Blue Universal Thermostat
with Automatic Heat/Cool
Changeover Option
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions for Model:
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATINGTHIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
Model
Programming Choices
7 Day 5/1/1 Day
Non-Programmable
1F95-0671
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
1F95-0671 Universal Thermostat
Description
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (with Aux. or Emergency Heat)
Systems with up to 4 Stages Heat, 2 Stages Cool
Heat Only Systems
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces
Cool Only Systems
Gas or Oil Heat
Electric Furnace
Hydronic (Hot Water) Zone Heat – 2 Wires
Hydronic (Hot Water) Zone Heat – 3 Wires
Wired Remote Temperature Sensor (Indoor or Outdoor)
Dual Fuel Feature (Heat Pump Mode, Outdoor Remote
Required)
SPECIFICATIONS
Electrical Rating:
Battery Power. . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 32°C)
Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage) . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.2°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C)
Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max.
Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . . 4.2"H x 6.4"W x 1.7"D
CAUTION
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
!
Topreventelectricalshockand/orequipmentdamage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
send product containing mercury.
Index
Installation
Page
2
3
5
6
9
10
14
Wiring Diagrams
Thermostat Quick Reference
Installer Configuration Menu
Operating Your Thermostat
Programming
Troubleshooting
PART NO. 37-6979A
0908
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAMS
Refer to equipment manufacturers' instructions for specific
system wiring information. After wiring, see CONFIGURA-
TION section for proper thermostat configuration.
Wiring diagrams shown are for typical systems and describe
the thermostat terminal functions.
TERMINAL DESIGNATION DESCRIPTIONS
Description
Terminal Designation
O/B ........................................... Changeover valve for heat pump energized constantly in cooling and off/heating
Y2............................................ 2nd Stage Compressor
Y............................................ Compressor Relay
G............................................ Fan Relay
RC............................................ Power for Cooling
RH............................................ Power for Heating
C............................................ Common wire from secondary side of cooling (Optional). Required for fault indication, continuous back-
light operation or remote temperature sensor operation 6 Powered closed 3rd wire for 3-wire zone valve
W/E........................................... Heat Relay/Emergency Heat Relay (Stage 1) (3rd Stage Heat in HP2)
W2............................................ 2nd Stage Heat (4th Stage Heat in HP2)
-............................................ Common (DC) for wired remote temperature sensor
S............................................ Frequency signal from remote temperature sensor
+............................................ Power (DC) to remote temperature sensor
L............................................ Compressor diagnostic indicator for systems with diagnostic connection typically found on Heat pump
systems or with Copeland's Comfort Alert
Figure 2 – Single Stage or Multi-Stage System (No Heat Pump)
with Single Transformer
Jumper
L
O/B
W/E
W2
G
RH
C
Y
RC
Y2
System
O
Energized Constantly
in
Blower/
Single
Stage 1
(SS1)
Diagnostic
Indicator
Input
Circulator
Fan Energized
on Call for
Cool (and
Heat if
No Output
No
Optional*
24 Volt
(Com-
mon)
Heat
24 Volt 24 Volt
Cool Mode
Output
Mode
Cool Mode
1st Stage
(Hot)
Heat
(Hot)
Cool
or
1st Stage
System
Malfunction
Switch
Input
B
Energized Constantly
in Heat, Off,
Emergency
Mode
Multi-
Stage 2
(MS2)
Cool
Mode
2nd
Heat Mode
2nd Stage
configured
for Electric
Heat)
Stage
Comfort Alert II Module
NEUTRAL
24VAC
HOT
or Similar System
Diagnostic Module
120VAC
See Module Instructions
for details
* Common connection required for diagnostic or malfunction indication.
CLASS II
TRANSFORMER
Single Stage and Multi-Stage Connections
Refer to equipment manufacturers' instructions for specific
system wiring information.
SINGLE STAGE (SS 1) gas, oil or electric.
MULTI-STAGE (MS 2) gas, oil or electric.
This thermostat is designed to operate a single-transformer
or two-transformer system.
After wiring, see INSTALLER CONFIGURATION section for
proper thermostat configuration.
You can configure the thermostat for use with the following
systems:
Figure 3 – Single Stage or Multi-Stage System (No Heat Pump)
with Two Transformers
Remove Jumper Wire
between RH & RC
Jumper
O/B
W/E
G
RH
RC
L
Y2
Y
C
W2
System
O
Energized Constantly
in
Blower/
Single
Stage 1
(SS1)
Circulator
Fan Energized
on Call for
Cool (and
Heat if
No Output
No
Heat
24 Volt 24 Volt Optional
Diagnostic
Indicator
(Optional)
Cool Mode
Output
Cool Mode
1st Stage
Mode
(Hot) (Hot)
Heat Cool
24 Volt
(Com-
mon)
1st Stage
B
Energized Constantly
in Heat, Off,
Emergency
Mode
Multi-
Stage 2
(MS2)
Cool
Mode
2nd
Heat Mode
2nd Stage
configured
for Electric
Heat)
Stage
NEUTRAL
24VAC
HOT
120VAC
COOLING
NEUTRAL
120VAC
HEATING
24VAC
HOT
CLASS II
TRANSFORMER
CLASS II
TRANSFORMER
3
Download from Www.Somanuals.com. All Manuals Search And Download.
WIRING DIAGRAMS
Figure 4 – Heat Pump Systems
Jumper
+W/E
RC
C
Y
Y2
+W2
G
RH
L
O/B
System
Heat Mode - 2nd
Heat Mode - 3rd
Stage, Emergency Stage, Emergency
Mode - 1st Stage Mode - 2nd Stage
O
Blower/
+Note: Dual Fuel option
de-energizes Heat mode
stage 1 (compressor)
when auxiliary heat
is energized
+Note: Dual Fuel option
de-energizes Heat mode
stage 1 (compressor)
when auxiliary heat
is energized
Heat Pump 1
(HP1)
Energized in
No
Circulator Fan
Energized on
Call for Heat
or Cool.
Optional*
24 Volt
(Com-
mon)
Cool Mode
Output
Diagnostic
Indicator
or System
Malfunction
Switch
Heat and
24 Volt 24 Volt
Cool Mode
1st Stage
(Hot)
Heat
(Hot)
Cool
B
Heat Mode - 3rd
Heat Mode-4th
Set Elect/Gas
Option for
Emergency
mode
2nd
Energized in
Heat, Off,
Emergency
Mode
Heat Pump 2
(HP2)
(Compressor)
Stage. Emergency
Stage, Emergency
Stage
(Com-
pressor)
Mode - 1st Stage Mode - 2nd Stage
+Note: Dual Fuel option +Note: Dual Fuel option
de-energizes Heat mode de-energizes Heat mode
stage 1 (compressor)
when auxiliary heat
is energized
stage 1 (compressor)
when auxiliary heat
is energized
Comfort Alert II Module
or Similar System
NEUTRAL
Diagnostic Module
120VAC
24VAC
HOT
See Module Instructions
for details
* Common connection required for diagnostic or malfunction indication.
+ Dual Fuel option, if selected turns off compressor(s) when Auxiliary stages energize.
CLASS II
TRANSFORMER
Heat Pump Connections
HEAT PUMP TYPE 1 (HP 1). Single stage compressor
system; gas or electric backup.
Refer to equipment manufacturers' instructions for specific
system wiring information.
HEAT PUMP TYPE 2 (HP 2). Multi-stage compressor or two
compressor system with gas or electric backup.
This thermostat is designed to operate a single-transformer
or two-transformer system.
After wiring, see INSTALLER CONFIGURATION section for
proper thermostat configuration.
You can configure the thermostat for use with the following
systems:
Figure 5 – 3-Wire (SPDT) Heat Only Zone Valve Wiring
Jumper
6
W
G
RH
C
Y
RC
System
Single Stage
3-wire
Zone Valve
application
Constant
24 Volt
(Com-
mon)
24 Volt
(Hot)
Cool
Blower/Circulator
Fan Energized
Closes
Valve
(6)
Opens
Valve
(4)
24 Volt
(Hot)
Heat
(5)
NEUTRAL
24VAC
HOT
120VAC
CLASS II
TRANSFORMER
4
Download from Www.Somanuals.com. All Manuals Search And Download.
THERMOSTAT QUICK REFERENCE
Home Screen Description
Figure 5 – Home Screen Display
Room
Temperature
Setting
Temperature
Battery Level Indicator
Indicating the current power level
of the 2 “AA” batteries:
Full power remaining.
Half power remaining
Change
The batteries should
be replaced at this time with 2 new
premium brand “AA” Alkaline batteries.
(See page 2 for more details)
Fan
Indicator
System
Indicator
Figure 6 – Programming & Configuration Items
8
2
4
12
3
10
11
1
9
5
7
6
13
Programming and Configuration Items
7
8
Displays "Run Schedule", "Schedule", or "Menu".
Displays "Save" when Cool SavingsTM is working.
"System On" indicates when heating or cooling stage
is energized. "System On +2" indicates when addi
tional stages are on.
1
Displays "Heat Pump" when system is configured
as Heat Pump thermostat.
9
2
The word "Hold" is displayed when the thermostat is
in the HOLD mode. "Temp" is displayed when the
thermostat is in a Temporary HOLD mode.
Displays "Hold" in programmable mode when not in
Hold mode. Displays Light Bulb in non-program-
mable mode.
10
Displays "Change Filter" when the system has run for
the programmed filter time period as a reminder to
change or clean your filter.
3
Initially displays "Auto Sched". If Auto Schedule had
been used or disabled, then it displays "Cool Savings"
when in the Cool Mode. Displays "Copy" in Schedule
mode and "Fan" in Fan Schedule mode.
11
4
Displays "Set" for setpoint when in Run Program mode.
"Call For Service" indicates a diagnostic fault in the
heating/cooling system, it does not indicate a fault in the
thermostat.
12
Displays System Mode (Heat, Em, Auto, Cool, Off)
or Time in menu mode.
5
Displays Fan mode (On, Auto) "Prog FAN On" or
"Run Sched" in Menu mode.
6
"Keypad Lockout" in Menu mode when selecting key-
pad Lockout or in RUN when a keypad Lockout is active.
13
5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER/CONFIGURATION MENU
Thermostat must be in Heat, Cool or Auto. Press and hold the Menu button for at least 5 seconds. The display will show item
#1 in the table below. Press Menu to advance to the next menu item. Press
or
to change a menu item options.
INSTALLER/CONFIGURATION MENU
Menu HP SS Press
Displayed
(Factory Default)
Comments
Press
to select from listed
options
or
Ref.
Button
1
1
1
MENU
(MS 2)
HP 1, HP 2, SS 1
Selects Multi-Stage (MS 2 No Heat Pump),
Heat Pump 1 (HP 1, 1 compressor),
Heat Pump 2 (HP 2, 2 compressor or 2
speed compressor), or Single Stage (SS 1)
2
3
2
3
2
3
MENU (GAS) for SS or MS
(ELE) for HP
ELE
GAS setting: furnace controls the blower
ELE setting: thermostat controls the blower
MENU
CS (3)
0, 1, 2, 4, 5, 6
Selects Cool Savings
Value 1 (low) to 6 (high),
Value 0 disables feature
4
5
4
–
4
5
MENU
MENU
E (On)
OFF
Selects Energy Management Recovery (EMR)
On or OFF.
CR Heat (ME)
SL, FA
Selects Adjustable Anticipation, cycle rate, Heat
(This item only appears when MS 2 or SS 1 is
selected above)
6
7
5
6
–
6
MENU
MENU
CR Heat Pump
(ME)
SL, FA
Selects Adjustable Compressor Anticipation
(Heat Pump) This item only appears when
HP 1, HP 2 is selected above
CR Cool (ME)
or
CR AU (FA)
SL, FA
SL
Selects Adjustable Anticipation, cycle rate, cool
(when MS 2 or SS 1 is selected above.) or
Selects the cycle rate for Auxiliary stage (when
HP 1 or HP 2 is selected above)
8
9
7
8
7
8
MENU
MENU
CL (OFF)
CL On
Compressor Lockout Time
Em Heat, Auto
Cool Off
Heat Cool Off,
Heat Off with Fan icon,
Heat Off without Fan icon
Cool Off, Auto Off
System Mode Configuration
with Automatic Changeover capability
or
Heat, Auto,Cool Off
10
11
9
9
MENU
dL (On)
0
dL OFF
Selects Display Light On or OFF
10 10 MENU
1 HI, 2 HI, 3HI, 4 HI,
Adjustable Ambient Temperature Display
(current temperature) 1 LO, 2 LO, 3 LO, 4 LO
12
13
11 11 MENU
12 12 MENU
°F
°C
Selects Fahrenheit/Celsius Temperature Display
(On) b
OFF
May select Beeper OFF to stop audible
key feedback
14 13 13 MENU
15 14 14 MENU
P (7)
3, 0
2
Defaults 7-day programming (P7) but non-
programmable (0) or 5/1/1 programming (P3)
is available on most models.
PS (4)
Selects Program periods per day:
4 = Morn, Day, Eve, Night
2 = Day, Night
16
17
18
15 15 MENU
16 16 MENU
Heat AS (On)
Cool AS (On)
Heat FA (On)
OFF
OFF
OFF
Automatic Schedule for heat mode
Automatic Schedule for cool mode
17
–
MENU
Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 config.
19
20
18
–
MENU
Cool FA (On)
OFF
Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 config.
19 17 MENU
MENU
Remote (OFF)
On
Selects Remote Sensor On/OFF
Remote
(In)
Outdoor
Selects Remote Sensor to outdoor
NA is Remote Sensor OFF
MENU
Indoor Loc
(On)
OFF
Selects Local Sensor (in thermostat) to OFF.
N/A if Remote is selected to Outdoor
6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER/CONFIGURATION MENU
21
22
20 18 MENU
21 19 MENU
dS (On)
Off
Selects Automatic Daylight Saving Time option
(OFF)
Keypad Lockout
L, P, Limit
Selects one of 3 Keypad Lockout configurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature Range
MENU
22 20 MENU
23 21 MENU
(000)
Keypad Lockout
1-999
L 62 to L 98
L 46 to L 82
06-50
Selects personal lockout code. 000 is NOT A
VALID CODE.
23
24
25
L Heat
(99)
Select Limited HEAT Range Temperature
L Cool
(45)
Select Limited COOL Range Temperature
24
–
MENU
CO
(05)
Selects outdoor Compressor OFF temperature
(Balance Point temperature). 05 disables fea-
ture. Outdoor Remote required
MENU
MENU
MENU
(dF)
EA
Selects between dF (dual Fuel) or EA (Electric
Aux) only available if CO is greater than 05
Cd
(60)
Selects Compressor delay OFF time in seconds
(only if dF is selected)
26
27
25
–
AO
(80)
Selects AO (Auxiliary OFF) temperature. Fea-
ture disabled if 80 is selected. Outdoor Remote
required
26 22 MENU Change Filter (OFF)
MENU Change Filter (200 h)
On
Selects Filter Change-out Indicator On or OFF.
25-1975 h
Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
28
27 23 MENU
MENU
(OFF)
Change UV Lamp
On
Selects UV Lamp
Timer: On/OFF
(350)
Change UV Lamp
25-1975
Selects number of Days between
changing UV Lamp
29
30
28 24 MENU
29 27 MENU
Cool On (o)
Heat On (b)
Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal
RUN SCHED
Returns to Normal Operation
1) This control can be configured for:
thermostat displays but the reduction in humidity will allow
comfort at the slightly higher temperature.
MS 2 – Multi-Stage System (no heat pump)
HP 1 – Heat Pump with one stage of compressor
HP 2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup
SS 1 – Single Stage System
To turn this feature on in the Cool mode press Cool
Savings. The display will show “Save” next to the set-
point temperature. When Cool Savings is making adjust-
ments to the room temperature display “Save” will be
flashing and the displayed room temperature may vary
within the adjustment range you selected.
2) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat.
If "Save" is not displayed and this feature is OFF, no
change will occur when the cooling system is continuously
running during periods of high demand.
3) Select Cool Savings™ value – Selects the amount of
adjustment for the Cool Savings™ feature in Cool mode
with 1 (1°) being the least amount of adjustment and 6
(6°) being the most amount of adjustment. Default value
is 3. Cool Savings is an optional energy saving feature that
can reduce your cooling costs. It is based on the principal
that lower indoor humidity makes a slightly higher tem-
perature feel more comfortable. Cool Savings operates
during periods of high demand which normally occur on
the hottest summer days when a cooling system may run
for hours to reach the thermostat setting. Long cooling
run times also lower the indoor humidity. Cool Savings,
very slowly, adjusts the setpoint temperature to make the
setpoint closer to the displayed room temperature, to a
maximum of the number of degrees you select. Adjust-
ing the setpoint temperature over a long cooling run time
allows the system to reach your set temperature and turn
off. The room temperature will actually be higher than the
4) Energy Management Recovery: (this step is skipped if
configured to be non-programmable).
Energy Management Recovery (E) On enables the ther-
mostat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start approximately 5 minutes early
(15 minutes for heat pump) for every 1° of temperature
required to reach setpoint.
Example: E On is selected and your heating is pro-
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65°, the difference between 65° and 70° is
5°. Allowing 5 minutes per degree, the thermostat setpoint
will change to 70° at 6:35 AM. Cooling allows approxi-
mately 15 minutes per degree, because it takes longer to
reach set temperature.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER/CONFIGURATION MENU
5, 6 & 7) Cycle Rate Selection – The factory default setting for 18 & 19) Select Fast Second Stage ON or OFF – Heat
pump or Multi-stage only, in the run mode, with the fast
Heat feature enabled (FA Heat On), if the Heat setpoint
temperature is manually raised by 3°F (2°C) or more
Heat and Cool modes, SS1, MS2, is medium cycle (ME).
For Heat Pump, HP1, HP2, the default setting is medium
(ME). For Emer (Aux) the default setting is fast cycle (FA).
above the actual temperature using
the second stage
To change cycle rate, press the
or
button.
will energize immediately. With FA OFF, second stage will
not energize until the setpoint temperature is 1°F or more
above actual temperature for more than ten minutes. The
Fast Cool feature (FA Cool) provides the same controls
when the setpoint temperature is lowered.
Cycle rate differentials for different settings are:
MODE
Fast
FA
Medium Slow
ME
SL
Heat (SS1, MS2)
Cool (SS1, MS2)
Heat Pump (HP1, HP2) 0.9°F
Emer (HP1, HP2) 0.6°F
0.4°F
0.9°F
0.6°F
1.2°F
1.2°F
-
1.7°F
1.7°F
1.7°F
1.7°F
20)Select Remote Temperature Sensor – This control
allows one wired remote temperature sensor (indoor,
F145-1328, or outdoor, F145-1378) be connected to it and
indicates the measured temperature in clock digits. This
menu enables you to select the remote sensor and also
configure it as indoor or outdoor temperature sensor. Fac-
tory default is off. Select Remote On and Remote in (for
indoor) or Outdoor Remote.
8) Select Compressor Lockout CL OFF or ON – Selecting
CL ON will cause the thermostat to wait 5 minutes be-
tween cooling cycles. This is intended to help protect the
compressor from short cycling. Some newer compressors
already have a time delay built in and do not require this
feature.Your compressor manufacturer can tell you if the
lockout feature is already present in their system. When
the thermostat compressor time delay occurs, it will flash
the setpoint for up to five minutes.
Local Temperature Sensor disable – This is applicable
only when indoor remote temperature sensor is enabled.
Factory default is Loc On.You can make it Loc Off if you
desire by using
or
buttons. Then, only the indoor
remote temperature reading will be used for control
9) System Mode Configuration – This thermostat is config-
ured for Heat and Cool (SYSTEM switch with Cool Off
Heat) default. It can also be configured for Heat and Cool
with Auto changeover (Heat, Auto, Cool, Off), Heat only
with fan (Off Heat), Heat only without fan, Auto only
(Auto Off), and Cool only (Cool Off).
21)Select Daylight Saving Time Calculation – This feature
will allow the thermostat to calculate the DST automati-
cally and apply it to the Real Time Clock display. Default
On. Use
or
touch keys to select the feature OFF.
22)Keypad Lockout – This step allows you to select the type
of lockout or limited range security required. If no lock-
out or limited range security is required, press MENU to
advance the menu.
10)Select Backlight Display – The display backlight improves
display contrast in low lighting conditions. When the "C"
terminal is powered, selecting backlight CdL ON will keep
the light on continuously. Select backlight OFF will turn the
light on momentarily after any button is pressed. When the
"C" terminal is not powered, the light will be on momentarily
after any button is pressed no matter whether the backlight
is selected ON or OFF.
Three security settings are available in this menu item.
Use the
or
buttons to select the lockout desired.
Lockout selections are:
"Keypad Lockout and L" = Total Lockout. Total Lockout
11)Select Temperature Display Adjustment 4 LO to 4 HI –
Allows you to adjust the room temperature display up to 4°
higher or lower. Your thermostat was accurately calibrated
at the factory, but you have the option to change the dis-
play temperature to match your previous thermostat. The
current or adjusted room temperature will be displayed.
locks all keys.
"Keypad Lockout and P" = Partial Lockout. Partial Lock-
out allows only the
your set temperature limits.
or
buttons to operate within
"Keypad Lockout and Limit" prevents changing the
temperature limits in the Configuration Menu.
12)Select F° or C° Readout – Changes the display readout
to Celsius or Fahrenheit as required.
Press Menu after selecting the type of lockout.
13)Select Audio Prompting (Beeper) On or Off – Factory
default setting is on (b, On). If you wish to turn off the
beeper select OFF.
"Keypad Lockout Combination Number Selection"
Display will read "000" "Keypad Lockout". Note: "000" is
not a valid combination choice.
14)Program Options: Selects configuration for 7 day (7) or
5/1/1 day (3) programming or non-programming (0) mode.
The default setting is 7, indicating 7 day programming.
The programs per week can be changed to 3 or 0 by
Skip this step and continue through the remaining configu-
ration menu items if you require an Air Filter Change out
indicator or Humidifier Pad Change out indicator by press-
ing the MENU button to advance.
pressing the
or
buttons. A selection of 0 days for
non-programmable will eliminate the need for EMR, and
that step in the menu will be skipped.
Return to this point when you are ready to start your
selected lock-out and continue by:
15)Program Steps per day – This control can be configured
for 4 or 2 program steps per day. Default is "4 PS" and
can be toggled between 4 PS and 2 PS.
Press
. Display will read "001".
or buttons to select your keypad lock-
Pressing
out combination number.
16 & 17) Select Automatic Schedule – With just one touch
of the Auto Schedule key this feature allows you to pro-
gram a desired comfort temperature into all the program
periods along with a 6° set back for night periods of both
Heat and Cool programs. Factory default is "On" for both.
When Heat AS On and Cool AS On are activated while
in Heat or Cool mode, select desired setpoint temperature
and press Auto Schedule. This value will be copied into
all the morning, day and evening program periods. The
night program periods will have a 6°F set back.
Record the number you select for future use.
Press MENU or RunSched to exit the menu. The security
feature you select will start. The system button will remain
active for 10 seconds to allow setting Heat, Off, Cool or
Auto.
23)Limited Heat Range – This feature provides a maximum
setpoint temperature for heat. The default setting is 99°F.
It can be changed between 62°F and 98°F by pressing the
or
button.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER/CONFIGURATION MENU
24)Limited Cool Range – This feature provide a minimum
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
clean your air filter. When "Change Filter" is displayed,
press MENU or RUN SCHED button to clear the display
and restart the time to the next filter change.
or
button.
28)Change UV Lamp – This feature allows the thermostat to
display the words "Change UV Lamp" (Call for Service
of UV bulb) after a set time of UV bulb operation. This is
a reminder to maintain your UV system at optimum level
of operation. When enabled the factory set interval for
"Change UV Lamp" to be displayed is 350 days of UV
bulb operation and can be adjusted in 25 day increments.
This should be adjusted with respect to the bulb's recom-
mended maintenance schedule.
25)Select Compressor Off (CO) Feature Using Outdoor
Sensor – This feature is applicable only in heat pump
modes and with an outdoor sensor installed and enabled.
When CO is enabled by selecting a temperature >05°F
(-15°C), the thermostat will use the outdoor sensor tem-
perature to determine when to switch to gas heat and shut
down the compressor.
When the outdoor temperature goes below the selected
temperature, the gas heat will begin. Default is 05 (Off or
disabled), but can be set in the range of 06 to 50 using the
When "Change UV Lamp" is displayed, you can clear it
by pressing MENU.
or
buttons.
29)Select Reversing Valve Output – The O/B option is
factory set at "O" position. This will accommodate the
majority of heat pump applications, which require the
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed
with this thermostat requires a "B" terminal, to energize
the changeover relay in HEAT, the O/B option should be
set at "B" position.
Select dF or EA – If CO is set > 05°F (-15°C), select dF
(default) if your system has a fossil fuel (gas or oil) Auxil-
iary heat. Select EA if your system has Electric Auxiliary
heat and you want the compressor to continue to run
while calling for Auxiliary stage.
Select Compressor Delay (Cd) – If dF is selected, after
the auxiliary heat is turned on, the compressor(s) shut
down is delayed for the time selected (in seconds). This
delay is factory set to 60, but can be set in the range of 0
to 99 using
or
buttons.
26)Select Auxiliary Off (AO) – This feature is applicable only
in heat pump modes and with an outdoor sensor installed
and enabled. Select the temperature that will inhibit the
auxiliary heating stage. As long as the outdoor tempera-
ture is above the setpoint, the auxiliary heat will not turn
on. The default setting is 80, but can be set in the range of
35 to 79. A setting of 80 disables this feature.
27)Select Filter Replacement Reminder and Set Run Time
Select the "Change Filter" reminder On or OFF. If se-
lected On, press MENU to select the time period from 25
to 1975 hours in 25 hours increments. In a typical system,
200 hours (default) of run time is approximately 30 days.
After the selected time of blower operation, the thermostat
will display "Change Filter" as a reminder to change or
OPERATINGYOUR THERMOSTAT
Check Thermostat Operation
NOTE
CAUTION
!
Do not allow the compressor to run unless the com-
pressor oil heaters have been operational for 6 hours
and the system has not been operational for at least
5 minutes.
To prevent static discharge problems, touch side of
thermostat to release static build-up before touching
any keys.
Heating System
1. Press SYSTEM button to select Heat. If the auxiliary
heating system has a standing pilot, be sure to light it.
If at any time during testing your system does not operate
properly, contact a qualified service person.
2. Press
to adjust thermostat setting to 1° above room
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
temperature. The heat pump system should begin to oper-
ate. The display should show “System On”. However, if
the system configuration is set to HP1 or HP2 and setpoint
temperature display is flashing, the 5 minute compressor
lockout feature is operating (see Configuration menu,
item 11).
3. Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP2 or HP1,
the auxiliary heat system should begin to operate and
the display will show “System On +2”.
1. Turn on power to system.
2. Press FAN button to select ON. The blower should begin
to operate.
3. Press FAN button to select AUTO. The blower should
stop immediately.
4. Press
to adjust the thermostat below room tempera-
ture. The heating system should stop operating.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATINGYOUR THERMOSTAT
Choose the System Setting
Emergency System
EM bypasses the Heat Pump to use the heat source wired to
terminal W/E on the thermostat. EM is typically used when
compressor operation is not desired, or you prefer back-up
heat only.
(Cool, Off, Heat, Em, Auto)
Press the SYSTEM button to select:
Heat: Thermostat controls only the heating system.
Off: Heating and Cooling systems are off.
Cool: Thermostat controls only the cooling system.
Auto: Auto Changeover is used in areas where both heating
and cooling may be required on the same day. AUTO allows
the thermostat to automatically select heating or cooling
depending on the indoor temperature and the selected heat
and cool temperatures. When using AUTO, be sure to set the
Cooling temperatures more than 1° Fahrenheit higher than
the heating temperature.
1. Press SYSTEM button to select EM. “EM” will flash
on the display.
2. Press
to adjust thermostat setting above room
temperature. The Emergency heating system will begin to
operate. The display will show "System On" and flashing
"EM" to indicate that the Emergency system is operating.
3. Press
to adjust the thermostat below room tempera-
ture. The Emergency heating system should stop operat-
ing.
Em: Setting is available only when the thermostat is config-
ured in HP1 or HP2 mode.
Manual Operation for
CAUTION
To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
!
Non-Programmable Mode
Press the SYSTEM button to select Heat or Cool and use
the buttons to adjust the temperature to your desired setting.
After selecting your desired settings you can also press the
SYSTEM button to select AUTO to allow the thermostat to
automatically change between Heat and Cool.
Cooling System
1. Press SYSTEM button to select Cool.
Manual Operation (Bypassing the Program)
Programmable Mode
2. Press
to adjust thermostat setting below room tem-
Adjust the temperature wherever you like and then press
the HOLD button. This will override the program. The HOLD
feature bypasses the program and allows you to adjust the
temperature manually, as needed. Whatever temperature
you set in HOLD will be maintained 24 hours a day, until you
manually change the temperature or press Run Schedule to
cancel HOLD and resume the programmed schedule.
perature. The blower should come on immediately on high
speed, followed by cold air circulation. The display should
show “System On”. If the setpoint temperature display is
flashing, the compressor lockout feature is operating (see
Configuration menu, item 5).
3. Adjust temperature setting to 3° below room temperature.
The second stage cooling should begin to operate and
the display should show “System On +2”.
Program Override (Temporary Override)
4. Press
to adjust the temperature setting above room
temperature. The cooling system should stop operating.
Press the
or
button to adjust the temperature. This
will override the temperature setting for a two hour override
period.
Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the
fan only when the heating or cooling system is on.
Fan On selection runs the fan continuously for increased air
circulation or to allow additional air cleaning.
Example: If you turn up the heat during the morning program,
it will be automatically lowered later, when the temporary hold
period ends. To cancel the temporary setting at any time and
return to the program, press Run Schedule.
If the SYSTEM button is pressed to select AUTO the
thermostat will change to Heat or Cool, whichever ran last. If
it switches to heat, but you want cool, or it changes to cool,
but you want heat, press both buttons simultaneously to
change to the other mode.
Fan Prog On indicates that the fan is programmed to be on
for the entire period. The Prog Fan On can be overridden
to have the fan cycle with the system. Press the FAN but-
ton to change the fan to Auto. The fan programming will be
overridden until the next program period begins or until Run
Schedule is pressed.
PROGRAMMING
7) Press Time once again to display month.
Set Current Time and Day
8) Press and hold either the
reach the correct month.
or
button until you
1) Press Menu button to enter installer menu. Then press
Time button once to indicate hour & AM or PM designa-
tion in clock display.
9) Press Time once again to display date of the month
along with day of the week at top row (which is automatic).
2) Press and hold either the
or
button until you
10) Press and hold either the
or
button until you
reach the correct hour and AM or PM designation.
3) Press Time again to display minutes only in clock
display.
4) Press and hold either the
reach the correct minutes.
reach the correct day of the month and day of the week
is automatically calculated and displayed at the top row.
11) Press RunSched button once; now the display will show
the correct time and room temperature.
or
button until you
5) Press Time once again to display year.
6) Press and hold either the
reach the correct year.
or
button until you
10
Download from Www.Somanuals.com. All Manuals Search And Download.
PROGRAMMING
Energy Saving Factory Pre-Program
The 1F95-0680 thermostats are programmed with the energy saving settings shown in the table below for all days of the week.
If this program suits your needs, simply set the thermostat clock and press the RunSched button.
The table below shows the factory set heating and cooling schedule for all days of the week.
* Wake Up
(Morn)
Leave For Work
(Day)
* Return Home
(Eve)
Go To Bed
(Night)
Heating
Program
6:00 AM
6:00 AM
70°F
75°F
8:00 AM
8:00 AM
62°F
83°F
5:00 PM
5:00 PM
70°F
75°F
10:00 PM
10:00 PM
62°F
78°F
Cooling
Program
* You can eliminate these two program periods in the configuration menu (reference #15) if the building is occupied all day.
Day period will change to 6:00 AM and 70° and can be programmed as required.
PlanningYour Program – Important
The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
The 1F95-0680 comes configured for 7 day programming and can also be configured for 5+1+1 programming (see configura-
tion section).
Factory settings are listed on Monday, Saturday and Sunday. If you are re-programming a 5+1+1 day schedule, pencil in your
own times and temperatures directly below the factory times and temperatures.
If you are re-programming a 7 day schedule, fill in all lines with the times and temperatures you want.
Keep the following guidelines in mind when planning your program.
• In Heating, lower temperatures will save energy.
• In Cooling, higher temperatures will save energy.
• If you plan on using Auto Changeover, do not program the heating temperature higher than the cooling temperature.
Worksheet for Re-Programming 5+1+1 and 7 Day Program
Heating
Program
Wake Up
(Morn)
Leave For Work
(Day)
Return Home
(Eve)
Go To Bed
(Night)
Fan
Fan
Fan
Fan
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
MON
TUE
WED
THU
FRI
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
SAT
SUN
Cooling
Program
Wake Up
(Morn)
Leave For Work
(Day)
Return Home
(Eve)
Go To Bed
(Night)
Fan
Fan
Fan
Fan
6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
MON
TUE
WED
THU
FRI
6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
SAT
SUN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
PROGRAMMING
Automatic Daylight Saving Calculation
Enter the Cooling Program
The Real Time Clock will adjust automatically for daylight sav- 1) Press the SYSTEM button until the Cool icon appears.
ings time, in the following manner:
2) Follow Enter Heating Program instructions for entering
Increment one hour at 2 AM on the second Sunday of March
and decrement one hour at 2 AM on the first Sunday of No-
vember. (New DST effective 2007).
cooling times and temperatures.
Automatic Schedule
This feature provides a method to program every day with the
most popular time and temperature settings using one key.
For this feature to be available, the Auto Schedule options
(Installer/Configuration menu item 16, AS Heat, or item 17,
AS Cool) must be selected On.
The daylight saving feature can be enabled or disabled in
installer configuration menu. Default is DS ON (enabled).
After entering installer configuration mode, momentarily
press MENU button until the display indicates dS (in actual
temperature digits) and on (default – in clock digits).
or
To use Auto Schedule, press RunSched to be sure you are in
normal operating mode. In SYSTEM Heat mode, use the keys
to select your “Comfort Temperature”. When your “Comfort
Temperature” is selected, press Auto Sched button. The
Auto Schedule key will disappear to indicate that the Auto
Schedule command has been accepted.
buttons will toggle display and operation from on to OFF.
Programming Tip: Copy Program
When programming your thermostat, you may copy the pro-
gram from one day to another day or group of days using the
Copy key. In 7 day programming mode, a day can be copied
to another day or all six other days. In 5/1/1 day programming
mode the weekday (Mon – Fri) program can be copied into
Sat and Sun or either Sat or Sun.
In Heat mode the thermostat will maintain your “Comfort Tem-
perature” during the Morning, Day and Evening periods and
setback 6° for the Night. Morning period will begin at 6:30 AM
and Night period will begin at 10:30 PM.
To copy a program from one day to another:
1) In Set Schedule mode, enter the program for the day or
select the day you wish to copy by pressing Advance Day.
2) Press Copy. On the display, "Copy" will begin to flash.
The day of the week being copied will show.
3) Press Advance Day. The day being copied will be indi-
cated and the other days will be flashing.
To set the Auto Schedule temperature for Cool mode, press
SYSTEM to change the mode to Cool and repeat setting the
temperature. In Cool mode, the thermostat will maintain your
selected “Comfort Temperature” continuously.
The “Comfort Temperature” can be temporarily overridden
by changing the setpoint temperature using the
or
4) If you wish to copy to all days skip to next step or press
Advance Day until the day you wish to copy to is flashing.
5) Press Copy. “Copy” will be on, the day you copied from
will disappear and the day(s) you copied to will be on.
6) If you wish to copy this same program into other days,
press Copy and repeat steps 2 through 5.
buttons. Once Auto Schedule has been set and the key has
disappeared, it can be reset in the Installer/ Configuration
menu.
Entering Fan Program
The fan can be programmed to turn on at the beginning of a
period and remain on through the whole period. In RunSched
mode when the FAN switch indicates Prog Fan On the fan is
programmed to be on for the period.
7) Press RunSched to return to normal operation.
Fill in the blank schedule on the next page then:
Enter the Heating Program
1) Press System button to select either Heat or Cool.
2) Press Menu button and then press Fan button to the right
of the display.
3) The top of the display will show the day(s) being pro-
grammed. The first period to be programmed will appear.
4) Press the Fan button to change from Auto to Prog.
5) Press the Fan button to the right of the display to change
to the next period.
6) Repeat steps 4 and 5 to program the fan for all periods of
the day.
7) Press Fan to advance to the next day of the week and
repeat steps 4 through 7 to program the fan for all days of
the week.
1) Press SYSTEM button to select Heat in the system switch
area indicating the active mode being programmed.
2) Press the Menu button and then press Schedule.
3) The top of the display will show the day(s) being pro-
grammed. The first period to be programmed will appear.
The set temperature will also be displayed and the time
will be flashing to indicate that the time can be changed.
4) Press
or
buttons to adjust the start time for the
period. The time will change in 15 minute increments.
5) Press the System Time button to change to the tempera-
ture flashing.
6) Press
or
buttons to change the temperature to
your selected temperature for the first heating period.
7) After you have set the time and temperature for the first
period, press Schedule to advance to the next program
period.
8) Repeat steps 4 through 7 until all of the program times
and temperatures are entered for all program periods for
that day.
9) Press Schedule button to change to the next day and
repeat steps 4 through 8 until all program days and peri-
ods are entered.
10)When programming is complete and all of the times and
temperatures match your desired heating schedule, press
RunSched. The thermostat will now run your program.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
PROGRAMMING
The example shows that the weight selected would prioritize
the overall averaged temperature between the two sensors.
The high weight selection caused the remote sensor to have
a higher influence in the calculated temperature average than
the local sensor and the low weight selection caused the
remote sensor to have less influence.
Wired Remote Temperature Sensing
One remote temperature sensor can be installed indoor or
outdoor and connected to the thermostat by a maximum
cable length of 100 meters (300 feet). Terminals +, S and - on
the terminal block allow connection of the remote sensor.
The thermostat must have 24 VAC Common connection to
terminal C for the remote sensor to operate. The remote sen-
sor can be enabled or disabled in the Installer/Configuration
menu, item 20.
Dual Fuel Temperature Setpoint
When the thermostat is configured for Heat Pump mode
and an outside remote sensor is installed and enabled, the
thermostat can monitor the outside temperature to determine
when to switch to auxiliary heat and shut down the compres-
sor. This eliminates the need for a fossil fuel kit.
When remote sensor, Remote, is selected Off (factory de-
fault), no remote sensor is enabled. When remote sensor is
selected On, the next step is to select the remote as indoor,
Remote In, or outdoor, Remote Outdoor. If the remote is se-
lected as Remote In, an additional step will be to select if the
temperature shown on the display will be from the thermostat,
Loc On, or the remote sensor Loc Off.
The Compressor Off temperature (CO) set in the configura-
tion menu, item 25, will determine when the auxiliary heat will
start and the compressor will shut off. Default setting is 05°F.
-15°C (feature disabled) and can be set for 06 to 50°. When
the outside temperature falls to the selected temperature, the
auxiliary heat system will begin.
In normal operation, when a remote sensor is enabled the
time digits of the display will alternate between the time and
the remote temperature for three seconds each. Above the
remote temperature will be "Remote", for indoor sensor or
"Outdoor Remote", for outdoor sensor. If the remote sensor
is an indoor sensor and the local display has been disabled,
the temperature displayed as the room temperature will be
the remote sensor temperature.
The auxiliary heat system can be fossil fuel (dF) or electric
heat (EA). This is selected after CO is set greater than 05°. If
the auxiliary heat is fossil fuel, (df), a delay time for the com-
pressor shut down (Cd) can be selected. Default for this delay
is 60 seconds but can be set from 0 to 99 seconds. If EA is
selected, there is no selection for Cd because the compres-
sor will shut down immediately.
Sensing Range:
Outdoor temperature range is -40oF to 140oF
Indoor temperature range is 32oF to 99oF
Weighing of Remote Reading:
The thermostat will weight or average the temperature of the
indoor remote sensor with the local sensor in the thermostat
for each program period. The averaging will be active only
when the local sensor and the indoor remote sensor are both
functional and enabled in the Installer/Configuration menu.
When the thermostat is in the Set Schedule mode, the weight
of the indoor sensor will be shown in the current temperature
digits of the display. The weight will show as A2 (average and
default), H4 (high) or L1 (low). Pressing the
or
but-
tons at the same time will change the weight for the program
period. The weight of the thermostat sensor is fixed.
In normal operation of the thermostat, the current tempera-
ture displayed will be the weighted average of the local
sensor and the remote sensor using the formula (local sensor
weight x local sensor temperature) + (remote sensor weight x
remote sensor temperature) / (local sensor weight + remote
sensor weight).
Example: Local sensor temperature is 80° and the remote
sensor is 70°.
If weight is selected H4, the averaged temperature of 72° will
be displayed.
(1 x 80) + (4 x 70) / 5 = 72°
If weight is selected A2, the average temperature of 73° will
be displayed.
(1 x 80) + (2 x 70) / 3 = 73.3°
If weight is selected L1, the average temperature of 75° will
be displayed.
(1 x 80) + (1 x 70) / 2 = 75°
13
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Reset Operation
Note: When thermostat is reset, installer configuration menu settings and programming will reset to factory settings.
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermo-
stat by removing the wires from terminals R and C (do not short them together) and removing batteries for 2 minutes. After
resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly
contact your heating/cooling service person or place of purchase.
Note: Be sure to review the installer configuration menu settings.
To reset the programming, clock and configuration settings, press the
or
and SYSTEM button simultaneously. The
thermostat should go blank and then all segments will be displayed momentarily.
Symptom
Possible Cause
Corrective Action
No Heat/No Cool/No Fan
(common problems)
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
Replace fuse or reset breaker.
Turn switch to ON.
3. Furnace blower compartment door or
panel loose or not properly installed.
4. Loose connection to thermostat or system.
Replace door panel in proper position to engage safety
interlock or door switch.
Tighten connections.
No Heat
1. Pilot light not lit.
Re-light pilot.
2. Furnace Lock-Out Condition. Heat
may also be intermittent.
Many furnaces have safety devices that shut down when
a lock-out condition occurs. If the heat works intermittently
contact the furnace manufacturer or local HVAC service
person for assistance.
3. Heating system requires service or
thermostat requires replacement.
Diagnostic: Set SYSTEM Switch to HEAT and raise the
setpoint above room temperature. Within a few seconds
the thermostat should make a soft click sound. This sound
usually indicates the thermostat is operating properly. If
the thermostat does not click, try the reset operation listed
above. If the thermostat does not click after being reset
contact your heating and cooling service person or place
of purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a HVAC service
person to verify the heating is operating correctly.
No Cool
1. Cooling system requires service or
thermostat requires replacement.
Same as diagnostic for No Heat condition except set the
thermostat to COOL and lower the setpoint below the
room temperature. There may be up to a five minute delay
before the thermostat clicks in Cooling.
Heat, Cool or Fan
Runs Constantly
1. Possible short in wiring.
Check each wire connection to verify they are not shorted
or touching together. No bare wire should stick out from
under terminal block. Try resetting the thermostat as de-
scribed above. If the condition persists the manufacturer
of your system or service person can instruct you on how
to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
Thermostat Setting &
Thermostat Thermometer
Disagree
1. Thermostat thermometer setting
requires adjustment.
The thermometer can be adjusted +/- 4 degrees. See
Temperature Display Adjustment in the Configuration
Menu section.
Furnace (Air Conditioner)
Cycles Too Fast or Too Slow
(narrow or wide
1. The location of the thermostat and/or
the size of the Heating System may
be influencing the cycle rate.
Digital thermostats provide precise control and cycle
faster than older mechanical models. The system turns
on and off more frequently but runs for a shorter time
so there is no increase in energy use. If you would like
an increased cycle time, choose SL for slow cycle in the
Configuration menu, step 7 (heat) or 8 (cool). If an ac-
ceptable cycle rate is not achieved, contact a local HVAC
service person for additional suggestions.
temperature swing)
Forgot Keypad
Lockout Code
Press the menu button (button will disappear) and hold in
for 20 seconds. This unlocks the thermostat.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
15
Download from Www.Somanuals.com. All Manuals Search And Download.
HOMEOWNER HELP LINE: 1-800-284-2925
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
Download from Www.Somanuals.com. All Manuals Search And Download.
|