T E C H N I C A L
A P P L I C A T I O N
B U L L E T I N
#
9 5 - 2 9 2 4
Tripp Lite Network-Grade
Power Distribution Units (PDUs)
Tripp Lite Network-Grade PDUs are highly reliable multiple-outlet strips that distribute power from a UPS system, generator or utility wall outlet to
multiple devices. Tripp Lite offers three separate types of rackmount PDUs (see selector guide, below) with features and benefits to match every
application—networking, server, telecom and more.
PDU Selector Guide
(Features/Benefits)
Choose a PDU by identifying the ideal features and benefits for your application.
Tripp Lite PDUs
Basic PDUs
See page 4
Metered PDUs
See page 5
Switched PDUs
See pages 6-7
Feature
Benefit
Multiple Outlets
Increase the number of devices that
can be powered by a UPS system,
generator or utility source.
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
High-Current Plug and Increase connection flexibility by
Low-Current Outlets*
converting a single high-amperage outlet
into multiple low-amperage outlets.
ꢀ
ꢀ
Long Input Power Cord Increases installation flexibility by allowing
devices to be located far from an input
power source.
Digital Load Meter
Avoid overloads and safely add loads
as total equipment power consumption
is displayed.
Remote Control of
Individual Outlets
(via SNMP, Web or
Telnet)
Reduces frequency of costly service calls
by rebooting locked devices. Extends
runtime of critical devices by turning off
nonessential loads during blackouts.
ꢀ
ꢀ
Remote monitoring and Prevents overloads that cause
condition reporting
equipment downtime.
* Select models.
Feature Focus (See page 8)
• PDUs with Redundant Input Cords and Automatic Transfer Switch (ATS)
• PDUs with Dual Input Cords and Dual Independent Power Circuits
See inside for an additional selector guide, application diagrams and complete specifications
Copyright © 2008 Tripp Lite. All rights reserved. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
PDU Application Diagrams
Tripp Lite PDUs can be used in a variety of applications. The most popular applications are shown below. Contact Tripp Lite's technical support
department at (773) 869-1234 for additional assistance with a specific application.
Application #2:
Application #1:
Adding More Outlets to a UPS System
Converting a Single High-Amperage Outlet
into Multiple Low-Amperage Outlets
Applicable Tripp Lite PDUs: Models with High-Amperage Plugs
Applicable Tripp Lite PDUs: All Models
1
2
Description: PDU plugs into UPS system outlet. PDU increases
total number of outlets powered by the UPS system (from 6 to 18 in
this example. Additional front panel outlet not shown.).
1
Description: PDU plugs into UPS system's high-amperage outlet
2
(30-amp L5-30R outlet in this example). PDU increases total
number of low-amperage outlets powered by the UPS system (from 8
to 32 in this example; additional 12 front panel outlets not shown).
2
2
PDU2430 Power Distribution Unit (Rear Panel Shown)
PDU1215 Power Distribution Unit (Rear Panel Shown)
2
1
2
1
SMART1000RM1U UPS System (Rear Panel Shown)
SMART3000RM2U UPS System (Rear Panel Shown)
Application #3:
Application #4:
Remotely Controlling Individual Outlets
(via SNMP, Web or Telnet)
Distributing Facility UPS/Generator Power
to Multiple Outlets
Applicable Tripp Lite PDUs: All Switched Models
Applicable Tripp Lite PDUs: All Models
1
1
Description: PDU's Ethernet port connects to network wall jack.
Description: PDU plugs into a wall outlet supported by facility
2
2
Remote user controls power to PDU outlets for a variety of
UPS/generator power. PDU distributes power to equipment via 16
purposes. Benefits include rebooting locked devices to reduce the
frequency of costly service calls and turning off nonessential loads
during blackouts to extend battery backup runtime for critical devices.
outlets. (All PDU models support facility UPS/generator applications,
including all available PDU features.)
Remote Computer
Network
Jack
TCP/IP
2
2
1
Power Distribution Unit
(PDUMH30NET Front Panel Shown)
Power Distribution Unit (PDUMV20HVNET Shown)
1
From Facility UPS/Generator Source
SU5000RT4U UPS System (Rear Panel Shown)
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Basic PDUs
✔
✔
✔
Multiple Outlets
Long Input Power Cord
All-Metal Cabinet with
Versatile Mounting Options
Tripp Lite Basic PDUs reliably distribute AC power from a UPS system, generator or utility wall outlet to multiple devices. Basic PDUs offer high-
quality plug/outlet connections and a switch-free design to prevent the PDU from being accidentally disconnected or shut down. Versatile all-metal
cabinets with detachable mounting hardware accommodate a variety of mounting options: wallmount, under-counter and 19-inch rackmount
mounting in 1U and/or zero-U formats*. Basic PDUs are available in a variety of capacities from 15A to 30A. The PDUNV model features multiple
detachable plugs to connect the PDU to a variety of outlets. The PDU40TDUAL model features two separate power circuits (with corresponding
color-coded power cord, circuit breaker and outlets), making it ideal for servers with redundant power supplies and other equipment in loaded racks.
* See specifications for mounting options supported by each model.
FEATURES
A
front panel
D
front panel
D
E
E
A
B
B
PDU1215
rear panel
rear panel
front panel
A
C
F
C
F
PDU1220 & PDU1220T have 5-15/20R outlets
PDU2430
D
D
A
A
A
E
E
rear panel
front panel
F
B
C
B
PDU1415
C
PDU1420T has 5-15/20R outlets
rear panel
F
A
PDU1230
D
H
E
C
D
E
(not shown)
A
A
B
A
H
B
H
rear panel
F
C
PDUNV
G
PDU12IEC has C20 inlet for detachable input cord (user-supplied)
PDU40TDUAL
A
C
B
C
E
(not shown)
D
A
A
(not shown)
E
D
B
PDUV15
PDUV20 has 5-20P plug and 5-15/20R outlets
PDUV30HV
A
B
C
Multiple High-Quality Outlets
Long Input Cord with High-Quality Input Plug
AC Circuit Breaker Protection
D
E
F
G
H
Rugged All-Metal Housing
Secure Mounting Hardware
Grounding Lug
Twist-Lock L5-20P to Straight-Blade 5-20P Plug Adapters
Dual Circuits
SPECIFICATIONS
Input
Plug
Type
Input
Cord
Length
Unit
Dimensions
(H x W x D, in) Rackmount Mount
0U
Wallmount/
Input
Voltage
Maximum
Input Current Breakers
Outlet
Front
Outlets
Rear
Outlets
1U
Vertical Under Counter
Model
Qty. & Type(E)
Mount
✔
PDU1215
PDU1220
PDU1220T
PDU2430
PDU1230
PDU1415
PDU1420T
PDU40TDUAL
PDUNV
120V
15A
20A
20A
30A
1 x 15A
1 x 20A
1 x 20A
2 x 15A
5-15P
13 (5-15R)
13 (5-15/20R)
13 (5-15/20R)
24 (5-15R)
1
1
12
12
12
12
15 ft.
15 ft.
15 ft.
15 ft.
15 ft.
15 ft.
15 ft.
2 x 10 ft.
10 ft.
n/a
1.75 x 17.5 x 4.5
1.75 x 17.5 x 4.5
1.75 x 17.5 x 4.5
1.75 x 17.5 x 4.5
1.75 x 17.5 x 5.25
1.75 x 25.75 x 2.25
1.75 x 25.75 x 2.25
3 x 71 x 1.5
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
120V
5-20P
✔
120V
L5-20P
L5-30P
L6-30P
5-15P
1
✔
✔
120V
12
✔
✔
208/240V
120V
30A 2 x 15A, 4 x 10A
18 (2 C19 / 16 C13) 4 C13 / 2 C19 12 C13
✔
✔
15A
20A
1 x 15A
14 (5-15R)
14 (5-15/20R)
40 (5-15/20R)
n/a
n/a
14
n/a
n/a
n/a
✔
✔
120V
1 x 20A
L5-20P
14
✔
120V
2 x 20A
16A
2 x 20A L5-20P / 5-20P (2)(B)
40
n/a
✔
100-250V
100-250V
120V
2 x 16A Supports 6 plugs(C) 14 (12 C13 / 2 C19)
2 x 16A C20 inlet (no cord)(D) 14 (12 C13 / 2 C19)
4 C13
4 C13
12
8 C13 / 2 C19
1.75 x 17.5 x 4.25
1.75 x 17.5 x 4.25
1.75 x 36 x 1.25
1.75 x 36 x 1.25
3.5 x 63.75 x 2.25
✔
PDU12IEC
PDUV15
16A
8 C13 / 2 C19
✔
✔
15A
1 x 15A
1 x 20A
2 x 15A
5-15P
5-20P
12 (5-15R)
12 (5-15/20R)
n/a
n/a
n/a
15 ft.
15 ft.
10 ft.
n/a
n/a
n/a
✔
PDUV20
120V
20A
30A(A)
12
✔
PDUV30HV
208V
L6-30P
38 (32 C13 / 6 C19)
38
✔
(A) Code-derated maximum input current is 80% of value shown.
(B) PDU40TDUAL is a two-corded, dual-circuit PDU in a vertical strip format with (2) twist-lock L5-20P plugs
and (2) adapters to support connection to straight-blade 5-20R outlets.
(C) PDUNV includes a C20 input plug, plus 5 adapters which terminate in C14, 5-15P, 5-20P, L5-20P or L6-20P.
(D) PDU12IEC has a C20 power inlet. User must supply input cord with C19 connection to attach to the PDU,
and any plug type to connect to a utility source. (E) 5-15/20R outlets accept 5-15P or 5-20P plugs.
Certifications vary by model.
4
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
Download from Www.Somanuals.com. All Manuals Search And Download.
Metered PDUs
✔
✔
✔
✔
Digital Load Meter(s)
Multiple Outlets
Long Input Power Cord
All-Metal Cabinet with
Versatile Mounting Options
Tripp Lite Metered PDUs reliably distribute AC power from a UPS system, generator or utility wall outlet to multiple devices. Each model features
a digital load meter that helps you maximize the amount of devices that can be safely added to the PDU (without overloading it) by displaying the
total power consumption of connected equipment. Metered PDUs offer high-quality plug/outlet connections and a switch-free or switch-protected
design to prevent the PDU from being accidentally disconnected or shut down. Versatile all-metal cabinets with detachable mounting hardware
accommodate a variety of mounting options:* wallmount, under-counter and 19-inch rackmount mounting in 1U and/or zero-U formats. Metered
PDUs are available in 15A, 20A, 30A and 40A capacities. The PDUMV40 model features two separate 20-amp power circuits (with corresponding
color-coded power cord, circuit breaker, load meter and outlets), making it ideal for servers with redundant power supplies and other equipment in
loaded racks. The PDUMV30 model includes high-current 120V input with two banks of outlets and dual meters. The PDUMV20HV model
includes 208/230V input with C13 and C19 outlets. The PDUMV30HV model includes 208V input with two banks of C13 and C19 outlets and dual
meters. The PDUMV30, PDUMV20HV and PDUMV30HV models also include plug retention brackets that hold connected equipment cables in
place. The PDUMH15AT and PDUMH20AT models include redundant inputs with Automatic Transfer Switching (see page 8 for more information)
and are user-upgradeable to switched PDUs (requires SNMPWEBCARD, sold separately).
* See specifications for mounting options supported by each model.
FEATURES
F
A
front panel
E
J
A
F
E
(not shown)
B
D
B
PDUMV15
PDUMV20 has L5-20P plug, 5-20P plug
adapter and 20 5-15/20R outlets
rear panel
C
PDUMH15
C
D
G
PDUMH20 has L5-20P plug, 5-20P plug adapter and 5-15/20R outlets
I
I
A
E
(not shown)
E
(not shown)
A
K
F
F
D
D
B
K
B
A
B
PDUMV30HV
C
I
C
PDUMV30 has 24 5-15/20R outlets
PDUMV20HV has C20 inlet, detachable cord with L6-20P, 8 additional C13 outlets and single meter
H
PDUMV40
front panel
front panel
B
F
B
A
A
E
E
rear panel
B
rear panel
F
C
C
H
PDUMH15AT
PDUMH20AT
A
B
C
D
Digital Load Meter
Multiple High-Quality Outlets
Long Input Cord with High Quality Input Plug
AC Circuit Breaker Protection
E
F
G
H
I
Secure Mounting Hardware
Rugged All-Metal Housing
Grounding Lug
Twist-Lock L5-20P to Straight-Blade 5-20P Plug Adapter
Dual Circuits
J
K
Lighted Power Switch with Safety Cover
Cord Retention Bracket
SPECIFICATIONS
Input
Plug
Type
Input
Cord
Length
15 ft.
15 ft.
15 ft.
15 ft.
2 x 10 ft.
2 x 12 ft.
2 x 12 ft.
10 ft.
Unit
Dimensions
(H x W x D, in) Rackmount Mount
0U
Wallmount/
Input
Voltage
120V
120V
120V
120V
120V
120V(A)
120V(A)
120V
Maximum
Input Current
Outlet
Front
Outlets
Rear
Outlets
12
12
n/a
n/a
n/a
n/a
8
n/a
n/a
n/a
1U
Vertical Under Counter
Model
Meters
1 x 15A
1 x 20A
1 x 15A
1 x 20A
2 x 20A
1 x 15A
1 x 20A
2 x 20A
1 x 20A
2 x 15A
Qty. & Type(E)
Mount
✔
✔
✔
✔
✔
✔
✔
✔
PDUMH15
PDUMH20
PDUMV15
PDUMV20
PDUMV40
PDUMH15AT
PDUMH20AT
PDUMV30
PDUMV20HV
PDUMV30HV
15A
20A
15A
20A
2 x 20A
15A
5-15P
L5-20P / 5-20P(C)
5-15P
13 (5-15R)
13 (5-15/20R)
16 (5-15R)
20 (5-15/20R)
32 (5-15/20R)
8 (5-15R)
1
1
16
20
32
8
1.75 x 17.5 x 4.5
1.75 x 17.5 x 4.5
1.5 x 48 x 1.5
1.75 x 60 x 1.25
3 x 71.25 x 1.5
1.75 x 17.5 x 14.5
1.75 x 17.5 x 14.5
3.75 x 63.75 x 2.25
3.75 x 63.75 x 2.25
3.5 x 63.75 x 2.25
✔
✔
n/a
n/a
n/a
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
L5-20P / 5-20P(C)
L5-20P / 5-20P (2)(D)
5-15P
20A
L5-20P / 5-20P(C)
L5-30P
16 (5-15/20R)
24 (5-15/20R)
8
✔
30A(B)
20A(B)
30A(B)
24
38
30
n/a
n/a
n/a
208/230V
208V
L6-20P (C20 inlet) 38 (32 C13 / 6 C19)
10 ft.
10 ft.
✔
✔
L6-30P 30 (24 C13 / 6 C19)
(A) Primary input (fixed cord) tolerances: 99-138V, 45-65Hz. Outside of this range, the PDU switches to the secondary input (detachable cord) if within 99-138V range.
Two front panel LEDs marked “primary” and “secondary” indicate the active input source.
(B) Code-derated maximum input current is 80% of value shown.
(C) Includes a twist-lock L5-20P input plug and an adapter to support connection to a straight blade 5-20R outlet. PDUMH20AT includes (2) cords with twist-lock L5-20P input
plugs and (2) adapters to support connection to straight-blade 5-20R outlets.
(D) PDUMV40 is a two-corded, dual-circuit PDU with (2) twist-lock L5-20P plugs and (2) adapters to support connection to straight-blade 5-20R outlets.
(E) 5-15/20R outlets accept 5-15P or 5-20P plugs.
Certifications vary by model.
5
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
Download from Www.Somanuals.com. All Manuals Search And Download.
Switched PDUs
✔
✔
✔
✔
✔
✔
Remote Control of Individual Outlets
Remote Monitoring and Condition Reporting
Digital Load Meter(s)
Long Input Power Cord
All-Metal Cabinet with
Versatile Mounting Options
Multiple Outlets
Tripp Lite Switched PDUs reliably distribute AC power from a UPS system, generator or utility wall outlet to multiple devices. A built-in network
interface allows users to remotely control individual outlets (and connected devices) via SNMP, Web or Telnet. This feature reduces the frequency of
costly service calls by enabling remote reboot of locked devices. It can also be used to extend the runtime of critical devices by allowing users to
turn off nonessential devices during a blackout. Each model features one or more digital load meters that help you maximize the amount of devices
that can be safely added to the PDU (without overloading it) by displaying the total power consumption of connected equipment. High-quality
plug/outlet connections and a switch-free design prevent the PDU from being accidentally disconnected or shut down. Versatile all-metal cabinets
with detachable mounting hardware accommodate a variety of mounting options: wallmount, under-counter and 19-inch rackmount mounting in 1U
and/or zero-U formats*. Switched PDUs are available in 15A, 20A and 30A capacities.
* See specifications for mounting options supported by each model.
SPECIFICATIONS
Input
Plug
Type
Unit
Dimensions
(H x W x D, in)
0U
Wallmount/
Input
Maximum
Outlet
Input Cord
Length
1U or 2U Vertical Under Counter
Rackmount Mount
Model
Voltage Input Current
Meters
Qty. & Type(E)
Mount
Horizontal Models
PDUMH15ATNET
PDUMH20ATNET
PDUMH30NET
PDUMH15HVNET
PDUMH20HVNET
PDUMH30HVNET
Vertical Models
PDUMV15NET
PDUMV20NET
PDUMV30NET
PDUMV20HVNET
PDUMV30HVNET
120V(A)
120V(A)
120V
15A
20A
30A(B)
15A(B)
20A(B)
30A(B)
1 x 15A
1 x 20A
1 (2 x 20A)(C)
5-15P
L5-20P / 5-20P(D)
L5-30P
8 (5-15R)
16 (5-15/20R)
16 (5-15/20R)
8 (C13)
2 x 12 ft.
2 x 12 ft.
10 ft.
1.75 x 17.5 x 14.5
1.75 x 17.5 x 14.5
3.5 x 17.5 x 12.5
1.75 x 17.5 x 14.75
1.75 x 17.5 x 14.75
3.5 x 17.5 x 12.5
1U
1U
2U
1U
1U
2U
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
208/230V
208/230V
208V
1 x 15A
C14 inlet
6.5 ft.
1 x 20A
1 (2 x 15A)(C)
L6-20P (C20 inlet)
L6-30P
8 (C13)
8.5 ft.
16 (C13)
10 ft.
120V
120V
15A(B)
20A(B)
30A(B)
20A(B)
30A(B)
1 x 15A
1 x 20A
1 (2 x 20A)(C)
5-15P
L5-20P / 5-20P(D)
L5-30P
16 (5-15/20R)
24 (5-15/20R)
10 ft.
10 ft.
10 ft.
10 ft.
10 ft.
4.25 x 49 x 2.25
4.25 x 63 x 2.25
4.25 x 70 x 2.25
4.75 x 64 x 2.25
4.75 x 70 x 2.25
n/a
n/a
n/a
n/a
n/a
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
120V
24 (5-15/20R)
208/230V
208V
1 x 20A
1 (2 x 15A)(C)
L6-20P (C20 inlet)
L6-30P
24 (20 C13 / 4 C19)
24 (20 C13 / 4 C19)
(A) Primary input (fixed cord) tolerances: 99-138V, 45-65Hz. Outside of this range, the PDU switches to the secondary input (detachable cord) if within 99-138V range. Two front panel LEDs marked “primary” and
“secondary” indicate the active input source. Includes built-in Ethernet jack with programmed and real-time remote control options via SNMP, Web or Telnet.
(B) Code-derated maximum input current is 80% of value shown.
(C) Switchable meter displays total load for PDU or for each output bank.
(D) Includes twist-lock input plug(s) and adapter(s) to support connection to a straight-blade outlet.
(E) 5-15/20R outlets accept 5-15P or 5-20P plugs.
Certifications vary by model.
REMOTE OUTLET CONTROL APPLICATIONS
A
B
Load Shedding
Remote Reboot
A
B
Remote Computer
Remote Computer
Network Jack
Network Jack
TCP/IP
TCP/IP
PDU
ON
PDU
OFF
Power Cycle
CRITICAL
LOAD
NON-CRITICAL
LOAD
LOCKED/FROZEN
DEVICE
6
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
Download from Www.Somanuals.com. All Manuals Search And Download.
Switched PDUs
FEATURES
A
D
A
D
G
front panel
front panel
C
C
F
F
F
rear panel
F
D
I
rear panel
I
G
E
B
E
B
H
PDUMH15ATNET
PDUMH20ATNET
J
E
A
D
C
G
F
A
I
F
F
F
C
D
15
G
J
J
E
B
I
PDUMH30NET
PDUMH15HVNET
J
G
D
G
A
A
C
I
F
F
F
F
15
15
C
D
J
B
E
E
J
B
I
PDUMH20HVNET
PDUMH30HVNET
A
A
J
C
J
J
J
E
C
D
D
G
G
B
F
D
D
F
(not shown)
(not shown)
E
H
B
PDUMV15NET
PDUMV20NET
A
A
I
E
J
J
E
C
F
J
J
C
G
D
D
D
D
G
F
B
(not shown)
(not shown)
B
PDUMV30NET
PDUMV20HVNET
A
Network Interface for Remote Monitoring and Individual Outlet Control
A
J
J
B
C
E
C
High-Quality Input Plug
Digital Load Meter
D
E
Multiple High-Quality Outlets
Long Input Power Cord
F
G
Secure Mounting Hardware
Rugged All-Metal Housing
H
Twist-Lock L5-20P to Straight-Blade 5-20P Plug Adapter
D
D
G
F
B
I
J
C14 or C20 Power Inlet
Cord Retention Bracket
(not shown)
PDUMV30HVNET
Tripp Lite World Headquarters 1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 • www.tripplite.com
7
Download from Www.Somanuals.com. All Manuals Search And Download.
PDUs with Automatic Transfer Switching (ATS)
Tripp Lite PDUs with Automatic Transfer Switching (ATS) reliably distribute AC power from a UPS system, generator or utility source to multiple
devices. Each model includes dual AC input plugs and an internal automatic transfer switch between available power sources. These features
safeguard the uptime of connected devices by automatically providing a backup source of AC power if one source fails or is taken off-line for
maintenance. The two input cords can be connected to two utility sources, two generator sources, two UPS systems or any combination of these
sources.
Providing Redundant Input Power Sources for Single-Cord Devices
Applicable Tripp Lite PDUs: PDUMH15AT, PDUMH20AT,
PDUMH15ATNET, PDUMH20ATNET
Primary Utility/Generator
Circuit Wall Outlet
Secondary Utility/Generator
Circuit Wall Outlet
1
Description: PDU's primary input plugs into primary UPS system
2
(attached to its own circuit in this example). PDU's secondary input
plugs into secondary UPS system (attached to its own circuit in this
3
example). PDU's internal Automatic Transfer Switch (ATS)
Secondary UPS System
(SMART3000RM2U
Rear Panel Shown)
monitors voltage and frequency levels, switching to secondary input
when primary input is outside of safe operating range (99-138V and
45-65 Hz).
Primary UPS System
(SMART3000RM2U
Rear Panel Shown)
1
2
*
UP TO 16
3
Power Distribution Unit
(PDUMH20AT Rear Panel Shown)
LOAD
* Front panel outlets not shown.
REDUNDANT INPUT APPLICATIONS
Choose one of the following application configurations to provide redundant input (when desired).
B
C
A
Utility or Generator
Power Source
Utility or Generator
Power Source
Utility or Generator
Power Source
Utility or Generator
Power Source
Utility or Generator
Utility or Generator
Power Source
Power Source
UPS
UPS
UPS
PDU
LOAD
PDU
LOAD
PDU
LOAD
PDUs with Dual Independent Power Circuits
Dual Independent Power Circuit PDUs provide an efficient and manageable power distribution solution for multiple servers with redundant power
supplies, combining the advantages of two separate high-current PDUs without the extra expense, increased space requirements and added
management complexity. Input plugs, input power cords, breakers and outlets are color-coded to match each independent circuit, allowing simplified
cable management for multi-server configurations.
Providing Independent Power Sources for Devices with Redundant Power Cords
UPS/Utility/
Generator Source
UPS/Utility/
Generator Source
Applicable Tripp Lite PDUs: PDU40TDUAL, PDUMV40
1
Description: Each PDU input cord plugs into an independent UPS,
1
2
utility and/or generator power source. PDU distributes power to
1
equipment with redundant power supplies (also appropriate for
equipment without redundant power supplies), providing an
independent power source for each power supply.
Power Distribution Unit (PDUMV40 Shown)
2
Redundant Power Supply Load
Copyright © 2008 Tripp Lite. All rights reserved.
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
8
200803016 95-2924