OWNER’S INSTRUCTIONS &
INSTALLATION MANUAL
MANUAL DE INSTRUCCIONES &
MANUAL DE INSTALACIÓN
MANUEL D’UTILISATION &
MANUEL D’INSTALLATION
Indoor Unit
AM18B1C09
AM26B1C13
Outdoor Unit
UM18B1C2
UM26B1C2
AM27B1C07
AM27B1C13
UM27B1C3
MULTI-SPLIT TYPE ROOM AIR CONDITIONER ( Cool )
ACONDICIONADOR DE AIRE DOMÉSTICO SISTEMA MULTI SPLIT ( Refrigeración )
CLIMATISEUR DE TYPE MULTIPLE ( Refroidissement )
E
S
F
DB98-05640A(3)
Contents
◆
PREPARING YOUR AIR CONDITIONER
◆◆◆Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
◆◆◆View of the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
◆◆◆Remote Control-Buttons and Display . . . . . . . . . . . . . . . . . . . . 6
◆◆◆Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
◆◆◆Inserting the Remote Control Batteries . . . . . . . . . . . . . . . . . . . 8
◆◆◆Installing the Remote Controller Holder . . . . . . . . . . . . . . . . . . 8
◆
OPERATING YOUR AIR CONDITIONER
◆◆◆5 Way Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
◆◆◆Selecting the Automatic Operating Mode . . . . . . . . . . . . . . . . 10
◆◆◆Cooling Your Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
◆◆◆Changing the Room Temperature Quickly . . . . . . . . . . . . . . . 12
◆◆◆Removing Excess Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . 13
◆◆◆Airing Your Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
◆◆◆Adjusting the Air Flow Direction Vertically . . . . . . . . . . . . . . . 15
◆◆◆Adjusting the Air Flow Direction Horizontally . . . . . . . . . . . . . 15
◆
◆
PROGRAMMING YOUR AIR CONDITIONER
◆◆◆Setting the On Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
◆◆◆Setting the Off Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
◆◆◆Setting the Sleep Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
RECOMMENDATIONS FOR USE
◆◆◆Operating Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . 19
◆◆◆Temperature and Humidity Ranges . . . . . . . . . . . . . . . . . . . . 20
◆◆◆Cleaning Your Air Conditioner . . . . . . . . . . . . . . . . . . . . . . . . . 21
◆◆◆Solving Common Problems . . . . . . . . . . . . . . . . . . . . . . . . . . 22
◆◆◆Installing a Filter (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
◆
TECHNICAL SPECIFICATIONS
E-3
View of the Unit
The design and shape are subject to change according to the model.
Indoor Unit
Air Inlet
Air flow blades (outlet)
Air filter
(under the grille)
Timer indicator
Remote Control Sensor
SAVING indicator
STANDARD indicator
NATURE indicator
SILENCE indicator
POWER indicator
On/Off & 5 Way
selection button
Note
◆ For details on the 5 Way, refer to page 9.
E-4
UM18B1C2
Outdoor Unit
Air Inlet(Rear)
Air Outlet
Connection Valve
Connection Valve
Connection Valve
UM26B1C2
Outdoor Unit
Air Inlet(Rear)
Air Outlet
UM27B1C3
Outdoor Unit
Air Inlet(Rear)
Air Outlet
E-5
Remote Control - Buttons and Display
Remote control
transmission indicator
Mode selection button
(AUTO, COOL, DRY, FAN)
Operating mode
(
AUTO,
COOL,
DRY,
FAN)
Temperature adjustment
buttons
Temperature setting
Turbo mode
Sleep mode
Turbo/Sleep mode
selection button
Fan speed
Fan speed adjustment
button
Air flow direction
Swing button
On Timer setting
On Timer button
Off Timer setting
Off Timer button
Battery discharge indicator
On/Off &
Timer Set/Cancel button
5 Way selection button
E-6
Getting Started
You have just purchased a split type air conditioner and it has been
installed by your installation specialist.
Your Owner’s Instructions contains valuable information on using your
air conditioner. Please take the time to read it as it will help you take full
advantage of the unit’s features.
The booklet is organized as follows.
◆ The following figures are shown on pages from 4 to 6 :
-
-
Indoor and outdoor units
Remote control(buttons and display)
They will help you find the buttons and understand the symbols displayed.
◆ In the main part of the installation book, you will find a series of
step-by-step procedures for each function available.
The illustrations in the step-by-step procedures use three different symbols:
PRESS
PUSH
HOLD DOWN
E-7
Inserting the Remote Control Batteries
You must insert or replace the remote control batteries when :
◆ You purchase the air conditioner
◆ The remote control does not work correctly
Note
◆ Use two AAA, LR03 1.5V batteries.
◆ Do not use old batteries or different kinds of batteries together.
◆ Batteries may be completely discharged after 12 months, even
◆ if they have not actually been used.
1
2
Push the battery cover on the rear of the remote control with your thumb
in the direction of the arrow and remove it.
Insert the two batteries, taking care to respect the polarities :
◆ + on the battery with + on the remote control.
◆ - on the battery with - on the remote control.
3
Close the cover by sliding it back until it clicks into place.
Installing the Remote Controller Holder
1
2
Place the remote controller holder on the wall.
Fix the remote controller holder by tightening the screws.
3
Put the remote controller into the holder as shown in the figure.
◆ If you want to install the holder easily, you had better install the holder
on the wooden frame.
E-8
5 Way Function
You can select the 5 Way function with operating mode of the air conditioner for
more comfortable circumstances. You can use the 5 Way function with the indoor
unit as well as the remote control. Thus, you can use this function
even though you have lost your remote control.
Using with the indoor unit
1
Press the
mode.
(ON/OFF) button one time and then select the desired
To obtain a(n)...
Then select...
Normal operating
(STANDARD) mode
Reducing the uncomfortable
temperature gradually
(NATURE) mode
(POWER) mode
(SAVING) mode
(SILENCE) mode
High fan speed
Compressor run time reduced
Fan speed reduces as the temperature
decreases
2
To stop the operating, press the
turn off.
(ON/OFF) button until all indicators
Note
Even if the air conditioner has been turned on via the ON/OFF
button on the unit, operations can still be controlled using the
remote control as usual.
Selecting with the Remote Control
To select the 5 Way function with the remote control, press the 5 Way
button one or more times until the desired mode is selected.
◆ Each time you press the 5 Way button:
Each 5 Way indicator on the indoor unit lights up in order.
E-9
Selecting the Automatic Operating Mode
You can start the air conditioner in Automatic mode from your remote
control. In the Automatic mode, the standard temperature and the
optimum fan speed is selected automatically. You can adjust the
standard temperature but not the fan speed.
1
If necessary, press the
(On/Off) button.
Result:
◆ The 5 Way indicator on the indoor unit lights up.
◆ The air conditioner starts up in the mode selected
when the unit was last used.
◆ The indoor unit beeps.
IMPORTANT
The air conditioner is fitted with a protection mechanism to
prevent the unit from being damaged when it is started
immediately after being:
◆ Plugged in
◆ Stopped
lt will start up normally after three minutes.
2
If the
is not displayed at the top of the remote control,
press the MODE button on the remote control one or more times until it
appears.
Result:
◆ The indoor unit beeps each time you press the MODE button.
◆ The air conditioner runs in AUTO mode.
Note
You can change modes at any time.
3
To adjust the standard temperature (The air conditioner automatically
set the standard temperature by the current room temperature.),
press the TEMPERATURE buttons one or more times.
SET TEMP. SET TEMP.
-4°F/-2°C -2°F/-1°C Standard temperature +2°F/+1°C +4°F/+2°C
< When you feel hot > < When you feel chilly >
-
SET TEMP. SET TEMP.
E-10
Cooling Your Room
You must select the Cool mode if you wish to adjust the:
◆ Cooling temperature
◆ Fan speed when cooling
1
If necessary, press the
(On/Off) button.
Result: The 5 Way indicator on the indoor unit lights up.
◆
◆ The air conditioner starts up in the mode selected
when the unit was last used.
◆ The indoor unit beeps.
IMPORTANT
The air conditioner is fitted with a protection mechanism to
prevent the unit from being damaged when it is started
immediately after being:
◆ Plugged in
◆ Stopped
lt will start up normally after three minutes.
2
If the
is not displayed at the top of the remote control,
press the MODE button on the remote control one or more times until it
appears.
Result:
◆
◆
The indoor unit beeps each time you press the MODE button.
The air conditioner runs in COOL mode.
Note
You can change modes at any time.
3
To adjust the temperature, press the TEMPERATURE buttons one or
more times until the required temperature is displayed.
Possible temperatures are between 65°F(18°C) and 86°F(30°C)
inclusive.
Result:
◆
Each time you press the TEMPERATURE buttons:
- The temperature is adjusted by 1°F(1°C)
- The indoor unit beeps
◆ The air conditioner starts cooling, provided that the room
temperature is higher than the selected temperature;
the fan will, however, operate.
4
Select the fan speed by pressing the FAN button one or more times
until the required setting is displayed:
Automatic (rotated :
)
Low
Medium
High
Result:
Each time you press the FAN button, the indoor unit beeps.
5
To control the direction of the air flow, refer to page 15.
E-11
Changing the Room Temperature Quickly
The Turbo cooling function is used to cool your room as quickly as possible.
Example :
You have just come home and find that the room is very
hot. You wish to cool it down as quickly as possible.
The Turbo function operates for 30 minutes with the maximum settings before
returning automatically to the mode and temperature previously selected.
1
If necessary, press the
(On/Off) button.
Result:
◆ The 5 Way indicator on the indoor unit lights up.
◆ The air conditioner starts up in the mode selected when the unit
was last used.
◆ The indoor unit beeps.
2
Press the
Result:
button.
◆ The temperature and fan settings are adjusted automatically.
◆ The air conditioner cools the room as quickly as possible.
◆ After 30 minutes, the air conditioner is reset automatically to the
previous mode, temperature and fan settings.
But, if you press the
button in DRY or FAN mode,
it will change to AUTO mode automatically.
3
If you wish to stop the Turbo function before the end of the 30-minute period,
press the
button one or more times until
or
disappears.
Result:
The air conditioner is reset automatically to the previous mode,
temperature and fan settings.
4
To control the direction of the air flow, refer to page 15.
E-12
Removing Excess Humidity
If the atmosphere in your room is very humid or damp, you can
remove excess humidity without lowering the room temperature too
much.
1
If necessary, press the
(On/Off) button.
Result: The 5 Way indicator on the indoor unit lights up.
◆
◆ The air conditioner starts up in the mode selected when
the unit was last used.
◆ The indoor unit beeps.
IMPORTANT
The air conditioner is fitted with a protection mechanism
to prevent the unit from being damaged when it is started
immediately after being:
◆ Plugged in
◆ Stopped
It will start up normally after three minutes.
2
If the
is not displayed at the top of the remote control, press the
MODE button on the remote control one or more times until it appears.
Result:
◆
◆
The indoor unit beeps each time you press the MODE button.
The air conditioner runs in DRY mode.
Note You can change modes at any time.
3
To adjust the temperature, press the TEMPERATURE buttons one or
more times until the required temperature is displayed.
Possible temperatures are between 65°F(18°C) and 86°F(30°C)
inclusive.
Result: ◆ Each time you press the TEMPERATURE buttons:
- The temperature is adjusted by 1°F(1°C)
- The indoor unit beeps
◆ The air conditioner starts removing the excess humidity;
the quantity of air is adjusted automatically.
4
To control the direction of the air flow, refer to page 15.
E-13
Airing Your Room
If the atmosphere in your room is stale, you can air the room using
the Fan feature.
1
If necessary, press the
(On/Off) button.
Result: The 5 Way indicator on the indoor unit lights up.
◆
◆ The air conditioner starts up in the mode selected when
the unit was last used.
◆ The indoor unit beeps.
2
If the
is not displayed at the top of the remote control,
press the MODE button on the remote control one or more times until it
appears.
Result:
◆
◆
◆
The indoor unit beeps each time you press the MODE button.
The air conditioner runs in FAN mode.
The temperature is set automatically.
Note
You can change modes at any time.
3
Select the fan speed by pressing the FAN button one or more times
until the required setting is displayed:
Low
Medium
High
Result: Each time you press the FAN button, the indoor unit beeps.
To control the direction of the air flow, refer to page 15.
4
E-14
Adjusting the Air Flow Direction Vertically
Depending on the position of the indoor unit on the wall of your room,
you can adjust the position of the outer air flow blade on the bottom of
the unit, thus increasing the efficiency of the air conditioner.
1
Press the SWING button one or more times as required.
Result: The outer blade is adjusted vertically.
RECOMMENDATION
When...
Adjust the blade to face...
Cooling
Upwards.
2
If you want the blade to move up and down automatically when the air
conditioner is operating, press the SWING button.
Result: The blade move up and down, around the base position set.
3
To stop the blade moving up and down, press the SWING button again.
Note
If you switch the air conditioner... Then the blade is...
Off
Closed completely.
On again
Set to the initial position powered.
Adjusting the Air Flow Direction Horizontally
There are two sets of inner air flow blades. Just as the outer air flow
blade can be adjusted vertically, the inner blades can be adjusted
horizontally.
1
Adjust each set of inner blades to the required position, by pushing or
pulling them sideways.
E-15
Setting the On Timer
The On Timer enables you to switch on the air conditioner automatically
after a given period of time. You can set the period of time from
30 minutes to 24 hours.
1
To set the operating time, press the ON TIMER button one or more times
until the required time is displayed. Possible time is between 0.5 hour and
24 hour inclusive.
2
Press the
(Set/Cancel) button to complete the setting.
Result: ◆ The remaining time is displayed.
◆ Blinking of the timer indicator stops.
◆ The selected mode and the temperature on the display
disappear after 10 seconds.
◆ The air conditioner will switch on automatically when the
counter displayed on the remote control reaches the set time
and disappears the On timer setting.
3
To select an operating mode in advance, press the
button until the
desired mode is displayed at the top of the remote control.
Result: ◆ The air conditioner will run in the selected mode when it is
turned on.
To Cancel the On Timer
1
To cancel the On Timer, press the ON TIMER button one or more times
until the timer setting disappears.
2
Press the
(Set/Cancel) button.
Note
If you want to turn on the air conditioner before the timer reaches
the setting time, press the (ON/OFF) button.
E-16
Setting the Off Timer
The Off Timer enables you to switch off the air conditioner automatically
after a given period of time. You can set the period of time from
30 minutes to 24 hours.
1
To set the operating time, press the OFF TIMER button one or more times
until the required time is displayed. Possible time is between 0.5 hour and
24 hour inclusive.
2
Press the
(Set/Cancel) button to complete the setting.
Result: ◆ The remaining time is displayed.
◆ Blinking of the timer indicator stops.
◆ The air conditioner will switch off automatically when the
counter displayed on the remote control reaches the set time
and disappears the Off timer setting.
Example If you would like to turn the air conditioner on after 2 hours
and to operate it for 2 hours:
1. Press the ON TIMER button until ‘2.0 Hr’ is displayed.
2. Press the (Set/Cancel) button.
3. Press the OFF TIMER button until ‘4.0 Hr’ is displayed.
4. Press the (Set/Cancel) button.
Note
You can see or change the setting mode and/or the temperature
by pressing the MODE button or the TEMPERATURE buttons
after setting the Off timer.
To Cancel the Off Timer
1
To cancel the Off Timer, press the OFF TIMER button one or more times
until the timer setting disappears.
2
Press the
(Set/Cancel) button.
Note
If you want to turn off the air conditioner before the timer reaches
the setting time, press the
(ON/OFF) button.
E-17
Setting the Sleep Timer
The Sleep Timer can be used when you are cooling your room to
switch the air conditioner off automatically after a period of six hours.
Note
If you wish to switch the unit off at a specific time, refer to
page 17.
1
2
Make sure that you have selected either COOL mode.
Press the
button one or more times until
appears on the
remote control.
Result: ◆ The indoor unit beeps.
◆ The air conditioner will be controlled as indicated in the
illustrations below.
Cooling The desired temperature is
increased by 2°F/1°C every
hour.
When it has been increased
by 4°F/2°C (after two hours),
the temperature is maintained
for four hours.
To Cancel the Sleep Timer
If you no longer wish to use the Sleep Timer that you have set, you
can cancel it at any time.
Press the
Result:
button.
◆
◆
◆
The indoor unit beeps.
The
The air conditioner operates normally.
is no longer displayed.
E-18
Operating Recommendations
Here are a few recommendations that you should follow when using
your air conditioner.
Topic
Recommendation
Power failure
If a power failure occurs when the air
conditioner is operating, the unit is switched off.
When the power returns, you must press the
(ON/OFF) button to restart it.
E-19
Temperature and Humidity Ranges
The following table indicates the temperature and humidity ranges
within which the air conditioner can be used.
If the air conditioner is used at... Then...
High temperatures
The automatic protection feature may
be triggered and the air conditioner
stopped.
Low temperatures
A water leak or some other malfunction
may occur if the heat exchanger
freezes.
High humidity levels
Water may condense on and drip
from the surface of the indoor unit if it
is used for long periods.
Mode
Outdoor Temperature
Indoor Temperature Indoor Humidity
Cooling
70°F to 109°F approx.
65°F to 90°F approx.
21°C to 43°C approx.
18°C to 32°C approx. 80% or less
Drying
65°F to 109°F approx.
65°F to 90°F approx.
18°C to 43°C approx.
18°C to 32°C approx.
-
◆◆ If the cooling operation is used at over 92°F/33°C(indoor temperature)
then, it does not cool as its full capacity.
E-20
Cleaning Your Air Conditioner
To get the best possible use out of your air conditioner, you must
clean it regularly to remove the dust that accumulates on the air filter.
Before cleaning your air conditioner, ensure that you
have switched off the breaker used for the unit.
IMPORTANT
1
2
Open the front grille by lifting the tabs on the lower right and left sides of
the indoor unit.
Disassemble the front grille by pulling it forwards.
3
4
5
Hold the edge of the air filter under the front grille and pull to release them.
Remove all dust on the air filters with a vacuum cleaner or brush.
Clean the front panel with a damp cloth and mild detergent
(do NOT use benzene, solvents or other chemicals).
6
Reassemble the air filters and the front grille.
Note
◆◆ If you have not used the air conditioner for a long period
of time, set the fan going for three to four hours to dry
the inside of the air conditioner thoroughly.
E-21
Solving Common Problems
Before contacting the after-sales service, perform the following simple checks.
They may save you the time and expense of an unnecessary call.
Problem
Explanation/Solution
The air conditioner does not
operate at all
◆ Check that the breaker used for the air conditioner is switched on.
◆ Check that the 5 Way indicator on the indoor unit is on;
if necessary press the
(On/Off) button on the remote control.
◆ Check whether the TIMER indicator on the indoor unit is switched on.
If so:
- Wait until the switch-on time is reached and the air conditioner starts
up automatically
- Cancel the timer (see pages 16 and 17 for further details)
The air conditioner does not
operate with the remote control
◆ Check that there are no obstacles between you and the indoor unit.
◆ Check the remote control batteries.
◆ Check that you are close enough to the indoor unit
(seven metres/yards/23ft. or less).
No beep is heard when you press
◆ Check that you are pointing the remote control at the remote control
sensor in the right of the indoor unit.
the
(On/Off) on the remote
control
◆ Replace the remote control batteries if necessary.
The air conditioner does not cool
◆ Check that the correct operating mode has been selected
(AUTO, COOL).
◆ The room temperature may be too low or too high.
◆ Dust may be blocking the air filter guard; refer to page 21 for cleaning
instructions.
◆ Check that there is no obstacle in front of the outdoor unit.
The fan speed does not change
when you press the FAN button
◆ Check that the operating mode is set to COOL or FAN ;
in the AUTO mode, the fan speed changes automatically and in the
DRY mode, it is set to AUTO.
The air flow direction does not
change when you press the
SWING button
◆ Check that the air conditioner has been switched on; if necessary,
press the
(On/Off) button on the remote control.
The timer is not correctly triggered
◆ Check that the timer has been programmed correctly; see pages 16
and 17.
Odours are permeated in the room ◆ Air the room.
during air conditioning
E-22
Installing a Filter (Option)
The air conditioner can be fitted with a deodorizing and Bio-Pure
filter to remove minute dust particles or odours. The service life of
the filter is approximately three months depending on the time
during which the air conditioner is used.
1
Remove the vinyl packing from the filter.
Note
Do not remove the packing from a deodorizing filter until you
wish to use the filter, as it will lose its properties.
Deodorizing
filter
2
3
Insert the filter in the filter holder and press the three insert tabs until
you hear a click.
Bio-Pure Filter
Open the front grille by pulling on the tabs on the lower right and left
sides of the indoor unit.
4
Take out the existing filter and replace it with the new one.
E-23
Technical Specifications
Indoor unit Outdoor unit Indoor unit Outdoor unit
MODEL
AM18B1C09 UM18B1C2
2 Comp + 2 Room
AM26B1C13 UM26B1C2
2 Comp + 2 Room
Type
Btu/h
Capacity Cooling
Performance
Ratings
A/B-Unit : 9000
10.0
A/B-Unit : 12500
10.0
SEER
Pts/h
CFM
dB
Moisture Removal
Air FLOW(Cooling, HIGH)
Sound Rating-Outdoor
The number of operation
Power source
3
-
4
-
255
-
-
300
-
-
57
60
Electrical
Data
1 Unit operation 2 Unit operation 1 Unit operation 2 Unit operation
208-230V~,60Hz
208-230V~,60Hz
A
Min.Ampacity
4.3
990
8.4
6.1
11.4
2550
B-Unit
W
Cooling Watts
1920
1360
B-Unit
A-Unit
A-Unit
Refrigeration Indoor unit
Lines
Flare
Flare
6.35 (1/4)
Connections
mm(in)
mm(in)
m(ft)
6.35 (1/4)
Liquid Line O. D.
9.52 (3/8)
12.70 (1/2)
Suction Line O.D.
Factory Pre-charge
Max. Line length
1
1
5.0 (
)
)
5.0 (
)
)
16 2
16 2
1
1
15.0 (
15.0 (
m(ft)
49 4
49 4
7.0 (23)
7.0 (23)
Max. Height Difference
m(ft)
790 x 245 x 165 880 x 638 x 310 790 x 245 x 165 1000 x 790 x 310
Dimensions
& Weight
mm(in)
Ibs
W X H X D
Net Weight
1
1
1
1
1 x
x
1 x 1 x
)
1 x 1 x 1 ) ( 1 x 1 x
)
(
(
(
31 8 92 62 ) 34 2 258 12 4 31 8 92 62 39 2 31 12 4
8
17
132.3
17
152.1
◆◆Standard rating conditions Cooling
Indoor
Outdoor
DB
80
WB
67
DB
WB
75
95
°F
26.7
19.4
35.0
23.9
°C
E-24
Indoor unit
Indoor unit
AM27B1C13
Outdoor unit
MODEL
AM27B1C07
UM27B1C3
2 Comp + 3 Room
Type
Btu/h
Performance Capacity Cooling
A-Unit : 13000, B/C-Unit : 7000
10.0
Ratings
SEER
Pts/h
CFM
dB
Moisture Removal
2.5
4
-
-
Air FLOW(Cooling, HIGH)
220
300
Sound Rating-Outdoor
The number of operation
Power source
-
-
62
1 Unit operation
2 Unit operation
3 Unit operation
Electrical
Data
208-230V~,60Hz
A
Min.Ampacity
A : 6.0, B(C) : 5.8 A+B(C) : 11.0, B+C : 6.2
A+B+C : 11.6
A+B+C : 2580
C-Unit
W
Cooling Watts
A+B(C) : 2450, B+C : 1380
B-Unit
A : 1350, B(C) : 1300
A-Unit
Refrigeration
Lines
Indoor unit
Flare
Connections
mm(in)
mm(in)
m(ft)
6.35 (1/4)
Liquid Line O. D.
Suction Line O.D.
Factory Pre-charge
Max. Line length
Max. Height Difference
12.70(1/2)
9.52 (3/8)
1
5.0 (
)
16 2
1
15.0 (
)
m(ft)
49 4
7.0 (23)
m(ft)
790 x 245 x 165
1000 x 790 x 310
Dimensions
& Weight
mm(in)
Ibs
W X H X D
Net Weight
1
1
1 x 1 x
(
1 x 1 x
)
(
31 8 92 62 )
39 2 31 12 4
8
17
154.3
E-25
INSTALLATION
MANUAL
E-26
Contents
◆
◆
PREPARING THE INSTALLATION
◆◆◆Deciding on Where to Install the Air Conditioner . . . . . . . . . . . 28
◆◆◆Air Conditioner and Accessories . . . . . . . . . . . . . . . . . . . . . . . 32
INSTALLING THE INDOOR UNIT
◆◆◆Fixing the Installation Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
◆◆◆Purging the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
◆◆◆Connecting the Assembly Cable . . . . . . . . . . . . . . . . . . . . . . . 35
◆◆◆Installing and Connecting the Indoor Unit Drain Hose . . . . . . 37
◆◆◆Installing and Connecting the Indoor Unit Assembly Piping . . 38
◆◆◆Cutting/Extending the Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 39
◆
◆
INSTALLING THE OUTDOOR UNIT
◆◆◆Connecting the Cables to the Outdoor Unit . . . . . . . . . . . . . . 40
◆◆◆Auxillary Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
◆◆◆Electrical Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
◆◆◆Checking Correct Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
◆◆◆Fixing the Unit in Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
COMPLETING THE INSTALLATION
◆◆◆Connecting Up and Purging the Circuit . . . . . . . . . . . . . . . . . . 45
◆◆◆Performing Leak Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
◆◆◆Placing the Indoor Unit in Position . . . . . . . . . . . . . . . . . . . . . 47
◆◆◆Checking and Testing Operations . . . . . . . . . . . . . . . . . . . . . . 48
◆◆◆Explaining Operations to the Owner . . . . . . . . . . . . . . . . . . . . 49
E-27
PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner
When deciding on the location of the air conditioner with the owner, the following restrictions
must be taken into account.
General
Do NOT install the air conditioner in a location where it will come into contact with the following elements:
◆
◆
◆
◆
◆
Combustible gases
Saline air
Machine oil
Sulphide gas
Special environmental conditions
If you must install the unit in such conditions, first consult your dealer.
Indoor Unit
◆
◆
◆
There must be no obstacles near the air inlet and outlet.
Install the indoor unit on a surface that can support its weight.
Choose a position that enables the piping and cables to be easily connected to the outdoor unit and the
recommended length of 5m (16ft. 5in) to be respected (15m (49ft. 3in) maximum).
◆
◆
◆
Leave enough clearance beneath the indoor unit to enable the filters to be removed without hindrance.
Maintain sufficient clearance around the indoor unit, as indicated in the diagram on the page opposite.
Make sure that the water dripping from the drain hose runs away correctly and safely.
Outdoor Unit
◆
The outdoor unit must NEVER be placed on its side or upside down, as the compressor lubrication oil will run into the
cooling circuit and seriously damage the unit.
◆
◆
◆
Choose a location that is dry and sunny, but not exposed to direct sunlight or strong winds.
Do not block any passageways or thoroughfares.
Choose a location where the noise of the air conditioner when running and the discharged air do not disturb any
neighbours.
◆
◆
◆
Choose a position that enables the piping and cables to be easily connected to the indoor unit and the recommended
length of 5m (16ft. 5in) to be respected (15m (49ft. 3in) maximum).
Install the outdoor unit on a flat, stable surface that can support its weight and does not generate any unnecessary
noise and vibration.
Position the outdoor unit so that the air flow is directed towards the outside, as indicated by the arrows on the top of
the unit.
◆
◆
Maintain sufficient clearance around the outdoor unit, as indicated in the diagram on the page opposite.
If the outdoor unit is installed at a height, ensure that its base is firmly fixed in position; the maximum height is
7m (23ft).
◆
Make sure that the water dripping from the drain hose runs away correctly and safely.
CAUTION
◆ You have just purchased a split-type room air conditioner and it has
been installed by your installation specialist.
◆ This device must be installed according to the national electrical rules.
E-28
PREPARING THE INSTALLATION
◆◆18,000Btu/h
Power supply
Ø, V, Hz
Indoor unit
Outdoor unit
UM18B1C2
AM18B1C09
1,208-230~,60
Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.
B-unit
9,000 Btu/h
25 mm (1 inch)
or more
A-unit
9,000 Btu/h
100 mm
(4 inch)
or more
160 mm
(6 inch)
or more
B
600 mm (24 inch)
minimum
(7 m (23ft) maximum)
A
(15 m (49ft. 3in)
maximum)
300 mm
(12 inch)
minimum
300 mm
(12 inch)
minimum
600 mm
(24 inch)
minimum
A
B
Circuit breaker
(20A)
Main power switch
Piping length and the height.
INDOOR UNIT
Pipe size
MAX. piping length MAX. height
Unit
Liquid
A
B
GAS
A
A-unit
B-unit
15 m (49ft. 3in)
15 m (49ft. 3in)
7 m (23ft)
7 m (23ft)
1/4"
"
3/8"
"
3/8
1/4
B
OUTDOOR UNIT
E-29
PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner (cont.)
◆◆26,000Btu/h
Power supply
Ø, V, Hz
Indoor unit
Outdoor unit
UM26B1C2
AM26B1C13
1,208-230~,60
Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.
B-unit
12,500 Btu/h
25 mm (1 inch)
or more
A-unit
12,500 Btu/h
100 mm
(4 inch)
or more
160 mm
(6 inch)
or more
B
(7 m (23ft) maximum)
600 mm (24 inch)
minimum
A
(15 m (49ft. 3in)
maximum)
300 mm
(12 inch)
minimum
300 mm
(12 inch)
minimum
600 mm
(24 inch)
minimum
A
B
Circuit breaker
(20A)
Main power switch
Piping length and the height.
INDOOR UNIT
Pipe size
MAX. piping length MAX. height
Unit
A
Liquid
A
B
GAS
A-unit
B-unit
15 m (49ft. 3in)
15 m (49ft. 3in)
7 m (23ft)
7 m (23ft)
1/4
"
"
1/2
"
"
1/2
1/4
B
OUTDOOR UNIT
E-30
PREPARING THE INSTALLATION
◆◆27,000Btu/h
Power supply
Ø, V, Hz
Indoor unit
Outdoor unit
UM27B1C3
AM27B1C07
AM27B1C13
1,208-230~,60
Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.
C-unit
7,000 Btu/h
B-unit
7,000 Btu/h
25 mm (1 inch)
or more
A-unit
13,000 Btu/h
100 mm
(4 inch)
or more
160 mm
(6 inch)
or more
B
(7 m (23ft) maximum)
600 mm (24 inch)
minimum
A
(15 m (49ft. 3in)
maximum)
300 mm
(12 inch)
minimum
300 mm
(12 inch)
minimum
600 mm
(24 inch)
minimum
A
B
Circuit breaker
(20A)
Main power switch
Piping length and the height.
INDOOR UNIT
Pipe size
MAX. piping length MAX. height
Unit
A
Liquid
A
B
GAS
A-unit
B-unit
C-unit
15 m (49ft. 3in)
15 m (49ft. 3in)
15 m (49ft. 3in)
7 m (23ft)
7 m (23ft)
7 m (23ft)
1/4
1/4
1/4
"
"
"
1/2"
3/8"
3/8"
B
OUTDOOR UNIT
E-31
PREPARING THE INSTALLATION
Air Conditioner and Accessories
The following accessories are supplied with the air conditioner.
The quantities are indicated in parentheses.
◆
Accessories in the Indoor Unit Case
Installation Plate (1) Remote Control (1)
Batteries for
Remote Control (2)
Owner’s Instruction
Booklet & Installation
Manual (1)
S
ION
UCT
STR
'S IN
NER
OW
O
NES
CIO
C
TRU
INS
L'US
ER
ÇÕE
TRU
DE
UAL
MAN
NI
P
UZIO
ISTR
S
INS
DE
UAL
MAN
N
IO
SAT
TILI
D'U
ANW
UEL
MAN
EI
SUNG
CHS
RAU
GEB
er
ndition
it
Splut-type Room Air Co
doméstico sistema Spl ate
dicionado
unità Separ
tipo Split
Aire acon
i
e
n
t
i
a
d
ia per amb
tore d'ar
Condiziona
cionado
aré
seur de type sép
Aparelho de ar condi
Climati
Geteilte
imaanlage
raumkl
Remote controller
holder (1)
Screws (2)
Accessories in the Outdoor Unit Case
Rubber Leg
Flare Nuts, 6.35mm(1/4˝)
outer pipe diameter
Flare Nuts,9.52mm(3/8˝)
outer pipe diameter
Flare Nuts, 12.70mm(1/2˝)
outer pipe diameter
◆
The assembly cable is depending on the option. [If they are not supplied, Using the
standard cable.(approved according to IEC standard.)]
E-32
INSTALLING THE INDOOR UNIT
Fixing the Installation Plate
Before fixing the installation plate to a wall or window frame, you
9
2
must determine the position of the 65mm( 16 inch) hole through
which the cable, piping and hose pass to connect the indoor unit up
to the outdoor unit. When facing the air conditioner in position on
the wall, the piping and cable can be connected from the:
◆ Right
◆ Left
◆ Rear (right or left)
1
2
Determine the position of the pipe and drain hose hole using the right
9
figure and drill the hole with an inner diameter of 65mm(
slants slightly downwards.
inch) so that it
2 16
If you are fixing the indoor unit to a...
Then follow Steps...
Wall
3.
Installation plate
Unit : mm(inch)
Window frame
4 to 6.
Pipe Hole
065mm(2 16
3
Fix the installation plate to the wall in a manner appropriate to the weight
of the indoor unit.
9
)
◆
If you are mounting the plate on a concrete wall with anchor bolts, the
3
anchor bolts must not project by more than 20mm( inch).
4
Unit : mm(inch)
4
5
Determine the positions of the wooden uprights to be attached to the
window frame.
252 (10)
(11)
275
5
1
2
Attach the wooden uprights to the window frame in a manner appropriate
to the weight of the indoor unit.
90(3
)
140 (5
)
8
Unit : mm(inch)
6
Using tapped screws, attach the installation plate to the wooden uprights,
as illustrated in the last figure opposite.
E-33
PREPARING THE INSTALLATION
Purging the Unit
On delivery, the indoor unit is loaded with an inert gas. All this gas
must therefore be purged before connecting the assembly piping.
To purge the inert gas, proceed as follows.
Unscrew the caps at the end of each pipe.
Result: All inert gas escapes from the indoor unit.
◆
To prevent dirt or foreign objects from getting into the pipes
during installation, do NOT remove the caps completely
until you are ready to connect the piping.
E-34
INSTALLING THE INDOOR UNIT
Connecting the Assembly Cable
The outdoor unit is powered from the indoor unit via the assembly cable.
If the outdoor unit is more than 5m(16ft. 5in) away from the indoor unit, the
cable must first be extended to a maximum of 15m(49ft. 3in).
1
2
Extend the assembly cable if necessary.
Open the front grille by pulling on the tabs on the lower right and left sides of
the indoor unit; if necessary, refer to page 21.
◆◆The designs and shape are subject to
change according to the model.
3
Remove the screw securing the connector cover, then open the connector
cover.
Connector
cover
4
Remove three screws securing the front panel, then detach the front panel
from the indoor unit.
E-35
INSTALLING THE INDOOR UNIT
Connecting the Assembly Cable (cont.)
5
Detach the control box from the indoor unit.
6
7
Install the conduit kit. (The conduit kit is optional)
Pass the assembly cable through the rear of the indoor unit and connect the
assembly cable to terminals as shown in the figure.
Control Box
◆ Each wire is labelled with the corresponding terminal number.
9
8
9
Pass the other end of the cable through the 65mm(
wall.
inch) hole in the
2 16
A
Reinstall the control box, then tighten the C screw.
◆ The C screw is provided with this manual.
10
11
Install the D terminal block cover, tightening the E screws.
The D terminal block cover and E screws are provided with this manual.
B
◆
◆◆The conduit kit is optional(A and B).
Replace the front panel, carefully tightening the screws.
Reinstall the front grille.
12
13
For further details on how to plug the other end of the assembly cable into
the outdoor unit, refer to pages 40 and 41.
Control Box
C
E
Terminal
block
cover
D
Indoor
unit
Earth
terminal
1
2
3
3
E
Outdoor
unit
1
2
E
A1 A2 A3
Earth terminal
E
E-36
INSTALLING THE INDOOR UNIT
Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any
condensation water is correctly drained outside. When passing the drain hose through
9
the 65mm(
inch) hole drilled in the wall, check that none of the following situations occur.
2 16
5cm
(2inch)
less
Ditch
The hose must
NOT slope
upwards.
The end of the drain
hose must NOT be
placed in water.
Do NOT bend the
hose in different
directions.
Keep a clearance of at
least 5cm(2inch)
between the end of the
hose and the ground.
Do NOT place the
end of the drain hose
in a hollow.
To install the drain hose, proceed as follows.
1
2
If necessary, connect the 2m(6ft. 7in) extension to the drain hose.
Shield
If you are using the extension, insulate the inside part of the extension
drain hose with a shield.
Drain hose
Extension drain hose
3
4
Pass the drain hose under the refrigerant piping, taking care to keep the
drain hose tight.
Pass the drain hose through the hole in the wall, making sure that it is
sloping downwards, as shown in the illustrations above.
◆
The hose will be fixed permanently into position once the
whole installation has been tested for gas leaks; refer to
page 47 for further details.
E-37
INSTALLING THE INDOOR UNIT
Installing and Connecting the Indoor Unit Assembly Piping
There are two refrigerant pipes of different diameters:
◆ A smaller one for the liquid refrigerant
◆ A larger one for the gas refrigerant
A short length of piping is already fitted to the air conditioner. You
must extend this piping using assembly piping (optionally supplied).
The connection procedure for the refrigerant piping varies according
to the exit position of the piping from the indoor unit, as seen when
facing the air conditioner in position on the wall:
◆ Right (A)
◆ Left (B)
◆ Rear
1
With a knife, cut out the appropriate knock-out piece on the rear of the
indoor unit (unless you are connecting directly from the rear).
B
A
2
3
Smooth the cut edges.
Remove the protection caps on the pipes and connect the assembly piping
to each pipe, tightening the nuts, first manually and then with a wrench,
applying the following torque.
Pipe
Outer Diameter
6.35 mm(1/4˝)
9.52 mm(3/8˝)
12.70 mm(1/2˝)
Torque
Liquid refrigerant
Gas refrigerant
Gas refrigerant
160kg•cm(11.6ft•lb )
300kg•cm(21.8ft•lb )
500kg•cm(36.4ft•lb )
◆
If the piping must be shortened or extended, refer to page 39.
4
5
Cut off any excess foam insulation.
If necessary, bend the pipe round, along the bottom of the indoor unit and
out through the appropriate hole, taking care to ensure that:
◆
◆
The piping does not jut out from the rear of the indoor unit
The bending radius is 100mm (4inch) or more
6
7
Pass the piping through the hole in the wall.
For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 45.
◆
The piping will be insulated and fixed permanently into
position once the whole installation has been tested for
gas leaks; refer to page 47 for further details.
E-38
INSTALLING THE INDOOR UNIT
Cutting/Extending the Piping
5 metres(16ft. 5in) of piping is supplied with the air
conditioner(Optional). This length can if necessary be:
◆ Extended to a maximum of 15m(49ft. 3in)
◆ Shortened as required
◆
If more than 5m(16ft. 5in) of piping is required:
◆ The assembly cable must also be extended
◆ Refrigerant must be added to the circuit by an
approved installer; otherwise, the indoor unit may
freeze
1
2
Make sure that you have the required tools available
(pipe cutter, reamer, flaring tool and pipe holder).
If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe,
and referring to the illustrations below for examples of edges cut correctly
and incorrectly.
90
O
Oblique
Rough
Burr
O
x
x
x
3
4
To prevent any gas from leaking out, remove all burrs at the cut end of the
pipe, using a reamer.
Slide a flare nut on to the pipe and modify the flare.
Pipe
Outer Diameter (D)
6.35 mm(1/4˝)
Depth (A)
Liquid refrigerant
Gas refrigerant
Gas refrigerant
1.3 mm(1/16˝)
1.8 mm(1/16˝)
2.0 mm(1/16˝)
9.52 mm(3/8˝)
12.70 mm(1/2˝)
5
Check that the flaring is correct, referring to the illustrations below for
examples of incorrect flaring.
x
x
x
x
Inclined
Damaged Surface
Cracked
Uneven Thickness
6
Align the pipes to be connected and tighten the flare nuts first manually
and then with a wrench, applying the following torque.
Pipe
Outer Diameter
6.35 mm(1/4˝)
9.52 mm(3/8˝)
12.70 mm(1/2˝)
Torque
Liquid refrigerant
Gas refrigerant
Gas refrigerant
160kg•cm(11.6ft•lb )
300kg•cm(21.8ft•lb )
500kg•cm(36.4ft•lb )
7
For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 45.
E-39
INSTALLING THE INDOOR UNIT
Connecting the Cables to the Outdoor Unit (cont.)
One electric cable must be connected to the outdoor unit:
◆ The assembly cable connecting the indoor unit to the outdoor unit
UM18B1C2
UM26B1C2
UM27B1C3
1
2
Remove the terminal board cover on the side of the outdoor unit.
Connect the assembly cable to terminals as shown in the figure.
◆
Each wire is labelled with the corresponding terminal number.
3
Connect the earth wires to the earth terminals.
◆
Refer to the page 43 for further details on how to check
that earthing is correct.
4
Replace the terminal board cover, carefully tightening the screw.
E-40
INSTALLING THE OUTDOOR UNIT
◆◆18/26◆◆
Outdoor unit
A1
A2
A3
B1
B2
B3
L1
A
L2
B
Terminal block
E
Earth terminal
Circuit Breaker
(Main Power supply cable)
E
E
E
Earth terminal
Earth terminal
Earth terminal
1
1
2
2
1
1
2
2
3
3
3
Assembly cable
3
E
Earth terminal
Indoor unit
A-unit
B-unit
◆◆27◆◆
Terminal block
L2
Outdoor unit
L1
A3
1
2
B3
C3
2
Earth terminal
E
A
B
Circuit Breaker
(Main Power supply cable)
Earth
1
1
2
2
3
3
E
1
1
2
2
3
E
1
1
2
2
3
3
E
E
terminal
Earth
Earth
Assembly
cable
terminal
terminal
E
3
E
Earth
Earth
Earth
terminal
terminal
terminal
Indoor
unit
A-unit
B-unit
C-unit
E-41
INSTALLING THE OUTDOOR UNIT
Auxiliary Circuit Breaker
◆ Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
connected to upper/lower terminal of auxiliary circuit breaker.
Outdoor unit
Distribution
board
◆ It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
Auxiliary
power s/w
◆◆The designs and shape are subject to
change according to the model.
Electrical Work
1
The supply voltage must be the same as the rated voltage of the
air conditioner.
2
3
Prepare the power souce for exclusive use with the air conditioner.
Use 20 amperes time delay fuse or circuit breaker.
AM27B1C07
AM27B1C13
AM26B1C13
MODEL
AM18B1C09
Power supply
208-230V~/60Hz
3G AWG 14
Power cable
Assembly cable
Operating current
Starting Current
Power consumption
4G AWG 16
11.4A
8.4A
22A
11.6A
31A
31A
1920W
2550W
2580W
◆
◆
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
Otherwise, the shot circuit in the NFB may occur.
E-42
INSTALLING THE OUTDOOR UNIT
Checking Correct Earthing
If the power distribution circuit does not have an earth or the earth
does not comply with specifications, an earthing electrode must be
installed. The corresponding accessories are not supplied with the air
conditioner.
1
Select an earthing electrode that complies with the specifications given in
the illustration opposite.
Carbon
plastic
Steel
core
To
earthing
screw
. 2
Determine a suitable location for the earthing electrode:
PVC-insulated green/
yellow wire, 2mm2 x 3.5 m
◆
◆
◆
In damp hard soil rather than loose sandy or gravel soil that has a
higher earthing resistance
Away from underground structures or facilities, such as gas pipes,
water pipes, telephone lines and underground cables
At least 2m(6ft. 7in) away from a lightening conductor earthing
electrode and its cable
Unit : cm(inch)
3
4
50(19
)
◆
The earthing wire for the telephone line cannot be used to
earth the air conditioner.
3
4
Dig a hole of the size indicated in the illustration opposite, drive the
earthing electrode into position and cover the top of the electrode
with the excavated soil.
1
Install a green/yellow insulated earthing wire (
2 mm2 or greater):
Ø
1.6 mm/ 16 ˝, section
◆
If the earthing wire is too short, connect an extension lead, soldering
the connection and wrapping it with insulating tape (do not bury the
soldered connection)
◆
Secure the earthing wire in position with staples
◆
If the earthing electrode is installed in an area of heavy traffic,
its wire must be connected securely.
5
6
Carefully check the installation, by measuring the earthing resistance with
an earthing resistance tester. If the resistance is above the required level,
drive the earthing electrode deeper into the ground or increase the number
of earthing electrodes.
Connect the earthing wire to the earthing screw on the air conditioner.
E-43
INSTALLING THE OUTDOOR UNIT
Fixing the Unit in Position
The outdoor unit must be installed on a rigid and stable base to avoid any increase
in the noise level and vibration, particularly if the outdoor unit is to be installed close
to a neighbour. If it is to be installed in a location exposed to strong winds or at a
height, the unit must be fixed to an appropriate support (wall or ground).
Unit : mm(inch)
660(26)
1
2
3
Position the outdoor unit so that the air flow is directed towards the
outside, as indicated by the arrows on the top of the unit.
Attach the outdoor unit to the appropriate support using anchor bolts.
Rubber leg
If the outdoor unit is exposed to strong winds, install shield plates around
the outdoor unit, so that the fan can operate correctly.
◆ Certainly fix up its rubber leg, in order to prevent its vibration and noise.
E-44
COMPLETING THE INSTALLATION
Connecting Up and Purging the Circuit
The outdoor unit is loaded with sufficient R22 refrigerant for 5m(16ft. 5in) of
piping. The air in the indoor unit and in the pipe must be purged.
If air remains in the refrigeration pipes, it will affect the compressor,
reduce to cooling capacity and could lead to a malfunction.
Refrigerant for air purging is not charged in the outdoor unit.
Use Vacuum Pump as shown at the figure.
1
Connect each assembly pipe to the appropriate valve on the outdoor unit
and tighten the flare nut.
Outdoor unit
Indoor unit
Gas pipe side
A
C
2
Referring to the illustration opposite, tighten the flare nut first manually
and then with a wrench, applying the following torque.
Liquid pipe side
B
D
Pipe
Outer Diameter
6.35 mm(1/4˝)
9.52 mm(3/8˝)
12.70 mm(1/2˝)
Torque
Liquid refrigerant
Gas refrigerant
Gas refrigerant
160kg•cm(11.6ft•lb )
300kg•cm(21.8ft•lb )
500kg•cm(36.4ft•lb )
3
4
Connect the charging hose of low pressure side of manifold gauge to the
packed valve having a service port as shown at the figure.
Open the valve of the low pressure side of manifold gauge
counterclockwise.
Indoor
A-unit
5
Purge the air from the system using vacuum pump for about 10 minutes.
Indoor
B-unit
-
-
-
-
-
-
Close the valve of the low pressure side of manifold gauge clockwise.
Make sure that pressure gauge show -0.1MPa(-76cmHg) after about
10minutes.
This procedure is very important in order to avoid gas leak.
Turn off the vacuum pump
A
B
Vacuum Pump
Remove the hose of the low pressure side of manifold gauge.
◆◆The designs and shape are subject to
change according to the model.
6
Set valve cork of both liquid side and gas side of packed valve to the open
position.
Valve stem
Liquid side
7
8
Mount the valve stem nuts and the service port cap to the valve, and
tighten them at the torque of 18N•m with a torque wrench.
Stem cap
Check for gas leakage.
Gas side
-
At this time, especially check for gas leakage from the 3-way valve’s
stem nuts, and from the service port cap.
Service port
You can install 15m of connecting pipe to the maximum, and you don’t have
to charge any additional refrigerant.
E-45
COMPLETING THE INSTALLATION
Performing Leak Tests
Before completing the installation (insulation of the cables, hose and
piping and fixing of the indoor unit to the installation plate), you must
check that there are no gas leaks.
C
D
To check for gas leaks on the...
Then, using a leak detector,
check the...
Indoor unit
Flare nuts at the end of sections
C and D.
Outdoor unit
Valves on sections A and B.
B
A
◆◆The designs and shape are subject to
change according to the model.
E-46
COMPLETING THE INSTALLATION
Placing the Indoor Unit in Position
Once you have checked that there are no leaks in the system, you can insulate
the piping, hose and cables and place the indoor unit on the installation plate.
1
To avoid condensation problems, place heat-resistant polyethylene foam
separately around each refrigerant pipe in the lower part of the indoor unit.
2
Wrap the refrigerant pipes and the drain hose located at the rear of the
indoor unit up in the absorbent pad.
◆
Triply wind the pipes and hose to the end of the indoor unit with
3
the absorbent pad (make intervals of 20mm / inch).
4
3
4
Wind insulating tape around the pipes, assembly cable and drain hose.
Installation plate
Place the resulting bundle carefully in the lower part of the indoor unit,
making sure that it does not jut out from the rear of the indoor unit.
5
6
Hook the indoor unit on to the installation plate and move the unit to the
right and left until you are sure that it is securely in place.
Finish wrapping vinyl tape around the rest of the piping leading to the
outdoor unit.
7
Using clamps (optionally supplied), attach the piping to the wall wherever
possible.
E-47
COMPLETING THE INSTALLATION
Checking and Testing Operations
To complete the installation, perform the following checks and tests
to ensure that the air conditioner is operating correctly.
1
Review all the following elements in the installation:
◆
◆
◆
◆
◆
◆
◆
Installation site strength
Piping connection tightness to detect any gas leakages
Connection wiring
Heat-resistant insulation of the piping
Drainage
Earthing wire connection
Correct operations (follow the steps below)
2
Press the On/Off button.
Result:
◆◆The indicator lights on the indoor unit flash at
half-second intervals.
◆◆While the indoor unit opens, the indoor unit fan runs
to start.
3
Press the
Result:
button.
The outdoor unit operates in cooling mode as
following the room temperature.
4
Air flow direction
Press the
button and check that the air
flow blades work properly.
E-48
COMPLETING THE INSTALLATION
Explaining Operations to the Owner
Before leaving the premises on which you have installed the air conditioner,
you should explain the following operations to the owner, making
reference to the appropriate pages in the owner’s instruction booklet.
1
How to start and stop the air conditioner.
2
How to select the operating mode and adjust the temperature and fan
settings.
3
4
How to adjust the air flow direction.
How to set the timers.
5
How to remove and clean the filters.
Once the owner is happy with the basic operations, hand over the owner’s
instruction booklet and this installation manual for storage in a handy and safe
place.
E-49
THIS AIR CONDITIONER IS MANUFACTURED BY:
ESTE AIRE ACONDICIONADO HA SIDO FABRICADO POR:
CE CLIMATISEUR EST FABRIQUE PAR:
ELECTRONICS
Printed in Korea
|