Xantrex Technology Power Supply XW4024 120 240 60 User Manual

XW4024-120/240-60  
XW4548-120/240-60  
XW6048-120/240-60  
Installation Guide  
XW Power Distribution Panel  
XW System Control Panel  
XW Solar Charge Controller  
XW Automatic Generator Start  
XW Power System  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Power System  
Installation Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About Xantrex  
Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from  
50 watt mobile units to 2.5 MW utility-scale systems for wind, solar, batteries, fuel cells, micro turbines, and backup  
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery chargers,  
programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical  
power.  
Trademarks  
XW Power System is a trademark of Xantrex International. Xantrex is a registered trademark of Xantrex International.  
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used  
herein for identification purposes only.  
Notice of Copyright  
XW Power System Installation Guide © May 2007 Xantrex International. All rights reserved.  
Exclusion for Documentation  
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)  
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL  
OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.  
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES,  
WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT  
OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE  
USER’S RISK; AND  
(c) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH  
STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY  
CANNOT BE GUARANTEED. APPROVED XANTREX CONTENT IS CONTAINED WITH THE ENGLISH  
LANGUAGE VERSION WHICH IS POSTED AT WWW.XANTREX.COM.  
Due to continuous quality improvement and product updates, the illustrations shown in this manual may not exactly match  
the unit purchased.  
Date and Revision  
May 2007, Revision A  
Part Number  
975-0239-01-01  
Product Numbers  
865-1000 (XW 6048-120/240-60)  
865-1005 (XW4548-120/240-60)  
865-1010 (XW4024-120/240-60)  
Contact Information  
Telephone: 1-800-670-0707 (toll free in North America)  
Telephone: 1-360-925-5097 (direct)  
Fax:  
1-800-994-7828 (toll free in North America)  
1-360-925-5143 (direct)  
Fax:  
Email:  
Web:  
www.xantrex.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Guide  
Purpose  
The purpose of this Installation Guide is to provide explanations and procedures for  
installing the XW Power System.  
Scope  
The Guide provides safety guidelines, detailed planning and procedures for installing  
the XW Inverter/Charger and related system components (the “XW Power System”).  
It does not provide details about configuration, operation, maintenance or  
troubleshooting. See the Operation Guide or Owner’s Manual of each device for this  
information. This Guide also does not provide details about particular brands of  
batteries. You need to consult individual battery manufacturers for this information.  
Audience  
The Guide is intended for anyone who needs to install the XW Power System.  
Installers should be certified technicians or electricians.  
Organization  
This guide is organized into four chapters and three appendices.  
Chapter 1, “Introduction” lists and describes the components and basic features of the  
XW Power System.  
Chapter 2, “Inverter/Charger Installation” describes how to mount and install the XW  
Inverter/Charger, and the XW Power Distribution Panel and XW Conduit Box.  
Chapter 3, “Xanbus Network Installation” provides detailed information for planning  
and installing the components necessary for network communication on a Xanbus  
system.  
Chapter 4, “XW Solar Charge Controller Installation” describes how to mount and  
connect the XW Charge Controller as part of the XW System.  
Chapter 5, “XW System Accessories Installation” describes how to mount and install  
the XW System Control Panel and the Automatic Generator Start.  
Appendix A, “Specifications” provides the electrical and environmental specifications  
for the XW Series.  
Appendix B, “Wiring Diagrams” illustrate the most basic configurations and are for  
reference only. Specific installations may require additional equipment to meet  
national or local electric codes. Ensure all safety requirements are strictly followed.  
Appendix C, “Alternate System Configurations” provides wiring diagrams for  
inverter/charger installations that do not require use of the power distribution panel  
and the XW Conduit Box.  
975-0239-01-01  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
About This Guide  
Conventions Used  
The following conventions are used in this guide.  
WARNING  
Warnings identify conditions or practices that could result in personal  
injury or loss of life.  
CAUTION  
Cautions identify conditions or practices that could result in damage to  
the XW Power System components or other equipment.  
Related Information  
Additional information about operating the XW Inverter/Charger, see the XW  
Inverter/Charger Operation Guide (975-0240-01-01).  
For more information about related components, refer to:  
XW Power System Intallation Overview (975-0238-01-01)  
XW System Control Panel Owner’s Guide (975-0298-01-01)  
XW Solar Charge Controller Owner’s Guide (975-0283-01-01)  
XW Automatic Generator Start Owner’s Guide (975-0307-01-01)  
These guides are available at www.xantrex.com. Printed copies should be included  
with the components.  
For more information about Xantrex Technology, Inc. as well as its products and  
services visit www.xantrex.com.  
iv  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
WARNING  
This chapter contains important safety and operating instructions as required by UL and  
CSA standards for inverters used in residential applications. Read and keep this  
Installation Guide for future reference.  
1. Before using the inverter, read all instructions and cautionary markings on the  
unit, the batteries, and all appropriate sections of this manual.  
2. Use of accessories not recommended or sold by Xantrex Technology Inc. may result in  
a risk of fire, electric shock, or injury to persons.  
3. The inverter is designed to be permanently connected to your AC and DC electrical  
systems. Xantrex recommends that all wiring be done by a certified technician or  
electrician to ensure adherence to the local and national electrical codes applicable in  
your jurisdiction.  
4. To avoid a risk of fire and electric shock, make sure that existing wiring is in good  
condition and that wire is not undersized. Do not operate the inverter with damaged or  
substandard wiring.  
5. Do not operate the inverter if it has been damaged in any way. If the unit is damaged,  
see the Warranty and Product Information section at the end of this manual.  
6. This unit does not have any user-serviceable parts. Do not disassemble the inverter  
except where noted for connecting wiring and cabling. See the Warranty Section in the  
XW Inverter/Charger Operation Guide and other component manuals for instructions  
on obtaining service. Attempting to service the unit yourself may result in a risk of  
electrical shock or fire. Internal capacitors remain charged after all power is  
disconnected.  
7. To reduce the risk of electrical shock, disconnect both AC and DC power from the  
inverter before attempting any maintenance or cleaning or working on any  
components connected to the inverter. Turning off controls will not reduce this risk.  
8. The inverter must be provided with an equipment-grounding conductor connected to  
the AC input ground.  
9. Do not expose this unit to rain, snow, or liquids of any type. This product is designed  
for indoor use only. Damp environments will significantly shorten the life of this  
product and corrosion caused by dampness will not be covered by the product  
warranty.  
10. To reduce the chance of short-circuits, always use insulated tools when installing or  
working with this equipment.  
11. Remove personal metal items such as rings, bracelets, necklaces, and watches when  
working with batteries.  
975-0239-01-01  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Instructions  
Limitations on Use  
WARNING: Limitations on Use  
The XW Power System is not intended for use in connection with life support  
systems or other medical equipment or devices.  
Explosive Gas Precautions  
1. Working in the vicinity of lead acid batteries is dangerous. Batteries generate  
explosive gases during normal operation. Therefore, you must read this guide and  
follow the instructions exactly before installing or using your inverter/charger.  
2. To reduce the risk of battery explosion, follow these instructions and those published  
by the battery manufacturer and the manufacturer of the equipment in which the  
battery is installed.  
FCC Information to the User  
This equipment has been tested and found to comply with the limits for a Class B digital  
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide  
reasonable protection against harmful interference in a residential installation. This  
equipment generates, uses and can radiate radio frequency energy and, if not installed and  
used in accordance with the instructions, may cause harmful interference to radio  
communications. However, there is no guarantee that interference will not occur in a  
particular installation. If this equipment does cause harmful interference to radio or  
television reception, which can be determined by turning the equipment off and on, the  
user is encouraged to try to correct the interference by one or more of the following  
measures:  
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and the receiver.  
Connect the equipment to a circuit different from that to which the receiver is  
connected.  
Consult the dealer or an experienced radio/TV technician for help.  
vi  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -v  
Limitations on Use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vi  
Explosive Gas Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vi  
FCC Information to the User - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vi  
1
Introduction  
System Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2  
System Diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2  
System Components and Accessories - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3  
XW Inverter/Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3  
XW Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3  
XW Power Distribution Panel Panel and XW Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–4  
XW Connection Kit for INV2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–5  
XW Solar Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–6  
XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–6  
XW Automatic Generator Start - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–7  
2
Inverter/Charger Installation  
Pre-Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–2  
Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–2  
Knockout Preparation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–2  
Clearance Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–3  
Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–3  
Step 1: Installing the Mounting Plate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–4  
Step 2: Mounting the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–6  
Step 3: Mounting the XW Power Distribution Panel and XW Conduit Box- - - - - - - - - - - - - - - - - - - - -2–7  
Step 4: Wiring the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–8  
Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–9  
Battery Bank Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–9  
Battery Cable Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–9  
Torque Values for the XW Series Inverter/Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Torque Values for the XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
Inverter Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
Backfeed Protection Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
Wiring the Inverter to the XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12  
Grounding the DC System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12  
Installing the Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13  
Making DC Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14  
Making AC Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16  
AC Connections and Communication Ports - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16  
975-0239-01-01  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Accessing the AC Terminal Block and AC Ground Bar - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17  
Grounding the AC System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18  
AC Wiring to the Inverter AC Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19  
AC Wiring to the XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19  
Wiring the XW Inverter/Charger to a XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - 2–21  
Generator Wiring to the XW Inverter/Charger using a XW Power Distribution Panel - - - - - - - 2–22  
AUX Port - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23  
AUX+12V Voltage Supply - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23  
AUX-RPO: User Remote Power Off (RPO) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24  
User Line Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24  
AUX Port Terminal Assignments - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24  
Basic Functional Test - Single Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25  
Confirm All Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25  
Applying DC Power to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25  
Enable the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26  
AC Voltage Check - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27  
Confirming Battery Charger Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27  
Step 5: Installing Additional Inverters- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–29  
Installation Steps - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–29  
Parts List for Dual-Inverter Configurations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–30  
Converting a Single-Inverter Power Distribution Panel to a Dual-Inverter Power Distribution Panel 2–30  
DC Wiring for a Dual-Inverter System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–30  
AC Wiring for a Dual-Inverter System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–32  
Parts List for a Triple-Inverter Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–34  
Converting a Single-Inverter Power Distribution Panel to a Triple-Inverter Power Distribution Panel 2–34  
DC Wiring for a Triple-Inverter System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–34  
AC Wiring for a Triple-Inverter System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–36  
Xanbus and AC Sync Cable - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–38  
Basic Functional Test - Multiple Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–39  
3
Xanbus Network Installation  
Xanbus-enabled Devices- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–2  
The Xanbus System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–2  
Network Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–3  
Ordering Network Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–5  
Network Layouts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–5  
Multi-Drop Backbone Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–5  
Daisy Chain Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–6  
Installing the Network - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–7  
Before You Begin the Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–7  
Installation Tools and Materials - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–7  
Guidelines for Routing the Xanbus Cables - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–7  
Mounting a Network Connector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–8  
Installing Xanbus-Enabled Devices - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–9  
Completing the Multi-Drop Backbone Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–9  
Completing the Daisy Chain Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10  
viii  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
4
XW Solar Charge Controller Installation  
Installing the Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2  
PV Array Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2  
Array Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2  
Array Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2  
Array Current - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2  
MPPT Voltage Range - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3  
Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3  
Choosing a Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3  
Removing the Wiring Terminals Cover - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5  
Removing Knockouts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5  
Mounting the Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–6  
Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–8  
Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–9  
DC Terminal Connector Locations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–9  
Wire Size and Over-current Protection Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–9  
Connecting the XW Solar Charge Controller to the Distribution Panel - - - - - - - - - - - - - - - - - - - - 4–12  
Commissioning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–14  
Configuration Screens - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–14  
Commissioning Units Using a XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–14  
5
XW System Accessories Installation  
The XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–2  
Materials and Tools Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–3  
Choosing a Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–3  
Mounting the XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–3  
Verifying the Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–7  
The XW Automatic Generator Start - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–7  
Preparing an Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–7  
Materials and Tools Required - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–7  
Choosing a Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–8  
Routing the Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–8  
Installing the XW Automatic Generator Start - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–9  
Mounting the Unit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–10  
Wiring to the 20-contact Connector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–10  
Connecting the Generator - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–12  
Connecting the Thermostats (optional) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–13  
Connecting an External Shutdown (optional) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–13  
Connecting an External Manual ON/OFF Switch (optional) - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–14  
Connecting an External ON/OFF LED - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–15  
Connecting the Wiring Harness to the XW Automatic Generator Start - - - - - - - - - - - - - - - - - 5–16  
Connecting the XW Automatic Generator Start to the Xanbus Network - - - - - - - - - - - - - - - - 5–17  
Verifying Power Is Available - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–18  
975-0239-01-01  
ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Appendix A Specifications  
Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–2  
XW Series Overload Capability - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–3  
Output Power Versus Ambient Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–4  
XW Series Efficiency - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–4  
Inverting Efficiency (Typical) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–4  
Charging Efficiency (Typical) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5  
Sell Mode Efficiency (Typical) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5  
Mechanical Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5  
Accessories- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–6  
Appendix B Wiring Diagrams  
Single-Inverter System (Backup only)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–3  
Single-Inverter System Renewable Energy (Solar) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–4  
Single-Inverter System Renewable Energy (Wind or Hydro) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–5  
Dual-Inverter System Renewable Energy (Solar) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–6  
Dual-Inverter System Renewable Energy (Wind or Hydro) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–7  
Appendix C Alternate System Configurations  
DC Grounding for Single-Inverter Systems - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2  
Battery Connections for Single Inverter Systems - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–3  
AC Grounding for Single-Inverter Systems - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4  
AC Output Wiring to the Inverter AC Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–5  
Generator Wiring to the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–6  
Utility Wiring to the Inverter Input - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–7  
Wind or Hydro DC Sources- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–8  
x
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figures  
Figure 1-1  
Figure 1-2  
Figure 1-3  
Figure 1-4  
Figure 1-5  
Figure 1-6  
Figure 1-7  
Figure 1-8  
Figure 2-1  
Figure 2-2  
Figure 2-3  
Figure 2-4  
Figure 2-5  
Figure 2-6  
Figure 2-7  
Figure 2-8  
Figure 2-9  
XW Power System Installation Diagram Example - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2  
XW Inverter/Charger- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3  
XW Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3  
Power Distribution Panel and XW Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–4  
XW Connection Kit for INV2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–5  
XW Solar Charge Controller- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–6  
XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–6  
Automatic Generator Start - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–7  
Clearance Requirements- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–3  
Mounting Plate Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–4  
Mounting the Bracket for the XW Inverter/Charger or Distribution Panel- - - - - - - - - - - - - -2–5  
Mounting the XW Inverter/Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–6  
Installing the XW Conduit Box - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–7  
Routing Communications Cables - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–8  
DC Grounding Using a Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12  
Battery Temperature Sensor (RJ11) Port Location and Installation - - - - - - - - - - - - - - - - - 2–13  
XW Inverter/Charger DC Connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14  
Figure 2-10 Battery Cable Connection- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14  
Figure 2-11 DC Connections to a Single Inverter Using a XW Power Distribution Panel - - - - - - - - - - - 2–15  
Figure 2-12 XW Inverter/Charger AC Connections and Communications Ports - - - - - - - - - - - - - - - - - 2–16  
Figure 2-13 AC Terminal Block - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17  
Figure 2-14 Grounding the AC System using the Distribution Panel- - - - - - - - - - - - - - - - - - - - - - - - - 2–18  
Figure 2-15 Wiring the XW Power Distribution Panel to the Sub-panel or Utility Grid - - - - - - - - - - - - 2–20  
Figure 2-16 Wiring the Inverter to the XW Power Distribution Panel- - - - - - - - - - - - - - - - - - - - - - - - 2–21  
Figure 2-17 Generator Wiring Using a XW Power Distribution Panel- - - - - - - - - - - - - - - - - - - - - - - - 2–22  
Figure 2-18 AUX Port Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23  
Figure 2-19 Power-up Display - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25  
Figure 2-20 Enable the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26  
Figure 2-21 Checking AC Voltage - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27  
Figure 2-22 Checking Charging Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27  
Figure 2-23 Functional Test for Single Inverter Systems- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–28  
Figure 2-24 DC Connections to Dual Inverters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–31  
Figure 2-25 Dual Inverter AC Breaker Arrangement and Wiring Enlargement with  
Multiple AC Input Sources - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–32  
Figure 2-26 AC Wiring for Dual-Inverter Systems- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–33  
Figure 2-27 DC Connections for a Triple-Inverter System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–35  
Figure 2-28 Triple-Inverter AC Breaker Arrangement and Wiring Enlargement with  
Multiple AC Input Sources - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–36  
Figure 2-29 Triple-Inverter AC Breaker Arrangement and Wiring Enlargement with a  
Single AC Input Source - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–37  
Figure 2-30 Wiring an External Bypass Switch for a Triple-Inverter Configuration- - - - - - - - - - - - - - - 2–37  
Figure 2-31 Installing the AC Sync Cable - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–38  
Figure 2-32 Functional Test for Multiple Inverters - Page 1 of 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–41  
975-0239-01-01  
xi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figures  
Figure 2-33 Functional Test for Multiple Inverters - Page 2 of 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–42  
Figure 3-1  
Network-Managed Power System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–2  
Xanbus Cable and RJ45 Connector Pin Numbers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–4  
Network Terminators- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–4  
3-Way Network Connector (sample configuration)- - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–4  
Multi-Drop Backbone Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–6  
Daisy Chain Network Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–6  
Recommended Mounting Orientation for Network Connector - - - - - - - - - - - - - - - - - - - - -3–8  
Options for Completing a Multi-Drop Backbone Layout - - - - - - - - - - - - - - - - - - - - - - - - -3–9  
Completing a Daisy-Chain Layout- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10  
Minimum Clearance Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–4  
Removing the Wiring Terminals Cover - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5  
Dimensions and Knockout Locations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5  
Knockout Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–6  
Mounting the XW Solar Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–7  
XW Solar Charge Controller Safety Ground Connector- - - - - - - - - - - - - - - - - - - - - - - - - -4–8  
DC Connection Terminals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–9  
Connecting Solar DC Sources in the Power Distribution Panel - - - - - - - - - - - - - - - - - - - - 4–13  
XW System Control Panel Xanbus Port Locations - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–2  
Inserting the Mounting Plate- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–4  
Securing the Mounting Plate- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–4  
Connecting the Network Cables - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–5  
Securing the XW System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–5  
Surface Mounting the XW System Control Panel- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -5–6  
Connecting the AGS Communications Cable to the XW Series - - - - - - - - - - - - - - - - - - - -5–7  
XW Automatic Generator Start External Connections - - - - - - - - - - - - - - - - - - - - - - - - - - -5–9  
XW Automatic Generator Start Wiring Harness- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–11  
Figure 3-2  
Figure 3-3  
Figure 3-4  
Figure 3-5  
Figure 3-6  
Figure 3-7  
Figure 3-8  
Figure 3-9  
Figure 4-1  
Figure 4-2  
Figure 4-3  
Figure 4-4  
Figure 4-5  
Figure 4-6  
Figure 4-7  
Figure 4-8  
Figure 5-1  
Figure 5-2  
Figure 5-3  
Figure 5-4  
Figure 5-5  
Figure 5-6  
Figure 5-7  
Figure 5-8  
Figure 5-9  
Figure 5-10 External On/Off Switch and LED Wiring Diagram- - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–15  
Figure 5-11 XW Automatic Generator Start External Connections - - - - - - - - - - - - - - - - - - - - - - - - - - 5–16  
Figure 5-12 Connecting the SCP- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–17  
Figure 5-13 Verifying Power is Available - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–18  
Figure A-1 XW Series AC Overload Capability- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–3  
Figure A-2 Output Power Versus Ambient Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–4  
Figure B-1 Single-Inverter System (Backup only) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–3  
Figure B-2 Single-Inverter System Renewable Energy (Solar) - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–4  
Figure B-3 Single-Inverter System Renewable Energy (Wind or Hydro) - - - - - - - - - - - - - - - - - - - - - B–5  
Figure B-4 Dual-Inverter System Renewable Energy (Solar) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–6  
Figure B-5 Dual-Inverter System Renewable Energy (Wind or Hydro) - - - - - - - - - - - - - - - - - - - - - - B–7  
Figure C-1 DC Grounding for an Inverter only - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–2  
Figure C-2 DC Connections to a Single Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–3  
Figure C-3 Grounding the AC System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–4  
Figure C-4 AC Output Wiring to the Inverter AC Distribution Panel- - - - - - - - - - - - - - - - - - - - - - - - C–5  
Figure C-5 Generator Wiring directly to the Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–6  
Figure C-6 Utility Wiring to the Inverter Input- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–7  
Figure C-7 Connecting Wind or Hydro DC Sources - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - C–8  
xii  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Tables  
Table 2-1  
Table 2-2  
Table 2-3  
Table 2-4  
Table 2-5  
Table 2-6  
Table 2-7  
Table 2-8  
Mounting Plate Fastener Recommendations- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4  
Recommended Battery Cable Size Versus Length- - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Battery Cable (in conduit) to Maximum Breaker/Fuse Size - - - - - - - - - - - - - - - - - - - - - 2–10  
Torque Values for AC Wiring (AC Terminals and Ground Bar) - - - - - - - - - - - - - - - - - - 2–10  
Torque Values for the Chassis Ground Lug - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Torque Values for the Inverter Battery Terminals - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10  
Torque Values for AC Disconnects and AC Breakers - - - - - - - - - - - - - - - - - - - - - - - - - 2–11  
Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus, and  
DC Positive Bus in the XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - -2–11  
Table 2-9  
Torque Values for the Power Distribution Bars in the XW Power Distribution Panel - - - - 2–11  
Table 2-10 Torque Values for the Battery Cables to the DC Negative Bus, and  
DC Positive Bus in the XW Power Distribution Panel - - - - - - - - - - - - - - - - - - - - - - - - - -2–11  
Table 2-11 User Connector Terminals and Functions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24  
Table 3-1  
Table 3-2  
Table 3-3  
Table 4-1  
Table 4-2  
Table 4-3  
Table 4-4  
Table 4-5  
Table 5-1  
Table 5-2  
Table 5-3  
Table 5-4  
Table 5-5  
Table 5-6  
Table A-1  
Table A-2  
T568A Standard Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3  
Xanbus Network Components and Part Numbers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5  
Minimum and Maximum Cable Length- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8  
MPPT Operational Window - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3  
Minimum Clearance Requirements- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–4  
Recommended Circuit Breakers for the XW Solar Charge Controller- - - - - - - - - - - - - - - 4–10  
One-Way Wire Distance and Wire Size for a 24 Vdc System - - - - - - - - - - - - - - - - - - - - 4–11  
One-Way Wire Distance and Wire Size for a 48 Vdc System - - - - - - - - - - - - - - - - - - - - 4–11  
Circuit Limitations- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–10  
Required Wiring Size Based on Length of Cable - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–11  
Contact Numbers and Functions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–11  
Wiring for Connecting Thermostats - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–13  
Wiring for Connecting an External Shutdown - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5–13  
Wiring for Connecting an External Manual ON/OFF Switch - - - - - - - - - - - - - - - - - - - - 5–14  
XW Power System Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–2  
XW Power System Mechanical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5  
975-0239-01-01  
xiii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
xiv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1
Chapter 1, “Introduction” lists and describes the components and basic  
features of the XW Power System.  
For this Topic  
See....  
“System Overview”  
page 1–2  
page 1–3  
“System Components and Accessories”  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
System Overview  
The XW Power System consists of several devices, components, and optional accessories  
that, when installed together, create a renewable energy power system that can be  
customized to suit nearly any application—off grid, grid tied, or backup. Up to three  
inverters can be installed in parallel to create larger 120/240 V 3-wire, single-phase  
systems allowing for increased capacity.  
System Diagram  
Figure 1-1 XW Power System Installation Diagram Example  
1–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Components and Accessories  
System Components and Accessories  
XW Inverter/Charger  
The XW Inverter/Charger is a modular “building block” sine-wave inverter/charger that  
can be used for both residential and commercial stand-alone, grid-backup, and grid-tie  
applications with battery energy storage. The XW Series is a self-contained DC to AC  
inverter, battery charger, and AC transfer switch. Up to three inverters can be installed in  
parallel to create larger 120-240-volt, 3-wire, single-phase systems allowing for increased  
capacity.  
Figure 1-2 XW Inverter/Charger  
A Battery Temperature Sensor (FGA # 808-0232-02) is also included with the XW  
Inverter/Charger. The Battery Temperature Sensor monitors the temperature of the battery  
bank and adjusts the charging accordingly. See page 2–13 for installation instructions for  
this accessory.  
XW Conduit Box  
A conduit box (FGA # 865-1025) is available to enclose the bottom of the XW  
Inverter/Charger and protect the cabling. Use of the conduit box may be required  
depending on the local electrical code. Be sure to consult with the local electrical authority  
to ensure the installation is code-compliant.  
Figure 1-3 XW Conduit Box  
975-0239-01-01  
1–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
The XW Conduit Box comes in two pieces and mounts directly to the bottom of the  
inverter/charger with keyhole slots and screws. It is secured to the inverter by two  
#10-32 screws and is secured to the wall by two screws (not provided).  
Internal wire barriers (or raceways) are included to keep communications wires separate  
from AC and DC power wires. The XW Conduit Box also includes multiple cable strap  
points.  
XW Power Distribution Panel Panel and XW Conduit Box  
The XW Power Distribution Panel (FGA: 865-1015) includes a mounting plate and XW  
Conduit Box. It is factory wired and labelled with everything to support a code-compliant  
single-inverter installation. It is designed to mount on the right side of the inverter/charger,  
but it can also be configured to mount on the left side. Internal wiring and breakers can be  
added to expand the XW Power System with up to three inverters, four charge controllers,  
or other equipment to support 120/240-volt, 3-wire, single-phase systems.  
The XW Power Distribution Panel and XW Conduit Box interface with:  
XW4024, XW4548, and XW6048 inverter/chargers  
XW Solar Charge Controllers (requires customer supplied breakers and wiring)  
C-Series Charge Controllers (requires customer supplied breakers and wiring).  
Internal wire barriers (or raceways) are included to keep communications wires separate  
from AC and DC power wires.  
XW Power Distribution Panel  
XW Power Distribution Panel includes:  
Power Distribution Panel enclosure with a field-reversible panel door  
Mounting Plate  
XW Conduit Box  
XW Conduit Box  
Mounting Plate  
The enclosure comes pre-wired with:  
3x 60A, 120/240 Vac, 2-pole, Square-D, Type QOU, DIN-rail mounted  
AC breakers (pre-wired to connect to one XW inverter)  
1x GJ250A 160 Vdc, 3/8" stud DC breaker  
1x Ground terminal bus bar  
1x Neutral terminal bus bar  
1 pair #4/0 AWG Battery Cables  
The panel door can be mounted on the right or left side of the XW Power  
Distribution Panel.  
AC Knockout slots = 8 (for dual 60A Square D, type QOU breakers)*  
DC Knockout slots = 8 small (for 60A DC breakers) and 3 large (for GJ breakers)  
*AC Breakers cannot exceed 60A.  
XW PDP Dimensions:  
30" (761mm) H x 16" (406mm) W x 8 ¼" (210mm) D  
Depth from the wall = 8 ¾" (223 mm)  
Figure 1-4 Power Distribution Panel and XW Conduit Box  
1–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Components and Accessories  
XW Connection Kit for INV2  
The XW Connection Kit for Inv2 (FGA # 865-1020) is the extension kit required for  
connecting a second or third XW Inverter/Charger in the same system.  
XW Connection Kit includes:  
XW Conduit Box with raceway barriers and cable strap  
connections points,  
3x 60 A, 120/240 Vac, 2-pole, Square-D, Type QOU, Din-Rail  
mountable, AC breakers (includes bypass plate)  
XW Conduit Box  
#6 AWG AC wiring to connect the inverter to the AC breakers  
(includes 4 conduit bushings)  
4x Power Distribution Bars (replaces factory-installed bars)  
1x GJ250A 160 Vdc, 3/8" stud DC breaker  
1x Bus Bar for DC positive  
1 pair #4/0 AWG battery cables  
AC Sync and Xanbus cables (not shown)  
60A, 120/240Vac AC  
Breakers  
AC Bypass Plate  
Power Distribution Bars  
#6 AWG AC Wiring  
15/16" bushing for AC sync  
and Xanbus knockouts  
GJ250A DC breaker  
1-3/8" bushings for AC  
Wiring knockouts  
#4/0 AWG battery cables  
DC Positive Bus Bar  
Figure 1-5 XW Connection Kit for INV2  
975-0239-01-01  
1–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
XW Solar Charge Controller  
The XW Solar Charge Controller (FGA # 865-1030) is a 60 amp charge controller with  
integrated PVGFP and separate Battery Temperature Sensor. The XW Solar Charge  
Controller can be used with 12-, 24-, 36-, 48-, and 60-volt DC battery systems. However,  
the XW Inverter/Charger can only work at 24 or 48 volts depending on the model. When  
the XW Solar Charge Controller is used with the XW Inverter/Charger, it is limited to 24-  
or 48-volt battery banks. The XW Solar Charge Controller will automatically detect the  
24- or 48-volt settings.  
Figure 1-6 XW Solar Charge Controller  
XW System Control Panel  
The XW System Control Panel features a graphical, backlit liquid crystal display that  
displays system configuration and diagnostic information for all devices connected to the  
network. When installed as an XW Power System accessory, the XW System Control  
Panel eliminates the need for separate control panels for each device and gives a single  
point of control to set up and monitor an entire XW Power System.  
FGA Number:  
865-1050  
Figure 1-7 XW System Control Panel  
1–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Components and Accessories  
XW Automatic Generator Start  
The XW Automatic Generator Start can automatically activate a generator to provide an  
XW Series Inverter/Charger with power to recharge depleted batteries or assist with heavy  
loads. The XW Automatic Generator Start adds intelligence to power management and  
eliminates time spent monitoring batteries and inverter loads.  
The XW Automatic Generator Start is compatible with popular generators, and can be  
configured to start the generator in response to low battery voltage, thermostat operation,  
or load size on the inverter battery. A quiet time setting prevents the generator from  
starting at inconvenient times. LEDs display the status of the XW Automatic Generator  
Start, while all user-defined settings are programmed through the XW System Control  
Panel.  
FGA Number:  
865-1060  
Figure 1-8 Automatic Generator Start  
Generator  
The generator should be a 120/240V, 2-wire or 3-wire generator with Auto Start capability.  
Important: Do not use a 120-volt only generator. The inverter will not accept  
power from a generator of this kind.  
The generator should also supply a Generator Run signal. This signal is used by the XW  
Automatic Generator Start to detect whether the generator is running. Some generator  
manufacturers refer to this signal as the Hour Meter Signal or Switched B+.  
Generator  
Compatibility  
The XW Automatic Generator Start supports most two and three-wire generator starters.  
Some manufacturers include, but are not limited to, Onan (Quiet Diesel, gasoline, and LP),  
Power Tech, Generac, Northern Lights, Fisher Panda, Westerbeke, Kohler, Honda, and  
Yamaha. Check with the generator manufacturer to ensure the generator in question  
includes automatic starting capabilities.  
XW System Control  
Panel  
A XW System Control Panel is required to configure the XW Automatic Generator Start  
and monitor generator starting and stopping activity.  
The XW System Control Panel also provides real-time clock information for the XW  
Automatic Generator Start Quiet Time and Exercise Time features.  
975-0239-01-01  
1–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1–8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger  
Installation  
2
Chapter 2, “Inverter/Charger Installation” describes how to mount and install  
the XW Inverter/Charger, and the XW Power Distribution Panel and XW  
Conduit Box.  
For this Topic  
See....  
“Pre-Installation”  
page 2–2  
page 2–4  
page 2–6  
“Step 1: Installing the Mounting Plate”  
“Step 2: Mounting the Inverter”  
“Step 3: Mounting the XW Power Distribution Panel and XW page 2–7  
Conduit Box”  
“Step 4: Wiring the Inverter”  
page 2–8  
“Step 5: Installing Additional Inverters”  
page 2–29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Pre-Installation  
Before installing the XW Inverter/Charger, read all instructions and cautionary markings  
located in this manual.  
Important: Be sure to obtain the appropriate permits, if necessary, prior to  
starting this installation. Installations must meet all local codes and standards.  
Installations of this equipment should only be performed by skilled personnel  
such as qualified electricians and Certified Renewable Energy (RE) System  
installers.  
WARNING: Personal Injury  
The XW Inverter/Charger weighs approximately 120 pounds (54 kg). To prevent personal injury,  
always use proper lifting techniques and have someone available to assist with lifting during  
installation.  
Location  
The XW Inverter/Charger is certified for indoor (heated or unheated) installations only.  
Close to battery  
bank  
Locate the inverter as close to the batteries as possible in order to keep the battery cable  
length short. The maximum recommended battery cable length is 10 feet (3 m).  
WARNING: Explosion and Corrosion Hazard  
Do not locate the inverter directly above the batteries or in the same compartment as vented  
batteries.  
Locate any electronic equipment susceptible to radio frequency and electromagnetic  
interference as far away from the inverter as possible.  
Fire safety  
Do not locate the inverter near readily flammable materials such as cloth, paper, straw, or  
plastic sheeting. Flammable materials should be kept a minimum distance of 24 inches  
(60 cm) from the top surface and 12 inches (30 cm) from either side surface and the front  
of the XW Inverter/Charger.  
Knockout Preparation  
Remove your choice of knockouts from the chassis to facilitate conduit installation for  
wire runs. Ensure no debris from this procedure remains inside the inverter enclosure.  
Important: Do not drill, cut, or punch holes into the XW power distribution  
Panel. Use only the knockouts provided for conduit entry.  
2–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-Installation  
Clearance Requirements  
Provide a minimum clearance of 6 inches (15 cm)—12 inches is preferred—around the top  
and 6 inches (15 cm) at the bottom of the inverter for ventilation. There must be at least  
three feet of clearance in front of the inverter. Ensure that the vents are not obstructed with  
foreign objects and that the minimum clearances are met.  
Figure 2-1 Clearance Requirements  
Mounting  
The XW Power System is designed to be mounted on a vertical surface. The supporting  
surface must be strong enough to support a minimum of 500 pounds (227 kg). To facilitate  
installation, a wall mounting plate (Xantrex p/n 210-0462-01-01) is provided for each XW  
Inverter/Charger and XW Power Distribution Panel. The mounting plate and hardware on  
the XW Inverter/Charger and XW Power Distribution Panel are designed to meet  
standards for structural and seismic stability. When properly installed, the system also  
meets Section 59 of UL 1741 for Static Loads.  
975-0239-01-01  
2–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Step 1: Installing the Mounting Plate  
Each XW Inverter/Charger and XW Power Distribution Panel requires a separate  
mounting plate. This bracket is first attached to the wall, then the inverter/charger or  
distribution panel is attached to the wall bracket.  
The wall bracket is attached to the wall with lag bolts or other fasteners, provided by the  
installer. A minimum of four ¼-inch diameter fasteners are required. The fasteners must  
be sufficiently strong to support 500 pounds.  
The wall bracket has mounting holes spaced 16 inches (40 cm) apart and is designed to  
span two wall studs spaced 16 inches on-center. Additional mounting holes are also  
provided for flexibility in mounting options. If the wall does not have 16-inch on-center  
studs, the installer will need to provide adequate supports for the brackets. For example, a  
sheet of plywood can be attached to the wall, and the wall brackets can then be attached to  
plywood.  
Both the XW Inverter/Charger and XW Power Distribution Panel use the same wall  
bracket. The brackets are designed to interlock (as shown in Figure 2-3), so that additional  
mounting plates are easily installed without additional measuring or levelling.  
The type of fastener required to secure the mounting plate varies according to the vertical  
surface and wall structure of your installation location.  
Table 2-1 Mounting Plate Fastener Recommendations  
Number of Screws  
Structure  
Required Fastener  
Per Bracket  
Wood studs at 16" (on center - O.C.)  
1/4" Ø × 3 1/2" long lag screw Four  
Wood studs not at 16" O.C. (3/4" minimum 1/4" Ø × 1" long wood screw  
plywood panel required)  
Six  
Steel studs at 16" O.C. (minimum 18 gauge) 1/4" Ø self-drilling screw  
Four  
16 (406)  
4 1/2 (115)  
1 3/4 (45)  
6 7/8  
9 3/16  
(233)  
(175)  
2 1/4  
(57)  
6 (153)  
2 (49)  
3/4 (19)  
17 (432)  
all measurements in inches  
(millimeters)  
Figure 2-2 Mounting Plate Dimensions  
2–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 1: Installing the Mounting Plate  
Wall studs 16" on center behind  
wallboard  
Side View  
2 × 4 wall stud  
Wallboard  
Plywood  
(optional)  
mounting plate  
Multiple mounting plates should fit together  
as shown.  
Add ¾" plywood if additional support is  
needed.  
60" (152.4 cm) from floor  
puts the inverter display  
panel at approx. 65"  
high.  
Locate the wall studs.  
1
2
3
4
5
If necessary, enhance the support surface with a ¾" plywood panel  
secured to the wall studs. Plywood should span at least three wall studs.  
Use hardware sized to support a minimum of 500 lbs (not provided) to  
secure the plywood to the wall.  
Using a level, secure the first mounting bracket to the wall. Use  
recommended anchoring hardware to secure the plate (see Table 2-1).  
Mount the next bracket adjacent to the first one. The brackets are designed  
to interlock, so additional mounting brackets are easily installed without  
additional measuring or levelling.  
Figure 2-3 Mounting the Bracket for the XW Inverter/Charger or Distribution Panel  
975-0239-01-01  
2–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Step 2: Mounting the Inverter  
3
2
1
1
2
Align the flange on the back of the XW Inverter/Charger with the bottom edge of the  
mounting plate.  
Lower the flange on the inverter onto the mounting plate.  
CAUTION: Before releasing the full weight of the unit, ensure the inverter is seated  
properly on the mounting plate.  
3
Secure the top of inverter with two #10 self-tapping screws (supplied).  
Figure 2-4 Mounting the XW Inverter/Charger  
2–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3: Mounting the XW Power Distribution Panel and XW Conduit Box  
Step 3: Mounting the XW Power Distribution Panel and XW Conduit  
Box  
Mount the XW Distribution Panel on the mounting bracket following the same procedure  
in Step 2.  
When mounting the XW Conduit Box as shown in Figure 2-5, it is not necessary to attach  
the front panel until all wiring is complete.  
Attach the back panel of the  
XW Conduit Box to the bottom  
1
of the inverter with two screws  
through the keyhole slots under  
the back panel top and the  
xantrex  
xantrex  
i  
I
F
a  
n
e
i  
corresponding holes in the  
bottom of the inverter (A).  
Secure the bottom edge of the  
back panel to the wall using two  
screws (B).  
l i  
t
Hybrid Inverter /Charger  
Power Distribution Panel  
NE
A
B
xantrex  
xantrex  
i  
i  
h
n
e
i  
a
Attach the front panel of the XW  
Conduit Box by sliding the  
bottom lip of the front panel over  
the lower edge of the back  
panel. Align the two holes in the  
front panel with the two holes in  
the back panel. Use the two  
#10-32 screws provided to  
secure the front panel to the  
back panel.  
2
Hybrid Inverter /Charger  
Power Distribution Panel  
Figure 2-5 Installing the XW Conduit Box  
975-0239-01-01  
2–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Step 4: Wiring the Inverter  
This section provides procedures for making AC and DC connections between the XW  
Inverter/Charger and the power distribution panel using the cables that are pre-installed in  
the distribution panel. This section also assumes that the XW Conduit Box was installed in  
the previous section.  
For diagrams and information about installing the inverter/charger without the XW  
Conduit Box and XW Power Distribution Panel, see Appendix C.  
Important: Communication and signal cables must be segregated from all DC and  
AC wiring. Therefore, a small raceway has been included in the design of both the  
XW Power Distribution Panel and the XW Conduit Box to separate the  
communications cables from the power cables. This is a small raceway run built into  
the bottom of both the XW Power Distribution Panel and the XW Conduit Box and is  
held in place by a single screw at the top of the raceway.  
Installation Tip  
Before making the AC or DC cable connections, route the communications cables through  
the raceway, but do not connect them to their components until after all the inverter  
connections are made. Once the AC and DC connections are made the run becomes  
difficult to access. Use different colors for the communications cables (or cable tags) to  
help make them easier to identify.  
Route the communications cables for any  
accessories being installed BEFORE  
making AC or DC Connections.  
IMPORTANT: When routing communications cables through the XW  
Power Distribution Panel, the raceway conduit must be used to keep the  
communications cables separate from the power cables.  
XW System  
Control Panel  
Do not connect to the  
XW Automatic  
Generator Start until  
all other connections  
have been made.  
Do not connect to  
the XW System  
Control Panel until  
all other  
connections have  
been made.  
XW Automatic  
Generator Start  
Raceway for Shunt  
Sense cable*.  
Raceway exits the  
panel through the  
back.  
Do not connect to  
the BTS to the  
batteries until the  
battery bank has  
been prepared and  
is ready to connect  
See Figure 2-12 on  
page 2–16 for an  
illustration showing  
the Communications  
Ports and where the  
accessories connect.  
to the inverter.  
Raceway for Communications  
Cables*  
Raceway for Communications  
Cables*  
BTS  
*To remove, remove the screws at  
the top (Or side) of the raceway.  
Figure 2-6 Routing Communications Cables  
2–8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
Batteries  
See the FAQs section of the Xantrex Web site for information on determining battery bank  
requirements.  
Consider the following recommendations for battery use.  
Use only the deep discharge types for inverter applications.  
Use the same battery type for all batteries in the bank.  
Use only batteries from the same lot and date in your battery bank. This information is  
usually printed on a label located on the battery.  
CAUTION: Damage to Equipment  
The XW Inverter/Charger is intended to operate with batteries as its source of DC power. Do not  
connect DC power sources, such as PV arrays, wind turbines, or micro-hydro turbines, directly to  
the XW Inverter/Charger without a battery. Connect DC power sources to a charge controller such  
as the XW Solar Charge Controller instead. If DC power sources are connected directly to the  
inverter, the DC rating of the inverter can be exceeded and the inverter can be damaged.  
Battery Bank Requirements  
The DC voltage of the inverter must match the nominal voltage of the system and all  
battery-connected devices. If the inverter is a 24-volt inverter, then the battery bank and all  
battery-connected devices in the system need to be configured for 24 volts.  
Important: The minimum recommended battery bank is 100 Ah. The inverter is designed to  
operate with batteries and should not be operated without them. Also, do not allow the battery  
bank to become completely discharged. If the voltage of the battery bank falls below 10 volts, the  
XW Power System will not operate.  
Battery Cable Requirements  
WARNING: Fire Hazard  
Undersized cables can overheat and melt, creating a fire hazard when subjected to heavy (peak)  
loads. Always use a cable of proper size and length, rated for the amperage of the inverter and  
batteries.  
Important: Use only fine-stranded copper cables for battery and inverter DC connections. Do  
not use coarse-stranded wire, as the lack of flexibility may damage battery and inverter terminals.  
Battery cable length  
Battery cable lugs  
Runs should be kept as short as practical. Length should not exceed 10 feet (3 m). For best  
performance, the positive and negative cables should run alongside each other. Avoid  
cable loops.  
Battery cables must have crimped copper compression lugs or crimped and soldered  
copper compression lugs. Soldered connections alone are not acceptable. Lugs must be  
rated for use with fine-stranded cable.  
Overcurrent  
protection  
For safety and compliance with regulations, battery overcurrent protection is required.  
Fuses and disconnects must be sized to protect the wiring in the system and are required to  
open before the wire reaches its maximum current carrying capability.  
975-0239-01-01  
2–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Terminal covers Color-coded snap-on DC terminal covers are provided to prevent accidental contact with  
the terminals. Terminal covers are required for all installations, even if a XW Conduit Box  
is used. It is also recommended that the shank of the ring terminals (cable lugs) be covered  
with heat shrink or some other form of insulation.  
Table 2-2 Recommended Battery Cable Size Versus Length  
Inverter Model  
Up to 5 Feet (1.5 m) (90°C wire)  
Up to 10 Feet (3 m) (90°C wire)  
2
2
XW4024  
#4/0 AWG (120 mm )  
#4/0 AWG (120 mm )  
2
2
XW4548  
XW6048  
#2/0 AWG (70 mm )  
#4/0 AWG (120 mm )  
2
2
#4/0 AWG (120 mm )  
#4/0 AWG (120 mm )  
Important: The NEC/CEC requires both overcurrent protection and a disconnect switch for  
residential and commercial electrical systems. These items are not supplied as part of the inverter,  
but are included in the XW Power Distribution Panel.  
Table 2-3 Battery Cable (in conduit) to Maximum Breaker/Fuse Size  
Cable Size  
Required  
Maximum Breaker/Fuse  
Size  
#2/0 (00) AWG  
175 amps  
250 amps  
#4/0 (0000) AWG  
Torque Values for the XW Series Inverter/Charger  
Table 2-4 Torque Values for AC Wiring (AC Terminals and Ground Bar)  
Wire Size  
AWG  
Torque Value  
In-lb N-m  
35  
14–10  
8
4
40  
45  
4.5  
5
6–4  
Table 2-5 Torque Values for the Chassis Ground Lug  
Wire Size  
Torque Value  
AWG  
6-4  
In-lbs  
45  
N-m  
5.1  
5.6  
3-2  
50  
Table 2-6 Torque Values for the Inverter Battery Terminals  
Torque Value  
Ft-lbs  
N-m  
15  
20.4  
2–10  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
Torque Values for the XW Power Distribution Panel  
Table 2-7 Torque Values for AC Disconnects and AC Breakers  
Wire Size  
AWG  
Torque Value  
In-lb N-m  
45  
16–10  
8
5
45  
45  
5
5
6–4  
Table 2-8 Torque Values for the Ground Bus, AC Neutral Bus, DC Negative Bus, and DC  
Positive Bus in the XW Power Distribution Panel  
Wire Size Torque Value  
AWG  
14 - 10  
8
In-lbs  
35  
N-m  
4.0  
4.5  
5.1  
5.6  
40  
6 - 4  
3 - 2/0  
45  
50  
Table 2-9 Torque Values for the Power Distribution Bars in the XW Power Distribution  
Panel  
Wire Size Torque Value  
AWG  
14 - 10  
8
In-lbs  
35  
N-m  
4.0  
4.5  
5.1  
5.6  
40  
6 - 4  
3 - 2/0  
45  
50  
Table 2-10 Torque Values for the Battery Cables to the DC Negative Bus, and DC  
Positive Bus in the XW Power Distribution Panel  
Torque Value  
Ft-lbs  
N-m  
15  
20.4  
Inverter Grounding  
Important: The grounding requirements vary by country and by application. All installations  
must comply with national and local codes. Consult local and national codes for specific grounding  
and bonding requirements for the desired installation.  
Backfeed Protection Requirements  
Important: Installers must make allowance for the amount of power that can  
be fed into a distribution panel and the means and location for feed-in, in  
accordance with NEC 2005 article 690.64 or similar requirements of the local  
electrical code.  
975-0239-01-01  
2–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Wiring the Inverter to the XW Power Distribution Panel  
Important: If a XW Conduit Box is installed, communication and Battery Temperature Sensor  
cables must run through the raceway at the rear of the XW Conduit Box. Before making AC and  
DC connections, route all communication and Battery Temperature Sensor cables through the  
raceways. The raceways becomes more difficult to access after all AC and DC wiring is completed.  
Grounding the DC System  
The inverter’s chassis ground bar (see Figure 2-7) is used to connect the chassis of the  
inverter to the DC grounding system. The terminal accepts wires from #14 AWG to  
#2 AWG.  
A
See Table 2-5 on page 2–10  
for torque values for the AC  
Chassis Ground.  
B
B
See Table 2-6 on page 2–10  
for torque values for the  
Ground bar in the XW Power  
Distribution Panel.  
A
Actual ground requirements may vary.  
Figure 2-7 DC Grounding Using a Power Distribution Panel  
2–12  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
Installing the Battery Temperature Sensor  
The Battery Temperature Sensor (BTS) port is for connecting to the Battery Temperature  
Sensor, which regulates battery charging based on battery temperature. Installing a sensor  
extends battery life by preventing overcharging in warm temperatures and undercharging  
in cold temperatures. This port is also considered part of the DC interface (see Figure 2-9).  
To install the Battery Temperature Sensor:  
1. Pass the end of the Battery Temperature Sensor cable through a conduit hole and insert  
the Battery Temperature Sensor plug into the Battery Temperature Sensor port.  
2. Route the cable to the battery enclosure and connect the ring terminal on the Battery  
Temperature Sensor directly to a battery terminal (recommended), or use the adhesive  
backing on the sensor back to attach the sensor to any side of the battery to be  
monitored.  
If using the adhesive backing, install the Battery Temperature Sensor on the side of the  
battery below the electrolyte level. It is best to place the sensor between batteries and  
place the batteries in an insulated box to reduce the influence of the ambient  
temperature outside the battery enclosure.  
Battery Temperature  
Sensor Port (RJ11)  
1
RJ11 jack  
Note: If other Xanbus  
connected components  
supply a BTS or are BTS  
enabled, it is not necessary  
to install all of them at once.  
Only one BTS needs to be  
installed.  
2
However, if multiple  
battery-banks are being  
used, multiple sensors can  
be installed. In which case,  
the system will use the  
highest temperature from  
all the input as it’s  
If using the adhesive backing, install  
the Battery Temperature Sensor on  
the side of the battery below the  
electrolyte level.  
operational parameter.  
Figure 2-8 Battery Temperature Sensor (RJ11) Port Location and Installation  
975-0239-01-01  
2–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Making DC Connections  
This section describes how to make DC connections between the inverter/charger and the  
power distribution panel (using the pre-installed DC cables in the distribution panel),  
between the distribution panel to the batteries (using battery cables provided by the  
installer—see Table 2-2 on page 2–10). This section also provides procedures for  
installing the battery temperature sensor. See Appendix C, “Alternate System  
Configurations” if the installation will not be including an XW Power Distribution Panel.  
WARNING: Shock Hazard  
Ensure that all AC and DC breakers are switched OFF before connecting or disconnecting the  
battery cables and that all sources of power (both AC and DC) are disconnected from the inverter.  
Positive (+, red)  
battery terminal  
Negative (–, black)  
battery terminal  
BTS port (RJ11)  
Battery Temperature  
Sensor (included)  
(FGA #808-0232-02)  
Chassis Ground  
Lug  
Bottom View  
Figure 2-9 XW Inverter/Charger DC Connections  
To connect the XW Power Distribution Panel to the inverter:  
1. Connect the pre-installed DC cables from the XW Power Distribution Panel to the  
inverter DC terminals. Figure 2-10 shows the proper stacking order of hardware. Be  
careful to observe proper polarity.  
2. Attach the DC terminal covers.  
3. Route the DC cables from the battery—with the cables not connected to the battery—  
and connect them to the XW Power Distribution Panel: negative to negative bus,  
positive to the input end of the DC breaker. To properly attach and torque the positive  
cable to the DC breaker, you may need to temporarily remove the breaker from the  
rail.  
4. Perform the procedures in “Making AC Connections” before connecting the DC  
cables from the XW Power Distribution Panel to the battery.  
Terminal surface  
Shrink-wrap to color-code  
Ensure nothing is between the terminal  
surface and the battery cable lug  
Battery cable lug  
the cable  
Flat washer  
Copper compression lug  
Split-ring washer  
3/8-15 x 5/8” bolt (supplied)  
Figure 2-10 Battery Cable Connection  
2–14  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
CAUTION: Damage to Equipment  
Do not put anything between the battery cable lug and the terminal surface. Overheating of the  
terminal may occur. Do not apply any type of antioxidant paste until after the battery cable wiring  
is tightened. The same applies for all DC connections. Do not over-tighten; observe all  
recommended torque values.  
CAUTION: Reverse Polarity Damage  
Before making the final DC connection or closing the DC breaker or disconnect, check cable  
polarity at both the battery and the inverter/charger. Positive (+) must be connected to positive (+).  
Negative (–) must be connected to negative (–).  
Reverse polarity damage is not covered by warranty.  
Actual cable requirements may vary.  
XW Power Distribution Panel  
(shown with door and front panel removed.)  
B
See Table 2-8 on page 2–11 for  
torque values for the Positive  
and Negative Bus in the XW  
Power Distribution Panel.  
B
C
See Table 2-10 on page 2–11 for  
torque values for the Battery  
Connections to the Positive and  
Negative Bus in the XW Power  
Distribution Panel.  
A
C
A
SeeTable 2-6onpage 2–10  
for torque values for the  
inverter battery connections.  
Torque connections to the battery terminals according  
to the battery manufacturer’s recommendations.  
Figure 2-11 DC Connections to a Single Inverter Using a XW Power Distribution Panel  
975-0239-01-01  
2–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Making AC Connections  
This section describes how to make AC connections between the XW Inverter/Charger  
and the XW Power Distribution Panel (using the pre-installed AC wiring in the XW Power  
Distribution Panel) and between the XW Power Distribution Panel and the AC distribution  
panel, or sub-panel (using wiring provided by the installer). See Appendix C, “Alternate  
System Configurations” if the installation will not be including an XW Power Distribution  
Panel.  
CAUTION: Damage to the Inverter  
The inverter’s AC output must never be wired to the utility or generator output. This will cause  
severe damage to the inverter which is not covered under warranty.  
Do not use a GFCI equipped AC source to power either the grid or generator inputs. The  
AC input filters on the XW may cause nuisance tripping of ground fault protected outputs.  
AC Connections and Communication Ports  
AC Connections  
The AC terminal block includes three terminals each (L1, L2 and Neutral) for AC Grid  
input, AC Generator input, and AC Load connections. The neutrals are connected to each  
other, requiring only one neutral connection when installed with an XW Power  
Distribution Panel. Without the XW Power Distribution Panel, additional neutral  
connections may be required at the input sources.  
Communication  
Ports  
Four communications ports and one AUX Port are located on the bottom of the inverter  
and support the following features.  
The two AC sync ports are used for connecting multiple inverters in parallel.  
The two Xanbus ports are used for network connections between inverters, charge  
controllers, and accessories.  
The AUX port provides 12 Vdc/250 mA output to control a relay, fan, indicator light  
or other device. The auxiliary output can be configured (using a XW System Control  
Panel) to trigger in response to low- or high-battery voltage or high- or low-battery  
temperature. The auxiliary output can also be triggered manually using a XW System  
Control Panel.  
xantrex  
Communications Ports  
Dual-knockouts  
(¾"–1")  
AC sync ports  
(RJ45) (×2)  
Xanbus ports  
(RJ45) (×2)  
AC access  
panel  
AUX port  
AC OUT  
AC IN  
AC IN  
L1  
N
L2 L1  
N
L2 L1  
N
L2  
Bottom View  
GRID  
(AC1)  
GEN  
AC  
AC terminal  
block  
(AC2)  
LOAD  
Hybrid Inverter/Charger  
Figure 2-12 XW Inverter/Charger AC Connections and Communications Ports  
2–16  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
Accessing the AC Terminal Block and AC Ground Bar  
All AC wiring connects to the AC terminal block located on the left-hand side of the  
inverter beneath the AC access cover.  
xantrex  
t
li
l  
/
t
Recessed  
edge  
Hybrid Inverter /Charger  
Remove the two screws on the AC  
access cover and slide it to the left of  
the inverter to remove it.  
When replacing the AC access cover,  
ensure its recessed edge slips inside  
the edge of the front panel.  
AC Terminals  
AC OUT  
AC IN  
N
AC IN  
L1  
N
L2 L1  
L2 L1  
N
L2  
GRID  
(AC1)  
GEN  
(AC2)  
AC  
LOAD  
AC Ground Bar  
Figure 2-13 AC Terminal Block  
975-0239-01-01  
2–17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Grounding the AC System  
Important: Place the Neutral-to-ground bond in a permanently installed AC distribution panel  
that is part of the system. This may be a main panel or a sub-panel.  
See Table 2-4 on page 10 for torque values for the AC terminal and AC Ground bar.  
See Figure 2-8 on page 2–11 for torque requirements for the ground bar in the XW Power  
Distribution Panel.  
Actual ground requirements may vary.  
* Depending on the location of the generator and  
local code requirements, the generator disconnect  
may be located in the power distribution panel.  
In an off-grid installation (i.e., where no utility grid is available), the  
generator can be connected to the breakers provided in the XW Power  
Distribution Panel. No additional breaker is required.  
Figure 2-14 Grounding the AC System using the Distribution Panel  
2–18  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
AC Wiring to the Inverter AC Distribution Panel  
An inverter AC distribution panel (also known as a sub-panel or inverter load panel) and  
AC conduit must be installed before AC wiring is connected to the inverter.  
Install the inverter AC distribution panel and conduit as follows:  
1. Determine the location for the inverter AC distribution panel and install it according to  
the manufacturer’s directions.  
2. Install an AC conduit between the XW Power Distribution Panel and the inverter AC  
distribution panel.  
3. Determine which circuits the inverter will power and install the appropriate circuit  
breakers into the inverter panel.  
4. For On-Grid systems:  
a) Disconnect all power to the main utility panel.  
b) Determine which circuits will be backed by the inverter(s) and remove their wires  
from the main panel.  
c) Reroute these wires to the new inverter subpanel.  
5. Remove unused breakers from utility panel. It is now safe to re-energize the main  
utility panel.  
6. Install a 60-amp maximum (disconnect) main circuit breaker in the inverter panel.  
This will later be wired to the inverter’s output.  
WARNING: Shock Hazard  
Before making any electrical connections, ensure both the AC and DC disconnect devices are in the  
OPEN (disconnect) position.  
CAUTION: Equipment Damage  
Verify that only one neutral/ground bond exists in the system. Having more than one neutral to  
ground bond in a system violates local electrical codes, may create a shock or fire hazard, and may  
cause some sensitive equipment to malfunction.  
CAUTION: Damage to the Inverter  
The inverter’s AC output must never be wired to the utility or generator output. This will cause  
severe damage to the inverter which is not covered under warranty.  
AC Wiring to the XW Power Distribution Panel  
To connect the XW Power Distribution Panel to the inverter:  
Important: The XW Inverter/Charger is provided with fixed disconnect limits for voltage and  
frequency. These limits are fixed when the unit is exporting power to the grid. The unit shall not be  
aggregated such that it can export more than 30 kW on a single point of common connection.  
Important: Both lines of input power must be connected in order for the XW Inverter/Charger to  
operate. For example, L1 and L2 of Grid Input and/or L1 and L2 of Gen Input need to be connected.  
1. Connect the wires labelled “INV1 N-LOAD (SPLIT PHASE)”, “INV1 L1-LOAD,  
and “INV1 L2-LOAD” (from the L1 and L2 terminals on the input (top) side of the  
output breaker and the neutral bus) to the AC Load (L1-LOAD, N-LOAD, L2-LOAD)  
terminals on the inverter. Connect the neutral wire first to the N-LOAD terminal.  
975-0239-01-01  
2–19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
2. Connect the wires labelled “INV1 L1-GRID” and “INV1 L2-GRID” to the inverter. If  
the AC source will be the utility grid, connect to the GRID (AC1) terminals  
(L1-GRID, L2-GRID). If the system will be off-grid and the only AC source will be a  
generator, these wires can be connected to the GEN (AC2) terminals (L1-GEN,  
L2-GEN). No additional neutral connection is needed when using the XW Power  
Distribution Panel. (Additional neutral terminals (N-GRID, N-GEN) are provided on  
the inverter for installations that do not use the XW Power Distribution Panel.)  
3. Connect L1 (from the L1 output Power Distribution Bar) and L2 (from the L2 output  
Power Distribution Bar), Neutral, and Ground to the sub-panel that supplies power to  
inverter loads.  
4. Connect L1 and L2 from the input side of the AC1 Breaker (L1 and L2 Power  
Distribution bars) to the utility grid AC Panel. Connect Neutral from the XW Power  
Distribution Panel to the utility grid AC panel. Connect the ground wire between the  
XW Power Distribution Panel and the utility grid AC panel.  
Power Distribution bars in the XW Power Distribution  
Panel accept up to a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for torque requirements.  
Actual wiring requirements may vary.  
Figure 2-15 Wiring the XW Power Distribution Panel to the Sub-panel or Utility Grid  
2–20  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
Wiring the XW Inverter/Charger to a XW Power Distribution Panel  
Power Distribution bars in the XW Power Distribution  
Panel accept up to a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for torque requirements.  
Actual wiring requirements may vary.  
Figure 2-16 Wiring the Inverter to the XW Power Distribution Panel  
975-0239-01-01  
2–21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Generator Wiring to the XW Inverter/Charger using a XW Power Distribution Panel  
CAUTION: Generators must be hard-wired to  
the XW Power Distribution Panel.  
In an off-grid installation (i.e., where no utility  
grid is available), the generator can be  
connected to the breakers provided in the XW  
Power Distribution Panel. No additional  
breaker is required.  
Actual wiring requirements may vary.  
Figure 2-17 Generator Wiring Using a XW Power Distribution Panel  
2–22  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4: Wiring the Inverter  
AUX Port  
The XW Series has a 12 Vdc auxiliary output that can be configured to trigger in response  
to one of the following battery conditions:  
low battery voltage  
high battery voltage  
low battery temperature  
high battery temperature  
any device fault  
The auxiliary output can also be triggered manually.  
The 12 Vdc output can be used to trigger a relay to disconnect batteries from the inverter/  
charger when battery voltage or temperature are out of the ideal range.  
The auxiliary output is designed to provide the following functions:  
Auxiliary 12 Vdc power supply  
Remote Power Off  
AUX Port  
Figure 2-18 AUX Port Location  
AUX+12V Voltage Supply  
DC voltage is available between JU-1 (AUX +12 V) and JU-3 (AUX-COM, signal return).  
The power available at these terminals is 12 Vdc and maximum current is 0.25 Adc  
(3 watts).  
AUX+12 V and AUX-COM terminals can be used: to power a relay (3 watts maximum).  
Additional fuses are not required, but may be required for some installations.  
AUX +12 V voltage supply can be programmed for different tasks ON and OFF using the  
XW System Control Panel.  
Default status of AUX+12 V is OFF.  
975-0239-01-01  
2–23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
AUX-RPO: User Remote Power Off (RPO)  
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through an  
external switch (normal open contact) will provide the system shut off function if the  
switch is closed.  
The external switch if pressed overrides the control provided from the front panel.  
If the external switch is cleared (not pressed), the system can be enabled back from the  
front panel.  
Select an external switch with normal open contact; consult your local system designer or  
qualified technician for specific installation instructions.  
User Line Wiring  
Use twisted pairs of #24 AWG to #12 AWG for connections. Carefully route the wires  
away from high power load cables to minimize noise effects on signal integrity.  
AUX Port Terminal Assignments  
Table 2-11 User Connector Terminals and Functions  
Pin  
Reference  
Name  
Function  
JU-1  
AUX+12V  
+12 V User Voltage +12 Vdc Voltage source: 0.25 Adc maximum  
Supply  
JU-2  
JU-3  
AUX-RPO  
AUX-COM  
Remote Power Off Remote Power Off Logic Level: Active Low.  
Connecting this signal shuts down system  
operation.  
Common Ground  
Reference  
Return Common Ground Reference for 12V,  
Remote Power Off signals.  
JU-4  
JU-5  
Not Operational Not Operational  
Not Operational Not Operational  
Not Operational  
Not Operational  
2–24  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic Functional Test - Single Inverter  
Basic Functional Test - Single Inverter  
The following steps will complete a basic functional test of the XW Inverter/Charger. If  
any test fails, please refer to the Troubleshooting section in the XW Inverter/Charger  
Operation Guide for assistance.  
Confirm All Connections  
Once the AC and DC wiring have been installed and connected, take a moment to go back  
over all connections and make sure they are secure and have been installed correctly.  
Applying DC Power to the Inverter  
CAUTION: Reverse Polarity Damage  
Before making the final DC connection or closing the DC breaker or disconnect, check cable  
polarity at both the battery and the inverter/charger. Positive (+) must be connected to positive (+).  
Negative (–) must be connected to negative (–).  
Reverse polarity damage is not covered by warranty.  
To apply DC power to the inverter:  
1. Before applying DC power to the inverter, measure the voltage and polarity of the  
cables (measure at the battery side of the disconnect or breaker).  
Important: Voltage should be between 40 to 60 volts for a 48-volt  
system, and 20 to 30 volts for a 24-volt system. If the DC voltage is low,  
the battery bank needs to be charged externally. Charge the battery bank  
and restart the functional test.  
2. Apply battery (DC) power to the inverter by closing the battery bank DC disconnect.  
The inverter will power up, the display will illuminate, but the inverter will remain in  
the Standby Mode (as shown in Figure 2-19).  
Note: If the inverter was  
previously powered up then it will  
power-up in the last operating  
state (Operating or standby)  
All LEDs temporarily illuminate.  
ON/OFF Button  
Figure 2-19 Power-up Display  
975-0239-01-01  
2–25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Enable the Inverter  
CAUTION: Equipment Damage  
Prior to activating the inverter, ensure that all AC loads are disconnected from the output of the  
inverter.  
By default, Invert Mode is enabled and the unit should start inverting upon transitioning  
from Standby Mode. If Invert Mode is disabled, the display will show (---) once out of  
Standby Mode. If the unit powers up in Standby Mode, prese the ON/OFF button  
momentarily to change the mode from Standby to Operating.  
To enable the inverter:  
Press the inverter ON/OFF button and the Equalize button at the same time. “En” is  
briefly displayed on the inverter panel to indicate the inverter is enabled.  
To disable the inverter:  
Press the inverter ON/OFF button and the Equalize button at the same time. “diS” is  
briefly displayed on the inverter panel to indicate the inverter is disabled.  
This display indicates the inverter  
is disabled.  
ON/OFF  
Button  
Equalize  
Button  
Equalize  
Button  
ON/OFF  
Button  
Briefly press the Equalize Button and the ON/OFF Button at the same time  
to enable or disable the Invert Mode.  
All LEDs temporarily illuminate.  
Figure 2-20 Enable the Inverter  
3. Monitor the INVERT (Green kW) LED to confirm which mode the inverter is in:  
LED Off – Invert Mode is disabled. The inverter/Charger is not powering the AC  
loads. However, if good AC is present, it is passed through to the loads.  
One blink/sec – The inverter/charger is in the Search Mode and is looking for an  
AC load greater than the Search Watts setting (default = 25 watts). The Display  
shows Sch (Search) when this mode has been enabled.  
LED On – The inverter/charger is on. The inverter is operating and is able to  
provide power to the AC loads. This is the default mode on initial powerup once  
the unit is taken out of Standby Mode.  
If the inverter is not operating or the INVERT LED (kW) does not illuminate, check all  
connections. Check the inverter’s DC voltage on the positive (+) and negative (–)  
terminals. Check the Fault LED. If the fault LED is illuminated, check for a fault code on  
the information panel. Correct the reported fault if possible and clear the fault. If the DC  
voltage is low, the battery bank needs to be charged externally. Charge the battery bank  
and restart the functional test.  
2–26  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic Functional Test - Single Inverter  
AC Voltage Check  
Important: This test requires the use of a voltmeter.  
To perform an AC voltage check:  
1. With the inverter on (INVERT [green, kW] LED on solid), verify the AC voltage at  
AC Loads block terminal L1-Load to N-Load.  
2. Verify that neutral is bonded to ground in the system by measuring the hot and neutral  
voltages relative to ground. Neutral-to-ground should equal zero (0) volts.  
3. After confirming the correct AC voltage, turn on your AC output breaker and place a  
load on the inverter (plug in a light or other load to an outlet the inverter is powering).  
4. Confirm that the AC load that was just applied works properly.  
AC OUT  
AC IN  
N
AC IN  
L1  
N
L2 L1  
L2 L1  
N
L2  
GRID  
(AC1)  
GEN  
(AC2)  
AC  
LOAD  
Figure 2-21 Checking AC Voltage  
Confirming Battery Charger Operation  
To confirm battery charger operation:  
1. Apply AC from grid or generator, confirm voltage.  
2. Check LEDs (AC1 or AC2) on the front panel. One of them must be illuminated for  
the unit to charge. Check the “A” LED. If the “A” LED is illuminated, the unit is  
charging and the battery current is displayed on the information panel.  
Amp LED  
Figure 2-22 Checking Charging Operation  
Important: Unless the inverter/charger settings have been changed, the inverter will charge as  
if it has a large (> 440 Ah) flooded battery bank (factory default setting). Therefore, ALL systems  
may need to have the battery charging set points “fine tuned” to avoid damage to the batteries.  
This completes the functional test. If all tests pass, the inverter is ready for use. If any of  
the inverter’s internal set points need to be adjusted, consult the configuration chapter of  
the operation guide.  
975-0239-01-01  
2–27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Figure 2-23 Functional Test for Single Inverter Systems  
2–28  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: Installing Additional Inverters  
Step 5: Installing Additional Inverters  
Installation Steps  
To install multiple inverters:  
1. Disconnect all power from the system.  
2. Mount additional inverter(s). See “Step 1: Installing the Mounting Plate” on page 2–4  
and “Step 2: Mounting the Inverter” on page 2–6.  
3. Install the XW Conduit Box. See “Step 3: Mounting the XW Power Distribution Panel  
and XW Conduit Box” on page 2–7.  
4. Install AC sync cable(s) as required. See “Xanbus and AC Sync Cable” on page 2–38.  
5. Install a XW System Control Panel to configure programmable settings and to name  
specific network components (e.g., XW1, XW2 etc.). See “The XW System Control  
Panel” on page 5–2.  
6. Convert the XW Power Distribution Panel to accommodate the extra inverter by  
installing the additional breakers and components. See page 2–30 for instructions on  
converting the XW Power Distribution Panel to a dual-inverter configuration. See  
page 2–34 for converting the XW Power Distribution Panel to a triple-inverter  
configuration.  
7. Attach Bypass interlock plate to distribution panel cover.  
8. Connect DC wiring. See Figure 2-24 on page 2–31 for dual-inverter configurations  
and Figure 2-27 on page 2–35 for triple-inverter configurations.  
9. Connect AC wiring. See Figure 2-26 on page 2–33 for dual-inverter configurations.  
For triple-inverter Configurations, see Figure 2-28, “Triple-Inverter AC Breaker  
Arrangement and Wiring Enlargement with Multiple AC Input Sources” on page 2–36  
or Figure 2-29, “Triple-Inverter AC Breaker Arrangement and Wiring Enlargement  
with a Single AC Input Source” on page 2–37.  
975-0239-01-01  
2–29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Parts List for Dual-Inverter Configurations  
Installing an additional inverter using the power distribution panel requires an XW  
Connection Kit (part number 856-1020), which contains the following components:  
XW Conduit Box  
Three 60 amp, 120/240 VAC, 2-pole, Square-D Type QOU, DIN-rail mount,  
AC breakers for Inverter Input, Output, and Bypass  
Four Power Distribution bars  
Custom Bypass Interlock  
#6 AWG AC wiring to connect the inverter to AC breakers  
GJ250A, 160VDC, 3/8" Stud, DC Breaker with copper bus bar for DC positive  
one pair #4/0 battery cables to connect the inverter to DC breakers  
Xanbus and AC Sync Cable (CAT 5 cable with RJ45 connectors wired to T568A  
standard).  
Miscellaneous bushings  
Important: When installing more than one inverter at a location, a XW  
System Control Panel will be required to give each inverter (as well as other  
Xanbus-enabled devices) a unique name and to modify the factory-installed  
default settings to match and support the installed configuration.  
Converting a Single-Inverter Power Distribution Panel to a Dual-Inverter Power  
Distribution Panel  
Remove upper wire cover and lower wire cover on the XW Power Distribution Panel.  
DC Wiring for a Dual-Inverter System  
1. Remove positive distribution plate attached to bottom terminal on existing DC  
disconnect/breaker.  
2. Install second DC disconnect/breaker (supplied in 865-1020) next to existing DC  
disconnect/breaker.  
3. Replace the factory-installed DC positive bus bar with the larger positive bus bar  
provided in the 865-1020. This larger DC positive bus bar supports up to three  
GJ250 Adc disconnect/breakers.  
4. Connect positive battery cable for second inverter (supplied in 865-1020) to top  
terminal on second DC disconnect/breaker.  
5. Connect negative battery cable for second inverter (supplied in 865-1020) to DC  
negative distribution plate.  
6. Connect positive and negative battery cables to second inverter.  
7. Remove knockout on the lower cover for additional disconnect/breaker to fit through.  
8. Re-install lower wire cover.  
2–30  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: Installing Additional Inverters  
AC Breakers shown in this illustration  
represent the breaker arrangement for a  
single AC source.  
Torque connections to the  
inverter DC terminals to  
10-15 ft/lbs.  
Actual cable requirements may vary.  
Torque connections to the battery  
terminals according to the battery  
manufacturer’s recommendations.  
Figure 2-24 DC Connections to Dual Inverters  
975-0239-01-01  
2–31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
AC Wiring for a Dual-Inverter System  
1. Disconnect the AC wires (from the utility grid or generator and to the sub-panel) and  
remove the factory-installed distribution bars connected to top and bottom terminals  
on the AC breakers.  
2. Remove bypass interlock bracket.  
3. Disconnect INV1 AC LOAD (INV1 L1-LOAD, INV1 L2-LOAD) wires from top  
terminals on right-hand side breaker.  
4. Add three additional dual-pole AC breakers (supplied in 865-1020) next to the  
existing three dual-pole AC breakers.  
5. Attach the four distribution bars (supplied in 865-1020) to top and bottom of AC  
breakers as shown in dual-inverter system wiring diagrams.  
6. Connect grid wiring and loads/subpanel wiring to the new distribution bars as shown  
in Figure 2-26.  
7. Connect INV1 LOAD (INV1 L1-LOAD, INV1 L2-LOAD), INV2 LOAD (INV2  
L1-LOAD, INV2 L2-LOAD), and INV2 GRID (INV2 L1-GRID, INV2 L2-GRID)  
wires to AC breakers as shown in Figure 2-26.  
8. Connect neutral (INV2 N-LOAD (SPLIT-PHASE)) and ground (INV2 GROUND)  
wiring as shown in dual-inverter system wiring diagrams.  
9. Connect wiring at the inverter/chargers as shown in Figure 2-26.  
10. Remove the knockouts on upper wire cover for additional breakers to fit through.  
11. Re-install upper wire cover. Relabel the AC breakers with the appropriate labels  
provided with the XW Power Distribution Panel.  
12. Install bypass interlock plate with provided screws and nylon shoulder washers  
(supplied in 865-1020).  
FROM MAIN AC  
DISTRIBUTION PANEL  
FROM GENERATOR  
DISCONNECT  
Power Distribution bars in the XW  
Power Distribution Panel accept up to  
a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for  
torque requirements.  
INV 1 IN  
(GEN)  
INV 2 IN  
(GEN)  
INV 1 IN  
(GRID)  
INV 2 IN  
(GRID)  
GRID  
BYPASS  
GRID  
BYPASS  
INV1 OUT  
(AC LOADS)  
INV 1 OUT  
(AC LOADS)  
TO INVERTER AC  
DISTRIBUTION PANEL  
Figure 2-25 Dual Inverter AC Breaker Arrangement and Wiring Enlargement with Multiple AC Input Sources  
2–32 975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: Installing Additional Inverters  
Power Distribution bars in the XW Power Distribution  
Panel accept up to a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for torque requirements.  
Figure 2-26 AC Wiring for Dual-Inverter Systems  
975-0239-01-01  
2–33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Parts List for a Triple-Inverter Configuration  
1 x XW Power Distribution Panel (PDP) and Accessory kit (mounts to first unit).  
1 x 865-1020 PDP extension kit for second unit.  
The following items are required for the third inverter (furthest from PDP) and should be  
sourced and prepared prior to the installation. (Note that all wiring will have to be custom  
cut to fit the third unit. Wiring supplied with the extension kit is intended for a second  
inverter in a two inverter system).  
1 x 865-1020 PDP extension kit.  
2 x AC Distribution Bars (100-0661-01-01).  
2.2 m (87”) x #6 AWG, 600 V, 105°C stranded white wire for neutral  
2.2 m (87”) x #6 AWG, 600 V, 105°C Black stranded wire for L1 Grid (AC1).  
2.2 m (87”) x #6 AWG, 600 V, 105°C Red stranded wire for L2 Grid (AC1).  
2.3m (91”) x #6 AWG, 600 V, 105°C Black stranded wire for L1 Gen (AC2).  
2.3 m (91”) x #6 AWG, 600 V, 105°C Red stranded wire for L2 Gen (AC2).  
2.4 m (95”) x #6 AWG, 600 V, 105°C Black stranded wire for L1 Gen (AC Load).  
2.4 m (95”) x #6 AWG, 600 V, 105°C Red stranded wire for L2 Gen (AC Load).  
1.6m (62”) #4/0 AGW, 105°C, Red stranded with #4/0 x 3/8 lugs crimped at each end  
for the positive battery cable.  
1.6m (62”) #4/0 AGW, 105°C, Black stranded with #4/0 x 3/8 lugs crimped at each  
end for the negative battery cable.  
External Bypass Switch - The XW Power Distribution Panel does not have enough  
breaker locations to accommodate bypass breakers in a triple-inverter system.  
Therefore, an external Bypass Switch may be needed. See Figure 2-30 on page 2–37  
for an illustration of how to wire an External Bypass Switch.  
Converting a Single-Inverter Power Distribution Panel to a Triple-Inverter Power  
Distribution Panel  
Remove upper wire cover and lower wire cover on the XW Power Distribution Panel.  
DC Wiring for a Triple-Inverter System  
1. Install all three DC disconnect/breakers (two supplied in 865-1020 and one with PDP).  
2. Install larger positive distribution plate (supplied in 865-1020).  
3. Connect negative battery cable for first inverter (supplied with PDP) to DC negative  
distribution plate.  
4. Connect negative battery cable for second inverter (supplied in 865-1020) to DC  
negative distribution plate.  
5. Connect negative battery cable for second inverter (custom, see material list) to DC  
negative distribution plate.  
2–34  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: Installing Additional Inverters  
6. Connect positive battery cable for first inverter (supplied with PDP) to top terminal on  
first DC disconnect/breaker.  
7. Connect positive battery cable for second inverter (supplied in 865-1020) to top  
terminal on second DC disconnect/breaker.  
8. Connect positive battery cable for third inverter (custom, see material list) to top  
terminal on third DC disconnect/breaker.  
9. Connect positive and negative battery cables to first inverter.  
10. Connect positive and negative battery cables to second inverter.  
11. Connect positive and negative battery cables to third inverter.  
Power Distribution bars in the XW Power Distribution  
Panel accept up to a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for torque requirements.  
AC Breakers shown in this  
illustration represent the breaker  
arrangement for multiple AC  
source.  
Torque connections to the  
inverter DC terminals to  
10-15 ft/lbs.  
Actual cable requirements may vary.  
Torque connections to the battery  
terminals according to the battery  
manufacturer’s recommendations.  
Figure 2-27 DC Connections for a Triple-Inverter System  
975-0239-01-01  
2–35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
AC Wiring for a Triple-Inverter System  
1. Prepare power distribution bars (supplied in 865-1020) by cutting away one of the  
four tabs, only three tabs per power distribution bar are required in a three inverter  
system. A total of 6 distribution bars should be prepared.  
2. Mount the nine breakers on the din rail and install power distribution bars as follows:  
a) Two distribution bars, L1 and L2 at the input (top) terminals of the INV1, INV2  
and INV3 Grid breakers.  
b) Two distribution bars, L1 and L2 at the input (top) terminals of the INV1, INV2  
and INV3 Gen breakers.  
c) Two distribution bars, L1 and L2 at the output (bottom) terminals of the INV1,  
INV2 and INV3 AC Load breakers.  
3. Connect L1 and L2, AC wiring from each INV Grid breaker to the corresponding AC  
Input (AC1) terminal on each of the three inverters.  
4. Connect L1 and L2, AC wiring from each INV Gen breaker to the corresponding AC  
Input (AC2) terminal on each of the three inverters.  
5. Connect L1 and L2, AC wiring from each INV AC Load terminal from each of the  
three inverters, to the corresponding AC INV Out breaker terminal in the PDP.  
6. Connect L1 and L2, AC Load wiring to the INV Out (AC Load) power distribution  
bar.  
7. Connect L1 and L2, AC wiring from the Generator disconnect to the Gen breaker  
power distribution bars.  
8. Connect L1 and L2, AC wiring from the Utility Grid distribution panel to the Grid  
breaker power distribution bars.  
9. Connect neutral wiring from INV1 (supplied with PDP), INV2 (supplied in 865-1050)  
and INV3 (custom, see material list) to the neutral distribution bar in the PDP.  
10. Connect ground wiring from INV1 (supplied with PDP), INV2 (supplied in 865-1050)  
and INV3 (supplied in 865-1050) to the ground distribution bar in the PDP.  
Power Distribution bars in the XW  
Power Distribution Panel accept up  
to a #2/0 AWG cable (maximum).  
See Figure 2-9 on page 2–11 for  
torque requirements.  
FROM AC DISTRIBUTION  
PANEL OR TRANSFER SWITCH  
FROM GENERATOR  
DISCONNECT  
INV 1 IN  
(GRID)  
INV 2 IN  
(GRID)  
INV 1 IN  
(GEN)  
INV 2 IN  
(GEN)  
INV 3 IN  
(GRID)  
INV 3 IN  
(GEN)  
INV 1 OUT  
(AC LOADS) (AC LOADS)  
INV2 OUT  
INV3 OUT  
(AC LOADS)  
TO INVERTER AC DISTRIBUTION  
PANEL OR TRANSFER SWITCH  
Figure 2-28 Triple-Inverter AC Breaker Arrangement and Wiring Enlargement with Multiple AC Input Sources  
2–36 975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5: Installing Additional Inverters  
Power Distribution bars in the  
XW Power Distribution Panel  
accept up to a #2/0 AWG cable  
(maximum).  
FROM AC SOURCE DISCONNECT  
OR TRANSFER SWITCH  
See Figure 2-9 on page 2–11 for  
torque requirements.  
INV 3 OUT  
(AC LOADS)  
INV1 IN  
(GRID OR GEN)  
INV3 IN  
INV2 IN  
(GRID OR GEN) (GRID OR GEN)  
INV 1 OUT  
(AC LOADS) (AC LOADS)  
INV 2 OUT  
TO INVERTER AC DISTRIBUTION  
PANEL OR TRANSFER SWITCH  
Figure 2-29 Triple-Inverter AC Breaker Arrangement and Wiring Enlargement with a Single AC Input Source  
Actual wiring requirements  
may vary.  
Figure 2-30 Wiring an External Bypass Switch for a Triple-Inverter Configuration  
975-0239-01-01  
2–37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Xanbus and AC Sync Cable  
A Xanbus and AC sync cable is required for multi-unit installation. The AC sync cable  
connects each inverter, and provides the necessary communication and control between  
multiple units.  
Install these cables, routing it through the XW Conduit Box raceway, prior to making the  
AC and DC wiring connections. See Figure 2-31.  
To install the AC Sync and Xanbus cables between inverters:  
Remove the two  
3
Route the cable as shown. Route any additional  
communication cables through the raceways.  
Replace the wiring raceways, ensuring not to pinch  
the cables. Secure the raceways to the XW Conduit  
Box with the screw that was removed earlier.  
1
factory-installed raceways  
for the communication  
cabling by removing the  
screw holding each  
raceway in place.  
IMPORTANT:  
In a 2-inverter system, install an AC Sync Cable from  
INV1 to INV2.  
Insert the RJ45 jack  
2
on the cable into  
one of the two AC  
Sync ports.  
In a 3-inverter system, “daisy-chain” an AC Sync  
Cable from INV1 to INV2 and from INV2 to INV3.  
Do NOT install terminators in an AC Sync Port.  
Figure 2-31 Installing the AC Sync Cable  
2–38  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic Functional Test - Multiple Inverters  
Basic Functional Test - Multiple Inverters  
The following steps will complete a basic functional test of multiple XW Inverter/  
Chargers. If any test fails, please refer to the Troubleshooting section in the XW Inverter/  
Charger Operation Guide for assistance.  
To perform a functional test on multiple inverters:  
1. Check/verify all wiring and cable connections.  
2. Measure DC voltage at the DC terminals on the inverter and confirm its within range  
and has correct polarity. The acceptable range is >20 Vdc for 24 V system or >40 Vdc  
for 48-V Systems.  
3. Switch INV1 DISCONNECT to ON position.  
4. Check inverter display for startup self-test during which all LED's will flash  
momentarily. Once self-test is complete, inverter will display "Stb". (The Fault/  
Warning LED may flash for a few seconds but eventually will turn off. If Fault/  
Warning LED persists, check to ensure battery temperature sensor is connected. Also,  
if the inverter has been pre-configured, it may go straight into normal operating  
mode.)  
5. Using the XW System Control Panel, set First (Master) Inverter Device Number  
a) Go to the inverter’s Advanced Settings menu by pressing Down arrow + Enter  
from System Status screen and then simultaneously pressing Enter + Up arrow +  
Down arrow.  
b) Select Multi Unit Config menu.  
c) Change Dev Number from “00” to “01”. The inverter will now appear as  
XW6048-01 in the device list.  
d) Press Exit to go back to the System Status screen.  
6. Switch INV2 DISCONNECT to ON position.  
7. Check inverter display for startup self-test during which all LED's will flash  
momentarily. Once self-test is complete, inverter will display "Stb". (If the inverter has  
been pre-configured, it may go straight into normal operating mode or display F66  
warning.)  
8. Using the XW System Control Panel, set Second (Slave) Inverter Device Number and  
Inverter Mode.  
a) Select new inverter XW6048-00 in the device list.  
b) Go to the inverter’s Advanced Settings>Multi-Unit Config menu.  
c) Change Dev Number from “00” to “02” (or the next number that hasn’t been  
used). The inverter will now appear as XW6048-02 in the device list.  
d) Change Invtr Mode from “SplitPhMaster” to “SplitPhSlave”.  
e) Press Exit until you see the System Status screen.  
9. Check for faults. If fault condition(s) exist, correct and restart Functional Test.  
10. If a third inverter is installed, repeat steps to configure it as a Slave.  
11. Using the XW System Control Panel, enable the System  
a) Go to System Settings menu  
b) Change System Mode to “Operating”  
c) Press Exit until you see the System Status screen.  
975-0239-01-01  
2–39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
12. Confirm Master inverter displays “0.00” and Slave(s) displays “---” on their front  
panels.  
13. Check for faults. If fault condition(s) exist, correct and restart Functional Test.  
14. Check voltage at AC LOAD terminals of the Master Inverter.  
15. Switch the AC Load breakers ON.  
16. Confirm operation of connected AC loads.  
17. Disconnect AC LOAD breakers.  
18. Using the XW System Control Panel, reduce Maximum Charge Rate.  
a) From System Status screen, go to System Settings and enable Cascading (if not  
enabled). With Cascading enabled, a change to a setting in one inverter will auto-  
matically ripple through to the other inverter(s) in the system.  
b) Go to Advanced Settings>Charger Settings in one of the inverters.  
c) Set Max Chg Rate to 10%.  
d) Press Exit until you see the System Status screen.  
19. Switch AC Input breakers ON. Note - all inverters in the system must be connected to  
the same AC Input source before they will qualify the source.  
20. Confirm both inverters start charging. Note -- With the Max Chg Rate set to 10% the  
maximum charge rate is limited to 10 A on each inverter. Depending on the battery  
bank’s state-of-charge, the output from one or more inverters may quickly drop to  
zero. This is considered normal operation.  
21. Check for faults. If fault condition(s) exist, correct and restart Functional Test.  
If the Inverters pass the Functional Test, proceed to Commissioning procedure as defined  
in XW Inverter/Charger Operation Guide.  
2–40  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic Functional Test - Multiple Inverters  
Figure 2-32 Functional Test for Multiple Inverters - Page 1 of 2  
975-0239-01-01  
2–41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter/Charger Installation  
Figure 2-33 Functional Test for Multiple Inverters - Page 2 of 2  
2–42  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network  
Installation  
3
Chapter 3, “Xanbus Network Installation” provides detailed information for  
planning and installing the components necessary for network  
communication on a Xanbus system.  
For this Topic  
See....  
“Xanbus-enabled Devices”  
“The Xanbus System”  
“Installing the Network”  
page 3–2  
page 3–2  
page 3–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network Installation  
Xanbus-enabled Devices  
The Xanbus™-enabled designation means that the product works on a Xanbus network.  
Xanbus-enabled products are:  
Easy to use. The Xanbus network simplifies operation and automates routine tasks.  
Reliable. Software control eliminates errors due to analog signalling.  
Accurate. Digital information is less susceptible to interference and line loss.  
The Xanbus System  
What is a network?  
A network is a collection of devices that perform individual functions, but also  
communicate and interact with the other devices. The network capability of the XW  
Power System provides a robust, integrated product solution that simplifies and automates  
the installation, configuration, control, monitoring, and integration of devices that deliver  
and distribute AC or DC power.  
Network  
components  
Each device is integrated into the network using cables, network connectors, and  
terminators. An example of a network-managed power system is shown in Figure 3-1.  
Figure 3-1 Network-Managed Power System  
Network  
The network can be installed in one of two configurations: as a multi-drop backbone (see  
configurations  
Figure 3-5) or as a daisy chain (see Figure 3-6).  
3–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Xanbus System  
Network Components  
A Xanbus network consists of the following components:  
Xanbus-enabled devices—these include the XW System Control Panel, the XW  
Inverter/Charger, XW Automatic Generator Start, and XW Charge Controller. The  
maximum number of Xanbus devices connected to a single Xanbus network should  
not exceed eight devices.  
Xanbus power supply—the network must have at least one device with a power supply  
to run the network. The total network current supplied by all the power-sourcing  
devices must be greater than or equal to the total current drawn by the power  
consuming devices. The power supply must be capable of providing 15 Vdc/200 mA  
to each device. The XW Inverter/Charger can provide sufficient network power.  
For example, in a system with an inverter/charger, a XW System Control Panel and an  
Automatic Generator Start, the inverter/charger is a power-sourcing device capable of  
providing 800 mA at 15 Vdc while the two other devices each consume a maximum of  
200 mA for a total maximum consumption of 400 mA. In this example, the network is  
properly configured from a power perspective because the power source is capable of  
providing more current than is needed: 800 mA > 400 mA.  
Important: See the specifications for each Xanbus device to determine how much power each  
device consumes or supplies.  
Xanbus cables—each Xanbus-enabled device is connected by a Category 5 (CAT 5 or  
CAT 5e) cable, a standard cable available from Xantrex or any computer supply store.  
The cable consists of eight conductors in four twisted pairs with an RJ45 modular  
connector wired to the T568A standard.  
CAUTION: Equipment Damage  
Do not use crossover cable.  
Table 3-1 contains the arrangements of wire colors to pin numbers for the T568A  
standard.  
Table 3-1 T568A Standard Wiring  
Pin Number Conductor Name CAT 5 Cable Insulation Color CAT 5e Cable Insulation Color  
1
2
3
4
5
6
7
8
NET_S  
NET_S  
NET_C  
CAN_L  
CAN_H  
NET_C  
NET_S  
NET_C  
White/Green  
Green  
White/Orange  
Orange  
White/Orange  
Blue  
White/Green  
Blue  
White/Blue  
Orange  
White/Blue  
Green  
White/Brown  
Brown  
White/Brown  
Brown  
975-0239-01-01  
3–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network Installation  
Pins:  
8 7 6 5 4 3 2 1  
Figure 3-2 Xanbus Cable and RJ45 Connector Pin Numbers  
Network terminators (Figure 3-3)—the Xanbus network must be properly terminated  
at each end with male or female network terminators to ensure the communication  
signal quality on the network. If the network is not properly terminated, signal quality  
is degraded and performance on the network is reduced. Permanent configuration  
without terminators is not supported by Xantrex. The XW Series and other  
Xanbus-enabled devices ship with one male terminator already installed. Depending  
on your network layout, this terminator may need to be removed and inserted into  
another device elsewhere in the network.  
Female network terminator  
Male network terminator  
Figure 3-3 Network Terminators  
Network connectors—The three-way connector houses three RJ45 inputs that provide  
a device connection point on a multi-drop backbone layout (see “Multi-Drop  
Backbone Layout” on page 3–5). All three inputs are wired identically and can accept  
either Xanbus cables or terminators. One input is available for connecting to a  
Xanbus-enabled device. The remaining inputs are reserved for connection to other  
network connectors, a Xanbus cable terminated with a female terminator, or a male  
terminator.  
The network connector is mounted to a bulkhead or a wall, as shown in Figure 3-4.  
To network connector  
To device  
To network connector  
or teminator  
Figure 3-4 3-Way Network Connector (sample configuration)  
3–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Xanbus System  
Ordering Network Components  
Table 3-2 provides a partial list of network components and part numbers. Ready-made  
cables are available in standard lengths from 3 feet to 75 feet.  
For the most up-to-date list, call an authorized Xantrex dealer or visit the Outlet Store at  
www.xantrex.com.  
Table 3-2 Xanbus Network Components and Part Numbers  
Network Component  
Part Number  
809-0901  
809-0905  
809-0903  
809-0935  
809-0936  
809-0937  
809-0938  
809-0939  
809-0940  
809-0941  
809-0942  
Network termination — Male (2 per pack)  
Network termination — Female (2 per pack)  
3-way network connector  
Network cable 3 ft. (0.9 m)  
Network cable 5 feet (1.5 m)  
Network cable 7 feet (2.0 m)  
Network cable 10 feet (3.0 m)  
Network cable 14 feet (4.3 m)  
Network cable 25 feet (7.6 m)  
Network cable 50 feet (15.2 m)  
Network cable 75 feet (22.9 m)  
Network Layouts  
Xanbus-enabled devices can be connected in one of two Xanbus network layouts:  
multi-drop backbone or daisy chain. Each network layout has advantages and  
disadvantages, depending on the application and/or environment. It is up to the installer or  
system designer to decide which layout is best for the installation.  
Important: Do not mix the two types of network layouts. Mixed configurations are not  
supported by Xantrex.  
Multi-Drop Backbone Layout  
In a multi-drop backbone layout, each Xanbus-enabled device on the network is connected  
by a drop cable to the network bus or backbone with a network connector, as shown in  
Figure 3-5.  
Terminators are required at both ends of the multi-drop backbone cable, as shown in  
Figure 3-5. Therefore, the Xanbus-enabled devices do not require their own termination.  
With only one terminator, the signal quality is degraded and performance on the network is  
reduced. Permanent configuration with only one terminator is not supported by Xantrex.  
If cables are placed at the end of the network, female terminators are required. Otherwise,  
male terminators can be inserted directly into the open jack of each network connector at  
the end of the network.  
Advantages In this layout, Xanbus-enabled devices can be removed or replaced while  
still keeping the network operating.  
Disadvantage The main disadvantage of this layout is the cost of the network  
connectors (a daisy chain layout uses no network connectors). Each device in this layout  
requires its own network connector.  
975-0239-01-01  
3–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network Installation  
3-way  
connectors  
Terminate  
network at  
each end  
Terminate  
network at  
each end  
with a female  
terminator.  
with a female  
terminator.  
Figure 3-5 Multi-Drop Backbone Layout  
Daisy Chain Layout  
In a daisy chain layout, each device on the network is linked with separate lengths of  
Xanbus cable, as shown in Figure 3-6. This layout does not require network connectors.  
As in the multi-drop backbone layout, two terminators are required to ensure the  
communication signal quality on the network. The Xanbus-enabled devices at each end of  
the chain must have a male terminator inserted into their open network ports.  
Advantage The advantage of this layout is that it is less expensive to install because  
network connectors are not required.  
Disadvantage The disadvantage of the daisy chain layout is that Xanbus-enabled  
devices cannot be removed from the network without interrupting the network. To make  
the network function after removing a device, you must connect the Xanbus-enabled  
devices on either side of the missing device to each other or replace the device.  
Male Terminator  
Terminate the network at each end.  
Male Terminator  
Figure 3-6 Daisy Chain Network Layout  
3–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Network  
Installing the Network  
Important: Do not mix the two types of network layouts. Mixed configurations are not  
supported by Xantrex.  
Important: Installing and replacing Xanbus-enabled devices in an existing system must be  
performed with the XW Power System in Standby mode. For more information about Standby  
mode, see the XW System Control Panel Owner’s Guide.  
Before You Begin the Installation  
Read the entire section before installing the network. It’s important to plan the  
installation from beginning to end.  
Assemble all the tools and materials required for the installation.  
Installation Tools and Materials  
Tools  
The following tools may be required to install the Xanbus cables.  
Phillips screwdriver, appropriately sized  
Drill and 1/8" bit  
Materials  
The following materials may be required to complete your installation.  
CAT 5 or CAT 5e cables (available from Xantrex or computer supply stores)  
Network connectors, if installing multi-drop backbone layout  
# 6 screws, 2 per each network connector installed  
Terminators  
Guidelines for Routing the Xanbus Cables  
WARNING: Shock hazard  
Do not route the Xanbus cables in the same conduit or panel as the AC and DC power cabling.  
:
To ensure maximum performance of your network, follow these guidelines when routing  
the Xanbus cables.  
Route the cables away from sharp edges that might damage the insulation. Avoid sharp  
bends in the cable—no less than a 4-inch (100 mm) radius.  
Allow at least 2 ¼ inches (57 mm) of space behind the wall to accommodate the depth  
of the unit and allow room for the cables to bend.  
Allow for some slack in the cable tension.  
Keep the alignment of wire pairs inside the sheath as straight as possible.  
Allow separation between data and power cables (data cables should only cross a  
power cable at right angles).  
Do not staple the cable with metal cable staples. Use appropriate hardware fasteners to  
avoid damage to the cable.  
Support horizontal cables using J hooks or cable trays.  
975-0239-01-01  
3–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network Installation  
The total length of the network, including all connected Xanbus-enabled devices and the  
XW Series, cannot exceed 130 feet (40 m). See Table 3-3.  
Table 3-3 Minimum and Maximum Cable Length  
Cable Length  
Minimum  
Maximum  
Backbone or daisy chain  
4 inches (10 cm) 130 feet (40 meters)  
Total backbone length or daisy chain 4 inches (10 cm) 130 feet (40 meters)  
Drop cable on backbone  
4 inches (10 cm) 10 feet (3 meters)  
Mounting a Network Connector  
To mount a network connector:  
1. Select an appropriate location with the connector in the recommended mounting  
orientation, as shown in Figure 3-7.  
Figure 3-7 Recommended Mounting Orientation for Network Connector  
2. Mark the position of the mounting screws.  
3. Pilot drill the two mounting holes.  
4. Fasten the network connector to the mounting surface with two #6 screws.  
3–8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Network  
Installing Xanbus-Enabled Devices  
If you are installing a Xanbus-enabled device on an existing Xanbus System, put the  
system in Standby mode using the System Settings menu on the XW System Control  
Panel.  
CAUTION: Equipment Damage  
Connect only to other Xanbus compatible devices.  
Although the cabling and connectors used in this network system are the same as ethernet  
connectors, this network is not an ethernet system. Equipment damage may result from  
attempting to connect Xanbus to different systems.  
Important: Mount cables and network connectors in a dry location.  
To install the Xanbus-enabled devices:  
1. Determine and prepare the location for each device. Refer to the installation procedure  
for each device elsewhere in this manual.  
2. Determine and measure the required cable length, taking into consideration your  
network layout, the routing, and strain relief requirements.  
Do not exceed the total recommended cable length of 130 feet (40 meters).  
3. Mount the devices according to the installation procedure elsewhere in this guide.  
4. Use an appropriate length of Xanbus cable to connect each device and (if used) 3-way  
network connector.  
5. Terminate the Xanbus network according to “Completing the Multi-Drop Backbone  
Layout” on page 3–9 or “Completing the Daisy Chain Layout” on page 3–10.  
Completing the Multi-Drop Backbone Layout  
To complete the multi-drop backbone layout:  
Attach a female terminator to the backbone cable at each end of the network (see  
Figure 3-8)  
Or  
Insert a male terminator into the open jack of the network connector at each end of the  
network (see Figure 3-8).  
Attach femaleterminator to  
end of backbone cable.  
To device  
To previous  
connector  
Insert male terminator into  
open jack of connector.  
Figure 3-8 Options for Completing a Multi-Drop Backbone Layout  
975-0239-01-01  
3–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xanbus Network Installation  
Completing the Daisy Chain Layout  
To complete the daisy chain layout:  
Insert a male terminator into the open network port of the Xanbus-enabled device at  
each end of the network. See Figure 3-9.  
Figure 3-9 Completing a Daisy-Chain Layout  
CAUTION: Unpredictable device behavior  
After connecting the Xanbus-enabled devices and terminating the network, do not plug terminators  
or other cables into any remaining open network ports on any Xanbus-enabled devices.  
Do not connect one end of the network to the other to make a ring.  
3–10  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller  
Installation  
4
Chapter 4, “XW Solar Charge Controller Installation” describes how to  
mount and connect the XW Charge Controller as part of the XW System.  
For this Topic  
See....  
“PV Array Requirements”  
“Mounting”  
page 4–2  
page 4–3  
page 4–8  
page 4–9  
page 4–14  
“Grounding”  
“Wiring”  
“Commissioning”  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Installing the Charge Controller  
This chapter describes installing the XW Solar Charge Controller with the XW Power  
System, including the power distribution panel. For stand-alone installation, see the XW  
Solar Charge Controller Owner’s Guide.  
PV Array Requirements  
Each Charge Controller must be connected to its own PV array. For optimum  
performance, each individual array must be composed of the same type of solar panel,  
with the same Voc and Vmp specifications.  
Important: The following information provides only general guidelines. The installation and  
rated performance of your PV array is subject to inspection and approval by the authority having  
jurisdiction.  
Array Size  
For PV array sizing guidelines, use the XW Solar Charge Controller PV array sizing tool  
accessible from www.xantrex.com/support.  
Although the Solar Charge Controller can harvest a maximum of 3500 W, the PV array  
size can be as large as 6720 W (based on 48 A × 140 Vdc = W).  
Array Voltage  
CAUTION; Equipment Damage  
The PV array voltage must never exceed 150 Voc (open circuit voltage) under  
any conditions.  
The maximum PV array voltage for XW Solar Charge Controller MPPT operation is  
140 Vdc.  
When calculating PV array size for the XW Solar Charge Controller, consider the  
expected Voc of the array under all possible conditions. Panel voltage increases with  
decreasing temperature. The array needs to be sized so that 150 Vdc does not occur, even  
at the lowest expected panel temperature during open circuit. The panel manufacturer  
provides a Voc rating per panel, but it is usually rated at 25 °C (77 °F).  
Array Current  
Important: The I (short circuit current) rating of the array must not exceed  
sc  
the 60 A input current rating of the XW Solar Charge Controller at any time.  
Panels rated up to 48 A at 25 °C (77 °F) are recommended to allow for increases in Isc at  
low panel temperatures and at solar noon. Ensure that the Isc rating under all conditions  
does not exceed 60 A. A factor of 1.25 is applied to the rated Isc at 25 °C (77 °F) when the  
panel is colder than -21 °C (70 °F).  
4–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
MPPT Voltage Range  
The XW Solar Charge Controller maximum power point tracking algorithm maximizes the  
output power of PV arrays as long as the operating voltage is within the MPPT operational  
window. Ensure that the PV array used in the system operates within the MPPT  
operational window.  
Effects of array voltages outside of the MPPT operational window are shown in Table 4-1.  
Table 4-1 MPPT Operational Window  
XW Solar Charge  
Voltage  
< Batt  
Effect of Array Voltage  
Controller Mode  
V
Charge Controller not operating.  
Low Light  
oc  
nom  
(system battery voltage)  
V
= Batt  
to 120 Vdc Maximum harvest of solar energy.  
Charging  
MPP  
nom  
(MPPT window)  
120 Vdc < V  
< 140 Vdc Charge Controller reduces the output  
current limit to protect the unit from voltage  
spikes.  
Thermal Derating  
MPP  
V
> 140 Vdc  
Charge Controller shuts down. Unit may be Over-voltage fault.  
MPP  
damaged if V > 150 V.  
(or V > 140 Vdc)  
oc  
oc  
Mounting  
The instructions in this section apply to an installation including the power distribution  
panel. Installation procedures will vary according to your specific application. For special  
applications, consult a qualified electrician or your Xantrex Certified Dealer.  
Important: Installations must be compliant with all local electrical codes. Installation of this  
equipment should only be performed by a qualified electrician or by a Certified Renewable Energy  
(RE) System installer.  
Choosing a Location  
The XW Solar Charge Controller is designed to be mounted vertically to the side or the top  
of the power distribution panel.  
The XW Solar Charge Controller must be installed indoors in a dry, protected location  
away from flammable materials, sources of high temperature, moisture, and vibration, and  
direct sunlight. The location must also be sheltered from direct sunlight, rain, snow, and  
wind-blown debris.  
CAUTION: Equipment Damage  
Never install the XW Solar Charge Controller where it is exposed to salt water spray. Exposure to  
salt water will void the warranty and may cause a malfunction or a shock hazard.  
975-0239-01-01  
4–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
WARNING: Explosion/Corrosion Hazard  
To reduce the risk of fire or explosion, do not install the XW Solar Charge Controller in sealed  
compartments containing batteries or in locations that require ignition-protected equipment.  
To reduce the risk of corrosion from hydrogen-sulfide gas vented by batteries, do not install the XW  
Solar Charge Controller in sealed compartments containing batteries.  
If using “sealed” batteries, the controller can be mounted in the same enclosure as long as  
it is adequately ventilated.  
For optimal and safe operation, ensure there is adequate clearance around the XW Solar  
Charge Controller. See Table 4-2. If clearances are reduced below these minimums, rated  
performance may not be achieved.  
Table 4-2 Minimum Clearance Requirements  
Location Minimum Clearance  
Above  
6 inches (150 mm) When units are mounted to the side of the power distribution  
panel in a vertical stack, the topmost unit must maintain the minimum clearance to  
the nearest surface.  
In front  
Sufficient room to allow for easy access to read the display, to prevent accidental  
contact with the heat sink, and to perform maintenance.  
On sides 6 inches (150 mm) on at least one side of the overall assembly. A maximum of two  
nits can be mounted side by side or side mounted against the power distribution panel.  
u
In both configurations, the minimum clearance around the outermost unit must be  
maintained.  
6 inches (150 mm) on top and side(s)  
Figure 4-1 Minimum Clearance Requirements  
4–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Removing the Wiring Terminals Cover  
Before mounting, you must remove the wiring terminals cover to access the mounting  
holes and the wiring terminals. The wiring terminals cover is secured with two Phillips  
#8-32 × 2 ½-inch screws on the front cover of the unit. See Figure 4-2.  
xantrex  
Remove screws to access  
the field-wiring terminals.  
Figure 4-2 Removing the Wiring Terminals Cover  
Removing Knockouts  
Six dual and two single knockouts are provided for routing battery, PV array, BTS, and  
network cables into the XW Solar Charge Controller. Bushings or conduits must be used  
to protect the wiring from damage from rough edges around the knockout holes.  
Keyhole slot for wall mounting  
Side screws for power distribution  
panel mounting  
2 7/8"  
(73 mm)  
12 ¾"  
(
323 mm)  
11"  
(280 mm)  
14 ½"  
(368 mm)  
Additional  
mounting holes  
¼"  
(6.35 mm)  
2 3/8"  
(60 mm)  
2 1/16"  
(53 mm)  
4 5/8"  
(118 mm)  
1"  
(25.4 mm)  
9/16"  
(14 mm)  
5 ¾"  
(146 mm)  
5 7/16"  
(138 mm)  
Figure 4-3 Dimensions and Knockout Locations  
975-0239-01-01  
4–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Single knockouts intended  
for BTS and network cables  
DUAL KNOCKOUT  
34.52 (1 3/16) & 27.78 (1 1/16)  
2 PL  
DUAL KNOCKOUT  
34.52 (1 3/16) & 27.78 (1 1/16)  
2 PL  
KNOCKOUT  
27.78 (1 1/16)  
KNOCKOUT  
27.78 (1 1/16)  
31.50 (1 ¼)  
25.9 (1) 26.47 (1)  
26.47  
(1)  
DUAL KNOCKOUT  
34.52 (1 3/16) & 27.78 (1 1/16)  
20.20  
(¾)  
50.80 (2)  
50.00 (2)  
25.0 (1)  
50.00 (2)  
50.80 (2)  
Figure 4-4 Knockout Dimensions  
Mounting the Controller  
The XW Solar Charge Controller can be mounted to either the side or the top of the power  
distribution panel. The power distribution panel has keyhole slots and screw holes for side  
mounting, and two pairs of conduit holes for top mounting the XW Solar Charge  
Controller.  
To mount the XW Solar Charge Controller to the side of the power distribution  
panel:  
1. Back out the top side screw on the XW Solar Charge Controller by ¼-inch.  
2. Remove the lower side screw on the XW Solar Charge Controller.  
3. Holding the unit against the side of the power distribution panel, insert the top side  
screw into one of the two keyhole slots on the side of the power distribution panel and  
pull the unit down into the slot.  
4. Insert the lower side screw through the hole on the inside of the power distribution  
panel and into the side of the XW Solar Charge Controller.  
5. Tighten the lower side screw to secure the XW Solar Charge Controller.  
To mount the XW Solar Charge Controller to the top of the power distribution  
panel:  
1. Remove a pair of knockouts from the top of the power distribution panel.  
2. Remove the bottom knockouts from the XW Solar Charge Controller.  
3. Align the knockouts on the power distribution panel and XW Solar Charge Controller,  
and secure the unit with two locking strain reliefs or threaded connectors.  
In a stand-alone installation, the XW Solar Charge Controller is mounted using three #10  
× ½-inch or #12 × ½-inch pan-head screws.  
To mount the XW Solar Charge Controller away from the power distribution panel:  
1. Remove the wiring terminals cover.  
2. Mark the location of the keyhole slot on the wall.  
3. Secure the top mounting screw in the location marked. Leave the screw head backed  
out approximately ¼ inch (6 mm).  
4. Place the controller onto the screw and pull it down into the keyhole slot.  
4–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
5. Insert two screws in the two mounting holes provided to secure the unit to the wall.  
6. Provide strain-relief clamps or conduit to prevent damage to the circuit board and  
terminal block from pulling on the wires.  
¼"  
Place keyhole  
slot over the  
mounting screw.  
xantrex  
Solar Charge Controller  
Secure with two more screws.  
Figure 4-5 Mounting the XW Solar Charge Controller  
975-0239-01-01  
4–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Grounding  
The XW Solar Charge Controller is designed to work only with negative-grounded  
electrical systems. Grounding for both PV and battery circuits is provided inside the  
wiring compartment. Each ground connection can accommodate up to #6 AWG wire size.  
A fuse rated at 1 A, 600 V (accessible from inside the wiring compartment) grounds the  
negative conductor of the PV array and provides PV ground-fault protection (PV-GFP).  
Replace with Littelfuse KLKD 1 or equivalent.  
Important: Only one Charge Controller is to have the PV-GFP fuse installed in  
installations with multiple parallel XW Series. Before mounting and connecting the XW  
Seriess, remove the PV-GFP fuse from each unit except one.  
WARNING: Shock Hazard  
Do not connect the battery negative to ground. NEC requirements specify that the battery  
negative ground must be done only through the 1A PV-GFP fuse. Bonding the battery  
negative to ground disables PV ground-fault protection. The battery compartment must  
only be grounded if it is metal.  
WARNING: Fire Hazard  
Ensure there is no other ground connection in the DC  
wiring or the PVGFP will be defeated and will not protect  
the array from ground fault conditions.  
xantrex  
This symbol identifies the  
protective conductor  
(grounding) connection.  
Solar Charge Controller  
Chassis ground terminals.  
The PVGFP fuse is located under the power  
connector circuit board  
Figure 4-6 XW Solar Charge Controller Safety Ground Connector  
WARNING: Shock Hazard  
Disconnect PV and battery circuits before removing the grounding connection or before removing  
or installing the PV-GFP fuse.  
4–8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
Wiring  
Important: Installations must meet all local electrical codes. Installations of this equipment  
should only be performed by a qualified electrician or a Certified Renewable Energy (RE) System  
Installer.  
WARNING: Shock Hazard  
Disconnect battery and PV sources before wiring.  
DC Terminal Connector Locations  
Terminal connectors for DC wiring are located inside the wiring compartment. The labels  
above the DC wiring terminals and inside the wiring compartment identify all the  
connection points. See Figure 4-7.  
CONNECTIONS DIAGRAM  
XANBUS  
AUX BTS XANBUS  
TERMINAL TORQUE REQUIREMENTS  
15lbf.in (1.7 Nm) FOR #14-10 AWG WIRE  
18lbf.in (2.0 Nm) FOR #8 AWG WIRE  
20lbf.in (2.2 Nm) FOR #6 AWG WIRE  
+
-
BATTERY  
+
PV  
BA-TTERY -  
PV  
+
Figure 4-7 DC Connection Terminals  
Wire Size and Over-current Protection Requirements  
The wiring, over-current protection devices (fuses and circuit breakers), and installation  
methods used must conform to all national and local electrical code requirements.  
Wiring must be protected from physical damage with conduit or a strain relief clamp.  
The BTS, auxiliary output, and network cables must pass through a different conduit than  
the conduits used for PV wiring and battery cables. Pull the BTS cable through the conduit  
first as the connector may not fit if other wires have been pulled first.  
Current rating  
The XW Solar Charge Controller is rated for 60 A maximum Isc. Since PV outputs can  
vary due to the array size or sunlight striking it, the safe minimum wire size must be  
chosen for maximum array short-circuit current. Consult PV array manufacturer  
specifications.  
Minimum wire  
gauge  
For installations where the PV array output is the maximum allowable 60 A Isc, the  
minimum allowable wire gauge is #6 AWG (13.3 mm2) copper wire with a 90 °C (194 °F)  
insulation rating. This wire gauge is determined by electrical code requirements regarding  
conduit knockout sizes, wire bending radius, and space available within the XW Solar  
Charge Controller wiring compartment.  
No crimp-on terminals or lugs are required.  
Over-current  
protection  
Over-current protection must be installed for the battery and PV circuits to protect the XW  
Solar Charge Controller from short circuits at its input and output. The NEC requires all  
circuits to be protected with a device rated for 125% of the rating of the circuit.  
975-0239-01-01  
4–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Table 4-3 Recommended Circuit Breakers for the XW Solar Charge Controller  
Xantrex Part  
Number  
Description  
865-1065  
Master Pack - Qty 6, Breaker 250A, 160 Vdc, Stud Terminal, Panel  
Mount, UL/CSA  
865-1070  
865-1075  
Master Pack - Qty 12, Breaker 80A, 125 Vdc, Panel Mount, UL/CSA  
Master Pack - Qty 48, Breaker 60A, 160 Vdc, Panel Mount, UL/CSA  
Battery Circuit  
The DC-rated fuse or circuit breaker between the battery and the XW Solar Charge  
Controller must have a maximum size of 1.25 × 60 A (the maximum current rating of the  
XW Solar Charge Controller). That is, the fuse or circuit breaker must be rated equal to or  
above 75 A.  
PV Circuit  
The DC-rated fuse or circuit breaker between the PV array and the XW Solar Charge  
Controller must be rated for the Isc of the array but will not exceed the 60 A rating.  
Long-distance wire  
runs  
If there is a significant distance between the PV array and the XW Solar Charge Controller  
or between the XW Solar Charge Controller and the battery, larger wires can be used to  
reduce the voltage drop and improve performance. Refer to Table 4-4 or Table 4-5.  
WARNING: Equipment damage  
Do not connect an array capable of delivering over 60 A I to the XW Solar Charge Controller.  
sc  
Wires larger than #6 AWG can be used only to reduce power loss in the wiring.  
To use a larger size wire, use a splicer block (terminal block) approved and rated for this  
application. This allows the larger cable size from the batteries to be “spliced” to the #6  
AWG wire connected to the XW Solar Charge Controller. The splicer block must be  
installed outside of the XW Solar Charge Controller wiring compartment.  
Follow manufacturer’s recommendations for torque and mounting. Splicer blocks and  
split-bolt kerneys are available from renewable energy suppliers.  
Important: Local and national electrical codes must be followed for determining additional  
installation requirements.  
Larger wire sizes may be used to improve performance, but may not be installed directly into this  
Charge Controller. Use a splicer block as previously described.  
Maximum one-way  
distance and wire  
size  
Refer to Table 4-4 or Table 4-5 and find the maximum current in the left column, and the  
one-way distance from the PV array to the XW Solar Charge Controller (or the distance  
from the XW Solar Charge Controller to the battery) on the same line, then read the wire  
size required at the top of the column.  
4–10  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
Table 4-4 One-Way Wire Distance and Wire Size for a 24 Vdc System  
Maximum one-way wire distance for a < 3% voltage drop assuming 60 Adc charging current  
For 24 Vdc systems  
a
Distance in feet (meters)  
Distance in feet (meters)  
Amps  
12 AWG  
10 AWG  
28.0 (8.54)  
23.2 (7.08)  
20.0 (6.10)  
17.4 (5.30)  
17.6 (4.76)  
14.0 (4.26)  
11.2 (3.42)  
9.4 (2.86)  
8 AWG  
6 AWG  
70.6 (21.52)  
58.8 (17.92)  
50.4 (15.36)  
44.2 (13.48)  
39.2 (11.94)  
35.2 (10.72)  
28.2 (8.60)  
23.6 (7.20)  
20.2 (6.16)  
17.6 (5.36)  
15.6 (4.76)  
14.2 (4.32)  
12.6 (3.84)  
4 AWG  
112.2 (34.2)  
93.4 (18.46)  
80.2 (24.44)  
70.0 (21.34)  
62.4 (19.02)  
56.0 (17.06)  
44.8 (13.66)  
37.4 (11.4)  
32.0 (9.76)  
28.0 (8.54)  
25.0 (7.62)  
22.4 (6.82)  
18.6 (5.66)  
3 AWG  
141.8 (43.22)  
118.2 (36.02)  
101.2 (30.84)  
88.6 (27.0)  
2 AWG  
179.2 (54.62)  
149.2 (45.48)  
128.0 (39.02)  
112.0 (34.14)  
99.6 (30.36)  
89.6 (27.32)  
71.6 (21.82)  
59.8 (18.22)  
51.2 (15.6)  
1 AWG  
225.0 (68.58)  
187.4 (57.12)  
160.8 (49.02)  
140.6 (42.86)  
125.0 (38.10)  
112.4 (34.26)  
90.0 (27.44)  
75.0 (22.86)  
64.2 (19.56)  
56.2 (17.12)  
50.0 (15.24)  
45.0 (13.72)  
37.4 (11.4)  
1/0 AWG  
17.6 (5.36)  
14.6 (4.46)  
12.6 (3.84)  
11.0 (3.36)  
9.8 (2.98)  
8.8 (2.68)  
44.4 (13.54)  
37.0 (11.28)  
31.8 (9.70)  
27.8 (8.48)  
24.8 (7.56)  
22.2 (6.76)  
17.8 (5.42)  
14.8 (4.52)  
12.8 (3.90)  
11.2 (3.42)  
283.4 (86.38)  
236.2 (72.00)  
202.4 (61.70)  
177.2 (54.02)  
157.4 (47.98)  
141.8 (43.20)  
113.4 (34.56)  
94.4 (28.78)  
81.0 (24.68)  
70.8 (24.58)  
63.0 (19.20)  
56.6 (17.26)  
47.2 (14.38)  
10  
12  
14  
16  
18  
20  
25  
30  
35  
40  
45  
50  
60  
78.8 (24.02)  
70.8 (21.58)  
56.6 (17.26)  
47.2 (14.38)  
40.4 (12.32)  
35.4 (10.78)  
31.4 (9.58)  
44.8 (13.66)  
39.8 (12.14)  
35.8 (10.92)  
29.8 (9.08)  
28.4 (8.66)  
23.6 (7.20)  
a.These wire sizes are not approved by UL to be installed in the controller, but may be used external to the controller (using a splicer block) to reduce  
voltage drop and improve performance.  
Table 4-5 One-Way Wire Distance and Wire Size for a 48 Vdc System  
Maximum one-way wire distance for a < 3% voltage drop assuming 60 Adc charging current  
For 48 Vdc systems  
a
Distance in feet (meters)  
Distance in feet (meters)  
Amps  
12 AWG  
10 AWG  
112.0 (34.16)  
92.8 (28.32)  
80.0 (24.40)  
69.6 (21.20)  
70.4 (19.04)  
56.0 (17.04)  
44.8 (13.68)  
37.6 (11.44)  
8 AWG  
6 AWG  
282.4 (86.80)  
235.2 (71.68)  
201.6 (61.44)  
176.8 (53.92)  
156.8 (47.76)  
140.8 (42.88)  
112.8 (34.40)  
94.4 (28.80)  
80.8 (26.64)  
70.4 (21.44)  
62.4 (19.04)  
56.8 (17.28)  
50.4 (15.36)  
4 AWG  
3 AWG  
2 AWG  
1 AWG  
1/0 AWG  
70.4 (21.44)  
58.4 (17.84)  
50.4 (15.36)  
44.0 (13.44)  
39.2 (11.92)  
35.2 (10.72)  
177.6 (54.16)  
148.0 (45.12)  
127.2 (38.8)  
111.2 (33.92)  
99.2 (30.24)  
88.8 (27.04)  
71.2 (21.68)  
59.2 (18.08)  
51.2 (15.60)  
44.8 (13.68)  
448.8 (136.8)  
567.2 (172.88) 716.8 (218.48) 900.0 (274.32) 1133.6 (345.52)  
10  
12  
14  
16  
18  
20  
25  
30  
35  
40  
45  
50  
60  
373.6 (113.84) 472.8 (144.08) 596.8 (181.92) 749.6 (228.48) 944.8 (288.00)  
320.8 (97.76)  
280.0 (85.36)  
249.6 (76.08)  
224.0 (68.24)  
179.2 (54.64)  
149.6 (45.60)  
128.0 (39.04)  
112.0 (34.16)  
100.0 (30.48)  
89.6 (27.28)  
74.4 (22.64)  
404.8 (123.36) 512.0 (156.08) 643.2 (196.08) 809.6 (246.80)  
354.4 (108.00) 448.0 (136.56) 562.4 (171.44) 708.8 (216.08)  
315.2 (96.08)  
283.2 (86.32)  
226.4 (69.04)  
188.8 (57.52)  
161.6 (49.28)  
141.6 (43.12)  
125.6 (38.32)  
113.6 (34.64)  
94.4 (28.80)  
398.4 (121.44) 500.0 (152.40) 629.6 (191.92)  
358.4 (109.28) 449.6 (137.04) 567.2 (172.80)  
286.4 (87.28)  
239.2 (72.88)  
204.8 (62.40)  
179.2 (54.64)  
159.2 (48.56)  
143.2 (43.68)  
119.2 (36.32)  
360.0 (109.76) 453.6 (138.24)  
300.0 (91.44)  
256.8 (78.24)  
224.8 (68.48)  
200.0 (60.96)  
180.0 (54.88)  
149.6 (45.60)  
377.6 (115.12)  
324.0 (98.72)  
283.2 (86.32)  
252.0 (76.80)  
226.4 (69.04)  
188.8 (57.52)  
a.These wire sizes are not approved by UL to be installed in the controller, but may be used external to the controller (using a splicer block) to reduce  
voltage drop and improve performance.  
975-0239-01-01  
4–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Connecting the XW Solar Charge Controller to the Distribution Panel  
WARNING: Shock Hazard  
Whenever a PV array is exposed to light, a shock hazard exists at the output wires or exposed  
terminals. To reduce the risk of shock during installation, cover the array with an opaque (dark)  
material before making the connections. PV arrays generate voltage whenever light strikes the  
surface of the array. Before connecting the XW Solar Charge Controller, cover the array to prevent  
any current from being generated.  
WARNING: Shock Hazard  
Do not connect the battery negative to ground. Bonding the battery negative to ground disables PV  
ground-fault protection.  
To connect the XW Solar Charge Controller:  
1. Connect the PV array’s positive (+) output to the PV array disconnect.  
2. Route another (+) cable from the other end of the PV disconnect to the terminal  
marked PV + in the XW Solar Charge Controller.  
3. Connect the PV array’s negative (–) output to the terminal marked PV – in the XW  
Solar Charge Controller.  
4. Connect a positive (+) cable from the terminal marked BAT + to the battery disconnect.  
5. Connect a second positive (+) cable to the other side of the battery disconnect and  
connect to the positive (+) battery terminal.  
6. Connect the negative (–) battery cable to the terminal marked BAT – in the XW Solar  
Charge Controller.  
7. Torque the Charge Controller terminals as follows.  
15 inch-pounds (1.7 Nm) for #14–10 AWG wire  
18 inch-pounds (2.0 Nm) for #8 AWG wire  
20 inch-pounds (2.2 Nm) for #6 AWG wire.  
Be careful not to overtighten. Allow some slack on the cables within the controller and  
secure the wiring with strain reliefs or cable clamps.  
See Figure 4-8.  
4–12  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
Actual wiring requirements may vary.  
Figure 4-8 Connecting Solar DC Sources in the Power Distribution Panel  
975-0239-01-01  
4–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
Commissioning  
During commissioning, the XW Solar Charge Controller prompts the installer to enter  
important system information such as the nominal battery voltage, battery type, and  
battery bank capacity. Ensure the system information is available prior to commissioning.  
If a XW System Control Panel is present, the XW System Control Panel is intended to be  
the configuration interface, so the prompt screens are suppressed. If you prefer to  
configure using the prompt screens, disconnect the Xanbus cable connecting the XW  
System Control Panel from the XW Solar Charge Controller before powering up for the  
first time.  
Configuration Screens  
When power is first applied to the XW Solar Charge Controller, several configuration  
screens prompt you to enter the following information:  
A “DC out” (battery) connection, which enables the XW Solar Charge Controller to  
read and share the same battery information with other Xanbus-enabled devices that  
charge or invert from the same battery bank.  
Battery type: Flooded (default), Gel, AGM, Custom.  
If you select Custom, the settings for battery type match the default settings for  
Flooded batteries until you reconfigure the settings on the Custom Battery menu.  
Nominal battery voltage of the battery bank connected to the XW Solar Charge  
Controller.  
The XW Solar Charge Controller automatically detects battery voltages of 12 V, 24 V  
and 48 V. If your nominal system voltage is 36 V or 60 V, enter the correct system  
voltage on this screen.  
Battery bank capacity, in amp-hours.  
Commissioning Units Using a XW System Control Panel  
In systems where an XW System Control Panel (SCP) is present, the SCP is intended to be  
the configuration interface. For information about SCP navigation and menus, see  
Appendix B, “XW System Control Panel Menus in the XW Inverter/Charger Operation  
Guide.  
Commissioning units using an SCP involves three separate procedures:  
1. Setting the Device Numbers for all XW Solar Charge Controllers.  
2. Configuring Connections and Charger Settings for the first XW Solar Charge  
Controller.  
3. Copying settings from the first unit to the other XW Solar Charge Controller.  
To set the Device Numbers for all XW Solar Charge Controllers:  
1. Ensure power is applied to the XW System Control Panel.  
2. Close the DC disconnect or use a selector switch to apply battery power to all of the  
XW Solar Charge Controllers at the same time. When the XW Solar Charge  
Controllers are powered up, they will detect that an SCP is already operating on the  
network, and be ready for configuration through the SCP. Do not apply PV power at  
this point.  
4–14  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Commissioning  
3. From the Select Device menu on the SCP, select a XW Solar Charge Controller (each  
unit should appear as “MPPT60 00” where the 60 stands for 60A, and the 00 is its  
device number).  
4. On the MPPT Setup menu, ensure the Advanced Settings item is displayed. If  
Advanced Settings are not displayed (and Basic Settings appears as the last item on the  
menu), press the up arrow, down arrow and Exit keys together. (See “Advanced menu”  
on page B-7 of the XW Inverter/Charger Operation Guide.)  
5. Select Advanced Settings, then select the Multi Unit Config menu. After entering the  
Multi Unit Config menu, the LCD backlight on the XW Solar Charge Controller to be  
configured will flash.  
6. On the Multi Unit Config menu, select Dev Number and set it to a number other than  
00.  
The device number can be set to any number between 01 and 31. For the first XW  
Solar Charge Controller, 01 is recommended. If you have two charge controllers,  
simply set them to 01 and 02.  
7. Press Exit until the Select Device menu is displayed.  
The XW Solar Charge Controller now appears as MPPT60 01 on the menu.  
8. Repeat steps 3 through 7 for the next XW Solar Charge Controller.  
When you have set the device number for all XW Solar Charge Controllers, you can  
configure Connections and Charger Settings for the first XW Solar Charge Controller.  
To configure Connections and Charger Settings for the first XW Solar Charge  
Controller:  
1. On the Select Device Menu, select “MPPT60 01.”  
2. Navigate to the Multi Unit Config menu and select Connections.  
On the Connections menu, you can configure PV In (PV input) and DC Conn (DC  
output, or the battery bank). If the system has only one battery bank, leave DC Conn at  
the default setting. The PV In setting allows you to differentiate which array is going  
to which XW Solar Charge Controller. This setting is used for status reporting only,  
not for any internal controls. Setting PV In to a non-default value is optional.  
3. Press Exit twice to leave the Connections menu and Multi Unit Config menu.  
4. From the Advanced Settings menu, select Charger Settings.  
5. Set the Battery Type, Battery Capacity, and any other charger settings required for  
your system.  
While in the Charger menu, ensure that the Nominal Battery Voltage is set correctly (it  
is shown as Batt Voltage and appears as the last item on the menu). If you select  
“Custom” for your Battery Type, you can further configure the Bulk, Absorption,  
Float and other settings for the charge cycle.  
The first charge controller should now be configured properly for your system.  
If multiple charge controllers are installed, you can now copy the first unit’s  
configuration over to other units.  
To copy the XW Solar Charge Controller setup to another unit:  
1. On the SCP, press Exit to leave the Advanced Settings menu and view the Select  
Device menu.  
2. On the Select Device Menu, select the next XW Solar Charge Controller for  
configuration.  
975-0239-01-01  
4–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW Solar Charge Controller Installation  
3. On the Advanced Settings menu, select Copy From, then select the XW Solar Charge  
Controller you want to copy from. You should select the unit with the device number  
that matches the first unit you configured.  
4. Press Enter.  
The settings are automatically copied from the selected unit.  
Note: The Copy From command will not give you any indication that it has completed  
its task. However, you can quickly check for yourself that the charger settings you have  
chosen have been copied properly by viewing some of the settings you originally  
configured.  
5. Uncover the PV array and/or apply power with the disconnect or selector switch.  
The XW Solar Charge Controller starts up in sleep mode and waits for a short period to  
determine that the input voltage is greater than the output voltage. After the input voltage  
exceeds the output voltage by the required margin for 10 seconds, the unit begins  
operating.  
4–16  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories  
Installation  
5
Chapter 5, “XW System Accessories Installation” describes how to mount  
and install the XW System Control Panel and the Automatic Generator Start.  
For this Topic  
See....  
“The XW System Control Panel”  
“The XW Automatic Generator Start”  
page 5–2  
page 5–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
The XW System Control Panel  
The XW Series Inverter/Charger can be controlled remotely by connecting a XW System  
Control Panel. The XW System Control Panel is optional for single inverter systems. The  
XW System Control Panel is required for configuring systems with multiple inverters. The  
XW System Control Panel allows access to programming features of the inverter and  
allows the system to be modified to specific installation requirements.  
The XW System Control Panel is connected to the inverter through one of two Xanbus  
ports.  
Figure 5-1 XW System Control Panel Xanbus Port Locations  
The XW System Control Panel is designed to be wall mounted (see “Mounting the XW  
System Control Panel” on page 5–3), and requires no connections other than the network  
cables or terminators that plug into the back of the unit.  
Because you cannot access the XW System Control Panel network inputs after the unit is  
mounted, the network cables need to be routed through the wall and connected before  
securing the XW System Control Panel.  
See Chapter 3, “Xanbus Network Installation”, for more information about installing a  
Xanbus-enabled device as part of a network-managed power system.  
5–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW System Control Panel  
Materials and Tools Required  
You will need these materials and tools to complete the installation:  
Mounting template sticker (supplied)  
Mounting plate (supplied)  
mounting plate (supplied)  
Four #6 screws (supplied)  
Two #8 screws (supplied)  
Cable clamps or hardware fasteners  
Xantrex network cables or equivalent (CAT 5 or CAT 5E cable with RJ45 connectors  
wired to T568A standard) A 7-foot cable is provided.  
Xantrex male network terminator (supplied).  
Phillips head screwdriver  
Jigsaw or small keyhole saw  
Power drill with 1/8" bit (optional)  
Choosing a Location  
Choose a location that is easily accessible. The XW System Control Panel should be  
mounted where you can have unobstructed access to the screen and buttons.  
The location should be indoors, dry, and free from corrosive or explosive fumes.  
WARNING: Explosion hazard  
The XW System Control Panel is not Ignition Protected. Do not install in areas requiring  
Ignition-Protected equipment, such as areas containing gasoline engines, tanks, or fuel-line fittings.  
Mounting the XW System Control Panel  
The XW System Control Panel can be mounted three ways:  
Flush mounted through an opening in a wall using the mounting plate  
Surface mounted using the mounting plate  
Flush mounted through an opening in a wall and secured with four #6 screws.  
WARNING: Shock hazard  
Before making an opening in a wall or panel, ensure there is no wiring or other obstruction within  
the wall.  
To flush mount the XW System Control Panel with mounting plate:  
1. Using a jigsaw and the supplied template sticker as a guide, cut out the hole for the  
mounting plate. The mounting plate fastens to walls up to 3/4 inch (19 mm) thick.  
2. Route the network cable from the GT Inverter inside the wall and through the opening.  
3. Insert the mounting plate with the two tabs in a vertical position into the hole (see  
Figure 5-2).  
975-0239-01-01  
5–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Tabs in vertical position  
Figure 5-2 Inserting the Mounting Plate  
4. Secure the mounting plate by tightening the two screws to rotate the tabs to the  
horizontal position (see Figure 5-3) and pull the tabs tight against the inner surface of  
the wall. Be careful not to overtighten the screws and damage the wall.  
Rotate tabs to  
horizontal position  
Figure 5-3 Securing the Mounting Plate  
5. Connect the network cable(s) (and terminator if necessary) to either input on the back  
of the XW System Control Panel. See Figure 5-4.  
Connect a network terminator to the XW System Control Panel if it is the last device  
at the end of a series-type network layout.  
Important: To ensure communication signal quality, the network must be terminated at each  
end with a terminator.  
5–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW System Control Panel  
Figure 5-4 Connecting the Network Cables  
6. Place the unit into the mounting plate and secure it with four #6 screws.  
Figure 5-5 Securing the XW System Control Panel  
7. Peel off the protective plastic coating covering the screen and indicator light.  
To flush mount the XW System Control Panel with no mounting plate:  
1. Peel the backing from the supplied mounting template sticker and place it in your  
chosen installation location. Use the template to mark the location for the area to be  
cut out.  
2. Pilot-drill the mounting holes (if necessary, depending on your mounting surface) and,  
using a jigsaw, cut out the hole in which the XW System Control Panel will be  
inserted.  
3. Route the network cable(s) from other Xanbus-enabled devices inside the wall and  
through the opening.  
975-0239-01-01  
5–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
CAUTION: Equipment damage  
Connect the XW System Control Panel only to other Xanbus-enabled devices.  
:
Although the cabling and connectors used in this network system are the same as Ethernet  
connectors, this network is not an Ethernet system. Equipment damage may result from  
attempting to connect these two different systems.  
4. Connect the network cable(s) (and terminator if necessary) to either input on the back  
of the XW System Control Panel. See Figure 5-4.  
Connect a network terminator to the XW System Control Panel if it is the last device  
at the end of a series-type network layout.  
5. Place the unit in the opening and secure it with four #6 screws.  
6. Peel off the protective plastic coating covering the screen and indicator light.  
To surface mount the XW System Control Panel:  
1. Using the supplied template sticker as a guide, mark the locations for two mounting  
screws and the access hole for the network cables.  
2. Using a hole saw, cut out the access hole for the network cable(s).  
3. Route the network cable(s) from other Xanbus-enabled devices inside the wall and  
through the access hole.  
4. Attach the mounting plate with two #6 screws.  
5. Connect the network cable(s) (and terminator if necessary) to either input on the back  
of the XW System Control Panel.  
Connect a network terminator to the XW System Control Panel if it is the last device  
at the end of a series-type network layout.  
6. Place the unit into the mounting plate and secure it with four #6 screws. See Figure  
5-6.  
7. Peel off the protective plastic coating covering the screen and indicator light.  
Figure 5-6 Surface Mounting the XW System Control Panel  
5–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
Verifying the Installation  
If network power (from an inverter/charger) is present, the backlight will come on and the  
XW System Control Panel will show the startup screen (see the XW Inverter/Charger  
Operation Guide), then show the System Home screen.  
The XW Automatic Generator Start  
Some generators allow automatic starting. Connecting an Automatic Generator Start to the  
generator and to the Xanbus network is required for the XW System to benefit from  
automatic generator start/stop capability.  
WARNING: Shock Hazard  
Auto-start generators can start automatically at any time.  
Affix the warning labels (supplied with the XW Automatic Generator Start) regarding auto-start  
generators on or near the main AC distribution panel and near the generator.  
The AGS connects to:  
• Inverter/Charger’s Xanbus port  
• Generator  
Automatic Generator Start  
Figure 5-7 Connecting the AGS Communications Cable to the XW Series  
Preparing an Installation  
Before installing the XW Automatic Generator Start Module, consider how and where the  
unit will be mounted. Pre-plan the connection routes between the XW Automatic  
Generator Start, the generator, thermostats, and the XW Automatic Generator Start. Refer  
to the XW AGS Owner’s Guide for additional information.  
See Chapter 3, “Xanbus Network Installation”, for more information about installing a  
Xanbus-enabled device as part of a network-managed power system.  
Materials and Tools Required  
The following tools and materials may be needed to install the XW Automatic Generator  
Start:  
Mounting template (supplied)  
Wiring harness (Xantrex part number 809-0917, supplied)  
Four #6 screws, 1¼ inch (supplied)  
975-0239-01-01  
5–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
#16 or #18 AWG wire (see “Wire Size and Length” on page 5–11)  
Xantrex network cables or equivalent (Category 5)  
Network terminators (if required)  
Phillips screwdriver  
Wire cutters and wire strippers  
Choosing a Location  
The XW Automatic Generator Start should be installed in a location that meets the  
following requirements:  
The unit is intended for use in a dry location. The XW Automatic Generator Start  
complies with UL458 Marine Supplement drip-test requirements, but the location  
should be as dry as possible.  
Dry  
The XW Automatic Generator Start operates between -4 and 122 °F (-20 and  
50 °C).  
Cool  
Safe  
The XW Automatic Generator Start is not ignition protected. Do not install it in  
areas requiring ignition-protected equipment, such as compartments housing  
gasoline engines.  
Avoid excessive wire lengths and use the recommended wire lengths and sizes  
(see “Wire Size and Length” on page 5–11). It is more important for the XW  
Automatic Generator Start to be close to the generator than close to the inverter,  
although for safety reasons, the XW Automatic Generator Start should not be  
installed in the same compartment as a gasoline-powered generator.  
Close to  
generator  
Routing the Connections  
WARNING: Explosion Hazard  
This equipment is not ignition protected. To prevent fire or explosion, do not  
install the XW Automatic Generator Start in locations that require  
ignition-protected equipment. This includes any space containing  
gasoline-powered machinery, fuel tanks, as well as joints, fittings, or other  
connections between components of a fuel system.  
Follow all relevant instructions exactly before installing or using your XW  
Automatic Generator Start.  
WARNING: Shock and Energy Hazards  
Before making any connections to the generator, ensure that the generator’s  
starter is disabled and the generator’s start battery is disconnected.  
Connection Types  
Because the XW Automatic Generator Start will be part of a Xanbus system, it is  
necessary to consider how to route two types of connections:  
connections to the generator, thermostats, and other external devices and switches,  
using the 20-contact connector and wiring harness.  
connections to other Xanbus-enabled devices, using network cables.  
For information on designing and installing the network, see the XW Inverter/Charger  
Operation Guide.  
5–8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
Network ports  
20-contact  
connector  
Network cables to other  
Xanbus-enabled devices  
Wiring harness (connection  
to generator, thermostats,  
and external switches)  
Figure 5-8 XW Automatic Generator Start External Connections  
Installing the XW Automatic Generator Start  
Installation  
Overview  
Installing the XW Automatic Generator Start involves the following steps:  
1. Mounting the unit.  
2. Connecting the wiring harness to:  
the generator (page 5–12)  
thermostats (optional) (page 5–13)  
external shutdown switch (optional) (page 5–13)  
external ON/OFF switch and LED (optional) (page 5–14)  
3. Connecting the wiring harness to the 20-contact connector on the XW Automatic  
Generator Start.  
4. Connecting the XW Automatic Generator Start to the XW System Control Panel and  
other network-enabled devices (page 5–16).  
Important: Because each installation varies according to the location, the  
type of generator, and the overall complexity of the Xanbus system, these  
instructions can offer only general guidelines for the many installation options  
available.  
WARNING: Shock Hazard  
Before installing the XW Automatic Generator Start as part of a pre-existing  
Xanbus system, put the system in Standby in order to disable the electrical  
operation of networked devices. See the Automatic Generator Start Owner’s  
Guide for instructions on putting the System in Standby.  
975-0239-01-01  
5–9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Mounting the Unit  
The XW Automatic Generator Start is to be mounted vertically on a wall with the  
connectors facing downwards.  
To mount the XW Automatic Generator Start:  
1. Hold the unit flush and square against the wall, panel, or horizontal surface.  
If the mounting surface requires pre-drill holes for the screws, use the supplied  
mounting template to mark, then drill, four holes.  
2. With a Phillips screwdriver and the supplied #6 screws, secure each corner of the XW  
Automatic Generator Start to the mounting surface.  
Wiring to the 20-contact Connector  
CAUTION: Shock Hazard  
All installation wiring should be performed by a qualified installer or electrician.  
WARNING: Fire, Shock, and Energy Hazards  
The 20-contact connector is intended for connection to Class 2 ELV (Extra Low  
Voltage) circuits only. Do not exceed the circuit limitations specified in the  
following section.  
ELV Circuits  
ELV (Extra-Low Voltage) circuits have an open-circuit voltage of not more than 30 Vrms  
or 42.2 VDC or peak, and are therefore not a shock hazard.  
Class 2 Circuits  
As per the US National Electrical Code (NEC) and the Canadian Electrical Code (CEC),  
available power in Class 2 circuits is limited to 100 VA, usually by current limiting by  
means of overcurrent protection or series resistance. The current is limited to 5 A for  
circuits with open-circuit voltage of 20 V, and to I=100/V for circuits with open circuit  
oc  
voltage between 20 V and 30 V.  
Circuit Limitations  
The relay contacts in the XW Automatic Generator Start are rated at 5 A maximum and all  
circuits on the 20-contact connector are rated at 30 V maximum.  
Ensure that all circuits connected to the 20-contact connector obey the following limits:  
Table 5-1 Circuit Limitations  
Circuit Parameter  
Circuit Maximum  
Open circuit voltage (V )  
30 V maximum  
oc  
Overcurrent protection  
(fuse size for open circuit voltage up to 20 V)  
5 A maximum  
5 A to 3.33 A  
Overcurrent protection  
(fuse size for open circuit voltage from 20 V to 30 V)  
(100/V amps  
oc  
maximum)  
Wiring Harness  
Connections to the generator, thermostats, and external ON/OFF switches are made using  
a wiring harness that plugs into the 20-contact connector (see Figure 5-8).  
5–10  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
The wires on the wiring harness can be extended to meet installation requirements. When  
extending the wire harness, ensure that the extension wires are the same color as the wires  
on the harness.  
To install the XW Automatic Generator Start using the wiring harness:  
1. Connect each wire on the harness to its intended wire or contact on the generator,  
thermostats, or external switches.  
2. Plug the harness into the connector on the bottom panel of the XW  
Automatic Generator Start.  
Wire Identification  
Each wire on the harness is identified by a number and a color. The wire numbers are  
shown in Figure 5-9 and their colors and functions are described in Table 5-3.  
Wire Size and  
Length  
Required wire sizes for the external connections to the wiring harness are:  
Table 5-2 Required Wiring Size Based on Length of Cable  
0–30 ft. (9 m)  
Over 30 ft. (9 m)  
18 AWG  
16 AWG  
When planning the routing for external connections, ensure that wire lengths are sufficient  
to plug the wiring harness into the XW Automatic Generator Start once all the external  
connections are complete.  
Figure 5-9 XW Automatic Generator Start Wiring Harness  
Table 5-3 Contact Numbers and Functions  
Wire  
Wiring Harness  
Wire Color  
Number Function  
1
2
3
4
5
6
Thermostat 1 input  
Yellow  
Gray  
Thermostat 1 return  
Thermostat 2 input  
Orange  
Gray  
Thermostat 2 return  
External shutdown input  
External shutdown return  
White/Black  
Gray  
975-0239-01-01  
5–11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Table 5-3 Contact Numbers and Functions (Continued)  
Wire  
Wiring Harness  
Wire Color  
Number Function  
7
External manual on input  
White/Green  
White/Red  
White/Blue  
8
External manual off input  
9
External ON/OFF LED Indicator output  
10  
Constant 12/24 V B+ (battery positive) for External ON/OFF/LED Red  
Indicator  
11  
External ON/OFF/LED Indicator return (connected internally to  
wire number 13)  
Black  
12  
13  
Generator run signal (switched B+) sense input  
Violet  
Black  
Generator run signal (switched B+) sense return (generator battery  
negative)  
14  
15  
16  
17  
18  
19  
20  
Relay 1 (Generator run/stop) Normally open contact  
Relay 1 (Generator run/stop) Normally closed contact  
Relay 1 (Generator run/stop) Common contact  
Relay 2 (Generator start) Normally open contact  
Relay 2 (Generator start) Common contact  
Blue  
White/Violet  
Gray  
White  
Gray  
Relay 3 (Preheat/cooldown) Normally open contact  
Relay 3 (Preheat/cooldown) Common contact  
Brown  
Gray  
Connecting the Generator  
To connect the XW Automatic Generator Start to a generator, you must identify the start  
wiring configuration of the generator you want to use. Generators must be auto-start  
capable, and generators equipped with remote operation connections are ideal.  
If the generator is equipped for remote operation, you must examine the wiring of the  
remote cable and connector (or read your generator’s documentation, if available) and  
identify the following wires:  
Ground  
Start  
Stop  
Generator run signal, also known as the Hour Meter or Switched B+ (battery positive)  
Wiring  
requirements  
To wire the XW Automatic Generator Start to the generator, you need #16 or #18 AWG  
wire connected between contacts 12 to 20 on the wiring harness. How many of these wires  
you connect and in which combination depends on your generator type.  
Generator types  
The XW Automatic Generator Start has 13 preset generator configurations, or “Gen  
Types” (see the XW Automatic Start Owner’s Guide for details on Generator Types). To  
ensure that the XW Automatic Generator Start is compatible with your generator’s starting  
circuitry, you must select your type of generator from the XW Automatic Generator Start  
menu on the XW System Control Panel after completing the installation.  
5–12  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
Important: You can only change GenType after you have put the system or the XW Automatic  
Generator Start into Standby mode. See the XW Inverter/Charger Operation Guide for instructions  
on putting the system in Standby Mode.  
This section describes the generator configurations and provides diagrams for connecting  
the wiring harness to the generator’s start wiring.  
Important: For an explanation of the terminology used in the following section, refer to  
Appendix B of the XW Automatic Generator Start Owner’s Guide. For more information about  
XW Automatic Generator Start internal relay activity and timing, see the Automatic Generator  
Start Owner’s Guide.  
Connecting the Thermostats (optional)  
Wires 1, 2, 3, and 4 on the wiring harness can be connected to two thermostats. Wires 1  
(yellow) and 2 (gray) are intended for thermostat 1 and wires 3 (orange) and 4 (gray) are  
intended for thermostat 2.  
Table 5-4 Wiring for Connecting Thermostats  
Wiring Harness  
Wire Number Function  
Wire Color  
Yellow  
Gray  
1
2
3
4
Thermostat 1 input (12/24 V)  
Thermostat 1 return (ground)  
Thermostat 2 input (12/24 V)  
Thermostat 2 return (ground)  
Orange  
Gray  
These wires connect to 12-volt/24-volt output signals from the thermostats. The XW  
Automatic Generator Start will start the generator in response to these signals.  
Thermostats can not be programmed using the XW Automatic Generator Start.  
For specific information about thermostat wiring and where XW Automatic Generator  
Start connections should be made, please consult your thermostat documentation or  
contact the thermostat manufacturer.  
Connecting an External Shutdown (optional)  
The external shutdown input is a 12-volt/24-volt input used to assure that the XW  
Automatic Generator Start keeps the generator off under conditions that may be potentially  
hazardous. Wire 5 (white/black) and 6 (gray) on the wiring harness are intended for an  
external switch or sensor (such as a moisture detector, carbon monoxide detector or coach  
running signal) that produces an active high 12-volt or 24-volt output.  
Table 5-5 Wiring for Connecting an External Shutdown  
Wiring Harness  
Wire number Function  
Wire Color  
White/Black  
Gray  
5
6
External shutdown input (12/24 V)  
External shutdown return (ground)  
975-0239-01-01  
5–13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Connecting an External Manual ON/OFF Switch (optional)  
The external manual ON/OFF inputs (wires 7 and 8 on the wiring harness) are intended for  
wiring to one or more remote ON/OFF switches for starting and stopping the generator  
manually. The other contact of the switch should be connected to ground. In order for the  
XW Automatic Generator Start to be able to detect these switches, wire the positive of the  
generator battery to the constant 12-volt/24-volt generator battery positive (wire 10 on the  
XW Automatic Generator Start wiring harness). See Figure 5-7.  
If the generator battery does not have the required voltage, any 12-volt or 24-volt power  
source will suit this purpose. If an alternate power source is used, the negative of the  
power source must be connect to the other contact of the switch.  
CAUTION: Equipment Damage  
Do not connect the XW Automatic Generator Start to a 48-volt battery bank. The  
XW Automatic Generator Start is limited to a 30V open-circuit maximum by its  
regulatory approval and cannot be connected to a 48-volt power source.  
Furthermore, tapping 12-volts or 24-volts from a 48-volt battery bank will  
unevenly wear out the batteries and shortens the battery bank life.  
Table 5-6 Wiring for Connecting an External Manual ON/OFF Switch  
Wire Number Function  
Wiring Harness Wire Color  
White/Green  
7
8
9
External manual on input  
External manual off input  
White/Red  
External On/Off LED Indicator White/Blue  
output  
10  
11  
Constant 12/24 V B+ for  
External On/Off/LED Indicator  
Red  
External On/Off/LED Indicator Black  
return  
Multiple control panels or simple contact closures can be wired to the external manual  
ON/OFF inputs. The XW Automatic Generator Start detects if any of the contacts close  
and will change its operating mode to External Manual On or External Manual Off (for  
more information, see the XW Automatic Generator Start Owner’s Guide). The XW  
Automatic Generator Start turns the generator on or off according to these inputs and the  
resulting operating mode change.  
The External Manual On and External Manual Off states are not affected by maximum  
generator run time. See the XW Automatic Generator Start Owner’s Guide for additional  
information.  
5–14  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
Connecting an External ON/OFF LED  
Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be connected to an LED or  
other light to accompany a remote external ON/OFF switch. This light turns on when the  
generator run signal is active to visually indicate that the generator is running.  
Important: With some generators, the generator run signal becomes active  
during the preheat stage, before the generator is actually running. In this case, the  
external ON/OFF LED (and the Generator On light on the XW Automatic  
Generator Start) will turn on during the preheat stage and remain on when the  
generator is running.  
For some generators, these lights will also remain on for a period of time after the  
generator has stopped.  
2K  
START PUSH BUTTON  
7
2K  
STOP PUSH BUTTON  
8
5K11  
EXTERNAL LED  
9
12V OR 24V  
10  
11  
EXTERNAL LED  
XW Automatic Generator Start  
GROUND  
13  
Figure 5-10 External On/Off Switch and LED Wiring Diagram  
975-0239-01-01  
5–15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Connecting the Wiring Harness to the XW Automatic Generator Start  
After all the external connections have been wired to the wiring harness, the connector on  
the wiring harness must be plugged into the 20-contact connector on the XW Automatic  
Generator Start.  
To connect the wiring harness to the XW Automatic Generator Start:  
With the click-tab on the wiring harness connector on top (away from the mounting  
surface), insert the wiring harness connector into the 20-contact connector on the XW  
Automatic Generator Start until the tab clicks into place.  
20-contact  
connector  
Click Tab  
Wiring harness (connection to  
generator, thermostats, and  
external switches)  
Figure 5-11 XW Automatic Generator Start External Connections  
5–16  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The XW Automatic Generator Start  
Connecting the XW Automatic Generator Start to the Xanbus Network  
CAUTION: Equipment Damage  
Connect only to other Xanbus-enabled devices.  
Although the cabling and connectors used in this network system are the same as  
Ethernet connectors, this network is not an Ethernet system. Equipment  
damage may result from attempting to connect a Xanbus-enabled device to an  
Ethernet system.  
To connect the XW Automatic Generator Start to the Xanbus network, plug a  
Category 5 network cable into one of the network ports on the bottom panel of the XW  
Automatic Generator Start. Connect the other end of that same cable to any  
Xanbus-enabled component that has an available network port. See Figure 5-8 on page  
5–9 for the location of the ports on the XW Automatic Generator Start.  
If the XW Automatic Generator Start is being installed on an existing Xanbus system, the  
system must first be put into Standby. See the XW Automatic Generator Start Owner’s  
Guide for instructions on putting the system in Standby.  
Depending on the layout of the Xanbus system, the following options are available for  
the other network connector on the XW Automatic Generator Start:  
A second network cable (in a “daisy-chain” network layout)  
A network terminator (in a “daisy chain” network layout where the XW Automatic  
Generator Start is the last device at one end of the network)  
Nothing (in a multi-drop backbone layout)  
Connect 1 or 2 Category 5  
network cables as required by  
the installation configuration.  
Figure 5-12 Connecting the SCP  
975-0239-01-01  
5–17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XW System Accessories Installation  
Verifying Power Is Available  
When the XW Automatic Generator Start has been installed properly, the Power and  
Network indicator lights illuminate.  
If one or both lights are out, check the network connections and ensure the network power  
supply is on.  
Verify Power and Network indicator  
lights are illuminated.  
Figure 5-13 Verifying Power is Available  
5–18  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
A
Appendix A, “Specifications” provides the electrical and environmental  
specifications for the XW Series.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Electrical Specifications  
Table A-1 XW Power System Electrical Specifications  
Model  
XW6048-120/240-60  
XW4548-120/240-60  
4,500 W  
XW4024-120/240-60  
4,000 W  
Continuous Output Power  
Surge Rating (10 seconds)  
Surge Current  
6,000 W  
12,000 W  
9,000 W  
8,000 W  
L-n: 105 A (7 sec)  
L-n: 75 A (20 sec)  
L-n: 70 A (7 sec)  
rms  
rms  
rms  
L-L: 52.5 A (7 sec)  
L-L: 40 A (20 sec)  
L-L: 35 A (7 sec)  
rms  
rms  
rms  
Waveform  
True Sine Wave  
Idle Consumption—invert mode, no load 28 W  
Idle Consumption—search mode  
AC Output Voltage  
26 W  
24 W  
< 8 W  
L-n: 120 Vac ±3%  
L-L: 240 Vac ±3%  
AC Input voltage range (Bypass/Charge  
Mode)  
L-n: 80–150 Vac (120 V nominal)  
L-L: 160–270 Vac (240 V nominal)  
AC Input Current (maximum 75%  
imbalance between L1-n, L2-n)  
L-n: 41.2 A  
L-L: 27.5 A  
L-n: 30.9 A  
L-L: 20.6 A  
L-n: 27.5 A  
L-L: 18.3 A  
AC Input Breaker  
60 A double-pole  
AC Input Frequency Range (Bypass/  
Charge Mode)  
55–65 Hz (default)  
44–70 Hz (allowable)  
a
L-n: 108–130 ±1.5 Vac  
L-L: 214–260 ±3.0 Vac  
AC1 voltage range—Sell Mode  
(automatically adjusts when entering Sell  
Mode)  
a
59.4–60.4 ±0.05 Hz  
AC1 Frequency range—Sell Mode  
(automatically adjusts when entering Sell  
Mode)  
AC Output Current (maximum 75%  
imbalance between L1-n, L2-n)  
L-n: 37.5 A  
L-L: 25.0 A  
L-n: 28.1 A  
L-L: 18.8 A  
L-n: 25.0 A  
L-L: 16.7 A  
AC Output Breaker  
60 A double-pole  
60.0 ±0.1 Hz  
< 5%  
AC Output Frequency  
Total Harmonic Distortion  
Automatic Transfer Relay  
Auxiliary Relay Output  
60 A  
0–12 Vdc, maximum 250 mA DC  
CEC Weighted Efficiency  
CEC Power Rating  
93.5%  
93%  
91%  
6,000 W  
50.4 Vdc  
44–64 Vdc  
127 A  
4,500 W  
50.4 Vdc  
44–64 Vdc  
95 A  
4,000 W  
25.2 Vdc  
22–32 Vdc  
171 A  
DC Input Voltage (Nominal)  
DC Input Voltage Range  
DC Current at Rated Power  
Continuous Charge Rate at L-L voltage  
Power Factor Corrected Charging  
100 A  
85 A  
150 A  
PF (0.98)  
a.This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of  
Common Connection  
A–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Specifications  
XW Series Overload Capability  
Loads presented to the inverter are seldom constant. Typically, large loads are operated for  
only short periods of time. In order to provide the maximum utility, Xantrex inverters are  
allowed to operate at power levels that exceed their continuous power ratings. This graph  
shows how loads that are larger than the inverter can sustain continuously can be operated  
for useful periods of time.  
The length of time that the inverter can operate at high power is limited by temperature.  
When large loads are run, the inverter’s temperature increases. At the point where more  
heat is created in the inverter than can be dissipated, its ability to operate becomes time  
limited.  
X W 6 0 4 8 A C  
O
v e r lo a d c a p a b ilit y ( L 1 - L 2 ) 2 4 0 V  
6 0  
5 5  
5 0  
4 5  
4 0  
3 5  
3 0  
2 5  
2 0  
1 5  
1 0  
5
0
1
1 0  
1 0 0  
c o  
1 0 0 0  
1 0 0 0 0  
t
[ S  
e
n
d
s )  
X W 6 0 4 8 A C  
O
v e r lo a d c a p a b ilit y ( L 1 - n ) 1 2 0 V u n b a la n c e d A C lo a d  
1 2 0  
1 1 0  
1 0 0  
9 0  
8 0  
7 0  
6 0  
5 0  
4 0  
3 0  
2 0  
1 0  
0
1
1 0  
1 0 0  
1 0 0 0  
1 0 0 0 0  
t
[ S e c o  
n
d
s )  
Figure A-1 XW Series AC Overload Capability  
975-0239-01-01  
A–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Output Power Versus Ambient Temperature  
When the internal temperature of the XW Series exceeds its rated range, the unit reduces it  
energy output to ensure maximum component ratings are not exceeded.  
XW Series Power Derating  
7000  
6000  
5000  
4000  
XW6048-Pwr_der  
XW4548-Pwr_der  
XW4024-Pwr_der  
3000  
2000  
1000  
0
-25  
-15  
-5  
5
15  
25  
35  
45  
55  
65  
75  
Figure A-2 Output Power Versus Ambient Temperature  
XW Series Efficiency  
Inverting Efficiency (Typical)  
100  
95  
90  
85  
80  
75  
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5  
Output Power (kW)  
A–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical Specifications  
Charging Efficiency (Typical)  
100  
95  
90  
85  
80  
Power Factor  
Efficiency  
7
15  
25  
35  
45  
55  
65  
75  
89  
100  
Battery Current (Amps)  
Sell Mode Efficiency (Typical)  
100  
97  
94  
91  
88  
85  
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5  
Expor t Pow e r (k W)  
Mechanical Specifications  
Table A-2 XW Power System Mechanical Specifications  
Model  
XW6048-120/240-60  
XW4548-120/240-60  
XW4024-120/240-60  
Supported Battery Types  
Battery bank size  
Non Volatile Memory  
Display Panel  
Flooded (default), Gel, AGM, Custom  
100–2000 Ah  
Yes  
Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level.  
Three-character display indicates output power or charge current, fault/warning codes.  
On/Off and equalize button  
Multiple Unit Configurations  
Up to 3 parallel units in 120/240 split-phase configuration  
975-0239-01-01  
A–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Table A-2 XW Power System Mechanical Specifications  
Model  
XW6048-120/240-60  
XW4548-120/240-60  
XW4024-120/240-60  
System Network  
Emissions  
Xanbus (publish-subscribe network, no need for hubs or special cards)  
FCC Class B  
Regulatory approvals  
Enclosure Type  
UL 1741 1st Edition: 2005 Version, CSA 107.1-01  
NEMA Type 1 - Indoor (sensitive electronic components sealed inside enclosure)  
32–104 °F (0–40 °C)  
Rated Temperature Range (meets all  
specifications)  
Operational Temperature Range  
Storage Temperature Range  
Inverter Dimensions (H × W × D)  
Shipping Dimensions  
-13–158 °F (-25–70 °C)  
-40–185 °F (-40–85 °C)  
23 × 16 × 9" (580 × 410 × 230 mm)  
28 x 22 ¼ x 10½" (711 x 565 x 267 mm)  
XW Power Distribution Panel  
Dimensions (H × W × D)  
30 × 16 × 8 ¼" (761 × 406 × 210 mm)  
Depth from the wall = 8 ¾" (223 mm)  
XW Power Distribution Panel  
Shipping Dimensions  
36 x 21 ¼ x 13" (914 x 533 x 330 mm)  
Inverter Weight  
Shipping Weight  
125 lb (57 kg)  
132 lb (60 kg)  
115 lb (52 kg)  
122 lb (55 kg)  
115 lb (52 kg)  
122 lb (55 kg)  
Accessories  
Accessory  
Part Number  
Power Distribution Panel  
Conduit Box  
865-1015  
865-1025  
865-1020  
865-1030  
Inverter #2 Connection Kit  
XW-MPPT60-150 Solar Charge Controller  
XW System Control Panel (System Control Panel II) 865-1050  
XW Automatic Generator Start  
Network cables  
865-1060  
3 ft (0.9 m): 809-0935  
5 ft (1.5 m): 809-0936  
7 ft (2.0 m): 809-0937  
10 ft (3.0 m): 809-0938  
14 ft (4.3 m): 809-0939  
25 ft (7.6 m): 809-0940  
50 ft (15.2 m): 809-0941  
75 ft (22.9 m): 809-0942  
Network terminators  
Male (2 per pack): 809-0901  
Female (2 per pack): 809-0905  
A–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
B
Appendix B, “Wiring Diagrams” illustrate the most basic configurations and  
are for reference only. Specific installations may require additional  
equipment to meet national or local electric codes. Ensure all safety  
requirements are strictly followed.  
For......  
See....  
“Single-Inverter System (Backup only)”  
page B–3  
page B–4  
page B–5  
page B–6  
page B–7  
“Single-Inverter System Renewable Energy (Solar)”  
“Single-Inverter System Renewable Energy (Wind or Hydro)”  
“Dual-Inverter System Renewable Energy (Solar)”  
“Dual-Inverter System Renewable Energy (Wind or Hydro)”  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B–2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Single-Inverter System (Backup only)  
Figure B-1 Single-Inverter System (Backup only)  
975-0239-01-01  
B-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
Single-Inverter System Renewable Energy (Solar)  
Figure B-2 Single-Inverter System Renewable Energy (Solar)  
B-4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Single-Inverter System Renewable Energy (Wind or Hydro)  
Figure B-3 Single-Inverter System Renewable Energy (Wind or Hydro)  
975-0239-01-01  
B-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
Dual-Inverter System Renewable Energy (Solar)  
Figure B-4 Dual-Inverter System Renewable Energy (Solar)  
B-6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
Dual-Inverter System Renewable Energy (Wind or Hydro)  
Figure B-5 Dual-Inverter System Renewable Energy (Wind or Hydro)  
975-0239-01-01  
B-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
B-8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate System  
Configurations  
C
Appendix C, “Alternate System Configurations” provides wiring diagrams  
for inverter/charger installations that do not require use of the power  
distribution panel and the XW Conduit Box.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate System Configurations  
DC Grounding for Single-Inverter Systems  
See Table 2-4, “Torque Values for AC Wiring (AC Terminals and Ground Bar),” on  
page 10.  
See Table 2-5, “Torque Values for the Chassis Ground Lug,” on page 10.  
See Table 2-6, “Torque Values for the Inverter Battery Terminals,” on page 10.  
This illustrates an example only. Actual  
ground requirements may vary.  
Figure C-1 DC Grounding for an Inverter only  
C–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Connections for Single Inverter Systems  
Battery Connections for Single Inverter Systems  
Torque connections to the  
inverter DC terminals to 10-  
15 ft./lbs.  
Torque connections to the battery  
terminals per battery manufacturer’s  
recommendations.  
This illustrates an example only. Actual cable requirements may vary.  
Figure C-2 DC Connections to a Single Inverter  
975-0239-01-01  
C–3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate System Configurations  
AC Grounding for Single-Inverter Systems  
This illustrates an example only. Actual ground requirements may vary.  
Figure C-3 Grounding the AC System  
C–4  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Output Wiring to the Inverter AC Distribution Panel  
AC Output Wiring to the Inverter AC Distribution Panel  
Actual wiring requirements may vary.  
Figure C-4 AC Output Wiring to the Inverter AC Distribution Panel  
975-0239-01-01  
C–5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate System Configurations  
Generator Wiring to the Inverter  
WARNING: Shock Hazard  
Before making any electrical connections, ensure both the AC and DC disconnect devices are in  
the OPEN (disconnect) position.  
Important: If the load is too big for the inverter to operate from battery power, do not install the  
load in the inverter powered electrical panel.  
Torque all inverter terminal block  
connections to 25 inch-pounds.  
This illustrates an example only. Actual wiring requirements may vary.  
Figure C-5 Generator Wiring directly to the Inverter  
C–6  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Utility Wiring to the Inverter Input  
Utility Wiring to the Inverter Input  
CAUTION: Damage to Equipment  
The inverter’s AC LOAD terminals must never be wired to any AC source such as a generator  
output or utility panel. This will cause severe damage to the inverter which is not covered under  
warranty.  
Actual wiring requirements may vary.  
Figure C-6 Utility Wiring to the Inverter Input  
975-0239-01-01  
C–7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alternate System Configurations  
Wind or Hydro DC Sources  
Actual wiring requirements may vary.  
Figure C-7 Connecting Wind or Hydro DC Sources  
C–8  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
A
G
AC Connections 2–16  
AC sync cable 2–38  
generator run signal 5–12  
Generator Wiring 2–22  
Ground Bar 2–17  
AC Terminal Block 2–17  
Additional Inverters 2–29  
Automatic Generator Start 1–7, 5–7  
AUX Port 2–23  
Grounding 2–11, 2–12, 4–8  
Grounding the DC System 2–12  
AUX Port Terminal Assignments 2–24  
AUX+12V Voltage Supply 2–23  
AUX-RPO  
H
Hydro C–8  
User Remote Power Off 2–24  
I
installation  
mounting 5–3, 5–5  
planning 5–3  
B
B+ wires 5–12  
battery bank requirements 2–9  
battery cable lugs 2–9  
Battery Cable Requirements 2–9  
Battery Cable Size 2–10  
Battery Temperature Sensor 2–13  
Breaker/Fuse Size 2–10  
Inverter Panel Mounting 2–19  
K
Knockout 2–2  
Knockouts 4–5  
C
L
Charge Controller 4–2  
charge controller 1–6  
Clearance 2–3  
LED Status Indicators  
Inverting 2–26  
Location 2–2  
commissioning 4–14  
Communication Ports 2–16  
Conduit Box 1–4, 2–7  
lugs, battery cable 2–9  
M
Mechanical Specifications A–5  
Mounting 2–3  
D
DC Connections 2–14  
Mounting Bracket 2–4  
mounting template 5–5  
Mounting the Distribution Panel 2–7  
Mounting the Inverter 2–6  
Dual-Inverter System Renewable Energy (Solar) B–6  
Dual-Inverter System Renewable Energy (Wind or Hydro)  
B–7  
E
O
e Emergy (Wind or Hydro) B–5  
external LED wire 5–12, 5–14  
external on/off LED 5–15  
external shutdown switch  
connecting to wiring harness 5–13  
input and return 5–11, 5–13  
overcurrent protection, requirements 2–9  
P
PV Array Requirements  
Array Voltage 4–2  
MPPT Voltage Range 4–3  
F
S
FCC information to the user ii–vi  
Fire safety 2–2  
safety instructions ii–v  
functional test 2–25, 2–39  
Single-Inverter System B–3  
Single-Inverter System Remewab B–5  
Single-Inverter System Renewable Energy (Solar) B–4  
switched B+ wires 5–12  
975-0239-01-01  
IX–1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
T
thermostat  
connecting 5–13  
inputs and returns 5–11, 5–13  
U
User Line Wiring 2–24  
V
verifying network power 5–7, 5–18  
W
web site i–iv  
Wind C–8  
Wire Size and Over-current Protection Requirements 4–9  
Wiring 4–9  
Wiring the Inverter 2–8  
X
Xantrex  
web site iv, i–iv  
XW Inverter/Charger 1–3  
XW System Control Panel 1–6, 5–2  
IX–2  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc.  
800 670 0707 Tel Toll Free in North America  
360 925 5097 Tel direct  
800 994 7828 Fax Toll Free in North America  
360 925 5143 Fax direct  
www.xantrex.com  
Printed in China  
975-0239-01-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weslo Treadmill Wetl15131 User Manual
Whirlpool Microwave Oven WMC10007 User Manual
White Outdoor Snow Blower 1150W User Manual
White Rodgers Thermostat 37 1752 2 User Manual
Wolf Cooktop CT36IU User Manual
XM Satellite Radio Satellite Radio SRXM 001 User Manual
Yamaha Musical Instrument Amplifier JX30B User Manual
Zanussi Oven FM 55 User Manual
Zebra Technologies Label Maker ZT210 User Manual
Zenoah Brush Cutter BC2602DLM User Manual