Trane Furnace DD1B060A9H31B User Manual

1 8 - CD2 1 D1 - 5  
Installer’s Guide  
High Efficiency Single Stage Upflow/ Horizontal  
and Downflow/ Horizontal Gas-Fired Furnaces,  
“Fan Assisted Combustion System”  
*UD1A040A9H21B  
*UD1B060A9H31B  
*UD1B080A9H31B  
*UD1C080A9H41B  
*__First letter may be “A” or “T”  
*UD1B100A9H31B  
*UD1C100A9H51B  
*UD1D120A9H51B  
*UD1D140A9H51B  
*DD1B060A9H31B  
*DD1B080A9H31B  
*DD1C100A9H51B  
*DD1D120A9H51B  
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES  
IMPORTANT — This Document is customer property and is to remain with this unit.  
Please return to service information pack upon completion of work.  
For VENT SIZING INFORMATION see:  
USA —  
National Fuel Gas Code ............. ANSI Z223.1/NFPA 54 (latest version)  
CANADA —  
Natural Gas Installation Code ...........CAN/CGA-B149.1 (latest version)  
Propane Installation Code .................CAN/CGA-B149.2 (latest version)  
USA/CANADA ALTERNATE —  
Category I Venting Guide .................................. Pub. No. 18-CH23D1-2  
*UD1-H  
*DD1-H  
Upflow/ Horizontal*  
Downflow/ Horizontal*  
*Horizontal Conversion for these furnaces may be left or right side rotation.  
A341789P07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
Contents  
Safety signal words are used to designate a degree or  
level of seriousness associated with a particular hazard.  
The signal words for safety markings are WARNING,  
and CAUTION.  
a. WARNING indicates a potentially hazardous situa-  
tion which, if not avoided, could result in death or  
serious injury.  
b. CAUTION indicates a potentially hazardous situation  
which, if not avoided, may result in minor or mod-  
erate injury. It is also used to alert against unsafe  
practices and hazards involving only property dam-  
age.  
Installation Instructions  
3
4
4
5
7
General Installation Instructions  
Location and Clearances  
Outline Drawing  
Upflow Installation  
Downflow Installation  
7
Air For Combustion and Ventilation  
Duct Connections  
8
10  
11  
11  
13  
13  
14  
15  
16  
17  
19  
19  
Return Air Filters  
Typical Upflow Return Air Filter Installations  
Alternate Upflow Filter Clip / Bracket Installation  
Typical Downflow Furnace Return Air Filter Installations  
General Venting Instructions  
Venting Into a Masonry Chimney  
Electrical Connections  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could re-  
sult in serious injury, death or property damage.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death, or property damage.  
Field Wiring Diagrams  
Gas Piping  
Sequence of Operation  
Start Up and Adjustment  
20  
Preliminary Inspections  
20  
20  
21  
22  
23  
Combustion and Input Check  
High Altitude Derate  
Lighting Instructions  
Control and Safety Switch Adjustment  
IFC Error Flash Codes  
Abnormal Conditions  
24  
24  
!
CAUTION  
To prevent shortening its service life, the furnace  
should not be used as a “Construction Heater” during  
the finishing phases of construction until the require-  
ments listed in item 9, a-g of the safety section of this  
publication have been met. Condensate in the pres-  
ence of chlorides and fluorides from paint, varnish,  
stains, adhesives, cleaning compounds, and cement  
create a corrosive condition which may cause rapid de-  
terioration of the heat exchanger.  
!
WARNING  
These furnaces are not approved or intended for instal-  
lation in manufactured (mobile) housing, trailers, or  
recreational vehicles.  
Failure to follow this warning could result in property  
damage, personal injury, or death.  
!
CAUTION  
Do NOT install the furnace in a corrosive or contami-  
nated atmosphere.  
18-CD21D1-5  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
LOCATION AND CLEARANCES  
GENERAL INSTALLATION INSTRUCTIONS  
The manufacturer assumes no responsibility for equip-  
ment installed in violation of any code or regulation.  
It is recommended that Manual J of the Air Condition-  
ing Contractors Association (ACCA) or A.R.I. 230 be fol-  
lowed in estimating heating requirements. When esti-  
mating heating requirements for installation at Alti-  
tudes above 2000 ft., remember the gas input must be  
reduced (See GAS INPUT ADJUSTMENT).  
The location of the furnace is normally selected by the  
architect, the builder, or the installer. However, before  
the furnace is moved into place, be sure to consider the  
following requirements:  
1. Is the location selected as near the chimney or vent  
and as centralized for heat distribution as practical?  
2. Do all clearances between the furnace and enclo-  
sure equal or exceed the minimums stated in Clear-  
ance Table on the Outline Drawings.  
3. Is there sufficient space for servicing the furnace  
and other equipment? A minimum of 24 inches  
front accessibility to the furnace must be provided.  
Any access door or panel must permit removal of  
the largest component.  
4. Are there at least 3 inches of clearance between the  
furnace combustion air openings in the front panel  
and any closed panel or door provided?  
5. Are the ventilation and combustion air openings  
large enough and will they remain unobstructed? If  
outside air is used, are the openings set above the  
highest snow accumulation level? (See the Air for  
Combustion and Ventilation section.)  
6. Allow sufficient height in supply plenum above the  
furnace to provide for cooling coil installation, if the  
cooling coil is not installed at the time of this furnace  
installation.  
Material in this shipment has been inspected at  
the factory and released to the transportation  
agency without known damage. Inspect exterior  
of carton for evidence of rough handling in ship-  
ment. Unpack carefully after moving equipment  
to approximate location. If damage to contents is  
found, report the damage immediately to the de-  
livering agency.  
Codes and local utility requirements governing the  
installation of gas fired equipment, wiring, plumbing,  
and flue connections must be adhered to. In the ab-  
sence of local codes, the installation must conform with  
latest edition of the National Fuel Gas Code ANSI  
Z223.1 • National Installation Code, CAN/CGA B149.1.  
The latest code may be obtained from the American Gas  
Association Laboratories, 400 N. Capitol St. NW,  
Washington D.C. 20001.  
7. A furnace shall be installed so electrical components  
are protected from water.  
These furnaces have been classified as Fan Assisted  
Combustion system CATEGORY I furnaces as required  
by ANSI Z21.47 “latest edition” and CAN/CGA 2.3.  
Therefore they do not require any special provisions for  
venting other than what is indicated in these instruc-  
tions. (Category I defined on page 14).  
These furnaces may be twinned. They shall have  
common returns with equal pressure drops or  
ducts with equivalent lengths and sizes. See Field  
Wiring Diagrams for Twinning on page 17 for  
proper hookup.  
8. If the furnace is installed in a residential garage,  
it must be installed so that the burners, and the ig-  
nition source are located not less than 18 inches  
above the floor and the furnace must be located or  
protected to avoid physical damage from vehicles.  
4
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
18-CD21D1-5  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
6
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
required.  
UPFLOW INSTALLATION  
Standoffs and screws (See Figure 1 on page 6) are in-  
cluded with the cased coils for attachment to the fur-  
nace. There are clearance alignment holes near the bot-  
tom of the coil wrapper and drill screws are used to en-  
gage the furnace top flange. The standoff is inserted  
into the cabinet alignment hole. The drill screws are in-  
serted through the standoffs then screwed into the fur-  
nace flange. The coil is always placed downstream of  
the furnace airflow. These instructions apply only if the  
coil is on top of an upflow furnace.  
REQUIRED FLOOR OPENING: (DOWNFLOW)  
3
A (width)  
B (depth)  
FURNACE  
FRONT  
D
C
SEE FIGURE 3 AND TABLE 1  
DRILL SCREWS (4)  
STANDOFFS (4)  
1
TABLE 1  
FLOOR OPENING PLENUM OPENING  
CABINET  
W IDTH  
RETURN  
DUCT W IDTH  
"A"  
"B"  
"C"  
"D"  
14-1/2"  
17-1/2"  
21"  
13-1/4"  
16-1/4"  
19-3/4"  
23-1/4"  
13-5/8"  
16-5/8"  
20-1/8"  
23-5/8"  
20-1/8"  
20-1/8"  
20-1/8"  
20-1/8"  
12-5/8"  
15-5/8"  
19-1/8"  
22-5/8"  
19-3/8"  
19-3/8"  
19-3/8"  
19-3/8"  
24-1/2"  
CASED  
COIL  
FOR VERTICAL  
INSTALLATIONS:  
HORIZONTAL INSTALLATION  
The coil and furnace must be fully supported when used  
in the horizontal position.  
Three brackets (with screws) are included with downflow  
furnaces for installation to stabilize and secure the fur-  
nace and TXC cased coil in the horizontal position.  
See Figure 4.  
SCREWS  
(BOTH SIDES)  
UPFLO  
FURNA  
IMPORTANT:  
W
The 2/4TXC cased coil must be placed downstream of the  
furnace. In horizontal installations, the apex of the coil  
may point either toward or away from the furnace. See  
CE  
STANDOFFS  
(BOTH SIDES)  
the 2/4TXC coil Installer's Guide for more details.  
DOWNFLOW INSTALLATION  
!
4CASED COIL CONNECTION  
WARNING  
Do NOT install the furnace directly on carpeting, tile or  
other combustible material other than wood flooring.  
BRACKET FOR DOWNFLOW  
FURNACE IN HORIZONTAL  
For  
vertical  
downflow  
application,  
subbase  
(BAYBASE205) must be used between the furnace and  
combustible flooring. When the downflow furnace is  
installed vertically with a cased coil, a subbase is not  
The cased coil is secured to the furnace and both the fur-  
nace and the cased coil must be properly supported. The  
brackets mount using the rear screws on the coil case  
and use the screws provided to secure the bracket to the  
furnace. The remaining bracket is placed as close to cen-  
ter as possible (horizontally) between the coil case front  
and the furnace bottom channel (for downflow/ horizontal  
furnace). Use four of the screws provided to secure the  
bracket.  
2
This furnace may be installed in an attic or crawl space  
in the horizontal position by placing the furnace on the  
left or right side (as viewed from the front in the up-  
right position). The horizontal furnace installation in an  
attic should be on a service platform large enough to al-  
low for proper clearances on all sides and service access  
to the front of the furnace (See Clearance Table on Out-  
line Drawings and Figure 5).  
18-CD21D1-5  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
If the furnace is suspended using perforated steel strap  
(plumber’s strap), it must be supported at all four cor-  
ners and in the middle at the front of the furnace.  
The forward most screw on the side of the furnace  
may be used to connect the strapping (See Figure 6).  
Line contact is only permissible between lines formed  
by the intersection of the top and two sides of the fur-  
nace casing and the building joists, studs, or framing.  
7
UNCONFINED  
50 CU. FT. OR MORE  
PER 1000 BTU/ HR.  
INPUT ALL EQUIP-  
MENT INSTALLED  
AIR FOR COMBUSTION AND VENTILATION  
Adequate flow of combustion and ventilating air must  
not be obstructed from reaching the furnace. Air open-  
ings provided in the furnace casing must be kept free of  
obstructions which restrict the flow of air. Airflow re-  
strictions affect the efficiency and safe operation of the  
furnace. Keep this in mind should you choose to re-  
model or change the area which contains your furnace.  
Furnaces must have a free flow of air for proper perfor-  
mance.  
Provisions for combustion and ventilation air shall be  
made in accordance with “latest edition” of Section 5.3,  
Air for Combustion and Ventilation, of the National  
Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4  
of CAN/ CGA B149 Installation Codes, and applicable  
provisions of the local building codes. Special conditions  
created by mechanical exhausting of air and fireplaces  
must be considered to avoid unsatisfactory furnace op-  
eration.  
Furnace locations may be in “confined space” or “uncon-  
fined space”. Unconfined space is defined in Table 2 and  
Figure 7. These spaces may have adequate air by infiltra-  
tion to provide air for combustion, ventilation, and dilu-  
tion of flue gases. Buildings with tight construction (for  
example, weather stripping, heavily insulated, caulked,  
vapor barrier, etc.), may need additional air provided as  
described for confined space.  
TYPICAL ATTIC PLATFORM INSTALLATION  
(UPFLOW/HORIZONTAL FURNACE SHOWN)  
A cutout is provided on both sides of the downflow fur-  
nace cabinet to allow a 90° elbow to be attached inside  
the cabinet and the vent piping to connect there. In  
horizontal, the downflow furnace may be vented  
through the top of the cabinet if needed. In vertical con-  
figuration, the downflow furnace may be vented using  
the side cabinet cutouts. This venting configuration  
could be used if an electronic air cleaner is installed.  
When the downflow furnace is vented through  
the left side of the furnace cabinet in horizontal  
or vertical configuration, Type B vent pipe must  
be used within the cabinet.  
CONFINED  
8
LESS THAN 50 CU. FT.  
PER 1000 BTU/ HR.  
INPUT ALL EQUIP-  
MENT INSTALLED  
Confined spaces are installations with less than 50 cu.  
ft. of space per 1000 BTU/ hr input from all equipment  
installed. Air for combustion and ventilation require-  
ments can be supplied from inside the building as in  
Figure 9 or from the outdoors, as in Figure 10.  
Typical Suspended Installation  
(Upflow/Horizontal Furnace Shown)  
8
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TABLE 3  
1. All air from inside the building as in Figure 9: The  
confined space shall be provided with two perma-  
nent openings communicating directly with an addi-  
tional room(s) of sufficient volume so that the com-  
bined volume of all spaces meets the criteria for an  
unconfined space. The total input of all gas utiliza-  
tion equipment installed in the combined space  
shall be considered in making this determination.  
Refer to Table 3, for minimum open areas required.  
2. All air from outdoors as in Figure 10: The confined  
space shall be provided with two permanent open-  
ings, one commencing within 12 inches of the top  
and one commencing within 12 inches of the bot-  
tom of the enclosure. The openings shall communi-  
cate directly, or by ducts, with the outdoors or  
spaces (crawl or attic) that freely communicate with  
the outdoors. Refer to Table 3, for minimum open  
areas required.  
MINIMUM FREE AREA IN SQUARE INCHES  
EACH OPENING (FURNACE ONLY)  
Furnace  
Air From Outside  
Maximum  
BTUH/INPUT  
Rating  
Air From  
Inside  
Vertical  
Horizontal  
Duct  
Duct  
40,000  
60,000  
80,000  
100,000  
120,000  
140,000  
100  
100  
100  
100  
120  
140  
10  
15  
20  
25  
30  
35  
20  
30  
40  
50  
60  
70  
9
3. The following types of installations will require use of  
OUTDOOR AIR for combustion, due to chemical expo-  
sures:  
* Commercial buildings  
* Buildings with indoor pools  
* Furnaces installed in commercial laundry rooms  
* Furnaces installed in hobby or craft rooms  
* Furnaces installed near chemical storage areas.  
Exposure to the following substances in the combus-  
tion air supply will also require OUTDOOR AIR for  
combustion:  
0
* Permanent wave solutions  
* Chlorinated waxes and cleaners  
* Chlorine based swimming pool chemicals  
* Water softening chemicals  
* Deicing salts or chemicals  
* Carbon Tetrachloride  
* Halogen type refrigerants  
* Cleaning solvents (such as perchloroethylene)  
* Printing inks, paint removers, varnish, etc.  
* Hydrochloric acid  
* Cements and glues  
* Antistatic fabric softeners for clothes dryers  
* Masonry acid washing materials  
TABLE 2  
MINIMUM AREA IN SQUARE FEET FOR  
UNCONFINED SPACE INSTALLATIONS  
WITH 8 FOOT CEILING  
FURNACE MAXIMUM  
MINIMUM AREA IN SQUARE FEET  
BTUH / INPUT RATING  
OF UNCONFINED SPACE  
40,000  
60,000  
80,000  
100,000  
120,000  
140,000  
250  
375  
500  
625  
750  
875  
18-CD21D1-5  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
DUCT CONNECTIONS  
All return air duct systems should provide for installa-  
tion of return air filters.  
Air duct systems should be installed in accordance with  
standards for air conditioning systems, National Fire  
Protection Association Pamphlet No. 90. They should  
be sized in accordance with ACCA Manual D or which-  
ever is applicable. Check on controls to make certain  
they are correct for the electrical supply.  
PREPARATION FOR UPFLOW BOTTOM AND SIDE  
RETURN AIR FILTER INSTALLATION  
All return air duct systems should provide for installa-  
tion of return air filters.  
Central furnaces, when used in connection with cooling  
units, shall be installed in parallel or on the upstream  
side of the cooling units to avoid condensation in the  
heating element, unless the furnace has been specifi-  
cally approved for downstream installation. With a par-  
allel flow arrangement, the dampers or other means  
used to control flow of air shall be adequate to prevent  
chilled air from entering the furnace, and if manually  
operated, must be equipped with means to prevent op-  
eration of either unit unless the damper is in full heat  
or cool position.  
1. Determine the appropriate postion to set the  
furnace in order to connect to the supply and return  
ductwork.  
2. The return air filter and rack are shipped in either  
the bottom or side location. Remove the filter and  
filter rack by first turning the two latches on the  
blower door and tilting the door forward to remove.  
Remove the filter by sliding it out of the rack.  
Compress the spring loaded filter rack to disengage  
the retaining pins/screws from the furnace sides  
and slide the filter rack out.  
On any job, flexible connections of nonflammable ma-  
terial may be used for return air and discharge con-  
nections to prevent transmission of vibration.  
Though these units have been specifically designed  
for quiet, vibration free operation, air ducts can act  
as sounding boards and could, if poorly installed, am-  
plify the slightest vibration to the annoyance level.  
When the furnace is located in a utility room adjacent  
to the living area, the system should be carefully de-  
signed with returns which minimize noise transmission  
through the return air grille. Although these winter air  
conditioners are designed with large blowers operating  
at moderate speeds, any blower moving a high volume  
of air will produce audible noise which could be objec-  
tionable when the unit is located very close to a living  
area. It is often advisable to route the return air ducts  
under the floor or through the attic. Such design per-  
mits the installation of air return remote from the liv-  
ing area (i.e. central hall).  
When the furnace is installed so that the supply ducts  
carry air circulated by the furnace to areas outside the  
space containing the furnace, the return air shall also  
be handled by a duct(s) sealed to the furnace and termi-  
nating outside the space containing the furnace.  
Minimum return air “entering temperature” for  
the furnace is 55° F.  
Where there is no complete return duct system, the re-  
turn connection must be run full size from the furnace  
to a location outside the utility room, basement, attic,  
or crawl space.  
The filter rails are spring loaded for automatic  
adjustment to allow standard size, locally obtainable  
replacement filters. The filter rack itself slides to  
adjust to the required width needed for bottom or  
side return.  
3. For upflow side return installations, remove the  
insulation around the opening in the blower compart-  
ment.  
!
WARNING  
Do NOT install the filter in the return duct directly  
above the furnace in horizontal applications. Install  
the filter remotely. Installing the filter directly above  
the furnace in horizontal applications may cause  
property damage, serious injury or death.  
!
WARNING  
TO PREVENT INJURY OR DEATH DUE TO CONTACT  
WITH MOVING PARTS, TURN THE POWER TO THE  
FURNACE OFF BEFORE SERVICING FILTERS.  
4. The side panels of the upflow furnace include  
locating notches that are used as guides for cutting  
an opening for return air, refer to Figure 12 and the  
outline drawing on page 5 for duct connection  
dimensions for various furnaces.  
5. If a 3/4" flange is to be used for attaching the air in-  
let duct, add to cut where indicated by solid lines  
in Figure 12. Cut corners diagonally and bend out-  
ward to form flange.  
6. If flanges are not required, and a filter frame is in-  
stalled, cut between the locating notches. See  
Figure 12.  
7. Upflow Furnaces: a filter rack is factory supplied  
for bottom or side return. Use the filter rack on ei-  
ther side or on the bottom if the filter is to be used  
within the furnace cabinet.  
DO NOT install return air through the back of the  
furnace cabinet.  
RETURN AIR DUCT CONNECTION  
NOTE:  
On upflow 5 or 6 ton airflow models, if the airflow re-  
quirement exceeds 1800 CFM, these models will re-  
quire return air openings and filters on both sides; OR  
1 side and the bottom; OR just the bottom.  
10  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
REMOVE FILTER FROM UPFLOW  
FURNACE WHEN RETURN DUCT IS  
ATTACHED TO FURNACE TOP SIDE  
(HORIZONTAL LEFT OR RIGHT  
APPLICATIONS) AS SHOWN.  
q w  
*
CUT OUT  
FOR  
SIDE  
LOCATING  
FILTER  
FILTER  
NOTCHES  
PROVIDED  
FOR SIDE  
RETURN  
CUTOUT  
*
*
FRONT  
of Furnace  
*
SEE OUTLINE DRAWING  
*
Close coupled (less than 36")  
return (filter directly beneath bottom  
side return) not recommended due to  
noise considerations. If used, securely  
attach 1/2" mesh metal hardware cloth  
protective screen to the inside bottom of  
filter grill.  
e
When the upflow furnace is installed in the horizon-  
tal right or left application and a return duct is at-  
tached to the top side as shown in Figure 11, re-  
move the filter from the furnace and install in a re-  
mote location.  
Do not install the filter in the return duct directly  
above the furnace in horizontal applications.  
When the upflow furnace is installed in the horizon-  
tal right or left application and a close coupled (less  
than 36") return duct is attached to the bottom side  
of the furnace as shown in Figure 11, securely at-  
tach a 1/2" mesh metal hardware cloth protective  
screen to the inside bottom of the filter grill to pre-  
vent personal injury from contacting moving  
parts when reaching into the return opening  
to replace the filter.  
Airflow  
BOTTOM FILTER RACK INSTALLATION  
11. The bottom panel of the upflow furnace must be  
removed for bottom return air. After removing the  
filter and filter rack, lay the furnace on its back.  
Remove the two 5/16" hex screws securing the front  
of the bottom channel to the cabinet. Rotate the  
channel downward (or remove by lowering the front  
edge of the channel and pulling forward). Slide the  
bottom return air panel out of the cabinet. Rotate  
the front channel to its original position and rein-  
stall the two 5/16” screws.  
Close coupled (less than 36") return (filter directly  
beneath bottom side return) is not recommended  
due to noise considerations.  
Downflow Furnaces: Brackets are factory sup-  
plied to mount filters in the return air duct work.  
8. Connect the duct work to the furnace. See Outline  
Drawing for supply and return duct size and loca-  
tion. Flexible duct connectors are recommended to  
connect both supply and return air ducts to the fur-  
nace.  
RETURN AIR FILTERS  
TYPICAL UPFLOW RETURN AIR  
FILTER INSTALLATIONS  
These furnaces require high velocity type air filters.  
The filters may be installed within the furnace blower  
compartment for UPFLOW furnaces in either a BOT-  
TOM or SIDE (left side or right side) return air inlet.  
Some filters may need to be trimmed for side or bottom  
filter use.  
If only the front of the furnace is accessible, it is  
recommended that both supply and return air ple-  
nums are removable.  
9. The horizontal installation of the upflow fur-  
nace requires an external filter section. Do  
NOT use the bottom return filter within the fur-  
nace. Filter kits are available for horizontal  
applications.  
10. When replacing a furnace, old duct work should be  
cleaned out. Thin cloths should be placed over the  
registers and the furnace fan should be run for  
10 minutes. Don’t forget to remove the cloths be-  
fore you start the furnace.  
NOTE:  
For upflow 5 ton airflow models where the airflow  
requirement exceeds 1800 CFM - Models will require  
return air openings and filters on: (1) both sides, or (2)  
one side and the bottom, or (3) just the bottom.  
The furnace and the bottom filter rack installation can  
be seen in Figure 13.  
18-CD21D1-5  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TABLE 4  
FILTER RACK INSTALLATION FOR SIDE RETURN AIR  
ON UPFLOW FURNACES (LEFT OR RIGHT)  
UPFLOW FURNACE RETURN AIR FILTERS  
CABINET  
WIDTH  
CABINET  
CABINET  
The following checklist should be used when installing a  
right or left side return filter on an upflow furnace:  
QTY*  
BOTTOM FILTER  
SIDE FILTER  
14-1/2"  
17-1/2"  
21"  
1
1
1
1
14" X 25" X 1"  
17" X 25" X 1"  
20" X 25" X 1"  
24" X 25" X 1"  
17-1/2" X 25" X 1"  
17-1/2" X 25" X 1"  
17-1/2" X 25" X 1"  
17-1/2" X 25" X 1"  
a. Remove the filter.  
b. Remove the filter rack.  
c. Leave the bottom panel in place.  
24-1/2"  
d. Make side cutout by following the directions in  
the “Return Air Duct Connections” section on  
page 10.  
e. Compress the filter rack and reinstall in the side  
position on the furnace. Confirm that the upper  
retaining pin/screw locks into the engagement  
hole in the blower deck and the lower pin/screw  
rests against the side of the bottom panel. See  
Figures 15-16, 19-20.  
*First letter may be "A" or "T"  
**NOTE: For upflow 5 ton airflow models where the airflow  
requirement exceeds 1800 CFM - Modles will require return air  
openings and filters on: (1) both sides, or (2) one side and the  
bottom, or (3) just on the bottom  
OPTIONAL FILTER RACK INSTALLATION FOR BOTTOM  
RETURN  
The following checklist should be used when installing a  
bottom return filter on an upflow furnace:  
a. Remove the filter.  
f. Reinstall the furnace filter in the side position by  
inserting the chamfer end first into the filter  
rack.  
b. Remove the filter rack.  
c. Remove the bottom panel.  
d. With the filter removed, the filter rack is com-  
pressed and then inserted into the bottom of the  
furnace. The retaining screw/pin on each side  
inserts into engagement holes at the bottom of  
the furnace cabinet side. See Figure 18.  
Optional conversion kits for horizontal filters are  
BAYFLTR203 for 17 1/2" width cabinets, BAYFLTR204  
for 21" width cabinets, and BAYFLTR205 for 24" width  
cabinets. These include filters and brackets necessary  
for horizontal filters. In addition, optional door kit  
BAYFLTR206 is also available. See Figures 17 and 22.  
e. Reinstall the furnace filter in the bottom position  
by inserting the chamfer end first into the filter  
rack.  
SIDE  
CUTOUT  
r
y
Airflow  
RETAINING  
PIN  
(Both Sides)  
SPRINGS  
BOTTOM  
FILTER  
PANEL  
RACK  
RAILS  
INSTALLED  
SIDE  
CUTOUT  
Typical Upflow Right Side Return Filter Rack Installation  
t
u
RETAINING  
PIN  
(Both Sides)  
SPRINGS  
BOTTOM  
PANEL  
INSTALLED  
FILTER  
RACK  
RAILS  
Optional door kit  
BAYFLTR206  
Typical Horizontal Filter Installation  
Typical Upflow Left Side Return Filter Rack Installation  
12  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
Filter  
Rack  
i
REAR  
Furnace  
Cabinet  
Side  
a
SIDE  
-OUT  
CUT  
Filter Rack  
Retaining  
Screw/Pin  
ALTERNATE FILTER  
CLIPS LOCATION  
Engagement Hole  
For Filter Rack  
Installation With  
Bottom Return  
s
o
Filter Rack  
Retaining  
Screw/Pin  
Furnace  
Cabinet  
Side  
Filter  
Rack  
Engagement Hole  
For Filter Rack  
Installation With  
Bottom Return  
Optional door kit  
BAYFLTR206  
Bottom Panel  
Furnace  
RETURN AIR FILTERS FOR UPFLOW FURNACE IN  
HORIZONTAL CONFIGURATION  
When the Upflow Furnace is installed in the horizontal  
configuration, the return air filters must be installed  
exterior to the furnace cabinet. Remote filter grilles  
may be used for homeowner convenience or the filters  
may be installed in the duct work upstream of the fur-  
nace. See Figure 17.  
p
Engagement Hole  
For Filter Rack  
Installation With  
Side Return  
Blower  
Deck  
BLOWER  
DECK  
ALTERNATE UPFLOW FILTER CLIP/ BRACKET INSTAL-  
LATION - KIT09224  
Furnace  
Cabinet  
Side  
1.Determine the location to be used. The furnace  
cabinet has dimples for location of the alternate fur-  
nace clips (Side return only). Pre-drill clearance  
holes with a 3/16" drill. Bottom return holes are  
pre-drilled. See Figure 21.  
2.Install the clips in front and rear of the desired loca-  
tion using the screws provided. The filter clip with  
the leaf spring mounts in the rear of the cabinet.  
TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER  
INSTALLATIONS  
Filter  
Rack  
Assembly  
Filter Rack  
Retaining  
Screw/Pin  
These furnaces require high velocity type air filters.  
Downflow furnace filters must be located outside the  
furnace cabinet. Typical installations are shown in Fig-  
ure 22. Tables 5 and 6 provide information for installa-  
tion of the filter retaining brackets shipped with down-  
flow furnaces.  
18-CD21D1-5  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TABLE 5  
GENERAL VENTING INSTRUCTIONS  
CABINET  
WIDTH  
FILTER  
SIZE  
FILTER BRACKET  
LOCATION *  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
14-1/2"  
17-1/2"  
21"  
2 - 14X20X1  
2 - 16X20X1  
2 - 16X20X1  
2 - 16X20X1  
12-7/8"  
14-3/8"  
13-1/8"  
11-5/8"  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon  
monoxide poisoning or death.  
24-1/2"  
* Location dimension is from end of duct to the screw holes for the bracket.  
The following steps shall be followed for each appliance  
connected to the venting system being placed into  
operation, while all other appliances connected to the  
venting system are not in operation:  
TABLE 6  
RETURN FILTER ACCESS FILTER ACCESS  
CABINET  
WIDTH  
1. Seal any unused openings in the venting system.  
DUCT  
OPENING -  
DIMENSION "A" DIMENSION "B"  
OPENING -  
WIDTH  
2. Inspect the venting system for proper size and  
horizontal pitch, as required in the National Fuel  
Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA  
B149 Installation Codes and these instructions.  
Determine that there is no blockage or restriction,  
leakage, corrosion and other deficiencies which  
could cause an unsafe condition.  
14-1/2"  
17-1/2"  
21"  
13-1/4"  
16-1/4"  
19-3/4"  
23-1/4"  
12"  
15"  
14"  
14"  
14"  
14"  
19-1/2"  
22"  
24-1/2"  
3. As far as practical, close all building doors and  
windows and all doors between the space in which  
the appliance(s) connected to the venting system  
are located and other spaces of the building.  
4. Close fireplace dampers.  
5. Turn on clothes dryers and any appliance not  
connected to the venting system. Turn on any  
exhaust fans, such as range hoods and bathroom  
exhausts, so they are operating at maximum speed.  
Do not operate a summer exhaust fan.  
6. Follow the lighting instructions. Place the appliance  
being inspected into operation. Adjust the  
thermostat so appliance is operating continuously.  
7. If improper venting is observed during any of the  
above tests, the venting system must be corrected  
in accordance with the National Fuel Gas Code,  
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149  
Installation Codes.  
8. After it has been determined that each appliance  
connected to the venting system properly vents  
where tested as outlined above, return doors,  
windows, exhaust fans, fireplace dampers and any  
other gas-fired burning appliance to their previous  
conditions of use.  
14  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
NOTE:  
VENT PIPING  
The following section does not apply if BAYVENT800B  
(Masonry Chimney Vent Kit) is used. All instructions  
with the kit must be followed.  
These furnaces have been classified as Fan-Assisted  
Combustion System, Category I furnaces under the  
“latest edition” provisions of ANSI Z21.47 and CAN/  
CGA 2.3 standards. Category I furnaces operate with a  
non-positive vent static pressure and with a flue loss of  
not less than 17 percent.  
TABLE 7  
MASONRY CHIMNEY VENTING  
Tile Lined Chimney  
Chimney Lining  
Flexible  
NOTE:  
Type Furnace  
Internal  
No  
External “B” Vent  
Metal Liner  
If desired, a side wall termination can be accomplished  
through the use of an “add-on” draft inducer. The in-  
ducer must be installed according to the inducer  
manufacturer’s instructions. Set the barometric pres-  
sure relief to achieve -0.02 inch water column.  
Single Fan  
Assist  
No  
Yes  
*Yes  
*Yes  
Fan Assist  
+
Fan Assist  
No  
No  
Yes  
Yes  
Fan Assist  
+
Natural  
Yes  
No  
*Yes  
NOTE: When the downflow furnace is vented through  
the left side of the furnace cabinet using the provided  
cutout, Type B vent piping must be used.  
The furnace shall be connected to a factory built chim-  
ney or vent complying with a recognized standard, or a  
* Flexible chimney liner size is determined by using the type “B” vent size for  
the available BTUH input, then reducing the maximum capacity by 20%  
(multiply maximum capacity times 0.80). The minimum capacity is the same  
as shown in the “B” vent tables.  
masonry or concrete chimney lined with a lining mate- External Masonry Chimney  
rial acceptable to the authority having jurisdiction.  
Venting of fan assisted appliances into external chim-  
neys (one or more walls exposed to outdoor tempera-  
tures), requires the chimney be lined with type “B”,  
double wall vent or suitable flexible chimney liner ma-  
terial. This applies in all combinations of common vent-  
ing as well as for fan assisted appliances vented alone.  
!
WARNING  
Furnace venting into an unlined masonry chimney or  
concrete chimney is prohibited.  
Failure to follow this warning could result in property  
damage, personal injury, or death.  
!
WARNING  
VENTING INTO A MASONRY CHIMNEY  
CARBON MONOXIDE POISONING HAZARD  
If the chimney is oversized, the liner is inadequate, or  
flue-gas condensation is a problem in your area, con-  
sider using the chimney as a pathway or chase for type  
“B” vent or flexible vent liner. If flexible liner material  
is used, size the vent using the “B” vent tables, then re-  
duce the maximum capacity by 20% (multiply 0.80  
times the maximum capacity). Masonry Chimney Kit  
BAYVENT800B may be used with these furnaces (Up-  
flow model furnaces only) to allow venting into a ma-  
sonry chimney. Refer to the BAYVENT800B Installer’s  
Guide for application requirements.  
Failure to follow the installation instructions for the  
venting system being placed into operation could re-  
sult in carbon monoxide poisoning or death.  
The following installation practices are recommended to  
minimize corrosion caused by condensation of flue prod-  
ucts in the furnace and flue gas system.  
1. Avoid an excessive number of bends.  
2. Horizontal runs should pitch upward at least 1/4" per  
foot.  
3. Horizontal runs should be as short as possible.  
4. All vent pipe or connectors should be securely sup-  
ported and must be inserted into, but not beyond  
the inside wall at the chimney vent.  
5. When vent connections must pass through walls or  
partitions of combustible material, a thimble must  
be used and installed according to local codes.  
6. Vent pipe through the roof should be extended to a  
height determined by National Fuel Gas Code or  
local codes. It should be capped properly to prevent  
rain water from entering the vent. Roof exit should  
be waterproofed.  
INTERNAL MASONRY CHIMNEYS  
Venting of fan assisted appliances into a lined, internal  
masonry chimney is allowed only if it is common vented  
with at least one natural draft appliance; OR, if the  
chimney is lined with type “B”, double wall vent or suit-  
able flexible liner material (See Table 7).  
!
WARNING  
The chimney liner must be thoroughly inspected to in-  
sure no cracks or other potential areas for flue gas  
leaks are present in the liner. Liner leaks will result in  
early deterioration of the chimney.  
7. Use type “B” double wall vent when vent pipe is  
routed through cool spaces (below 60° F.).  
Failure to follow this warning could result in carbon  
monoxide poisoning or death.  
18-CD21D1-5  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TABLE 8  
ELECTRICAL CONNECTIONS  
GAS VENT TERMINATION  
!
WARNING  
ROOF PITCH  
FLAT TO 7/12  
MINIMUM HEIGHT  
The cabinet must have an uninterrupted or unbroken  
ground according to National Electrical Code, ANSI/  
NFPA 70 – “latest edition” and Canadian Electrical  
Code, CSA C22.1 or local codes to minimize personal  
injury if an electrical fault should occur.  
Failure to follow this warning could result in an electri-  
cal shock, fire, injury, or death.  
1.0 FEET *  
1.5 FEET  
2.0 FEET  
2.5 FEET  
3.25 FEET  
4.0 FEET  
5.0 FEET  
6.0 FEET  
7.0 FEET  
7.5 FEET  
8.0 FEET  
OVER 7/12 TO 8/12  
OVER 8/12 TO 9/12  
OVER 9/12 TO 10/12  
OVER 10/12 TO 11/12  
OVER 11/12 TO 12/12  
OVER 12/12 TO 14/12  
OVER 14/12 TO 16/12  
OVER 16/12 TO 18/12  
OVER 18/12 TO 20/12  
OVER 20/12 TO 22/12  
!
CAUTION  
* THIS REQUIREMENT COVERS MOST INSTALLATIONS  
The integrated furnace control is polarity sensitive. The  
hot leg of the 115 VAC power must be connected to the  
BLACK field lead.  
d
!
WARNING  
To prevent injury or death due to electrical shock or  
contact with moving parts, lock unit disconnect switch  
in the open position before servicing the unit.  
Failure to follow this warning could result in electri-  
cal shock, personal injury, or death.  
Make wiring connections to the unit as indicated on en-  
closed wiring diagram. As with all gas appliances using  
electrical power, this furnace shall be connected into a  
permanently live electric circuit. It is recommended  
that it be provided with a separate “circuit protection  
device” electric circuit. The furnace must be electrically  
grounded in accordance with local codes or in the ab-  
sence of local codes with the National Electrical Code,  
ANSI/NFPA 70 “latest edition” or Canadian Electrical  
Code, CSA C22.1, if an external electrical source is uti-  
lized.  
All field supplied wiring must conform with the tem-  
perature limitation for Type T wire [63° F. (35° C)],  
when installed in accordance with these instructions  
and wiring diagrams supplied with the furnace. A dis-  
connecting means must be located within sight from,  
and readily accessible to, the furnace.  
8. Where long periods of airflow are desired for com-  
fort, use long fan cycles instead of continuous air-  
flow.  
9. Apply other good venting practices as stated in the  
venting section of the National Fuel Gas Code  
ANSI Z223.1 “latest edition”.  
10. Vent connectors serving appliance vented by  
natural draft or non-positive pressure shall  
not be connected into any portion of a mecha-  
nized draft system operating under positive  
pressure.  
11. Horizontal pipe runs must be supported by hangers,  
straps or other suitable material in intervals at a  
minimum of every 3 feet of pipe.  
Refer to the SERVICE FACTS literature for unit wiring  
diagrams in addition to the diagram inside the blower  
door.  
12. A furnace shall not be connected to a chimney or  
flue serving a separate appliance designed to burn  
solid fuel.  
13. The flow area of the largest section of vertical vent  
or chimney shall not exceed 7 times the smallest  
listed appliance categorized vent area, flue collar  
area, or draft hood outlet area unless designed in  
accordance with approved engineering methods.  
π(D*)2  
4
Maximum Vent or Tile  
Lined Chimney Flow Area  
=
X 7  
*Drafthood outlet diameter, flue collar diameter, or listed appliance cat-  
egorized vent diameter.  
16  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE  
1 STAGE HEATING  
USING A 1 STAGE HEATING THERMOSTAT  
NO COOLING  
FURNACE  
SEE  
NOTE 7  
TWIN  
SEE  
NOTE 6  
TO 115 V 1 PH.,  
60 HZ., POWER  
SUPPLY PER  
B/C  
B/C  
LOCAL CODES  
HUM SEE  
NOTE 5  
From Dwg. 21B341437 P01  
EAC SEE  
NOTE 5  
From Dwg. B341437 Rev. 1  
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE  
1 STAGE HEATING, 1 STAGE COOLING  
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT  
(OUTDOOR SECTION WITHOUT TRANSFORMER)  
FURNACE  
SEE  
NOTE 7  
TWIN  
OUTDOOR UNIT  
(NO TRANSFORMER)  
SEE  
NOTE 8  
SEE  
NOTE 6  
B/C  
B/C  
TO 115 V 1 PH.,  
60 HZ., POWER  
SUPPLY PER  
LOCAL CODES  
HUM SEE  
NOTE 5  
EAC SEE  
NOTE 5  
From Dwg. B341436 Rev. 1  
From Dwg. 21B341436 P01  
18-CD21D1-5  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TWINNING  
These furnaces may be twinned. Twinning requires that  
two furnaces with the same configuration, capacity, and  
airflow must be used. They shall have common returns  
with equal pressure drops or ducts with equivalent  
lengths and sizes. See Field Wiring Diagrams below for  
proper hookup.  
TWINNING CONNECTION DIAGRAM  
FOR TWINNING 1 STAGE FURNACES WITH  
SINGLE WIRE TWINNING FEATURE  
1 STAGE HEAT  
1 STAGE HEATING ONLY THERMOSTAT  
ONLY  
THERMOSTAT  
(WITH FAN SWITCH)  
FURNACE NO. 1  
FURNACE NO. 2  
BLOWER OPERATION OF  
UNIT NO. 2 IS SYNCRONIZED  
WITH UNIT NO. 1 VIA SIGNALS  
FROM TWIN CONNECTION.  
TWIN  
TWIN  
SEE NOTE 4  
ISOLATION RELAY  
(FIELD SUPPLIED)  
SEE NOTE 4  
R1  
R1  
ISOLATION RELAY  
SEE NOTE 4  
SEE NOTE 3  
B/C  
B/C  
B/C  
From Dwg. 21B341422 Rev. 3  
TWINNING CONNECTION DIAGRAM  
FOR TWINNING 1 STAGE FURNACES WITH  
SINGLE WIRE TWINNING FEATURE  
1 STAGE HEAT / 1 STAGE COOL THERMOSTAT  
1 STAGE  
OUTDOOR UNIT  
(WITH TRANSFORMER)  
HEATING / COOLING  
THERMOSTAT  
FURNACE NO. 1  
FURNACE NO. 2  
BLOWER OPERATION OF  
UNIT NO. 2 IS SYNCRONIZED  
WITH UNIT NO. 1 VIA SIGNALS  
FROM TWIN CONNECTION.  
TWIN  
TWIN  
ISOLATION RELAY  
(FIELD SUPPLIED)  
SEE NOTE 3  
SEE NOTE 4  
OUTDOOR UNIT  
(NO TRANSFORMER)  
R1  
ISOLATION RELAY  
SEE NOTE 4  
R1  
SEE NOTE 5  
B/C  
B/C  
B/C  
ISOLATION RELAY  
(FIELD SUPPLIED)  
SEE NOTE 4  
From Dwg. 21B341423 Rev. 2  
18  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
GAS PIPING  
!
WARNING  
This unit is shipped standard for left side installation of  
gas piping. A piping knockout is also provided in the  
right side for an alternate piping arrangement. The in-  
stallation of piping shall be in accordance with piping  
codes and the regulations of the local gas company. Pipe  
joint compound must be resistant to the chemical reac-  
tion with liquefied petroleum gases.  
Refer to piping Table 9 for delivery sizes. Connect gas  
supply to the unit, using a ground joint union and a  
manual shut-off valve as shown in Figure 24. National  
codes require a condensation drip leg to be installed  
ahead of the controls as shown in Figure 24.  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could re-  
sult in serious injury, death or property damage. Never  
test for gas leaks with an open flame. Use a commer-  
cially available soap solution made specifically for the  
detection of leaks to check all connections. A fire or ex-  
plosion may result causing property damage, personal  
injury, or loss of life.  
LEFT SIDE PIPING (STANDARD)  
f
The furnace and its individual shut-off valve must be dis-  
connected from the gas supply piping system during any  
pressure testing of that system at test pressures in ex-  
cess of 1/2 psig.  
The furnace must be isolated from the gas supply piping  
by closing its individual manual shut-off valve during  
any pressure testing of the gas supply piping system at  
test pressures equal to or less than 1/2 psig.  
!
CAUTION  
Use a backup wrench on the gas valve when installing  
gas piping to prevent damage to the gas valve and  
manifold assembly.  
RIGHT SIDE PIPING (OPTIONAL)  
NOTE:  
Maximum pressure to the gas valve for natural gas is  
13.8" W.C. Minimum pressure is 5.0" W.C. Maximum  
pressure to the gas valve for propane is 13.8" W.C.  
Minimum pressure is 11.0" W.C.  
All gas fittings must be checked for leaks using a soapy  
solution before lighting the furnace.  
DO NOT CHECK WITH AN OPEN FLAME!  
The following warning complies with State of California law, Proposition 65.  
!
WARNING  
Hazardous Gases!  
TOP VIEW OF RIGHT SIDE PIPING  
Exposure to fuel substances or by-products of  
incomplete fuel combustion is believed by the state of  
California to cause cancer, birth defects, or other  
reproductive harm.  
SEQUENCE OF OPERATION  
THERMOSTAT CALL FOR HEAT  
R and W thermostat contacts close signaling the control  
module to run its self-check routine. After the control  
module has verified that the pressure switch contacts  
are open and the limit switch(es) contacts are closed,  
the draft blower will be energized.  
!
WARNING  
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY,  
DEATH AND EQUIPMENT DAMAGE, DO NOT STORE  
COMBUSTIBLE MATERIALS, GASOLINE OR OTHER  
FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.  
18-CD21D1-5  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
As the induced draft blower comes up to speed, the  
pressure switch contacts will close and the ignitor warm  
up period will begin. The ignitor will heat for approx. 20  
seconds, then the gas valve is energized to permit gas  
flow to the burners. The flame sensor confirms that ig-  
nition has been achieved within the 6 second ignition  
trial period.  
5. Use the following factors if necessary:  
For 1 Cu. Ft. Dial Gas Flow CFH =  
Chart Flow Reading ÷ 2  
For 1/2 Cu. Ft. Dial Gas Flow CFH =  
Chart Flow Reading ÷ 4  
For 5 Cu. Ft. Dial Gas Flow CFH =  
10X Chart Flow Reading ÷ 4  
After the flame sensor confirms that ignition has been  
achieved, the delay fan ON period (fixed at 45 seconds)  
begins timing. After the delay of 45 seconds, the indoor  
blower motor will be energized and will continue to run  
during the heating cycle.  
6. Multiply the final figure by the heating value of the  
gas obtained from the utility company and compare  
to the nameplate rating. This must not exceed the  
nameplate rating.  
7.Changes can be made by adjusting the manifold  
pressure or changing orifices (orifice change may  
not always be required). To adjust the manifold  
pressure:  
a.Turn off all electrical power to the system.  
b.Attach a manifold pressure gauge to the outlet pres-  
sure tap marked "OUT PRESS TAP" on White-  
Rodgers gas valve model 36F or boss marked "OUT  
P" on White-Rodgers gas valve model 36G. (See Fig-  
ure 26 for White-Rodgers gas valve model 36F and  
Figure 25 for White-Rodgers gas valve model 36G).  
For the gas valve model 36F, measurement re-  
quires removal of the plug and installation of a  
barbed fitting. Attach flexible tubing and a manom-  
eter to the barbed fitting.  
For the gas valve model 36G, do not remove the  
pressure tap test screw. Using a 3/32" hex wrench,  
loosen the pressure tap test screw one turn and in-  
stall 5/16" flexible tubing and a manometer directly  
onto the outlet pressure boss.  
c. Turn on system power and energize valve.  
d.Remove the regulator adjustment screw cap on the  
gas valve for manifold pressure adjustment.  
e.Turn the adjustment nut clockwise to increase the  
gas flow rate, and counterclockwise to decrease the  
gas flow rate using a 3/32" hex wench.  
f. The final manifold pressure setting shall be 3.5"  
W.C. with an input of no more than nameplate rat-  
ing and no less than 93% of the nameplate rating,  
unless the unit is derated for high altitude.  
g.Replace the regulator adjustment screw cap and  
tighten securely.  
h.Turn off all electrical power to the system.  
i. Remove the manometer and flexible tubing. Re-  
move the barbed fitting and replace the plug or  
tighten the pressure test screw.  
j. Turn on electrical power to the system and energize  
valve.  
When the thermostat is satisfied, R and W thermostat  
contacts open, the gas valve will close, the flames will  
extinguish, and the induced draft blower will be de-en-  
ergized. The indoor blower motor will continue to run  
for the fan off period (fixed at 100 seconds), then will be  
de-energized by the control module.  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could re-  
sult in serious injury, death or property damage. Never  
test for gas leaks with an open flame. Use a commer-  
cially available soap solution made specifically for the  
detection of leaks to check all connections. A fire or ex-  
plosion may result causing property damage, personal  
injury, or loss of life.  
START-UP AND ADJUSTMENT  
PRELIMINARY INSPECTIONS  
With gas and electrical power “OFF”  
1. Duct connections are properly sealed  
2. Filters are in place  
3. Venting is properly assembled  
4. Blower door is in place  
Turn knob on main gas valve within the unit to the  
OFF” position. Turn the external gas valve to “ON”.  
Purge the air from the gas lines. After purging, check  
all gas connections for leaks with a soapy solution – DO  
NOT CHECK WITH AN OPEN FLAME. Allow 5 min-  
utes for any gas that might have escaped to dissipate.  
LP Gas, being heavier than air, may require forced ven-  
tilation. Turn the knob on the gas valve in the unit to  
the “ON” position.  
COMBUSTION AND INPUT CHECK  
1. Make sure all gas appliances are off except the fur-  
nace.  
2. Clock the gas meter with the furnace operating (de-  
termine the dial rating of the meter) for one revolu-  
tion.  
3. Match the “Sec” column in the gas flow (in cfh)  
Table 12 with the time clocked.  
k. Using a leak detection solution or soap suds, check  
for leaks at plug or pressure boss screw.  
4. Read the “Flow” column opposite the number of sec-  
onds clocked.  
20  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
HIGH ALTITUDE DERATE  
!
CAUTION  
Input ratings (BTUH) of these furnaces are based on  
sea level operation and should not be changed at eleva-  
tions up to 2,000 ft.  
Replace and/ or tighten all plugs removed or loosened  
when adjusting gas pressure. Leak check the fittings  
before placing the furnace into regular service.  
Failure to follow this warning could result in fire, ex-  
plosion, or property damage.  
If the installation is 2,000 ft. or above, the furnace input  
rate (BTUH) shall be reduced 4% for each 1,000 ft.  
above sea level. The furnace input rate shall be checked  
by clocking the gas flow rate (CFH) and multiplying by  
the heating value obtained from the local utility sup-  
plier for the gas being delivered at the installed altitude.  
Input rate changes can be made by adjusting the mani-  
fold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas)  
or changing orifices (orifice change may not always be  
required). If the desired input rate cannot be achieved  
with a change in manifold pressure, then the orifices  
must be changed. LP installations will require an orifice  
change.  
Installation of this furnace at altitudes above 2,000 ft.  
(610m) shall be in accordance with local codes, the Na-  
tional Fuel Gas Code, ANSI Z223.1/ NFPA 54 or Na-  
tional Standard of Canada, Natural Gas and Propane  
Installation Code, CSA B149.1. Installation of this fur-  
nace at altitudes above 2,000 ft. (610m) shall be made in  
accordance with the listed high Altitude Conversion Kit  
available with this furnace.  
For LP gases, the final manifold pressure setting shall  
be 10.5" W.C. with an input of no more than the name-  
plate rating and no less than 93% of the nameplate rat-  
ing, unless the unit is derated for altitude.  
Table 10 lists the main burner orifices shipped with the  
furnace. If a change of orifices is required to correct the  
input rate, refer to Table 11.  
TABLE 9  
NATURAL GAS ONLY  
TABLE OF CUBIC FEET PER HOUR OF GAS  
FOR VARIOUS PIPE SIZES AND LENGTHS  
LENGTH OF PIPE  
PIPE  
SIZE  
10  
132  
278  
520  
1050  
20  
92  
30  
73  
40  
63  
50  
56  
60  
50  
70  
46  
1/2  
3/4  
1
190  
350  
730  
152  
285  
590  
130  
245  
520  
115  
215  
440  
105  
195  
400  
96  
180  
370  
1-1/4  
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas  
IMPORTANT:  
TABLE 10  
ORIFICE SIZES  
Re-install the propane orifices to the same depth as the  
orifices supplied with the equipment.  
MAIN BURNER ORIFICE  
DRILL SIZE  
INPUT  
RATING  
BTUH  
NUMBER  
OF  
BURNERS  
See Table 13 for help in selecting orifices if orifice  
change is required. Furnace input rate and tempera-  
ture rise should be checked again after changing ori-  
fices to confirm the proper rate for the altitude.  
Installations above 4,000 feet may require a pressure  
switch change. If required, use the BAYHALT*** Kit  
(High Altitude Accessory Kit) listed in PRODUCT DATA.  
NAT. GAS  
LP GAS  
40,000  
60,000  
80,000  
100,000  
120,000  
140,000  
2
3
4
5
6
7
45  
45  
45  
45  
45  
45  
56  
56  
56  
56  
56  
56  
TABLE 11  
PART NUMBERS FOR REPLACEMENT ORIFICES  
!
WARNING  
DRILL  
SIZE  
PART  
NUMBER  
DRILL  
SIZE  
PART  
NUMBER  
EXPLOSION HAZARD!  
PROPANE GAS IS HEAVIER THAN AIR AND MAY  
COLLECT IN ANY LOW AREAS OR CONFINED  
SPACES. IN ADDITION, ODORANT FADE MAY MAKE  
THE GAS UNDETECTABLE EXCEPT WITH A WARN-  
ING DEVICE. IF THE GAS FURNACE IS INSTALLED  
IN A BASEMENT, AN EXCAVATED AREA OR A  
CONFINED SPACE, IT IS STRONGLY RECOM-  
MENDED TO CONTACT A GAS SUPPLIER TO IN-  
STALL A GAS DETECTING WARNING DEVICE IN  
CASE OF A GAS LEAK.  
44  
45  
46  
47  
48  
49  
50  
ORF00501  
ORF00644  
ORF00909  
ORF00910  
ORF01099  
ORF00503  
ORF00493  
54  
55  
56  
57  
58  
59  
ORF00555  
ORF00693  
ORF00907  
ORF00908  
ORF01338  
ORF01339  
NOTE: The manufacturer of your furnace does NOT test  
any detectors and makes no representations regarding  
any brand or type of detector.  
18-CD21D1-5  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
TABLE 12  
TABLE 13  
GAS FLOW IN CUBIC FEET PER HOUR  
2 CUBIC FOOT DIAL  
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW  
Orifice  
Twist Drill  
Size If  
Installed  
At Sea  
ALTITUDE ABOVE SEA LEVEL  
and Orifice Required At Other Elevations  
8
9
900  
800  
720  
655  
600  
555  
514  
480  
450  
424  
400  
379  
360  
343  
327  
313  
300  
288  
277  
267  
257  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
248  
240  
232  
225  
218  
212  
206  
200  
195  
189  
185  
180  
176  
172  
167  
164  
160  
157  
153  
150  
147  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
144  
141  
138  
136  
133  
131  
129  
126  
124  
122  
120  
116  
112  
109  
106  
103  
100  
97  
82  
84  
86  
88  
90  
92  
94  
96  
98  
100  
104  
108  
112  
116  
120  
124  
128  
132  
136  
140  
144  
88  
86  
84  
82  
80  
78  
76  
75  
73  
72  
69  
67  
64  
62  
60  
58  
56  
54  
53  
51  
50  
Level  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
2000 3000 4000 5000 6000 7000 8000 9000 10000  
42  
43  
44  
45  
46  
47  
42 43 43 43 44 44 45 46  
44 44 44 45 45 46 47 47  
45 45 45 46 47 47 48 48  
46 47 47 47 48 48 49 49  
47 47 47 48 48 49 49 50  
47  
48  
50  
50  
51  
52  
48 48 49 49 49 50 50  
51  
54  
55  
56  
57  
58  
54 55 55 55 55 55 56 56  
55 55 55 56 56 56 56 56  
56 56 57 57 57 58 59 59  
56  
57  
60  
63  
64  
58 59 59 60 60  
59 60 60 61 62 62 63 63  
From National Fuel Gas Code - Table F-4  
61 62 63  
LIGHTING INSTRUCTIONS  
!
WARNING  
DO NOT attempt to manually light the burner.  
Failure to follow this warning could result in property  
damage, personal injury or death.  
95  
92  
90  
Lighting instructions appear on each unit. Each  
installation must be checked out at the time of  
initial start up to insure proper operation of all  
components. Check out should include putting  
the unit through one complete cycle as outlined  
below.  
Regulator  
Adjustment  
Outlet Pressure Boss  
g
Turn on the main electrical supply and set the thermo-  
stat above the indicated temperature. The ignitor will  
automatically heat, then the gas valve is energized to  
permit the flow of gas to the burners. After ignition and  
flame is established, the flame control module monitors  
the flame and supplies power to the gas valve until the  
thermostat is satisfied.  
Inlet Pressure  
Boss (opt.)  
On/Off Switch  
TO SHUT OFF  
White-Rodgers 36G gas valve  
For complete shutdown: Move the control switch on the  
main gas valve to the “OFF” position (See Figures 25  
and 26). Disconnect the electrical supply to the unit.  
h
On/Off Switch  
!
CAUTION  
If this is done during the cold weather months, provi-  
sions must be taken to prevent freeze-up of all water  
pipes and water receptacles.  
Failure to follow this warning could result in property  
damage.  
Whenever your house is to be vacant, arrange to  
have someone inspect your house for proper tem-  
perature. This is very important in below freez-  
ing weather. If for any reason your furnace  
should fail to operate damage could result, such  
as frozen water pipes.  
White-Rodgers 36F gas valve  
22  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
INSTRUCTIONS TO THE OWNERS  
CONTROL AND SAFETY SWITCH  
In the event that electrical, fuel, or mechanical  
failures occur, the owner should immediately  
turn the gas supply off at the manual gas valve,  
located in the burner compartment (See Figure  
24). Also turn off electrical power to the furnace  
and contact the service agency designated by  
your dealer.  
ADJUSTMENT  
LIMIT SWITCH CHECK OUT  
The limit switch is a safety device designed to close the  
gas valve should the furnace become overheated. Since  
proper operation of this switch is important to the  
safety of the unit, it must be checked out on initial  
start up by the installer.  
To check for proper operation of the limit switches, set  
the thermostat to a temperature higher than the indi-  
cated temperature to bring on the gas valve. Restrict  
!
WARNING  
Should overheating occur, or the gas supply fail to  
the airflow by blocking the return air or by disconnect- shut off, shut off the gas valve to the unit before shut-  
ting off the electrical supply.  
Failure to follow this warning could result in property  
damage, personal injury or death.  
ing the blower. When the furnace reaches the maxi-  
mum outlet temperature as shown on the rating plate,  
the burners must shut off. If they do not shut off after a  
reasonable time and overheating is evident, a faulty  
limit switch is probable and the limit switch must be re-  
placed. After checking the operation of the limit control,  
be sure to remove the paper or cardboard from the re-  
turn air inlet, or reconnect the blower.  
The following warning complies with State of California law, Proposition 65.  
!
WARNING  
This product contains fiberglass wool insulation!  
Fiberglass dust and ceramic fibers are believed by the  
State of California to cause cancer through inhalation.  
Glasswool fibers may also cause respiratory, skin, or  
eye irritation.  
AIRFLOW ADJUSTMENT  
Check inlet and outlet air temperatures to make sure  
they are within the ranges specified on the furnace rat-  
ing nameplate. If the airflow needs to be increased or  
decreased, see the wiring diagram for information on  
changing the speed of the blower motor.  
PRECAUTIONARY MEASURES  
Avoid breathing fiberglass dust.  
Use a NIOSH approved dust/ mist respirator.  
!
WARNING  
Avoid contact with the skin or eyes. Wear long-  
sleeved, loose-fitting clothing, gloves, and eye  
protection.  
Disconnect power to the unit before removing the  
blower door.  
Failure to follow this warning could result in property  
damage, personal injury or death.  
Wash clothes separately from other clothing: rinse  
washer thoroughly.  
This unit is equipped with a blower door switch which  
cuts power to the blower and gas valve causing shut-  
down when the door is removed. Operation with the  
door removed or ajar can permit the escape of danger-  
ous fumes. All panels must be securely closed at all  
times for safe operation of the furnace.  
Operations such as sawing, blowing, tear-out, and  
spraying may generate fiber concentrations requiring  
additional respiratory protection. Use the appropriate  
NIOSH approved respirator in these situations.  
FIRST AID MEASURES  
Eye Contact – Flush eyes with water to remove dust. If  
symptoms persist, seek medical attention.  
NOTE:  
Direct drive motors have bearings which are perma-  
nently lubricated and under normal use, lubrication is  
not recommended.  
Skin Contact Wash affected areas gently with soap  
and warm water after handling.  
INDOOR BLOWER TIMING  
OPERATING INFORMATION  
The control module controls the indoor blower. The  
blower starts approximately 45 seconds after ignition.  
The FAN-OFF period is approximately 100 seconds  
from the interruption of gas flow.  
ROOM AIR THERMOSTAT HEAT ANTICIPATOR  
ADJUSTMENT  
Set the thermostat heat anticipator according to the  
current flow measured, or the settings found in the  
notes on the furnace wiring diagram (found inside the  
furnace casing).  
FLAME ROLL-OUT DEVICE  
All models are equipped with a thermal control device  
on the burner cover. In case of flame roll-out, the device  
will cause the circuit to open which shuts off all flow of  
gas.  
ABNORMAL CONDITIONS  
1. EXCESSIVE COMBUSTION VENT PRESSURE OR  
FLUE BLOCKAGE  
If pressure against the induced draft blower outlet  
becomes excessive, the pressure switch will shut off  
the gas valve until acceptable combustion pressure  
is again available.  
18-CD21D1-5  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer’s Guide  
2. LOSS OF FLAME OR GAS SUPPLY FAILURE These devises should be listed by Underwriters Labora-  
If loss of flame occurs during a heating cycle (when tories, Inc. Standards for Single and Multiple Station  
flame is not present at the sensor), the control mod- Carbon Monoxide Alarms, UL 2034 or CSA Interna-  
ule will retry the ignition sequence up to two times tional Standard, Residential Carbon Monoxide Alarming  
after the sensor cools. If ignition is not achieved, it Devices, CSA 6.19.  
will lockout the furnace.  
3. POWER FAILURE  
NOTE:  
The manufacturer of your furnace does not test any de-  
tectors and makes no representations regarding any  
brand or type of detector.  
If there is a power failure during a heating cycle,  
the system will restart the ignition sequence auto-  
matically when power is restored, if the thermostat  
still calls for heat.  
!
WARNING  
4. INDUCED DRAFT BLOWER FAILURE  
Failure to follow safety warnings exactly, could  
result in a fire or explosion causing property  
damage, personal injury or loss of life.  
If pressure is not sensed by the pressure switch, it  
will not allow the gas valve to open, therefore the  
unit will not start. If failure occurs during a running  
cycle, the pressure switch will cause the gas valve  
to close and shut the unit down.  
— Do not store or use gasoline or other flammable  
vapors and liquids in the vicinity of this or any  
other appliance.  
Carbon monoxide, fire or smoke can cause serious  
bodily injury, death, and/ or property damage.  
— WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
A variety of potential sources of carbon monoxide can be  
found in a building or dwelling such as gas-fired clothes  
dryers, gas cooking stoves, water heaters, furnaces and  
fireplaces. The U.S. Consumer Product Safety Commis-  
sion recommends that users of gas-burning appliances  
install carbon monoxide detectors as well as fire and  
smoke detectors per the manufacturers installation in-  
structions to help alert dwelling occupants of the pres-  
ence of fire, smoke or unsafe levels of carbon monoxide.  
• Do not touch any electrical switch;  
do not use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
• If you cannot reach your gas supplier,  
call the fire department.  
— Installation and service must be performed by  
a qualified installer, service agency or the gas  
supplier.  
INTEGRATED FURNACE CONTROL ERROR FLASH CODES  
Normal - No call for Heat  
Flashing Slow ---  
Flashing Fast ---  
Continuous ON ---  
Normal - Call for Heat  
Replace IFC  
Continuous OFF --- Check Power  
2 Flashes ---  
System Lockout (Retries or Recycles exceeded)  
Draft Pressure Error - Possible problems:  
a) Venting problem  
b) Pressure switch problem  
3 Flashes ---  
c) Inducer problem  
4 Flashes ---  
5 Flashes ---  
6 Flashes ---  
7 Flashes ---  
8 Flashes ---  
Open Temperature Limit Circuit  
Flame sensed when no flame should be present  
115 volt AC power reversed, poor grounding or system voltage too low  
Gas valve circuit error  
Low flame sense signal  
Check Ignitor Circuit and Line "N" to 24VAC "Common" voltage (2 volts)  
[possible grounding problem]  
9 Flashes ---  
Trane  
6200 Troup Highway  
Tyler, TX 75707  
File Number  
Supersedes  
Date  
18-CD21D1-5  
18-CD21D1-4  
05/08  
For more information contact  
your local dealer (distributor)  
Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right  
to change design and specifications without notice.  
24  
18-CD21D1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tascam Cassette Player DA 20 User Manual
Technicolor Thomson Video Game Controller LCP 400 User Manual
The Eltron Company Printer LP2022 User Manual
Toshiba All in One Printer e STUDIO203 User Manual
Toshiba Webcam R30 A User Manual
Tripp Lite Computer Drive U232 006 User Manual
Tripp Lite Power Supply APS1250F User Manual
Troy Bilt Snow Blower 772C0767 User Manual
Uniden Cordless Telephone UIP300 User Manual
Weber Outdoor Fireplace 43028 User Manual