Studer Innotec Top Cover C Ip23 User Manual

User’s and installer’s Manual  
Sine wave Inverter, Battery charger, Transfersystem  
XP-COMPACT - XPC 1400-12  
XP-COMPACT - XPC 2200-24  
XP-COMPACT - XPC 2200-48  
Temperature sensor CT-35  
Remote control RCC-01  
Solar charge regulator Cxxxx-S  
AC cable cover CFC-01  
IP-23 top cover C-IP23  
STUDER INNOTEC  
Rue des Casernes 57  
CH – 1950 Sion  
TEL : ++41 (0)27 205 60 80  
FAX : ++41 (0)27 205 60 88  
E-MAIL : [email protected]  
STUDER INNOTEC  
XP-COMPACT  
English description  
1
General Information  
1.1 Operating instructions  
This manual is part of the delivery package of every XP-COMPACT inverter-charger.  
It serves as guidelines for safe and efficient operation of XP-COMPACT. The  
instructions are only valid for use with the following devices and options:  
XP-COMPACT XPC 1400-12  
XP-COMPACT XPC 2200-24  
XP-COMPACT XPC 2200-48  
Temperature sensor CT-35  
Remote Control RCC-01  
AC cable cover CFC-01  
IP23 cover C-IP23  
Solar charge controller CxxxxS  
Every person who installs a XP-COMPACT and/or works with it must be fully familiar  
with the content of this manual and must follow exactly all the warning and safety  
instructions. Installation of or any work on the XP-COMPACT must be carried out by  
a skilled and trained personnel. Installation and application must comply with the  
respective local installations codes and safety regulations.  
1.2 Quality and Warranty  
During production and assembling, all XP-COMPACT appliances go through many  
controls and tests. Production, controls and tests are carried out in accordance with  
firm and established procedures. Every XP-COMPACT has its own serial number,  
which helps to refer back to its original data in the event of controls or repairs. That is  
why you should never remove the identification plate showing the serial number. The  
production assembly and tests on all XP-COMPACT appliances are totally carried out  
in our company in Sion, Switzerland. The warranty for these appliances is valid for  
uses and operating possibilities mentioned in this manual.  
The warranty period for the XP-COMPACT is 2 years.  
1.3 Warranty Disclaimer  
We do not accept any liability for any damages occurring through use, manipulation,  
working situation and handling, which are not explicitly mentioned in these operating  
instructions.  
Following cases are not covered by the warranty:  
High voltage at INPUT (i.e. 48V at the Battery INPUT of XP-COMPACT 1400-  
12)  
Reverse polarity on Battery connections (+/- reversed)  
Running liquid or oxidation through condensation in the appliance  
Defects caused by force, physical or mechanical means  
Changes not explicitly authorized by STUDER INNOTEC  
Not or only partly tightened screws and nuts after change of fuses or cables  
connecting  
Transport damage, i.e. through bad handling and /or packing  
XP-COMPACT V5.4  
5/77  
STUDER INNOTEC  
XP-COMPACT  
Damage from atmospheric over voltage (lightning)  
1.4 Liability Disclaimer  
Respecting this manual, servicing and method of installation, functioning, application  
and maintenance of the appliance can not be controlled or supervised by STUDER  
INNOTEC. Hence we do not accept any liability and responsibility for damages,  
losses and costs which result through the use of this appliance or which result  
through incorrect installation, incorrect operation or wrong application and  
maintenance, or which by some other means maybe connected to each other.  
The use of STUDER INNOTEC’s inverters does exclusively involve the user’s  
liability.  
This device is not designed for applications involving health care and medical  
treatments where the patient life is concerned and where any mishap may be lethal.  
Similarly, we do not accept any liability for any violation of the patents rights or  
violation of any third party’s rights resulting from the use of this appliance  
STUDER INNOTEC reserves the right to modify the technical data or these operating  
instructions without any prior notice.  
1.5 Warning  
This manual must be readily available for the user at any time. The user must be  
familiar with the precautions and safety aspects in the country of installation.  
During operation of XP-COMPACT, high voltages are generated at the connections  
and inside of the appliance which could be lethal. Work on the appliance and on the  
installation should only be carried out by skilled and trained people.  
The whole installation connected with the XP-COMPACT must comply with the rules  
and codes in force.  
People without the written authorization from STUDER INNOTEC are strictly  
forbidden to carry out any change or repair on the appliances. For authorized  
changes only original parts are to be used.  
The XP-COMPACT may only be used when it has been installed in accordance with  
these instructions and all parts have been correctly assembled and installed.  
The XP-COMPACT may only be connected to lead-acid or lead-gel batteries.  
Caution: Even when a XP-COMPACT has been disconnected from all  
connections, at the OUTPUT point there could still be deadly voltages present.  
To remove these voltages you must switch on the XP-COMPACT ON with the  
ON/OFF switch. After one minute the electronics are discharged and any work  
can now be safely carried out.  
The XP-COMPACT is only suitable for internal use and under no circumstances  
should it be subjected to snow, rain, or any other wet conditions.  
By installations in motorized vehicles the XP-COMPACT must be protected from  
water-spray and any other wet conditions.  
Caution: In normal use lead-acid and lead-gel batteries give out explosive  
gases. Never smoke or allow a spark or flame in the vicinity of batteries. The  
batteries must always be stored or placed in a well ventilated room, they  
should be placed in such a way that there is no danger of short-circuit through  
carelessness. Never charge frozen batteries.  
1.6 Special precautions  
While working on batteries there should always be a second person close to you  
or within your voice range, in case help is needed.  
XP-COMPACT V5.4  
6/77  
STUDER INNOTEC  
XP-COMPACT  
Plenty of fresh water and soap must be ready at hand so that in case of acid  
coming in contact with skin, eyes and clothes, the areas in question can be  
thoroughly washed.  
If acid enters the eyes, you must thoroughly wash them with cold running water  
for at least 15 minutes. It is recommended that you immediately consult a  
medical doctor.  
Baking powder neutralizes battery acid electrolyte. Always keep some at hand.  
Special care must be taken when working with metal tools near or on the  
batteries. With tools such as screwdrivers, spanners etc. short-circuits can  
result. Sparks produced by the short circuit can cause an explosion.  
When working on batteries all personal metal items such as rings, necklaces  
and bracelets must be removed. Batteries are so powerful that short-circuit with  
these items can melt them and thus cause severe burns. Always follow the  
battery manufacturer instructions.  
Under certain conditions XP-COMPACT or a connected generator can start  
automatically. While working on an electrical installation you must ensure that  
these appliances are disconnected beforehand from the installation.  
2
Introduction  
The XP-COMPACT is a sine wave inverter with integrated battery charger with many  
additional functions, it has been developed to be used as stand-alone (no grid-  
feeding) AC provider, or as continuous / break-free current supply provider (UPS).  
2.1 Principle schematic  
Notes:  
(1) The neutral of the appliance is not connected to the earth whatever the  
function mode is. If requested and according to the local regulation, an automatic  
XP-COMPACT V5.4  
7/77  
STUDER INNOTEC  
XP-COMPACT  
connection between Neutral and earth in inverter mode only may be done by  
installing a bridge internally to the unit. Please contact your installer regarding this  
point.  
(2) Remote control for remote adjustment of the input limit. (see chap. 4.6.3)  
2.2 Description of the main functions  
2.2.1 The inverter  
The sine wave inverter XP-COMPACT generates a sinusoidal AC voltage with an  
exceptionally precise voltage and stabilized frequency. In order to start large electric  
motors, the user has the possibility to use a short surge power which is 3 times the  
nominal power of the XP-COMPACT.  
The inverter is protected against overload and short circuit. A power stage with the  
latest MOS-FET power transistors, a toroidal transformer, and a fast regulating  
system makes a robust and reliable inverter with the highest efficiency. A 1-20 Watt  
adjustable charge detection system allows the smallest energy consumption and  
ensures a long life for the battery.  
2.2.2 The transfer system  
XP-COMPACT can be connected to an AC source. For example a stand-by  
emergency generator or the AC network. With the transfer system, on one side you  
have an alternating voltage at the output for the use of consumer appliances. On the  
other side the battery park is being charged. The distribution of energy between the  
consumer appliances and battery charger is automatic.  
2.2.3 The battery charger  
The built-in battery charger is so designed that it can charge the battery quickly and  
fully. A microprocessor controlled, Step charging process, ensures the optimal  
charging of the battery. The desired charging current can be set continuously from 0  
to 20/37/45 A, as per the model. The setting is made accordingly to the battery  
capacity and power available.  
The battery charger is designed for lead-acid and lead-gel batteries. Thanks to the  
floating charge system the batteries can remain continuously connected.  
2.2.4 The solar charge controller (optional)  
With the built-in solar charge controller, the XP-COMPACT is a complete solar-  
power-center. In a solar installation this controller ensures that the batteries are  
charged correctly. With the XP-COMPACT, batteries can be charged with a  
generator and with the solar modules at the same time. The charging of batteries with  
both energy sources is carried out fully automatically.  
2.2.5 Remote control  
As an option, a remote control RCC-01 can be connected to XP-COMPACT. All  
operating features and displays, save the adjustment levels (22/23/24/26), are  
available on the remote control. It is supplied with a 20m long cable. This cable can  
be up to 40m long. On the remote control, output power and charging current are  
also displayed.  
XP-COMPACT V5.4  
8/77  
STUDER INNOTEC  
XP-COMPACT  
2.3 Battery connecting  
Lead-acid batteries are normally available in blocks of 2V, 6V or 12V. In most cases,  
to generate the necessary operating voltage and the capacity of the batteries for the  
XP-COMPACT many batteries have to be connected together in parallel and or in  
series. Here are 3 examples of connection:  
2.3.1 Connection in parallel  
2.3.2 Serial connection  
2.3.3 Serial and parallel connection  
XP-COMPACT V5.4  
9/77  
STUDER INNOTEC  
XP-COMPACT  
3
Mounting and installing  
3.1 Installation place  
The location of the XP-COMPACT must be driven by the following criteria:  
Protection from unauthorized handling  
Dry dust free room, no condensation  
Never install directly over the battery and never in a cabinet together with the  
batteries  
Keep ventilation holes free  
In mobile installations it is important to keep the vibrations down as low as  
possible  
3.2 Fixing  
3.2.1 Fixing the XP-COMPACT  
Basically the XP-COMPACT can be installed in any desired location. Preferred is that  
the appliance be wall mounted with battery cables downwards. The XP-COMPACT is  
fixed on the wall with four screws through the four holes (diameter 5.5mm) which are  
accessible from the outside. In motor vehicles XP-COMPACT must be fixed on  
vibrations reducing elements. The XP-COMPACT must not be fixed on a combustible  
base, as the back of the casing can get hot and reach up to 80 degree Celsius.  
3.2.2 Protection cover IP-23  
This cover IP23 (Order ref. CIP-23) can be easily  
installed after the fixation of the XP-COMPACT. For that  
release a little the too screws down and more the tow up.  
Then it’s possible to pass the IP 23 cover between the  
XP-COMPACT and the wall. The cover must touch the  
screws. Lock on the four screws, it’s ready.  
3.3 Connections  
3.3.1 General instructions on connecting  
The cable connection on the terminals AC INPUT / AC OUTPUT / 16A 230VAC  
are carried out with a screwdriver Nr.1 and the connection on the SOLAR  
terminal with a screwdriver Nr.2.  
The conductor cross section on the terminals AC INPUT / AC OUTPUT / 16A  
230VAC of the connecting cable must be minimum 2.5mm2.  
All connecting cables and also the mounted battery cables, must be fixed with  
strain relief clamps.  
The XP-COMPACT is delivered with battery cables already connected.  
The battery cables must never be extended. If the extension is unavoidable then  
the conductor cross section must be elevated accordingly.  
To protect the battery cable, a fuse corresponding to the conductor cross  
section must be fixed directly on to the battery.  
All cables must be tightly screwed in place. For safety, a yearly control is  
recommended. In mobile installations control must be carried out more often.  
Connecting must be done by qualified personnel. Material such as cable,  
connectors and distribution boxes, fuses etc. used in the installation must  
comply with the respective valid low-voltage installation rules and regulations.  
XP-COMPACT V5.4  
10/77  
STUDER INNOTEC  
XP-COMPACT  
3.3.2 Protection  
connections  
cover  
of  
the  
terminals  
The protection is available as an option (Order ref.  
CFC-01) and avoid to do wrong hazardous  
connection on the terminals 230Vac. It mounted  
with strain relief clamps for the cable.  
3.4 Connection Plan  
A Battery +/-  
B SOLAR +/-  
C Remote contr.  
D Equalize  
E Transfer delay  
F Temp.  
Battery cable (already installed)  
Connection terminal for Solar modules  
Connection terminal for Remote Control RCC-01  
Slide switch for equalization of the Battery  
Slide switch for Transfer Delay  
Connection terminal for Temperature sensor CT-35  
Connection terminal for Auxiliary Contact  
Connection terminal for AC-input. Located directly  
above this terminal is the automatic safety cut-out for  
this terminal.  
G Aux. Contact  
H AC Input  
J ID Plate  
Identification plate with Technical data and Serial  
number  
K AC Output  
L Caution…  
Connection terminal for AC-output  
Caution: Check Polarity (+/-) before connecting the  
battery !  
M Don’t…  
N 16A Protection  
Do not open without disconnecting all terminals  
16A Protection switch for the Transfer system  
XP-COMPACT V5.4  
11/77  
STUDER INNOTEC  
XP-COMPACT  
3.5 Cabling  
Connecting the XP-COMPACT is a very important step of the installation. You must  
take care that all connection work is carried out in a clean and correct way and that  
under no circumstance a cable is connected to a wrong terminal.  
Connecting of the XP-COMPACT must be carried out in the following order. In case  
of dismantling this order must be reversed.  
3.6 Pre-installation settings  
Before you start with the cabling of the XP-COMPACT you must set the type of  
battery. In case sealed-gel batteries are used then you must set the small slide-  
switch „Equalize“ which is on the front with the connection terminals, in OFF position.  
In case of „normal“ lead-acid – batteries, these can handle a higher equalizing  
charge, the same slide switch can be set in ON position. In case of doubt leave the  
setting in OFF position.  
This will allow an equalizing cycle (higher end of charge voltage) during the next  
charge process. Since then equalizing will occur every 25 usual cycles.  
3.6.1 Connection to battery  
Get the batteries ready for connection: Matching battery terminals, matching fuse on  
a clamp. Prepare battery cables, if necessary press on cable tabs/shoes. Connect  
red cable on Plus (+)-Pole and the black cable on the Minus (-) Pole. On connecting  
the second cable to the battery pole a spark is produced, because for a short time  
high current flows in the XP-COMPACT to charge the capacitors. For this reason  
follow strictly the safety measures described in this manual. Check if the red LED  
OFF (13) is lit. If it is not lit, press shortly on the switch ON/OFF (19), now OFF  
should be lit.  
On connecting the battery the XP-COMPACT needs 1 – 2 Minutes to calculate the  
actual capacity of the battery. During this time the battery condition is shown as  
100% charged. (LED 14 – 17 lit).  
If the LED 12 Battery Low/High is lit, the battery charge is too low. If the LED 12  
Battery Low/High is blinking, the battery charge is too high.  
Caution: With a wrong battery voltage the XP-COMPACT can be destroyed. (for  
example: connecting a XPC 1400-12 to a 48V-Battery).  
Nevertheless, if the XP-COMPACT had been connected with reverse polarity, it is  
highly probable that the fuse inside the casing is defect. Before opening the casing  
cover all terminals must be disconnected including the battery. If the XP-COMPACT  
does not function after the changing of the fuse and correcting of the polarity, it  
means that it is defect and must be sent for repair.  
3.6.2 Connection to the 230Vac-consumer appliances (AC OUTPUT)  
The 230V consumer appliances must be connected to the terminals AC OUTPUT  
with cables which cross section has to follow the local rules in force (usually  
2.5mm2). Connections are marked as follows “N“ Neutral, “PE“ Earth (connected to  
the appliance box), “L“ Live.  
Caution: High voltages can be there. Make sure that the XP-COMPACT is  
turned off (LED 13 lighting) before the connection.  
3.6.3 Connection to the 230Vac Input (AC INPUT)  
The 230V-supply from network or from a generator must be connected to the input  
terminals AC INPUT with cables which cross section depends on the power source  
(usually 2.5mm2). Connections are marked as follows: “N“ Neutral, “PE“ Earth, “L“  
Live (connected to the appliance case).  
XP-COMPACT V5.4  
12/77  
STUDER INNOTEC  
XP-COMPACT  
3.6.4 Connect the solar modules: SOLAR +/- (Only for solar option)  
Solar modules are connected on these terminals. Under no circumstances should  
any other energy source i.e. wind generator be connected to these terminals! Only  
solar modules must be connected with two cables +/-. Depending on the power of the  
modules, the cable cross section should be 2.5 up to 6mm2. Before connecting it is  
necessary to check with a Voltmeter that the voltage of the Module meets the  
following values:  
XPC 1400-12 17-25V/30A, XPC 2200-24 34 – 45V/30A, XPC 2200-48 68 – 90V/20A.  
3.6.5 Connection to Auxiliary Contact  
This contact is a potential free change over contact the currents and voltages allowed  
for this contact are max. 16A/250Vac. The LED 5 “Contact active” shows the position  
of them: alight mind active and off mind non-active. The schematic view of the  
connections on the front, show the relay in the non-active mode.  
3.6.6 Connection to Remote control  
The Remote Control RCC-01 is connected in the terminal marked „Remote control“  
with a 20m long cable and a RJ11/8 connector. The Remote Control can be plugged  
IN or plugged OUT during any operation situation. Push in the connector softly until  
you hear the „click“ showing that the connector is locked. The same applies to the  
plug in the Remote Control.  
The length of the cable for Remote Control should not exceed 40m. We deliver it with  
20m cable.  
3.6.7 Connection to Temperature Sensor (Temp.)  
The temperature sensor CT-35 is connected in the terminal marked „Temp“ with a  
3m long cable and a RJ11/6 connector. The temperature sensor can be plugged IN  
or plugged OUT during any operating situation. Push in the connector softly until you  
hear the „click“ showing that the connector is locked. The temperature sensor must  
be glued to the wall of the battery or near it. The Temperature Sensor cable must  
not be tied together with the battery cables or laid in a rope/bundle.  
4
Control  
4.1 Display and control parameters  
XP-COMPACT V5.4  
13/77  
STUDER INNOTEC  
XP-COMPACT  
4.2 Display and control parameters on remote control panel (optional)  
4.3 Light Emitting Diodes (LED)  
LED  
Marking  
LED lit  
LED blinks  
Voltage  
corresponding to  
self-adjusted  
A voltage outside the self-adjusted  
values is at the AC IN input, or the XP-  
COMPACT is in synchronization  
1
AC IN  
values is at the AC phases  
IN input.  
Battery charger is  
working  
The battery charger is locked OFF  
(see chap. 4.7) or provisory out of  
order. In that last case it will restart  
within 10 seconds  
2
3
CHARGER  
Connected solar  
modules are  
delivering energy  
Program mode for  
Aux. Contact  
Auxiliary Contact is  
activated  
Aux. Cont.  
SOLAR  
CHARGE  
4
5
6
Program  
Contact  
active  
Contact  
manual  
manually activated  
Transfer system is Transfer (bypass) is disabled (see  
active. In- coming  
chap. 4.8)  
7
TRANSFER voltage is being  
sent directly to AC  
OUT outlet  
There is a voltage  
The Inverter is in Standby-Mode  
8
9
AC OUT  
at the AC OUT  
outlet  
INVERTER Inverter is working Forced Inverter Mode (see chap. 4.6)  
XP-COMPACT V5.4  
14/77  
STUDER INNOTEC  
XP-COMPACT  
For the time being  
the XP-COMPACT  
10  
11  
Over Temp. is out of service  
because of  
overheating.  
The XP-COMPACT  
is out of service  
Overload  
because of  
overload or short-  
circuit  
Batt.  
Low/High  
Battery voltage is  
too low  
XP-COMPACT is  
Battery voltage is or was to high  
XP-COMPACT is for the time being  
12  
13  
turned off. Turning turned off. Turning it back on will  
OFF  
it back on is only  
possible manually.  
Battery equalizing  
is set  
follow automatically !  
14  
EQUALIZE  
State of charge of  
the battery  
LED 15 – Absorption time is running  
15–18  
Display the value of the output power in % of Pnom (in  
Inverter Mode) and the charge current in Amps (in Charger  
Mode).  
POWER  
MONITOR  
25  
4.4 Push buttons  
Turning the XP-COMPACT on and off (Help Button for  
Programming)  
Alarm Signal off (Help Button for Programming)  
19  
ON/OFF  
RESET  
20  
21  
Aux. Contact Control Aux. contact (Help Button for Programming)  
4.5 Turning Knobs  
22  
23  
24  
CHARGER Adjustment for max. Charging Current  
Adjustment for Transfer Voltage Threshold (TRANSFER –  
INVERTER)  
TRANSFER  
STANDBY Adjustment for „Standby“ system  
4.6 The Inverter  
An Inverter is built in the XP-COMPACT, which generates a sinusoidal alternating  
voltage of a very high quality. With this Inverter any 230Vac alternating voltage  
appliance up to the nominal power of your XP-COMPACT can be operated. Thanks  
to the generous dimensioning of the XP-COMPACT, you can operate appliances  
requiring higher power than the nominal power of the XP-COMPACT for a short time.  
The XP-COMPACT provides up to 3-times the nominal power to start motors.  
The Inverter mode is displayed through LED 9 (Inverter). If the Inverter Mode is  
disabled (see chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation  
and you have 230Vac at the output AC OUT. The actual power of the connected  
appliance is displayed on the power monitor 25 and on the Remote Control.  
XP-COMPACT V5.4  
15/77  
STUDER INNOTEC  
XP-COMPACT  
4.6.1 Charge detection system „Standby“  
In order to avoid unnecessary discharge of the battery, the inverter switches OFF  
automatically if no appliance is connected and switches ON automatically again if  
appliance is connected. The LED 8 blinks if the inverter is in Standby-Mode. The  
switching-on/starting level can be adjusted with the turning knob 24 „STANDBY”.  
Adjusting the switching-on level is as follows: Switch off all consuming devices, turn  
the Turning Knob 24 to the right until the LED 8 is blinking, switch on the smallest  
consuming device (i.e. Mobile phone charger), turn the Turning Knob slowly to the  
left until LED 8 is lit.  
If the Standby-Mode is not wanted, turn the Turning Knob 24 to the left, to the OFF  
position.  
4.6.2 Overload  
If the Inverter is too long or too heavily overloaded, it switches off. The LED 11  
„Overload“ is lit and LED 13 „OFF“ blinks. After ca. 10 seconds the Inverter switches  
on automatically. If the Inverter is overloaded four times one after another in a short  
time, then it no longer switches on automatically. The LED 13 remains lit. Press the  
push button 19 „ON/OFF“ in order to switch on the Inverter.  
4.6.3 Overheating (Over Temp.)  
If the Inverter has been overloaded for a long time or it has been working in too high  
surrounding temperatures, it will switch off. The LED 10 „Over Temp.“ is lit and the  
LED 13 „OFF“ blinks. After cooling down, the inverter switches back on automatically.  
One minute before the inverter switches off for too high temperature it gives out an  
acoustic alarm signal. If the Auxiliary Contact has been programmed to detect the  
high temperature then it synchronizes the relay with the alarm signal. In this way, for  
example, an emergency back- up system can be started without any break in the  
energy supply.  
4.6.4 Battery Condition  
Deep discharge of the lead-acid batteries leads to high losses in capacity and early  
aging. That is why the battery condition is continuously controlled and supervised.  
With low volt-age the inverter switches off. The LED 12 „L/H Batt.“ is lit and the LED  
13 „OFF“ blinks. When the battery voltage gets up to 12.1V / 24.2V / 48.4V, the  
Inverter switches on automatically. One minute before the Inverter switches off due to  
low voltage it gives out an acoustic alarm signal. If the Auxiliary Contact has been  
programmed to detect the low voltage then it synchronizes the Aux. Contact with the  
alarm signal. In this way, for example, an emergency back up system can be started  
without any break in the energy supply.  
The low voltage is set to 11.6V / 23.2V / 46.4V. These settings are standard for most  
batteries. These voltage levels are maintained by the built-in Battery-Management-  
System of the XP-COMPACT by matching the load and the battery condition.  
This setting is comparable with the levels of 10.8V/ 21.6V / 43.2 which are given  
for most batteries at nominal load.  
All voltage levels can be programmed. See the instructions under the section on  
Programming. Check with your battery supplier which voltage values should be set.  
4.7 The battery charger  
4.7.1 Cycle of charge  
The full automatic XP-COMPACT Battery Charger is adjusted at the factory so that  
most lead-acid and lead-gel batteries can be charged to the maximum. As soon as  
the minimum alternating voltage for the AC IN set on the Turning Knob 23 is available  
XP-COMPACT V5.4  
16/77  
STUDER INNOTEC  
XP-COMPACT  
at the input (LED 1 AC IN is lit), the Battery Charger is switched on automatically  
(LED 2 CHARGER is lit). The battery is fully automatically charged matching to the  
charge level, the adjusted volt-age levels and the charge current. Thanks to the built-  
in Float Charge System, the batteries can be left connected for unlimited time with  
the Battery Charger switched on.  
During the charging phase the appliances at the outlet AC OUT are continually  
supplied with power (LED 8 AC OUT is lit).  
The charger functions are shown in the following diagram:  
4.7.2 Default values for battery voltage thresholds  
Absorption  
time  
Equalization  
Low voltage  
Float charge  
Absorption  
Equalization  
time  
12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V  
12/24/48V  
12/24/48V  
11.6 23.2 46.4 13.5 27.0 54.0 14.4 28.8 57.6 15.6 31.2 62.4  
2h  
20’  
These values can be modified by mean of the optional remote control  
4.7.3 Equalization charging  
Before you program the XP-COMPACT for Equalization-charge you must check with  
your supplier that the batteries are suitable for this process.  
Equalization is recommended for the lead-acid batteries in order to mix well the  
electrolyte fluid and to clean the lead plates.  
If the XP-COMPACT is operating with a lead-acid battery, which is suitable for  
equalization, the slide switch „Equalize“ which is on the cable connection side, must  
be placed in the ON position. In this setting, every 25 charge cycles an equalization is  
carried out for 20 minutes (factory setting). During such a charge cycle the LED 14 is  
lit and during equalizing it is blinking. Charge cycle with equalization can be started  
independently from the actual program. For this purpose the slide switch must be slid  
from “OFF” to the “ON” position. The LED 14 will light up. If the periodic equalization  
is not required, slide switch must be slid back to the „OFF“ position after the  
completion of the manual cycle.  
The equalizing voltage can be changed. How to proceed is explained in chap. 5.3.  
Batteries not designed for equalize should never been charged this way.  
CAUTION: During the equalization process, the batteries produce a lot more  
gas. DANGER OF AN EXPLOSION !! The battery room must be well ventilated.  
XP-COMPACT V5.4  
17/77  
STUDER INNOTEC  
XP-COMPACT  
Equalization mode should never be used when using Gel-Batteries.  
4.7.4 Charging current  
The maximum charging current for the battery can be adjusted with the Turning Knob  
22 (CHARGER). The charging current of the battery should be set to approximately  
10 – 20% of the battery capacity (at C10). This means that the charging current for a  
battery with 300Ah should be set between 30 – 60A.  
The charging current is displayed on POWER MONITOR (25) of the front panel  
or on the Remote Control.  
4.7.5 Battery Condition  
Built-in microprocessor with a specially developed algorithm calculates the actual  
state of charge of the battery and displays it on LED 15 – 18. The LED 14 is lit when  
the system is carrying out a charge cycle with equalization.  
Notice: the exact measure of the battery state of charge with electrical parameters is  
al-most impossible. The display of the state of charge is always more or less precise.  
The measure system built in the XP-COMPACT takes into account the battery  
voltage, the discharge and charge current as well as the undulation of the voltage. If  
the battery and the XP-COMPACT are used according to their technical data, the  
battery state of charge is displayed accurately. In the following cases of use the  
display can diverge:  
Battery charge or discharge with too high  
currents  
Battery cable cross section too small  
Battery connections badly tightened or corroded  
Charge of the battery with external battery  
charger  
Discharge of the battery with users not  
connected to the XP-COMPACT  
Work with defective or sulphated batteries  
This means that the display can, within few minutes  
during the charge, commute from 25% to 75% or  
during the discharge, to the opposite direction.  
As many of the working cases mentioned above often occur, the measure system of  
the XP-COMPACT takes into account, during the charge, only the peaks of the  
voltage undulation. As a consequence, the battery voltage at the start of the  
absorption stage, measured by a voltmeter will appear deeper. By decrease of the  
charge current the voltage will reach the exact values.  
For safety reasons, you must get the recommended charge voltage and charge  
currents from your battery supplier. The voltage levels and charge characteristics can  
be changed through Programming. The instruction for programming of battery  
charger is in the section „Programming“ (Chap. 5.3). The correct charging is  
mandatory for a safe function and a long-life of the battery.  
The battery charger functions are described by the graphic in chap. 4.7.1.  
4.8 The Transfer system  
When an AC voltage is at the input AC IN of the XP-COMPACT, the LED 1 AC IN is  
lit. When this voltage matches the lowest adjusted value set by the Turning Knob 23  
TRANSFER, and the frequency is between 44Hz and 65Hz, this voltage is switched  
directly to the battery charger and to the output AC OUT. The LED 7 TRANSFER is  
XP-COMPACT V5.4  
18/77  
STUDER INNOTEC  
XP-COMPACT  
lit. The inverter is switched off and the battery charger switched on. This process is  
automatic, unless the charger mode or the transfer mode is disabled (see Chap. 5.5).  
The maximum current of the Transfer switch is 16A. That means through this system,  
consuming devices up to a maximum of al 3700 Watt can be operated. When the  
Battery Charger is working, part of this power is used for charging according to the  
power sharing system.  
The Transfer system is protected against overload with a circuit breaker on the AC  
Input side of the XP-COMPACT. If the system has been overloaded, the button/pin of  
the fuse will pop out. To put the automatic safety system back in to operating you  
must push this pin back.  
Note: in the Inverter operation, The XP-COMPACT generates a true sinusoidal and  
quartz stabilized output voltage. However if the XP-COMPACT is supplied from a grid  
or a generator and the transfer contact is active, then you have at the output AC OUT  
the same voltage as that at the input. This voltage can not be modified by the XP-  
COMPACT !  
4.8.1 Set the transfer voltage threshold  
The voltage threshold of the transfer can be adjusted between 150 to 230V with the  
turning knobs (23). From factory this value is 200V. Most appliances can work on this  
voltage. When the Input voltages reach the selected value on turning knob, the  
inverter switches off and the AC INPUT goes directly on the AC OUTPUT. When the  
voltage INPUT is less of 20V the value set, the transfer is stopped and the OUTPUT  
switches back on the inverter.  
Note : Don’t use the turning knobs “TRANSFER” (23) to adjust the AC OUTPUT  
voltage ! This is only it’s only a voltage threshold level to enable or disable the  
transfer.  
4.8.2 FAST (UPS)- MODE for the Transfer Switch  
The quick and break free Transfer mode is programmed with a slide switch „Transfer  
De-lay“ OFF, which is on the front side (cable connections side).  
The aim of the XP-COMPACT is to supply the appliance with a break-free alternating  
volt-age. When the incoming voltage AC IN no longer matches values which have  
been set with the Turning Knob 23, the inverter switches on at once. The transfer is  
carried out in 0.02 seconds. This quick transfer ensures a break-free function for  
most appliances. If you have an alternating voltage back at the input AC IN, transfer  
system starts up again with-out any break, and the inverter is stopped.  
4.8.3 Delayed mode of the Transfer System  
The delayed mode of the transfer system „Transfer Delay ON“ is programmed with  
the slide switch on front with the cable connections. The XP-COMPACT provides a  
break-free alternating voltage for the appliance. A quick transfer switch is not always  
sensitive nor is it always desired. For example, when the appliances are operated by  
a small back-up generator. An overload of a short period on such a generator, i.e.  
start of a vacuum cleaner etc., has the effect of decreasing the voltage for a short  
time. As in such cases the transfer to the Inverter is not desired, the transfer system  
can be programmed with a delay. When the slide switch (Transfer delay) is in the  
„On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If the  
voltage falls below 100Vac, the transfer takes place without delay ! The transfer  
switching to the Inverter takes place without any break.  
XP-COMPACT V5.4  
19/77  
STUDER INNOTEC  
XP-COMPACT  
4.9 The Solar charge controller (option)  
The XP-COMPACT also has a Solar Charge Controller built in. For charging the  
batteries, Solar modules can be connected to the screw terminal SOLAR +/-. The in-  
built controller is a „Shunt controller“ for the maximum input current of 30A for XPC  
1400-12 and XPC 2200-24 and 20A for XPC 2200-48. The operating voltage of solar  
panels to be connected must match the actual operating voltage of the XP-  
COMPACT and never exceeds the max. rated value.  
Under no circumstances should any other systems such as wind-generator be  
connected at the input of the Solar Charge Controller.  
The Solar Charge Controller works automatically and is always in operation. As soon  
as the energy is delivered from the Solar Charge Controller, LED 3 “SOLAR  
CHARGE” is lit and the batteries are being charged. The Solar Charge Controller  
works even when the Battery Charger is functioning. The way of working is the  
principally the same as that of the Battery Charger. The function is described in the  
section on Battery Charger. The programming and the adjustments are carried out in  
accordance with the same conditions. Check with your battery supplier which  
adjustments must be carried out for your battery.  
4.10 The Multifunctional Contact  
In the XP-COMPACT there is a built-in programmable power relay. The potential-free  
change-over contact (NO – NC) of this power relay is connected to the screw  
terminal AUX CONTACT.  
Maximum Contact load: 230Vac / 12Vdc / 24Vdc / 16A !  
> 36Vdc / 3A !  
With the Push Button 21 „AUXILIARY CONTACT“ the contact can be manually  
switched on or off independently from programming and from the operating situation.  
The LED 5 “Contact active” shows the status of the contact. The drawing up the  
screw terminal “AUX CONTACT” is the inactive position mode, LED 5 “Contact  
active” off.  
The switching on and off of this contact can be freely programmed for every  
operating situation of the XP-COMPACT witch situation is indicated with a LED.  
There is no limitation to its application and it is left to your wishes as to where and  
how you would like to use it. The example and the setting of this contact are  
explained in chapter 5.4.  
In factory we program this for a dysfunction alarm. The contact is active when one of  
these situations is detected:  
Over temperature (LED 10 lit)  
Overload (LED 11 lit)  
Over or less voltage of batteries (LED 12 lit or blinking)  
XP-COMPACT is turned off manually or with a fault (LED 13 lit)  
In case this function is not wished, it must be modified by programming according to  
procedure in chap. 5.4.  
XP-COMPACT V5.4  
20/77  
STUDER INNOTEC  
XP-COMPACT  
4.11 The Remote Control RCC-01  
As an option, a Remote  
Control can be connected to  
the  
operating  
XP-COMPACT.  
controls  
All  
and  
displays except from level  
adjustment are available on  
the Remote Control. The  
Remote Control is supplied  
with a 20m long cable. It can  
as long as 40m. The Remote  
Control is suitable for surface  
mounting on the wall or on to  
a switch board. It is fixed with  
4 screws. The XP-COMPACT  
can also be programmed with  
the Remote Control. The  
Programming is descry-bed in  
the section „Programming“.  
The output power and the charging currents are displayed on the Remote Control.  
In the Remote Control there is an additional Alarm Contact and a built-in Control  
Input. These two functions are available through Tip-jack RJ11/4 for use. This  
Auxiliary Contact is Front / Work Contact (max. 0.5A!), which is independent from the  
Auxiliary Contact of the XP-  
COMPACT. This con-tact is  
active in case of an alarm of  
the XP-COMPACT.  
The Control Input is connected  
in parallel to the ON/OFF-  
push  
button.  
The  
XP-  
COMPACT can be switched on  
or off through this input with an  
impulse button or an impulse  
contact.  
Caution: No external voltage  
should be connected to this  
Input Control.  
Order Number for Remote Control: RCC-01  
Dimensions: H x B x T / 111.5 x 136.5 x 25mm  
4.12 The Temperature sensor CT-35  
Operating voltage of lead-acid batteries change depends on the  
temperature. To correct the operating voltages according to the  
actual temperatures, a temperature sensor can be connected to the  
XP-COMPACT.  
The compensation through the sensor is –3mV/°C/Cell.  
Order Number: CT-35  
Dimensions: H x B x T / 58 x 51.5 x 22mm  
XP-COMPACT V5.4  
21/77  
STUDER INNOTEC  
XP-COMPACT  
5
Programming (possible only with the remote control RCC-01)  
The XP-COMPACT (except for 60Hz versions) is equipped with a Flash  
processor fitted out with EEPROM Memory, which means that even when it is  
disconnected from the battery, the parameters that were programmed for the  
application remain after a new connection to the battery.  
It is possible to reinitialize (RESET) the XP-COMPACT by pressing  
simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A  
beep will confirm the RESET. The inverter switches off after this operation. It  
can be turned on again after the beep. The programmed parameters will  
remain.  
5.1 Standard setting  
The XP-COMPACT is delivered with the following default settings:  
Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13  
Battery voltage :  
Low voltage  
Float Charge  
11.6V / 23.2V / 46.4V  
13.5V / 27.0V / 54.0V  
End of Charge Voltage 14.4V / 28.8V / 57.6V  
Equalization  
15.6V / 31.2V / 62.4V  
2 Hours  
Absorption Time :  
Equalizing Time :  
20 Minutes  
5.2 Reset value (default settings)  
To come back to the default settings, press simultaneously on the push buttons  
20/21 during at least 2 seconds. A beep will confirm the comeback to the factory  
settings. The inverter switches off after this operation. It can be turned on again after  
the beep.  
5.3 Battery voltages and absorption time  
5.3.1 Set the voltage and timing threshold  
The programming is done in accordance with  
the following steps:  
Push and hold down, the Push Button 21  
(Program) and the Push Button 19 (Change  
status)  
for  
minimum  
2
seconds  
simultaneously.  
With the Push Button 20 (select) select which  
of the battery level and of the absorption time  
have to be changed.  
These four red LED’s show the function set:  
Low voltage  
LED 13 (ON/OFF)  
Float charge  
Absorption (End of charge)  
Equalization  
LED 12 (Batt. Low/high)  
LED 11 (Overload)  
LED 10 (Overtemp.)  
Absorption Time  
LED 10/11/12/13 (altogether)  
XP-COMPACT V5.4  
22/77  
STUDER INNOTEC  
XP-COMPACT  
With the Push Button 19 (Change status) set the desired parameter (voltage or time)  
to modify (LED 14/ 15/16/17/18). Push Button 19 (Change status) to set the desired  
value according to the table 5.3.2.  
If desired, repeat the operation with any other parameter (voltage or time) to be  
changed.  
If during 30 seconds no buttons are pressed, the selected values are automatically  
stored and the XP-COMPACT switches back in to the normal operating status.  
The voltage levels and times changed through programming are only first active with  
the next charge cycle!  
The voltage level which is not suitable can greatly reduce the battery life or  
could even destroy it ! Therefore check beforehand with your battery supplier.  
5.3.2 Table of voltage and timing threshold  
The voltage levels (low voltage, float charge, end of charge and equalization) and the  
duration of the absorption charge can be changed.  
The display of these voltages and the times in the program mode are in accordance  
with the diagram shown below:  
Equali-  
zation  
time  
Absorption  
Low voltage  
Float charge  
LED 12  
Absorption  
Equalization  
time  
LED  
10/11/12/13  
12/24/48  
4h  
LED 13  
24  
LED 11  
24  
LED 10  
24  
LED 10/11  
12  
48  
12  
24  
48  
12  
48  
12  
48  
12/24/48  
3h  
14 12.0  
15 11.8  
16 11.6  
17 11.4  
18 11.2  
24.0  
23.6  
23.2  
22.8  
22.4  
48.0  
47.2  
46.4  
45.6  
44.8  
13.7  
13.6  
13.5  
13.4  
13.3  
27.4  
27.2  
27.0  
26.8  
26.6  
54.8  
54.4  
54.0  
53.6  
53.2  
16.2  
15.6  
15  
32.4  
31.2  
30  
64.8  
62.4  
60  
16.2  
15.9  
15.6  
15.3  
15  
32.4  
31.8  
31.2  
30.6  
30  
64.8  
63.6  
62.4  
61.2  
60  
3h  
2h  
1h  
0 – 1’  
2h  
1h  
40’  
20’  
14.4  
14.2  
28.8  
28.4  
57.6  
56.8  
The heavy printed values show the standard settings.  
5.4 Auxiliary contact  
5.4.1 Principle  
The Auxiliary Contact can be basically programmed for any operating situation of the  
XP-COMPACT which is indicated with a LED. The programming is possible for one  
or more operating situations. If the contact is programmed for many situations, it is  
activated as soon as the XP-COMPACT finds itself in any one of the programmed  
situations. That means that the work of the contact meets that of the logic OR–  
Function.  
5.4.2 The programming of the Auxiliary Contact  
The programming of the Auxiliary Contact is carried out in the following Steps:  
The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4  
„Program“ is lit as an indication, that the XP-COMPACT is in program mode.  
A blinking LED shows the programmed condition for the auxiliary contact (LED  
10/11/ 12/13 factory setting).  
With the Push Button 20 (select), select the desired condition in which the  
contact should be activated.  
With the Push Button 19 (Change status) confirm or change the status for this  
condition. If desired, with the Push Button 20 (select) select another condition in  
which the contact should be activated.  
With the Push Button 19 (Change status) confirm or change the status for this  
condition. If during 30 seconds no buttons are pushed, then the settled values  
XP-COMPACT V5.4  
23/77  
STUDER INNOTEC  
XP-COMPACT  
are automatically stored and the XP-COMPACT switches back to normal  
operating condition.  
5.4.3 Auxiliary Contact as generator starter  
As per the battery capacity  
When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18)  
is used as a condition, you must then take note of the following requirements.  
If you have to start an emergency back-up supply with a battery having a certain  
residual capacity, then two battery levels must be programmed. The first (i.e. Battery  
25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e.  
Battery 100% LED15) for stopping or disabling the Auxiliary Contact. Programmed  
like this the Auxiliary Contact works with the lowest set condition and stops when it  
has reached the highest programmed condition through charging.  
Example: start of a generator with the XP-COMPACT  
In order to program the auxiliary contact to start at 25% and to stop at 75% of the  
battery state-of-charge, here is the procedure to follow:  
Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then  
the states will be displayed blinking (factory settings LED’s 10/11/12/13). As  
these states are not wished for the start of the generator, they must be disabled.  
With the key (select) 20, select the LED’s to disable (the active LED’s are  
blinking) and disable them with the key 19 Change Status. Select the other  
LED’s to switch off with the key (select) 20 and switch them off with the key 19  
Change Status until all are disabled.  
Then select the LED 17 with the key (select) 20 and activate the contact with the  
key 19 Change Status. The generator will start once the LED 17 switches of.  
Then select the LED 16 with the key (select) 20 and activate the contact with the  
key 19 Change Status. The generator will stop once the LED 16 switches on.  
If no key is activated during 30 seconds, the normal operation states are  
displayed automatically again.  
For a control the key Program can be pressed at least 2 seconds. The values set are  
displayed blinking.  
5.4.4 Auxiliary Contact as Twilight Witch (with solar charger option)  
The Auxiliary Contact of the XP-COMPACT can also be used as a twilight switch, i.e.  
to operate automatically the exterior lighting. With it the connected solar modules  
measure the light intensity. If the XP-COMPACT is operating without solar modules  
and a twilight-switching function is desired, you can connect small solar cells with the  
nominal voltage of the XP-COMPACT on to the SOLAR terminals for the purpose of  
measuring the light intensity. To function as a twilight-switch the Auxiliary Contact  
must be programmed so that the condition SOLAR CHARGE (LED 3) is active.  
Programming must be carried out in steps and in accordance with the description for  
the programming of the Auxiliary Contact.  
5.4.5 Power cut of the second priority loads  
The auxiliary contact can also be used to cut the power of less priority loads when  
the battery state of charge is lower than a given threshold. In that case, only one of  
the battery state of charge, or the “transfer” function will be programmed as power cut  
criteria.  
The second priority loads will be supplied only when the generator is ON or when the  
battery has a sufficient threshold.  
5.4.6 Manual operating of Auxiliary Contact  
XP-COMPACT V5.4  
24/77  
STUDER INNOTEC  
XP-COMPACT  
The Auxiliary Contact can be operated at any time with the Push Button 21 (AUX.  
CONTACT). The LED 6 „Contact manual“ lights up as information that the Contact is  
manually operated, and LED 5 „Contact active“ lights up when the Contact is active.  
By pushing the Push Button 21 a second time, the Contact is disabled. By pushing it  
the third time, automatic functions are restored.  
5.5 Disabling some of the XP-COMPACT functions  
Each different function charger, inverter and transfer can be disabled. This is useful  
for specific applications witch required to disable some of these three functions.  
If you press the buttons 19 and 20 more than 2 seconds you can have access to the  
different possibilities, shown in the following diagram.  
In programming mode the display shows only the different types of program with the  
three LED’s 2, 7 and 9 to each function. To change the type of programming, press  
shortly the button 20 until you reach the right function used according to the table  
below. After 10 seconds the XP-COMPACT exits the programming mode and loads  
the new change.  
In user mode, the disabled functions are displayed by blinking LED. So you can see  
which mode is disabled.  
5.5.1 Diagram of the different modes  
Shows an off LED  
Shows a blinking LED  
Shows a lighted LED  
All the functions are enabled. This is the  
factory setting.  
The inverter is disabled. Only the transfer  
switch and the charger will work normal-  
ly.  
Inverter and charger are both disabled.  
Only the transfer switch function is ena-  
bled in input voltage and frequency is OK  
Charger and transfer switch are disabled  
the inverter will work continuously even if  
there is a correct AC voltage at the input.  
XP-COMPACT V5.4  
25/77  
STUDER INNOTEC  
XP-COMPACT  
6
Installation Maintenance  
Apart from the periodic controls mentioned for the connections, the XP-COMPACT  
does need any maintenance. Keep the appliance clean and from time to time, wipe it  
clean with a damp cloth.  
7
Declaration of CE Compliance  
Hereby we state that the products described in this user manual comply with the  
following standards:  
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir.  
89/336/EEC, LVD 73/23/EEC, EN 50091-2, EN 60950-1.  
CH - 1950 Sion, the 1st of March 2003  
STUDER INNOTEC (R. Studer)  
XP-COMPACT V5.4  
26/77  
STUDER INNOTEC  
XP-COMPACT  
8
Technical Data  
XP-COMPACT V5.4  
27/77  

Minolta Bizhub C300 User Manual