Quick Startup Guide for
SIMOVERT MASTERDRIVES
6SE70 VC
Vector Control
Section 1:
Parameterization of Base Drive
Parameterization of Rectifier
Simovis Trace Setup Method
When Should a Drive be re-Tuned
Section 2:
Section 3:
Section 4:
DROM-02069
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE:
These instructions do not purport to cover all details or variations in equipment, nor to
provide for every possible contingency to be met in connection with installation,
operation or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purposes, please
contact your local Siemens office.
Further, the contents of these instructions shall neither become a part of nor modify
any prior or existing agreement, commitment or relationship. The sales contract
contains the entire obligation of Siemens Energy & Automation. The warranty
contained in the contract between the parties is the sole warranty of Siemens Energy &
Automation. Any statements contained herein do not create new warranties nor
modify the existing warranty.
Note:
This Quick Startup Guide is not an autonomous document, but is intended to direct users to
the section in the Operating Instructions which are important for start-up. Thus, these brief
instructions can only be completely valid when used in conjunction with the Operating
Instructions. It is especially important to observe the warning and information regarding
potential hazards in the Operating Instructions.
Warning:
•
•
Electrical equipment has parts an components which are at hazardous voltage levels.
If the warning information in the detailed Operating Instructions is not observed, this
can result in severe bodily injury or material damage.
•
•
Only appropriately qualified personnel may work with this equipment.
These personnel must be knowledgeable with all of the warning information and
service/maintenance measures of the Operating Instruction.
Perfect and safe operation of this equipment assumes professional transport, storage, erection
and installation as well as careful operating control and service.
Version 1.0 March 1, 2000
Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 4
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1:
Parameterization of Base Unit
SIMOVERT MASTERDRIVES
6SE70 VC
Vector Control
1.1 Power Section Defintion
1.2 Factory Reset
1.3 Basic Start-up
1.3.1 Volts/Hz without encoder feedback
1.3.2 Volts/Hz with encoder feedback
1.3.3 Vector Control without encoder feedback
1.3.4 Vector Control with encoder feedback
1.4 Drive Control Word
1.5 Communication Board Configuration
Note: Refer to Operating Instruction Manual for power and control connections.
Version 1.0 March 1, 2000
Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 6
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
1.1 Power Section Definition
Note: Power Section is pre-defined at the factory. Power Section
Definition is required if a new board CUVC board is put into the drive or
boards are switched between units with different ratings. Drive should
be defaulted and re-parameterized after Power Section Definition.
Select “Power Section Definition”
Menu
P060 = 8
Input Code for unit (PWE)
(Refer to Compendium section
6.3 or use the bookmark “PWE
P070 = ?
Listing” or check the following
table)
P060 = 1
Return to Parameter Menu
Version 1.0 March 1, 2000
Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit List
P070:
Parameter Value (PWE)
P072:
Rated Output Current in Amps
In[A]
Frequency Converter
AC-AC type
3 AC 200V to 230V
*1
PWE
14
21
27
32
39
48
54
64
70
13
29
41
87
Order Number
6SE7021-1CA60
6SE7021-3CA60
6SE7021-8CB60
6SE7022-3CB60
6SE7023-2CB60
6SE7024-4CC60
6SE7025-4CD60
6SE7027-0CD60
6SE7028-1CD60
6SE7031-0CE60
6SE7031-3CE60
6SE7031-6CE60
6SE7032-0CE60
In[A]
10.6
13.3
17.7
22.9
32.2
44.2
54.0
69.0
81.0
100.0
131.0
162.0
202.0
Frequency Inverter
DC-AC type
DC 270V to 310V
*1
PWE
15
22
28
33
40
49
55
65
71
20
34
86
92
Order Number
6SE7021-1R60
6SE7021-3RA60
6SE7021-8RB60
6SE7022-3RB60
6SE7023-2RB60
6SE7024-4RC60
6SE7025-4RD60
6SE7027-0RD60
6SE7028-1RD60
6SE7031-0RE60
6SE7031-3RE60
6SE7031-6RE60
6SE7032-0RE60
In[A]
10.6
13.3
17.7
22.9
32.2
44.2
54.0
69.0
81.0
100.0
131.0
162.0
202.0
Page 8
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Frequency Converter
AC-AC type
3 AC
380V to 460V
PWE
Air Cooled
PWE
Water
Cooled
*1
Order Number
In[A]
3
9
11
18
25
35
42
46
52
56
66
74
82
90
98
102
108
112
116
147
151
164
6SE7016-1EA61
6SE7018-0EA61
6SE7021-0EA61
6SE7021-3EB61
6SE7021-8EB61
6SE7022-6EC61
6SE7023-4EC61
6SE7023-8ED61
6SE7024-7ED61
6SE7026-0ED61
6SE7027-2ED61
6SE7031-0EE60
6SE7031-2EF60
6SE7031-5EF60
6SE7031-8EF60
6SE7032-1EG60
6SE7032-6EG60
6SE7033-2EG60
6SE7033-7EG60
6SE7035-1EK60
6SE7036-0EK60
6SE7037-0EK60
6.1
8.0
10.2
13.2
17.5
25.5
34.0
37.5
47.0
59.0
72.0
92.0
124.0
146.0
186.0
210.0
260.0
315.0
370.0
510.0
590.0
690.0
233
237
168
1
*
Based on 3kHz carrier frequency setting, larger frames have maximum carrier
frequency restrictions
Version 1.0 March 1, 2000
Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Frequency Inverter
DC-AC type
DC
PWE
PWE
Water
Cooled
*1
Order Number
In[A]
510V to 650V
Air Cooled
4
10
12
19
26
36
43
47
53
57
67
75
83
91
99
103
109
113
117
120
123
126
127
134
135
140
150
153
154
163
181
185
194
6SE7016-1TA61
6SE7018-0TA61
6SE7021-0TA61
6SE7021-3TB61
6SE7021-8TB61
6SE7022-6TC61
6SE7023-4TC61
6SE7023-8TD61
6SE7024-7TD61
6SE7026-0TD61
6SE7027-2TD61
6SE7031-0TE60
6SE7031-2TF60
6SE7031-5TF60
6SE7031-8TF60
6SE7032-1TG60
6SE7032-6TG60
6SE7033-2TG60
6SE7033-7TG60
6SE7035-1TJ60
6SE7036-0TJ60
6SE7037-0TK60
6SE7038-6TJ60
6SE7041-1TM60
6SE7041-1TK60
6SE7041-3TM60
6SE7041-6TM60
6SE7042-1TQ60
6SE7041-3TL60
6SE7037-0TJ60
6SE7038-6TS60
6SE7041-1TS60
6SE7042-5TN60
6.1
8.0
10.2
13.2
17.5
25.5
34.0
37.5
47.0
59.0
72.0
92.0
124.0
146.0
186.0
210.0
260.0
315.0
370.0
510.0
590.0
690.0
860.0
1100.0
1100.0
1300.0
1630.0
2090.0
1300.0
690.0
6450.0
6270.0
2470.0
206
209
212
213
221
226
236
239
199
167
247
250
244
Page 10
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Frequency Converter
AC-AC type
3 AC
500V to 575V
PWE
Air Cooled
PWE
Water
Cooled
*1
Order Number
In[A]
1
5
7
6SE7014-5FB61
6SE7016-2FB61
6SE7017-8FB61
6SE7021-1FB61
6SE7021-5FB61
6SE7022-2FC61
6SE7023-0FD61
6SE7023-4FD61
6SE7024-7FD61
6SE7026-1FE60
6SE7026-6FE60
6SE7028-0FF60
6SE7031-1FF60
6SE7031-3FG60
6SE7031-6FG60
6SE7032-0FG60
6SE7032-3FG60
6SE7033-0FK60
6SE7033-5FK60
6SE7034-5FK60
4.5
6.2
7.8
11.0
15.1
22.0
29.0
34.0
46.5
16
23
30
37
44
50
60
62
68
78
84
94
100
104
136
141
143
61.0
66.0
79.0
108.0
128.0
156.0
192.0
225.0
297.0
354.0
452.0
222
227
229
1
*
Based on 3kHz carrier frequency setting, larger frames have maximum carrier
frequency restrictions
Version 1.0 March 1, 2000
Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Frequency Inverter
DC-AC type
DC
PWE
PWE
Water
Cooled
*1
Order Number
In[A]
675V to 810V
Air Cooled
2
6
8
17
24
31
38
45
51
61
63
69
79
85
95
101
105
110
114
118
121
124
128
130
132
138
144
6SE7014-5UB61
6SE7016-2UB61
6SE7017-8UB61
6SE7021-1UB61
6SE7021-5UB61
6SE7022-2UC61
6SE7023-0UD61
6SE7023-4UD61
6SE7024-7UD61
6SE7026-1UE60
6SE7026-6UE60
6SE7028-0UF60
6SE7031-1UF60
6SE7031-3UG60
6SE7031-6UG60
6SE7032-0UG60
6SE7032-3UG60
6SE7033-0UJ60
6SE7033-5UJ60
6SE7034-5UJ60
6SE7035-7UK60
6SE7036-5UK60
6SE7038-6UK60
6SE7041-0UM60
6SE7041-1UM60
6SE7041-2UM60
6SE7041-4UM60
6SE7041-4UQ60
6SE7042-1TQ60
6SE7041-6UQ60
6SE7041-1UL60
6SE7042-4ULJ60
6SE7041-1UL60
4.5
6.2
7.8
11.0
15.1
22.0
29.0
34.0
46.5
61.0
66.0
79.0
108.0
128.0
156.0
192.0
225.0
297.0
354.0
452.0
570.0
650.0
860.0
990.0
1080.0
1230.0
1400.0
200
202
204
207
210
214
216
218
224
230
148
234
195
197
1580.0
155
157
159
1080.0
2450.0
1230.0
Page 12
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Frequency Inverter
DC-AC type
DC
PWE
PWE
Water
Cooled
*1
Order Number
In[A]
675V to 810V
Air Cooled
161
165
169
173
177
179
182
186
188
190
192
6SE7043-3UR60
6SE7044-1UR60
6SE7044-8UR60
6SE7045-7UR60
6SE7046-5UR60
6SE7036-5UR60
6SE7038-6US60
6SE7041-1US60
6SE7041-2US60
6SE7042-1UN60
6SE7042-3UN60
3270.0
4090.0
4900.0
5720.0
6540.0
4940.0
6540.0
6160.0
5840.0
2050.0
2340.0
245
248
251
253
240
242
Frequency Converter
AC-AC type
3 AC
660V to 690V
PWE
Air Cooled
PWE
Water
Cooled
*1
Order Number
In[A]
58
72
76
80
88
6SE7026-0HF60
6SE7028-2HF60
6SE7031-0HG60
6SE7031-2HF60
6SE7031-5HF60
6SE7031-7HG60
6SE7032-1HG60
6SE7033-0HK60
6SE7033-5HK60
6SE7034-5HK60
55.0
82.0
97.0
118.0
145.0
171.0
208.0
297.0
354.0
452.0
96
106
137
142
146
223
228
232
Frequency Inverter
DC-AC type
DC
PWE
PWE
Water
Cooled
*1
Order Number
In[A]
890V to 930V
Air Cooled
59
73
6SE7026-0WF60
6SE7028-2WF60
60.0
82.0
Version 1.0 March 1, 2000
Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
DC
PWE
PWE
Water
Cooled
*1
Order Number
In[A]
890V to 930V Air Cooled
77
81
89
97
6SE7031-0WG60
6SE7031-2WF60
6SE7031-5WF60
6SE7031-7WG60
6SE7032-1WG60
6SE7033-0WJ60
6SE7033-5WJ60
6SE7034-5WJ60
6SE7035-7WK60
6SE7036-5WK60
6SE7038-6WK60
6SE7041-0WM60
6SE7041-1WM60
6SE7041-2WM60
6SE7041-4WM60
6SE70414WQ60
6SE7041-6WM60
6SE7041-6WM60
6SE7034-5WK60
6SE7041-1WL60
6SE7042-4WR60
6SE7041-2WL60
6SE7043-3WR60
6SE7044-1WR60
6SE7044-8WR60
6SE7045-7WR60
6SE7046-5WR60
6SE7036-5WS60
6SE7038-6WS60
6SE7041-1WS60
6SE7041-2WS60
6SE7042-1WN60
6SE7042-3WN60
97.0
118.0
145.0
171.0
208.0
297.0
354.0
452.0
570.0
650.0
860.0
990.0
1080.0
1230.0
1400.0
107
111
115
119
122
125
129
131
133
139
145
201
203
205
208
211
215
217
219
225
231
149
235
1580.0
152
156
158
160
162
166
170
174
178
180
183
187
189
191
193
238
196
452.0
1080.0
2450.0
1230.0
3270.0
4090.0
4900.0
5720.0
6540.0
4940.0
6540.0
6160.0
5840.0
2050.0
2340.0
198
246
249
252
254
241
243
Page 14
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2 Factory Reset
6: Parameter Changes permitted
via PMU and Serial Interface
(OP1 and PC)
P053 = 6
2: Menu Select = Fixed Settings
P060 = 2
P366 = 0
Select Factory Setting
0: Standard
Start Parameter Reset
0: Parameter Reset
1: No Parameter Change
P970 = 0
Version 1.0 March 1, 2000
Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 16
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3 Basic Start-up without Motor Connected to Load
1.3.1 Volts/Hz without Encoder
P060=5
P060 = 5
Select “Drive Settings”
P071 = Input Line Voltage
AC-AC Converter=460Volt
DC-AC Inverter = 620Volt
P071 = ?
P095 = Select Motor Type
2: Asynchronous 1PH7 Motor
10: IEC Induction Motor
P095 = ?
11: NEMA Induction Motor
P095 = 2
10 or 11
P097 = Motor Code number for
1PH7 motor (See Appendix)
P097 = ?
Motor Nameplate Information
P101= Motor Voltage (V)
P101 = 460
P102 = Motor Rated Current (A)
P102 = xxx
P095 = 10
11
P104 = Cos (phi) per nameplate
P105 = Rated Horsepower
P104 = ? P105 = ?
Version 1.0 March 1, 2000
Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
P106 = NEMA Motor Nameplated
efficiency (if unknown set =0.8)
P106 = ?
P107 = Rated Motor Frequency
P108 = Nameplated Rotor RPM
P107 = 60
P108 = xxxx
P115 = 1
“Automatic Parameterization”
P115 = 1
P340 = 3
P340 = Carrier Frequency
Low # = Cooler Motor and Drive
High # = Lower Motor Noise
P383 = Motor Thermal Time
Constant. If constant unknown use
general guidelines;
P383 = xxxx
2 Pole Motor = 480 seconds
4 Pole Motor = 600 seconds
6 Pole Motor = 720 seconds
P452 = Maximum Forward Speed in
Percentage (usually 100%)
P452 = 100
Page 18
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
P453 = Maximum Reverse Speed in
Percentage (usually -100%)
P453 = -100
P060 = 1
P060 = Return to Parameter Menu
P128 = Maximum Motor Current
Options: P128 = P102
P128=1.1*P102
P128 = xxxx
P128=1.5*P102
P462 = Acceleration Time in seconds
P464 = Deceleration Time in seconds
P462 = xxxx
P464 = xxxx
P443i2= 11
P443i2(Index2) = 11
Configures drive for analog input
(0-10Vdc) to be active at
terminals X101 pin#15 and
pin#16
If 4-20mA is required closed
CUVC board mounted jumper
S3, position 1 and 2.
Start/Stop Control is located on
the PMU (operator control panel
mounted directly on the drive)
Speed Setpoint is controlled with
the Up / Down arrows.
Version 1.0 March 1, 2000
Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Connect External Wiring as connection diagram.
Customer
Connection Points
Internal Connections
Step 1: Dry set of contacts between terminals X101, pin#1 and pin#5 for
Local/Remote Mode Selection. Jumper if not required.
Step 2: Dry set of contacts between terminals X101, pin#1 and pin#8 for
Coast to Stop Selection. Jumper if not required.
Step 3: Dry set of contacts between terminals X101, pin#1 and pin#9 for
Source of Main Start/Stop Selection.
Step 4: Dry set of contacts between terminals X101, pin#1 and pin#7 for
Source of Fault Reset. Leave open if not required. “P” button on PMU
will be fault reset location if pin#7 is not used.
Step 5: Dry set of contacts between terminals X101, pin#1 and pin#6 for
Fixed Speed or Preset Speed Selection. Leave open if not required.
Page 20
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Speed value is determined by P402. A selection of P402=100% will be
a full speed reference setpoint.
Step 6: Fault Status is provided by a 24 Vdc signal at terminals X101
pin#3 with respect to pin#2. Leave open if not required.
Step 7: Drive Operating Status is provided by a 24 Vdc signal at
terminals X101 pin#4 with respect to pin#2.
Step 8: Connect external speed reference 0-10Volt or 4-20 mA (CUVC
board mounted jumper S3 pin 2 and 2 must be closed for mA input).
Adjust over the full range and monitor P447. With a zero input r447
should read near 0.00, and with full value r447 should read near 100%.
Step 9: Connect the motor to the load, unless the plan is to install an
encoder feedback or change to Vector Control.
Standard Commissioning for a Volts/Hz
controlled motor without feedback is
complete, after adjusting only 19
parameters.
Version 1.0 March 1, 2000
Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3.2 Volts/Hz with Encoder
Note: Complete section 1.3.1 before operating the motor with encoder feedback.
P060=5
P060 = 5
Select “Drive Settings”
P100=0
P100 = 0
P130 = ?
Selects Volts/Hz
with Encoder Feedback
P130 = Select Type of Encoder
11: Pulse Encoder
15: Pulse Encoder with Zero Pulse
P151 = Pulse Per Revolution (PPR)
P060 = Return to Parameter Menu
P151 = ?
P060 = 1
Page 22
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Additional Connection for +15 Vdc Encoder.
Step 10: Set Speed Reference to 20%.
Step 11: Provide Start command. Note that if Signal A and Signal B are
reversed, the motor will accelerate rapidly.
Step 12: Connect the motor to the load, unless the plan is to change to
Vector Control.
Standard Commissioning for a Volts/Hz
controlled motor with feedback is
complete, after adjusting only 24
parameters.
Version 1.0 March 1, 2000
Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3.3 Vector Control without Encoder Feedback
Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback).
P060=5
P060 = 5
Select “Drive Settings”
P100=3
P100 = 3
P060 = 1
P115 = 4
Wait
Selects Vector Control
without Encoder Feedback
P060 = Return to Parameter Menu
If you plan to use an encoder, go to
section1.3.4, otherwise continue.
P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
This test will adjust the following
parameters
P103, P120
Wait for display to change back
to o009.
Page 24
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
P115=5 Controller Optimization
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
P115=5
Wait
This test is best performed on a
coupled motor under actual conditions;
however, if the load is cyclic (0-100%
load variation), manual tuning may be
preferred.
This test will adjust the following
parameters
P116, P223, P235, P236,
P240, P471
Step 10: Set Speed Reference to 20%, and monitor speed feedback
r000, current feedback r004, and actual DC BUS r006. If stable
increase speed in increments and continue to monitor feedbacks.
Standard Commissioning for a Vector
Controlled motor without feedback is
complete, after adjusting only 24
parameters, and utilizing two of the self-
tuning options.
Version 1.0 March 1, 2000
Page 25
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3.4 Vector Control with Encoder Feedback
Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback), and
section 1.3.3 (Vector control without encoder feedback)
Step 10: Operate the uncoupled motor if sections 1.3.1 and 1.3.3 are complete and
verify operation of the motor without faults.
P060=5
P060 = 5
P100 = 4
P130 = ?
P151 = ?
P060 = 1
P115 = 4
Select “Drive Settings”
P100=4
Selects Vector Control
with Encoder Feedback
Connect encoder as per
diagram
P130 = Select Type of Encoder
11: Pulse Encoder
15: Pulse Encoder with Zero Pulse
P151 = Pulse Per Revolution (PPR)
P060 = Return to Parameter Menu
P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
Page 26
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
This test will adjust the following
parameters
P103, P120
Wait for display to change back
to o009.
Wait
P115=5 Controller Optimization
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
P115=5
This test is best performed on a
coupled motor under actual conditions;
however, if the load is cyclic (0-100%
load variation), manual tuning may be
preferred.
Wait
This test will adjust the following
parameters
P116, P223, P235, P236,
P240, P471
Step 11: Set Speed Reference to 20%, and monitor speed feedback
r000, current feedback r004, and actual DC BUS r006. If stable
increase speed in increments and continue to monitor feedbacks.
Standard Commissioning for a Vector
Controlled motor with feedback is
complete, after adjusting only 31
parameters, and utilizing two of the self-
tuning options.
Version 1.0 March 1, 2000
Page 27
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 28
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
1.4 Drive Control Word
Function Diagrams will be referred to in brackets with their number. Please refer to
function diagrams in the compendium. Example [Diagram Number]
Digital Inputs/Outputs:
Binector Assignments for Control
may be made from Digital Inputs
Assign Digital Inputs
P555, P556 & P557 can be used
to assign Coast to Stop
Assign Off2(Coast Stop)
P558, P559 & P560 can be used
to assign Quick Stop
Assign Off3(Quick Stop)
P554 MUST be assigned to
activate drive. Note:
Assign ON/OFF1
Acceleration and Deceleration
will be based on ramp generator
[320]
[180] Assign Other
Functionality as
Required
See [190]
Assign Other Control
Functionality as
Required
Version 1.0 March 1, 2000
Page 29
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 30
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
1.5 Communication Board Configuration
Select “Board Configuration”
Menu
P060 = 4
CBx Inserted? YES
Parameterize CBx Boards
See Function Diagrams
NO
P711 = ?
to
Simolink Address
0: Dispatcher (Master)
>0: Transceiver (Slave)
P721.1…5 = ?
SLB Inserted?
YES
NO
SLB Telegram Failure Time
P740 = ?
P741 = ?
P742 = ?
SLB Transmit Power
1: Up to 15 m
2: Up to 25 m
3: Up to 40 m
P740 = 0
P740
= 1
P743=0, Automatic number of
node evaluation.
Enter Number of Channels
P743 = 0
P745 = ?
Enter Simolink Cycle Time(must
P746 = ?
correspond to pulse frequency, i.e. =3.2)
Simolink Receive Address =
Node. Channel
P749.1…8 = ?
CBP Inserted?YES
NO
Input CBP Bus Addresses
Return to Parameter Menu
P918.1…2 = ?
P060 = 1
Version 1.0 March 1, 2000
Page 31
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 32
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2:
Parameterization of a Rectifer
Unit
SIMOVERT MASTERDRIVES
6SE70 VC
Vector Control
2.0 Power Section Defintion
2.1 Factory Reset
Basic Start-up
2.2 Rectifier or Regen without auto-transformer
2.3 Regen with auto-transformer
Version 1.0 March 1, 2000
Page 33
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 34
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
2.0 Power Section Definition
Note: Power Section is pre-defined at the factory. Power Section
Definition is required if a new board CUR board is put into the drive or
boards are switched between units with different ratings. CUR cards will
exist Regen Rectifiers and Large Common Rectifiers. The smaller
Common Rectifier will not have parameters. Drive should be defaulted
and re-parameterized after Power Section Definition.
P51=3 : Export Mode
P051 = 3
P52=2: Function select “Initialization”
P052 = 2
Input Code for unit (PWE)
(Refer to the following table)
P070 = xxx
P052 = 0
Return to Parameter Menu
Version 1.0 March 1, 2000
Page 35
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit List
P070:
Parameter Value (PWE)
P075:
Rated DC Output Current in Amps
In[A]
Large Common Rectifier
AC-DC type
3 AC 380V to 460V
3 AC 500V to 575V
3 AC 660V to 690V
PWE
Order Number
In[A
821.0
1023.0
1333.0
1780.0
103
105
109
118
6SE7038-2EH85-0AA0
6SE7041-0EH85-0AA0
6SE7041-3EK85-0AA0
6SE7041-8EK85-0AA0
101
104
107
111
120
6SE7037-7FH85-0AA0
6SE7041-0FH85-0AA0
6SE7041-3FK85-0AA0
6SE7041-5FK85-0AA0
6SE7041-8FK85-0AA0
774.0
1023.0
1285.0
1464.0
1880.0
102
106
108
110
119
6SE7037-7HH85-0AA0
6SE7041-0HH85-0AA0
6SE7041-3HK85-0AA0
6SE7041-5HK85-0AA0
6SE7041-8HK85-0AA0
774.0
1023.0
1285.0
1464.0
1880.0
Page 36
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Regenerative Rectifier
AC-DC type
3 AC
380V to 460V
PWE
PWE
Order Number
In[A]
Air Cool Water Cool
14
20
31
39
42
48
51
54
57
63
66
73
79
6SE7022-1EC85-1AA0
6SE7024-1EC85-1AA0
6SE7028-6EC85-1AA0
6SE7031-7EE85-1AA0
6SE7032-2EE85-1AA0
6SE7033-1EE85-1AA0
6SE7033-8EE85-1AA0
6SE7034-6EE85-1AA0
6SE7036-1EE85-1AA0
6SE7038-2EH85-1AA0
6SE7041-0EH85-1AA0
6SE7041-3EK85-1AA0
6SE7041-8EK85-1AA0
21.0
41.0
86.0
173.0
222.0
310.0
375.0
463.0
605.0
821.0
1023.0
1333.0
1780.0
3 AC
15
6SE7022-7FC85-1AA0
27.0
500V to 575V
21
28
32
38
44
46
49
52
55
61
67
71
74
80
6SE7024-1FC85-1AA0
6SE7027-2FC85-1AA0
6SE7028-8FC85-1AA0
6SE7031-5FE85-1AA0
6SE7032-4FE85-1AA0
6SE7032-7FE85-1AA0
6SE7033-5FE85-1AA0
6SE7034-2FE85-1AA0
6SE7035-4FE85-1AA0
6SE7037-7FH85-1AA0
6SE7041-0FH85-1AA0
6SE7041-3FK85-1AA0
6SE7041-5FK85-1AA0
6SE7041-8FK85-1AA0
41.0
72.0
94.0
151.0
235.0
270.0
354.0
420.0
536.0
774.0
1023.0
1285.0
1464.0
1880.0
Version 1.0 March 1, 2000
Page 37
Download from Www.Somanuals.com. All Manuals Search And Download.
Regenerative Rectifier
AC-DC type
3 AC
660V to 690V
PWE
PWE
Order Number
In[A]
Air Cool Water Cool
36
43
47
53
56
62
68
72
75
81
6SE7031-4HE85-1AA0
6SE7032-2HE85-1AA0
6SE7032-7HE85-1AA0
6SE7034-2HE85-1AA0
6SE7035-3HE85-1AA0
6SE7037-7HH85-1AA0
140.0
222.0
270.0
420.0
536.0
774.0
6SE7041-0HH85-1AA0 1023.0
6SE7041-3HK85-1AA0
6SE7041-5HK85-1AA0
6SE7041-8HK85-1AA0
1285.0
1464.0
1880.0
Page 38
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1 Factory Reset
P51=3 : Export Mode
P051 = 3
P52=2: Function select “Initialization”
P077=0 for standard default
P052 = 2
P077 = 0
P052 = 0
P052 = 1
P052=0 Return to Parameter Menu
P052=1 Perform Factory Reset
Version 1.0 March 1, 2000
Page 39
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 40
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Basic Start-up (Regenerative Rectifier without
Autotransformer)
P051=2
P051 = 2
Select “Basic Mode Settings”
P053 =6 Access Parameter
P053 = 6
P052 = 5
P071 = 460
P052 = 5
Drive Settings
P071 = Input Rectifier Voltage
Generally = 460 Volt
P320 = 20
P320 = 20
Smooth Load Amps, to
prevent input line sags
from effecting the DC BUS
regulator
P773 = 1.00
P773= 1.00
Deadband Converter, to
prevent “toggling” between
Regen and Rectifier
bridges.
Version 1.0 March 1, 2000
Page 41
Download from Www.Somanuals.com. All Manuals Search And Download.
With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9
P052 = 21
P052 = 0
The circuit identification test will take
about 10 seconds.
P052=0 Drive back to ready mode.
Standard Commissioning for a Common
Rectifier or a Regenerative Rectifier
without Autotransformer is complete, after
adjusting only 8 parameters.
Page 42
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Connect External Wiring as connection diagram.
Customer
Connection Points
Internal Connections
Step 1: Dry set of contacts between terminals X101, pin#6 and pin#13
for Local/Remote Mode Selection. Jumper if not required.
Step 2: Dry set of contacts between terminals X101, pin#6 and pin#10
for Coast to Stop Selection. Jumper if not required.
Step 3: Dry set of contacts between terminals X101, pin#6 and pin#9 for
Source of Main Start/Stop Selection.
Step 4: Dry set of contacts between terminals X101, pin#6 and pin#11
for Source of Fault Reset. Leave open if not required. “P” button on
PMU will be fault reset location if pin#11 is not used.
Step 5: Drive Operating Status is provided by a 24 Vdc signal at
terminals X104 pin#19 with respect to pin#20.
Version 1.0 March 1, 2000
Page 43
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 44
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3 Basic Start-up (Regenerative Rectifier with
Autotransformer)
P051=2
P051 = 2
Select “Basic Mode Settings”
P053 =6 Access Parameter
P053 = 6
P052 = 5
P071 = 460
P052 = 5
Drive Settings
P071 = Input Rectifier Voltage
Generally = 460 Volt
P320 = 20
P320 = 20
Smooth Load Amps, to
prevent input line sags
from effecting the DC BUS
regulator
P773= 1.00
P773 = 1.00
Deadband Converter, to
prevent “toggling” between
Regen and Rectifier
bridges.
Version 1.0 March 1, 2000
Page 45
Download from Www.Somanuals.com. All Manuals Search And Download.
P571=0 Selects Autotransformer
P571 = 0
P318 = 95%
Selects percentage of nominal
DC BUS voltage. In cases where
the input line voltage is
dependable a setting of 100% is
permissible.
P318 = 95
P052 = 21
P052 = 0
With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9
The circuit identification test will take
about 10 seconds.
P052=0 Drive back to ready mode.
Standard Commissioning for a
Regenerative Rectifier with
Autotransformer is complete, after
adjusting only 10 parameters.
Page 46
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3:
Simovis Trace Setup Method
SIMOVERT MASTERDRIVES
6SE70 VC
Vector Control
Version 1.0 March 1, 2000
Page 47
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 48
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
3.0 Simovis Trace
Load Simovis from
Vector Control
Documentation CD
Option: To speed up your
communication link set the
drive P701 = 38,400 with the
PMU and configure Simovis
for 38,400 communication.
Launch Simovis
from Desktop Icon
C
Select USS Bus Address,
Drive and SW Version.
Note: Proper Simovis Cable
must be used. (RS 232)
A
Add a Drive in
Simovis Bus
Configuration
B
C
A
B
Version 1.0 March 1, 2000
Page 49
Download from Www.Somanuals.com. All Manuals Search And Download.
Double Click Selected
Drive to start Simovis
Window
Green Box should be lit up
in the lower left corner
Verify Drive
Connection
A
Select Trace from
Diagnostics Menu Bar
B
B
A
Page 50
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Select Record Settings in
the Lower Left Corner
A
B
C
Select Desired Channels
to Record
Each Interval = (4.0 / P340) seconds.
Pre-trigger is in Percentage (%).
Set the Record Interval
and Pre-trigger
Function
Diagram
[720]
To Trigger With a Binector, Select:
Trigger Channel = K431
Trigger Condition “=” “1 Hex”
Select Trigger Channel
D
K431 is the output of a Binector to
Connector Converter that will be
configured on the following page.
B
C
D
A
Version 1.0 March 1, 2000
Page 51
Download from Www.Somanuals.com. All Manuals Search And Download.
To Configure the Trace to
Trigger with a Binector
follow instructions on this
page.
Select “Function Block
Grafics” from the
Parameter Menu Bar
A
The block activated by Parameter
U952.89 is selected with 289.
Select Function
Number 289
Zoom X 2
(with right Mouse click)
B
Set Trigger Binector in
U076.01
(i.e. U076.01 = 18 Din5)
C
Function
Diagram
[720]
K431 can now be used to
trigger the Trace function
when Binector (i.e. DIN 5) is
asserted high.
Activate Block
U952.89 = 4
D
A
D
B
C
Page 52
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Go to the Trace Window
(Diagnostics Menu – Trace)
A
Verify Record Settings B
Start Trace C
Trigger Trace
Observe Status Message
D
A
B
C
D
Version 1.0 March 1, 2000
Page 53
Download from Www.Somanuals.com. All Manuals Search And Download.
Click Data Set to
make it Active
Select Data Trace
Scale
A
Click and Drag
scale to shift it up
and down.
Vertical Axis
B
Y▲& Y ▼ to
change Scale
Click and drag “T”
marker to shift
Horizontal Scale.
Scale
Horizontal Axis
C
Note: Background can be changed
with right mouse click.
Traces can be saved for reference.
Move “[ ]” to
change scale
A
B
C
Page 54
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4:
When to Re-Tune the Drive
SIMOVERT MASTERDRIVES
6SE70 VC
Vector Control
Version 1.0 March 1, 2000
Page 55
Download from Www.Somanuals.com. All Manuals Search And Download.
Page 56
Version 1.0 March 1, 2000
Download from Www.Somanuals.com. All Manuals Search And Download.
4.0 Conditions that would merit re-tuning the drive
Hardware additions made to the drive, such as an output reactor or a
dv/dt filter.
Physical changes to the process, such as the motor being changed
(even if the it is an identical motor, bearing changes and coupling
changes can have an influence on performance), gearbox changes,
length of motor cables changed.
Process changes, such as motor loading, and speed range changes to
name a few. Note that since the type of change described is wide-
ranging manual tuning may be a better alternative. Review the
parameters effected for P115=5.
Software changes, P068, P095, P097, P100(this includes any changes
in P101 through P109), P339, P340, P357.
Exceptions:
• If the carrier frequency of P340 is adjusted in multiples that re-
tuning is not required (ie: 2.5 kHz to 5.0 kHz)
• If P100 is changed from a value of 4 to 5.
Repair or Maintenance, such as replacing either the motor or the CUVC
logic card.
Exceptions:
• If tuning parameters P103, P116, P120, P223, P235, P236,
P240 and P471 had been recorded prior to the CUVC card
being replaced.
Version 1.0 March 1, 2000
Page 57