Weil McLain Burner UO 3 CV User Manual

R02 01/09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Hazard Def nitions and Owner’s Information........................................................................................3  
Information To Be Used Only By Qualif ed Service Technicians  
General Information.........................................................................................................................................4  
Table 1 Burner Specication................................................................................................................................4  
Notice Special Requirements..............................................................................................................................5  
Table 2 Air Tube Combination (ATC) Codes ………………………………………………………….. .....................5  
Inspect/Prepare Installation Site.................................................................................................................6  
Inspect Chimney or Direct Vent System..............................................................................................................6  
Combustion Air Supply........................................................................................................................................7  
Clearances to burner and appliance ...................................................................................................................7  
Combustion chamber - Burner Retrotting..........................................................................................................7  
Prepare the Burner...........................................................................................................................................8  
Low Firing Rate Bafe.........................................................................................................................................8  
Burner Fuel Unit ..................................................................................................................................................8  
Attach Air Tube....................................................................................................................................................8  
Nozzle and Pump Pressure.................................................................................................................................8  
Install Burner Nozzle ...........................................................................................................................................8  
Check/Adjust Electrodes .....................................................................................................................................9  
Servicing nozzle line assembly...........................................................................................................................9  
Check/Adjust ‘Z’ Dimension - F Heads .............................................................................................................10  
Check/Adjust ‘Z’ Dimension - L & V Heads ....................................................................................................... 11  
Mount burner on appliance...........................................................................................................................9  
Mounting Options ................................................................................................................................................9  
Mounting Dimensions..........................................................................................................................................9  
Installing the Oil Tank & Supply System............................................................................................................12  
Fuel Line Valves & Filter....................................................................................................................................12  
Wire Burner .......................................................................................................................................................13  
Burner Packaged with Appliance.......................................................................................................................13  
Burner Installed at Job Site ...............................................................................................................................13  
Special Wiring Required with Covered Burners ................................................................................................13  
Burner Control .................................................................................................................................................14  
GeniSys Model 7505 Control ............................................................................................................................14  
Wiring ................................................................................................................................................................14  
Typical Burner Sequence of Operation for GeniSys 7505 Control....................................................................15  
Typical Burner Sequence of Operation for R7184P Control..............................................................................17  
Start-up Burner/Set Combustion..............................................................................................................18  
Startup/checkout ...............................................................................................................................................19  
Set Combustion with Instruments......................................................................................................................19  
Perform Regular Maintenance...................................................................................................................20  
Parts Diagram...................................................................................................................................................22  
Beckett Limited Warranty Information ...................................................................................................24  
Page 2  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Hazard Denitions  
WARNING  
Owner’s Responsibility  
Indicates a hazardous situ-  
ation, which, if not avoided,  
will result in death or serious injury.  
!
!
DANGER  
Incorrect installation, adjustment,  
and use of this burner could result in  
severe personal injury, death, or sub-  
stantial property damage from re,  
Indicates a hazardous  
!
carbon monoxide poisoning, soot or explosion.  
WARNING  
situation, which, if not  
avoided, could result in death or serious  
injury.  
Contact a professional, qualied service agency for the  
installation, adjustment and service of your oil heating  
system. This work requires technical training, trade ex-  
perience, licensing or certication in some states and the  
proper use of special combustion test instruments.  
Indicates a hazardous  
situation, which, if not  
avoided, could result in minor or moderate  
injury.  
!
CAUTION  
Please carefully read and comply with the following  
instructions:  
y Never store or use gasoline or other ammable  
liquids or vapors near this burner or appliance.  
y Never attempt to burn garbage or refuse in this  
appliance.  
y Never attempt to light the burner/appliance by  
throwing burning material into the appliance.  
y Never attempt to burn any fuel not specied and  
approved for use in this burner.  
Within the boundaries of the hazard warning, there will  
be information presented describing consequences if the  
warning is not heeded and instructions on how to avoid  
the hazard.  
NOTICE  
Intended to bring special attention to  
information, but not related to personal injury or property  
damage.  
y Never restrict the air inlet openings to the burner  
or the combustion air ventilation openings in the  
room.  
NOTICE  
This manual contains information that applies to both AF and AFG burners. These burners may  
appear to be basically identical, but there are differences in design and performance. Please review the comparison  
chart below:  
Feature  
AF  
AFG  
Static Pressure Capability  
Blower Wheel Design  
Conventional - Low range  
Standard strip  
Enhanced - Medium range  
Special tablock  
Inlet Airow Design  
Standard inlet bell  
“F” Series ONLY  
Optional, as specied  
Not required  
Special airguide  
UL Air Tube Combinations  
Igniter Gaskets Baseplate/Barrier  
Low Firing Rate Bafe  
“F” or “M” Series  
Required, always specied  
Required, per specication  
Figure 1. Burner label location  
6104BAFG R06  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Impaired Burner Perfor-  
mance and Fire Hazard.  
Do NOT operate the burner beyond specif ca-  
tions outlined in the following Table.  
To the Owner:  
!
WARNING  
Thank you for purchasing a Beckett burner  
for use with your heating appliance. Please pay at-  
tention to the Safety Warnings contained within this  
instruction manual. Keep this manual for your records  
and provide it to your qualied service agency for use  
in professionally setting up and maintaining your oil  
burner.  
y For applications beyond these limits, consult  
Beckett Technical Service at 1-800-645-2876.  
y NOTE: Some packaged appliances with burners  
may be agency listed as a unit to operate beyond  
these limits. Consult the appliance manufac-  
turer’s specications and agency approvals for  
verication.  
Your Beckett burner will provide years of efcient op-  
eration if it is professionally installed and maintained  
by a qualied service technician. If at any time the  
burner does not appear to be operating properly, im-  
mediately contact your quali f ed service agency  
for consultation.  
Table 1 – Burner Specif cations  
‘F’ Head (AF & AFG)  
(Note 1) Firing rate range: ..............0.40 – 3.00 GPH  
Capacity  
Input: ....................... 56,000 – 420,000 Btu  
We recommend annual inspection/service of your  
oil heating system by a qualif ed service agency.  
‘L1’ Head (AFG Only)  
Firing rate range: ..................0.40 - 1.10 GPH  
Input: ..................... 56,000 – 154,000 Btu/h  
Daily – Check the room in which your burner/appli-  
ance is installed. Make sure:  
• Air ventilation openings are clean and unobstruct-  
ed  
• Nothing is blocking burner inlet air openings  
• No combustible materials are stored near the heat-  
ing appliance  
• There are no signs of oil or water leaking around  
the burner or appliance  
‘L2’ Head (AFG Only)  
Firing rate range: .................0.50 - 1.00 GPH  
Input: ...................... 70,000 – 140,000 Btu/h  
‘V1’ Head (AFG Only)  
Firing rate range: .................0.75 - 2.75 GPH  
Input: .................... 105,000 – 385,000 Btu/h  
Certications/ UL listed to comply with ANSI/UL296 and CSA-B140.0  
Approvals  
Fuels  
U. S No. 1 or No. 2 heating oil only (ASTM D396)  
Canada No. 1 stove oil or No. 2 furnace oil only  
Weekly  
• Check your oil tank level. Always keep your oil tank  
full, especially during the summer, in order to pre-  
vent condensation of moisture on the inside surface  
of the tank.  
CAUTION  
!
DO NOT USE GASOLINE, CRANKCASE OIL,  
OR ANY OIL CONTAINING GASOLINE.  
Electrical  
Power supply:............ 120 volts AC, 60 Hz single phase  
Operating load: .......... Amps max  
Do NOT Alter the Original  
Burner Design  
WARNING  
Motor: .........................1/7 hp, 3450 rpm, NEMA 48M frame  
PSC rotation CCW when facing  
!
shaft end  
Tampering with or altering the burner design  
could seriously impair performance, resulting  
in loss of static pressure, damage to the system  
components, reduced air volume, heavy smoke,  
ame impingement, appliance sooting, hot gas  
puff-back, and asphyxiation or re hazards.  
Maintain the design to its original conguration.  
Only use parts specied for AF or AFG Burners  
Do NOT remove the air guide from the AFG chassis.  
Do NOT use ‘M’ Series air tube combinations on AF Burn-  
ers.  
Ignition: ......................Continuous duty solid-state igniter  
Fuel pump  
Air tube  
Outlet pressure: ..................................Note 2  
ATC code: ...................................See Table 2  
Dimensions  
(with cover)  
Height (maximum) ....................... 12.5 inches  
Width (maximum) .......................... 15 inches  
Depth ......................................... 9.25 inches  
Air tube diameter ....................... 4.00 inches  
o
Ambient  
Operating  
+32 F. (0 C.) Minimum  
o
+115 F. (+46 C.) Maximum  
Temperature (See above Warning)  
Never try to convert an AF to an AFG or vice versa  
Any design alteration will:  
Moisture 5% to 95% RH, non-condensing and non-crystallizing  
Note 1: Approval agency listed rating for these burners is 0.40 to 3.00  
y Void UL Listing  
gph. However, the ring rate range is limited by the specic  
air tube combination being used. Refer to Table 2.  
Note 2. See appliance manufacturer’s burner specications for rec-  
ommended pump discharge pressure.  
y Void manufacturer’s warranties  
y Seriously impact burner performance  
y Greatly increase your liability risk  
Page 4  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Specications  
Table 2 – Air Tube Combination (ATC) codes  
Firing  
Rate  
(gph)  
Head  
Static  
plate  
size  
Ven-  
turi  
ATC Codes for usable air tube lengths  
(‘A’ in inches; See Figure 3.)  
(min-  
max)  
(inches)  
4-1/2  
5
5-3/8  
6-5/8  
7
7-1/4  
9
10-1/2  
13  
16  
0.50-0.75  
0.75-1.25  
0.85-1.35  
0.85-1.65  
1.10-2.00  
1.65-2.50  
2.50-3.00  
0.50-1.10  
0.50-1.00  
0.75-2.75  
0.40-0.75  
F0  
F3  
3-3/8U  
2-3/4U  
2-3/4U  
2-3/4U  
2-3/4U  
2-3/4U  
None  
None  
None  
AF44XR  
AF44XN  
-
AF53XR  
AF53XN  
AF65XR  
AF65XN  
-
AF72XR  
AF72XN  
AF72WH  
AF72YB  
AF72XO  
AF72XP  
AF72XS  
-
AF90XR  
AF90XN  
AF90WH  
AF90YB  
AF104XR  
AF104XN  
AF130XR  
AF130XN  
A160XR  
-
-
AF160XN  
F4  
None AF44WH  
-
AF53WH AF65WH  
-
AF104WH AF130WH AF160WH  
F6  
None  
None  
None  
None  
8hole  
8hole  
8hole  
AF44YB  
AF44XO  
AF44XP  
AF44XS  
-
-
AF53YB  
AF65YB  
-
AF104YB  
AF130YB  
AF160YB  
F12  
F22  
F31  
L1  
-
AF53XO  
AF65XO  
-
AF90XO  
AF90XP  
AF104XO  
AF130XO  
AF160XO  
-
AF53XP  
AF56XP  
-
AF104XP  
AF130XP  
AF160XP  
-
AF53XS  
AF65XS  
-
AF90XS  
AF104XS  
AF130XS  
AF160XS  
3-3/8U  
2-3/4U  
2-3/4U  
3-1/2U  
AFG50MB  
AFG50MP  
AFG50MD  
-
-
-
-
-
-
-
AFG70MB  
AFG70MP  
AFG70MD  
-
AFG90MB  
AFG90MP  
AFG90MD  
AF90WG  
-
-
-
-
-
-
-
L2  
-
-
V1  
F0  
-
-
-
None AF44WG  
AF53WG AF65WG  
AF72WG  
AF104WG AF130WG  
A160WG  
Notice Special Requirements  
Professional Service  
Required  
Incorrect installation, adjustment,  
and use of this burner could result  
in severe personal injury, death, or  
substantial property damage from  
WARNING  
y THE INSTALLATION OF A BURNER SHALL BE  
IN ACCORDANCE WITH THE REGULATIONS  
OF AUTHORITIES HAVING JURISDICTION.  
y For recommended installation practices in the  
U.S. refer to the latest edition of NFPA 31. (CSA-  
B139 and CSA-B140 in Canada.  
!
re, carbon monoxide poisoning, soot or explo-  
y
Concealed damage — If you discover damage to  
the burner or controls during unpacking, notify the sion.  
carrier at once and le the appropriate claim.  
When contacting Beckett for service information  
— Please record the burner serial number (and  
have available when calling or writing). You will  
nd the serial number on the silver label located  
on the left rear of the burner. Refer to Figure 1.  
Please read and understand the manual supplied with  
this equipment. This equipment must be installed, ad-  
justed and put into operation only by a qualied individu-  
al or service agency that is:  
y
y Licensed or certied to install and provide tech-  
nical service to oil heating systems.  
y Experienced with all applicable codes, standards  
and ordinances.  
y Responsible for the correct installation and com-  
mission of this equipment.  
y Skilled in the adjustment of oil burners using  
combustion test instruments.  
The installation must strictly comply with all applicable  
codes, authorities having jurisdiction and the latest revi-  
sion of the National Fire Protection Association Standard  
for the installation of Oil-burning Equipment, NFPA 31  
(or CSA-B139 and CSA-B140 in Canada).  
Regulation by these authorities take precedence over  
the general instructions provided in this installation  
6104BAFG R06  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspect/Prepare Installation Site  
Inspect Chimney or Direct Vent System  
5. No other appliance connection should be made to  
the same ue pipe.  
6. The ue pipe should have an upward pitch toward  
the chimney of at least 1/4” per foot of length. It  
should t tightly and should not project into the  
chimney.  
7. Any leakage between tiles, around clean-out  
doors, or around the vent pipe should be sealed.  
Fire, Smoke & Asphyxia-  
tion Hazard  
y Carefully inspect the chimney or exhaust vent  
system.  
y Make sure it is properly sized and in good work-  
ing condition.  
WARNING  
!
y Follow the instructions supplied by the appliance  
manufacturer.  
INSULATED STAINLESS STEEL CHIMNEY LINERS  
y The installation must strictly comply with all ap-  
plicable codes, authorities having jurisdiction and  
the latest revision of the National Fire Protection  
Association Standard NFPA 31 for the installa-  
tion of chimneys and vent sizing, (or CSA-B139  
and CSA-B140 in Canada).  
y Regulation by these authorities take precedence  
over the general instructions provided in this in-  
stallation manual.  
The new designs of high efciency oil furnaces  
and boilers in conjunction with ame retention oil  
burners are more efcient. One result of increased  
efciency is lower ue gas temperatures. As  
ue gases rise in the chimney, they will cool and  
condense when they reach the dew point. The  
condensation will mix with the sulphur in the ue  
gases creating sulphuric acid. The acid will attack  
the chimney mortar, brick and clay liners caus-  
ing corrosion, deterioration and blockage of the  
chimney. Eventually the blockage could prevent  
exhausting the ue gases. Instead, the ue gases  
could vent out the barometric damper into the liv-  
ing space.  
1. Starting with minimum gph ring rate, the mini-  
mum size recommended is 6” ue pipe with 8” X  
8” inside chimney, unless specied otherwise by  
the appliance manufacturer.  
2. A chimney ue shall extend at least 3 feet above  
the highest point at which the chimney comes  
in contact with the roof, and not less than 2 feet  
above the highest roof surface or structure within  
10 feet horizontally of the chimney. Refer to Fig-  
ure 2.  
Therefore, it is strongly recommended that an ap-  
proved insulated stainless steel liner be installed.  
y For those installations not requiring a chimney,  
such as through-the-wall vented appliances, fol-  
low the instructions given by the appliance and  
power venter (if used) manufacturers.  
3. Any accumulation of soot or debris in chimney  
offsets should be removed  
4. Any obstructions such as a protruding joint or a  
piece of broken tile wedged in the chimney should  
be removed.  
Figure 2 – Chimney Design - Above the Roof  
NOTE: Correct  
chimney design is  
shown by dotted  
lines. Incorrect  
chimney design,  
as shown by the  
solid lines, may  
result in down-  
drafts.  
Page 6  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspect/Prepare Installation Site  
Combustion air supply  
Adequate Combustion  
Outside air kit applications  
Refer to separate instruction sheet supplied with  
AF/AFG outside air kit for installation. This optional  
kit allows combustion air to be piped directly to the  
burner (Beckett part number 51747).  
WARNING  
and Ventilation Air Supply  
Required  
!
Failure to provide adequate air supply could  
seriously affect the burner performance and re-  
sult in damage to the equipment, asphyxiation,  
explosion or re hazards.  
Clearances to burner and appliance  
y Provide space around burner and appliance for  
easy service and maintenance.  
y Check minimum clearances against those shown  
by the appliance manufacturer and by applicable  
building codes.  
y The burner cannot properly burn the fuel if it is not  
supplied with a reliable combustion air source.  
y Follow the guidelines in the latest editions of the  
NFPA 31 and CSA-B139 regarding providing ad-  
equate air for combustion and ventilation.  
Protect Steel Combustion  
Chamber From Burnout  
WARNING  
!
Appliance located in conned space  
Failure to comply could result in damage to the  
heating equipment and result in re or asphyxi-  
ation hazards.  
The conned space should have two (2) permanent  
openings: one near the top of the enclosure and  
one near the bottom of the enclosure. Each open-  
ing shall have a free area of not less than (1) one  
square inch per 1,000 BTU’s per hour of the total  
input rating of all appliances within the enclosure.  
The openings shall have free access to the build-  
ing interior, which should have adequate inltration  
from the outside.  
y When retrotting appliances that have unlined  
stainless steel combustion chambers, protect  
the chamber by lining the inside surfaces with a  
ceramic ber blanket, such as a wet-pac or other  
suitable refractory material.  
y Some steel chambers may not require liners  
because the appliance was designed and tested  
for use with ame retention burners. Refer to the  
manufacturer’s instructions.  
Exhaust fans and other air-using devices  
Size air openings large enough to allow for all air-  
using devices in addition to the minimum area re-  
quired for combustion air. If there is any possibility  
of the equipment room developing negative pres-  
sure (because of exhaust fans or clothes dryers, for  
example), either pipe combustion air directly to the  
burner or provide a sealed enclosure for the burner  
and supply it with its own combustion air supply.  
Combustion chamber — Burner retrof t-  
ting  
Verify that the appliance combustion chamber pro-  
vides at least the minimum dimensions given in  
Table 3.  
Direct air supply and sidewall venting  
y Some AFG burners are equipped with combus-  
tion air boots to allow use of outside air for com-  
bustion.  
Table 3. Chamber Dimensions  
Chamber Dimensions (inches)  
y When sidewall venting appliances, carefully fol-  
low appliance and power venter instructions for  
installation and wiring.  
Firing Rate Round  
Rectangular  
Width Length  
Height Floor to  
nozzle  
(GPH)  
I.D.  
0.50  
0.75  
1.00  
1.25  
1.50  
2.00  
2.50  
3.00  
8
7
8
12  
12  
5-6  
5-6  
5-6  
5-6  
6-7  
6-7  
7-8  
7-8  
9
8
9
10  
11  
12  
14  
16  
18  
9
10  
11  
12  
15  
17  
18  
12.5  
12.5  
13  
Follow the Outside Air Kit  
Instructions Exactly  
WARNING  
!
10  
11  
12  
13  
14  
Failure to comply could result in impaired com-  
bustion, appliance soot-up, puffback of smoke,  
and re or asphyxiation hazards.  
13.5  
14  
y Do not attempt to install outside air piping to  
the burner without using the outside air kit and  
instructions.  
15  
6104BAFG R06  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspect/Prepare Installation Site  
Prepare the Burner  
Table 4. AFG Reduced Firing Rates (with  
LFRB)  
Low Firing Rate Baff e  
Burner head type  
Low Firing Rate Bafe installed  
up to 0.65 gph  
The AFG Low Firing Rate Bafe (LFRB) reduces  
the air ow and pressure. The LFRB is sometimes  
used for ring rates under 1.00 gph as listed in  
Table 4. Refer to the appliance manufacturer’s in-  
structions. Do not omit the LFRB when specied.  
Omitting the bafe when specied or installing the  
bafe when not specied could result in impaired  
burner performance.  
F0  
F3 or L1  
F4 or F6  
V1  
up to 0.85 gph  
up to 0.90 gph  
up to 1.00 gph  
Table 5. Nozzle Flow Rate by Size  
Nozzle f ow rate U. S. gallons per hour of No. 2 fuel oil when  
pump pressure (psig) is:  
Burner fuel unit  
Nozzle  
size  
(rated at  
100 psig)  
125  
psi  
140 psi  
150 psi  
175 psi  
200 psi  
y Verify that the burner fuel unit is compatible with  
the oil supply system. For more details, refer to  
the pump manufacturer’s instructions provided  
with the burner.  
0.40  
0.50  
0.60  
0.65  
0.75  
0.85  
0.90  
1.00  
1.10  
1.20  
1.25  
1.35  
1.50  
1.65  
1.75  
2.00  
0.45  
0.56  
0.67  
0.73  
0.84  
0.95  
1.01  
1.12  
1.23  
1.34  
1.39  
1.51  
1.68  
1.84  
1.96  
2.24  
0.47  
0.59  
0.71  
0.77  
0.89  
1.01  
1.07  
1.18  
1.30  
1.42  
1.48  
1.60  
1.77  
1.95  
2.07  
2.37  
0.49  
0.61  
0.74  
0.80  
0.92  
1.04  
1.10  
1.23  
1.35  
1.47  
1.53  
1.65  
1.84  
2.02  
2.14  
2.45  
0.53  
0.66  
0.79  
0.86  
0.99  
1.13  
1.19  
1.32  
1.46  
1.59  
1.65  
1.79  
1.98  
2.18  
2.32  
2.65  
0.56  
0.71  
0.85  
0.92  
1.06  
1.20  
1.27  
1.41  
1.56  
1.70  
1.77  
1.91  
2.12  
2.33  
2.48  
2.83  
Attach air tube (if not already installed)  
If using a ange and gasket, slide them onto the air  
tube. Then attach the air tube to the burner chassis  
using the four sheet metal screws provided. Refer  
to Figure 4 for details.  
Nozzle and Pump Pressure  
Correct Nozzle and Flow  
WARNING  
!
Rate Required  
Incorrect nozzles and ow rates  
could result in impaired combus-  
tion, under-ring, over-ring, soot-  
ing, puff-back of hot gases, smoke  
and potential re or asphyxiation hazards.  
2.25  
2.50  
2.52  
2.80  
2.66  
2.96  
2.76  
-
2.98  
-
-
-
Use only nozzles having the brand, ow rate (gph), spray  
angle and pattern specied by the appliance manufac-  
turer.  
Follow the appliance manufacturer’s specications for  
the required pump outlet pressure for the nozzle, since  
this affects the ow rate.  
Install burner nozzle (if not already in-  
stalled)  
1. Remove the plastic plug protecting the nozzle  
adapter threads  
y Nozzle manufacturers calibrate nozzle ow rates  
at 100 psig.  
2. Place a 3/4” open-end wrench on the nozzle  
adapter. Insert the nozzle into the adapter and n-  
ger tighten. Finish tightening with a 5/8” open-end  
wrench. Use care to avoid bending the burner head  
support legs or electrodes. If you remove the head  
to replace the nozzle (type “L1”/“L2” or “V1” heads),  
carefully reconnect the head to the nozzle adapter,  
making sure that the head support makes contact  
with the nozzle adapter shoulder. Refer to Figure  
5 or 6.  
y When pump pressures are higher than 100 psig,  
the actual nozzle ow rate will be greater than  
the gph stamped on the nozzle body. (Example:  
A 1.00 gph nozzle at 140 psig = 1.18 gph)  
Securely tighten the nozzle (90 torque inch pounds). For  
typical nozzle ow rates at various pressures refer to  
Table 5.  
Page 8  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Prepare the Burner  
3. If the nozzle is already installed, remove the noz-  
zle line assembly to verify that the nozzle size and  
spray pattern are correct for the application (per ap-  
pliance manufacturer’s information). Verify that the  
electrode tip settings comply with Figure 3.  
4. If the nozzle is not installed, obtain a nozzle from  
the manufacturer, having the capacity and spray  
angle specied in the appliance manufacturer’s in-  
formation. For conversions or upgrades, when in-  
formation is not available for the application:  
y Refer to Table 6 to select the mid-range nozzle  
spray angle for the head type being used.  
Figure 3. – Electrode Tip Adjustment  
Standard Dimensions for F, L1, and V1 Heads.  
y Fire the burner and make sure the combustion  
is acceptable and the ame is not impinging on  
chamber surfaces.  
y If a shorter ame is needed, select a wider spray  
angle. If a longer ame is needed, select a nar-  
rower spray angle.  
The Dimensions shown below are for use with L2 heads  
and M series air tube combinations ending with an ‘N’ suf-  
x (example: AFG70MDAQN)  
y Either hollow or solid spray patterns may be used.  
If combustion results are not satisfactory with the  
selected spray pattern, try the other pattern.  
Table 6. Nozzle Spray Angles  
Recommended nozzle spray angles  
“F” head  
“L1” & “L2” head  
“V1” head  
70° or 80° nozzle  
45°, 60°, or 70° nozzle  
45°, 60°, or 70° nozzle  
Mount burner on appliance  
Check/adjust electrodes  
Check the electrode tip settings. Adjust if neces-  
sary to comply with the dimensions shown in Fig-  
ure 3. To adjust, loosen the electrode clamp screw  
and slide/rotate electrodes as necessary. Securely  
tighten the clamp screw when nished.  
Mounting options  
1. Bolt the burner to the appliance using the fac-  
tory-mounted ange or an adjustable ange.  
Mounting dimensions  
Servicing nozzle line assembly  
1. Turn off power to burner before proceeding.  
2. Disconnect oil connector tube from nozzle line.  
3. Loosen the two screws securing igniter retain-  
ing clips and rotate both clips to release igniter  
baseplate. Then tilt igniter back on its hinge.  
4. Remove splined nut.  
1. When using the Beckett universal adjustable  
ange, mount the air tube at a 2° downward  
pitch unless otherwise specied by the appli-  
ance manufacturer.  
2. Verify that the air tube installed on the burner  
provides the correct insertion depth. See Fig-  
ure 7.  
5. “F” head air tube. - Remove nozzle line as-  
sembly from burner, being careful not to  
damage the electrodes or insulators while  
handling. To ease removal of long assemblies  
(over 9 inches), rotate assembly 180° from  
installed position after pulling partially out of  
tube.  
6. “L1”, “L2”, and “V1” head air tubes. - Slide  
nozzle line assembly forward (further into air  
tube) so the head clears the venturi opening.  
Then rotate the nozzle line assembly 90° so  
the nozzle line end points up. Pull the nozzle  
line assembly toward you and remove assem-  
bly from burner.  
3. The end of the air tube should normally be ¼”  
back from the inside wall of the combustion  
chamber. Never allow the leading edge of the  
head assembly to extend into the chamber, un-  
less otherwise specied by the heating appli-  
ance manufacturer. Carefully measure the in-  
sertion depth when using an adjustable ange.  
Verify the insertion depth when using a welded  
ange.  
7. To replace the nozzle assembly, reverse the  
above steps.  
6104BAFG R06  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Prepare the Burner  
Figure 4. Check/Adjust ‘Z’ Dimension for ‘F’ Heads  
1-1/8”  
1-3/8”  
Adjust the ‘Z’ dimen-  
sion to the required  
specif cation.  
Incorrect Adjustments could cause combus-  
tion problems, carbon deposition from ame  
impingement, heavy smoke generation and  
re hazard.  
WARNING  
!
y Make all adjustments exactly as outlined in  
the following information.  
Check/Adjust ‘Z’ Dimension - ‘F’ heads  
Burner Dimensions  
1. The important ‘Z’ dimension is the distance from the face of the nozzle  
to the at face of the head (or heat shield, if applicable). This dis-  
tance for F heads is 1-” (1-” if the air tube has a heat shield). The  
“Z” dimension is factory set for burners shipped with the air tube in-  
stalled. Even if factory set, verify that the “Z” dimension has not been  
changed.  
For usable length A (inches)  
F Head  
L1  
L2  
V1  
Dimension (inches)  
Head  
Head  
Head  
1/4  
7/32  
1/4  
N/A  
H (nozzle to head), +1/32  
L (Total tube length)  
2. Use the following procedure to adjust the “Z” dimension, if it is not  
correct:  
A+1/2  
A+1/2  
A+1/2  
A+1/2  
A+2-1/4  
(Note 1)  
A+1-1/8 A+1-1/8 A+1-1/8  
R (electrode length), + 1/4  
y
y
y
Turn off power to the burner.  
Disconnect the oil connector tube from the nozzle line  
See above gure. Loosen the splined nut from the nozzle line.  
Loosen the hex head screw securing the escutcheon plate to the  
burner housing.  
1-3/8  
1-3/8  
1-3/8  
S (adapter to static plate), +  
1/16  
A+ 15/16  
A+ 3/16  
A+ 3/16  
A+ 3/16  
Q (nozzle line length),  
y
Place the end of a ruler at the face of the nozzle and, using a  
straight edge across the head, measure the distance to the face of  
the head. A Beckett T501 gauge may also be used.  
Slide the nozzle line forward or back until this dimension for F  
heads is 1-” (1-” to the face of the heat shield, if applicable).  
Tighten the hex head screw to secure the escutcheon plate to the  
burner chassis. Then tighten the splined nut and attach the oil con-  
nector tube.  
1-1/8  
1-3/8  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Z (F head-no heat shield)  
(F head-with heat shield)  
N/A  
N/A  
1-3/8  
1-3/4  
N/A  
1-3/4  
N/A  
1-3/4  
Z (L1 head w/straight  
shroud) (L1/L2/V1 head  
w/conic shroud)  
y
y
Note 1: 1-3/8 for dimension A less than 4”; 1-5/8 for dimension A from 4”  
through 4-1/2 “, 2-13/32 for dimension A greater than 4-1/2”.  
3. Recheck the “Z” dimension periodically when servicing to ensure the  
escutcheon plate has not been moved. You will need to reset the “Z”  
dimension if you replace the air tube or nozzle line assembly. The  
Beckett Z gauge (part number Z-2000) is available to permit checking  
the F head “Z” dimension without removing the burner from the appli-  
ance.  
Page 10  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Prepare the Burner  
burners shipped with the air tube installed. Even if factory set, verify  
that the “Z” dimension has not been changed.  
2. Use the following procedure to adjust the “Z” dimension, if it is not  
correct:  
Figure 5. Check/Adjust ‘Z’ Dimension - L1 &  
L2 Heads  
y
y
y
Turn off power to the burner.  
Disconnect the oil connector tube from the nozzle line.  
Refer to gure. Loosen the splined nut from the nozzle line.  
Loosen the hex head screw securing the escutcheon plate to the  
burner housing.  
y
Place the end of a ruler at the leading edge of the head and, us-  
ing a straight edge across the end of the air tube, measure the  
distance to the end of the tube. A Beckett T501 gauge may also  
be used.  
y
y
Slide the nozzle line forward or back until this dimension is 1-”  
for L1 & L2 heads if the tube has a straight shroud, or 1-¾” if the  
air tube has a conic shroud.  
Tighten the hex head screw to secure the escutcheon plate to  
the burner chassis. Then tighten the splined nut and attach the  
oil connector tube.  
L1/L2 heads (see Table 7 and Figure 3 for dimensions)  
1. See gure above. The important “Z” dimension is the distance from  
the leading edge of the head to the end of the air tube. This distance  
for L1 & L2 heads is 1-” if the tube has a straight shroud or 1-¾” if  
the air tube has a conic shroud. The “Z” dimension is factory set for  
3. Recheck the “Z” dimension periodically when servicing to ensure  
the escutcheon plate has not been moved. You will need to reset  
the “Z” dimension if you replace the air tube or nozzle line assem-  
bly.  
2. Use the following procedure to adjust the “Z” dimension, if it is not  
correct:  
Figure 6. Check/Adjust ‘Z’ Dimension - V1  
Heads  
y
y
y
Turn off power to the burner.  
Disconnect the oil connector tube from the nozzle line.  
See gure above. Loosen the splined nut from the nozzle line.  
Loosen the hex head screw securing the head adjusting plate to  
the burner housing.  
y
Loosen the acorn nut. Move the head adjusting plate until the “0”  
lines up with the reference indicator on the housing, and retighten  
the hex head screw. Place the end of a ruler at the leading edge of  
the head and, using a straight edge across the end of the air tube,  
measure the distance to the end of the tube. A Beckett T501 gauge  
may also be used.  
y
y
Slide the nozzle line forward or back until this dimension is 1-¾” for  
V1 heads. Tighten the acorn nut.  
Tighten the hex head screw to secure the head adjusting plate to  
the burner chassis. Then tighten the splined nut and attach the oil  
connector tube.  
V1 heads (see Table below and Figure above for dimensions)  
1. See gure above. The important “Z” dimension is the distance from  
the leading edge of the head to the end of the air tube. This distance  
for V1 heads is 1-¾”. The “Z” dimension is factory set for burners  
shipped with the air tube installed. Even if factory set, verify that the  
“Z” dimension has not been changed.  
3. Recheck the “Z” dimension periodically when servicing to ensure the  
escutcheon plate has not been moved. You will need to reset the “Z”  
dimension if you replace the air tube or nozzle line assembly.  
Table for initial adjusting plate settings for V1  
Head  
Set head position adjusting plate (V1 head only)  
V1 Adjusting  
Plate Setting  
AFG with V1  
Head  
1. After setting “Z” dimension, loosen head adjusting plate hex head  
screw and nozzle line splined nut. Move the nozzle line assembly until  
the burner reference indicator lines up with the head adjusting plate  
setting number given in Table shown below.  
Burner Firing  
Rates  
2. Tighten the hex head screw and splined nut. (DO NOT loosen the  
acorn nut when setting head position.) Refer to the manufacturer’s in-  
structions for OEM settings.  
3. The position of the head affects air ow volume and pattern. For most  
applications, the burner will perform satisfactorily with the air adjust-  
ment plate setting of Table shown below.  
4. If combustion results indicate the need for change, adjust the head po-  
sition adjusting plate forward or back one position at a time to optimize  
combustion.  
0
1
2
3
4
5
6
0.75-1.00  
1.00-1.50  
1.50-1.75  
1.75-2.00  
2.00-2.25  
2.25-2.50  
2.50-2.75  
6104BAFG R06  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mount burner on appliance  
Figure 8. – Inside Tank Gravity Feed System  
Figure 7. – Mounting Burner in Appliance  
If space between burner  
air tube and opening  
exceeds 1/2 inch, pack  
burner opening with ce-  
ramic fiber refractory.  
Tilt down 2o  
SK8745  
Installing the Oil Tank and Supply System  
Oil Leak and Fire Hazard  
WARNING  
!
Figure 9. – Outside Buried Tank-Lift System  
Install the oil tank following applicable stan-  
dards in the U.S. by referring to the latest  
edition of NFPA 31 or CSA-B139 & CSA-B140  
in Canada, and all authorities having jurisdic-  
tion.  
Do Not Use Tef on Tape  
CAUTION  
!
Damage to the pump could cause impaired  
burner operation, oil leakage and appliance  
soot-up.  
y Never use Teon tape on fuel oil ttings.  
y Tape fragments can lodge in fuel line compo-  
nents and fuel unit, damaging the equipment  
and preventing proper operation.  
NOTICE  
To further protect the fuel supply sys-  
tem and reduce nozzle orice plugging with ring rates  
below 0.75 gph, a dual ltration system can be installed.  
This typically consists of a 50 micron primary lter,  
located near the fuel tank and a secondary lter rated for  
at least 10 microns located near the burner.  
y Use oil-resistant pipe sealant compounds.  
Note: to determine the proper fuel line size, refer  
to the fuel pump manufacturer’s instructions pro-  
vided with the burner. Refer to Figure 8 or Figure 9  
for typical installation layouts.  
Fuel supply level with or above burner –  
Fuel Line Valves and Filter  
Do Not Install By-pass Plug  
with 1-Pipe System  
WARNING  
Install two high quality, oil duty rated, fusible  
handle design shutoff valves in accessible loca-  
tions on the oil supply line. Locate one close to the  
tank and the other close to the burner, upstream of  
the lter for service access.  
!
Failure to comply could cause Immediate pump  
seal failure, pressurized oil leakage and the  
potential for a re and injury hazard.  
Install a generous capacity lter inside the building  
between the fuel tank shutoff valve and the burner,  
locating both the lter and the valve close to the  
burner for ease of servicing. Filter should be rated  
for 50 microns or less.  
y The burner is shipped without the by-pass plug  
installed.  
y Install the by-pass plug in two-pipe oil supply  
systems ONLY.  
Page 12  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wire burner  
Wire burner  
Oil Supply Pressure  
Control Required  
CAUTION  
!
Burner packaged with appliance  
Damage to the lter or pump seals could cause  
oil leakage and a re hazard.  
WARNING  
y The oil supply inlet pressure to the burner can-  
not exceed 3 psig.  
y Insure that a pressure limiting device is installed  
in accordance with the latest edition of NFPA 31.  
y Do NOT install valves in the return line.  
(NFPA 31, Chapter 8.)  
y Gravity Feed Systems: Always install an anti-  
siphon valve in the oil supply line or a solenoid  
valve (RWB Part # 2182602U) in the pump/noz-  
zle discharge tubing to provide backup oil ow  
cut-off protection.  
Electrical Shock Hazard  
!
Electrical shock can cause severe  
personal injury or death.  
y Disconnect electrical power before installing or  
servicing the burner.  
y Provide ground wiring to the burner, metal con-  
trol enclosures and accessories. (This may also  
be required to aid proper control system opera-  
tion.)  
y Perform all wiring in compliance with the Na-  
tional Electrical Code ANSI/NFPA 70 (Canada  
CSA C22.1)  
The burner may be equipped with a single-stage  
fuel unit for these installations. Connect the fuel  
supply to the burner with a single supply line if you  
want a one-pipe system (making sure the bypass  
plug is NOT installed in the fuel unit.) Manual bleed-  
ing of the fuel unit is required on initial start-up. If  
connecting a two-pipe fuel supply, install the fuel  
unit bypass plug.  
y Refer to appliance manufacturer’s wiring diagram  
for electrical connections.  
Burner installed at jobsite  
y Refer to Figures 11a and 11b, for typical burner  
wiring, showing cad cell primary controls. Burner  
wiring may vary, depending on primary control  
actually used.  
y Refer to the appliance manufacturer’s wiring dia-  
gram prior to connecting the burner wiring. All wir-  
ing must be in accordance with the latest revision  
of National Electric Code NFPA 70 and all local  
codes and regulations. In Canada, all wiring is  
to be in accordance with the Canadian Electrical  
Code, Part 1.  
Fuel supply below the level of the burner –  
When the fuel supply is more than eight feet below  
the level of the burner, a two-pipe fuel supply sys-  
tem is required. Depending on the fuel line diam-  
eter and horizontal and vertical length, the instal-  
lation may also require a two-stage pump. Consult  
the fuel unit manufacturer’s literature, included with  
the burner, for lift and vacuum capability.  
Fuel line installation –  
y Continuous lengths of heavy wall copper tubing  
are recommended. Always use f are f ttings.  
Never use compression f ttings.  
The 7505 primary control with valve-on delay (pre-  
time) and burner motor-off delay (post-time) re-  
quires a constant 120 volts AC power source sup-  
plied to the BLACK wire on the control. The RED  
wire goes to the appliance limit circuit. Please note  
that other control manufacturers may use different  
wire colors for power and limit connections.  
y Always install ttings in accessible locations.  
Proper routing of fuel lines is required to prevent  
air cavitation and vibration.  
Frozen Plumbing and  
Water Damage Hazard  
Special wiring required with covered  
If the residence is unattended in severely cold  
weather, burner primary control safety lockout,  
heating system component failures, power  
outages or other electrical system failures  
could result in frozen plumbing and water  
damage in a matter of hours. For protection,  
take preventive actions such as having a  
security system installed that operates during  
power outages, senses low temperature and  
initiates an effective action. Consult with your  
heating contractor or a home security agency.  
burners  
The mounting plate is not a conduit connec-  
tion point. Pass conduit and attached connector  
through the opening in the mounting plate and at-  
tach it directly to the burner-mounted 4x4 electrical  
box.  
If attaching a burner cover to a previously installed  
burner, attach the mounting plate and then slide the  
conduit into the “J” shaped conduit slot.  
6104BAFG R06  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Controls  
GeniSys Model 7505 Control  
Wiring  
Explosion, Fire, Scald,  
and Burn Hazard  
Fire or Explosion Hazard  
All heating appliances must have  
HIGH LIMIT protection to interrupt  
electrical power and shutdown the  
burner if operating or safety controls  
fail and cause a runaway condition.  
Can cause severe injury, death, or  
property damage.  
y The control can malfunction if it gets wet,  
leading to accumulation of oil or explosive oil  
vapors.  
y Never install where water can ood, drip or  
condense on the control.  
y Follow the appliance manufacturer’s wiring  
diagrams and note all required safety controls.  
y Typical safety controls include high temperature  
or pressure limits, low water cutoffs, pressure  
relief valves and blocked ue sensing switches.  
y Verify all limit and safety controls are installed  
and functioning correctly, as specied by the  
manufacturer, applicable safety standards,  
codes and all authorities having jurisdiction.  
y Ensure that the appliance is free of oil and oil  
vapor before starting or resetting the burner.  
y
Never use a control that has been wet - replace it.  
Features  
Thermostat / Operating and Limit Control Compatible  
Welded Relay Protection  
Limited Recycle  
Limited Reset  
3 Status Lights  
Valve-On Delay / Motor-Off Delay (Field  
programmable with 52067 GeniSys Display)  
15 Second Lockout Time  
Interrupted or Intermittent Duty Ignition  
Technician Pump Priming Mode  
Disable Function  
Incorrect Wiring Will Re-  
sult in Improper Control  
Operation  
y GeniSys wiring label colors may not match the  
wire colors of the burner or other manufacturers’  
controls.  
y The GeniSys Control should be wired according  
to the appliance manufacturer’s instructions.  
Cad Cell Resistance Indicator  
Communication Ports  
Figure 10.  
Yellow Light  
Green Light  
Reset Button  
with Red Light  
Wiring  
Connections  
Communication Port 2  
Communication Port 1  
Cad Cell  
Connections  
Thermostat Terminals  
Alarm Module:  
For adding isolated  
low voltage alarm  
contacts to the base  
control. See Alarm  
Module Instructions for  
specications.  
Display Module:  
For programming and  
diagnostics  
Page 14  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Controls  
Typical Burner Sequence of Operation for GeniSys 7505 Control.  
Refer to the appliance manufacturer’s wiring diagram for actual specications.  
9
1
3
5
6
Pump  
prime  
Standby  
4
2
Trial for  
ignition  
Lockout  
Valve-on delay  
Ignition carryover  
7
8
Recycle  
Run  
Motor-off delay  
6. Run: The ame is sustained until the call for heat  
is satised. The burner is then sent to Motor-Off  
Delay, if applicable, or it is shut down and sent to  
Standby.  
1. Standby: The burner is idle, waiting for a call for  
heat.  
2. Valve-On Delay: The igniter and motor are on while  
the control delays turning on the oil solenoid valve  
for the programmed time.  
7. Recycle: If the ame is lost while the burner is  
ring, the control shuts down the burner, enters a  
60 second recycle delay, and repeats the ignition  
sequence. The control will continue to Recycle  
each time the ame is lost, until it reaches a pre-set  
time allotment. The control will then go into Hard  
Lockout instead of recycle. This feature prevents  
excessive accumulation of oil in the appliance ring  
chamber.  
3. Trial For Ignition : The oil solenoid valve is  
energized. A ame should be established within the  
factory set trial for ignition time (lockout time).  
4. Lockout: The control has shut down for one of the  
following safety reasons:  
a. The trial for ignition (lockout) time expired without  
ame being established.  
b. The cad cell detected ame at the end of the  
Valve On Delay state.  
8. Motor-Off Delay: If applicable, the oil solenoid  
valve is turned off and the control delays turning the  
motor off for the set motor-off delay time before the  
control returns to standby.  
To reset the control from lockout click the button 1-  
second.  
9. Pump Prime: The igniter and motor are on with the  
oil solenoid valve energized for 4 minutes. During  
Pump Prime mode, the cad cell is disregarded,  
allowing the technician to prime the pump without  
having to jumper the cad cell.  
NOTE: A recurrence of the above failure modes or a  
failed welded relay check could cause the control to  
enter a Hard Lockout state that must be reset only  
by a qualied service technician.  
To reset from Hard Lockout, hold the reset button for  
15 seconds until the yellow light turns on.  
5. Ignition Carryover: Once ame is established,  
the igniter remains on for 10 additional seconds to  
ensure ame stability.  
6104BAFG R06  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Controls  
Figure 1 1a. – Interrupted ignition, valve-on delay  
only (no motor-off delay)  
Figure 1 1b. – Interrupted ignition, valve-on delay  
and motor-off delay  
L1  
L2  
W
R
L1  
L2  
W
R
SAFETY AND  
OPERATING  
LIMITS  
SAFETY AND  
OPERATING  
LIMITS  
THERMOSTAT  
THERMOSTAT  
IGNITER  
MOTOR  
IGNITER  
MOTOR  
IGNITER  
L2 (IGN)  
IGNITER  
L2 (IGN)  
MOTOR  
L2 (MTR)  
MOTOR  
L2 (MTR)  
L1  
LIMIT  
L1 - LIMIT  
JUMPER  
LIMIT  
L2  
L2  
TR  
TW  
VALVE  
TR  
VALVE  
OIL VALVE  
OIL VALVE  
L2 (VLV)  
L2 (VLV)  
TW  
TR-TW TERMINALS  
LOCATED ON OPPOSITE  
SIDE OF CONTROL  
TR-TW TERMINALS  
LOCATED ON OPPOSITE  
SIDE OF CONTROL  
CAD  
CELL  
CAD  
CELL  
CAD CELL  
CAD CELL  
Reset Button Operation  
Table 2 explains what action the control will take when the reset button is pressed for different lengths of time  
during the various burner operating states.  
Table 2 - Reset Button Operation  
Pushing the reset button will:  
If the burner is in the  
Button Click  
Button Hold  
Button Hold  
(press 15+ seconds)  
below state:  
(press < 1 second)  
(press > 1 second)  
Reset from Restricted (Hard)  
Lockout  
Lockout  
Valve-on Delay, Trial for  
Reset from Soft Lockout  
Go to Pump Prime (see  
Disable the Burner:  
Enables Pump Priming:  
Ignition, Ignition Carryover “Priming the Pump” above)  
Any time the burner is running, After the reset button has been  
press and hold the reset button held for 15 seconds, the button  
Yellow light ashes to indicate  
to disable the burner. The  
burner will remain off as long  
as the button is held.  
can then be clicked during the  
next ignition sequence to enter  
Pump Prime mode.  
cad cell resistance. See “Cad  
Cell Resistance Indicator” for  
Run (igniter is shut off)  
table of resistance values.  
Motor-Off Delay,  
Standby  
No action  
Pump Prime  
No action  
Exit Pump Prime mode and return to Standby  
Table 3 - Status Lights  
Light Color  
On Continuously  
Flashing  
Red  
Restricted (Hard) Lockout  
Soft Lockout  
Green  
Flame Sensed during normal operation (Could Recycle  
be stray light during standby)  
Yellow  
Control is in Pump Prime mode or  
Cad Cell resistance. See “Cad Cell Resistance  
Reset button currently held for 15+ seconds.  
Indicator” on page 18 for a table of resistance  
values.  
Page 16  
610
4
B
A
F
G
R  
06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner Controls  
Typical Burner Wiring & Burner Sequence of Operation for R7184P Control.  
Refer to the appliance manufacturer’s wiring diagram for actual specications.  
Figure 10. – Typical Burner Wiring  
7. RECYCLE. If the ame is lost while the burner is  
1. STANDBY. The burner is idle, waiting for a call for  
heat. When a call for heat is initiated, there is a 3-  
10 second delay while the control performs a safe  
start check.  
2. VALVE-ON DELAY. The ignition and motor are  
turned on for a 15 second valve-on delay.  
3. TRIAL FOR IGNITION (TFI). The fuel valve is  
opened. A ame should be established within the  
15 second lockout time.  
4. LOCKOUT. If ame is not sensed by the end of  
the TFI, the control shuts down on safety lockout  
and must be manually reset. If the control locks out  
three times in a row, the control enters restricted  
lockout.  
ring, the control shuts down the burner, enters a 60  
second recycle delay, and then repeats the above  
ignition sequence. If ame is lost three times in a  
row, the control locks out to prevent cycling with  
repetitious ame loss due to poor combustion.  
8. BURNER MOT OR-OFF DELAY. The fuel valve  
is closed and the burner motor is kept on for the  
selected motor-off delay time before the control re-  
turns the burner to standby.  
5. IGNITION CARRYOVER. Once ame is estab-  
lished, the ignition remains on for 10 seconds to  
ensure ame stability before turning off. If the con-  
trol is wired for intermittent duty ignition, the ignition  
unit stays on the entire time the motor is running.  
6. RUN. The burner runs until the call for heat is sati-  
ed. The burner is then sent to burner motor off  
delay, if applicable, or it is shut down and sent to  
standby.  
61351  
Control System Features  
Feature Interrupted  
ignition  
Limited reset,  
Limited recycle  
Diagnostic LED,  
cad cell indicator  
Valve-on  
delay  
Burner motor Alarm Con-  
off delay  
tacts  
R7184A  
R7184B  
R7184P  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
Optional  
6104BAFG R06  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wire burner  
3. Set the thermostat substantially above room tem-  
perature.  
4. Close the line voltage switch to start the burner.  
If the burner does not start immediately you may  
Some Thermostats Are Polar-  
ity Sensitive. Reversed polarity  
could cause erratic cycling of the burner control.  
NOTICE  
y Connect the wire from the RH or R terminal on the  
thermostat to the TR terminal on the control.  
y Connect the wire from the W terminal on the  
thermostat to the TW terminal on the control.  
have to reset the burner primary control.  
5. Initiate a call for heat.  
6. After the burner starts, press and hold the reset  
button for 15 seconds until the yellow light turns on.  
This indicates that the button has been held long  
enough.  
Make connections to the control’s terminals as shown  
in Figures 11a and 11b. Refer to the label on the un-  
derside of the control for wiring details.  
7. Release the reset button. The yellow light will turn  
off and the burner will start up again.  
8. At burner start up, click the reset button while the  
igniter is still on. This will transition the control to a  
dedicated Pump Prime mode, during which the mo-  
tor, igniter, and valve are powered for four minutes.  
The yellow light will be on.  
9. Bleed the pump until all froth and bubbles are  
purged. If desired, terminate the call for heat or  
hold the reset button for at least one second to exit  
Pump Prime mode and return to Standby.  
10. At the end of 4 minutes, the yellow light will turn off  
and the control will automatically return to standby  
mode.  
11. If prime is not established during the four minute  
pump prime mode, return to step 8 to re-enter Pump  
Prime mode. Repeat steps 8 through 10 until the  
pump is fully primed and the oil is free of bubbles.  
12. Terminate the call for heat, and the control will re-  
sume normal operation.  
Note: Motor-off delay on a 7505P will be disabled if  
the safety and operating limits as shown in Figures  
11a and 11b interrupt power to the control terminal  
L1.  
Connect thermostat leads to the TR and TW  
terminals on the control or jumper the TR and  
TW terminals on the control, as directed by the  
appliance wiring diagram.  
Thermostat anticipator Current: 0.1 amp  
Thermostat voltage: 24 volts AC  
Note that if the thermostat short cycles or operates  
improperly, it may require an isolation relay for proper  
operation. The Beckett A/C Ready Kit (part no. 51950U)  
provides this function. Wiring instructions are included  
with the A/C Ready Kit.  
Cad Cell Resistance Indicator  
During the burner Run state, click the reset button  
(less than 1 second) to check the cad cell resistance  
range. The yellow light will ash 1 to 4 times, de-  
pending on the amount of light detected by the cad  
cell. See chart below:  
Start up burner/set combustion  
Yellow Light Flashes  
Flame Detection Range  
Normal (0 - 400 ohms)  
Hot Gas Puff-Back and  
Heavy Smoke Hazard  
Failure to prime the pump properly could result  
in unstable combustion, hot gas puff-back and  
heavy smoke.  
1
2
3
4
Normal (400 - 800 ohms)  
Normal (800 - 1600 ohms)  
Limited (1600 ohms - Lockout)  
y Do not allow oil to spray into a hot combustion  
chamber while bleeding air from the pump.  
y Install a gauge in the nozzle discharge port  
tubing or fully open the pump bleed valve to  
prevent oil spray from accumulating in the com-  
bustion chamber during the air bleed procedure.  
y Ensure that all bubbles and froth are purged  
from the oil supply system before tightening the  
pump bleed valve.  
Resetting From Restricted or Hard Lockout  
If the control continues to lockout without a satised  
call for heat, or fails the motor relay check, the control  
enters Hard (restricted) Lockout in order to limit accu-  
mulation of unburned oil in the combustion chamber.  
To reset, hold the button down for 15 seconds until  
the red light turns off and the yellow light turns on.  
y Ensure that the appliance is free of oil and oil  
vapor before starting or resetting the burner.  
Always verify the control functions according to all  
specications before leaving the installation site.  
Replace the control if it does not operate as speci-  
ed.  
1. Open the shutoff valves in the oil supply line to the  
burner.  
2. Close air band and partially open air shutter. This  
is an initial air setting for the pump bleeding pro-  
cedure only. Additional adjustments must be made  
with instruments.  
Page 18  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Startup/Checkout  
4. After the 60 second recycle period, the control  
will try to restart the system.  
Startup / Checkout  
Explosion and Fire Hazard  
WARNING  
5. After the 15 second lockout time, the control  
will lock out the burner and the reset button will  
ash. Verify that the burner motor and igniter  
are off and that the burner oil solenoid valve (if  
used) is not energized.  
!
Failure to follow these instructions  
could lead to equipment malfunc-  
tion and result in heavy smoke  
emission, soot-up, hot gas puff-  
back, re and asphyxiation hazards.  
6. Open the hand valve in the oil line.  
y Do not attempt to start the burner when excess  
oil has accumulated in the appliance, the ap-  
pliance is full of vapor, or when the combustion  
chamber is very hot.  
y Do not attempt to re-establish ame with the  
burner running if the ame becomes extin-  
guished during start-up, venting, or adjustment.  
y Vapor-Filled Appliance: Allow the unit to cool  
off and all vapors to dissipate before attempting  
another start.  
7. Click the reset button and verify that the red light  
in the reset button shuts off and that the burner  
lights.  
8. End the call for heat.  
Before leaving the installation, verify that all thermo-  
stat and boiler/furnace control wiring is correct. Con-  
sult heating appliance manual for directions.  
y Oil-Flooded Appliance: Shut off the electrical  
power and the oil supply to the burner and then  
clear all accumulated oil before continuing.  
y If the condition still appears unsafe, contact the  
Fire Department. Carefully follow their directions.  
y Keep a re extinguisher nearby and ready for  
use.  
Set combustion with instruments  
OIL-BURNING EQUIPMENT  
CAUTION  
!
SHALL BE CONNECTED TO  
FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES  
TO ENSURE SAFE AND PROPER OPERATION OF  
THE BURNER.  
If the burner or control fails any of the following tests,  
recheck control wiring. If the burner or control still fails  
any tests, replace the control.  
1. Allow the burner to run for approximately 5 to 10  
minutes.  
2. Set the stack or over-re draft to the level specied  
Check Safety Features  
by the appliance manufacturer.  
Safe Start Check  
y Natural Draft Applications; typically over-re  
draft is -0.01” or -0.02” w.c.  
1. Place a jumper across the cad cell terminals.  
y Direct Venting; typically may not require draft  
2. Refer to the steps for “Start up burner/set  
combustion” and have the system call for heat.  
adjustment.  
y High Eff ciency/Positive Pressure Appliances;  
also vary from traditional appliances (see manu-  
facturer’s recommendations).  
3. Burner must not start. Verify that the green light  
is on continuously and that the control remains  
in Standby mode.  
3. Follow these four steps to properly adjust the burn-  
er:  
4. End the call for heat and remove the cad cell  
jumper.  
Step 1: Adjust the air shutter/band until a trace of  
Simulate Flame Failure and Ignition Failure  
smoke is achieved.  
1. Refer to the steps for “Start up burner/set  
combustion” and have the system call for heat.  
Step 2: At the trace of smoke level, measure the  
CO (or O ) . This is the vital reference  
2
2
point for further adjustments. Example:  
2. After ame is established and the burner igniter  
turns off, close the hand valve in the oil supply  
line.  
13.5% CO (2.6% O )  
2
2
Step 3: Increase the air to reduce the CO by  
2
1.5 to 2 percentage points. (O will be in-  
creased by approximately 2.0 to 2.7 per-  
2
3. At ame loss, the control will enter Recycle  
mode. Verify that the green light is ashing. The  
control will remain in Recycle for 60 seconds.  
centage points.) Example: Reduce CO  
2
from 13.5% to 11.5% (2.6% to 5.3% O ).  
2
6104BAFG R06  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform regular maintenance  
Step 4: Recheck smoke level. It should be Zero.  
ˆ Verify the nozzle is the one originally specied by  
the appliance manufacturer and replace the noz-  
zle with one having the exact specications from  
the same manufacturer.  
This procedure provides a margin of  
reserve air to accommodate variable  
conditions.  
• If the draft level has changed, recheck  
ˆ Clean and inspect the electrodes for damage, re-  
placing any that are cracked or chipped.  
ˆ Check electrode tip settings. Replace electrodes  
if tips are rounded.  
the smoke and CO levels and readjust  
2
the burner if necessary  
4. Once combustion is set, tighten all fasteners on air  
band, air shutter and head adjusting plate or es-  
cutcheon plate.  
ˆ Inspect the igniter spring contacts. Clean or re-  
place if corroded.  
ˆ Clean the cad cell grid surface, if necessary.  
ˆ Make sure Low Firing Rate Bafe is in place if  
required for the burner application. Omitting the  
bafe can result in unacceptable burner combus-  
tion.  
5. Burner equipped with cover - Reinstall the cover  
and repeat Steps 2 and 4. If CO increases (O  
2
2
decreases), remove the cover and adjust the air  
setting so the CO (O ) with cover on meets re-  
quirements of Step 3.  
ˆ Inspect all gaskets. Replace any that are dam-  
aged or would fail to seal adequately.  
2
2
ˆ Inspect the combustion head and air tube. Re-  
move any carbon or foreign matter. Replace all  
damaged units with exact parts.  
ˆ Clean the blower wheel, air inlet, air guide, burner  
housing and static plate of any lint or foreign ma-  
terial.  
6. Start and stop the burner several times to ensure  
satisfactory operation. Test the primary control and  
all other appliance safety controls to verify that they  
function according to the manufacturer’s specica-  
tions.  
ˆ If motor is not permanently lubricated, oil motor  
with a few drops of SAE 20 nondetergent oil at  
each oil hole. DO NOT over oil motor. Excessive  
oiling can cause motor failure.  
Perform regular maintenance  
ˆ Check motor current. The amp draw should not  
exceed the nameplate rating.  
ˆ Check all wiring for secure connections or insula-  
tion breaks.  
ˆ Check the pump pressure and cutoff function.  
ˆ Check primary control safety lockout timing.  
ˆ Check ignition system for proper operation.  
ˆ Inspect the vent system and chimney for soot ac-  
cumulation or other restriction.  
Annual Professional Ser-  
vice Required  
WARNING  
!
Tampering with or making incorrect  
adjustments could lead to equip-  
ment malfunction and result in  
asphyxiation, explosion or re.  
y DO NOT TAMPER WITH THE UNIT OR CON-  
TROLS - CALL YOUR QUALIFIED SERVICE  
TECHNICIAN OR SERVICEMAN.  
ˆ Clean all ue passages and ue pipe. Replace  
corroded or damaged pipes.  
y To ensure continued reliable operation, a quali-  
ed service technician must service this burner  
annually.  
y More frequent service intervals may be required  
in dusty or adverse environments.  
y Operation and adjustment of the burner requires  
technical training and skillful use of combustion  
test instruments and other test equipment.  
ˆ Clean the appliance thoroughly according to the  
manufacturer’s recommendations.  
ˆ Check the burner performance. Refer to the sec-  
tion “Set combustion with test instruments”.  
ˆ It is good practice to make a record of the service  
performed and the combustion test results.  
Shutting the Burner Off  
IF THE BURNER IS SHUT DOWN  
FOR AN EXTENDED PERIOD OF  
TIME, ALWAYS KEEP THE VALVE SHUT OFF.  
CAUTION  
!
ˆ Replace the oil supply line lter. The line lter car-  
tridge must be replaced to avoid contamination of  
the fuel unit and nozzle.  
ˆ Inspect the oil supply system. All ttings should  
be leak-tight. The supply lines should be free of  
water, sludge and other restrictions.  
ˆ Remove and clean the pump strainer if applica-  
ble.  
Turn off all electric power to the burner.  
Note: There could be more than one disconnect  
switch.  
Page 20  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Perform regular maintenance  
Replace the blower wheel:  
1. Turn off all power to the burner before servic-  
ing.  
2. Disconnect the burner motor wires.  
3. Remove the bolts securing the motor to the  
burner housing.  
Figure 12. Blower wheel assembly  
4. Remove the motor and blower wheel.  
5. Remove the existing blower wheel.  
6. Referring to the gure below, slide the new  
blower wheel onto the shaft.  
y Use a feeler gauge to set the wheel-to-motor  
gap, as shown below. (AF = 0.125 +1/64 inch,  
AFG = 0.030 +1/64 inch)  
Use a Feeler Gauge to set  
the gap to;  
AF = 0.125 +1/64 inch  
AFG = 0.030 +1/64 inch  
y Slide blower wheel toward motor until it con-  
tacts feeler gauge.  
y Rotate the blower wheel until the setscrew is  
centered on the at of the motor shaft. Tighten  
the setscrew to secure the wheel.  
SK9190  
7. DO NOT use a motor that has endshield open-  
ings outside the blower wheel circumference  
(represented by the dashed line).  
8. Install the motor on the burner housing. Tighten  
screws. Reconnect wires.  
9. Restore power, start the burner and perform  
combustion tests. Refer to the section “Set  
combustion with test instruments”.  
6104BAFG R06  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
23  
24  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
For best performance specify genuine  
Beckett  
replacement parts  
#
1
2
3
4
Part No.  
Description  
#
16  
Part No.  
51771U  
51304  
5880  
Description  
Burner Housing Assembly  
Air Band - Specify # of slots  
Air Shutter - Specify # of slots  
Valve Cordset  
Igniter & Base Plate  
Igniter Gasket Kit  
Low Firing Rate Bafe  
Cad Cell Detector  
Specify*  
Specify*  
21807U  
17 & 18  
19  
20  
7006U  
Not Shown 21887U  
PD Timer Delay Cordset  
CleanCut Pump  
21  
22  
5
6
7
8
2184404U  
5394  
Copper Oil Line - 8”  
Splined Nut  
5940  
Electrode Kit - M Head up to 9”  
3666  
Specify *  
Welded Flange  
3811  
Gasket Only  
3493  
Escutcheon (F & L1/L2 heads)  
23  
24  
25  
26  
27  
Specify *  
Specify *  
5685  
Retention Head Assembly  
Nozzle Line Electrode & Head Assembly  
Pedestal Kit  
9
2139  
2454  
Hole Plug  
Coupling  
10  
11  
2182602U  
32395U  
Solenoid Valve Kit (delay)  
Cover  
31231U (AFG)  
31841U (AF)  
Air Guide (AFG)  
Air Inlet Bell (AF)  
12  
13  
2999U (AFG)  
2459U (AF)  
Blower Wheel (AFG)  
Blower Wheel (AF)  
21805U  
4189  
PSC Motor  
Mounting Screws  
* Contact your Beckett Representative for part num-  
ber and pricing.  
** Contact your Beckett Representative for available  
pre and post time settings.  
14  
15  
5770  
Electrical Box  
7505P  
Replaces R7184P - Pre and Post-  
time**  
6104BAFG R06  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited  
WARRANTY  
For Residential, Commercial and Specialty Burners  
The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett for resale or for  
incorporation into a product for resale (“Customers”) that its equipment is free from defects in material and workmanship under normal use and  
service for 60 months from the date of manufacture for Residential Burners and 18 months from the date of manufacture for Commercial and  
Specialty Burners. Residential burner models include: AF, AFG, AFII, NX, SF, SR and SMG. Commercial burner models include: CF375,  
CF500, CF800, CF1400, CF2300A, CF2500, CF3500A, CG10, CG15, CG25 and CG50. Specialty burner models include: ADC, ADCP, ARV,  
SDC and SM. The provisions of this warranty are extended to individual major burner components as follows:  
a) 60 months from date of manufacture for all Beckett-branded major components, except for 12 Vdc components.  
b) 18 months from date of manufacture for all non-Beckett-branded major components and Beckett branded 12 Vdc components.  
Note: Normal service items found to be defective upon receipt by the customer are covered by this warranty.  
THIS WARRANTY DOES NOT EXTEND TO EQUIPMENT SUBJECTED TO MISUSE, NEGLECT, OR ACCIDENT: NOR DOES THIS WARRANTY APPLY  
UNLESS THE PRODUCT COVERED BY IT IS PROPERLY INSTALLED BY A QUALIFIED, COMPETENT TECHNICIAN, WHO IS LICENSED WHERE  
STATE AND LOCAL CODES REQUIRE, AND WHO IS EXPERIENCED IN MAKING SUCH INSTALLATIONS, IN ACCORDANCE WITH THE LATEST  
EDITION OF NFPA NO. 31 OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE (NFPA  
NO. 54) AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE AND NATIONAL CODES HAVING JURISDICTIONAL AUTHORITY.  
Equipment, which is defective in material or workmanship and within the warranty period, may be returned for credit as follows:  
Beckett Burners, Beckett-branded major components and non-Beckett-branded major components that came as original equipment on a Beckett burner  
or were sold as a replacement part by Beckett should be returned, freight prepaid, to Beckett’s home office. Credit will be issued to the customer unless  
the returned equipment is determined by Beckett to be out of warranty or damaged by user, in which case the equipment will be scrapped.  
Note: Beckett is not responsible for any labor cost for removal and replacement of equipment.  
THIS WARRANTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE, AND PROVIDES EXCLUSIVE REMEDIES EXPRESSLY IN LIEU OF ALL OTHER  
REMEDIES, AND IN PARTICULAR THERE SHALL BE EXCLUDED THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR  
PURPOSE. IN NO EVENT WILL BECKETT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGE OF ANY NATURE. Beckett neither assumes nor  
authorizes any person to assume for Beckett any other liability or obligation in connection with the sale of this equipment, Beckett’s liability and Customer’s  
exclusive remedy being limited to credit as set forth above.  
R.W. BECKETT CORPORATION  
P.O. Box 1289 Elyria, Ohio 44036  
Form No. 61545 R72905  
The Oilheat Manufacturers’ Association supports the use of low sulfur fuels as dened by ASTM D396, Grades No. 1 Low Sulfur  
and No. 2 Low Sulfur, as the preferred heating fuel for the following reasons:  
• Low sulfur fuels reduce deposits on heat exchanger surfaces, extending the service interval between cleanings.  
• The reduced deposits increase the efciency of the appliance.  
• Low sulfur fuels reduce particulate emissions.  
• Low sulfur fuels reduce oxides of nitrogen emissions.  
R.W. BECKETT CORPORATION  
U.S.A.: P.O. Box 1289 · Elyria, Ohio 44036  
Canada: R.W. Beckett Canada, Ltd. · Unit #3, 430 Laird Road · Guelph, Ontario N1G 3X7  
Form Number 6104 BAFG R06  
Printed in U.S.A.  
01/14/09  
© 2008 R.W. Beckett Corporation  
Page 24  
6104BAFG R06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weil McLain Boiler SB0203 User Manual
Whirlpool Freezer EH18EFX User Manual
Whirlpool Washer GCAM2792LQ0 User Manual
Whistler Radar Detector 550 User Manual
White Rodgers Thermostat 1E30 W User Manual
WiebeTech Laptop Docking Station NBDDV4 User Manual
Woodstock Scale D4028 User Manual
Xilinx Computer Hardware EDK 92I User Manual
Zanussi Cooktop ZCGHL54 User Manual
Zebra Technologies Printer GX420 User Manual