Toshiba Power Supply TOSNIC 7000S User Manual

6 F 3 H 1 0 0 1  
Uninterruptible Power System (UPS)  
TOSNIC-7000S  
Instruction Manual (OPERATION)  
REQUIREMENT  
This manual should be delivered to the persons who  
will ultimately use and maintain the UPS.  
Read this manual carefully before operating the UPS.  
Store the manual in a safe place so it can be referred  
to when needed.  
July 1999  
©
ALL Rights Reserved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
1. Introduction  
This manual is designed to ensure the safe and correct operation of the TOSNIC-7000S  
Uninterruptible Power System (hereafter referred to as "UPS unit"). Please read the "Safety  
Precautions" and "Operation" sections of this manual carefully before use and make sure you  
have a thorough understanding of the information in these two sections. Keep the manual  
handy in a place near the unit so you can refer to it instantly when needed.  
Note that this manual was written based on the standard circuits shown in figures 6.2 (page  
13). The delivered UPS system may, if desired by the customer, differ from the standard  
configuration. Similarly, the displayed markings may differ from those on the standard  
system. If this is the case, follow the operating procedures and indications provided in the  
development circuit diagrams created individually for the UPS system actually delivered.  
Also, while this manual uses the term UPS, the equipment may be marked "CVCF" according  
to customer specifications. If this is the case, remember that the term UPS in the manual is  
equivalent to CVCF.  
2. Safety Precautions  
This manual and the labels on the UPS main unit contain important information designed to  
ensure that the UPS unit is used correctly and safely and prevent property loss and injury to  
operators and maintenance personnel. Operators and maintenance personnel should follow  
all precautions noted in the manual and should have a thorough understanding of the  
meaning of the safety signs and safety symbols shown below.  
Safety signs  
Safety sign  
Meaning  
Indicates that failure to observe proper handling  
WARNING procedures may result in death or serious injury  
Indicates that failure to observe proper handling  
procedures may result in injury* or property damage  
CAUTION  
*
Here "injury" refers to burns, electrical shock or other injuries that do not  
require hospitalization or long-term medical care.  
Safety symbols  
Safety symbol  
Meaning  
PROHIBITED  
The exact nature of what is prohibited is indicated in  
pictorial or text form in or near the symbol  
MANDATORY  
The exact nature of what must be done is indicated in  
pictorial or text form near the symbol.  
- 2 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
2. Safety Precautions (continued)  
Use  
Special considerations (*) are required when using equipment that affects the  
lives and safety of human beings (**) or has a critical effect on maintaining  
public services (***). Be sure to contact Toshiba in such cases. The use of such  
equipment without special consideration may result in serious accidents.  
*
Means holding through consultations with system designers regarding  
system operation and management and building a backup system for use in  
the event of UPS failure.  
** Operating room equipment  
Life support equipment (artificial dialysis, incubators, etc.)  
Noxious gas or smoke eliminators  
Equipment that must be provided under fire laws, construction standards or  
other ordinances  
Equipment equivalent to the above  
*** Equipment used to supervise or control airways, railways, roads, sea  
lanes or other transportation routes  
Equipment used to control nuclear power plants, etc.  
Equipment used to control communications  
Equipment equivalent to the above  
Warranty  
The warranty on this product may not cover all primary, secondary or tertiary  
damage resulting from error or failure of this unit, connected units or software.  
Checking Warning Labels  
Check to make sure that warning labels are displayed in the appropriate places  
(see page 6).  
If labels are not present or are smudged and therefore illegible, contact the  
Toshiba Service Center .  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
2. Safety Precautions (continued)  
WARNING  
If the unit begins to emit smoke or strange odors, immediately turn off circuit  
breakers 52R and 72B.  
Continued use may result in fire. Contact the Toshiba Service Center.  
MANDATORY  
Contact the Toshiba Service Center in the event of malfunction or failure.  
This unit should be repaired only by authorized Toshiba  
service personnel. Servicing by untrained personnel may  
increase the scale of the failure or result in electric shock or  
injury.  
MANDATORY  
Do not attempt to modify or move the unit yourself or to have this done by a  
third party.  
Electric shock, injury or failure may result if persons other  
than specially trained Toshiba technicians attempt to modify  
or move the unit.  
Be sure to contact Toshiba if you wish modifications to be  
made or if you wish to move the unit.  
PROHIBITED  
Only open the front panel when performing necessary operations.*  
Operating parts and high-voltage areas inside the UPS have  
been provided with covers as a safety precaution. Still,  
touching areas other than those that must be touched to  
perform necessary operations may result in electric shock,  
burns or other injuries.  
*
In this case, "necessary operations" means  
operating circuit breakers/auxiliary  
switches and inserting/removing memory  
cards  
MANDATORY  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
2. Safety Precautions (continued)  
Do not open the rear door.  
WARNING  
The parts inside carry high voltage. Touching them may  
result in electric shock, burns or failure.  
PROHIBITED  
CAUTION  
Operators should be qualified* personnel.  
Operation of the UPS by unqualified or untrained personnel  
may result in electric shock, injury or failure.  
*
In accordance with customer stipulations  
MANDATORY  
Make sure the air vents on the front and top of the unit are not blocked.  
Blocking the vents will cause the temperature inside the unit  
to rise and may result in fire or unit failure.  
PROHIBITED  
Make sure you understand the meaning of the warning labels on the equipment,  
and follow the precautions indicated.  
Operating the equipment with an inadequate understanding  
of these matters may result in electric shock or burns.  
See Page 6 for the location of these warning labels.  
MANDATORY  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
2. Safety Precautions (continued)  
Checking warning labels  
(1) The locations of the warning labels on the UPS are shown in Figure 2.1.  
Check to make sure that these warning labels are in place.  
Note that the placement and content of the warning labels may differ  
depending on the capacity of the UPS. Verify the locations by referring to  
the warning label placement figure provided with the "Maintenance &  
Inspection 6F3H1002" manual.  
(2) Read all warning labels and make sure you understand their meaning.  
(3) Make sure warning labels are always legible. Do not allow them to become  
smudged and do not remove or cover them up.  
A
Locations of the Warning Labels (Example: 300 kVA)  
WARNING  
Hazardous voltage  
can cause injury or death.  
Do not touch primary side  
of MCCB.  
B
Hazardous voltage  
can shock.  
Connect  
grounding terminal  
to ground  
before operating.  
C
WARNING  
Hazardous voltage  
can cause injury or death.  
(Discharge takes  
approx. 20 minutes)  
D
WARNING  
G
F
Q
H
Hazardous voltage  
can cause injury or death.  
Be always  
turn on  
Do not turn off  
in running  
WARNING  
WARNING  
Hazardous voltage  
Do not open panel  
while operating.  
Rotating shaft  
can cause injury.  
Do not touch  
rotating section.  
can cause injury or death.  
T
Do not touch live part  
of orange wiring.  
E
Check having fixed completely  
with the screw of a unit,  
when restoring this unit.  
CAUTION  
Hot surface can burn.  
Do not touch transformer  
or reactor.  
*
**  
The nameplate B is attached at the ground wire connection points in each section.  
The nameplates E are mounted in the vicinity of the main circuit transformers and  
reactors that can be seen from the back of the panel.  
Figure 2.1  
Unit Interior Front (with front panel open) and Warning Labels (Example)  
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
3. Handling Precautions  
Perform daily and periodic inspections as noted in the maintenance and inspection  
plan.  
In order to ensure a long service life and optimal performance,  
the equipment must be installed in a suitable environment, must  
be operated correctly, and must be given the proper daily and  
periodic inspections. Maintenance and inspections are  
particularly effective in preventing accidents caused by changes  
in components that will occur over time. Be sure to have  
periodic maintenance work and inspections done by Toshiba  
service and maintenance personnel.  
For more information on servicing programs and fee options,  
contact the Toshiba Service Center.  
Operate the unit within the ambient conditions noted in the specifications.  
Operating the unit outside these ranges may result in failure.  
During operation, do not turn off the air conditioner for the UPS chamber and the  
battery chamber.  
This will cause the temperature in these chambers to rise and may result in failure.  
PROHIBITED  
When starting or stopping the equipment, monitor the operation on the graphic  
display panel LCD and follow the procedures described in Chapter 8 "Operation".  
Operating the unit in other than the prescribed manner may result in failure.  
*
The startup and stop procedures presented in this instruction  
manual are the operating procedures for independent UPS nits.  
For system-wide operating procedures for when other  
distribution panels are present, refer to the corresponding  
operating procedures manual.  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
3. Handling Precautions (continued)  
Do not turn the circuit breakers ON when control power source switch (8A) is OFF.  
This may result in failure.  
Certain units also have a control power source switch (8D).  
This switch has the same functions as the switch 8A.  
PROHIBITED  
Do not turn the control power source switch (8A) to the OFF position when the  
circuit breakers are ON.  
This may result in failure.  
Certain units also have a control power source switch (8D).  
This switch has the same functions as the switch 8A.  
PROHIBITED  
When operating the keys on the graphic display panel, hold down the key for at  
least 0.5 second.  
The operation may not be performed if the key is held down for  
shorter periods of time.  
When operating the reset key on the graphic display panel, hold down the key for at  
least 5 seconds.  
The reset operation may not be performed if the key is held  
down for shorter periods of time.  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
3. Handling Precautions (continued)  
When the unit has stopped due to failure, be sure to remove the memory card  
before resetting the LCD Failure Error screen on the panel.  
Resetting (restarting) the UPS without removing the memory card will  
delete the data needed to determine the cause of the failure.  
Do not leave the unit for long periods of time (1 week) with control power source  
switch (8A) in the OFF position.  
This can cause the backup capacitor on the control board to become  
discharged and result in incorrect time display and other problems.  
PROHIBITED  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
4. Contents  
1. Introduction ····························································································································2  
2. Safety Precautions·················································································································2  
3. Handling Precautions ············································································································7  
4. Contents································································································································10  
5. Appearance···························································································································11  
6. Controls and Circuit Configuration·····················································································12  
6.1 Panel Controls·················································································································12  
6.2 Circuit Configuration········································································································13  
6.3 Panel Controls·················································································································14  
6.3.1 Panel Key-switch·································································································15  
6.3.2 Panel Keys ··········································································································15  
7. Panels····································································································································17  
7.1 Graphic Display Panel·····································································································17  
7.2 LCD Display·····················································································································20  
7.2.1 Normal Display Screen························································································21  
7.2.2 Failure Display Screen ························································································23  
7.2.3 Warning Data Display Screen·············································································23  
7.2.4 LCD Screen Switching ························································································24  
8. Operation ······························································································································25  
8.1 Types of Operation··········································································································26  
8.2 Pre-operational check ·····································································································26  
8.3 Procedures ······················································································································27  
8.3.1 Startup ················································································································27  
8.3.2 Switch Power Supply (UPS Bypass)····························································31  
8.3.3 Stop ·····················································································································32  
8.3.4 Complete Shutdown····························································································34  
8.3.5 Changing Between Floating Charge and Equalized Charge  
(For HS or AHH individual battery systems) ·····················································36  
8.3.6 Changing to Floating Charge etc. (for MSE individual battery)··························38  
8.3.7 Changing the Power Supply to Maintenance Bypass. ·······································39  
9. Troubleshooting···················································································································40  
9.1 Types of Errors················································································································42  
9.2 LCD Failure Displays·······································································································43  
9.2.1 Failure Data Screen ····························································································43  
9.2.2 Warning Data Screen··························································································44  
9.2.3 Failure Messages································································································45  
9.2.4 Scrolling Through LCD Screens in the Event of Failure ·····································48  
9.3 Saving Waveforms ··········································································································50  
9.4 Restoring UPS Operation································································································50  
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
5. Appearance  
Only open the front panel when performing necessary  
operations.*  
Operating parts and high-voltage areas inside the UPS have  
been provided with covers as a safety precaution. Still, touching  
areas other than those that must be touched to perform  
necessary operations may result in electric shock, burns or other  
injuries.  
WARNIN  
G
*
In this case, "necessary operations" means operating circuit  
breakers/auxiliary switches (6CH/8A) and inserting/removing  
memory cards  
Do not open the rear door.  
The parts inside carry high voltage. Touching them may result in  
electric shock, burns or failure.  
Make sure the air vents on the front and top of the unit are not  
blocked.  
CAUTION  
Blocking the vents will cause the temperature inside the unit to  
rise and may result in fire or unit failure.  
Example: 300 kVA  
Graphics display panel  
Front panel handle (includes a lock)  
Front air vent  
Channel base  
Figure 5.1  
Unit Exterior (front)  
*
This is an example of the appearance of a standard configuration unit (300 kVA) UPS.  
In some cases, depending on system configuration, an additional panel may be  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
6. Controls and Circuit Configuration  
If the unit begins to emit smoke or strange odors, immediately  
WARNIN turn off circuit breakers 52R and 72B.  
Continued use may result in fire. Contact the Toshiba Service  
Center .  
G
6.1 Panel Controls  
Figure 6.1 and Table 6.1 show the locations and functions of the controls used for the circuit  
configurations (see Figures 6.2) on the UPS.  
Do not turn the circuit breakers ON when control power source  
switch (8A) is OFF.  
This may result in failure.  
Do not turn the control power source switch (8A) to the OFF  
position when the circuit breakers are ON.  
This may result in failure.  
NOTES  
* Certain systems are also provided with a control power source  
switch (8D).  
This switch has the same functions as the switch 8A.  
If an MCCB with auxiliary handles is used as the circuit  
breaker, use the auxiliary handles during operation.  
Example: 300 kVA  
c52R  
d72B  
e52R  
f52M  
g52L  
h8A  
i6CH  
The figure above is only an example; the layout may be  
different depending on capacity and system configuration.  
Figure 6.1 Location of Control (in panel)  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 6.1  
Control Functions  
Normal Status  
No.  
Device  
Name / Function  
Remarks  
During Operation  
Main circuit AC input circuit breaker  
When the AC input is normal, power is  
supplied to the UPS through this circuit  
breaker.  
Main circuit DC input circuit breaker  
When AC input has been cut off, power is  
supplied from the battery to the UPS  
through this circuit breaker.  
When the circuit breaker  
is tripped in manual  
mode, reset it by grasping  
the handle and pulling it  
down or to the right.  
52R  
ON  
c
72B  
52C  
52M  
52L  
8A  
ON  
ON  
OFF  
ON  
ON  
ON  
d
Bypass AC circuit breaker  
When bypass power is supplied, power is  
supplied to the load through this circuit  
breaker.  
Maintenance bypass AC circuit breaker  
When bypass power is supplied for UPS  
maintenance, power is supplied to the  
load through this circuit breaker.  
AC output circuit breaker  
e
f
While UPS power or bypass power is  
supplied, power is supplied to the load  
through this circuit breaker.  
g
h
i
Control power source switch  
Certain systems are  
also provided with the  
switch 8D.  
When AC input is normal, pressing this  
switch supplies power to the control power  
source.  
Precharge circuit button  
6CH  
Pressing this button supplies power to the  
circuit that precharges the DC electrolytic  
capacitor before power is supplied to  
circuit breaker 52R.  
6.2 Circuit Configuration  
52R  
UPS  
AC INPUT  
72B  
52L  
AC OUTPUT  
BATTERY  
52C  
BYPASS  
AC INPUT  
52M  
Figure 6.2  
Standard Circuit Configuration  
- 13 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
6.3  
Panel Controls  
When the unit has stopped due to failure, be sure to remove the  
memory card before resetting the LCD Failure Error screen on the  
panel, so you can give it to the service person.  
Resetting (restarting) the UPS without removing the memory card will  
delete the data needed to determine the cause of the failure.  
NOTES  
Every effort has been made to ensure safety in unit handling.  
However, when removing the memory card, do not touch the other  
sections of the unit.  
Touching the other sections of the unit may result in electric shock.  
The locations of the controls on the panel are shown in Figure 6.3.1. For the functions of  
each of the controls, see Section 6.3.1 "Panel Key-switch" and Section 6.3.2 "Panel Keys."  
i
SCROLL  
j
WARNING  
FAULT  
UPS SUPPLY  
(**)  
CONVERTER  
AC INPUT  
INVERTER  
UPS  
FLOATCHARGE  
EQUAL CHARGE  
AC  
SWITCH  
AC OUTPUT  
BATTERIES  
DISCHARGE  
c
e
BYPASS INPUT  
BYPASS  
k
g
UPS  
STOP  
CHARGE AC SWITCH FAULT  
OPERATION  
EQUAL  
FLOAT  
BYPASS  
RESET  
OPERATION  
INHIBITED  
RUN  
UPS  
d
f
l(***)  
NOTE ***  
h(*)  
Do not use the keypad on  
graphic display panel l.  
This keypad is used to  
change the internal  
settings and should  
only be used by  
maintenance  
Figure 6.3.1  
Panel Controls  
(For individual battery systems. For HS or AHH batteries.)  
personnel.  
It is not used during  
normal operation.  
*
This will be the "FLOAT" key for MSE individual battery systems.  
** This will be the "PROTECTION" LED for MSE individual battery  
systems.  
- 14 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
6.3.1 Panel Key-switch  
Table 6.2 shows the function of the key-switch on the graphic display panel.  
Table 6.2 Key-switch Function  
Function  
No.  
Name  
Remarks  
c
OPERATION  
LOCK  
Setting this key-switch to the "OPERATION"  
side enables operation using the buttons on  
the panel; setting it to the "OPERATION  
INHIBITED" side prevents operation. When  
the switch is set to the "OPERATION  
INHIBITED" side, buttons d - h and k in  
Table 6.3 are inoperative and pressing them  
has no effect upon the operation of the UPS.  
LCD scroll buttons i and j are effective  
regardless of the position of this switch.  
Normally setting the  
switch to the  
OPERATION INHIBITED"  
prevents operational  
errors. The key can be  
removed when it is set to  
the "OPERATION  
INHIBITED" position; it  
cannot be removed when  
the switch is set to the  
"OPERATION" position.  
6.3.2 Panel Keys  
Table 6.3 shows the functions of the keys on the graphic display panel.  
When operating the keys on the graphic display panel, hold down the key for  
at least 0.5 second.  
When operating the reset key on the graphic display panel, hold down the  
NOTES  
key for at least 5 seconds.  
The operation may not be performed if the key is held down for shorter periods  
of time.  
Table 6.3  
Name  
Key Functions (For HS or AHH individual battery systems)  
No.  
Function  
Remarks  
d
RUN  
Starts up the UPS.  
The UPS starts up when this key is  
pressed after the required operational  
preparations are complete.  
e
f
g
STOP  
UPS  
Stops the UPS.  
Pressing this key during operation  
prepares the UPS to be stopped with  
the required procedure.*  
Changes to UPS power  
supply  
Pressing this key during UPS operation  
when bypass power is being supplied  
changes it to UPS power.  
BYPASS  
Changes to bypass power  
supply  
Pressing this key during UPS operation  
when the bypass is normal changes it to  
bypass power.  
- 15 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 6.3  
Name  
Key Functions (For HS or AHH individual battery systems) (continued)  
No.  
Function  
Remarks  
h
FLOAT / EQUAL**,  
***  
Changes the battery charging Pressing this key during UPS operation  
mode.  
changes the status to equalized charge  
(If it is currently set to floating charge) or  
floating charge (If it is currently set  
equalized charge).  
i
j
k
SCROLL UP  
SCROLL DOWN  
RESET  
These keys switch the screen For details, see Section 9.2.4 "Scrolling  
displayed on the LCD.  
Through LCD Screens in the Event of  
Failure" on Page 47, and Section 7.2.4  
"Changing the LCD Screen switching"  
on page 24.  
Resets the Failure Data  
screen and Warning Data  
screen shown on the LCD.  
*
Pressing this key when a power outage has occurred (during DC operation), causing a  
trip error and stopping the UPS. For special systems in which a separate DC UPS is  
connected to this unit for use as a control power source, the unit stops normally.  
** In an MSE individual battery system, the FLOAT switch switches the battery charge mode  
from protected to floating.  
*** This switch is not present in shared battery systems.  
- 16 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
7. Panels  
7.1 Graphic Display Panel  
Figure 7.1.1 and 7.1.2 and Table 7.1 show the locations and functions of the controls on the  
graphic display panel.  
11  
SCROLL  
12  
13  
14  
17  
16  
WARNING  
FAULT  
UPS SUPPLY  
15  
20  
AC INPUT  
INVERTER  
UPS  
CONVERTER  
24  
FLOAT CHARGE  
EQUAL CHARGE  
AC  
SWITCH  
AC OUTPUT  
BATTERIES  
(*) 21  
18  
25  
DISCHARGE  
BYPASS INPUT  
BYPASS  
19  
23  
UPS  
CHARGE  
AC SWITCH  
FAULT  
OPERATION  
EQUAL  
FLOAT  
OPERATION  
INHIBITED  
STOP  
BYPASS  
RESET  
RUN  
UPS  
22  
(**)  
*
This will be the "PROTECTION" LED for MSE individual battery systems.  
** This will be the "FLOAT" key for MSE individual battery systems.  
Figure 7.1.1  
Graphic Display Panel Controls (For HS or AHH battery)  
- 17 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
11  
12  
SCROLL  
13  
14  
17  
16  
WARNING  
FAULT  
UPS SUPPLY  
15  
20  
AC INPUT  
INVERTER  
UPS  
CONVERTER  
24  
18  
FLOAT CHARGE  
DISCHARGE  
AC  
SWITCH  
AC OUTPUT  
BATTERIES  
25  
BYPASS INPUT  
BYPASS  
19  
23  
UPS  
AC SWITCH  
FAULT  
OPERATION  
OPERATION  
INHIBITED  
STOP  
BYPASS  
RESET  
RUN  
UPS  
22  
Figure 7.1.2  
Graphic Display Panel Control  
(Graphic Display Panel of the type without the equalized  
charge mode and the protection charge mode).  
- 18 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 7.1  
Display Panel Functions (For HS or AHH individual battery systems)  
No.  
Name  
Function  
11  
LCD INDICATOR  
Displays help messages, measurement data and  
warning descriptions. For more information, see Section  
7.2 "LCD Display."  
12  
13  
14  
15  
UPS SUPPLY LED  
WARNING LED  
FAULT LED  
This LED lights up when the UPS is operating.  
This LED blinks in the event of an warning.  
This LED lights up in the event of a UPS failure.  
AC INPUT LED  
This LED lights up when the AC input circuit breaker  
(52R) has gone ON.  
16  
17  
CONVERTER LED  
INVERTER LED  
This LED is unlit when the converter has stopped  
operating. It blinks when the converter is starting up  
and is lit when startup is complete.  
This LED is unlit when the inverter has stopped  
operating. It blinks while the inverter is starting up and is  
lit when startup is complete.  
18  
19  
20  
21  
AC OUTPUT LED  
BATTERIES LED  
This LED lights up when the AC output circuit breaker  
(52L) is ON and AC voltage has been established.  
This LED lights up when the main circuit DC input circuit  
breaker (72B) has goes ON.  
FLOATING CHARGE  
LED**  
This LED lights up when the charging mode is set to  
floating charge.  
EQUAL CHARGE LED*, **  
This LED lights up when the charging mode is set to  
equalized charge.  
22  
23  
DISCHARGE LED  
This LED lights up when the battery is being discharged.  
BYPASS INPUT LED  
This LED lights up when the bypass input circuit breaker  
(52C) has gone ON.  
24  
25  
UPS LED  
This LED lights up when the selector switch is set to the  
UPS side.  
BYPASS LED  
This LED lights up when the selector switch is set to the  
bypass side.  
*
This becomes the PROTECTION LED in MSE individual battery systems.  
** This switch is not present in shared battery systems.  
- 19 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
7.2 LCD Display  
The LCD Display screens consist of the following screens.  
(1) Normal Display screen ............. Initial display, operation guidance, and measurement  
value display  
(2) Failure Data Display screen ..... Displays detailed data when a failure occurs.  
(3) Warning Data Display screen... Displays detailed data when a warning occurs.  
The operator can switch between these screens by pressing the scroll keys.  
: Scroll up  
: Scroll down  
Normal Display screen  
Failure Data  
Display screen  
Warning Data  
Display screen  
- 20 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
7.2.1 Normal Display Screen  
The Normal Display screen indicates the operational status of the UPS and provides a total of  
nine screens: one Operation Guidance Display screen and eight Measurement Value Display  
screens.  
Table 7.2 presents examples of these screens.  
Table 7.2  
Normal Display Screen  
Description  
No. LCD Screen  
1
Help screen  
(Example 1) Operation status  
Shows the status of the UPS at the top and help  
messages or measurements underneath.  
(Example 1)Shows help messages when starting  
or stopping operation.  
OPERATION GUIDANCE  
MOVE #52R TO “ON” POSITION  
(Example 2)  
(Example 2)Shows the output voltage and output  
current during operation.  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
Voltage (example)  
Current ratio (example)  
2
3
Measurement screen  
(Example) Output voltage  
Shows the output voltage between lines.  
O/P VOLTAGE (LINE)  
U - V  
V - W  
W - U  
200[V]  
200[V]  
200[V]  
Measurement screen  
(Example) Output current (RMS  
Shows the RMS value for the output current for  
each phase as a proportion (%) of the rated  
value.  
value)  
O/P CURRENT (r.m.s)  
U
V
W
50[%]  
50[%]  
50[%]  
4
Measurement screen  
(Example) Output current (peak)  
Shows the peak value for the output current for  
each phase as a proportion (%) of the rated  
value.  
O/P CURRENT (PEAK)  
Peak value for actual output current  
× 100 [%]  
U
V
W
50[%]  
50[%]  
50[%]  
TMRS value for rated current × 1.41  
- 21 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 7.2  
Measurement screen  
Normal Display Screen (continued)  
5
6
7
8
9
Shows the output frequency.  
(Example) Output frequency  
O/P FREQUENCY  
FREQ.  
60.0[Hz]  
Measurement screen  
(Example) AC input  
Shows the frequency and voltage values for AC  
input.  
AC INPUT  
AC I/P-V 200[V]  
FREQ. 60.0[Hz]  
Measurement screen  
(Example) Bypass input  
Shows the frequency and voltage values for  
bypass input.  
BYPASS INPUT  
BYP I/P-V 200[V]  
FREQ.  
60.0[Hz]  
Measurement screen  
(Example) DC value  
Shows the DC voltage and DC current.  
For the current value, "-" indicates charging and  
the absence of a plus/minus sign indicates  
discharging.  
DC INPUT  
DC-V  
401[V]  
BATT-V 401[V]  
BATT- I  
0[A]  
Measurement screen  
(Example) Counter value  
Shows the total time of UPS operation and the  
number of times the battery has been operated  
and total time for battery use (the time AC input  
has been off).  
MODE COUNT  
UPS  
17544[H]  
BATTERY 32[MIN]  
0[TIM]  
- 22 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
7.2.2 Failure Display Screen  
The Failure Display screen indicates the presence or absence of failure data and displays  
that data if present.  
Table 7.3  
Failure Display Screen  
Description  
LCD Screen  
Presence or absence of failure data  
This screen indicates the presence or absence of  
failure data.  
This screen is displayed if there is no failure data,  
or if all failure data has been reset with the "fault  
display rest" key.  
FAULT  
NO FAULT INFORMATION  
Failure data  
The failure data, the time the failure occurred, and  
an indication as to whether or not there is any  
other failure data is displayed with this screen if a  
failure occurs.  
FAULT  
1
52R TRIP  
When there is other failure data, that other data  
can be displayed using the △ ▽ scroll keys.  
98-09-09 08:05:30  
ANOTHER ITEM  
*
If there is failure data, that data will remain in the system, even after the actual cause of the  
failure has been resolved, until the failure display reset key on the front of the panel is  
pressed and held down for at least 5 seconds. Note that the failure data is not deleted when  
the unit is turned off.  
7.2.3 Warning Data Display Screen  
The Warning Data Display screen indicates the presence or absence of warning data and  
displays that data if present.  
Table 7.4  
Warning Data Display Screen  
Description  
LCD Screen  
Presence or absence of warning data  
This screen indicates the presence or absence of  
warning data.  
This screen is displayed if there is no warning  
data, or if all warning data has been reset with the  
"fault display reset" key.  
WARNING  
NO ALARM INFORMATION  
Warning date  
The warning data, the time the warning occurred,  
and an indication as to whether or not there is any  
other warning data is displayed with this screen if  
a warning occurs.  
When there is other warning data, that other data  
can be displayed using the △ ▽ scroll keys.  
WARNING  
1
72B MIS OPE  
98-09-09 08:05:30  
ANOTHER ITEM  
- 23 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
7.2.4 LCD Screen Switching  
The and scroll buttons on the front of the panel are used to switch the screen  
displayed on the LCD.  
See figure 6.3.1 for the location of the and scroll buttons.  
Symbol Name  
SCROLL  
Description  
Moves to the previous screen  
(see Figure 7.2)  
UP  
SCROLL  
DOWN  
Moves to the next screen  
(see Figure 7.2)  
Initial screen <Normal screen>  
UPS SUPPLY  
WARNING  
AC-VO  
AC- I O  
200[V]  
50[%]  
NO ALARM INFORMATION  
FAULT  
NO FAULT INFORMATION  
O/P VOLTAGE (LINE)  
U - V  
V - W  
W - U  
200[V]  
200[V]  
200[V]  
O/P CURRENT (r.m.s)  
MODE COUNT  
UPS 17544[H]  
BATTERY 32[MIN]  
0[TIM]  
U
V
50[%]  
50[%]  
50[%]  
W
O/P CURRENT (PEAK)  
DC INPUT  
U
V
W
50[%]  
50[%]  
50[%]  
DC-V  
BATT-V 401[V]  
BATT- I 0[A]  
401[V]  
O/P FREQUENCY  
BYPASS INPUT  
BYPI/P-V 200[V]  
FREQ.  
60.0[Hz]  
FREQ.  
60.0[Hz]  
AC INPUT  
AC I/P-V 200[V]  
FREQ. 60.0[Hz]  
Figure 7.2  
Using the Scroll Keys  
- 24 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8. Operation  
Operators should be qualified* personnel.  
Operation of the UPS by unqualified or untrained personnel may  
result in electric shock, injury or failure.  
*
In accordance with customer stipulations  
CAUTION  
Make sure you understand the meaning of the warning labels  
on the equipment, and follow the precautions indicated.  
Operating the equipment with an inadequate understanding of  
these matters may result in electric shock or burns.  
See Page 6 for the location of these warning labels.  
This section will describe the basic procedures used to operate the UPS.  
Operate the unit within the ambient conditions noted in the  
specifications.  
Operating the unit outside these ranges may result in failure.  
During operation, do not turn off the air conditioner for the UPS  
chamber and the battery chamber.  
This will cause the temperature in these chambers to rise and  
may result in failure.  
NOTES  
When starting or stopping the equipment, monitor the  
operation on the graphic display panel LCD and follow the  
procedures.  
Do not leave the unit for long periods of time (1 week) with  
control power source switch (8A) in the OFF position.  
This can cause the backup capacitor on the control board to  
become discharged and result in incorrect time display and other  
problems.  
- 25 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.1 Types of Operation  
This section summarizes the types of operations covered in this manual and their objectives.  
Refer to the attached operating procedures document for specific details on the operating  
procedures.  
No.  
1
Operation  
General Description/Objective  
Page No.  
Page 27  
Page.31  
Startup  
Starts up and operates the stopped UPS.  
2
Switch Power Supply Switches between UPS power supply and  
bypass power supply.  
3
4
Stop  
Stops a UPS that is operating.  
Page 32  
Page 34  
Complete shutdown Turns off the control power supply and shuts  
down the UPS completely.  
5
6
Charge  
(floating/equalized)  
Changes the mode for battery charging (in the  
case of HS or AHH individual battery).  
Page 36  
Page 39  
Floating charge  
Used to change the charging mode manually  
from protective charge to floating charge (in  
the case of an MSE individual battery).  
7
Supply power to  
maintenance  
bypass  
Changes the supply of power to the load to  
bypass power supply (when the UPS must be  
shut down completely for maintenance,  
inspection, etc.).  
Page 39  
8.2 Pre-operational check  
Be sure to check the following items before operating the UPS:  
(1) Make sure all internal covers are in place.  
(2) Make sure all doors are closed. If doors are opened to operate circuit breakers, switches  
and the like, be sure to close them afterward.  
(3) Make sure the air conditioners in the UPS chamber and battery chamber are operating.  
(4) When starting up the UPS, make sure all circuit breakers (52R,72B,52C,52L and 52M)  
and switches (8A and 6CH) are off. (Certain systems are also provided with the switch  
8D.)  
(5) When starting up the UPS, check on the equipment supplying power to the UPS to make  
sure AC input voltage is being supplied to the UPS.  
- 26 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3 Procedures  
8.3.1 Startup  
Table 8.1 shows the procedure used to start up the UPS.  
LED status  
: Unlit  
: Lit  
: Blinking  
Table 8.1  
Startup Procedures  
Step Procedure  
1 Turn on the control  
LCD/LED Status (After Execution)  
OPERATION GUIDANCE  
power supply switch  
(8A) on the panel.  
MOVE #52C AND #52L TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "BYPASS" LED lit.  
BYPASS  
2
Turn on the bypass AC  
input 52C and the AC  
output 52L circuit  
breakers.  
MOVE #6CH TO ‘ON’ POSITION  
(The UPS will change  
to bypass power  
supply status and AC  
output voltage will be  
generated.)  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "BYPASS INPUT" and The "OUTPUT"LEDs lit.  
3
Turn on the precharge  
circuit switch (6CH)*.  
BYPASS  
WAIT FOR A WHILE  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
*
The control power supply switch 8A is left in the on state (Do not turn this switch off.)  
- 27 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.1  
Startup Procedures (continued)  
Step Procedure  
4 Wait several seconds.**  
LCD/LED Status (After Execution)  
BYPASS  
MOVE #52R TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
5
When the message  
appears, turn on the  
main circuit AC input  
circuit breaker (52R).  
BYPASS  
WAIT FOR A WHILE  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "AC INPUT" LED Lit.  
6
Wait several seconds.  
BYPASS  
PRESS ‘RUN’ SWITCH  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
** Do not turn on circuit breaker 52R until the following message appears on the display:  
"MOVE #52R TO ‘ON’ POSITION"  
- 28 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.1  
Startup Procedures (continued)  
Step Procedure  
Hold down the "RUN"  
LCD/LED Status (After Execution)  
7
8
9
key (d in Figure 6.3.1  
on page 14) for at least  
0.5 second.  
BYPASS  
UPS START-UP  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "CONVERTER" and "INVERTER" LEDs blinking.  
Wait several seconds  
for the startup process  
to finish.  
BYPASS  
MOVE #72B TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "CONVERTER" and "INVERTER" LEDs lit.  
When the message  
appears, turn on the  
main circuit DC input  
circuit breaker (72B).  
BYPASS  
AC-VO  
AC- I O  
200[V]  
50[%]  
PRESS ‘UPS’ SWITCH  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "BATTERIES" and "FLOAT CHARGE" LEDs lit.  
- 29 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.1  
Startup Procedures (continued)  
Step Procedure  
10 Hold down the “UPS”  
LCD/LED Status (After Execution)  
key (g in the Figure  
6.3.1 on page14) for at  
least 0.5 second. *  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
The will start the  
power supply  
changing process.  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "BYPASS" LED unlit and “UPS” LED lit.  
11  
Wait several seconds  
for the process to be  
completed (change to  
UPS power supply).  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
This completes the  
UPS staartup  
operation.  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
*If for some reason the AC switch dose not function, contact the Toshiba Service Center.  
Do not manually operate the solenoid contactor (which is part of AC switch).  
- 30 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.2 Switch Power Supply (UPS Bypass)  
Table 8.2 shows the procedure used to switch between UPS power supply and bypass power  
supply.  
Table 8.2  
UPS Power Supply Bypass Power Supply  
Step Procedure  
LCD/LED Status (After Execution)  
1
Check to make sure  
power is being  
UPS SUPPLY  
supplied to the UPS.  
AC-VO  
AC- I O  
200[V]  
50[%]  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
2
Hold down the  
"BYPASS" key (f in  
Figure 6.3.1 on page  
14) for at least 0.5  
second.  
BYPASS  
AC-VO  
AC- I O  
PRESS ‘UPS’ SWITCH  
200[V]  
50[%]  
The will start the  
power supply  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
changing process.  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The “UPS” LED unlit and “BYPASS” LED lit.  
3
Wait several seconds  
for the process to be  
completed.  
BYPASS  
AC-VO  
AC- I O  
PRESS ‘UPS’ SWITCH  
200[V]  
50[%]  
Change to bypass  
power supply is  
completed.  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
*
To change from bypass to UPS power supply, use the procedure starting with Step 10 in  
Table 8.1 on page 30. If for some reason the AC switch dose not function, contact the  
- 31 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Toshiba Service Center. Do not manually operate the solenoid contactor (which is part of AC  
switch).  
- 32 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.3 Stop  
Table 8.3 shows the procedure used to stop the UPS.  
Table 8.3 Stop  
Step Procedure  
1 Change to bypass  
LCD/LED Status (After Execution)  
supply as described in  
Table 8.2 on page 31.  
BYPASS  
AC-VO  
AC- I O  
200[V]  
50[%]  
PRESS ‘UPS’ SWITCH  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The “UPS” LED unlit and “BYPASS” LED lit.  
2
Hold down the "STOP"  
key (e in Figure 6.3.1  
on page 14) for at least  
0.5 second.  
BYPASS  
RESTART : PRESS ‘RUN’ SWITCH  
SHUTDOWN : MOVE #72B TO ‘OFF’  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The “FLOAT CHARGE” and “CONVERTER”  
and “INVERTER” LEDs unlit.  
- 33 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.2  
Stop (continued)  
Step Procedure  
3 Turn off the main DC  
LCD/LED Status (After Execution)  
input circuit  
BYPASS  
breaker(72B).  
RESTART : PRESS ‘RUN’ SWITCH  
SHUTDOWN : MOVE #52R TO ‘OFF’  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The “BATTERIES” LED unlit.  
4
This complete UPS  
shutdown  
BYPASS  
RESTART : PRESS ‘RUN’ SWITCH  
SHUTDOWN : MOVE #52R TO ‘OFF’  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
- 34 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.4 Complete Shutdown  
This section describes the procedure used to turn off the control power source and shut  
down the UPS completely (to turn everything up to the control power source off).  
Table 8.4  
Complete Shutdown  
Step Procedure  
LCD/LED Status (After Execution)  
1-4  
5
Same as steps 1-4 in Section 8.3.3 "Stop."  
When the message  
appears, turn off the  
main circuit AC input  
circuit breaker (52R).  
BYPASS  
MOVE #52C AND #52L TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "AC INPUT" LED unlit.  
6
Turn off the AC output  
circuit breaker (52L).  
OPERATION GUIDANCE  
MOVE #52C TO ‘OFF’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "AC INPUT" LED unlit.  
7
Turn off the Bypass  
input circuit breaker  
(52C).  
OPERATION GUIDANCE  
MOVE #6CH TO ‘OFF’ POSITION  
WAIT ABOUT 20 MINUTES  
MOVE #8A TO ‘OFF’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "BYPASS INPUT" LED unlit.  
- 35 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.4  
Complete Shutdown (continued)  
Step Procedure  
LCD/LED Status (After Execution)  
8
Turn off the precharge  
circuit switch (6CH).  
OPERATION GUIDANCE  
MOVE #6CH TO ‘OFF’ POSITION  
WAIT ABOUT 20 MINUTES  
MOVE #8A TO ‘OFF’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
9
Wait about 20 minutes  
until the DC capacitor  
has been discharge.*  
OPERATION GUIDANCE  
MOVE #6CH TO ‘OFF’ POSITION  
WAIT ABOUT 20 MINUTES  
MOVE #8A TO ‘OFF’ POSITION  
10  
Using the scroll keys,  
change the display  
screen and check to  
make sure that the DC  
voltage is 0V (see  
Section 7.2.4 “LCD  
Screen Switching” on  
page 24).  
DC INPUT  
DC-V  
BATT-V  
BATT- I  
0[V]  
0[V]  
0[A]  
11  
Set the control power  
supply switch (8A) to  
the OFF position. *  
Nothing at all is displayed on the LCD and all LEDs are  
unlit.  
Complete shutdown  
*
This operation is different from that displayed in the help message on the screen.  
Be sure to perform the operation as described here.  
- 36 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.5 Changing Between Floating Charge and Equalized Charge  
(For HS or AHH individual battery systems)  
This section describes the procedure used to change the charging mode. This operation  
does not apply to shared battery systems.  
(1) Table 8.5 shows the procedure used to change manually from floating charge to  
equalized charge.  
Table 8.5  
Step Procedure  
Changing From Floating Charge to Equalized Charge  
LCD/LED Status (After Execution)  
1
Check to make sure  
that the "FLOAT  
UPS SUPPLY  
CHARGE" LED is lit.  
AC-VO  
AC- I O  
200[V]  
50[%]  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
2
Hold down the "FLOAT  
/ EQUAL" key (h in  
Figure 6.3.1 on page  
14) for at least 0.5  
second.  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
Change to  
equalized charge is  
complete.  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "EQUAL CHARGE" LED lit.  
The "FLOAT CHARGE" LED unlit.  
*
In equalized charge mode, the battery is charged for a set period of time at a voltage about  
5% (depending on the type of battery) higher than normal (floating) charge, in order to  
prevent variations in battery performance. This must be done about once every six months, in  
spring and autumn if possible.  
The TOSNIC-7000S UPS is equipped with a function that performs the equalized charging  
process automatically when restoring the battery charge after a power outage or the like.  
- 37 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
(2) Table 8.5 shows the procedure used to change manually from equalized charge to  
floating charge.  
After the charging mode has been changed to equalized charge using the procedure  
on the previous page, the mode will automatically change back to floating charge after  
a set period of time has elapsed. Therefore, normally there is no need to change the  
mode manually as described below.  
Table 8.6  
Step Procedure  
Changing From Equalized Charge to Floating Charge  
LCD/LED Status (After Execution)  
1
Check to make sure  
that the "EQUAL  
UPS SUPPLY  
CHARGE" LED is lit.  
AC-VO  
AC- I O  
200[V]  
50[%]  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
2
Hold down the "FLOAT  
/ EQUAL" key (h in  
Figure 6.3.1 on page  
14) for at least 0.5  
second.  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
Change to floating  
UPS  
charge is complete.  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "FLOAT CHARGE" LED lit.  
The "EQUAL CHARGE" LED unlit.  
- 38 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.6 Changing to Floating Charge etc. (for MSE individual battery)  
Table 8.7 shows the procedure used to change manually from protective charge to floating  
charge.  
This operation does not apply to shared battery systems.  
(1) An MSE battery normally operate in floating charge mode.  
(2) To prevent the battery temperature from rising, the mode changes automatically to  
protective charge mode when a "BATT FAULT1" (BATTERY OVER TEMP.) warning  
occurs.  
(3) In protective charge mode, the battery is automatically charged at a voltage about 5%  
lower than normal (floating) charge when the battery temperature has risen above the  
rated value, in order to prevent deterioration caused by excessive charging at high  
temperatures.  
(4) After a set amount of time has elapsed (about 6 hours), if the "BATT FAULT1"  
(BATTERY OVER TEMP.) warning message has disappeared, the mode will  
automatically change back to floating charge. As a result, it will not normally be  
necessary to change the mode manually as described below.  
Table 8.7  
Step Procedure  
Changing from Protective Charge to Floating Charge  
LCD/LED Status (After Execution)  
1
2
3
Check to make sure  
that the  
"PROTECTION" LED  
is lit..  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
Check to make sure  
that the "BATT FAULT1"  
warning message has  
disappeared.  
FLOAT CHARGE  
PROTECTION  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
Hold down the  
"FLOAT" key (h in  
Figure 6.3.1 on page  
14) for at least 0.5  
second.  
UPS SUPPLY  
AC-VO  
AC- I O  
200[V]  
50[%]  
Change to floating  
UPS  
charge is complete.  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
PROTECTION  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
The "FLOAT CHARGE" LED lit.  
The "PROTECTION" LED unlit.  
- 39 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
8.3.7 Changing the Power Supply to Maintenance Bypass  
This UPS must be completely shut down when performing maintenance and inspections. In  
such cases, the power supply to the load will go through the maintenance bypass. Table 8.8  
shows the procedure used to change the power supply to this maintenance bypass. Table 8.9  
shows how to change the power supply from the maintenance bypass back to the UPS.  
Table 8.8  
Changing From UPS to maintenance Bypass Power Supply  
LCD/LED Status (After Execution)  
Step Procedure  
1-3  
4
Same as steps 1-5 in Section 8.3.4 "Stop."  
Turn ON maintenance  
BYPASS  
bypass AC circuit  
breaker 52M. *,**  
MOVE #52C AND #52L TO ‘ON’  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
52R  
OFF  
72B  
52C  
ON  
52M  
ON  
52L  
ON  
MCCB  
OFF  
5
Perform steps 6  
When the UPS is shutdown completely, nothing at all will be  
through 11 in Table 8.4 displayed on the LCD screen and all LEDs will be unlit.  
“Complete Shutdown”  
on page 34 to shut  
down the UPS  
completely.  
52R  
OFF  
72B  
52C  
OFF  
52M  
ON  
52L  
MCCB  
OFF  
OFF  
Change to  
maintenance bypass  
power supply  
complete.  
* During load operation, always operate the circuit breakers in the following order :  
52M ON52lL OFF52C OFF  
** When power is supplied to the UPS, circuit breaker 52M cannot be turned on.  
- 40 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 8.9  
Changing From Maintenance Bypass to UPS Power Supply  
Step Procedure  
LCD/LED Status (After Execution)  
BYPASS  
1
Same as steps 1-4 in  
Section 8.3.1 “Startup”  
MOVE #52R TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
BATTERIES  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
52R  
OFF  
72B  
52C  
ON  
52M  
OFF  
52L  
ON  
MCCB  
OFF  
2
Turn OFF maintenance  
bypass AC circuit breaker  
BYPASS  
, ,  
52M. * ** ***  
MOVE #52R TO ‘ON’ POSITION  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
FLOAT CHARGE  
AC  
BATTERIES  
EQUAL CHARGE  
DISCHARGE  
SWITCH  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
52R  
OFF  
72B  
52C  
ON  
52M  
ON  
52L  
ON  
MCCB  
OFF  
3
Same as steps 5-11 in Section 8.3.1 “Startup”  
Change to UPS power supply complete.  
*
During load operation, ALWAYS operate the circuit breakers in the following order:  
52C ON 52L ON 52M OFF  
** UPS power supply is disabled when the 52M circuit breaker is in the on state.  
*** This operation is different from that displayed in the help message on the screen.  
Be sure to perform the operation as described here.  
- 41 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9. Troubleshooting  
When an error occurs on the UPS, error data is displayed on the LCD screen and the  
waveform is saved. This section will describe the types of errors, the error messages  
displayed on the LCD screen, the process of saving waveforms and the procedures used to  
correct the errors.  
9.1 Types of Errors  
The following types of errors may occur on the UPS:  
No.  
1
Name  
Description  
Fault (Trip)  
The UPS has been tripped and has stopped operating.  
2
Warning-1  
The converter has been stopped and power is being supplied  
(Converter stop/ from the battery. When the warning has been corrected, power is  
Input power  
error)  
automatically supplied from AC input.  
3
4
5
Warning-2  
(Stop and  
restart)  
The unit changes to bypass power supply and the UPS stops  
operating. When the warning has been corrected, the unit will  
automatically be restarted and revert to UPS power supply.  
Warning-3  
(Operation  
control)  
An error or phenomenon related to an error occurred. Since this  
problem does not directly affect operation, the system switches to  
synchronized mode.  
Warning-4  
(guidance)  
An error or indication of an error has occurred, but operation was  
not affected.  
- 42 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.2 LCD Failure Displays  
When a failure occurs, a screen such as that shown in Figure 9.1, and when a warning  
occurs, a screen such as that shown in Figure 9.2, will be displayed on the LCD.  
FAULT  
FAULT STOP  
1
52R TRIP  
98-09-09 08:05:30  
ANOTHER ITEM  
SERVICEMAN CALL  
Select the desired failure data with the scroll buttons.  
Detailed failure data can be displayed.  
Figure 9.1  
Failure Display  
WARNING  
UPS SUPPLY  
ALARM  
1
72B MIS OPE  
AC-VO  
AC- I O  
200[V]  
50[%]  
98-09-09 08:05:30  
ANOTHER ITEM  
When a warning (a limitation on operation or a guidance failure) occurs, "ALARM" will be displayed in the upper  
right of the LCD.  
Select the desired warning data with the scroll buttons.  
Detailed warning data can be displayed.  
Figure 9.2  
Warning Display  
9.2.1 Failure Data Screen  
This screen appears when a trip error is detected.  
Up to 10 screens of failure data can be displayed.  
Figure 9.3 and Table 9.1 show a sample screen and describe the data shown in the screen.  
FAULT  
1
52R TRIP  
98-09-09 08:05:30  
ANOTHER ITEM  
c
d
e
f
Figure 9.3  
Sample Failure Data Screen  
Table 9.1  
Failure Data Screen Descriptions  
No.  
Name  
Description  
c
No.  
The number of the message in the order that it was detected (1 - 10).  
(Up to 10 screens of failure data can be displayed.)  
d
Failure  
Message  
Shows the nature of the failure. For details, see Section 9.2.3  
"Failure Messages".  
e
f
Time  
The date and time (in 24-hour time) that the failure was detected.  
Scroll indicator Indicates whether there is a failure screen before or after this screen.  
indicates there is a failure screen before this screen.  
indicates there is a failure screen after this screen.  
↑↓ indicates there are failure screens both before and after this  
screen.  
- 43 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.2.2 Warning Data Screen  
These screens appear when a warning has occurred. Up to 10 screens can be displayed.  
Figure 9.4 and Table 9.2 show an example of this type of screen and describe the data  
shown in the screen.  
WARNING  
1
72B MIS OPE  
98-09-09 08:05:30  
ANOTHER ITEM  
c
d
e
f
Figure 9.4  
Sample Warning Data Screen  
Table 9.2  
Warning Data Screen Descriptions  
No.  
Name  
Description  
c
No.  
The number of the message in the order that it was detected (1 - 10).  
(Up to 10 screens of warning data can be displayed.)  
d
Warning  
Message  
Shows the nature of the warning. For details, see Section 9.2.3  
"Failure Messages".  
e
f
Time  
The date and time (in 24-hour time) that the warning was detected.  
Scroll indicator Indicates whether there is a warning screen before or after this screen.  
indicates there is a warning screen before this screen.  
indicates there is a warning screen after this screen.  
↑↓ indicates there are warning screens both before and after this  
screen.  
- 44 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.2.3 Failure Messages  
Figures 9.6 show the locations for failure detection. Tables 9.4 through 9.8 list the failure  
messages described in Section 9.2.1 "Failure Data Screen". The content and display text for  
the failure and warning messages in Tables 9.4 through 9.8 have been created based on  
the standard protective configuration shown in Figures 9.6.UPS units can be shipped with  
different protective configurations from the standard if this is specified by the customer. See  
the protective configuration indicated on the elementary wiring diagram created for each  
UPS unit shipped.  
47R  
95S  
27S  
59S  
51I  
51IO  
51CO  
51C  
59I  
27I  
51L1  
51L  
49H  
45  
INVERTER  
CONVERTER  
52R  
52L  
52RT  
76  
76CH  
30MU  
86MU  
83F  
72BT 72BO  
71BF  
5E  
80PS  
26C  
48S  
80B1 80B2  
UPS  
WDCPU  
WDDSP  
95C  
59C  
47C  
26B  
33B  
52CO  
52C  
27C  
52M  
Figure 9.6  
Protective Detector Locations  
- 45 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 9.4  
Fault (Trip)  
#
Item  
LCD Message  
Indication  
Description  
1
2
3
4
5
52RT  
72BT  
71BF  
86MU  
52R TRIP  
AC input circuit breaker #52R tripped.  
DC input circuit breaker #72B tripped.  
DC Main circuit fuse blew.  
72B TRIP  
DC FUSE BLW  
MU FAULT1  
An inverter or converted fuse blew.  
WDCPU WDCPU  
An error occurred in the main control  
microprocessor (CPU).  
6
7
8
80PS  
80B1  
5E  
CONT. PS. ERR  
The control power supply voltage fell.  
BATT UV  
Battery voltage is below discharged voltage.  
EPO SW ON  
An emergency stop was specified by the external  
contact input. (Option)  
Table 9.5  
Warning - 1 (Converter stop/Input power error)  
Description  
#
Item  
LCD Message  
Indication  
1
2
3
27S  
59S  
95S  
AC I/P UV  
AC I/P OV  
AC input voltage is low.  
AC input voltage is high.  
I/P FREQ. ERR  
AC input frequency error.  
Table 9.6  
Warning - 2 (Stop and restart)  
Description  
#
Item  
LCD Message  
Indication  
1
2
3
4
5
6
7
8
27I  
59I  
51L  
51I  
51IO  
76  
AC O/P UV  
AC O/P OV  
AC O/P OL  
AC O/P OC  
INV OC  
AC output voltage is low.  
AC output voltage is high.  
Load is too high.  
Load overcurrent.  
Inverter overcurrent.  
DC OC  
Excessive current in DC section of main circuit.  
Excessive voltage in DC section of main circuit.  
AC input overcurrent.  
45  
DC OV  
51C  
AC I/P OC  
9
51CO  
CONV OC  
Converter overcurrent.  
10 30MU  
MU FAULT2  
The converter and/or inverter gate voltage fell,  
or the converter and/or inverter overheated.  
11 26C  
OVER TEMP  
Temperature high in cubicle.  
12 WDDSP CONTROL ERR  
An error occurred in the control microprocessor  
(DSP).  
- 46 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 9.7  
LCD Message  
Warning-3 (Operation control)  
Description  
#
Item  
Indication  
1
2
3
59C  
27C  
95C  
BYPASS OV  
BYPASS UV  
BYPASS ASY  
Bypass input voltage is high.  
Bypass input voltage is low.  
Bypass input frequency error.  
Table 9.8  
Warning - 4 and 5 (Guidance)  
Description  
#
Item  
LCD Message  
Indication  
1
2
3
49H  
LOAD LIMIT  
Load has exceeded prescribed level.  
Load current peak value is high.  
51LI  
72BO  
O/P OC (PEAK)  
72B MIS OPE.  
72B has gone off during operation.  
(Including operation error)  
4
5
6
7
8
9
26B  
BATT FAULT1  
BATT FAULT2 *  
BATT UV (ALM)  
BATT OC  
Battery temperature has risen.  
33B  
Battery fluid level has gone below prescribed level.  
Battery voltage is near discharged voltage.  
Charging current is high.  
80B2  
76CH  
47R  
AC PHASE ERR  
BYPASS ERR  
STARTUP ERR  
52C MIS OPE.  
Phase ration of AC input is reserved.  
Phase ration of bypass input is reserved.  
Startup was not completed.  
47C  
10 48S  
11 52CO  
52C has gone off during opearion.  
(Including operation error)  
12 83F  
SWITCH ERR  
Changeover switch error.  
* This message is deleted in case of a sealed type NS and HHS or MSE battery.  
- 47 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.2.4 Scrolling Through LCD Screens in the Event of Failure  
When the unit has stopped due to failure, be sure to remove the  
memory card before resetting the LCD Failure Error screen on the  
panel, so you can give it to the service person.  
Resetting (restarting) the UPS without removing the memory card will  
delete the data needed to determine the cause of the failure.  
NOTES  
Every effort has been made to ensure safety in unit handling.  
However, when removing the memory card, do not touch the other  
sections of the unit.  
Touching the other sections of the unit may result in electric shock.  
This section describes how to scroll through the LCD screens when a failure has occurred (in  
other words, when Failure Data screens exist).  
Figure 9.8 shows the locations of the scroll keys used to scroll through the LCD screens. See  
Table 9.9 and Figure 9.9 for a discussion of the scroll keys and how they are used for screen  
scrolling.  
Note that pressing the "RESET" key k will delete the waveform data stored on the memory  
card as well as the Failure and Warning Data Screens. Be sure to remove the memory card  
before pressing the "RESET" key.  
i
SCROLL  
j
WARNING  
FAULT  
UPS SUPPLY  
AC INPUT  
INVERTER  
UPS  
CONVERTER  
FLOATCHARGE  
EQUAL CHARGE  
AC  
SWITCH  
AC OUTPUT  
BATTERIES  
DISCHARGE  
BYPASS INPUT  
BYPASS  
k
UPS  
CHARGE  
AC SWITCH  
FAULT  
OPERATION  
EQUAL  
FLOAT  
OPERATION  
INHIBITED  
STOP  
RESET  
BYPASS  
RUN  
UPS  
Figure 9.8 Position of Scroll Keys in Failure Data Screens  
(For Individual battery systems. For HS or AHH batteries.)  
- 48 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 9.9  
Scroll Keys  
No.  
i
Name  
Description  
SCROLL UP  
SCROLL DOWN  
RESET  
Scrolls to the previous screen (see Figure 9.9)  
Scrolls to the next screen (see Figure 9.9)  
j
k
Deletes the stored waveform and failure and warning data  
from the memory card.  
Normal Data  
Display screen  
(*)  
Failure Data  
Display screen  
(**)  
i
ii  
Warning Data  
Display screen  
(**)  
i
ii  
Remarks  
* See section 7.2.1 (on page 21, Normal Display Screen", for details on the content of the  
Normal Display screen.)  
**  
i
ii , etc. represent the order in which the failures occurred.  
Figure 9.9  
Changing Screens with Scroll Keys  
- 49 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.3 Saving Waveforms  
When the unit has stopped due to failure, be sure to remove the  
memory card before resetting the LCD Failure Error screen on the  
panel, so you can give it to the service person.  
Resetting (restarting) the UPS without removing the memory card will  
delete the data needed to determine the cause of the failure.  
NOTES  
Every effort has been made to ensure safety in unit handling.  
However, when removing the memory card, do not touch the other  
sections of the unit.  
Touching the other sections of the unit may result in electric shock.  
When a trip error occurs, do the following:  
[Procedure]  
Trip error occurs; UPS stops operating  
(1) Open the front door on the UPS graphic display panel (see Figure 5.1 on page 11).  
(2) Remove the memory card from the back of the door.  
(Verify that the memory card write LED shown in Figure 9.10 goes out.)  
(3) Insert a new memory card.  
(4) Close the door.  
(5) Give the memory cards that you have removed to the serviceman.  
Table 9.10  
Functions of the Memory Card Unit  
Name  
Description  
f
c Memory card  
Records failure data and waveforms.  
This memory card can record the data for four events.  
g
d Memory card eject button  
e Memory card write LED  
f Power LED  
Pressing this button ejects the memory card.*  
e
Lights when data is being written o the memory card.*  
Lights when power is applied to the waveform  
recording system from the operation power supply.  
(This LED will always be lit when the UPS is  
operating.)  
c
g Memory card manual write switch Used to write arbitrary data to the memory card.**  
d
Notes:  
*
Do not remove the memory card when the LED e is lit.  
** The switch g is used when adjusting the UPS and should only be used by  
a Toshiba serviceman or by maintenance personnel. This switch is not  
used during normal operation.  
Figure 9.10  
Memory Card Unit  
- 50 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
9.4 Restoring UPS Operation  
Contact the Toshiba Service Center in the event of malfunction  
or failure.  
This unit should be repaired only by authorized Toshiba service  
personnel. Servicing by untrained personnel may increase the  
scale of the failure or result in electric shock or injury.  
Do not attempt to modify or move the unit yourself or to have  
this done by a third party.  
Electric shock, injury or failure may result if persons other than  
specially trained Toshiba technicians attempt to modify or move  
the unit. Be sure to contact Toshiba if you wish modifications to  
be made or if you wish to move the unit.  
Only open the front panel when performing necessary  
operations.*  
WARNING  
Operating parts and high-voltage areas inside the UPS have  
been provided with covers as a safety precaution. Still, touching  
areas other than those that must be touched to perform  
necessary operations may result in electric shock, burns or other  
injuries.  
*
In this case, "necessary operations" means operating circuit  
breakers/auxiliary switches and inserting/removing memory  
cards.  
Do not open the rear door.  
The parts inside carry high voltage. Touching them may result in  
electric shock, burns or failure.  
This section describes the procedure used to restore UPS operation. Table 9.11 shows an  
example in which the UPS is restored after a trip error has occurred on circuit breaker 52R  
with the message "52R TRIP."  
- 51 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 F 3 H 1 0 0 1  
Table 9.11  
Restoring UPS Operation (Example)  
LCD/LED Status (After Execution)  
Step Procedure  
1
Check the LCD screen.  
FAULT  
Also check for other  
Failure Data screens  
by scrolling with scroll  
keys i and j on the  
panel.  
1
52R TRIP  
98-09-09 08:05:30  
ANOTHER ITEM  
UPS  
INVERTER  
AC INPUT  
CONVERTER  
2
Turn 6CH OFF.  
FLOAT CHARGE  
EQUAL CHARGE  
DISCHARGE  
AC  
SWITCH  
BATTERIES  
AC OUTPUT  
BYPASS  
BYPASS INPUT  
3
4
Remove the memory  
card in the panel and  
insert a new memory  
card.*  
Contact the Toshiba  
Service Center.  
Follow the directions given by Service Center personnel.  
In the case of other failures as well, restore by doing the following:  
(1) Check the nature of the failure on the LCD screen.  
(2) Contact the Toshiba Service Center.  
(3) Follow the directions given by Service Center personnel.  
Note:  
*
Before removing the memory card, always verify that the memory card write LED shown in  
figure 9.10 is not lit.  
- 52 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson DVD Player DTH220E User Manual
Technika MP3 Player MP 329 User Manual
Toshiba DVD Player SD 2150 User Manual
Transcend Information Digital Photo Frame TS2GPF810B User Manual
Transition Networks Switch SISTM10XX 162 LR User Manual
Trust Computer Products Tablet 15694 User Manual
Uniden Cordless Telephone EXI3246 Series User Manual
Vivotek Security Camera PT1111 User Manual
Vizio Speaker FB 120B User Manual
Vizualogic Car Video System HindsightTM User Manual