York Champion Plus Dnp042 User Manual

036-21366-007-A-1205  
®
DESCRIPTION  
York® Affinity™ Series packaged cooling/heating air condi-  
tioners are designed for outdoor installation. Only utility and  
duct connections are required at the point of installation.  
TECHNICAL GUIDE  
The gas-fired heaters have aluminized steel tubular heat  
exchangers and hot surface to pilot ignition. They are avail-  
able in natural gas with field conversion to propane.  
AFFINITY™ SERIES  
SINGLE PACKAGE GAS/ELECTRIC  
AIR COOLED AIR CONDITIONERS  
2 THRU 5 NOMINAL TON  
FEATURING  
FACTORY MOUNTED TXV  
COOLING/GAS HEATING UNITS (NATURAL GAS OR  
PROPANE)  
DNP024, 030, 036, 042, 048 AND 060  
13 SEER  
LOW PROFILE  
QUIET OPERATION  
COMMON FOOTPRINT  
OPTIONAL SLIDE IN MOTORIZED DAMPERS  
OPTIONAL SLIDE IN ECONOMIZERS  
OPTIONAL PROPANE CONVERSION KIT  
OPTIONAL HIGH ALTITUDE CONVERSION KIT  
(NATURAL GAS/PROPANE)  
OPTIONAL LOW NOx KIT  
FULL PERIMETER BASE RAILS  
BOTTOM AND SIDE UTILITY CONNECTIONS  
1” OR 2” CLEANABLE FILTERS STANDARD ON ALL  
3 PHASE MODELS. OPTIONAL ON 1 PHASE MODELS  
WARRANTY - 1 PHASE  
10 year compressor  
20 year heat exchanger  
5 year other parts  
WARRANTY - 3 PHASE  
5 year compressor  
10 year heat exchanger  
1 year other parts  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
036-21366-007-A-1205  
will build-up. The condensate pan conforms to ASHRAE 62-  
89 standards (Ventilation for Acceptable Indoor Air Quality).  
STANDARD FEATURES/BENEFITS  
OPERATING EFFICIENCY - All units provide high operating  
efficiencies and have a minimum AFUE of 80% and SEER of  
13.0. All efficiencies exceed legislated minimum levels.  
CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI cop-  
per connection is more durable over time. The connection is  
rigidly mounted to assure proper fit and leak tight seal.  
ON SITE FLEXIBILITY - All model sizes share a common,  
compact design cabinet in a single footprint. The installer has  
the flexibility of setting one curb and placing the proper ton-  
nage unit on that curb after the internal load has been deter-  
mined. Field convertible duct connections from side shot to  
down shot allows the installer to have greater flexibility with  
less inventory.  
DURABLE FINISH - With a heavy duty cabinet made of pow-  
der-painted, galvanized steel the neutral color blends into  
surrounding areas. The powdered paint provides a better  
paint to steel bond, which resists corrosion and rust creep.  
The special primer formulas and glossy finish insures less  
fading when exposed to sunlight and offers a more attractive  
on site appearance. This paint finish meets ASTM-B117 stan-  
dards for 1000 hours salt spray rating. The highest in the  
industry.  
LOWER INSTALLATION COST - Installation time and costs  
are reduced by easy power and control wiring connections.  
The small base dimension means less space is required on  
the ground or roof, plus, the installer can fit this unit between  
the wheel wells of full size pick-up truck. All models are well  
under 500 pounds.  
FULL PERIMETER BASE RAILS - The easily removable  
base rails provide a solid foundation for the entire unit and  
protects the unit during shipment. The rails provide fork lift  
access from all sides, and rigging holes are also provided so  
that an overhead crane can be used to place the units on a  
roof. On applications where the unit is placed on a pad, the  
base will keep the unit off the pad to deter corrosion. On  
applications where height is limited, the inch high base rails  
may be removed on location.  
All units are completely wired, charged with R-22 and tested  
prior to shipment. Unique test stations using a new state of the  
art computerized process system are used to insure product  
quality. Refrigerant charge and component part numbers are  
verified via computers at assembly. Vital run test statistics  
such as system pressure, motor currents, air velocity and tem-  
perature, unit vibration, and gas system safeties are monitored  
and recorded by the system to insure unit performance.  
MORE ATTRACTIVE APPEARANCE - A single piece Water  
Shed top cover containing a top discharge condenser fan  
arrangement requires less square footage on installation and  
provides a wider variety of installations. The one piece design  
adds greater water integrity. Rounded corners with water drip  
edges add to the attractive appearance. The cabinet panels  
have a non-fibrous insulation that will not release insulation  
fibers into conditioned area.  
Equal size, side supply and return duct connections allows  
easy hook-up of ducts to match low crawl spaces without  
transition pieces.  
UTILITY CONNECTIONS MADE EASY - Gas and electric  
utility knockouts are provided through the bottom as well as  
the side of the unit. Utility connections can be made quickly  
and with a minimum amount of field labor. A field supplied  
and field installed electrical disconnect switch must be  
installed.  
TOP DISCHARGE - The top discharge condenser fan does  
not disrupt neighboring areas or dry-out vegetation surround-  
ing the unit. The warm air from the top mounted fan is blown  
up away from the structure and any landscaping. This allows  
compact location on multi-unit applications.  
CONVERTIBLE AIRFLOW DESIGN - The bottom duct open-  
ings are covered when they leave the factory ready to be  
used for a side supply / side return application. If a bottom  
supply / bottom return application is desired, you simply  
remove the two panels from the bottom of the unit and place  
them in the side supply / side return duct openings. No panel  
cutting is required and no accessory panel is necessary.  
Convertible airflow design allows maximum field flexibility and  
minimum inventory.  
CONDENSER COIL GRILLE - A multi-piece totally enclosed,  
rigidly mounted condenser coil grille provides protection from  
objects after installation and provides protection during transit.  
LOW OPERATING SOUND LEVEL - The upward air flow  
carries the normal operating noise up and away from the liv-  
ing area. The rigid top panel effectively isolates any motor  
sound. Isolator mounted compressor and the rippled fins of  
the condenser coil muffle the normal fan motor and compres-  
sor operating sounds. The unique formed base pan also aids  
in sound alterations with it's Super-Structure design. This  
design strategically places embossments in the pan for opti-  
mum strength and rigidity.  
CONDENSATE PAN - A non-corrosive, long-lasting, water-  
tight pan is positioned below the evaporator coil to collect and  
drain all condensate. Less collection of stagnate condensate  
Unitary Products Group  
3
 
036-21366-007-A-1205  
FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate  
over a wide range of design conditions with a constant CFM,  
electrically commutated (ECM) fan motor. These units easily  
match all types of applications and provide greater on site  
flexibility to match comfort requirement. These models have 2  
cooling speeds and a single heating speed. The cooling  
speed is factory set and can be field adjusted to a second  
speed. The heating speed is factory set to maintain mid point  
rise at the units heating input. It cannot be field adjusted. This  
allows maximum comfort conditions.  
LOW MAINTENANCE - Long life, permanently lubricated  
condenser and evaporator fan motor bearings need no  
annual maintenance adding greater reliability to the unit.  
Blower assembly can be easily cleaned by the unique Slip-  
Track slide-out blower assembly.  
SECURED SERVICE ACCESS PORTS - Protected, exter-  
nally mounted, re-usable service access ports are provided  
on both the high and low lines for ease of evacuating and  
charging the system. No final field mounting required.  
EASY SERVICE ACCESS - A large, single panel covers the  
electrical and gas controls makes servicing easy. The blower  
compartment has an additional large panel with a built-in  
handle tab. Removing this panel will allow the blower assem-  
bly to slide-out for easy removal for maintenance and ease of  
trouble shooting.  
Two ton models operate over a wide range of design condi-  
tions with a 3-speed direct-drive fan motor. These single  
phase models have the Comfort-Match system that allows  
different speed taps for heating or cooling operations.  
SIMPLE CONTROL CIRCUIT - A low voltage printed circuit  
board contains a diagnostic indicator light and a low voltage  
terminal strip. An additional set of pin connectors is also pro-  
vided to simplify the field interface of external controls. Mate-  
n-lock plug connectors are used. The electrical control box is  
not located in the compressor compartment. The controls are  
mounted on a Control-Tilt control panel to allow the access  
cover to be removed for trouble shooting and maintenance  
without affecting the normal system operating pressures. All  
wiring internal to the unit is color/number coded.  
REPLACEMENT PARTS - The installer requires no special  
training to replace any of the components of these units and  
does not need to maintain an inventory of unique parts.  
SYSTEM INTEGRATION - Each unit has the internal ability  
to integrate an electronic air cleaner or humidifier to work in  
conjunction with the base unit.  
FIELD-INSTALLED ACCESSORIES  
PROTECTED COMPRESSOR - The compressor is internally  
protected against high pressure and temperature. This is  
accomplished by the simultaneous operation of high pressure  
relief valve and a temperature sensor which protect the com-  
pressor if undesirable operating conditions occur.  
LOW NOx KIT - Kit includes all the necessary hardware and  
instructions to field convert units to reduce emissions to less  
than 40 nanogram per Joule. California requirement on single  
phase models only.  
PROPANE CONVERSION KIT - Kit includes burner orifices,  
gas valve conversion and installation instructions necessary  
to field convert unit from natural gas to propane.  
EXCLUSIVE COIL DESIGN - Grooved copper tubes and  
enhanced aluminum fin construction improves heat transfer  
for maximum efficiency and durability.  
HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane)  
- Kit includes all necessary labels and instructions to field  
alter units with natural gas/propane for installations above  
2000 feet. Burner orifices must be obtained from Source 1  
Parts. Propane Conversion Kit must be obtained separately.  
HEAT EXCHANGERS - Are corrosion-resistant, aluminized-  
steel tubular construction to provide long-life, trouble-free  
operation. The unique blow-through design also assures that  
condensate does not collect in humid areas when in the cool-  
ing cycle. This adds to longer heat exchanger life and higher  
long term efficiencies.  
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modu-  
lating integrated economizer provides simultaneous opera-  
tion between the mechanical cooling and economizer  
operation. Independent blade design insures proper control  
and less than 1% leak rate. Includes hood and mesh bird  
screen filter integrated into the hood, dry bulb sensor and  
relief damper. Separate field accessories of single enthalpy  
and dual enthalpy are also available. A built-in barometric  
relief of 25% is provided.  
POST PURGE INDUCED DRAFT COMBUSTION - Exhausts  
combustion products from the heat exchanger upon comple-  
tion of the heating cycle to prolong the heat exchanger life.  
SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this  
self diagnostic control, less on site time is required to trouble  
shoot these units.  
HOT SURFACE TO PILOT IGNITION - Provides faster heat  
delivery. This ignition is highly reliable, durable and elimi-  
nates nuisance lockouts. Also assures starts in damp condi-  
tions.  
SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb  
sensor standard in economizer kit. Provides improved econo-  
mizer operation by sensing the dry bulb temperature from  
outdoors plus the enthalpy content of the outdoor air.  
MULTI PORT IN-SHOT BURNERS - No field adjustment is  
required to mix the air and gas. These burners are con-  
structed of high-grade corrosion-resistant, aluminized-steel.  
DUAL ENTHALPY SENSOR - Additional sensor to single  
enthalpy sensor. Sensor senses both the return air tempera-  
ture dry bulb and humidity in conjunction with the single  
4
Unitary Products Group  
 
036-21366-007-A-1205  
enthalpy to determine the most economical mix. Single  
Enthalpy sensor also required.  
50% of outdoor air (field supplied). Closes on power loss,  
includes hood and screen assembly.  
PRESSURE SWITCH UPGRADE KIT - Contains screw in  
type High pressure, Low Pressure/Loss of Charge switch,  
freeze protection switch and lockout relay. Switches are  
placed onto existing scharder ports located in the unit by fur-  
nished adapters. When abnormal conditions are sensed  
through the pressure switches, the unit will lock out prevent-  
ing any further operation until reset or problem is corrected.  
Package agency approved.  
RECTANGLE TO ROUND ADAPTERS - Kit includes one  
supply and one return air rectangle to round duct adapter.  
Adapters are preformed and designed to fit over current duct  
openings on the base unit. Transition is from side square duct  
opening to 14" round duct opening.  
ROOF CURBS - NRCA approved curbs provide proper fit to  
base unit for rooftop installations. Curbs are designed to be  
assembled through hinge pins in each corner. Kit also pro-  
vides seal strip to assure a water tight seal. 8 and 14 inch  
high roof curbs are available.  
HAIL GUARD KIT - Kit contains protective grilles made of  
expanded aluminum with full perimeter frame. Sloped hoods  
are also included to assure maximum protection.  
MANUAL OUTDOOR DAMPER - Provides 0% through 50%  
outdoor air capability (field adjustable). Designed for duct  
mounted side supply/return applications. Includes hood and  
screen assembly.  
ANTI SHORT CYCLE TIMER - Automatically prevents the  
compressor from restarting for 5 minutes after cycled off.Not  
required if Thermostat 2ET07700224 and 2ET04700224 are  
used.  
WALL THERMOSTAT - The units are designed to operate  
with 24-volt electronic and electro-mechanical thermostats.  
All units can operate with single stage heat / single stage cool  
thermostats - with or without the economizer.  
FILTER / FRAME KIT (Single Phase only) - Kit contains the  
necessary hardware to field install return air filters into the  
base unit. Pre-cut filter racks and appropriate cleanable stan-  
dard size filters are shipped in one kit. The filter rack is suit-  
able for either 1" or 2" filters. (1" filter is supplied) This kit is  
available for single phase horizontal or vertical duct applica-  
tion only. Standard in all 3 Phase models.  
LOW AMBIENT KIT - Kit provides necessary hardware to  
convert unit to operate in cooling cycle down to 0º F. Stan-  
dard unit operation 45º F.  
TRANSFORMER KIT - Kit provides necessary hardware to  
provide single phase models from factory furnished 40 VA  
transformer capability to 75 VA transformer capability.  
(Required on installations with economizer or motorized  
damper.)  
MOTORIZED FRESH AIR DAMPER - Designed for duct  
mounted side supply/return and unit mounted down supply/  
return applications. Damper capable of providing 0% through  
Unitary Products Group  
5
036-21366-007-A-1205  
DIRECT DRIVE  
CONDENSER  
FAN MOTOR  
BLOW-THROUGH DESIGN  
WITH RELIABLE ALUMINIZED  
STEEL TUBULAR HEAT EX HANGERS  
C
HIGHLY EFFICIENT ENHANCED  
COPPER TUBE/ALUMINUM FIN  
EVAPORATOR COIL  
HIGHLY EFFICIENT  
ENHANCED COPPER  
TUBE/ALUMINUM FIN  
CONDENSER COIL  
LONG LASTING  
POWDER PAINT  
FINISH  
DECORATIVE  
PROTECTIVE  
COIL GAURD  
REAR AND BOTTOM  
RETURN AIR  
AND SUPPLY AIR  
DUCT OPENINGS  
HIGH EFFICIENCY  
COMPRESSOR  
RIGIDLY  
MOUNTED  
HOT SURFACE PILOT  
ASSEMBLY  
HIGH GRADE ALUMINIZED  
IN-SHOT BURNERS  
HEAVY GAUGE  
REMOVABLE  
BASE RAILS  
LOW VOLTAGE  
TERMINAL BLOCK  
SELF-DIAGNOSTIC CONTROLS WITH  
"COMFORT-MATCH" SPEED CONTROL  
DIRECT DRIVE  
BLOWER MOTOR WITH  
SLIDE-OUT BLOWER ASSEMBLY  
AUTOMATIC GAS VALVE (1/2" - 14 NPTI)  
POWER VENTER MOTOR  
HIGH VOLTAGE  
TERMINAL BLOCK  
FIGURE 2 - UNIT COMPONENT LOCATION  
TABLE 1: PHYSICAL DATA  
DNP  
MODEL  
024  
10 x 8  
1/2  
030  
10 x 8  
3/4  
036  
11 x 10  
3/4  
042  
12 x 11  
1
048  
12 x 11  
1
060  
12 x 11  
1
CENTRIFUGAL BLOWER (Dia. x W. in.)  
EVAPORATOR  
BLOWER  
FAN MOTOR HP  
ROWS DEEP  
2
3
3
3
3
3
EVAPORATOR  
FINS PER INCH  
COIL  
15  
13  
13  
13  
16  
16  
FACE AREA (Sq. Ft.)  
3.5  
3.5  
3.5  
4.5  
4.5  
4.5  
PROPELLER DIA. (in.)  
22  
22  
22  
22  
22  
22  
CONDENSER  
FAN MOTOR HP  
FAN  
1/4  
1/4  
1/4  
1/4  
1/3  
1/3  
3,500  
2
NOM. CFM TOTAL  
2,200  
2
2,400  
1
2,400  
2
2,400  
2
3,000  
2
ROWS DEEP  
CONDENSER  
FINS PER INCH  
COIL  
20  
20  
20  
20  
20  
20  
FACE AREA (Sq. Ft.)  
11.7  
6 / 4  
11.7  
4 / 9  
11.7  
6 / 12  
14.7  
9 / 6  
14.7  
8 / 4  
14.7  
8 / 8  
CHARGE  
FILTER  
REFRIGERANT 22 (lbs./oz.)  
3.1 / 19.5 x 11.5 3.1 / 19.5 x 11.5 3.1 / 19.5 x11.5  
FACE AREA (Sq. Ft.) Size (Actual)  
2.6 / 19 x 19.5 2.6 / 19 x 19.5 2.6 / 19 x 19.5  
(2 Reqd.)  
(2 Reqd.)  
(2 Reqd.)  
NATURAL GAS BURNER ORIFICE NO.  
(Drill Size)  
43  
55  
43  
55  
43  
55  
40  
40  
40  
FURNACE  
SECTION  
PROPANE BURNER ORIFICE NO.  
(Drill Size)  
53  
53  
53  
GAS CONNECTION SIZE  
1/2 NPTI  
Recip  
1/2 NPTI  
Scroll  
1/2 NPTI  
Scroll  
1/2 NPTI  
Scroll  
1/2 NPTI  
Scroll  
1/2 NPTI  
Scroll  
COMPRESSOR HERMETIC TYPE, (Qty. = 1)  
6
Unitary Products Group  
   
036-21366-007-A-1205  
TABLE 2: RATINGS COOLING/GAS HEATING  
1
GAS HEAT CAPACITY / EFFICIENCIES  
5
NET COOLING CAPACITY  
SOUND  
MODEL  
DNP  
TEMP.  
RISE  
RATING  
INPUT  
(MBH)  
OUTPUT  
(MBH)  
NUMBER OF  
BURNERS  
AFUE  
(%)  
3
4
MBH  
2
SEER  
EER  
(dbels)  
(°F) RANGE  
024N03606  
024N05606  
030N03606  
030N03625  
030N03646  
030N05606  
030N05625  
030N05646  
036N03606  
036N03625  
036N03646  
036N03658  
036N05606  
036N05625  
036N05646  
036N05658  
036N07206  
036N07225  
036N07246  
036N07258  
042N06506  
042N06525  
042N06546  
042N06558  
042N09006  
042N09025  
042N09046  
042N09058  
048N06506  
048N06525  
048N06546  
048N06558  
048N09006  
048N09025  
048N09046  
048N09058  
048N11006  
048N11025  
048N11046  
048N11058  
060N06506  
060N06525  
060N06546  
060N06558  
060N09006  
060N09025  
060N09046  
060N09058  
060N11006  
060N11025  
060N11046  
060N11058  
25.4  
25.4  
30.6  
30.6  
30.6  
30.6  
30.6  
30.6  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
37.4  
44  
13.3  
13.3  
13.4  
13.4  
13.4  
13.4  
13.4  
13.4  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.65  
13.7  
13.7  
13.7  
13.7  
13.7  
13.7  
13.7  
13.7  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.2  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
13.0  
11.6  
11.6  
81  
81  
80  
80  
80  
80  
80  
80  
81  
81  
81  
81  
81  
81  
81  
81  
81  
81  
81  
81  
80  
80  
80  
80  
80  
80  
80  
80  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
84  
45  
70  
36  
56  
36  
36  
36  
56  
56  
56  
36  
36  
36  
36  
56  
56  
56  
56  
72  
72  
72  
72  
64  
64  
64  
64  
86  
86  
86  
86  
64  
64  
64  
64  
86  
86  
86  
86  
107  
107  
107  
107  
64  
64  
64  
64  
86  
86  
86  
86  
107  
107  
107  
107  
80.2  
80.2  
80.2  
80.2  
80.2  
80.2  
80.2  
80.2  
80.4  
80.4  
80.4  
80.4  
80.2  
80.2  
80.2  
80.2  
80.1  
80.1  
80.1  
80.1  
80.6  
80.6  
80.6  
80.6  
80.8  
80.8  
80.8  
80.8  
80.8  
80.8  
80.8  
80.8  
80.6  
80.6  
80.6  
80.6  
80.5  
80.5  
80.5  
80.5  
80.8  
80.8  
80.8  
80.8  
80.6  
80.6  
80.6  
80.6  
80.5  
80.5  
80.5  
80.5  
2
3
2
2
2
3
3
3
2
2
2
2
3
3
3
3
4
4
4
4
3
3
3
3
4
4
4
4
3
3
3
3
4
4
4
4
5
5
5
5
3
3
3
3
4
4
4
4
5
5
5
5
25 - 55  
30 - 60  
25 - 55  
25 - 55  
25 - 55  
30 - 60  
30 - 60  
30 - 60  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
30 - 60  
30 - 60  
30 - 60  
30 - 60  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
45 - 75  
45 - 75  
45 - 75  
45 - 75  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
35 - 65  
35 - 65  
35 - 65  
35 - 65  
45 - 75  
45 - 75  
45 - 75  
45 - 75  
25 - 55  
25 - 55  
25 - 55  
25 - 55  
35 - 65  
35 - 65  
35 - 65  
35 - 65  
45 - 75  
45 - 75  
45 - 75  
45 - 75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
11.75  
10.65  
10.65  
10.65  
10.65  
10.65  
10.65  
10.65  
10.65  
11.7  
45  
45  
45  
70  
70  
70  
45  
45  
45  
45  
70  
70  
70  
70  
90  
90  
90  
90  
80  
44  
80  
44  
80  
44  
80  
44  
108  
108  
108  
108  
80  
44  
44  
44  
48  
48  
11.7  
80  
48  
11.7  
80  
48  
11.7  
80  
48  
11.7  
108  
108  
108  
108  
135  
135  
135  
135  
80  
48  
11.7  
48  
11.7  
48  
11.7  
48  
11.7  
48  
11.7  
48  
11.7  
48  
11.7  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
55.5  
11.2  
11.2  
80  
11.2  
80  
11.2  
80  
11.2  
108  
108  
108  
108  
135  
135  
135  
135  
11.2  
11.2  
11.2  
11.2  
11.2  
11.2  
11.2  
1.  
Net Cooling Capacity = ARI 210 standard rating conditions.  
(dbels) = ARI 270-95  
2.  
3.  
Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the  
total electric power input in watt-hours during the same period.  
4.  
5.  
Tested in accordance with ARI 210 Standard Rating Conditions.  
AFUE = Annual Fuel Utilization Efficiency.  
Unitary Products Group  
7
 
036-21366-007-A-1205  
TABLE 3: DNP024 COOLING CAPACITIES - 2 TON  
TEMPERATURE OF AIR ON CONDENSER COIL  
TEMPERATURE OF AIR ON CONDENSER COIL  
95°F  
SENSIBLE CAPACITY  
ENTERING DRY BULB, °F  
AIR ON  
EVAPORATOR  
COIL  
85°F  
1
SENSIBLE CAPACITY  
NET  
CAP.  
MBH  
POWER  
INPUT  
KW  
NET  
CAP.  
MBH  
POWER  
INPUT  
KW  
ENTERING DRY BULB, °F  
83 80 77 74 71  
8.1 #N/A #N/A  
WB  
CFM  
°F  
86  
68  
86  
83  
80  
77  
74  
71  
68  
72  
24.7  
22.6  
20.9  
20.6  
26.4  
24.1  
22.3  
22.0  
28.0  
25.6  
23.7  
23.3  
28.2  
25.8  
23.8  
23.5  
28.3  
25.9  
24.0  
23.6  
1.90  
1.91  
1.89  
1.88  
1.94  
1.94  
1.93  
1.92  
1.97  
1.98  
1.96  
1.95  
2.01  
2.01  
1.99  
1.98  
2.04  
2.04  
2.02  
2.01  
15.0 13.3 11.6 9.9  
18.4 16.7 14.9 13.2 11.5  
23.1  
21.0  
19.5  
19.5  
24.6  
22.3  
20.7  
20.7  
26.0  
23.7  
22.0  
22.0  
26.2  
23.9  
22.1  
22.2  
26.5  
24.1  
22.3  
22.3  
2.03  
2.03  
2.00  
1.99  
2.08  
2.08  
2.05  
2.04  
2.13  
2.13  
2.09  
2.09  
2.15  
2.15  
2.12  
2.11  
2.18  
2.18  
2.14  
2.14  
15.0 13.3 11.6 9.9  
18.1 16.4 14.7 13.0 11.3  
8.1 #N/A #N/A  
67  
9.8  
8.1  
11.0  
11.7  
9.5  
7.8  
10.8  
11.0  
600  
62  
20.9 19.5 17.8 16.1 14.4 12.7  
20.6 20.2 18.5 16.8 15.1 13.4  
19.5 19.4 17.7 16.0 14.3 12.5  
19.5 19.5 17.9 16.2 14.5 12.7  
57  
72  
17.0 14.9 12.9 10.9 8.9 #N/A #N/A  
16.7 14.7 12.7 10.7 8.6 #N/A #N/A  
67  
20.7 18.7 16.7 14.7 12.7 10.6  
22.3 21.6 19.9 17.9 15.9 13.9  
22.0 21.8 20.7 18.7 16.7 14.6  
8.6  
11.8  
12.6  
20.1 18.1 16.1 14.1 12.1 10.0  
20.7 20.7 19.4 17.4 15.3 13.3  
20.7 20.7 19.6 17.6 15.6 13.5  
8.0  
11.3  
11.5  
700  
62  
57  
72  
19.0 16.6 14.3 12.0 9.6 #N/A #N/A  
18.5 16.1 13.8 11.5 9.1 #N/A #N/A  
67  
23.1 20.8 18.5 16.1 13.8 11.5  
23.7 23.7 22.0 19.7 17.4 15.0  
23.3 23.3 22.9 20.5 18.2 15.9  
9.1  
22.2 19.8 17.5 15.2 12.8 10.5  
22.0 22.0 21.1 18.8 16.4 14.1  
22.0 22.0 21.3 19.0 16.7 14.3  
8.2  
11.8  
12.0  
800  
62  
12.7  
13.5  
57  
72  
20.4 17.7 15.1 12.4 9.8 #N/A #N/A  
19.9 17.2 14.6 11.9 9.3 #N/A #N/A  
67  
24.5 22.1 19.5 16.8 14.2 11.5  
23.8 23.8 23.0 20.3 17.7 15.0  
23.5 23.5 23.2 20.6 17.9 15.3  
8.8  
23.1 21.2 18.5 15.8 13.2 10.5  
22.1 22.1 21.7 19.1 16.4 13.7  
22.2 22.2 21.8 19.2 16.5 13.9  
7.9  
900  
62  
12.4  
12.6  
11.1  
11.2  
57  
72  
21.8 18.8 15.9 12.9 9.9 #N/A #N/A  
21.3 18.3 15.4 12.4 9.4 #N/A #N/A  
67  
25.9 23.5 20.5 17.5 14.5 11.5  
24.0 24.0 24.0 21.0 18.0 15.0  
23.6 23.6 23.6 20.6 17.6 14.7  
8.6  
12.0  
11.7  
24.1 22.5 19.5 16.5 13.5 10.5  
22.3 22.3 22.3 19.3 16.4 13.4  
22.3 22.3 22.3 19.4 16.4 13.4  
7.6  
1000  
62  
10.4  
10.4  
57  
TEMPERATURE OF AIR ON CONDENSER COIL  
105°F  
TEMPERATURE OF AIR ON CONDENSER COIL  
115°F  
AIR ON  
EVAPORATOR  
COIL  
SENSIBLE CAPACITY  
SENSIBLE CAPACITY  
NET  
CAP.  
MBH  
POWER  
INPUT  
NET  
CAP.  
MBH  
POWER  
INPUT  
ENTERING DRY BULB, °F  
ENTERING DRY BULB, °F  
KW  
KW  
WB  
CFM  
°F  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
21.5  
19.5  
18.4  
18.5  
22.8  
20.7  
19.5  
19.6  
24.1  
21.8  
20.5  
20.7  
24.3  
22.0  
20.7  
20.8  
24.5  
22.2  
20.9  
21.0  
2.20  
2.17  
2.15  
2.15  
2.24  
2.21  
2.19  
2.19  
2.28  
2.25  
2.24  
2.24  
2.32  
2.29  
2.27  
2.27  
2.36  
2.33  
2.31  
2.31  
14.4 12.7 10.9 9.2  
7.5 #N/A #N/A  
20.0  
18.1  
17.3  
17.5  
21.0  
19.0  
18.2  
18.4  
22.1  
20.0  
19.1  
19.3  
22.3  
20.2  
19.3  
19.5  
22.5  
20.4  
19.5  
19.7  
2.36  
2.30  
2.30  
2.31  
2.40  
2.34  
2.34  
2.35  
2.43  
2.38  
2.38  
2.38  
2.48  
2.43  
2.43  
2.43  
2.53  
2.47  
2.47  
2.48  
13.7 12.0 10.3 8.6  
6.9 #N/A #N/A  
67  
17.6 15.9 14.2 12.5 10.8  
9.1  
7.4  
9.9  
17.2 15.4 13.7 12.0 10.3  
8.6  
6.9  
8.9  
9.1  
600  
62  
18.4 18.3 16.7 15.0 13.3 11.6  
18.5 18.5 16.9 15.2 13.5 11.8  
17.3 17.3 15.7 14.0 12.3 10.6  
17.5 17.5 15.9 14.2 12.5 10.8  
57  
72  
10.0  
16.0 14.0 12.0 9.9  
7.9 #N/A #N/A  
15.3 13.3 11.2 9.2  
7.2 #N/A #N/A  
67  
19.4 17.6 15.5 13.5 11.5  
9.5  
7.4  
18.6 17.0 15.0 12.9 10.9  
8.9  
6.9  
9.1  
9.2  
700  
62  
19.5 19.4 18.3 16.2 14.2 12.2  
19.6 19.6 18.5 16.4 14.4 12.4  
10.2  
10.4  
18.2 18.2 17.2 15.1 13.1 11.1  
18.4 18.4 17.3 15.3 13.3 11.3  
57  
72  
17.6 15.3 13.0 10.6 8.3 #N/A #N/A  
16.8 14.5 12.2 9.8  
7.5 #N/A #N/A  
67  
21.1 19.2 16.9 14.5 12.2  
9.9  
7.5  
20.0 18.5 16.2 13.9 11.5  
9.2  
6.9  
9.2  
9.4  
800  
62  
20.5 20.5 19.8 17.5 15.2 12.8  
20.7 20.7 20.0 17.7 15.4 13.0  
10.5  
10.7  
19.1 19.1 18.6 16.2 13.9 11.6  
19.3 19.3 18.7 16.4 14.1 11.7  
57  
72  
19.0 16.3 13.7 11.0 8.3 #N/A #N/A  
18.1 15.4 12.7 10.1 7.4 #N/A #N/A  
67  
21.6 20.3 17.7 15.1 12.4  
9.8  
7.1  
9.7  
9.9  
20.2 19.5 17.0 14.3 11.6  
9.0  
6.3  
8.4  
8.6  
900  
62  
20.7 20.7 20.4 17.7 15.1 12.4  
20.8 20.8 20.5 17.9 15.2 12.6  
19.3 19.3 19.0 16.4 13.7 11.1  
19.5 19.5 19.2 16.6 13.9 11.3  
57  
72  
20.3 17.3 14.3 11.4 8.4 #N/A #N/A  
19.3 16.3 13.3 10.3 7.4 #N/A #N/A  
67  
22.2 21.4 18.6 15.6 12.6  
9.7  
6.7  
9.0  
9.1  
20.4 20.4 17.7 14.8 11.8  
8.8  
5.8  
7.6  
7.8  
1000  
62  
20.9 20.9 20.9 17.9 15.0 12.0  
21.0 21.0 21.0 18.0 15.1 12.1  
19.5 19.5 19.5 16.5 13.5 10.6  
19.7 19.7 19.7 16.7 13.7 10.8  
57  
1.  
These capacities are net capacities (the indoor fan heat is deducted).  
ALL SENSIBLE CAPACITY  
8
Unitary Products Group  
   
036-21366-007-A-1205  
TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D)  
TEMPERATURE OF AIR ON CONDENSER COIL  
125°F  
AIR ON  
EVAPORATOR  
COIL  
1
SENSIBLE CAPACITY  
ENTERING DRY BULB, °F  
NET  
CAP.  
MBH  
POWER  
INPUT  
KW  
WB  
°F  
CFM  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
18.4  
16.6  
16.2  
16.5  
19.3  
17.4  
17.0  
17.2  
20.1  
18.1  
17.7  
18.0  
20.4  
18.3  
17.9  
18.2  
20.6  
18.5  
18.1  
18.4  
2.5  
2.4  
2.5  
2.5  
2.6  
2.5  
2.5  
2.5  
2.6  
2.5  
2.5  
2.5  
2.6  
2.6  
2.6  
2.6  
2.7  
2.6  
2.6  
2.7  
13.1  
16.7  
16.2  
16.5  
14.6  
17.8  
17.0  
17.2  
16.0  
18.9  
17.7  
18.0  
17.1  
18.7  
17.9  
18.2  
18.3  
18.5  
18.1  
18.4  
11.4  
15.0  
16.2  
16.5  
12.5  
16.4  
17.0  
17.2  
13.7  
17.9  
17.7  
18.0  
14.5  
18.6  
17.9  
18.2  
15.3  
19.3  
18.1  
18.4  
9.7  
8.0  
11.5  
13.1  
13.2  
8.5  
6.3  
9.8  
#N/A  
8.1  
#N/A  
6.4  
13.3  
14.8  
14.9  
10.5  
14.4  
16.0  
16.2  
11.3  
15.5  
17.3  
17.5  
11.8  
16.2  
17.7  
17.9  
12.3  
16.9  
18.1  
18.4  
600  
700  
800  
900  
1000  
11.4  
11.5  
6.5  
9.6  
7.9  
9.8  
8.1  
#N/A  
8.3  
#N/A  
6.3  
12.4  
14.0  
14.2  
9.0  
10.3  
12.0  
12.1  
6.7  
10.0  
10.1  
#N/A  
8.5  
7.9  
8.1  
#N/A  
6.2  
13.2  
15.0  
15.1  
9.2  
10.9  
12.6  
12.8  
6.5  
10.3  
10.5  
#N/A  
8.2  
8.0  
8.1  
#N/A  
5.6  
13.5  
15.0  
15.3  
9.3  
10.9  
12.4  
12.6  
6.3  
9.7  
7.1  
9.9  
7.3  
#N/A  
7.9  
#N/A  
4.9  
13.9  
15.1  
15.4  
10.9  
12.1  
12.4  
9.2  
6.2  
9.4  
6.5  
1.  
These capacities are net capacities (the indoor fan heat is deducted).  
ALL SENSIBLE CAPACITY  
Unitary Products Group  
9
036-21366-007-A-1205  
TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON  
AIR ON EVAPORATOR COIL  
TEMPERATURE  
1,000 CFM  
1,250 CFM  
WB °F  
OF AIR ON  
WB °F  
CONDENSER COIL  
72  
67  
62  
57  
72  
67  
62  
57  
NET CAP.MBH  
33.6  
2.4  
31.6  
2.4  
30.3  
2.3  
30.2  
2.3  
34.5  
2.6  
32.4  
2.6  
31.1  
2.5  
31.0  
2.5  
TOTAL POWER INPUT kW  
86  
23.6  
20.7  
17.8  
14.9  
12.0  
N/A  
N/A  
32.7  
2.6  
29.2  
26.3  
23.4  
20.5  
17.5  
14.6  
11.7  
30.5  
2.6  
30.3  
30.3  
28.4  
25.5  
22.6  
19.7  
16.8  
28.8  
2.6  
30.2  
30.2  
29.6  
26.7  
23.8  
20.8  
17.9  
28.9  
2.5  
27.2  
23.5  
19.7  
16.0  
12.3  
N/A  
N/A  
33.5  
2.8  
32.4  
29.7  
25.9  
22.2  
18.5  
14.8  
11.0  
31.3  
2.8  
31.1  
31.1  
31.1  
27.3  
23.6  
19.9  
16.2  
29.6  
2.8  
31.0  
31.0  
31.0  
27.3  
23.5  
19.8  
16.1  
29.7  
2.7  
83  
85 °F  
80  
77  
74  
71  
68  
NET CAP. MBH  
TOTAL POWER INPUT kW  
86  
23.1  
20.2  
17.3  
14.4  
11.5  
N/A  
N/A  
31.0  
2.9  
29.0  
26.1  
23.2  
20.3  
17.3  
14.4  
11.5  
28.3  
2.9  
28.8  
28.8  
27.9  
25.0  
22.1  
19.2  
16.3  
27.3  
2.9  
28.9  
28.9  
28.4  
25.4  
22.5  
19.6  
16.7  
27.3  
2.9  
26.9  
23.1  
19.4  
15.7  
12.0  
N/A  
N/A  
32.2  
3.1  
31.3  
29.7  
26.0  
22.3  
18.5  
14.8  
11.1  
29.4  
3.1  
29.6  
29.6  
29.6  
25.9  
22.1  
18.4  
14.7  
28.3  
3.0  
29.7  
29.7  
29.7  
26.0  
22.2  
18.5  
14.8  
28.3  
3.0  
83  
95 °F  
80  
77  
74  
71  
68  
NET CAP.MBH  
TOTAL POWERINPUT kW  
86  
22.6  
19.6  
16.7  
13.8  
10.9  
N/A  
N/A  
29.3  
3.2  
27.6  
25.1  
22.2  
19.3  
16.4  
13.5  
10.5  
26.2  
3.3  
27.3  
27.3  
26.4  
23.5  
20.6  
17.7  
14.8  
25.7  
3.2  
27.3  
27.3  
26.8  
23.8  
20.9  
18.0  
15.1  
25.7  
3.2  
26.4  
22.6  
18.9  
15.2  
11.5  
N/A  
N/A  
30.8  
3.4  
29.4  
28.6  
25.1  
21.4  
17.6  
13.9  
10.2  
27.5  
3.4  
28.3  
28.3  
28.3  
24.6  
20.8  
17.1  
13.4  
27.0  
3.3  
28.3  
28.3  
28.3  
24.6  
20.9  
17.2  
13.4  
27.0  
3.3  
83  
105 °F  
80  
77  
74  
71  
68  
NET CAP.MBH  
TOTAL POWER NPUT kW  
86  
22.0  
19.0  
16.1  
13.2  
10.3  
N/A  
N/A  
27.6  
3.5  
26.2  
24.1  
21.2  
18.3  
15.4  
12.5  
9.6  
25.7  
25.7  
24.9  
22.0  
19.1  
16.2  
13.3  
24.2  
3.5  
25.7  
25.7  
25.2  
22.2  
19.3  
16.4  
13.5  
24.0  
3.5  
25.8  
22.1  
18.4  
14.7  
10.9  
N/A  
N/A  
29.4  
3.6  
27.5  
27.5  
24.2  
20.5  
16.8  
13.0  
9.3  
27.0  
27.0  
27.0  
23.3  
19.5  
15.8  
12.1  
25.7  
3.6  
27.0  
27.0  
27.0  
23.2  
19.5  
15.8  
12.1  
25.6  
3.6  
83  
115 °F  
80  
77  
74  
71  
68  
NET CAP. MBH  
24.1  
3.6  
25.6  
3.7  
TOTAL POWER INPUT kW  
86  
83  
80  
77  
74  
71  
68  
21.4  
18.4  
15.5  
12.6  
9.7  
24.8  
23.2  
20.2  
17.3  
14.4  
11.5  
8.6  
24.2  
24.2  
23.4  
20.5  
17.6  
14.7  
11.8  
24.0  
24.0  
23.6  
20.7  
17.7  
14.8  
11.9  
25.3  
21.6  
17.9  
14.2  
10.4  
N/A  
N/A  
25.6  
26.4  
23.3  
19.6  
15.9  
12.1  
8.4  
25.7  
25.7  
25.7  
22.0  
18.3  
14.5  
10.8  
25.6  
25.6  
25.6  
21.9  
18.1  
14.4  
10.7  
125 °F  
N/A  
N/A  
1.  
These capacities are net capacities (the indoor fan heat is deducted)  
ALL SENSIBLE CAPACITY  
10  
Unitary Products Group  
 
036-21366-007-A-1205  
TABLE 5: DNP036 COOLING CAPACITIES - 3 TON  
AIR ON EVAPORATOR COIL  
TEMPERATURE  
OF AIR ON  
CONDENSER COIL  
1,200 CFM  
WB °F  
1,350 CFM  
WB °F  
72  
67  
62  
57  
72  
44  
67  
62  
57  
NET CAP.  
MBH  
43.3  
39.9  
37.4  
2.9  
36.7  
40.5  
38  
37.2  
TOTAL POWER  
INPUT kW  
2.93  
2.89  
2.88  
3.08  
3.05  
3.06  
3.04  
86  
83  
80  
77  
74  
71  
68  
29.5  
26  
35.8  
32.3  
28.8  
25.3  
21.8  
18.3  
14.8  
37.4  
37.4  
34.8  
31.3  
27.8  
24.3  
20.8  
36.7  
36.7  
35.6  
32.1  
28.6  
25.1  
21.6  
31.8  
27.8  
23.8  
19.9  
15.9  
-
38.4  
34.4  
30.4  
26.4  
22.5  
18.5  
14.5  
38  
37.2  
37.2  
36.7  
32.7  
28.7  
24.7  
20.7  
38  
85 °F  
22.5  
19  
36.7  
32.7  
28.7  
24.7  
20.7  
15.5  
-
-
-
NET CAP.  
MBH  
41.4  
3.22  
37.1  
3.27  
35.7  
3.18  
35.3  
3.15  
42.5  
3.32  
38  
36.6  
3.28  
36.2  
3.25  
TOTAL POWER  
INPUT kW  
3.37  
86  
83  
80  
77  
74  
71  
68  
28.5  
25  
34.8  
31.3  
27.8  
24.3  
20.8  
17.3  
13.8  
35.7  
35.7  
33.5  
30  
35.3  
35.3  
33.9  
30.4  
26.9  
23.4  
19.9  
31  
27  
23  
19  
15  
-
36.9  
33.7  
29.7  
25.7  
21.7  
17.7  
13.8  
36.6  
36.6  
25.5  
31.5  
17.6  
23.6  
19.6  
36.2  
36.2  
35.5  
31.5  
27.5  
23.5  
19.5  
95 °F  
21.5  
18  
14.5  
-
26.5  
23  
-
19.5  
-
NET CAP.  
MBH  
38.5  
3.61  
34.8  
3.61  
33.9  
3.5  
33.6  
3.48  
39.6  
3.73  
35.8  
3.72  
34.8  
3.61  
34.5  
3.59  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
27.6  
24.1  
20.6  
17.1  
13.6  
-
33.6  
30.1  
26.6  
23.1  
19.6  
16.1  
12.6  
33.9  
33.9  
32  
33.6  
33.6  
32.2  
28.7  
25.2  
21.7  
18.2  
29.9  
26  
22  
18  
14  
-
35.1  
32.4  
28.4  
24.4  
20.5  
16.5  
12.5  
34.8  
34.8  
33.9  
29.9  
25.9  
21.9  
18  
34. 5  
34.5  
33.8  
29.8  
25.8  
21.8  
17.9  
105 °F  
28.5  
25  
21.5  
18  
-
-
NET CAP.  
MBH  
35.6  
4.01  
32.6  
3.95  
32.2  
3.82  
31.9  
3.8  
36.7  
4.14  
33.5  
4.07  
33.1  
3.93  
32.8  
3.92  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
26.6  
23.1  
19.6  
16.1  
12.6  
-
32.4  
28.9  
25.4  
21.9  
18.4  
14.9  
11.4  
32.2  
32.2  
30.6  
27.1  
23.6  
20.1  
16.6  
31.9  
31.9  
30.6  
27.1  
23.6  
20.1  
16.6  
28.9  
24.9  
21  
17  
13  
-
33.4  
31.1  
27.1  
23.2  
19.2  
15.2  
11.2  
33.1  
33.1  
32.3  
28.3  
24.3  
20.3  
16.3  
32.8  
32.8  
32.1  
28.1  
24.1  
20.2  
16.2  
115 °F  
-
-
NET CAP.  
MBH  
32.8  
4.4  
30.2  
4.3  
30.4  
4.1  
30.1  
4.1  
33.7  
4.5  
31.2  
4.4  
31.3  
4.3  
30  
TOTAL POWER  
INPUT kW  
4.2  
86  
83  
80  
77  
74  
71  
68  
25.6  
22.1  
18.6  
15.1  
11.6  
-
31.2  
27.7  
24.2  
20.7  
17.2  
13.7  
10.2  
30.4  
30.4  
19.1  
25.6  
22.1  
18.6  
15.1  
30.1  
30.1  
28.9  
25.4  
21.9  
18.4  
14.9  
27.9  
23.9  
19.9  
15.9  
12  
31.6  
29.9  
25.9  
21.9  
17.9  
13.9  
9.9  
31.3  
31.3  
30.6  
26.6  
22.7  
18.7  
14.7  
31  
31  
125 °F  
30.4  
26.4  
22.5  
18.5  
14.5  
-
-
-
1.  
These capacities are net capacities (the indoor fan heat is deducted).  
ALL SENSIBLE CAPACITY  
Unitary Products Group  
11  
 
036-21366-007-A-1205  
TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON  
AIR ON EVAPORATOR COIL  
TEMPERATURE  
OF AIR ON  
CONDENSER COIL  
1,350 CFM  
WB °F  
1,500 CFM  
WB °F  
72  
67  
62  
57  
72  
67  
62  
57  
NET CAP.  
48.4  
3.4  
44.5  
3.3  
40.9  
3.3  
41.2  
3.3  
54.0  
3.8  
49.6  
3.7  
45.6  
3.6  
46.0  
3.7  
TOTAL POWER  
86  
83  
80  
77  
74  
71  
68  
33.0  
29.1  
25.2  
21.3  
17.3  
N/A  
N/A  
46.1  
3.8  
39.9  
36.0  
32.0  
28.1  
24.2  
20.3  
16.4  
42.4  
3.6  
40.9  
40.9  
38.1  
34.2  
30.2  
26.3  
22.4  
39.6  
3.8  
41.2  
41.2  
40.4  
36.5  
32.6  
28.7  
24.7  
39.1  
3.6  
36.8  
32.4  
28.1  
23.7  
19.3  
N/A  
N/A  
51.3  
4.2  
44.4  
40.1  
35.7  
31.3  
27.0  
22.6  
18.2  
47.3  
4.0  
45.6  
45.6  
42.4  
38.1  
33.7  
29.3  
25.0  
44.1  
4.2  
46.0  
46.0  
45.0  
40.7  
36.3  
31.9  
27.6  
43.5  
4.0  
85 °F  
NET CAP.  
TOTAL POWER  
86  
83  
80  
77  
74  
71  
68  
32.2  
28.3  
24.4  
20.5  
16.6  
N/A  
N/A  
43.5  
4.2  
38.8  
34.9  
31.0  
27.1  
23.1  
19.2  
15.3  
40.0  
4.1  
39.6  
39.6  
37.6  
33.7  
29.8  
25.9  
21.9  
37.2  
4.1  
39.1  
39.1  
38.7  
34.8  
30.8  
26.9  
23.0  
37.2  
4.0  
35.9  
31.6  
27.2  
22.8  
18.5  
N/A  
N/A  
48.5  
4.6  
43.3  
38.9  
34.5  
30.2  
25.8  
21.4  
17.1  
44.6  
4.5  
44.1  
44.1  
41.9  
37.6  
33.2  
28.8  
24.5  
41.4  
4.6  
43.5  
43.5  
43.1  
38.7  
34.4  
30.0  
25.6  
41.5  
4.5  
95 °F  
NET CAP.  
TOTAL POWER  
86  
83  
80  
77  
74  
71  
68  
31.3  
27.4  
23.5  
19.6  
15.7  
N/A  
N/A  
41.0  
4.6  
38.0  
34.1  
30.2  
26.2  
22.3  
18.4  
14.5  
37.6  
4.5  
37.2  
37.2  
36.2  
32.3  
28.3  
24.4  
20.5  
34.7  
4.5  
37.2  
37.2  
36.7  
32.8  
28.8  
24.9  
21.0  
35.4  
4.5  
34.9  
30.6  
26.2  
21.8  
17.4  
N/A  
N/A  
45.7  
5.1  
42.3  
38.0  
33.6  
29.2  
24.9  
20.5  
16.1  
41.9  
5.0  
41.4  
41.4  
40.3  
36.0  
31.6  
27.2  
22.8  
38.7  
5.1  
41.5  
41.5  
40.9  
36.5  
32.2  
27.8  
23.4  
39.4  
5.0  
105 °F  
NET CAP.  
TOTAL POWER  
86  
83  
80  
77  
74  
71  
68  
30.4  
26.5  
22.6  
18.7  
14.7  
N/A  
N/A  
38.5  
5.0  
37.2  
33.3  
29.3  
25.4  
21.5  
17.6  
13.7  
35.2  
5.0  
34.7  
34.7  
34.7  
30.8  
26.9  
23.0  
19.0  
32.3  
4.9  
35.4  
35.4  
34.7  
30.8  
26.8  
22.9  
19.0  
33.6  
4.9  
33.9  
29.5  
25.2  
20.8  
16.4  
N/A  
N/A  
43.0  
5.6  
41.4  
37.1  
32.7  
28.3  
24.0  
19.6  
15.2  
39.2  
5.5  
38.7  
38.7  
38.7  
34.3  
30.0  
25.6  
21.2  
36.0  
5.5  
39.4  
39.4  
38.7  
34.3  
29.9  
25.6  
21.2  
37.4  
5.5  
115 °F  
NET CAP.  
TOTAL POWER  
86  
83  
80  
77  
74  
71  
68  
29.5  
25.6  
21.7  
17.7  
13.8  
N/A  
N/A  
36.3  
32.4  
28.5  
24.6  
20.7  
16.7  
12.8  
32.3  
32.3  
33.3  
29.4  
25.4  
21.5  
17.6  
33.6  
33.6  
32.7  
28.8  
24.9  
20.9  
17.0  
32.9  
28.5  
24.1  
19.8  
15.4  
N/A  
N/A  
40.5  
36.1  
31.8  
27.4  
23.0  
18.7  
14.3  
36.0  
36.0  
37.1  
32.7  
28.3  
24.0  
19.6  
37.4  
37.4  
36.4  
32.1  
27.7  
23.3  
19.0  
125 °F  
1.  
These capacities are net capacities (the indoor fan heat is deducted)  
ALL SENSIBLE CAPACITY  
12  
Unitary Products Group  
 
036-21366-007-A-1205  
TABLE 7: DNP048 COOLING CAPACITIES - 4 TON  
AIR ON EVAPORATOR COIL  
TEMPERATURE  
OF AIR ON  
CONDENSER COIL  
1,400 CFM  
WB °F  
1,600 CFM  
WB °F  
72  
67  
62  
57  
72  
67  
62  
57  
NET CAP.  
MBH  
54.0  
49.2  
45.6  
3.62  
45.9  
55.2  
50.4  
46.6  
3.79  
46.9  
TOTAL POWER  
INPUT kW  
3.69  
3.66  
3.57  
3.85  
3.83  
3.73  
86  
83  
80  
77  
74  
71  
68  
35.8  
31.7  
27.7  
23.6  
19.6  
-
43.7  
39.6  
35.6  
31.6  
27.5  
23.5  
19.4  
45.6  
44.6  
42.4  
38.4  
34.3  
30.3  
26.2  
45.9  
45.3  
43.6  
39.5  
35.5  
31.4  
27.4  
39.1  
34.5  
29.8  
25.1  
20.5  
-
47.7  
43  
46.6  
46.6  
45.7  
41  
46.9  
46.9  
46.9  
42.3  
37.6  
32.9  
28.3  
85 °F  
38.3  
33.7  
29  
36.3  
31.7  
27  
24.3  
19.7  
-
-
NET CAP.  
MBH  
51.8  
4.07  
46.8  
4.04  
43.8  
4.01  
44.0  
3.99  
51.9  
4.21  
46.9  
4.18  
43.9  
4.15  
44.2  
4.12  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
35.4  
31.4  
27.4  
23.3  
19.3  
-
42.9  
38.9  
34.9  
30.8  
26.8  
22.7  
18.7  
43.8  
42.8  
40.9  
36.8  
32.8  
28.7  
24.7  
44.0  
43.2  
41.5  
37.5  
33.4  
29.4  
25.4  
38.4  
33.8  
29.1  
24.4  
19.8  
-
46.4  
41.7  
37.1  
32.4  
27.7  
23.1  
18.4  
43.9  
43.9  
43.5  
38.8  
34.1  
29.5  
24.8  
44.2  
44.2  
44.2  
39.5  
34.8  
30.2  
25.5  
95 °F  
-
-
NET CAP.  
MBH  
48.7  
4.49  
44.3  
4.45  
41.4  
4.38  
41.7  
4.34  
49.2  
4.63  
44.7  
4.59  
41.8  
4.51  
42.1  
4.48  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
34.1  
30.0  
26.0  
22.0  
17.8  
-
41.3  
37.7  
33.6  
29.6  
25.6  
21.5  
17.5  
41.4  
40.7  
38.9  
34.9  
30.8  
26.8  
22.8  
41.7  
41.1  
39.4  
35.3  
31.3  
27.3  
23.2  
37.1  
32.4  
27.8  
23.1  
18.4  
-
4.44  
40.6  
35.9  
31.3  
26.6  
21.9  
17.3  
41.8  
41.8  
41.6  
36.9  
32.3  
27.6  
22.9  
42.1  
42.1  
42.1  
37.4  
32.7  
28.1  
23.4  
105 °F  
-
-
NET CAP.  
MBH  
45.7  
4.91  
41.8  
4.86  
39.1  
4.74  
39.4  
4.70  
46.4  
5.05  
42.5  
5
39.7  
4.87  
40  
TOTAL POWER  
INPUT kW  
4.83  
86  
83  
80  
77  
74  
71  
68  
32.7  
28.7  
24.6  
20.6  
16.6  
-
39.7  
36.5  
32.4  
28.4  
24.4  
20.3  
16.3  
39.1  
38.7  
37.0  
32.9  
28.9  
24.9  
20.8  
39.4  
38.9  
37.2  
33.2  
29.1  
25.1  
21.1  
35.8  
31.1  
26.4  
21.8  
17.1  
-
42.5  
39.5  
34.8  
30.1  
25.5  
20.8  
16.2  
39.7  
39.7  
39.7  
35  
40  
40  
115 °F  
40  
35.3  
30.6  
26  
30.4  
25.7  
21  
-
-
21.3  
NET CAP.  
MBH  
42.7  
4.3  
39.3  
5.3  
36.8  
5.1  
37.0  
5.0  
43.6  
5.5  
40.2  
5.4  
37.6  
5.2  
37.9  
5.2  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
31.4  
27.3  
23.3  
19.2  
15.2  
-
38.0  
35.3  
31.2  
27.2  
23.1  
19.1  
15.1  
36.8  
36.7  
35.1  
31.0  
27.0  
22.9  
18.9  
37.0  
36.8  
35.1  
31.0  
27.0  
23.0  
18.9  
34.5  
29.8  
25.1  
20.5  
15.8  
-
40.5  
38.4  
33.7  
29  
37.6  
37.6  
37.6  
33.2  
28.5  
23.8  
19.2  
37.9  
37.9  
37.9  
33.2  
28.5  
23.9  
19.2  
125 °F  
24.4  
19.7  
15  
-
-
1.  
These capacities are net capacities (the indoor fan heat is deducted).  
ALL SENSIBLE CAPACITY  
Unitary Products Group  
13  
 
036-21366-007-A-1205  
TABLE 8: DNP060 COOLING CAPACITIES - 5 TON  
AIR ON EVAPORATOR COIL  
TEMPERATURE  
OF AIR ON  
CONDENSER COIL  
1,500 CFM  
WB °F  
1,800 CFM  
WB °F  
72  
67  
62  
57  
72  
67  
62  
57  
NET CAP.  
MBH  
63.5  
57.6  
4.44  
52.7  
53.1  
64.3  
58.3  
53.3  
53.7  
TOTAL POWER  
INPUT kW  
4.49  
4.38  
4.27  
4.68  
4.63  
4.57  
4.45  
86  
83  
80  
77  
74  
71  
68  
39.4  
35.0  
30.6  
26.3  
21.9  
--  
47.5  
43.2  
38.8  
34.4  
30.0  
25.7  
21.3  
52.7  
50.9  
46.5  
42.1  
37.7  
33.4  
29.0  
53.1  
53.1  
50.5  
46.2  
41.8  
37.4  
33.1  
41.4  
36.1  
30.7  
25.4  
20.0  
--  
49.6  
44.3  
38.9  
33.5  
28.2  
22.8  
17.4  
53.3  
52.0  
46.6  
41.2  
35.9  
30.5  
25.1  
53.7  
53.7  
50.7  
45.3  
39.9  
34.6  
29.2  
85 °F  
--  
--  
NET CAP.  
MBH  
60.6  
4.96  
56.0  
4.90  
52.1  
4.80  
51.5  
4.73  
61.2  
5.12  
56.6  
5.05  
52.6  
4.95  
52.0  
4.88  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
38.2  
33.9  
29.5  
25.1  
20.7  
--  
46.6  
42.2  
37.8  
33.5  
29.1  
24.7  
20.3  
52.1  
49.8  
45.4  
41.1  
36.7  
32.3  
27.9  
51.5  
51.5  
48.7  
44.4  
40.0  
35.6  
31.2  
43.3  
38.0  
32.6  
27.3  
21.9  
--  
52.6  
47.2  
41.9  
36.5  
31.1  
25.8  
20.4  
52.6  
52.6  
50.3  
44.9  
39.5  
34.2  
28.8  
52.0  
52.0  
52.0  
46.7  
41.3  
35.9  
30.6  
95 °F  
--  
--  
NET CAP.  
MBH  
57.6  
5.52  
53.3  
5.43  
49.5  
5.34  
49.3  
5.27  
58.4  
5.69  
54.1  
5.60  
50.2  
5.51  
50.0  
5.43  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
37.1  
32.7  
28.4  
24.0  
19.6  
--  
45.3  
40.9  
36.6  
32.2  
27.8  
23.4  
19.1  
49.5  
48.4  
44.1  
39.8  
35.4  
31.0  
26.6  
49.3  
49.3  
46.4  
42.1  
37.7  
33.3  
29.0  
42.6  
37.2  
31.8  
26.5  
21.1  
--  
51.8  
46.4  
41.1  
35.7  
30.3  
25.0  
19.6  
50.2  
50.2  
49.1  
43.7  
38.3  
33.0  
27.6  
50.0  
50.0  
50.0  
44.7  
39.3  
33.9  
28.6  
105 °F  
--  
--  
NET CAP.  
MBH  
54.6  
6.07  
50.6  
5.97  
46.9  
5.89  
47.1  
5.81  
55.7  
6.26  
51.6  
6.16  
47.9  
6.07  
48.0  
5.99  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
36.0  
31.6  
27.2  
22.8  
18.5  
--  
44.0  
39.7  
35.3  
30.9  
26.5  
22.2  
17.8  
46.9  
46.9  
42.9  
38.5  
34.1  
29.7  
25.4  
47.1  
47.1  
44.2  
39.8  
35.4  
31.0  
26.7  
41.8  
36.4  
31.1  
25.7  
20.3  
--  
51.0  
45.6  
40.3  
34.9  
29.5  
24.2  
18.8  
47.9  
47.9  
47.9  
42.5  
37.1  
31.8  
26.4  
48.0  
48.0  
48.0  
42.7  
37.3  
31.9  
26.6  
115 °F  
--  
--  
NET CAP.  
MBH  
51.6  
6.62  
47.9  
6.51  
44.4  
6.43  
44.9  
6.35  
52.9  
6.82  
49.1  
6.71  
45.5  
6.62  
46.0  
6.54  
TOTAL POWER  
INPUT kW  
86  
83  
80  
77  
74  
71  
68  
34.8  
30.5  
26.1  
21.7  
17.3  
--  
42.8  
38.4  
34.0  
29.6  
25.3  
20.9  
16.5  
44.4  
45.5  
41.6  
37.2  
32.8  
28.4  
24.1  
44.9  
44.9  
41.9  
37.5  
33.1  
28.7  
24.4  
41.0  
35.6  
30.3  
24.9  
19.6  
--  
50.2  
44.8  
39.5  
34.1  
28.7  
23.4  
18.0  
45.5  
45.5  
46.7  
41.3  
35.9  
30.6  
25.2  
46.0  
46.0  
46.0  
40.7  
35.3  
29.9  
24.6  
125 °F  
--  
--  
1.  
These capacities are net capacities (the indoor fan heat is deducted).  
ALL SENSIBLE CAPACITY  
14  
Unitary Products Group  
 
036-21366-007-A-1205  
1
TABLE 9: TWO TON AIR PERFORMANCE  
EXTERNAL STAIC PRESSURE - IWG  
.50 .60 .70  
MODEL #  
DNP  
(Cooling/  
Heating)  
.10  
.20  
.30  
.40  
.80  
.90  
1.00 1.10  
MTR  
SPD  
SIDE SUPPLY AIR PERFORMANCE - 208 VOLT  
HI  
-
-
-
-
-
-
-
-
-
-
984 443 894 422 751 390 608 358  
-
-
-
-
-
-
-
-
-
-
-
-
024  
MED 994 333 947 321 901 309 854 297 774 280 695 263 615 246  
-
-
-
-
-
-
-
-
LOW 743 243 700 235 657 226 614 218  
-
-
-
-
-
-
-
-
-
-
SIDE SUPPLY AIR BLOWER PERFORMANCE - 230 VOLT  
HI  
-
-
-
-
-
-
-
-
-
-
-
-
929 491 809 473 688 454  
-
-
-
-
-
-
-
-
-
-
-
-
024  
MED  
999 353 944 338 865 319 785 299 706 280  
-
-
-
-
-
-
-
-
LOW 998 372 906 333 813 294 721 255 651 241  
-
-
-
-
BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208 VOLT  
HI  
-
-
-
-
-
-
-
-
-
-
886 398 805 380 676 351 547 322  
-
-
-
-
-
-
-
-
-
-
-
-
024  
MED 895 300 853 289 811 278 769 267 697 252 625 237 554 221  
-
-
-
-
-
-
-
-
LOW 669 219 630 211 591 204 553 196  
-
-
-
-
-
-
-
-
-
-
BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 VOLTS  
HI  
-
-
-
-
-
-
-
-
-
-
-
-
836 442 728 425 620 409  
-
-
-
-
-
-
-
-
-
-
-
-
024  
1.  
MED  
899 318 850 304 778 287 707 269 635 252  
-
-
-
-
-
-
-
-
LOW 898 335 815 300 732 265 649 230 586 217  
-
-
-
-
Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer  
Unitary Products Group  
15  
 
036-21366-007-A-1205  
1
TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS  
EXTERNAL STATIC PRESSURE - IWG  
MODEL #  
DNP  
MODE  
(COOLING / HEATING)  
CFM  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.0  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
COOLING  
(FACTORY SETTING)  
030  
030  
030  
030  
036  
036  
036  
036  
036  
042  
042  
042  
042  
048  
048  
048  
048  
048  
060  
060  
060  
060  
1000  
1250  
850  
248  
342  
169  
300  
354  
442  
207  
383  
442  
410  
450  
450  
388  
427  
476  
458  
476  
476  
439  
659  
439  
576  
576  
298  
385  
217  
338  
396  
503  
231  
432  
503  
457  
500  
500  
433  
476  
532  
511  
532  
532  
526  
809  
526  
757  
757  
325  
431  
237  
378  
436  
563  
254  
478  
563  
504  
553  
553  
478  
525  
587  
564  
587  
587  
559  
814  
559  
788  
788  
365  
474  
278  
416  
511  
606  
298  
543  
606  
575  
641  
641  
545  
599  
687  
654  
687  
687  
636  
946  
636  
872  
872  
385  
510  
302  
447  
548  
648  
320  
581  
648  
646  
729  
729  
612  
673  
786  
744  
786  
786  
716  
1001  
716  
929  
929  
411  
562  
334  
493  
599  
685  
349  
628  
685  
687  
798  
798  
652  
716  
872  
814  
872  
872  
748  
1053  
748  
979  
979  
470  
614  
374  
539  
641  
721  
-
498  
657  
401  
576  
677  
774  
-
500  
694  
431  
609  
721  
826  
-
COOLING  
(FIELD SETTING)  
HEATING (2 TUBE)  
(FACTORY SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
1100  
1200  
1350  
700  
COOLING  
(FACTORY SETTING)  
COOLING  
(FIELD SETTING)  
HEATING (2 TUBE)  
(FACTORY SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
1250  
1350  
1350  
1500  
1500  
1275  
1400  
1600  
1525  
1600  
1600  
1500  
1800  
1500  
1700  
1700  
-
-
-
HEATING (4 TUBE)  
(FACTORY SETTING)  
-
-
-
COOLING  
(FACTORY SETTING)  
729  
830  
830  
691  
759  
958  
-
780  
872  
872  
739  
812  
994  
-
830  
939  
939  
787  
865  
1030  
-
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
COOLING  
(FACTORY SETTING)  
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
-
-
-
HEATING (5 TUBE)  
(FACTORY SETTING)  
-
-
-
COOLING  
(FACTORY SETTING)  
816  
1124  
816  
1000  
1000  
884  
1176  
884  
1121  
1121  
941  
1180  
941  
1188  
1188  
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
HEATING (5 TUBE)  
(FACTORY SETTING)  
060  
1.  
Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11  
and 12.  
16  
Unitary Products Group  
 
036-21366-007-A-1205  
1
TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS  
EXTERNAL STATIC PRESSURE - IWG  
MODEL #  
DNP  
MODE  
(COOLING / HEATING)  
CFM  
.20  
.30  
.40  
.50  
.60  
.70  
.80  
.90  
1.0  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
WATTS  
COOLING  
(FACTORY SETTING)  
030  
030  
030  
030  
036  
036  
036  
036  
036  
042  
042  
042  
042  
048  
048  
048  
048  
048  
060  
060  
060  
060  
1000  
1250  
850  
248  
342  
169  
300  
354  
442  
207  
383  
442  
410  
450  
450  
388  
427  
476  
458  
476  
476  
345  
567  
345  
504  
504  
298  
385  
217  
338  
396  
503  
231  
432  
503  
457  
500  
500  
433  
476  
532  
511  
532  
532  
487  
663  
487  
603  
603  
325  
431  
237  
378  
436  
563  
254  
478  
563  
504  
553  
553  
478  
525  
587  
564  
587  
587  
554  
794  
554  
698  
698  
365  
474  
278  
416  
511  
606  
298  
543  
606  
575  
641  
641  
545  
599  
687  
654  
687  
687  
569  
917  
569  
771  
771  
385  
510  
302  
447  
548  
648  
320  
581  
648  
646  
729  
729  
612  
673  
786  
744  
786  
786  
654  
948  
654  
831  
831  
411  
562  
334  
493  
599  
685  
349  
628  
685  
687  
798  
798  
652  
716  
872  
814  
872  
872  
745  
1015  
745  
1043  
1043  
470  
614  
374  
539  
641  
721  
-
498  
657  
401  
576  
677  
774  
-
500  
694  
431  
609  
721  
826  
-
COOLING  
(FIELD SETTING)  
HEATING (2 TUBE)  
(FACTORY SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
1100  
1200  
1350  
700  
COOLING  
(FACTORY SETTING)  
COOLING  
(FIELD SETTING)  
HEATING (2 TUBE)  
(FACTORY SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
1250  
1350  
1350  
1500  
1500  
1275  
1400  
1600  
1525  
1600  
1600  
1500  
1800  
1500  
1700  
1700  
-
-
-
HEATING (4 TUBE)  
(FACTORY SETTING)  
-
-
-
COOLING  
(FACTORY SETTING)  
729  
830  
830  
691  
759  
958  
-
780  
872  
872  
739  
812  
994  
-
830  
939  
939  
787  
865  
1030  
-
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
COOLING  
(FACTORY SETTING)  
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
-
-
-
HEATING (5 TUBE)  
(FACTORY SETTING)  
-
-
-
COOLING  
(FACTORY SETTING)  
784  
1048  
784  
1102  
1102  
835  
1155  
835  
1155  
1155  
896  
1175  
896  
1202  
1202  
COOLING  
(FIELD SETTING)  
HEATING (3 TUBE)  
(FACTORY SETTING)  
HEATING (4 TUBE)  
(FACTORY SETTING)  
HEATING (5 TUBE)  
(FACTORY SETTING)  
060  
1.  
Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11  
and 12.  
Unitary Products Group  
17  
 
036-21366-007-A-1205  
TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON  
RESISTANCE, IWG  
DESCRIPTION  
CFM  
1,100  
.05  
500  
.01  
600  
.01  
.00  
.02  
700  
.01  
800  
.02  
900  
.03  
1,000  
.04  
1,200  
.06  
1,300  
.07  
1,400  
.08  
1,500  
.09  
1,600  
.09  
WET EVAPORATOR COIL  
1
.00  
.00  
.01  
.01  
.01  
.01  
.02  
.03  
.04  
.05  
.06  
ECONOMIZER  
FILTER FRAME KIT  
.01  
.04  
.06  
.08  
.10  
.13  
.16  
.17  
.18  
.19  
.20  
1.  
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air  
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON  
RESISTANCE, IWG  
DESCRIPTION  
CFM  
1,100  
.02  
1,200  
.03  
1,300  
.04  
1,400  
.05  
1,500  
.06  
1,600  
.07  
1,700  
.07  
1,800  
.08  
1,900  
.09  
2,000  
.09  
WET EVAPORATOR COIL  
1
.02  
.02  
.02  
.03  
.03  
.04  
.04  
.04  
.05  
.05  
ECONOMIZER  
FILTER FRAME KIT  
.04  
.04  
.05  
.05  
.06  
.07  
.08  
.09  
.10  
.11  
1.  
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air  
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
NOTE:  
HEAT ANTICIPATOR  
SHOULD BE SET AT 0.35  
AMPS FOR ALL MODELS.  
THERMOSTAT  
UNIT TERMINAL STRIP  
** = Minimum wire size of 18 AWG  
wire should be used for all  
field installed 24 volt wire.  
**  
R
R
G
Y
G
Y
24 VOLT  
TRANSFORMER  
W
C
W
C
PROGRAMMABLE  
THERMOSTAT ONLY  
FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING  
18  
Unitary Products Group  
     
036-21366-007-A-1205  
C
O
N
T
A
C
T
O
R
C
O
N
T
A
C
T
O
R
F
I
E
L
D
-
S
U
P
P
L
I
E
D
F
I
E
L
D
-
S
U
P
P
L
I
E
D
D
I
S
C
O
N
N
E
C
T
D
I
S
C
O
N
N
E
C
T
S
P
P
S
I
H
O
U
N
G
L
E
A
P
S
P
E
L
T
P
P
S
H
R
E
S
E
E
W
E
R
H
O
U
A
P
G
R
O
U
N
D
R
D
T
E
A
F
T
E
A
R
T
O
E
L
E
C
T
R
I
C
A
L
Y
W
E
R
G
R
O
U
N
D
L
U
G
T
A
B
L
E
S
T
O
S
I
Z
E
P
L
Y
R
D
T
E
A
F
T
E
A
R
T
O
E
L
E
C
T
R
I
C
A
L
L
U
G
H
E
D
I
S
C
O
N
N
E
C
T
T
A
B
L
E
S
T
O
S
I
Z
E
H
E
D
I
S
C
O
N
N
E
C
T
FIGURE 4 - POWER WIRING FIELD DIAGRAM  
TABLE 14: ELECTRICAL DATA  
VOLTAGE  
SUPPLY  
AIR  
BLOWER  
MOTOR  
FLA  
MAX.  
HACR  
BREAKER POWER  
SIZE,  
MAX.  
COND.  
FAN  
MOTOR,  
FLA  
COMPRESSOR  
1
MINIMUM  
CIRCUIT  
AMPACITY  
UNIT  
LIMITATIONS  
MODEL  
FUSE  
SIZE,  
TRANSFORMER  
SIZE (VA)  
POWER SUPPLY  
DNP  
FACTOR  
2
MIN.  
MAX.  
RLA  
LRA  
AMPS  
AMPS  
024  
030  
030  
030  
036  
036  
036  
036  
042  
042  
042  
042  
048  
048  
048  
048  
060  
060  
060  
060  
208/230-1-60  
208/230-1-60  
208/230-3-60  
460-3-60  
187  
187  
187  
432  
187  
187  
432  
540  
187  
187  
432  
540  
187  
187  
432  
540  
187  
187  
432  
540  
253  
253  
253  
504  
253  
253  
504  
630  
253  
253  
504  
630  
253  
253  
504  
630  
253  
253  
504  
630  
8.0  
13.6  
8.6  
5.7  
17.2  
11.4  
5.7  
4.7  
20  
53.5  
67  
1.1  
1.1  
1.1  
0.6  
1.1  
1.1  
0.6  
0.6  
1.3  
1.3  
0.7  
0.6  
1.9  
1.9  
1.0  
0.8  
2.8  
2.8  
2.8  
2.8  
2.6  
6.8  
6.8  
6.8  
6.8  
6.8  
6.8  
6.8  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
9.1  
16.5  
24.9  
18.7  
13.4  
29.4  
22.2  
14.8  
13.3  
35.4  
27.8  
18.5  
16.8  
39.5  
26.5  
18.4  
17.3  
43.2  
33.5  
22.6  
21.2  
20  
35  
25  
20  
45  
30  
20  
20  
50  
40  
25  
25  
60  
35  
25  
25  
60  
45  
30  
30  
20  
35  
25  
20  
45  
30  
20  
20  
50  
40  
25  
25  
60  
35  
25  
25  
60  
45  
30  
30  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
40  
40  
75  
75  
40  
75  
75  
75  
40  
75  
75  
75  
40  
75  
75  
75  
40  
75  
75  
75  
55  
39  
208/230-1-60  
208/230-3-60  
460-3-60  
88  
77  
39  
575-3-60  
31  
208/230-1-60  
208/230-3-60  
460-3-60  
104  
88  
13.9  
6.4  
5.4  
23.4  
13  
44  
575-3-60  
34  
208/230-1-60  
208/230-3-60  
460-3-60  
126  
93  
6.4  
5.1  
25  
46.5  
37.2  
150  
123  
70  
575-3-60  
208/230-1-60  
208/230-3-60  
460-3-60  
17.3  
8.4  
7.0  
575-3-60  
53  
1.  
Rated in accordance with ARI Standard 110, utilization range “A”.  
Dual element, time delay type.  
2.  
Unitary Products Group  
19  
   
036-21366-007-A-1205  
All dimensions are in inches.  
They are subject to change with-  
out notice. Certified dimensions  
will be provided upon request.  
FIGURE 5 - UNIT DIMENSIONS - FRONT  
TABLE 15: UNIT DIMENSIONS FRONT  
1 2  
TABLE 16: UNIT MINIMUM CLEARANCES  
DIMENSION  
UNIT SIZE  
CLEARANCES  
“A”  
“B”  
FRONT  
BACK  
36”  
0”  
024, 030, 036  
042, 048, 060  
33-1/2  
41-1/2  
18-1/4  
23-1/8  
LEFT SIDE (Filter-Access)  
RIGHT SIDE  
24”  
12”  
0”  
3
BELOW UNIT  
4
36” (For Condenser Air Discharge)  
ABOVE UNIT  
1.  
A 1” clearance must be provided between any combus-  
tible material and the supply air ductwork.  
2.  
3.  
4.  
The products of combustion must not be allowed to  
accumulate within a confined space and recirculate.  
Units may be installed on combustible floors made from  
wood or class A, B, or C roof covering material.  
Units must be installed outdoors. Overhanging struc-  
tures or shrubs should not obstruct condenser air dis-  
charge outlet.  
20  
Unitary Products Group  
     
036-21366-007-A-1205  
FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM  
1
4
-
1
/
2
S
A
I
I
D
R
E
S
U
P
P
L
Y
O
P
E
N
I
N
G
2
8
-
3
/
8
C
O
N
D
E
N
S
E
R
C
O
I
L
1
4
-
1
/
2
B
A
C
K
B
O
T
T
O
M
S
U
P
P
L
Y
A
I
R
O
P
E
N
I
N
G
3
-
3
/
8
S
I
D
E
R
E
T
U
R
N
A
I
R
O
P
E
N
I
N
G
1
4
-
1
/
2
3
-
1
/
2
4
1
-
3
/
4
1
5
1
5
1
-
3
/
4
1
5
B
O
T
T
O
M
R
E
T
U
R
N
A
I
R
O
P
E
N
I
N
G
3
-
1
/
2
2
9
-
9
/
1
6
1
-
3
/
4
FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM  
Unitary Products Group  
21  
   
036-21366-007-A-1205  
C
O
N
T
O
R
O
N
L
W
I
R
I
N
G
T
O
P
O
W
E
R
S
U
P
P
Y
T
H
I
D
O
O
R
F
I
E
L
D
S
U
P
P
L
I
E
D
T
E
R
M
O
S
T
A
T
D
I
S
C
O
N
N
E
C
T
S
W
I
T
C
H
L
O
C
A
T
E
D
T
O
R
E
A
R
O
F
U
N
I
T
R
E
T
U
R
N
A
I
R
D
U
C
T
S
U
P
P
L
Y
A
I
R
D
U
C
T
T
O
G
A
S
U
P
P
L
Y
L
I
N
E
M
A
N
U
A
L
G
A
S
S
H
U
T
-
O
F
F
V
A
L
V
E
FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION  
M
A
N
U
A
L
G
A
S
S
H
U
T
-
O
F
F
V
A
L
V
E
F
I
E
L
D
S
U
P
P
L
I
E
D
D
I
S
C
O
U
N
N
E
C
T
S
W
I
T
C
H
M
O
N
T
E
D
O
N
U
N
I
T
T
O
P
O
W
E
R
S
U
P
P
L
Y
T
O
G
A
S
S
U
P
P
L
Y
L
I
N
E
C
O
N
T
R
O
L
W
I
R
I
N
G
T
O
I
N
D
O
O
R
T
H
E
R
M
O
S
T
A
T
R
E
T
U
R
N
A
I
R
D
U
C
T
S
U
P
P
L
Y
A
I
R
D
U
C
T
FIGURE 9 - TYPICAL ROOF CURB INSTALLATION  
22  
Unitary Products Group  
   
036-21366-007-A-1205  
R
O
O
F
C
U
R
B
I
R
N
S
T
A
L
L
A
T
I
O
N
E
A
R
D
U
C
T
R
I
B
O
O
F
C
U
R
B
N
S
T
A
L
L
A
T
I
O
N
O
T
T
O
M
D
U
C
T
S
I
L
A
B
O
N
G
R
O
U
N
D
N
S
T
A
L
L
A
T
I
O
N
FIGURE 10 - TYPICAL DUCT APPLICATIONS  
TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY  
CORNER WEIGHTS  
(location, lbs.)  
SHIPPING  
WEIGHT  
(lbs.)  
OPERATING  
WEIGHT  
(lbs.)  
ROOF  
CURB  
(lbs.)  
UNIT  
SIZE  
ECONOMIZER  
(lbs.)  
“A”  
100  
133  
“B”  
96  
“C”  
98  
“D”  
101  
104  
024, 030, 036  
042, 048, 060  
400  
475  
395  
470  
8” - 70  
14” - 75  
40  
130  
102  
FIGURE 11 - UNIT CENTER OF GRAVITY  
Unitary Products Group  
23  
     
036-21366-007-A-1205  
R
E
C
D
O
U
M
M
E
N
D
E
D
C
T
S
I
Z
E
1
7
-
1
/
2
"
X
1
6
-
3
/
4
"
4
2
-
2
/
3
4
5
-
1
/
8
4
0
-
3
/
4
1
7
-
5
/
8
1
7
-
1
/
4
4
3
-
1
/
4
3
-
1
/
2
O
P
E
N
I
N
G
F
O
R
2
2
R
E
T
U
R
N
A
I
R
D
U
C
T
O
P
E
N
I
N
G
F
O
R
1
S
U
P
P
L
Y
A
I
R
D
U
C
T
R
E
C
D
O
U
M
M
E
N
D
E
D
C
T
S
I
Z
E
1
7
-
1
/
8
"
X
2
1
-
1
/
2
"
1
4
1
FIGURE 12 - ROOF CURB DIMENSIONS  
1
"
3
/
4
"
X
1
"
W
I
D
E
G
A
S
K
E
T
I
N
G
F
O
R
C
U
R
B
F
R
A
M
E
A
N
D
A
L
L
D
U
C
T
S
U
P
P
O
R
T
S
U
R
F
A
C
E
S
U
N
I
T
B
A
S
E
U
N
I
T
B
A
S
E
R
A
I
L
W
O
O
D
N
A
I
L
E
R
C
O
U
N
T
E
R
F
L
A
S
H
I
N
G
8
"
M
I
N
.
A
B
O
V
E
F
I
N
I
S
H
E
D
R
O
O
F
1
4
"
C
A
N
T
S
T
R
I
P
C
U
R
B
F
R
A
M
E
I
N
S
U
L
A
T
I
O
N
A
N
D
R
O
O
F
I
N
G
M
A
T
E
R
I
A
L
I
N
S
U
L
A
T
I
O
N
R
O
O
F
D
E
C
T
A
N
D
R
O
O
F
I
N
G
M
A
T
E
R
I
A
L
FIGURE 13 - ROOF CURB CROSS SECTION  
1. 8” Roof curb also available  
24  
Unitary Products Group  
   
036-21366-007-A-1205  
FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY)  
Unitary Products Group  
25  
 
036-21366-007-A-1205  
N E U T R A L  
DELAY  
ON  
OFF  
DELAY  
OFF  
FIGURE 15 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-1-60 POWER SUPPLY)  
26  
Unitary Products Group  
 
036-21366-007-A-1205  
FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY)  
Unitary Products Group  
27  
 
036-21366-007-A-1205  
N E U T R A L  
DELAY  
ON  
OFF  
DELAY  
OFF  
FIGURE 17 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-3-60 POWER SUPPLY)  
28  
Unitary Products Group  
 
036-21366-007-A-1205  
FIGURE 18 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY)  
Unitary Products Group  
29  
 
036-21366-007-A-1205  
FIGURE 19 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY)  
30  
Unitary Products Group  
 
036-21366-007-A-1205  
FIGURE 20 - TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY)  
Unitary Products Group  
31  
 
036-21366-007-A-1205  
5. Select indoor blower cooling speed from unit wiring dia-  
gram Table 1. Heating speed is preset at the factory.  
TYPICAL WIRING DIAGRAM NOTES  
1. All field wiring to be accomplished following city, local  
and/or national codes in effect at time of installation of  
this unit.  
6. If both LR and ASCT are present, wire 801/BL and 805/  
BL are connected to ASCT-3 if LR only is present wire  
801/BL and 805/BL are connected to M1 coil. If ASCT  
only is present wire 202/Y is connected to ASCT-3. If  
neither LR or ASCT are present, Wire 202/Y is connect  
to M1 coil.  
2. Caution: Label all wires prior to disconnection when ser-  
vicing controls. Wiring errors can cause improper and  
dangerous operation if any of the wire as supplied with  
this unit must be removed it must be replaced with type  
105°C, 600V wire or equivalent clearly renumbered for  
identification. Verify proper operation after servicing.  
7. Shunt contact also used with crankcase heater.  
(Optional).  
3. Motors are inherently protected.  
4. See unit nameplate for maximum fuse size and minimum  
circuit ampacity.  
Open all disconnects before servicing this unit.  
LEGEND :  
ALS  
AUXILLARY LIMIT SWITCH  
ANTI-SHORT CYCLE TIMER  
(OPTIONAL ACCESSORY)  
COMPR COMPRESSOR  
ASCT  
EAC  
ELECTRIC AIR CLEANER RELAY OUTPUT  
ON CONTROL BOARD, 24-1-60, 18VA MAX.  
FS  
FREEZESTAT SWITCH (OPTIONAL ACCESSORY)  
OPEN @ 250 F  
HP  
HIGH PRESSURE SWITCH (OPTIONAL  
ACCESSORY) OPENS @ 380 PSIG  
HOT SURFACE TO PILOT  
HSP  
HUM  
HUMIDIFER RELAY OUTPUT ON CONTROL  
BOARD, 24-1-60, 18VA MAX.  
LP  
LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)  
OPEN @ 7 PSIG  
LR  
LS  
M1  
M2  
PS  
LOCK OUT RELAY (OPTIONAL ACCESSORY)  
LIMIT SWITCH  
CONTACTOR, COMPR. & O.D.FAN  
CONTACTOR, DRAFT INDUCER MOTOR  
PRESSURE SWITCH MAKES @  
.193 IWC NOM. (.33 IWC MAX.)  
RC1/RC2 COMPR. START & OUTDOOR FAN RUN CAPACITOR  
RS  
T1  
ROLL OUT SWITCH  
TRANSFORMER, 24V, 40VA  
TRANSFORMER, 480/240 VOLT  
TERMINAL BLOCK, 24V, I.D.  
MOTOR "SPEED" CONNECTION  
IDENTIFIED TERMINAL ON CAPACITOR  
ROOM THERMOSTAT 24V CONNECTIONS  
TB1 ON CONTROL BOARD  
T2  
TB2  
FACTORY WIRING AND DEVICES  
OPTIONAL WIRING AND DEVICES  
FIELD WIRING  
DNP LEGEND WIRING DIA.  
FIGURE 21 - TYPICAL WIRING DIAGRAM LEGEND  
32  
Unitary Products Group  
   
036-21366-007-A-1205  
without modification to building structure, duct work and base  
unit. Condensate pan shall be internally sloped and conform  
to ASHRAE 62-89 self-draining standards, with 3/4” NPTI  
copper, ridged mount connection.  
MECHANICAL SPECIFICATIONS  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility. YORK’s  
DNP is a unit that gives you the flexibility and choices you  
need in today’s market. These packaged cooling/heating air  
conditioners are designed for outdoor installation. Only utility  
and duct connections are required at the point of installation.  
The gas fired heaters have aluminized steel tubular heat  
exchangers and hot surface to pilot ignition. They are avail-  
able in natural gas with field conversion to propane.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
Fan shall be direct drive, multi-speed design. Job site  
selected (BHP) brake horsepower shall not exceed the  
motors nameplate horsepower rating. Fan wheel shall be  
double-inlet type with forward-curved blades, dynamically  
balanced to operate smoothly throughout the entire range of  
operation. Airflow design shall be constant air volume. Bear-  
ings shall be sealed and permanently lubricated for longer life  
and no maintenance. Fan assembly shall be “Slip Track”  
(slide-out) design for easy removal and cleaning.  
DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling/Gas Heating units, designed for outdoor mounted  
installation. For SEER ratings, refer to technical literature.  
They shall have built in, equal size, field convertible duct  
connections for down discharge supply/return or horizontal  
discharge supply/return. The units shall be factory wired,  
piped, charged with R-22 refrigerant and factory tested prior  
to shipment. All unit wiring shall be both numbered and  
color coded. All units shall be manufactured in a facility cer-  
tified to ISO 9001 standards, and the cooling performance  
shall be rated in accordance with DOE and ARI test proce-  
dures. The heating performance shall be rated to DOE and  
GAMA test procedures. Units shall be CSA listed and classi-  
fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/  
CAN/CSA No. 236-M90 conditions.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to cor-  
rosion resistant steel spider bracket and shall be statically  
balanced for smooth operation. The outdoor fan motor shall  
be totally enclosed with permanently lubricated bearings and  
internally protected against overload conditions.  
REFRIGERANT COMPONENTS  
Compressors:  
a. Shall be fully hermetic type, direct drive, internally  
protected with internal high-pressure relief and over  
temperature protection. The hermetic motor shall be  
suction gas cooled and have a voltage range of + or  
- 10% of the unit nameplate voltage.  
UNIT CABINET  
Unit cabinet shall be constructed of G90 galvanized steel,  
with exterior surfaces coated with a non-chalking, powdered  
paint finish, certified at 1000 hours salt spray test per ASTM-  
B117 standards. The unit top shall be a single piece “Water  
Shed” design, with drip edges and no-seam corners to pro-  
vide optimum water integrity. Unit shall have a rigidly  
mounted condenser coil guard to provide protection from  
objects and personnel after installation. Indoor blower section  
shall be insulated with up to 3/4” thick, aluminum, foil faced  
insulation, fastened to prevent insulation from entering the air  
stream. Cabinet panels shall be “large” size, easily remov-  
able for servicing and maintenance, with built-in lift handles.  
Unit shall be built on a formed, “Super-Structure” design base  
pan, with embossments at critical points to add strength,  
rigidity and aid in minimizing sound. Full perimeter base rails  
shall be provided to assure reliable transit of equipment,  
overhead rigging, for truck access and proper sealing on roof  
curb applications. Base rails shall be removable, when  
required, to lower unit height. Filters shall be furnished and  
be accessible through a removable access door, sealed air-  
tight. Units vertical discharge and return duct configuration  
shall be designed to fit between standard 24” O.C. beams  
b. Shall have internal isolation and sound muffling to  
minimize vibration and noise, and be externally iso-  
lated on a dedicated, independent mounting.  
Coils:  
a. Evaporator and condenser coils shall have alumi-  
num plate fins mechanically bonded to seamless  
internally enhanced copper tubes with all joints  
brazed.  
b. Evaporator coil shall be of the direct expansion,  
blow through design, while condenser coil shall be  
draw through design.  
Refrigerant Circuit and Refrigerant Safety Components:  
a. Shall include independent thermal expansion  
devices (TXV).  
b. Shall include filter/strainer to eliminate any foreign  
matter.  
Unitary Products Group  
33  
 
036-21366-007-A-1205  
UNIT OPERATING CHARACTERISTICS  
ELECTRICAL REQUIREMENTS  
Unit shall be capable of starting and running at 125º F out-  
door temperature, exceeding maximum load criteria ARI  
Standard 210/240. The compressor, with standard controls,  
shall be capable of operation down to 45º F outdoor tempera-  
ture. Accessory low ambient kit shall be available for opera-  
tion to 0º F.  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
34  
Unitary Products Group  
036-21366-007-A-1205  
Unitary Products Group  
35  
Subject to change without notice. Printed in U.S.A.  
036-21366-007-A-1205  
Copyright © 2005 by Unitary Products Group. All rights reserved.  
Supersedes: 036-21366-006-A-1005  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Mitsubishi Electronics Pffy Nemu A User Manual
Philips Sbc Sc 477 User Manual
Precisionaire Pb1900 0604 User Manual
Ricoh Aficio 2025 User Manual
Ricoh Aficio 8070 User Manual
Samsung As24a1 2 Rc User Manual
Samsung Aw0510b User Manual
Samsung Mfp 29ppm Printer Slm2875fdxaa User Manual
Spt Wa 1211s User Manual
Toshiba All In One Printer E Studio202s User Manual