1.4  
1.7  
1.9  
2.0  
2.1  
2.2  
2.3  
5.1  
5.8  
6.5  
6.8  
7.0  
7.2  
7.3  
7.4  
4.3  
4.9  
5.5  
5.7  
5.9  
6.0  
6.1  
6.2  
0.8  
1.2  
1.5  
1.7  
1.8  
1.9  
2.1  
2.2  
5.5  
6.3  
7.0  
7.4  
7.6  
7.8  
7.9  
8.1  
4.6  
5.3  
5.9  
6.2  
6.4  
6.6  
6.7  
6.8  
0.4  
0.7  
1.0  
1.2  
1.3  
1.5  
-
5.9  
6.9  
7.7  
8.1  
8.3  
8.6  
-
5.0  
5.8  
6.5  
6.8  
7.0  
7.2  
-
1015  
1035  
1050  
1080  
1100  
1120  
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.  
2.Refer to Table 13 for additional static resistances.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total  
static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
Johnson Controls Unitary Products  
21  
 
262260-YTG-E-1008  
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY  
240 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
8000  
BHP  
BLOWER  
SPEED,  
(RPM)  
6000  
BHP  
7000  
BHP  
9000  
BHP  
9400  
BHP  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
208 VOLT AND STANDARD DRIVE  
870  
900  
930  
950  
980  
1015  
6.0**  
5.0  
4.0  
3.0  
2.0  
1.0  
0.4  
0.8  
1.1  
1.3  
1.6  
1.9  
2.1  
3.2  
4.1  
4.6  
5.3  
5.9  
1.8  
2.7  
3.4  
3.9  
4.5  
5.0  
0.1  
0.5  
0.9  
1.1  
1.4  
1.7  
2.3  
3.5  
4.5  
5.1  
5.8  
6.5  
2.0  
2.9  
3.8  
4.3  
4.9  
5.5  
-
-
-
-
-
-
-
-
-
-
-
-
0.2  
0.6  
0.8  
1.2  
1.5  
3.8  
4.9  
5.5  
6.3  
7.0  
3.2  
4.1  
4.6  
5.3  
5.9  
-
-
-
0.1  
0.4  
0.7  
1.0  
5.1  
5.9  
6.9  
7.7  
4.3  
5.0  
5.8  
6.5  
-
-
-
-
-
-
0.2  
0.6  
7.3  
8.2  
6.1  
6.9  
208 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.0  
3.5  
3.0  
2.5  
2.0  
1.0  
1.3  
1.6  
1.8  
1.9  
2.0  
2.1  
2.3  
2.4  
4.6  
5.3  
5.8  
6.1  
6.2  
6.4  
6.6  
6.7  
3.9  
4.5  
4.9  
5.1  
5.2  
5.4  
5.5  
5.6  
1.1  
1.4  
1.7  
1.8  
1.9  
2.0  
2.1  
2.2  
5.1  
5.8  
6.3  
6.5  
6.8  
7.0  
7.2  
7.3  
4.3  
4.9  
5.3  
5.5  
5.7  
5.9  
6.0  
6.1  
0.8  
1.2  
1.5  
1.6  
1.7  
1.8  
1.9  
2.1  
5.5  
6.3  
6.9  
7.1  
7.4  
7.6  
7.8  
7.9  
4.6  
5.3  
5.8  
6.0  
6.2  
6.4  
6.6  
6.7  
0.4  
0.7  
1.0  
1.1  
1.2  
1.3  
1.5  
-
5.9  
6.9  
7.5  
7.8  
8.1  
8.3  
8.6  
-
5.0  
5.8  
6.3  
6.6  
6.8  
7.0  
7.2  
-
-
0.2  
0.5  
0.6  
0.7  
-
-
7.3  
7.9  
8.3  
8.6  
-
-
6.1  
6.7  
7.0  
7.3  
-
1010  
1020  
1035  
1050  
1075  
1100  
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE  
870  
900  
6.0**  
5.0  
4.0  
3.5  
2.5  
1.5  
1.0  
0.4  
0.8  
1.1  
1.3  
1.6  
1.9  
2.0  
2.1  
3.2  
4.1  
4.6  
5.3  
5.9  
6.1  
1.8  
2.7  
3.4  
3.9  
4.5  
5.0  
5.1  
0.1  
0.5  
0.9  
1.1  
1.4  
1.7  
1.8  
2.3  
3.5  
4.5  
5.1  
5.8  
6.5  
6.6  
2.0  
2.9  
3.8  
4.3  
4.9  
5.5  
5.6  
-
-
-
-
-
-
-
-
-
-
-
-
0.2  
0.6  
0.8  
1.2  
1.5  
1.6  
3.8  
4.9  
5.5  
6.3  
7.0  
7.3  
3.2  
4.1  
4.6  
5.3  
5.9  
6.1  
-
-
-
930  
0.1  
0.4  
0.7  
1.0  
1.1  
5.1  
5.9  
6.9  
7.7  
7.9  
4.3  
5.0  
5.8  
6.5  
6.7  
-
-
-
950  
-
-
-
980  
0.2  
0.6  
0.7  
7.3  
8.2  
8.6  
6.1  
6.9  
7.3  
1015  
1025  
230/460/575 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.0  
3.5  
3.0  
2.0  
1.5  
1.0  
1.3  
1.6  
1.9  
2.0  
2.1  
2.3  
2.4  
2.5  
4.6  
5.3  
5.9  
6.2  
6.4  
6.6  
6.7  
6.8  
3.9  
4.5  
5.0  
5.2  
5.4  
5.5  
5.6  
5.7  
1.1  
1.4  
1.7  
1.9  
2.0  
2.1  
2.2  
2.3  
5.1  
5.8  
6.5  
6.8  
7.0  
7.2  
7.3  
7.4  
4.3  
4.9  
5.5  
5.7  
5.9  
6.0  
6.1  
6.2  
0.8  
1.2  
1.5  
1.7  
1.8  
1.9  
2.1  
2.2  
5.5  
6.3  
7.0  
7.4  
7.6  
7.8  
7.9  
8.1  
4.6  
5.3  
5.9  
6.2  
6.4  
6.6  
6.7  
6.8  
0.4  
0.7  
1.0  
1.2  
1.3  
1.5  
-
5.9  
6.9  
7.7  
8.1  
8.3  
8.6  
-
5.0  
5.8  
6.5  
6.8  
7.0  
7.2  
-
-
0.2  
0.6  
0.7  
-
-
7.3  
8.2  
8.6  
-
-
6.1  
6.9  
7.3  
-
1015  
1035  
1050  
1080  
1100  
1120  
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.  
2. Refer to Table 11 for additional static resistances.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
22  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT  
180 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
6000  
BHP  
BLOWER  
SPEED,  
(RPM)  
4500  
BHP  
5250  
BHP  
6750  
BHP  
7200  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
BHP  
KW  
208 VOLT AND STANDARD DRIVE  
850  
870  
6.0**  
5.5  
4.5  
3.5  
3.0  
2.0  
1.0  
0.9  
1.0  
1.1  
1.2  
1.3  
1.4  
1.6  
2.4  
2.5  
2.6  
2.7  
2.9  
3.0  
3.2  
2.1  
2.2  
2.4  
2.5  
2.6  
2.7  
2.9  
0.6  
0.7  
0.8  
0.9  
1.0  
1.1  
1.3  
2.9  
3.0  
3.1  
3.2  
3.4  
3.6  
3.8  
2.6  
2.7  
2.8  
2.9  
3.0  
3.2  
3.4  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1.0  
3.4  
3.5  
3.6  
3.7  
3.8  
4.0  
4.4  
3.0  
3.1  
3.2  
3.3  
3.4  
3.6  
3.9  
-
-
-
-
-
-
-
-
-
-
-
-
915  
0.2  
0.4  
0.5  
0.6  
0.8  
4.1  
4.4  
4.5  
4.7  
5.0  
3.7  
3.0  
4.0  
4.2  
4.5  
-
-
-
965  
0.2  
0.3  
0.4  
0.6  
5.0  
5.1  
5.4  
5.6  
4.5  
4.6  
4.8  
5.0  
980  
1010  
1040  
208 VOLT AND HIGH STATIC DRIVE  
965  
980  
6.0  
5.5  
4.5  
3.5  
2.0  
1.0  
1.2  
1.3  
1.4  
1.6  
1.9  
2.1  
2.7  
2.9  
3.1  
3.4  
3.6  
3.9  
2.5  
2.6  
2.8  
3.0  
3.2  
3.5  
0.9  
1.0  
1.2  
1.4  
1.7  
1.9  
3.2  
3.4  
3.6  
3.9  
4.4  
4.7  
2.9  
3.0  
3.2  
3.5  
3.9  
4.2  
0.6  
0.7  
0.9  
1.1  
1.4  
1.6  
3.7  
3.8  
4.1  
4.5  
5.0  
5.5  
3.3  
3.4  
3.7  
4.0  
4.5  
4.9  
0.4  
0.5  
0.7  
0.9  
1.2  
-
4.4  
4.5  
4.8  
5.1  
5.8  
-
3.9  
4.0  
4.3  
4.6  
5.2  
-
0.2  
0.3  
0.4  
-
5.0  
5.1  
5.5  
-
4.5  
4.6  
4.9  
-
1025  
1065  
1125  
1170  
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE  
870  
915  
6.0**  
5.0  
4.0  
3.5  
2.5  
1.5  
1.0  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
1.6  
2.5  
2.6  
2.7  
2.9  
3.0  
3.1  
3.4  
2.2  
2.4  
2.5  
2.6  
2.7  
2.8  
3.0  
0.7  
0.8  
0.9  
1.0  
1.1  
1.2  
1.4  
3.0  
3.1  
3.2  
3.4  
3.6  
3.7  
3.9  
2.7  
2.8  
2.9  
3.0  
3.2  
3.3  
3.5  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.1  
3.5  
3.6  
3.7  
3.8  
4.0  
4.2  
4.5  
3.1  
3.2  
3.3  
3.4  
3.6  
3.8  
4.0  
-
-
-
-
-
-
0.2  
0.4  
0.5  
0.6  
0.7  
0.9  
4.1  
4.4  
4.5  
4.7  
4.9  
5.1  
3.7  
3.9  
4.0  
4.2  
4.4  
4.6  
-
-
-
965  
0.2  
0.3  
0.4  
0.5  
-
5.0  
5.1  
5.4  
5.7  
-
4.5  
4.6  
4.8  
5.1  
-
980  
1015  
1050  
1065  
230/460/575 VOLT AND HIGH STATIC DRIVE  
980  
6.0  
4.5  
4.0  
2.5  
1.5  
1.0  
1.3  
1.6  
1.7  
1.9  
2.1  
2.2  
2.9  
3.2  
3.4  
3.6  
3.9  
4.0  
2.6  
2.9  
3.0  
3.2  
3.5  
3.6  
1.0  
1.3  
1.4  
1.7  
1.8  
1.9  
3.4  
3.8  
3.9  
4.4  
4.7  
4.8  
3.0  
3.4  
3.5  
3.9  
4.2  
4.3  
0.7  
1.0  
1.1  
1.4  
1.6  
1.7  
3.8  
4.4  
4.5  
5.0  
5.5  
5.6  
3.4  
3.9  
4.0  
4.5  
4.9  
5.0  
0.5  
0.8  
0.9  
1.2  
-
4.5  
5.0  
5.1  
5.8  
-
4.0  
4.5  
4.6  
5.2  
-
0.3  
5.1  
4.6  
1045  
1065  
1125  
1170  
1190  
0.6  
5.6  
5.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.  
2. Refer to the additional Static Resistances table.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
Johnson Controls Unitary Products  
23  
 
262260-YTG-E-1008  
TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT  
210 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
BLOWER  
SPEED,  
(RPM)  
6000  
BHP  
7000  
BHP  
8000  
BHP  
9000  
BHP  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
208 VOLT AND STANDARD DRIVE  
870  
900  
930  
950  
980  
995  
1015  
6.0**  
5.0  
4.0  
3.0  
2.0  
1.5  
1.0  
1.3  
1.4  
1.6  
1.7  
1.9  
2.1  
2.2  
3.6  
3.8  
4.1  
4.2  
4.5  
4.6  
4.8  
3.0  
3.2  
3.4  
3.6  
3.8  
3.9  
4.0  
0.7  
0.9  
1.1  
1.3  
1.5  
1.6  
1.7  
4.3  
4.7  
5.0  
5.1  
5.4  
5.5  
4.7  
3.7  
4.0  
4.2  
4.3  
4.5  
4.7  
4.8  
0.2  
0.4  
0.6  
0.8  
1.0  
1.1  
1.2  
5.1  
5.6  
5.9  
6.0  
6.3  
6.4  
6.6  
4.3  
4.7  
5.0  
5.1  
5.3  
5.4  
5.6  
-
-
-
-
-
-
0.1  
0.2  
0.4  
0.5  
0.7  
6.7  
6.9  
7.2  
7.5  
7.8  
5.7  
5.8  
6.1  
6.3  
6.6  
208 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.5  
3.5  
2.5  
2.0  
1.0  
1.7  
1.9  
2.1  
2.3  
2.5  
2.6  
2.9  
4.2  
4.5  
4.5  
4.9  
5.1  
5.3  
5.6  
3.6  
3.8  
3.9  
4.1  
4.3  
4.4  
4.7  
1.3  
1.5  
1.6  
1.8  
2.0  
2.1  
2.3  
5.1  
5.4  
5.5  
5.8  
6.1  
6.3  
6.8  
4.3  
4.5  
4.7  
4.9  
5.1  
5.3  
5.7  
0.8  
1.0  
1.1  
1.3  
1.4  
1.5  
1.8  
6.0  
6.3  
6.4  
6.7  
7.1  
7.3  
7.9  
5.1  
5.3  
5.4  
5.7  
6.0  
6.2  
6.6  
0.2  
0.4  
0.5  
0.7  
0.9  
1.0  
-
6.9  
7.2  
7.5  
8.0  
8.4  
8.6  
-
5.8  
6.1  
6.3  
6.7  
7.0  
7.2  
-
995  
1025  
1050  
1065  
1100  
230/460/575 VOLT AND STANDARD DRIVE  
870  
900  
6.0**  
5.0  
4.0  
3.5  
2.5  
2.0  
1.5  
1.0  
1.3  
1.4  
1.6  
1.7  
1.9  
2.1  
2.2  
2.3  
3.6  
3.8  
4.1  
4.2  
4.5  
4.6  
4.8  
4.9  
3.0  
3.2  
3.4  
3.6  
3.8  
3.9  
4.0  
4.1  
0.7  
0.9  
1.1  
1.3  
1.5  
1.6  
1.7  
1.8  
4.3  
4.7  
5.0  
5.1  
5.4  
5.5  
5.7  
5.8  
3.7  
4.0  
4.2  
4.3  
4.5  
4.7  
4.8  
4.9  
0.2  
0.4  
0.6  
0.8  
1.0  
1.1  
1.2  
1.3  
5.1  
5.6  
5.9  
6.0  
6.3  
6.4  
6.6  
6.7  
4.3  
4.7  
5.0  
5.1  
5.3  
5.4  
5.6  
5.7  
-
-
-
-
-
-
930  
0.1  
0.2  
0.4  
0.5  
0.6  
0.7  
6.7  
6.9  
7.2  
7.5  
7.8  
8.0  
5.7  
5.8  
6.1  
6.3  
6.6  
6.7  
950  
965  
995  
1015  
1025  
230/460/575 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
1.5  
1.0  
1.7  
1.9  
2.1  
2.2  
2.3  
2.5  
2.6  
2.9  
3.1  
4.2  
4.5  
4.6  
4.8  
4.9  
5.1  
5.3  
5.6  
5.8  
3.6  
3.8  
3.9  
4.0  
4.1  
4.3  
4.4  
4.7  
4.9  
1.3  
1.5  
1.6  
1.7  
1.8  
2.0  
2.1  
2.3  
2.5  
5.1  
5.4  
5.5  
5.7  
5.8  
6.1  
6.3  
6.8  
7.0  
4.3  
4.5  
4.7  
4.8  
4.9  
5.1  
5.3  
4.7  
5.9  
0.8  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
1.8  
1.9  
6.0  
6.3  
6.4  
6.6  
6.7  
7.1  
7.3  
7.9  
8.3  
5.1  
5.3  
5.4  
5.6  
5.7  
6.0  
6.2  
6.6  
6.9  
0.2  
0.4  
0.5  
0.6  
0.7  
0.9  
1.0  
-
6.9  
7.2  
7.5  
7.8  
8.0  
8.4  
8.6  
-
5.8  
6.1  
6.3  
6.6  
6.7  
7.0  
7.2  
-
995  
1015  
1025  
1050  
1065  
1100  
1120  
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.  
2. Refer to the additional Static Resistances table.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
24  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT  
240 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
8000  
BHP  
BLOWER  
SPEED,  
(RPM)  
6000  
BHP  
7000  
BHP  
9000  
BHP  
9400  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
BHP  
KW  
208 VOLT AND STANDARD DRIVE  
870  
900  
930  
950  
980  
995  
1015  
6.0**  
5.0  
4.0  
3.0  
2.0  
1.5  
1.0  
1.3  
1.4  
1.6  
1.7  
1.9  
2.1  
2.2  
3.6  
3.8  
4.1  
4.2  
4.5  
4.6  
4.8  
3.0  
3.2  
3.4  
3.6  
3.8  
3.9  
4.0  
0.7  
0.9  
1.1  
1.3  
1.5  
1.6  
1.7  
4.3  
4.7  
5.0  
5.1  
5.4  
5.5  
4.7  
3.7  
4.0  
4.2  
4.3  
4.5  
4.7  
4.8  
0.2  
0.4  
0.6  
0.8  
1.0  
1.1  
1.2  
5.1  
5.6  
5.9  
6.0  
6.3  
6.4  
6.6  
4.3  
4.7  
5.0  
5.1  
5.3  
5.4  
5.6  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1  
0.2  
0.4  
0.5  
0.7  
6.7  
6.9  
7.2  
7.5  
7.8  
5.7  
5.8  
6.1  
6.3  
6.6  
-
-
-
0.1  
0.2  
-
8.5  
8.6  
-
7.1  
7.3  
-
208 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.5  
3.5  
2.5  
2.0  
1.0  
1.7  
1.9  
2.1  
2.3  
2.5  
2.6  
2.9  
4.2  
4.5  
4.5  
4.9  
5.1  
5.3  
5.6  
3.6  
3.8  
3.9  
4.1  
4.3  
4.4  
4.7  
1.3  
1.5  
1.6  
1.8  
2.0  
2.1  
2.3  
5.1  
5.4  
5.5  
5.8  
6.1  
6.3  
6.8  
4.3  
4.5  
4.7  
4.9  
5.1  
5.3  
5.7  
0.8  
1.0  
1.1  
1.3  
1.4  
1.5  
1.8  
6.0  
6.3  
6.4  
6.7  
7.1  
7.3  
7.9  
5.1  
5.3  
5.4  
5.7  
6.0  
6.2  
6.6  
0.2  
0.4  
0.5  
0.7  
0.9  
1.0  
-
6.9  
7.2  
7.5  
8.0  
8.4  
8.6  
-
5.8  
6.1  
6.3  
6.7  
7.0  
7.2  
-
-
-
-
0.1  
8.5  
7.1  
995  
0.2  
8.6  
7.3  
1025  
1050  
1065  
1100  
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE  
870  
900  
6.0**  
5.0  
4.0  
3.5  
2.5  
2.0  
1.5  
1.0  
1.3  
1.4  
1.6  
1.7  
1.9  
2.1  
2.2  
2.3  
3.6  
3.8  
4.1  
4.2  
4.5  
4.6  
4.8  
4.9  
3.0  
3.2  
3.4  
3.6  
3.8  
3.9  
4.0  
4.1  
0.7  
0.9  
1.1  
1.3  
1.5  
1.6  
1.7  
1.8  
4.3  
4.7  
5.0  
5.1  
5.4  
5.5  
5.7  
5.8  
3.7  
4.0  
4.2  
4.3  
4.5  
4.7  
4.8  
4.9  
0.2  
0.4  
0.6  
0.8  
1.0  
1.1  
1.2  
1.3  
5.1  
5.6  
5.9  
6.0  
6.3  
6.4  
6.6  
6.7  
4.3  
4.7  
5.0  
5.1  
5.3  
5.4  
5.6  
5.7  
-
-
-
-
-
-
-
-
-
-
-
-
930  
0.1  
0.2  
0.4  
0.5  
0.6  
0.7  
6.7  
6.9  
7.2  
7.5  
7.8  
8.0  
5.7  
5.8  
6.1  
6.3  
6.6  
6.7  
-
-
-
-
-
-
950  
965  
0.1  
0.2  
-
8.5  
8.6  
-
7.1  
7.3  
-
995  
1015  
1025  
-
-
-
230/460/575 VOLT AND HIGH STATIC DRIVE  
950  
980  
6.0  
5.0  
4.5  
4.0  
3.5  
3.0  
2.5  
1.5  
1.0  
1.7  
1.9  
2.1  
2.2  
2.3  
2.5  
2.6  
2.9  
3.1  
4.2  
4.5  
4.6  
4.8  
4.9  
5.1  
5.3  
5.6  
5.8  
3.6  
3.8  
3.9  
4.0  
4.1  
4.3  
4.4  
4.7  
4.9  
1.3  
1.5  
1.6  
1.7  
1.8  
2.0  
2.1  
2.3  
2.5  
5.1  
5.4  
5.5  
5.7  
5.8  
6.1  
6.3  
6.8  
7.0  
4.3  
4.5  
4.7  
4.8  
4.9  
5.1  
5.3  
4.7  
5.9  
0.8  
1.0  
1.1  
1.2  
1.3  
1.4  
1.5  
1.8  
1.9  
6.0  
6.3  
6.4  
6.6  
6.7  
7.1  
7.3  
7.9  
8.3  
5.1  
5.3  
5.4  
5.6  
5.7  
6.0  
6.2  
6.6  
6.9  
0.2  
0.4  
0.5  
0.6  
0.7  
0.9  
1.0  
-
6.9  
7.2  
7.5  
7.8  
8.0  
8.4  
8.6  
-
5.8  
6.1  
6.3  
6.6  
6.7  
7.0  
7.2  
-
-
-
-
0.1  
8.5  
7.1  
995  
0.2  
8.6  
7.3  
1015  
1025  
1050  
1065  
1100  
1120  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.  
2. Refer to the additional Static Resistances table.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
Johnson Controls Unitary Products  
25  
 
262260-YTG-E-1008  
TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT  
300 MBH - BOTTOM DUCT CONNECTIONS  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
CFM  
10000  
BHP  
BLOWER  
SPEED,  
(RPM)  
7500  
BHP  
8750  
BHP  
11250  
BHP  
12500  
BHP  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
ESP  
KW  
208 VOLT AND STANDARD DRIVE  
975  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
2.4  
5.9  
6.2  
6.6  
6.9  
7.3  
7.7  
8.0  
4.9  
5.1  
5.4  
5.7  
6.0  
6.3  
6.6  
5.0  
0.7  
0.9  
1.1  
1.3  
1.6  
1.8  
7.3  
7.7  
8.1  
8.5  
8.9  
9.3  
9.7  
6.0  
6.3  
6.7  
7.0  
7.3  
7.6  
8.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005  
1040  
1070  
1100  
1135  
1165  
-
-
-
-
-
-
0.2  
0.4  
0.6  
0.8  
1.0  
9.7  
10.2  
10.6  
11.1  
11.6  
8.0  
8.3  
8.7  
9.1  
9.5  
-
-
-
-
-
-
-
-
-
-
-
-
0.2  
13.5  
11.0  
208 VOLT AND HIGH STATIC DRIVE  
1140  
1180  
1215  
1255  
1290  
1330  
1365  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
2.2  
2.5  
2.7  
3.0  
3.2  
3.5  
3.7  
7.7  
8.2  
6.3  
6.7  
7.0  
7.4  
7.8  
8.2  
8.6  
1.6  
1.9  
2.1  
2.4  
2.7  
3.0  
3.2  
9.4  
9.9  
7.7  
8.1  
8.5  
9.0  
9.4  
9.9  
10.3  
0.9  
1.2  
1.4  
1.7  
2.0  
2.3  
2.6  
11.2  
11.8  
12.3  
12.9  
13.5  
14.1  
14.7  
9.2  
9.7  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3  
0.6  
0.9  
1.2  
1.5  
1.8  
13.7  
14.3  
15.0  
15.6  
16.4  
17.0  
11.2  
11.7  
12.3  
12.8  
13.4  
13.9  
8.6  
10.4  
11.0  
11.5  
12.0  
12.6  
10.1  
10.6  
11.1  
11.6  
12.1  
9.1  
9.5  
10.0  
10.5  
230/460/575 VOLT AND STANDARD DRIVE  
975  
6.0*  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
1.4  
1.6  
1.8  
2.0  
2.1  
2.4  
2.6  
5.9  
6.2  
6.6  
6.9  
7.3  
7.7  
8.0  
4.9  
5.1  
5.4  
5.7  
6.0  
6.3  
6.6  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
7.3  
7.7  
8.1  
8.5  
8.9  
9.3  
9.7  
6.0  
6.3  
6.7  
7.0  
7.3  
7.6  
8.0  
0.5  
0.7  
0.9  
1.1  
1.3  
1.6  
1.8  
8.8  
9.2  
7.2  
7.6  
8.0  
8.3  
8.7  
9.1  
9.5  
-
-
-
-
-
-
-
1005  
1040  
1070  
1100  
1135  
1165  
0.1  
0.3  
0.6  
0.8  
1.0  
1.3  
10.9  
11.4  
11.9  
12.4  
13.0  
13.5  
8.9  
-
-
9.7  
9.4  
-
-
-
10.2  
10.6  
11.1  
11.6  
9.8  
-
-
-
10.2  
10.6  
11.0  
0.2  
0.4  
0.7  
14.3  
14.9  
15.5  
11.7  
12.2  
12.7  
230/460/575 VOLT AND HIGH STATIC DRIVE  
1140  
1180  
1215  
1255  
1290  
1330  
1365  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
2.4  
2.7  
2.9  
3.2  
3.4  
3.7  
3.9  
7.7  
8.2  
6.3  
6.7  
7.0  
7.4  
7.8  
8.2  
8.6  
2.1  
2.3  
2.6  
2.9  
3.1  
3.4  
3.7  
9.4  
9.9  
7.7  
8.1  
8.5  
9.0  
9.4  
9.9  
10.3  
1.6  
1.9  
2.2  
2.5  
2.7  
3.0  
3.3  
11.2  
11.8  
12.3  
12.9  
13.5  
14.1  
14.7  
9.2  
9.7  
1.1  
1.4  
1.7  
2.0  
2.2  
2.6  
2.9  
13.1  
13.7  
14.3  
15.0  
15.6  
16.4  
17.0  
10.7  
11.2  
11.7  
12.3  
12.8  
13.4  
13.9  
0.5  
0.8  
1.1  
1.4  
-
15.0  
15.8  
16.4  
17.2  
-
12.3  
12.9  
13.5  
14.1  
-
8.6  
10.4  
11.0  
11.5  
12.0  
12.6  
10.1  
10.6  
11.1  
11.6  
12.1  
9.1  
9.5  
10.0  
10.5  
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.  
2. Refer to the additional Static Resistances table.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the  
total static pressure of the blower.  
* Do NOT close the pulley below 1 turn open.  
** Factory setting.  
15 HP Motor is required.  
26  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 16: BLOWER MOTOR AND DRIVE DATA  
BELT  
(NOTCHED)  
1
ADJUSTABLE MOTOR PULLEY  
FIXED BLOWER PULLEY  
OUTSIDE PITCH  
MOTOR  
BLOWER  
DRIVE RANGE  
(RPM)  
MODEL  
SIZE  
OUTSIDE PITCH  
PITCH  
LENGTH QTY.  
(IN.)  
EFF.  
(%)  
DESIG-  
NATION  
BORE DESIG-  
(IN.) NATION  
BORE DESIG-  
HP FRAME  
DIA.  
(IN.)  
DIA.  
(IN.)  
DIA.  
(IN.)  
DIA.  
(IN.)  
(IN.) NATION  
Standard 850/1065  
BK90  
1-1/8  
BK80  
8.75  
7.75  
11.75  
10.75  
11.3  
8.4  
1
BX70  
BX68  
BX83  
BX81  
BX81  
82.8  
69.8  
84.8  
82.8  
82.8  
84.0  
1
1
1
1
1
1
2
15 TON  
5
184 T  
83  
89  
1VP56  
1VP68  
5.35  
6.75  
4.3-5.3  
High  
965/1190  
Static  
7.4  
1
Standard 870/1025  
BK120  
11.4  
10.4  
11.1  
9.5  
1-3/16  
1-3/16  
1-7/16  
17.5 &  
20 TON  
2
2
7.5 213 T  
1-3/8  
5.5-6.5  
5.5-6.5  
High  
950/1120  
Static  
BK110  
Standard 950/1120 10 215 T 89.5  
High  
1VP68  
6.75  
7.5  
1-3/8 1B5V110  
25 TON  
1140/1365 15 254 T  
91  
1VP75X  
6.2-7.4 1-5/8 1B5V94  
9.7  
1-7/16 5VX840  
Static  
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because  
they are located in the moving air, upstream of any heating device.  
2. Do NOT close this pulley below 1 turn open.  
1
TABLE 17: STATIC RESISTANCES  
RESISTANCE, IWG  
CFM  
DESCRIPTION  
15 TON  
17.5 TON  
20 TON  
25 TON  
4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500  
WET COIL  
0.1  
0.3  
0.3  
0.4  
0.4  
0.1  
0.1  
0.4  
0.4  
0.5  
0.5  
0.1  
0.1  
0.4  
0.5  
0.5  
0.5  
0.1  
0.1  
0.4  
0.4  
0.5  
0.5  
0.1  
0.2  
0.1  
0.4  
0.5  
0.5  
0.5  
0.1  
0.3  
0.1  
0.5  
0.5  
0.6  
0.6  
0.2  
0.5  
0.1  
0.4  
0.4  
0.5  
0.5  
0.1  
0.1  
0.4  
0.5  
0.5  
0.5  
0.1  
0.1  
0.5  
0.5  
0.6  
0.6  
0.2  
0.1  
0.4  
0.5  
0.5  
0.5  
0.1  
0.1  
0.6  
0.5  
0.6  
0.6  
0.2  
0.1  
0.6  
0.6  
0.7  
0.7  
0.3  
18kW  
36kW  
54kW  
72kW  
ELECTRIC HEAT  
OPTIONS  
(DH models only)  
ECONOMIZER OPTION  
HORIZONTAL DUCT CONNECTIONS2  
0.1  
0.2  
0.3  
0.2  
0.3  
0.5  
0.3  
0.5  
0.6  
1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for  
Horizontal Duct Connections.  
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures  
to the ESP values on the respective unit’s blower performance table.  
TABLE 18: POWER EXHAUST PERFORMANCE  
STATIC RESISTANCE OF RETRUN DUCTWORK, IWG  
MOTOR  
SPEED1  
0.2  
0.3  
0.4  
0.5  
0.6  
CFM  
kW  
CFM  
kW  
CFM  
kW  
CFM  
kW  
CFM  
kW  
HIGH2  
MEDIUM  
LOW  
5250  
4900  
4400  
0.83  
0.77  
0.72  
4500  
3900  
3700  
0.85  
0.79  
0.74  
4200  
3500  
3000  
0.88  
0.82  
0.78  
3750  
2900  
-
0.93  
0.85  
-
3000  
0.99  
-
-
-
-
1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.  
2. The factory setting.  
Johnson Controls Unitary Products  
27  
     
262260-YTG-E-1008  
TABLE 19: DH 180, 210 & 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
BRKR1  
SIZE  
(AMPS)  
90  
ID  
MIN.  
CIRCUIT  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS AMPACITY  
(AMPS)  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
--  
13.5  
27  
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
70.9  
70.9  
109.7  
156.9  
166.2  
70.5  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
--  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
--  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
90  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
21.8  
21.8  
11.0  
9.6  
184  
184  
90  
4.5  
4.3  
2.2  
1.7  
4.5  
4.3  
2.2  
1.7  
4.5  
4.3  
2.2  
1.7  
12.8  
12.8  
6.4  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
0.0  
110  
175  
200  
90  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
13.5  
27  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
13.5  
27  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
70.5  
90  
124.3  
145.9  
189.2  
35.6  
35.6  
62.1  
73.0  
94.6  
30.2  
30.2  
125  
175  
225  
45  
45  
70  
80  
110  
35  
35  
50  
DH180  
(15)  
73  
5.2  
49.8  
58.5  
75.8  
86.6  
70  
90  
110  
110  
125  
175  
200  
110  
110  
150  
175  
225  
50  
50  
70  
90  
110  
40  
86.6  
25.6  
25.6  
12.8  
10.2  
32.1  
32.1  
14.3  
12.9  
190  
190  
95  
20.0  
20.0  
10.0  
7.5  
118.7  
165.9  
175.2  
86.2  
86.2  
133.3  
154.9  
198.2  
43.2  
43.2  
66.6  
77.5  
99.1  
33.9  
33.9  
DH210  
(17 1/2)  
40  
60  
70  
90  
75  
52.7  
61.3  
78.7  
101.2  
101.2  
118.7  
165.9  
175.2  
100.8  
100.8  
133.3  
154.9  
198.2  
46.6  
46.6  
66.6  
77.5  
99.1  
39.9  
39.9  
52.7  
61.3  
125  
125  
125  
175  
200  
125  
125  
150  
175  
225  
60  
60  
70  
90  
110  
50  
237  
237  
130  
85  
20.0  
20.0  
10.0  
7.5  
DH240  
(20)  
18.0  
36.0  
54.0  
72.0  
50  
60  
70  
90  
78.7  
NOTE 1: HACR Type per NEC.  
28  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 20: DH 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
ID  
MIN.  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
CIRCUIT  
AMPACITY  
(AMPS)  
BRKR1  
SIZE  
(AMPS)  
150  
150  
150  
200  
200  
150  
150  
150  
175  
225  
70  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
-
-
-
120.5  
120.5  
128.7  
175.9  
185.2  
118.1  
118.1  
140.8  
162.4  
205.7  
56.1  
13.5  
27.0  
40.6  
54.1  
-
1
2
2
2
-
37.5  
74.9  
112.7  
150.2  
-
43.3  
86.6  
129.9  
173.2  
-
208  
230  
460  
575  
37.1  
37.1  
17.2  
12.4  
239  
239  
125  
80  
4.5  
4.3  
2.2  
1.7  
28.0  
26.0  
13.0  
10.0  
0.0  
0.0  
0.0  
0.0  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
300  
(25)  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
21.7  
43.3  
65.0  
86.6  
-
17.3  
34.6  
52.0  
69.3  
56.1  
70.4  
81.2  
70  
80  
90  
102.9  
41.3  
41.3  
110  
50  
50  
18.0  
36.0  
54.0  
72.0  
1
2
2
2
55.8  
64.5  
81.8  
60  
70  
90  
NOTE 1: HACR Type per NEC.  
TABLE 21: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
ID  
MIN.  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
CIRCUIT  
AMPACITY  
(AMPS)  
BRKR1  
SIZE  
(AMPS)  
150  
150  
150  
200  
225  
150  
150  
175  
200  
250  
80  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
-
-
-
131.5  
131.5  
141.9  
189.1  
198.4  
131.1  
131.1  
156.5  
178.2  
221.5  
62.9  
13.5  
27.0  
40.6  
54.1  
-
1
2
2
2
-
37.5  
74.9  
112.7  
150.2  
-
208  
230  
460  
575  
37.1  
37.1  
17.2  
12.4  
239  
239  
125  
80  
4.5  
4.3  
2.2  
1.7  
38.6  
38.6  
19.3  
15.4  
0.0  
0.0  
0.0  
0.0  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
43.3  
86.6  
129.9  
173.2  
-
21.7  
43.3  
65.0  
86.6  
-
300  
(25)  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
62.9  
80  
78.3  
89.1  
110.7  
47.5  
47.5  
80  
100  
125  
60  
60  
70  
18.0  
36.0  
54.0  
72.0  
1
2
2
2
17.3  
34.6  
52.0  
69.3  
62.6  
71.2  
88.5  
80  
100  
NOTE 1: HACR Type per NEC.  
Johnson Controls Unitary Products  
29  
   
262260-YTG-E-1008  
TABLE 22: DH 180, 210 & 240 ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
ID  
MIN.  
CIRCUIT  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
BRKR1  
SIZE  
(AMPS)  
100  
100  
125  
175  
200  
100  
100  
150  
175  
225  
50  
50  
70  
90  
110  
40  
40  
60  
70  
90  
110  
110  
150  
200  
200  
110  
110  
150  
175  
225  
60  
60  
80  
90  
110  
45  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS AMPACITY  
(AMPS)  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
--  
13.5  
27  
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
1
2
2
2
--  
80.9  
80.9  
122.2  
169.4  
178.7  
80.5  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
--  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
--  
37.5  
74.9  
112.7  
150.2  
--  
43.3  
86.6  
129.9  
173.2  
--  
21.7  
43.3  
65.0  
86.6  
--  
17.3  
34.6  
52.0  
69.3  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
208-3-60  
230-3-60  
460-3-60  
575-3-60  
21.8  
21.8  
11.0  
9.6  
184  
184  
90  
4.5  
4.3  
2.2  
1.7  
4.5  
4.3  
2.2  
1.7  
4.5  
4.3  
2.2  
1.7  
12.8  
12.8  
6.4  
10.0  
10.0  
5.0  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
13.5  
27  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
13.5  
27  
40.6  
54.1  
--  
18.0  
36.0  
54.0  
72.0  
--  
18.0  
36.0  
54.0  
72.0  
--  
82.6  
136.8  
158.4  
201.7  
40.6  
41.3  
68.4  
79.2  
100.9  
34.2  
34.2  
54.8  
63.5  
80.8  
96.6  
96.6  
131.2  
178.4  
187.7  
96.2  
DH180  
(15)  
73  
5.2  
4.0  
25.6  
25.6  
12.8  
10.2  
32.1  
32.1  
14.3  
12.9  
190  
190  
95  
20.0  
20.0  
10.0  
7.5  
10.0  
10.0  
5.0  
96.2  
145.8  
167.4  
210.7  
48.2  
48.2  
72.9  
83.7  
105.4  
37.9  
37.9  
57.7  
DH210  
(17 1/2)  
45  
60  
70  
90  
75  
4.0  
66.3  
83.7  
111.2  
111.2  
131.2  
178.4  
187.7  
110.8  
110.8  
145.8  
167.4  
210.7  
51.6  
51.6  
72.9  
83.7  
105.4  
43.9  
125  
125  
150  
200  
200  
125  
125  
150  
175  
225  
60  
60  
80  
90  
110  
50  
237  
237  
130  
85  
20.0  
20.0  
10.0  
7.5  
10.0  
10.0  
5.0  
DH240  
(20)  
18.0  
36.0  
54.0  
72.0  
43.9  
57.7  
66.3  
83.7  
50  
60  
70  
90  
4.0  
NOTE 1: HACR Type per NEC.  
30  
Johnson Controls Unitary Products  
 
262260-YTG-E-1008  
TABLE 23: DH 300 ELECTRICAL DATA STANDARD MOTOR WITH POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
ID  
MIN.  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
CIRCUIT  
AMPACITY  
(AMPS)  
BRKR1  
SIZE  
(AMPS)  
150  
150  
150  
200  
200  
150  
150  
175  
175  
225  
70  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
-
-
-
130.5  
130.5  
141.2  
188.4  
197.7  
128.1  
128.1  
153.3  
174.9  
218.2  
61.1  
13.5  
27.0  
40.6  
54.1  
-
1
2
2
2
-
37.5  
74.9  
112.7  
150.2  
-
43.3  
86.6  
129.9  
173.2  
-
208  
230  
460  
575  
37.1  
37.1  
17.2  
12.4  
239  
239  
125  
80  
4.5  
4.3  
2.2  
1.7  
28.0  
26.0  
13.0  
10.0  
10.0  
10.0  
5.0  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
300  
(25)  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
21.7  
43.3  
65.0  
86.6  
-
17.3  
34.6  
52.0  
69.3  
61.1  
76.6  
87.5  
70  
80  
90  
109.1  
45.3  
45.3  
110  
50  
50  
18.0  
36.0  
54.0  
72.0  
1
2
2
2
4.0  
60.8  
69.5  
86.8  
70  
70  
90  
NOTE 1: HACR Type per NEC.  
TABLE 24: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET  
COMPRESSORS  
HEATER OPTION  
MAX.  
FUSE/  
ID  
MIN.  
MODEL  
(TON-  
OD FAN  
MOTORS  
FLA EACH  
CONV  
OUTLET  
AMPS  
BLOWER  
MOTOR  
FLA  
CIRCUIT  
AMPACITY  
(AMPS)  
BRKR1  
SIZE  
(AMPS)  
175  
175  
175  
225  
225  
175  
175  
175  
225  
250  
80  
VOLTAGE  
RLA  
LRA  
MODEL KW STAGES AMPS  
EACH  
EACH  
NAGE)  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
None  
E18  
E36  
E54  
E72  
-
-
-
141.5  
141.5  
154.4  
201.6  
210.9  
141.1  
141.1  
169.0  
190.7  
234.0  
67.9  
13.5  
27.0  
40.6  
54.1  
-
1
2
2
2
-
37.5  
74.9  
112.7  
150.2  
-
208  
230  
460  
575  
37.1  
37.1  
17.2  
12.4  
239  
239  
125  
80  
4.5  
4.3  
2.2  
1.7  
38.6  
38.6  
19.3  
15.4  
10.0  
10.0  
5.0  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
43.3  
86.6  
129.9  
173.2  
-
21.7  
43.3  
65.0  
86.6  
-
300  
(25)  
18.0  
36.0  
54.0  
72.0  
-
1
2
2
2
-
67.9  
80  
84.5  
95.3  
117.0  
51.5  
51.5  
90  
110  
125  
60  
60  
70  
18.0  
36.0  
54.0  
72.0  
1
2
2
2
17.3  
34.6  
52.0  
69.3  
4.0  
67.6  
76.2  
93.5  
90  
100  
NOTE 1: HACR Type per NEC.  
Johnson Controls Unitary Products  
31  
   
262260-YTG-E-1008  
1
TABLE 26: ELECTRIC HEAT CORRECTION  
FACTORS  
TABLE 25: DH VOLTAGE LIMITATIONS  
VOLTAGE  
POWER SUPPLY  
kW CAP. MULTI-  
PLIER  
MIN.  
MAX.  
NOMINAL VOLTAGE  
VOLTAGE  
208/230-3-60  
187  
253  
208  
230  
460  
575  
1.00  
0.92  
0.92  
0.92  
208  
240  
480  
600  
414  
518  
506  
506  
460-3-60  
575-3-60  
1. Utilization Range “A” in accordance with ARI Standard  
110.  
CONTROL WIRING  
COOLING / HEATING (24 VOLT THERMOSTAT)  
THERMOSTAT1  
TERMINALS  
UNIT TERMINAL  
BLOCK 1TB2  
COOLING ONLY (24 VOLT THERMOSTAT)  
THERMOSTAT1  
R
RH  
RC  
Y1  
Y2  
TERMINALS  
Y1  
Y2  
W1  
UNIT TERMINAL  
BLOCK 1 TB2  
RC  
RH  
R
ADD  
JUMPER  
W2  
G
Y1  
Y2  
Y1  
Y2  
ADD  
JUMPER  
W1  
W2  
B
W1  
W2  
G
W1  
W2  
24 VOLT  
TRANSFORMER  
X
3
3
A1  
A2  
Y3  
G
G
B
X
B
124 Volt Thermostat 2TH04701024 or 2TH04701524  
(with Subbase 2TB04700324).  
LED1  
24 VOLT  
TRANSFORMER  
LED2  
4
A1  
A2  
NOT USED  
2Terminal strip 1TB - located on relay board in 24-volt section  
of the unit control box.  
4
COM  
A1  
3Second stage heating is not required on units with a single stage  
electric heater.  
ADD  
JUMPER  
A2  
T
POWER WIRING  
T
L1  
Refer to the  
TO REMOTE SENSOR  
2THO4702224 IF USED  
LINE VOLTAGE  
TERMINAL  
BLOCK 2TB  
ELECTRICAL DATA  
tables to size the  
power wiring, the  
fuses and the  
L2  
L3  
1Electronic programmable thermostat 2ET04700224 (includes subbase).  
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.  
3Second stage heating is not required on units with a single stage electric heater.  
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers  
when the thermostat switches to the set-back position.  
IN CONTROL BOX  
disconnect switch.  
GROUND LUG  
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.  
FIGURE 3 - TYPICAL DH FIELD WIRING DIAGRAM  
32  
Johnson Controls Unitary Products  
     
262260-YTG-E-1008  
TABLE 27: PHYSICAL DATA  
DH  
MODELS  
Centrifugal Blower (Dia. x Wd. in.)  
180  
210  
18 x 15  
7.5  
4
240  
18 x 15  
7.5  
4
300  
18 x 15  
10/15  
4
15 x 15  
EVAPORATOR  
BLOWER  
Fan Motor HP Standard/Hi Static  
Rows Deep  
5
4
13.5  
15.5  
30  
EVAPORATOR  
COIL  
Fins Per Inch  
13.5  
20.0  
30  
13.5  
20.0  
30  
13.5  
25.0  
30  
Face Area (Sq. Ft.  
Propeller Dia. (in.) (Each)  
Fan Motor Hp (Each)  
Nom. CFM (Each)  
CONDENSER  
FANS  
1
1
1
1
(Two Per Unit)  
5765  
3
7000  
3
7000  
3
7200  
2
Rows Deep (Each)  
CONDENSER  
COILS  
Fins Per Inch (Each)  
13  
15  
15  
20  
(Two Per Unit)  
Face Area (Sq. Ft.) (Total)  
7.5 Ton Scroll  
36.0  
2
43.3  
2
43.3  
-
43.3  
-
COMPRESSOR  
(Qty. Per Unit)  
10 Ton Scroll  
-
-
2
-
12.5 Ton Scroll  
-
-
-
2
Quantity Per Unit (16” X 20” X 2” or 4“)  
Quantity Per Unit (16” X 25” X 2” or 4“)  
Quantity Per Unit (18” X 24” X 2” or 4“)  
Total Face Area (sq. ft.)  
-
4
4
4
-
4
4
4
AIR  
FILTERS  
5
-
-
-
15.0  
23/10  
21/10  
20.0  
24/0  
24/8  
20.0  
24/2  
27/2  
20.0  
21/1  
21/1  
System #1  
System #2  
Refrigerant 22  
(lbs./oz.)  
CHARGE  
TABLE 28: OPERATING WEIGHTS (LBS.)  
MODEL SIZE  
15 TON  
17.5 TON  
20 TON  
2100  
25 TON  
2345  
DH (Cooling Only)  
1900  
2100  
2140  
1950  
2150  
2190  
BASIC  
UNIT  
240Mbh  
2300  
2545  
DH  
(Gas/Electric)  
320Mbh  
2340  
2585  
Economizer  
160  
Economizer with  
Power Exhaust  
245  
Motorized Damper  
150  
25  
30  
35  
40  
10  
18kW  
36kW  
54kW  
72kW  
OPTIONS  
Electric Heater  
(DH only)  
Hot Gas Bypass  
Supply Fan VFD  
Roof Curb  
185  
175  
185  
185  
Barometric Damper  
45  
55  
Economizer/Motorized Damper Rain Hood  
Economizer/Power Exhaust Rain Hood  
Wood Skid  
ACCY.  
90  
220  
TABLE 29: SUPPLY FAN VFD WEIGHTS, IN LBS.  
SUPPLY FAN MOTOR  
230V  
460V  
575V  
W/O MANUAL BYPASS  
25  
30  
30  
30  
25  
30  
30  
30  
30  
30  
35  
40  
5.0 hp  
7.5 hp  
10.0 hp  
15.0 hp  
W/MANUAL BYPASS  
5.0 hp  
30  
35  
35  
40  
30  
35  
35  
35  
35  
35  
40  
45  
7.5 hp  
10.0 hp  
15.0 hp  
Johnson Controls Unitary Products  
33  
     
262260-YTG-E-1008  
ECONOMIZER / MOTORIZED DAMPER,  
FIXED OUTDOOR INTAKE AIR AND  
POWER EXHAUST RAIN HOODS  
(See detail "Y")  
BLOWER ACCESS  
(Location Of  
Optional VFD)  
FIELD-SUPPLIED  
DISCONNECT SWITCH  
LOCATION  
BLOWER MOTOR ACCESS  
(Location Of Optional  
VFD Bypass)  
COMPRESSOR  
ACCESS  
(See detail "X")  
BLOWER  
COMPARTMENT  
ACCESS  
OPTIONAL COIL  
GUARD KIT  
(Auxiliary)  
DOT PLUG  
(For pressure  
Drop Reading)  
48-5/8" (15 Ton)  
52-5/8" (17.5 thru 25 Ton)  
ELECTRIC  
GAS HEAT  
ACCESS  
CONDENSER  
COILS  
VENT AIR  
OUTLET  
HOODS  
21"  
5"  
7-1/8"  
COMBUSTION  
AIR INLET  
HOOD  
6-3/8"  
9-3/4"  
92"  
(C)  
5-7/8"  
(A)  
GAS SUPPLY  
ENTRY  
CONTROL WIRING  
ENTRY  
46-5/8"  
CONTROL BOX  
ACCESS  
11-1/2"  
(B)  
35"  
POWER WIRING  
ENTRY  
BOTTOM SUPPLY  
AND RETURN  
AIR OPENINGS  
(See Note)  
FRONT  
VIEW  
RETURN AIR  
SUPPLY AIR  
OUTDOOR AIR  
RETURN  
AIR  
3-3/4"  
33"  
SUPPLY  
AIR  
2-3/4"  
21-1/2"  
11-1/8"  
OUTDOOR AIR  
(Economizer)  
UNIT BASE WITH RAILS  
(B)  
(D)  
Shown separately to illustrate  
Bottom Duct openings, Power  
and Gas Piping Connection  
locations  
All dimensions are in inches. They are  
subject to change without notice. Certi-  
fied dimensions will be provided upon  
request.  
POWER WIRING  
ENTRY  
GAS SUPPLY  
ENTRY  
(A)  
CONTROL WIRING  
ENTRY  
8-1/8"  
9-3/4"  
NOTE:  
46-5/8"  
For curb mounted units, refer to the curb hanger  
dimensions of the curb for the proper size of the  
supply and return air duct connections.  
9-1/4"  
12-1/2"  
FIGURE 4 - UNIT DIMENSIONS DH180, 210, 240 & 300 (FRONT VIEW)  
TABLE 30: UTILITIES ENTRY DATA  
OPENING SIZE  
HOLE  
USED FOR  
(DIA.)  
1-1/8” KO  
Side  
A
Control Wiring  
3/4” NPS (Fem.)  
3-5/8” KO  
Bottom  
Side  
Bottom  
1
Power Wiring  
B
3” NPS (Fem.)  
C
D
2-3/8” KO  
Gas Piping (Front)  
,
2
1-11/16” Hole  
Gas Piping (Bottom)  
1. One-inch gas piping NPT required.  
2. Opening in the bottom of the unit can be located by the slice in  
the insulation.  
NOTE: All entry holes should be field sealed to prevent rain  
water entry into the building.  
34  
Johnson Controls Unitary Products  
     
262260-YTG-E-1008  
EVAPORATOR  
SECTION  
DOT PLUG  
(For pressure  
drop reading)  
40-3/8"  
FILTER  
ACCESS  
SUPPLY  
AIR  
RETURN  
AIR  
COMPRESSOR  
ACCESS  
OUTDOOR  
AIR  
40-1/2"  
SUPPLY AIR  
ACCESS  
18-5/8"  
1" NPT FEMALE  
COND. DRAIN  
CONNECTION  
27-3/4"  
Dimensions listed are for side  
5-1/8"  
RETURN AIR  
ACCESS  
duct flange openings; see  
Field Accessories for Side  
Duct Flange Kit.  
OUTDOOR AIR  
COMPARTMENT  
ACCESS  
28-5/8” (15 TON)  
39-5/8"  
(17.5 thru 25 TON)  
REAR  
VIEW  
FIGURE 5 - REAR VIEW DIMENSIONS  
NOTE:Units are shipped with the bottom duct openings  
covered. An accessory flange kit is available for  
connecting side ducts.  
For bottom duct applications:  
For side duct applications:  
1. Remove the side panels from the supply and return air  
compartments to gain access to the bottom supply and  
return air duct covers.  
1. Replace the side panels on the supply and return air  
compartments with the side duct flange accessory kit  
panels.  
2. Remove and discard the bottom duct covers. Duct  
openings are closed with sheet metal covers except  
when the unit includes a power exhaust option. The  
covering consists of a heavy black paper composition.  
2. Connect ductwork to the flanges on those panels.  
3. Replace the side supply and return air compartment  
panels.  
Johnson Controls Unitary Products  
35  
 
262260-YTG-E-1008  
NOTE: ELEC / ELEC Models: Units and ductwork are  
approved for zero clearance to combustible material  
when equipped with electric heaters.  
TABLE 31: MINIMUM CLEARANCES  
LOCATION  
CLEARANCE  
36”  
Front  
24” (Less Economizer)  
49” (With Economizer)  
Rear  
GAS / ELEC Models: A 1” clearance must be  
provided between any combustible material and the  
supply air ductwork for a distance of 3 feet from the  
unit.  
24” (Less Economizer)  
Left Side (Filter Access)  
Right Side (Cond. Coil)  
3
36” (With Economizer)  
36”  
0”  
1
Below Unit  
The products of combustion must not be allowed to  
accumulate within a confined space and recirculate.  
72” With 36” Maximum  
Horizontal Overhang (For  
Condenser Air Discharge)  
2
Above Unit  
Locate unit so that the vent air outlet hood is at least:  
1. Units may be installed on combustible floors made from wood or  
class A, B, or C roof covering material.  
• Three (3) feet above any force air inlet located  
within 10 horizontal feet (excluding those integral to  
the unit).  
2. Units must be installed outdoors. Overhanging structures or  
shrubs should not obstruct condenser air discharge outlet.  
3. If economizer is factory installed, the unassembled rain hood  
must be removed from its ride along position in front of evapora-  
tor coil, or in the outdoor air compartment, prior to final installa-  
tion.  
• Four (4) feet below, four horizontal feet from, or one  
foot above any door or gravity air inlet into the  
building.  
• Four (4) feet from electric and gas meters,  
regulators and relief equipment.  
ECONOMIZER  
MOTORIZED  
DAMPER  
POWER EXHAUST  
RAIN HOOD  
(on Return Air Compartment)  
SUPPLY AIR  
RAIN HOOD  
(on Outdoor Air Compartment)  
COMPARTMENT  
ECONOMIZER / MOTORIZED DAMPER  
AND POWER EXHAUST RAIN HOODS  
FIXED  
OUTDOOR AIR  
INTAKE HOOD  
(located on  
Return Air  
Compartment)  
36-5/8”  
1“ CONDENSATE  
DRAIN  
(Must be trapped)  
16-1/8”  
5”  
28-3/16”  
92”  
REAR VIEW  
LH VIEW  
DETAIL “Y”  
UNIT WITH RAIN HOODS  
FIGURE 6 - UNIT DIMENSIONS DH180, 210, 240 & 300 (RAINHOOD)  
36  
Johnson Controls Unitary Products  
   
262260-YTG-E-1008  
(17.5, 20 & 25 Ton)  
FIGURE 7 - UNIT CENTER OF GRAVITY  
FIGURE 8 - TYPICAL UNIT APPLICATIONS  
Johnson Controls Unitary Products  
37  
   
262260-YTG-E-1008  
E
B
F
C
D
A
A
C
F
R
O
N
T
F
R
O
N
T
D
B
FIGURE 9 - UNIT 4 POINT LOAD  
FIGURE 10 - UNIT 6 POINT LOAD  
TABLE 32: DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT DISTRIBUTION  
OPERATING  
UNIT MODEL  
WEIGHT  
(lb)  
A
B
C
D
DH180C00  
DH180N24  
DH180N32  
DH210C00  
DH210N24  
DH210N32  
DH240C00  
DH240N24  
DH240N32  
DH300C00  
DH300N24  
DH300N32  
1900  
2100  
2140  
1950  
2150  
2190  
2100  
2300  
2340  
2345  
2545  
2585  
445  
492  
501  
457  
504  
513  
492  
539  
548  
461  
501  
509  
484  
535  
545  
497  
548  
558  
535  
586  
596  
502  
545  
553  
506  
559  
570  
519  
572  
583  
559  
612  
623  
720  
781  
794  
465  
514  
524  
477  
526  
536  
514  
563  
573  
662  
718  
729  
TABLE 33: DH 180, 210, 240 & 300 6 POINT LOAD WEIGHT DISTRIBUTION  
OPERATING  
UNIT MODEL  
WEIGHT  
(lb)  
A
B
C
D
E
F
DH180C00  
DH180N24  
DH180N32  
DH210C00  
DH210N24  
DH210N32  
DH240C00  
DH240N24  
DH240N32  
DH300C00  
DH300N24  
DH300N32  
1900  
2100  
2140  
1950  
2150  
2190  
2100  
2300  
2340  
2345  
2545  
2585  
293  
324  
330  
300  
331  
337  
324  
354  
360  
303  
329  
334  
306  
338  
344  
314  
346  
352  
338  
370  
377  
321  
348  
353  
323  
357  
364  
332  
366  
372  
357  
391  
398  
339  
368  
374  
342  
378  
385  
351  
387  
394  
378  
414  
421  
487  
528  
537  
327  
362  
369  
336  
370  
377  
362  
396  
403  
460  
499  
507  
309  
342  
348  
317  
350  
357  
342  
374  
381  
435  
472  
479  
38  
Johnson Controls Unitary Products  
       
262260-YTG-E-1008  
(17.5 thru  
25 Ton)  
(17.5 thru  
25 Ton)  
FIGURE 11 - UNIT ROOF CURB DIMENSIONS  
(17.5 & 20 Ton)  
FIGURE 12 - ROOF CURB DUCT OPENINGS  
DIMENSIONS  
FIGURE 13 - CUT AWAY OF ROOF CURB  
1. The 2” space between the ducts allows for “jumping” an  
existing roof joist.  
2. The 58-1/2” overall dimension of the ducts allows  
ductwork penetration between roof joists that are  
spaced on 72” centers.  
NOTE: Ducts can be installed into the curb from the roof. All  
electrical and gas line connections can be made  
inside the curb.  
Johnson Controls Unitary Products  
39  
     
262260-YTG-E-1008  
FIGURE 14 - TYPICAL ROOFTOP INSTALLATION  
THERMOSTAT  
TERMINALS  
CONTROL  
TERMINAL  
BLOCK  
W1  
W1  
W2  
Y1  
G
1
W2  
Y1  
2
Y2  
OCC  
P
P1  
Y2  
X
G
R
C
Smoke  
Detector  
R
SD  
C
Jumper 3  
R
SD  
SD  
C
4
RC  
5
OCC  
24 VAC  
Class 2  
6
X
TERMINALS ON  
A LIMITED  
NUMBER OF  
THERMOSTATS  
1
Second stage heating not required on single stage heating units.  
2
Second stage cooling not required on single stage cooling units.  
3
Jumper is required if there is no Smoke Detector circuit.  
4
Jumper is required for any combination of R, RC, or RH.  
5
OCC is an output from the thermostat to indicate the Occupied condition.  
X is an input to the thermostat to display Error Status conditions.  
6
®
FIGURE 15 - TYPICAL S IMPLICIT Y CONTROL WIRING DIAGRAM  
40  
Johnson Controls Unitary Products  
   
262260-YTG-E-1008  
supply/return, and be available with factory installed options  
or field installed accessories. The units shall be factory  
wired, piped, charged with R-22 refrigerant and factory  
tested prior to shipment. All unit wiring shall be both num-  
bered and color coded. All units shall be manufactured in a  
facility certified to ISO 9001 standards and the cooling per-  
formance shall be rated in accordance with DOE and ARI  
test procedures. Units shall be CSA listed, classified to  
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90  
conditions.  
GUIDE SPECIFICATIONS  
GENERAL  
Units shall be manufactured by Unitary Products in an ISO  
9001 certified facility.  
York's Sunline Ultra™ units are convertible single package  
units. All models have dual independent refrigerant circuits  
for efficient part load operation and maximum comfort con-  
trol. Although the units are primarily designed for curb  
mounting on a roof, they can also be slab-mounted at  
ground level or set on steel beams above a finished roof.  
Cooling only, cooling with gas heat and cooling with electric  
heat models are available with a wide variety of factory-  
mounted options and field-installed accessories to make  
them suitable for almost every application. All units are self-  
contained and assembled on full perimeter base rails with  
holes in the four corners for overhead rigging. Every unit is  
completely piped, wired, charged and tested at the factory  
to simplify the field installation and to provide years of  
dependable operation. All models (including those with an  
economizer) are suitable for either bottom or horizontal duct  
connections. Models with power exhaust are suitable for  
bottom duct connections only. For bottom duct, remove the  
sheet metal panels from the supply and return air openings  
through the base of the unit. For horizontal duct, replace the  
supply and return air panels on the rear of the unit with a  
side duct flange accessory. All supply air blowers are  
equipped with a belt drive that can be adjusted to meet the  
exact requirements of the job. A high static drive option is  
available for applications with a higher CFM and/or static  
pressure requirement.  
UNIT CABINET  
Unit cabinet shall be constructed of galvanized steel, with  
exterior surfaces coated with a non-chalking, powdered  
paint finish, certified at 1000 hour salt spray test per ASTM-  
B117 standards. Indoor blower section shall be insulated  
with a minimum 1/2" thick insulation, coated on the airside.  
Aluminum foil faced insulation shall be used in the furnace  
compartment and be fastened with ridged fasteners to pre-  
vent insulation from entering the air stream. Cabinet panels  
shall be "large" size, easily removable for servicing and  
maintenance. Full perimeter base rails shall be provided to  
assure reliable transit of equipment, overhead rigging and  
proper sealing on roof curb applications. Disposable 2" fil-  
ters shall be furnished and be accessible through a remov-  
able access door, sealed airtight. Units filter track shall be  
designed to accommodate either 2" or 4" filters. Fan perfor-  
mance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evapora-  
tor fan performance without removing panels or creating air  
by-pass of the coils. Condensate pan shall be internally  
sloped and conform to ASHRAE 62-89 self-draining stan-  
dards. Condensate connection shall be a minimum of 1" I.D.  
female and be a ridged mount connection. Unit shall incor-  
porate a fixed outdoor air damper with an outdoor air intake  
opening covered with a bird screen and a rain hood painted  
to match the exterior of the unit.  
Each unit shall have 2 condenser fan motors. All compres-  
sors include crankcase heat and internal pressure relief.  
Every refrigerant circuit includes an expansion valve, a liq-  
uid line filter-drier, a discharge line high pressure switch and  
a suction line with a freezestat and low pressure/loss of  
charge switch. The unit control circuit includes a 75 VA  
transformer, a 24-volt circuit breaker and a relay board with  
two compressor lockout circuits, a terminal strip for thermo-  
stat wiring, plus an additional set of pin connectors to sim-  
plify the interface of additional field controls. All models are  
CSA approved. All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater ele-  
ments carry an additional 4-year warranty. Aluminized steel  
tubular heat exchangers carry an additional 9-year warranty.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
Fan shall be a belt drive assembly and include an adjustable-  
pitch motor pulley. Job site selected (B.H.P.) brake horse-  
power shall not exceed the motors nameplate horsepower  
rating, plus the service factor. Units shall be designed not to  
operate above service factor. Fan wheel shall be double-inlet  
type with forward-curved blades, dynamically balanced to  
operate smoothly throughout the entire range of operation.  
Airflow design shall be constant air volume.  
DESCRIPTION  
A variable air volume (VAV) option using a variable frequency  
drive (VFD) is available for applications requiring a constant  
supply duct static pressure. Units equipped for VAV shall be  
controlled by a duct pressure transducer with a 0 - 5” WC pres-  
sure range. The pressure transducer shall provide a 0 - 5 VDC  
output signal to a VAV control board which, in turn shall provide  
a 2 - 10 VDC speed reference signal to the VFD. The VAV  
control board shall operate using factory-installed Supply  
Air, Return Air and Outside Air Temperature Sensors. Units  
equipped with VFD’s shall have factory-installed manual  
bypass as an option.  
Units shall be factory-assembled, single packaged, DH***N  
Electric Cooling/Gas Heat, DH***C/E Electric Cooling/  
Optional Electric Heat, designed for outdoor mounted instal-  
lation. The 15 ton units shall have minimum EER ratings of  
10.8, the 17.5 ton units shall have minimum EER ratings of  
10.2, the 20 ton units shall have minimum EER ratings of 9.7  
and the 25 ton units shall have minimum EER ratings of 9.6.  
They shall have built-in field convertible duct connections  
for down discharge supply/return or horizontal discharge  
Johnson Controls Unitary Products  
41  
 
262260-YTG-E-1008  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
2. Freeze-protection thermostat, evaporator coil. If  
any of the above safety devices trip, a LED  
(light-emitting diode) indicator shall flash a  
diagnostic code that indicates which safety  
switch has tripped.  
The outdoor fans shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to cor-  
rosion resistant steel spider brackets and shall be dynami-  
cally balanced for smooth operation. The 2 outdoor fan  
motors shall be totally enclosed with permanently lubricated  
bearings, internally protected against overload conditions and  
staged independently.  
d. Unit shall incorporate "AUTO RESET" compressor  
over temperature, over current protection.  
e. Unit shall operate with conventional thermostat  
designs and have a low voltage terminal strip for  
easy hook-up.  
REFRIGERANT COMPONENTS  
Compressors:  
f. Unit control board shall have on-board diagnostics  
and fault code display.  
a. Shall be Scroll compressors internally protected with  
internal high-pressure relief and over temperature  
protection.  
g. Standard controls shall include anti-short cycle and  
low voltage protection, and permit cooling operation  
down to 0 °F.  
b. Shall have internal spring isolation and sound muf-  
fling to minimize vibration and noise, and be exter-  
nally isolated on a dedicated, independent mounting.  
h. Control board shall monitor each refrigerant safety  
switch independently.  
Coils:  
i.  
Control board shall retain last 5 fault codes in non  
volatile memory, which will not be lost in the event of  
a power loss.  
a. Evaporator and condenser coils shall have alumi-  
num plate fins mechanically bonded to seamless  
internally enhanced copper tubes with all joints  
brazed. Special Phenolic coating shall be available  
as a factory option.  
GAS HEATING SECTION (DH***N MODELS)  
Shall be designed with induced draft combustion with post  
purge logic and energy saving direct spark ignition, redun-  
dant main gas valve. Ventor wheel shall be constructed of  
stainless steel for corrosion resistance. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 25° F. Burners shall be of the in-  
shot type, constructed of aluminum coated steel and contain  
air mixture adjustments. All gas piping shall enter the unit  
cabinet at a single location through either the side or curb,  
without any field modifications. An integrated control board  
shall provide timed control of evaporator fan functioning and  
burner ignition. Heating section shall be provided with the fol-  
lowing minimum protection:  
b. Evaporator and Condenser coils shall be of the  
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
a. Balance-port thermostatic expansion valve with  
independent circuit feed system.  
b. Filter drier/strainer to eliminate any moisture or for-  
eign matter.  
c. Accessible service gage connections on both suc-  
tion and discharge lines to charge, evacuate, and  
measure refrigerant pressure during any necessary  
servicing or troubleshooting, without losing charge.  
a. Primary and auxiliary high-temperature limit switches.  
b. Induced draft motor speed sensor.  
d. The refrigeration system shall provide at least 15° F  
of sub-cooling at design conditions.  
c. Flame roll out switch (automatic reset).  
e. All models shall have two independent circuits.  
d. Flame proving controls. Unit shall have two inde-  
pendent stages of capacity.  
f. Hot gas bypass option shall be factory-installed on  
compressor #1 discharge line to provide cooling in  
low-load applications. HGBP shall be a standard  
feature on VAV models and an optional feature on  
CV models.  
ELECTRIC HEATING (DH***C/E MODELS)  
Nickel chromium electric heating elements shall be provided  
as required by the application with 1 or 2 stage control, as  
required, from 13.5 KW to 72 KW capacities. The heating  
section shall have a primary limit control(s) and automatic  
reset to prevent the heating element system from operating  
at an excessive temperature. Units with Electric Heating shall  
be wired for a single point power supply with branch circuit  
fusing (where required).  
UNIT CONTROLS  
a. Unit shall be complete with self-contained low-volt-  
age control circuit protected by a resetable circuit  
breaker on the 24-volt transformer side.  
b. Unit shall incorporate a lockout circuit which pro-  
vides reset capability at the space thermostat or  
base unit, should any of the following standard  
safety devices trip and shut off compressor.  
UNIT OPERATING CHARACTERISTICS  
Unit shall be capable of starting and running at 125° F  
outdoor temperature, exceeding maximum load criteria of  
ARI Standard 340/360. The compressor, with standard  
c. Loss-of-charge/Low-pressure switch.  
1. High-pressure switch.  
42  
Johnson Controls Unitary Products  
262260-YTG-E-1008  
controls, shall be capable of operation down to 0° F outdoor  
temperature. Unit shall be provided with fan time delay to  
prevent cold air delivery before heat exchanger warms up  
(Gas heat only).  
cooling shall modulate the economizer in order to main-  
tain a supply air temperature (SAT) programmable set-  
point. With the use of a field-installed indoor air quality  
sensor, the controller shall provide Demand Ventilation  
by modulating the economizer dampers to allow more  
ELECTRICAL REQUIREMENTS  
outside airflow upon detection of elevated indoor CO  
2
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
concentrations above a programmable set-point. With an  
additional field-installed outdoor air quality sensor, Differ-  
ential Demand Ventilation shall be provided.  
The outdoor intake opening shall be covered with a rain  
hood that matches the exterior of the unit. Water elimina-  
tor/filters shall be provided.  
STANDARD LIMITED WARRANTIES  
Compressor 5 Years  
Simultaneous economizer/compressor operation is also  
possible. Dampers shall fully close on power loss.  
Heat Exchanger 10 Years  
Electric Heat Element 5 Years  
Other Parts 1 Year  
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and  
return air dampers that are interlocked and positioned by  
a 2-position, spring-return damper actuator. The maxi-  
mum leakage rate for the outdoor air intake dampers shall  
not exceed 2% when dampers are fully closed and operat-  
ing against a pressure differential of 0.5 IWG. A unit-  
mounted potentiometer shall be provided to adjust the  
outdoor and return air damper assembly to take in the  
design CFM of outdoor air to meet the ventilation require-  
ments of the conditioned space during normal operation.  
Whenever the indoor fan motor is energized, the dampers  
open up to one of two pre-selected positions - regardless  
of the outdoor air enthalpy. Dampers return to the fully  
closed position when the indoor fan motor is de-ener-  
gized. Dampers shall fully close on power loss.  
OPTIONAL OUTDOOR AIR (Shall be made available by  
either/or):  
ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER - Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring-  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in CFM of outdoor air to  
meet the minimum ventilation requirement of the condi-  
tioned space during normal operation. During econo-  
mizer operation, a mixed-air temperature control shall  
modulate the outdoor and return air damper assembly to  
prevent the supply air temperature from dropping below  
55°F. Changeover from compressor to economizer oper-  
ation shall be provided by an integral electronic enthalpy  
control that feeds input into the basic module. The out-  
door intake opening shall be covered with a rain hood  
that matches the exterior of the unit. Water eliminator/fil-  
ters shall be provided. Simultaneous economizer/com-  
pressor operation is also possible. Dampers shall fully  
close on power loss.  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
ROOF CURB - 14" high, full perimeter curb with wood  
nailer (shipped knocked-down).  
100% BAROMETRIC RELIEF DAMPER - Contains a  
rain hood, air inlet screen, exhaust damper and mount-  
ing hardware. Used to relieve internal air pressure  
through the unit.  
PROPANE CONVERSION KIT - Contains new orifices  
and gas valve parts to convert from natural to L.P. gas.  
One per unit required.  
HIGH ALTITUDE - NATURAL GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude.  
BAS-READY ECONOMIZER - Outdoor and return air  
dampers that are interlocked and positioned by a fully-  
modulating, spring return damper actuator. The maxi-  
mum leakage rate for the outdoor air intake dampers  
shall not exceed 2% when dampers are fully closed and  
operating against a pressure differential of 0.5 IWG.  
HIGH ALTITUDE - PROPANE GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude. Must be used with propane conversion kit.  
BURGLAR BARS - Designed to work with above roof  
curbs, depending on unit model. Fits duct openings of  
curb supply and return air openings.  
For units with optional VAV or Simplicity® Intelli-Com-  
fort™ control, free-cooling shall be available while the  
outdoor dry bulb temperature (OAT) remains below a  
programmable set-point of the controller. Field-installed  
humidity sensors for either outdoor air or outdoor &  
return air streams are available to provide free-cooling  
based on single-enthalpy or dual-enthalpy configura-  
tions, respectively. If free-cooling is available, a call for  
SIDE DUCT FLANGE - Supply and return air duct  
flanges for side duct applications. Do not use on units  
with power exhaust.  
Johnson Controls Unitary Products  
43  
HIGH STATIC DRIVE - May include a belt, blower pulley,  
motor pulley or a motor change to enhance blower per-  
formance.  
DIRTY FILTER SWITCH  
PHASE MONITOR  
COIL GUARD  
WOOD SKID - Allows unit to be handled with 90" forks.  
POWERED GFI CONVENIENCE OUTLET  
NON-POWERED GFI CONVENIENCE OUTLET  
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -  
Contains all hood panels and the hardware for assem-  
bling.  
®
BAS CONTROLS - S implicity Intelli-Comfort, CPC,  
JOHNSON, HONEYWELL, NOVAR, YORK COMMER-  
CIAL COMFORT SYSTEM (YCCS)  
ANTI-RECYCLE TIMER - Assures 5-minute off time  
between compressor cycles.  
HINGED FILTER DOOR ACCESS AND TOOL FREE  
ACCESS PANELS  
COIL GUARD KIT - Guard for cooling coil.  
OTHER FACTORY INSTALLED OPTIONS  
HINGED TOOL FREE BLOWER, BLOWER MOTOR,  
FILTER AND ELECTRICAL ACCESS PANELS  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
HIGH STATIC DRIVE  
STAINLESS STEEL HEAT EXCHANGER  
STAINLESS STEEL DRAIN PAN  
2" THROW AWAY FILTERS  
4" PLEATED FILTERS  
TECHNICOAT PHENOLIC COATED CONDENSER  
AND EVAPORATOR COIL  
DISCONNECT SWITCH  
SUPPLY AIR SMOKE DETECTOR  
RETURN AIR SMOKE DETECTOR  
ELECTRONIC SINGLE ENTHALPY ECONOMIZER  
Subject to change without notice. Printed in U.S.A.  
262260-YTG-E-1008  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 262260-YTG-D-0708  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Panasonic Kx Pw32cl User Manual
Radio Shack Tad 3809 User Manual
Samsung Db98 17032ae User Manual
Samsung Um 26a1 B1 B2 User Manual
Sanyo Spw Umr164exh56 User Manual
Sanyo Uf 811 User Manual
Sears 20071234 User Manual
Sharp Mx 312nv User Manual
Toshiba Air Conditioner Rav Sm1102ut E User Manual
Xerox All In One Printer 123 User Manual