11. TROUBLE SHOOTING
PROBLEM
CAUSES
SOLUTIONS
Heating inefficient during the first
combustions. Lack of draft.
Improper adjustment of the
Adjust the damper, minimize the
barometric damper (opened too
wide). Chimney flue restriction (too
long., or too many 90o elbows)
chimney length and use 45o elbows.
Furnace heats well, warm air plenum Improper installation of the ducts,
is very hot by there is not much heat little static pressure, unbalanced
Reinstall the ducts correctly.
Respect the minimum static pressure
of 0.20 in. w.c.
coming out in the room.
system (too many warm air outlets
and not enough cold air inlets).
Furnace consumes a lot of wood.
The thermostat which controls the
damper is continuously activated or
is too close to a source of cold air.
Damper not properly adjusted.
Relocate the thermostat. Adjust the
chain that links the damper to the
damper motor. Rebalance the
ventilation system in order to
House not insulated enough. Ash
increase the air flow in the room
drawer is not tightly closed. Furnace where the thermostat is located.
too small for the surface to be
heated. Unbalanced ventilation
system, very little heat where the
thermostat is located.
Fan start-up is too slow.
Fan “ON” setting too high. Return air Lower the temperature starting point.
is too cold (temperature lower than
65 degrees). Limit control not well
located in the warm air plenum.
The “fan ON” setting on limit control
is set at 150°F, it may reduced in
some particular installations. Reduce
the fresh air flow. Relocate the limit
control.
A lot of creosote, moderate heat
output.
Wet wood, lack of draft. Barometric
damper not properly adjusted. Dirty
chimney.
Use dry wood. Adjust the barometric
damper. Clean the chimney flue and
the furnace exchangers.
Furnace heats a lot but the warm air
plenum does not get hot.
Wet wood or low grade wood. Too
much cold air return for the hot air
ducts. Unbalanced ventilation
system. Blower speed too high
Use dry wood. Reinstall the
ventilation system correctly. Use a
lower blower speed.
IMPORTANT NOTE
FOR, INSTALLATION OF A CENTRAL HEATING VENTILATION SYSTEM, IT IS HIGHLY
RECOMMENDED TO CONSULT A HEATING SYSTEM VENTILATION SPECIALIST.
N.B.: UNITED STATES STOVE COMPANY IS NOT RESPONSIBLE FOR POOR APPLIANCE
PERFORMANCES, DUE TO AN IMPROPER INSTALLATION.
19
Download from Www.Somanuals.com. All Manuals Search And Download.