York Champion D2eb User Manual

®
CHAMPION® SERIES  
SINGLE PACKAGE AIR CONDITIONERS  
ELECTRIC/ELECTRIC, AIR-COOLED  
Supersedes: Nothing  
174065-YIM-A-0206  
INSTALLATION INSTRUCTION  
MODELS D2EB018 THRU 060  
1-1/2 THRU 5 TON  
(8.8 - 9.4 EER)  
EXPORT  
damage should be noted on the carrier's freight bill. Aseparate  
request for inspection by the carrier's agent should be made in  
writing. Refer to Form 50.15-NM for additional information.  
GENERAL  
Model D2EB units are factory assembled cooling only air condi-  
tioners designed for outdoor installation on a rooftop or a slab.  
Field-installed electric heater accessories are available to provide  
electric heat combined with electric cooling. All units and heaters  
are certified by CSA.  
REFERENCE  
Additional information on the design, installation, operation  
and service of this equipment is available in the following refer-  
ence forms:  
The units are completely assembled on rigid, but easily remov-  
able base rails. All piping, refrigerant charge, and electrical wir-  
ing is factory installed and tested. The units require only electric  
power and duct connections at the point of installation.  
174065  
-General Installation  
511.26-N1.1V -Electric Heater Accessory  
The electric heaters have nickel-chrome resistance wire ele-  
ments and utilize single point power connection.  
REPLACEMENT PARTS  
INSPECTION  
Refer to Replacement Parts Manual for complete listing of  
replacement parts on this equipment.  
As soon as a unit is received, it should be inspected for possible  
damage during transit. If damage is evident, the extent of the  
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make  
the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury  
and/or equipment damage may result if installation procedure is not handled properly.  
CAUTION  
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH  
THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE  
LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED  
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.  
WARNING  
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE  
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY  
OR PROPERTY DAMAGE.  
174065-YIM-A-0206  
CLEARANCES  
FILTERS  
All units require certain clearances for proper operation and  
service. Refer to Figure 3 for the clearances required for com-  
bustion, construction, servicing and proper unit operation.  
Single phase units are shipped without a filter and is the responsi-  
bility of the installer to secure a filter in the return air ductwork or  
install a Filter/Frame Kit (1FF0114).  
WARNING:Do not permit overhanging structures or shrubs to  
obstruct the condenser air discharge outlet.  
A filter rack and a filters are standard on three phase units.  
Filters must always be used and must be kept clean. When fil-  
ters become dirt laden, insufficient air will be delivered by the  
blower, decreasing your units efficiency and increasing operat-  
ing costs and wear-and-tear on the unit and controls.  
DUCT WORK  
These units are adaptable to downflow use as well as rear sup-  
ply and return air duct openings. To convert to downflow, use  
the following steps:  
Filters should be checked monthly especially since this unit  
may be used for both heating and cooling.  
1. Remove the duct covers found in the bottom return and  
supply air duct openings. There are four (4) screws secur-  
ing each duct cover (save these screws to use later).  
CONDENSATE DRAIN  
2. Install the duct covers, removed in step one, to the rear sup-  
ply and return air duct openings. Secure with the four (4)  
screws used in step one.  
A condensate trap is required to be installed in the condensate  
drain. The plumbing must conform to local codes. Use a seal-  
ing compound on male pipe threads. Install the condensate  
3. Seal the duct covers with silicone caulking.  
3
drain line ( “ NPTF) to spill into an open drain.  
4
Downflow units must have an L-shaped supply duct without  
any outlets or registers located directly below the supply outlet  
of the unit.  
SERVICE ACCESS  
Access to all serviceable components is provided by the follow-  
ing removable panels:  
Duct work should be designed and sized according to the  
methods of the Air Conditioning Contractors of America  
(ACCA), as set forth in their Manual D.  
Blower service access  
Electrical/filter access  
Compressor service access  
A closed return duct system shall be used. This shall not pre-  
clude use of economizers or ventilation air intake. Flexible  
joints may be used in the supply and return duct work to mini-  
mize the transmission of noise.  
Refer to Figure 3 for location of these access panels and mini-  
mum clearance.  
THERMOSTAT  
CAUTION: When fastening duct work to the side duct flanges on  
the unit, insert the screws through the duct flanges only.  
DO NOT insert the screws through the casing. Outdoor  
duct work must be insulated and waterproofed.  
The room thermostat should be located on an inside wall ap-  
proximately 56" above the floor where it will not be subject to  
drafts, sun exposure or heat from electrical fixtures or appli-  
ances. Follow manufacturer's instructions enclosed with the  
thermostat for general installation procedure. Four or five color  
coded insulated wires (minimum #18 AWG) should be used to  
connect thermostat to unit. See Figure 2.  
NOTE: Be sure to note supply and return openings.  
Refer to Figure 3 for information concerning rear and bottom  
supply and return air duct openings.  
TABLE 3 - PHYSICAL DATA  
DEB  
MODELS  
018  
024  
030  
036  
042  
048  
060  
11 x 10  
1
CENTRIFUGAL BLOWER (Dia. x Wd. in.)  
FAN MOTOR HP (Three Speed)  
ROWS DEEP  
9 X 6  
1
2
10 X 8  
1
2
10 X 8  
1
2
10 x 8  
3
4
11 X 10  
11 x 10  
EVAPORATOR  
BLOWER  
3
4
3
4
2
13  
2
15  
2
15  
2
15  
2
15  
2
13  
3
EVAPORATOR  
COIL  
FINS PER INCH  
16  
FACE AREA (Sq. Ft.)  
PROPELLER DIA. (in.)  
FAN MOTOR HP  
2.19  
2.81  
4.38  
4.38  
4.38  
5.62  
5.26  
22  
1
4
22  
1
4
22  
1
4
22  
1
4
22  
1
4
22  
1
4
22  
1
4
CONDENSER  
FAN  
NOM. CFM TOTAL  
1,800  
1
2,200  
1
2,400  
1
2,400  
1
2,400  
1
2,800  
1
2,800  
1
ROWS DEEP  
CONDENSER  
COIL  
FINS PER INCH  
18  
16  
20  
18  
16  
13  
20  
FACE AREA (Sq. Ft.)  
REFRIGERANT 22 (lbs./oz.)  
FACE AREA (Sq. Ft. / Qty. / Size)  
8.3  
3 / 4  
8.3  
3 / 5  
8.3  
8.3  
11.7  
4 / 7  
16.4  
5 / 15  
16.4  
5 / 15  
CHARGE  
FILTER  
3 / 13  
3 / 10  
2.14 / 2 / 14" x 22"  
Recip Recip Recip  
COMPRESSOR HERMETIC Type, (Qty. = 1)  
Recip  
Recip  
Scroll  
Scroll  
Unitary Products Group  
3
174065-YIM-A-0206  
POWER AND CONTROL WIRING  
Electrical line must be sized properly to carry the load. Each  
unit must be wired with a separate branch circuit fed directly  
from the meter panel and properly fused.  
Field wiring to the unit must conform to provisions of the current  
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.  
The unit must be electrically grounded in accordance with local  
codes or, in their absence, with the N.E.C./C.E.C. Voltage toler-  
ances which must be maintained at the compressor terminals  
during starting and running conditions are indicated on the unit  
Rating Plate and Table 3.  
Refer to Figure 2 for typical field wiring and to the appropriate unit  
wiring diagram for control circuit and power wiring information.  
COMPRESSORS  
The wiring entering the cabinet must be provided with me-  
chanical strain relief.  
Units are shipped with compressor mountings factory-adjusted  
for shipping. CAUTION: Loosen compressor mounting bolts  
half turn before operating unit.  
A fused or HACR breaker disconnect switch should be field pro-  
vided for the unit. If any of the wire supplied with the unit must be  
replaced, replacement wire must be of the type shown on the wir-  
ing diagram.  
CONTROL WIRING  
UNIT TERMINAL STRIP  
NOTE:  
THERMOSTAT  
HEAT ANTICIPATOR  
SHOULD BE SET AT 0.25  
AMPS FOR ALL MODELS.  
**  
R
R
** = Minimum wire size of 18 AWG  
wire should be used for all field  
installed 24 volt wire.  
G
G
Y
Y
PROGRAMMABLE  
THERMOSTAT ONLY  
24 VOLT TRANSFORMER  
W
W
*
* = Only required on units with  
supplemental electric heat.  
C
C
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can  
cause improper and dangerous operation. Verify proper operation after servicing.  
POWER WIRING  
REFER TO ELECTRICAL DATA  
TABLES TO SIZE THE DISCON-  
NECT SWITCH, WIRING &  
OVERCURRENT PROTECTION.  
FIG. 2 - TYPICAL FIELD WIRING DIAGRAM  
4
Unitary Products Group  
174065-YIM-A-0206  
TABLE 4 - ELECTRICAL DATA (BASIC UNIT)  
VOLTAGE  
LIMITATIONS COMPRESSOR  
SUPPLY  
AIR  
BLOWER CIRCUIT SIZE, BREAKER POWER  
MAX.  
MINIMUM FUSE  
MAX.  
HACR  
COND.  
FAN  
MOTOR,  
FLA  
UNIT  
MODEL POWER SUP-  
DEB  
TRANSFORMER  
SIZE (VA)  
1
PLY  
MOTOR, AMPACITY AMPS  
FLA  
SIZE, FACTOR  
AMPS  
2
MIN. MAX.  
RLA  
LRA  
018 208/230-1-60 187  
024 208/230-1-60 187  
030 208/230-1-60 187  
036 208/230-1-60 187  
042 208/230-1-60 187  
048 208/230-1-60 187  
060 208/230-1-60 187  
253  
253  
253  
253  
253  
253  
253  
9.0  
48.0  
60.0  
1.1  
1.1  
1.1  
1.1  
1.1  
1.3  
1.3  
2.6  
2.6  
2.6  
3.5  
3.5  
4.0  
4.0  
14.9  
18.1  
22.1  
26.2  
30.2  
35.8  
44.4  
20  
25  
30  
35  
40  
45  
60  
20  
25  
30  
35  
40  
45  
60  
.96  
.96  
.96  
.96  
.96  
.96  
.96  
40  
40  
40  
40  
40  
40  
40  
11.5  
14.7  
17.3  
20.5  
24.4  
28.9  
73.0  
94.0  
120.0  
140.0  
165.0  
= Rated in accordance with ARI Standard 110, utilization range “A”.  
= Dual element, time delay type.  
* = KW listed is for 240 volts, use this table for 208 or 230 volts.  
KW CAP. MULTI-  
ELECTRIC HEAT  
CORRECTION  
FACTORS  
NOMINAL VOLTAGE  
VOLTAGE  
PLIER  
.75  
.92  
208  
230  
240  
Unitary Products Group  
5
174065-YIM-A-0206  
TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)  
COMPRESSOR  
ELECTRIC HEAT ACCESSORY  
SUPPLY  
AIR  
BLOWER  
MOTOR,  
FLA  
COND.  
FAN  
MOTOR  
FLA  
MAX.  
FUSE  
MAX.  
MINIMUM  
CIRCUIT  
AMPACITY  
POWER  
SUPPLY  
HACR2  
SIZE,1 BREAKER  
AMPS  
SIZE  
TOTAL  
AMPS  
RLA  
LRA  
MODEL NO.  
KW  
2NH04500506  
2NH04500706  
1
2
3.8/5.0 *  
5.6/7.5 *  
18.1/20.8  
27.1/31.3  
25.8/29.3  
37.1/42.3  
30/30  
40/45  
30/30  
40/45  
018 208/230-1-60 9.0  
024 208/230-1-60 11.2  
48.0  
60.0  
1.1  
1.1  
2.6  
2.6  
2NH04500506  
2NH04500706  
2NH04501006  
1
2
2
3.8/5.0 *  
5.6/7.5 *  
7.5/10.0 *  
18.1/20.8  
27.1/31.3  
36.1/41.7  
25.8/29.3  
37.1/42.3  
48.4/55.3  
30/30  
40/45  
50/60  
30/30  
40/45  
50/60  
2NH04500506  
2NH04500706  
2NH04501006  
2NH04501506  
1
2
2
2
3.8/5.0 *  
5.6/7.5 *  
7.5/10.0 *  
11.3/15.0 *  
18.1/20.8  
27.3/31.3  
36.1/41.7  
54.2/62.5  
25.8/29.3  
37.1/42.3  
48.4/55.3  
71.0/81.4  
30/30  
40/45  
50/60  
80/90  
30/30  
40/45  
50/60  
80/90  
030 208/230-1-60 12.0  
036 208/230-1-60 17.3  
042 208/230-1-60 20.5  
73.0  
94.0  
1.1  
1.1  
1.1  
2.6  
3.5  
3.5  
2NH04501006  
2NH04501506  
2
2
7.5/10.0 *  
11.3/15.0 *  
36.1/41.7  
54.2/62.5  
49.5/56.5  
72.1/82.5  
50/60  
80/90  
50/60  
80/90  
2NH04500506  
2NH04500706  
2NH04501006  
2NH04501506  
1
2
2
2
3.8/5.0 *  
5.6/7.5 *  
7.5/10.0 *  
11.3/15.0 *  
18.1/20.8  
27.1/31.3  
36.1/41.7  
54.2/62.5  
30.2/30.4  
38.2/43.4  
49.5/56.5  
72.1/82.5  
40/40  
50/50  
50/60  
80/90  
40/40  
50/50  
50/60  
80/90  
120.0  
2NH04501006  
2NH04501506  
2NH04502006  
2NH04502506  
2
2
2
2
7.5/10.0 *  
11.3/15.0 *  
15.0/20.0 *  
36.1/41.7  
54.2/62.5  
50.1/57.1  
72.1/83.1  
60/60  
80/90  
72.2/83.3 95.3/109.2 100/110 100/110  
60/60  
80/90  
048 208/230-1-60 24.4  
140.0  
165.0  
1.3  
1.3  
4.0  
7.0  
18.8/25.0 * 90.3/104.2 117.8/135.2 125/150 125/150  
2NH04501006  
2NH04501506  
2NH04502006  
2NH04502506  
2
2
2
2
7.5/10.0 *  
11.3/15.0 *  
15.0/20.0 *  
36.1/41.7 70/70  
54.2/62.5 80/90  
72.2/83.3 99.0/112.9 100/125 100/125  
53.9/60.8  
76.5/86.9  
70/70  
80/90  
060 208/230-1-60 28.9  
18.8/25.0 * 90.3/104.2 121.6/139.0 125/150 125/150  
* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.  
** = KW listed is for 480 volts, use table on previous page for 460 volts.  
= Dual element, time delay type.  
= Standard circuit breakers may be used in Canada and on applications  
over 60 amps where the heaters are separately fused.  
6
Unitary Products Group  
174065-YIM-A-0206  
Checking Supply Air CFM  
a dry coil, the compressors should be deactivated while the test  
is being run.  
To check the supply air CFM after the initial balancing has been  
completed:  
4.Knowing the pressure drop across a dry coil, the actual CFM  
through the unit can be determined from the curve in Coil Delta  
P vs. Supply Air CFM figure.  
1.Remove the two ¼ inch dot plugs in the duct panel.  
2.Insert at least 8 inches of ¼ inch tubing into each of these  
holes for sufficient penetration into the airflow on both sides of  
the indoor coil.  
WARNING! Failure to properly adjust the total system air quan-  
tity can result in extensive system damage.  
After readings have been obtained, remove the tubes and rein-  
stall the two ¼ inch plugs removed in Step 1.  
3.Using an inclined manometer, determine the pressure drop  
across the dry evaporator coil. Since the moisture on an evapo-  
rator coil may vary greatly, measuring the pressure drop across  
a wet coil under field conditions would be inaccurate. To ensure  
NOTE: De-energize the compressors before taking any test  
measurements to ensure a dry indoor coil.  
DEB Coil Delta P vs Airflow  
DEB018  
DEB048  
DEB024  
0.4  
0.35  
0.3  
0.25  
0.2  
DEB018  
DEB048  
DEB024  
DEB030, 36, & 42  
DEB060  
0.15  
0.1  
DEB060  
0.05  
0
DEB030-42  
400  
600  
800  
1000  
1200  
1400  
1600  
1800  
2000  
2200  
-0.05  
Airflow (CFM)  
Unitary Products Group  
7
174065-YIM-A-0206  
TABLE 6 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB018  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 600 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
59  
61  
23.9  
20.2  
16.4  
9.0  
8.0  
6.9  
5.3  
-
63  
25.9  
22.8  
19.7  
13.6  
12.0  
10.4  
8.0  
5.5  
-
65  
27.9  
25.4  
23.0  
18.1  
16.0  
13.8  
10.6  
7.4  
67  
29.9  
28.1  
26.3  
22.6  
19.9  
17.3  
13.3  
9.2  
69  
71  
73  
75  
65  
70  
17.8  
19.8  
21.8  
31.1  
29.3  
27.6  
24.0  
21.7  
19.3  
16.0  
12.7  
9.3  
32.3  
30.6  
28.9  
25.4  
23.4  
21.3  
18.7  
16.1  
13.4  
10.8  
33.6  
31.9  
30.2  
26.8  
25.1  
23.3  
21.4  
19.5  
17.6  
15.7  
34.8  
33.1  
31.5  
28.3  
26.8  
25.3  
24.1  
22.9  
21.7  
20.5  
12.2  
14.9  
17.5  
75  
6.6  
9.9  
13.2  
85  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
90  
95  
100  
105  
110  
115  
-
-
5.2  
-
-
-
-
6.0  
TABLE 7 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB024  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
59  
61  
18.0  
15.2  
12.4  
9.6  
6.7  
6.3  
6.0  
5.3  
-
63  
19.6  
16.9  
14.3  
11.6  
9.0  
8.3  
7.6  
6.6  
5.5  
-
65  
21.1  
18.6  
16.2  
13.7  
11.2  
10.3  
9.3  
7.8  
6.4  
-
67  
22.6  
20.3  
18.1  
15.8  
13.5  
12.3  
11.0  
9.1  
69  
23.9  
21.9  
19.8  
17.8  
15.7  
14.5  
13.3  
11.1  
8.9  
71  
73  
75  
65  
70  
13.5  
15.0  
16.5  
25.3  
23.4  
21.6  
19.8  
17.9  
16.7  
15.5  
13.1  
10.6  
8.2  
26.6  
25.0  
23.4  
21.8  
20.2  
19.0  
17.8  
15.0  
12.3  
9.6  
27.9  
26.5  
25.2  
23.8  
22.4  
21.2  
20.0  
17.0  
14.0  
11.0  
8.0  
10.1  
11.8  
13.5  
75  
6.7  
8.6  
10.5  
80  
-
-
-
-
-
-
-
-
5.4  
7.5  
85  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
90  
95  
100  
105  
110  
115  
7.2  
-
5.3  
6.7  
-
-
-
-
-
5.7  
6.8  
TABLE 8 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB030  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,000 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
22.5  
19.3  
16.0  
12.8  
9.6  
5.6  
-
59  
23.4  
20.5  
17.6  
14.7  
11.8  
7.9  
-
61  
24.3  
21.7  
19.1  
16.5  
14.0  
10.3  
6.6  
5.4  
-
63  
25.3  
23.0  
20.7  
18.4  
16.1  
12.6  
9.1  
7.2  
5.3  
-
65  
26.2  
24.2  
22.2  
20.3  
18.3  
15.0  
11.6  
9.1  
67  
27.1  
25.4  
23.8  
22.1  
20.5  
17.3  
14.1  
10.9  
7.8  
69  
71  
73  
75  
65  
70  
21.6  
27.5  
26.0  
24.5  
23.0  
21.5  
18.8  
16.2  
13.5  
10.9  
8.3  
28.0  
26.6  
25.2  
23.8  
22.4  
20.3  
18.3  
16.1  
14.0  
11.9  
9.8  
28.4  
27.1  
25.9  
24.7  
23.4  
21.9  
20.3  
18.7  
17.1  
15.5  
14.0  
28.8  
27.7  
26.6  
25.5  
24.4  
23.4  
22.4  
21.3  
20.3  
19.2  
18.1  
18.0  
75  
14.5  
80  
11.0  
85  
7.4  
90  
-
-
-
-
-
-
95  
100  
105  
110  
115  
-
-
-
-
6.6  
-
-
-
-
-
-
-
-
-
-
-
5.7  
TABLE 9 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB036  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,200 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
13.4  
11.4  
9.3  
7.2  
5.1  
5.5  
5.9  
5.5  
-
59  
15.4  
13.4  
11.4  
9.4  
7.5  
7.4  
7.3  
6.6  
6.0  
5.4  
-
61  
17.4  
15.5  
13.6  
11.7  
9.8  
63  
19.4  
17.6  
15.8  
13.9  
12.1  
11.0  
9.9  
65  
67  
69  
71  
73  
75  
65  
70  
11.5  
21.4  
19.6  
17.9  
16.2  
14.5  
12.8  
11.2  
10.2  
9.3  
23.4  
21.7  
20.1  
18.4  
16.8  
14.6  
12.5  
11.4  
10.3  
9.2  
24.6  
23.3  
22.0  
20.6  
19.3  
17.6  
15.9  
15.0  
14.0  
13.1  
12.1  
25.9  
24.9  
23.9  
22.8  
21.8  
20.6  
19.3  
18.5  
17.7  
16.9  
16.1  
27.1  
26.4  
25.7  
25.1  
24.4  
23.6  
22.8  
22.1  
21.4  
20.7  
20.0  
28.4  
28.0  
27.6  
27.3  
26.9  
26.5  
26.2  
25.6  
25.1  
24.5  
24.0  
9.3  
75  
7.1  
80  
-
-
-
-
-
-
-
-
85  
90  
9.2  
95  
8.6  
100  
105  
110  
115  
7.8  
9.0  
7.1  
8.2  
-
6.4  
7.3  
8.3  
-
5.7  
6.5  
7.3  
8.1  
8
Unitary Products Group  
174065-YIM-A-0206  
TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB042  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
21.9  
18.5  
15.1  
11.7  
8.2  
6.5  
-
59  
23.5  
20.3  
17.1  
13.9  
10.8  
9.1  
7.4  
5.8  
-
61  
25.0  
22.1  
19.2  
16.2  
13.3  
11.7  
10.0  
7.9  
63  
26.6  
23.9  
21.2  
18.5  
15.8  
14.2  
12.7  
10.0  
7.3  
65  
67  
69  
71  
73  
75  
65  
70  
20.3  
28.1  
25.7  
23.2  
20.8  
18.4  
16.8  
15.3  
12.0  
8.7  
29.7  
27.5  
25.3  
23.1  
20.9  
19.4  
17.9  
14.1  
10.2  
6.4  
30.6  
28.6  
26.6  
24.5  
22.5  
21.0  
19.5  
16.3  
13.0  
9.8  
31.6  
29.7  
27.8  
25.9  
24.0  
22.6  
21.1  
18.4  
15.8  
13.2  
10.5  
32.6  
30.8  
29.1  
27.3  
25.6  
24.1  
22.7  
20.6  
18.6  
16.5  
14.5  
33.6  
32.0  
30.4  
28.7  
27.1  
25.7  
24.3  
22.8  
21.4  
19.9  
18.5  
16.7  
75  
13.0  
80  
9.4  
85  
5.7  
90  
-
-
-
-
-
-
95  
100  
105  
110  
115  
-
-
5.8  
-
-
-
-
5.5  
-
-
-
-
-
-
6.5  
TABLE 11 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB048  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
57  
59  
17.3  
14.7  
12.2  
9.7  
7.2  
6.1  
-
61  
19.1  
16.8  
14.5  
12.1  
9.8  
7.7  
5.7  
5.3  
-
63  
21.0  
18.8  
16.7  
14.5  
12.4  
9.4  
65  
22.8  
20.9  
18.9  
17.0  
15.0  
11.0  
7.0  
67  
24.7  
22.9  
21.2  
19.4  
17.6  
12.7  
7.7  
69  
71  
73  
75  
65  
70  
13.5  
15.4  
26.1  
24.7  
23.3  
21.8  
20.4  
16.6  
12.7  
11.1  
9.5  
27.6  
26.5  
25.4  
24.2  
23.1  
20.5  
17.8  
15.1  
12.4  
9.7  
29.0  
28.2  
27.5  
26.7  
25.9  
24.4  
22.8  
19.1  
15.3  
11.6  
7.8  
30.5  
30.0  
29.6  
29.1  
28.6  
28.3  
27.9  
23.0  
18.2  
13.4  
8.6  
10.7  
12.7  
75  
7.8  
10.0  
80  
-
-
-
-
-
-
-
-
7.3  
85  
-
-
-
-
-
-
-
90  
95  
6.3  
100  
105  
110  
115  
-
5.9  
6.5  
7.1  
-
5.5  
6.0  
6.6  
-
-
5.0  
5.5  
6.0  
7.8  
-
-
-
-
5.4  
6.2  
7.0  
TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB060  
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 2,000 CFM/TON  
INDOOR WB TEMPERATURE (F)  
OUTDOOR  
TEMPERATURE  
(F)  
55  
25.3  
22.2  
19.2  
16.1  
13.1  
10.3  
7.6  
6.6  
5.6  
-
57  
25.8  
23.0  
20.1  
17.3  
14.5  
11.7  
8.9  
59  
26.3  
23.7  
21.1  
18.5  
15.9  
13.1  
10.3  
8.9  
61  
63  
65  
67  
69  
71  
73  
75  
65  
70  
26.8  
24.4  
22.1  
19.7  
17.3  
14.5  
11.6  
10.1  
8.6  
27.3  
25.1  
23.0  
20.9  
18.8  
15.9  
13.0  
11.3  
9.6  
27.8  
25.9  
24.0  
22.1  
20.2  
17.3  
14.3  
12.5  
10.6  
8.7  
28.3  
26.6  
24.9  
23.3  
21.6  
18.6  
15.7  
13.6  
11.6  
9.5  
28.7  
27.4  
26.1  
24.7  
23.4  
21.1  
18.7  
16.7  
14.6  
12.5  
10.5  
29.1  
28.2  
27.2  
26.2  
25.2  
23.5  
21.8  
19.7  
17.6  
15.6  
13.5  
29.6  
28.9  
28.3  
27.7  
27.0  
25.9  
24.8  
22.7  
20.7  
18.6  
16.5  
30.0  
29.7  
29.4  
29.1  
28.9  
28.3  
27.8  
25.8  
23.7  
21.6  
19.5  
75  
80  
85  
90  
95  
100  
105  
110  
115  
7.7  
6.6  
7.6  
5.4  
6.2  
7.0  
7.9  
-
-
-
5.5  
6.2  
6.8  
7.5  
Unitary Products Group  
9
174065-YIM-A-0206  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
FRONT  
“A”  
COMPRESSOR  
SERVICE ACCESS  
COMPARTMENT PANEL  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
1
DIMENSION  
“A”  
LOW VOLTAGE CONN.  
“ DIA. KNOCKOUT  
UNIT SIZE  
(OVERALL)  
2 3  
018 - 042  
048 - 060  
33 1  
8
2
411  
2
SIDE SUPPLY  
AIR OPENING  
REFRIGERANT  
CONNECTIONS  
SIDE RETURN  
AIR OPENING  
ELECTRICAL/FILTER  
SERVICE ACCESS  
COMPARTMENT PANEL  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
17  
28  
47  
(OVERALL)  
17  
28  
1
22  
49  
2 1  
22  
2
(OVERALL)  
3
LOW VOLTAGE CONN.  
“ DIA. KNOCKOUT  
11  
2
FRONT  
UNIT CONDENSATE  
CONNECTION “ NPTI  
(TRAP REQUIRED)  
4 1  
2
HIGH VOLTAGE  
CONN. 1 “ x “ DIA.  
KNOCKOUT  
All dimensions are in inches. They are  
subject to change without notice. Certified  
dimensions will be provided upon request.  
SIDE SUPPLY  
AIR OPENING  
14  
43  
40  
26  
28  
22  
6
14  
BACK  
OUTDOOR  
COIL  
3
CONDENSATE  
DRAIN “ NPTI  
SIDE RETURN  
AIR OPENING  
BOTTOM SUPPLY  
AIR OPENING  
2 3  
8
14  
13  
4
15  
3
15  
4
13  
4
15  
28  
CLEARANCES  
(Minimum)  
BOTTOM RETURN  
AIR OPENING  
3
Front  
Back  
12"  
0"  
13  
4
Left Side (Filter Access) 24"  
Units may be installed on combustible floors made from wood or class A,  
B or C roof covering material.  
Right Side  
Below Unit1  
24"  
0"  
Units must be installed outdoors. Overhanging structures or shrubs  
should not obstruct outdoor air discharge outlet.  
36" (For Condenser  
Air Discharge)  
Above Unit2  
FIG. 3 - DIMENSIONS AND CLEARANCES  
10  
Unitary Products Group  
174065-YIM-A-0206  
SEQUENCE OF OPERATION  
Heating  
Cooling  
The following sequences of operation are based on using a  
standard single-stage cooling thermostat.  
WITH POWER TO UNIT AND THERMOSTAT IN HEATING  
MODE.  
WITH POWER TO UNIT AND THERMOSTAT IN COOLING  
MODE.  
1. If the fan switch on the thermostat is in the “ON” position,  
the 24 volts at “G” will energize the “K1" relay contacts, and  
energize the indoor blower motor. If the fan switch on the  
thermostat is in the ”AUTO" position, the blower will oper-  
ate only when there is a call for heating by the thermostat.  
1. If the fan switch on the thermostat is in the “ON” position,  
the 24 volts at “G” will energize the “K1" relay on the fan  
control board, close the ”K1" relay contacts, and energize  
the indoor blower motor. If the fan switch is in the “AUTO”  
position, the blower will operate only when there is a call for  
cooling by the thermostat.  
2. On a call for heating, the thermostat will send 24 volts to  
“W1" on the fan control board. The 24 volts signal will ener-  
gize relay ”K2" on the fan control board, and the first stage  
of electric heat will be energized.  
2. On a call for cooling, the thermostat will send 24 volts to “Y”  
on the fan control board. The 24 volt signal will energize  
contactor “M1", and power will be supplied to the compres-  
sor and outdoor fan motor. If the fan switch on the thermo-  
stat is on the ”AUTO" position, the thermostat will also send  
a 24 volt signal to “G” on the fan control board and the in-  
door blower will operate as indicated in step 1.  
3. When the heating demand is satisfied, the electric heat will  
be de-energized when the 24 volt “W1" and ”W2" signals  
are removed. If the fan switch on the thermostat is in the  
“ON” position, the indoor blower will continue to run. If the  
fan switch is in the “AUTO” position, the “K1" relay will open  
and de-energize the indoor blower motor after the appropri-  
ate time delay.  
3. When the demand for cooling has been satisfied, the “M1"  
contactor will be de-energized when the 24 volt ”Y" signal is  
removed. If the fan switch on the thermostat is energized  
when the 24 volt “Y” signal is removed. If the fan switch on  
the thermostat is in the “ON” position, the indoor blower will  
continue to run. If the fan switch is in the “AUTO” posi-  
tion, the 24 volt “G” signal will be removed, and after a  
60 second delay, the “K1" relay will open and de-  
energize the indoor blower motor,  
Please refer to Table 13 for more information.  
TABLE 13 - THERMOSTAT SIGNALS (SINGLE PHASE UNITS)  
BOARD FUNCTION  
BOARD FUNCTION  
ON FAN INSTANT ON  
“G”  
OFF FAN INSTANT OFF  
FAN INSTANT ON  
COMPRESSOR AND OUTDOOR FAN INSTANT ON  
FAN INSTANT ON  
HEATER BANK 1 ELEC. HEAT INSTANT ON  
ON  
ON  
“G”  
“Y”  
“W1"  
”W2"  
COMPRESSOR AND OUTDOOR FAN INSTANT OFF  
FAN 60 SECOND DELAY OFF  
HEATER BANK 1 ELEC. HEAT INSTANT OFF  
FAN 5 SECOND DELAY OFF  
OFF  
OFF  
FAN INSTANT ON  
FAN INSTANT ON  
HEATER BANK 1 ELEC. HEAT INSTANT ON  
1
ON  
ON HEATER BANK 1 ELEC. HEAT 2 SEC. DELAY OFF  
HEATER BANK 2 ELEC. HEAT INSTANT ON  
“G”  
“W1"  
1
HEATER BANK 1 ELEC. HEAT 2 SEC. DELAY OFF  
OFF HEATER BANK 2 ELEC. HEAT INSTANT OFF  
FAN 5 SECOND DELAY OFF  
HEATER BANK 1 ELEC. HEAT INSTANT OFF  
FAN 5 SECOND DELAY OFF  
OFF  
FAN INSTANT ON  
FAN INSTANT ON  
HEATER BANK 1 ELEC. HEAT INSTANT ON  
HEATER BANK 2 ELEC. HEAT 10 SECOND DELAY ON  
HEATER BANK 3 ELEC. HEAT 20 SECOND DELAY ON  
HEATER BANK 1 ELEC. HEAT INSTANT ON  
HEATER BANK 2 ELEC. HEAT 10 SECOND DELAY ON  
HEATER BANK 3 ELEC. HEAT 20 SECOND DELAY ON  
ON  
ON  
“G”  
“W1"  
”W2"  
“W1"  
”W2"  
HEATER BANK 1 ELEC. HEAT INSTANT OFF  
1
HEATER BANK 2 ELEC. HEAT 2 SECOND DELAY ON  
HEATER BANK 3 ELEC. HEAT 1 SECOND DELAY ON  
FAN 6 12 SECOND DELAY OFF  
STAGE 1 ELEC. HEAT INSTANT OFF  
1
HEATER BANK 2 ELEC. HEAT 2 SECOND DELAY ON  
HEATER BANK 3 ELEC. HEAT 1 SECOND DELAY ON  
FAN 6 12 SECOND DELAY OFF  
OFF  
OFF  
Unitary Products Group  
11  
174065-YIM-A-0206  
SECURE OWNER'S APPROVAL: When the system is functioning properly, secure the owner's approval. Show him the  
location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature  
settings within the limitations of the system.  
MAINTENANCE  
NORMAL MAINTENANCE  
WARNING:Prior to any of the following maintenance proce-  
dures, shut off all power to the unit, to avoid per-  
sonal injury.  
OUTDOOR COIL- Dirt should not be allowed to accumulate on  
the outdoor coil surface or other parts in the air circuit. Cleaning  
should be as often as necessary to keep the coil clean. Use a  
brush, vacuum cleaner attachment, or other suitable means. If  
water is used to clean the coil, be sure that the power to the unit  
is shut off prior to cleaning.  
Periodic maintenance consists of changing or cleaning filters  
and general cleaning of the outdoor coil.  
FILTERS - Inspect once a month. Replace Disposable or clean  
Permanent Type as necessary. DO NOT replace Permanent  
Type with Disposable.  
CAUTION: Exercise care when cleaning the coil so that the  
coil fins are not damaged.  
Do not permit the hot condenser air discharge to be  
obstructed by overhanging structures or shrubs.  
MOTORS - Indoor and outdoor fan motors are permanently lu-  
bricated and require no maintenance.  
12  
Unitary Products Group  
174065-YIM-A-0206  
FOR DUAL POINT  
ELECTRIC HEAT  
POWER SUPPLY  
SEE DETAIL A  
SEE  
DETAIL  
"B"  
SECONDARY POWER SUPPLY  
FOR DUAL POINT ELEC HEAT  
208/230-1-60  
USE COPPER  
CONDUCTORS ONLY  
POWER SUPPLY  
208/230-1-60  
USE COPPER  
CONDUCTORS ONLY  
F2  
F4  
F1  
F3  
709/BK  
703/BK  
710/PR  
705/PR  
(M1)  
(M1)  
(K3)  
(K5)  
(HTR2)  
(HTR3)  
711/BK  
713/PR  
F5  
F6  
706/BK  
714/BK  
708/PR  
716/PR  
(K4)  
(K6)  
(HTR4)  
(HTR5)  
DETAIL A  
DUAL POINT ELECTRIC HEAT (SEE NOTE 9)  
FIG. 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY)  
Unitary Products Group  
13  
174065-YIM-A-0206  
TYPICAL WIRING DIAGRAM LEGEND  
CB  
CIRCUIT BREAKER 24V, 3 AMP  
CCH  
COMPR  
DS  
F1 F2 F3  
F4 F5 F6  
F7 F8 F9  
F24  
CRANKCASE HEATER (OPTIONAL)  
COMPRESSOR  
DEFROST SENSOR, CLOSES @ 31˚F, OPENS @ 55˚F.  
FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT)  
FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT)  
FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT)  
FUSE 24V SECONDARY, 5 AMP  
FS  
HP  
FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26˚ F  
HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG  
ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)  
ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)  
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)  
ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT)  
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)  
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)  
RELAY INDOOR FAN MOTOR  
HTR 1  
HTR 2  
HTR 3  
HTR 4  
HTR 5  
HTR 6  
K1  
K2  
RELAY ELECTRIC HEATER  
K3  
RELAY ELECTRIC HEATER, 24 VDC COIL  
K7  
RELAY LIMIT TRIP, 25 VDC COIL  
LP  
LS  
M1  
M2  
LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG  
LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)  
CONTACTOR, COMPRESSOR & OUTDOOR FAN  
CONTACTOR, ELECTRIC HEAT, 230V COIL  
M3  
CONTACTOR, ELECTRIC HEAT, 230V COIL  
PTCR  
RC1/RC2  
RC1  
RC2  
RC3  
START ASSIST (OPTIONAL DEVICE)  
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR  
COMPRESSOR START CAPACITOR (ALTERNATE)  
OUTDOOR FAN RUN CAPACITOR (ALTERNATE)  
INDOOR FAN RUN CAPACITOR  
RVS  
REVERSING VALVE SOLENOID  
S2/P2  
S3/P3  
S4/P4  
S3/P3  
T1  
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE  
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE  
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V  
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V  
TRANSFORMER, 24V, 40 VA  
TB2  
TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS  
IDENTIFIED TERMINAL ON RUN CAPACITOR  
ROOM THERMOSTAT 24V CONNECTIONS  
TB1 ON FAN/ELEC HEAT CONTROL BOARD  
FACTORY WIRING AND DEVICES  
OPTIONAL WIRING AND DEVICES  
FIELD WIRING  
TYPICAL WIRING DIAGRAM NOTES  
14  
Unitary Products Group  
174065-YIM-A-0206  
NOTES  
Unitary Products Group  
15  
NOTES  
Unitary Products Group  
5005 York Drive, Norman Oklahoma 73069  
Subject to change without notice. Printed in U.S.A.  
Copyright © by York International Corporation 2006. All Rights Reserved.  
Supersedes: Nothing  
174065-YIM-A-0206  

Lexmark S800 User Manual
Murphy Gear Oil Pressure Sender Egpk 95083n User Manual
Newair Ac 10000h User Manual
Nissan Vq35de User Manual
Samsung As12hpbn User Manual
Samsung As18a9 A0 Rcd User Manual
Samsung Avmbc026ea B 0 User Manual
Samsung Lcd 24bi User Manual
Sears Kenmore 66162467 User Manual
Vector Iveco Motos V08 Ent M75 User Manual