Split System Heat Pumps
Split System Heat Pumps
7 1/2 through 20Ton - 50 Hz
Air Handlers
5 through 20Ton - 50 Hz
July 2000
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction
2
4
6
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
7
8
9
Performance Data
12
Cool and Heat Performance
Fan Performance
12
24
31
Electric Power
Connection andWiring
Dimension andWeights
Mechanical Specifications
33
39
55
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Heat Pumps
Air Handlers
• 3-D® Scroll compressors
• Low voltage terminal board
• Expansion valve(s)
• ModelTWA155-200B have dual
compressors with independent
refrigerant circuits
• Compressor motor overload protection
• Control transformer
• Convertible
• PVC double-sloped, removeable drain
pan
• Fan relay
• High and low pressure cut-out
switches
• Efficient evaporator coil
• Baked enamel finish
• Filter access panel
• Internal pressure relief valve
• Liquid line filter drier, factory installed
• Holding charge of dry nitrogen
• Copper tube, aluminum plate fin coils
• Low ambient cooling to 35° F (1.7° C)
as manufactured
• Weather resistant baked enamel finish
• Heavy gauge steel cabinet
• Mounting/lifting rails under base
• 1” (25.4 mm) throwaway filters
standard with provisions for field
supplied 2”
(50.8 mm) filters
• Adjustable belt drive motor
• Single point power entry to electric
heaters
• Refrigerant piping and/or electrical
connections provided from either side
Odyssey™ air handler versatility is further
increased by a complete line of optional
accessories designed to match and easy
to install:
All condensing units offer these optional
accessories:
• Head Pressure Control — Low Ambient
CoolingTo 0° F (-17.8° C)
• Coil Guards Kits
• Isolators both Rubber-in-Shear and
SpringType
• Discharge Plenum and Grille
• Return Grille
• Anti-Short-Cycle Kit
• Subbase
• Time Delay Relay
• Electric Heaters
• High Static Evaporator Motor
• Isolators both Rubber-in-Shear and
SpringType
4
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Heat Pump Options
Trane split systems have been specified
in thousands of applications and you’ll
find Odyssey will win you even more
jobs with it’s smaller, more manageable
cabinet.
Odyssey air handler versatility is further
increased by a complete line of
accessories designed to match and
install smoothly:
• Discharge Plenum and Grille
• Return Grille
The Odyssey™ split system product line
includes heat pumps in both single and
dual compressor options.
TWA075A andTWA100A single
compressor models feature single
refrigeration circuitry lowering job
installation costs by requiring only one
set of refrigerant lines.These units are
ideal for either the low cost, new
construction jobs as well as renovation
and replacement buildings.
Air Handlers Offer More Flexibility
Flexibility is a key to meeting changing
market requirements. Odyssey split
systems offer various compressor
options and convertible air handlers.The
air handlers can be installed either
vertically in a mechanical room or
horizontally above a ceiling. And it
doesn’t require any removal of panels or
reconfiguration of the drain pan to make
either airflow application work. All the air
handlers feature factory installed belt
drive and ball bearing evaporator fans
with adjustable sheaves for maximum
airflow performance.The standard motor
on theTWE100A air handler will deliver
4000 cfm (1888 l/s) at 0.8” (20.32 mm)
ESP. Plus oversized motors are available
for higher static applications.
• Subbase
• Electric Heaters
• High Static Evaporator Motor
• Isolators both Rubber-in-Shear and
SpringType
• A Full Line of Thermostats
In addition, Odyssey modelsTWA155B
throughTWA200B are dual compressor
units that give true standby protection; if
one compressor fails, the second will
automatically start-up. Also, the first
compressor can be serviced without
shutting down the unit since refrigerant
circuits are independent.
Odyssey™ —A Complete Split System
Odyssey delivers the flexibility to select a
complete system that meets your
particular job requirements. Air Handlers
are designed, tested and rated with
condensing units to let you select the
proper match between capacity and
load. Condensing units can also be
matched withTrane built-up air handlers.
These matched systems can be quickly
engineered for specific applications.
Dual compressors are not just for
protection, they also save energy costs.
Most buildings are designed for the peak
load requirements yet the building
usually operates at less than peak load.
During light load conditions only one
compressor functions to maintain the
space comfort thus reducing the need
for energy.
LowAmbient Cooling Operation
Each condensing unit can operate to
35° F (1.7° C) as standard. An accessory
Head Pressure Control gives you the
capability to operate to 0° F (-17.8° C). All
condensing units offer these accessories:
• Head Pressure Control
• Coil Guard Kits
• Isolators both Rubber-in-Shear and
SpringType
• Anti-Short-Cycle Kit
• Time Delay Relay
TWA-PRC001-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the catalogued airflow and
performance considerations.The System
Selection Program will simulate product
performance for a set of given
conditions. It is recommended that the
program should be run at the lowest
outdoor ambient and supply air flow
rates requiring cooling or heating
operation for a particular unit. For more
information on the System Selection
Program contact your localTrane
Representative.
should be reviewed with the localTrane
Representative.
pressure control will allow operation to
0° F (-17.8° C) outdoor ambient.When
using these units with control systems
such as bypass changeoverVariable Air
Volume, consider the requirement for a
head pressure control to allow low
ambient cooling.
LowAmbient Cooling
As manufactured, these units can
operate to 35° F (1.7° C) in the cooling
mode of operation. An accessory head
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances that appear inadequate
Typical Horizontal Air HandlerApplication
TypicalVerticalAir Handler Application
Typical Split System Application
6
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Cooling Capacity
actualTotal Static Pressure is 1.10 - 0.10 =
1.00 in. (27.9 - 2.5 = 25.4 mm)
(275 - 25 = 250 Pa)
Air Delivery Selection
Step 1 — Calculate the building’s total
and sensible cooling loads at design
conditions. Use theTrane calculation
form or any other standard accepted
method.
External static pressure drop through the
air distribution system has been
calculated to be 0.77 inches (19.6 mm) of
water gauge. FromTable PD-24 static
pressure drop through the electric heater
is 0.12 inches (3.0 mm) of water (0.77 +
0.12 = .89 in.) (19.6 + 3.0 = 22.6 mm).
EnterTable PD-15 forTWE090A4 at 2500
cfm (1180 l/s) and .90 static pressure.The
standard motor at 790 rpm will give the
desired airflow.
With 2500 cfm (1180 l/s) and 1.00 inches
(250 Pa) (0.8 kW),Table 26-1 shows a 1.07
Bhp.
Step 2 — Size the equipment usingTable
PD-1. Match the cooling loads at design
conditions.
Note:The formula below the table can be
used to calculate Fan Motor Heat,
Constant x Motor Power =
Fan Motor Heat
Example:The following are the building
cooling requirements
3.5 x Bhp = MBh
a
3.5 x 1.07
= 3.75 MBh
Electrical Characteristics: 380-415/50/3
1.375 x (kW) = kW
1.375 x 0.8 = 1.1 kW
b
Summer Design Conditions: Entering
Evaporator Coil: 80 DB/67WB
(27 DB/19WB° C)
NetTotal Cooling Capacity
= 79.6 MBh – 3.75 = 75.85 MBh
= 23.3 kW - 1.1 = 22.2 kW
Net Sensible Cooling Capacity
= 57.1 MBh – 3.75 = 53.35 MBh
= 16.7 MBh - 1.1 = 15.6 kW
Outdoor Ambient: 95° F (35° C)
c
Total Cooling Load: 75 MBh (22kW)
d
Sensible Cooling Load: 53 MBh
(15.5 kW)
Heating Capacity
Step 1 — Calculate the building heating
load using theTrane calculation form or
any other standard accepted method.
e
Airflow: 2500 cfm (1,180 l/s)
External Static Pressure: 0.77 in.
(19.6 mm) w.g. (193 Pa)
Step 2 — Size the equipment usingTable
PD-9 to match the heating loads at
Table PD-1 shows that aTWA075A
matched with aTWE075A has a gross
cooling capacity of 82.4 MBh (24.1 kW)
and 59.5 MBh (17.4 kW) sensible capacity
at 95 DB (35° C) ambient and 2500 cfm
(1180 l/s) and 80 DB/67WB (27 DB/19WB)
air entering the evaporator.
design conditions.The following are
building heating requirements:
a
Total Heating Load: 110 MBh (32.2 kW)
b
Outdoor Ambient (Winter): 17° F
(-8.3° C) DB
c
To find the net cooling capacities, fan
motor heat must be subtracted.
Determine the total unit static pressure:
Indoor ReturnTemperature: 70° F
(21.1° C) DB
d
External Static
0.77 in
Airflow: 2500 cfm (1180 l/s)
Table PD-9 indicates the mechanical
heating portion of the heat pump will
provide 37.5 MBh (11.0 kW) for the winter
design conditions.
(19.6 mm) (193 Pa)
Standard Filter
0.10 in
1 in. (25.4 mm)
(2.5 mm) (25 Pa)
Supplementary Electric Heat
0.23 in
Step 3 — Because 37.5 MBh (11.0 kW) is
less than the building’s required heating
capacity, a supplementary heater must
be selected. 110 - 37.5 = 72.5 MBh (32.2 -
11.0 = 21.2 kW) minimum heater capacity.
(5.8 mm) (57 Pa)
Total Static Pressure
1.10 in
FromTable PD-25, the 24.22 kW heater
has a capacity of 82,670 Btuh. FromTable
34-1, the 24.22 kW heater at 400V
indicates the heater model number is
BAYHTRL435A.This heater will be
adequate to cover the residual heat
capacity needed for the application.
(27.9 mm) (275 Pa)
Note:The Evaporator Fan Performance
Table has included the effect of a 1 in.
(25.4 mm) filter already.Therefore, the
TWA-PRC001-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
Split System Heat Pump Model Nomenclature
T
W
A
0
7
5
A
D
0
0
D
A
1
2
3
4
5
6
7
8
9
10
11
12
Digit 8 - Electrical Characteristics
Digits 1, 2, 3 - ProductType
TWA = Split System Heat Pump
D = 380-415/3/50
Digit 9, 10 - Factory - Installed Options
Digits 4, 5, 6 - Nominal Gross Cooling Capacity
(MBh)
00 = Packed Stock
0S = Black Epoxy Coated Coil
075 = 75
100 = 100
155 = 155
200 = 200
Digit 11- Minor Design Sequence
D = Fourth
Digit 12- Service Digit
Digit 7- Major Development Sequence
A = First
A = Single Compressor
B = Dual Compressor
Air Handler Model Nomenclature
T
W
E
0
5
0
A
D
0
0
C
A
1
2
3
4
5
6
7
8
9
10
11
12
Digit 8 - Electrical Characteristics
Digits 1, 2, 3 - ProductType
D = 380-415/3/50
TWE = Cooling Convertible
Digit 9, 10 - Factory - Installed Options
00 = Packed Stock
Digits 4, 5, 6 - Nominal Gross Cooling
Capacity (MBh)
Digit 11- Minor Design Sequence
C = Third
050 = 50
075 = 75
100 = 100
155 = 155
200 = 200
Digit 12- Service Digit
A = First
Digit 7- Refrigerant Circuit
A = Single
B = Dual
8
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(Heat Pumps)
Table GD-1 — General Data — Heat Pumps
TWA075A
TWA100A
Cooling Performance1
Gross Cooling Capacity, BTUH (KW)
Matched Air Handler, BTUH (KW)
Heat Pump Only2, BTUH (KW)
ARI Net Cooling Capacity3
System Power KW
Heat Pump Only Power KW
Heating Performance
ARI Heating with Matched Air Handler
HighTemperature Capacity, BTUH (KW)
LowTemperature Capacity, BTUH (KW)
Compressor
82,000 (23.97)
109,000 (31.97)
105,000 (30.75)
105,000 (30.75)
10.32
82,000 (23.97)
80,000 (23.35)
7.36
6.61
9.22
75,000 (21.82)
47,000 (13.84)
106,000 (31.05)
69,000 (20.29)
Number
Type
No. Speeds
1
3D®Scroll
1
1
3D®Scroll
1
No. Motors
1
1
Motor HP (KW)
6.25 (4.7)
2875
8.8
8.33 (6.21)
2875
8.8
Motor RPM
ARI Sound Rating (Bels)4
System Data5
No. Refrigerant Circuits
Suction Line, in. (mm) OD
Liquid Line, in. (mm) OD
Outdoor Coil —Type
Tube Size, in. (mm) OD
Face Area, sq. ft. (m2)
Rows
1
1.375 (34.9)
0.500 (12.7)
Plate Fin
0.375 (9.5)
19.2 (1.78)
2
1
1.375 (34.9)
0.500 (12.7)
Plate Fin
0.375 (9.5)
24.0 (2.23)
2
Fins Per Inch (Fins per mm)
Outdoor FanType
No. Used
18 (457)
Propeller
1
18 (457)
Propeller
1
Diameter, in. (mm)
DriveType
26.00 (660.4)
Direct
28.00 (711)
Direct
No. Speeds
1
1
CFM6, (L/S)
4700 (2218.2)
1
6700 (3161.7)
1
No. Motors
Motor HP (KW)
0.33 (.24)
925
18.0 (8.16)
0.75 (.56)
925
24.25 (11.0)
Motor RPM
R-22 Refrigerant Charge, Lbs7 (Kg)
Notes:
1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering wet
bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the
effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for
operation to 20% of nominal cfm. Rated accordance with ARI Standard 210.
2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.2° C) saturated suction temperature and at 95° F
(35° C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.2 m) of 1.375, 0.500 OD interconnect-
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C)
entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm.
4. ARI Sound Rating is rated in accordance with ARI Standard 270.
5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3
m) For greater lengths, refer to refrigerant piping applications manual.
6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of
interconnecting refrigerant lines.
TWA-PRC001-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(Heat Pumps)
Table GD-2 General Data — Heat Pumps
TWA155B
TWA200B
Cooling Performance1
Gross Cooling Capacity, BTUH (KW)
Matched Air Handler, BTUH (KW)
Condensing Unit Only2, BTUH (KW)
ARI Net Cooling Capacity3
166,000 (48.57)
216,000 (63.24)
209,000 (61.18)
196,000 (61.18)
20.61
161,000 (47.04)
160,000 (46.74)
14.98
System Power KW
Condensing Unit Power KW
13.20
18.52
Heating Performance
ARI Heating with Matched Air Handler
HighTemperature Capacity, BTUH (KW) 151,000 (44.27)
206,000 (60.26)
135,000 (39.66)
LowTemperature Capacity, BTUH (KW)
95,000 (27.67)
Compressor
Number
Type
No. Speeds
2
3D®Scroll
1
2
3D®Scroll
1
No. Motors
2
2
Motor HP
6.25 (4.7)
2875
8.8
8.33 (6.21)
2875
8.8
Motor RPM, (KW)
ARI Sound Rating (Bels)4
System Data5
No. Refrigerant Circuits
Suction Line, in. (mm) OD
Liquid Line, in. (mm) OD
Outdoor Coil —Type
Tube Size, in. (mm) OD
Face Area, sq. ft. (m2)
Rows
2
1.375 (34.9)
0.500 (12.7)
Plate Fin
0.375 (9.5)
38.4 (3.57)
2
2
1.375 (34.9)
0.500 (12.7)
Plate Fin
0.375 (9.5)
48.0 (4.46)
2
Fins Per Inch(mm)
Outdoor FanType
No. Used
18 (457)
Propeller/Propeller
2
18 (457)
Propeller/Propeller
2
Diameter, in. (mm)
DriveType
26.00/26.00 (660.4/660.4)
Direct/Direct
1
28.00/28.00 (711/711)
Direct/Direct
1
13400 (6323.5)
2
No. Speeds
CFM6, (L/S)
9800 (4624.6)
2
No. Motors
Motor HP, (KW)
Motor RPM
0.33 (.24)
925
36.0 (16.32)
0.75 (.56)
925
48.5 (22.0)
R-22 Refrigerant Charge, Lbs7 (Kg)
Notes:
1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering
wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include
the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for
operation to 20% of nominal cfm. Rated accordance with ARI Standard 210.
2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.6° C) saturated suction temperature and at 95° F
(35° C) ambient.
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.6 m) of 1.375, 0.500 OD interconnect-
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C)
entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm.
4. ARI Sound Rating is rated in accordance with ARI Standard 270.
5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3
m) For greater lengths, refer to refrigerant piping applications manual.
6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor.
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of
interconnecting refrigerant lines.
10
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(Air Handlers)
Table GD-3 — General Data —Air Handlers
TWE050A
TWE075A
TWE100A
TWE100B
System Data1
No. Refrigerant Circuits
Suction Line, in. (mm) OD
Liquid Line, in. (mm) OD
Indoor Coil —Type
Tube Size, in. (mm) OD
Face Area, sq. ft. (m2)
Rows
1
1
1
2
1.120 (28.4)
0.38 (9.7)
Plate Fin
0.375 (9.5)
5.00 (.47)
3
1.380 (35.0)
0.50 (12.7)
Plate Fin
0.375 (9.5)
8.07 (.75)
3
1.380 (35.0)
0.50 (12.7)
Plate Fin
0.375 (9.5)
11.18 (1.0)
3
1.380 (35.0)
0.50 (12.7)
Plate Fin
0.375 (9.5)
11.18 (1.0)
3
Fins Per Inch
12
12
12
12
Refrigerant Control
Drain Connection No.
ExpansionValve ExpansionValve ExpansionValve ExpansionValve
4
4
4
4
Drain Connection Size, in. (mm) 0.75 (19.0)
0.75 (19.0)
PVC
0.75 (19.0)
PVC
0.75 (19.0)
PVC
Drain ConnectionType
Indoor FanType
No. Used
PVC
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
1
1
15.0 (381)
15.0 (381)
Belt
1
15.0 (381)
15.0 (381)
Belt
1
15.0 (381)
15.0 (381)
Belt
Diameter, in. (mm)
Width, in. (mm)
DriveType
12.0 (304.8)
12.0 (304.8)
Belt
No. Speeds
1
1
1
1
CFM, (L/S)
No. Motors
1670 (788.2)
1
2500 (1179.9)
1
3325 (1569.2)
1
3325 (1569.2)
1
Motor HP, (KW)
— Standard/Oversized
0.75/1.0 (.55/.74) 1.0/1.5 (.74/1.11) 1.5/2.0 (1.11/1.49) 1.5/2.0 (1.11/1.49)
Motor RPM (Standard)
Motor Frame Size (Standard)
Filters —Type
Furnished
1425
1425
56
Throwaway
1425
56
Throwaway
1425
56
Throwaway
56
Throwaway
Yes
Yes
3
Yes
4
Yes
4
No.
1/1
Recommended Size, in. (mm) 16x20x1/20x20x1
16x25x1
16x25x1
16x25x1
406.4x508x25.
406.4/635/25.4
406.4/635/25.4
406.4/635/25.4
4/508x508x25.4
Table GD-3 — General Data — Continued
TWE155B
TWE200B
System Data
No. Refrigerant Circuits
Suction Line, in. (mm) OD
Liquid Line, in. (mm) OD
Indoor Coil —Type
Tube Size, in. (mm) OD
Face Area, sq. ft. (m2)
Rows
2
2
1.38 (35.0)
0.500 (12.7)
Plate Fin
0.375 (9.5)
21.63 (2.01)
3
1.38 (35.0)
0.500 (12.7)
Plate Fin
0.375 (9.5)
16.33 (1.52)
3
Fins Per Inch
12
12
Refrigerant Control
Drain Connection No.
Drain Connection Size, in. (mm)
Drain ConnectionType
Indoor FanType
No. Used
Diameter, in. (mm)
Width, in. (mm)
DriveType
ExpansionValve
ExpansionValve
4
1.000 (25.4)
PVC
FC Centrifugal
2
15.0 (381)
15.0 (381)
Belt
4
1.000 (25.4)
PVC
FC Centrifugal
2
15.0 (381)
15.0 (381)
Belt
No. Speeds
1
1
CFM, (L/S)
5000 (2360.0)
6650 (3138.4)
No. Motors
1
1
Motor HP, (KW)
— Standard/Oversized
2.0/3.0 (1.49/2.24)
3.0/5.0 (2.24/3.72)
Motor RPM (Standard)
Motor Frame Size (Standard)
Filters —Type
1425
145T
Throwaway
Yes
1425
184T
Throwaway
Yes
Furnished
No.
8
4/4
Recommended Size, in. (mm)
15x20x2
16x20x2/16x25x2
381x508x50.8
406.4x508x50.8/406.4x635x50.8
Notes:
1. ARI certified with various condensing units per ARI Standard 210. Refer to Performance Data section in this catalog.
TWA-PRC001-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-1 — Gross Cooling Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler
Ambient Temperature
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
61
67
73
61
67
67
73
61
67
73
CFM
2250
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
75
80
85
90
75.7 60.5 83.8 50.3 92.4 34.1 73.2 59.2 80.9 49.1 89.1 32.9 70.2 57.7 77.5 47.8 85.3 31.6 66.7 56.0 73.6 46.2 81.1 30.2
76.2 70.8 84.0 58.2 92.4 44.8 73.7 69.5 81.1 57.0 89.1 43.6 70.8 68.1 77.6 55.4 85.4 42.2 67.5 66.4 73.8 53.8 81.2 40.7
78.3 78.3 84.1 68.4 92.5 55.4 76.1 76.1 81.2 67.1 89.3 54.2 73.6 73.6 77.8 65.6 85.5 52.8 70.6 70.6 74.0 63.9 81.4 51.3
82.3 82.3 84.6 78.7 92.7 65.9 80.0 80.0 81.8 77.5 89.4 64.5 77.4 77.4 78.6 76.0 85.6 63.0 74.3 74.3 75.0 74.4 81.5 61.4
2500
2750
3000
75
80
85
90
77.2 63.4 85.3 49.5 93.9 34.7 74.6 62.1 82.3 48.2 90.5 33.6 71.4 60.5 78.8 46.8 86.6 32.2 67.8 58.8 74.8 45.2 82.2 30.6
77.9 74.7 85.5 61.0 93.9 46.4 75.4 73.4 82.4 59.5 90.5 45.1 72.4 72.0 78.9 58.0 86.7 43.7 68.9 68.9 75.0 56.3 82.4 42.2
80.9 80.9 85.6 72.0 94.1 57.9 78.6 78.6 82.6 70.7 90.7 56.7 75.9 75.9 79.2 69.2 86.8 55.3 72.8 72.8 75.3 67.5 82.6 53.7
85.0 85.0 86.4 83.4 94.1 69.1 82.7 82.7 83.6 82.1 90.8 67.8 79.8 79.8 79.9 79.9 87.0 66.3 76.6 76.6 76.7 76.7 82.7 64.7
75
80
85
90
78.5 66.1 86.5 51.2 95.1 35.3 75.7 64.8 83.4 49.9 91.6 34.1 72.5 63.2 79.8 48.4 87.6 32.7 68.9 61.5 75.8 46.8 83.1 31.1
79.4 78.5 86.6 63.4 95.2 47.8 76.5 76.5 83.6 62.0 91.7 46.6 73.8 73.8 80.0 60.5 87.7 45.2 70.7 70.7 75.9 58.8 83.3 43.6
83.1 83.1 86.9 75.4 95.3 60.3 80.7 80.7 83.9 74.1 91.8 59.0 77.9 77.9 80.4 72.6 87.9 57.6 74.6 74.6 76.5 70.9 83.5 55.8
87.4 87.4 88.1 87.9 95.4 72.3 84.9 84.9 85.0 85.0 92.0 71.0 82.0 82.0 82.0 82.0 88.0 69.5 78.6 78.6 78.7 78.7 83.7 67.8
75
80
85
90
79.5 68.8 87.6 52.8 96.1 35.8 76.8 67.4 84.4 51.5 92.5 34.5 73.5 65.9 80.7 50.0 88.4 33.1 69.8 64.1 76.6 48.4 83.9 31.5
80.7 80.7 87.7 65.8 96.2 49.2 78.3 78.3 84.6 64.4 92.6 47.9 75.4 75.4 80.9 62.8 88.6 46.5 72.2 72.2 76.8 61.1 84.1 45.0
85.1 85.1 88.1 78.8 96.4 62.6 82.6 82.6 85.0 77.4 92.7 61.1 79.6 79.6 81.5 75.9 88.7 59.6 76.3 76.3 77.5 74.2 84.3 58.0
89.5 89.5 89.6 89.6 96.5 75.4 86.9 86.9 87.0 87.0 93.0 74.1 83.8 83.8 83.9 83.9 89.0 72.5 80.4 80.4 80.5 80.5 84.6 70.9
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.
Table PD-1 — Gross Cooling Capacities (KW) TWA075A Heat Pump withTWE075AAir Handler
Ambient Temperature
85
95
105
67
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
61
67
73
61
67
73
61
67
73
L/S
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
1062
24
27
29
32
22.2 17.7 24.5 14.7 27.1 10.0 21.4 17.3 23.7 14.4 26.1 9.6 20.5 16.9 22.7 14.0 25.0 9.3 19.5 16.4 21.6 13.5 23.7 8.8
22.3 20.7 24.6 17.0 27.1 13.1 21.6 20.4 23.7 16.7 26.1 12.8 20.7 19.9 22.7 16.2 25.0 12.4 19.8 19.5 21.6 15.7 23.8 11.9
22.9 22.9 24.6 20.0 27.1 16.2 22.3 22.3 23.8 19.6 26.1 15.9 21.5 21.5 22.8 19.2 25.0 15.5 20.7 20.7 21.7 18.7 23.8 15.0
24.1 24.1 24.8 23.1 27.1 19.3 23.4 23.4 23.9 22.7 26.2 18.9 22.7 22.7 23.0 22.3 25.1 18.5 21.8 21.8 22.0 21.8 23.9 18.0
1180
1298
1416
24
27
29
32
22.6 18.6 25.0 14.5 27.5 10.2 21.8 18.2 24.1 14.1 26.5 9.8 20.9 17.7 23.1 13.7 25.3 9.4 19.9 17.2 21.9 13.2 24.1 9.0
22.8 21.9 25.0 17.9 27.5 13.6 22.1 21.5 24.1 17.4 26.5 13.2 21.2 21.1 23.1 17.0 25.4 12.8 20.2 20.2 21.9 16.5 24.1 12.4
23.7 23.7 25.1 21.1 27.5 17.0 23.0 23.0 24.2 20.7 26.6 16.6 22.2 22.2 23.2 20.2 25.4 16.2 21.3 21.3 22.1 19.8 24.2 15.7
24.9 24.9 25.3 24.4 27.6 20.2 24.2 24.2 24.5 24.0 26.6 19.9 23.4 23.4 23.4 23.4 25.5 19.4 22.4 22.4 22.5 22.5 24.2 18.9
24
27
29
32
23.0 19.4 25.3 15.0 27.8 10.3 22.2 19.0 24.4 14.6 26.8 10.0 21.2 18.5 23.4 14.2 25.6 9.6 20.2 18.0 22.2 13.7 24.3 9.1
23.3 23.0 25.4 18.5 27.9 14.0 22.4 22.4 24.5 18.2 26.8 13.6 21.6 21.6 23.4 17.7 25.7 13.2 20.7 20.7 22.2 17.2 24.4 12.8
24.3 24.3 25.4 22.1 27.9 17.6 23.6 23.6 24.6 21.7 26.9 17.3 22.8 22.8 23.5 21.3 25.7 16.9 21.9 21.9 22.4 20.8 24.4 16.3
25.6 25.6 25.8 25.7 27.9 21.2 24.9 24.9 24.9 24.9 26.9 20.8 24.0 24.0 24.0 24.0 25.8 20.3 23.0 23.0 23.0 23.0 24.5 19.9
24
27
29
32
23.3 20.1 25.6 15.5 28.1 10.5 22.5 19.7 24.7 15.1 27.1 10.1 21.5 19.3 23.6 14.6 25.9 9.7 20.4 18.8 22.4 14.2 24.6 9.2
23.6 23.6 25.7 19.3 28.2 14.4 22.9 22.9 24.8 18.9 27.1 14.0 22.1 22.1 23.7 18.4 25.9 13.6 21.1 21.1 22.5 17.9 24.6 13.2
24.9 24.9 25.8 23.1 28.2 18.3 24.2 24.2 24.9 22.7 27.1 17.9 23.3 23.3 23.8 22.2 26.0 17.5 22.3 22.3 22.7 21.7 24.7 17.0
26.2 26.2 26.2 26.2 28.2 22.1 25.4 25.4 25.5 25.5 27.2 21.7 24.5 24.5 24.6 24.6 26.0 21.2 23.5 23.5 23.6 23.6 24.8 20.8
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.
12
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100AAir Handler
Ambient Temperature
85
95
105
67
115
Enter.
Dry
Bulb
Entering Wet Bulb
73 61
61
67
73
61
67
73
61
67
73
CFM
3000
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
75
80
85
90
101.6 80.9 111.8 67.1 122.7 45.2 97.7 79.0 107.6 65.4 118.1 43.6 93.6 76.9 103.2 63.6 113.2 41.9 89.4 74.8 98.6 61.7 108.2 40.1
102.1 94.6 112.0 77.2 122.7 59.2 98.4 92.6 107.8 75.3 118.0 57.5 94.4 90.6 103.4 73.5 113.2 55.7 90.4 88.6 98.8 71.5 108.2 53.8
104.6 104.6 112.1 90.6 122.8 72.8 101.3 101.3 107.9 88.7 118.2 71.1 97.9 97.9 103.5 86.7 113.4 69.3 94.3 94.3 98.9 84.6 108.4 67.4
109.6 109.6 112.7 104.1 122.9 86.4 106.3 106.3 108.6 102.2 118.3 84.6 102.8 102.8 104.4 100.2 113.5 82.8 99.1 99.1 100.1 98.2 108.5 80.7
3325
3650
3975
75
80
85
90
103.4 84.5 113.7 65.6 124.6 46.0 99.4 82.5 109.4 63.8 119.8 44.4 95.2 80.5 104.8 61.9 114.8 42.7 90.9 78.3 100.1 59.9 109.6 40.8
104.3 99.5 113.9 80.6 124.6 61.1 100.4 97.5 109.5 78.7 119.8 59.3 96.4 95.5 104.8 76.6 114.9 57.5 92.0 92.0 100.2 74.6 109.7 55.6
107.8 107.8 114.0 95.0 124.7 75.9 104.4 104.4 109.6 93.1 120.0 74.1 100.8 100.8 105.2 91.1 115.0 72.3 97.0 97.0 100.6 89.0 109.9 70.4
113.0 113.0 114.9 109.8 124.8 90.6 109.5 109.5 110.8 107.9 120.0 88.6 105.8 105.8 106.5 105.9 115.1 86.7 102.0 102.0 101.9 101.9 110.0 84.7
75
80
85
90
105.0 88.0 115.3 67.7 126.1 46.8 100.9 85.9 110.8 65.8 121.2 45.0 96.6 83.9 106.1 63.9 116.1 43.2 92.2 81.7 101.3 62.0 110.8 41.3
106.2 104.2 115.4 83.8 126.1 62.8 102.3 102.3 110.9 81.7 121.3 61.1 98.0 98.0 106.2 79.7 116.2 59.2 94.3 94.3 101.4 77.6 111.0 57.4
110.6 110.6 115.6 99.3 126.3 78.8 107.0 107.0 111.2 97.3 121.4 77.0 103.3 103.3 106.7 95.3 116.4 75.2 99.4 99.4 102.0 93.3 111.1 73.3
115.9 115.9 117.0 115.4 126.3 94.4 112.3 112.3 112.2 112.2 121.5 92.5 108.4 108.4 108.4 108.4 116.5 90.5 104.5 104.5 104.4 104.4 111.3 88.5
75
80
85
90
106.3 91.3 116.6 69.7 127.5 47.4 102.2 89.3 112.0 67.8 122.4 45.6 97.9 87.2 107.3 65.9 117.2 43.7 93.4 85.0 102.4 63.9 111.8 41.9
107.4 107.4 116.7 86.6 127.5 64.5 103.9 103.9 112.1 84.7 122.5 62.7 100.1 100.1 107.4 82.6 117.3 60.9 96.2 96.2 102.5 80.5 112.0 59.0
113.0 113.0 117.1 103.4 127.6 81.6 109.3 109.3 112.7 101.5 122.7 79.8 105.5 105.5 108.1 99.4 117.5 78.0 101.5 101.5 103.3 97.4 112.2 76.1
118.5 118.5 118.4 118.4 127.7 98.2 114.8 114.8 114.7 114.7 122.8 96.3 110.8 110.8 110.7 110.7 117.6 94.3 106.6 106.6 106.6 106.6 112.4 92.3
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.
Table PD-2 — Gross Cooling Capacities (KW) TWA100A Heat Pump with TWE100A Air Handler
Ambient Temperature
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
61
67
73
61
67
67
73
61
67
73
L/S
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
1416
24
27
29
32
29.7 23.7 32.7 19.7 35.9 13.2 28.6 23.1 31.5 19.1 34.6 12.8 27.4 22.5 30.2 18.6 33.1 12.3 26.2 21.9 28.9 18.1 31.7 11.8
29.9 27.7 32.8 22.6 35.9 17.3 28.8 27.1 31.6 22.1 34.6 16.8 27.6 26.5 30.3 21.5 33.2 16.3 26.5 25.9 28.9 20.9 31.7 15.8
30.6 30.6 32.8 26.5 35.9 21.3 29.7 29.7 31.6 26.0 34.6 20.8 28.7 28.7 30.3 25.4 33.2 20.3 27.6 27.6 29.0 24.8 31.7 19.7
32.1 32.1 33.0 30.5 36.0 25.3 31.1 31.1 31.8 29.9 34.6 24.8 30.1 30.1 30.6 29.3 33.2 24.2 29.0 29.0 29.3 28.8 31.8 23.6
1569
1723
1876
24
27
29
32
30.3 24.7 33.3 19.2 36.5 13.5 29.1 24.2 32.0 18.7 35.1 13.0 27.9 23.6 30.7 18.1 33.6 12.5 26.6 22.9 29.3 17.5 32.1 11.9
30.5 29.1 33.3 23.6 36.5 17.9 29.4 28.6 32.1 23.0 35.1 17.4 28.2 28.0 30.7 22.4 33.6 16.8 26.9 26.9 29.3 21.8 32.1 16.3
31.6 31.6 33.4 27.8 36.5 22.2 30.6 30.6 32.1 27.2 35.1 21.7 29.5 29.5 30.8 26.7 33.7 21.2 28.4 28.4 29.4 26.1 32.2 20.6
33.1 33.1 33.6 32.2 36.5 26.5 32.1 32.1 32.4 31.6 35.1 25.9 31.0 31.0 31.2 31.0 33.7 25.4 29.9 29.9 29.8 29.8 32.2 24.8
24
27
29
32
30.7 25.8 33.8 19.8 36.9 13.7 29.5 25.2 32.4 19.3 35.5 13.2 28.3 24.6 31.1 18.7 34.0 12.7 27.0 23.9 29.7 18.1 32.5 12.1
31.1 30.5 33.8 24.5 36.9 18.4 30.0 29.9 32.5 23.9 35.5 17.9 28.7 28.7 31.1 23.3 34.0 17.3 27.6 27.6 29.7 22.7 32.5 16.8
32.4 32.4 33.8 29.1 37.0 23.1 31.3 31.3 32.6 28.5 35.6 22.6 30.2 30.2 31.2 27.9 34.1 22.0 29.1 29.1 29.9 27.3 32.5 21.5
33.9 33.9 34.3 33.8 37.0 27.6 32.9 32.9 32.8 32.8 35.6 27.1 31.8 31.8 31.7 31.7 34.1 26.5 30.6 30.6 30.6 30.6 32.6 25.9
24
27
29
32
31.1 26.7 34.1 20.4 37.3 13.9 29.9 26.1 32.8 19.9 35.9 13.3 28.7 25.5 31.4 19.3 34.3 12.8 27.3 24.9 30.0 18.7 32.7 12.3
31.5 31.5 34.2 25.4 37.3 18.9 30.4 30.4 32.8 24.8 35.9 18.4 29.3 29.3 31.4 24.2 34.4 17.8 28.2 28.2 30.0 23.6 32.8 17.3
33.1 33.1 34.3 30.3 37.4 23.9 32.0 32.0 33.0 29.7 35.9 23.4 30.9 30.9 31.6 29.1 34.4 22.8 29.7 29.7 30.3 28.5 32.9 22.3
34.7 34.7 34.7 34.7 37.4 28.8 33.6 33.6 33.6 33.6 35.9 28.2 32.4 32.4 32.4 32.4 34.4 27.6 31.2 31.2 31.2 31.2 32.9 27.0
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.
TWA-PRC001-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-3 — Gross Cooling Capacities (MBh) TWA155A Heat Pump with TWE155AAir Handler
Ambient Temperature
85
95
105
67
115
Enter.
Dry
EnteringWet Bulb
73 61
CFM
4500
Bulb
61
67
73
61
67
73
61
67
73
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
75 152.8 121.6169.0 101.2 186.3 68.7 147.6 119.0 163.1 98.8 179.6 66.4 141.5 116.0 156.2 96.0 171.9 63.7 134.4 112.5 148.4 92.9 163.4 60.8
80
85
90
153.5 142.2 169.3 117.1 186.4 90.4 148.5 139.6 163.5 114.7 179.7 87.9 142.6 136.6 156.4 111.4 172.1 85.0 135.8 133.3 148.7 108.0 163.7 82.0
157.6 157.6 169.5 137.4 186.6 111.5 153.3 153.3 163.7 134.8 180.0 109.0 148.1 148.1 156.9 131.8 172.5 106.2 142.1 142.1 149.2 128.4 164.1 103.1
165.7 165.7 170.4 158.1 186.8 132.2 161.1 161.1 164.8 155.5 180.2 129.6 155.7 155.7 158.2 152.6 172.7 126.6 149.6 149.6 150.9 149.3 164.3 123.4
5000
5500
6000
75
80
85
90
155.8 127.4 172.1 99.7 189.4 70.0 150.4 124.7 166.0 97.1 182.4 67.6 144.0 121.6 158.8 94.2 174.5 64.9 136.7 118.1 150.8 90.9 165.7 61.8
156.9 150.0 172.2 122.3 189.5 93.4 151.8 147.5 166.1 119.7 182.6 90.9 145.7 144.4 159.1 116.6 174.7 88.1 138.7 138.7 151.1 113.1 166.0 84.9
162.9 162.9 172.7 144.6 189.8 116.5 158.3 158.3 166.6 141.9 182.9 114.0 152.8 152.8 159.6 138.9 175.1 111.2 146.5 146.5 151.8 135.5 166.5 108.0
171.3 171.3 174.1 167.4 189.9 138.9 166.4 166.4 168.3 164.8 183.1 136.2 160.7 160.7 160.9 160.9 175.4 133.2 154.3 154.3 154.4 154.4 166.8 129.9
75
80
85
90
158.3 132.9 174.6 103.0 191.8 71.3 152.8 130.2 168.3 100.5 184.7 68.7 146.2 127.0 161.0 97.5 176.5 65.9 138.8 123.5 152.7 94.2 167.5 62.7
160.1 157.7 174.8 127.4 192.0 96.3 154.1 154.1 168.6 124.6 184.9 93.8 148.6 148.6 161.3 121.5 176.9 90.9 142.3 142.3 153.1 118.0 168.0 87.8
167.4 167.4 175.3 151.5 192.3 121.3 162.6 162.6 169.2 148.8 185.3 118.8 156.8 156.8 162.0 145.7 177.1 115.4 150.3 150.3 154.0 142.3 168.3 112.1
176.1 176.1 177.5 176.4 192.6 145.3 171.0 171.0 171.2 171.2 185.6 142.6 165.0 165.0 165.2 165.2 177.6 139.6 158.3 158.3 158.5 158.5 168.9 136.2
75
80
85
90
160.5 138.2 176.8 106.3 193.9 72.2 154.8 135.5 170.3 103.7 186.6 69.6 148.1 132.3 162.8 100.7 178.3 66.7 140.6 128.7 154.4 97.4 169.1 63.6
162.6 162.5 177.0 132.2 194.1 99.1 157.7 157.7 170.6 129.4 186.9 96.5 151.9 151.9 163.2 126.3 178.7 93.7 145.4 145.4 154.8 122.7 169.7 90.5
171.5 171.5 177.7 158.2 194.3 125.6 166.4 166.4 171.4 155.5 187.1 122.9 160.4 160.4 164.1 152.4 179.0 119.8 153.6 153.6 156.1 148.9 170.1 116.4
180.4 180.4 180.6 180.6 194.8 151.5 175.1 175.1 175.2 175.2 187.6 148.8 168.9 168.9 169.0 169.0 179.5 145.7 161.9 161.9 162.1 162.1 170.6 142.3
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.
Table PD-3 — Gross Cooling Capacities (KW) TWA155A Heat Pump withTWE155AAir Handler
Ambient Temperature
85
95
105
67
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
61
67
73
61
67
73
61
67
73
L/S
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
2124
24
27
29
32
44.7 35.6 49.5 29.6 54.6 20.1 43.2 34.8 47.8 28.9 52.6 19.4 41.4 34.0 45.7 28.1 50.3 18.7 39.4 32.9 43.5 27.2 47.8 17.8
44.9 41.6 49.6 34.3 54.6 26.5 43.5 40.9 47.9 33.6 52.6 25.7 41.7 40.0 45.8 32.6 50.4 24.9 39.8 39.0 43.5 31.6 47.9 24.0
46.1 46.1 49.6 40.2 54.6 32.6 44.9 44.9 47.9 39.5 52.7 31.9 43.4 43.4 45.9 38.6 50.5 31.1 41.6 41.6 43.7 37.6 48.0 30.2
48.5 48.5 49.9 46.3 54.7 38.7 47.2 47.2 48.2 45.5 52.8 37.9 45.6 45.6 46.3 44.7 50.6 37.1 43.8 43.8 44.2 43.7 48.1 36.1
2360
2596
2832
24
27
29
32
45.6 37.3 50.4 29.2 55.4 20.5 44.0 36.5 48.6 28.4 53.4 19.8 42.2 35.6 46.5 27.6 51.1 19.0 40.0 34.6 44.2 26.6 48.5 18.1
46.0 43.9 50.4 35.8 55.5 27.4 44.4 43.2 48.6 35.0 53.5 26.6 42.7 42.3 46.6 34.1 51.2 25.8 40.6 40.6 44.2 33.1 48.6 24.9
47.7 47.7 50.6 42.3 55.6 34.1 46.3 46.3 48.8 41.6 53.6 33.4 44.7 44.7 46.7 40.7 51.3 32.5 42.9 42.9 44.4 39.7 48.7 31.6
50.1 50.1 51.0 49.0 55.6 40.7 48.7 48.7 49.3 48.3 53.6 39.9 47.1 47.1 47.1 47.1 51.3 39.0 45.2 45.2 45.2 45.2 48.8 38.0
24
27
29
32
46.4 38.9 51.1 30.2 56.2 20.9 44.7 38.1 49.3 29.4 54.1 20.1 42.8 37.2 47.1 28.6 51.7 19.3 40.6 36.2 44.7 27.6 49.0 18.4
46.9 46.2 51.2 37.3 56.2 28.2 45.1 45.1 49.4 36.5 54.1 27.5 43.5 43.5 47.2 35.6 51.8 26.6 41.7 41.7 44.8 34.6 49.2 25.7
49.0 49.0 51.3 44.4 56.3 35.5 47.6 47.6 49.5 43.6 54.3 34.8 45.9 45.9 47.4 42.7 51.8 33.8 44.0 44.0 45.1 41.7 49.3 32.8
51.6 51.6 52.0 51.7 56.4 42.6 50.1 50.1 50.1 50.1 54.3 41.8 48.3 48.3 48.4 48.4 52.0 40.9 46.4 46.4 46.4 46.4 49.4 39.9
24
27
29
32
47.0 40.5 51.8 31.1 56.8 21.1 45.3 39.7 49.9 30.4 54.6 20.4 43.4 38.7 47.7 29.5 52.2 19.5 41.2 37.7 45.2 28.5 49.5 18.6
47.6 47.6 51.8 38.7 56.8 29.0 46.2 46.2 50.0 37.9 54.7 28.3 44.5 44.5 47.8 37.0 52.3 27.4 42.6 42.6 45.3 35.9 49.7 26.5
50.2 50.2 52.0 46.3 56.9 36.8 48.7 48.7 50.2 45.5 54.8 36.0 47.0 47.0 48.1 44.6 52.4 35.1 45.0 45.0 45.7 43.6 49.8 34.1
52.8 52.8 52.9 52.9 57.0 44.4 51.3 51.3 51.3 51.3 54.9 43.6 49.4 49.4 49.5 49.5 52.6 42.7 47.4 47.4 47.5 47.5 50.0 41.7
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.
14
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-4 — Gross Cooling Capacities (MBh) TWA200A Heat Pump with TWE200AAir Handler
Ambient Temperature
85
95
105
67
115
Enter.
Dry
Bulb
Entering Wet Bulb
73 61
61
67
73
61
67
73
61
67
73
CFM
6000
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
75 200.7 159.3220.9132.5242.6 89.4 192.9 155.4212.4129.1233.3 86.1 184.8151.3203.6125.5223.6 82.8 176.4 147.1 194.5 121.8213.6 79.3
80
85
90
201.5 186.0 221.2 152.1 242.5 117.0 194.0 182.1 212.8 148.5 233.3 113.4 186.2 178.1 204.0 144.7 223.7 109.8 178.1 174.0 194.7 140.4 213.8 106.2
206.2 206.2 221.4 178.3 242.8 143.7 199.7 199.7 213.0 174.4 233.6 140.2 192.9 192.9 204.3 170.5 224.0 136.5 185.8 185.8 195.2 166.4 214.1 132.8
216.2 216.2 222.3 204.7 243.0 170.3 209.5 209.5 214.2 200.8 233.8 166.8 202.5 202.5 205.8 196.9 224.1 162.6 195.2 195.2 197.2 193.0 214.3 158.7
6675
7350
8025
75
80
85
90
204.4 166.6 224.8 129.6 246.5 91.1 196.4 162.6 216.1 125.9 236.9 87.8 188.1 158.5 207.0 122.1 226.9 84.3 179.4 154.2 197.6 118.3 216.6 80.6
205.8 195.9 225.1 159.0 246.5 120.7 198.1 192.0 216.2 154.9 236.9 117.2 190.2 188.0 207.2 151.0 227.1 113.6 181.5 181.5 197.9 146.9 216.8 109.8
212.7 212.7 225.3 187.3 246.7 149.9 205.9 205.9 216.7 183.3 237.2 146.3 198.8 198.8 207.7 179.3 227.4 142.7 191.4 191.4 198.6 175.3 217.2 138.9
223.1 223.1 226.9 216.3 246.8 178.4 216.1 216.1 218.7 212.4 237.3 174.6 208.8 208.8 210.2 208.5 227.6 170.8 201.2 201.2 201.0 201.0 217.4 166.8
75
80
85
90
207.6 173.6 228.0 133.8 249.6 92.7 199.4 169.5 219.1 130.1 239.8 89.1 190.8 165.4 209.8 126.3 229.6 85.5 182.1 161.1 200.2 122.4 219.1 81.8
209.7 205.5 228.1 165.1 249.7 124.3 202.0 201.6 219.3 161.2 239.9 120.8 193.6 193.6 210.0 157.2 229.8 117.1 186.1 186.1 200.5 153.0 219.4 113.4
218.4 218.4 228.6 195.9 250.0 155.8 211.3 211.3 219.9 192.0 240.3 152.2 203.9 203.9 210.8 187.9 230.2 148.5 196.2 196.2 201.5 183.8 219.8 144.8
229.1 229.1 231.1 227.5 250.1 186.4 221.9 221.9 221.7 221.7 240.4 182.5 214.3 214.3 214.1 214.1 230.4 178.6 206.3 206.3 206.2 206.2 220.0 174.6
75
80
85
90
210.3 180.3 230.8 137.8 252.3 93.8 202.0 176.2 221.6 134.1 242.3 90.3 193.3 172.0 212.1 130.3 231.9 86.6 184.4 167.7 202.4 126.4 221.1 82.8
212.4 212.4 231.0 171.2 252.4 127.7 205.3 205.3 221.9 167.2 242.5 124.2 197.8 197.8 212.5 163.1 232.1 120.5 190.1 190.1 202.8 159.0 221.5 116.7
223.4 223.4 231.6 204.3 252.7 161.5 216.1 216.1 222.8 200.3 242.8 157.9 208.4 208.4 213.6 196.2 232.3 153.7 200.5 200.5 204.1 192.1 221.7 149.7
234.5 234.5 234.3 234.3 252.9 194.0 227.0 227.0 226.8 226.8 243.1 190.1 219.0 219.0 218.9 218.9 232.8 186.2 210.8 210.8 210.7 210.7 222.2 182.1
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.
Table PD-4 — Gross Cooling Capacities (KW)TWA200A Heat Pump withTWE200AAir Handler
AmbientTemperature
85
95
105
67
115
Enter.
Dry
Bulb
EnteringWet Bulb
73 61
61
67
73
61
67
73
61
67
73
L/S
ID
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
2832
24
27
29
32
58.8 46.7 64.7 38.8 71.0 26.2 56.5 45.5 62.2 37.8 68.3 25.2 54.1 44.3 59.6 36.7 65.5 24.2 51.6 43.1 57.0 35.7 62.5 23.2
59.0 54.5 64.8 44.5 71.0 34.2 56.8 53.3 62.3 43.5 68.3 33.2 54.5 52.1 59.7 42.4 65.5 32.2 52.1 50.9 57.0 41.1 62.6 31.1
60.4 60.4 64.8 52.2 71.1 42.1 58.5 58.5 62.4 51.1 68.4 41.0 56.5 56.5 59.8 49.9 65.6 40.0 54.4 54.4 57.2 48.7 62.7 38.9
63.3 63.3 65.1 59.9 71.2 49.9 61.3 61.3 62.7 58.8 68.5 48.8 59.3 59.3 60.3 57.7 65.6 47.6 57.2 57.2 57.7 56.5 62.7 46.5
3150
3469
3787
24
27
29
32
59.9 48.8 65.8 37.9 72.2 26.7 57.5 47.6 63.3 36.9 69.4 25.7 55.1 46.4 60.6 35.8 66.4 24.7 52.5 45.2 57.9 34.6 63.4 23.6
60.3 57.4 65.9 46.6 72.2 35.4 58.0 56.2 63.3 45.4 69.4 34.3 55.7 55.0 60.7 44.2 66.5 33.3 53.1 53.1 57.9 43.0 63.5 32.2
62.3 62.3 66.0 54.8 72.2 43.9 60.3 60.3 63.4 53.7 69.5 42.8 58.2 58.2 60.8 52.5 66.6 41.8 56.0 56.0 58.1 51.3 63.6 40.7
65.3 65.3 66.4 63.3 72.2 52.2 63.3 63.3 64.0 62.2 69.5 51.1 61.1 61.1 61.6 61.1 66.6 50.0 58.9 58.9 58.9 58.9 63.7 48.8
24
27
29
32
60.8 50.8 66.8 39.2 73.1 27.1 58.4 49.6 64.1 38.1 70.2 26.1 55.9 48.4 61.4 37.0 67.2 25.0 53.3 47.2 58.6 35.8 64.1 23.9
61.4 60.2 66.8 48.3 73.1 36.4 59.1 59.0 64.2 47.2 70.3 35.4 56.7 56.7 61.5 46.0 67.3 34.3 54.5 54.5 58.7 44.8 64.2 33.2
64.0 64.0 66.9 57.4 73.2 45.6 61.9 61.9 64.4 56.2 70.3 44.6 59.7 59.7 61.7 55.0 67.4 43.5 57.5 57.5 59.0 53.8 64.4 42.4
67.1 67.1 67.7 66.6 73.2 54.6 65.0 65.0 64.9 64.9 70.4 53.4 62.7 62.7 62.7 62.7 67.5 52.3 60.4 60.4 60.4 60.4 64.4 51.1
24
27
29
32
61.6 52.8 67.6 40.4 73.9 27.5 59.1 51.6 64.9 39.3 70.9 26.4 56.6 50.4 62.1 38.2 67.9 25.4 54.0 49.1 59.3 37.0 64.7 24.3
62.2 62.2 67.6 50.1 73.9 37.4 60.1 60.1 65.0 49.0 71.0 36.4 57.9 57.9 62.2 47.8 68.0 35.3 55.7 55.7 59.4 46.5 64.9 34.2
65.4 65.4 67.8 59.8 74.0 47.3 63.3 63.3 65.2 58.6 71.1 46.2 61.0 61.0 62.5 57.5 68.0 45.0 58.7 58.7 59.8 56.3 64.9 43.8
68.7 68.7 68.6 68.6 74.1 56.8 66.5 66.5 66.4 66.4 71.2 55.7 64.1 64.1 64.1 64.1 68.2 54.5 61.7 61.7 61.7 61.7 65.1 53.3
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.
TWA-PRC001-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(TWA075A)
Table PD-5 —Gross Cooling Performance (MBh) TWA075A Heat Pump Only
ODTemp
Suction ReferenceTemperature °F
°F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
165
70.0
4.58
191
170
77.4
4.67
197
176
85.1
4.78
203
182
93.1
4.89
209
188
101.3
5.02
215
195
109.6
5.14
222
65
75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
68.2
5.04
75.2
5.15
82.5
5.27
90.1
5.39
97.8
105.6
5.65
5.52
Head press PSIG
Cap. Btuh/1000
OD Unit KW
219
225
72.3
5.71
231
79.2
5.84
238
86.4
5.97
245
93.6
6.10
252
101.1
6.24
85
95
65.5
5.59
Head press PSIG
Cap. Btuh/1000
OD Unit KW
250
62.3
6.22
256
68.7
6.35
263
75.3
6.48
270
82.0
6.61
277
88.9
6.74
284
95.9
6.88
Head press PSIG
Cap. Btuh/1000
OD Unit KW
283
58.6
6.93
289
64.6
7.06
296
70.8
7.18
304
77.1
7.31
311
83.7
7.45
319
90.3
7.59
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
318
54.4
7.72
325
60.0
7.83
332
65.8
7.95
340
71.8
8.08
347
78.0
8.22
355
84.4
8.36
Table PD-5 —Gross Cooling Performance (KW) TWA075A Heat Pump Only
ODTemp
Suction ReferenceTemperature °C
°C
-1.1
1.7
4.4
7.2
10
12.8
Head pressure (kPA)
Capacity (kW)
1136
20.5
1173
22.6
1213
24.9
1255
27.2
1298
29.7
1343
32.1
18.3
23.9
29.4
35.0
40.6
OD Unit Power (kW)
4.58
4.67
4.78
4.89
5.02
5.14
Head pressure (kPA)
Capacity (kW)
1315
20.0
5.04
1355
22.0
5.15
1397
24.2
5.27
1440
26.4
5.39
1484
28.6
5.52
1531
30.9
5.65
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
1509
19.2
5.59
1552
21.2
5.71
1596
23.2
5.84
1642
25.3
5.97
1689
27.4
1738
29.6
6.24
OD Unit Power (kW)
6.10
Head pressure (kPA)
Capacity (kW)
1721
18.3
6.22
1766
20.1
6.35
1812
22.0
6.48
1860
24.0
6.61
1909
26.0
6.74
1959
28.1
6.88
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
1948
17.2
1995
18.9
7.06
2043
20.7
7.18
2093
22.6
7.31
2144
24.5
7.45
2197
26.5
7.59
OD Unit Power (kW)
6.93
Head pressure (kPA)
Capacity (kW)
2192
15.9
7.72
2240
17.6
7.83
2290
19.3
7.95
2341
21.0
8.08
2395
22.8
8.22
2450
24.7
8.36
46.1
48.9
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
OD Unit Power (kW)
2320
15.3
8.13
2369
16.9
8.24
2419
18.5
8.36
2471
20.2
8.49
2526
22.0
8.62
2583
23.8
8.76
16
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(TWA100A)
Table PD-6— Gross Cooling Performance (MBh) TWA100A Heat Pump Only
ODTemp
Suction ReferenceTemperature °F
°F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
175
94.8
6.26
181
104.0
6.41
187
113.6
6.57
194
123.5
6.74
201
133.7
6.93
208
144.2
7.12
65
Head press PSIG
200
207
213
220
227
235
75
85
Cap. Btuh/1000
OD Unit KW
90.4
6.92
99.1
7.08
108.1
7.25
117.5
7.44
127.3
7.64
137.3
7.85
Head press PSIG
Cap. Btuh/1000
OD Unit KW
229
85.7
7.70
235
93.9
7.88
242
102.5
8.07
250
111.5
8.27
257
120.8
8.49
265
130.4
8.71
Head press PSIG
Cap. Btuh/1000
OD Unit KW
259
80.7
8.60
266
88.6
8.79
274
96.8
9.00
282
105.4
9.22
290
114.2
9.44
298
123.3
9.67
95
Head press PSIG
Cap. Btuh/1000
OD Unit KW
293
75.5
9.60
300
83.0
9.82
308
91.0
10.05
316
99.2
10.28
325
107.6
10.51
334
116.2
10.74
105
115
Head press PSIG
Cap. Btuh/1000
OD Unit KW
328
70.0
10.72
337
77.4
10.96
345
85.0
11.21
354
92.9
11.45
363
100.9
11.69
372
109.0
11.92
Table PD-6 —Gross Cooling Performance (MBh) TWA100A Heat Pump Only
ODTemp
Suction ReferenceTemperature °F
°C
-1.1
1.7
4.4
7.2
10
12.8
Head pressure (kPA)
Capacity (kW)
1206
27.7
1247
30.4
6.41
1290
33.3
6.57
1336
36.2
6.74
1383
39.2
6.93
1432
42.2
7.12
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
6.26
Head pressure (kPA)
Capacity (kW)
1382
26.5
6.92
1425
29.0
7.08
1470
31.7
7.25
1518
34.4
7.44
1568
37.3
7.64
1621
40.2
7.85
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
1576
25.1
7.70
1622
27.5
7.88
1670
30.0
8.07
1721
32.7
8.27
1774
35.4
8.49
1829
38.2
8.71
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
1788
23.6
8.60
1837
25.9
8.79
1888
28.3
9.00
1941
30.9
9.22
1997
33.5
9.44
2055
36.1
9.67
OD Unit Power (kW)
Head pressure (kPA)
Capacity (kW)
2017
22.1
9.60
2069
24.3
9.82
2124
26.6
2181
29.0
2240
31.5
2300
34.0
OD Unit Power (kW)
10.05
10.28
10.51
10.74
Head pressure (kPA)
Capacity (kW)
2265
20.5
2321
22.7
2379
24.9
2440
27.2
2502
29.5
2565
31.9
OD Unit Power (kW)
10.72
10.96
11.21
11.45
11.69
11.92
TWA-PRC001-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(TWA155A)
Table PD-7 —Gross Cooling Performance (MBh) TWA155A Heat Pump Only
ODTemp
Suction Reference Temperature °F
°F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
165
137.2
9.13
170
151.6
9.33
176
166.8
9.54
182
182.4
9.77
188
195
65
75
198.5
10.02
214.9
10.27
Head press PSIG
Cap. Btuh/1000
OD Unit KW
191
197
203
209
215
191.6
11.02
222
207.0
11.29
133.6
10.06
147.5
10.29
161.8
10.52
176.6
10.77
Head press PSIG
Cap. Btuh/1000
OD Unit KW
219
128.5
11.16
225
141.7
11.40
232
155.4
11.65
238
169.3
11.91
245
252
85
183.6
12.18
198.1
12.46
Head press PSIG
Cap. Btuh/1000
OD Unit KW
250
256
263
147.6
12.94
270
277
284
95
122.2
12.43
134.7
12.68
160.8
13.20
174.3
13.47
188.1
13.75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
283
114.9
13.85
289
296
304
311
319
105
115
126.7
14.10
138.8
14.35
151.2
14.61
164.0
14.89
177.1
15.17
Head press PSIG
Cap. Btuh/1000
OD Unit KW
318
325
117.7
15.65
332
340
347
355
106.7
15.41
129.1
15.89
140.8
16.15
152.9
16.42
165.4
16.70
Table PD-7 —Gross Cooling Performance (KW) TWA155A Heat Pump Only
ODTemp
Suction Reference Temperature °C
°C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
1136
40.2
9.13
1174
44.4
9.33
1213
48.8
9.54
1255
53.4
9.77
1299
58.1
1343
62.9
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
10.02
10.27
Head pressure (kPA)
Capacity (kW)
1315
39.1
1355
43.2
1397
47.4
1440
51.7
1485
56.1
1532
60.6
OD Unit Power (kW)
10.06
10.29
10.52
10.77
11.02
11.29
Head pressure (kPA)
Capacity (kW)
1510
37.6
1552
41.5
1597
45.5
1642
49.6
1690
53.8
1738
58.0
OD Unit Power (kW)
11.16
11.40
11.65
11.91
12.18
12.46
Head pressure (kPA)
Capacity (kW)
1722
35.8
1767
39.5
1813
43.2
1860
47.1
1909
51.0
1960
55.1
OD Unit Power (kW)
12.43
12.68
12.94
13.20
13.47
13.75
Head pressure (kPA)
Capacity (kW)
1949
33.6
1996
37.1
2044
40.6
2093
44.3
2145
48.0
2197
51.9
OD Unit Power (kW)
13.85
14.10
14.35
14.61
14.89
15.17
Head pressure (kPA)
Capacity (kW)
2192
31.2
2241
34.5
2291
37.8
2342
41.2
2395
44.8
2451
48.4
OD Unit Power (kW)
15.41
15.65
15.89
16.15
16.42
16.70
18
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(TWA200A)
Table PD-8 —Gross Cooling Performance (MBh) TWA200A Heat Pump Only
OD Temp
Suction Reference Temperature °F
° F
30
35
40
45
50
55
Head press PSIG
Cap. Btuh/1000
OD Unit KW
177
187.4
12.50
183
189
196
203
210
65
75
205.7
12.81
224.7
13.14
244.4
13.49
264.7
13.86
285.6
14.25
Head press PSIG
Cap. Btuh/1000
OD Unit KW
203
209
216
223
230
238
178.8
13.84
196.0
14.17
213.9
14.53
232.6
14.91
252.1
15.32
272.1
15.75
Head press PSIG
Cap. Btuh/1000
OD Unit KW
231
238
245
253
260
269
85
169.4
15.42
185.8
15.79
203.0
16.18
220.8
16.60
239.3
17.04
258.4
17.49
Head press PSIG
Cap. Btuh/1000
OD Unit KW
262
159.6
17.24
269
175.3
17.65
277
191.7
18.08
285
293
302
95
208.8
18.52
226.4
18.98
244.5
19.44
Head press PSIG
Cap. Btuh/1000
OD Unit KW
296
304
164.3
19.74
312
320
329
338
105
115
149.2
19.29
180.1
20.20
196.5
20.68
213.4
21.15
230.6
21.62
Head press PSIG
Cap. Btuh/1000
OD Unit KW
332
340
349
358
367
377
138.5
21.55
153.1
22.05
168.4
22.55
184.1
23.05
200.2
23.54
216.5
24.01
Table PD-8 — Gross Cooling Performance (KW) TWA200A Heat Pump Only
ODTemp
Suction ReferenceTemperature °C
°C
-1.1
1.7
4.4
7.2
10.0
12.8
Head pressure (kPA)
Capacity (kW)
1219
54.9
1261
60.2
1305
65.8
1351
71.5
1399
77.5
1449
83.6
18.3
23.9
29.4
35.0
40.6
46.1
OD Unit Power (kW)
12.50
12.81
13.14
13.49
13.86
14.25
Head pressure (kPA)
Capacity (kW)
1397
52.3
1441
57.4
1487
62.6
1536
68.1
1588
73.8
1642
79.7
OD Unit Power (kW)
13.84
14.17
14.53
14.91
15.32
15.75
Head pressure (kPA)
Capacity (kW)
1593
49.6
1640
54.4
1689
59.4
1741
64.7
1796
70.1
1852
75.7
OD Unit Power (kW)
15.42
15.79
16.18
16.60
17.04
17.49
Head pressure (kPA)
Capacity (kW)
1808
46.7
1857
51.3
1910
56.1
1965
61.1
2022
66.3
2081
71.6
OD Unit Power (kW)
17.24
17.65
18.08
18.52
18.98
19.44
Head pressure (kPA)
Capacity (kW)
2040
43.7
2093
48.1
2149
52.7
2207
57.5
2268
62.5
2329
67.5
OD Unit Power (kW)
19.29
19.74
20.20
20.68
21.15
21.62
Head pressure (kPA)
Capacity (kW)
2290
40.5
2348
44.8
2408
49.3
2470
53.9
2533
58.6
2597
63.4
OD Unit Power (kW)
21.55
22.05
22.55
23.05
23.54
24.01
TWA-PRC001-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-9 — Gross Heating Capacities (MBh)
TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM
Outdoor
Heating Capacity (BTUH/1000) At
Total Power in Kilowatts At
Temperature
(°F)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
60
70
75
80
60
70
75
80
-18
-13
-8
-3
2
34.9
35.5
36.5
37.9
30.4
31.5
33.1
35.0
37.5
40.3
43.5
47.1
51.1
55.4
60.1
64.8
69.7
74.8
80.2
85.6
91.2
96.8
102.5
28.5
30.0
31.8
34.0
36.7
39.7
43.1
46.9
51.0
55.3
60.0
64.7
69.6
74.7
79.9
85.3
90.8
96.2
101.9
26.9
28.6
30.6
33.2
36.1
39.3
42.9
46.8
50.9
55.3
60.0
64.7
69.5
74.5
79.6
84.9
90.2
95.6
101.2
5.5
5.5
5.4
5.4
5.4
5.4
5.5
5.5
5.6
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.7
6.9
7.1
5.6
5.6
5.6
5.6
5.7
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.6
6.8
7.0
5.7
5.7
5.8
5.8
5.9
6.0
6.1
6.2
6.3
6.4
6.6
6.8
6.9
7.1
5.8
5.9
5.9
6.0
6.1
6.2
6.3
6.5
6.6
6.8
6.9
7.1
7.3
7.5
7.6
7.8
8.0
8.2
8.4
39.7
42.0
44.8
48.0
51.7
55.8
60.3
65.0
69.9
75.1
80.6
86.2
92.0
97.8
7
12
17
22
27
32
37
42
47
52
57
62
67
72
7.3
7.5
7.7
7.9
7.1
7.3
7.5
7.7
103.7
8.1
Table PD-9 — Gross Heating Capacities (KW)
TWA075A Heat Pump withTWE075A Air Handler At 1180 L/S
Outdoor
Heating Capacity (KW) At
Total Power in Kilowatts At
Temperature
(°C)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0 . 0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2
10.2
10.4
10.7
11.1
8.9
9.2
9.7
8.4
8.8
9.3
7.9
8.4
9.0
9.7
5.5
5.6
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.6
6 . 8
6.9
7.1
7.3
7.5
7.7
7.9
8.1
8.4
6.0
6.1
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7. 4
7.6
7.8
8.0
8.2
8.4
8.7
8.9
9.2
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7. 7
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
10.3
11.0
11.8
12.7
13.8
15.0
16.2
1 7. 6
19.0
20.4
21.9
23.5
25.1
26.7
28.3
30.0
10.0
10.7
11.6
12.6
13.7
14.9
16.2
1 7. 6
19.0
20.4
21.9
23.4
25.0
26.6
28.2
29.8
11.6
10.6
11.5
12.6
13.7
14.9
16.2
1 7. 6
18.9
20.3
21.8
23.3
24.9
26.4
28.0
29.6
12.3
13.1
14.1
15.1
16.3
1 7. 7
19.0
20.5
22.0
23.6
25.2
26.9
28.6
30.4
7.9
8 . 1
8.3
8.5
8.8
9.0
9.2
9.5
9.8
10.0
7.9
8.1
8.4
8.6
8.8
9.1
9.3
9.6
Airflow = 2500 cfm (1179 L/s)
Correction Factors - Other Airflows
(Table Value x Correction Factor = Value at new airflow)
HeatingCapacity(HighTemp.)=75,000(21.82)
HeatingCapacity(LowTemp.)=47,000(13.84)
Compressor Power (High Temp) = 5.41 kW
Compressor Power (Low Temp) = 4.55 kW
Coeff. Of Perf. (High Temp) = 3.2
Coeff. Of Perf. (Low Temp) = 2.3
Outdoor Fan Power = 550 watts
Airflow
2250CFM
1061L/s
x0.99
2750CFM
1297L/s
x1.01
HeatingCapacity
Compressor Kw
x1.02
x0.98
Indoor Fan Power = 800 watts
Values at ARI Rating Conditions of:
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)
Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.
20
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-10 — Gross Heating Capacities (MBh)
TWA100A Heat Pump withTWE100A Air Handler At 3325 CFM
Outdoor
Heating Capacity (BTUH/1000) At
Total Power in Kilowatts At
Temperature
(°F)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
60
70
75
80
60
70
75
80
-18
-13
-8
-3
2
21.9
33.4
40.8
46.7
52.3
57.7
63.2
68.9
74.8
80.9
87.3
93.6
100.2
107.1
114.4
121.9
129.7
137.7
145.9
39.6
43.6
47.5
43.0
46.0
49.2
52.8
56.5
60.6
65.1
69.9
75.1
80.6
86.5
92.6
98.9
105.6
112.7
120.1
127.8
135.6
143.7
44.8
47.3
50.2
53.4
57.0
5.6
6.2
6.6
6.8
7.0
7.2
7.4
7.5
7.7
7.3
7.5
7.6
7.8
7.9
7.9
8.0
8.1
8.2
8.4
8.5
8.6
8.8
9.0
9.1
9.4
9.6
9.8
10.1
10.3
10.6
10.9
11.2
11.6
8.4
8.5
8.6
8.7
8.8
8.9
9.1
9.2
9.4
51.5
55.7
60.1
64.8
69.8
75.1
80.8
86.8
92.9
99.3
106.0
113.2
120.6
128.3
136.2
144.3
7
60.8
65.1
69.8
74.9
80.3
86.2
92.2
98.5
105.2
112.3
119.7
127.3
135.1
143.2
8.1
8.2
8.4
8.5
8.7
8.9
9.1
9.3
9.5
9.8
10.1
10.4
10.7
11.0
12
17
22
27
32
37
42
47
52
57
62
67
72
7.9
9.6
9.8
8.0
8.2
8.4
8.6
8.8
9.1
9.3
9.6
9.9
10.1
10.3
10.6
10.9
11.2
11.5
11.9
12.2
Table PD-10 — Gross Heating Capacities (KW)
TWA100A Heat Pump withTWE100A Air Handler At 1570 L/S
Outdoor
Heating Capacity (KW) At
Total Power in Kilowatts At
Temperature
(°C)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2 . 8
5.6
8.3
11.1
13.9
16.7
19.4
22.2
6.4
9.8
11.6
12.8
13.9
15.1
16.3
17.6
19.0
20.4
22.0
23.7
25.4
2 7. 2
29.1
31.0
33.1
35.3
37.6
39.9
42.3
12.6
13.5
14.4
15.4
16.6
17.8
19.1
20.5
22.0
23.6
25.3
2 7. 1
29.0
30.9
33.0
35.2
37.4
13.1
13.9
14.7
15.6
16.7
17.8
19.1
20.4
21.9
23.5
25.2
2 7. 0
28.8
30.8
32.9
35.0
37.3
39.6
41.9
5.5
5.6
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.6
6.8
6 . 9
7.1
7.3
7.5
7.7
7.9
8.1
8.4
6.0
6.1
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.6
7.8
8.0
8.2
8.4
8.7
8.9
9.2
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
11.9
13.7
15.3
16.9
18.5
20.2
21.9
23.7
25.6
2 7. 4
29.3
31.3
33.5
35.7
38.0
40.3
42.7
7.9
8.1
8.3
8.5
8.8
9.0
9.2
9.5
9.8
10.0
7.9
8.1
8.4
8.6
8.8
9.1
9.3
9.6
39.7
42.1
Airflow = 3325 cfm (1569 L/s)
Correction Factors - Other Airflows
(Table Value x Correction Factor = Value at new airflow)
HeatingCapacity(HighTemp.)=106,000(31.05)
HeatingCapacity(LowTemp.)=69,000(20.29)
Compressor Power (High Temp) = 7.61 kW
Compressor Power (Low Temp) = 6.38 kW
Coeff. Of Perf. (High Temp) = 3.30
Coeff. Of Perf. (Low Temp) = 2.4
Outdoor Fan Power = 644 watts
Airflow
3000CFM
1416L/s
x0.99
3675CFM
1734L/s
x1.01
HeatingCapacity
Compressor Kw
x1.02
x0.98
Indoor Fan Power = 1,170 watts
Values at ARI Rating Conditions of:
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)
Note:
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.
TWA-PRC001-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-11 — Gross Heating Capacities (MBh)
TWA155B Heat Pump withTWE155B Air Handler At 5000 CFM
Outdoor
Heating Capacity (BTUH/1000) At
Total Power in Kilowatts At
Temperature
(°F)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
60
70
75
80
60
70
75
80
-18
-13
-8
-3
2
69.7
71.1
73.1
76.0
79.8
84.5
90.2
96.7
104.2
112.6
121.8
131.3
141.4
151.9
163.0
174.4
186.2
198.0
210.0
60.9
63.2
66.4
70.4
75.4
81.1
87.7
95.1
103.2
111.9
121.4
131.0
140.9
151.3
162.2
173.3
184.6
196.0
207.6
57.2
60.2
63.9
68.4
73.9
80.0
87.0
94.6
102.9
111.8
121.3
130.8
140.7
151.0
161.6
172.5
183.6
194.8
206.2
54.0
57.4
61.6
66.8
72.7
79.3
86.6
94.4
102.8
111.8
121.3
130.7
140.5
150.6
161.0
171.7
182.6
193.5
204.8
11.1
11.0
11.0
10.9
10.9
11.0
11.1
11.2
11.3
11.5
11.7
12.0
12.3
12.6
12.9
13.2
13.6
14.0
14.4
11.4
11.3
11.4
11.4
11.5
11.6
11.8
12.0
12.2
12.5
12.8
13.1
13.4
13.8
14.1
14.5
14.9
15.3
15.7
11.5
11.6
11.6
11.7
11.9
12.1
12.3
12.5
12.8
13.1
13.4
13.8
14.1
14.5
14.8
15.2
15.6
16.0
16.4
11.8
11.8
12.0
12.1
12.3
12.6
12.8
13.1
13.4
13.7
14.1
14.4
14.8
15.2
15.6
15.9
16.3
16.7
17.1
7
12
17
22
27
32
37
42
47
52
57
62
67
72
Table PD-11 — Gross Heating Capacities (KW)
TWA155B Heat Pump withTWE155B Air Handler At 2360 L/S
Outdoor
Heating Capacity (KW) At
Total Power in Kilowatts At
Temperature
(°C)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2
20.4
20.8
21.4
22.3
23.4
24.7
26.4
28.3
30.5
33.0
35.7
38.5
41.4
44.5
47.7
17.8
18.5
19.4
20.6
22.1
23.8
25.7
27.8
30.2
32.8
35.5
38.3
41.3
44.3
47.5
16.8
17.6
18.7
20.0
21.6
23.4
25.5
27.7
30.1
32.7
35.5
38.3
41.2
44.2
47.3
50.5
53.8
57.0
60.4
15.8
16.8
18.0
19.6
21.3
23.2
25.3
27.6
30.1
32.7
35.5
38.3
41.1
44.1
47.2
5.5
5.6
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.6
6.8
6.9
7.1
7.3
7.5
7.7
7.9
8.1
8.4
6.0
6.1
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.6
7.8
8.0
8.2
8.4
8.7
8.9
9.2
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
7.9
8.1
8.3
8.5
8.8
9.0
9.2
9.5
9.8
10.0
7.9
8.1
8.4
8.6
8.8
9.1
9.3
9.6
51.1
54.5
58.0
61.5
50.7
54.0
57.4
50.3
53.5
56.7
60.0
60.8
Correction Factors - Other Airflows“(Table Value
Correction Factor = Value at new airflow)
Airflow = 5000 cfm (2360 L/s)
HeatingCapacity(HighTemp.)=151,000(44.27)
HeatingCapacity(LowTemp.)=95,000(27.67)
Compressor Power (High Temp) = 10.94 kW
Compressor Power (Low Temp) = 9.18 kW
Coeff. Of Perf. (High Temp) = 3.2
Airflow
4500CFM 5500CFM“
2124 L/s 2596 L/s
HeatingCapacity
Compressor Kw
x 0.99
x 1.02
x 1.01
x 0.98
Coeff. Of Perf. (Low Temp) = 2.3
Outdoor Fan Power = 1100 watts
Indoor Fan Power = 1700 watts
Values at ARI Rating Conditions of:
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)
Note:
1.Rated with 25 feet of 1-3/8"" suction and 1/2"" liquid line."
22
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(System)
Table PD-12 — Gross Heating Capacities (MBh)
TWA200B Heat Pump withTWE200B Air Handler At 6675 CFM
Outdoor
Heating Capacity (BTUH/1000) At
Total Power in Kilowatts At
Temperature
(°F)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
60
70
75
80
60
70
75
80
-18
-13
-8
-3
2
43.5
68.9
82.3
80.3
87.1
94.2
85.7
91.0
97.0
88.4
93.0
98.4
10.8
12.3
13.0
13.4
13.8
14.1
14.5
14.8
15.1
15.4
15.7
16.0
16.4
16.7
17.2
14.5
14.8
15.1
15.3
15.6
15.8
16.1
16.4
16.7
17.1
17.4
17.8
18.2
18.6
19.1
19.6
20.1
20.6
21.2
15.6
15.8
16.0
16.2
16.4
16.7
17.0
17.3
17.6
18.0
18.4
18.8
19.2
19.7
20.2
20.7
21.2
21.8
22.4
16.5
16.7
16.8
17.1
17.3
17.6
17.9
18.2
18.5
18.9
19.4
19.8
20.3
20.8
21.3
21.9
22.4
23.0
23.7
93.2
101.6
109.4
117.8
126.8
136.4
146.7
157.6
169.3
181.2
193.5
206.5
220.3
234.6
249.2
264.0
279.4
103.6
110.8
118.6
127.2
136.5
146.5
157.2
168.8
180.5
192.7
205.7
219.4
233.6
248.2
262.9
278.2
104.5
111.3
118.8
127.1
136.1
146.0
156.6
168.1
179.8
192.0
205.0
218.7
232.9
247.4
262.1
277.2
103.5
113.7
124.2
135.0
146.2
157.9
170.2
182.4
195.1
208.4
222.4
236.9
251.7
266.7
282.3
7
12
17
22
27
32
37
42
47
52
57
62
67
72
17.6
18.1
18.5
19.1
Table PD-12 — Gross Heating Capacities (KW)
TWA200B Heat Pump with TWE200B Air Handler At 3150 L/S
Outdoor
Heating Capacity (KW) At
Total Power in Kilowatts At
Temperature
(°C)
Indicated Indoor Dry BulbTemperature
Indicated Indoor Dry BulbTemperature
15.6
21.1
23.9
26.7
15.6
21.1
23.9
26.7
27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2
12.7
20.2
24.1
27.3
30.3
33.3
36.4
39.5
42.8
46.2
49.8
53.4
57.1
61.0
65.1
69.4
73.7
78.1
82.7
23.5
25.5
27.6
29.7
32.0
34.5
37.1
39.9
42.9
46.2
49.6
53.0
56.7
60.5
64.5
68.7
73.0
77.3
25.1
26.6
28.4
30.3
32.4
34.7
37.2
40.0
42.9
46.0
49.4
52.8
56.4
60.2
64.3
68.4
72.7
77.0
25.9
27.2
5.5
5.6
5.7
5.8
5.9
6.0
6.2
6.3
6.5
6.6
6.8
6.9
7.1
7.3
7.5
7.7
7.9
8.1
8.4
6.0
6.1
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.6
7.8
8.0
8.2
8.4
8.7
8.9
9.2
6.2
6.3
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
6.5
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
28.8
30.6
32.6
34.8
37.2
39.9
42.7
45.9
49.2
52.6
56.2
60.0
64.0
68.2
72.4
76.7
81.2
7.9
8.1
8.3
8.5
8.8
9.0
9.2
9.5
9.8
10.0
7.9
8.1
8.4
8.6
8.8
9.1
9.3
9.6
81.8
81.5
Correction Factors - Other Airflows
(Table Value x Correction Factor = Value at new airflow)
Airflow = 6700 cfm (3162 L/s)
Heating Capacity (High Temp.) = 206,000 (60.26)
Heating Capacity (Low Temp.) = 135,000 (39.66)
Compressor Power (High Temp) = 14.92 kW
Compressor Power (Low Temp) = 12.62 kW
Coeff. Of Perf. (High Temp) = 3.2
Airflow
6000CFM
2832L/s
x0.99
7325CFM
3457L/s
x1.01
HeatingCapacity
Compressor Kw
x1.02
x0.98
Coeff. Of Perf. (Low Temp) = 2.4
Values at ARI Rating Conditions of:
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)
Outdoor Fan Power = 1,100 watts
Indoor Fan Power = 2,290 watts
Note:
1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line."
TWA-PRC001-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(Air Handler)
Table PD-13 — Evaporator Fan Performance —TWE050A
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40" .50" .60" .70" .80"
.90"
1.00"
1.10"
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
0.75 HP Standard Motor and Drive
1400
1500
1600
1700
1800
1900
2000
2100
—
—
—
—
—
—
—
—
646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71
607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71
625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74
601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77
625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76
642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80
659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84
674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89
1.0HPOversizedMotorandHighStaticDrive
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Table PD-13— Evaporator Fan Performance —TWE050A
External Static Pressure (Pascal)
25
50
75
100 125 150
174
199
224
249
274
L/S
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW
0.56 Standard Motor and Drive
661
708
755
802
850
897
944
991
646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53
607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53
625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55
601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57
625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57
642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60
659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.67
674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66
0.75KWOversizedMotorandHighStaticDrive
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in
0.5 turn increments.
Table PD-14 — Blower Speeds
Motor DriveTurns Open
Drive
6
5
4
3
2
1
0
Standard
High Static
N/A
N/A
590
713
639
772
688
832
737
891
786
951
835
1009
24
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(Air Handler)
Table PD-15 — Evaporator Fan Performance TWE075A
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.10
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2000
2125
2250
2375
2500
2625
2750
2875
3000
443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89
453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96
463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03
473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10
445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14
464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17
484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21
504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24
524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27
1.0 HP Standard Motor
andHighStaticDrive
1.0 HP Standard Motor
and Low Static Drive
1.5 HP Oversized Motor
andHighStaticDrive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway
filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are
made in 0.5 turn increments.
Table PD-15— Continued
External Static Pressure (In. Of Water Column)
120 1.30 1.40 1.50 1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
CFM
2000
2125
2250
2375
2500
2625
2750
2875
3000
844 0.96 871 1.02 897 1.09 924 1.15 950 1.21
852 1.03 879 1.09 906 1.16 933 1.22
859 1.10 886 1.17 914 1.23 942 1.30
866 1.17 894 1.24 922 1.30 950 1.37
870 1.21 899 1.29 928 1.36
874 1.25 903 1.33 932 1.42
877 1.29 907 1.38 937 1.47
880 1.33 911 1.43 942 1.52
884 1.37 915 1.48 946 1.58
Table PD-15 — Evaporator Fan Performance TWE075A
External Static Pressure (Pascal)
25
50
75
100
125 150 174
199
224
249
274
L/S
944
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
443 0.33 489 0.37 535 0.40 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66
453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72
463 0.37 510 0.41 556 0.45 602 0.50 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77
473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82
445 0.35 489 0.40 533 0.45 578 0.50 622 0.54 667 0.60 711 0.64 756 0.69 784 0.74 813 0.80 842 0.85
464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87
484 0.40 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.90
504 0.42 540 0.46 576 0.51 612 0.55 648 0.60 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92
524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.80 821 0.87 853 0.95
1003
1062
1121
1180
1239
1298
1357
1416
.75 KW Standard Motor
andHighStaticDrive
.75 KW Standard Motor
and High Static Drive
1.12 KW Oversized Motor
andHighStaticDrive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway
filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are
made in 0.5 turn increments.
Table PD-15 — Continued
External Static Pressure (Pascal)
324 349 374
299
398
L/S
944
RPM KW RPM KW RPM KW RPM KW RPM KW
844 0.72 871 0.76 897 0.81 924 0.86 950 0.90
852 0.77 879 0.81 906 0.87 933 0.91
859 0.82 886 0.87 914 0.92 942 0.97
866 0.87 894 0.92 922 0.97 950 1.02
870 0,90 899 0.96 928 1.01
1003
1062
1121
1180
1239
1298
1357
1416
874 0.93 903 0.99 932 1.06
877 0.96 907 1.03 937 1.10
880 0.99 911 1.07 942 1.13
884 1.02 915 1.10 946 1.18
Table PD-16 — Blower Speeds
Motor DriveTurns Open
Drive
6
5
4
3
2
1
0
Standard
Low Static N/A
High Static N/A
N/A
600
428
700
650
464
750
700
499
800
750
535
850
800
571
900
850
606
950
TWA-PRC001-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(Air Handler)
Table PD-17 — Evaporator Fan Performance TWE100A,TWE100B
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.20
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600
2775
2950
3125
3300
3475
3650
3825
4000
460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16
473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20
487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25
501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30
520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37
541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48
562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59
582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74
602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89
1.5 HP Standard Motor
andDrive
2.0 HP Oversized Motor
andHighStaticDrive
1.5 HP Standard Motor
and Low Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway
filters.
Table PD-17— Continued
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are
made in 0.5 turn increments.
External Static Pressure (In. Of Water Column)
1.40 1.60
CFM
RPM BHP RPM BHP
4. Low Static Drive must be field supplied.
2600
2775
2960
3125
3300
3475
3650
3825
4000
881 1.30 936 1.45
884 1.36 938 1.51
886 1.41 939 1.57
889 1.47 941 1.64
892 1.54 945 1.73
897 1.63 950 1.85
902 1.73 955 1.99
912 1.89 960 2.18
922 2.04 965 2.30
Table PD-17— Evaporator Fan Performance TWE0100A,TWE100B
External Static Pressure (Pascal)
25
50
75
100 125 150
174
199
224
249
274
L/S
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW
1227
1310
1392
1475
1557
1640
1723
1805
1888
460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.70 772 0.75 826 0.87
473 0.28 576 0.34 613 0.40 649 0.45 686 0.51 723 0.57 748 0.63 775 0.69 830 0.75 884 0.80 938 0.89
487 0.32 519 0.37 552 0.43 587 0.50 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93
501 0.37 532 0.42 565 0.48 599 0.54 632 0.60 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97
520 0.43 548 0.48 581 0.54 613 0.60 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02
541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.80 721 0.87 746 0.90 764 0.95 793 1.00 846 1.10
562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19
582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.30
602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41
1.49 KW Oversized Motor
andHighStaticDrive
1.12 KW Standard
Motor and Drive
.75 KW Standard Motor
and Low Static Drive
Notes:
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway
filters.
Table PD-17— Continued
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 3.0 turns open. Adjustments are
made in 0.5 turn increments.
External Static Pressure (Pascal)
349
398
4. Low Static Drive must be field supplied.
L/S
RPM KW RPM KW
1227
1310
1392
1475
1557
1640
1723
1805
1888
881 0.97 936 1.08
506 1.01 540 1.13
886 1.05 939 1.17
889 1.10 941 1.22
892 1.15 945 1.29
897 1.22 950 1.38
902 1.29 955 1.48
912 1.41 960 1.63
922 1.52 965 1.72
Table PD - 18 — Blower Speeds
Motor SheaveTurns Open
Drive
6
5
4
3
2
1
0
Standard
Low Static N/A
High Static N/A
N/A
587
453
606
629
485
641
671
518
677
713
550
713
755
583
748
796
615
784
26
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(Air Handler)
Table PD-19 — Evaporator Fan Performance — TWE155B
External Static Pressure (Inches of Water Column)
.10"
.20"
.30"
.40"
.50" .60" .70" .80" .90"
1.00"
1.20"
140
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2.0HPStandardMotorandDrive
3.0HPOversizedMotor
andHighStaticDrive
4000
4250
4500
4750
5000
5260
5500
5750
6000
628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03
633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11
637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19
641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27
645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13
650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28
652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44
653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61
655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78
Table PD-19 — Evaporator Fan Performance TWE155B
External Static Pressure (Pascal)
25
50
75
100
125 150 174
199
224
249
299
349
L/S
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW RPM KW
1.49KWStandardMotorandDriveSystem
2.24KWOversizedMotor
andHighStaticDriveSystem
1888
2006
2124
2242
2360
2482
2596
2714
2832
628 1.00 653 1.03 678 1.07 692 1.10 708 1.13 723 1.17 738 1.19 749 1.20 759 1.21 795 1.24 851 1.38 907 1.51
633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57
637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63
641 1.06 666 1.12 691 1.14 705 1.20 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.50 940 1.69
645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.30 806 1.35 839 1.42 896 1.59
650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.30 790 1.36 819 1.43 849 1.51 907 1.70
652 1.10 678 1.16 703 1.22 721 1.28 734 1.30 747 1.33 775 1.36 804 1.43 832 1.51 861 1.60 920 1.82
653 1.10 680 1.17 706 1.25 726 1.31 743 1.30 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95
655 1.11 681 1.19 709 1.30 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07
Notes:
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
Table PD-20—Blower Speeds
Motor SheaveTurns Open
Drive
6
5
4
3
2
1
0
Standard
High Static
619
777
648
806
677
835
705
863
734
892
763
921
N/A
950
TWA-PRC001-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(Air Handler)
Table PD-21— Evaporator Fan Performance TWE200B
External Static Pressure (In. Of Water Column)
0.10
0.20
0.30
0.40 0.50 0.60 0.70 0.80
0.90
1.00
1.20
140
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5200
5525
5850
6175
6500
6825
7150
7475
7800
461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39
479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60
497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81
473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02
492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22
510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42
528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62
550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85
572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08
3.0Standard
Motorand
LowStaticDrive LowStaticDrive
3.0 HP Standard
Motor and Field-Supplied
5HPOversizedMotor
andHighStaticDrive
Notes:
Table PD-21— Continued
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in
0.5 turn increments.
External Static Pressure (In. Of Water Column)
1.60 1.80
CFM
RPM BHP RPM BHP
5200
5525
5850
5175
8500
8825
7150
7475
7800
944 2.75 989 3.12
952 2.96 997 3.33
961 3.17 1006 3.54
970 3.38 1015 3.75
978 3.59 1023 3.96
986 3.80
994 4.01
1003 4.25
1012 4.50
Table PD-21— Evaporator Fan Performance TWE200B
External Static Pressure (Pascal)
25
50
75
100 125 150
174
199
224
249
299
349
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2454
2608
2761
2914
3068
3221
3374
3528
3681
461 0.55 503 0.68 545 0.80 587 0.77 619 0.87 685 1.04 723 1.19 750 1.30 777 1.41 851 1.63 898 1.78
479 0.66 521 0.78 563 0.90 605 0.90 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94
497 0.75 539 0.88 581 1.00 623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.90 915 2.10
473 0.74 515 0.86 557 0.98 599 1.10 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52
492 0.84 534 0.95 576 1.08 618 1.20 660 1.30 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.40
510 0.93 552 1.06 594 1.19 636 1.30 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.30 941 2.55
528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.70
550 1.20 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.10 840 2.21 865 2.32 914 2.59 959 2.87
572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04
StandardMotor 3.0 HP Standard
3.0HPand
LowStaticDrive LowStaticDrive
Motor and Field-Supplied
5HPOversizedMotor
andHighStaticDrive
Notes:
Table PD-21— Continued
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.
2. Tabulated brake horsepower is the motor shaft output required.
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn
increments.
External Static Pressure (Pascal)
398 448
CFM
RPM BHP RPM BHP
2454
2608
2761
2914
3068
3221
3374
3528
3681
944 2.05 989 2.33
952 2.21 997 2.48
961 2.36 1006 2.64
970 2.52 1015 2.80
978 2.68 1023 2.95
941 2.55 986 2.83
994 2.99
Table PD-22 — Blower Speeds
Motor SheaveTurns Open
1003 3.17
1012 3.36
Drive
6
5
4
3
2
1
0
Standard
Low Static
Field-Supplied Low Static
High Static
706
457
574
N/A
732
478
595
821
758
500
617
862
784
521
638
903
811
542
659
945
837
563
680
986
863
585
702
1027
28
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-23— Discharge PlenumAnd GrilleAssemblyThrow Distance —Air Handler
Unit
Louver Angle Deflection Position
Model No.
CFM
L/S
Straight
20, Ft. (m)
40, Ft. (m)
55, Ft. (m)
1400
1600
1800
2000
2200
2100
661
755
850
944
1038
38 (11.6)
42 (12.8)
46 (14.0)
48 (14.6)
51 (15.5)
49 (14.9)
24 (7.3)
22 (6.7)
26 (7.9)
29 (8.8)
33 (10.1)
36 (11.0)
31 (9.4)
18 (5.5)
20 (6.1)
22 (6.7)
24 (7.3)
25 (7.6)
27 (8.2)
31 (9.4)
37 (11.3)
43 (13.1)
50 (15.2)
38 (11.6)
TWE050
TWE075
991
2400
2700
3000
3200
3600
1133
1274
1416
1510
1699
52 (15.9)
55 (16.8)
58 (17.7)
56 (17.1)
62 (18.9)
43 (13.1)
48 (14.6)
53 (16.2)
46 (14.0)
51 (15.5)
35 (10.7)
38 (11.6)
42 (12.8)
38 (11.6)
42 (12.8)
29 (8.8)
31 (9.4)
32 (9.8)
30 (9.1)
33 (10.1)
4000
4400
4800
4300
4900
1888
2077
2265
2029
2313
66 (20.1)
71 (21.6)
76 (23.2)
42 (12.8)
47 (14.3)
57 (17.4)
62 (18.9)
67 (20.4)
32 (9.8)
47 (14.3)
52 (15.9)
56 (17.1)
29 (8.8)
32 (9.8)
35 (10.7)
38 (11.6)
42 (12.8)
21 (6.4)
25 (7.6)
TWE100
TWE155
TWE200
38 (11.6)
5400
6000
5600
6400
2549
2832
2643
3020
52 (15.9)
57 (17.4)
50 (15.2)
56 (17.1)
44 (13.4)
49 (14.9)
40 (12.2)
46 (14.0)
37 (11.3)
41 (12.5)
33 (10.1)
38 (11.6)
29 (8.8)
32 (9.8)
27 (8.2)
30 (9.1)
7200
8000
3398
3776
62 (18.9)
66 (20.1)
51 (15.5)
57 (17.4)
42 (12.8)
47 (14.3)
33 (10.1)
35 (10.7)
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by
throw factor:
Terminal Velocity
50 FPM (.25 m/s)
100 FPM (.51 m/s)
150 FPM (.76 m/s)
Throw Factor
x
x
x
1.50
.75
.50
PD-24 — Static Pressure DropThroughAccessories —Air Handler
Discharge
Unit
Model No.
Return Grille
Plenum and Grille2
Electric Heaters (Kw)
CFM
L/S
In.W.C.1 Pascal In.W.C.1 Pascal
3.5-7
10-14
17-24
35
1400
1600
2000
2100
661
755
944
991
.09
.12
.18
.05
(22.4)
(29.9)
(44.8)
(12.5)
.16
.21
.33
.19
(39.8)
(52.3)
(82.2)
(47.3)
.06
08
.13
.06
.08
.13
.03
.12
.14
.19
.05
—
—
—
TWE050A
TWE075A
.02
.08
2400
3000
1133
1416
.08
.13
(19.9)
(32.4)
.27
.40
(67.2)
(99.6)
.03
.06
.06
.12
.08
.17
.12
.23
TWE100A
TWE100B
2800
3200
4300
1321
1510
2029
.04
.07
.07
(10.0)
(17.4)
(17.4)
.34
.43
.18
(84.7)
(107.1)
(44.8)
.03
.06
.02
.04
.13
.02
.14
.19
.04
.20
.26
.05
4800
6000
5600
2265
2832
2643
.09
.15
.07
(22.4)
(37.4)
(17.4)
.23
.34
.32
(57.3)
(84.7)
(79.7)
.03
.06
.04
.03
.06
.04
.06
.12
.10
.08
.17
.15
TWE155B
TWE200B
6400
8000
3020
3776
.11
.17
(27.4)
(42.3)
.43
.66
(107.1)
(164.3)
.06
.10
.0-6
.10
.13
.20
.19
.30
1. Return air filter ESP included in Fan Performance Table data.
2. At louver opening angle of 42° F (5.5° C). For ESP at other angle openings, see accessory Installer’s Guide.
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by
throw factor:
Terminal Velocity
50 FPM (.25 m/s)
100 FPM (.51 m/s)
150 FPM (.76 m/s)
Throw Factor
x
x
x
1.50
.75
.50
.
TWA-PRC001-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-25 — Auxiliary Electric Heat Capacity —Air Handler
No.
Stage 1
Stage 2
Btuh
Total
Unit
Total
of
KW
Btuh
KW
KW
KW
Btuh
KW
Model No.
KW Stages Input
Output Output Input
Output Output Output Output
TWE050, 075,100
3.47
6.92
10.39
17.31
1
1
1
2
3.47
9.92
10.39
10.39
11,851
23,606
35,457
35,457
3.47
6.92
10.39
10.39
—
—
—
—
—
—
—
—
—
11,851
23,606
35,457 10.39
3.47
6.92
6.92
23,606
6.92 59,063 17.31
TWE075, 100A, 100 24.22
2
13.83
47,213
13.83
10.39
35,457 10.39 82,670 24.22
TWE155, 200
6.94
13.83
20.78
34,62
1
1
2
2
6.94
13.83
13.83
20.78
23,701
47,213
47,213
70,915
6.94
13.83
13.83
20.78
—
—
6.94
—
—
23,701
—
—
23,701
47,213 13.83
6.94
6.94 70,915 20.78
13.89 118,128 34.61
13.84
47,213
*Heaters are rated at 400v. For other than rated voltage,
2
2
Voltage
Voltage
Rated Voltage
Capacity =
x Rated Capacity and KW =
x Rated KW.
(
)
(
)
Rated Voltage
30
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-1— Electrical Characteristics — Motors — Air Handler
Standard Fan Motor
Oversized Fan Motor
Unit
Amps
Amps
Model No.
TWE050
TWE075
TWE100
TWE155
TWE200
Volts
Phase
FLA
1.4
3.2
3.6
4.6
7.6
LRA
8.2
19.7
25.5
37.5
39.2
Phase
FLA
1.8
4.0
5.3
6.9
9.0
LRA
21.6
25.5
37.5
39.2
65.1
380/415
380/415
380/415
380/415
380/415
3
3
3
3
3
3
3
3
3
3
Table ED-2 — UnitWiring — Air Handler
Minimum
Circuit
Ampacity
Maximum Fuse
Size or Maximum
Circuit Breaker
Unit
Model No.
Unit Operating
Voltage Range
TWE050
TWE075
TWE100
380/415
380/415
380/415
2
4
5
15
15
15
TWE155
TWE200
380/415
380/415
6
10
15
15
Table ED-3— Electrical Characteristics — Motors — 60 Cycle — Heat Pumps
Compressor Motor
Condenser Fan Motor
Amps
FLA LRA
Amps
Unit
RLA
(Ea.)
LRA
(Ea.)
Model No.
No.
Volts
Phase
No.
Volts
Phase
(Ea.)
(Ea.)
TWA075AD
TWA100AD
TWA155BD
TWA200BD
1
1
2
2
380/415
380/415
380/415
380/415
3
3
3
3
11.0
14.9
11.0
14.9
90.0
118.0
90.0
1
1
2
2
380/415
380/415
380/415
380/415
1
1
1
1
1.6
2.7
1.6
2.7
3.7
7.0
3.7
7.0
118.0
Table ED-4 — UnitWiring — Heat Pumps
Minimum
Circuit
Ampacity
Maximum Fuse
Size or Maximum
Circuit Breaker
Unit
Model No.
Unit Operating
Voltage Range
TWA075
TWA100
380/415
380/415
18.0
25.6
30
40
TWA155
TWA200
380/415
380/415
31.6
45.2
40
60
TWA-PRC001-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-5— UnitWiringWith Electric Heat (Single Point Connection) —Air Handlers
Heater
Model No.
Heater
KW Rating1
3.47
To Use
with Unit
Control
Stages
Minimum
Maximum
Circuit Ampacity 2
Fuse Breaker Size 2
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
2
9
17
24
39
11
15
20
25
40
15
20
30
45
60
15
25
30
45
60
30
40
60
90
40
50
60
90
6.92
TWE050AD
10.39
17.31
3.47
6.92
18
26
41
56
12
19
27
42
57
21
36
51
81
25
40
55
85
10.39
17.31
24.22
3.47
TWE075AD
6.92
10.39
20.78
24.22
6.94
13.83
20.78
34.62
6.94
TWE100AD,TWE100BD
TWE155BD
13.83
20.78
34.62
TWE200BD
1. KW ratings are at 400v for 3 phase, 400v air handlers
2
2
Voltage
Voltage
Rated Voltage
For other than rated voltage, ampacity =
x Rated Capacity and KW =
Rated KW.
(
)
(
)
Rated Voltage
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Field wire must be rated at least 75° C.
4. Field wire must be rated at least 90° C.
32
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Jobsite
Connections
Wiring shown with dashed lines is to be
furnished and installed by the customer.
All customer- supplied wiring must be
copper only and must conform to NEC
and local electrical codes. Codes may
require line of sight between disconnect
switch and unit.
NOTE:
1.When electric heater accessory is used
single point power entry or dual point
power entry is field optional. Single point
power entry option is through electric
heater only.
TWA050/TWE050
FieldWiring:
A
B
C
— 3 power wires. Line voltage.
— 3 power wires. Line voltage.
— Heat pump thermostat: 6 wires,
24 volts.
— Electric heat: add 2 additional
wires, 24 volts.
— 2 wires, 24 volts.
D
— Outdoor thermostat: add 1
additional wire per ODT, 24 volts.
— Electric heat: add 1 additional
wire, 24 volts.
(2)TWA050/TWE100B
FieldWiring:
A
B
C
— 3 power wires. Line voltage.
— 3 power wires. Line voltage.
— Heat pump thermostat: 7 wires,
24 volts Electric Heat: add 2
additional wires, 24 volts.
— 5 wires, 24 volts to outdoor
section ‘’A’’ 2 wires, 24 volts to
outdoor section ‘’B’’ 2 wires, 24
volts between outdoor sections
‘’A’’ ‘’B’’
— Electric heat: add 1 additional
wire, 24 volts.
— Outdoor thermostat: add 1
additional wire, 24 volt.
TWA075A/TWE075A;
TWA100A/TWE100A
FieldWiring:
D
— 9 wires, 24 volts.
— Electric heat: add 4 additional
wires, 24 volts.
— Outdoor thermostat: add 3
additional wires, 24 volts.
A
B
C
— 3 power wires, line voltage.
— 3 power wires, line voltage.
— Heat pump thermostat: 6 wires,
24 volts.
D
TWA155B/TWE155B;
TWA200B/TWE200B
FieldWiring:
A
B
C
— Electric heat: add 2 additional
wires, 24 volts.
— 6 wires, 24 volts.
— 3 power wires, line voltage.
— 3 power wires, line voltage.
— Heat pump thermostat: 7 wires,
24 volts.
— Electric heat: add 2 additional
wires, 24 volts.
— 7 wires, 24 volts.
D
— Outdoor thermostat: add 1
additional wire, 24 volts.
— Electric heat: add 1 additional
wire, 24 volts.
(2)TWA075A/TWE155B;
(2)TWA100A/TWE200B
FieldWiring:
D
— Electric heat: add 4 additional
wires, 24 volts.
A
B
C
— 3 power wires, line voltage.
— 3 power wires, line voltage.
— Heat pump thermostat: 7 wires,
24 volts.
— Outdoor thermostat: add 1
additional wire, 24 volts.
— Electric heat: add 2 additional
wires, 24 volts.
TWA-PRC001-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(Heat Pump)
Heat Pump — Single Compressor
Typical unit wiring diagram. For specific
wiring, see individual Service Facts.
34
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(Heat Pump)
TWA-PRC001-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(Heat Pump)
Heat Pump — Dual Compressors
Typical unit wiring diagram. For specific
wiring, see individual Service Facts.
36
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(Heat Pump)
TWA-PRC001-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical
Wiring
(Air Handler)
Air Handler
Typical unit wiring diagram. For specific
wiring, see individual Service Facts.
38
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Heat Pump)
Figure DD-1 — TWA075 Heat Pump
All dimensions are in inches and millimeters.
Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)
TWA-PRC001-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Heat Pump)
Figure DD-2 — 10TonTWA100A Heat Pump
All dimensions are in inches and millimeters.
Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)
40
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Heat Pump)
Figure DD-3 — TWA155B Heat Pump
All dimensions are in inches and millimeters.
Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)
TWA-PRC001-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Heat Pump)
Figure DD-4 — TWA200B Heat Pump
All dimensions are in inches and millimeters.
Note 1
MINIMUM CLEARANCE FOR PROPER
OPERATION IS 36 INCHES (914 MM)
FROM WALLS, SHRUBBERY, PRIVACY
FENCES, ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72
INCHES (1828 MM)
42
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handler)
Figure DD-5 — TWE050AAir Handlers
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
TWA-PRC001-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handler)
Figure DD-6 —TWE075A Air Handler
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
44
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handler)
Figure DD-7—TWE100AAir Handler
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
TWA-PRC001-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handler)
Figure DD-8—TWE100BAir Handler
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
46
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handlers)
Figure DD-9—TWE050A, 075A, 100A andTWE100BAir Handler
All dimensions are in inches and millimeters.
Table DD-1 —Air Handler Dimensions — in. (mm)
Model No.
TWE050A
AA
AB
AC
AD
AE
AF
AJ
AK
AL
35 5/8
(905)
12 1/16
1 5/8
32 1/4
2 15/16
(74.6)
32 1/4
7 13/16
12 3/8
34 9/16
(878)
(306.4)
(41.3)
(819.2)
(819.2)
(198.4)
(314.3)
16
(406.4)
16
(406.4)
16
(406.4)
TWE075A
TWE100A
TWE100B
45 1/8
16
(406.4)
16
(406.4)
16
(406.4)
1 11/16
41 15/16
6 5/8
41 3/4
7
36 7/8
(1146.2)
(42.9)
(1065.2)
(168.3)
(1060.5)
(177.8)
(936.6)
61 1/8
1 11/16
57 15/16
6 5/8
57 13/16
7
36 7/8
(1552.6)
(42.9)
(1471.6)
(168.3)
(1468.4)
(177.8)
(936.6)
61 1/8
1 11/16
57 15/16
6 5/8
57 13/16
7
36 7/8
(1552.6)
(42.9)
(1471.6)
(168.3)
(1468.4)
(177.8)
(936.6)
TWA-PRC001-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handler)
Figure DD-10— TWE155B Air Handler
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
48
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handlers)
Figure DD-11 —TWE200BAir Handler
All dimensions are in inches and millimeters.
Notes:
1. Length, Width, and Height Dimensions do not include 1/2”
(12.7mm) access panel depth.
2. Removable drain pan and attached drain connection may be
installed on either end of unit in either the vertical or horizontal
configuration. Plastic drain pan access plate on the end of unit
opposite drain connection must be removed to slide drain pan out
for cleaning. Access plate must be reinstalled after sliding drain
pan back into unit.
3. If periodic drain pan cleaning is required, allow room for partial
removal of pan on drain connection end of unit.
TWA-PRC001-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Air Handlers)
Figure DD-12—TWE155B and 200BAir Handlers
All dimensions are in inches and millimeters.
Table DD-2 —Air Handler Dimensions — in. (mm)
Model No.
TWE155B
TWE200B
A
B
C
D
E
F
G
H
J
77 1/4 (1962.2)
89 1/4 (2267)
1 3/16 (30.2)
1 11/16 (42.9)
48 (1219.2)
50 13/16 (1290.6) 11 1/2 (292.1)
11 7/16 (290.5)
18 (457.2)
20 1/8 (511.2)
3 3/8 (85.7)
3 1/16 (77.8)
35 1/16 (890.6)
39 1/8 (993.8)
73 7/8 (1876.4)
82 7/8 (2105)
3 3/4 (95.3)
4 9/16 (115.9)
Table DD-2—Air Handler Dimensions — in. (mm) (Continued)
Model No.
TWE155B
TWE200B
K
L
M
N
P
Q
R
S
T
35 1/16 (890.6)
39 1/8 (993.8)
2 13/16 (71.4)
4 7/8 (123.8)
18 (457.2)
20 (508)
3 9/16 (90.5)
3 (76.2)
2 7/8 (73)
35 1/16 (890.6)
39 1/8 (993.8)
3 3/4 (95.3)
4 9/16 (115.9)
35 1/16 (890.6)
39 1/8 (993.8)
73 3/8 (1863.7)
82 7/8 (2105)
4 13/16 (122.2)
50
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Accessories)
Figure DD-13— Electric Heater forTWE050, 075, 100Air Handlers
All dimensions are in inches and millimeters.
Figure DD-14 — Electric Heater forTWE155 and 200Air Handlers
TWA-PRC001-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(Accessories)
Table DD-3 — Discharge Plenum And Grille
Dimensions — in. (mm)
Figure DD-15 — Discharge Plenum and Grille
All dimensions are in inches and millimeters.
Model
Model No.
A
B
C
TWE050 BAYPLNM015
TWE075 BAYPLNM016
TWE100 BAYPLNM017
3715/16 2115/16
28
(963.6) (557.2) (711.2)
471/2
(1206.5) (635) (711.2)
631/2
25 28
(1612.9) (635) (711.2)
25
28
Table DD-4 — Discharge Plenum And Grille
Dimensions — in. (mm)
For Use with Electric Heat
Model
Model No.
A
B
C
29
TWE050 BAYPLNM025
TWE075 BAYPLNM026
TWE100 BAYPLNM027
TWE155 BAYPLNM028
TWE200 BAYPLNM029
3715/16 2115/16
(963.6) (557.2) (736.6)
471/2
(1206.5) (635) (736.6)
631/2
25 29
(1612.9) (635) (736.6)
791/2 2711/16
35
(2019.3) (703.3) (889)
921/2
35
(2349.5) (773.1) (889)
25
29
307/16
Table DD-5 — Subbase Dimensions — in.
(mm)
Figure DD-16 — Subbase
Model
Model No.
A
B
TWE050 BAYBASE001
TWE075 BAYBASE002
TWE100 BAYBASE003
TWE155 BAYBASE004
TWE200 BAYBASE005
38
22
(965.2)
(558.8)
471/2
25
(635)
(1206.5)
631/2
25
(1612.9)
(635)
791/2
275/8
(2019.3)
(701.7)
921/2
307/16
(2349.5)
(773.1)
52
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
(Heat Pumps)
TableW-1 — Unit and CornerWeights — Lbs (Kg)
Unit
Shipping
Net
CornerWeights
Model No.
TWA075A
Maximum — lbs (Kg) Maximum — lbs (Kg)
1
2
3
4
390
343
(155.6)
112
(50.8)
89
(40.4)
63
(28.6)
79
(35.8)
(176.9)
TWA100A
TWA155B
TWA200B
468
414
146
106
68
94
(212.3)
(187.8)
(66.2)
(48.1)
(30.1)
(42.6)
816
(370.1)
970
(440.0)
740
(335.7)
885
(401.4)
195
(88.5)
253
(114.8)
186
(84.4)
250
(113.4)
175
(79.4)
190
(86.2)
184
(83.5)
192
(87.1)
TableW-2 —AccessoryWeights — Net Lbs (Kg)
Unit
RIS
Steel Spring
Isolators
Anti Short
Coil
Guard
Low
Ambient
Model No.
Isolators
CycleTimer
Thermostats
TWA075A
2
(.9)
12
(5.4)
1
(.5)
8
(3.6)
1
(.5)
23
(10.4)
TWA100A
TWA155B
TWA200B
2
12
1
11
1
23
(.9)
(5.4)
(.5)
(5)
(.5)
(10.4)
2
(.9)
2
(.9)
12
(5.4)
12
(5.4)
1
(.5)
1
(.5)
22
(10)
34
(15.4)
1
(.5)
1
(.5)
23
(10.4)
23
(10.4)
TWA155B, 200B
TWA075A, 100A
TWA-PRC001-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
(Air Handlers)
TableW-3 —Air Handlers, Coils,And CornerWeights — Lbs (Kg)1
Unit
Shipping
Net
CornerWeights —Vertical
CornerWeights — Horizontal
Model No.
TWE050
Maximum (lbs)
Maximum (lbs)
#1
59
(26.8)
#2
59
(26.8)
#3
59
(26.8)
#4
59
(26.8)
A
54
(24.5)
B
64
(29)
C
D
54
(24.5)
298
(135)
262
(118.9)
64
(29.03)
TWE075
TWE100
TWE125
TWE200
388
346
79
79
79
79
77
84
81
73
(176)
(157)
(35.9)
(35.9)
(35.9)
(35.9)
(35)
(38.1)
(36.7)
(33.1)
473
(214.6)
754
(342)
886
(401.9)
419
(190.1)
690
(313)
820
(372)
107
(48.5)
173
(78.5)
204
(92.5)
107
(48.5)
173
(78.5)
204
(92.5)
107
(48.5)
173
(78.5)
204
(92.5)
107
(48.5)
173
(78.5)
204
(92.5)
102
(46.3)
174
(79)
185
(84)
113
(51.3)
156
(70.8)
228
(103.4)
113
(51.3)
190
(86.2)
221
(100.3)
102
(46.3)
170
(77.1)
179
(81.2)
Note:
1.
If application requires steam or hot water heating coils, field supplied isolators must be utilized.
Vertical
TWE050, 075, 100
Vertical
TWE155, 200
Horizontal
TWE050, 075, 100
Horizontal
TWE155, 200
TableW-4—AccessoryWeights — Lbs (Kg)
RIS
RIS
Steel Spring Steel Spring
Discharge
Plenum
Discharge
Plenum
Electric
Heat
Min. Max.
Isolator
Floor
Isolator
Suspended
Mount
Isolator
Floor
Isolator
Suspended
Mount
Unit
Model No.
Return
Air Grille
Oversized
Motor
And Grille1
And Grill2
Subbase
Mount
Mount
TWE050
58
(26.3)
93
(42.2)
3
(1.4)
32/43
(14.5/19.5)
14
(6.4)
31
(14.1)
2
(.9)
9
(4)
12
(5.4)
6
(2.7)
TWE075
TWE100
TWE155
TWE200
73
123
5
27/45
19
48
2
6
12
6
(33.1)
(55.8)
(2.3)
(12.3/20.4)
(8.6)
(21.8)
(.9)
(2.7)
(5.4)
(2.7)
92
(41.7)
124
(56.3)
145
(65.8)
156
(70.8)
230
(104.3)
264
(119.8)
7
(3.2)
10
(4.5)
12
(5.4)
27/45
(12.3/20.4)
79/100
(35.8/45.4)
79/100
(35.8/45.4)
23
(10.4)
27
(12.3)
31
(14.06)
50
(22.7)
80
(36.3)
88
(40)
2
(.9)
2
(.9)
2
(.9)
7
(3.2)
7
(3.2)
9
(4)
12
(5.4)
12
(5.4)
12
(5.4)
6
(2.7)
6
(2.7)
6
(2.7)
Note:
1.
2.
For use when no heat is supplied.
For use with electric heat.
54
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
low evaporator coil temperatures are
encountered.
Controls
Heat Pumps
Heat pump units shall be completely
factory wired with necessary controls
and contactor pressure lugs or terminal
block for power wiring. Control wiring
shall be 24-volt control circuit which
includes fusing and control transformer.
Units shall provide external location for
mounting a fused disconnect device.
Time delay timers to prevent
General
Refrigeration System — Dual
Compressor
Unit shall be assembled on heavy gauge
steel mounting/lifting rails and shall be
weather proofed. Unit shall include a
hermetic scroll or reciprocating
compressor(s), plate fin condenser coil,
fans and motors, controls, and holding
charge of nitrogen. Operating Range
shall be between 115° F and 35° F in
cooling as standard from factory. Unit
shall be UL 1995 listed and rated in
accordance with ARI Standard 210/240 or
340/360.
TWA155B,TWA200B units shall have
two separate and independent
refrigeration circuits. Each refrigeration
circuit shall have an integral subcooling
circuit. A refrigeration filter drier shall be
provided as standard. Unit shall have
both a liquid line and suction gas line
service valve with gauge ports.
compressors in dual compressor units
from simultaneous start-up and anti-
recycle timers are available as optional
accessories.
Unit shall have twoTrane direct drive,
hermetic scroll compressors with
centrifugal oil pump and provide positive
lubrication to all moving parts. Motor
shall be suction gas-cooled and shall
have a voltage utilization range of plus or
minus 10 percent of nameplate voltage.
Crankcase heater, discharge line
thermostat, internal temperature, and
current-sensitive motor overloads shall
be included for maximum protection.
Scroll type compressor shall provide
inherently low vibration and noise by
having no suction and discharge valves.
External high and low pressure cutout
devices shall be provided. Evaporator
defrost control provided in indoor
blower coil shall prevent compressor
slugging by temporarily interrupting
compressor operation when low
evaporator coil temperatures are
encountered.
Defrost Controls
Casing
Electronic timed initiated, temperature
terminated defrost system with choice
of 50, 70, or 90 minute cycle shall be
included.Timed override limits defrost
cycle to 10 minutes.
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 500 hours
in salt spray test. Unit shall have
removable end panels which allow
access to all major components and
controls.
LowAmbient Operation
Standard units shall start and operate to
approximately 35° F (1.7° C) when
matched withTrane air handlers and
coils. Optional head pressure control
accessory permits operation to 0° F
(-17.8° C).
Refrigeration System — Single
Compressor
ACCESSORIES
TWA075A,TWA100A units shall have a
single refrigeration circuit. Each
LowAmbient Head Pressure Control —
This accessory shall modulate the RPM
of unit outdoor fan motor in response
to outdoor ambient temperatures and
liquid line temperature. Accessory
provides unit cooling operation to
outdoor temperatures of 0° F (-17.8° C).
refrigeration circuit has an integral
subcooling circuit. A refrigeration filter
drier, expansion valve, and check valves
shall be provided as standard.The unit
shall have both a liquid line and suction
gas line service valve with gauge port.
Condenser Coil
Coils shall be internally finned or smooth
bore, 3/8" (10mm) copper tubes
mechanically bonded to a configured
aluminum plate fin as standard. Coil
shall be factory pressure and leak tested
to 420 psig (2,930 kPa) air pressure.
Metal grilles with PVC coating for coil
protection is optional.
Vibration Isolation Packages — This
accessory shall reduce transmission of
noise and vibration to building
structures, equipment, and adjacent
spaces. Packages shall be available in
either neoprene-in-shear or spring-flex
types.
Unit shall have one direct drive,Trane
hermetic scroll compressor with
centrifugal oil pump providing positive
lubrication to moving parts. Motor shall
be suction gas-cooled and shall have a
voltage utilization range of plus or minus
10 percent of nameplate voltage.
Time Delay Relay —This accessory
shall prevent compressors in dual
compressor unit from coming on line
simultaneously.Timer shall be 24-volt,
60 cycle, with four minute timing
period.
Crankcase heater, discharge line
Condenser Fan And Motor(s)
thermostat, internal temperature, and
current-sensitive motor overloads shall
be included for maximum protection.
Scroll type compressor shall provide
inherently low vibration and noise by
having no suction and discharge valves.
External high and low pressure cutout
devices shall be provided. Evaporator
defrost control provided in indoor
blower coil unit shall prevent
Direct-drive, statically and dynamically
balanced, 26 or 28 inch (660 or 711 mm)
propeller fan(s) with aluminum blades
and electro-coated steel hubs shall be
used in draw-through vertical discharge
position. Either permanently lubricated
totally enclosed or open construction
type motors shall be provided and shall
have built-in current and thermal
Anti-Short-CycleTimer —This
accessory shall prevent rapid on-off
compressor cycling in light load
conditions by not allowing compressor
to operate for 5-7 minutes upon
shutdown.This accessory shall consist
of a 24-volt, 60 cycle, solid state timing
device with either 5 or 7 minute fixed-
off timing period.
overload protection. Motor(s) shall have
either ball or sleeve bearing type.
compressor slugging by temporarily
interrupting compressor operation when
TWA-PRC001-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Condenser Coil Guard — Metal grille
with PVC coating shall be provided to
alleviate coil damage.
internally wye connected on 400 volt,
three phase. Each 400 volt heater shall
have automatic line break high limit
controls.
internally enhanced copper tubing and
shall be factory pressure and leak tested
at 375 psig (2586 kPa). Coil is arranged
for draw-through airflow and shall
provide a double sloped condensate
drain pan constructed of PVC plastic.The
drain pan shall be removable for
cleaning.The condensate drain pan can
be installed in any of four positions
allowing for vertical or horizontal
Black Epoxy Coated Condenser Coil —
This factory installed option is designed
to provide corrosion protection of air
cooled condenser coils for seacoast
application. The black epoxy coil
protection is a factory applied thermoset
vinyl coating, bonded to normal
aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B177.
Discharge Plenums and Grilles —
Accessory discharge plenums shall be
available for vertical, free discharge
applications. Plenums shall be
constructed of heavy-gauge, zinc coated,
galvanized steel finished with baked
enamel to match the air handler unit.
Grilles shall be satin finished aluminum
and have four-way adjustable louvers.
application and providing external
connections on either side of the unit.
Evaporator Fan
Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be standard.
Thermal overload protection shall be
standard on motor. Fan and motor
bearings shall be permanently
lubricated. Oversized motors shall be
available as an option for high static
application. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT)
ReturnAir Grilles —Accessory return air
grille shall be provided for vertical front,
free return applications. Grilles shall be
installed in place of the front lower side
panel. Grille shall be satin finished
Air Handlers
General
aluminum with non-adjustable louvers.
Air handler units shall be completely
factory assembled including coil,
condensate drain pan, fan motor(s),
filters, and controls in an insulated
casing that can be applied in either
vertical or horizontal configuration. Unit
shall be rated and tested in accordance
with ARI standard 210/240 or 340/360.
Unit shall be UL listed and labeled in
accordance with UL 1995 for indoor
blower coil units.
Mounting Subbase —The accessory
shall be available for vertical floor mount
configurations. Subbase shall be
constructed of heavy gauge, zinc coated,
galvanized steel with baked enamel
finish to match air handler unit. Subbase
is required in the vertical air flow
application for condensate drain
trapping and when isolators are
required.
Controls
Magnetic evaporator fan contactor, low
voltage terminal strip, check valve(s), and
single point power entry shall be
included. All necessary controls shall be
factory-installed and wired. Evaporator
defrost control shall be included to
prevent compressor slugging by
temporarily interrupting compressor
operation when low evaporator coil
temperatures are encountered.
Casing
Vibration Isolators —This accessory
shall reduce transmission of noise and
vibration to building structures,
equipment, and adjacent spaces.
Packages shall be available in either
neoprene-in shear or spring-flex types in
floor or suspended mountings.
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Casing shall be completely insulated
with cleanable, foil faced, fire-retardant,
permanent, odorless, glass fiber
material. All insulation edges shall be
either captured or sealed. Knockouts
shall be provided for unit electrical
power and refrigerant piping
Filters
One inch, throw-away filters shall be
standard onTWE050A,TWE075A,
TWE100A andTWE120B model air
handlers. Filters shall be accessible from
the side coil access panel. Filter rack can
be field converted to two inch capability.
Two inch, throw-away filters shall be
standard onTWE155B andTWE200B
models.
Oversized Motors — Field installed
oversized motors shall be available for
high static pressure applications.
CONTROL OPTIONS
Standard IndoorThermostats —Two
stage heating and cooling operation or
one stage heating and cooling
thermostats shall be available in either
manual or automatic changeover.
connections. Captive screws shall be
standard on all access panels.
Refrigeration System
ACCESSORIES
TheTWE050A,TWE075A,TWE100A units
shall have a single refrigeration circuit
and theTWE100B,TWE155B,TWE200B
units shall have dual refrigeration
circuits. Each refrigeration circuit is
controlled by a factory installed thermal
expansion valve.
Electric Heaters — UL and CSA
Programmable Electronic Night Setback
Thermostat —The option shall provide
heating setback and cooling setup with 7-
day programming capability.
approved electric heat modules shall be
available for installation directly on fan
discharge. Electric heaters shall be
available in a wide range of capacities
with one or two stage control, single-
point electric power connection, and
terminal strip connections. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
OutdoorThermostat —This option shall
provide staging control of electric
heaters based on a set outdoor
temperature.
Evaporator Coil
Configured aluminum fin surface shall
be mechanically bonded to 3/8" (10 mm)
56
TWA-PRC001-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
TWA-PRC001-EN
PL-UN-TWA-PRC001-EN-07-00
TWA-PRC001-EN-05/98
TheTrane Company
Supersedes
An American Standard Company
Stocking Location
Inland - LaCrosse
For more information contact your
local distributor (dealer), local district
office, or e-mail us at
SinceTheTrane Company has a policy of continuous product and product data improvement, it reserves the
right to change design and specifications without notice.