AIR CONDITIONER (MULTI TYPE)
Installation manual
Outdoor Unit
Model name:
<Heat Pump Model>
<Cooling Only Model>
For commercial use
MMY-MAP0804HT8-E
MMY-MAP1004HT8-E
MMY-MAP1204HT8-E
MMY-MAP1404HT8-E
MMY-MAP1604HT8-E
MMY-MAP0804T8-E
MMY-MAP1004T8-E
MMY-MAP1204T8-E
MMY-MAP1404T8-E
MMY-MAP1604T8-E
MMY-MAP0804HT8Z-E
MMY-MAP1004HT8Z-E
MMY-MAP1204HT8Z-E
MMY-MAP1404HT8Z-E
MMY-MAP1604HT8Z-E
MMY-MAP0804T8Z-E
MMY-MAP1004T8Z-E
MMY-MAP1204T8Z-E
MMY-MAP1404T8Z-E
MMY-MAP1604T8Z-E
MMY-MAP0804HT8ZG-E
MMY-MAP1004HT8ZG-E
MMY-MAP1204HT8ZG-E
MMY-MAP1404HT8ZG-E
MMY-MAP1604HT8ZG-E
MMY-MAP0804T8ZG-E
MMY-MAP1004T8ZG-E
MMY-MAP1204T8ZG-E
MMY-MAP1404T8ZG-E
MMY-MAP1604T8ZG-E
English
Installation manual
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Work undertaken
Protective gear worn
1 PRECAUTIONS FOR SAFETY
Protective gloves
‘Safety’ working clothing
All types of work
WARNING
Gloves to provide protection for electricians and from heat
Insulating shoes
Clothing to provide protection from electric shock
Electrical-related
work
General
•
•
•
•
Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install
the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
Only a qualified installer(*1) or qualified service person(*1) is allowed to do installationwork. If installation is carried out by
an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause
fire, electric shock, water leak or other failure.
Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit
breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1)
or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the
indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being
carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm
or more or to remove the intake grille of the indoor unit to undertake work.
Wear protective gloves and safety work clothing during installation, servicing and removal.
Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and
result in injury.
When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work.
Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in
progress” sign near the circuit breaker before proceeding with the work.
When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the
work. Parts and other objects may fall from above, possibly injuring a person below.
The refrigerant used by this air conditioner is the R410A.
Work done at heights
(50 cm or more)
Helmets for use in industry
Transportation of
heavy objects
Shoes with additional protective toe cap
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Warning Indications on the Air Conditioner Unit
•
•
•
Warning indication
Description
WARNING
WARNING
ELECTRICAL SHOCK HAZARD
•
•
ELECTRICAL SHOCK HAZARD
Disconnect all remote
electric power supplies
before servicing.
Disconnect all remote electric power supplies before servicing.
•
•
•
•
WARNING
WARNING
Moving parts.
Do not operate unit with grille
removed.
Moving parts.
Do not operate unit with grille removed.
Stop the unit before the servicing.
Stop the unit before the servicing.
•
•
You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact
your dealer.
•
Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water
leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.
CAUTION
CAUTION
High temperature parts.
You might get burned
when removing this panel.
Selection of installation location
High temperature parts.
You might get burned when removing this panel.
•
If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit
concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the
measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the
unit, it may ignite and cause a fire.
When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if
the bands should break.
•
CAUTION
•
•
CAUTION
Do not touch the aluminum
fins of the unit.
Doing so may result in injury.
Do not touch the aluminium fins of the unit.
Doing so may result in injury.
•
•
•
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric
shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may
cause imperfect combustion.
Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with
a neighbour, install the air conditioner while considering the noise.)
CAUTION
CAUTION
BURST HAZARD
Open the service valves before
the operation, otherwise there
might be the burst.
BURST HAZARD
Installation
Open the service valves before the operation, otherwise there might be the
burst.
•
Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause
the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient
durability may cause the outdoor unit to fall, which may result in injury.
•
•
•
•
Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result
in the unit falling down, or other accidents.
Be sure to fix the screws back which have been removed for installation or other purposes.
CAUTION
CAUTION
Do not climb onto the
fan guard.
Doing so may result in injury.
Do not climb onto the fan guard.
Doing so may result in injury.
EN
3-EN
4-EN
– 2 –
– 3 –
5-EN
6-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Refrigerant piping
Relocation
•
Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is
operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over
pressurized, which may cause a injury.
•
Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the
air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or
vibration may result.
•
•
•
•
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in
the flare nut after a long period, which may result in refrigerant leakage.
Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic
gas may be produced.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a
fire source, such as a cooking range, noxious gas may be generated.
When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air
completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air
completely may cause the air conditioner to malfunction.
•
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting
the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked
in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or
other trouble.
Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant
when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the
outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
•
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
•
•
•
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes
in contact with fire, noxious gas may be generated.
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE
LAYER.
Electrical wiring
•
•
•
•
Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may
result in electric shocks and/or electrical leaks.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to
provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on
insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you may
receive an electric shock.
•
The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
•
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the conventional refrigerant.
•
•
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use
of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
Check that the product is properly earthed. (grounding work)
•
•
Accordingly the exclusive tools are required for the new refrigerant (R410A).
Incomplete earthing may cause electric shock.
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
•
•
•
Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
After completing the repair or relocation work, check that the ground wires are connected properly.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations
and laws.
To Disconnect the Appliance from Main Power Supply.
This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
•
•
•
•
Install the circuit breaker where it can be easily accessed by the agent.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended
may give rise to smoking and/or a fire.
•
•
•
Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow
may occur on the terminal block and may result in fire.
When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires
securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
Test run
•
Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor
unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an
electric shock if the power is turned on without first conducting these checks.
•
When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning,
abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner,
do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service
person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for
instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause
mechanical problems to escalate or result in electric shocks or other failure.
•
•
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 MΩ or more
between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such
as a leak or electric shock is caused at user’s side.
Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
•
Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where
the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF
position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position
until the repairs are completed.
•
•
After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
2 ACCESSORY PARTS
3 INSTALLATION OF NEW REFRIGERANT
AIR CONDITIONER
Part name
Owner’s Manual
Installation Manual
CD-ROM
Q’ty
1
Shape
Usage
(Be sure to hand it to the customers.)
(Be sure to hand it to the customers.)
–
–
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the
new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
2
For other languages that do not appear in this Installation Manual,
Please refer to the enclosed CD-ROM.
1
1
–
(Owner’s manual,
Installation manual)
Attached pipe
(for Ø22.2)
Connecting pipe for gas side piping
(MAP080, MAP100 type)
Attached pipe
(for Ø28.6)
Connecting pipe for gas side piping
(MAP120, MAP140, MAP160 type)
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
1
1
Required Tools and Cautions on handling
F-GAS label
Fill the items on the label after adding refrigerant.
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used tools
Gauge manifold
Usage
Proper use of tools/parts
Exclusive to R410A
Vacuuming, charging refrigerant
and operation check
Charging hose
Exclusive to R410A
Charging cylinder
Gas leak detector
Charging refrigerant
Checking gas leak
Unusable (Use the Refrigerant charging balance.)
Exclusive to R410A
Usable if a counter-flow preventive adapter is
attached
Vacuum pump
Vacuum drying
Vacuum pump with counterflow
Flare tool
Vacuum drying
R22 (Existing article)
Flare processing of pipes
Bending processing of pipes
Recovering refrigerant
Tightening flare nut
Cutting pipes
Usable by adjusting size
R22 (Existing article)
Bender
Refrigerant recovery device
Torque wrench
Exclusive to R410A
Exclusive to Ø12.7mm and Ø15.9mm
R22 (Existing article)
Pipe cutter
Exclusive to R410A
Enter the refrigerate name for identification
Refrigerant canister
Charging refrigerant
Welding machine/Nitrogen gas
cylinder
Welding of pipes
R22 (Existing article)
R22 (Existing article)
Refrigerant charging balance
Charging refrigerant
EN
7-EN
8-EN
– 4 –
– 5 –
9-EN
10-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Installation space
Leave space necessary for running, installation and servicing.
4 SELECTION OF INSTALLATION PLACE
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
Air discharge
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Air intake
Air intake
Air intake
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special
maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where an organic solvent is used.
Air intake
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to
devices listed above may occur.)
Installation/servicing
surface
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
Square hole for
handling
• Places with poor ventilation.
Outdoor unit top view
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
10mm or more
20mm or more
20mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
▼ Combination of outdoor units
5 CARRYING IN THE OUTDOOR UNIT
Cooperating outdoor unit
Unit 2
Model name
(Standard type)
Unit 1
Unit 3
CAUTION
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
MMY-AP1814*
MMY-AP2014*
MMY-AP2214*
MMY-AP2414*
MMY-AP2614*
MMY-AP2814*
MMY-AP3014*
MMY-AP3214*
MMY-AP3414*
MMY-AP3614*
MMY-AP3814*
MMY-AP4014*
MMY-AP4214*
MMY-AP4414*
MMY-AP4614*
MMY-AP4814*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
–
–
–
–
Handle the outdoor unit carefully, observing the following items.
• When using a forklift or other machinery for loading/unloading in transportation, insert the prongs of the forklift
into the rectangular holes for handling as shown below.
• When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and
tie the unit from 4 sides.
(Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused
to the outer surface of the outdoor unit.)
–
–
–
–
–
–
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
MMY-MAP1604*
MMY-MAP1604*
–
–
–
(There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
–
–
GOOD
NO GOOD
NO GOOD
–
–
Plaster
Rope
–
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
Rectangular
holes for
handling
Plaster
Side
NO GOOD
Front /Back
GOOD
Rectangular
holes for
lifting
Reinforcing
plate
Cooperating outdoor unit
Model name
(High Efficiency Model)
Unit 4
Unit 1
Unit 2
Unit 3
–
Prongs of the
forklift
MMY-AP1624*
MMY-AP2424*
MMY-AP2624*
MMY-AP2824*
MMY-AP3024*
MMY-AP3224*
MMY-AP3424*
MMY-AP3624*
MMY-AP3824*
MMY-AP4024*
MMY-AP4224*
MMY-AP4424*
MMY-AP4624*
MMY-AP4824*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP1204*
–
–
–
–
–
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1204*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1004*
MMY-MAP1204*
EN
11-EN
12-EN
– 6 –
– 7 –
13-EN
14-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Weight centre and weight
6 INSTALLATION OF THE OUTDOOR UNIT
WARNING
◆Weight centre of an outdoor unit
•
•
Be sure to install the outdoor unit in a place able to bear its weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Perform specified installation work to protect against strong wind and earthquakes.
If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
(B)
(A)
Anchor bolt position
920
Anchor bolt position
700
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating)
Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise)
are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall
will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat
surface.)
2. Mount a snowfall-hood onto the air inlet and the air outlet.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air inlet and the air outlet.
Snowfall-hood for air
outlet (locally procured)
Snowfall-hood for air
outlet
(4 faces)
(locally procured)
X
X
Stand
(locally procured)
1. To install multiple outdoor units, arrange them with 20mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
Weight (kg)
20mm or more
20mm or more
No.
(A)
(B)
Model type
MAP080
X (mm)
500
Y (mm)
390
Z (mm)
Heat pump model
Cooling only model
MAP100
MAP120
MAP140
MAP160
645
700
242
330
241
605
350
330
M12 anchor bolt
4 positions/unit
Installation Manual
Installation Manual
SMMS-i
SMMS-i
• Anchor bolt positions are as shown below:
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C ≥ D)
310 or
more
310 or
more
Continuous hole
(15 x 20 long hole)
A
A
A
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
the header unit.)
B
(Unit: mm)
Liquid piping
Model type
MAP080*, MAP1000*, MAP120*
MAP1404*, 1604*
A
B
▼ Figure 1
▼ Figure 2
700
920
990
GOOD
NO GOOD
1210
Header unit
A
Follower unit Follower unit
Header unit
A
Follower unit Follower unit
B
C
B
C
2. When drawing out the refrigerant pipe from the
underside, set the height of the stand to 500mm or
more.
3. Do not use 4 stands on the corner to support the
outdoor unit.
NO GOOD
GOOD
Main pipe
NO GOOD
To the indoor unit
Main pipe
To the indoor unit
Gas piping
[Inverse connection of a gas-side branch unit]
▼ Figure 3
▼ Figure 4
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
GOOD
NO GOOD
GOOD
GOOD
Follower unit
C
Header unit
A
Follower unit
B
Header unit
A
Follower unit Follower unit
B
C
Install the vibration-proof
rubber so that the bent part
of the fixing leg is
Anchor bolt
grounded.
Vibration-proof rubber
Main pipe
Main pipe
To the indoor unit
NO GOOD
NO GOOD
NO GOOD
To the indoor unit
Extension valve
To gas-side branch
unit
The bent part of the
fixing leg is not
grounded.
• When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed
±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
(Horizontal line)
(Horizontal line)
(A arrow view)
Do not connect
a branch unit
vertically.
Within ±15
degrees
Within ±15 degrees
A
(B arrow view)
B
At a level position
EN
15-EN
16-EN
– 8 –
– 9 –
17-EN
18-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
When drawing pipes downward
7 REFRIGERANT PIPING
[Vertical connection of branch units]
▼ Figure 5
▼ Figure 6
WARNING
GOOD
NO GOOD
•
•
If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
After installation, check that the refrigerant gas does not leak.
Header unit
A
Follower unit Follower unit
B
C
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range,
noxious gas may be generated.
Connection of refrigerant pipe
• The refrigerant pipe connecting section is set in the
outdoor unit. Remove the front panel and the piping/
wiring panel. (M5: 9 pcs.)
• As shown in the illustration on the right, the hooks are
at the right and left sides of the front panel. Lift up and
remove the front panel.
L-shaped
pipe
Hook
To gas-side
branch unit
To gas-side
branch unit
To gas-side branch
unit
To gas-side branch
unit
Front panel
• Pipes can be drawn out forward or downward from the
outdoor unit.
• Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header
unit. Use an extension valve for installation (See the figure above.).
Specify the pipe diameter in advance to allow for adding another unit.
Piping/wiring panel
(Rear piping)
• When drawing out the pipe forward, draw it out to the
outside via the piping/wiring panel, and leave a space
of 500mm or more from the main pipe connecting the
outdoor unit with the indoor unit, considering service
work or other work on the unit. (For replacing the
compressor, 500mm or more space is required.)
• When drawing out the pipe downward, remove the
knockouts on the base plate of the outdoor unit, draw
the pipes out of the outdoor unit, and perform piping on
(Left
(Right
piping)
piping)
(Left piping)
(Right piping)
Drawing out
downward
the right/left or rear side. Downward length of the balance pipe should be 5m or less.
Ball valve of gas
side
Ball valve of gas
side
Ball valve of liquid
side
Packed valve of liquid
side
Packed valve of
balance pipe
Packed valve of
balance pipe
(MAP080, MAP100, MAP120)
(MAP140, MAP160)
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Type
Pipe
diameter
REQUIREMENT
Draw-out forward
Draw-out downward
• For a welding work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside
of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not
contaminate the refrigerant.
Cut the L-shaped pipe at the horizontal straight Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally. pipe, and the socket and pipe procured locally.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level
of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten
the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the
flare nut while holding the valve mounting plate with a spanner.)
Gas
pipe
MAP140
MAP160
Liquid
pipe
Gas pipe
Liquid
pipe
Ø28.6
Gas
pipe
Gas pipe
Attachment pipe
Attachment
pipe
Socket
Balance
pipe
Balance
pipe
Socket
Pipe
Section
to be cut
Packed valve of
Pipe
Outer dia. of
copper pipe
balance pipe
Section
to be cut
Tightening torque (N•m)
6.4 mm
9.5 mm
14 to 18 (1.4 to 1.8 kgf•m)
33 to 42 (3.3 to 4.2 kgf•m)
50 to 62 (5.0 to 6.2 kgf•m)
63 to 77 (6.3 to 7.7 kgf•m)
Ball valve of gas side
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Packed valve of liquid
side
12.7 mm
15.9 mm
Copper pipe outer
dia.
When using R410A
tool
When using
conventional tool
9.5
12.7
15.9
0 to 0.5
1.0 to 1.5
Pipe connection method of valve at the gas side (Example)
Pipe
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Type
Draw-out forward
Draw-out downward
diameter
+0
-0.4
Copper pipe outer dia.
A
A
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
Cut the L-shaped pipe at the vertical straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
9.5
13.2
16.6
19.7
12.7
15.9
Gas
pipe
Gas pipe
Gas pipe
Liquid
Liquid
pipe
MAP080
MAP100
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
Gas
Ø22.2
pipe
Attachment
pipe
pipe
Attachment
Balance
pipe
Balance
pipe
Socket
Pipe
pipe
Socket
Section
to be cut
Pipe
Section to be
cut
Cut the L-shaped pipe at the horizontal straight Cut the L-shaped pipe at the vertical straight
section, then braze the supplied attachment section, then braze the supplied attachment
pipe and the socket and pipe procured locally. pipe and the socket and pipe procured locally.
Gas
pipe
Liquid
pipe
Liquid
pipe
Gas pipe
MAP120
Ø28.6
Gas pipe
Attachment pipe
Socket
Gas
pipe
Balance
pipe
Balance
pipe
Attachment
pipe
Socket
Section
to be cut
Pipe
Pipe
Section to be
cut
EN
19-EN
20-EN
– 10 –
– 11 –
21-EN
22-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Table 1
Coupling size of brazed pipe
Capacity code
Connected section
Indoor unit
Equivalent to
capacity rank
External size
Internal size
Equivalent to HP
capacity
2.2
2.8
3.6
4.5
5.6
7.1
8
007
009
012
015
018
024
027
030
036
048
056
072
096
0.8
1
G
K
1.25
1.7
2
(Unit: mm)
2.5
3
Connected section
Internal size
3.2
4
9
External size
Standard outer dia.
of connected
Min. depth of
insertion
Min. thickness
of coupling
11.2
14
Standard outer dia.
(Allowable difference)
Oval value
copper pipe
5
C
F
K
G
6
6
16
+0.04
-0.02
6.35
9.52
6.35 (±0.03)
9.52 (±0.03)
12.70 (±0.03)
15.88 (±0.03)
19.05 (±0.03)
22.22 (±0.03)
28.58 (±0.04)
34.90 (±0.04)
38.10 (±0.05)
41.28 (±0.05)
6.45 (
9.62 (
)
)
7
8
0.06 or less
0.08 or less
0.10 or less
0.13 or less
0.15 or less
0.16 or less
0.20 or less
0.25 or less
0.27 or less
0.28 or less
0.50
0.60
0.70
0.80
0.80
0.82
1.00
1.20
1.26
1.35
8
22.4
28
+0.04
-0.02
7
10
+0.04
-0.02
12.70
15.88
19.05
22.22
28.58
34.92
38.10
41.28
12.81 (
16.00 (
19.19 (
22.36 (
28.75 (
35.11 (
38.31 (
41.50 (
)
)
)
)
)
)
)
)
9
8
Table 2
+0.04
-0.02
9
8
+0.03
-0.03
11
11
13
14
15
15
10
10
12
13
14
14
Capacity code
Outdoor unit
model name
(High Efficiency
model)
Capacity code
Outdoor unit
model name
(Standard model)
No. of
No. of
indoor
units
+0.03
-0.03
indoor
units
Equivalentto Equivalentto
Equivalentto Equivalentto
+0.06
-0.02
HP
capacity
HP
capacity
+0.04
-0.04
MMY-MAP0804∗
MMY-MAP1004∗
MMY-MAP1204∗
MMY-MAP1404∗
MMY-MAP1604∗
MMY-AP1814∗
MMY-AP2014∗
MMY-AP2214∗
MMY-AP2414∗
MMY-AP2614∗
MMY-AP2814∗
MMY-AP3014∗
MMY-AP3214∗
MMY-AP3414∗
MMY-AP3614∗
MMY-AP3814∗
MMY-AP4014∗
MMY-AP4214∗
MMY-AP4414∗
MMY-AP4614∗
MMY-AP4814∗
8
22.4
28
13
16
20
23
27
30
33
37
40
43
47
48
48
48
48
48
48
48
48
48
48
—
—
—
—
—
—
16
—
—
—
24
26
28
30
32
34
36
38
40
42
44
46
48
—
—
—
—
—
—
27
—
—
—
40
43
47
48
48
48
48
48
48
48
48
48
48
+0.08
-0.02
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
+0.08
-0.02
33.5
40
—
—
—
—
45
MMY-AP1624∗
—
45
Selection of pipe size
50.4
56
—
—
—
61.5
68
—
—
◆Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
MMY-AP2424∗
MMY-AP2624∗
MMY-AP2824∗
MMY-AP3024∗
MMY-AP3224∗
MMY-AP3424∗
MMY-AP3624∗
MMY-AP3824∗
MMY-AP4024∗
MMY-AP4224∗
MMY-AP4424∗
MMY-AP4624∗
MMY-AP4824∗
68
73
73
78.5
85
78.5
85
90
90
NOTE
96
96
101
106.5
112
118
123
130
135
101
106.5
112
118
123
130
135
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
* For combination of the outdoor units, refer to “Combination of outdoor units”.
Installation Manual
Installation Manual
Remarks
SMMS-i
SMMS-i
No.
(1)
Piping parts
Name
Selection of pipe size
Connecting pipe size of outdoor unit
Header
unit A
Follower Follower
unit B
unit C
Follower
unit D
Type
MAP080
Gas side
Ø22.2
Liquid side
Ø12.7
Outdoor unit
È
Outdoor unit
connection piping
kit
Outdoor unit
Same as connecting
pipe size of the
outdoor unit.
Outdoor unit
connecting pipe
MAP100
MAP120
MAP140
MAP160
Ø22.2
Ø12.7
Ø28.6
Ø12.7
Ø28.6
Ø15.9
Ø28.6
Ø15.9
(2) Balance pipes Ø9.5
(1)
(1)
(1)
(8)
Pipe size for connecting piping between outdoor units
(1) Outdoor unit connecting pipes
Total capacity codes of
outdoor units at the
(8)
(8)
Gas
side
Liquid Balanc
downstream side
(2)
side
e pipe
(2)
Equivalentto Equivalentto
Pipe size differs based
on the total capacity
code value of outdoor
units at the
downstream side.
(See Table 2.)
HP
capacity
Between Outdoor Main connecting
(3) Main
piping
unit connection
piping kits
piping between
outdoor units
(2)
45.0 to below
61.5
(8) Outdoor unit connection piping kit (For linking of outdoor units)
16 to below 22
Ø28.6
Ø34.9
Ø15.9
Ø19.1
61.5 to below
73.0
22 to below 26
(7) Branching header
(6)
(4) Branching pipe
Ø9.5
73.0 to below
101.0
26 to below 36
36 or more
Ø34.9
Ø41.3
Ø19.1
Ø22.2
First branch
Y-shape
101.0 or more
(6) Y-shaped branching joint
(4)
(5) Indoor unit connecting pipe
(5)
branching joint
Size of main piping
(5)
(5)
(5)
Total capacity codes of all
outdoor units
Indoor unit
(4)
Gas
side
Liquid
side
Equivalent to
Equivalent to
capacity
HP
8 to below 12
12 to below 14
14 to below 22
22.4 to below 33.5
33.5 to below 38.4
38.4 to below 61.5
Ø22.2
Ø28.6
Ø28.6
Ø12.7
Ø12.7
Ø15.9
(6)
Outdoor unit
connection piping
kit of header unit
È
First branching
section
(6)
(4)
(6)
(6)
(4)
Pipe size differs based
on the capacity code
of the outdoor unit.
(See Table 2.)
(4)
Main piping
(3)
61.5 to below
101.0
22 to below 36
Ø34.9
Ø19.1
(5)
(5)
(5)
(5)
(5)
101.1 to below
130.0
36 to below 46
46 or more
Ø41.3
Ø22.2
Ø22.2
Indoor unit
130.0 or more
* Ø41.3
*
Maximum equivalent length of main pipe is 70m or less (The actual
length is 50m or less.).
Pipe size between branching sections *1
Total capacity codes of indoor
units at downstream side
Gas
side
Liquid
side
Equivalent to
Equivalent to HP
Pipe size differs based
on the total capacity
code value of indoor
units at the
capacity
Below 2.4
Below 6.6
Ø12.7
Ø15.9
Ø22.2
Ø28.6
Ø34.9
Ø41.3
Ø9.5
Ø9.5
downstream side. If
the total value
2.4 to below 6.4
6.4 to below 12.2
12.2 to below 20.2
6.6 to below 18.0
18.0 to below 34.0
34.0 to below 56.5
Branching section
È
Branching section
Branching pipe
(4)
Ø12.7
Ø15.9
Ø19.1
Ø22.2
exceeds the capacity
code of the outdoor
unit, apply the
capacity code of the
outdoor unit. (See
Table 1 and 2.)
20.2 to below 35.2 56.5 to below 98.5
35.2 or more 98.5 ore more
*1: If exceeding the main pipe size, set the size to the same as the
main pipe size.
EN
23-EN
24-EN
– 12 –
– 13 –
25-EN
26-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
No.
(5)
Piping parts
Name
Selection of pipe size
Connecting pipe size of indoor unit
Remarks
Liquid
Allowable length of refrigerant pipes and allowable height
difference between units
Capacity rank
Gas side
side
Ø6.4
Ø6.4
Ø6.4
Ø9.5
Ø12.7
D
15m or less real length
Real length exceeds 15m
Ø9.5
Ø12.7
Ø12.7
Ø15.9
Ø22.2
Branching section
È
Indoor unit
007 to 012 type
Follower unit
Indoor unit
connecting pipe
Outdoor unit
015 to 018 type
024 to 056 type
072 to 096 type
A
B
C
Header Follower Follower
unit unit unit
Height
difference
between
outdoor
units
Selection of branching section (Y-shaped branching joint)
Total capacity code of indoor units
H3 ≤ 5 m
Ld
Lc
La
Model name
Lb
Equivalent to
Equivalent to HP
capacity
Y-shaped
branching joint
Branching section
(6)
Below 6.4
Below 18.0
18.0 to below 40.0
40.0 to below 70.5
70.5 or more
RBM-BY55E
RBM-BY105E
RBM-BY205E
RBM-BY305E
LA
LB
6.4 to below 14.2
14.2 to below 25.2
25.2 or more
Y-shape
branching joint
Outdoor unit connection piping kit
(For linking of outdoor units)
The longest piping between outdoor units:
L0 ≤ 25 m
Selection of branching section (Branching header)
Total capacity code of indoor units
Height
difference
between
outdoor
Model name
Equivalent to
capacity
Equivalent to HP
and indoor
units:
H1 ≤ 70 m
Below 14.2
Below 40.0
RBM-HY1043E
For 4
branches
Branching header
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2043E
Below 14.2 Below 40.0 RBM-HY1083E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2083E
*2
Branching header
Y-shaped branching
joint
Branching section Branching header
(7)
Indoor unit connecting
For 8
branches
L7
c
pipe
First branching
section
Indoor unit
a
b
d
e
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of header. When the total capacity codes of all outdoor units are 12 to below
26 (equivalent to HP) and you use a branching header for the first branching section, use
a RBM-HY2043E or RBM-HY2083E regardless of the total capacity codes of outdoor units
at downstream side. In addition, you cannot use a branching header for the first branching
section when the total capacity codes of all outdoor units are over 26 (equivalent to HP).
L3
The longest piping length: L ≤ 235 m
The longest piping length from the first branch: Li ≤ 90 m
Height
difference
between
Y-shaped
branching joint
Outdoor unit connection piping kit (For linking of outdoor units)
L6
L5
L4
indoor units:
H2 ≤ 40 m
*3
Total capacity code of outdoor units
i
h
j
g
f
Model name
Equivalent to
Equivalent to HP
capacity
Outdoor unit
connection piping
Indoor unit
Outdoor unit
Below 26.0
Below 73.0
RBM-BT14E
RBM-BT24E
Branching section
(8)
kit (For linking of
outdoor units)
connection piping
kit (For linking of
outdoor units)
(j)
26.0 or more
Above 73.0
*3: Downstream side when regarding the main piping as the start point
Installation Manual
Installation Manual
SMMS-i
SMMS-i
◆System restriction
Airtightness test
After the refrigerant piping has been finished, execute an airtight test.
Outdoor unit combination
Total capacity of outdoor units
Indoor unit connection
Up to 4 units
Up to 48 HP
Up to 48 units
For an airtight test, connect a nitrogen gas canister as shown in the figure on the next page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side
and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on
header unit.
Total capacity of indoor units
(varies depending on the height difference between
indoor units.)
H2 ≤ 15m
135% of outdoor units’ capacity
105% of outdoor units’ capacity
15m < H2
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen
gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side
before applying pressure.
(When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the
liquid side are ball valves.)
◆Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) ≥ B ≥ C ≥ D
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit
and those to indoor units at a right angle as shown in figure 1 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
Do not connect them as in figure 2 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
• For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side.
Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
◆Allowable length and allowable height difference of refrigerant piping
Low pressure High pressure
Allowable
Item
Pipes
gauge
gauge
value
Connected to indoor unit
Main piping
Lessthan 34HP or
less
Total extension of
pipe (liquid pipe,
real length)
Less than 96kW
96kW or more
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4
+ L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
Gas side valve fully closed
Header outdoor unit
Service port
Gauge
manifold
VL
VH
34HP or more
Equivalent length
Real length
500m
235m
Farthest piping length L (*1)
Main piping length
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
190m
Brazed
Packed valve details
Reducing
valve
Equivalent length
Real length
120m (*2)
100m (*2)
L1
To outdoor unit
To gauge manifold
Copper pipe
Pipe length
Farthest equivalent piping length from the first branch Li
(*1)
Liquid-side service port
Liquid-side valve
Fully
90m (*3)
25m
L3 + L4 + L5 + L6 + j
LA + LB + Ld (LA + Lb, LA + LB + Lc)
La, Lb, Lc, Ld
Gas-side valve
closed
Farthest equivalent piping length between outdoor units L0
(*1)
Copper
pipe
To
Balance
service port
Service port
outdoor
To
outdoor
unit
Maximum equivalent piping length of pipes connected to
outdoor units
10m
unit
Gas-side
service port
Liquid valve fully closed
Nitrogen
gas
Fully
closed
Maximum real length of pipes connected to indoor units
Maximum equivalent length between branching sections
Upper outdoor
30m
50m
a, b, c, d, e, f, g, h, i, j
L2, L3, L4, L5, L6, L7
Piping at site
Balance valve
Piping at site
Piping at site
70m (*4)
40m (*5)
–
–
units
Service port
Height between outdoor and indoor
units H1
Lower outdoor
Balanced pipe side valve
fully closed
Height
difference
units
Height between indoor units H2
40m
5m
–
–
Height between indoor units H3
Connected to other follower units
*1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j)
Able to detect a serious leakage
1. Apply pressure 0.3MPa (3.0kg/cm²G) for 5 minutes or more.
2. Apply pressure 1.5MPa (15kg/cm²G) for 5 minutes or more.
*2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less.
*3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m.
*4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m.
*5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
Available to detect slow leakage
3. Apply pressure 3.73MPa (38kg/cm²G) for approx. 24 hours.
• If there is no pressure decrease after 24 hours, the test is passed.
EN
27-EN
28-EN
– 14 –
– 15 –
29-EN
30-EN
Installation Manual
Installation Manual
SMMS-i
NOTE
SMMS-i
Vacuum drying
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure
will change by about 0.01MPa (0.1kg/cm²G) per 1°C. Consider the pressure change when checking the test result.
• Be sure to perform vacuuming from both liquid and gas sides.
• Be sure to use a vacuum pump equipped with the counter-flow prevention function so that oil in the pump will
not flow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A
refrigerant, a problem may be caused in the refrigerating cycle.)
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points.
Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other
methods. After sealing, execute an airtight test again.
After finishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the liquid side,
gas side, and balance pipe side and connect a vacuum pump as shown in the figure below. Be sure to perform vacuuming for
the liquid, gas, and balance pipe sides.
Low pressure High pressure
gauge
gauge
Connected to indoor unit
Packed valve fully closed
(gas side)
Main pipe
Gauge
manifold
V
L
VH
Header outdoor unit
Service port
Brazed
Packed valve details
To outdoor unit
To gauge manifold
To
outdoor
unit
Fully
closed
Gas-side valve
Liquid-side service port
Liquid-side valve
P
Service port
To
Balance
outdoor
unit
service port
Vacuum pump
Gas-side
Packed valve fully closed
(liquid side)
service port
Fully
closed
Piping at site
Piping at site
Balance
valve
Piping at site
Service port
Packed valve fully closed
(balance)
Follower units
• Use a vacuum pump with a high vacuuming degree [-100.7kPa (5Torr, -755mmHg)] and large exhaust gas
amount (40L/minute or larger).
• Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the
packed valves at the liquid side, gas side, and balance pipe side are fully closed.
• If the pressure does not reach -100.7kPa or less, continue vacuuming for 1 hour or more. If the pressure does
not reach -100.7kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage.
• If the pressure reaches -100.7kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on
the gauge manifold fully and stop the vacuum pump. Leave it as it is for 1 hour to confirm that the vacuuming
degree does not change.
If the degree of vacuum loss is large, moisture may remain in the pipes. In that case, inject dry nitrogen gas and
apply pressure to 0.05MPa and perform vacuuming again.
• After finishing the above procedure of vacuuming, exchange the vacuum pump with a refrigerant canister and
advance to the additional charging of refrigerant.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Table 2
Adding refrigerant
C (Corrective amount
of refrigerant) (kg)
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Combined HP (HP)
Combined outdoor units (HP)
8
8HP
10HP
12HP
14HP
16HP
10HP
10HP
12HP
12HP
16HP
16HP
16HP
16HP
12HP
12HP
16HP
16HP
16HP
16HP
16HP
16HP
8HP
–
–
–
–
1.5
2.5
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
16
24
26
28
30
32
34
36
38
40
42
44
46
48
–
–
–
–
–
3.5
–
–
–
8.5
NOTE
–
–
–
10.5
0.0
8HP
–
–
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional
refrigerant.
10HP
10HP
12HP
10HP
12HP
14HP
16HP
12HP
12HP
12HP
12HP
14HP
16HP
16HP
16HP
8HP
–
–
3.0
–
–
5.0
–
–
7.5
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Heat pump
type
–
–
8.5
Charging amount (kg)
11.5
Standard type
–
–
9.5
–
–
11.5
12.5
3.0
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Cooling only
type
–
–
Charging amount (kg)
10.5
10.5
10.5
11.5
11.5
10HP
12HP
10HP
12HP
12HP
12HP
14HP
16HP
–
–
–
–
4.0
Corrective amount of refrigerant
depending on HP of co-
operating outdoor units
(Table 2)
Additional refrigerant charge
amount per 1m liquid pipe
(Table 1)
Additional refrigerant charge
amount at local site
6.0
Real length of liquid pipe
=
×
+
–
7.0
–
8.0
Table 1
–
10.0
12.0
14.0
0.0
Liquid pipe dia. (mm)
6.4
9.5
12.7
15.9
19.1
22.2
–
Additional refrigerant amount/1m liquid
pipe (kg/m)
–
0.025
0.055
0.105
0.160
0.250
0.350
–
8HP
8HP
8HP
8HP
8HP
10HP
8HP
8HP
8HP
10HP
10HP
10HP
10HP
12HP
12HP
–
-4.0
-4.0
-2.0
0.0
10HP
10HP
10HP
8HP
8HP
–
10HP
10HP
8HP
–
–
8HP
8HP
8HP
8HP
10HP
10HP
10HP
10HP
12HP
-6.0
-6.0
-6.0
-6.0
-5.0
-4.0
-2.0
0.0
10HP
10HP
10HP
10HP
12HP
12HP
12HP
12HP
8HP
High Efficiency type
10HP
10HP
10HP
10HP
12HP
12HP
12HP
2.0
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
EN
31-EN
32-EN
– 16 –
– 17 –
33-EN
34-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Full opening of the valve
F-GAS label
Open the valves of the outdoor unit fully.
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of Gas
• Global Warming Potential (GWP) of Gas
R410A
1975
MAP080
MAP100
MAP120
MAP140
MAP160
Packed valve
Ball valve
CAUTION
Using a 4mm-hexagonal wrench, Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the
fully open the valve rods.
stopper. (Full open)
1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included
transparent protective sheet over the label to prevent the writing from rubbing off.
Position of screwdriver slot
Fully opened
Service
port
Valve unit
Fully closed
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any
relevant local legislation.
Using flathead
screwdriver, turn it
counterclockwise by
90° until it hits the
stopper. (Full open)
Liquid side
(1)
(2)
Slot
Flare nut
*
When opened fully, do not apply
excessive torque after the screwdriver hits
the stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Balance packed valve
Using a 4mm-hexagonal wrench, fully open the valve rods.
Balance pipe
Ball valve
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper.
(Full open)
Pre-charged Refrigerant at Factory [kg],
specified in the nameplate
R410A
kg
Additional Charge on Installation Site
kg
kg
[kg]
Gas side
Fully opened
Fully closed
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping/wiring panel with the piping
cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
When using the piping cover
When not using the piping cover
8 ELECTRIC WIRING
Piping/wiring panel
Piping/wiring panel
WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
Drawing-out sideward
Drawing-out sideward
CAUTION
Fill silicon or putty into the
periphery of the pipes.
Close the opening with the
pipe cover.
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise,
the unit may break down.
Drawing-out
frontward
Drawing-out
frontward
Drawing-out
downward
Drawing-out
downward
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
◆Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm)
Ø15.9 - Ø19.1
Interval
2m
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.
Ø22.2 - Ø41.3
3m
Power supply specifications
Do not bridge the power between outdoor units
through the equipped terminal blocks (L1, L2, L3,
N).
Power supply for
outdoor units
NO GOOD
◆Power wiring selection
Standard model
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Power Supply
MCA
(A)
MOCP
(A)
Model
Phase and frequency
Nominal Voltage
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
23.5
25.5
28.5
33.2
36.5
32
32
40
40
50
3N~ 50Hz
380-400-415V
MMY-AP1814*
MMY-AP2014*
MMY-AP2214*
MMY-AP2414*
MMY-AP2614*
MMY-AP2814*
MMY-AP3014*
MMY-AP3214*
49.0
51.0
54.0
57.0
62.0
65.0
69.7
73.0
63
63
63
63
80
80
80
100
3N~ 50Hz
380-400-415V
EN
35-EN
36-EN
– 18 –
– 19 –
37-EN
38-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Power Supply
Phase and frequency
Specifications for communication wiring
MCA
(A)
MOCP
(A)
Model
Nominal Voltage
MMY-AP3414*
MMY-AP3614*
MMY-AP3814*
MMY-AP4014*
MMY-AP4214*
MMY-AP4414*
MMY-AP4614*
MMY-AP4814*
82.5
85.5
90.5
93.5
98.2
101.5
106.2
109.5
100
100
100
125
125
125
125
125
◆Design of communication wiring
Summary of communication wiring
3N~ 50Hz
380-400-415V
Header outdoor
Follower outdoor
High efficiency model
MCA
(A)
MOCP
(A)
Model
Phase and frequency
Nominal Voltage
MMY-AP1624*
3N~ 50Hz
380-400-415V
46.9
63
U1 U2 U3 U4 U5 U6
U1 U2 U3 U4 U5 U6
MMY-AP2424*
MMY-AP2624*
MMY-AP2824*
MMY-AP3024*
70.4
72.4
74.5
76.5
80
80
100
100
Central control
controller
3N~ 50Hz
380-400-415V
U1 U2
U3 U4
Communication wiring between outdoor units (Shield wire)
MMY-AP3224*
MMY-AP3424*
MMY-AP3624*
MMY-AP3824*
MMY-AP4024*
MMY-AP4224*
MMY-AP4424*
MMY-AP4624*
MMY-AP4824*
93.8
95.9
97.9
100.0
102.0
105.0
108.0
111.0
114.0
125
125
125
125
125
125
125
125
125
Communication wiring between indoor and outdoor units
(Shield wire)
Communication wiring between indoor units (Shield wire)
3N~ 50Hz
380-400-415V
U1 U2
A
A
B
B
U1 U2
A
B
U1 U2
A
B
U1 U2
A
B
Indoor unit
Indoor unit
Indoor unit
Indoor unit
A
B
A
B
Remote controller
Remote controller
Remote controller
(Group control)
L1L2L3 N
L1L2L3 N
L1L2L3 N
L1L2L3 N
• Communication wiring and central control wiring use 2-core non-polarity wires.
Use 2-core shield wires to prevent noise trouble.
In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
Perform the ground of wires at one side only for the header outdoor unit.
• Use 2-core non-polarity wire for remote controller. (A, B terminals)
Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
Circuit breaker
(Earth leakage breaker)
Main switch
(Fuse)
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Be sure to keep the rule of below tables about size and length of communication wiring.
◆Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
Central
control
controller
Indoor unit
Super modular multi system
U1 U2
U3 U4
No.1
No.2
A B
No.8
A B
No.4
A B
No.7
A B
No.3
Table-1
L4
A B
A B
Header
Follower
unit
Header
unit
Follower
unit
Header
unit
Follower Follower
unit
unit
U3 U4
unit
(A.B)
Remote controller
U3 U4
U3 U4
U3 U4
U3 U4
U3 U4
U3 U4
Outdoor unit
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
Connection of power wires and communication wires
L5
Table-1
L1
Table-2
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and
communication wires through the holes.
L2
L3
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
A
U1 U2
U1 U2
A
Indoor unit
A
B
A
B
A
B
A
B
A
B
B
A
B
B
Table-3
L7
L6
Remote controller
Remote controller
Remote controller
Piping/wiring panel
Table-1
Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring
(L4)
Knockout for the
communication wire
Knockout for the power
Wiring
2-core, non-polarity
supply wire
Knockout for the power
wire
Type
Shield wire
Size/Length
1.25 mm2: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)
NOTE
Be sure to separate the power wire and communication wires.
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
Table-2
Communication wiring between outdoor units (L5)
Wiring
2-core, non-polarity
Type
Shield wire
Size/Length
1.25 mm2 to 2.0 mm2/Up to 100 m (L5)
Table-3
Remote controller wiring (L6, L7)
Wire
Size
2-core, non-polarity
0.5 mm2 to 2.0 mm2
• Up to 500 m (L6 + L7)
Length
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
EN
39-EN
40-EN
– 20 –
– 21 –
41-EN
42-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Screw size and tightening torque
Tightening torque
(N•m)
Screw size
Power supply terminal
Earth screw
M6
M8
2.5 to 3.0
5.5 to 6.6
Power supply terminal
block
◆Communication wire connection
Cord clamps
Get the communication wire through the cutout on the side of the electric parts box and connect it to the communication wire
terminals, then fix it with the communication cable clamp.
Communication
terminal block
Power supply wires
Cord clamp
Earth screw
U1 U2 U3 U4 U5 U6
Communication
wires
TO
TO
TO
OUTDOOR
UNIT
CENTRAL
CONTROL
LER
INDOOR
UNIT
◆Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electric parts box and connect the power supply
wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply wire
with the 2 cord clamps.
U5, U6: Communication wiring between outdoor units
U3, U4: Central control device
2. Be sure to use round-type crimping terminals for power connection.
U1, U2: Communication wiring between Indoor/Outdoor unit
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
Screw size and tightening torque
Tightening torque
(N•m)
Screw size
M3.5
L1 L2 L3
N
Communication wire terminal
0.80 to 0.96
L1 L2 L3
N
10mm or more
Power supply wire
Earth line
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Regulation of high frequency wave
9 ADDRESS SETTING
On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1)
at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7-
segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a
malfunction.
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused
from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the
interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the
interface point.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by
turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Ssc (*1)
Model
Ssc (kVA)
1004
MMY-MAP0804HT8(Z)(ZG)-E
MMY-MAP0804T8(Z)(ZG)-E
Automatic addressing:
Manual addressing:
setting addresses using SW15 on the interface P.C. board on the header outdoor unit
setting addresses on the wired remote controller.
* When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group
operation and no Remote controller)
MMY-MAP1004HT8(Z)(ZG)-E
MMY-MAP1004T8(Z)(ZG)-E
1290
1560
1692
1942
MMY-MAP1204HT8(Z)(ZG)-E
MMY-MAP1204T8(Z)(ZG)-E
MMY-MAP1404HT8(Z)(ZG)-E
MMY-MAP1404T8(Z)(ZG)-E
MMY-MAP1604HT8(Z)(ZG)-E
MMY-MAP1604T8(Z)(ZG)-E
REQUIREMENT
Access
door cover
• High voltage parts exist in the electrical control box.
If you set addresses on an outdoor unit, operate the
unit through the access door shown on the illustration
on the right to avoid electric shock. Do not remove the
cover of electrical control box.
Cover of the electrical
control box
Fixing screw for the
access door cover
* After finishing operations, close the access door cover
and fix it with the screw.
Automatic address setting
No central control:
Central control of 2 or more refrigerant lines:
go to Address setting procedure 1
go to Address setting procedure 2
When controlling a single refrigerant line
When controlling 2 or more refrigerant lines
centrally
(Example)
centrally
Address setting
procedure
To procedure 1
To procedure 2
Central
remote
Outdoor
Indoor
Central
remote
Outdoor
Outdoor
Indoor
Central
remote
Outdoor
controller
controller
controller
System wiring
diagram
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Remote
Remote
Remote
controller
Remote
Remote
Remote
controller
controller controller
controller controller
EN
43-EN
44-EN
– 22 –
– 23 –
45-EN
46-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
◆Address setting procedure 1
◆Address setting procedure 2
1
2
Turn on indoor units first, and then turn on outdoor units.
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system.
(Factory default: Address 1)
About one minute after turning the power on, confirm that the 7-segment display on the interface
U. 1. L08 (U. 1. flash)
P.C. board of the header outdoor unit indicates
.
NOTE
3
4
Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom
side.
Auto 1 → Auto 2 → Auto 3
The 7-segment display indicates
.
U. 1. - - - (U. 1. flash)
After the indication,
When the flashing stops and
complete.
starts flashing on the display.
Interface P.C. board on the header outdoor unit
U. 1. - - - (U. 1. light)
remain lit on the display, the setting is
SW06
SW07
SW09
SW10
Interface P.C. board on the header outdoor unit
1 2 3 4
SW11
1 2 3 4
SW12
1 2 3 4
SW13
1 2 3 4
SW14
SW05
SW15
SW04
3
D600 D601 D602 D603
D604
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
2,4
SW02
SW03
SW01
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
({: switch ON, ✕: switch OFF)
SW13
SW14
Line (system) address
1
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
3
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
4
1
2
3
4
REQUIREMENT
1
2
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
✕
{
{
{
{
{
{
{
{
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
{
✕
✕
✕
{
{
✕
✕
{
{
✕
✕
{
{
✕
✕
{
{
✕
✕
{
{
✕
✕
{
{
✕
✕
✕
✕
✕
{
{
{
{
✕
✕
✕
✕
{
{
{
{
✕
✕
✕
✕
{
{
{
{
✕
✕
✕
✕
✕
✕
✕
✕
✕
{
{
{
{
{
{
{
{
✕
✕
✕
✕
✕
✕
✕
✕
{
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group
before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case,
the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to
make one unit the header unit using wired remote controller.
3
4
5
6
7
(Example)
Controlling 2 or more refrigerant lines as a group
8
9
Outdoor
Indoor
Outdoor
Indoor
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
System wiring
diagram
Indoor
Indoor
(Group control)
Remote
controller
Installation Manual
Installation Manual
SMMS-i
SMMS-i
9
Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor
unit of each refrigerant line.
SW13
SW14
Line (system) address
1
–
–
–
2
–
–
–
3
–
–
–
4
1
2
3
4
26
27
28
{
{
{
{
✕
{
✕
{
{
✕
✕
✕
{
{
{
“–”: not used for system address setting (Do not change their positions.)
2
Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the
header outdoor units that will be connected to the central control. (Factory default: disconnected)
9
U1 U2 U3 U4 U5 U6
TO
TO
INDOOR
UNIT
TO
OUTDOOR
UNIT
CENTRAL
CONTROL
LER
10 Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
2
Header unit interface P.C. board
U1 U2 U3 U4 U5 U6
TO
TO
INDOOR
UNIT
TO
OUTDOOR
UNIT
CENTRAL
CONTROL
LER
SW15
SW04 SW05
3
4
Turn on indoor units first, and then turn on outdoor units.
7-segment
display
D600 D601 D602 D603 D604
SW01 SW02 SW03
About 1 minute after turning the power on, confirm that the 7-segment display on the interface
U. 1. L08 (U. 1. flash)
P.C. board of the header outdoor unit indicates
.
5
6
Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
SW13
SW14
Auto 1 → Auto 2 → Auto 3
The 7-segment display indicates
.
U. 1. - - - (U. 1. flash)
After the indication,
When the flashing stops and
complete.
starts flashing on the display.
U. 1. - - - (U. 1. light)
, remains lit on the display, the setting is
7
8
Repeat steps 4 to 6 for other refrigerant lines.
SW30
1
2
After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that
has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
EN
47-EN
48-EN
– 24 –
– 25 –
49-EN
50-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
*The items in bold font must be set manually.
Switch setting (setting example when
controlling 2 or more refrigerant lines
centrally)
CAUTION
Relay connector connection
Outdoor units (setting manually)
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Outdoor unit’s interface
Header unit
Follower unit
Header unit
2
Follower unit
Header unit
3
Factory default
P.C. board
SW13, 14
(No setting
required)
(No setting
required)
1
1
(Line (system) address)
Dip switch 2 of SW30
(Terminator of indoor/
outdoor communication
line and central control
line)
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
Set to OFF
after setting
addresses.
Set to OFF
after setting
addresses.
(No setting
required)
(No setting
required)
ON
ON
Connect after
setting
addresses.
Connect after
setting
addresses.
Connect after
setting
addresses.
Relay connector
Open
Open
Open
▼ Wiring example of 2 refrigerant lines
Refrigerant line 1
Refrigerant line 2
Outdoor
unit
Outdoor
unit
Central
control
controller
Follower unit
U3 U4
Follower unit
Header unit
Header unit
Header unit
U3 U4
U3 U4
U3 U4
U3 U4
Indoor unit 1
Indoor unit 2
Indoor unit 1
Indoor unit 2
Indoor unit 3
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
Remote
controller
Relay
connector
Relay
connector
Relay
connector
Line (system) address
Indoor unit address
1
1
1
2
1
3
2
2
1
2
2
2
1
2
2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
Group address
Header unit
Follower unit
Follower unit
Follower unit
Follower unit
A
B
A
B
A
B
A
B
A
B
In the example above, disconnect the remote controller connections between the indoor units and connect
a wired remote controller to the target unit directly before address setting.
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Individual
Group
CODE No.
Indoor units
(automatic setting)
SET DATA SETTING
UNIT No.
R.C.
No.
SET DATA
CODE No.
Line (system) address
Indoor unit address
Group address
1
1
0
1
2
0
2
1
1
2
3
1
0
TEMP.
ON / OFF
2, 5, 8
4, 7, 10
11
2
2
3, 6, 9
TIMER SET
TIME
FILTER
RESET TEST
SET CL
1
Pair the indoor unit to set and the remote controller
one-to-one.
Turn on the power.
SET
CL
TEST
1
Push and hold the
,
, and
buttons at
the same time for more than 4 seconds.
LCD starts flashing.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
<Line (system) address>
To find an indoor unit’s position from its
address
Confirming the indoor unit
addresses and the position of
an indoor unit using the
remote controller
NOTE
2
3
Push the TEMP.
repeatedly to set the CODE No. to
/
buttons
1. Do not use address numbers 29 or 30 when setting
system addresses using the remote controller.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [E04] (Indoor/
outdoor communication error) will appear if they are
mistakenly used.
2. If you set addresses to indoor units in 2 or more
refrigerate lines manually using the remote
controller and will control them centrally, set the
header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface
P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected
to the same central control, except the unit that
has the lowest address. (For unifying the
termination of the wiring for the central control of
indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.
.
▼ When checking unit numbers controlled as a
group
Push the TIME buttons repeatedly to
set a system address.
/
(Match the address with the address on the
interface P.C. board of the header outdoor unit in
the same refrigerant line.)
CODE No.
SET DATA
SETTING
UNIT No.
◆Confirming the numbers and
R.C.
No.
positions of indoor units
SET
4
Push
button.
TEMP.
ON / OFF
(It is OK if the display turns on.)
To see the indoor unit address of an
indoor unit which you know the position of
TIMER SET
TIME
<Indoor unit address>
3
FILTER
RESET TEST
▼ When the unit is individual (the indoor unit is
paired with a wired remote controller one-to-
one), or it is a group-controlled one.
1
2
Stop
SET CL
5
6
7
Push the TEMP.
repeatedly to set the CODE No. to
/
buttons
.
Push the TIME buttons repeatedly to
set an indoor unit address.
/
1
SET
CODE No.
Push the
button.
(Execute it while the units are stopped.)
UNIT No.
(It is OK if the display turns on.)
The indoor unit numbers in a group are indicated one after
another. The fan and louvers of the indicated units are
activated.
<Group address>
TEMP.
ON / OFF
• After finishing all the settings above, set the
address of the central control devices. (For the
setting of the central control address, refer to the
installation manuals of the central control
devices.)
1
VENT
TEST
8
9
Push the TEMP.
repeatedly to set the CODE No. to
/
buttons
Starts
running
TIMER SET
TIME
1
Push and hold the
and
buttons at
.
the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the
group are activated.
FILTER
RESET TEST
SET CL
•
Push the TIME
set a group address. If the indoor unit is
individual, set the address to ; header
/
buttons repeatedly to
2
unit,
; follower unit,
.
2
Push the
button (left side of the
Individual
Header unit
Follower unit
: 0000
: 0001
: 0002
button). Each time you push the button, the
indoor unit numbers are indicated one after
another.
• The first-indicated unit number is the address of
the header unit.
(Execute it while the units are running.)
In case of group
control
}
ON / OFF
1
2
Push the
button if the units stop.
button (left side of the
SET
10 Push the
button.
Push the
button).
A unit numbers
(It is OK if the display turns on.)
• Only the fan and louvers of the indicated indoor
unit are activated.
TEST
11 Push the
button.
is indicated on the LCD (it will
The address setting is complete.
TEST
disappear after a few seconds). The indicated
number shows the system address and indoor unit
address of the unit.
3
Push the
button to finish the procedure.
All the indoor units in the group stop.
(
SETTING
flashes. You can control the unit after
SETTING
has disappeared.)
When 2 or more indoor units are connected to the
remote controller (group-controlled units), a
number of other connected units appears each
▼ To check all the indoor unit addresses using
an arbitrary wired remote controller.
(When communication wirings of 2 or more
time you push the
button).
button (left side of the
EN
51-EN
52-EN
– 26 –
– 27 –
53-EN
54-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
TEST
refrigerant lines are interconnected for central
control)
6
Push the
button to finish the procedure.
6
Push the
button (left side of the
button) repeatedly to select another indoor
UNIT No. to change.
▼ To change all the indoor unit addresses using
an arbitrary wired remote controller.
(The method is available when the addresses
have already been set automatically.)
Changing the indoor unit
address using a remote
controller
Repeat steps 4 to 6 to change the indoor unit
addresses so as to make each of them unique.
CODE No.
SET DATA SETTING
UNIT No.
(When communication wirings of 2 or more
refrigerant lines are interconnected for central
control)
R.C.
No.
7
8
Push the
button (left side of the
button) to check the changed addresses.
TEMP.
ON / OFF
To change an indoor unit address using a
wired remote controller.
NOTE
If the addresses have been changed
correctly, push the
procedure.
TIMER SET
TEST
button to finish the
You can change the addresses of indoor units in each
refrigerant line using an arbitrary wired remote controller.
TIME
1
FILTER
RESET TEST
▼ The method to change the address of an
individual indoor unit (the indoor unit is paired
with a wired remote controller one-to-one), or
an indoor unit in a group.
(The method is available when the addresses
have already been set automatically.)
SET CL
2
* Enter the address check/change mode and change
the addresses.
6
3
4
5
CODE No.
SET DATA SETTING
UNIT No.
(Execute it while the units are stopped.)
R.C.
No.
CODE No.
You can check indoor unit addresses and positions of the
indoor units in a single refrigerant line.
SET DATA SETTING
UNIT No.
TEMP.
ON / OFF
R.C.
No.
When an outdoor unit is selected, the indoor unit numbers of
the refrigerant line of the selected unit are indicated one after
another and the fan and louvers of the indicated indoor units
are activated.
TIMER SET
TIME
TEMP.
ON / OFF
3
5
FILTER
RESET TEST
1
3
TIMER SET
TIME
SET CL
4
2
TEST
1
Push and hold the TIME
and
buttons
FILTER
RESET TEST
SET CL
at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
Cancels the line selection
8
Finish
(Address Change) are indicated on the LCD
display. (Select an outdoor unit.)
If no number appears on UNIT No., no outdoor unit exists on
CL
the line. Push
step 2.
button and select another line following
1
2, 6, 7
2
3
Push the
(left side of the button) and
SWING/FIX
(Execute it while the units are stopped.)
buttons repeatedly to select a system
address.
(Execute it while the units are stopped.)
SET
CL
TEST
SET
1
Push and hold the
,
, and
buttons at
Push the
address selection.
button to confirm the system
1
Push and hold the TIME
/
buttons at
the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group,
the first indicated UNIT No. is that of the head
unit.)
the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD
display.
• The address of an indoor unit connected to the
selected refrigerant line is indicated on the LCD
display and its fan and louvers are activated.
2
Push the
button (left side of the
4
Push the
button (left side of the
2
Push
(left side of the button) and
buttons repeatedly to select a system
button) repeatedly to select an indoor unit
number to change if 2 or more units are
controlled in a group. (The fan and louvers
of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
SWING/FIX
button). Each time you push the button, the
indoor unit numbers of the selected
refrigerant line are indicated one after
another.
• Only the fan and louvers of the indicated indoor
unit are activated.
address.
3
4
Push the TEMP.
repeatedly to select
/
buttons
for CODE No..
◆To select another system address
Push the TIME
change the value indicated in the SET DATA
section to that you want.
/
buttons repeatedly to
CL
5
Push the
CL button to return to step 2.
• After returning to step 2, select another system
address and check the indoor unit addresses of
the line.
SET
5
Push the
button.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
SET
3
Push the
button.
Resetting the address
• The address of one of the indoor units
connected to the selected refrigerant line is
indicated on the LCD display and the fan and
louvers of the unit are activated.
(Resetting to the factory
Central control
controller
default (address undecided))
Method 1
Clearing each address separately using a wired remote
controller.
U1 U2
U3 U4
At first, the current indoor unit address is
displayed in SET DATA.
Header
unit
Header
unit
Header
unit
Follower unit
Follower unit
(No system address is indicated.)
U3 U4
U3 U4
U3 U4
U3 U4
U3 U4
Set the system address, indoor unit address and group
address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting
procedures using the wired remote controller on the previous
pages.)
CODE No.
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
SET DATA SETTING
UNIT No.
R.C.
No.
Method 2
TEMP.
ON / OFF
Clearing all the indoor unit addresses on a refrigerate line at
once from the outdoor unit.
TIMER SET
TIME
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
1
Turn off the refrigerant line to reset to the
factory default and set the header outdoor
unit of the line as below.
4
A
B
A
B
A
B
A
B
A
B
FILTER
RESET TEST
SET CL
6
8
Remote
controller
Remote
controller
Remote
controller
Remote
controller
1) Disconnect the relay connectors between the
[U1, U2] and [U3, U4] terminals.
Finish
(Leave them as they are if they have already
been disconnected.)
Press to finish
setting.
5, 7
Indoor units to have their addresses initialized
2) Turn on dip switch 2 of SW30 on the interface
P.C. board of the header outdoor unit if the
switch is OFF.
4
Push the TIME
change the value of the indoor unit address
in SET DATA.
Change the value in SET DATA to that of a
new address.
/
buttons repeatedly to
2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on
the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header
outdoor unit of the refrigerant line as follows.
(Leave it as it is if it has already been set to
ON.)
SW01 SW02 SW03
SW04
Clearable addresses
SET
5
6
Push the
button to confirm the new
Confirm that the 7-segment display indicates
“A.d.buS” and turn SW04 ON for more than five
seconds.
address on SET DATA.
2
2
1
2
2
2
System/indoor unit/group address
Push the
button (left side of the
Confirm that the 7-segment display indicates
“A.d.nEt” and turn SW04 ON for more than five
seconds.
button) repeatedly to select another address
to change. Each time you push the button,
the indoor unit numbers in a refrigerant line
are indicated one after another. Only the fan
and louvers of the selected indoor unit are
activated.
Central control address
3
4
Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
completed successfully.
Repeat steps 4 to 6 to change the indoor unit
addresses so as to make each of them unique.
If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
SET
7
8
Push the
button.
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
(All the segments on the LCD display light up.)
TEST
Push the
button to finish the procedure.
5
Set the addresses again after finishing the clearance.
EN
55-EN
56-EN
– 28 –
– 29 –
57-EN
58-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
◆When executing a test run using
the interface P.C. board on the
outdoor unit
You can execute a test run by operating switches on the
interface P.C. board of the header outdoor unit.
“Individual trial”, which tests each indoor unit separately, and
“corrective trial”, which tests all the indoor units connected,
are available.
NOTE
10TEST RUN
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor
unit is OPEN.
• Before turning on the power, confirm that the
resistance between the terminal block of power
supply and the earth is more than 1MΩ using a 500V
megohmmeter.
TEMP.
ON / OFF
2, 4
3
• The running mode follows the mode setting on the
remote controller of the target indoor unit.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after
turning the power on or stopping running.
TIMER SET
TIME
FILTER
RESET TEST
SET CL
1, 5
<Individual test operation>
▼ Finishing operation
Do not run the unit if it is less than 1MΩ.
TEST
1
Push and hold the
button for more than 4
▼ Starting operation
1
Set the rotary switches on the interface P.C.
board of the header unit back: SW01 to [1],
SW02 to [1] and SW03 to [1].
seconds. TEST appears on the LCD display
and the unit enters the trial mode.
(TEST is indicated on the LCD display during
the test run.)
CAUTION
1
Set the running mode to “COOL” or “HEAT”
on the remote controller of the indoor unit to
be tested.
•
Turn on the power and turn on the case heater of the
compressor.
7-segment display
(The unit will run in the current mode unless
you set the mode otherwise.)
To save the compressor when it is activated, leave the
power on for more than 12 hours.
[A]
[U1]
[B]
TEST
[
]
7-segment display
[A]
[B]
Methods of test run
[U1]
[
]
ON / OFF
2
3
Push the
Push the
button.
MODE
button to switch the running
◆When executing a test run using a
mode to COOL or HEAT.
remote controller
2
Set the rotary switches on the interface P.C.
board of the header outdoor unit: SW01 to
[16], SW02 and SW03 to the address of the
indoor unit to be tested.
NOTE
Operate the system normally to check the running condition
using the wired remote controller. Follow the instructions in
the supplied owner’s manual when operating the unit.
If you use a wireless remote controller for operations, follow
the instructions in the installation manual supplied with the
indoor unit.
To execute a test run forcibly under the condition that the
thermostat automatically turns the unit off due to the indoor
temperature, follow the procedure below.
• Do not run the unit in any mode other than COOL or
HEAT.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
SW02
SW03
Indoor unit address
1 to 16
1 to 16
1 to 16
1 to 16
1
2
3
4
1 to 16 Set number of SW02
17 to 32 Set number of SW02 + 16
33 to 48 Set number of SW02 + 32
49 to 64 Set number of SW02 + 48
The forcible test run will automatically stop after 60 minutes
to prevent continuous forcible running and return to normal
running.
TEST
7-segment display
[B]
CAUTION
[A]
[
]
[
]
ON / OFF
4
5
Push the
button to stop running
Do not use forcible running except for a test run as it
overloads the unit.
ꢀ
Address display of the
corresponding indoor unit
after finishing the trial run.
The indication on the LCD display returns to
the status of procedure 1.
3
Push and hold SW04 for more than 10
seconds.
TEST
Push the
button to exit the trial mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.)
7-segment display
[A]
[B]
[
]
[
]
ꢀ
ꢀ
Address display of the
[FF] is displayed for 5
corresponding indoor unit seconds.
Installation Manual
Installation Manual
SMMS-i
SMMS-i
<Corrective trial>
Interface PC board
▼ Start operation
SW04 SW05 SW15
Push switch
Push switch
1
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
D600 D601 D602 D603 D604
7-segment
display [A]
7-segment
display [B]
SW01 SW02 SW03
Rotary switches
7-segment display
[A]
[C
[H
[B]
]
]
[
[
]
]
2
Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A]
[B]
[C
[H
]
]
[
[
-
C
H
]
]
-
▼ Stop operation
1
Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[
]
EN
59-EN
60-EN
– 30 –
– 31 –
61-EN
62-EN
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Check code
11TROUBLESHOOTING
Indication on 7-segment display on the outdoor unit
Auxiliary code
Check code name
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by
checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Outdoor temp. sensor miswiring
Outdoor pressure sensor miswiring (TE1, TL)
F15
—
—
Set every dip switch to OFF after checking.
Outdoor temp. sensor miswiring
Outdoor pressure sensor miswiring (Pd, Ps)
F16
7-Segment display and check code
F22
F23
F24
F31
—
—
—
—
TD3 sensor error
Ps sensor error
Rotary switch setting value
D600 D601 D602 D603 D604
Pd sensor error
Indication
LED
SW01
SW02
SW03
Outdoor EEPROM error
A
B
01: Compressor 1
02: Compressor 2
03: Compressor 3
H01
H02
H03
Compressor breaking down
Compressor error (Locked)
Current detection circuit error
Outdoor unit number
(U1 to U4)
A
B
1
1
1
Outdoor unit check code
01: Compressor 1
02: Compressor 2
03: Compressor 3
Check code display*
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
01: Compressor 1
02: Compressor 2
03: Compressor 3
Check code (indicated on the 7-segment display on the outdoor unit)
H05
H06
H07
—
—
—
TD1 sensor miswiring
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Low pressure proctive operation
Oil level down detection
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
Check code name
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
05: TK5 sensor error
E06
Number of indoor units which received normally
Decrease of number of indoor units
Indoor/outdoor communication circuit error
Duplication of indoor addresses.
H08
H15
H16
Temperature sensor error for oil level
TD2 sensor miswiring
E07
E08
—
Duplicated indoor addresses
—
01: Communication between indoor and outdoor units
02: Communication between outdoor units
E12
E15
E16
Automatic addressing start error
01: TK1 oil circuit error
02: TK2 oil circuit error
03: TK3 oil circuit error
04: TK4 oil circuit error
05: TK5 oil circuit error
—
No indoor unit during automatic addressing
Capacity over / number of connected indoor units
Oil level detector circuit error
00: Capacity over
01~: Number of connected units
H25
L04
L06
L08
L10
L17
L28
L29
L30
L31
P03
—
—
TD3 sensor miswiring
00: Header is nothing
02: 2 or more header units
E19
E20
Number of header outdoor unit error
Outdoor system address duplication
Duplication of indoor units with priority
Indoor unit group/address unset
Outdoor unit capacity unset.
Mismatch of the outdoor unit model
Outdoor connected quantity over
IPDU quantity error
01: Other line indoor connected
02: Other line indoor connected
Number of prior indoor units
Other lines connected during automatic addressing
—
—
—
—
E23
E25
E26
E28
E31
F04
F05
—
Sending error between outdoor units communication
Duplicated follower outdoor address set up
Decrease of connected outdoor units
Follower outdoor unit error
—
Number of outdoor units which received normally
Detected outdoor
(*1)
IPDU number information
(*1)
IPDU quantity information
IPDU communication error
Detected indoor unit address
External interlock of indoor unit
Other compressor errors
—
—
TD1 sensor error
—
—
TD2 sensor error
Discharge temperature TD1 error
01: TE1 sensor
02: TE2 sensor
TE1 sensor error
TE2 sensor error
F06
01: Compressor 1
02: Compressor 2
03: Compressor 3
P04
High-pressure SW system operation
Phase missing/power failure detection
Inverter DC voltage error (on compressor)
F07
F08
F12
—
—
—
TL sensor error
TO sensor error
TS1 sensor error
00:
01: Compressor 1
02: Compressor 2
03: Compressor 3
P05
01: Compressor 1
02: Compressor 2
03: Compressor 3
F13
TH (Heat sink) sensor error
Installation Manual
Installation Manual
SMMS-i
SMMS-i
Check code
12MACHINE CARD AND LOGBOOK
Indication on 7-segment display on the outdoor unit
Auxiliary code
Check code name
Machine card
01: Compressor 1
02: Compressor 2
03: Compressor 3
P07
Heat sink overheat error
Indoor overflow error
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before
delivery to the customer.
P10
P13
Detected indoor unit address
—
Outdoor unit flow back error detected
Describe the following items on the machine card:
01: TS condition
02: TD condition
name, address and telephone number of the installer, his service department, the service department of the party concerned
or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
P15
Gas leak detection
P17
P18
P19
P20
—
Discharge temperature TD2 error
Discharge temperature TD3 error
4-way valve inverse error
—
Logbook
Update the log periodically after maintenance as defined in EN378-4.
Detected outdoor unit number
—
High-pressure protective operation
0 *: IGBT circuit
1 *: Position detection circuit error
3 *: Motor lock error
Describe the following items on the logbook:
1. details of the maintenance and repair works;
Outdoor fan IPDU error
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities
of refrigerant which have been transferred from the system on each occasion (see also EN378-4);
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
4 *: Motor current detected
C *: TH sensor error
D *: TH sensor error
P22
(NOTE)
Ignore 0-F appearing in the position of “*”.
E *: Inverter DC voltage error
(outdoor unit’s fan)
01: Compressor 1
02: Compressor 2
03: Compressor 3
P26
P29
G-TR short protection error
7. significant periods of non-use.
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor position detecting circuit error
*1PDU number information
01:Compressor 1
02:Compressor 2
03:Compressors 1 and 2
04:Compressor 3
05:Compressors 1 and 3
06:Compressors 2 and 3
07:Compressors 1, 2 and 3
08:Fan
09:Compressor 1 and fan
0A:Compressor 2 and fan
0B:Compressors 1, 2 and fan
0C:Compressor 3 and fan
0D:Compressors 1, 3 and fan
0E:Compressors 2, 3 and fan
0F:Compressors 1, 2, 3, and fan
EN
63-EN
64-EN
– 32 –
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
Important
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is
safe, without the toxicity or combustibility of ammonia, and is
not restricted by laws to be imposed which protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its concentration should rise excessively.
Suffocation from leakage of R410A is almost non-existent.
With the recent increase in the number of high concentration
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective
use of floor space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the
multi conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if
the refrigerant accidentally leaks out, its concentration does
not reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
NOTE 2 :
The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15% or larger than the
respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
(3) If an indoor unit is installed in each partitioned room and
the refrigerant piping is interconnected, the smallest
room of course becomes the object. But when a
mechanical ventilation is installed interlocked with a gas
leakage detector in the smallest room where the density
limit is exceeded, the volume of the next smallest room
becomes the object.
Total amount of refrigerant (kg)
3
Min. volume of the indoor unit installed room (m )
3
≤ Concentration limit (kg/m )
Refrigerant piping
The concentration limit of R410A which is used in multi air
3
conditioners is 0.44kg/m .
Outdoor unit
Very
NOTE 1 :
small
Indoor unit
room
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be as
charged in each independent device.
Small
room
Medium
room
Large room
Mechanical ventilation device - Gas leak detector
Outdoor unit
NOTE 3 :
e.g., charged
e.g.,
amount (10kg)
charged amount (15kg)
The minimum indoor floor area compared with the amount of
refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
2
35
30
25
20
15
10
5
m
density limit of
3
0.44 kg/m
Room A Room B Room C Room D Room E Room F
Indoor unit
(countermeasures
not needed)
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A,
B and C is 10kg.
Range above the
density limit of
0.44 kg/m
(countermeasures
needed)
3
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
0
10
20
30
Total amount of refrigerant
kg
|