Trane Heat Pump WCY024G1 User Manual

WCY-IOM-1D  
18-BB33D8-5  
INSTALLATION  
OPERATION  
MAINTENANCE  
ALL phases of this installation must comply with  
NATIONAL, STATE AND LOCAL CODES  
Model:  
WCY024G1  
WCY030G1  
WCY036G1  
WCY042G1  
WCY048G1  
WCY060G1  
Single Package Heat Pump  
13-14 SEER Convertible  
2 - 5 Ton  
BAYLIFT002A  
LIFTING LUG KIT  
IMPORTANT—ThisDocumentiscustomerpropertyandistoremainwiththisunit. Pleasereturntoserviceinformationpackuponcompletionofwork.  
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING  
WARNING:  
NOTICE  
Warnings and Cautions appear at appro-  
priate locations throughout this manual.  
Read these carefully.  
Indicates a potentially haz-  
ardous situation which, if not avoided, could  
result in death or serious injury.  
WARNING:  
All phases of this installation must comply with the NATIONAL,  
STATE & LOCAL CODES. In the absence of local codes, the  
installation must conform with National Electric Code -- ANSI/  
NFPA 70 or "LATEST REVISION."  
CAUTION:  
Indicates a potentially haz-  
ardous situation which, if not avoided, may  
result in minor or moderate injury. It may also  
be used to alert against unsafe practices  
and where property-damage-only accidents  
could occur.  
Since The Trane Companyhas a policy of continuous product and product data  
improvement, it reserves the right to change design and specification without notice.  
07/02  
© 2002 American Standard Inc. All rights reserved  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A  
(WCY024-060G Models)  
2
SEE NOTE 1  
SEE NOTE 2  
FIELD SUPPLIED  
SUPPORTS  
AT EACH END  
OF CURB  
ROOFING  
ROOF INSULATION  
FIELD SUPPLIED  
CANT STRIP  
ROOF DECK  
FIELD SUPPLIED  
RIGID INSULATION  
ROOF MOUNTING  
CURB  
NOTE 1: The WCY036-042G Models extend  
out past this end of the curb only.  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
NOTE 2: Only the WCY048-060G Models  
extend past both the end and the  
side of the curb as illustrated  
CONVERTING HORIZONTAL TO DOWNFLOW  
3
NOTE  
SUPPLY OPENING  
1. REMOVE THE SCREW NEAREST TO THE  
OPENING AND PULL THE PANEL FIRMLY  
TOWARD THE OUTSIDE OF THE UNIT TO  
DISENGAGE THE BACK ATTACHMENT.  
SHEET METAL  
SCREWS  
HORIZONTAL RETURN  
AIR COVER  
RETURN OPENING  
2. REMOVE RIGHT HAND SCREW AND  
MOVE PANEL TO THE RIGHT OR  
REMOVE BOTH SCREWS.  
HORIZONTAL SUPPLY  
AIR COVER  
3. REMOVE EXTERIOR GASKET MATERIAL.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONAL DATA  
WCY024-060G OUTLINE - BACK  
4
CORNER WEIGHT(LBS)  
W1 W2 W3 W4  
UNIT  
WEIGHT  
MODEL  
A
B
C
D
E
F
G
H
17  
17  
J
K
L
M
10  
10  
14  
N
3
P
WCY024G  
WCY030G  
79  
82  
74  
64  
74  
86  
104  
110  
118  
118  
134  
157  
331  
342  
398  
398  
504  
502  
21  
21  
25-3/8  
24-3/8  
56-1/2  
64  
36 29-3/16 18-9/16 11-1/16 6-9/16 6-13/16  
36 29-1/16 18-9/16 11-1/16 6-9/16 11-1/8  
17-1/2  
17-1/2  
20  
4-7/16  
8-3/4  
WCY036G 110  
WCY042G 110  
WCY048G 149  
WCY060G 126  
82  
88  
19-1/4 27-1/2  
19-1/4 27-1/2  
24-1/4 28-1/2  
3
82  
88  
104  
98  
117  
121  
65-1/8  
45  
33-1/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16  
3-1/2 8-5/16  
20  
28  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONAL DATA  
WCY024-060G OUTLINE - FRONT  
5
CLEARANCE TO  
RECOMMENDED SERVICE CLEARANCE  
COMBUSTIBLE MATERIAL  
BACK  
* 6.0"  
BOTTOM  
BACK  
0.0"  
1.0"  
LEFT SIDE  
RIGHT SIDE  
FRONT SIDE  
30.0"  
24.0"  
30.0"  
LEFT SIDE  
RIGHT SIDE  
FRONT SIDE  
TOP  
6.0"  
6.0"  
* 18" WITH FRESH AIR ACCESSORY  
* 30" WITH ECONOMIZER  
12.0"  
36.0"  
MODEL  
A
B
36  
36  
45  
C
D
WCY024G  
WCY030G  
56-1/2  
64  
29-3/16 12-15/16  
29-3/16 14-1/2  
33-3/8 14-13/16  
WCO36G  
WCY042G  
WCY048G  
WCY060G  
65-1/8  
From Dwg. 21D664  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REQUIRED CLEARANCE FOR UNIT INSTALLATION  
AND ROOF PENETRATION HOLE SIZE REQUIRED  
6
D
A
SERVICE  
CLEARANCE  
LINES  
SERVICE  
CLEARANCE  
LINES  
SUPPLY AIR  
B
RETURN AIR  
C
SIDE RAIL  
WOOD NAILER  
SERVICE CLEARANCE & PENETRATION DIMENSIONS  
HOLE IN ROOF  
MODEL NO.  
WCY024-030G  
WCY036-042G  
WCY048-060G  
A
B
C
D
E
F
30" 30" *12" 24" 36" 25"  
30" 30" *12" 30" 44" 25"  
42" 30" *12" 36" 50" 25"  
E
F
* 18" WITH FRESH AIR ACCESSORY  
* 30" WITH ECONOMIZER  
LOCATIONS AND RECOMMENDATIONS  
These units are designed for outdoor installation. For proper instal-  
lation, the following recommendations must be considered.  
AVOID LOCATING THE UNIT WHERE SNOW TENDS TO DRIFT.  
This will reduce the times when it is necessary for the customer to  
remove the snow from around the unit. MAKE CERTAIN THE  
CUSTOMER KNOWS THAT SNOW ACCUMULATIONS SHOULD  
BE REMOVED FROM THE SIDES OF THE UNIT FOR BEST  
EFFICIENCY.  
NOTE: Unit shipped for horizontal installation. Convert to  
downflow per instruction.  
The discharge air from the condenser fans must be unrestricted for  
a minimum of 3 feet above the unit.  
A snow drift barrier may be installed around the unit to prevent a  
build up of snow on the sides of the unit. The barrier should be of  
sufficient distance from the unit to prevent restriction of airflow to  
and from unit.  
Roof Mounting Curb (field assembled BAYCURB030A and  
BAYCURB033A, BAYCURB034A)orafieldfabricatedcurbmustbe  
in place before unit is hoisted to the roof.  
LOCATE THE UNIT SO THAT THE WATER VAPOR THAT DIS-  
CHARGESUPWARDDURINGDEFROSTDOESNOTCONDENSE  
ON WINDOWS AND FOG THEM OR CAUSE ICICLES TO FORM  
ON OVERHANGS.  
Roof Mounting Curb (frame) must be installed on a flat, level  
section of the roof (max. of 1/4" per foot pitch), providing a level  
mounting surface for the unit. In addition, provide sufficient  
height above the roof to prevent water from entering unit.  
1. Be sure the mounting curb spans structural members (trusses)  
of the roof, thereby providing sufficient support for weight of the  
unit, curb and duct(s) plus any accessories (factory or field  
installed). See Figures 1, 2, 3, 4, 5, 6, 7, 8, 9,10,11 and 12.  
In locations where deep snows are encountered,RAlSE THE UNlT  
AMINIMUMOF12"OFFTHEROOF,DECKORSLAB—thechance  
of the coil being blocked with snow will be reduced. The water that  
occurs during the defrost has a better chance of flowing from the  
vicinity of the unit.  
NOTE: If any internal accessories are to be added to the unit it  
should be done at the shop if at all practical.  
Roof Mounting Curb used with WCY—F models is approximately  
14" high. This is normally sufficient height to prevent snow blockage  
and additional clearance is not necessary.  
2. Unit should be positioned so Roof-Run-Off water does not pour  
directly on unit.  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Access and service clearances for the unit must be given careful  
consideration when locating the duct entrance openings. Fig-  
ures 6 and 8 provide unit dimensions.  
3. For “Roof Top Application,” unit must be elevated above roof with  
a mounting Curb or Frame.  
4. Exhaust vents or other sources of contaminated air should not be  
near unit air inlet if outside air is to be introduced as a make-up  
air or the economizer ventilation feature is to be used.  
12. All fabricated outdoor ducts should be as short as possible.  
13. Be sure the hole in the structure for the ducts is large enough to  
accommodatethefabricatedductsandtheinsulationsurrounding  
them. (See Figure 6.)  
5. Check the handling facilities to insure the safety of personnel and  
the unit(s).  
6. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID PER-  
SONAL INJURIES AND/OR DAMAGE TO EQUIPMENT.  
CLEARANCES  
1. The recommended clearances for single-unit installations are  
illustrated in Figures 5 and 6. These minimum requirements are not  
only an important consideration when determining unit placement,  
but they are also essential to ensure adequate serviceability,  
maximum capacity, and peak operating efficiency.  
7. The unit must be mounted level for proper drainage of defrost  
water through the holes in the base pan.  
8. Flexible duct connectors must be of a flame retardant material. All  
duct work outside of the structure must be insulated and weath-  
erproofed in accordance with local codes.  
2. Any reduction of the unit clearances indicated in this illustration  
may result in condenser coil starvation, or the recirculation of warm  
condenser air. Actual clearances which appear to be inadequate  
should be reviewed with a local sales engineer.  
9. Roof flashing must be installed to seal the roof curb cavity and  
must conform to local building codes.  
IMPORTANT!: To convert to downflow remove covers from  
thedownflowsupplyandreturnairopeningsandplacethem  
over the horizontal supply and return air openings (painted  
side out) and secure with sheet metal screws.  
10. Holes through exterior walls must be sealed in accordance with  
local codes.  
INSTALLATION  
UNIT SUPPORT  
If unit is to be roof mounted, check building codes for weight  
distribution requirements. Refer to accessory roof curb mounting  
instructions. Check unit nameplate for supply voltage required.  
Determine if adequate electrical power is available. Refer to speci-  
fication sheet.  
IMPORTANT!: DO NOT LIFT THE UNIT WITHOUT TEST-  
LIFTING FOR BALANCE AND RIGGING.DO NOT LIFT THE  
UNIT IN WINDY CONDITIONS OR ABOVE PERSONNEL. DO  
NOT LIFT THE UNIT BY ATTACHING A CLEVIS, HOOKS,  
PINS OR BOLTS TO THE UNIT CASING, CASING HARD-  
WARE, ANGLES, TABS OR FLANGES. FAILURE TO OB-  
SERVE THESE WARNINGS MAY RESULT IN EQUIPMENT  
DAMAGE.  
LOCATION AND CLEARANCES  
Installation of the unit should conform to local building codes or, in  
the absence of local codes, to the ANSI/NFPA No. 70-1987 National  
Electrical Code or “Latest Revision.” Canadian installations must  
conform to CSA and local codes.  
4. When the curb and air ducts have been properly installed, the unit  
is ready to be hoisted to the roof and set in position.  
Select a location that will permit unobstructed airflow into the  
condenser coil and away from the fan discharge and permit unob-  
structed service access into the compressor compartment. Sug-  
gested airflow clearances and service clearances are given in  
Figure 5.  
IMPORTANT!: “Spreader Bars” must be used when  
hoisting unit.  
5. IMPORTANT: The unit must be lowered into position P.V.C.  
rubber tape on the curb flange permits the unit to be  
repositioned if required without destroying the P.V.C. rub-  
ber seals affixed to mounting curb.  
PLACING AND RIGGING  
1. Before preparing the unit for lifting, check the outline drawing for  
center of gravity for lifting safety. Because of placement of  
internal components, the unit weight may be unevenly distrib-  
uted . Approximate unit weights are given in outline drawing on  
page 3.  
6. PLACING UNIT ON MOUNTING CURB—The unit is designed  
with a perimeter drip lip that is lower than the unit base ban, see  
Figure 7 insert “A”.  
7. Position the unit drip lip down over and in contact with the outside  
corner of the curb, as illustrated in Figure 7 insert “A”. Continue  
to lower unit on top of curb, with the unit drip lip astraddle and in  
contact with both the end and side rail of curb, the unit is now  
resting on top of curb.  
NOTE: Accessory BAYLIFT002A Four (A) lifting lugs are recom-  
mended for rigging the unit for hoisting. See Figure 7 insert “B”.  
2. Insert the four lifting lugs in openings provided in drip lip on  
perimeter of unit. See Figure 7 insert “B”.  
8. Takethetwo(2)holddownbracketsshippedwithcurbandsecure  
unit to curb with hold down brackets as illustrated in Figure 8  
insert “A”.  
3. Before hoisting the unit, be sure that the proper method of rigging  
is used, with straps or slings and spreader bars for protection  
during lifting.  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
SPREADER BARS  
OUTDOOR COIL  
END OF UNIT  
BASE OF UNIT  
REST ON TOP OF  
CURB RAILS  
DRIP LIP ON  
PERIMETER OF UNIT  
“B”  
UNIT CORNER  
DRIP LIP  
DIMPLE  
BAYLIFT002A  
LIFTING LUGS  
CURB CORNER  
SEE DETAIL “A”  
GASKET SEAL  
“A”  
NOTE: The inner perimeter of the Drip Lip on all  
units should be flush with the outer perimeter  
of the curb on the two sides shown here. See  
Figure 2 for the location of the unit overhang  
on the WCY036-060G Models with  
BAYCURB030A.  
8
EXISTING  
SHEET METAL  
SCREW  
HOLD-DOWN  
BRACKET WITH  
CURB  
“A”  
FLANGE OF  
CURB  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
ROOFTOP -- UNITS  
4. Place the unit on the frame or roof curb. Refer to Figures 9 or  
10.  
For roof top applications using a field fabricated frame and ducts,  
use the following procedure:  
5. Secure the unit to the frame or roof curb.  
1. The frame must be located and secured by bolting or welding to  
the roof. Flashing is required.  
6. Insulate any ductwork outside of the structure with at least two (2)  
inches of insulation and then weatherproof. There must be a  
weatherproof seal where the duct enters the structure.  
2. The hole in the roof must be prepared in advance of installing the  
unit.  
7. Complete the installation according to the instructions in the  
following sections of this manual.  
3. Secure the ducts to the roof.  
TYPICAL ROOFTOP APPLICATIONS WITH FRAME  
(WCY024-060G MODELS)  
9
RETURN AIR SUPPLY AIR  
WEATHER-PROOF  
DUCT  
ROOF FLASHING  
ANGLE IRON  
FRAME  
TYPICAL ROOFTOP APPLICATION WITH FRAME  
(WCY024-060G MODELS)  
0
WEATHER-PROOF  
DUCT  
ROOF FLASHING  
SUPPLY AIR  
ROOF FLASHING  
RETURN AIR  
ANGLE IRON  
FRAME  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
GROUND LEVEL -- HORIZONTAL UNITS  
2. Attach the supply and return air ducts to the unit.  
For ground level installations, the unit should be positioned on a pad  
the size of the unit or larger. The unit must be level on the pad. The  
pad must not come in contact with the structure (See Figure 11.) Be  
sure the outdoor portion of the supply and return air ducts are as  
short as possible.  
3. Insulate any ductwork outside of the structure with at least 2  
inches of insulation and weatherproof. There must be a weath-  
erproof seal where the duct enters the structure.  
4. Complete the installation according to the instructions in the  
following sections of this manual.  
Proceed with the installation as follows:  
1. Place the unit on the pad and the five (5) rubber isolators  
provided.  
TYPICAL GROUND LEVEL APPLICATION  
(WCY024-060G MODELS)  
q
OUTDOOR AIR  
DISCHARGE  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
SIDING  
OUTDOOR AIR  
INTAKE  
SUPPORT PAD  
FOUNDATION  
EXTERIOR  
WALL  
INSULATE  
WEATHERPROOF  
OR RAIN SHIELD  
ISOLATORS  
(1 PER CORNER  
AND 1 UNDER  
FLEXIBLE DUCT  
CONNECTORS  
UNIT CONTROL BOX)  
2046.eps  
DUCTWORK  
ATTACHING DOWNFLOW DUCTWORKTOROOFCURB  
ATTACHING HORIZONTAL DUCTWORK TO UNIT  
Supply and return air flanges are provided on the roof curb for easy  
duct installation. All ductwork must be run and attached to the curb  
before the unit is set into place.  
All conditioned air ductwork should be insulated to minimize heat-  
ing and cooling duct losses. Use a minimum of two (2) inches of  
insulation with a vapor barrier. The outside ductwork must be  
weatherproofed between the unit and the building.  
Follow these guidelines for ductwork construction:  
When attaching ductwork to a horizontal unit, provide a flexible  
watertight connection to prevent noise transmission from the unit to  
the ducts. The flexible connection must be indoors and made out  
of heavy canvas.  
Connections to the unit should be made with three-inch canvas  
connectors to minimize noise and vibration transmission.  
Elbows with turning vanes or splitters are recommended to mini-  
mize air noise and resistance.  
The first elbow in the ductwork leaving the unit should be no closer  
than two feet from the unit, to minimize noise and resistance.  
NOTE: Do not draw the canvas taut between the solid ducts.  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUCT ATTACHMENT METHODS  
w
AIR PROOF  
THIS SEAM  
UNIT BASE  
AIR PROOF  
THIS SEAM  
UNIT BASE  
UNIT EXTERIOR  
FIELD DUCT  
FIELD  
DUCT  
WEATHERPROOF  
THIS SEAM  
UNIT DUCT  
FLANGE  
UNIT DUCT  
FLANGE  
UNIT DUCT FLANGE  
FIELD DUCT  
UNIT BASE  
AIR PROOF  
THIS SEAM  
UNIT EXTERIOR  
UNIT DUCT  
FLANGE  
UNIT DUCT FLANGE  
WATERPROOF SEAM  
UNIT DUCT  
FLANGE  
WITH BUTYL OR  
SILICONE  
WEATHERPROOF  
THIS SEAM  
UNIT BASE  
FIELD DUCT  
NOT RECOMMENDED  
FIELD DUCT  
FIELD DUCT  
DOWNFLOW  
UNIT EXTERIOR  
The following warning complies with State of California law, Proposition 65.  
WEATHERPROOF  
THIS SEAM  
UNIT DUCT  
FLANGE  
FIELD DUCT  
WARNING:  
This product contains  
fiberglass wool insulation! Fiberglass dust and ceramic  
fibers are believed by the State of California to cause  
cancer through inhalation. Glasswool fibers may also  
cause respiratory, skin, or eye irritation.  
HORIZONTAL  
CONDENSATE DRAIN PIPING  
A 3/4-inch female NPT condensate drain connection is pro-  
vided on the evaporator access panel end of the unit. See  
Figure4. Provideatrapandfillitwithwaterbeforestartingthe  
unittoavoidairfrombeingdrawnthrough. Followlocalcodes  
and standard piping practices when running the drain line.  
Pitch the line downward away from the unit. Avoid long  
horizontal runs. See Figure 13.  
eTYPICAL CONDENSATE DRAIN PIPING  
3
/
4" PVC OR COPPER  
TUBING AND FITTINGS  
NOTE: Do not use reducing fittings in the drain lines. The  
condensate drain must be:  
Made of 3/4" pipe size.  
1-1/2" MIN.  
Pitched 1/4" per foot to provide free drainage to  
convenient drain system.  
Trapped.  
Must not be connected to closed drain system.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FILTER INSTALLATION  
TABLE 1  
AIR FILTERS  
NOMINAL  
FILTER*  
(Sq Ft) SIZE RESISTANCE  
FILTER  
UNIT  
CFM  
800  
FiltersaretobeusedwiththeWCY024-060Gheating/cooling  
units. Thebasicunitdoesnothavefiltersinit. However,afilter  
frame accessory is offered that will allow filters to be installed  
within the unit.  
WCY024G  
WCY030G  
WCY036G  
WCY042G  
WCY048G  
WCY060G  
2.67  
3.33  
4.00  
4.67  
5.33  
6.67  
0.05  
0.05  
0.05  
0.05  
0.05  
0.05  
1000  
1200  
1400  
1600  
2000  
Otherwise a filter rack must be installed by the installer in the  
duct work.  
Affix the filter label supplied with the unit adjacent to the filter  
area.  
*Filters must be installed in the return air system. The above  
square footages are based on 300 F.P.M. face velocity. If  
permanent filters are used, size per mfg. recommendation  
with clear resistance of 0.05"WC.  
ELECTRICAL WIRING  
CONTROL WIRING (CLASS II)  
ELECTRICAL CONNECTIONS  
Low voltage control wiring should not be run in conduit with power  
wiring unless Class 1 wire of proper voltage rating is used. Route  
the thermostat cable or equivalent single leads of No. 18 AWG  
colored wire from the thermostat subbase terminals through the  
rubber gromment on the unit. See Figure 5 for the control entry  
location. Make connections as shown on the unit wiring diagram  
and in Figure 14.  
Electrical wiring and grounding must be installed in accordance with  
local codes or, in the absence of local codes, with the National  
Electrical Code ANSI/NFPA 70, Latest Revision.  
ELECTRICAL POWER  
It is important that proper electrical power be available for the unit.  
Voltage variation should remain within the limits stamped on the unit  
nameplate.  
Do not short thermostat wires since this will damage the control  
transformer.  
DISCONNECT SWITCH  
Provide an approved weather-proof disconnect either on the side of  
the unit or within close proximity and within sight of the unit.  
Recommended wire sizes and lengths for installing the unit thermo-  
stat are provided in Table 2. The total resistance of these low  
voltage wires must not exceed one (1) ohm. Any resistance in  
excess of 1 ohm may cause the control to malfunction because of  
the excessive voltage drop  
OVER CURRENT PROTECTION  
The branch circuit feeding the unit must be protected as shown on  
the unit rating plate.  
TABLE 2  
POWER WIRING  
THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH  
The power supply lines must be run in weathertight conduit to the  
disconnect and into the bottom of the unit control box. Provide strain  
relief for all conduit with suitable connectors.  
WIRE SIZE  
MAXIMUM LENTGH (Ft)  
18  
16  
14  
75  
125  
200  
Provide flexible conduit supports whenever vibration transmission  
may cause a noise problem within the building structure.  
Be sure all connections are made tight. See Figure 14.  
NOTES: For branch circuit wiring (main power supply to unit  
disconnect), wire size for the length of run should be determined  
using the circuit ampacity found on the unit nameplate and the  
N.E.C.  
For more than 3 conductors in a raceway or cable, see the  
N.E.C. for derating the ampacity of each conductor.  
THERMOSTAT HEAT ANTICIPATOR  
The thermostat heat anticipators should be set to equal the amper-  
age draw of the W1 thermostat circuit.  
IMPORTANT: Upon completion of wiring check all electrical  
connections,includingfactorywiringwithintheunit. Makesure  
all connections are tight. Replace and secure all electrical box  
covers and access doors before leaving the unit or turning on the  
power to the unit.  
GROUNDING: THEUNITMUSTBEELECTRICALLYGROUNDED  
IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL  
ELECTRIC CODE.  
NOTE: Ground the unit internally as provided. See wiring  
diagram for location.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
After all electrical wiring is complete, set the thermostat system  
switch in the OFF position so that the compressor will not run  
andthenapplypowerbyclosingthesystemmaindisconnectswitch.  
This will activate the compressor sump heat. Do not change the  
Thermostat System Switch until power has been applied long  
enough to evaporate any liquid R-22 in the compressor. It is  
recommended that the sump heater be energized for eight (8) hours  
prior to starting.  
WCY-G FIELD WIRING DIAGRAM  
r
NOTES:  
1. FUSED DISCONNECT SIZE, POWER WIRING AND  
GROUNDING OF EQUIPMENT MUST COMPLY WITH  
CODES.  
2. BE SURE POWER SUPPLY AGREES WITH  
EQUIPMENT AND HEATER NAMEPLATE.  
3. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM  
CONDUCTOR.  
4. SEE HEATER NAMEPLATE FOR CURRENT RATING  
OF HEATER USED.  
5. SEE UNIT AND HEATER DIAGRAM FOR  
ELECTRICAL CONNECTION DETAILS.  
6. IF ELECTRIC HEATER ACCESSORY IS NOT  
INSTALLED OMIT THE ELECTRIC HEATER,  
ASSOCIATED POWER WIRES AND THE ‘W’ AND ‘X2’  
THERMOSTAT WIRES.  
7. FIG. 3 DEMONSTRATES CONNECTION OF THE  
OUTDOOR THERMOSTAT ACCESSORY ONLY. FOR  
FURTHER UNIT CONNECTION DETAILS REFER TO  
THE OTHER FIGURES.  
8. THE 41A(BR) WIRE IS FIRST STAGE ELECTRIC  
HEAT. IF THE ELECTRIC HEATER ACCESSORY  
HAS TWO HEATING STAGES THE 41C(BR) WIRE IS  
SECOND STAGE ELECTRIC HEAT.  
9. WHEN THE BAYECON054A OR –055A ECONOMIZER  
IS INSTALLED THE BAYRLAY003 RELAY  
ACCESSORY KIT IS REQUIRED TO INTERFACE  
THE ECONOMIZER TO THE HEAT PUMP FOR  
PROPER SYSTEM OPERATION. WHEN THE  
BAYECON054B OR –055B OR 073A ECONOMIZER IS  
INSTALLED, THE BAYRLAY004A RELAY  
ACCESSORY KIT IS REQUIRED TO INTERFACE  
THE ECONOMIZER TO THE HEAT PUMP FOR  
PROPER SYSTEM OPERATION.  
10. THE BAYSTAT033A OUTDOOR THERMOSTAT  
ACCESSORY KIT CONTAINS A THERMOSTAT AND  
A RELAY. THE RELAY IS NOT REQUIRED TO BE  
USED IN THIS APPLICATION.  
From Dwg. 756978 Rev. 5  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START - UP  
PRE-START QUICK CHECKLIST  
To start the unit in the cooling mode, set the thermostat system  
switch to COOL and move the thermostat COOL indicator to a  
setting below room temperature. The condenser (outdoor) fan  
motor compressor and evaporator (indoor) fan motor will operate  
automatically.  
Is the unit properly located and level with the proper clearance?  
See Figure 5.  
Is the duct work correctly sized, run, taped, insulated, and  
weatherproofed with proper unit arrangement. See Ductwork  
Installation section.  
OPERATING PRESSURES  
Is the condensate line properly sized, run, trapped, and pitched?  
After the unit has operated in the cooling mode for a short period of  
time, install pressure gauges on the gauge ports of the discharge  
and suction line valves. Check the suction and discharge pressures  
and compare them to the normal operating pressures provided in  
the unit's SERVICE FACTS.  
Is the filter of the correct size and number? Is it clean and in place?  
Is the wiring properly sized and run according to the unit wiring  
diagram?  
NOTE: Do not use the pressures from the unit's SERVICE FACTS  
to determine the unit refrigerant charge. The correct charge is  
shown on the unit nameplate. To charge the system accurately,  
weigh in tIhe charge according to the unit nameplate.  
Are all the wiring connections, including those in the unit, tight?  
Has the unit been properly grounded and fused with the recom-  
mended fuse size? See Wiring Data.  
VOLTAGE  
Is the thermostat level, correctly wired, well located, and set for the  
With the compressor operating, check the line voltage at the unit.  
The voltage should be within the range shown on the unit name-  
plate. If low voltage is encountered, check the size and length of the  
supply line from the main disconnect to the unit. The line may be  
undersized for the length of the run.  
proper heat anticipation?  
Have the air conditioning systems been checked at the service  
ports for charge and leak tested if necessary?  
Do the condenser fan and indoor blower turn free without rubbing,  
and are they tight on the shafts?  
COOLING SHUT DOWN  
Place the system selector in the OFF position or reset thermostat at  
a setting above room temperature.  
Has the indoor blower speed been determined and the proper  
speed been set? See the Unit Wiring Diagram.  
Do not de-energize the main power disconnect except when unit it  
to be serviced. Power is required to keep the heat pump compres-  
sor warm and boil off refrigerant in the compressor.  
Has all work been done in accordance with applicable local and  
national codes?  
STARTING THE UNIT IN THE HEATING MODE  
NOTE: See the section on "Sequence of Operation" for a descrip-  
tion of the heat pump heating operating sequence.  
Are all covers and access panels in place to prevent air loss and  
safety hazards?  
STARTING THE UNIT IN THE COOLING MODE  
Check to make sure all grilles an registers are open an all unit  
access doors are closed before start-up.  
CAUTION: Before starting the system on the cooling cycle, turn the  
thermostat switch to OFF and close the unit disconnect switch. This  
procedure energizes the compressor crankcase heater, vaporizing  
any liquid refrigerant in the crankcase. This is a precaution against  
foaming at startup which could damage the compressor bearings.  
Allow the heater to operate a minimum of eight (8) hours.  
Slowly set the thermostat above rom temperature until achieving a  
first stage call for heat and place the fan switch in the AUTO or ON  
position.  
HEATING SHUT-DOWN  
Place the system selector switch at OFF or place the heating  
selector lever at a setting below room temperature.  
NOTE: See the section on "Sequence of Operation" for a descrip-  
tion of the cooling operating sequence.  
WARNING:  
DO NOT OPERATE THE UNIT  
WITHOUT THE EVAPORATOR FAN ACCESS PANEL IN  
PLACE. REINSTALL THE ACCESS PANEL AFTER  
PERFORMING ANY MAINTENANCE PROCEDURES ON THE  
FAN. OPERATING THE UNIT WITHOUT THE ACCESS  
PANEL PROPERLY INSTALLED MAY RESULT IN SEVERE  
PERSONAL INJURY OR DEATH.  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEQUENCE OF OPERATION  
GENERAL  
thermostat. When placed in the emergency heat position, it will  
disable the compressor, bypass the outdoor thermostats, if pro-  
vided, and engage the supplementary electric heaters and indoor  
fan.  
Operation of the unit heating and cooling cycles is automatic for  
HEAT and COOL functions. (The optional automatic changeover  
thermostat, when in the AUTO position, automatically changes to  
heat or cool with sufficient room temperature change.) The fan  
switch can be placed in either the ON position, causing continuous  
evaporator (indoor) fan operation, or the AUTO position causing fan  
operation to coincide with heating or cooling run cycles.  
DEMAND DEFROST OPERATION  
During the heating cycle, the outdoor coil may require a defrost  
cycle which is determined by the demand defrost control (DFC).  
This control continuously measures the outdoor coil temperature  
(CBS) and the outdoor ambient temperature (ODS-B) and calcu-  
lates the difference or delta-T measurement. When the calculated  
delta-T is met, the demand defrost control (DFC) opens the circuit  
to the outdoor fan motor (ODM) and energizes the switch-over valve  
(SOV), placing the unit in the cooling mode to defrost the outdoor  
coil. The outdoor coil temperature sensor (CBS) terminates the  
defrost cycle, or times off after twelve minutes in defrost, the (DFC)  
energizes the outdoor fan motor (ODM) and twelve seconds later  
de-energizes the (SOV), which returns the unit to the heating mode.  
Supplementary electric heat, if provided, is brought on to control  
indoor temperature during the defrost cycle.  
COOLING MODE  
(NOTE: TSH & TSC are contacts internal to the indoor thermostat.)  
With the disconnect switch in the ON position, current is supplied to  
the compressor crankcase heater and control transformer. (The  
outdoor fan relay (ODF) relay is energized through normally closed  
contacts on the defrost timer control (DFC) on the 460V and 600V  
units only.) The cooling cycle is enabled through the low voltage  
side of the control transformer to the “R” terminal on the indoor  
thermostat. With the system switch in the AUTO position and TSC-  
1 contacts closed, power is supplied to the “O” terminal on the  
indoor thermostat to the switchover valve coil (SOV). This energizes  
the switch-over valve (SOV) and places it in the cooling position (it  
is in the heating position when de-energized).  
ICM FAN MOTOR ADJUSTMENTS  
If the airflow needs to be increased or decreased, see the Airflow  
Table in the Service Facts. Information on changing the speed of the  
blower motor is in the Blower Performance Table.  
Blower speed changes are made on the ICM Fan Control mounted  
in the control box. The ICM Fan Control controls the variable speed  
motor.  
There is a bank of 8 dip switches, (See Figure 15), located at the  
upper right side of the board. The dip switches work in pairs to match  
the cooling/heat pump airflow (CFM/TON), Fan off-delay options,  
and electric heat airflow adjustment. The switches appear as shown  
in Figure 15.  
When the indoor temperature rises 1-1/2 degrees, TSC-2 contacts  
close, supplying power to the “Y” terminal on the indoor thermostat,  
and to the compressor contactor (CC). This starts the outdoor fan  
motor and compressor. The TSC-2 contacts also provide power to  
the “G” terminal which provides power to the fan relay (F) starting  
the indoor fan motor.  
HEATING MODE  
With the disconnect switch in the “ON” position, current is supplied  
to the compressor crankcase heater and control transformer. (The  
outdoor fan relay (ODF) is energized through normally closed  
contacts on the defrost timer control (DFC) on the 460V and 600V  
units.) Starting at the “R” terminal on the indoor thermostat, current  
goes through the system switch (which is in “AUTO” position) to the  
TSH-1 contacts. When closed, these contacts supply power to  
terminal ”Y” on the indoor thermostat as well as to the heating  
anticipator. The switch-over valve will not energize because of the  
high resistance of the heating anticipator in the thermostat. Power  
is provided from “Y” to the compressor contactor (CC) which starts  
the compressor and outdoor fan motor. The indoor thermostat  
contact TSH-1 also provides power to “G” terminal on the indoor  
thermostat energizing the fan relay (F), which starts the indoor fan  
motor.  
t
ICM FAN CONTROL  
CFM  
DIP  
SELECTION  
SWITCHES  
LIGHT  
SUPPLEMENTARY HEAT  
The supplementary electric heat is brought on when the indoor  
temperature drops 1-1/2 degrees below the thermostat setting.  
TSH-2 contacts close providing power to the “W” terminal on the  
indoor thermostat and to the supplementary heater control circuit.  
NOTE: The fan relay (F) must have been energized. An outdoor  
thermostat may have been added to disallow the second stage (if  
provided) of electric heat above a selected outdoor temperature. If  
the outdoor temperature falls below the setting on the outdoor  
thermostat, this additional heater stage will come on. When the  
outdoor air temperature rises, and the outdoor T-stat setpoint is  
reached, the system will revert back to first stage electric heating.  
When the indoor ambient is satisfied, TSH-2 contacts will open and  
the unit will revert back to the compressor only heating mode and  
then off. For emergency heat (use of supplementary electric heat  
only), an emergency (EMERG) heat switch is provided within the  
DIP SWITCHES (TYPICAL SETTINGS)  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEMAND DEFROST SYSTEM  
DEFROST CONTROL  
The demand defrost control measures heat pump outdoor ambient  
temperature with a sensor located outside the outdoor coil.  
PIN IDENTIFICATION  
FRC_DFT  
A
second sensor located on the outdoor coil is used to measure the  
coil temperature. The difference between the ambient and the  
colder coil temperature is the difference or delta-T measurement.  
This delta-T measurement is representative of the operating state  
and relative capacity of the heat pump system. By measuring the  
change in delta-T, we can determine the need for defrost. The coil  
sensor also serves to sense outdoor coil temperature for termina-  
tion of the defrost cycle.  
TEST_COMMON  
TST  
FAULT DETECTION  
A fault condition is indicated by the flashing light on the defrost  
control inside the heat pump control box.  
DEFROST CONTROL CHECKOUT  
Normal operation requires:  
a. LED on board flashing 1 time/second.  
In normal operation, the defrost control light will flash once each  
second. If the light is flashing more than once per second or not-at-  
all, refer to the service manual for that unit.  
b. 24V AC between R & B  
c. 24V AC between Y & B with unit operating  
PIN IDENTIFICATION (See Figure)  
1. TEST_COMMON (Shorting any of the other pins to this pin  
causes the function of the other pin to be executed. Leaving this  
pin open results in the normal mode of operation.)  
d. Defrost initiation when FRC_DFT pin is shorted to  
TEST_COMMON pin.  
If a defrost control problem is suspected, proceed to DEMAND  
DEFROST CONTROL CHECKOUT in this Service Facts.  
2. TST = Test (Shorting TEST_COMMON to this pin speeds up  
all defrost board timings.)  
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin  
for two (2) seconds to initiate a forced defrost. Remove the short  
after defrost initiates.)  
Do NOT connect 24 VAC to T1  
(ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.  
WARNING:  
PROCEDURE FOR TESTING SENSORS  
TEMP °F  
86  
81  
75  
70  
65  
59  
55  
50  
45  
41  
36  
32  
25  
19  
14  
10  
5
RESISTANCE  
7.85K  
Measure the temperature the subject sensor is exposed to. If the sensor is mounted on a  
tube, place the lead on an Annie A-8 (or equiv.) temperature tester on the same tube near  
the sensor and insulate the bulb.  
8.85K  
10.24K  
11.59K  
13.14K  
15.32K  
16.93K  
19.41K  
22.20K  
24.76K  
28.45K  
31.84K  
37.50K  
46.44K  
53.94K  
57.64K  
67.06K  
78.05K  
Unplug the sensor and measure the resistance with a good quality ohmmeter (Simpson  
260 or equiv.). Read the value as quickly as possible to prevent the meter current from  
changing the resistance reading.  
Using the chart on the right, locate (as close as possible) the actual sensor temperature.  
The measured resistance should be relatively close to the resistance value shown in the  
chart.  
Example:  
Sensor temp.  
= 19°F.  
Measured Resistance  
= 46K ohms  
This sensor is good since the measured value is relatively close to the  
chart value.  
0
FLASH RATE INDICATIONS:  
1 — Flash/Second = Normal operation.  
2 — Flashes/Second = Fault A (Low T) i.e.: Inoperative compressor, loss of charge, open ambient sensor, shorted coil sensor.  
3 — Flashes/Second = Fault B (20 defrosts terminated on time)  
Fault C (High T) i.e.: SOV stuck in heating, shorted ambient sensor, open coil sensor, closed TXV,  
OD motor failure, OD fan on in defrost, undercharged unit.  
4 — Flashes/Second = Fault A & C or A & B  
For additional information consult Pub. No. 34-1001 Heat Pump Defrost Controls.  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEMAND DEFROST CONTROL CHECKOUT  
SYMPTOMS  
CHECKS  
YES/NO  
ACTIONS  
1. LED off.  
N
Y
Repair low voltage wiring.  
Complete Check #2.  
1. 24V R-B & Y-B at board, with unit running?  
N
Y
Y
Replace defrost control.  
LED is bad but control will still function.  
Remove short.  
2.Short FRC_DFT pin to TEST_COMMON pin.  
Is defrost cycle initiated?  
2. LED flashing very rapidly (greater  
than 4 times/sec) or appears to be on  
continuously.  
TEST_COMMON pin shorted to TST pin?  
N
N
Replace defrost control.  
3. Control does not initiate a normal  
defrost.  
OD Temp. below 49°F.  
OD Coil temp. below 35°F.?  
"Delta" T increasing?  
Check refrigerant circuits for balanced  
distribution of refrigerant if OD coil is  
frosting and delta T is not increasing  
N
Y
N
Y
Refer to SYMPTOM #1.  
Complete Check #2.  
1. LED flashing?  
Repair low voltage wiring.  
Complete Check #3.  
2. Check for 24V Y-B at board with unit running.  
3. Check sensors for correct mounting  
(connection) and resistance.  
Remount or replace sensor if necessary.  
N
Y
N
Y
Replace defrost control.  
4. Short FRC_DFT pin to TEST_COMMON pin.  
Is defrost cycle initiated?  
Y-B signal or control may be intermittent  
Repair low voltage wiring.  
Replace defrost control.  
4. Control does not initiate a forced  
defrost.  
24V R-B & Y-B at board with unit running?  
5. Defrost initiates manually but terminates in less than 10 seconds.  
Replace defrost control.  
6. Defrost initiates manually but  
terminates on time.  
1. Coil sensor circuit open or reading at a very  
high resistance?  
Y
N
Replace coil sensor.  
2. Does OD fan cycle off in defrost?  
Replace defrost control.  
3. Windy weather preventing normal  
termination?  
7. Defrost initiates on approximately  
15/25 minute intervals.  
Be sure OD coil is clean.  
N
Y
Complete Check #2.  
Replace coil sensor.  
1. Coil sensor open or reading a very  
high resistance?  
N
Y
N
Y
Complete Check #3.  
Replace ambient sensor.  
Replace defrost control.  
Remove short.  
2. Ambient sensor reading less than normal?  
3. OD fan off in defrost?  
8. Defrost initiates on approximately  
30/45 minute intervals.  
1.TEST_COMMON pin shorted to TST pin?  
Replace defective sensor (Clear coil and  
reset Emergency heat light).  
N
Y
2. Do both sensors check OK?  
3. Verify correct system charge.  
Complete SYMPTOM #3.  
Adjust as needed.  
4. Verify a "forced defrost" terminates less than  
15 minutes.  
N
Replace defrost control.  
5. OD fan motor off in defrost.  
6. Verify proper SOV operation.  
See SYMPTOM #9.  
Replace if necessary.  
Replace defrost control.  
9. OD fan runs during defrost.  
10. No SOV delay on defrost  
termination.  
The soft-switch time is defeated when J1  
is cut.  
Y
Has J1 been cut?  
N
Y
Replace defrost control.  
11. ODS-A burned out.  
Check low voltage wiring for miswire.  
1. B to T greater than 10 volts?  
N
N
N
Check for short in low voltage wiring.  
Repair low voltage wiring.  
12. On SCROLL bearing units,  
compressor does not operate.  
1. 24V R-B at board & 24V Y-B at board?  
2. Check protective devices in YO circuit . 24V  
YO-B present after 30 seconds.  
Y-B signal or control may be intermittent  
13. On SCROLL bearing units, no 30 Check voltage between control terminals 2 and  
second off delay at defrost initiation.  
7,force a defrost cycle. Is 24V present for 30  
seconds and 0V thereafter?  
N
Replace defrost control.  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
MAINTENANCE PERFORMED BY SERVICEMAN--  
ROUTINE MAINTENANCE BY OWNER  
HEATING SEASON  
You can do some of the periodic maintenance functions for  
your WCY-G unit yourself; this includes replacing the dispos-  
able or cleaning the permanent air filters, cleaning the unit  
cabinet,clearingthecondensercoil,andconductingageneral  
unit inspection on a regular basis.  
Complete the unit inspections and service routines described below  
at the beginning of each heating season.  
Visually inspect the unit to ensure that the airflow required for  
condenser coil is not obstructed from the unit.  
Be sure to inspect them at least once each month when  
the system is in constant operation. (In new homes, check  
the filters every week for the first four (4) weeks.)  
Inspect the control panel wiring to verify that all electrical  
connections are tight and that the wire insulation is intact.  
If you have disposable-type filters, replace them with new  
filters of the same type and size. Do not attempt to clean  
disposable filters.  
WARNING:  
TO PREVENT INJURY OR DEATH  
.
DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING  
PARTS. LOCK UNIT DISCONNECT SWITCH IN OPEN  
POSITION BEFORE SERVICING UNIT.  
Permanent-type filters can be cleaned by washing them with  
a mild detergent and water. Make sure that the filters are  
thoroughly dry before re-installing them in the unit (or duct  
system).  
WARNING:  
TO PREVENT AN EXPLOSION  
OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE,  
DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE  
OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE  
UNIT.  
NOTE: It may be necessary to replace permanent filters  
annually if washing fails to clean the filter or if the filter shows  
signs of deterioration. Be sure to use the same type and size  
as was originally installed.  
The following warning complies with State of California law, Proposition 65.  
WARNING:  
This product contains  
CONDENSER COIL  
fiberglass wool insulation! Fiberglass dust and ceramic  
fibers are believed by the State of California to cause  
cancer through inhalation. Glasswool fibers may also  
cause respiratory, skin, or eye irritation.  
Unfiltered air circulates through the unit's condenser coil and  
cancausethecoil'ssurfacetobecomecloggedwithdust, dirt,  
etc. To clean the coil, vertically (i.e., with the fins) stroke the  
coil surface with a soft-bristled brush.  
PRECAUTIONARY MEASURES  
Be sure to keep all vegetation away from the condenser coil  
area.  
Avoid breathing fiberglass dust.  
MAINTENANCE PERFORMED BY SERVICEMAN--  
COOLING SEASON  
Use a NIOSH approved dust/mist respirator.  
To keep your unit operating safely and efficiently, the manu-  
facturer recommends that a qualified serviceman check the  
entire system at least once each year and any other time that  
you feel one is needed. Your serviceman should examine  
these areas of your WCY-G unit:  
Avoid contact with the skin or eyes. Wear long-  
sleeved, loose-fitting clothing, gloves, and eye  
protection.  
Wash clothes separately from other clothing: rinse  
washer thoroughly.  
filters (for cleaning or replacement)  
motors and drive system components  
gaskets (for possible replacement)  
safety controls (for mechanical cleaning)  
Operations such as sawing, blowing, tear-out, and  
spraying may generate fiber concentrations requiring  
additional respiratory protection. Use the appropriate  
NIOSH approved respirator in these situations.  
FIRST AID MEASURES  
Eye Contact  
electrical components and wiring (for possible replacement and  
connection tightness)  
-
Flush eyes with water to remove dust.  
If symptoms persist, seek medical  
attention.  
condensate drain (for cleaning)  
unit duct connections (to see that they are physically sound and  
sealed to the unit casing)  
Skin Contact - Wash affected areas gently with soap  
and warm water after handling.  
unit mounting support (for structural integrity)  
the unit (for obvious unit deterioration)  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
HIGH EFFICIENCY HEAT PUMP  
WCZ, WCY AND WCX  
Models Less Than 20 Tons for Residential Use*  
(Parts Only)  
This limited warranty is extended by American Standard Inc., to the original purchaser and to any  
succeeding owner of the real property to which the Heat Pump is originally affixed, and applies to  
products purchased and retained for use within the U.S.A. and Canada.  
If any part of your Heat Pump fails because of a manufacturing defect within five years from the date  
of the original purchase,Warrantor will furnish without charge the required replacement part. Any  
local transportation, related service labor, diagnosis calls, refrigerant and related items are not  
included.  
In addition, if the sealed motor-compressor(s) fail(s) or the outdoor coilshould become defective,  
either or both events occurring because of a manufacturing defect within the sixth through tenth year  
from the date of original purchase,Warrantor will furnish without charge the required replacement  
compressor and/or outdoor coil. Any local transportation, related service labor, diagnosis calls,  
refrigerant and related items are not included.  
NOTE: If your Heat Pump is installed within one mile of salt water, including but not limited to  
seacoasts and inland waterways, your outdoor coil warranty as stated above is limited to five years  
from the date of original purchase.  
This limited warranty does not cover failure of your Heat Pump if it is damaged while in your  
possession, damage caused by unreasonable use of the Heat Pump and/or damage from failure to  
properly maintain the Heat Pump as set forth in the Use and Care manual (see Proper  
Maintenance section).  
This limited warranty applies to product installed on or after 10/1/2001 where product is manufactured  
after 1/1/2000.This limited warranty is not retroactive to any installations prior to 10/1/2001 or on  
product produced prior to 2000.  
THE LIMITEDWARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER  
WARRANTIES AND LIABILITIES,WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS  
OR IMPLIED, IN LAW OR IN FACT, INCLUDING BUT NOT SPECIFICALLY LIMITEDTO IMPLIED  
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO  
EVENT SHALLWARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL  
DAMAGES.  
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow  
the exclusion or limitation of incidental or consequential damages, so the above limitation or  
exclusion may not apply to you.This limited warranty gives you specific legal rights, and you may  
also have other rights which vary from state to state.  
Parts will be provided by our factory organization through an authorized service organization in your  
area listed in the yellow pages. If you wish further help or information concerning this limited  
warranty, contact:  
American Standard Inc.  
Troup Highway  
GW-624-1802  
Tyler,TX 75711-9010  
Attention: Manager, After Sales Support  
*This limited warranty is for residential usage of this equipment and not applicable when this  
Page 19  
equipment is used for a commercial application. A commercial use is any application where the end  
Download from Www.Somanuals.com. All Manuals Search And Download.  
purchaser uses the product for other than personal, family or household purposes.  
LIMITED WARRANTY  
HIGH EFFICIENCY HEAT PUMP  
WCZ, WCY, WCX, WCC, WCD, WCH, WCM AND WSC  
Models Less Than 20 Tons for Commercial Use*  
(Parts Only)  
This warranty is extended by American Standard Inc., to the original purchaser and to any  
succeeding owner of the real property to which the Heat Pump is originally affixed, and applies to  
products purchased and retained for use within the U.S.A. and Canada. There is no warranty  
against corrosion, erosion or deterioration.  
If any part of your Heat Pump fails because of a manufacturing defect within one year from the  
date of the original purchase, Warrantor will furnish without charge the required replacement part.  
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the  
second through fifth year from the date of original purchase, Warrantor will furnish without charge  
the required replacement compressor. Warrantor’s obligations and liabilities under this warranty  
are limited to furnishing F.O.B. Warrantor factory or warehouse replacement parts for Warrantor’s  
products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost  
refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability  
shall be limited solely to the purchase price of the equipment under warranty shown to be  
defective.  
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL  
OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN  
NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN FACT, INCLUDING  
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR  
PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR  
ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.  
Some states do not allow limitations on how long an implied warranty lasts or do not allow the  
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion  
may not apply to you. This warranty gives you specific legal rights, and you may also have other  
rights which vary from state to state.  
American Standard Inc.  
Troup Highway  
GW-604-4800  
Tyler, TX 75711-9010  
Attention: Manager, After Sales Support  
* This warranty is for commercial usage of said equipment and not applicable when the equipment  
is used for a residential application. Commercial use is any application where the end purchaser  
uses the product for other than personal, family or household purposes.  
The Trane Company  
Unitary Products Group  
6200 Troup Highway  
Technical Literature - Printed in U.S.A.  
Tyler, TX 75707-9010  
An American-Standard Company  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Teac Computer Drive CD58E User Manual
Technicolor Thomson GPS Receiver GPS280 User Manual
Telenetics Network Card MIU56 User Manual
Thermador Dishwasher P24 User Manual
Therma Stor Products Group Dehumidifier 200 MAX User Manual
Topcom Network Card WBR 754SG User Manual
Toro Dryer Accessories 99051SL User Manual
Trilogy Touch Technology Computer Monitor Trilogy Touch Monitor User Manual
VBrick Systems Network Hardware VB4000 User Manual
Vidikron Projection Television vision70 User Manual