Trane Water Dispenser SYS APM001 EN User Manual

Applications  
Engineering Manual  
Chiller System Design and  
Control  
SYS-APM001-EN  
May 2009  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chiller System Design  
and Control  
Susanna Hanson, applications engineer  
Mick Schwedler, applications manager  
Beth Bakkum, information designer  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preface  
This manual examines chilled-water-system components, configurations,  
options, and control strategies. The goal is to provide system designers with  
options they can use to satisfy the building owners’ desires, but this manual  
is not intended to be a complete chiller-system design manual.  
System designers may get the most use from this manual by familiarizing  
themselves with chilled-water-system basics and understanding the benefits  
of various options. Thereafter, when a specific job will benefit from these  
advantages, consult appropriate sections of the manual in detail.  
The Engineers Newsletters that are referenced in this manual are available at:  
www.trane.com/commercial/library/newsletters.asp  
Trane, in proposing these system design and application concepts, assumes no  
responsibility for the performance or desirability of any resulting system design. Design of  
the HVAC system is the prerogative and responsibility of the engineering professional.  
“Trane” and the Trane logo are registered trademarks, and TRACE, System Analyzer and  
TAP are trademarks of Trane, a business of Ingersoll-Rand.  
© 2009 Trane All rights reserved  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Contents  
Preface .................................................................................................. i  
Primary System Components ................................................... 1  
Application Considerations ...................................................... 18  
System Design Options ............................................................ 27  
System Configurations .............................................................. 42  
Chilled-Water System Variations ........................................... 70  
System Issues and Challenges ............................................... 79  
Low T Syndrome .......................................................................... 79  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iii  
System Controls ........................................................................... 87  
Conclusion ...................................................................................... 96  
Glossary ........................................................................................... 97  
References ..................................................................................... 100  
Index ................................................................................................ 103  
iv  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
Primary System Components  
Chilled-water systems consist of these functional parts:  
Chillers that cool the water or fluid  
Loads, often satisfied by coils, that transfer heat from air to water  
Chilled-water distribution pumps and pipes that send chilled water to the  
loads  
Condenser-water pumps, pipes, and cooling towers or condenser fans that  
reject heat from the chiller to ambient air  
Controls that coordinate the operation of the mechanical components  
together as a system  
In most cases, the chillers purpose is to make water colder. Some chillers cool a  
mixture of water and other chemicals, most commonly added to prevent  
freezing in low-temperature applications. Other additives may be used to  
modify the properties of the fluid, thereby making it more suitable for its  
intended application. For the purposes of this manual, the term water can be  
understood to be any such acceptable fluid, with recognition of the diverse  
applications in which chillers are used.  
For more details on the basic operation  
and components of a chilled-water  
system, consult another Trane  
publication, Chilled-Water Systems, part  
of the Air Conditioning Clinic Systems  
Series (TRG-TRC016-EN).  
The chiller rejects the heat extracted from the chilled water, plus the heat of  
compression (in the vapor-compression cycle), or the heat of absorption (in the  
case of an absorption chiller) to either the ambient air (air-cooled) or to another  
circuit of water (water-cooled). If the compressor-motor is refrigerant cooled,  
the chiller also rejects heat generated by motor inefficiency. Air-cooled  
condensers use fans to facilitate cooling by the ambient air. Water-cooled  
condensers typically use an evaporative cooling tower.  
After the water has been chilled, it is distributed via pumps, pipes, and valves  
(the distribution system) to the loads, where a heat exchanger—for example, a  
cooling coil in an air-handler—transfers heat from the air to the chilled water,  
which is returned to the chiller.  
Each component of the chilled-water system is explained in more detail in the  
following sections.  
Chiller  
There are a variety of water chiller types. Most commonly, they are absorption,  
centrifugal, helical rotary, and scroll. Some reciprocating chillers are also  
available. Chillers can be either air- or water-cooled. Major vapor-compression  
chiller components include an evaporator, compressor(s), condenser, and  
expansion device(s) (Figure 1). This manual discusses the chillers evaporator  
and condenser and their relationship to the chilled-water system.  
Specific application considerations for  
absorption chillers are addressed in  
another Trane publication, Absorption  
Chiller System Design (SYS-AM-13).  
SYS-APM001-EN  
Chiller System Design and Control  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Primary System Components  
Figure 1. Typical vapor-compression chiller  
Compressor  
Condenser  
Evaporator  
Water-cooled chillers are typically installed indoors; air-cooled chillers are  
typically installed outdoors—either on the roof or next to the building. In cold  
climates, air-cooled chillers may have a remote evaporator inside the building  
for freeze protection.  
Chiller evaporator  
The evaporator section of a water chiller is a shell-and-tube, refrigerant-to-  
water heat exchanger. Depending on the chillers design, either the  
refrigerant or the water is contained within the tubes.  
In a flooded shell-and-tube evaporator (Figure 2), cool, liquid refrigerant  
at low pressure enters the distribution system inside the shell and moves  
uniformly over the tubes, absorbing heat from warmer water that flows  
through the tubes.  
Figure 2. Flooded evaporator cut-away  
Refrigerant  
Vapor  
Liquid  
Refrigerant  
Chilled  
Water  
Supply  
Tube Bundle  
Chilled  
Water  
Return  
Liquid Level  
Sensor  
2
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Primary System Components  
In a direct-expansion (DX) shell-and-tube evaporator (Figure 3), warmer  
water fills the shell while the cool, lower-pressure liquid refrigerant flows  
through the tubes.  
Figure 3. Direct-expansion evaporator cut-away  
Chilled Water  
Supply  
Chilled  
Water  
Return  
Baffles  
Refrigerant  
Vapor  
Liquid  
Refrigerant  
Tube Bundle  
In either design, there is an approach temperature, which is the temperature  
difference between the refrigerant and exit water stream temperatures. The  
approach temperature is a measure of the heat transfer efficiency of the  
evaporator.  
Effect of chilled-water temperature  
For a given chiller, as the leaving chilled-water temperature drops, the  
refrigerant temperature and pressure must also drop. Conversely, as the  
leaving chilled-water temperature rises, so do the refrigerant temperature  
and pressure. When the leaving chilled-water temperature changes, the work  
a compressor must do also changes. The effect of leaving chilled-water  
temperature change on power consumption can be 1.0 to 2.2 percent per  
degree Fahrenheit [1.8 to 4.0 percent per degree Celsius]. Always consider  
the energy consumption of the entire system—not only the chiller. It is  
important to remember that although reducing leaving chilled-water  
temperature penalizes the chiller, it may reduce the overall system energy  
because less water is pumped through the system. System interactions are  
Effect of chilled-water flow rate and variation  
The evaporator is sensitive to the water flow rate. Excessive flow may result  
in high water velocity, erosion, vibration, or noise. Insufficient flow reduces  
heat-transfer efficiency and causes poor chiller performance, which might  
cause the chiller controls to invoke safeties. Some designers have concerns  
over low flow rates causing fouling. Generally, as Webb and Li noted, these  
concerns are unwarranted since the chilled-water loop is a closed system,  
thus reducing the chances of materials entering the system and causing  
fouling. Chilled-water flow through the evaporator must be kept within  
specific minimum and maximum limits. Contact the manufacturer for these  
limits.  
SYS-APM001-EN  
Chiller System Design and Control  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Primary System Components  
Some chiller controls can accommodate very little flow variation during  
machine operation. Other, more sophisticated, chiller controls allow some  
flow variation. Some chillers can tolerate flow-rate variations—as much as 50  
percent per minute or greater—while others can only tolerate up to 2 percent  
per minute. It is important that chiller capabilities are matched to system  
requirements. Contact the chiller manufacturer to determine the allowable  
rate of flow variation before varying the flow through the evaporator in a  
chiller. Flow variation is discussed in detail in the section “Variable-Primary-  
Water-cooled condenser  
To cool a building or process, the transferred heat must ultimately be rejected  
outdoors or to another system (heat recovery). The total amount of heat  
rejected includes the sum of the evaporator load, the compressor work, and  
the motor inefficiency. In a hermetic chiller, where the motor and compressor  
are in the same housing, these loads are all rejected through the condenser.  
In an open chiller, where the motor is separate from the compressor and  
connected by a shaft, the motor heat is rejected directly to the surrounding  
air. The evaporator load and the compressor work are rejected through the  
condenser, and the motor heat must be taken care of by the equipment  
rooms air-conditioning system.  
Effect of condenser-water temperature  
For a given chiller, as the leaving condenser-water temperature rises,  
refrigerant temperature and pressure also rise. Conversely, as the leaving  
condenser-water temperature drops, so do refrigerant temperature and  
pressure. As the refrigerant pressure and temperature changes, the work a  
compressor must do also changes. The effect of leaving-condenser-water  
temperature change on power consumption can be 1.0 to 2.2 percent per  
degree Fahrenheit [1.8 to 4.0 percent per degree Celsius]. Always consider  
the energy consumption of the entire system—not just the chiller. It is  
important to remember that although raising the leaving condenser-water  
temperature penalizes the chiller energy, it may reduce the energy used by  
the condenser pumps and cooling tower through the use of reduced flow  
rates and higher thermal driving-forces on the tower. System interactions are  
covered in more detail in “System Design Options” beginning on page 27.  
Effect of condenser-water flow rate  
The condenser is sensitive to the water flow rate. Excessive flow may result  
in high water velocity, erosion, vibration, or noise, while insufficient flow  
reduces heat transfer efficiency and causes poor chiller performance.  
Therefore, condenser-water flow through the chiller should be kept within a  
specific range of limits, except during transient startup conditions. Contact  
the manufacturer for these limits. Some chillers may allow extended  
operation below the selected flow rates.  
If water velocity through the condenser tubes is too low for significant  
periods of time and the water is extremely hard, long-term fouling of the  
tubes may also occur. Webb and Li tested a number of internally-enhanced  
condenser tubes at low velocity (3.51 ft/s [1.07 m/s]) and high water hardness.  
4
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Primary System Components  
While they found that some of the internally-enhanced tubes fouled in the  
long term, they concluded:  
Because of the high hardness and low water velocity used in these  
tests, we do not believe that the fouling experienced is typical of that  
expected in commercial installations. With use of good maintenance  
practices and water quality control, all of the tubes tested are  
probably suitable for long-term-fouling applications.  
It is important to remember that a chiller selected for low flow does not  
necessarily have low velocity through its tubes, as discussed in the chapter  
“System Design Options” on page 27. If tube fouling is a major concern,  
consider the use of smooth, rather than internally-enhanced, tubes in the  
condenser for ease of cleaning.  
Air-cooled condenser  
Air-cooled chillers do not use condenser-water, since they reject their heat by  
passing ambient air across refrigerant-to-air heat exchangers. In packaged  
air-cooled chillers, the manufacturers improve performance by staging fans  
in response to chiller load and ambient, dry-bulb temperature. Air-cooled  
chillers can also be split apart. One technique is to use an indoor remote  
evaporator with a packaged air-cooled condensing unit outdoors. Another  
technique is to locate the compressor(s) and the evaporator indoors (also  
known as a condenserless chiller) with an air-cooled condenser outdoors. It is  
also possible to have an indoor air-cooled condenser.  
Packaged or Split System?  
A number of different options are  
available for packaging and splitting the  
components of an air-cooled chiller. There  
is an excellent discussion in Chilled-Water  
Systems, part of the Air Conditioning  
Clinic Systems Series (TRG-TRC016-EN).  
Air-cooled versus water-cooled condensers  
One of the most distinctive differences in chiller heat exchangers continues to  
be the type of condenser selected—air-cooled versus water-cooled. When  
comparing air-cooled and water-cooled chillers, available capacity is the first  
distinguishing characteristic. Air-cooled condensers are typically available in  
packaged chillers ranging from 7.5 to 500 tons [25 to 1,580 kW]. Packaged  
water-cooled chillers are typically available from 10 to nearly 4,000 tons [35 to  
14,000 kW].  
Maintenance  
A major advantage of using an air-cooled chiller is the elimination of the  
cooling tower. This eliminates the concerns and maintenance requirements  
associated with water treatment, chiller condenser-tube cleaning, tower  
mechanical maintenance, freeze protection, and the availability and quality of  
makeup water. This reduced maintenance requirement is particularly  
attractive to building owners because it can substantially reduce operating  
costs. However, see “Energy efficiency” below.  
Systems that use an open cooling tower must have a water treatment  
program. Lack of tower-water treatment results in contaminants such as  
bacteria and algae. Fouled or corroded tubes can reduce chiller efficiency and  
lead to premature equipment failure.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
   
Primary System Components  
Low-ambient operation  
Air-cooled chillers are often selected for use in systems with year-round  
cooling requirements that cannot be met with an airside economizer. Air-  
cooled condensers have the ability to operate in below-freezing weather, and  
can do so without the problems associated with operating the cooling tower  
in these conditions. Cooling towers may require special control sequences,  
basin heaters, or an indoor sump for safe operation in freezing weather.  
For process applications, such as computer centers that require cooling year-  
round, this ability alone often dictates the use of air-cooled chillers.  
Energy efficiency  
Water-cooled chillers are typically more energy efficient than air-cooled  
chillers. The refrigerant condensing temperature in an air-cooled chiller is  
dependent on the ambient dry-bulb temperature. The condensing  
temperature in a water-cooled chiller is dependent on the condenser-water  
temperature, which is dependent on the ambient wet-bulb temperature.  
Since the design wet-bulb temperature is often significantly lower than the  
dry-bulb temperature, the refrigerant condensing temperature (and pressure)  
in a water-cooled chiller can be lower than in an air-cooled chiller. For  
example, at an outdoor design condition of 95°F [35°C] dry-bulb temperature,  
78°F [25.6°C] wet-bulb temperature, a cooling tower delivers 85°F [29.4°C]  
water to the water-cooled condenser. This results in a refrigerant condensing  
temperature of approximately 100°F [37.8°C]. At these same outdoor  
conditions, the refrigerant condensing temperature in an air-cooled  
condenser is approximately 125°F [51.7°C]. A lower condensing temperature,  
and therefore a lower condensing pressure, means that the compressor  
needs to do less work and consumes less energy.  
This efficiency advantage may lessen at part-load conditions because the dry-  
bulb temperature tends to drop faster than the wet-bulb temperature (see  
Figure 4). As a result, the air-cooled chiller may benefit from greater  
condenser relief. Additionally, the efficiency advantage of a water-cooled  
chiller is much less when the additional cooling tower and condenser pump  
energy costs are considered. Performing a comprehensive energy analysis is  
the best method of estimating the operating-cost difference between air-  
cooled and water-cooled systems.  
6
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Primary System Components  
Figure 4. Air-cooled or water-cooled efficiency  
Dry Bulb  
Wet Bulb  
12  
12  
12  
12  
12  
Midn1ig2ht  
Noon  
Midnight  
midnight  
midnight  
Another advantage of an air-cooled chiller is its delivery as a “packaged  
system.” Reduced design time, simplified installation, higher reliability, and  
single-source responsibility are all factors that make the factory packaging of  
the condenser, compressor, and evaporator a major benefit. A water-cooled  
chiller has the additional requirements of condenser-water piping, pump,  
cooling tower, and associated controls.  
Water-cooled chillers typically last longer than air-cooled chillers. This  
difference is due to the fact that the air-cooled chiller is installed outdoors,  
whereas the water-cooled chiller is installed indoors. Also, using water as the  
condensing fluid allows the water-cooled chiller to operate at lower pressures  
than the air-cooled chiller. In general, air-cooled chillers last 15 to 20 years,  
while water-cooled chillers last 20 to 30 years.  
To summarize the comparison of air-cooled and water-cooled chillers, air-  
cooled chiller advantages include lower maintenance costs, a pre-packaged  
system for easier design and installation, and better low-ambient operation.  
Water-cooled chiller advantages include greater energy efficiency (at least at  
design conditions) and longer equipment life.  
Loads  
In comfort-cooling applications, cooling loads are often satisfied by air  
handlers equipped with coils to transfer heat from the conditioned space air  
to circulating chilled-water. Air is cooled and dehumidified as it passes across  
the finned surface of the cooling coils. Since the psychrometric process of  
conditioning air takes place at the coils, selection of the optimum coil size  
and type from the wide variety available is important for proper system  
performance.  
Some specialized process loads do not involve cooling air. Instead, they may  
involve heat transfer directly within a piece of process equipment, such as the  
cooling jacket of an injection-molding machine.  
SYS-APM001-EN  
Chiller System Design and Control  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Primary System Components  
Heat transferred from the loads can be controlled in a number of ways:  
Three-way valve  
Two-way valve  
Variable-speed pump  
Face-and-bypass dampers  
Three-way valve load control  
A three-way control valve (Figure 5) regulates the amount of water passing  
through a coil in response to loads. The valve bypasses unused water around  
the coil and requires a constant flow of water in the system, regardless of  
load. A drawback of this bypass is that the temperature of the water leaving  
the three-way valve is reduced at part-load conditions. This can be a major  
contributor to so-called “low T syndrome” discussed on page 79. Three-way  
valves are used in many existing systems, especially in those with constant-  
volume pumping.  
Figure 5. Three-way valve  
Airflow  
Three-Way  
Bypass  
Modulating  
Pipe  
Valve  
Two-way valve load control  
A two-way, water modulating valve (Figure 6) at the coil performs the same  
water throttling function as the three-way valve. The coil sees no difference  
between these two methods. The chilled-water system, however, sees a great  
difference. In the case of the two-way valve, all flow in the coil circuit is  
throttled. No water is bypassed. Consequently, a system using two-way  
valves is a variable-flow chilled-water system. The temperature of the water  
leaving the coil is not diluted by bypass water so at part-load conditions, the  
system return-water temperature is higher than with three-way valve control.  
8
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Primary System Components  
Figure 6. Two-way valve  
Airflow  
Two-Way  
Modulating  
Valve  
Variable-speed pump load control  
By using a pump for each coil (Figure 7), the flow may be controlled by  
varying the pump speed. In such systems, there may be no control valves at  
the coil. This can reduce both the valve and the valve installation costs, but  
increases coil pump and maintenance costs.  
Figure 7. Variable-speed pump load control  
Airflow  
Variable  
Speed Pump  
Face-and-bypass dampers  
Figure 8 shows a control variation using an uncontrolled or “wild” coil. In  
this system, control of the conditioned air supply is executed by face-and-  
bypass dampers that permit a portion of the air to bypass the coil surface.  
Advantages of this strategy are the elimination of control valves and  
improved part-load dehumidification. A disadvantage is that all the water is  
SYS-APM001-EN  
Chiller System Design and Control  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Primary System Components  
pumped all the time; however, in systems with very small water pressure  
drops, this system arrangement may work economically.  
Figure 8. Uncontrolled water flow with bypass damper  
Bypass  
Damper  
Airflow  
Face  
Damper  
Chilled-Water Distribution System  
Chilled water is circulated through fixed piping—most commonly steel,  
copper, or plastic—that connects the chiller with various load terminals.  
Piping is sized to meet pressure loss, water velocity, and construction cost  
parameters.  
Additional reference information on the  
components of a chilled-water  
distribution system is available in the  
2008 ASHRAE HVAC Systems and  
Equipment Handbook, chapter 12,  
“Hydronic Heating and Cooling System  
Design.”  
Chilled-water pump  
The chilled-water pump creates pressure to circulate chilled water within the  
loop. Generally, the pump must overcome the frictional pressure losses  
caused by the piping, coils, and chiller and the pressure differential across  
open control valves in the system. The pump, while working at the system  
static pressure, does not need to overcome this static pressure. For example,  
in a forty-story building, the pump need not overcome the static pressure due  
to those forty stories.  
The chilled-water pump is typically located upstream of the chiller; however,  
it may be anywhere in the system, provided that the pump:  
meets the minimum pump net positive suction-head requirements. That  
is, the system pressure at the pump inlet must be both positive and high  
enough to allow the pump to operate properly;  
maintains the minimum dynamic pressure head at critical system  
components (usually the chiller). If the dynamic pressure head is not high  
enough at these components, proper flow will not be established through  
them;  
10  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
       
Primary System Components  
accommodates the total pressure (static head plus dynamic head) on  
system components such as the chillers evaporator, valves, etc.  
Note that the pump heat is added to the water and must be absorbed by the  
chiller. Generally, this represents a very small temperature increase.  
Multiple pumps are often used for redundancy. Depending on the terminal  
control devices and system configurations, the chilled-water pumps may be  
either constant- or variable-flow.  
As previously stated, pumps may be either on the inlet or the outlet of the  
chiller, as long as the inlet of the pump experiences an adequate, positive  
suction pressure. In applications where there is a significant liquid column  
head (for example, a high-rise building), the pump is often located at the  
chillers outlet so that the evaporator bundle is subject only to the static head  
(rather than the static head plus the dynamic head added by the pump). The  
need for high-pressure water boxes on the chiller can be eliminated.  
Conversely, an advantage of locating the pump at the chillers inlet is that if  
the pump motor rejects its heat to the water, the heat can be removed directly  
by the chiller. The chiller does not need to compensate for the pump heat by  
making colder water.  
Pump per chiller  
Figure 9. Pump per chiller  
In either a primary–secondary or variable-primary-flow system, using one  
pump per chiller simplifies system hydraulics (Figure 9). The pump can be  
selected to produce the flow and pressure drop necessary for the specific  
chiller. Bringing on additional pumps changes system hydraulics, but only  
minimally. One drawback of such a system is a lack of redundancy, since the  
pump and chiller are dedicated to one another. This may be overcome by  
using a spare pump, pipes, and valves so that the spare pump could work  
with any chiller during emergency conditions.  
Pump  
Pump  
Manifolded pumps  
Load  
In an effort to resolve the redundancy consideration, some designers prefer  
to manifold pumps and provide n+1 pumps, where n is the number of chillers  
(Figure 10). Such an arrangement allows any pump to be used with any  
chiller. However, system hydraulics become more complicated. Unless all  
piping runs and evaporator pressure drops are equal, the amount of water  
flowing to each chiller will differ. As discussed in “Moderate ’low T  
syndrome’" on page 68, manifolded pumps present a control opportunity  
when low T is experienced.  
Figure 10. Manifolded pumps  
Manifolded  
Pumps  
Either pump configuration can be successful; one pump per chiller simplifies  
the hydraulics, while manifolded pumps allow redundancy.  
Distribution piping  
Load  
By itself, the distribution system is easy to understand. Figure 11 shows a  
simplified distribution system consisting of multiple cooling coils, each  
controlled by a thermostat that regulates the flow in its respective coil. The  
SYS-APM001-EN  
Chiller System Design and Control  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Primary System Components  
valves may be either three-way or two-way. As previously discussed, three-  
way valves require constant water flow, while two-way valves allow the water  
flow in the system to vary. As flow varies, the pump may simply ride its curve  
or use a method of flow control such as a variable-speed drive. Refer to the  
distribution-system options.  
Figure 11. Simplified distribution system  
Expansion  
Tank  
Pump  
Chiller  
Distribution  
Piping  
Loads  
The distribution system may contain other components, such as an  
expansion tank, control valves, balancing valves, check valves, and an air  
separator, to name a few. The density, and therefore the volume, of the water  
in a “closed” chilled-water distribution system varies as it undergoes  
changes in temperature. The expansion tank allows for this expansion and  
contraction of water volume.  
Figure 12. Constant flow system  
Pumping arrangements  
CV  
Pump  
Variations on three basic pumping arrangements are common. They are  
referred to as constant flow, primary-secondary (decoupled) flow, and  
variable-primary flow (VPF). The implications and nuances of each of these is  
Chillers  
Constant flow system  
When a chiller is on, a constant speed pump dedicated to it is on, and there  
need not be any other pumps operated in the system (Figure 12). This is a  
simple system and makes the most sense when there will only be one chiller  
operated at a time in the system. Challenges with this system arise at part  
load when chillers are in the parallel arrangement (refer to “Parallel Chillers”  
on page 42). To solve some of these problems, the chillers can be placed in  
Three-Way  
Control  
Valve  
Load  
12  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
       
Primary System Components  
the series, or another pumping arrangement can be considered. Reducing the  
flow rate affects this system types energy use all the time, so careful  
attention to flow rates and temperature is critical (refer to “System Design  
Figure 13. Primary-secondary system  
CV  
Pump  
Chillers  
Primary-secondary system  
In this configuration (Figure 13), the distribution piping is decoupled from the  
chiller piping and is known as the primary-secondary or decoupled system.  
There is constant primary flow through the operating chiller(s) and variable  
secondary flow through the loads. A bypass pipe between the two balances  
the primary flow with the secondary flow. Because there are more pumps  
and a bypass, this system costs more than a constant flow system to install.  
CV  
Pump  
Bypass (Decoupler)  
VV  
Pump  
Two-Way  
Control  
Valve  
Load  
Variable-primary system  
This pumping arrangement (Figure 14) was made possible in recent years by  
advanced chiller controls that permit varying the flow through the chillers.  
Like a constant flow system, the distribution piping is directly connected to  
the chiller piping. Flow is varied through at least most of the loads and the  
chillers. A smaller bypass (compared to the primary-secondary system)  
ensures chiller minimum flow rates are avoided. Fewer pumps and smaller  
bypass lead to lower first costs compared to the primary-secondary system.  
Operation costs can also be lower, but the plant is controlled differently than  
in other pumping arrangements and operator training is essential. This  
system type is covered in detail in “Variable-Primary-Flow Systems” on  
Figure 14. Variable-primary system  
VV  
Pump  
~
Chillers  
VV  
Pump  
~
Condenser-Water System  
Minimum Flow Bypass Valve  
As in chilled-water distribution systems, condenser-water system piping—  
most commonly steel, copper, or plastic—is sized to meet a projects  
operating pressure, pressure loss, water velocity, and construction cost  
parameters. Pressure drop through piping and the chillers condenser, plus  
the cooling tower static lift, is overcome by use of a condenser-water pump.  
Two-Way  
Control  
Valve  
Load  
To ensure optimum heat transfer performance, the condenser-heat transfer  
surfaces must be kept free of scale and sludge. Even a thin deposit of scale  
can substantially reduce heat transfer capacity and chiller efficiency. Specifics  
of cooling-tower-water treatment are not discussed in this manual. Engage  
the services of a qualified water treatment specialist to determine the level of  
water treatment required to remove contaminants from the cooling tower  
water.  
Cooling tower  
To reject heat, water is passed through a cooling tower where a portion of it  
evaporates, thus cooling the remaining water. A particular cooling towers  
effectiveness at transferring heat depends on water flow rate, water  
temperature, and ambient wet bulb. The temperature difference between the  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
             
Primary System Components  
water entering and leaving the cooling tower is the range. The temperature  
difference between the leaving water temperature and the entering wet-bulb  
temperature is the approach.  
Effect of load on cooling tower performance  
As the building load—or heat rejection—decreases, range and approach also  
decrease. This means that when the building is at part load, the cooling tower  
can provide colder water at the same ambient wet-bulb temperature.  
Effect of ambient conditions on cooling tower performance  
As ambient wet-bulb temperature drops, the approach—at a constant load—  
increases. This is counter-intuitive to many, and it must be considered when  
cooling-tower-control strategies are developed. Detailed descriptions of these  
additional information, refer to 2008 ASHRAE HVAC Systems and Equipment  
Handbook, chapter 39, “Cooling Towers.”  
Condenser-water pumping arrangements  
Water-cooled chillers require condenser-water-system variations to be  
considered. For a discussion of condenser-water temperatures and flow  
rates, refer to “System Design Options” on page 27. Since air-cooled-chiller  
condenser controls are part of the chiller design, they are not discussed in  
this manual.  
Most important, the inlet to the pump must have sufficient net positive head.  
This often means locating the pump below the cooling-tower sump.  
Single tower per chiller  
Figure 15. Manifolded condenser-  
water pumps  
In some applications each chiller has a dedicated cooling tower. This is most  
likely to occur when chillers, and their accompanying towers, are purchased  
at different times during the facilitys life—such as when additions are made.  
Cooling  
Towers  
Manifolded pumps  
A much-used pumping arrangement has a single cooling-tower sump with  
manifolded pumps, one condenser water line, and separate, smaller, pipes  
for each chiller as shown in Figure 15. This provides a number of advantages:  
Manifolded  
Pumps  
Pumping redundancy  
If cooling towers cells can be isolated, any cooling-tower cell can run with  
any chiller.  
Hydraulics are generally less problematic than on the chilled-water side.  
Cooling towers can be located remotely from chillers, with only a single  
supply and return pipe to connect them.  
Chillers  
14  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
     
Primary System Components  
Unit-Level Controls  
The chilled-water supply temperature is usually controlled by the chiller.  
Most commonly, supply water temperature is used as the sensed variable to  
permit control of chiller capacity to meet system load demand. Supply-  
temperature control strategies may be used on either constant- or variable-  
flow systems. As previously discussed, flow control is executed at the load  
terminals using three-way or two-way valves, or separate pumps for each  
coil. Control capabilities run the gamut from slow-acting pneumatic controls,  
to electromechanical controls, to sophisticated digital controls that use "feed-  
forward" algorithms tuned to give superior performance.  
Chiller control  
Todays chiller controls are capable of doing more than simply turning the  
chiller on and off. At a minimum, these controls should monitor:  
Safety points, such as bearing temperatures and electrical points, that  
may cause motor failure when out of range.  
Data points that may cause operational problems if corrective action is  
not taken. An example is low chilled-water or refrigerant temperature,  
which may result in freezing in or around the evaporator tubes.  
General points to ensure proper chiller performance and refrigerant  
containment.  
Table 1. Recommended chiller-monitoring points per ASHRAE Standard 147  
Flow  
Flow  
Inlet Pressure  
Inlet Temperature  
Outlet Pressure  
Outlet Temperature  
Refrigerant Pressure  
Refrigerant Temp.  
Level  
Inlet Pressure  
Chilled Water (or other  
secondary coolant)  
Condenser  
Water  
Inlet Temperature  
Outlet Pressure  
Outlet Temperature  
Refrigerant Pressure  
Refrigerant Temp.  
Level  
Evaporator  
Condenser  
Refrigerant  
Pressure  
Compressor Discharge Temp.  
Compressor Suction Temp.  
Addition of (in Refrigerant Log)  
PPM Refrigerant Monitor Level  
Date and Time Data  
Signature of Reviewer  
Amperes Per Phase  
Volts Per Phase  
Oil  
Temperature  
Addition of  
Vibration Levels  
Purge  
Exhaust Time  
Discharge Count  
Dry Bulb  
Logs  
Ambient Temperatures  
Motor  
Wet Bulb  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
   
Primary System Components  
In addition to monitoring data, it is vital that the chiller controls alert  
operators to possible problems. Diagnostic messages are necessary for the  
operator to respond to safety issues and data points that are outside normal  
operating ranges. While communicating these diagnostic messages is a  
requirement, some chiller controls include factory-installed programming  
that responds to the issue causing the diagnostic messages. For example,  
when the chilled-water temperature nears freezing, the chiller sends a  
diagnostic message and adapts its operation by reducing the compressor  
capacity, raising the chilled-water temperature to a safer condition.  
Finally, the chiller controls should communicate with a system-level  
controller. There are many system aspects that are outside the chillers direct  
control, such as condenser-water temperature and the amount of fluid  
flowing through the evaporator and condenser. To minimize the system  
energy costs, the system controls must coordinate chiller, pump, cooling-  
tower, and terminal-unit controls. This can only be done if adequate  
information is communicated from each system component to the system-  
level controls. System-level control is discussed in detail in “System  
Controls” beginning on page 87.  
Centrifugal chiller capacity control  
The capacity of a centrifugal chiller can be modulated using inlet guide vanes  
(IGV) or a combination of IGV and a variable-speed drive (adjustable-  
frequency drive, AFD)(Figure 16). Variable-speed drives are widely used with  
fans and pumps, and as a result of the advancement of microprocessor-based  
controls for chillers, they are being applied to centrifugal water chillers.  
For more information about chillers,  
Trane Air Conditioning Clinics are  
available for centrifugal (TRG-TRC010-  
EN), absorption (TRG-TRC011-EN) and  
helical-rotary (TRG-TRC012-EN) chiller  
types.  
Figure 16. Centrifugal chiller with AFD  
Compressor  
Inlet Guide Vanes  
Condenser  
Adjustable  
Frequency  
Drive  
Evaporator  
ASHRAE 90.1 requires a chiller to meet both full and part-load efficiency  
requirements. Using an AFD with a centrifugal chiller degrades the chillers  
full-load efficiency. This causes an increase in electricity demand or real-time  
pricing charges. At the time of peak cooling, such charges can be ten (or  
more) times the non-peak charges. In return, an AFD can offer energy savings  
16  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
   
Primary System Components  
by reducing motor speed at “low-lift” conditions, when cooler condenser  
water is available.  
Certain system characteristics favor the application of an AFD, including:  
A substantial number of part-load operating hours (for example, when an  
air- or water-economizer is not installed in the system)  
The availability of cooler condenser water (condenser-water reset)  
Chilled-water reset control  
Chiller savings using condenser- and chilled-water-temperature reset,  
however, should be balanced against the increase in pumping and cooling-  
tower energy. Performing a comprehensive energy analysis is the best  
method of determining whether an AFD is desirable. It is important to use  
actual utility costs, not a “combined” cost, for demand and consumption  
charges. It is also important to include drive maintenance and replacement  
costs, since the drive life is shorter than the chiller life. See “Energy and  
Depending on the application, it may make sense to use the additional  
money that would be needed to purchase an AFD to purchase a more  
efficient chiller instead. This is especially true if demand charges are  
significant, or if the condenser water is close to its design temperature most  
of the time (e.g., in a hot and humid climate such as Miami).  
Consider the following analysis of an 800-ton office building with two  
chillers. The analysis compares equally priced high efficiency or AFD-  
equipped chillers, as one or both of the chillers. Utility costs for the combined  
or “blended” rate are $0.10 per kWh and for the actual rate are $12 per kW  
and $0.06 per kWh.  
Simple paybacks using the combined rate analysis show almost no difference  
between the two options (Table 2). However, when utility costs with an actual  
consumption and demand component are used, the difference between the  
alternatives is much more pronounced. The conclusion is that using actual  
energy rates matters a great deal.  
Table 2. Analysis of high-efficiency chiller options with combined vs actual rates  
Simple paybacks, humid climate  
AFD on both chillers  
Combined rate  
Actual rate  
12.7  
7.2  
7.1  
6.1  
6.3  
High efficiency on both chillers  
AFD on one chiller  
8.3  
10.8  
High efficiency on one chiller  
7.7  
SYS-APM001-EN  
Chiller System Design and Control  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Application Considerations  
Chiller system size affects design and control considerations. Each size comes  
with its own set of advantages and challenges.  
Small Chilled-Water Systems (1-2 chillers)  
Figure 17. Small chilled-water system schematic  
Pump  
Air-Cooled Chiller  
Control  
Valve  
Load  
A common design goal for the small chilled-water system with one or two  
chillers (Figure 17) is to minimize complexity while balancing energy  
consumption goals. Smaller chilled-water systems may have smaller budgets  
allotted for operation and maintenance and may run unattended more often  
than larger systems. Keeping it simple, while capitalizing on chilled water  
advantages, is the hallmark of a successful project.  
The first cost of a small system is a common hurdle faced by a building owner.  
There are ways to minimize first costs without sacrificing operating costs. For  
example, a wider design T reduces flow rates, which in turn reduces pipe and  
pump sizes. In addition to reducing pump and pricing costs, this may also allow  
the designer to avoid installing a storage tank to meet the required chiller “loop  
multiple chillers, using a variable-primary-flow design (“Variable-Primary-Flow  
Systems” on page 55) can reduce the number of pumps, starters, electrical  
equipment, and space required.  
18  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
       
Application Considerations  
Constant flow  
Constant flow is simple and often applied to small systems up to 200 tons—  
as long as the system pressure drop is fairly low and a wider T is applied to  
reduce the system flow rate. In constant flow systems, appropriate chilled-  
water reset reduces chiller energy. These two strategies for saving energy  
(reducing flow rates and/or chilled-water temperature reset) can be used  
successfully in the constant flow designs more common in small chilled-  
water systems. These two strategies are covered in “Selecting Chilled- and  
Constant flow systems use either a balancing or pressure-reducing valve or,  
in a few cases, trim the pump impeller to set the system design flow.  
Pressure-reducing valves waste pump energy. Another option designers use  
to reduce pumping energy and increase system flexibility is to install a  
variable frequency drive on the pump motor and set it at a constant speed  
during system commissioning.  
If, instead, system flow is balanced by trimming the pump impeller, flow  
adjustment is much more difficult. Using a variable frequency drive at a set  
speed allows the flow to be decreased or increased in the future if necessary.  
This approach is more cost effective because the cost of variable frequency  
drives has dropped. Any incremental cost will be offset by the elimination of  
the balancing valves and pump starter.  
Variable flow  
Although a variable-primary-flow system may cost more than a constant flow  
system, it is growing in popularity because it is less expensive than installing  
a decoupled system. Another reason for its increased popularity is that pump  
energy is reduced.  
Some owners are concerned that the controls are more complex, but variable  
flow systems can work very simply in the small chilled-water system when  
there is only one chiller or when two chillers are piped in series. Key control  
issues for variable flow systems are discussed in “Variable-Primary-Flow  
Systems” on page 55, and variable flow with series chillers in “Series  
Condensing method  
Many small chilled-water systems use air-cooled chillers because of the lower  
maintenance requirements of the condensing circuit. Water-cooled systems  
are generally more energy efficient and have more options for features such  
as heat recovery, though some air-cooled chillers have partial heat recovery  
options.  
To help the owner decide on the system selection, a comprehensive energy  
analysis is the best method of estimating the life cycle cost difference  
between air-cooled and water-cooled systems. Energy analysis is likely  
required for many facilities seeking LEED certification, so it may already be  
SYS-APM001-EN  
Chiller System Design and Control  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Application Considerations  
Number of chillers  
The number of chillers to install is a function of redundancy requirements  
and first cost. In general, the more chillers installed, the higher the initial cost.  
Therefore, many small systems only use one chiller. Most chillers in the 20  
through 200 ton range use multiple compressors with multiple refrigeration  
circuits and provide a reasonable level of cooling redundancy. The only  
system controls installed on a single chiller installation may be a clock and  
ambient lockout switch to enable and disable the chilled-water system. If only  
one chiller is used, a system that varies the flow rate through the chiller can  
be quite simple to operate. Minimum and maximum flows and maximum  
rate of change for the flow would still need to be addressed (see “Variable-  
As systems get larger, the owner may require more redundancy, leading  
them to install multiple chillers. Some designers use 200 tons as the  
maximum job size for a single chiller.  
When there is more than one chiller, there are many more system control  
decisions to be made including:  
enabling the second chiller,  
turning the second chiller off, and  
failure recovery.  
Two-chiller plants require higher system control intelligence than single  
chiller plants. Sequencing logic, discussed in “System Configurations” on  
page 42, varies based on system configuration, and failure recovery is  
discussed on page 95.  
Parallel or series  
Parallel configurations are more common than series configurations. (See  
“Parallel Chillers” on page 42.) In chiller systems with an even number of  
chillers, there are advantages to putting them into a series configuration,  
especially if low or variable water flow is desired. This offers the benefits of  
better system efficiency and higher capacity because the upstream chiller  
produces water at a warmer temperature. Series chillers should not be  
applied with low system Ts, because the maximum flow through the chillers  
may be reached. Efforts to eliminate the so-called “Low T syndrome” (page  
79) must be addressed for both configurations. The energy and control  
requirements of series chillers are covered in “Series Chillers” on page 44.  
Part load system operation  
For small chilled-water systems, especially those with only one chiller, part  
load system energy use may be dominated by ancillary equipment,  
especially in a constant flow system. At low loads, constant speed pumps  
and tower fans constitute a much larger portion of the chiller plant energy  
20  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Application Considerations  
than at full load. Variable frequency drives for unloading tower fans and  
chilled-water pumps may provide benefits, depending on the costs, system  
operating hours, system type, and outdoor air conditions. (See “System  
Mid-Sized Chilled-Water Systems  
(3-5 Chillers)  
Figure 18. Mid-sized chilled-water system schematic  
Distribution Pumps  
Loads  
In addition to the design decisions faced by the small chilled-water system  
designer, the following objectives may be encountered by the mid-sized  
system designer.  
Managing control complexity  
execution become more critical and more complex. There are simply more  
combinations of equipment and operating scenarios. On the other hand,  
systems this size generally have more highly-skilled operators who can  
understand proper operation and maintenance. To help operators  
understand expected system operation, chiller plant controls are usually  
more customized and sophisticated.  
Preferential vs. equalized loading and run-time  
With more chillers, sequencing options might include preferentially loading  
the most efficient chiller or equalizing the run time of chillers. The decision  
hinges on how different these chillers are and the preferred maintenance  
routine. For example, a chiller plant with one quite old—though still reliable—  
chiller may periodically enable that chiller to ensure it continues to function,  
SYS-APM001-EN  
Chiller System Design and Control  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Application Considerations  
but use it sparingly due to its lower efficiency. Or, a chiller may have a  
different fuel source, used as a hedge against either high demand or high  
energy consumption charges for other energy sources. (See Alternative  
Energy Sources” on page 82.) Some chilled-water systems have unequally  
sized chillers, allowing fewer chillers to operate. (See “Unequal Chiller  
Large Chilled-Water Systems  
(6+ Chillers, District Cooling)  
Figure 19. Large chilled-water system schematic  
~
~
~
~
~
Large chilled-water systems with six or more chillers (Figure 19) have  
different challenges than smaller systems. Examples of these types of  
systems are commonly found on campuses with multiple buildings,  
downtown districts, and mixed-use residential and commercial  
developments.  
22  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Application Considerations  
Creating one centralized chilled-water system takes significant foresight,  
initial investment, and building development with a multi-year master plan. If  
the initial plant is built to accommodate many future buildings or loads, the  
early challenge is operating the system efficiently with much lower loads  
than it will experience when the project is complete. The system may need to  
blend parallel and series configurations (“Series–Counterflow Application”  
on page 77) to accommodate the wide range of loads the plant experiences  
during phased construction.  
Another type of large chilled-water system could actually start out as more  
than one chilled water-system. An existing set of buildings can be gradually  
added to the central system, or two geographically distant chilled-water  
systems can be connected. “Plant Expansion” on page 83 discusses the  
unique control and hydraulic challenges of “double-ended” chilled-water  
systems.  
Operating large chilled-water systems can be different as well. As system  
load drops, chillers are turned off. Individual chiller unloading characteristics  
are not as important, because operating chillers are more heavily loaded.  
Pipe size  
Practical pipe size limitations start to affect the maximum size of a chilled-  
water system. As the systems get larger, it becomes more difficult to  
accommodate the increasing pipe sizes, both in cost and in space. Large Ts  
can help reduce flow and required pipe size. (See “Selecting Chilled- and  
larger the system, the higher the T should be.  
Water  
Large systems are almost always water-cooled. Both chilled water (a closed  
loop) and condenser water (usually an open loop) pipes will have to be filled  
with water. In some locations, it is difficult to find enough fresh water to fill a  
very large system with water, especially if the chilled-water system is quite  
distant from the loads. Cooling towers consume water, which can be  
significant and difficult to obtain in some locations. The search for both  
locally available make-up water and energy savings can lead to the  
exploration of alternative condensing sources like lake, river, or well water.  
(See “Well, river, or lake water” on page 72.) In rare instances, salt water or  
brackish water can be applied if the system uses an intermediate heat  
exchanger, or if the chiller is constructed with special tubes.  
Power  
Large chilled-water systems can be challenged by site power availability.  
Transformer size may be dictated by local regulations. On-site power  
generation may be part of the project, leading to using higher voltages inside  
the chilled-water system to avoid transformer losses and costs. Alternative  
fuels for some or all of the chillers may be attractive (Alternative Energy  
SYS-APM001-EN  
Chiller System Design and Control  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Application Considerations  
To minimize power, large systems must be very efficient. The upside of a  
large system is the amplification of energy savings. A relatively small  
percentage of energy saved becomes more valuable. For this reason, the  
highly efficient series-counterflow arrangement is popular for large systems.  
Controls  
The designers of medium and large chilled-water systems are more likely to  
consider the pros and cons of direct-digital controls (DDC) versus  
programmable-logic controls (PLC). These platforms deliver similar results,  
depending on proper design, programming, commissioning, and operation.  
For more information about chiller plant  
controls, consult the Trane applications  
guide, Tracer Summit™ Chiller Plant  
Control Program (BAS-APG004-EN).  
One way to think of PLC is “fast, centralized control with redundancy.” PLC  
has a faster processing speed, with some hot-redundancy features—such as  
an entirely redundant system processor that is ready to take over if the main  
system processor fails.  
Conversely, DDC can be considered “steady, distributed control with  
reliability.” DDC controls feature easy programming and user-friendly  
operation. In the DDC environment, a failure of the system processor results  
in the lower-level processors defaulting to a pre-determined operating mode.  
The speed of the PLC system can be one of its challenges. Controls that are  
steady and do not overreact to minor changes work very well, even in large  
chilled-water systems.  
Chiller Plant System Performance  
Chiller performance testing  
All major chiller manufacturers have chiller performance test facilities in the  
factory, in a laboratory, or both. A chiller performance test in accordance with  
the test procedures in ARI Standard 550/590 can be performed at the factory  
under controlled conditions, with industrial grade instrumentation and  
computerized data collection devices. This test ensures that the chiller meets  
its promised performance criteria. If it does not, corrections are made before  
it leaves the factory.  
Limitations of field performance testing  
After the chiller is installed at the job site, the system conditions will be less  
controllable than in a test facility, and therefore unsuitable for chiller  
acceptance testing. While measuring the performance of the entire chiller  
plant is more difficult, it can help identify operating problems or evaluate the  
effectiveness of system control methods and setpoints.  
The goal is to operate as efficiently as possible and to sustain a high level of  
individual equipment and coordinated operation. A proper energy  
management system can help trend and diagnose problems or changes over  
time.  
24  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
     
Application Considerations  
Guidelines for system efficiency monitoring  
ASHRAE Guideline 22 Instrumentation for Monitoring Central Chilled-Water  
Plant Efficiency was first published in June 2008. It states:  
For a copy of ASHRAE Guideline 22 and  
other ASHRAE publications, visit the  
ASHRAE bookstore at www.ashrae.org/  
bookstore.  
Guideline 22 was developed by ASHRAE to provide a source of  
information on the instrumentation and collection of data needed for  
monitoring the efficiency of an electric-motor-driven central chilled-  
water plant. A minimum level of instrumentation quality is  
established to ensure that the calculated results of chilled-water  
plant efficiency are reasonable. Several levels of instrumentation are  
developed so that the user of this guideline can select that level that  
suits the needs of each installation.  
The basic purpose served by this guideline is to enable the user to  
continuously monitor chilled-water plant efficiency in order to aid in  
the operation and improvement of that particular chilled-water plant,  
not to establish a level of efficiency for all chilled-water plants.  
Therefore, the effort here is to improve individual plant efficiencies  
and not to establish an absolute efficiency that would serve as a  
minimum standard for all chilled-water plants.  
Guideline 22 includes a discussion of:  
types of sensors and data measurement devices  
calibration  
measurement resolution, accuracy, and uncertainty  
calculation methods  
example specification  
examples of measured long-term performance  
Guideline 22 recommends tracking and archiving the following over the life  
of the plant, in addition to normal equipment operating trends. The ability to  
obtain this information is dependent on the instrumentation and data  
measurement capabilities of the system.  
1
Average days outdoor air temperature (obtain the outside air  
temperature every 30 minutes and find the average of these samples each  
day)  
2
3
4
Days high temperature  
Days low temperature  
Days high wet-bulb temperature (calculate from temperature and  
enthalpy)  
5
Chilled-water supply temperature (average, max and min if chilled-water  
temperature is not fixed)  
6
7
8
Total ton-hours (kWh) production of chilled water for the day  
Total kWh power input for each component for the day  
Average kW/ton (COP) for the plant for the day  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
   
Application Considerations  
Energy and economic analysis of alternatives  
The process of making decisions between multiple, competing alternatives is  
simplified with the assistance of simulation software. Many packages are  
available for this purpose (see sidebar). While not every analysis will require  
the same level of detail for decision-making purposes, computer-assisted  
analysis computations are now easy and fast, and it is no longer necessary to  
make many simplifying assumptions. When performing a simulation of  
alternatives, use software that allows for:  
Prominent software for energy analysis  
includes TRACE™, System Analyzer™,  
eQuest, and EnergyPlus.  
1
Full year analysis  
a
b
Schedules, including holidays, affect the loads and the equipment.  
Weather, including coincident temperature, solar, and wind effects will  
have an effect, not just on the loads but on the energy performance of  
equipment.  
2
Actual energy rate definition  
a
Time-of-day and time-of-year rate capabilities are important. Some  
utilities stipulate that some hours and/or months are on peak,” while  
others are “mid peak” or “off peak,” and charge differently.  
Blended electricity rates computed from  
a full year’s energy cost divided by the  
full year’s kWh are not acceptable. Not  
every alternative will use energy the  
same way, and not every unit of energy  
will have the same effective cost. See  
b
Demand or other fixed costs are almost always present in some  
fashion, so that utilities are compensated for the amount of  
instantaneous capacity they provided. Some rates will include  
"ratchet" clauses, which charge a minimum percentage of the previous  
12 months’ peak demand.  
c
Stepped-rates, also known as floating cut-offs, are used to reward  
energy consumers with flatter load profiles. The amount of energy  
used almost all the time will have the least expensive rate.  
d
Blended or combined electricity rates are not acceptable (see sidebar).  
3
Life-cycle analysis  
a
b
c
First costs are rarely overlooked in an economic analysis.  
Maintenance costs also are likely to be different in each alternative.  
Replacement costs will be important when evaluating alternatives  
with equipment not expected to have the same useful life, or if one  
alternative is to delay some amount of action by one or more years.  
d
e
Escalation factors on recurring costs such as maintenance and energy.  
More advanced economic parameters may be desirable as well to  
include financing and tax implications.  
For the purposes of achieving ASHRAE Standard 90.1 compliance using the  
Energy Cost Budget method, or for certifications under the United States  
Green Building Councils LEED program, software tools must be tested in  
accordance with ASHRAE Standard 140. This test is also required for tax  
incentives offered by the United States federal government.  
ASHRAE Standard 140 was developed  
to create a basis for defining and testing  
capabilities of energy analysis software  
packages. Test results are submitted to  
ASHRAE and publicly available before  
software is considered compliant with  
the Standard.  
®
26  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
   
System Design Options  
There are many chilled-water-system design options; however, in a basic  
sense, each option is a function of flow, temperature, system configuration,  
and control. This section discusses the effect of flow rate and temperature  
decisions.  
It is important to remember that temperatures and flow rates are variables.  
By judicious selection of these variables, chilled-water systems can be  
designed to both satisfy chilled-water requirements and operate cost  
effectively.  
Chilled-water systems are often designed using flow rates and temperatures  
applied in testing standards developed by the Air-Conditioning, Heating, and  
Refrigeration Institute (AHRI), ARI 550/590–2003 for vapor compression  
chillers and ARI 560–2000 for absorption chillers (see sidebar). These  
benchmarks provide requirements for testing and rating chillers under  
multiple rating conditions. They are not intended to prescribe the proper or  
optimal flow rates or temperature differentials for any particular system. In  
fact, as component efficiency and customer requirements change, these  
standard rating conditions are seldom the optimal conditions for a real  
system, and industry guidance recommends lower flow rates with resultant  
higher temperature differences. There is great latitude in selecting flow rates,  
temperatures, and temperature differences.  
For more information, refer to ARI  
Standard 550/590-2003, Performance  
Rating of Water Chilling Packages Using  
the Vapor Compression Cycle and the  
ARI Standard 560-2000, Absorption  
Water Chiller and Water Heating  
Packages. Both are published by the Air-  
Conditioning, Heating, and Refrigeration  
Institute. www.ahrinet.org  
Selecting Chilled- and Condenser-Water  
Temperatures and Flow Rates  
Leaving chilled-water and entering condenser-water temperature selection  
can be considered independently of their respective flow rates. However,  
temperatures and flow rates should be selected together to design an  
efficient and flexible chilled-water system.  
Guidance for Chilled- and Condenser-Water Flow Rates  
The ASHRAE GreenGuide (pp 146-147) states:  
In recent years, the 60% increase in required minimum chiller  
efficiency from 3.80 COP (ASHRAE Standard 90-75) to 6.1 COP  
(ASHRAE Standard 90.1-2004) has led to reexamination of the  
assumptions used in designing hydronic media flow paths and in  
selecting movers (pumps) with an eye to reducing energy  
consumption… Simply stated, increase the temperature difference  
in the chilled water system to reduce the chilled-water pump flow  
rate…  
The CoolTools™ Chilled Water Plant Design Guide recommends starting with  
a chilled-water temperature difference of 12°F to 20°F [7°C to 11°C], and it  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
             
System Design Options  
recommends a design method that starts with condenser-water temperature  
difference of 12°F to 18°F [7°C to 10°C].  
Standard rating temperatures  
Currently, the standard rating condition temperatures in ARI 550/590 and  
ARI 560 are:  
Evaporator leaving water temperature: 44°F [6.7°C]  
Water-cooled condenser, entering water temperature: 85°F [29.4°C]  
Air-cooled condenser, entering air dry bulb: 95°F [35.0°C]  
For years, these temperature definitions were the benchmarks in system  
designs. Today, designers apply a variety of different temperatures.  
ARI 550/590 reflects this trend by allowing the chilled-water and condenser-  
water temperatures to be selected at non-standard points and the chiller to be  
tested as specified by the standard.  
Chilled-Water Temperatures  
Currently, comfort cooling systems are designed with chilled-water supply  
temperatures that range from 44°F [6.7°C] to 38°F [3.3°C], and, in some cases,  
as low as 34°F [1.1°C]. Reasons to decrease the chilled-water temperature  
include the following:  
Chilled water (without antifreeze) at  
34°F (1.1°C) is possible with some  
chillers that use sophisticated  
evaporator-design and chiller-control  
methods.  
The system design more readily accommodates wider temperature  
differences (lower flow rates) than the standard rating conditions (see  
Lower water temperature allows lower air temperatures (and flows) to be  
selected, resulting in reduced airside installed and operating costs.  
Colder water in the same chilled-water coil may provide better  
dehumidification.  
Colder water can be used to increase the capacity of an existing chilled-  
water distribution system. In some instances, this can save significant  
capital expenditures to add capacity to large central plants that have  
reached their flow limits.  
Some system designers hesitate to use lower chilled-water temperatures,  
concerned that the chiller will become less efficient. As discussed in “Effect of  
chilled-water temperature” on page 3:  
Lower chilled-water temperature makes the chiller work harder. However,  
while the lower water temperature increases chiller energy consumption,  
it significantly reduces the chilled-water flow rate and pump energy. This  
combination often lowers system energy consumption.  
Lower chilled-water temperatures may require more insulation on piping  
to prevent unwanted condensation (“sweating”). Ensure that pipes are  
properly insulated at all water temperatures. Lower temperature water  
often does not require more insulation.  
28  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
   
System Design Options  
Condenser-Water Temperatures  
Todays chillers can run at various entering condenser-water temperatures,  
from design temperature to the lowest-allowable temperature for that  
particular chiller design. However, many existing older chillers are limited in  
their allowable condenser-water temperatures. Contact the chiller  
manufacturer for these limits. Optimal condenser-water temperature control  
is discussed in the section, “System Controls” on page 87.  
Chilled- and Condenser-Water Flow Rates  
The selection of chilled-water and condenser-water flow rates is a powerful  
tool that designers have at their disposal. Kelly and Chan , and Schwedler  
and Nordeen , found that reducing flow rates can reduce the costs of  
chilled-water system installation and/or operation. The ASHRAE  
GreenGuide states, “Reducing chilled- and condenser-water flow rates  
(conversely, increasing the Ts) can not only reduce operating cost, but,  
more important, can free funds from being applied to the less efficient  
infrastructure and allow them to be applied toward increasing overall  
efficiency elsewhere.”  
Standard rating flow conditions  
Presently, the standard-rating-condition flow rates for electric chillers in ARI  
550/590 are:  
2.4 gpm/ton [0.043 L/s/kW] for evaporator  
3.0 gpm/ton [0.054 L/s/kW] for condenser  
This evaporator flow rate corresponds to a 10°F [5.6°C] temperature  
difference. Depending on the compressor efficiency, the corresponding  
condenser temperature difference is 9.1°F to 10°F [5.1°C to 5.6°C].  
Absorption chillers are rated using ARI Standard 560–2000, Absorption Water  
Chiller and Water Heating Packages . The evaporator flow rates are the same  
as those used in ARI 550/590; however, condenser (often called cooling  
water) flow rates differ depending on the absorption chiller design. Table 3  
shows the standard rating conditions for various absorption chillers.  
Table 3. Standard rating conditions for absorption chillers  
Condenser Flow Rate  
Absorption Chiller Type  
gpm/tonkkkkk L/s/kW  
Single Effect  
3.60  
4.00  
4.00  
0.065  
0.072  
0.081  
Steam or hot water  
Direct fired  
Double Effect  
SYS-APM001-EN  
Chiller System Design and Control  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
System Design Options  
Selecting flow rates  
Designers may use the standard rating conditions to compare  
manufacturers’ performances at exactly the same conditions. However, these  
standards allow any flow rates to be used and certified comparisons to be  
made at a wider range of conditions.  
For a given load, as flow rate decreases, the temperature differential  
increases. Table 4 reflects a 450-ton [1,580-kW refrigeration] chilled-water  
system, both as a base case and with low flow.  
Table 4. Standard rating conditions for chilled-water systems  
Chilled Water System  
Base Case  
1,080 [68.1]  
54.0 [12.2]  
44.0 [6.7]  
1,350 [85.2]  
85.0 [29.4]  
94.3 [34.6]  
256.0  
Low Flow  
675 [42.6]  
57.0 [13.9]  
41.0 [5.0]  
900 [56.8]  
85.0 [29.4]  
99.1 [37.3]  
292.0  
Evaporator flow rate, gpm [L/s]  
Entering  
Leaving  
Chilled water  
temperature F [C]  
Condenser flow rate, gpm [L/s]  
Entering  
Leaving  
Condenser water  
temperature F [C]  
Chiller power, kW  
In this example, notice that the leaving chilled-water temperature decreases  
and the leaving condenser-water temperature increases. This means that the  
chillers compressor must provide more lift and use more power. At first  
glance, the design team may decide the chiller power difference is too large  
to be overcome by ancillary equipment savings. The key question is, How  
does this impact system energy consumption? Using the following  
assumptions, we can calculate system energy usage:  
80 feet of water [239 kPa] pressure drop through chilled-water piping  
30 feet of water [89.7 kPa] pressure drop through condenser-water piping  
78°F [25.6°C] design wet bulb  
93 percent motor efficiency for pumps and tower  
75 percent pump efficiency  
Identical pipe size in chilled- and condenser-water loops (either a design  
decision, or indicating changing flows in an existing system)  
The pressure drop through the chiller will decrease due to the lower flow  
rates. When using the same size pipe, the pressure drop falls by nearly the  
square of the decreased flow rate. While this is true for straight piping, the  
pressure drop does not follow this exact relationship for control valves or  
branches serving loads of varying diversity.  
Be sure to calculate the actual pressure drop throughout the system.  
Hazen–Williams and Darcy–Weisbach calculate the change is to the 1.85 and  
30  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Design Options  
1.90 power, respectively. The examples here use the more conservative 1.85  
power:  
1.85  
DP2/DP1 = (Flow2)/(Flow1)  
Given different flow rates and entering water temperatures, a different  
cooling tower can be selected for the low-flow condition (Table 6):  
Table 5. Low-flow conditions for chilled-water pump  
Base Case  
1,080 [68.1]  
80.0 [239]  
29.7 [88.8]  
39.9 [29.8]  
32.0  
Low Flow*  
675 [42.6]  
33.5 [100]  
12.6 [37.7]  
10.5 [7.80]  
8.4  
Flow rate, gpm [L/s]  
System pressure drop, ft water [kPa]  
Evaporator-bundle pressure drop, ft water [kPa]  
Pump power output, hp [kW]  
Pump electrical power input, kW  
Table 6. Low-flow conditions for cooling tower  
Base Case  
1,350 [85.2]  
19.1 [57.1]  
30.0 [22.4]  
24.1  
Low Flow*  
900 [56.8]  
12.6 [37.7]  
20.0 [14.9]  
16.0  
Flow rate, gpm [L/s]  
Static head, ft water [kPa]  
Tower fan power output, hp [kW]  
Tower fan electrical power input, kW  
Table 7. Low-flow conditions for condenser-water pump  
Base Case  
Low Flow*  
900 [56.8]  
14.2 [42.5]  
9.6 [28.7]  
12.6 [37.7]  
11.0 [8.2]  
8.8  
Flow rate, gpm [L/s]  
1,350 [85.2]  
30 [89.7]  
19.9 [59.5]  
19.1 [57.1]  
31.4 [23.4]  
25.2  
System pressure drop, ft water [kPa]  
Condenser-bundle pressure drop, ft water [kPa]  
Tower static lift, ft water [kPa]  
Pump power output, hp [kW]  
Pump electrical input, kW  
* Low-flow conditions represented in Table 5 through Table 8 are 1.5 gpm/ton [0.027 L/s/kW] chilled water  
and 2.0 gpm/ton [ 0.036 L/s/kW] condenser water.  
SYS-APM001-EN  
Chiller System Design and Control  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Design Options  
The total system power is now as follows:  
Table 8. Total system power  
Component Power (kW)  
Chiller  
Base Case  
256.0  
32.0  
Low Flow*  
292.0  
8.4  
Chilled-water pump  
Condenser-water pump  
Cooling tower  
25.2  
8.8  
24.1  
16.0  
Total power for chilled-water system  
337.3  
325.2  
* Low-flow conditions represented in Table 5 through Table 8 are 1.5 gpm/ton [0.027 L/s/kW] chilled water  
and 2.0 gpm/ton [0.036 L/s/kW] condenser water.  
Figure 20. System summary at full load  
300  
250  
Tower  
200  
150  
100  
Condenser Water  
Pumps  
Chilled Water  
Pump  
50  
0
Chiller (100%  
Load)  
2.4/3.0  
1.5/3.0  
2.4/2.0  
1.5/2.0  
Chilled/Condenser Water Flows, gpm/ton  
It becomes clear that flow rates can affect full-load system power (Figure 20).  
Even though the chiller requires more power in the low-flow system, the  
power reductions experienced by the pumps and cooling tower result in an  
overall savings for the system.  
What happens at part-load conditions? Figure 21 shows the part-load  
performance based on the following assumptions:  
The chilled-water pump includes a variable-frequency drive.  
The condenser-water pump remains at constant power.  
The cooling tower is controlled to produce water temperatures lower than  
design.  
32  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Design Options  
Figure 21. Chilled water system performance at part load  
350  
300  
Base  
250  
Low Flow*  
200  
kW  
150  
100  
50  
50  
0
25% Load  
50% Load  
75% Load  
Full Load  
* Low-flow conditions in Figure 21 are 1.5 gpm/ton [0.027 L/s/kW] chilled water and 2.0 gpm/ton  
[0.036 L/s/kW] condenser water.  
While the magnitude of the benefit of low-flow changes depends on the  
chiller type used (centrifugal, absorption, helical-rotary, scroll), all chilled-  
water systems can benefit from judicious use of reduced flow rates as  
recommended by the ASHRAE GreenGuide .  
Coil response to decreased entering water temperature  
A coil is a simple heat exchanger. To deliver the same sensible and latent  
capacity when supplied with colder water, the coils controls respond by  
reducing the flow rate of the water passing through it. Because the amount of  
water decreases while the amount of heat exchanged remains constant, the  
leaving water temperature increases. Thus, by supplying colder water to the  
coils, a low-flow system can be applied to an existing building. In a retrofit  
application, it is wise to reselect the coil, using the manufacturers selection  
program, at a new chilled-water temperature to ensure its performance will  
meet the requirements.  
If coil performance data is not available  
from the original manufacturer, its  
performance could be approximated  
using current selection programs and  
known details about the coil, such as fins  
per foot, number of rows, tube diameter,  
etc. Some designers use the following  
approximation instead. For each 1.5 to  
2.5°F [0.8°C to 1.4°C] the water  
temperature entering the coil is reduced,  
the coil returns the water 1°F [0.6°C]  
warmer and gives approximately the  
same sensible and total capacities. This  
is a rough approximation and a coil’s  
actual performance depends on its  
design.  
One possible concern of low supply-water temperatures is the ability of the  
valve to control flow properly at low-load conditions. A properly-sized valve  
with good range can work well in low-flow systems. In existing systems,  
valves may need to be replaced if they cannot operate with the new range of  
flows, but the coils do not need to be replaced.  
Example of coil reselection at colder temperature/reduced flow rate  
Water temperatures and flow rates are variables. They should be selected to  
achieve an efficient and flexible water distribution system. Consider the  
following example of a six-row coil in an existing air handling unit.  
Table 9 shows an example of selecting a chilled-water cooling coil in a  
3
13,000-cfm (6.1-m /s) VAV air-handling unit. The left-hand column shows the  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
       
System Design Options  
performance of this coil when it is selected with a 44°F [6.7°C] entering fluid  
temperature and a 10°F [5.6°C] fluid temperature rise (T). To provide the  
required 525 MBh [154 kW] of cooling capacity, the coil requires 105 gpm [6.6  
L/s] of water.  
The right-hand column shows the performance of same coil, but in this case  
it is selected with 40°F [4.4°C] entering fluid and a 15.6°F [8.7°C] T. To  
provide the equivalent capacity, the coil requires only 67.2 gpm [4.2 L/s] of  
water.  
Table 9. Impact of supply temperature and flow rate on cooling coil selection  
“Conventional”  
system design  
“Low flow”  
system design  
2
2
Coil face area, ft [m ]  
29.01 [2.69]  
448 [2.3]  
6 rows  
29.01 [2.69]  
448 [2.3]  
6 rows  
Face velocity, fpm [m/s]  
Coil rows  
Fin spacing, fins/ft [fins/m]  
Total cooling capacity, MBh [kW]  
Entering fluid temperature, °F [°C]  
Leaving fluid temperature, °F [°C]  
Fluid T, °F [°C]  
85 [279]  
525 [154]  
44 [6.7]  
54 [12.2]  
10 [5.6]  
105 [6.6]  
14.0 [41.8]  
85 [279]  
525 [154]  
40 [4.4]  
55.6 [13.1]  
15.6 [8.7]  
67.2 [4.2]  
6.3 [18.8]  
Fluid flow rate, gpm [L/s]  
Fluid pressure drop, ft H O [kPa]  
2
By lowering the entering fluid temperature, this coil can deliver the same  
cooling capacity with 36% less flow, at less than half of the fluid pressure  
drop, with no impact on the airside system.  
Cooling-tower options with low flow  
Smaller tower  
Like coils, cooling towers are heat exchangers—although often  
misunderstood heat exchangers. The tower exchanges heat between the  
entering (warmest) water temperature and the ambient wet-bulb  
temperature. Therefore, in a new system or when a cooling tower is replaced,  
a low-flow system design allows a smaller, more efficient cooling tower to be  
selected. How is this possible?  
Keep in mind that a cooling tower is not limited to a specific tonnage. A  
cooling tower is a heat exchanger that exchanges heat between the entering  
water temperature and the ambient wet bulb. By varying the flow or the  
temperature, the tower capacity can be changed—often increased.  
Since the amount of heat to be rejected, Q, is approximately the same in  
standard-rating-condition and low-flow systems, we can estimate the heat  
exchange area necessary to reject the heat:  
34  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Design Options  
Q = U x A x T , where  
1
1
A = area,  
U = coefficient of heat transfer, and  
T = temperature difference  
so, for a roughly equivalent heat rejection,  
U x A x T = U x A x T  
2
1
1
2
and for a constant coefficient of heat transfer,  
A x T = A x T  
1
1
2
2
Using standard rating conditions, the temperature difference between tower  
entering temperature and ambient wet bulb, T is  
1
T = 94.2 – 78 = 16.2°F or [34.6 – 25.6 = 9.0°C]  
1
while at typical low-flow conditions, T is  
2
T = 99.1 – 78 = 21.1°F or [37.3 – 25.6 = 11.7°C]  
2
Therefore:  
A × 16.2 = A × 21.1 or A = 0.77 A  
1
1
2
2
So, the tower would theoretically need only 77% of the heat exchange area to  
achieve the same heat rejection capacity, simply by reducing the flow rate  
from 3.0 gpm/ton [0.054 L/s/kW] to 2.0 gpm/ton [0.036 L/s/kW].  
The heat exchange capacity can be altered by changing the surface area or  
airflow, or some combination of the two. A cooling-tower manufacturers  
selection program can give the exact size and power requirements. In the  
example previously summarized on pages 30-32, both the cooling-tower size  
and airflow (hence, required fan power) were reduced.  
Same tower, smaller approach  
Another option is to use the same cooling tower at a lower flow rate. In a new  
system, this is a design decision, but in an existing system, it is often a  
constraint that the tower cannot be changed. Given the same heat-rejection  
load, the low-flow system allows the cooling tower to return colder water;  
that is, the tower's approach to the ambient wet-bulb temperature decreases.  
In the previous example of 450 tons [1580 kW], the same cooling tower would  
have resulted in a leaving tower-water temperature of 83.5°F [28.6°C] instead  
of the 85°F [29.4°C] with the smaller cooling tower. It is important to realize  
that the entering temperature for the tower would be approximately 97.6°F  
[36.4°C]. Therefore, the effect of reduced flow rate on chiller energy  
consumption is partially offset by the lower leaving tower-water temperature.  
The system would use less pump energy at the lower flow conditions.  
SYS-APM001-EN  
Chiller System Design and Control  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Design Options  
Table 10. Same tower, smaller approach  
Same tower,  
smaller  
Present  
approach  
Capacity, tons  
450 [1,580]  
450 [1,580]  
[kW refrigeration]  
Approach, °F [°C]  
7 [3.8]  
1350 [85.2]  
94.3 [34.6]  
85 [29.4]  
78 [25.6]  
5.5 [3]  
Flow rate, gpm [L/s]  
Cooling tower  
900 [56.8]  
97.6 [36.4]  
83.5 [28.6]  
78 [25.6]  
Entering temperature, F [C]  
Leaving temperature, F [C]  
Ambient wet-bulb  
temperature, F [C]  
Same tower, larger chiller  
One retrofit option that benefits many building owners is installing a new,  
larger chiller selected for a lower flow rating and re-using the existing cooling  
tower, condenser-water pump, and condenser-water pipes. In many cases,  
this allows the building owner to increase the chilled-water-system capacity  
for an expansion, with a limited budget. An example can easily demonstrate  
this.  
A hospital presently has a 450-ton [1,580-kW refrigeration] chiller that needs  
to be replaced. The condenser water flow is 1,350 gpm [85.2 L/s]. The present  
cooling-tower selection conditions are summarized in Table 11. Recently, the  
cooling-tower fill was replaced. The tower, condenser water piping, and  
pump are in good condition. The hospital is planning an addition with 50  
percent more load for a total of 675 tons [2,370 kW]. Must the hospital replace  
the condenser water system? The answer is “no,” as long as the chiller is  
selected properly.  
How is this possible? As long as the new chillers condenser-water pressure  
drop is at or below that of the present chiller, the same amount of water can  
still be pumped. With the same flow rate, a 675-ton [2,370-kW] chiller may be  
selected with a condenser-water-temperature rise of approximately 15°F  
[8.3°C]. Using the cooling-tower manufacturers selection software, the same  
cooling tower can be selected at the elevated temperature difference. As  
shown in Figure 22, the new selection point will be:  
entering water temperature: 103°F [39.4°C]  
leaving water temperature: 88°F [31.1°C]  
ambient wet bulb: 78°F [25.6°C]  
36  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Design Options  
Table 11. Retrofit capacity changes  
Larger  
chiller,  
Present  
same tower  
Capacity, tons  
450 [1,580]  
675 [2,370]  
[kW refrigeration]  
Flow rate, gpm [L/s]  
1350 [85.2]  
94.3 [34.6]  
85 [29.4]  
1,350 [85.2]  
103 [39.4]  
88 [31.1]  
Cooling tower  
Entering temperature, F [C]  
Leaving temperature, F [C]  
Ambient wet-bulb  
78 [25.6]  
78 [25.6]  
temperature, F [C]  
It quickly becomes evident that the same cooling tower and flow rate are  
adequate to reject more heat—in this case, approximately 50 percent more  
heat.  
Figure 22. Cooling tower re-selection with different chiller capacities  
90  
Reselected tower for 50% more  
heat rejection with 15°F [8.3°C]  
range  
Y
85  
80  
Original design point  
for tower with 10°F  
[5.6°C] range  
75  
70  
Design Point (original)  
Design Point (new)  
Y
65  
55  
65  
70  
80  
60  
75  
Wet-Bulb Temperature (°F)  
Retrofit opportunities  
The low-flow concepts for chilled- and condenser-water just described in  
pages 33 through 37 present tremendous retrofit opportunities. Building  
owners may need to increase the capacity of an existing system, for example,  
in response to a building addition. In many of these buildings, the condenser  
water system (piping, pump, and tower) is in good condition, but is  
considered to be too small. Or, the system has expanded but the chilled water  
pipes and/or coils cannot be changed. By changing from traditional design  
conditions, the existing infrastructure can often be used while providing  
additional capacity.  
SYS-APM001-EN  
Chiller System Design and Control  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Design Options  
In both cases, either reusing an existing tower, or reusing existing chilled  
water piping, the design engineer can often help reduce total project costs  
using the existing infrastructure by selecting a chiller with a higher  
temperature differential.  
Cost Implications  
By reducing either chilled- or condenser-water flow rates, the following  
installed-cost reductions are possible:  
Several considerations should be kept in  
mind when determining sizes for new  
systems. As pipe size is decreased, so  
are valve and specialty sizes and costs.  
Remember that reducing pipe size  
increases pressure drop. Keep a balance  
between first cost and operating costs.  
This can significantly reduce the system  
retrofit costs because existing pipes may  
be used.  
Reduced size of pumps, valves, strainers, fittings, and electrical  
connections  
In new systems, reduced pipe sizes  
In existing systems, more capacity from existing chilled-water piping  
Reduced cooling-tower size, footprint, and fan power  
If a physically-smaller cooling tower is selected using low flow, its reduced  
footprint can benefit building owners in a number of ways:  
Reduced real estate requirements (often more important than realized)  
Reduced structural requirement, since the amount of tower water is  
reduced  
Reduced excavation and material costs in the case of a large, built-up  
tower with a concrete sump  
Improved aesthetics because of the reduced tower height  
In addition to reducing installation costs, operating cost reductions for the  
whole system are also available. Due to a smaller pump and/or tower, the  
pump and tower operating costs can be reduced substantially with less  
adverse impact on the chiller operating cost. Analysis programs such as  
EnergyPlus, eQuest, TRACE™, or System Analyzer™ software can be used to  
determine annual operating costs. Nordeen and Schwedler showed that  
operating costs for chilled-water systems using absorption chillers can  
benefit greatly from reduced condenser-water flow. Figure 23 shows  
operating costs as generated with System Analyzer analysis software.  
38  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
   
System Design Options  
Figure 23. Annual system operating costs (absorption chillers)  
$40,000  
$35,000  
$30,000  
$25,000  
$20,000  
$15,000  
$10,000  
$5,000  
$-  
4.45 gpm/ton  
3.60 gpm/ton  
3.09 gpm/ton  
Condenser Water Flow  
Kelly and Chan compare the operational costs of chilled-water system  
designs in site locations. Their summary states:  
In conclusion, there are times you can ’have your cake and eat it too.’  
In most cases, larger Ts and the associated lower flow rates will not  
only save installation cost but will usually save energy over the  
course of the year. This is especially true if a portion of the first cost  
savings is reinvested in more efficient chillers. With the same cost  
chillers, at worst, the annual operating cost with the lower flows will  
be about equal to “standard” flows but still at a lower first cost.  
Misconceptions about Low-Flow Rates  
Some common misconceptions about low-flow systems include:  
1
2
3
Low flow is only good for long piping runs  
Low flow only works well for specific manufacturers’ chillers  
Low flow can only be applied to new chilled-water systems  
Lets discuss each of these three misconceptions.  
Misconception 1—Low flow is only good for long piping  
runs.  
One way to examine this claim is to use our previous example, but to  
concentrate on the condenser-water side. We’ll start with the example  
covered on pages 30-32. Using the same chiller, but a smaller cooling tower  
SYS-APM001-EN  
Chiller System Design and Control  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Design Options  
and a more conservative zero condenser-water-pipe pressure drop, we can  
examine the effect of reducing flow rates.  
Table 12. Reduced flow-rate effect  
Condenser Water Pump  
Base Case  
1350 [85.2]  
0
Low Flow  
900 [56.8]  
0
Flow rate, gpm [L/s]  
System pressure drop, ft water [kPa]  
Condenser bundle pressure drop, ft water [kPa]  
Tower static lift, ft water [kPa]  
Pump power output, hp [kW]  
Pump fan electrical input, kW  
19.9 [59.5]  
19.1 [57.1]  
17.7 [13.2]  
14.2  
9.6 [28.7]  
12.6 [37.7]  
6.7 [5.0]  
5.4  
Figure 24. System energy consumption (no pipes)  
350.0  
3.0 gpm/ton 2.0 gpm/ton  
300.0  
250.0  
200.0  
15 0 . 0  
10 0 . 0  
50.0  
0.0  
25%  
50%  
75%  
100%  
System Load  
Energy consumption for the chiller, condenser-water pump, and cooling-  
tower fans is shown in Figure 24. Note that only at full load does the total  
power of the chilled-water plant increase. Recall that this is with absolutely  
no pressure drop through the condenser-water piping, valves, or fittings. It is  
interesting to note that the break-even point at full load is approximately  
8 feet of head (water) [23.9 kPa]. Also note that at all part-load conditions, the  
total power of the low-flow system is less than that of the base system. It is  
easy to see that even for short piping runs, reducing flow rates can improve  
plant energy consumption.  
40  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Design Options  
Misconception 2—Low flow only works for specific  
manufacturers’ chillers.  
Demirchian and Maragareci , Eley , and Schwedler and Nordeen  
independently showed that system energy consumption can be reduced by  
reducing flow rates. It is interesting to note that in the systems studied, three  
different chiller manufacturers chillers were examined, yet the energy  
savings only varied from 2.0 to 6.5 percent. In all cases, regardless of which  
manufacturers chillers were used, the system energy consumption was  
reduced. In addition, Demirchian and Maragareci , and Schwedler and  
Nordeen also noted reduced first costs.  
Misconception 3—Low flow can only be applied to new  
chilled-water systems.  
page 34, there are distinct opportunities to use existing infrastructure  
(pumps, pipes, coils, and cooling towers) to either expand available cooling  
capacity and/or reduce system energy costs by using lower flow rates.  
Upon examination, it is clear that low-flow systems allow savings even on  
short piping runs, work with all manufacturers’ chillers, and can be used in  
retrofit applications. As a designer, remember to review the benefits to the  
building owner. Often, reducing flow rates can provide significant value.  
Consulting engineers, utilities, and ASHRAE have all concluded that reducing  
chilled- and condenser-water flow rates (conversely, increasing the Ts)  
reduces both installed and operating costs. It is important to reduce chilled-  
and condenser-water system flow rates to provide optimal designs to  
building owners and operators.  
SYS-APM001-EN  
Chiller System Design and Control  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Configurations  
Multiple chilled-water systems are more common than single chilled-water  
systems for the same reason that most commercial airplanes have more than  
one engine—the balance of reliability and cost. The most typical system  
configuration, by far, has two chillers. Since system loads can vary throughout  
a wide spectrum, multiple chilled-water systems can often operate with one  
chiller. During these periods, if the system is designed properly, the energy  
required to operate a second chiller and its auxiliaries can be conserved.  
This section examines:  
Constant flow systems  
Systems in which flow is constant through chillers, but variable through the  
rest of the system  
Systems in which flow varies throughout the entire system—including the  
chillers  
Parallel Chillers  
Figure 25 shows a system with two chillers piped in parallel, using a single  
chilled-water pump.  
Figure 25. Parallel chillers with a single, common chiller pump  
54°F [12.2°C]  
54°F [12.2°C]  
Chiller 2 (Off)  
49°F [9.4°C]  
Constant  
Flow  
Pump  
44°F [6.6°C]  
Chiller 1 (On)  
With constant flow loads, water flows in both chillers continually, whether the  
chiller is operating or not. Clearly, this can disrupt the supply chilled-water  
temperature when only one chiller is operating. The temperatures indicated in  
Figure 25 show how the supply water temperature rises when one chiller is  
cycled off in response to a part-load condition. This may result in inadequate  
dehumidification capabilities or the inability to satisfy specific loads.  
42  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
             
System Configurations  
Alternatively, the operating chiller can be reset to produce a lower supply  
temperature at this condition. In this way, the mixed system supply-water  
temperature may be maintained at a more acceptable temperature. This  
complicates the control system and presents the possibility of increasing  
chiller energy consumption due to the requirement for lower-temperature  
water. There will also be a low limit to this water temperature, dependent on  
the chillers low pressure cut-out control, low evaporator-refrigerant-  
temperature limits, or low leaving chilled-water limits. The more chillers in  
the system, the worse the problem becomes. For this reason, this  
configuration is seldom used in systems with more than two chillers.  
Additionally, ASHRAE/IESNA Standard 90.1–2007 (Section 6.5.4.2) prohibits  
this type of system when the pump is larger than 10 hp [7.5 kW]. The standard  
requires that, in systems that contain more than one chiller piped in parallel,  
system water flow must be reduced when a chiller is not operating.  
Figure 26. Parallel chillers with separate, dedicated chiller pumps  
Off  
42°F  
[5.6°C]  
On  
54°F  
[12.2°C]  
60% to 70% of  
system flow  
Coil starved for flow  
If separate, dedicated chiller pumps are used (Figure 26), a chiller–pump pair  
can be cycled together. This solves the flow mixing problem described  
above, but presents a new problem. Below 50-percent load, only one chiller  
and one pump are operating. The total water flow in the system decreases  
significantly, typically 60 to 70 percent of full system flow, according to the  
pump–system curve relationship.  
Ideally, at this part-load flow rate, all of the coils will receive less water,  
regardless of their actual need. Typically, however, some coils receive full  
water flow and others receive little or no water. In either case, heavily-loaded  
coils or the loads farthest from the pump will usually be “starved” for flow.  
Examples of spaces with constant heavy loads that may suffer include  
computer rooms, conference rooms, photocopy rooms, and rooms with high  
solar loads.  
SYS-APM001-EN  
Chiller System Design and Control  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
Series Chillers  
If chillers are piped in series, as in Figure 27, the mixing problem disappears  
and the starving coils problem (when one of the pumps in a parallel  
arrangement is not running) is resolved. Series flow presents a new set of  
temperature and flow control challenges.  
Figure 27. Series chillers  
System T greater than 14°F  
One reason series chilled-water systems  
should be designed using at least a 14  
degree T is because a lower T ignores  
the opportunity for lower flow rates and  
reduced pump energy. For small, packaged  
chillers, a reason to have at least a 14  
degree T is to avoid exceeding the chillers  
maximum flow rate. The system will more  
likely experience evaporator flow limit  
maximums if the T is too low.  
49°F [9.4°C]  
56°F [13.3°C]  
42°F [5.5°C]  
Chiller 2  
Chiller 1  
setpoint = 42°F [5.5°C]  
setpoint = 42°F [5.5°C]  
Loads  
The flow rate through each chiller is the entire system flow, that is, double the  
individual flow rate of two parallel chillers. This means that the chiller  
evaporator must accommodate the doubled water quantity. This may be  
accommodated by using fewer water passes in the evaporator, which may  
result in decreased chiller efficiency.  
However, this efficiency loss due to fewer passes is more than offset by the  
increased efficiency of the upstream chiller, now operating at a warmer  
temperature.  
Pressure losses are additive when the chillers are piped in series. This  
increases total system pressure drop, thereby using more pump energy. On  
the other hand, series chillers work particularly well in low-flow systems,  
where the system temperature difference is greater than 14°F [7.8°C],  
resulting in less pressure drop.  
Low-flow systems were discussed in detail in “Selecting flow rates” on  
page 30. Series chillers are also suited to variable flow systems, where the  
operating pressure drop is reduced. Variable flow is discussed beginning on  
page 55.  
Temperature control can be executed in several ways. Figure 27 shows a  
strategy where the controller on each chiller is set at the system design  
setpoint. Either chiller can be used to meet the system demand for up to 50  
44  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
       
System Configurations  
percent of the system load. At system loads greater than 50 percent, the  
upstream chiller is preferentially loaded because it will attempt to produce  
the design leaving chilled-water temperature. Any portion of the load that  
remains is directed to the downstream chiller.  
If chiller setpoints are staggered (upstream at 49°F [9.4°C] and downstream at  
42°F [5.5°C]), the downstream chiller is loaded first. The upstream machine  
then meets any portion of the system load that the downstream chiller cannot  
meet. This control strategy offers several benefits. The first is that the  
upstream chiller is always operating at an elevated temperature. This allows  
it to operate at a higher efficiency. Also, placing an absorption chiller in the  
upstream position increases its capacity. As an example, an absorption chiller  
that can produce 500 tons [1,760 kW] at a leaving chilled-water temperature  
of 44°F [6.6°C] may produce 600 tons [2,110 kW] at 50°F [10°C]. Centrifugal,  
helical-rotary, reciprocating, and scroll chillers experience capacity and  
efficiency changes to a lesser degree. By judicious use of the series  
configuration, these benefits can provide reduced installed cost and fuel  
flexibility to the building owner. While not shown, a single manual bypass  
with proper valving can provide for servicing of chillers.  
Equal loading of the two chillers may be accomplished by using a chiller  
plant management system to dynamically reset the upstream chillers  
setpoint in response to changes in system load.  
Primary–Secondary (Decoupled) Systems  
The root cause of the difficulties with parallel chiller control in a constant  
volume system is the fixed relationship between chiller- and system-flow  
rates. If, instead, we can hydraulically decouple the production (chiller) piping  
from the distribution (load) piping, it is possible to control them separately.  
The fixed relationships are then broken apart. The production pumps are  
typically constant volume, while the distribution pumps are variable volume.  
Hydraulic decoupling  
Figure 28 shows the basic decoupled system. This strategy is also referred to  
as a primary–secondary pumping arrangement. Separate pumps are  
dedicated to production and distribution. While the same water is pumped  
twice (by different pumps), there is no duplication of pumping energy. This is  
because the production pumps overcome only the chiller and production-  
side pressure drop while the distribution pumps overcome only the  
distribution system pressure drop.  
SYS-APM001-EN  
Chiller System Design and Control  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Configurations  
Figure 28. Decoupled arrangement  
Check valves  
Some designers recommend the  
installation of a check valve in the  
bypass line of a primary–secondary  
system to eliminate the possibility of  
deficit flow in the bypass line. The  
premise is that if there is a system  
problem (low temperature differential),  
the check valve will put the primary and  
secondary pumps in series and pump  
more water through the chiller, thus  
balancing the primary and secondary  
flow requirements. This is not universally  
accepted.  
CV Pump  
Chiller 3  
CV Pump  
Chiller 2  
Coad  
states:  
One constraint is that if the system is  
designed as variable flow and is  
experiencing operating problems  
related to low return water  
CV Pump  
temperatures, the solution is not in the  
plant but rather in the load.  
Chiller 1  
Production  
Distribution  
and  
Bypass Line  
One solution that has been suggested  
is to install a check valve in the plant  
common pipe or decoupling line circuit  
… However, to be realistic, all that the  
check valve can do is assure that no  
water bypasses the chillers, which in  
turn has the effect of increasing flow in  
the chiller. Thus with the installation of  
the check valve must be an algorithm  
to either slow down system pump(s)  
when flow increases beyond the design  
maximum for the on chiller or turn on  
additional chillers. Thus the check valve  
solution offers its own problems and  
many designers feel very  
VV Pump  
~
The unrestricted bypass line hydraulically decouples, or separates, the  
production and distribution pumps so that they cannot operate in a series  
coupled pumping arrangement.  
Although the two pumping systems are independent, they have three things  
in common:  
uncomfortable with forcing pumps into  
series operation without the benefit of  
understanding the full impact thereof.  
bypass piping,  
no-flow static head (from the building water column), and  
water.  
This manual does not recommend the  
use of check valves in the bypass line.  
Changes in flows or pressures, due to variations in dynamic head or the  
number of chillers operating, cannot cross the bypass line.  
The extent of decoupling depends solely on the restriction (or lack of  
restriction) in the bypass pipe. Total decoupling is accomplished only if the  
bypass piping has zero pressure loss at any flow. Since this is not possible,  
some insignificant pump coupling will exist. The important issue is to keep  
the bypass piping free of unnecessary restrictions such as check valves (see  
sidebar).  
46  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
     
System Configurations  
Production  
An individual production (chiller) pump need only pump water from the  
return bypass tee (point A in Figure 29), through its chiller, and into the tee at  
the supply-end of the bypass line (point B in Figure 29). This represents a  
relatively small pressure differential and a low pumping-power requirement.  
In addition, each individual pump operates only when its corresponding  
chiller runs. Production loops are independent of one another, as well as from  
the distribution loop. They may consist of pump–chiller pairs that act as  
independent chillers. Or, manifolded and stepped pumps can be teamed with  
automatic, two-position chiller valves to operate in the same way as pump–  
chiller pairs. Figure 29 shows the latter arrangement. Temperature control is  
also independent. The conventional chilled-water temperature controller  
furnished with the chiller serves this function.  
Figure 29. Production loop  
Automated Isolation  
Valves  
Chiller 3  
Production  
Pumps  
Chiller 2  
Chiller 1  
Production  
Distribution  
B
A
Bypass Line  
Return  
Supply  
Chillers may be of any type, age, size, or manufacturer. System operation is  
simplest, however, if all of the chillers are designed to operate with the same  
leaving chilled-water temperature and through the same system temperature  
rise (temperature difference) across the chiller.  
Note: If the chillers in a decoupled system make the same chilled-water  
temperature, then all the operating chillers are loaded to equal percentages.  
There may be times when preferentially loading a chiller is desired. This is  
SYS-APM001-EN  
Chiller System Design and Control  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Configurations  
Distribution  
Distribution pumps take water from the supply water tee (point B in  
Figure 29), push it through all the distribution piping and load terminals, and  
then on to the return water tee (point A in Figure 29). This pump can (and  
should) allow variable flow.  
Figure 30. Distribution loop  
By itself, the distribution system is easy to understand. Figure 30 shows a  
simplified distribution system consisting of multiple cooling coils, each  
controlled by a valve that regulates the flow in its respective coil. In this case,  
the flow control valves should not be three-way because a constant flow is  
not desired. Instead, two-way modulating valves are used. As the aggregate  
loads change system flow, a constant speed pump would “ride” its flow-rate  
versus head-pressure relationship. This means that in response to the change  
of flow required, the pump will find a new equilibrium point along its  
operating curve (move from point A to point B in Figure 31).  
Return  
Supply  
Bypass Line  
Loads  
Alternatively, multiple pumps or variable-speed pumps can be used to limit  
the dynamic pumping head, similar to VAV fan control. Properly designed,  
part-load pumping power can approach the theoretical cubic relationship to  
flow, thus reducing energy consumption significantly. Today, most decoupled  
systems use a variable-speed drive on the distribution pump, and it may be  
required by the applicable energy code.  
Distribution  
A common strategy for operating the variable speed pump is to adjust the  
speed of the pumps motor to create a sufficient differential pressure, P, a t  
one or more critical points in the system, as shown in Figure 33. This  
pressure difference tends to decrease when the air-handler control valves  
open in response to increasing loads. To restore the P across the system,  
the pump controller increases the speed of the pump. Conversely, when the  
air-handler control valves close in response to decreased coil loads, the  
pump controller slows the pump speed to maintain the target P.  
Figure 31. Example pump curve  
Pump Curve  
B
A
Head  
Distribution-loop benefits of decoupled system arrangement  
The distribution system benefits from the ability to accommodate load  
diversity, the fact that system flow is variable, and (in a properly operating  
system) the fact that return water is maintained at temperatures near design.  
The last assumption is discussed further in “Low T syndrome” on page 79.  
Flow  
Load diversity. Not all chilled-water loads peak simultaneously. Therefore,  
the quantity of water that flows at any one time is reduced from the “sum of  
the peaks” load that would be required in a constant-flow distribution loop.  
This presents the possibility of reducing chiller, pump, and pipe sizes  
significantly.  
Variable flow. Because two-way control valves are used on the cooling coils,  
only the water that the loads actually use is pumped. Most of the time, this  
means a significantly reduced flow rate, accompanied by an even more  
significant reduction in pumping energy.  
48  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
     
System Configurations  
Elevated return-water temperatures. Because unused chilled water does not  
bypass the cooling coils (two-way, rather than three-way, control valves), all  
water that is returned accomplishes some cooling. Theoretically, the return-  
water temperature will always be at least as high as it is at full load. From a  
practical standpoint, this is not always possible, but it is closely approached  
in a properly operating system. In fact, at most part-load conditions, water  
returns from properly functioning air-conditioning coils at higher-than-design  
temperatures. In systems that use counterflow cooling coils, this occurs  
because the water leaving the coil tries to approach the temperature of the  
entering airstream.  
Warm return water provides advantages in system design. It permits  
“preferential” loading of chillers, for example. Warmer return water is useful  
with all systems, but particularly so with heat recovery and free cooling  
applications. For more information, refer to “Chilled-Water System  
Pumping arrangements  
Common  
Various distribution system arrangements are possible. A single, large  
pumping station, as shown in Figure 29, can be used. The station may consist  
of single or multiplexed pumps sequenced on or off.  
Campus  
Alternatively, each of several secondary distribution systems can be piped in  
parallel. For example, Figure 32 shows separate distribution systems for each  
of three loads. Clearly, this arrangement lends itself to the possibility of plant  
expansion by simply adding secondary distribution pumps to the existing  
plant.  
Figure 32. Campus pumping  
arrangement  
Tertiary or distributed  
Tertiary pumping is an extension of primary–secondary pumping when the  
distribution or secondary pump must overcome diverse and severe pumping  
requirements.  
SecondaryDistribution  
System loads can also be decoupled from the secondary distribution system.  
This is frequently done with very large systems. Figure 33 shows one method  
of providing “tertiary pumping” at the loads. A “load” may be something as  
large as an entire building, or as small as an individual cooling coil. When  
one or more loads have extreme head requirements, the degree of range  
ability of the distribution pump is severely curtailed. Tertiary pumping allows  
the excess pumping requirements to be placed on a third pumping system  
thus shielding the distribution pump from divergent pressure requirements.  
Pumps  
Most importantly, the loads must be controlled so that only the water needed  
to perform cooling is taken from the distribution loop. Water must not be  
allowed to flow into the return piping until it has sustained a specific  
temperature rise. Tertiary pumps can be either constant flow or variable flow,  
to best meet the terminal load requirements.  
SYS-APM001-EN  
Chiller System Design and Control  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
System Configurations  
Figure 33. Tertiary pumping arrangement  
Check Valve  
Chiller 2  
Chiller 1  
Differential  
Pressure  
Transmitter  
Variable-Speed  
Drive  
Loads  
Loads  
Control  
Valve  
Decoupled system–principle of operation  
Figure 34. Decoupled system supply  
At the tee connecting the supply and bypass lines, a supply–demand  
relationship exists, as shown in Figure 34. Think of the total flow rate from all  
operating pump–chiller pairs as supply. Demand is the distribution system  
flow required to meet loads. Whenever supply and demand flows are  
unequal, water will flow into, or out of, the bypass line. Flow can be sensed  
directly or inferred from the bypass-water temperature.  
tee  
Return  
Supply  
(Production)  
Excess  
Supply  
An inadequate supply to meet demand causes return water to flow out of the  
bypass leg of the tee and into the distribution system. The mixture of chiller-  
supply water and warm system-return water, then, flows into the distribution  
loop. Supply-water temperature control is compromised when this happens.  
If the bypass-line flow into the supply tee (Figure 34) can be sensed, its  
presence can be used to energize another pump-chiller pair. The increase in  
supply water flow from the additional pump changes the supply–demand  
relationship at the tee, eliminating return-water mixing. As long as return-  
water mixing does not occur at the supply tee, no additional chiller capacity is  
required. When mixing does occur, an additional chiller may be needed,  
depending on the amount of mixing that can be tolerated.  
Bypass  
Inadequate  
Supply  
Demand  
(Distribution)  
Much of the time, supply exceeds demand and the surplus flows to the return  
tee. If a chiller pump is stopped prematurely, the bypass-line flow will again  
50  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Configurations  
show a deficit and the pump will be cycled on again. The amount of surplus  
flow necessary depends on the size of the chiller to be shut off. The surplus  
flow must exceed a certain quantity before shutting off a chiller–pump pair. If  
all chillers are equal in size, the surplus-flow signal can be a constant value.  
Control of the number of chillers is accomplished by simply noting the  
direction of flow in the bypass line. Thus, the system operates as a flow-  
based demand system, not a temperature-based demand system.  
Flow-based control  
To properly operate a primary–secondary system, an indication of direction  
of flow and the flow rate through the bypass line is necessary. This may be  
done either directly or indirectly. When bypass flow is from supply to return,  
it is called surplus. Bypass flow moving from return to supply is termed  
deficit.  
Flow-sensing  
Direct flow-sensing in the bypass line can be accomplished in several ways. A  
number of flow-metering technologies have been used successfully. These  
include Pitot tube, venturi, orifice plate, differential pressure, turbine,  
impeller, vortex, magnetic, and ultrasonic transit-time. The accuracy, ease of  
installation, maintainability, and cost of meter technologies vary widely. To  
give accurate results, a flow meter must be calibrated periodically, with some  
flow meters requiring more-frequent calibration than others. When using  
flow-sensing devices, it is important to understand the range of flows a  
device can properly measure and its calibration requirements. The readings  
will only be as good as the instrumentation. Also note that many flow-  
measurement devices require several diameters of straight pipe for accurate  
readings.  
Temperature-sensing  
Mixed water streams at the outlets of the supply- and return-water tees  
(Figure 35) can be used to indirectly determine the supply–demand  
relationship. Standard temperature-mixing equations can be used to  
determine the exact amount of surplus or deficit flow in the bypass line.  
Figure 35. Temperature-sensing  
(Optional)  
D
(Required)  
A
B
The five temperatures sensed—at points A, B, C, D, and E—are received by a  
programmable controller. (Some control systems use only two sensors, at  
points B and D, in conjunction with “pre-programmed” algebraic mixing  
equations.) Processing software applies the classic mixing equations and  
determines the resulting action to properly control the chilled-water system.  
C
(Optional)  
(Required)  
(Optional)  
E
Note that sensor D needs to be very accurate, especially if there are many  
chillers, since small temperature changes may warrant chiller sequencing.  
Either temperature-sensing strategy has a cost and flexibility advantage if a  
building or chiller-plant management system already exists or is planned.  
Return Main  
Supply Main  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
51  
     
System Configurations  
Chiller sequencing in decoupled systems  
Given the amount and direction of flow in the bypass line, chillers can be  
added or subtracted.  
Adding a chiller  
When there is deficit flow in the bypass line, the system is receiving water at  
a temperature above the desired supply water temperature. At this point in  
time, a chiller and pump may be added. Many operators sense deficit flow for  
a particular amount of time (for example, 15 minutes) to ensure that the  
deficit flow is not a result of some transient condition. This reduces the  
chances of cycling a chiller; that is, turning on a chiller and then turning it off  
after a short time.  
Subtracting a chiller  
A chiller may be turned off when enough surplus water is flowing through the  
bypass line. How much is enough? Enough so that the chiller does not need  
to cycle on again in a short time period. Many system operators compare the  
amount of surplus flow with the flow rate of the chiller they are considering  
turning off. If this ratio is 110 to 115 percent, they turn the chiller off. Lets look  
at an example:  
Chiller 1 can make 960 gpm [60.6 L/s] of 40°F [4.4°C] chilled-water, while  
Chiller 2 can make 1,440 gpm [90.8 L/s]. At present, there is 1,100 gpm  
[69.4 L/s] of surplus flow in the bypass line.  
The surplus bypass flow is presently 115 percent of Chiller 1s flow. If we  
turn Chiller 1 off, we will have 140 gpm [8.8 L/s] of surplus flow left.  
Note that the surplus bypass flow is presently only 76 percent of Chiller  
2s flow. If we turn Chiller 2 off, we will have 340 gpm [21.5 L/s] of deficit  
flow. It is clear that we would have to cycle that chiller back on soon.  
In this case, we could turn Chiller 1 off and leave Chiller 2 on for the most  
efficient use of the chillers.  
Multiple chilled-water plants on a distribution loop  
When decoupled systems are used on large campus-type systems, added  
loads are often located some distance away from the original loads. Yet,  
planners like the idea of somehow hooking the new loads to the existing  
system. The double-ended system shown in Figure 36 is one way of handling  
this requirement. A second production facility is placed at a convenient  
location in the new part of the campus. Its distribution plant is laid out as a  
mirror image of the original piping, and connects to it at the ends of each  
system. Each production facility has its own bypass.  
Both production loops feed into the now common distribution loop.  
Depending on the flows from the production facility distribution pumps,  
loads could be served by either plant.  
52  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
Figure 36. Double-ended decoupled system  
Check Valves  
Chiller 2  
Existing Plant  
Chiller 1  
Existing Bypass Line  
Production  
Distribution  
Loads  
New Bypass Line  
Distribution  
Production  
New Plant  
Chiller 3  
Chiller 4  
One of the benefits of decoupled water systems is that they are simple to  
control. The distribution pump flow is determined by a pressure transducer  
located at the furthest load. Flow in the decoupler indicates when to start and  
stop chillers and the chiller pumps are turned on and off with the chillers.  
Much of this simplicity is lost when multiple chiller plants are connected to  
the same system. The system shown in the figure above is a fairly simple  
example, but even so it can be used to show the difficulty of controlling these  
systems. The following sections point out some of the complications.  
Other chiller plant/distribution loop  
arrangements are possible, but if used,  
they should be reviewed to make certain  
they will be free from hydronic  
problems.  
Pump control in a double-ended decoupled system  
Chiller pump control in a double-ended decoupled system remains  
unchanged; the chiller pump is started when the chiller is enabled. On a  
single-plant decoupled system, the distribution pump's speed is modulated  
based on a pressure sensor located at the end of the loop (point of lowest  
pressure) to maintain sufficient pressure drop across all the loads.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
53  
 
System Configurations  
When more than one chiller plant is operating, finding the right location  
for the differential pressure sensor can be difficult. The point of lowest  
pressure in the system shifts depending on which loads are using the most  
water. It will probably be necessary to have a number of differential pressure  
sensors in the distribution loop. In that instance, the control system  
determines the lowest differential pressure signal and uses it to determine  
what speed signals to send to the distribution pumps. Sending the same  
speed signal to both distribution pumps is simple and will prevent the pumps  
from “fighting” each other for the load. However, it will likely result in more  
chillers operating than would be required to meet the load (more on this  
below). There is one exception: If only one chilled-water plant has an  
operating chiller, the distribution pump associated with that plant should be  
the only one operating.  
Chiller sequencing in a double-ended decoupled system  
In addition to pump control, the sequencing of chillers must be integrated  
between the two plants. With a double-ended plant, it is possible to have one  
plant operating in deficit flow and the other with sufficient surplus flow to  
meet the needs of the loads (load/flow imbalance). In other words, a  
sufficient number of chillers are operating to meet the load, but the  
distribution pumps are not delivering the flow to where it is needed. There  
are two solutions to this problem:  
1
Adjust the speeds of the distribution pumps to move the water to where it  
is needed. This solution is simple in concept but difficult in application  
and will not be covered here. It increases complexity and should be  
considered carefully prior to implementation. If this is attempted, both  
distribution pump speeds should be changed slowly, and in opposite  
directions (increase one, decrease the other).  
2
Allow each of the plants to make start/stop decisions based on the flow in  
its decoupler. In this case, the needs of the loads will be met; however,  
more chillers may be running than would otherwise be required.  
Starting chillers. When deficit flow is detected at a chilled-water plant, a  
chiller associated with that plant should be started. This should start chillers  
in the plant closest to the loads using the most water and help avoid the load/  
flow imbalance described above. Deficit flow can be detected by either of the  
common flow detection methods. (See “Flow-based control” on page 51.)  
Note that this limits the operator's flexibility to preferentially start chillers in  
the plant further from the load (preferential start may be desirable to load the  
plant with the most efficient chillers first, for example).  
Stopping chillers. On a single-plant decoupled system, surplus flow through  
the decoupler pipe is the normal operating mode. When the surplus flow  
exceeds the flow of one of the chillers in the plant by a fixed percentage, that  
chiller and its pump can be stopped and the plant will still be creating surplus  
flow. On double-ended plants this same logic can be used; however, a chiller  
should only be shut off when both plants have sufficient surplus to shut off a  
chiller. Only one chiller should be stopped at this time, and it should be the  
one in the plant with the most surplus flow. Thus, the normal operating mode  
for a double-ended plant is with one plant in surplus and the other operating  
54  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
with a surplus that may, or may not, be large enough to indicate stopping a  
chiller in that plant.  
Other plant designs  
There are many other ways to connect chillers to distributed loops and each  
provides its own challenges and opportunities. The advent of variable-  
primary-flow chilled-water systems offers some new opportunities as does  
distributed pumping. In any case, getting system design advice specific to  
your system early in the process can prevent or identify many operational  
challenges.  
Variable-Primary-Flow Systems  
Two main physical differences distinguish this type of system from the more  
familiar primary–secondary design, which hydraulically “decouples” the  
constant-flow production side of the chilled-water loop from the variable-flow  
distribution side. The variable-primary-flow (VPF) design eliminates the  
constant-flow chiller pumps and uses the variable-flow pumps to circulate  
water throughout the entire chilled water loop (Figure 37). Both systems  
include a bypass line, but the VPF bypass will be smaller.  
Figure 37. Variable-primary-flow system  
Typ  
Chiller 1  
Isolation Valves  
Chiller 2  
Flow Meter  
(Alternative to Chiller P)  
Bypass Line  
Modulating  
Control Valve  
Airside Coils with Two-Way  
Control Valves  
Bypass Line  
Alternate  
Location  
In a VPF system, water flow varies throughout the entire system—  
through the evaporator of each operating chiller as well as through the  
cooling coils. Two-way control valves on coils, check (or isolation) valves on  
chillers, and a bypass pipe with a control valve are required to implement a  
VPF system.  
Variable-flow chiller pumps eliminate the need for a separate distribution  
pump.  
SYS-APM001-EN  
Chiller System Design and Control  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Configurations  
The bypass can be positioned either upstream or downstream of the  
cooling coils.  
A control valve in the bypass ensures that the amount of flow through the  
operating chiller(s) never falls below the minimum limit, but remains  
closed most of the time.  
Notice that the VPF design adds a modulating control valve in the bypass  
line. At low loads, the bypass valve delivers the water necessary to maintain  
the minimum evaporator-flow limit of each operating chiller. By contrast, the  
bypass line in a primary-secondary system ensures constant chiller flow at all  
times.  
A less obvious difference between variable and constant primary flow lies in  
system operation. In a primary-secondary system, a chiller and its primary  
pump typically operate in tandem. The VPF design can separate pump  
control (delivering enough water) from chiller sequencing (making the water  
cold enough).  
Like the secondary pump in a primary-secondary system, the pumps in a  
typical VPF system operate to maintain a target differential pressure, P, a t a  
specific point in the system (Figure 37). This pressure difference tends to  
decrease when the air-handler control valves open in response to increasing  
loads. To restore the P across the system, the pump controller increases the  
speed of the pump. Conversely, when the air-handler control valves close in  
response to decreased coil loads, the pump controller slows the pump speed  
to maintain the target P.  
Meanwhile, the plant controller stages the chillers on and off to match  
cooling capacity with system load. If the air handlers operate properly, the  
difference between the return- and supply-water temperatures, T, remains  
nearly constant. Therefore, increasing the water flow through the chiller  
evaporators increases the load on the operating chillers.  
Advantages of variable primary flow  
The desire to make or save money lies at the heart of many of our decisions.  
In the context of HVAC design, decisions made to save money often involve a  
trade-off between acquisition expense and operating cost. If you can realize  
savings on both fronts, so much the better.  
Perhaps this explains the increased interest in chilled water systems with VPF.  
VPF designs use fewer pumps and fewer piping connections than primary–  
secondary systems, which means fewer electrical lines and a smaller  
footprint for the plant. These factors reduce the initial cost of the chilled-  
water system, although the savings may be partially offset by additional  
costs for flow-monitoring and bypass flow (bypass line and control valve).  
VPF designs may also require more programming for system control than  
other designs.  
Operational savings of VPF  
designs  
Bahnfleth and Peyer  
discuss the  
operational savings of VPF designs. For  
many common systems, however, the  
primary pump power on which they base  
their assessment may be too high.  
As for operating costs, how much a VPF design saves depends on the  
pressure drops and efficiency of the pumps (see sidebar). A VPF design  
displaces the small, inefficient, low-head primary pumps used in primary–  
56  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
 
System Configurations  
secondary systems. The pressure drops previously satisfied by the  
distribution pumps are instead satisfied by the now larger primary-only  
pumps, permitting selection of larger, more efficient pumps (with efficiencies  
similar to those of the secondary pumps in a primary–secondary system).  
Dispelling a common  
misconception  
True or false: “Chillers operate more  
efficiently in a system with variable  
rather than constant primary flow  
because of the greater log mean  
temperature difference (LMTD).”  
VPF systems present building owners with several cost-saving benefits that  
are directly related to the pumps. The most obvious cost savings result from  
eliminating the constant flow primary pumps, which, in turn, avoids the  
material and labor expenses incurred with the associated piping connections,  
mechanical room space, and electrical service. Although the number of  
pumps is reduced, the sizes of both the pumps and the variable-frequency  
drives increase since the pumps must be sized to overcome the entire  
systems pressure drop. This offsets some of the installed cost savings of  
having fewer pumps.  
It is true that the return water  
temperature in a properly operating VPF  
system remains constant as the amount  
of flow changes. It is also true that the  
LMTD can be increased by changing the  
production (primary) side of the chilled-  
water loop from constant to variable  
flow. But there are other facts to  
consider.  
Building owners often cite pump-related energy savings as the reason they  
installed a VPF system. With the help of a software analysis tool such as  
System Analyzer™, TRACE™ 700, Chiller Plant Analyzer, or EnergyPlus, you  
can determine whether the anticipated energy savings justify the use of  
variable-primary flow in a particular application.  
In a system with constant primary flow:  
Entering-evaporator temperature and  
LMTD fall as the cooling load  
diminishes.  
The convective heat transfer  
coefficient, like the primary flow,  
remains constant despite reductions  
in load.  
It may be easier to apply a variable-primary-flow system rather than a  
primary–secondary system to an existing constant-flow chilled-water plant.  
Unlike the primary–secondary design, the bypass can be positioned almost  
anywhere in the chilled-water loop and an additional pump is unnecessary.  
In a system with variable primary flow:  
The convective heat transfer  
coefficient in the chiller evaporator  
decreases with a reduction in flow.  
Chiller selection requirements  
Reduced flow decreases the overall  
heat-transfer effectiveness of the  
chiller evaporator.  
Variable-flow systems require chillers that can operate properly when  
evaporator flow varies. Varying the water-flow rate through the chiller  
evaporator poses two control challenges for those who design and operate  
VPF systems:  
The net effect is that the power  
consumption for a given chiller is  
virtually the same whether the chiller’s  
evaporator flow is variable or constant.  
1
Maintaining the chiller flow rate between the minimum and maximum  
limits of the evaporator  
2
Managing transient flows without compromising stable operation,  
especially in multi-chiller plants  
Evaporator flow limits  
Select for a minimum evaporator-flow limit that is 60 percent of the chiller’s  
design flow rate. One benefit of VPF systems is reduced pumping energy. To  
realize this benefit, chilled water flow must not remain constant. As the flow  
decreases, it approaches the minimum flow rate of the chillers—so, how do  
we select for a minimum chiller flow rate that will result in the pump-energy  
savings?  
The answer depends on the type of chiller, but generally speaking, lower is  
better because it extends the ability of a single chiller to operate at low loads  
without bypass flow. Most of the potential savings are realized by the time  
that the system flow rate decreases to 50 percent of design.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
57  
System Configurations  
Experience with actual VPF plants indicates that a minimum evaporator-flow  
limit of 60 percent for packaged chillers and 40 percent or less for configured  
chillers work well.  
Chiller manufacturers specify minimum and maximum limits for evaporator  
water flow. Their objective?  
To promote good heat transfer and stable control (minimum flow limit)  
To deter vibration and tube erosion (maximum flow limit)  
In the past, the typical range for water velocity in a chiller was 3 to 11 feet per  
second. Today, manufacturer-conducted testing shows that specific chillers  
may accommodate evaporator flow rates as low as 1.5 feet per second,  
depending on tube type. This is good news for VPF systems because it  
extends the chillers ability to operate effectively without the addition of  
bypass flow.  
The minimum flow limit for a chiller can be lowered by selecting an  
evaporator with more passes (a common option for machines with cooling  
capacities of 150 tons or more). Granted, more passes may require a higher  
evaporator pressure drop and more pumping power (Table 13). However, as  
the system flow rate decreases, the evaporator pressure drop also decreases  
by approximately the square of the flow rate reduction. Therefore, the pump  
requires less extra power to work against the pressure drop as the system  
flow rate drops below the design value.  
The other benefit of the added pass is better turndown with a wider  
evaporator T, which starts at a lower design flow rate for the same cooling  
capacity. In the case of the two-pass chiller, when using a 15° T, the chiller  
invoked minimum flow prior to reaching the 50 percent system flow rate. This  
could cause a more complicated transition from one to two chillers, as  
more pumping energy will be used in the system that requires bypassed flow  
more of the time.  
1
Table 13. Effect of number of passes on minimum evaporator flow and pressure drop at reduced flow with packaged chillers  
Design  
flow rate  
gpm [L/s]  
Evap. pressure  
drop at design  
flow, ft.water  
[kPa]  
Evap. pressure  
drop at 80%  
flow rate,  
Evaporator pressure  
drop at 50% flow rate,  
ft. water [kPa]  
Minimum flow  
rate, gpm [L/s]  
Evaporator pressure  
drop at minimum  
flow rate, ft. water  
[kPa]  
ft.water [kPa]  
2 pass  
3 pass  
180 [11.4]  
180 [11.4]  
113 [7.4]  
13.7 [40.9]  
42.6 [127.3]  
5.6 [16.7]  
9.0 [26.9]  
28.7 [85.8]  
3.5 [10.5]  
3.5 [10.5]  
77 [4.9]  
52 [3.3]  
77 [4.9]  
2.6 [7.8]  
4.0 [12.0]  
2.5 [7.5]  
11.9 [35.6]  
2 pass  
(15° T)  
flow too low, use min.  
2.5 [7.5]  
3 pass  
116 [7.3]  
19.6 [58.6]  
12.8 [38.3]  
5.0 [14.9]  
52 [3.3]  
4.0 [12.0]  
(15° T)  
1 Chillers may have slight differences in capacity, depending on which variable (flow, capacity, or T) is allowed to adjust.  
58  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Configurations  
Small packaged chillers typically offer less design flexibility than larger  
machines. It may not be possible to select a small packaged chiller with a  
minimum flow rate of less than 60 percent of the design system flow… but  
don’t let this deter you from designing a VPF plant that includes small  
packaged chillers. Remember, pump power drops with the cube of the  
reduction in flow, so even a modest 20 percent decrease in flow results in a  
50 percent pump energy reduction. A 40 percent flow reduction yields an 80  
percent pump energy reduction. The key to making variable flow with limited  
flow turndown work properly is devising a plant layout and sequencing  
strategy that accommodates the chillers minimum evaporator-flow limit.  
Managing transient water flows  
The second requirement of the selected chillers is proper control during  
“transient flows.” This situation refers to the hydraulic effects caused by an  
isolation valve when it opens (before the associated chiller starts) or closes  
(after the chiller stops). To illustrate what happens, lets look at an example.  
Assume that the two-chiller VPF system in Figure 37 is designed for a 16°F  
[8.9°C] T and that it delivers 40°F [4.4°C] chilled water. The temperature of  
the return water remains relatively constant at 56°F [13.3°C], provided that  
the coils and two-way valves function properly. Only Chiller 1 operates when  
the cooling load is low; the isolation valve for Chiller 2 remains closed.  
As the cooling load increases, the pump controller increases the rate of  
chilled water flow through the system. Chiller 2 starts when Chiller 1 can no  
longer produce 40°F [4.4°C] water. Opening the isolation valve for Chiller 2  
almost instantly reduces the flow rate through Chiller 1 by half (Table 14),  
which effectively doubles the T. Chiller 1s controller will unload the machine  
as quickly as possible, but in the interim, it will attempt to produce a 32°F T  
[0°C] and cool the water to 24°F [-4.4°C]. If the chiller cannot unload quickly  
enough, built-in fail-safes should stop and lock out the chiller before damage  
occurs… but at the expense of satisfying the cooling load. The system can be  
designed and operated to keep this scenario from occurring. This information  
is provided in the following sections.  
Table 14. Flow-rate changes that result from isolation-valve operation  
Number of operating chillers  
1
2
3
4
5
Flow-rate reduction when an isolation valve  
opens*  
50%  
33%  
25%  
20%  
17%  
*Flow-rate reduction is expressed as a percentage of the actual chilled water flow rate  
prior to transition:  
number of chillers operating  
% flow-rate reduction = 1–  
number of chillers operating +1  
Select for the greatest tolerance to large changes in flow rate. Theobjective  
is to simplify system control by minimizing the need for “supplemental”  
demand limiting or valve control as chillers come online. Chillers that are  
well-suited for variable primary flow can tolerate and respond to rapid flow-  
SYS-APM001-EN  
Chiller System Design and Control  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
rate changes (Table 14). Selecting chillers with these characteristics improves  
the likelihood of stable, uninterrupted operation.  
Estimate the expected flow-rate changes and make sure that the chillers you  
select can adapt to them. For example, one of the newest unit controllers on  
the market can reliably maintain the desired chilled water temperature with a  
flow-rate reduction of 50 percent per minute. Figure 38 shows the response  
of a chiller equipped with this controller in a more extreme situation. The  
flow dropped 67 percent in 30 seconds, with limited effect on the leaving  
chilled water temperature. Another, less robust chiller controller permits  
flow-rate changes of less than 2 percent per minute and would need 25  
minutes to adapt to a flow-rate reduction of 50 percent. Fluctuations of 2  
percent or more are typical, even during normal system operation.  
Attempting to limit flow-rate changes to this extent while starting or stopping  
a chiller is impractical, if not impossible.  
When comparing prospective chillers, consider the transient-flow tolerance  
of the unit controllers. Then work closely with the chiller manufacturer to  
devise a flow-transition sequence that accounts for the unique operating  
characteristics of both the chiller and the application. Transient flow rate  
control is discussed in more detail on page 65.  
Figure 38. Example of chiller control responsiveness to flow-rate reduction*  
*Data represents a Trane AdaptiView™ and CH530 chiller controller with flow compensation.  
Select for nearly equal pressure drops across all chiller evaporators. A VPF  
design loads and unloads the chiller(s) based primarily on the rate of water  
flow through the evaporator. If a difference in size or type of evaporator gives  
one chiller a lower pressure drop than the others in the plant, that chiller will  
receive a higher rate of water flow and a correspondingly greater load.  
Dissimilar pressure drops can make it difficult to provide stable plant  
operation. Table 15 demonstrates this effect in a two-chiller system (similar to  
the one shown in Figure 37). In this case, more water flows through Chiller 1s  
60  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
evaporator because its selection pressure drop is lower than that of Chiller 2.  
Load is proportional to flow rate and temperature difference, tons = (gpm ×  
T) / 24. Because Chiller 1 is asked to satisfy a load that exceeds its capacity,  
it cannot satisfy the chilled water setpoint when the return water temperature  
equals the design condition. Meanwhile, Chiller 2 is less than fully loaded.  
Balancing the system at the design condition, for example, by installing a  
balancing valve in series with Chiller 1, reduces this problem and works well  
at design and part load conditions. Alternatively, you could increase the load  
on Chiller 2 by lowering its chilled water setpoint; however, this complicates  
system control. The simplest solution is to select chillers that have (nearly)  
equal pressure drops at their design flow rates, whether the capacities are  
the same or not.  
Table 15. Effect of dissimilar evaporator pressure drops  
Capacity,  
tons  
Flow rate, gal/min  
Pressure drop, ft H 0*  
2
Selection  
750  
Actual  
Selection  
Actual  
14.3  
Change, %  
+9.2  
Chiller 1  
Chiller 2  
500  
300  
819  
381  
12  
20  
450  
14.3  
-15.3  
*Values shown here are based on the assumption that pressure drop changes with the square of the flow  
rate.  
System design and control requirements  
If experience has taught us anything about implementing variable primary  
flow, its this: The single, most important contribution of the engineer is to  
provide written, detailed descriptions of the plant’s sequence of  
operation.  
These descriptions should include control sequences for:  
Full- and part-load operation  
Minimum and maximum flow-rate management  
Transient flow-rate changes  
Starting and stopping chillers  
Furthermore, this information must be shared early in the design process.  
Without specific, documented sequences of operation, it is unlikely that the  
controls provider will devise programs that operate the plant as intended.  
Bottom line: VPF plants that work result from close, early-on collaboration  
between the engineer, the chiller manufacturer, and the controls provider.  
Variable primary flow is a value-added option that can help your clients curb  
operating costs at a lower initial cost than traditional primary–secondary  
designs … but only if you select the right components, install them properly,  
and operate them in accordance with a well-thought-out control scheme.  
SYS-APM001-EN  
Chiller System Design and Control  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Configurations  
Accurate flow measurement  
The success of a variable-primary-flow installation depends on the quality of  
the flow-measuring device that controls the system bypass valve (and  
perhaps also indicates the plant load). Some practitioners use a flow meter  
to directly detect the flow rate (C in Figure 37); others use a differential  
pressure sensor (D) that monitors the change in water pressure across the  
chiller evaporator and then correlates the pressure differential to a water flow  
rate.  
Select a flow measurement device with accurate and repeatable  
measurements. Regardless of which type of device you use, the flow meter  
or differential pressure sensor must be of high quality; that is, the device  
must provide accurate and repeatable measurements. For the plant to  
operate well, the device also must remain calibrated and perform reliably  
over time. Purchase prices vary widely, but the adage “you get what you pay  
for” typically holds true. In our experience, the cost of a suitable flow-  
measuring device is closer to $1,000 USD than to $100 USD. Put simply, don’t  
compromise on accurate sensing devices when negotiating potential cost  
reductions during the “value engineering” phase of a project.  
One further caveat about measurement accuracy: Proper installation is  
critical to ensure accurate readings. If the manufacturer states that at least 10  
pipe diameters of uninterrupted flow are required both upstream and  
downstream of the sensing device, then make sure that the piping layout  
complies.  
Select an accurate proof-of-flow device for each chiller. Flow reductions  
through chillers in VPF systems often cause paddle-type flow switches to  
flutter or open altogether, which shuts down the chiller. To provide accurate,  
reliable confirmation of flow, select a sensitive pressure-differential switch  
(or other high-quality device) and install it properly, piping it across the  
evaporator.  
Bypass locations  
A bypass is required whether the primary flow is constant or variable. In a  
primary–secondary system, the decoupler allows excess primary water to be  
bypassed. In the VPF system, the bypass allows excess flow only when  
needed to maintain the chillers' minimum flow requirements.  
There are three common locations for the VPF bypass line:  
Place the smaller bypass required for a VPF system in the same position  
as the bypass in a “decoupled” system. A variable-speed drive on the  
pump located near the chillers reduces flow and allows substantial  
energy and operating cost savings. One drawback is that the valve must  
work against higher pressures—possibly causing wear and lack of  
controllability.  
Use three-way valves at some of the system coils. While this approach  
ensures minimum chiller flow, it reduces the pump operating cost-  
savings, due to the increased system flow and decreased return-water  
temperature.  
62  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Configurations  
Locate a bypass line and valve near the end of the piping run. The bypass  
control valve sees a lower operating pressure and may provide more  
stable control. Some operating cost savings may be sacrificed to maintain  
the pump-operating pressure at a higher level with the bypass located  
away from the chillers. The line sizes must be large enough to allow the  
minimum flow rate.  
One final method to ensure minimum evaporator flow is to have a constant  
load and flow somewhere in the system. However, if in the future the system  
changes and this constant flow no longer occurs, the system is likely to have  
operating issues when its flow approaches the chillers minimum.  
Delivering the appropriate bypass flow requires attention to line sizing,  
control-valve selection, and the response time of the system.  
Bypass flow control  
In a VPF system, the sole purpose of the bypass line with modulating control  
valve is to assure that the rate of chilled water flow through each operating  
chiller never falls below the minimum limit required by the manufacturer.  
Select a suitable control valve of high quality. When the bypass line is  
positioned near the chiller plant (A in Figure 37), as it is in many VPF  
installations, the control valve is exposed to comparatively high operating  
pressures. Selecting an appropriate valve actuator is critical because the  
valve must close against this pressure. As for the valve itself, choose one that  
maintains a linear relationship between valve position and flow rate;  
otherwise, the valve may permit too much water flow when it begins to open.  
Note: A common butterfly valve won’t provide the necessary flow  
characteristics. Some have found that pressure-independent valves work well  
as a bypass valve. Verify the suitability of a particular valve by requesting  
flow-versus-position data from the supplier.  
Locating the bypass line far from the chiller plant (B in Figure 37) lowers the  
operating pressure for the control valve.  
Minimize control lag. Regardless of where the bypass line is situated (at A or  
B in Figure 37), the control valve must react quickly to changes in system  
flow. You can improve control response either by hard-wiring the flow-  
sensing device, valve controller, and valve actuator; or by selecting devices  
that communicate directly with each other. Avoid relaying input/output  
signals through multiple system controllers.  
Chiller sequencing in VPF systems  
The success of a VPF application depends on more than the chilled-water  
system. It requires careful orchestration of the entire HVAC system, which  
means air handlers and coil-control valves as well as chillers and pumps.  
Proper sequencing helps to maintain the flow rate through each evaporator  
within the range recommended by the chiller manufacturer. As the system  
SYS-APM001-EN  
Chiller System Design and Control  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Configurations  
flow nears the maximum limit for the operating chiller(s), another machine  
must be brought online. Similarly, as the system load and flow decrease,  
chillers must be shut down to reduce the need for bypass water flow.  
Adding a chiller in a VPF system  
The simplest way to control a VPF system is to monitor the leaving-  
evaporator water temperature and allow the operating chiller(s) to load  
almost fully before bringing the next chiller online. As long as the system can  
maintain the target temperature, there is no need to activate another chiller.  
When the operating chiller(s) no longer provide enough cooling, the plant  
controller should start the next chiller. For example, when the temperature  
exceeds the design setpoint by a certain amount (for example, 1.5°F [0.8°C])  
for a set time (for example, 15 minutes) an additional chiller starts.  
One caveat: The next chiller should start before the chilled water flow reaches  
the maximum limit of the operating chiller(s), even if the operating chillers  
are not yet fully loaded. (This would rarely happen; most pipe velocity limits  
are below that of the chillers.)  
As chillers are brought online, flow rates may fluctuate substantially, and this  
occurs quite often in a system with two chillers. All systems, with any  
number of chillers, will find the most difficult transition when adding or  
subtracting the second chiller. An example will help explain the challenges.  
.
Table 16. Flow-rate-fluctuation examples  
Design  
flow rate  
gpm [L/s]  
Minimum  
flow rate  
gpm [L/s]  
Maximum  
flow rate  
gpm [L/s]  
Chiller 1  
Chiller 2  
960 [60.6]  
576 [36.3]  
675 [42.6]  
2,110 [133.1]  
2,474 [156.1]  
1,440 [90.8]  
At a point in time, Chiller 1 is active and has 1,100 gpm [69.4 L/s] flowing  
through its evaporator. It can no longer satisfy the required system supply  
temperature. What happens if Chiller 2’s valve is opened with no other action  
taken? If we assume that pressure drops are equal, 550 gpm [34.7 L/s] will  
flow through each chiller. This means Chiller 1s flow rate drops by 50 percent  
as fast as Chiller 2s isolation valve opens (probably beyond what its controls  
can respond to) and we are below each chillers minimum flow rate. Be aware  
that this could become an issue since chiller controls may protect the chiller  
by shutting it off. The result is that some combination of pump speed, bypass  
valve control, and slow-acting valves at the chillers must do two things:  
Keep change in flow rate within the equipment limitations  
Keep each chiller’s flow rate above its minimum  
64  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Configurations  
Controlling transient flows is mandatory, regardless of plant size. The  
number of chillers in the plant will not alter the degree of care needed to  
properly manage transient flow-rate changes because the transition from one  
operating chiller to two is inevitable in almost all plants.  
Temporarily unload the operating chillers before starting the next one.  
Reduce shock resulting from transient flows by unloading the operating  
chillers before opening an isolation valve to bring another chiller online.  
In his article, “Primary-Only vs. Primary-  
Secondary Variable Flow Systems,”  
Steven T. Taylor, principal of Taylor  
Engineering LLC, notes that unloading  
the active chillers before starting  
You can accomplish this by imposing a demand limit of 50 to 60 percent on  
the operating chillers, or by raising the chilled water setpoint one to three  
minutes before the isolation valve actuates. (See sidebar.)  
another produces warmer chilled water.  
Although the temperature increase  
seldom causes problems for comfort  
cooling, it may be unacceptable in  
industrial/process applications.  
Open the chiller isolation valves slowly to encourage stable operation. How  
slowly? That depends. If the chiller controller can only handle a flow-rate  
change of 2 percent per minute, then the isolation valve must take 25 minutes  
to open… far too long for most applications. Besides helping with chiller  
stability, slow valve operation reduces the likelihood of valve-induced water  
hammer in the piping system.  
With sophisticated chiller controls, a 30-percent-per-minute change in the rate  
of flow should work well in most applications. At this rate, the isolation valve  
will transition from fully closed to fully open in about two minutes.  
Like the bypass valve, be sure to select isolation valves that maintain a linear  
relationship between valve position and flow rate.  
The bottom line is that control of VPF systems must be considered during  
system design.  
Subtracting a chiller in a VPF system  
Subtracting a chiller in a VPF system is not simple, either. It is important to  
devise a “stop” strategy that protects the chillers from short-cycling.  
Knowing when to stop a chiller (to provide sufficient downtime between  
chiller starts) often is more challenging than knowing when to start it. The  
most reliable way to do so—assuming that the VPF system is properly  
installed, calibrated, and maintained—is to monitor the power draw of the  
operating chillers. (See sidebar.) Most unit controllers measure running load  
amps (RLA) at regular intervals. The %RLA (actual RLA divided by design  
RLA) provides a good indication of the present chiller load.  
Sequencing based on load  
Some plant operators prefer to sequence  
chillers by comparing the actual system  
load with the total plant capacity that  
would result if a chiller is turned off.  
However, this method can be less  
reliable than one based on power draw  
because flow- and temperature-sensing  
devices require periodic recalibration to  
correct for drift.  
Base the “stop” strategy for a multi-chiller plant with equally sized machines  
on the sum of the present %RLA for all chillers divided by the number of  
operating chillers minus one. If the result is less than the desired capacity for  
the operating chiller(s), then stop one of the machines.  
For example, suppose that a plant consists of three equally sized chillers,  
each of which is presently running at 60 percent of full-load capacity. If one  
chiller is shut off, the two chillers still online would operate at approximately  
90 percent of full-load capacity; (60% + 60% + 60%) / (3-1) = 90%. Having the  
remaining two chillers operating almost fully loaded risks the need to restart  
a chiller if the load increases.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
65  
 
System Configurations  
A more conservative approach might be to wait to turn off the chiller until it  
would result in no higher than 80 percent capacity for the remaining  
operating chillers. Going back to the example, if the desired (n-1) chiller  
capacity were 80 percent, it would not be appropriate to shut down a chiller.  
In this case, the plant controller should not turn off any of the chillers until  
each of them unloaded to 53 percent; (53% + 53% + 53%) / (3-1) = 80%.  
Note: For plants with unequally sized chillers, weight the %RLA value of each  
chiller by its design capacity and compare the weighted value with that of the  
chiller to be sequenced off.  
The other thing that must be checked before subtracting a chiller is how the  
system flow can be handled by one less chiller. As an example, suppose that  
two chillers are running near their minimum flow. Chiller 1 is at 650 gpm [41.0  
L/s] and Chiller 2 is at 760 gpm [47.9 L/s], so the system total is 1,410 gpm  
[88.9 L/s].  
Choice 1: Turn off Chiller 1. It is obvious that we should be able to turn  
Chiller 1 off and satisfy system load as long as the flow rate doesn’t increase  
too rapidly. However, the current system flow rate is close to Chiller 2s  
design flow rate of 1440 gpm [90.8 L/s], and if the system flow increases, we  
may need to restart Chiller 1.  
Choice 2: Turn off Chiller 2. If Chiller 1 has a condenser water temperature  
lower than design, its capacity has increased. Could we turn off Chiller 2?  
Chiller 1s flow is certainly within the allowable limits, but it may or may not  
be able to supply the required capacity. In this case, the dilemma is to ensure  
that there is enough chilled water capacity after a chiller is turned off.  
Obviously, control is an extremely important aspect of a VPF system.  
Other VPF control considerations  
Select slow-acting valves to control the airside coils.  
Valves that open and close slowly moderate the normal fluctuations of chilled  
water flow through the loop.  
Use multiple air handlers, and stagger their start/stop times.  
Unless it is programmed to do otherwise, the building automation system  
will simultaneously shut down all of the air handlers when the occupied  
period ends. If two chillers are operating when this happens—and if all of the  
coil-control valves close at the same time—then chilled water flow through  
the evaporators will drop to zero almost instantaneously. Such a dramatic  
change not only causes problems for the chillers, but also may deadhead the  
pumps.  
To help ensure that flow-rate changes remain within acceptable limits,  
“divide” the air handlers into several groups. Then implement control  
schedules that shut down each group individually at 10-minute intervals.  
66  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Configurations  
Plant configuration  
Consider a series arrangement for small VPF applications.  
When the plant consists of only two chillers and expansion is unlikely, you  
can simplify control by piping the evaporators in series. Doing so avoids flow  
transitions because the water always flows through both chillers. The series  
arrangement requires careful selection because the pump must be sized for  
the pressure drop through both chillers. However, the extra pressure quickly  
decreases (by roughly the square of the flow rate) as the flow rate slows. For  
example, at 80 percent of design flow, the evaporator pressure drop is only  
64 percent of design. Given this operating characteristic, a VPF design may  
permit a slightly higher system pressure drop than a comparable primary–  
secondary system without a noticeable penalty in operating cost. “Series  
For more information, refer to the Trane  
Engineers Newsletter, Don’t Overlook  
Optimization Opportunities in ’Small’  
Chilled Water Systems” (ADM-APN009-  
EN).  
Chillers” on page 44 discussed these arrangements in greater detail.  
Note: To further reduce the system P, lower the required rate of chilled-water  
flow through the system by increasing the temperature difference between the  
supply and return. Plants that supply 40°F [4.4°C] chilled water based on aT of  
16°F [8.9°C] or more are increasingly common.  
Assess the economic feasibility of VPF for single-chiller plants.  
Although most VPF applications consist of two or more chillers, variable  
primary flow also offers potential operating-cost savings in a new or existing  
single-chiller plant. Instead of a bypass line and flow-sensing devices,  
minimum flow through the chiller can be maintained by three-way valves.  
(Use enough three-way valves to assure that the minimum evaporator-flow  
rate of the chiller is always satisfied.) This simple approach will reduce  
pumping costs while providing the chiller with enough chilled water.  
To quantify the savings potential of variable versus constant primary flow in  
a single-chiller plant, we examined a two-story office building in St. Louis,  
Missouri. The HVAC system includes a 50-ton scroll chiller and a 5-hp chilled  
water pump. Figure 39 illustrates the results of our analysis. Although the  
absolute savings are not large, variable primary flow did reduce the cost of  
operating the chilled water system by more than 6 percent … enough to  
warrant further investigation. The difference in installed costs is a variable-  
speed drive, a differential pressure sensor, and a pump controller.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
67  
 
System Configurations  
Figure 39. Example of operating-cost savings for a VPF, single-chiller plant  
Analysis results are based on a 50-ton scroll chiller and a 5-hp chilled water pump for two-story office building  
in St. Louis, Missouri.  
Moderate “low T syndrome” by manifolding the chilled water pumps  
Manifolding two or more chilled water pumps (or slightly oversizing a single  
pump) can provide an individual chiller with more than its design chilled  
water flow… which means that you can fully load the chiller even if the return  
water temperature is colder than design.  
Sometimes described as “overpumping,” this strategy does not cure “low T  
syndrome”; it merely reduces the adverse effect of low T on system  
operation. (Refer to “Low T syndrome” on page 79). An example of low  
T syndrome is receiving a depressed (for example, 49°F [9.4°C]) return-  
water temperature rather than the design (for example, 56°F [13.3°C]) return-  
water temperature.  
Again, the only methods to load the chiller are to decrease the chilled-water  
leaving temperature or to increase the flow. If the pumping power and speed  
allows, the operator may be able to increase the chillers flow rate and  
capacity. Do not exceed the pumps operating envelope.  
Guidelines for a successful VPF system  
Chiller selection  
Select for the lowest possible minimum evaporator-flow limit (no more  
than 40–60 percent of system flow)  
Select for the greatest tolerance to large flow-rate changes, while  
maintaining required temperature setpoint  
Select chillers with approximately equal pressure drops across the  
evaporator at the design flow rate  
68  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Configurations  
Understand the specific loading/unloading characteristics of the chiller  
controller  
Bypass flow  
Select a high-quality control valve with linear-flow characteristics  
Select flow-sensing devices that deliver precise, repeatable  
measurements  
Minimize control lag by hard-wiring the controls or by selecting devices  
that communicate directly  
Chiller sequencing  
Temporarily unload the operating chillers before starting the next  
Open chiller isolation valves slowly to encourage stable operation  
Let the operating chiller(s) load almost fully before starting another  
Prevent short-cycling by devising a “stop” strategy based on the power  
draw of the operating chillers  
Plant configuration  
Consider a series arrangement for small VPF applications to avoid  
transient flows  
Assess the economic feasibility of variable primary flow for single-chiller  
plants  
Moderate “low T syndrome” by manifolding multiple chilled-water  
pumps or slightly oversizing a single chilled-water pump  
Take care to properly manage transient flows regardless of the number of  
chillers in the plant  
Airside control  
Select slow-acting valves to control the chilled-water coils  
Use more than one air handler and stagger their start/stop times  
SYS-APM001-EN  
Chiller System Design and Control  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chilled-Water System Variations  
A number of chilled-water system variations can and should be used when  
appropriate. Each configuration offers specific advantages to solve problems  
and add value to the system.  
Heat Recovery  
ASHRAE/IESNA Standard 90.1–2007 requires heat recovery in specific  
applications. Indoor air quality concerns have spurred the use of systems that  
subcool supply air to dehumidify, then temper, the air to satisfy space  
conditions. ASHRAE/IESNA Standard 90.1–2007 limits the amount of new  
reheat energy used in these applications. With these drivers, and energy costs,  
there has been a resurgence of heat recovery chillers. The example on page 75  
describes a cost-effective recovered-heat strategy. This scheme is commonly  
used for service-water heating in resort hotels and for certain process loads.  
A separate application manual discusses heat recovery, as does an Engineers  
Newsletter , so it is not discussed in depth in this manual. However,  
considerations for heat recovery on chilled-water system design are discussed.  
Figure 40. Sidestream plate-and-frame  
heat exchanger  
Condenser “Free Cooling” or Water  
Economizer  
There are several ways to accomplish free cooling through the use of a water  
economizer circuit. Three common techniques for chilled water systems are  
using a plate-and-frame heat exchanger, refrigerant migration, or well, river, or  
Chiller 2  
lake water. Each technique is discussed in more detail below and in an  
Engineers Newsletter  
.
Plate-and-frame heat exchanger  
A plate-and-frame heat exchanger may be used in conjunction with a cooling  
tower to provide cooling during very low wet-bulb temperature conditions.  
When it is to be used for these purposes, designers often specify a cooling  
tower larger than necessary for design conditions so that it can be used for  
many hours with the plate-and-frame heat exchanger.  
Chiller 1  
Bypass Line  
In this type of water economizer, the water from the cooling tower is kept  
separate from the chilled-water loop by a plate-and-frame heat exchanger. This  
is a popular configuration because it can achieve high heat-transfer efficiency  
without cross-contamination. With the addition of a second condenser-water  
pump and proper piping modifications, this heat exchanger can operate  
simultaneously with the chiller, provided the chiller is placed downstream of the  
heat exchanger (as shown in Figure 40). As much heat as possible is rejected  
through the heat exchanger while the chiller handles the rest of the cooling  
Plate-and-Frame  
Heat Exchanger  
70  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
                 
Chilled-Water System Variations  
load. The details of operation are discussed in “Sidestream plate-and-frame  
Plate-and-frame heat exchangers isolate the building loop from the water in  
the open cooling tower loop, but they must be cleaned, typically annually.  
The labor and parts for cleaning and reassembly (e.g., gasketing) is an  
expense that should be factored into the life-cycle cost of this option.  
Refrigerant migration  
Another method of “free” cooling is to transfer heat between the cooling  
tower water and the chilled water inside a centrifugal chiller through the use  
of refrigerant migration, also known as a thermosiphon. Figure 41 shows a  
centrifugal chiller equipped for refrigerant migration free cooling. When the  
temperature of the water from the cooling tower is colder than the desired  
chilled-water temperature, the compressor is turned off and automatic shut-  
off valves inside the chiller refrigerant circuit are opened, as shown in  
Figure 42. Because refrigerant vapor migrates to the area with the lowest  
temperature (and pressure), refrigerant boils in the evaporator and the vapor  
migrates to the cooler condenser. After the refrigerant condenses, it flows by  
gravity back through a shutoff valve to the evaporator. This allows refrigerant  
to circulate between the evaporator and condenser without the need to  
operate the compressor.  
Depending on the application, it is possible for refrigerant migration in a  
centrifugal chiller to satisfy many hours of cooling load without operating the  
compressor. Free cooling chillers serving systems that can tolerate warmer  
chilled-water temperatures at part-load conditions can produce more than 60  
percent of the rated capacity without compressor operation. There are no  
cooling coil fouling concerns because the cooling-tower water flows through  
the chiller condenser and is separate from the chilled-water loop. There is no  
additional expense for cleaning, as the condenser tubes are the same as  
those used for normal cooling mode and should already be on a  
maintenance schedule. In addition, fewer pipes, pumps, and fittings are  
required, and no additional heat exchanger is required.  
Figure 41. Refrigerant migration chiller in compression cooling mode  
Conditioner  
Refrigerant  
Economizers  
Storage Tank  
Evaporator  
Compressor  
SYS-APM001-EN  
Chiller System Design and Control  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Chilled-Water System Variations  
Figure 42. Refrigerant migration chiller in free-cooling mode  
Conditioner  
Refrigerant  
Storage Tank  
Economizers  
Compressor  
Evaporator  
One option is to equip one or more parallel chillers with the refrigerant  
migration cycle (Figure 43). This essentially turns the chiller into a shell-and-  
tube heat exchanger run-around loop.  
Figure 43. Water economizer piped in parallel with chillers  
Cooling Tower  
Chiller 1  
Chiller 2  
Refrigerant Migration Chiller  
Chilled-Water  
Loop  
Bypass Line  
Distribution  
Pump  
Well, river, or lake water  
There are times when well, river, or lake water will be pumped through the  
condenser. In these cases, examine the cost of pumping the water versus the  
benefit of more water passing through the condenser. The environmental  
limitations imposed by local codes are another consideration. Some locales  
will not allow well water to be dumped after being used. Other local  
authorities limit the maximum water temperature that may be returned to a  
72  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Chilled-Water System Variations  
body of water. Flow rates need to be carefully selected to balance the  
economic and environmental requirements.  
Preferential Loading  
Preferential loading is desirable for systems that use heat recovery or free  
cooling to allow the equipment used in these schemes to remain more fully  
loaded. In a heat recovery system, a more heavily loaded heat recovery  
chiller produces more heat that can be recovered for the desired process.  
Similarly, if the condenser free cooling method is preferentially loaded in the  
sidestream arrangement discussed below, it receives the warmest return  
water temperature and thus continues to operate as load and/or condenser  
water temperature increases.  
Preferential loading may also be beneficial for use with either a high-  
efficiency chiller that should be fully loaded whenever possible, or a chiller  
using a fuel other than electricity, such as an absorption chiller using waste  
steam from a cogeneration plant, or a chiller coupled with an engine that  
generates electricity. When used with the latter, the system is able to  
preferentially load the alternate fuel chiller when the cost of electricity is high.  
Preferential loading - parallel arrangement  
If a chiller in a decoupled system is moved to the distribution side of the  
bypass line in a primary-secondary system, due to system hydraulics and  
temperatures, the chiller is preferentially loaded when it is turned on. As  
shown in Figure 44, Chiller 1 always receives the warmest system water and  
is preferentially loaded. As previously discussed, chillers on the production  
side of the bypass line (Chillers 2 and 3) are loaded to equal percentages. The  
parallel preferential arrangement works best if Chiller 1 is capable of creating  
the desired system supply water temperature, as it will be sending chilled  
water directly to the distribution system.  
Figure 44. Parallel preferential loading arrangement  
Chiller 3  
Equal  
Percentage  
Loading  
Production  
Distribution  
Chiller 2  
Bypass Line  
Preferential  
Loading  
Chiller 1  
SYS-APM001-EN  
Chiller System Design and Control  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Chilled-Water System Variations  
One caveat when applying this arrangement is that chillers on the production  
side of the bypass line will run more often at low part-load conditions. Older  
chillers or newer chillers with a high cycle point may not have this capability.  
Preferential loading - sidestream arrangement  
Figure 45 shows a simple modification to the traditional decoupled  
arrangement. The sidestream arrangement ensures that the chiller piped in  
the sidestream position still receives the warmest entering-water  
temperature and can fully load it whenever the chiller plant operates.  
Figure 45. Sidestream preferential  
loading arrangement  
This arrangement is unique because it not only allows preferential loading,  
but it also permits the cooling device (chiller, heat exchanger, etc.) in the  
sidestream position to operate at any leaving-water temperature. This  
configuration precools the system-return water for the chillers downstream,  
reduces their loads and energy consumption, and decreases the overall  
operating cost of the chilled-water system.  
Chiller 3  
When cooling devices are located in the return piping of the distribution loop,  
they do not contribute to system demands for flow. They simply reduce the  
temperature of return water to the production loop. While this is  
counterproductive to the principle of striving for the highest possible return  
water temperature, it is often the best way to obtain free cooling, specialized  
heat recovery, or reduce the capital cost of ice storage equipment.  
Chiller 2  
Bypass Line  
Sidestream, decoupled applications are usually most economical when the  
sidestream chiller is smaller than those on the production side of the bypass  
line. Since pumping requirements and energy consumption change with  
modifications to the system arrangement, it is best to use a computerized  
analysis tool to model the economic effects.  
Chiller 1  
The following are different system configurations that can benefit from the  
sidestream application.  
Sidestream position receives the  
warmest return water.  
Sidestream plate-and-frame heat exchanger  
A free-cooling heat exchanger may be capable of chilling water to only 48°F  
[8.9°C] during some periods. Rather than overlook this portion of cooling  
capacity assistance, the heat exchanger does whatever it can to its portion of  
the total return stream. Figure 40 on page 70 shows a possible chilled- and  
condenser-water piping arrangement that allows for simultaneous waterside  
economizer and chiller operation. Chillers operating downstream can reduce  
chilled-water temperature further, allowing simultaneous free cooling and  
mechanical cooling. This configuration increases the hours that the heat  
exchanger may be used. Since this capacity is brought to bear on the  
warmest water in the system, it allows the highest heat exchanger  
effectiveness and has the greatest impact.  
74  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
       
Chilled-Water System Variations  
Sidestream heat recovery  
A similar situation occurs if a heat-recovery chiller is placed in this  
sidestream position (see Figure 46). This chiller may be equipped with a  
Referred to as “distribution sidestream,”  
an alternative location is to apply the  
chiller at the air handler that requires  
reheat. The heat recovery chiller can  
cool either the supply or return chilled  
water. If only a small amount of heating  
is needed, this may be accomplished  
with a water-to-water heat pump.  
heat recovery condenser or it could be a standard, single-condenser chiller  
operating as a heat pump in a heating control mode. The chiller may not be  
capable of cooling water to the system supply temperature. That is  
unimportant with this configuration. Think of the machine as a heater instead  
of a chiller. Its primary function is heating, and cooling is a beneficial by-  
product. The passing return-chilled-water stream appears as an infinite heat  
source to the heat recovery chiller. The chiller only cools its evaporator water  
enough to satisfy the heating demand. This avoids the control predicament  
of deciding how to reject surplus condenser heat when the cooling and  
heating loads of a chiller do not strike a perfect heat balance.  
Figure 46. Heat recovery chiller in sidestream position  
Off  
50.2°F  
[10.1°C]  
Chilled  
Water  
40°F  
[4.4°C]  
Production  
900 gpm [56.8 L/s]  
40°F [4.4°C] 75 gpm  
Bypass Line  
51.2°F  
[10.7°C]  
42.7°F [5.9°C]  
Heat  
Recovery  
Chiller  
Chilled  
Water  
Distribution  
56°F  
[13.3°C]  
825gpm  
[52 L/s]  
300 gpm [18.9 L/s]  
Sidestream with alternative fuels or absorption  
An absorption chiller may be applied in a sidestream location. This allows the  
chiller to be loaded whenever utility rates make it beneficial. It also ensures  
that the absorption water chiller receives the warmest entering-water  
temperature, allowing it to operate more efficiently and produce more  
cooling.  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75  
     
Chilled-Water System Variations  
Sidestream system control  
The flexibility of sidestream applications is increased by the fact that the  
devices are used to pre-cool return water, not to produce the system chilled-  
water temperature. This means that they may be loaded by a different signal.  
In the case of a plate-and-frame heat exchanger, as long as return water is  
being cooled, there is an advantage to using it. A heat-recovery chiller can be  
loaded to produce just the amount of hot water necessary using the  
condenser-water leaving temperature as a signal. If preferential loading is  
used with an absorption chiller, it may be loaded simply by decreasing its  
leaving-water temperature.  
Sidestream configurations may also be used to preferentially load chillers or  
a heat exchanger used in a variable-primary-flow system, or to isolate chillers  
that are incapable of the same flow variations as the rest of the system.  
Preferential loading – series arrangement  
As previously discussed in “Series Chillers” on page 44, preferential loading  
is very simple when chillers are placed in series. If both the upstream and  
downstream chillers are given the system leaving water temperature  
setpoint, the upstream chiller is preferentially loaded and the downstream  
chiller operates whenever the upstream chiller can no longer achieve  
setpoint. If the downstream chiller is given the system setpoint, and the  
upstream chiller is given a warmer setpoint, then the downstream chiller  
loads first. Another method for preferential loading uses compressor RLA to  
determine when to bring on the next chiller.  
Figure 47. Preferential loading - series arrangement  
49°F [9.4°C]  
56°F [13.3°C]  
42°F [5.5°C]  
Chiller 2  
setpoint = 42°F [5.5°C]  
Chiller 1  
setpoint = 42°F [5.5°C]  
Loads  
76  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
 
Chilled-Water System Variations  
Series–Counterflow Application  
Another system configuration that can be very energy efficient incorporates  
the previously described series application, but does so for both the chilled  
water and condenser water. Figure 48 shows such a configuration. The  
chilled- and condenser-water flow directions are opposite, or counter, to one  
another (thus the name, series-counterflow).  
The series–counterflow configuration can  
work with all types of chillers. Duplex™  
large chiller may be built as a Duplex  
machine, and would itself constitute a  
series-counterflow arrangement. The  
evaporator and condenser water circuits  
are common to both halves of the  
Duplex. Increased efficiency comes from  
the separation of the compressors and  
refrigerant circuits.  
Note that the downstream machine, in this case, produces 40°F [4.4°C] chilled  
water, while the upstream machine produces 50°F [10°C] chilled water. The  
downstream machine receives 85°F [29.4°C] condenser water, while the  
upstream machine receives 95°F [35°C] condenser water. Therefore, the  
pumping requirements are only 1.2 gpm/ton on the chilled water side and 1.5  
gpm/ton on the condenser water side—greatly reducing pumping, piping,  
and cooling tower costs. The configuration has the effect of equalizing each  
chillers required lift, as shown in Figure 49.  
Figure 48. Series-counterflow arrangement  
Upstream Chiller  
105 °F [40.6°C]  
Downstream Chiller  
95 °F [35°C]  
50 °F [10°C]  
85 °F [29.4°C]  
40 °F [4.4°C]  
60 °F [15.5°C]  
Figure 49. Equal lift concept  
105°F  
105°F  
[40.6°C]  
[40.6°C]  
95°F  
[35°C]  
Upstream Chiller  
Series-  
Counterflow  
Arrangement  
Single  
Compressor  
Chiller  
Downstream Chiller  
55°F [30.6°C]  
65°F [36.1°C]  
55°F [30.6°C]  
50°F  
[10°C]  
40°F  
40°F  
[4.4°C]  
[4.4°C]  
Series-series counterflow  
Figure 48 shows two Duplex™ chillers in series. Chiller module (combination  
of two Duplex chillers) power savings can be as high as 19% compared with a  
single chiller operating at the same conditions. Because the Duplex chiller is  
actually two refrigerant circuits in series on a common water circuit,  
Figure 48 operates with the efficiency of four chiller circuits in a series-  
counterflow arrangement. But system control is simply for two chillers in  
For more information, refer to the  
ASHRAE Journal article, “Series-Series  
Counterflow for Central Chilled Water  
Plants.”  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
77  
           
Chilled-Water System Variations  
series. The left half of Figure 50 shows a modularized configuration where  
series chiller modules are placed in parallel with each other, so that any  
upstream chillers valves could be “paired” with virtually any downstream  
chiller by opening the appropriate valves. The condenser side in a  
counterflow arrangement is shown in the right half of Figure 50. The  
advantages of this system for large chilled water systems include highest  
efficiency, scalability as the project grows, and high redundancy without a  
significant investment in extra equipment.  
Figure 50. Series arrangement of evaporators and condensers  
98.9°F  
55.0°F  
[12.8°C]  
Evaporators  
Condensers  
[37.2°C]  
Circuit 1 Circuit 2  
Circuit 1 Circuit 2  
Circuit 1 Circuit 2  
Circuit 1 Circuit 2  
Circuit 1 Circuit 2  
Circuit 1 Circuit 2  
3 Chiller Modules  
Circuit 2 Circuit 1  
45.1°F  
[7.3°C]  
91.3°F  
[32.9°C]  
3 Chiller Modules  
Circuit 2 Circuit 1  
Circuit 2 Circuit 1  
Circuit 2 Circuit 1  
Circuit 2 Circuit 1  
Circuit 2 Circuit 1  
85.0°F  
[29.4°C]  
37.0°F  
[2.8°C]  
Unequal Chiller Sizing  
Many designers seem to default to using the same capacity chillers within a  
chilled-water plant.  
There are benefits to using unequally-sized chillers  
to meet the system loads. One is that when a chiller is brought online, so is  
its ancillary equipment, thus increasing system energy consumption. In  
general, the smaller the chiller, the smaller the ancillary equipment. Another  
is being able to ensure that chillers are efficiently loaded. Many times this can  
be accomplished by using chillers that do not have the same capacity.  
Examine the use of 60/40 splits (one chiller at 60 percent of system capacity,  
the other at 40 percent) or 1/3–2/3 splits (one chiller at 1/3 of system capacity  
the other at 2/3). The benefit is that the system load can be more closely  
matched with the total chiller capacity, increasing total system efficiency by  
eliminating the operation of chillers and ancillary equipment for more hours  
of the year. One caveat for variable-primary-flow systems is that if the  
pressure drops are different across the unequally sized chillers, they will load  
even more unequally without the use of pressure-reducing valves that  
require extra pump energy, as shown in Table 15 on page 61.  
78  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Issues and Challenges  
Low T Syndrome  
For many years the “low T syndrome” debate has raged.  
The symptom  
of the problem is that, in large systems, return-water temperature is too low,  
thus not allowing the chillers to fully load. Many system operators simply turn  
on more pumps and chillers to satisfy flow requirements, which wastes energy.  
For primary-secondary systems, some system designers advocate putting a  
check valve in the bypass line—thus putting chilled-water primary and  
secondary pumps in series and varying the flow through chiller evaporators.  
Other designers install primary pumps that are larger than necessary and “over  
pump” chillers at part-load conditions. These solutions are all “band-aids” and  
do not treat the source of the problem. Coad points to the fact that a properly  
operating hydraulic system will work as designed and explains the fallacies in  
the check valve and over pumping approaches. (Refer to the “Check valves”  
sidebar on page 46.) Taylor recommends that a number of mitigating  
procedures be implemented to eliminate the problem. They include:  
Eliminating three-way valves  
Ensuring that airside control is not causing the problem  
Properly maintaining the system, including regular air filter changes, coil  
cleaning, control calibration, and proper setpoints  
Before applying band-aid approaches in an attempt to “fix” symptoms such as  
low T syndrome, ensure that the system is operating properly using some or  
all of the procedures Taylor discusses. In addition to these procedures, simply  
reducing the chilled-water supply temperature will have the effect of raising the  
system return-water temperature in systems using two-way valves.  
Amount of Fluid in the Loop  
Two questions must be answered when determining how much fluid is  
necessary to maintain proper chilled-water-system control:  
How fast can the specific chiller respond to changing conditions?  
How fast can the system respond to changing conditions?  
The amount of fluid the loop requires to operate properly is related to the larger  
of these two answers. Note that both answers describe an amount of time.  
Required Volume = Flow Rate × Loop Time  
Where:  
Required Volume = the amount of fluid in the coil, pipes, evaporator barrel,  
storage tank, etc., in gallons [liters]  
SYS-APM001-EN  
Chiller System Design and Control  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
System Issues and Challenges  
Flow Rate = the system flow rate, in gpm [L/s]  
Loop Time = the time it takes for fluid to leave the chiller, move through  
the system, and return to the chiller, allowing for stable system operation,  
in minutes [seconds]  
Chiller response to changing conditions  
Follow the manufacturers advice for the specific chiller being considered.  
This determines the absolute minimum amount of water the loop requires.  
However, this is the chiller minimum, not the system minimum, as discussed  
in the next section. Many of todays chillers have controls that respond  
quickly to changing conditions. Some chillers can react to a change in return  
water temperature in one minute; other chillers may require five or more  
minutes to react. The response varies, depending on chiller type and design.  
System response to changing conditions  
It is important to understand that even if a chiller can respond to rapidly  
changing conditions, the interaction between the chiller, system pumps, and  
control valves may define the minimum loop time. These components may  
“hunt” if the system conditions change too rapidly. Review these interactions  
to ensure that system control will be stable.  
Example  
A specific chiller requires at least two minutes of water in the loop to operate  
properly. However, after considering the system interaction, its decided that  
a five-minute loop time will work best. The system design flow rate is 960  
gpm [60.6 L/s].  
Required Volume = 960 gpm × 5 minutes = 4,800 gallons  
= 60 L/s × 5 minutes × (60 seconds/1 minute)= 18,180 liters  
If the volume of fluid in the evaporator bundle, piping, and coils is less than  
the required volume, a tank should be added to increase loop volume. For  
optimal stability, the tank should be placed in the return water position and  
be designed to mix the returning-water stream with the water currently in the  
tank. In systems with no bypass, the tank may be placed in the supply chilled-  
water position.  
Alternatively, the designer could:  
increase pipe sizes (increases system volume and reduces pump energy)  
design system for a lower flow rate (lowers required volume and reduces  
pumping energy, especially when same-sized pipes are used)  
80  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Issues and Challenges  
Contingency  
Today, many organizations have contingency plans for critical areas of their  
business. Some deal with natural disasters and others with the loss of power  
in critical areas. However, few have actually taken the time to think about  
what a loss of cooling would mean to their facility. If the cooling system  
failed or was suddenly grossly undersized due to weather, etc., how would  
that affect business? What financial risk would be involved with a loss of  
cooling?  
Cooling contingency planning is intended to minimize the losses a facility  
may incur as a result of a total or partial loss of cooling. It allows a building  
owner to act more quickly by having a plan in place and by proactively  
preparing his or her facility to accept temporary equipment. Although a  
number of facilities are prepared after the construction phase, the  
construction phase provides an easy and cost-effective opportunity to  
prepare a facility and is a logical time to provide water stub outs and  
electrical connections. This helps to keep costs down and reduces the need to  
shut down existing equipment to make necessary building preparations.  
Cooling contingency planning is the process of preparing for a loss of cooling  
while in a non-emergency situation. This allows common sense, rather than  
panic, to prevail during a critical event. The following topics are general and  
broad in scope. They provide a sense of what is involved in the planning  
process. Contingency planning itself is very detailed and situation-specific.  
Minimum capacity required  
It is important to first identify the minimum capacity required. With multiple  
chillers in a facility, it may be acceptable to have less tonnage in an  
emergency situation. For example, a facilitys chiller plant may consist of  
1,800 tons [6,330 kW], but the minimum tonnage required may only be 1,200  
tons [4,220 kW]. Therefore, it is also important to identify the plan of action if  
Chiller 1 fails, if Chiller 2 fails, if Chillers 2 and 3 fail, and so on.  
Type and size of chiller  
The type and size of contingency cooling required by a facility are determined  
by several factors. In turn, the choice of chiller determines how the facility is  
prepared. Examples of parameters that determine the chiller are:  
Electrical requirements  
Ease of installation (air-cooled chillers are easier to set up)  
Location or available space  
Comfort or process cooling  
SYS-APM001-EN  
Chiller System Design and Control  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Issues and Challenges  
Location of equipment  
Location can be a major factor in contingency planning. When selecting the  
location of the temporary equipment, it is important to consider:  
Water and electrical connections location  
Sound sensitive areas in the facility  
Location easily accessible to service staff  
Equipment separated from the public  
Water and electrical connections  
Water connection size requirements  
External stub out locations  
Sufficient power to run the temporary unit  
Possible generator requirement  
Ancillary equipment  
Pumping system requirements  
Temporary hose requirements  
Electrical cable requirements  
This section briefly described some of the items to consider when  
establishing a cooling contingency plan. There may be other considerations,  
depending on the application. For information about failure recovery, see  
page 95.  
Alternative Energy Sources  
Energy source redundancy is receiving increased attention due to rate  
variations and reliability issues brought about by the deregulation of  
electrical utilities across the country. There are two basic approaches to meet  
these issues:  
Provide an alternate source of internally-generated electricity to serve a  
system in the event of general failure or an unacceptably high temporary  
cost of electricity (time-of-day or real-time rates).  
Provide an alternate source of chilled-water producing capability, possibly  
fueled by natural gas, another fossil fuel, or even using low cost electricity  
as an alternative energy source.  
Electricity generation  
The design, construction, and operation of full-capacity, electrical-generation  
systems is well understood. The electrical-generation capacity can be sized to  
allow an entire facility to operate or it can be sized for an emergency  
82  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Issues and Challenges  
situation. Electrical generation can be outsourced to avoid internal  
capitalization.  
A variation of electrical generation uses an engine indirectly- or directly-  
coupled to a chiller. Either variation produces chilled water using an  
alternative fuel such as natural gas or fuel oil. The indirect-coupling method  
allows the chiller to operate using an alternative fuel or electricity from the  
grid. An engine directly-coupled to a chiller can only run using the alternative  
fuel.  
Alternative fuel  
Some designers prefer to employ chillers that use fossil fuels or perhaps  
renewable fuels. Examples are absorption chillers using natural gas, steam,  
hot water, landfill gas, biodiesel, or waste-to-energy boilers. Plants with these  
chillers, discussed in detail elsewhere , allow the owner to take advantage  
of expected fuel rate separations.  
Thermal storage  
Another successfully applied alternative-energy source is thermal storage.  
Chillers make either ice or chilled water during times of lower electricity  
costs. The energy is stored in tanks and then discharged to satisfy cooling  
loads during times of high electrical costs. Other manuals and an Engineers  
Newsletter describe the use of thermal storage in detail.  
Use any of these technologies to provide value to the building owner through  
judicious use of alternative fuels.  
Plant Expansion  
Plant expansion can be performed easily in either a primary–secondary or  
variable-primary-flow system by adding another chiller and pump to the  
system. The two major considerations will be whether the chilled-water  
distribution pipes will be able to handle the flow and how to install the new  
chiller while other chillers are still providing cooling. When the new system  
flow rate complies with good piping practice and the pumps can deliver the  
water, the process works well.  
To maintain chilled-water flow during installation of a new chiller, some  
plants are constructed with piping stubs in place for the new chiller. In this  
way, the new chiller can be installed while the system is still operating, then  
the valves in the stubs can be opened.  
When decoupled systems are used on large campus-type systems, added  
loads are often located some distance away from the original loads. Yet,  
planners like the idea of somehow hooking the new loads to the existing  
system. The “double-ended” system discussed in “Chiller sequencing in a  
double-ended decoupled system” on page 54 is one way of handling this  
requirement.  
SYS-APM001-EN  
Chiller System Design and Control  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Issues and Challenges  
Retrofit Opportunities  
A tremendous retrofit opportunity can be realized if the low-flow concepts  
discussed in the chapter “System Design Options” on page 27 are utilized.  
Building owners may need to increase the capacity of an existing system, for  
example, in response to a building addition. In many of these buildings, the  
condenser water system (piping, pump, and tower) is in good condition, but  
is considered to be too small. By changing from traditional design conditions,  
the existing infrastructure can often be used while still providing additional  
capacity. A detailed discussion of this starts on page 37.  
Applications Outside the Chiller’s Range  
Designers may wish to use chillers to provide cooling for which the flow rate  
or temperature requirements are not within the allowable ranges of a  
particular chiller, even though the chiller has adequate capacity. This often  
occurs with manufacturing processes. Lets look at two examples showing  
system designs that can satisfy the desired conditions.  
Flow rate out of range  
A plastic injection molding process requires 80 gpm [5.1 L/s] of 50°F [10°C]  
water and returns that water at 60°F [15.6°C]. The selected chiller can operate  
at these temperatures, but has a minimum flow rate of 120 gpm [7.6 L/s]. The  
following system in Figure 51 can satisfy the process. Decoupling the chiller  
from the process load allows the water flow to be different, ensuring that the  
flow through the chiller is within acceptable limits. With a single chiller  
system, one pump and a three-way valve gives the same results.  
Figure 51. Flow rate out of range for equipment  
50°F [10°C]  
80 gpm [5.1 L/s]  
50°F [10°C]  
120 gpm [7.6 L/s]  
Constant Volume Pump  
Bypass  
Pipe  
Process  
Load  
50°F [10°C]  
40 gpm [2.3 L/s]  
Chiller  
56.7°F [13.7°C]  
120 gpm [7.6 L/s]  
60°F [15.6°C]  
80 gpm [5.1 L/s]  
Constant Volume Pump  
120 gpm [7.6 L/s]  
84  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
         
System Issues and Challenges  
Temperatures out of range  
A laboratory load requires 120 gpm [7.6 L/s] of water entering the process at  
85°F [29.4°C] and returning at 95°F [35°C]. The accuracy required is more  
precise than the cooling tower can provide. The selected chiller has adequate  
capacity, but a maximum leaving-chilled-water temperature of 60°F [15.6°C].  
Using a pair of bypass pipes allows the mixing valve to supply the proper  
temperature to the process load and maintains acceptable water flow rates  
and temperatures through the chiller. In the example shown in Figure 52, the  
chiller and process flow rates are equal, although this is not a requirement.  
For example, if the chiller had a higher flow rate, more water would bypass  
and mix with the warm return water.  
Figure 52. Temperatures out of range for equipment  
85°F [29.4°C]  
120 gpm [7.6 L/s]  
60°F [15.6°C]  
35 gpm [2.2 L/s]  
60°F [15.6°C]  
120 gpm  
[7.6 L/s]  
Mixing  
Valve  
Constant Volume  
Pump  
60°F [15.6°C]  
85 gpm  
[5.4 L/s]  
Process  
Load  
95°F [35°C]  
85 gpm [5.4 L/s]  
Bypass  
Pipes  
Chiller  
70°F [21.1°C]  
120 gpm  
[7.6 L/s]  
95°F [35°C]  
35 gpm [2 .2 L/s]  
95°F [35°C]  
120 gpm [7.6 L/s]  
Constant Volume  
Pump  
120gpm [7.6 L/s]  
Precise temperature control  
An example of a process application layout where the required temperature  
control tolerance is more precise than the chiller controls allow is shown in  
For example, when Chiller 2 is turned on, it takes a certain amount of time to  
reach its supply-temperature setpoint. The dedicated control valve remains  
closed and water is bypassed until Chiller 2 reaches its setpoint, which keeps  
the water temperature supplied to the process within tolerance. When Chiller  
2 reaches its setpoint, the control valve opens.  
This design requires a different chiller-sequencing strategy than the standard  
decoupled system. Water must not be allowed to bypass from the return side  
to the supply side, since this will cause the temperature of the water supplied  
to the process to vary outside the tolerance. Set the system controls to turn  
on Chiller 2 before deficit flow occurs.  
SYS-APM001-EN  
Chiller System Design and Control  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
System Issues and Challenges  
Figure 53. Precise temperature control, multiple chillers  
Control  
Valves  
Variable-Speed  
Pump  
Process  
Load  
Bypass  
Chiller  
1
Chiller  
2
86  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Controls  
Chilled-Water System Control  
Chilled water reset—raising and lowering  
Many chilled-water plants use chilled water reset, that is, the chillers leaving-  
water temperature setpoint, in an effort to reduce chiller energy consumption.  
This can either be accomplished by the chiller controller or by the system  
controller.  
Raising the chilled-water temperature reduces chiller energy consumption. In a  
constant-volume pumping system, this may reduce overall system energy  
consumption as long as humidity control is not lost. Humidity control may be  
lost if, as chilled-water temperature is increased, the air temperature leaving the  
coil increases to a point where it no longer performs adequate  
dehumidification.  
In a variable-volume pumping system, however, raising the chilled-water  
temperature increases pump energy, often substantially, and typically increases  
total system energy. Before considering increased chilled-water temperature,  
the system operator should calculate the increased pumping energy and  
compare it with the chiller energy savings. It should be noted that ASHRAE/  
IESNA Standard 90.1–2007 requires chilled-water reset for constant-volume  
systems—with some exceptions—but exempts variable-volume systems from  
this requirement for the reasons discussed.  
An often overlooked method of decreasing system energy consumption is to  
reduce the chilled-water temperature, thereby decreasing pumping energy but  
increasing chiller energy. This strategy is possible with adequate chiller capacity  
and lift capability. Reducing chilled-water temperature may also improve  
dehumidification in the building. Another result of reducing the chilled-water  
temperature is increased chiller capacity during times when the condenser  
water temperature is cooler than design. This allows more time before another  
chiller and its ancillary equipment are started.  
Be aware that any change in chilled-water setpoint requires changes to be made  
to the system chiller-sequencing algorithms to ensure that system capacity is  
met. This added complication may not be warranted.  
Chilled-water pump control  
In constant flow systems, the pumps are either on or off, providing relatively  
constant flow when turned on. In practice, some flow variation will occur as  
system pressure drop changes. In a variable-flow system, pump control is most  
often performed by maintaining a pressure differential at a selected point in the  
system. For example, a variable-speed drive will increase its speed if the sensed  
pressure differential is too low, or slow down if the pressure differential is too  
SYS-APM001-EN  
Chiller System Design and Control  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
System Controls  
high. The control point is selected to minimize over-pressurizing the system  
and to assure adequate flow at all critical loads.  
Critical valve reset (pump pressure optimization)  
Often, pumps are controlled to maintain a constant-pressure differential at a  
remote coil. Unless this coil serves the zone requiring the most pressure (the  
critical zone), the pump provides more pressure than necessary and  
consumes more power than necessary. Systems that have integrated airside  
and chiller plant control systems and contain valves with direct digital  
controls present an opportunity for further pump operating-cost reduction. If  
a system is monitored to determine the critical valve at each point in time, the  
pumps operating pressure can be reset so that the critical zones control  
valve is nearly wide open.  
Integrated control allows a system-level controller to determine the critical  
zone and reset the pumps setpoint dynamically, therefore reducing pump  
operating costs.  
Air-handler controllers know the position of their individual valves, which  
modulate to maintain the required water flow through the coil. The building  
automation system continually monitors the valve controllers, looking for the  
most open valve. The controller resets the pump setpoint so that at least one  
valve, the one requiring the highest inlet pressure, is nearly wide open. The  
result is that the pump generates only enough pressure to get the required  
water flow through this “critical” valve, thus saving pumping energy.  
Addendum ak to ASHRAE 90.1-2007 now requires pump pressure for many  
chilled water systems. It will become part of 90.1-2010.  
Number of chillers to operate  
Some practitioners believe that operating more chillers at the same time  
permits each chiller to operate more efficiently. From a system perspective,  
this is rarely true. The chillers are not the sole energy consumers in the  
plant—activating a chiller also activates the condenser water pump, perhaps  
a chilled water pump, and tower fans. One analysis showed that if all  
operating chillers are equipped with variable frequency drives (VFDs), the  
only time it makes sense to run more chillers than necessary is if the  
condenser water drops below 65°F. Without VFDs on the chillers, the system  
never used less energy with the extra chiller operating.  
88  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Controls  
Table 17. VFDs and centrifugal chillers performance at 90% load  
ECWT  
85°F  
80°F  
75°F  
70°F  
65°F  
2 Chillers*  
306.4  
1 Chiller  
268.0  
Difference  
-38.4  
268.0  
238.0  
-30.0  
230.8  
210.6  
-20.2  
195.2  
185.7  
-9.5  
160.3  
164.3  
+4.3  
Note: Data shows only chiller power.  
* Load equally divided.  
If the chiller and tower capabilities are conducive to this strategy, the location  
and load profile determine if, when, and for how long the right conditions  
might occur. Determine the optimum control sequence for the entire plant by  
performing a detailed energy analysis of each component. Base the analysis  
on realistic load profiles and ambient conditions, and account for the energy  
used by all ancillary equipment.  
For VPF systems, there will likely not be enough system flow to allow more  
chillers than necessary to operate without requiring bypass to stay above the  
chillers’ minimum flows.  
Condenser-Water System Control  
Minimum refrigerant pressure differential  
Every chiller requires a certain refrigerant pressure differential between the  
evaporator and condenser in order to operate. The chiller must develop its  
pressure differential within a manufacturer-specified time or its controls will  
shut it off. During some start-up conditions, this pressure differential may be  
hard to produce within the time limitation.  
An example of such a condition is an office building that has been  
unoccupied during a cool, clear, fall weekend. The tower sump water is at  
40°F [4.4°C]. Monday is sunny and warm, which requires a chiller to be turned  
on. Since the chiller is lightly loaded and the tower sump is large, the  
pressure differential cannot be reached before the chiller turns off. If the  
condenser flow rate for a given chiller can be reduced, this scenario is less  
likely to occur. The lower flow rate increases the leaving condenser-water  
temperature, which increases the condenser-refrigerant temperature and  
refrigerant pressure.  
SYS-APM001-EN  
Chiller System Design and Control  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
System Controls  
The flow reduction options include:  
Cooling tower bypass  
Chiller bypass  
One or two throttling valves in the condenser-water pipe with the pump  
riding its curve  
A variable-speed condenser water pump  
After the minimum-pressure differential is reached, the flow may be  
increased as long as that minimum-pressure difference is maintained. Some  
designers and operators become concerned with possible fouling of  
condenser-water tubes during these start-up conditions. There is little to fear  
due to the short duration of reduced flow operation and the limited  
occurrences. The advantages and disadvantages of these options are  
discussed in a variety of publications.  
Condenser-water temperature control  
Cooling-tower-fan control  
Cooling towers operate to produce a desired sump water temperature. As the  
heat rejection load and ambient wet-bulb temperature change, the cooling  
tower fans must move more or less air to produce the desired water  
temperature.  
Cycling a single fan. Cycling a single fan on and off is one method to  
maintain rough water temperature control. Since airflow changes greatly  
between fan speeds, so does heat rejection. Temperature swings of 7°F to  
10°F [3.9°C to 5.6°C] are not uncommon. Some chillers, especially older  
chillers with pneumatic controls, may operate poorly in response to these  
changing temperatures. Make sure that the fan does not cycle too often and  
damage the motor, drive, or fan assembly.  
Two-speed fans. The installation of two-speed cooling tower fans is an  
option that reduces temperature swings. Typically, the low fan speed is  
between 50 and 70 percent of full speed. Since the heat rejection changes  
roughly in proportion with the fan speed, the temperature swing will be only  
50 to 75 percent of cycling a single fan. Again, take care not to cycle too often  
between speeds—or the gear box may incur excessive wear and fail. A  
distinct advantage of two-speed fans is that at low speed, the fan power is  
greatly reduced. Since the fan power varies with the cube of the speed  
(approximately) the power at half speed is about 15 percent of full speed.  
“Pony” motors. Another option offered by cooling-tower manufacturers is to  
have two separate motors available to drive the fan. The smaller motor is  
referred to as a “pony” motor. It operates at two-thirds of the full speed and  
uses about 30 percent of the full speed power. While controlling the tower, it  
is important to minimize cycling between speeds.  
Variable-speed drives. Because the cost of variable-speed drives for cooling-  
tower fans has decreased, variable-speed drives have become more  
90  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
System Controls  
prevalent than either two-speed fans or pony motors. Using variable-speed  
drives on cooling-tower fans offers two distinct benefits. First, the tower-  
water-temperature control is extremely good. Second, the fan power varies  
with the cube of the speed, so there is great potential for energy savings.  
Variable-speed drives also allow the fan speed to be changed without fear of  
gear box or motor wear. They may also offer acoustical advantages by  
significantly lowering sound power at reduced speeds. Variable-speed drives  
are also applicable to existing chilled-water systems.  
Chiller–tower energy balance  
The subject of condenser-water temperature control has been studied by a  
number of people. In recent years, Braun and Didderich ; Hydeman,  
Gillespie, and Kammerud ; and Schwedler have all independently noted  
that balancing chiller and cooling-tower energy is important. Hydeman, et al.,  
showed that at various loads and ambient conditions, the optimal condenser-  
water temperature for a specific chilled-water system depends on both chiller  
load and ambient conditions (see Figure 54). All the studies showed that  
during many points of operation, the optimal condition is not the lowest  
water temperature the cooling tower can produce. It is important for the  
system designer and operator to examine the use of system-level controls to  
set the tower-sump temperature setpoint to reduce the sum of chiller-plus-  
tower energy. This optimal chiller-tower control can be automated by a  
chiller-plant management system.  
Figure 54. Chiller-tower energy consumption  
1,650 tons [5,803 kw]  
65°F [18.3°C] wet bulb  
1,160 tons [4,080 kw]  
59°F [15°C] wet bulb  
730 tons [2,567 kw]  
54°F [12.2°C] wet bulb  
Coldest condenser water that the  
tower can produce at this load and  
wet-bulb temperature  
Highest cooling capacity  
available at this condenser-  
water temperature  
Figure 54 from Hydeman, et al., used with permission.  
SYS-APM001-EN  
Chiller System Design and Control  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
System Controls  
Variable condenser water flow  
Chiller-tower-pump balance  
There are times when a system designer may choose to vary the condenser  
water flow in addition to, or instead of, the cooling-tower fan speed. This may  
be beneficial in systems with high pumping power. If a variable-speed drive  
is installed, the flow may be reduced and the pump power can be reduced  
substantially—approximately with the cube of the speed. Attempting to vary  
both the pump and the tower fan speeds is complex and requires adequate  
time for design and implementation.  
Keep the flow through the condenser above the minimum allowable flow rate  
for the chillers condenser. The operator should regularly log the condenser  
approach temperature (the temperature difference between the condensers  
refrigerant temperature and the condenser-water leaving temperature) to  
ensure that the tubes are not becoming fouled. The approach temperature  
may be monitored using a chiller plant management system.  
Tower and/or tower nozzle design can affect the allowable condenser-water  
flow. If the flow drops below the manufacturers specified limit, the water is  
no longer evenly distributed over the tower fill. This results in a decrease in  
cooling-tower heat-transfer effectiveness. In extreme cases, it can also result  
in water freezing in the cooling tower. If variable tower flow is a  
consideration, contact the cooling-tower manufacturer to determine the flow  
limit and possibly choose nozzles or cooling-tower configurations that can  
handle variable-water flow.  
Most water-cooled, chilled-water systems use a constant condenser water  
flow rate. However, the condenser water flow rate can be varied between the  
minimum and maximum flows allowed for the specific chiller (refer to  
product catalog or selection program).  
But reducing the condenser water flow rate affects the power consumption of  
the pumps, chiller, and cooling tower, as described below:  
Condenser water pump: Pump power is reduced because both the flow  
rate and the pressure drop through the piping and condenser are  
reduced.  
Chiller: Compressor power is increased because, as the flow rate  
decreases, the temperature of the water leaving the condenser increases.  
At a given load, this increases the compressor lift and, therefore, its  
energy use.  
Cooling tower: As explained above, the temperature of the water  
returning to the cooling tower is warmer. This increases the effectiveness  
of the heat exchanger. But the water flow rate is decreased, which can  
either improve or reduce the effectiveness of the cooling tower. So, for a  
given load, reducing the flow rate through the cooling tower sometimes  
decreases and sometimes increases energy use.  
92  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Controls  
These three energy consumers must be balanced to minimize overall energy  
use. This makes varying condenser water flow complex, but the strategy  
below has been implemented on projects.  
Control of the condenser water pumps and cooling tower fans is based on  
chiller load, which is calculated using the chilled-water flow rate and  
temperature differential. When the chiller load is less than 80 percent, the  
control system varies the speeds of both the cooling tower fan and  
condenser-water pump in proportion to chiller load, until the minimum  
allowable condenser-water flow rate is reached. As chiller load decreases  
further, the condenser-water pump remains at the minimum speed, while the  
cooling tower fan speed continues to decrease.  
Figure 55. Effect of chiller load on water pumps and cooling tower fans  
100  
100  
80  
80  
pump speed  
60  
40  
20  
60  
40  
fan speed  
20  
0
chiller load  
10 20 30 40 50 60 70 80 90 100  
chiller load, %  
The minimum allowable condenser water flow rate is the highest of the  
following:  
The June 2006 ASHRAE Journal article,  
“Prescription for Chiller Plants,(Baker,  
Roe, and Schwedler) details a chilled-  
water plant with variable-speed  
condenser water pumps.  
Minimum water flow rate required through the chiller condenser (consult  
chiller manufacturer)  
Minimum water flow rate required through the cooling tower fill (consult  
cooling tower manufacturer)  
Minimum water flow rate required to properly cool the pump motor  
(consult pump manufacturer)  
Minimum water flow rate that produces enough pressure to overcome  
the static lift from the base of the cooling tower to the top of the tower  
Decoupled condenser-water system  
To overcome possible problems with variable-water flow across a cooling  
tower, some designers decouple the condenser-water system as shown in  
Figure 56. This arrangement allows energy optimization through a reduction  
of pumping power without excessively complicating the system. Because  
cooling towers work best with full water flow over the transfer media, a  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
93  
 
System Controls  
separate wetting (recirculation) pump provides a constant flow of water  
through the tower. This is a low-energy pump, as very little lift is required.  
Dedicated, variable-flow condenser pumps (CDWP-1 and CDWP-2) permit a  
reduction in the pumping energy whenever the temperature of condenser  
water results in an unproductive reduction of condenser refrigerant pressure.  
While the number of dedicated pumps may seem complicated at first,  
remember the number of valves and controls that are eliminated.  
Figure 56. Decoupled condenser-water system  
Cooling Tower Fan (Inverter)  
Cooling  
Tower  
Water Sump  
Tower Water  
Recirculation  
Pump  
CDWP-2  
(Inverter)  
Chiller 2  
CDWP-1  
(Inverter)  
Chiller 1  
94  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
System Controls  
Failure Recovery  
With all the varied approaches available to potential customers, it sometimes  
seems that the main idea gets lost. People purchase chilled-water plants to  
reliably produce chilled water to satisfy another need, such as comfort or  
process cooling. Therefore, when the plant operates there must be a process  
in place to recover from the failure of a chilled- or condenser-water pump,  
cooling tower, or chiller. Failure recovery should be integral to the chilled-  
water plant control system. Refer to Figure 57. If the control sequence tries to  
start Chiller 2 and its pump, but the pump has an electrical malfunction, the  
sequence should immediately lock out Chiller 2 and its pump. The control  
system should then automatically attempt to start Chiller 3 and its pump. At  
the same time, the control system should send a pump malfunction alarm to  
the system operator.  
Figure 57. Failure recovery  
Chiller 3 Start  
Chiller 2 Unavailable  
Chiller 1 Running  
Bypass Line  
Return  
Supply  
SYS-APM001-EN  
Chiller System Design and Control  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Conclusion  
It is vital to have a clear understanding of chilled-water system concepts and  
their application. There is nothing particularly complex about the principles  
involved. Instead, system design is simply a matter of exercising a few key rules  
of applied physics.  
A myriad of choices are available for the design and operation of chilled-water  
systems. These choices include flow rates, temperatures, system  
configurations, and control options. After determining the needs and wants of  
the building owner and chiller plant operator, judicious use of these choices  
allows designers to provide solutions that add real value. When applying the  
principles in this manual, it is important to remember the following rules:  
Rule 1. Strive for simplicity. Simple does not always mean using the fewest  
components. Simplicity is usually elegant in its ability to be universally  
understood.  
Rule 2. If the system designer can explain how a design works, there is a good  
chance that the system will function well. If the designer can’t explain how the  
design works, there is no chance that the system will operate efficiently.  
Rule 3. If the system operator understands the designers explanation of how  
the system works, there is a good chance that the system will work. If the  
system operator doesn’t understand the explanation, there is no chance that  
the system will operate efficiently.  
96  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
 
Glossary  
ASHRAE. American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers (www.ashrae.org).  
building automation system (BAS). A centralized control and monitoring  
system for a building.  
chilled water. Also known as leaving-chilled-water or leaving-evaporator-water;  
chilled water is the cold water produced by the chiller (flowing through the tube  
bundle in the evaporator) and pumped to the air handler coils throughout the  
building. Within the evaporator, refrigerant surrounds the tube bundle and  
accepts heat from the return chilled water.  
chiller. An air-conditioning system that circulates chilled water to various  
cooling coils in an installation.  
coil. An evaporator or condenser made up of tubing either with or without  
extended surfaces (fins).  
condenser. The region of the chiller where refrigerant vapor is converted to  
liquid so that the temperature and pressure can be decreased as the refrigerant  
goes into the evaporator.  
condenser relief. The heat sink temperature difference from design outdoor air  
temperature for air-cooled equipment and design cooling water temperature for  
water-cooled equipment. This term is used to quantify the effect of condensing  
temperature on the power consumed by cooling equipment.  
condenser water, leaving. See cooling water.  
cooling tower water. See cooling water.  
cooling water. Also known as tower water, leaving-cooling water, leaving-  
condenser water, entering-absorber water, condenser-absorber water, entering-  
cooling water, or cooling tower water; obtained from the source (tower, river,  
pond, etc.) to which heat is rejected, flows through the tubes that run through  
the absorber and the condenser, and is returned to the source.  
In electrically driven chillers, the cooling water picks up heat only from the  
condenser. In an absorption chiller, the cooling water also has to pick up heat  
from the absorber. The water typically flows from the source at 85°F [29.4C],  
first to the absorber and then to the condenser (series flow). Associated water  
temperatures are referred to as entering-absorber-water temperature (or  
leaving-tower-water temperature) and leaving-condenser-water temperature (or  
entering-tower-water temperature).  
SYS-APM001-EN  
Chiller System Design and Control  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Glossary  
COP. Coefficient of Performance; cooling effect divided by heat input  
(dimensionless); the reciprocal of efficiency.  
direct digital control. Programming used by building control systems to  
control variable outputs, such as valves or actuators. In the HVAC industry,  
DDC means direct digital control by a microprocessor controller with no  
intermediate device.  
evaporator. The region in the chiller where the system chilled water is  
continuously cooled down by flashing the refrigerant to vapor in a deep  
vacuum as it picks up heat from the returning system water.  
fouling. Deposits of foreign material in the water side of tubing in  
refrigeration condensers or chillers that affect the transfer of heat.  
heat exchanger. A device used to transfer heat between two physically  
separated fluids.  
heat transfer. The movement of heat from one body or substance to another.  
The three methods of heat transfer are conduction, convection, and radiation.  
load. Any one of several output devices that are to be controlled by a  
building management panel.  
mechanical-compression refrigeration cycle. The electrically driven chiller  
makes use of an electric motor, driving a compressor to produce chilled  
water for cooling. It does this via a mechanical process that uses a refrigerant  
for a working fluid. Inside the vessel are pressure and temperature  
differentials, where heat is absorbed at a low temperature and then rejected  
at a higher temperature.  
psychrometric chart. A chart that shows the relationship between the  
temperature, pressure, and moisture content of the air.  
psychrometric measurement. The measurement of temperature, pressure,  
and humidity of air using a psychrometric chart.  
pumps (system)  
chilled water. Circulates the chilled water through the evaporator  
section of the chiller and then through the building coils.  
cooling water. Circulates the cooling water from the source through  
the chiller, condenser, and back to the source.  
shell-and-tube. A designation for a type of heat exchangers consisting of a  
tube bundle within a shell or casing. Often used in chiller condensers and  
evaporators.  
shell-and-tube flooded evaporators. Evaporators that use water flow through  
tubes built into a cylindrical evaporator with refrigerant on the outside of the  
tubes.  
98  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Glossary  
temperature, ambient. The temperature of the air surrounding the object  
under consideration.  
temperature, wet-bulb. A measure of the degree of moisture in the air. It is  
the temperature of evaporation for an air sample, measured with a  
thermometer that has its bulb covered by a moistened wick.  
tower water. See cooling water.  
three-way valve. A flow-control valve with three fluid-flow openings. It  
controls constant flow through or around the load.  
two-way valve. A flow-control valve with two fluid-flow openings.  
valve, throttling. A small valve used primarily in gauge lines to shut off the  
line between readings, and to throttle the line to prevent fluctuations during  
readings.  
SYS-APM001-EN  
Chiller System Design and Control  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
References  
1
2
3
Webb, R.L. and W. Li. “Fouling in Enhanced Tubes Using Cooling Tower  
Water, Part I: Long-Term Fouling Data.International Journal of Heat and  
Mass Transfer 43, no. 19 (October 2000): 3567-3578.  
Schwedler, M. and B. Bradley. An Idea for Chilled-Water Plants Whose  
Time Has Come...Variable-Primary-Flow Systems,Engineers Newsletter  
28, no. 3 (1999), Trane.  
American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers. ASHRAE HVAC Systems and Equipment Handbook, Chapter  
12, “Hydronic Heating and Cooling System Design” and Chapter 39,  
“Cooling Towers.” ASHRAE, 2008.  
4
American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers. ASHRAE Standard 147-2002: Reducing the Release of  
Halogenated Refrigerants from Refrigeration and Air-Conditioning  
Equipment and Systems. ASHRAE, 2002.  
5
6
7
Air-Conditioning, Heating, and Refrigeration Institute. ARI Standard 550/  
590–2003: Performance Rating of Water Chilling Packages Using the  
Vapor Compression Cycle. AHRI, 2003.  
American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers. ASHRAE Guideline 22: Instrumentation for Monitoring Central  
Chilled-Water Plant Efficiency. ASHRAE, 2008.  
American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers. ASHRAE Standard 140-2007: Standard Method of Test for the  
Evaluation of Building Energy Analysis Computer Programs. ASHRAE,  
2007.  
8
9
American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers. ASHRAE GreenGuide: The Design, Construction, and  
Operation of Sustainable Buildings. 2nd ed. ASHRAE, 2006.  
Air-Conditioning, Heating, and Refrigeration Institute. ARI Standard 560–  
1992: Absorption Water Chiller and Water Heating Package. AHRI, 1992.  
10 Kelly, D.W. and T. Chan. “Optimizing Chilled-Water Plants.Heating/  
Piping/Air Conditioning (January 1999): 145-7.  
11 Schwedler, M. and A. Nordeen. “Low Flow Works for Absorbers Too!”  
Contracting Business (November 1998): 108-112.  
12 Demirchian, G.H. and M.A. Maragareci. “The Benefits of Higher  
Condenser-Water T at Logan International Airport Central Chilled-Water  
Plant.IDEA 88th Annual Conference Proceedings (1997): 291–300.  
13 Eley, C. “Energy Analysis–Replacement of Chillers for Buildings 43, 47,  
and 48.” Eley Associates, CA, April 1997.  
14 Coad, W.J. A Fundamental Perspective on Chilled-Water Systems,”  
Heating/Piping/Air Conditioning (August 1998): 59-66.  
100  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
                             
References  
15 Bahnfleth, W. and E. Peyer. “Comparative Analysis of Variable and  
Constant Primary-Flow Chilled-Water-Plant Performance.HPAC  
Engineering (April 2001).  
16 Houghton, D. “Know Your Flow—A Market Survey of Liquid Flow Meters.”  
E SOURCE Tech Update TU-96-3 (March 1996).  
17 Taylor, S.T. Primary-Only vs. Primary-Secondary Variable Flow Systems.”  
ASHRAE Journal (February 2002).  
18 Kreutzmann, J. “Campus Cooling: Retrofitting Systems.HPAC  
Engineering (July 2002).  
19 Groenke, S. and M. Schwedler. "Series-Series Counterflow for Central  
Chilled Water Plants." ASHRAE Journal 44, no. 6 (June 2002): 23-29.  
20 American Society of Heating, Refrigerating, and Air-Conditioning  
Engineers and the Illuminating Engineering Society of North America.  
ASHRAE/IESNA Standard 90.1–2007 : Energy Standard for Buildings  
Except Low-Rise Residential Buildings. ASHRAE and IESNA, 2007.  
21 Trane Applications Engineering Group. Waterside Heat Recovery in HVAC  
Systems. Applications Engineering Manual. Trane, 2003 (SYS-APM005-  
EN).  
22 Schwedler, M. “Waterside Heat Recovery.Engineers Newsletter 36, no. 1  
(February 2007), Trane. (ADM-APN023-EN)  
23 Hanson, S. “Free Cooling Using Water Economizers.Engineers  
Newsletter 37, no. 3 (September 2008), Trane. (ADM-APM029-EN)  
24 Landman, W. “Two Good Old Ideas Combine to Form One New Great  
Idea.Engineers Newsletter 20, no. 1 (1991), Trane.  
25 Eppelheimer, D. and B. Bradley. “Chilled-Water Plants and…Asymmetry  
as a Basis of Design.Engineers Newsletter 28, no. 4, (October 1999),  
Trane.  
26 Landman, W. and B. Bradley. “Off-Design Chiller Performance.Engineers  
Newsletter 25, no. 5 (December 1996), Trane.  
27 Avery, G. “Controlling Chillers in Variable-Flow System.ASHRAE Journal  
(February 1998): 42-45.  
28 Kirsner, W. “The Demise of the Primary-Secondary Pumping Paradigm for  
Chilled-Water Plant Design.Heating/Piping/Air Conditioning (November  
1996).  
29 Taylor, S.T. Degrading Delta-T in New and Existing Chilled Water  
Plants.Cool $ense National Forum on Integrated Chiller Retrofits,  
Lawrence Berkeley National Laboratory and Pacific Gas & Electric  
(September 1997).  
30 Schwedler, M. and D. Brunsvold. Absorption Chiller System Design.  
Applications Engineering Manual. Trane, 1999. (SYS-AM-13)  
31 Trane Applications Engineering Group. “Thermal Storage –  
Understanding Its Economics.” Ice Storage Systems, Engineered Systems  
Clinics. Trane, 1991. (ISS-CLC- 1)  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
101  
                                 
References  
32 Trane Applications Engineering Group. “Thermal Storage –  
Understanding the Choices.” Ice Storage Systems, Engineered Systems  
Clinics. Trane, 1991. ( ISS-CLC-2)  
33 Trane Applications Engineering Group. “Thermal Storage –  
Understanding System Design.” Ice Storage Systems, Engineered  
Systems Clinics. Trane, 1991. (ISS-CLC- 3)  
34 Trane Applications Engineering Group. “Thermal Storage–Understanding  
Control Strategies.” Ice Storage Systems, Engineered Systems Clinics.  
Trane, 1991. (ISS-CLC-4)  
35 Solberg, P. Ice Storage as Part of a LEED® Building Design.Engineers  
Newsletter 36, no. 3. (September 2007), Trane. (ADM-APN025-EN)  
36 Trane CenTraVac Group. “Condenser-Water Temperature Control for  
CenTraVac™ Centrifugal Chiller Systems.Engineering Bulletin. Trane,  
May 1997. (CTV-PRB006-EN)  
37 Trane Engineers. “Water-Cooled Series R Chiller - Models RTHB & RTHC  
Condenser Water Control.Engineering Bulletin. Trane, August 1999.  
(RLC-EB-4)  
38 Braun, J.E. and G.T. Diderrich. “Near Optimal Control of Cooling Towers  
for Chilled-Water Systems.ASHRAE Transactions 96, no. 2 (1990): 806-13.  
39 Hydeman, M., K. Gillespie, and R. Kammerud. “CoolTools Project: A  
Toolkit to Improve Evaluation and Operation of Chilled Water Plants.Cool  
$ense National Forum on Integrated Chiller Retrofits. Lawrence Berkeley  
National Laboratory and Pacific Gas & Electric (September 1997).  
40 Schwedler, M., and B. Bradley. “Tower Water Temperature–Control It  
How???” Engineers Newsletter 24, no. 1 (1995), Trane.  
102  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYS-APM001-EN  
                 
Index  
A
absorption refrigeration 98  
ASHRAE  
GreenGuide 27, 29, 33  
Guideline 22 25  
B
bypass flow control 63  
bypass locations 62  
bypass valve 8  
C
campus pumping arrangements 49  
centrifugal chiller capacity control 16  
check valves 46  
chilled water  
flow rate 3, 27, 29  
temperature 3, 27  
chilled-water distribution system 10  
chilled-water pump 10  
chilled-water pump control 87  
chilled-water reset 87  
chilled-water systems  
configurations 42  
control 87  
large 22  
mid-sized 21  
overview 1  
parallel arrangement 42  
performance testing 24  
plant expansion 83  
series arrangement 44  
series-counterflow 77  
series-series counterflow 77  
small 18  
variations 70  
water temperatures 28  
chiller range  
applications outside 84  
chillers  
centrifugal 16  
number of 20  
overview of 1  
unequal sizing 78  
condenser 97  
air-cooled 5  
air-cooled vs water-cooled 5  
flow rate 4, 29  
free cooling or water economizer 70  
water temperature 4, 29  
water-cooled 4  
condenser-water pumping arrangements 14  
condenser-water system 13  
condenser-water system control 89  
condenser-water temperature control 90  
condenser-water temperatures 29  
condensing method 19  
configurations  
parallel or series 20  
constant flow 19  
constant-flow system 12  
contingency plan 81  
control 15  
flow-based 51  
SYS-APM001-EN  
Chiller System Design and Control  
Download from Www.Somanuals.com. All Manuals Search And Download.  
103  
 
Index  
controls  
chilled-water system control 87  
condenser-water system control 89  
direct-digital 24  
managing control complexity 21  
programmable-logic 24  
cooling tower 13, 97  
cooling water 97  
cost implications 38  
D
dampers 9  
decoupled systems 45  
condenser water system 93  
double-ended 52  
distribution  
piping 11  
pumps 48  
district cooling 22  
double-ended decoupled systems 52  
E
energy  
alternative sources 82  
equalized loading 21  
evaporator 98  
effect of chilled-water flow rate 3  
effect of chilled-water temperature 3  
overview 2  
F
face-and-bypass dampers 9  
failure recovery 95  
fans  
single 90  
two-speed 90  
flow  
constant 19  
standard rating flow conditions 29  
variable 19  
flow measurement 62  
flow rates 27, 29  
chilled water 3  
guidance 27  
low flow 34  
misconceptions 39  
selecting 30  
flow-based control 51  
fluid in the loop 79  
free cooling 70, 71  
H
heat exchanger 98  
heat recovery 70  
hydraulic decoupling 45  
L
lake water 72  
large chilled-water systems 22  
load  
part-load operation 20  
loading  
equalized 21  
preferential 21, 73  
104  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
loads  
overview 7  
low T syndrome 79  
low flow  
cooling-tower options 34  
misconceptions 39  
M
manifolded pumps 11, 14  
mechanical-compression refrigeration 98  
mid-sized chilled-water systems 21  
minimum pressure differential 89  
monitoring  
system efficiency 25  
motors  
pony 90  
P
parallel arrangement 73  
parallel chillers 42  
parallel configuration 20  
part-load system operation 20  
performance testing 24  
pipe size 23  
piping  
distribution 11  
plant expansion 83  
plate-and-frame heat exchanger 70  
pony motors 90  
preferential loading 21, 73  
series arrangement 76  
pressure differential 89  
primary-secondary systems 13, 45  
production pumps 47  
pumping arrangements 12, 14, 49  
campus 49  
common 49  
tertiary 49  
pumps 98  
arrangements 12, 14, 49  
chilled water 10  
control 87  
distribution 48  
manifolded 11, 14  
production 47  
variable-speed 9  
R
refrigerant migration 71  
retrofit opportunities 37, 84  
river water 72  
S
sequencing options 21  
series arrangement 76  
series chillers 44  
series configuration 20  
series-counterflow application 77  
series-series counterflow 77  
sidestream arrangement 74  
sidestream heat recovery 75  
sidestream plate-and-frame heat exchanger 74  
sizing  
unequal chiller sizing 78  
small chilled-water systems 18  
SYS-APM001-EN  
Chiller System Design and Control  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
standard rating flow conditions 29  
standard rating temperatures 28  
system configurations 42  
system control 87  
system controls 87, 89  
system design options 27  
system issues and challenges 79  
T
temperature  
chilled water 3, 27, 28  
condenser water 27, 29  
control 85  
out of range 85  
standard rating 28  
tertiary pumping arrangements 49  
thermal storage 83  
three-way valve 8  
two-speed fans 90  
two-way valve 8  
U
unequal chiller sizing 78  
unit-level control 15  
V
valves  
check valves 46  
three-way valve 8  
two-way valve 8  
variable condenser water flow 92  
variable flow 19  
variable primary flow  
advantages of 56  
chiller sequencing 63  
guidelines 68  
plant configuration 67  
systems 13  
variable-speed drives 90  
variable-speed pump 9  
W
water economizer 70  
water temperatures 27, 28  
coil response to 33  
well, river, or lake water 72  
wild coil 9  
106  
Chiller System Design and Control  
SYS-APM001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
Date  
SYS-APM001-EN  
May 2009  
Tra n e  
www.trane.com  
Supersedes  
SYS-APM001-EN  
For more information, contact your local Trane  
office or e-mail us at [email protected]  
Trane has a policy of continuous product and product data improvement and reserves the right to  
change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Telenetics Network Card 202T MIU202T User Manual
Toshiba PDAs Smartphones E350 E355 User Manual
Toshiba Scale SL 9000 LSB User Manual
Toshiba Security Camera IPSe16X User Manual
Tripp Lite Switch B021 000 19 User Manual
UTStarcom Cell Phone CDM 8625 User Manual
Victor Technology Calculator 1210 2 Series User Manual
Viking Refrigerator VIRB364 User Manual
Villaware Waffle Iron BELGIAN WAFFLER User Manual
Vizio Flat Panel Television VX37L User Manual