York Csa Dh 036 User Manual

254597-YTG-B-0507  
®
DESCRIPTION  
®
YORK Sunline Ultra units are convertible single package air  
conditioners with a common cabinet and a common roof curb  
for the 3, 4 and 5 ton sizes. The units were designed for light  
commercial and commercial applications. They can easily be  
installed on a roof curb, slab, roof jack or frame.  
TECHNICAL GUIDE  
All units include:  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
AND SINGLE PACKAGE  
Powder Paint finish that meets ASTM-B-117 1000 hour  
salt spray standards  
Permanently lubricated motors  
AIR CONDITIONERS  
Bottom or side air discharge configuration capability  
(field convertible)  
DH 036, 048 & 060  
3, 4 & 5 NOMINAL TONS  
Manufactured under the quality standards of ISO9001  
12.2 THROUGH 13.2 SEER  
®
S implicity Control Board  
Copper tube/aluminum fin coils  
Easy access to all components  
Rigging holes in base rails for lifting  
Fork lift slots on three sides  
Single point power connection  
Complete factory package - tested, charged and wired  
CSA agency listing on all units  
WARRANTY  
Factory Limited Parts Warranty  
One-year parts warranty  
A Five-year parts warranty on the compressor and  
electric heat elements.  
Ten-year parts warranty on the gas-fired heat  
exchangers.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
254597-YTG-B-0507  
PRODUCT NOMENCLATURE  
3-5 Ton Sunline Ultra Model Number Nomenclature  
D H 048 N04 A 2 A AA 1 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
Product Identifier  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
H = 12.0 SEER A/C  
SS Drain Pan  
CPC Controller, DFS, APS  
Johnson Controller, DFS, APS  
Nominal Cooling Capacity  
Honeywell Controller, DFS, APS  
036 = 3.0 Ton  
048 = 4.0 Ton  
060 = 5.0 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Simplicity IntelliComfort Controller w/ModLinc  
2" Pleated filters  
Heat Type and Nominal Heat Capacity  
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
C00 = Cooling Only. Suitable for Field  
Installed Electric Heat  
Product Generation  
Gas Heat Options  
1 = First Generation  
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)  
N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)  
N08 = 80 MBH Output Aluminized Steel, 1 Stage  
(036, 060, 072)  
2 = Second Generation  
Additional Options  
Hinged Filter Door & Toolless Access Cabinet  
N10 = 100 MBH Output Aluminized Steel, 1 Stage  
(048, 060, 072)  
Standard Cabinet  
D06 = 60 MBH Output Aluminized Steel, 2 Stage  
(036, 048, 060, 072)  
D10 = 100 MBH Output Aluminized Steel, 2 Stage  
(036*, 048, 060, 072)  
AA = None  
BA = Hinged Filter Door & Toolless Access Panels  
BB = Phase Monitor, Hinged Filter Door & Toolless  
Access Panels  
BC = Coil Guard, Hinged Filter Door & Toolless  
Access Panels  
BD = Dirty Filter Switch, Hinged Filter Door &  
Toolless Access Panels  
BE = Phase Monitor & Coil Guard, Hinged Filter  
Door & Toolless Access Panels  
BF = Phase Monitor & Dirty Filter Switch, Hinged  
Filter Door & Toolless Access Panels  
BG = Coil Guard & Dirty Filter Switch, Hinged Filter  
Door & Toolless Access Panels  
AB = Phase Monitor  
AC = Coil Guard  
S04 = 40 MBH Output Stainless Steel, 1 Stage (036)  
S06 = 60 MBH Output Stainless Steel, 1 Stage (048)  
S08 = 80 MBH Output Stainless Steel, 1 Stage  
(036, 060, 072)  
AD = Dirty Filter Switch  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
AS = Bottom Drain Connection  
RC = Coil Guard & American Flag  
TA = Technicoat Condenser Coil  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator and Condenser Coil  
S10 = 100 MBH Output Stainless Steel, 1 Stage  
(048, 060, 072)  
T06 = 60 MBH Output Stainless Steel, 2 Stage  
(036, 048, 060, 072)  
T10 = 100 MBH Output Stainless Steel, 2 Stage  
(036*, 048, 060, 072)  
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,  
Hinged Filter Door & Toolless Access Panels  
Electric Heat Options  
E05 = 5 KW  
E07 = 7 KW  
E10 = 10 KW  
E15 = 15 KW  
E20 = 20 KW  
E30 = 30 KW  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
Installation Options  
*(D, T) 10 = 92 MBH Output on 036 Models  
Airflow  
A = No Options Installed  
B = Option 1  
C = Option 2  
D = Options 1 & 2  
E = Option 3  
A = Direct Drive  
B = Direct Drive/Single Input Economizer  
D = Direct Drive/Motorized Damper  
N = Belt Drive  
F = Option 4  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
P = Belt Drive/Single Input Economizer  
R = Belt Drive/Motorized Damper  
Voltage  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
Unitary Products Group  
3
 
254597-YTG-B-0507  
gas valve, if applicable, and the temperature limit  
switch on gas heat units. The unit control board will  
alarm on ignition failures, compressor lockouts and  
repeated limit switch trips.  
FEATURES  
All models are available with a wide variety of factory-  
mounted options such as stainless steel heat exchangers,  
electric heaters, phase monitor, convenience outlet, dirty filter  
switch, disconnect switch, smoke detectors, and coil guard to  
make them suitable for almost every application.  
Nuisance Trip Protection- To prevent nuisance  
trouble calls, the control board uses a “three strikes,  
you’re out” philosophy. The high and low-pressure  
switches and the freezestats must trip three times  
within two hours before the unit control board will  
lock out the compressor.  
All units are self-contained and assembled on full perimeter  
base rails with forklift holes on three sides and holes for over-  
head rigging. Every unit is completely piped, wired, charged  
and tested at the factory to simplify the field installation and to  
provide years of dependable operation.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
All models (including those with an economizer) are suitable for  
either bottom or horizontal duct connections. For bottom duct,  
remove the sheet metal panels from the supply and return air  
openings through the base of the unit. For horizontal duct,  
remove the supply and return air panels on the rear of the unit.  
All models are available with these “factory mounted” outdoor  
air damper options:  
All units have long lasting powder paint cabinets with 1000  
hour salt spray test approval under ASTM-B117 procedures.  
Single enthalpy economizer  
Motorized outdoor air damper  
All models are CSA listed.  
Warranty - All models include a one-year limited parts  
warranty on the complete unit. Compressors and electric  
heater elements carry a five-year warranty. Gas heat  
exchangers carry a 10-year parts warranty.  
Supply air blowers are equipped with either direct drive or  
belt drive that can be adjusted to meet the exact require-  
ments of the job.  
All compressors are equipped with internal pressure relief.  
Every refrigerant circuit includes a liquid line filter-drier, a high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch to protect all system compo-  
nents.  
Gas Heat Operation - All single phase models with gas  
heat have minimum annual fuel utilization efficiency  
(AFUE) of 80%. All three phase models with gas heat  
have minimum steady state efficiency of 80%. Each sec-  
tion includes a durable heat exchanger with aluminized  
steel or optional stainless steel tubes, a redundant gas  
valve, spark ignition, power venting, an ignition module  
for 100% shut-off and all of the safety controls required  
to meet the latest ANSI standards.  
®
®
S implicity Controls - S implicity control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0ºF outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit  
or through a knockout in the piping panel on the front of  
the unit.  
Electric Heat Operation - All electric heat models are  
wired for a single power source and include a bank of  
nickel chromium elements mounted at the discharge of  
the supply air blower to provide a high velocity and uni-  
form distribution of air across the heating elements.  
Every element is fully protected against excessive tem-  
perature by thermal limit switches.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti short cycle delay can be temporarily  
overridden with the push of a button.  
The power supply wiring can be routed into the control  
box through a threaded pipe connection (field supplied)  
in the base pan of the unit or through a knockout in the  
wiring panel on the side of the unit.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable and are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
4
Unitary Products Group  
 
254597-YTG-B-0507  
FIGURE 1 - UNIT CUTAWAY  
BAS Controls - York’s Sunline™ series units offer factory  
mounted BAS controls such as S implicity INTELLI-Com-  
fort™, Novar, Honeywell, Johnson, and CPC.  
PHENOLIC COATED EVAPORATOR AND CON-  
DENSER COILS - Special coating process that utilizes  
®
TM  
Technicoat 10-1 processes. Coating is applied by total  
immersion of the complete coil for maximum protection.  
FACTORY-INSTALLED OPTIONS  
ELECTRIC HEATERS - Wired for single point power  
supply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
FILTER OPTIONS - Standard units are shipped with 1”  
throw-away filters installed. 2” pleated filters are offered  
as a factory installed option.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
CONVENIENCE OUTLET - This 110 volt outlet can be  
“powered” by the unit with a stepdown transformer or the  
unit may be ordered with a “non-powered” convenience  
outlet that can be wired in the field.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
DISCONNECT SWITCH - For gas heat units and cooling  
units with electric heat, a HACR breaker sized to the unit  
is provided. For cooling only units, a switch sized to the  
largest electric heat available for the particular unit is  
provided. Factory installed option only.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to a  
pre-set position whenever the supply air blower is oper-  
ating and will drive fully closed when the blower unit  
shuts down.  
BAS - Building Automation System Controls  
®
S implicity INTELLI-Comfort™ CONTROL - The York®  
®
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
S implicity INTELLI-Comfort™ control is factory installed.  
It includes a supply air sensor, a return air sensor, and an  
outside air sensor. There are provisions for a field  
Unitary Products Group  
5
   
254597-YTG-B-0507  
installed dirty filter indicator switch, an air-proving switch,  
an Outside Air Humidity sensor, a Return Air Humidity  
sensor, an Inside IAQ sensor, and an Outside Air IAQ  
sensor. Construction mode operation, 365-day real time  
clock with 7 day programming plus holiday scheduling is  
built-in. Two different modes of demand ventilation are  
SMOKE DETECTORS - (supply air & return air) The  
smoke detectors stop operation of the unit by interrupting  
power to the control board if smoke is detected within the  
air compartment.  
achieved through the INTELLI-Comfort™ using CO sen-  
2
sors. It uses an inside CO sensor to perform Demand  
2
Ventilation. It can also use an Outside CO sensor to per-  
2
Factory installed Smoke Detectors in the return air,  
may be subjected to freezing temperatures during  
“off” times due to outside air infiltration. These  
smoke detectors have an operational limit of 32°F  
to 131°F. Smoke detectors installed in areas that  
could be outside those limitations will have to be  
moved to prevent having false alarms.  
form Differential Demand Ventilation. It uses a Patented  
Comfort Ventilation algorithm to provide comfortable ven-  
tilation air temperature. The patented economizer-loading  
algorithm will protect the equipment when harsh operating  
conditions exist. Humidity in the occupied space or return  
duct can be monitored and controlled via humidity sen-  
sors and the on-board connection for hot gas re-heat sys-  
tem. It uses the INTELLI-Start™ algorithm to maximize  
energy savings by recovering the building from the Unoc-  
cupied Setpoints to the Occupied Setpoints just in time for  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
®
the Occupied Time Period to begin. The S implicity  
INTELLI-Comfort™ balances space temperature, ventila-  
STAINLESS STEEL HEAT EXCHANGER - For applica-  
tions in corrosive environments, this option provides a  
full stainless steel heat exchanger assembly.  
tion air temperature, CO and humidity for ultimate com-  
2
fort.  
®
S implicity INTELLI-Comfort™ with MOD LINK CON-  
STAINLESS STEEL DRAIN PAN - An optional rust-  
proof stainless steel drain pan is available to provide  
years of trouble-free operation in corrosive environ-  
ments.  
®
TROL - The York® S implicity INTELLI-Comfort™ with  
Mod Link control is factory installed. It includes all the  
features of the INTELLI-Comfort™ control with an addi-  
tional control to translate communications from MOD-  
BUS to the BACnet MSTP protocol.  
BOTTOM DRAIN CONNECTION - An optional bottom  
drain connection is available for inside the curb connec-  
tions for applications in cold environments to reduce  
freezing drain lines.  
Novar® BAS CONTROL - The Novar® ETC-3 building  
automation system controller is factory installed.  
Includes supply air sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
PHASE MONITORS - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of-  
phase condition.  
JOHNSON CONTROLS BAS CONTROL - The Johnson  
Control YK-UNT-1126 building automation system con-  
troller is factory installed. Includes supply air sensor,  
return air sensor, dirty filter indicator switch, and air prov-  
ing switch.  
DIRTY FILTER SWITCH - This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
CPC BAS CONTROL - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND  
ACCESS PANELS (not hinged) - This option allows for  
easy access and maintenance.  
NOTE:Knobs are shipped inside the unit to prevent ship-  
ping damage. These must be field installed for  
tool-less operation.  
HONEYWELL BAS CONTROL - The Honeywell  
W7750C building automation system controller is factory  
installed. Includes air supply sensor, return air sensor,  
dirty filter indicator switch, and air proving switch.  
6
Unitary Products Group  
254597-YTG-B-0507  
tudes up to 6,000 feet. This accessory supplements the  
basic propane conversion kit.  
FIELD-INSTALLED ACCESSORIES  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
LOW NOX KIT - Required to reduce the emission of  
nitrogen oxides below 40 nano grams per joule.  
POWER EXHAUST - Our single input economizer  
options are available with power exhaust. Whenever the  
outdoor air intake dampers are opened for free cooling,  
the exhaust fan will be energized to prevent the condi-  
tioned space from being over-pressurized during econo-  
mizer operation.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
The power exhaust option can only be used on bot-  
tom duct configurations.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to  
some pre-set position whenever the supply air blower is  
operating and will drive fully closed when the blower unit  
shuts down.  
BAROMETRIC RELIEF DAMPER - This damper acces-  
sory can be used to relieve internal building air pressure  
on units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
ELECTRIC HEATERS wired for single point power sup-  
ply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
ENTHALPY ACCESSORY CONTROL KIT - This kit  
contains the required components to convert a single  
enthalpy economizer to dual enthalpy.  
BURGLAR BARS - Mount in the supply and return  
openings to prevent entry into the duct work.  
ROOF CURBS - Eight and fourteen-inch high roof curbs  
provide a water-tight seal between the unit and the fin-  
ished roof. These full perimeter curbs meet the require-  
ments of the National Roofing Contractors Association  
(NRCA) and are shipped knocked-down for field assem-  
bly.  
FLUE EXHAUST EXTENSION KIT - In locations with  
wind or weather conditions which may interfere with  
proper exhausting of furnace combustion products, this  
kit can be installed to prevent the flue exhaust from  
entering nearby fresh air intakes.  
Roof curbs are designed to fit inside the base rails of the  
unit and include both a wood nailing strip and duct  
hanger supports.  
CO SENSOR - Senses CO levels and automatically  
overrides the economizer when levels rise above the  
present limits.  
2
2
HIGH ALTITUDE NATURAL GAS - Burner orifices and  
pilot orifices are provided for proper furnace operation at  
altitudes up to 6,000 feet.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
PROPANE - Burner orifices, pilot orifices and gas valve  
parts are provided to convert a natural gas furnace to  
propane.  
HAIL GUARD - Hail Guard kit is available to prevent unit  
from hail damage. This is a sloped hood that fits above  
the coil.  
HIGH ALTITUDE PROPANE - Burner orifices and pilot  
orifices are provided for proper furnace operation at alti-  
GAS PIPING KIT - This kit supplies all necessary fittings  
and shut off valve.  
Unitary Products Group  
7
 
254597-YTG-B-0507  
1
TABLE 1: SOUND POWER RATING  
-12  
SOUND POWER (db 10  
Watts)  
Octave Band Centerline Frequency (Hz)  
ESP  
BLOWER  
UNIT  
SIZE  
dB(A)  
@
10Ft.2  
41  
CFM  
SWL  
dB(A)  
IWG SPEED  
KW  
63  
125  
250  
500  
1,000  
2,000  
4,000  
8,000  
036  
048  
060  
1,200  
1,600  
2,000  
0.6  
LOW  
HIGH  
HIGH  
0.60  
0.80  
1.00  
84  
85  
86  
84  
85  
86  
74  
75  
76  
67  
68  
69  
69  
70  
71  
62  
63  
64  
57  
58  
59  
52  
53  
54  
74  
75  
76  
0.55  
0.45  
42  
43  
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The  
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan  
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-  
tee requiring a dBA value or sound data in any other form than sound power level ratings.  
2. At a distance of 10 feet from the blower.  
1
1
TABLE 3: GAS HEAT RATINGS  
TABLE 2: CAPACITY RATINGS - (ARI 210/240)  
EER2  
SEER3  
12.25  
13.20  
12.20  
MBH  
INPUT  
MBH  
OUTPUT  
AFUE  
(%)  
TEMP  
RISE ºF  
MODEL  
DH036  
DH048  
DH060  
MBH  
MODEL  
42.5  
46.5  
57.0  
11.1  
DH036N04  
DH036N08  
50  
100  
40  
80  
80.9  
80.5  
15 - 45  
40 - 70  
11.4  
10.6  
DH048N06  
DH048N10  
75  
125  
60  
100  
80.9  
80.3  
25 - 55  
45 - 75  
1. 80/67°F Indoor and 95°F outdoor.  
2. EER = Energy Efficiency Ratio at full load - the cooling  
capacity in Btu’s per hour (Btuh) divided by the power  
input in watts, expressed in Btuh per watt (Btuh/watt).  
3. SEER = Seasonal Energy Efficiency Ratio.  
DH060N08  
DH060N10  
100  
125  
80  
100  
80.5  
80.3  
25 - 55  
35 - 65  
1. All units are single-stage heating.  
TABLE 4: 2 STAGE GAS HEAT RATINGS  
MBH INPUT  
MBH OUTPUT  
STEADY STATE EFFICIENCY  
RISE  
MINIMUM HEATING  
AIRFLOW (CFM)  
MODEL1  
1
ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE  
2ND STAGE  
MIN. MAX.  
45  
69  
45  
75  
45  
75  
75  
115  
75  
35.8  
55.2  
35.7  
60.4  
35.8  
60.4  
60.8  
92  
79.4  
80.0  
79.4  
80.5  
79.4  
80.5  
81.1  
35  
55  
25  
45  
35  
45  
70  
90  
70  
75  
70  
75  
790  
950  
DH036D06  
DH036D10  
DH048D06  
DH048D10  
DH060D06  
DH060D10  
80.2  
60.8  
100.6  
60.8  
100.6  
81.1  
790  
125  
75  
80.5  
1230  
1010  
1230  
81.1  
125  
80.5  
1. Models are 3Ø only.  
8
Unitary Products Group  
       
254597-YTG-B-0507  
TABLE 5: DH036 COOLING CAPACITIES (3 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
EVAPORATOR  
TOTAL  
TOTAL  
COIL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
55.2  
49.1  
44.7  
42.4  
55.2  
49.1  
44.7  
42.4  
51.9  
46.1  
42.0  
39.8  
49.4  
43.9  
40.0  
37.9  
46.9  
41.7  
38.0  
36.0  
3.18  
3.13  
3.05  
3.05  
3.18  
3.13  
3.05  
3.05  
3.15  
3.10  
3.02  
3.03  
3.12  
3.07  
2.99  
3.00  
3.09  
3.04  
2.96  
2.97  
35.2 30.7 26.2 21.8 17.3  
-
-
51.5  
45.8  
41.2  
39.9  
50.0  
44.5  
40.0  
38.8  
48.6  
43.2  
38.9  
37.6  
46.4  
41.2  
37.1  
35.9  
44.2  
39.3  
35.4  
34.2  
3.44  
3.35  
3.30  
3.35  
3.41  
3.32  
3.27  
3.32  
3.38  
3.29  
3.23  
3.29  
3.36  
3.27  
3.21  
3.27  
3.34  
3.25  
3.20  
3.25  
34.1 29.7 25.2 20.7 16.2  
-
-
41.7 37.2 32.8 28.3 23.8 19.4 14.9  
44.7 43.6 39.1 34.6 30.1 25.7 21.2  
42.4 42.4 42.4 37.9 33.4 29.0 24.5  
40.2 35.7 31.3 26.8 22.3 17.8 13.4  
41.2 41.2 38.8 34.3 29.8 25.3 20.9  
39.9 39.9 39.9 35.4 31.0 26.5 22.0  
1500  
35.2 30.7 26.2 21.8 17.3  
-
-
31.5 27.5 23.6 19.6 15.6  
-
-
41.7 37.2 32.8 28.3 23.8 19.4 14.9  
44.7 43.6 39.1 34.6 30.1 25.7 21.2  
42.4 42.4 42.4 37.9 33.4 29.0 24.5  
37.2 33.2 29.2 25.3 21.3 17.3 13.3  
40.0 39.2 36.3 32.3 28.3 24.3 20.3  
38.8 38.8 37.5 33.5 29.6 25.6 21.6  
1350  
1200  
1050  
900  
30.0 26.5 23.0 19.5  
-
16.0  
-
28.9 25.4 21.9 18.4 14.9  
-
-
35.7 32.2 28.7 25.2 21.7 18.2 14.7  
41.2 37.7 34.2 30.7 27.2 23.7 20.2  
39.8 39.8 37.3 33.8 30.3 26.8 23-3  
34.2 30.7 27.2 23.7 20.2 16.7 13.2  
38.9 37.2 33.7 30.2 26.7 23.2 19.8  
37.6 37.6 35.1 31.6 28.1 24.6 21.1  
27.3 24.3 21.2 18.2  
-
15.2  
-
26.2 23.2 20.2 17.2 14.1  
-
-
32.6 29.6 26.5 23.5 20.5 17.4 14.4  
37.7 34.7 31.6 28.6 25.6 22.5 19.5  
37.9 37.0 34.5 31.4 28.4 25.4 22.3  
31.1 28.1 25.0 22.0 19.0 16.0 12.9  
36.2 34.1 31.1 28.0 25.0 22.0 18.9  
35.9 34.9 32.3 29.3 26.3 23.2 20.2  
24.6 22.1 19.5 16.9 14.4  
-
-
23.6 21.0 18.4 15.9 13.3  
-
-
29.5 26.9 24.4 21.8 19.2 16.7 14.1  
34.2 31.6 29.1 26.5 23.9 21.4 18.8  
36.0 34.2 31.7 29.1 26.5 24.0 21.4  
28.0 25.4 22.9 20.3 17.7 15.2 12.6  
33.5 30.9 28.4 25.8 23.2 20.7 18.1  
34.2 32.1 29.5 27.0 24.4 21.8 19.3  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
105°F  
115°F  
SENSIBLE CAPACITY1  
SENSIBLE CAPACITY1  
TOTAL  
TOTAL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
47.6  
42.5  
38.0  
37.4  
46.5  
41.6  
37.1  
36.5  
45.4  
40.6  
36.2  
35.7  
43.2  
38.7  
34.5  
34.0  
41.1  
36.7  
32.8  
32.3  
3.65  
3.56  
3.49  
3.54  
3.62  
3.53  
3.46  
3.52  
3.60  
3.51  
3.44  
3.49  
3.57  
3.48  
3.41  
3.47  
3.54  
3.45  
3.39  
3.44  
32.3 27.8 23.3 18.9 14.4  
-
-
43.6  
39.3  
34.8  
34.9  
42.9  
38.6  
34.2  
34.3  
42.2  
37.9  
33.6  
33.7  
40.1  
36.1  
32.0  
32.1  
38.0  
34.2  
30.3  
30.4  
3.85  
3.76  
3.67  
3.73  
3.83  
3.74  
3.66  
3.72  
3.82  
3.73  
3.64  
3.70  
3.78  
3.69  
3.61  
3.67  
3.75  
3.66  
3.58  
3.64  
30.4 26.0 21.5 17.0 12.5  
-
-
39.0 34.5 30.0 25.6 21.1 16.6 12.1  
38.0 38.0 36.6 32.1 27.6 23.1 18.7  
37.4 37.4 37.4 32.9 28.5 24.0 19.5  
37.8 33.3 28.8 24.3 19.9 15.4 10.9  
34.8 34.8 34.4 29.9 25.4 20.9 16.5  
34.9 34.9 34.9 30.5 26.0 21.5 17.0  
1500  
29.7 25.8 21.8 17.8 13.8  
-
-
28.0 24.0 20.0 16.0 12.0  
-
-
36.0 32.0 28.0 24.0 20.1 16.1 12.1  
37.1 36.6 34.1 30.1 26.1 22.2 18.2  
36.5 36.5 35.2 31.2 27.2 23.3 19.3  
34.8 30.8 26.8 22.8 18.8 14.9 10.9  
34.2 34.0 32.0 28.0 24.0 20.0 16.0  
34.3 34.3 32.9 28.9 24.9 21.0 17.0  
1350  
1200  
1050  
900  
27.2 23.7 20.2 16.7 12.2  
-
-
25.5 22.0 18.5 15.0 11.5  
-
-
33.0 29.5 26.0 22.5 19.0 15.5 12.0  
36.2 35.2 31.7 28.2 24.7 21.2 17.7  
35.7 35.7 33.0 29.5 26.0 22.5 19.0  
31.8 28.3 24.8 21.3 17.8 14.3 10.8  
33.6 33.1 29.6 26.1 22.6 19.1 15.6  
33.7 33.7 30.9 27.4 23.9 20.4 16.9  
24.6 21.6 18.5  
-
12.5  
-
-
22.9 19.9 16.9 13.8 10.8  
-
-
29.9 26.9 23.8 20.8 17.8 14.7 11.7  
33.9 32.1 29.0 26.0 23.0 19.9 16.9  
34.0 32.9 30.3 27.2 24.2 21.2 18.1  
28.7 25.7 22.6 19.6 16.6 13.5 10.5  
31.6 30.0 27.0 23.9 20.9 17.9 14.9  
32.1 30.9 28.2 25.1 22.1 19.1 16.0  
22.0 19.4 16.8 14.3 11.7  
-
-
20.4 17.8 15.2 12.7 10.1  
-
-
26.8 24.2 21.7 19.1 16.5 14.0 11.4  
31.5 28.9 26.4 23.8 21.2 18.7 16.1  
32.3 30.1 27.5 24.9 22.4 19.8 17.2  
25.6 23.0 20.4 17.9 15.3 12.7 10.2  
29.5 26.9 24.4 21.8 19.2 16.7 14.1  
30.4 28.0 25.4 22.9 20.3 17.7 15.2  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE  
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor  
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.  
NOMINAL RATING  
Unitary Products Group  
9
 
254597-YTG-B-0507  
TABLE 6: DH048 COOLING CAPACITIES (4 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
TOTAL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
59  
53  
47  
47  
58  
53  
47  
46  
57  
52  
46  
45  
54  
49  
43  
43  
51  
46  
41  
40  
3.3  
3.2  
3.2  
3.1  
3.3  
3.2  
3.2  
3.1  
3.3  
3.2  
3.2  
3.1  
3.2  
3.1  
3.1  
3.1  
3.2  
3.1  
3.1  
3.0  
46  
53  
47  
47  
42  
50  
47  
46  
39  
47  
46  
45  
35  
43  
43  
43  
32  
39  
41  
40  
40  
49  
47  
47  
37  
46  
47  
46  
34  
42  
46  
45  
31  
39  
43  
43  
29  
35  
41  
40  
34  
43  
47  
47  
32  
41  
46  
46  
30  
38  
45  
45  
27  
35  
42  
41  
25  
32  
38  
38  
28  
38  
42  
41  
27  
35  
41  
41  
25  
33  
41  
40  
23  
31  
38  
37  
22  
28  
35  
34  
23  
32  
36  
35  
22  
30  
36  
35  
21  
29  
36  
36  
19  
27  
34  
33  
18  
25  
31  
31  
-
-
55  
49  
44  
43  
54  
48  
43  
42  
53  
48  
42  
41  
51  
45  
40  
39  
48  
42  
38  
37  
3.5  
3.4  
3.4  
3.3  
3.5  
3.4  
3.4  
3.3  
3.5  
3.4  
3.4  
3.3  
3.5  
3.4  
3.4  
3.3  
3.5  
3.5  
3.4  
3.4  
43  
49  
44  
43  
40  
47  
43  
42  
37  
45  
42  
41  
34  
41  
40  
39  
30  
37  
38  
37  
37  
47  
44  
43  
35  
44  
43  
42  
33  
41  
42  
41  
30  
37  
40  
39  
27  
34  
38  
37  
32  
41  
44  
43  
30  
39  
43  
42  
28  
36  
43  
41  
26  
33  
40  
38  
23  
30  
36  
35  
26  
35  
38  
37  
25  
33  
38  
37  
23  
32  
39  
37  
22  
29  
36  
34  
20  
27  
33  
31  
20  
30  
32  
31  
20  
28  
33  
32  
19  
27  
34  
32  
17  
25  
32  
30  
16  
23  
29  
28  
-
-
26  
30  
29  
-
25  
31  
30  
-
24  
32  
31  
-
23  
30  
29  
-
21  
25  
24  
-
20  
26  
25  
-
19  
27  
27  
-
19  
26  
25  
-
24  
26  
26  
-
23  
28  
27  
-
22  
30  
28  
-
21  
28  
26  
-
2000  
-
-
-
-
1800  
1600  
1400  
1200  
21  
28  
27  
18  
24  
24  
20  
26  
24  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
105°F  
115°F  
SENSIBLE CAPACITY1  
SENSIBLE CAPACITY1  
TOTAL  
TOTAL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
50  
45  
39  
39  
50  
44  
39  
38  
49  
44  
39  
38  
47  
42  
37  
36  
44  
40  
35  
34  
3.8  
3.7  
3.6  
3.6  
3.8  
3.7  
3.6  
3.6  
3.8  
3.7  
3.6  
3.6  
3.8  
3.7  
3.6  
3.5  
3.7  
3.7  
3.6  
3.5  
41  
45  
39  
39  
38  
44  
39  
38  
35  
43  
39  
38  
32  
39  
37  
36  
29  
36  
35  
34  
35  
44  
39  
39  
33  
41  
39  
38  
31  
39  
39  
38  
28  
35  
37  
36  
25  
32  
35  
34  
30  
39  
39  
39  
28  
36  
40  
38  
26  
34  
41  
38  
24  
31  
38  
35  
22  
29  
34  
32  
24  
33  
34  
33  
23  
31  
35  
33  
21  
30  
37  
33  
20  
27  
33  
31  
18  
25  
30  
28  
18  
27  
28  
27  
18  
26  
30  
28  
17  
25  
32  
29  
16  
23  
29  
27  
15  
21  
27  
25  
-
-
45  
40  
35  
35  
45  
40  
35  
34  
45  
40  
35  
34  
43  
38  
33  
33  
41  
36  
32  
31  
4.0  
4.0  
3.8  
3.8  
4.0  
4.0  
3.9  
3.8  
4.1  
4.1  
3.9  
3.8  
4.0  
4.0  
3.8  
3.7  
3.9  
3.9  
3.8  
3.7  
39  
40  
35  
35  
36  
40  
35  
34  
33  
40  
35  
34  
30  
37  
33  
33  
27  
34  
32  
31  
33  
40  
35  
35  
31  
39  
35  
34  
29  
37  
35  
34  
26  
34  
33  
33  
24  
30  
32  
31  
28  
37  
35  
35  
26  
34  
37  
34  
24  
32  
39  
34  
22  
29  
35  
31  
20  
27  
32  
29  
22  
31  
30  
29  
21  
29  
32  
29  
20  
27  
34  
30  
18  
25  
31  
27  
17  
23  
28  
25  
16  
25  
24  
23  
16  
24  
27  
24  
15  
23  
30  
25  
14  
21  
27  
23  
13  
20  
25  
22  
-
-
22  
22  
22  
-
21  
25  
23  
-
20  
27  
24  
-
19  
25  
23  
-
16  
17  
16  
-
16  
20  
18  
-
16  
23  
19  
-
15  
21  
18  
-
20  
18  
18  
-
19  
22  
19  
-
18  
25  
20  
-
17  
23  
19  
-
2000  
-
-
-
-
1800  
1600  
1400  
1200  
18  
23  
21  
14  
20  
18  
16  
21  
18  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE  
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor  
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.  
NOMINAL RATING  
10  
Unitary Products Group  
 
254597-YTG-B-0507  
TABLE 7: DH060 COOLING CAPACITIES (5 TON)  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
85°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
95°F  
SENSIBLE CAPACITY1  
ENTERING DRY BULB, °F  
TOTAL  
TOTAL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
82  
70  
67  
66  
78  
67  
64  
63  
75  
64  
61  
60  
72  
62  
59  
58  
69  
59  
56  
55  
4.3  
4.2  
4.0  
4.0  
4.3  
4.2  
4.0  
4.0  
4.3  
4.2  
4.0  
4.0  
4.3  
4.2  
4.0  
4.0  
4.2  
4.1  
4.0  
4.0  
56  
67  
67  
66  
53  
63  
64  
63  
49  
58  
61  
60  
44  
53  
59  
58  
40  
48  
56  
55  
50  
61  
67  
66  
47  
57  
64  
63  
43  
53  
61  
60  
40  
49  
57  
57  
36  
44  
53  
54  
43  
54  
66  
66  
41  
51  
62  
63  
38  
48  
58  
59  
35  
44  
53  
55  
32  
40  
49  
50  
37  
48  
59  
59  
35  
45  
56  
57  
33  
42  
52  
54  
30  
39  
48  
50  
28  
36  
44  
46  
30  
41  
52  
52  
29  
39  
50  
51  
27  
37  
47  
49  
25  
34  
44  
45  
24  
32  
40  
42  
-
-
76  
65  
62  
61  
73  
62  
60  
58  
70  
60  
57  
56  
67  
58  
55  
54  
65  
56  
53  
52  
4.6  
4.5  
4.5  
4.4  
4.6  
4.5  
4.4  
4.4  
4.6  
4.5  
4.4  
4.4  
4.6  
4.5  
4.4  
4.4  
4.6  
4.5  
4.4  
4.4  
54  
65  
62  
61  
50  
60  
60  
58  
46  
56  
57  
56  
43  
51  
55  
54  
39  
46  
53  
52  
48  
58  
62  
61  
44  
54  
60  
58  
41  
50  
57  
56  
38  
46  
54  
54  
34  
42  
51  
51  
41  
51  
62  
61  
38  
48  
59  
58  
36  
45  
55  
56  
33  
41  
51  
51  
30  
38  
47  
47  
34  
45  
55  
54  
32  
42  
53  
52  
30  
39  
50  
50  
28  
37  
46  
47  
26  
34  
43  
43  
28  
38  
49  
47  
26  
36  
47  
46  
25  
34  
45  
45  
24  
32  
42  
42  
22  
30  
39  
39  
-
-
34  
46  
46  
-
33  
44  
45  
-
32  
42  
43  
-
30  
39  
40  
-
28  
39  
39  
-
27  
38  
39  
-
26  
36  
38  
-
25  
34  
36  
-
31  
42  
41  
-
30  
41  
40  
-
29  
39  
39  
-
27  
37  
37  
-
25  
35  
34  
-
24  
35  
34  
-
23  
34  
34  
-
22  
32  
32  
-
2500  
2250  
2000  
1750  
1500  
28  
36  
37  
23  
32  
33  
26  
35  
35  
21  
30  
30  
TEMPERATURE OF AIR ON CONDENSER COIL  
AIR ON  
EVAPORATOR  
COIL  
105°F  
115°F  
SENSIBLE CAPACITY1  
SENSIBLE CAPACITY1  
TOTAL  
TOTAL  
POWER  
POWER  
CAP.1  
MBH  
CAP.1  
MBH  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
INPUT2 kW  
INPUT2 kW  
CFM  
WB °F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
68  
60  
56  
55  
67  
58  
55  
54  
65  
57  
53  
52  
62  
54  
51  
50  
59  
52  
48  
47  
5.0  
4.8  
4.8  
4.7  
4.9  
4.8  
4.7  
4.7  
4.9  
4.8  
4.7  
4.7  
4.9  
4.8  
4.7  
4.6  
4.9  
4.7  
4.7  
4.6  
51  
60  
56  
55  
48  
57  
55  
54  
44  
54  
53  
52  
40  
49  
51  
50  
36  
44  
48  
47  
44  
55  
56  
55  
42  
52  
55  
54  
39  
48  
53  
52  
35  
44  
50  
50  
32  
40  
47  
47  
38  
49  
56  
55  
36  
46  
54  
53  
33  
43  
52  
52  
31  
40  
48  
48  
28  
36  
43  
43  
31  
42  
49  
48  
30  
40  
48  
47  
28  
38  
46  
46  
26  
35  
43  
43  
24  
32  
39  
39  
25  
35  
43  
42  
24  
34  
42  
41  
23  
32  
41  
41  
21  
30  
38  
38  
20  
28  
35  
35  
-
-
61  
55  
50  
49  
60  
54  
49  
49  
60  
54  
49  
48  
56  
51  
46  
46  
53  
48  
43  
43  
5.3  
5.1  
5.1  
5.0  
5.3  
5.1  
5.0  
5.0  
5.2  
5.1  
5.0  
5.0  
5.2  
5.0  
5.0  
4.9  
5.2  
5.0  
4.9  
4.9  
48  
55  
50  
49  
45  
53  
49  
49  
42  
52  
49  
48  
38  
47  
46  
46  
34  
43  
43  
43  
41  
53  
50  
49  
39  
50  
49  
49  
36  
47  
49  
48  
33  
42  
46  
46  
30  
38  
43  
43  
35  
46  
50  
49  
33  
44  
49  
49  
31  
41  
48  
48  
28  
38  
44  
44  
26  
34  
40  
40  
28  
39  
43  
43  
27  
38  
43  
43  
26  
36  
43  
42  
24  
33  
39  
39  
22  
30  
36  
36  
21  
33  
37  
36  
21  
32  
37  
37  
20  
30  
37  
37  
19  
28  
34  
34  
18  
26  
32  
31  
-
-
29  
36  
35  
-
28  
36  
35  
-
27  
36  
36  
-
25  
33  
33  
-
22  
29  
28  
-
22  
30  
29  
-
22  
30  
30  
-
21  
29  
29  
-
26  
30  
29  
-
26  
31  
31  
-
25  
32  
32  
-
23  
30  
29  
-
20  
23  
23  
-
20  
25  
25  
-
20  
26  
26  
-
19  
25  
25  
-
2500  
2250  
2000  
1750  
1500  
24  
31  
31  
20  
27  
27  
22  
27  
27  
18  
23  
23  
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE  
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.  
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor  
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.  
NOMINAL RATING  
Unitary Products Group  
11  
 
254597-YTG-B-0507  
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
0.40 0.50 0.60  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
TONNAGE  
0.20  
WATTS RPM  
0.30  
WATTS RPM  
0.70  
WATTS RPM  
0.80  
WATTS  
RPM  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
843  
817  
790  
-
-
-
-
-
-
860  
775  
700  
-
-
-
-
-
-
880  
854  
828  
802  
-
-
-
-
-
925  
850  
760  
670  
-
-
-
-
-
919  
893  
867  
840  
818  
-
1005  
920  
840  
745  
956  
930  
906  
881  
858  
842  
833  
-
1065  
993  
970  
944  
920  
898  
882  
867  
858  
847  
1145  
1030  
1008  
985  
961  
940  
922  
904  
893  
880  
1195  
1067  
1046  
1025  
1001  
980  
962  
942  
932  
1235  
1170  
1100  
1030  
950  
895  
820  
785  
995  
905  
815  
740  
695  
650  
-
1065  
980  
900  
820  
755  
705  
665  
640  
1125  
1040  
970  
890  
835  
765  
725  
680  
1
665  
3
-
-
-
-
-
-
-
-
-
916  
730  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
1103  
1085  
1064  
1040  
1020  
1003  
982  
WATTS  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
1270  
1210  
1145  
1075  
1005  
945  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1102  
1081  
1060  
1044  
1024  
1010  
992  
1180  
1115  
1050  
995  
920  
870  
815  
-
-
1121  
1100  
1086  
1067  
1053  
1034  
1140  
1085  
1035  
965  
-
-
-
1
3
880  
1107  
1099  
1080  
1000  
960  
970  
835  
920  
953  
780  
855  
905  
1. For 208 Volts multiply values by 0.95.  
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table  
for resistance values on applications other than gas / electric units with side duct airflows.  
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
AIR  
UNIT  
TONNAGE  
FLOW  
CFM  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
WATTS RPM  
0.80  
RPM  
WATTS RPM  
WATTS RPM  
WATTS RPM  
WATTS RPM  
WATTS RPM  
WATTS  
1235  
1170  
1100  
1030  
950  
895  
820  
785  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
843  
817  
790  
-
-
-
-
-
-
860  
775  
700  
-
-
-
-
-
-
880  
854  
828  
802  
-
-
-
-
-
925  
850  
760  
670  
-
-
-
-
-
919  
893  
867  
840  
818  
-
1005  
920  
840  
745  
956  
930  
906  
881  
858  
842  
833  
-
1065  
993  
970  
944  
920  
898  
882  
867  
858  
847  
1145  
1030  
1008  
985  
961  
940  
922  
904  
893  
880  
1195  
1125  
1040  
970  
890  
835  
1067  
1046  
1025  
1001  
980  
962  
942  
932  
995  
905  
815  
740  
695  
650  
-
1065  
980  
900  
820  
755  
705  
665  
640  
1
665  
4
-
-
-
-
-
-
765  
725  
-
-
-
680  
916  
730  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
1103  
1085  
1064  
1040  
1020  
1003  
982  
WATTS  
2000  
1900  
1800  
1700  
1600  
1500  
1400  
1300  
1200  
1270  
1210  
1145  
1075  
1005  
945  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1102  
1081  
1060  
1044  
1024  
1010  
992  
1180  
1115  
1050  
995  
920  
870  
815  
-
-
1121  
1100  
1086  
1067  
1053  
1034  
1140  
1085  
1035  
965  
-
-
-
1
4
880  
1107  
1099  
1080  
1000  
960  
970  
835  
920  
953  
780  
855  
905  
1. Models shown at 230/460 Volts with side duct connections.  
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table  
for resistance values on applications other than gas / electric units with side duct airflows.  
12  
Unitary Products Group  
   
254597-YTG-B-0507  
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
AIR  
UNIT  
FLOW  
CFM  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
WATTS RPM  
0.80  
WATTS  
TONNAGE  
RPM  
1059  
1032  
1005  
980  
930  
877  
-
WATTS RPM  
WATTS RPM  
WATTS RPM  
WATTS RPM  
WATTS RPM  
1660  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
1560  
1077  
1590  
1095  
1074  
1049  
1022  
983  
941  
894  
855  
-
1630  
1114  
1094  
1069  
1044  
1010  
976  
940  
903  
884  
864  
-
1650  
1134  
1116  
1090  
1066  
1039  
1009  
980  
1158  
1140  
1116  
1090  
1064  
1040  
1014  
988  
1685  
1181  
1167  
1142  
1117  
1092  
1070  
1047  
1022  
1001  
987  
1720  
1640  
1535  
1440  
1340  
1225  
1095  
970  
1405  
1054  
1470  
1525  
1370  
1190  
1080  
1000  
885  
815  
-
1560  
1440  
1250  
1100  
1020  
940  
860  
815  
770  
-
1595  
1475  
1350  
1160  
1050  
980  
1620  
1505  
1410  
1260  
1100  
1020  
940  
1260  
1024  
1275  
1160  
1002  
1170  
1060  
957  
1070  
1
950  
908  
975  
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
950  
905  
-
925  
850  
964  
948  
880  
835  
910  
870  
-
-
-
908  
805  
-
-
-
882  
740  
926  
780  
965  
830  
AVAILABLE EXTERNAL STATIC PRESSURE-IWG2  
1.10 1.20 1.30  
WATTS RPM WATTS RPM WATTS RPM  
AIR  
FLOW  
CFM  
UNIT  
0.90  
WATTS RPM  
1.00  
WATTS RPM  
1.40  
WATTS RPM  
1.50  
TONNAGE  
RPM  
-
WATTS  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193  
1170  
1148  
1121  
1100  
1079  
1058  
1035  
1020  
1004  
1665  
1580  
1480  
1385  
1285  
1180  
1060  
960  
-
-
-
1202  
1180  
1155  
1133  
1110  
1090  
1071  
1056  
1038  
1620  
1530  
1425  
1340  
1240  
1135  
1030  
965  
-
-
-
-
1190  
1169  
1143  
1122  
1103  
1088  
1070  
1475  
1385  
1280  
1190  
1100  
1035  
925  
-
-
-
-
1
1205  
1178  
1158  
1134  
1118  
1101  
1445  
1330  
1240  
1140  
1065  
980  
-
-
-
-
-
-
-
5
1222  
1196  
1164  
1145  
1130  
1375  
1295  
1175  
1105  
1045  
-
-
-
-
1197  
1170  
1158  
1205  
1130  
1075  
-
-
900  
1198  
1184  
1150  
1110  
860  
880  
1. Models shown at 230/460 Volts with side duct connections.  
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table  
for resistance values on applications other than gas / electric units with side duct airflows.  
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (3-5 TON) SIDE DUCT APPLICATION  
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
UNIT  
MOTOR  
TONNAGE SPEED  
HI  
1535 320 1493 335 1452 349 1416 363 1377 376 1340 390 1299 403 1260 417 1219 430  
MED/HI 1444 263 1398 276 1355 290 1315 303 1271 316 1227 329  
1179  
343  
1125  
358 1053 374  
2
2
2
MED  
1300 208 1254 221  
1211  
1102  
908  
234  
195 1050 207  
145 838 158  
1166  
246  
1119  
996  
-
258 1070 272 1006 288  
939  
303  
897  
313  
3
4
5
MED/LOW 1197  
171  
1049 130  
1149  
968  
183  
134  
220  
-
930  
-
235  
-
869  
-
248  
-
-
-
-
-
-
-
-
-
LOW  
HI  
2056 636 2017 696 1978 714 1942 734 1906 749 1864 764 1815 769 1728 743 1582 685  
MED/HI 1866 539 1832 557 1795 571 1754 585 1722 602 1679 619 1636 638 1582 653 1508 639  
MED 1680 408 1641 426 1594 438 1558 455 1517 472 1469 490 1415 505 1370 521 1337 536  
MED/LOW 1582 362 1541 380 1495 391 1465 406 1426 423 1377 440 1326 455 1292 469 1247 485  
LOW  
HI  
1300 223 1258 237 1202 247  
2256 883 2258 931 2247 950 2223 964 2182 979 2125 971 2044 940 1958 898 1864 854  
2119 808 2089 826 2051 844 2014 859 1965 861 1896 843 1801 806  
2020 637 1999 656 1985 675 1947 696 1910 715 1876 730 1832 740 1793 756 1725 748  
-
-
-
-
-
-
-
-
-
-
-
-
MED/HI 2145 771 2127 784  
MED  
MED/LOW 1757 413 1713 432 1677 451 1639 468 1597 479 1559 497 1521 513 1472 523  
LOW 1570 327 1536 339 1499 356  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.  
2. Side Duct application (230 Volts)  
Unitary Products Group  
13  
   
254597-YTG-B-0507  
TABLE 12: BELT DRIVE BLOWER MOTOR AND DRIVE DATA  
BELT  
(NOTCHED)  
1
ADJUSTABLE MOTOR PULLEY  
FIXED BLOWER PULLEY  
OUTSIDE PITCH  
MOTOR  
BLOWER  
RANGE  
(RPM)  
MODEL  
SIZE  
OUTSIDE  
DIA.  
PITCH  
DIA.  
PITCH  
LENGTH QTY.  
(IN.)  
DESIG-  
NATION  
BORE DESIG-  
(IN.)  
BORE DESIG-  
HP FRAME  
DIA.  
(IN.)  
DIA.  
(IN.)  
NATION  
(IN.)  
NATION  
(IN.)  
(IN.)  
3 TON  
4 TON  
5 TON  
790/1120 1 1/2  
790/1120 1 1/2  
850/1220 1 1/2  
56  
56  
56  
1VL40  
1VL40  
1VL40  
2.7-3.7  
2.7-3.7  
2.7-3.7  
2.4-3.4  
2.4-3.4  
2.4-3.4  
5/8  
5/8  
5/8  
AK61  
AK61  
AK56  
5.9  
5.9  
5.4  
5.7  
5.7  
5.2  
1
1
1
A36  
A36  
A36  
37.3  
37.3  
37.3  
1
1
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located  
in the moving air, upstream of any heating device.  
TABLE 13: STATIC RESISTANCES  
RESISTANCE, IWG  
DESCRIPTION  
CFM  
1000  
0.07  
0.04  
0.06  
0.06  
0.08  
1200  
0.08  
0.05  
0.07  
0.07  
0.10  
1400  
0.09  
0.06  
0.08  
0.08  
0.12  
1600  
0.11  
0.07  
0.09  
0.09  
0.14  
1800  
0.13  
0.08  
0.11  
0.10  
0.16  
2000  
0.15  
0.10  
0.13  
0.11  
0.18  
2200  
0.17  
0.12  
0.15  
0.12  
0.20  
2400  
0.20  
0.14  
0.17  
0.14  
0.23  
2600  
0.23  
0.16  
0.20  
0.16  
0.26  
2800  
0.26  
0.19  
0.23  
0.19  
0.29  
3000  
ECONOMIZER1 3  
0.30  
0.22  
0.26  
0.22  
0.32  
ELECTRIC  
7-15KW  
20-30KW  
HEATERS1  
BOTTOM DUCT CONNECTIONS1  
COOLING ONLY2  
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.  
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.  
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air  
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 14: ELECTRIC HEATER CFM LIMITATIONS  
MINIMUM SUPPLY AIR CFM  
UNITMODELSIZE NOMINAL  
VOLTAGE  
HEATER SIZE NOMINAL KW  
TONS  
5
7
10  
15  
20  
30  
208/230-3-60  
460-3-60  
1100  
1100  
1100  
-
1200  
1200  
1200  
1300  
1300  
1300  
1600  
1600  
1600  
1200  
1200  
1200  
1300  
1300  
1300  
1600  
1600  
1600  
1300  
1300  
1300  
1300  
1300  
1400  
1600  
1600  
1600  
-
3
-
-
575-3-60  
-
-
208/230-3-60  
460-3-60  
1300  
1300  
1300  
-
-
4
5
-
-
575-3-60  
-
-
208/230-3-60  
460-3-60  
1600  
1600  
1600  
-
1600  
1600  
1800  
-
-
575-3-60  
14  
Unitary Products Group  
     
254597-YTG-B-0507  
TABLE 15: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
35  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
26.7  
26.7  
29.4  
37.8  
51.3  
65.2  
26.7  
26.7  
32.6  
41.9  
57.8  
73.7  
29.3  
29.3  
32.7  
41.0  
54.5  
68.4  
29.3  
29.3  
35.8  
45.1  
61.1  
77.0  
32.9  
32.9  
32.9  
41.0  
54.5  
68.4  
90.3  
32.9  
32.9  
35.8  
45.1  
61.1  
77.0  
102.3  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
--  
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
35  
35  
40  
60  
70  
35  
35  
35  
45  
60  
80  
40  
40  
40  
45  
60  
70  
40  
40  
40  
50  
70  
80  
45  
45  
45  
45  
60  
70  
100  
45  
45  
45  
208-3-60  
13.1  
13.1  
13.1  
13.1  
110.0  
110.0  
110.0  
110.0  
2.3  
2.3  
2.3  
2.3  
8.0  
8.0  
0.0  
0.0  
0.0  
0.0  
DH036  
2
2
230-3-60  
208-3-60  
230-3-60  
2
2
10.6  
10.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
DH048  
2
2
2
2
208-3-60  
230-3-60  
16.0  
16.0  
137.0  
137.0  
2.3  
2.3  
10.6  
10.6  
0.0  
0.0  
8.0  
11.9  
15.9  
22.2  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
DH060  
2
2
50  
70  
80  
110  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
Unitary Products Group  
15  
 
254597-YTG-B-0507  
TABLE 16: ELECTRICAL DATA - DH036-060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
23.9  
23.9  
25.9  
34.3  
47.8  
61.7  
23.9  
23.9  
29.1  
38.4  
54.3  
70.2  
12.3  
13.5  
18.4  
23.7  
32.6  
23.9  
23.9  
25.9  
34.3  
47.8  
61.7  
23.9  
23.9  
29.1  
38.4  
54.3  
70.2  
12.3  
13.5  
18.4  
23.7  
32.6  
9.4  
SIZE  
(AMPS)  
30  
30  
35  
35  
50  
70  
30  
30  
35  
40  
60  
80  
15  
15  
20  
25  
35  
30  
30  
35  
35  
50  
70  
30  
30  
35  
40  
60  
80  
15  
15  
20  
25  
35  
15  
20  
25  
30  
35  
35  
35  
40  
50  
70  
90  
35  
35  
40  
40  
60  
80  
100  
20  
20  
20  
25  
35  
50  
15  
20  
25  
30  
40  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
None  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
--  
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
208-3-60  
13.1  
110.0  
2.3  
5.2  
0.0  
2
DH036  
(3.0)  
2
230-3-60  
460-3-60  
208-3-60  
13.1  
6.7  
110.0  
54.0  
2.3  
1.3  
2.3  
5.2  
2.6  
5.2  
0.0  
0.0  
0.0  
2
6.8  
8.2  
2
2
2
10.1  
13.6  
19.5  
--  
4.0  
5.6  
12.1  
16.4  
23.5  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
2
2
13.1  
110.0  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
2
2
230-3-60  
13.1  
110.0  
2.3  
5.2  
0.0  
DH048  
(4.0)  
2
6.8  
8.2  
2
2
2
460-3-60  
575-3-60  
6.7  
5.1  
54.0  
44.0  
1.3  
1.3  
2.6  
2.0  
0.0  
0.0  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
--  
5.3  
7.5  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
15.2  
21.6  
28.0  
27.5  
27.5  
27.5  
34.3  
47.8  
61.7  
83.5  
27.5  
27.5  
29.1  
38.4  
54.3  
70.2  
95.5  
14.3  
14.3  
18.4  
23.7  
32.6  
46.6  
11.0  
15.2  
21.6  
28.0  
39.1  
2
2CE04510525  
2CE04510725  
2
208-3-60  
230-3-60  
16.0  
16.0  
137.0  
137.0  
2.3  
2.3  
5.2  
5.2  
0.0  
0.0  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2
2CE04510525  
2CE04510725  
2
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
2CE04513046  
None  
10.6  
15.9  
21.2  
29.6  
--  
DH060  
(5.0)  
2
6.8  
8.2  
2
2
2
2
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
8.3  
6.4  
69.0  
58.0  
1.3  
1.3  
2.6  
2.0  
0.0  
0.0  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
16  
Unitary Products Group  
 
254597-YTG-B-0507  
TABLE 17: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
45  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
36.7  
36.7  
41.9  
50.3  
63.8  
77.7  
36.7  
38.4  
45.1  
54.4  
70.3  
86.2  
39.3  
39.6  
45.2  
53.5  
67.0  
80.9  
39.3  
41.7  
48.3  
57.6  
73.6  
89.5  
42.9  
42.9  
45.2  
53.5  
67.0  
80.9  
102.8  
42.9  
42.9  
48.3  
57.6  
73.6  
89.5  
114.8  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
--  
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
45  
45  
60  
70  
80  
45  
45  
50  
60  
80  
90  
50  
50  
50  
60  
70  
90  
50  
50  
50  
60  
80  
90  
50  
50  
50  
60  
70  
90  
110  
50  
50  
50  
208-3-60  
13.1  
13.1  
13.1  
13.1  
110.0  
110.0  
110.0  
110.0  
2.3  
2.3  
2.3  
2.3  
8.0  
8.0  
10.0  
10.0  
10.0  
10.0  
DH036  
2
2
230-3-60  
208-3-60  
230-3-60  
2
2
10.6  
10.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
DH048  
2
2
2
2
208-3-60  
230-3-60  
16.0  
16.0  
137.0  
137.0  
2.3  
2.3  
10.6  
10.6  
10.0  
10.0  
8.0  
11.9  
15.9  
22.2  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
DH060  
2
2
60  
80  
90  
125  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
Unitary Products Group  
17  
 
254597-YTG-B-0507  
TABLE 18: ELECTRICAL DATA - DH036-060 BELT DRIVE W/POWERED CONVENIENCE OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
33.9  
33.9  
38.4  
46.8  
60.3  
74.2  
33.9  
34.9  
41.6  
50.9  
66.8  
82.7  
17.3  
19.7  
24.7  
29.9  
38.8  
33.9  
33.9  
38.4  
46.8  
60.3  
74.2  
33.9  
34.9  
41.6  
50.9  
66.8  
82.7  
17.3  
19.7  
24.7  
29.9  
38.8  
13.4  
20.2  
26.6  
33.0  
37.5  
37.5  
38.4  
46.8  
60.3  
74.2  
96.0  
37.5  
37.5  
41.6  
50.9  
66.8  
82.7  
108.0  
19.3  
19.7  
24.7  
29.9  
38.8  
52.8  
15.0  
20.2  
26.6  
33.0  
44.1  
SIZE  
(AMPS)  
45  
45  
45  
50  
70  
80  
45  
45  
45  
60  
70  
90  
20  
20  
25  
30  
40  
45  
45  
45  
50  
70  
80  
45  
45  
45  
60  
70  
90  
20  
20  
25  
30  
40  
15  
25  
30  
35  
50  
50  
50  
50  
70  
80  
100  
50  
50  
50  
60  
70  
90  
110  
25  
25  
25  
30  
40  
60  
20  
25  
30  
35  
45  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
None  
2CE04511058  
2CE04511558  
2CE04512058  
None  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
--  
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
208-3-60  
13.1  
110.0  
2.3  
5.2  
10.0  
2
DH036  
(3.0)  
2
230-3-60  
460-3-60  
208-3-60  
13.1  
6.7  
110.0  
54.0  
2.3  
1.3  
2.3  
5.2  
2.6  
5.2  
10.0  
5.0  
2
6.8  
8.2  
2
2
2
10.1  
13.6  
19.5  
--  
4.0  
5.6  
12.1  
16.4  
23.5  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
--  
2
2
13.1  
110.0  
10.0  
8.0  
11.9  
15.9  
--  
5.3  
7.5  
10.6  
15.9  
21.2  
--  
2
2
230-3-60  
13.1  
110.0  
2.3  
5.2  
10.0  
DH048  
(4.0)  
2
6.8  
8.2  
2
2
2
460-3-60  
575-3-60  
6.7  
5.1  
54.0  
44.0  
1.3  
1.3  
2.6  
2.0  
5.0  
4.0  
10.1  
13.6  
19.5  
--  
10.6  
15.9  
21.2  
--  
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
--  
5.3  
7.5  
12.1  
16.4  
23.5  
--  
10.2  
15.3  
20.4  
--  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
--  
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
--  
2
2CE04510525  
2CE04510725  
2
208-3-60  
230-3-60  
16.0  
16.0  
137.0  
137.0  
2.3  
2.3  
5.2  
5.2  
10.0  
10.0  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2
2CE04510525  
2CE04510725  
2
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
2CE04513046  
None  
10.6  
15.9  
21.2  
29.6  
--  
DH060  
(5.0)  
2
6.8  
8.2  
2
2
2
2
10.1  
13.6  
19.5  
28.8  
--  
10.6  
15.9  
21.2  
30.4  
12.1  
16.4  
23.5  
34.6  
--  
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
8.3  
6.4  
69.0  
58.0  
1.3  
1.3  
2.6  
2.0  
5.0  
4.0  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
18  
Unitary Products Group  
 
254597-YTG-B-0507  
TABLE 19: PHYSICAL DATA  
DH  
048  
12 X 10  
1
MODELS  
Centrifugal Blower (Dia. x Wd. in.)  
036  
12 X 10  
3/4  
060  
12 X 10  
1
EVAPORATOR  
BLOWER  
Fan Motor HP (Direct Drive)  
Fan Motor HP (Belt Drive)  
Rows Deep  
1 1/2  
4
1 1/2  
4
1 1/2  
4
EVAPORATOR  
COIL  
Fins Per Inch  
13  
13  
13  
Face Area (Sq. Ft.)  
Propeller Dia. (in.)  
Fan Motor Hp  
4.3  
5.1  
5.1  
24  
24  
24  
CONDENSER  
FANS  
1/2  
1/2  
1/2  
Nom. CFM  
4500  
2
4200  
2
4200  
2
Rows Deep  
CONDENSER  
COILS  
Fins Per Inch  
18  
18  
18  
Face Area (Sq. Ft.)  
17.1  
17.1  
17.1  
COMPRESSOR  
(Qty. Per Unit)  
Recip. Type  
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)  
Quantity Per Unit (14” X 25” X 1” or 2“)  
Total Face Area (sq. ft.)  
2
1
2
1
2
1
AIR  
FILTERS  
6.3  
6.3  
6.3  
Refrigerant 22  
(lbs./oz.)  
CHARGE  
10/8  
10/4  
10/14  
1
TABLE 20: ELECTRIC HEAT CORRECTION FACTORS  
kW CAP.  
TABLE 21: VOLTAGE LIMITATIONS  
VOLTAGE  
NOMINAL VOLTAGE  
VOLTAGE  
POWER SUPPLY  
MULTIPLIER  
MIN.  
MAX.  
208  
230  
460  
575  
0.75  
0.92  
0.92  
0.92  
208  
240  
480  
600  
208/230-3-60  
187  
253  
460-3-60  
575-3-60  
414  
540  
506  
630  
1. Utilization Range “A” in accordance with ARI Standard  
110.  
Unitary Products Group  
19  
     
254597-YTG-B-0507  
TYPICAL POWER WIRING  
TYPICAL CONTROL WIRING  
COOLING ONLY (24 VOLT THERMOSTAT)  
COOLING / HEATING (24 VOLT THERMOSTAT)  
THERMOSTAT1 UNIT TERMINAL  
THERMOSTAT1  
TERMINALS  
TERMINALS  
STRIP TB1  
UNIT TERMINAL  
RV  
R
RH  
STRIP TB1  
ADD  
JUMPER  
24 VOLT  
YC  
GF  
Y1  
Y2  
G
RC  
Y
R
Y1  
Y2  
W1  
W2  
G
TRANSFORMER  
24 VOLT  
TRANSFORMER  
W
G
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER  
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.  
C
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
MULTI STAGE  
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND  
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF  
HEAT, USE THERMOSTAT 2TH0471024.  
1
THERMOSTAT  
TERMINALS  
UNIT TERMINAL  
STRIP TB1  
RC  
RH  
Y1  
24 VOLT  
TRANSFORMER  
ADD  
JUMPER  
R
Y1  
Y2  
W1  
W2  
G
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
SINGLE STAGE  
2
3
Y2  
W1  
THERMOSTAT1  
4
W2  
UNIT TERMINAL  
STRIP TB1  
TERMINALS  
G
B
RH  
RC  
Y
C
R
Y1  
W1  
G
LED 1  
X
ADD  
JUMPER  
NOT  
USED  
LED 2  
COM  
A1  
OCC  
W
4
G
ADD  
JUMPER  
C
A2  
24 VOLT  
TRANSFORMER  
T
TO REMOTE SENSOR  
2TH040702224 IF USED  
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).  
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.  
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).  
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT  
2TH04700224.  
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE  
ELECTRIC HEATER OR 2 STAGE GAS HEAT.  
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR  
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY  
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE  
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.  
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING  
20  
Unitary Products Group  
 
254597-YTG-B-0507  
FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW  
FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW  
Unitary Products Group  
21  
   
254597-YTG-B-0507  
DETAIL “A”  
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD  
DETAIL “B”  
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD  
22  
Unitary Products Group  
   
254597-YTG-B-0507  
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)  
TABLE 23: MINIMUM CLEARANCES  
LOCATION  
CLEARANCE  
24” (Cooling/Electric Heat)  
32” (Gas Heat)  
Front  
Rear  
12” (Less Economizer)  
36” (With Economizer or Fixed  
Air/Motorized Damper)  
FILTER  
ACCESS  
BLOWER MOTOR  
ACCESS  
24” (Less Economizer)  
36” (With Economizer)  
Left Side (Filter Access)  
DOT PLUGS  
Right Side (Cond. Coil)  
Below Unit1  
24”  
0”  
FIELD-SUPPLIED  
DISCONNECT SWITCH  
LOCATION  
72” (For  
Condenser Air Discharge)  
Above Unit2  
MOUNTING BRACKET  
FOR DICONNECT SWITCH  
(Shipped attached to the  
blower housing inside  
A,B  
the blower compartment)  
1. Units may be installed on combustible floors made  
from wood or class A, B, or C roof covering material.  
2. Units must be installed outdoors. Overhanging struc-  
tures or shrubs should not obstruct condenser air dis-  
charge outlet.  
WIRING ENTRY  
(See Detail “B”)  
CONTROL BOX  
ACCESS  
DISCONNECT SWITCH LOCATION  
AND MOTOR ACCESS PANEL FOR  
UNIT WITH “BELT-DRIVE” OPTION  
FIGURE 8 - DISCONNECT/BLOWER ACCESS  
LOCATION  
TABLE 22: UTILITIES ENTRY  
HOLE  
OPENING SIZE (DIA.)  
USED FOR  
Side  
Bottom  
Side  
1
2
A
7/8” KO  
Control Wiring  
B
Power Wiring  
2” KO  
Bottom  
C
D
1-5/8” KO  
1-1/2” KO  
Gas Piping (Front)  
Gas Piping (Bottom)  
1. Opening in the bottom to the unit can be located by the  
side in the insulation.  
2. Do not remove the 2” knockout ring.  
Unitary Products Group  
23  
         
254597-YTG-B-0507  
FIGURE 9 - TYPICAL APPLICATIONS  
24  
Unitary Products Group  
 
254597-YTG-B-0507  
BACK OF UNIT  
BACK OF UNIT  
A
A
7
7
44 /8  
44 /8  
1
1
82 /4  
82 /4  
B
F
D
X
X
C
B
E
APPROXIMATE  
APPROXIMATE  
CENTER OF GRAVITY  
CENTER OF GRAVITY  
CONDENSER COIL  
END OF UNIT  
CONDENSER COIL  
END OF UNIT  
C
D
FRONT OF UNIT  
FRONT OF UNIT  
Y
Y
FIGURE 10 - FOUR AND SIX POINT LOADING  
TABLE 24: DH 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION  
4-Point Loading (lb)  
6-Point Loading (lb)  
UNIT  
TOTAL  
A
B
C
D
A
B
83  
C
82  
D
E
F
125  
134  
137  
139  
141  
135  
147  
151  
143  
154  
157  
159  
123  
132  
134  
136  
138  
133  
144  
148  
141  
152  
154  
156  
157  
168  
171  
173  
176  
169  
183  
189  
179  
193  
196  
198  
160  
171  
174  
177  
179  
172  
186  
192  
182  
196  
199  
202  
84  
90  
104  
112  
113  
115  
117  
112  
122  
125  
119  
128  
130  
132  
105  
113  
115  
117  
119  
114  
123  
127  
120  
130  
132  
133  
107  
114  
116  
118  
120  
115  
125  
128  
122  
131  
133  
135  
DH036 Cooling/ Electric  
DH036N04  
565  
605  
615  
625  
635  
610  
660  
680  
645  
695  
705  
715  
89  
88  
91  
90  
89  
DH036D06  
93  
92  
91  
DH036N08  
94  
93  
92  
DH036D10  
91  
89  
88  
DH048 Cooling/ Electric  
DH048(D,N)06  
DH048(D,N)10  
DH060 Cooling/ Electric  
DH060D06  
98  
97  
96  
101  
96  
100  
95  
99  
93  
103  
105  
106  
102  
103  
105  
101  
102  
104  
DH060N08  
DH060(D,N)10  
TABLE 25: CENTER OF GRAVITY  
DIMENSION  
3 - 5 TON  
40-¾”  
X
Y
19-¾”  
Unitary Products Group  
25  
     
254597-YTG-B-0507  
TABLE 26: OPERATING WEIGHTS (LBS.)  
MODEL SIZE  
DH (Cooling Only)  
3 TON  
565  
605  
-
4 TON  
5 TON  
645  
-
610  
-
N04  
N06  
N08  
N10  
D06  
D10  
660  
-
-
BASIC  
UNIT  
625  
-
705  
715  
695  
715  
DH  
(Gas/Electric)  
680  
660  
680  
615  
635  
Economizer  
Motorized Damper  
50  
26  
18  
23  
28  
92  
10  
5
OPTIONS  
ACCY.  
5 - 7 kW  
10 - 15 kW  
20 - 30 kW  
Electric Heater  
Roof Curb  
Barometric Relief / Fixed Air Damper  
Belt-Drive Blower  
FIGURE 11 - ROOF CURB DIMENSIONS  
26  
Unitary Products Group  
   
254597-YTG-B-0507  
UNIT CABINET  
GUIDE SPECIFICATIONS  
Unit cabinet shall be constructed of G90 galvanized steel,  
with exterior surfaces coated with a non-chalking, powdered  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility.  
paint finish, certified at 1000 hours salt spray test per  
ASTMB117 standards. Indoor blower section shall be insu-  
lated with a minimum 1/2” thick insulation, coated on the air-  
side. Aluminum foil faced insulation shall be used in the  
furnace compartment and be fastened with ridged fasteners  
to prevent insulation from entering the air stream. Cabinet  
panels shall be “large” size, easily removable for servicing  
and maintenance. Full perimeter base rails shall be provided  
to assure reliable transit of equipment, overhead rigging and  
proper sealing on roof curb applications. Disposable 1" filters  
shall be furnished and be accessible through a removable  
access door, sealed airtight. Units filter track shall be  
designed to accommodate either 1" or 2" filters. Fan perfor-  
mance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evaporator  
fan performance without removing panels or creating air by-  
pass of the coils. Condensate pan shall be internally sloped  
and conform to ASHRAE 62-89 self-draining standards. Con-  
densate connection shall be a minimum of 3/4” I.D. female  
and be a ridged mount connection.  
®
York's Sunline Ultra units are convertible single package  
units. Although the units are primarily designed for curb  
mounting on a roof, they can also be slab-mounted at ground  
level or set on steel beams above a finished roof. Cooling  
only, cooling with gas heat and cooling with electric heat  
models are available with a wide variety of factory-mounted  
options and field-installed accessories to make them suitable  
for almost every application. All units are self-contained and  
assembled on full perimeter base rails with holes in the four  
corners for overhead rigging. Every unit is completely piped,  
wired, charged and tested at the factory to simplify the field  
installation and to provide years of dependable operation. All  
models (including those with an economizer) are suitable for  
either bottom or horizontal duct connections. Models with  
power exhaust are suitable for bottom duct connections only.  
For bottom duct, remove the sheet metal panels from the  
supply and return air openings through the base of the unit.  
For horizontal duct, remove the supply and return air panels  
on the rear of the unit.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
The indoor fan shall be a factory installed with either direct  
drive or belt drive assembly that includes an adjustable pitch  
motor pulley. Job site selected brake horsepower (B.H.P.)  
shall not exceed the motors nameplate horsepower rating,  
plus the service factor. Units shall be designed not to operate  
above service factor. Fan wheel shall be double-inlet type  
with forward-curved blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant air volume. Bearings shall be sealed  
and permanently lubricated for longer life and no mainte-  
nance.  
All non-Scroll compressors include crankcase heaters and all  
compressors have internal pressure relief. Every refrigerant  
circuit includes a liquid line filter-drier, a discharge line high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch.The unit control circuit  
includes a 75 VA transformer, a 24-volt circuit breaker and a  
relay board with a compressor lockout circuit, a terminal strip  
for thermostat wiring, plus an additional set of pin connectors  
to simplify the interface of additional field controls. All units  
have long lasting powder paint cabinets with 1000 hour salt  
spray test approval under ASTMB117 procedures. All models  
are CSA listed. All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater ele-  
ments carry a 5-year warranty. Aluminized steel and Stainless  
steel tubular heat exchangers carry a 10-year warranty.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to a  
corrosion resistant steel spider bracket and shall be dynami-  
cally balanced for smooth operation. The outdoor fan motor  
shall be totally enclosed with permanently lubricated bear-  
ings, internally protected against overload conditions and  
staged independently.  
DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat  
and designed for outdoor mounted installation.  
The 3 ton, 4 ton and 5 ton units shall have minimum SEER  
ratings of 12.2, 13.2 and 12.2 respectively. They shall have  
built-in field convertible duct connections for down discharge  
supply/return or horizontal discharge supply/return, and be  
available with factory installed options or field installed acces-  
sories. The units shall be factory wired, piped, charged with  
R-22 refrigerant and factory tested prior to shipment. All unit  
wiring shall be both numbered and color coded. All units the  
cooling performance shall be rated in accordance with DOE  
and ARI test procedures. Units shall be CSA listed, classified  
to ANSI Z21.47, UL 1995/CSA No. 236 standards.  
REFRIGERANT COMPONENTS  
Compressor:  
a. Shall be internally protected with internal high-pres-  
sure relief and over temperature protection.  
b. Shall have internal spring isolation and sound muf-  
fling to minimize vibration and noise, and be exter-  
nally isolated on a dedicated, independent  
mounting.  
Unitary Products Group  
27  
 
254597-YTG-B-0507  
Coils:  
a. Evaporator and condenser coils shall have alumi-  
GAS HEATING SECTION (SINGLE OR 2 STAGE)  
Shall be designed with induced draft combustion with post  
purge logic, energy saving direct spark ignition, and redun-  
dant main gas valve. Venter wheel shall be constructed of  
stainless steel for corrosion resistance. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 25°F. Burners shall be of the  
inshot type, constructed of aluminum coated steel and con-  
tain air mixture adjustments. All gas piping shall enter the unit  
cabinet at a single location through either the side or curb  
without any field modifications. Integrated control boards  
shall provide timed control of evaporator fan functioning and  
burner ignition. Heating section shall be provided with the fol-  
lowing minimum protection:  
num plate fins mechanically bonded to seamless  
internally enhanced copper tubes with all joints  
brazed. Special Phenolic coating shall be available  
as a factory option.  
b. Evaporator and Condenser coils shall be of the  
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
a. Thermal expansion devices (TXV’s).  
b. Filter drier/strainer to eliminate any moisture or for-  
eign matter.  
a. Primary and auxiliary high-temperature limit  
switches.  
c. Accessible service gage connections on both suc-  
tion and liquid lines to charge, evacuate, and mea-  
sure refrigerant pressure during any necessary  
servicing or troubleshooting, without losing charge.  
b. Induced draft motor speed sensor.  
c. Flame roll out switch.  
d. The refrigeration system shall provide at least 15°F  
of sub-cooling at design conditions.  
d. Flame proving controls.  
e. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
UNIT CONTROLS  
a. Unit shall be complete with self-contained low-volt-  
age control circuit protected by a resetable circuit  
breaker on the 24-volt transformer side.  
ELECTRIC HEATING SECTION  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 5 thru 30 KW, offering two  
stages of capacity - 16 KW and above on 208/230 volt heaters  
and 20 KW and above on 460 and 575 volt heaters. The heat-  
ing section shall have a primary limit control(s) and automatic  
reset to prevent the heating element system from operating at  
an excessive temperature. The heating section assembly  
shall slide out of the unit for easy maintenance and service.  
Units with Electric Heating shall be wired for a single point  
power supply with branch circuit fusing (where required).  
b. Unit shall incorporate a lockout circuit which pro-  
vides reset capability at the space thermostat or  
base unit, should any of the following standard  
safety devices trip and shut off compressor.  
c. Loss-of-charge/Low-pressure switch.  
d. High-pressure switch.  
e. Freeze-protection thermostat, evaporator coil.  
f. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
UNIT OPERATING CHARACTERISTICS  
a. Unit shall be capable of starting and running at 125°F  
outdoor temperature, exceeding maximum load crite-  
ria of ARI Standard 210/240. The compressor, with  
standard controls, shall be capable of operation  
down to 0°F outdoor temperature. Unit shall be pro-  
vided with fan time delay to prevent cold air delivery  
before heat exchanger warms up (Gas heat only).  
g. Unit shall incorporate “AUTO RESET” compressor  
over temperature, over current protection.  
h. Unit shall operate with conventional thermostat  
designs and have a low voltage terminal strip for  
easy hook-up.  
i.  
Unit control board shall have on-board diagnostics  
and fault code display.  
ELECTRICAL REQUIREMENTS  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
j.  
Standard controls shall include anti-short cycle and  
low voltage protection, and permit cooling operation  
down to 0°F.  
k. Control board shall monitor each refrigerant safety  
switch independently.  
l.  
Control board shall retain last 5 fault codes in non  
volatile memory which will not be lost in the event of  
a power loss.  
28  
Unitary Products Group  
254597-YTG-B-0507  
STANDARD LIMITED WARRANTIES  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
Compressor 5 Years  
ROOF CURB - 14"and 8” high, full perimeter curb with  
wood nailer (shipped knocked-down).  
Heat Exchanger 10 Years  
Electric Heat Element 5 Years  
Other Parts 1 Year  
BAROMETRIC RELIEF DAMPER - Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit.  
OPTIONAL OUTDOOR AIR (Shall be made available by  
either/or):  
PROPANE CONVERSION KIT - Contains new orifices  
and gas valve parts to convert from natural to L.P. gas.  
One per unit required.  
ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER- Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in CFM of outdoor air to  
meet the minimum ventilation requirement of the condi-  
tioned space during normal operation. During econo-  
mizer operation, a mixed-air temperature control shall  
modulate the outdoor and return air damper assembly to  
prevent the supply air temperature from dropping below  
55°F. Changeover from compressor to economizer oper-  
ation shall be provided by an integral electronic enthalpy  
control that feeds input into the basic module. The out-  
door intake opening shall be covered with a rain hood  
that matches the exterior of the unit. Water eliminator/fil-  
ters shall be provided. Simultaneous economizer/com-  
pressor operation is also possible. Dampers shall fully  
close on power loss.  
HIGH ALTITUDE - NATURAL GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude.  
HIGH ALTITUDE - PROPANE GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude. Must be used with propane conversion kit.  
LOW NOX - Required to reduce the emission of nitrogen  
oxides below 40 nanograms per joule.  
GAS PIPING - Contains 1/2” pipe nipples, fittings and  
gas cock (including panel assess gaskets) required for  
bottom gas supply connection with external shut off.  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
ELECTRIC HEATERS  
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -  
Contains all hood panels and the hardware for assem-  
bling.  
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air  
dampers are positioned by a 2-position, spring-return  
damper actuator. The maximum leakage rate for the out-  
door air intake dampers shall not exceed 2% when  
dampers are fully closed and operating against a pres-  
sure differential of 0.5 IWG. A unit-mounted potentiome-  
ter shall be provided to adjust the outdoor damper  
assembly to take in the design CFM of outdoor air to  
meet the ventilation requirements of the conditioned  
space during normal operation. Whenever the indoor fan  
motor is energized, the dampers open up to one of two  
pre-selected positions - regardless of the outdoor air  
enthalpy. Dampers return to the fully closed position  
when the indoor fan motor is de-energized. Dampers  
shall fully close on power loss.  
MANUAL OUTDOOR AIR DAMPER  
COIL GUARD KIT - Guard for cooling coil.  
HAIL GUARD  
FLUE EXHAUST EXTENSION  
OTHER FACTORY INSTALLED OPTIONS  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
STAINLESS STEEL HEAT EXCHANGER  
STAINLESS STEEL DRAIN PAN  
BOTTOM DRAIN CONNECTION  
Unitary Products Group  
29  
254597-YTG-B-0507  
®
TECHNICOAT PHENOLIC COATED CONDENSER  
AND EVAPORATOR COIL  
BAS CONTROLS (S implicity INTELLI-Comfort™,  
CPC, JOHNSON, HONEYWELL, NOVAR)  
ELECTRONIC SINGLE ENTHALPY ECONOMIZER  
DIRTY FILTER SWITCH  
BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR  
WITHOUT A CONTROLLER)  
HINGED FILTER DOOR ACCESS AND TOOLESS  
ACCESS PANELS  
PHASE MONITOR  
COIL GUARD  
2" PLEATED FILTERS  
POWERED GFI CONVENIENCE OUTLET  
NON-POWERED GFI CONVENIENCE OUTLET  
DISCONNECT SWITCH  
SUPPLY AIR SMOKE DETECTOR  
RETURN AIR SMOKE DETECTOR  
30  
Unitary Products Group  
254597-YTG-B-0507  
Unitary Products Group  
31  
Subject to change without notice. Printed in U.S.A.  
254597-YTG-B-0507  
Copyright © 2007 by Unitary Products Group. All rights reserved.  
Supersedes: 254597-YTG-A-0306  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Philips Tea1104 User Manual
Ryobi P541 User Manual
Sears 47003 User Manual
Sharp Al 2030 User Manual
Silva Battery Charger Solar Panel User Manual
Silvercrest Sul 1000 A1 User Manual
Soleus Air Air Conditioner 21 User Manual
Soleus Air Kfh 18 User Manual
Whirlpool 3pach21dd0 User Manual
York D2eb030 User Manual