Trane Ventilation Hood 1500 CFM User Manual

Installation  
Owner  
Maintenance  
Vertical Unit Ventilator  
Classroom Unit Ventilator  
Model VUV  
Models  
“A” and later Design Sequence  
VUVE  
750 CFM 1500 CFM  
October 2007  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Installation/Startup/Commissioning  
Pre-installation Checklist  
4
4
5
General Information  
7
Dimensions/Weights  
14  
24  
Installation Instructions  
Electrical Requirements  
26  
27  
Pre-Startup Checklist  
Maintenance  
30  
31  
33  
Warranty Information  
Troubleshooting Checklist  
Unit Wiring  
UV-SVN03D-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-installation  
Checklist  
Jobsite Inspection  
Always perform the following checks before accepting a unit:  
1. Verify that the nameplate data matches the data on the sales order and bill of  
lading (including electrical data).  
2. Verify that the power supply complies with the unit nameplate specifications.  
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not  
sign the bill of lading accepting the unit(s) until inspection has been com-  
pleted. Check for damage promptly after the unit(s) are unloaded. Once the  
bill of lading is signed at the jobsite, the unit(s) are now the property of the  
SOLD TO party and future freight claims MAY NOT be accepted by the freight  
company.  
Microbial Growth!  
Wet interior unit insulation can become an amplification site for  
microbial growth (mold), which may cause odors and damage to the  
equipment and building materials. If there is evidence of microbial  
growth (mold) on the interior insulation, the insulation should be  
removed and replaced prior to operating the system.  
Jobsite Storage  
This unit is intended for indoor use only. To protect the unit from damage due to  
the elements, and to prevent possible IAQ contaminant sources from growing.  
1. Place the unit(s) on a dry surface or raise above the ground to assure ade-  
quate air circulation beneath the unit.  
2. Cover the unit(s) with a water proof tarp to protect them from the elements.  
3. Make provisions for continuous venting of the covered units to prevent  
moisture from standing on the unit(s) surfaces. Wet interior unit insulation  
can become an amplification site for microbial growth (mold) which can be a  
cause of odors and possible indoor air quality problems.  
4. Do not stack units.  
4
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Information  
Unit Nameplate  
nance (oiling is not needed), and/or  
bearing replacement.  
The unit nameplate is located in the  
left hand end pocket, behind the con-  
trol box. It includes the unit model  
number, serial number, electrical char-  
acteristics, and other pertinent unit da-  
ta.  
Filters  
Filter sizing for the unit ventilator are  
an off-the-shelf design to reduce or  
help eliminate local stocking of the fil-  
ters.  
Factory Shipment  
Sliding Fan Deck  
Before shipment, each unit is leak test-  
ed, and run tested for proper control  
operation.  
Convenient access to the fan motor  
and wheels for maintenance and ser-  
viceability may be made through  
Trane’s easy-slide fan deck design.  
Access  
A three panel front access of the unit  
ventilator allows for speedy set-up  
during field commissioning. This de-  
sign allows for the end pocket of the  
unit ventilator to be open while the fan  
(airside) section stays closed.  
Outside/Return-Air Dampers  
The outside-air/return-air damper is a  
one piece, linkage free design result-  
ing in a superior air-tight seal.  
Field Installed Controls  
(Option)  
The unit comes equipped with a fan  
speed switch, damper blade (only),  
and an optional low temperature de-  
tection.  
End Pockets  
Access for piping and controls is made  
through the unit ventilator’s end pock-  
ets.  
Coil Connections  
End Device Control Package  
(Option)  
The coil headers and drain connec-  
tions are made within the unit chassis  
to allow a tight seal and help prevent  
air leakage around the coil. The con-  
nection sizes vary dependent upon  
type of coil combination specified.  
Units containing the End Device con-  
trol design will incorporate a pre-  
wired, selected control components to  
a terminal strip for wiring a field pro-  
vided controller and temperature sen-  
sor.  
Coil Type  
Size (in.)  
Hydronic Cooling (Main) Coil or  
Heating/Cooling Changeover Coil  
3/4" Nominal  
7/8" I.D.  
Note: for controller operation malfunc-  
tion of any non-Trane, field installed  
controls, consult the literature or tech-  
nical support of the controls manufac-  
turer.  
1/2" Nominal  
5/8" I.D.  
Heating (Auxiliary) Coil  
Steam Heating Coil  
1" FNPT  
3/8" O.D. Liquid  
7/8" O.D. Suction  
Direct Expansion Coil  
Tracer™ ZN520 Control Package  
(Option)  
Unit Drain Pan  
The ZN520 electronic digital controller  
is a factory installed, tested and com-  
missioned LonTalk™ certified design.  
It may be used in a stand-alone control  
scheme, or as part of a building auto-  
mation system. The controller is pre-  
wired to Trane selected control com-  
ponents best suited for room comfort.  
For more information on the ZN520  
unit controller operation and service  
issues, refer to CNT-SVX04A-EN  
(ZN520 control manual).  
The drain pan is dual-sloped for effec-  
tive condensate removal. It is made  
from a non-corrosive material to help  
eliminate issues associated to leaking  
or standing water. It may be easily re-  
moved for cleaning. The drain pan  
connection size for all Trane VUVE  
models is 7/8" O.D.  
Motor  
Motors for the VUVE model do not in-  
clude an external fan bearing on the  
end of the fan shaft. This helps avoid  
issues related to fan bearing mainte-  
UV-SVN03D-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Information  
OA/RA Actuator (Option)  
Table 1: OA/RA actuator specification  
Table 2: Face-bypass actuator specification  
The OA/RA actuator provides true  
spring return operation for positive  
close-off of the OA/RA damper. The  
spring return system of the actuator  
closes the outside damper if power is  
lost to the building. When ordered  
with factory controls, the actuator is a  
3-point floating design. A 2 to 10 VDC  
actuator is available when other than  
Trane controls are specified. See Table  
1 for OA/RA technical data.  
Power Supply  
24 VAC  
24 VAC  
20% 50/60 HZ  
10%  
Power Supply  
24 VAC  
20% 50/60 HZ  
10%  
Power  
Running: 2.5 W  
24 VAC  
2 W  
Consumption Holding: 1 W  
Transformer  
Sizing  
Overload  
Protection  
Control Signal 2 to 10 VDC  
3-point floating with Trane controls  
Angle of  
Rotation  
Torque  
Direction of  
Rotation  
Position  
Indication  
Run Time  
(nominal)  
Power  
5 VA (class 2-power source)  
Consumption  
Transformer  
Sizing  
Angle of  
Rotation  
Torque  
Direction of  
Rotation  
Position  
Indication  
Run Time  
(nominal)  
Manual  
3 VA (class 2-power source)  
Electronic throughout 0 to  
95-degree rotation  
Maximum 95-degree  
Adjustable with mechanical stop  
35-inch/lb  
Note: Because the damper actuator is  
a spring return type an inner spring  
will close the damper upon loss of  
power. If the need to service or replace  
the actuator is required, the spring  
must be "loaded" for the damper to  
function properly. The term loaded  
means that the blade must be held in  
the return air position upon replace-  
ment of the actuator.  
Maximum 95-degree  
Adjustable with mechanical stop  
35-inch/lb  
Spring return reversible with CW/  
CCW mounting  
Visual indicator, 0 to 95-degrees  
Reversible with switch L/R  
Clip-on indicator  
90-second constant  
External push button  
Less than 35 dB  
90-second constant (independent of  
load)  
Running: 30 dB  
Override  
Noise Level  
Control Signal 3-point floating  
Noise Level  
Face and Bypass Actuator (Option)  
The face and bypass damper actuator  
incorporates a direct couple design. It  
provides electronic protection against  
overload. A limit switch is not includ-  
ed, nor required as part of the design.  
When reaching the damper end posi-  
tion, the actuator automatically stops.  
The gears can be manually disen-  
gaged with a button on the housing.  
See Table 2 for face and bypass actua-  
tor specifications.  
Table 3: Mod. water valve specification.  
Table 4: Isolation valve specification.  
Power Supply  
Power Supply  
24 VAC  
4 W  
-
50/60 HZ  
24 VAC  
5 W  
-
50/60 HZ  
Power  
Power  
Consumption  
Max. Duty Cycle  
Nominal Timing  
Operating Ambient  
Temp.  
Consumption  
Max. Fluid Temp.  
15%  
120 sec.  
0 to 65°C  
32 to 150°F  
94°C  
200°F  
1°C  
Min. Fluid Temp.  
34°F  
Modulating Water Valves (Option)  
The modulating control valve provides  
optimum control of hot and chilled wa-  
ter flow in various heating and cooling  
applications. They are designed to  
provide sinusoidal valve actuator trav-  
el and operate silently, resisting water  
hammer.  
Min./Max. Fluid Temp. 1 to 95°C  
34 to 203°F  
Max. Operating Pressure  
Max. Close-off Pressure  
300 psi  
1/2" = 30 psi  
3/4" = 20 psi  
1" = 15 psi  
Operating Pressure  
Differential  
Max. - 4 bar (60 psi)  
Pressure Rating  
Static - 20 bar (300 psi)  
Burst - 100 bar (1500 psi)  
Linear  
Flow Characteristic  
The actuator on the valve is a 24V, 3-  
point floating type. See Table 3 for  
modulating water valve specifications.  
Isolation Valve (Option)  
On heating coils, and two-pipe changeover applications, the valve is normally  
open to help prevent the coil from freezing in-case of power loss.  
For cooling, the valve is normally closed and opens when there is a call for cool-  
ing. See Table 4 for isolation valve specifications.  
The isolation valve is a two position  
24V, spring return type valve. It pro-  
vides added control in heating and  
cooling applications when used in  
conjunction with the face and bypass  
damper.  
6
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions/Weights/  
Clearance  
!
WARNING  
Improper Unit Lift!  
Test lift unit approximately 24 inches to verify proper  
center of gravity lift point. To avoid dropping of unit,  
reposition lifting point if unit is not level. Failure to  
properly lift unit could result in death or serious injury  
or possible equipment or property-only damage.  
Table G1: VUVE general data  
Description  
Unit Size  
0750  
69  
16 5/8  
1000  
81  
1250  
93  
1500  
105  
Unit Length w/o end covers (inches)  
Unit Depth - Standard (inches)  
Unit Depth - with false back (inches)  
Unit Height - Standard (inches)  
Shipping Weight (Lbs.)  
16 5/8  
21 1/4  
30  
16 5/8  
16 5/8  
21 1/4  
21 1/4  
21 1/4  
30  
30  
30  
320  
405  
450  
470  
14 x 20 x 1 (2)  
14 x 24 x 1 (1)  
14 x 30 x 1 (1)  
7 x 54 x 1 (1)  
14 x 20 x 1 (2)  
14 x 24 x 1 (1)  
7 x 66 x 1 (1)  
14 x 24 x 1 (2)  
14 x 30 x 1 (1)  
7 x 78 x 1 (1)  
Nominal Filter Size and  
Quantity (inches)  
7 x 42 x 1 (1)  
Dynamic Air Filter Nominal  
Size (inches) & Qty.  
7/8 ID Hose  
FC / 2  
7/8 ID Hose  
FC / 2  
7/8 ID Hose  
FC / 4  
7/8 ID Hose  
FC / 4  
Drain Connection Size (inches)  
Fan Type / Quantity  
Motor Data  
Quantity  
Horsepower (ea)  
Number of Fan Speeds (Standard)  
If DX or electric heat used  
Number of Fan Speed (ZN520)  
1
1/4  
3
1
1/4  
3
2
1/10  
3
2
1/10  
3
1
1
1
1
3
3
3
3
If exhaust fan or ERSA used  
If DX or electric heat used  
2
2
2
2
1
1
1
1
Coil Volume (gal.)  
Coil Type A  
0.178  
0.311  
0.311  
0.444  
0.444  
0.610  
0.610  
0.395  
0.228  
0.410  
0.410  
0.571  
0.571  
0.809  
0.809  
0.593  
0.277  
0.510  
0.510  
0.704  
0.704  
1.014  
1.014  
0.742  
0.327  
0.610  
0.610  
0.931  
0.931  
1.213  
1.213  
0.837  
B
C
D
E
F
G
H
Unit Location and Clearances  
service personnel to perform mainte-  
nance or repair. Provide sufficient  
room to make water, and electrical  
connection(s). Local and national  
codes should be followed in providing  
electrical power connections. A 36"  
clearance at the unit front is sufficient  
for maintenance and service of the  
equipment.  
Locate the unit in an indoor area. The  
ambient temperature surrounding the  
unit must not be less than 45°F. Do not  
locate the unit in areas subject to  
freezing.  
Attention should be given to service  
clearance and technician safety. The  
unit should contain enough space for  
UV-SVN03D-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Standard Depth Unit  
8
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Falseback Unit  
UV-SVN03D-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Dynamic Air Barrier Unit  
10  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
End Covers  
UV-SVN03D-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Wall Boxes  
12  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions  
Crossover Piping  
16 5/8" DEPTH UNIT  
7/8" I.D. FIELD  
CONN.W/ SHUT  
OFFVALVE  
1 1/2"  
FLUSH  
RETURN  
3"  
S R  
SUPPLY  
24"  
3 1/2"  
4 1/2"  
19 3/8"  
TOPVIEW  
3 5/8"  
5 3/8"  
SIDEVIEW  
21 1/4" DEPTH UNIT  
7/8" I.D. FIELD  
CONN. W/ SHUT  
OFF VALVE  
1 1/4"  
FLUSH  
RETURN  
3"  
SUPPLY  
S R  
24"  
19 3/8"  
3 1/2"  
4 1/2"  
TOPVIEW  
8 1/4"  
10"  
SIDEVIEW  
Notes: 1-3/8" o.d. and 2-1/8" o.d. crossover piping  
1
2
Crossover piping is available for all 2 or 4-pipe coils selections. Trane pro-  
vides the crossover for the cold water only. The crossover pipe is factory in-  
sulated with 3/8"-thick insulation.  
Expansion compensation between the factory piping package and the cross-  
over piping is achieved using a flex hose rated at 250 psi working pressure.  
flex hose is only available with factory mounted piping packages.  
Expansion compensation for the crossover piping must be handled external  
to the unit ventilator.  
Crossover connections terminate in the same end pocket as the main coil con-  
nection. The main coil connection for 2-pipe systems is the heating coil. the  
main coil connection for 4-pipe systems is the cooling coil.  
3
4
UV-SVN03D-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Interior Wall  
w/ sheetrock  
Wall Box Installation  
Installation in Masonry Walls  
A typical method of installing the wall  
box in a masonry wall opening is  
shown in Figure 1.  
The following instructions are general  
recommendations for installing wall  
intake boxes. Consult the architectural  
plans for specific requirements.  
Outside  
Wall  
Unit  
Grout the top and bottom of the wall  
box frame as noted. A sloped water  
dam located in the space between the  
unit and wall facilitates moisture  
drainage. Grouting at the ends of the  
intake box will complete the seal be-  
tween the wall box frame and the ma-  
sonry opening.  
Additional materials required to com-  
plete any specific installations (such as  
duct connections, metal mounting  
plates, or flanges) are not furnished by  
Trane.  
Rubber  
Seals  
Grout  
Weep  
Holes  
Floor  
For best results, all air intake boxes  
should be removable from outside of  
the building. Weep holes must be at  
the bottom to permit free drainage. A  
positive air and moisture seal should  
be provided around all edges.  
Installation in Curtain Walls  
In all cases, the wall intake box should  
be caulked to provide a tight, weather-  
proof seal, Figure 2.  
Water dam sloped  
toward exterior  
Figure 1: Masonry wall installation  
General Instructions  
Note: A minimum of 2-1/8” of clear-  
ance must be maintained between the  
exterior wall and back of the unit. Fail-  
ure to provide this gap will not allow  
the wall box to fit properly.  
Trane wall boxes are illustrated in the  
dimensional section of this manual.  
Dimensions are actual, and may be  
used to define the wall opening.  
Interior Wall  
w/ sheetrock  
Outside  
Wall  
Unit  
Vertical louvers in the wall intake box  
provide extra strength for a high load  
bearing capacity. The lintel may be  
omitted on masonry wall installations.  
Caulking  
Rubber  
Seals  
Weep holes are provided in the out-  
side face of the bottom channel in the  
wallbox frame. Install all wall boxes to  
permit free drainage through the weep  
holes to the outside of the building.  
Flanged  
wallbox  
Weep  
Holes  
All wallboxes are furnished with dia-  
mond pattern expanded aluminum  
bird screen.  
Note: V1 and V2 (vertical) wall models  
are all unflanged. H2, V3 and V6 are  
flanged.  
Water dam sloped  
toward exterior  
Figure 2: Flanged wall box installation  
in 2" curtain wall  
14  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
General Installation Checks  
Location Considerations  
Selecting the appropriate location for  
installing a unit is very important. The  
following factors should be consid-  
ered:  
5
6
Internal access to the unit is pro-  
vided by the removable front pan-  
el. Sufficient space should be  
allowed to lift the panel for mainte-  
nance purposes.  
The checklist below is a summary of  
the steps required to successfully in-  
stall a unit. This checklist is intended to  
acquaint the installing personnel with  
procedures required in the installation  
process. It does not replace the de-  
tailed instructions called out in the ap-  
plicable sections of this manual.  
1
Floor design must have sufficient  
structure to withstand the weight  
of the unit while allowing for  
openings in the floor for a return  
air duct, electrical and piping sup-  
ply lines fed through the floor.See  
page 7 for unit weights.  
Ensure the floor surface is level.  
Note: The unit leveling legs can be  
adjusted to accommodate slight  
out-of-level installation surfaces.  
1
Carefully remove the stretch wrap  
and top cardboard cover. Check  
the unit for shipping damage and  
material shortage; file a freight  
claim and notify appropriate sales  
representation. If end panels have  
been ordered, the panel will al-  
ready be mounted to the unit.  
Unit Mounting  
Note: All wall intake boxes should be  
installed prior to mounting the unit  
ventilator. Refer to Page 14 for wall  
box installation instructions.  
2
Wall space design should allow the  
unit to be mounted to the wall se-  
curely. The wall surface behind  
the unit should be smooth and lev-  
el. Wall and floor moldings should  
be removed prior to installation. A  
wall slightly out of level may cause  
problems with unconditioned air  
leaking into the room. Remove  
any object projecting more then  
1/8” (.3175cm) from the wall sur-  
face. Note: Additional gasket or  
furr strips may be installed to ac-  
commodate for an uneven wall.  
The 1/2” mounting or anchoring holes  
are located on the back of the unit on  
each end. See Figures 3.  
Note: The unit ventilator is pack-  
aged in clear stretch wrap to allow  
for immediate visual inspection. A  
protective cardboard cover helps  
prevent scratching and other cos-  
metic blemishes during transport.  
Note: All mounting fasteners are to be  
provided by the installer.  
2
3
Remove remaining cardboard  
blocking.  
Remove the unit’s left front panel  
to verify nameplate/sales order  
number is correct. It is located be-  
hind the control box.  
3
There are two removable knock-  
outs in the rear of the unit, on ei-  
ther end, for piping and electrical  
supply lines. A pipe chase is locat-  
ed in the upper back portion of the  
unit for crossover piping. The out-  
side air opening is located in the  
lower back of the unit and the path  
to the wallbox on the outside wall  
should be unobstructed.  
4
Remove shipping bracket from the  
lower rear corners of the unit to  
separate the unit from the skid. Ac-  
cess to the screws holding the  
bracket to the skid is obtained in-  
side the unit.  
4
The physical layout of the room  
should accommodate any accesso-  
ries ordered with the unit. Condi-  
tioned air is distributed through  
the grille on top of the unit and re-  
turned through the return air grille  
on the bottom of the unit. Avoid  
placing any objects that may ob-  
struct either grille or interfere with  
airflow.  
5
6
Rotate the fan wheels manually.  
The wheels should move freely  
and be in proper alignment. Visu-  
ally inspect the fan area for ob-  
structions or shipping damage.  
Remove all applicable knockouts  
for coil piping and electrical con-  
nections.  
UV-SVN03D-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 3: Mounting hole location  
F
E
C
B
C
B
A
D
A
B
C
D
E
F
Standard Unit (no Falseback)  
Standard falseback  
1.31  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.31  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.31  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.31  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
13.50  
2.13  
2.13  
2.13  
2.13  
2.13  
2.13  
13.50  
2.13  
2.13  
2.13  
2.13  
2.13  
2.13  
13.50  
2.13  
2.13  
2.13  
2.13  
2.13  
2.13  
13.50  
2.13  
2.13  
2.13  
2.13  
2.13  
2.13  
2.75  
66.39  
67.00  
67.00  
67.00  
67.00  
67.00  
67.00  
78.39  
79.00  
79.00  
79.00  
79.00  
79.00  
79.00  
90.39  
91.00  
91.00  
91.00  
91.00  
91.00  
91.00  
102.39  
103.00  
103.00  
103.00  
103.00  
103.00  
103.00  
10.38  
10.00  
10.00  
10.00  
10.00  
10.00  
10.00  
10.38  
10.00  
10.00  
10.00  
10.00  
10.00  
10.00  
10.38  
10.00  
10.00  
10.00  
10.00  
10.00  
10.00  
10.38  
10.00  
10.00  
10.00  
10.00  
10.00  
10.00  
45.64  
47.00  
47.00  
47.00  
47.00  
47.00  
47.00  
57.64  
59.00  
59.00  
59.00  
59.00  
59.00  
59.00  
69.64  
71.00  
71.00  
71.00  
71.00  
71.00  
71.00  
81.64  
83.00  
83.00  
83.00  
83.00  
83.00  
83.00  
075  
100  
125  
150  
26.00  
24.44  
23.44  
22.44  
21.44  
20.44  
2.75  
29" stepdown falseback  
28" stepdown falseback  
27" stepdown falseback  
26" stepdown falseback  
25" stepdown falseback  
Standard Unit (no Falseback)  
Standard falseback  
26.00  
24.44  
23.44  
22.44  
21.44  
20.44  
2.75  
29" stepdown falseback  
28" stepdown falseback  
27" stepdown falseback  
26" stepdown falseback  
25" stepdown falseback  
Standard Unit (no Falseback)  
Standard falseback  
26.00  
24.44  
23.44  
22.44  
21.44  
20.44  
2.75  
29" stepdown falseback  
28" stepdown falseback  
27" stepdown falseback  
26" stepdown falseback  
25" stepdown falseback  
Standard Unit (no Falseback)  
Standard falseback  
29" stepdown falseback  
28" stepdown falseback  
27" stepdown falseback  
26" stepdown falseback  
25" stepdown falseback  
26.00  
24.44  
23.44  
22.44  
21.44  
20.44  
16  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Unit Mounting  
rather than the holes located in the  
unit’s end pockets.  
End Panels  
Note: All wall intake boxes should be  
installed prior to mounting the unit  
ventilator. Refer to Page 14 for wall  
box installation instructions.  
When ordered as an option, end cov-  
ers ship already attached to the verti-  
cal unit ventilator. The following  
section is for installing end covers pur-  
chased as an add-on.  
Note: Ensure the unit is level. Coils  
and drain pans inside the unit are  
pitched properly for draining before  
shipment.  
The 1/2” mounting or anchoring holes  
are located on the back of the unit on  
each end. See Figure 3.  
It is recommended end panels be in-  
stalled on the unit ventilator after all  
piping, wiring and accessory installa-  
tion is completed. To install the end  
panel:  
5
Ensure the unit rests tightly  
against the wall. Check for proper  
seal and that air does not leak un-  
derneath the unit.  
1
Note: All mounting fasteners are to  
be provided by the installer. Check  
the gasket on the rear of the unit  
and around the fresh air open-  
ing. Gaps around the openings  
can lead to outside air leaks into  
the room.  
1
Insert the four factory provided  
metal studs into the four pre-  
mounted nuts on the inside of the  
panel.  
Subbase (option)  
A subbase may be used to increase the  
unit height and aid in leveling the unit.  
The subbase is shipped separately for  
field installation. Slots and leveling  
screws are provided on the subbase.  
2
Remove all electrical and piping  
knockouts where required for in-  
stallation.  
2
3
4
Align each stud with the four pre-  
drilled holes on the side of the  
unit.  
1
Remove the leveling legs provided  
with the unit. See Figure 4.  
Secure the panel to the unit by fas-  
tening with the four factory pro-  
vided nuts.  
!
WARNING  
Unit Base  
Improper Unit Lift!  
Test lift unit approximately 24  
inches to verify proper center of  
gravity lift point. To avoid drop-  
ping of unit, reposition lifting  
point if unit is not level. Failure to  
properly lift unit could result in  
death or serious injury or possible  
equipment or property-only dam-  
age.  
Weld  
Nuts  
Do not overtighten screws.  
Subbase  
2"- 6"  
CAUTION  
Equipment Damage!  
For leveling legs  
Do not run units for any length of  
time without all panels and filters  
properly installed. Failure to do so  
may result in equipment failure.  
Figure 4: Subbase with leveling legs  
2
Set the unit on the subbase and  
fasten with four, 3/8” x 16’ x 1”  
hex head cap screws and 3/8" lock  
washers.  
3
Set the unit into selected location  
and adjust leveling legs if neces-  
sary to ensure level fit.  
Note: Care should be taken when  
handling the unit to ensure that the  
front return air grille does not  
bend.  
Note: Hex screws and lock wash-  
ers are provided by the factory.  
They are located in a baggy and are  
used to attach the base to the unit  
ventilator. Pre-drilled slots in the  
subbase flange will line up with  
the weld nuts in the bottom of the  
unit.  
4
Push the unit tightly against the  
wall to compress the seal on the  
back edge of the unit and intake  
opening. Anchor the unit by using  
the 1/2” mounting holes in both  
end pockets.  
3
The bottom of the subbase has  
weld nuts in four slots. Place the  
leveling legs in those slots and lev-  
el the unit.  
Units containing a falseback; The  
falseback unit ventilator contains  
mounting holes located on the  
falseback metal. Use these holes  
UV-SVN03D-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Piping Installation  
7
After the condensate drain piping  
has been completed, check water  
flow to ensure the system proper-  
ly carries and away all condensate  
accumulation.  
Installation Crossover Piping  
Crossover piping is available for all hy-  
dronic coils. It is either 1 3/8’’ \[34.9\] or  
2 1/8’’ \[54\] in diameter (O.D.) as spec-  
ified by the customer. Crossover pip-  
ing can be found in either the left or  
right hand end pocket. See crossover  
submittal drawings page 13 for dimen-  
sional data.  
Before installation of piping package,  
the shipping bracket holding the pip-  
ing in place, must be removed.  
Proper installation of piping is neces-  
sary to provide efficient coil operation  
and to prevent damage during opera-  
tion. Follow standard piping practices  
and include all accessories as neces-  
sary.  
Note: A P-trap is factory supplied in ev-  
ery vertical unit ventilator.  
Trane Piping Packages (Option)  
Trane Standard Piping Package in-  
cludes a 2-way or 3-way valve with by-  
pass balance valve, ball valves, Petes  
plugs and unions. A strainer and cir-  
cuit balancing valve are optional.  
On 4-pipe coils, crossover piping con-  
nects to the main cooling coil.  
Piping connection knockouts are  
shown pages 8 to 10. Field connection  
types and sizes for unit coils are listed  
in Table 5. These sizes are provided for  
field piping connection.  
Factory insulation is provided on all  
crossover piping.  
1
All union connections should be  
tightened in the field. Units are  
shipped with union connections  
hand tightened only in the factory.  
When a Trane piping package is or-  
dered, it is installed with the connec-  
tions made to the supply and return of  
both the coil and the crossover piping.  
However, supply and return connec-  
tions must be made in the field when a  
piping package is furnished by the in-  
staller.  
A 7/8’’ OD condensate drain connec-  
tion is provided on the chilled water  
supply end of the unit.  
Note: All connections made in the field  
should be sweat connections.  
1
Attach a flexible condensate drain  
hose over the drain pan connec-  
tion and secure with a hose clamp.  
Piping packages are not shipped insu-  
lated. Any insulation should be provid-  
ed in the field by the installing  
contractor.  
The crossover piping is located at the  
back of the unit along the wall and the  
ends of the piping are flush with the  
end of the unit.  
The drain pan on the vertical is vacu-  
um molded with a drain connection  
and P-Trap on the cooling coil, connec-  
tion side.  
The auxiliary drain pan (optional) is  
the main condensate connection to  
the unit when specified. The chilled  
water or DX coil drain pan will empty  
into the auxiliary drain pan if a factory  
installed, auxiliary pan is ordered. All  
field piping condensate connections  
should be made at the auxiliary drain  
pan.  
Expansion compensation between the  
piping package and the crossover pip-  
ing is achieved using flex hoses rated  
at 250 psi working pressure. Expan-  
sion compensation for the crossover  
piping must be handled external to the  
unit ventilator.  
Note: Condensate removal to the main  
system should be made through the  
bottom of the unit ventilator. If other  
location for condensate removal is de-  
sired, a specific field cut-out for the  
connection should be made in the back  
of the unit ventilator. To help avoid  
cold air infiltration, the field cut-out  
should only be large enough to allow  
for the condensate hose to exit the  
unit.  
Table 7: Coil data for field piping  
Coil Type  
Connection Location  
Field Connection Size  
7/8" OD/5/8" OD  
4-Pipe Chilled Water/Hot Water  
2-Pipe Changeover Coil  
Hot Water Only  
Steam  
Left or Right (opposite ends)  
To field reverse the slope of a vertical  
unit drain pan.  
Left or Right  
Left or Right  
7/8" OD  
7/8" OD  
2
Slide out fan deck (disconnecting  
the condensate line and fan plug  
will release fan deck for sliding).  
Left or Right  
1" MPT  
Chilled Water/Electric Heat  
Chilled Water/Steam  
DX  
Left Cooling  
7/8" OD  
Left or Right  
7/8" OD/1" MPT  
3
4
Remove pipe clamp that hold the  
p-trap to the drain pan.  
Left  
7/8" Suction, 3/8" Discharge  
7/8" Suction, 3/8" Discharge/5/8" OD  
7/8" Suction, 3/8" Discharge/1" MPT  
7/8" Suction, 3/8" Discharge/NA  
NA  
DX/Hot Water  
Left Cooling/Right Heating  
Left Cooling/Right Heating  
Left Cooling/Right Heating  
Right  
DX/Steam  
Remove clips that hold the drain  
pan in-place.  
DX/Electric Heat  
Electric Heat  
5
6
Lift and rotate the drain pan.  
Notes:  
Reconnect p-trap to the drain pan  
and replace clips to secure the pan  
to the fan deck.  
1. Supply and return connections are located on the same end of each coil.  
2. All Trane piping packages have union connections; all units with piping packages by others have sweat  
connections.  
3. Coil connections are sweat except steam coils, which are threaded.  
18  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Split System Units  
Steam Piping  
The following refrigerant piping and  
interconnecting wiring instructions  
apply to unit ventilators with direct ex-  
pansion type cooling coils used in con-  
junction with air-cooled condensing  
units. Reference must also be made to  
the condensing unit installation and  
wiring manuals which are shipped  
with the condensing unit.  
When air, water or another product is  
heated, the temperature or heat trans-  
fer rate can be regulated by a modulat-  
ing steam pressure control valve.  
Since pressure and temperature do  
not vary at the same rate as load, the  
steam trap capacity, which is deter-  
mined by the pressure differential be-  
tween the trap inlet and outlet, may be  
adequate at full load, but not some  
lesser load.  
Note: The ETL listing mark applied to a  
unit ventilator does not apply to any  
associated refrigerant condensing  
unit.  
There are detailed methods for deter-  
mining condensate load under various  
operating conditions. However, in  
most cases this is not necessary if the  
coils are piped as shown in Figure 5.  
Follow the procedure documented in  
the ASHRAE Systems Handbook,  
Steam Systems.  
Refrigerant Piping  
Unit ventilators with direct expansion  
cooling contain a nitrogen holding  
charge in the evaporator coils. Con-  
nections are ‘‘pinched-off’’ at the fac-  
tory.  
Temp. Regulating Valve  
To connect the condensing unit lines,  
cut off the stubouts and swage. The  
condensing unit lines can then be  
brought into the swage and brazed.  
Trane recommends the use of nitro-  
gen purge when brazing refrigerant  
lines to prevent formation of oxides in  
the lines.  
Coil  
To Condensate  
return  
H= 12"  
minimum  
Vacuum Equalizer  
F&TTrap  
See text for sizing  
Install the refrigerant suction and liq-  
uid lines as described in the condens-  
ing unit installation instructions. The  
TXV is factory installed on the Unit  
Ventilator. Piping should be run  
straight out through the back of the  
unit. Access piping knockouts are lo-  
cated in the rear panels of the unit, as  
shown in dimensional section of this  
manual.  
Gravity flow to  
vented receiver  
Figure 5: Steam piping  
Recommended refrigerant line con-  
nections for various unit combinations  
are given in Table 7. Typical Superheat  
Charging Charts are shown in the  
Trane Service Facts found in the con-  
densing unit section manual. Refriger-  
ant charge weights can also be  
determined with your local Trane  
sales engineer using a valid Trane Se-  
lection Program.  
UV-SVN03D-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 6b: Steam piping  
Modulating Water Valves (Option)  
The actuator on the valve is a 24V, 3-  
point floating valve. The actuator can  
be easily removed from the valve body  
by pressing in on the locking tab and  
rotating the actuator 45° counter-  
clockwise (See Figure 6a). The 2-way  
valves are bi-directional flow. The 3-  
way valves can be mixing or diverting  
(See Figure 6b).  
Use the following steps to complete  
cartridge assembly removal:  
Closed  
Open  
1
2
Remove valve actuator.  
B
Remove the cartridge assembly  
from the valve body with the en-  
closed tool.  
A
3
4
Solder the valve in accordance with  
normal soldering practices.  
Re-install the cartridge after solder-  
ing by tightening until it bottoms  
out. The top surface of the car-  
tridge will be flush with the top  
edge of the body casting.  
B
A
Note: The actuator must be removed if  
soldering is being conducted near the  
valve. High heat may cause damage to  
the actuator’s plastic body/mecha-  
nisms.  
2-way valve  
Note: Do not overtighten. Maxi-  
mum torque is 40 in-lb.  
AB<->B  
B
5
Replace valve actuator and wire in  
accordance with instructions.  
Plumbing the Valve  
The valve may be plumbed in any an-  
gle but preferably not with the actua-  
tor below horizontal level of the body.  
Make sure there is enough room  
around the actuator for servicing or re-  
placement.  
AB  
AB<->A  
A
For use in diverting applications, the  
valve is installed with the flow water  
entering through the bottom AB port  
and diverting through end ports A or  
B. In mixing applications the valve is  
installed with inlet to A or B and outlet  
through AB.  
3-way valve  
AB  
On applications without the optional,  
factory installed piping packages, it is  
important to remove the cartridge as-  
sembly from the valve body with the  
provided tool (Figure 7).  
Mount directly to the tube or pipe. Do  
not grip the actuator while making or  
tightening plumbing connections. Ei-  
ther hold valve body by hand or attach  
an adjustable spanner (38mm/1-1/2”)  
across the hexagonal or flat faces on  
the valve body. See Figure 8.  
Figure 6a: Remove modulating valve  
actuator by pressing in tab (inset) and  
turning actuator 45° counterclockwise.  
Figure 7: Cartridge removal tool  
Figure 8: Proper plumbing technique  
for modulating valves  
20  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Manually Opening Valve  
the normally open (NO) or normally  
closed (NC) contacts, driving the valve  
to an intermediate position until a fur-  
ther change at the controller.  
Figure 12: Removing valve actuator  
The manual opener can be manipulat-  
ed only when in the up position. The A  
port can be manually opened by firmly  
pushing the white manual lever down  
to the midway position and pushing  
the lever in. In this position, both A  
and B ports are open. This “manual  
open” position may be used for filling,  
venting and draining the system or  
opening the valve during power fail-  
ure.  
The valve is set between the limits of  
the controller to satisfy various load  
requirements. In the event of power  
failure, the valve will stay in the posi-  
tion it was in before loss of power.  
When power is restored, the valve will  
again respond to controller demand.  
The valve can be closed by depressing  
the white lever lightly and then pulling  
the lever outward. The valve and actu-  
ator will return to the automatic posi-  
tion when power is restored.  
Isolation Valves  
Installation  
The valve can be mounted in any posi-  
tion on a vertical line. If the valve is  
mounted horizontally, the actuator  
must be even with or above the center  
line. Make sure there is enough room  
to remove actuator cover for servicing.  
Mount the valve on the tube or pipe.  
To install the actuator to the valve  
body:  
Note: If the valve is powered open, it  
cannot be manually closed, unless the  
actuator is removed.  
3
Align the slot on the shaft of the  
valve with the valve body notch on  
side of body. See Figure 13.  
Wiring  
Note: Ensure the flow through the  
valve is in the direction indicated by  
the arrow stamped on the valve body.  
A controller and a separate transform-  
er is required to operate each valve.  
See Figures 9 and 10. Port A “open”  
and “closed” denote valve open and  
closed positions.  
Figure 9: Wiring for modulating valve  
actuator  
Figure 13: Installing isolation valve  
Figure 11: Proper mounting for  
4
5
Install body valve into pipe.  
isolation valves.  
Wiring connections may be made  
either before or after actuator in-  
stalled on body.  
Servicing/Removal of Valves  
The actuator can be removed from the  
valve body. Removing the actuator is  
recommended if soldering is being  
conducted near the valve. To remove  
the actuator:  
6
7
Place the manual operating lever  
on the actuator in the OPEN posi-  
tion.  
Align actuator coupling to slot on  
the shaft of the valve body and fit  
the head onto the valve body to  
ensure the shaft seats correctly,  
Figure 11.  
Figure 10: Wiring for modulating valve  
1
Place the manual operating lever  
actuator  
to the Open position, Figure 12  
The typical floating controller is an  
SPDT controller with a center-off posi-  
tion. On a change in temperature from  
the set point, the controller will close  
2
Depress the locking button and lift  
actuator until it separates from the  
valve body.  
8
Press the actuator and valve body  
until it secures together.  
UV-SVN03D-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Soldering procedures are as  
follows:  
Wiring  
Supply Power  
All classroom unit ventilators have  
115V motor power. Motor data can be  
found in Tables G1.  
1
Remove actuator as stated earlier.  
CAUTION  
2
Place valves on the pipe. Rotate  
valve stem so the shaft slot points  
at the notch in the side of the body  
(90° to flow direction). This pro-  
tects the plug inside the valve by  
removing it from the seat, Figure  
14.  
Use Copper Conductors  
Control Power  
Only!  
Unit terminals are not designed to  
accept other types of conductors.  
Failure to use copper conductors  
may result in equipment damage.  
!
WARNING  
Hazardous Voltage!  
Disconnect all electric power, in-  
cluding remote disconnects be-  
fore servicing. Follow proper  
lockout/tagout procedures to en-  
sure the power can not be inad-  
vertently energized. Failure to  
disconnect power before servic-  
ing could result in death or seri-  
ous injury.  
Power supply wiring is to be connect-  
ed to terminals 1 and 2 at the junction  
box in the left end pocket, below the  
discharge air grille.  
3
Sweat the joints, keeping outer  
surface free from solder.  
Note: Do not use silver solder due  
to high temperature require-  
ments.  
Electric Heat (option)  
Supply Power  
Supply power wiring is to be connect-  
ed to the following line terminals in  
the right hand end pocket:  
CAUTION  
Equipment Damage!  
-Wiring diagrams provided in this  
manual are for reference only. Ac-  
tual wiring for particular options/  
units may vary. Refer to the dia-  
gram provided on the equipment  
for specific information. Failure to  
do so may result in equipment fail-  
ure.  
208V or 240V, 3-phase,  
3 wire system: L1, L2 and L3.  
480V, 3-phase, 4 wire system:  
L1, L2, L3 and N (neutral)  
See Page 34 for a typical unit line and  
interconnecting wiring diagram for  
Electric Heat Coils.  
Figure 14: Preparation for soldering  
-When installing field provided  
controls, do not alter or remove  
any built-in unit safeties. Tamper-  
ing with unit safeties may cause  
unit overheating and possible fire  
hazard.  
-Do not remove or alter the wiring  
of the Time Delay Relay (DL). Do-  
ing so may result in premature  
motor failures.  
CAUTION  
Heating Coils with Direct  
Expansion Cooling  
Heating options for direct expansion  
cooling in the unit ventilator are hot  
water, steam or electric heat.  
Equipment Damage!  
480 V/3-Wire is NOT compatible  
with Trane Classroom Unit Venti-  
lator equipment. There must be a  
4-wire system with a separate  
ground. Failure to provide a 4-wire  
system may result in equipment  
damage.  
These coils facilitate direct expansion  
cooling with standard capacities. The  
supply and return connections are lo-  
cated in the right hand end pocket. Hot  
water field connections are made with  
a 5/8’’ \[15.9\] OD male sweated joint,  
while steam coils have a 1’’ \[25.4\]  
male pipe thread (MPT) connection.  
See Table 7 for coil connection sizes.  
Note: The supply neutral wire must  
be connected to the neutral terminal  
block.  
Unit ventilator controls and control  
wiring can be factory mounted or field  
installed.  
Operational controls and an electric  
heating safety device are factory  
mounted. The safety device is a high  
temp cut-out which de-energizes elec-  
tric heating elements through the K1  
safety contactor.  
Wiring diagrams illustrate the stan-  
dard unit motors with one and two  
speed control. Terminal wiring is pro-  
vided by Trane and the actual compo-  
nents used for a particular installation  
may differ. Control and line diagrams  
for the exact control system used are  
provided with each unit.  
Electric heat coils provide a third way  
to supply heating to the direct expan-  
sion cooling. The coil utilizes three to  
six preheat elements which are factory  
wired.  
22  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
!
WARNING  
Hazardous Voltage!  
IMPORTANT:  
Disconnect all electric power, in-  
cluding remote disconnects be-  
fore servicing. Follow proper  
lockout/tagout procedures to en-  
sure the power can not be inad-  
vertently energized. Failure to  
disconnect power before servic-  
ing could result in death or seri-  
ous injury.  
INSTALLER MUST MOUNTTHERMAL  
EXPANSION VALVE BULB AND FROST  
PROTECTION BULB (if suppled)TO  
SUCTION LINE AFTER CONNECTION  
OF FIELD REFRIGERANT PIPING  
X39001939010A  
Wiring (continued)  
X
12  
DX System  
A typical unit ventilator with DX coil in-  
cludes an outside air thermostat, a  
frost prevention thermostat and a 24V  
transformer for condensing unit con-  
trol.  
9
3
3:00  
4:00  
9:00  
8:00  
6
X
RECOMMENDED  
BULB PLACEMENT  
MOUNT BULB IN  
HORIZONTAL PLANE  
Wire sizing is the same as given for the  
thermostat wiring in the condensing  
unit installation instructions, or may  
be obtained from the nameplate. The  
condensing unit must be controlled by  
the same room thermostat that also  
controls the unit ventilator.  
Figure 15: Frost stat/TXV valve  
installation tag  
Note: Depending on the controls pack-  
age ordered with the unit, not all in-  
stallations will require mounting the  
frost stat bulb.  
Split System Start-Up  
After all piping and wiring has been  
completed, follow the instructions  
provided with the condensing unit for  
control testing and system start-up. If  
sweat type field-piped systems are be-  
ing used, then pressure testing, evacu-  
ation and refrigerant charging will be  
required.  
Two bulbs will also be shipped with a  
split system unit:  
Frost stat bulb  
TXV valve (used with R410a).  
Both components are to be field in-  
stalled using the installation kit  
shipped with the unit. For complete in-  
stallation instructions and locations,  
refer to the tag attached to the installa-  
tion kit within the unit. See Figure 15  
for an example of the installation tag.  
UV-SVN03D-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Requirements  
Table E1: VUV 075-150, Electrical Performance  
Blower  
Motor  
FLA (ea)  
3.0  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
3.0  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.6  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
Blower  
Motor  
HP  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
1/4  
Number of  
Electric  
Heat  
kW  
Electric  
Heat  
Amps  
0.00  
Minimum  
Circuit  
Ampacity  
3.8  
Overcurrent  
Protective  
Device  
15  
Unit  
No. of  
Heating  
Total  
FLA  
Model No.  
Voltage  
Fan Motor  
Elements  
VUVE075  
115/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/3  
208/60/3  
208/60/3  
208/60/3  
230/60/1  
230/60/1  
230/60/1  
230/60/1  
230/60/3  
230/60/3  
230/60/3  
230/60/3  
265/60/1  
265/60/1  
265/60/1  
265/60/1  
460/60/3  
460/60/3  
460/60/3  
460/60/3  
115/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/3  
208/60/3  
208/60/3  
208/60/3  
230/60/1  
230/60/1  
230/60/1  
230/60/1  
230/60/3  
230/60/3  
230/60/3  
230/60/3  
265/60/1  
265/60/1  
265/60/1  
265/60/1  
460/60/3  
460/60/3  
460/60/3  
460/60/3  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0.00  
0.00  
4.39  
5.86  
8.79  
0.00  
4.39  
5.86  
8.79  
0.00  
5.85  
7.80  
11.70  
0.00  
5.85  
7.80  
11.70  
0.00  
5.82  
7.80  
11.70  
0.00  
5.85  
7.80  
11.70  
0.00  
0.00  
5.86  
7.81  
11.72  
0.00  
5.86  
7.81  
11.72  
0.00  
7.80  
10.40  
15.60  
0.00  
7.80  
10.40  
15.60  
0.00  
7.80  
10.40  
15.60  
0.00  
7.80  
10.40  
15.60  
3.00  
0.00  
1.60  
2.0  
15  
21.10  
28.20  
42.30  
0.00  
22.70  
29.80  
43.90  
1.60  
28.4  
37.3  
54.9  
2.0  
30  
40  
60  
15  
12.20  
18.69  
24.40  
0.00  
13.80  
20.29  
26.00  
1.60  
17.3  
25.4  
32.5  
2.0  
20  
30  
35  
15  
24.40  
32.50  
48.80  
0.00  
26.00  
34.10  
50.40  
1.60  
32.5  
42.6  
63.0  
2.0  
35  
45  
70  
15  
14.10  
21.49  
28.10  
0.00  
15.70  
23.09  
29.70  
1.00  
19.6  
28.9  
37.1  
1.3  
20  
30  
40  
15  
21.00  
28.20  
42.20  
0.00  
22.00  
29.20  
43.20  
1.00  
27.5  
36.5  
54.0  
1.3  
30  
40  
60  
15  
7.00  
8.00  
10.0  
18.9  
18.9  
3.8  
15  
14.10  
14.10  
0.00  
15.10  
15.10  
3.00  
20  
20  
VUVE100  
15  
0.00  
1.60  
2.0  
15  
28.20  
37.50  
56.30  
0.00  
29.80  
39.10  
57.90  
1.60  
37.3  
48.9  
72.4  
2.0  
40  
50  
80  
15  
16.30  
24.79  
32.50  
0.00  
17.90  
26.39  
34.10  
1.60  
22.4  
33.0  
42.6  
2.0  
25  
35  
45  
15  
32.50  
43.30  
65.00  
0.00  
34.10  
44.90  
66.60  
1.60  
42.6  
56.1  
83.3  
2.0  
45  
60  
90  
15  
18.80  
28.66  
37.50  
0.00  
20.40  
30.26  
39.10  
1.00  
25.5  
37.8  
48.9  
1.3  
30  
40  
50  
15  
28.20  
37.50  
56.30  
0.00  
29.20  
38.50  
57.30  
1.00  
36.5  
48.1  
71.6  
1.3  
40  
50  
80  
15  
9.40  
10.40  
19.80  
19.80  
13.0  
24.80  
24.8  
15  
18.80  
18.80  
25  
25  
24  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Requirements  
Table E1: VUV 075-150, Electrical Performance (continued)  
Blower  
Motor  
FLA (ea)  
2.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
2.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
1.0  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
0.9  
Blower  
Motor  
HP  
Number of  
Electric  
Heat  
kW  
Electric  
Heat  
Amps  
0.00  
Minimum  
Circuit  
Ampacity  
4.5  
Overcurrent  
Protective  
Device  
15  
Unit  
No. of  
Heating  
Total  
FLA  
Model No.  
Voltage  
Fan Motor  
Elements  
VUVE125  
115/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/3  
208/60/3  
208/60/3  
208/60/3  
230/60/1  
230/60/1  
230/60/1  
230/60/1  
230/60/3  
230/60/3  
230/60/3  
230/60/3  
265/60/1  
265/60/1  
265/60/1  
265/60/1  
460/60/3  
460/60/3  
460/60/3  
460/60/3  
115/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/1  
208/60/3  
208/60/3  
208/60/3  
208/60/3  
230/60/1  
230/60/1  
230/60/1  
230/60/1  
230/60/3  
230/60/3  
230/60/3  
230/60/3  
265/60/1  
265/60/1  
265/60/1  
265/60/1  
460/60/3  
460/60/3  
460/60/3  
460/60/3  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
1/10  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
0
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0
3
4
6
0.00  
4.00  
0.00  
0.00  
2.00  
2.3  
15  
7.32  
35.20  
46.90  
70.40  
0.00  
37.20  
48.90  
72.40  
2.00  
46.3  
60.9  
90.3  
2.3  
50  
9.76  
70  
14.65  
0.00  
100  
15  
7.32  
20.30  
31.03  
40.70  
0.00  
22.30  
33.03  
42.70  
2.00  
27.6  
41.0  
53.1  
2.3  
30  
9.76  
45  
14.65  
0.00  
60  
15  
9.75  
40.60  
54.20  
81.30  
0.00  
42.60  
56.20  
83.30  
2.00  
53.0  
70.0  
103.9  
2.3  
60  
13.00  
19.50  
0.00  
80  
110  
15  
9.75  
23.50  
35.82  
46.90  
0.00  
25.50  
37.82  
48.90  
1.80  
31.9  
47.0  
60.9  
2.0  
35  
13.00  
19.50  
0.00  
50  
70  
15  
9.75  
35.20  
46.90  
70.40  
0.00  
37.00  
48.70  
72.20  
1.80  
46.0  
60.7  
90.0  
2.0  
50  
13.00  
19.50  
0.00  
70  
100  
15  
9.75  
11.70  
23.50  
23.50  
0.00  
13.50  
25.30  
25.30  
4.00  
16.6  
31.40  
31.4  
4.5  
20  
13.00  
19.50  
0.00  
35  
35  
VUVE150  
15  
0.00  
0.00  
2.00  
2.3  
15  
8.56  
41.20  
54.90  
82.40  
0.00  
43.20  
56.90  
84.40  
2.00  
53.8  
70.9  
105.3  
2.3  
60  
11.42  
17.13  
0.00  
80  
110  
15  
8.56  
23.80  
36.36  
47.50  
0.00  
25.80  
38.36  
49.50  
2.00  
32.0  
47.7  
61.6  
2.3  
35  
11.42  
17.13  
0.00  
50  
70  
15  
11.40  
15.20  
22.80  
0.00  
47.50  
63.30  
95.00  
0.00  
49.50  
65.30  
97.00  
2.00  
61.9  
81.4  
121.0  
2.3  
70  
90  
125  
15  
11.40  
15.20  
22.80  
0.00  
27.40  
41.87  
54.80  
0.00  
29.40  
43.87  
56.80  
1.80  
36.5  
54.6  
70.8  
2.0  
40  
60  
80  
15  
11.40  
15.20  
22.80  
0.00  
41.20  
54.90  
82.30  
0.00  
43.00  
56.70  
84.10  
1.80  
53.5  
70.7  
104.9  
2.0  
60  
80  
110  
15  
11.40  
15.20  
22.80  
13.70  
27.40  
27.40  
15.50  
29.20  
29.20  
19.1  
36.30  
36.3  
20  
40  
40  
UV-SVN03D-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pre-Start  
Checklist  
Pre-Start-up Checklist  
Before energizing the unit, the following system devices must be checked:  
____ Is the high voltage power supply correct and in accordance with the nameplate ratings?  
____ Is the field wiring and circuit protection the correct size?  
____ Is the low voltage control circuit wiring correct per the unit wiring diagram?  
____ Is the piping system clean/complete and correct?  
____ Is unit serviceable? (See clearance specifications on page 7).  
____ Are all the unit access panels secure and in place?  
____ Is the water flow established and circulating through all the units?  
____ Is the condensate line properly sized, run, trapped and pitched?  
____ Does the indoor blower turn freely without rubbing?  
____ Has all work been done in accordance with applicable local and national codes?  
____ Has heat transfer fluid been added in the proper mix to prevent freezing if required?  
26  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Periodic Maintenance  
Cleaning of the Drain Pan  
!
WARNING  
The following maintenance sugges-  
tions apply to all types of unit ventila-  
tors, chilled water, hot water, split  
systems and electric. Additional infor-  
mation for controls not supplied by  
The Trane Company should be ob-  
tained from the controls manufactur-  
er.  
The unit ventilators drain pan is re-  
movable for periodic cleaning or easy  
access for maintenance/drainage is-  
sues. Use Figure 16, and the steps be-  
low for removing the drain pan.  
Hazardous Service  
Procedures!  
The maintenance and trouble-  
shooting procedures recommend-  
ed in this section of the manual  
could result in exposure to electri-  
cal, mechanical or other potential  
safety hazards. Always refer to  
the safety warnings provided  
throughout this manual concern-  
ing these procedures. When possi-  
ble, disconnect all electrical  
1
2
Turn off power to the unit and re-  
move the front panel.  
Split system unit ventilators include a  
condensing unit and the instructions  
provided with the condensing unit will  
apply to the entire refrigerant system.  
Disconnect the condensate drain  
line from the P-trap.  
3
4
Disconnect fan plug.  
Filters  
power including remote discon-  
nects before servicing. Follow  
proper lockout/tagout procedures  
to ensure the power can not be in-  
advertently energized. When nec-  
essary to work with live electrical  
components, have a qualified li-  
censed electrician or other indi-  
vidual who has been trained in  
handling live electrical compo-  
nents perform these tasks. Failure  
to follow all of the recommended  
safety warnings provided, could  
result in death or serious injury.  
Remove (4) pan clips located at  
each end of the pan’s front.  
The air filters supplied with Trane UV’s  
are specially designed for high lint  
content. Depending upon room condi-  
tions, these filters will normally need  
to be replaced every 4 to 8 weeks. To  
assure proper unit operation, inspect  
the filters monthly and clean or re-  
place as required.  
5
6
7
Slide out fan board.  
Remove drain pan for cleaning.  
When reinstalling, reverse se-  
quence.  
Overloaded filters will reduce unit air  
handling capacity, which may result in  
insufficient heating during the morn-  
ing warm-up period and loss of natural  
cooling capacity during mild weather.  
Filter Replacement  
Slide out fanboard  
Service Access  
The air filter on the vertical unit is lo-  
cated near the bottom of the unit Filter  
sizing may be found on Table G1.  
.
To access the unit for water balancing,  
motor access or other start-up and  
maintenance functions, use one of the  
following methods:  
3
4
1
2
1
2
3
To remove the filters, take-off the  
air section’s front panel.  
1
2
3
Remove the end pocket front  
panel.  
Slide the filter out of the filter rack  
on the bottom of the unit.  
Remove the return air grille by re-  
leasing the mounting screws.  
Figure 16: Removal of drainpan  
Replace old filter with new filter  
and re-attach front panel.  
If there is no shelving or other ob-  
structions, removing the end panel  
may allow more access.  
CAUTION  
Equipment Damage!  
Do not operate unit without filters  
or grilles in place. Failure to do so  
may cause equipment failure  
UV-SVN03D-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
11 Attach new motor to fan shaft  
and reverse steps to complete in-  
stallation.  
CAUTION  
!
WARNING  
Equipment Damage!  
Support the fanboard to prevent  
the deck from sliding too far for-  
ward and falling out of the unit.  
Failure to do so may cause equip-  
ment damage.  
Hazardous Service  
Procedures!  
The maintenance and trouble-  
shooting procedures recommend-  
ed in this section of the manual  
could result in exposure to electri-  
cal, mechanical or other potential  
safety hazards. Always refer to  
the safety warnings provided  
throughout this manual concern-  
ing these procedures. When possi-  
ble, disconnect all electrical  
5
When reinstalling, use the same  
steps in reverse order.  
Motor  
The fan motor is a permanent split ca-  
pacitor type motor with voltage specif-  
ic power. See Table E1 through E3 for  
electrical performance and motor volt-  
age.  
power including remote discon-  
nects before servicing. Follow  
proper lockout/tagout procedures  
to ensure the power can not be in-  
advertently energized. When nec-  
essary to work with live electrical  
components, have a qualified li-  
censed electrician or other indi-  
vidual who has been trained in  
handling live electrical compo-  
nents perform these tasks. Failure  
to follow all of the recommended  
safety warnings provided, could  
result in death or serious injury.  
Table E3: Motor Voltage  
Unit Voltage  
115-60-1  
208-60-1  
230-60-1  
208-60-3  
460-60-3  
265-60-1  
230-60-3  
Motor Voltage  
115-60-1  
Figure 17: Fan board removal for fan/  
motor access  
208/230-60-1  
208/230-60-1  
208/230-60-1  
265-60-1  
265-60-1  
208/230-60-1  
Access to Fanboard & Motor  
If a replacement motor is required, it  
should be ordered from The Trane  
Company. To replace the fan motor,  
complete the following steps:  
The unit ventilator fan board can be re-  
moved for service to the blower motor  
and fan wheels. The fan board must  
also be removed for easier access to  
the unit coils for cleaning and mainte-  
nance. Utilize the following steps for  
proper removal of the fanboard.  
Figure 18: Loosen screws  
6
7
8
9
Complete steps for removal of  
fan board.  
Disconnect the motor ground  
wire.  
1
Turn off power to the unit and re-  
move the front panel.  
Using a 7/16” Allen wrench, loos-  
en the coupling on the fan shaft.  
2
3
4
Disconnect P-trap from drain pan.  
Disconnect fan plug.  
Loosen the screw on the motor  
clamp until it allow the motor to  
be lifted off the base, Figure 18.  
Figure 19: Lift/pull motor forward  
Slide fan board by pulling deck  
forward, Figure 17.  
10 Lift the motor and pull forward  
until fan shaft separates from the  
motor, Figure 19.  
28  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Note: These hydronic valves are de-  
signed and tested for silent operation.  
However, water noise may occur as a  
result of high water velocity. Piping  
noises may also occur in high temper-  
ature (over 212° F) systems with insuf-  
ficient water pressure.  
!
WARNING  
Hazardous Service  
Procedures!  
The maintenance and trouble-  
shooting procedures recommend-  
ed in this section of the manual  
could result in exposure to electri-  
cal, mechanical or other potential  
safety hazards. Always refer to  
the safety warnings provided  
throughout this manual concern-  
ing these procedures. When possi-  
ble, disconnect all electrical  
Note: Do not use petroleum-based or  
mineral oil type boiler additives. Com-  
pounds with a 50% water dilution that  
can be used are diethylene glycol,  
etheylene glycol and propylene glycol.  
Coil Cleaning  
Periodically the hydronic coils should  
be cleaned from dirt accumulation that  
could reduce the unit performance. To  
clean the equipment coil:  
power including remote discon-  
nects before servicing. Follow  
proper lockout/tagout procedures  
to ensure the power can not be in-  
advertently energized. When nec-  
essary to work with live electrical  
components, have a qualified li-  
censed electrician or other indi-  
vidual who has been trained in  
handling live electrical compo-  
nents perform these tasks. Failure  
to follow all of the recommended  
safety warnings provided, could  
result in death or serious injury.  
1
2
3
Remove the unit’s front panel.  
Remove the unit’s front nosing.  
Removed the coil’s solid steel  
front cover.  
4
5
Vacuum the dust/particles from  
the coil face.  
Reverse order for re-installation.  
Modulating Valves  
The valve should be serviced by a  
trained, experienced technician. For  
detailed installation and removal  
steps, refer to Pages 18-20 in this man-  
ual.  
Preventive Maintenance  
A comprehensive preventive mainte-  
nance program should be established  
for a unit ventilator system. The fol-  
lowing are several key elements:  
For general servicing or malfunction,  
follow one of the appropriate steps:  
Inspect the filters monthly. Follow  
the Filter Replacement instruc-  
tions.  
1
2
3
If the valve is leaking, drain system  
OR isolate valve from the system.  
DO NOT remove valve body from  
plumbing.  
Inspect and clean the drain pan  
every three months.  
Ensure the cartridge needs to be  
replaced. If so, follow appropriate  
steps explained for cartridge as-  
sembly removal.  
Check the coils for ‘‘dirt’’ accumu-  
lation every three to six months.  
Clean the coils at least once each  
year.  
If the motor or other internal parts  
of the actuator is damaged, replace  
the entire actuator assembly.  
Inspect the unit ventilator insula-  
tion every three months; thor-  
oughly clean as needed.  
UV-SVN03D-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
Information  
Warranty Information  
Standard Warranty  
The standard unit ventilator warranty is Trane’s parts-only warranty, running 12-months from startup, not to  
exceed 18-months from shipment.  
Extended Warranty  
The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard  
1-year coverage through the fifth year.  
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems  
Group sales territories and must be ordered prior to start-up.  
30  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Checklist  
!
WARNING  
Hazardous Service Procedures!  
The maintenance and trouble shooting procedures recommended in this section of the manual could result in  
exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings pro-  
vided throughout this manual concerning these procedures. When possible, disconnect all electrical power  
including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power  
can not be inadvertently energized. When necessary to work with live electrical components, have a qualified  
licensed electrician or other individual who has been trained in handling live electrical components per these  
tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious in-  
jury.  
If operating difficulties are encountered, refer to page 31 and 32 for probable causes and corrective measures. If suggested  
corrective measures have been taken, and the trouble still persists, contact the control supplier or the local Trane Sales Of-  
fice.  
Problem  
Heating Cooling Cause  
Correction  
X
X
Main power off  
Check fuses  
Room sensor is not properly set  
Reset room sensor temperature  
Start the warm-up cycle earlier in the  
morning to provide appropriate time-  
frame to increase room temperature prior  
to space occupation.  
Room sensor is providing a false reading due  
to walls being cold from the night temperature  
setting.  
X
X
Room too warm  
(outside air temperature is below 35° F)  
Sensor is mounted on a block wall that is  
leaking cold air into the room through the  
mounting holes.  
Relocate sensor.  
Replace malfunctioning component, or  
contact the control’s contractor, or if Trane  
controls, see CNT-SVX04A-EN for more  
information concerning Tracer™ controls.  
Face and bypass damper, or coil valve is  
malfunctioning.  
X
X
Room sensor is not properly set  
Reset room sensor temperature  
Replace malfunctioning component, or  
contact the control’s contractor, or if Trane  
controls, see CNT-SVX04A-EN for more  
information concerning Tracer™ controls.  
Face and bypass damper or coil control valve  
is malfunctioning.  
X
Room too warm  
(outside air temperature is above 35° F)  
Ensure OA damper is in the open  
position.  
X
X
X
OA damper is in the closed position  
Clogged filter  
Replace filter  
Check flow of hot water through the  
control valve.  
Control valve is malfunctioning  
Check the boiler reset schedule to  
determine if the loop temperature can be  
decreased.  
X
X
Boiler  
Room too warm  
Steam  
Check the operation of the control valves  
(outside air temperature is above 35° F)  
Unit utilizes Wall Fin auxiliary radiation:  
The economics of the unit ventilator  
selection dictate that, in most cases, the  
unit will be sized to provide adequate  
X
Outside air temperature is above 60 to 65° F natural (ventilation) cooling without  
outside temperatures up to 60-65 F.  
Above this point, a changeover should be  
made to the mechanical cooling cycle.  
UV-SVN03D-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Checklist  
Problem  
Heating Cooling Cause  
Correction  
X
X
Room sensor is not properly set  
Clogged filter  
Reset room sensor temperature  
Replace filter  
Replace malfunctioning component, or  
contact the control’s contractor, or if Trane  
controls, see CNT-SVX04A-EN for more  
information concerning Tracer™ controls.  
Face and bypass damper, or coil valve is  
malfunctioning.  
X
Room too cool  
Ensure OA damper is in the closed or  
minimum outside air position.  
X
X
X
OA damper is in the open position  
On hot water and steam type units, check  
the boiler pressure or temperature to  
ensure that the requirements are being  
met.  
Boiler pressure or temperature design  
requirements not being met  
Room too cool  
Unit utilizes Wall Fin auxiliary radiation:  
Check the operation of the wall fin  
controls.  
Radiation controls malfunctioning  
X
X
Room sensor is not properly set  
Clogged filter  
Reset room sensor temperature  
Replace filter  
Replace malfunctioning component, or  
contact the control’s contractor, or if Trane  
controls, see CNT-SVX04A-EN for more  
information concerning Tracer™ controls.  
Face and bypass damper, or coil valve is  
malfunctioning.  
X
Room too hot  
Ensure OA damper is in the minimum  
outside air position.  
X
X
OA damper is in the open position  
Check the temperature of the water  
leaving the chiller to ensure that it meets  
design requirements.  
Chiller temperature design requirements not  
being met  
If the motor fails to start, and other motors on Check the unit switch to ensure it is in the  
the same circuit are functioning ON position.  
X
X
Motor  
If the motor fails to start, and other motors on Check for loose switch or motor  
the same circuit are functioning connection.  
32  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
Field Installed Wiring  
120V/1 PH - 3-Speed  
UV-SVN03D-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
End Device Controls  
120V/1 PH - 3-Speed, DX/Hot Water  
34  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
End Device Package  
480V/3 PH - 3-Speed, Chilled Water/Electric Heat (6-Element) -page 1  
UV-SVN03D-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
End Device Package  
480V/3 PH - 3-Speed, Chilled Water/Electric Heat (6-Element) -page 2  
36  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
End Device Package  
120V/1 PH - 3-Speed, 4-Pipe Hot Water/Chilled Water  
UV-SVN03D-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Wiring  
Tracer ZN520  
120V/1 PH - 3-Speed, 4-Pipe Hot Water/Chilled Water  
38  
UV-SVN03D-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UV-SVN03D-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
Date  
UV-SVN03D-EN  
October 2007  
Supersedes  
UV-SVN03C-EN May 2006  
Trane  
A business of American Standard Companies  
Trane has a policy of continuous product and data improvement and reserves the right to change  
design and specifications without notice.  
For more information, contact your local district  
office or e-mail us at [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam CD Player MD CD1 User Manual
TP Link Network Card TL PA201 User Manual
TP Link Network Router TD 8840 User Manual
Trane Air Conditioner TAM7A0B30H21SB User Manual
Triax DVR STR 333 User Manual
Tunturi Waterskis J620P User Manual
ViewSonic Computer Monitor E96f+ User Manual
Viking Outdoor Storage viking User Manual
VocoPro Microphone VHF 3300 User Manual
Weed Eater Blower 530088756 User Manual