HIGH PERFORMANCE TRANSISTOR INVERTER
TRUE TORQUE CONTROL DRIVE SERIES
PROFIBUS-DP COMMUNICATIONS INTERFACE
December, 1998
ICC #10160-001
Download from Www.Somanuals.com. All Manuals Search And Download.
Usage Precautions
Operating Environment
•= Please use the interface only when the ambient temperature of the inverter unit into
which the interface is installed is within the following specified temperature limits:
Operation: -10 ∼ +40°C (+14 ∼ +104°F)
Storage:
-25 ∼ +65°C (-13 ∼ +149°F)
•= Avoid installation locations that may be subjected to large shocks or vibrations.
•= Avoid installation locations that may be subjected to rapid changes in temperature or
humidity.
Installation • Wiring
•= Do not touch charged parts such as the terminal block while the inverter’s CHARGE
lamp is lit. A charge will still be present in the inverter unit’s internal electrolytic
capacitors, and therefore touching these areas may result in an electrical shock.
Always turn all inverter input power supplies OFF, and wait at least 5 minutes after the
CHARGE lamp has gone out before connecting communication cables or motor wiring.
•= When installing the interface board into the inverter and making wiring connections,
make certain that no clippings or wiring leads that could cause device failure fall into
the inverter or onto electronic components.
•= Proper ground connections are vital for both safety and signal reliability reasons. For
proper grounding procedures, please refer to the section in this manual pertaining to
grounding (section 3).
•= Route the communication cables separate from the inverter input/output power wiring.
•= To avoid the possibility of electric shock due to leakage currents, always ground the
inverter unit’s E/GND terminal and the motor. To avoid misoperation, do not connect
the Profibus interface board's shield terminal to either of the above-mentioned grounds
or any other power ground.
Other Precautions
•= The inverter’s EEPROM has a life span of 10,000 write cycles. Do not write to the
same parameter register more than 10,000 times.
•= Do not touch or insert a rod or any other item into the inverter while power is applied,
as this may lead to electrical shock or inverter damage.
•= Commission the disposal of the interface board to a specialist.
•= Do not assign the same address to more than one inverter in the same network.
•= Individual slave addresses can be set from 0 ∼ 125. Addresses 126 and above are
invalid, and will cause the inverter to trip "OPTION PCB ERROR".
•= When the inverter’s control power supply is turned on, the inverter performs
initialization functions for approximately 2 seconds, during which communications
capabilities are disabled. Communications capabilities will also be disabled for
approximately 2 seconds after momentary control power supply outages or inverter
resets.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
1. Interface Board Diagram..........................................................................5
2. Interface Board Installation / Removal ...................................................6
2.1
2.2
2.3
Before Installation ............................................................................................6
Installation Procedure.......................................................................................7
Removal.........................................................................................................11
2.3.1
2.3.2
Before Removal ......................................................................................11
Removal Procedure.................................................................................11
3. Grounding...............................................................................................14
4. Equipment Specifications .....................................................................14
5. Maintenance And Inspection.................................................................15
6. Storage And Warranty............................................................................16
6.1
6.2
Storage ..........................................................................................................16
Warranty ........................................................................................................16
7. G3 Parameter Settings...........................................................................17
8. Feature Summary...................................................................................18
9. Exchanged Data Structures ..................................................................20
9.1
9.2
9.3
Output (Control) Data Format.........................................................................20
Input (Status) Data Format.............................................................................22
Diagnostics.....................................................................................................24
10. Parameter Register Access................................................................25
10.1
10.2
10.3
10.4
Parameter Number / Action Output Words .................................................25
Parameter Number / Action Input Words....................................................26
Parameter Access Procedure.....................................................................27
Register Access Error Codes......................................................................28
11. Parameter Registers...........................................................................29
11.1
11.2
Read-Only Registers ..................................................................................31
Read/Write Registers .................................................................................33
GROUP:FUNDAMENTAL PARAMETERS #1......................................33
GROUP:FUNDAMENTAL PARAMETERS #2......................................34
GROUP:PANEL CONTROL PARAMETERS .......................................34
GROUP:TERMINAL SELECTION PARAMETERS ..............................35
GROUP:SPECIAL CONTROL PARAMETERS....................................39
GROUP:FREQUENCY SETTING PARAMETERS...............................40
11.2.1
11.2.2
11.2.3
11.2.4
11.2.5
11.2.6
3
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.7
11.2.8
11.2.9
11.2.10
11.2.11
11.2.12
11.2.13
GROUP:PROTECTION FUNCTION PARAMETERS...........................43
GROUP:PATTERN RUN CONTROL PARAMETERS..........................45
GROUP:FEEDBACK CONTROL PARAMETERS................................48
GROUP:COMMUNICATION SETTING PARAMETERS......................49
GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS........................50
GROUP:UTILITY PARAMETERS........................................................51
GROUP:MOTOR RATING PARAMETERS .........................................53
11.3
Inverter Fault Codes ...................................................................................55
12. GSD File .............................................................................................. 57
13. Notes ................................................................................................... 59
4
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Interface Board Diagram
Standoff mounting holes
Plated SHIELD connection
point for grounding (refer to
Section 3).
Network connector (CN1)
Standoff mounting holes
5
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Interface Board Installation / Removal
The Profibus Communications Option ROM enclosed with the Profibus kit is
compatible only with G3 inverters with V120 or later main software. An error will
occur if the option ROM is installed in an inverter with pre-V120 main software. The
main software version number is printed on the CPU package (IC1) on the control
board. Additionally, this version number can be read from inverter memory by
displaying the parameter CPU VERSION in GROUP:UTILITY PARAMETERS. If you
are unsure of the software version of your inverter, please contact Toshiba
International Corporation for more information.
The Profibus option ROM version number is printed on the label attached to the
ROM. The option ROM version number can also be read from the inverter’s memory
and displayed on the LCD panel after initialization by displaying the parameter ROM
VERSION in GROUP:UTILITY PARAMETERS. The option ROM version number
replaces the standard ROM version number after installation/initialization.
IMPORTANT NOTE: The option ROM included with the Profibus interface kit
is for installation into G3 230V/460V units only. Do not install the option ROM into
any other inverter unit (such as H3, E3, or G3 600V units). All inverter units other
than the G3 230V/460V series are shipped from the factory with full communications
capability, and installation of the option ROM may cause incorrect operation or
inverter damage.
Please note that due to internal mechanical clearances, not all Profibus connectors
can be used on all inverter units. Ensure that the Profibus connector that you plan on
using does not come into contact with any of the drive’s internal components, circuit
boards or brackets. Toshiba has determined that connectors such as the ERNI
103648 (non-terminated) and 103649 (terminated) will work for all installations. If you
have difficulty locating a connector which will work properly in your unit, please
contact Toshiba International Corporation for assistance.
Additionally, certain drive models require a modified panel support bracket to allow
installation of the Profibus interface. Specifically, all G3 460v 10HP through 50HP
and 230v 7.5HP through 25HP units require a modified panel support bracket. To
obtain this support bracket, contact your local distributor or Toshiba International
Corporation.
2.1 Before Installation
All parameters will be automatically reset to the factory default values after the option
ROM is installed in the inverter. If it is desired to retain the current parameter
settings, the user should access the user-changed parameter group to display and
record all the parameters and setting values that have been changed from factory
defaults. Even if the current settings are saved to non-volatile memory by setting the
STANDARD SETTING MODE SELECTION parameter in GROUP:UTILITY
PARAMETERS to 5*, they will be erased from memory during initialization of the option
ROM.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
•= Setting the standard mode selection parameter will be referred to in this manual
as performing a TYPE X RESET, where X is the parameter setting value.
2.2 Installation Procedure
Installation of the TOSHIBA Profibus option ROM and interface board into a
TOSVERT-130 G3 inverter should only be performed by a qualified technician
familiar with the maintenance and operation of the G3. To install the option ROM and
interface board, complete the following steps:
1. Record the option ROM version number located on the label of the option ROM in
the following box. The option ROM version is the number immediately following
the “V” on the ROM label. For example, if the label indicates “V6402”, the option
ROM version is 6402. This version number will be used later in the installation
process. Option ROM version =
.
Record the standard ROM version number prior to option ROM installation. The
standard ROM version can be read from parameter ROM VERSION in
GROUP:UTILITY PARAMETERS.
Standard ROM version =
.
2.
3.
CAUTION! Verify that all input power sources to the inverter have
been turned OFF and are locked and tagged out.
DANGER!
Wait at least 5 minutes for the inverter’s electrolytic
capacitors to discharge before proceeding to step 4. Do not touch any internal
parts with power applied to the inverter, or for at least 5 minutes after
power to the inverter has been removed. A hazard exists temporarily for
electrical shock even if the source power has been removed.
4.
Remove the inverter’s cover (open the door on units with hinged doors).
Verify that the CHARGE LED has gone out before continuing the installation
process.
5. Loosen the 4 screws attaching the G3’s operation panel support bracket to the
control board support bracket, and then remove the operation panel and support
bracket as a unit (refer to Figure 1).
7
Download from Www.Somanuals.com. All Manuals Search And Download.
operation panel
support bracket
operation panel support
bracket screws
Figure 1: G3 with front cover removed
6.
CAUTION! The option ROM PCB assembly and interface board are
static-sensitive devices. Standard electrostatic-sensitive component handling
precautions should be observed. Locate the option ROM connector, labeled
CN41, on the lower-left side of the control PCB. Line up the connector on the
back of the option ROM PCB with CN41. Install the option ROM by pressing
gently but firmly on the option ROM PCB until a slight “click” is felt. Verify that the
option ROM PCB is seated properly and firmly in CN41. If the option ROM
connector does not appear to be mating with CN41 properly, verify that the ROM
is oriented properly and that there are no obstructions in either connector.
7. Install the 4 nylon standoffs into the holes provided in the control board support
bracket (refer to Figure 2).
8
Download from Www.Somanuals.com. All Manuals Search And Download.
standoff mounting holes
Figure 2: G3 with front cover and operation panel support bracket
removed
8. Install the Profibus network cable through the access holes at the bottom of the
inverter and route the cable in order to make connections to the interface board
connector (CN1). Take care to not route the cable near any sharp edges or in
positions where it may be pinched.
9. Connect the Profibus cable to the interface board connector (CN1). If a ground
cable is going to be used, attach the ground cable to the plated hole near CN1 on
the lower-right portion of the Profibus board (refer to section 3).
CAUTION! Extremely high voltages exist in the area near the Profibus
interface board and connector. Ensure that no stray wires come into contact with
any internal inverter components. Also ensure that the communications cable is
not routed in such a manner that it may come into contact with high-voltage
inverter components, or inverter components that may heat up during operation
and damage the cable insulation.
10. Install the interface board into the inverter by carefully aligning the 4 nylon
standoffs with the 4 mounting holes provided in the interface board. Ensure that
connector CN5A on the back side of the interface board is aligned with connector
CN5 on the front side of the control board.
11. Press the interface board firmly onto the standoffs and connector CN5 until the
standoff retaining tabs lock. Ensure that CN5 and CN5A are thoroughly
interlocked.
12. Carefully re-install the operation panel and support bracket and tighten the 4
screws that attach the operation panel support bracket to the control board
support bracket. Once installed, take a moment to verify that all interface board
and network components have sufficient clearance from other drive components.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
13. If a ground cable is being used, connect the ground cable to the selected ground
point.
14. Reinstall the inverter’s cover (close and latch the door on units with hinged
doors).
DANGER!
Do not operate the unit with the cover off / cabinet
door open.
15. Turn all power sources to the inverter unit ON, and verify that the inverter
functions properly. If the inverter unit does not appear to power up, or does not
function properly, immediately turn power OFF. Repeat steps 2 ∼ 4 to remove
all power from the inverter. Then, verify all connections. Contact Toshiba
International Corporation for assistance if the problem persists.
16. To perform final verification that the option ROM is installed properly, display the
value of the ROM VERSION parameter in GROUP:UTILITY PARAMETERS. This
number should match the option ROM version number that was recorded in step
1. If this parameter value does not match the option ROM version number
recorded in step 1, repeat steps 2 ∼ 4 to remove all power from the inverter,
then re-verify that the option ROM is installed properly. If the option ROM
appears to be installed properly, but the version numbers still do not match,
contact Toshiba International Corporation for further assistance.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3 Removal
Removal of the Profibus interface board from a TOSVERT-130 G3 inverter should
only be performed by a qualified technician familiar with the maintenance and
operation of the G3. In order to protect the interface board connector’s reliability, do
not repeatedly connect and disconnect the interface. Use the following procedure if it
becomes necessary to remove the Profibus interface board from the inverter.
CAUTION! Do not remove the interface board while power is applied to
the inverter. Removing the interface board with power applied may damage the
inverter.
2.3.1 Before Removal
The inverter will display an error message if the option ROM becomes dislodged or is
removed from its socket. The inverter must be reset to clear this error. Therefore, all
parameters will be automatically reset to the factory default values after an option
ROM has been removed from the inverter. If it is desired to retain the current
parameter settings, the user should access the user-changed parameter group to
display and record all the parameters and setting values that have been changed
from factory defaults. Even if the current settings are saved using the TYPE 5
RESET function, they will be erased from memory during the re-initialization of the
inverter after the option ROM has been removed.
2.3.2 Removal Procedure
1.
2.
CAUTION! Verify that all input power sources to the inverter have
been turned OFF and are locked and tagged out.
DANGER!
Wait at least 5 minutes for the inverter’s electrolytic
capacitors to discharge before proceeding to step 3. Do not touch any internal
parts with power applied to the inverter, or for at least 5 minutes after
power to the inverter has been removed. A hazard exists temporarily for
electrical shock even if the source power has been removed.
3.
Remove the inverter’s cover (open the door on units with hinged doors).
Verify that the CHARGE LED has gone out before continuing the removal
process.
4. Loosen the 4 screws attaching the operation panel support bracket to the control
board support bracket and remove the operation panel and support bracket as a
unit (refer to Figure 3).
Download from Www.Somanuals.com.1A1ll Manuals Search And Download.
operation panel
support bracket
operation panel support
bracket screws
Figure 3: G3 with front cover removed
5.
CAUTION! The option ROM PCB and Profibus interface board are
static-sensitive devices. Standard electrostatic-sensitive component handling
precautions should be observed. Release the 4 corners of the interface board
from the standoffs by pressing down on the standoff locking tabs with a small flat-
headed screwdriver. Be careful to not apply any abnormal stress to the interface
board while performing this, as this may damage the interface board or control
board connectors.
6. Remove the interface board from the inverter.
7. Disconnect the communications cable from the interface board connector (CN1),
and pull the cable out through the access holes at the bottom of the inverter.
8. Locate the option ROM in the option ROM connector, labeled CN41, on the
lower-left side of the control PCB. Gently work the option ROM PCB up and
down while pulling on it until the ROM releases from the control PCB option ROM
connector.
IMPORTANT NOTE: Do not remove the option ROM on inverter units that
were received from the factory with option ROMs pre-installed. Units that are
shipped from the factory with option ROMs pre-installed (H3 and 600V G3 units,
for example) require these ROMs for correct operation, and removal of the option
ROM may cause incorrect operation or inverter damage. If you are in doubt
about the requirement of an option ROM in your inverter unit, contact Toshiba
International Corporation for assistance.
9. Carefully re-install the operation panel and support bracket and tighten the 4
screws that attach the operation panel support bracket to the control board
support bracket.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Reinstall the inverter’s cover (close and latch the door on units with hinged
doors).
DANGER!
Do not operate unit with the cover off / cabinet
door open.
11. Turn all power sources to the inverter unit ON, and verify that the inverter
functions properly. If the inverter unit does not appear to power up, or does not
function properly, immediately turn power OFF. Repeat steps 1 ∼ 3 to remove
all power from the inverter. Then, verify all connections. Contact Toshiba
International Corporation for assistance if the problem persists.
12. To re-initialize the inverter after the ROM has been removed, perform a TYPE 3
reset. After the initialization sequence, display the value of the ROM VERSION
parameter in GROUP:UTILITY PARAMETERS. This number should match the
standard ROM version number that was recorded prior to option ROM installation.
If this parameter value does not match the value recorded earlier, contact
Toshiba International Corporation for further assistance.
Download from Www.Somanuals.com.1A3ll Manuals Search And Download.
3. Grounding
Grounding is of particular importance for reliable, stable operation. Communication
system characteristics may vary from system to system, depending on the system
environment and grounding method used. The Profibus interface card is provided
with a plated SHIELD connection point by CN1, on the lower right-hand side of the
board. This SHIELD connection point is directly connected to the metallic housing of
the DB9 connector, which should then be connected to the shield of the Profibus
network cable through the Profibus connector. To ground the network cable shield,
therefore, connect a wire with lug terminal to this SHIELD point, and then connect the
other end of the wire to an appropriate ground. For specific details and requirements
regarding protective grounding and the Profibus network, refer to the Profibus
Standard (DIN 19245, part 1).
Please be sure to consider the following points for making proper ground
connections:
Grounding method checkpoints
1. Make all ground connections such that no ground current flows through the
inverter case.
2. Ensure that all grounds are connected to points that are at the same potential as
inverter grounds.
3. Do not connect the Profibus interface board's SHIELD connection point to a
power ground or any other potential noise-producing ground connection (such as
the inverter's E/GND terminal).
4. Do not make connections to unstable grounds (paint-coated screw heads,
grounds that are subjected to inductive noise, etc.)
4. Equipment Specifications
Item
Specification
Indoors, less than 1000m above sea level, do not
expose to direct sunlight or corrosive / explosive gasses.
Operating Environment
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
-10 ∼ +40°C (+14 ∼ +104°F)
-25°C ∼ +65°C (-13 ∼ +149°F)
20% ∼ 90% (without condensation)
5.9m/s2 {0.6G} or less (10 ∼ 55Hz)
According to DIN 19245, part 1
Self-cooled
Grounding
Cooling Method
14
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Maintenance And Inspection
Preventive maintenance and inspection is required to maintain the Profibus
communication interface in its optimal condition, and to ensure a long operational
lifetime. Depending on usage and operating conditions, perform a periodic
inspection once every three to six months. Before starting inspections, always turn
off all power supplies to the inverter unit, and wait at least five minutes after the
inverter’s “CHARGE” lamp has gone out.
DANGER!
Do not touch any internal parts with power applied
to the inverter, or for at least 5 minutes after power to the inverter has been
removed. A hazard exists temporarily for electrical shock even if the source
power has been removed.
Inspection Points
•= Check that the network connector screws are not loose. Tighten if necessary.
•= Check that there are no defects in any attached grounding wire terminal crimp
points. Visually check that the crimp points are not scarred by overheating.
•= Visually check the wiring and cables for damage.
•= Clean off any accumulated dust and dirt. Place special emphasis on cleaning the
ventilation ports of the inverter and all installed PCBs. Always keep these areas
clean, as adherence of dust and dirt can cause premature component failure.
•= If use of the inverter unit is discontinued for extended periods of time, turn the
power on at least once every two years and confirm that the unit still functions
properly.
•= Do not perform hi-pot tests on the inverter or Profibus interface board, as they
may damage the unit’s internal components.
Please pay close attention to all periodic inspection points and maintain a good
operating environment.
Download from Www.Somanuals.com.1A5ll Manuals Search And Download.
6. Storage And Warranty
6.1 Storage
Observe the following points when the Profibus interface board is not used
immediately after purchase or when it is not used for an extended period of time.
•= Avoid storing the interface board in places that are hot or humid, or that contain
large quantities of dust or metallic dust. Store the interface board in a well-
ventilated location.
•= When not using the Profibus interface board for an extended period of time, turn
the power on at least once every two years and confirm that it still functions
properly.
6.2 Warranty
The Profibus communications interface kit is covered under warranty for a period of
12 months from the date of installation, but not to exceed 18 months from the date of
shipment from the factory. For further warranty or service information, please contact
Toshiba International Corporation.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
7. G3 Parameter Settings
Profibus interface board communications are enabled by setting parameter
COMMUNICATION SELECTION in GROUP:COMMUNICATION SETTING PARAMETERS
to 2 (Profibus, Modbus, DeviceNet). None of the Tosline-F10 communication
parameter settings apply when using the Profibus interface. For more information on
methods for changing parameter settings, refer to the TOSHIBA G3 Operation
Manual.
The following is a list of the parameter settings that are required during setup to
enable Profibus communications:
Parameter
BLIND FUNCTION
SELECTION
Group
GROUP:UTILITY
PARAMETERS
Required Value
1
COMMUNICATIONS PARMS GROUP:UTILITY
1
2
BLIND
PARAMETERS
COMMUNICATION
GROUP:COMMUNICATION
SETTING PARAMETERS
GROUP:COMMUNICATION
SETTING PARAMETERS
SELECTION
INVERTER ID NUMBER
any value other than
126 ∼ 255.
Note: Although the INVERTER ID NUMBER parameter can be set from 0 to 255,
the allowable Profibus slave addresses range only from 0 to 125. Therefore,
if this parameter is set to a value from 126 to 255, the Profibus interface card
will trip “OPTION PCB ERROR” upon initialization. To correct this error, set
the INVERTER ID NUMBER parameter to a value from 0 to 125.
To implement any parameter changes in GROUP:COMMUNICATION SETTING
PARAMETERS, the drive must be reset after making the changes.
If the drive into which a Profibus communications interface board is installed trips
“OPTION PCB ERROR” for any reason during initialization or operation (for example,
if it becomes loose from its mounting connections), it is incapable of being reset via
the Profibus network. When this trip condition occurs, therefore, the drive can only
be reset locally via the panel or control terminal block.
If drive control (frequency command input, RUN/STOP, etc.) is to be performed via
the Profibus network, the following inverter parameters must also be set as shown:
Parameter
Group
Required
Value
COMMAND MODE SELECTION
FREQUENCY MODE SELECTION GROUP:UTILITY PARAMETERS
GROUP:UTILITY PARAMETERS
3
3
Of course, input data can always be monitored from the network regardless of the
settings of COMMAND MODE SELECTION and FREQUENCY MODE SELECTION. Also
note that if the COMMAND MODE SELECTION or FREQUENCY MODE SELECTION
parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.
Download from Www.Somanuals.com.1A7ll Manuals Search And Download.
8. Feature Summary
The Toshiba Profibus-DP interface provides a wide array of network data access and
drive control features. Combined with the flexible configuration and high-speed data
transfer capabilities of the Profibus network, this allows powerful networked control
and monitoring systems to be designed. Some of the main features provided in the
G3 Profibus-DP interface which allow for this control and configurability are briefly
described here:
Protocol
Profibus DP (Decentralized Periphery). The interface can also co-exist
simultaneously on networks using Profibus-FMS.
Network Baud Rates
Supports all Profibus baud rates from 9.6kbaud to 12Mbaud. The network baud rate
is automatically detected and continuously monitored during operation; no parameter
settings are necessary.
Global Control Functions
•= Freeze mode: Input (monitor) data values are held constant at the drive until the
next “freeze” command or an “unfreeze” command is received.
Used primarily for synchronized monitoring of multiple Profibus
nodes.
•= Sync mode:
Output (control) data values are held constant at the drive until the
next “sync” command or an “unsync” command is received. Used
primarily for synchronized control of multiple Profibus nodes.
•= Clear_Data:
All output (control) data values are cleared to “0”.
Address Change Functions
Set_slave_address function supported – allows modification of the drive’s INVERTER
ID NUMBER parameter. The INVERTER ID NUMBER parameter can also be
changed while in the DATA_EXCHANGE state by accessing parameter register 204
(hex). Refer to sections 10 and 11 of this document for more information on
accessing parameter registers.
Network Watchdog
A network watchdog function is always operating within the interface – in the event of
a disconnection from the network or loss of the network master, the interface will
automatically stop the drive for safety (note that either the COMMAND MODE
SELECTION or FREQUENCY MODE SELECTION parameter must be set to 3 (network
control) in order for the drive to stop when a watchdog time-out occurs).
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Indicators
1 green LED is provided to indicate when the interface has achieved the
DATA_EXCHANGE state with the network master. This serves as a convenient
indicator that the master and drive are configured properly and are exchanging data.
Isolation
The network interface portion of the Profibus-DP board is fully optically-isolated for
optimal noise-immunity characteristics.
Network Connector
The network interface is a standard DB9 connector with the following signals
provided:
Pin Number
Function
In/Out
3
4
Profibus network “B” (positive) data line
In/out
Out
RTS signal – direction control for fiber optic network
interface
5
6
DGND – power supply ground internally connected to the
interface board’s isolated ground
-
-
VP – power supply +5v internally connected to the
interface board’s isolated P5.
8
Profibus network “A” (negative) data line
No connection
In/out
-
1, 2, 7, 9
In addition to the above signals, the metallic housing of the DB9 connector is
connected to the shield section of the interface board. The shield section contains a
plated connection point where a ground wire can be attached to connect the network
cable shield to ground. Refer to section 3 of this document for more information
related to grounding.
Input/Output Data
The interface’s cyclic data sizes are fixed at 8 bytes of output (control) data
configured as 4 words, and 16 bytes of input (status) data configured as 7 words and
2 bytes. For detailed explanations of the format and usage of this data, refer to
sections 9 and 10 of this document.
Download from Www.Somanuals.com.1A9ll Manuals Search And Download.
9. Exchanged Data Structures
9.1 Output (Control) Data Format
The output data structure from the network master to the G3 Profibus interface card
is comprised of 8 bytes structured as 4 words:
Offset
Data
Explanation
Command word
high byte
0
Bit-level drive control command word (refer to
Table 1 : Command Word Format)
Command word
low byte
1
Frequency
command high byte
2
3
Drive’s frequency command
Frequency
command low byte
Parameter number
/ action high byte
4
5
Parameter action bits and upper 4 bits of the
parameter register number. Refer to section 10
Parameter number for a detailed explanation of this data word
low byte
Parameter data to
6
7
During parameter register writes, this word
write high byte
contains the data to write. Refer to section 10
Parameter data to for a detailed explanation of this data word
write low byte
The data contained in the frequency command word must be the desired frequency
command multiplied by 100, and then converted to hexadecimal. In other words, if a
frequency command of 55.34Hz is desired, then 55.34 x 100 = 5534, which
converted to hexadecimal is 0x159E. The frequency command high byte (offset 2)
must therefore contain 0x15, and the frequency command low byte (offset 3) must
contain 0x9E.
In this way, the G3’s allowable frequency command range of 0.00Hz ∼ 400.00Hz
equates to network values of 0x0000 ∼ 0x9C40.
Regardless of the frequency command value sent via the Profibus network to the
drive, the actual operating frequency of the drive will still be limited locally by the
LOWER LIMIT FREQUENCY, UPPER LIMIT FREQUENCY, and MAXIMUM OUTPUT
FREQUENCY parameter settings.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 : Command Word Format
Function
Bit
Setting
0
RUN command
0: Stop
1: Run
1
2
3
STOP Command (has priority
over RUN command)
0: run enabled
1: stop
Forward / reverse run
selection
0: reverse
1: forward
0: Acc / dec #1
1: Acc / dec #2
Acc/dec #1 / #2 selection
4
5
6
7
Reserved
Value is ignored
Reserved
Reserved
Jog mode selection
0: Normal (acc/dec mode)
1: Jog mode
8
9
Feedback control
0: Feedback valid
1: Feedback invalid
Compulsory DC injection
braking mode
0:No compulsory DC injection braking
1:Compulsory DC injection below DC
INJECTION START FREQUENCY
A
B
C
D
Fundamental parameter
switching
0: V/F #1
1: V/F #2
Gate block (coast stop)
command
0: Normal
1: Gate block
0: Does nothing
1: Emergency off
0: Does nothing
1: Reset when tripped
Emergency off command
Reset command (trip clear)
E
F
Reserved
Reserved
Value is ignored
Download from Www.Somanuals.com.2A1ll Manuals Search And Download.
9.2 Input (Status) Data Format
The input data structure from the G3 Profibus interface card to the network master is
comprised of 16 bytes structured as 7 words and 2 independent bytes:
Offset
Data
Explanation
Status word
high byte
0
Bit-level drive status word (refer to Table 2 :
Status Word Format)
Status word
low byte
1
Output frequency
high byte
2
3
Drive’s current operating frequency
Output frequency
low byte
IV input terminal
value high byte
4
5
Continuously reports the value of the drive’s IV
analog input terminal. 0 ∼ 100% terminal input
corresponds to data values of 0x0000 ∼ 0xFFFF
IV input terminal
value low byte
RR input terminal
value high byte
6
7
Continuously reports the value of the drive’s RR
analog input terminal. 0 ∼ 100% terminal input
corresponds to data values of 0x0000 ∼ 0xFFFF
RR input terminal
value low byte
Input terminal
monitor high byte
8
9
Bit-level status word of drive’s digital input
terminals (refer to Table 3 : Input Terminal
Monitor Word Format)
Input terminal
monitor low byte
Drive output
current monitor
0x00 ∼ 0xFF corresponds to 0 ∼ 255% drive
10
11
rated load current
Drive output
voltage monitor
0x00 ∼ 0xFF corresponds to 0 ∼ 255% drive
rated output voltage
Parameter number
/ action high byte
12
13
Parameter action bits and upper 4 bits of the
parameter register number. Refer to section 10
Parameter number for a detailed explanation of this data word
low byte
Parameter data
response high byte
During parameter register reads, this word
contains the requested data response. Refer to
section 10 for a detailed explanation of this data
word
14
15
Parameter data
response low byte
22
Download from Www.Somanuals.com. All Manuals Search And Download.
In order to determine the drive’s actual output frequency, the data contained in the
output frequency word (offsets 2 and 3) must first be converted from hexadecimal to
decimal, and then divided by 100. For example, if the output frequency high byte is
0x12 and the output frequency low byte is 0x34, then 0x1234 converted to decimal is
4660. Dividing this number by 100, the actual operating frequency of 46.60Hz is
obtained.
In this way, network data values of 0x0000 ∼ 0x9C40 correspond to the G3’s actual
allowable output frequency range of 0.00Hz ∼ 400.00Hz.
Table 2 : Status Word Format
Bit
Function
Run / stop status
Value
0
0: Stopped
1: Running
0: Run enabled
1: Stopped
0: Reverse
1: Forward
1
2
3
Run enable status
Forward / reverse status
Accel / decel #1 / #2 selection 0: Accel / decel #1
status
1: Accel / decel #2
Always “0”
4
5
Reserved
Fault status
0: Faulted
1: Not Faulted
6
7
Reserved
Always “0”
Jog mode status
0: Normal (accel/decel mode)
1: Jog mode
8
9
Feedback enable status
0: Feedback invalid
1: Feedback valid
0: DC injection braking inactive
1: DC injection braking active
0: V/F #1
Compulsory DC injection
braking mode
A
B
C
Fundamental parameter
switching
1: V/F #2
Coast stop command status
0: Normal
1: Coast to stop
0: Normal
Emergency off command
1: Emergency off
Always “0”
0: Normal
D
E
Reserved
Main Circuit Undervoltage
1: Undervoltage
F
Reserved
Always “0”
Download from Www.Somanuals.com.2A3ll Manuals Search And Download.
Table 3 : Input Terminal Monitor Word Format
Bit
Terminal
Value
0
F
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
1
2
3
4
5
6
7
R
S1
S2
S3
S4
S5 (option)
S6 (option)
8
9
Reserved
Reserved
Reserved
Reserved
Reserved
S7 (option)
Always 0
A
B
C
D
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
0: Terminal – CC open
1: Terminal – CC shorted
E
F
RES
ST
9.3 Diagnostics
When the drive trips, 1 byte of high-priority user diagnostics is supplied to the master.
The value of the diagnostics byte is the drive’s fault code. Refer to section 11.3 for a
list of drive fault codes.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Parameter Register Access
10.1 Parameter Number / Action Output Words
To access inverter parameters, 2 output words are provided in the output data
structure. The structure of these 2 output words is as follows:
Parameter number / action word
15
14
13
12 11
8
7
4
3
0
Bit #:
Parameter number (12 bits)
Parameter number / action
high byte (offset 4)
Parameter number
low byte (offset 5)
Parameter data write word
15
12 11
8
7
4
3
0
Bit #:
Parameter data (16 bits)
Parameter data to write
high byte (offset 6)
Parameter data to write
low byte (offset 7)
Download from Www.Somanuals.com.2A5ll Manuals Search And Download.
10.2 Parameter Number / Action Input Words
The response by the G3 interface card to parameter read and write requests is
placed in 2 input words of the input data structure. The structure of these 2 input
words is as follows:
Parameter number / action response word
15
14
13
12 11
8
7
4
3
0
Bit #:
Parameter number (12 bits)
0
0
Parameter number / action
response high byte (offset 12)
Parameter number
response low byte (offset 13)
Parameter data / error code response word
15
12 11
8
7
4
3
0
Bit #:
Parameter data / error code (16 bits)
Parameter data response
high byte (offset 14)
Parameter data response
low byte (offset 15)
26
Download from Www.Somanuals.com. All Manuals Search And Download.
10.3 Parameter Access Procedure
In order to read from a parameter or write to a parameter, 2 control bits are provided.
These bits, labeled Req1 and Req0 in the Parameter number / action word, can have
the following values:
Req1
Req0
Meaning
0
0
1
1
0........... No action (idle state)
1........... Parameter read
0........... Parameter write
1........... Reserved: do not use
Similarly, when the drive responds to a parameter read or write request, 2 status bits
are provided. These bits, labeled Resp1 and Resp0 in the Parameter number /
action response word, can have the following values:
Resp1 Resp0
Meaning
0
0
1
1
0........... No action (idle state acknowledge)
1........... Parameter read success acknowledge
0........... Parameter write success acknowledge
1........... Error indication
Performing a parameter read or write action from the Profibus master involves the
following process:
1. Send a “no action” code (Req1=0 and Req0=0). Every parameter access must
begin from the idle state. Once this state is sent, the Profibus master must then
wait for the G3 Profibus interface card to respond with an idle state acknowledge
(Resp1=0 and Resp0=0).
2. If the action is to be a data write, set the parameter data in the parameter data
write word. If the action is to be a data read, the parameter data write word value
is irrelevant.
3. Set the parameter register number (12 bits) and action code (Req1 and Req0).
For a list of parameter register numbers, refer to section 11.
4. Once the G3 Profibus interface receives the read or write request, it will begin
processing it. Typically, the drive will require from 20ms to 40ms to complete
each parameter access request (read or write).
5. Once the drive has completed the request, it will place its response in the
parameter number / action response word and data / error code response word:
•= If the request was a read, and the read was performed successfully, this will
be indicated to the master by Resp1:Resp0 changing from 0:0 to 0:1. The
parameter number response (12 bits) will equal the accessed parameter
number, and the resulting data read will be placed in the data / error code
response word.
•= If the request was a write, and the write was performed successfully, this will
be indicated to the master by Resp1:Resp0 changing from 0:0 to 1:0. The
parameter number response (12 bits) will equal the accessed parameter
number, and the data written to the drive will be reflected in the data / error
code response word.
Download from Www.Somanuals.com.2A7ll Manuals Search And Download.
•= If an error occurred during the read or write request, this will be indicated to
the master by Resp1:Resp0 changing from 0:0 to 1:1. The parameter
number response (12 bits) will equal the parameter number that the master
was attempting to access, and an error code reflecting the failure cause will
be placed in the data / error code response word. For a list of possible error
codes, refer to section 10.4.
6. In order to perform another parameter read or write, the master must once again
send a “no action” code (Req1=0 and Req0=0), and the drive must once again
respond with an idle state acknowledge (Resp1=0 and Resp0=0) before the next
read or write action can take place. Until a “no action” code is sent to the drive,
the drive will ignore all data in the Parameter number / action word and
Parameter write data word. Also, as long as the master sends the “no action”
code, the drive will loop-back in the parameter number / action response word
and parameter data / error code response word whatever data is sent to it in the
corresponding output words.
10.4 Register Access Error Codes
When a parameter read or write error occurs, one of the following error codes will be
returned in the Parameter data response word (offsets 14 and 15 of the input data
structure):
Error Code
Meaning
0x0001................ cannot execute
0x0002................ data error (written data value outside of valid range)
0x0003................ invalid register
0x0004................ attempt to write to a read-only register
0x0005................ attempt to read from a write-only register
0x0006................ other / unclassified error
28
Download from Www.Somanuals.com. All Manuals Search And Download.
11. Parameter Registers
How To Use This Section:
This section contains tables which describe all of the parameter registers accessible
from the Profibus network. The descriptions for the columns in the listed tables are
as follows:
Register ............The register number used to access the parameter.
Bit .....................This column only applies to read-only registers (section 11.1). If the
register is comprised of a collection of individual bit-oriented status
items (for example, register 0D), this column will indicate which bit(s)
in the word-sized register the corresponding parameter described in
the Function column uses (bit 0 = LSB, bit F = MSB). If the
parameter uses the whole register, "word" will appear in this column,
indicating the parameter consumes the entire register (this does not
mean, however, that all register bits are used: refer to the
explanation for Mask below). All read/write registers (section 11.2)
have word-size data. Other possible values in this column are "low
byte" (bits 0 ∼ 7) and "high byte" (bits 8 ∼ F).
Function............Describes the function accessed through this parameter register.
Bank .................0 = RAM (volatile), 1 = EEPROM (nonvolatile), 0/1 = RAM &
EEPROM, 2, 3 and 6 = code space (read-only). IMPORTANT: the
inverter’s EEPROM has a life span of 10,000 write cycles. Do not
write to a read/write holding register whose bank is listed as 1 or 0/1
more than 10,000 times.
Mask.................The data bits within a register that are not covered by the
hexadecimal mask (for example, bits 8 ∼ F if the mask is 00FF) will
always be returned as 0 during data reads and will be ignored during
data writes. For example, if a hexadecimal value of AB98 is sent to
a register whose mask is 00FF, the actual value written to the
register's corresponding parameter will be 0098. As this is not
considered an error, no exception response will be generated if this
type of extraneous data condition occurs.
Adjustment Range ...Indicates valid data settings in real terms (Hz, ON/OFF, etc.)
Multiplier ...........Indicates scaling factor used to convert Adjustment Range data into
integer values. The equation used for this conversion is:
Actual Holding Register Data = Real Data ÷ Multiplier
For example, if 60.00Hz MAXIMUM OUTPUT FREQUENCY were
desired, register 26 must be set to [60.00 ÷ 0.01] = 6000 decimal (=
1770 hex).
Download from Www.Somanuals.com.2A9ll Manuals Search And Download.
Example Table Excerpt:
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
MAXIMUM OUTPUT
FREQUENCY
26
0 / 1
FFFF
0.01
0BB8 ∼ 9C40 (30.00∼400.00)
(∗)
BASE FREQUENCY #1
27
28
0 / 1
0 / 1
FFFF
0030
0.01
1
09C4 ∼ 9C40 (25.00∼400.00)
0000: Input voltage level
0020: Automatic setting
0030: Stationary setting
BASE FREQUENCY
VOLTAGE SELECT
(0)
(1)
(2)
(∗)
MAXIMUM OUTPUT
VOLTAGE #1
29
0 / 1
0 / 1
FFFF
0020
0000 ∼ 0258 (0 ∼ 600)
REVERSE OPERATION
DISABLE SELECT
2A
0000: Reverse allowed
(0)
(1)
0020: Reverse not allowed
Other Programming Register Notes:
•= All register numbers indicated are in hexadecimal notation (for example, 29 hex =
41 decimal). Occasionally, hexadecimal notation in this document may also take
the form of a number beginning with “0x”.
•= Throughout this document, the abbreviations "LL", "UL", and "Fmax" will stand for
LOWER LIMIT FREQUENCY, UPPER LIMIT FREQUENCY, and MAXIMUM
OUTPUT FREQUENCY, respectively.
•= Reading from or writing to registers marked as "Reserved" will generate an
“invalid register” error (error code 0x0003)
•= Certain parameter registers cannot be written to while the inverter is running.
These registers will be indicated by the character (∗). If an attempt is made to
write to these registers while the inverter is running, a “cannot execute” error
(error code 0x0001) will be generated.
•= The parameter register data for all read/write registers with Bank information
listed as 0/1 will be retrieved from bank 0 (RAM) during reads and will be written
to both banks 0 and 1 (RAM and EEPROM) during writes.
•= All parameters in GROUP:COMMUNICATION SETTING PARAMETERS (section
11.2.10) are retrieved by the drive from non-volatile memory upon inverter
initialization only. When any of these registers are modified, therefore, the drive
must be reset for the changed values to take effect.
•= If the COMMAND MODE SELECTION or FREQUENCY MODE SELECTION
parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
11.1 Read-Only Registers
Register
Bit
Function
Bank
Mask
Adjustment Range
Multiplier
word Reserved
01 ∼ 09
0A
word RX terminal analog input
value
0
0
FFFF
FFFF
0000 ~ 7FFF (-100% ~ 0%)
7FFF ~ FFFF (0% ~ 100%)
1
0B
word Frequency command
monitor
0.01
0.1
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz)
0 ~ 255%
0C
0D
word Input voltage monitor(Note 1)
0
0
FFFF
00FF
word Output terminal status
monitor
Refer to Table 4 (page 32)
0E
0F
10
11
word Inverter Status 1
word Inverter Status 2
word Present trip
0
0
0
0
FFFF
00FF
00FF
7F00
Refer to Table 5 (page 32)
Refer to Table 6 (page 32)
high
byte
4th Past trip (most recent)
low
byte
3rd past trip
007F
7F00
007F
FFFF
FFFF
Refer to section 11.3 for fault
codes
12
high
byte
2nd past trip
0
low
byte
1st past trip (oldest)
13
14
word Pre-compensation output
frequency
0
0
0.01
0.01
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz)
0000 ∼ 9C40
(0.00 ∼ 400.00 Hz)
word Post-compensation output
frequency
15
16
word Torque current monitor
word Excitation current monitor
word PID feedback value
word Motor overload ratio
word Inverter overload ratio
word DBR overload ratio
word Input power (%)
0
0
0
0
0
0
0
0
0
0
FFFF
00FF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
(Note 2)
0.01
1
00 ∼ FF (0 ~ 255%)
(Note 2)
17
0.02
18
0 ~ 65535
0 ~ 65535
0 ~ 65535
0 ~ 6553.5
(Note 3)
100/65535
100/65535
100/65535
0.1
19
1A
1B
1C
1D
1E
word Input power (kW)
word Output power (%)
word Output power (kW)
word Reserved
(Note 2)
0.1
(Note 2, Note 3)
1F, 20
21
word Input / output power units
0
0
0008
0003
0000: 0.01kW
0008: 0.1kW
0000: terminal
0001: panel
22
word Command mode status
0002: option
0003: RS232C
0000: terminal
0004: panel
23
word Frequency mode selection
status
0
000C
0008: option
000C: RS232C
24
25
low
byte
Profibus interface card
software revision
high
byte
Profibus interface card
software version
word Output current (amps)
FFFF
0.0 ~ 6553.5 A
0.1
(Note 1)
These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2)
These registers use signed data (data values larger than 7FFFH are negative). If the register data is
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (register data) + 1].
Download from Www.Somanuals.com.3A1ll Manuals Search And Download.
(Note 3)
If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.
Table 4: Output Terminal Status Monitor (register 0D)
Lower
Byte
Bit
Output Terminal
0
1
Single-Bit
Read Mask
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
unused (always 0)
unused (always 0)
FAN
OFF
ON
0004
0008
0010
0020
0040
0080
FL
FLB-FLC shorted
OFF
FLA-FLC shorted
ON
MS relay
OUT (option)
RCH
OUTB-OUTC shorted
RCHA-RCHC open
LOWA-LOWC open
OUTA-OUTC shorted
RCHA-RCHC shorted
LOWA-LOWC shorted
LOW
Table 5: Inverter Status 1 (register 0E)
Lower
Byte
Bit
Inverter Status
0
1
Single-Bit
Read Mask
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
running (acc/dec)
unused (always 0)
forward / reverse
acc/dec #1/#2
running
0001
reverse
forward
0004
0008
acc/dec #1
acc/dec #2
for inverter use
for inverter use
for inverter use
jog/normal mode
normal (acc/dec)
jog mode
0080
Upper
Byte
Bit
Inverter Status
0
1
Single-Bit
Read Mask
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
feedback ON/OFF
DC inj. braking
V/F #1/#2
OFF
OFF
feedback active
DC inj. braking active
V/F #2
0001
0002
0004
0008
0010
V/F #1
coasting
not coasting
not in emergency off
coasting
emergency off
for inverter use
for inverter use
for inverter use
in emergency off
Table 6 : Inverter Status 2 (register 0F)
Upper
Byte
Bit
Inverter Status
0
1
Single-Bit
Read Mask
bit 0
bit 1
bit 2
bit 3
bit 4
accelerating
decelerating
for inverter use
retry
not accelerating
not decelerating
accelerating
decelerating
0001
0002
not retrying
stopped
retrying
running
0008
0010
running (including DC
injection braking)
bit 5
bit 6
bit 7
for inverter use
for inverter use
tripped
not tripped
tripped
0080
32
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2 Read/Write Registers
11.2.1 GROUP:FUNDAMENTAL PARAMETERS #1
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
MAXIMUM OUTPUT
FREQUENCY
26
0 / 1
FFFF
0.01
0BB8 ∼ 9C40 (30.00∼400.00)
(∗)
BASE FREQUENCY #1
27
28
0 / 1
0 / 1
FFFF
0030
0.01
1
09C4 ∼ 9C40 (25.00∼400.00)
0000: Input voltage level
0020: Automatic setting
0030: Stationary setting
BASE FREQUENCY
VOLTAGE SELECT
(0)
(1)
(2)
(∗)
MAXIMUM OUTPUT
VOLTAGE #1
29
0 / 1
0 / 1
FFFF
0020
0000 ∼ 0258 (0 ∼ 600)
REVERSE OPERATION
DISABLE SELECT
2A
0000: Reverse allowed
0020: Reverse not allowed
0000 ~ Fmax
(0)
(1)
UPPER LIMIT FREQUENCY
LOWER LIMIT FREQUENCY
VOLTS PER HERTZ
2B
2C
2D
0 / 1
0 / 1
0 / 1
FFFF
FFFF
000F
0.01
0.01
0000 ∼ UL, Fmax
0000: Constant torque
0001: Variable torque
0002: Auto. torque boost
(1)
(2)
(3)
PATTERN
(∗)
0006: #3 w/ auto. energy savings (4)
000A: Vector control (5)
000E: #5 w/ auto. energy savings (6)
VOLTAGE BOOST #1
2E
2F
1, 2
0 / 1
0 / 1
FFFF
FFFF
0.1
0000 ∼ 012C (0.0 ∼ 30.0)
ACCELERATION TIME #1
0.01
0.1
0001 ∼ EA60 (0.01~ 600.00)
0001 ∼ EA60 (0.1~ 6000.0)
0001 ∼ EA60 (0.01~ 600.00)
0001 ∼ EA60 (0.1~ 6000.0)
DECELERATION TIME #1
30
31
0 / 1
0 / 1
FFFF
0030
0.01
0.1
ACC/DEC PATTERN #1
SELECTION
0000: Linear
(0)
(1)
(2)
(3)
0010: Self-adjusting
0020: S-Pattern #1
0030: S-Pattern #2
ACCEL/DECEL PATTERN
ADJUST LOW
32
33
0 / 1
0 / 1
00FF
00FF
1
1
0003 ~ 00FD (0 ∼ 50)
(Note 1)
ACCEL/DECEL PATTERN
ADJUST HIGH
0003 ~ 00FD (0 ∼ 50)
(Note 1)
Note 1: Register data = (desired setting x 5 + 3), converted to hexadecimal
Download from Www.Somanuals.com.3A3ll Manuals Search And Download.
11.2.2 GROUP:FUNDAMENTAL PARAMETERS #2
Register
Function / Title
Bank
0 / 1
0 / 1
Mask
FFFF
FFFF
Adjustment Range
Multiplier
BASE FREQUENCY #2
34
35
0.01
1
09C4 ∼ 9C40 (25.00 ∼ 400.00)
MAXIMUM OUTPUT
VOLTAGE #2
0000 ∼ 0258 (0 ∼ 600)
VOLTAGE BOOST #2
36
37
0 / 1
0 / 1
FFFF
00FF
0.1
1
0000 ∼ 012C (0.0 ∼ 30.0)
ELECTRONIC THERMAL
PROTECT LVL #2
000A ∼ 0064 (10 ∼ 100)
STALL PROTECTION
SELECTION #2
38
0 / 1
0040
0000: ON
(0)
(1)
0040: OFF
STALL PROTECTION
LEVEL #2
39
0
0 / 1
0 / 1
00FF
FFFF
1
000A ∼ 00D7 (10 ∼ 215)
ACCELERATION TIME #2
3A
0.1
0001 ∼ EA60 (0.1~ 6000.0)
0.01
0001 ∼ EA60 (0.01~ 600.00)
DECELERATION TIME #2
3B
3C
0 / 1
0 / 1
FFFF
0030
0.1
0001 ∼ EA60 (0.1~ 6000.0)
0001 ∼ EA60 (0.01~ 600.00)
0000: Linear
0.01
ACC/DEC PATTERN #2
SELECTION
(0)
0010: Self-adjusting
0020: S-Pattern #1
(1)
(2)
(3)
0030: S-Pattern #2
ACC/DEC #1/#2 SWITCH
FREQUENCY
3D
0 / 1
FFFF
0.01
0000 ∼ Fmax
11.2.3 GROUP:PANEL CONTROL PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
0000: Reverse
Multiplier
DIRECTION SELECTION
(FORWARD/REV)
3E
0 / 1
0004
(0)
0004: Forward
(1)
(0)
(1)
(1)
(2)
(1)
(2)
(0)
(1)
(2)
(0)
(1)
STOP PATTERN
SELECTION
3F
40
41
42
0 / 1
0 / 1
0 / 1
0 / 1
0040
0004
0008
0030
0000: Decelerated stop
0040: Coast stop
0000: V/F #1
FUNDAMENTAL PARAM
SWITCHING
0004: V/F #2
ACCEL/DECEL #1/#2
SELECTION
0000: Acc / dec #1
0008: Acc / dec #2
0000: All possible
0010: OL only
PANEL RESET SELECTION
0020: OL, OC only
0000: Feedback valid
0001: Feedback invalid
PANEL FEEDBACK
CONTROL
43
0 / 1
0001
34
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.4 GROUP:TERMINAL SELECTION PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
INPUT TERMINAL
SELECTION
44
0 / 1
0001
0000: Standard functions
0001: Individual selections
(0)
(1)
“R” INPUT TERMINAL
FUNCTION
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
1
0 / 1
FFFF
0000 ∼ FFFF (0 ∼ 54)
“S1” INPUT
TERMINAL FUNCTION
Refer to Table 7 (page 37)
“S2” INPUT
TERMINAL FUNCTION
“S3” INPUT
TERMINAL FUNCTION
“S4” INPUT
TERMINAL FUNCTION
“F” INPUT TERMINAL
FUNCTION
“RES” INPUT
TERMINAL FUNCTION
“ST” INPUT
TERMINAL FUNCTION
“S5” INPUT
TERMINAL FUNCTION
“S6” INPUT
TERMINAL FUNCTION
“S7” INPUT
TERMINAL FUNCTION
POTENTIAL TERMINAL
FUNCTION
R,S1-S7 TERMINAL
RESPONSE TIME
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
00FF
00FF
00FF
00FF
FFFF
1
1
1
1
0001 ∼ 0064 (1 ∼ 100)
0001 ∼ 0064 (1 ∼ 100)
0001 ∼ 0064 (1 ∼ 100)
0001 ∼ 0064 (1 ∼ 100)
F INPUT TERMINAL
RESPONSE TIME
RES INPUT TERMINAL
RESPONSE TIME
ST INPUT TERMINAL
RESPONSE TIME
“RCH” CONTACTS
FUNCTION
0 ∼ FFFF (0 ∼ 63)
Refer to Table 8 (page 38)
“RCH” CONTACTS DELAY
TIME
56
57
58
0 / 1
0 / 1
0 / 1
00FF
00FF
FFFF
1
1
0001 ∼ 0064 (1 ∼ 100)
“RCH” CONTACTS HOLD
TIME
0001 ∼ 0064 (1 ∼ 100)
“LOW” CONTACTS
FUNCTION
0 ∼ FFFF (0 ∼ 63)
Refer to Table 8 (page 38)
“LOW” CONTACTS DELAY
TIME
59
5A
5B
0 / 1
0 / 1
0 / 1
00FF
00FF
FFFF
1
1
0001 ∼ 0064 (1 ∼ 100)
“LOW” CONTACTS HOLD
TIME
0001 ∼ 0064 (1 ∼ 100)
“FL” CONTACTS
FUNCTION
0 ∼ FFFF (0 ∼ 63)
Refer to Table 8 (page 38)
“FL” CONTACTS DELAY
TIME
5C
5D
5E
0 / 1
0 / 1
0 / 1
00FF
00FF
FFFF
1
1
0001 ∼ 0064 (1 ∼ 100)
“FL” CONTACTS HOLD
TIME
0001 ∼ 0064 (1 ∼ 100)
“OUT” CONTACTS
FUNCTION
0 ∼ FFFF (0 ∼ 63)
Refer to Table 8 (page 38)
“OUT” CONTACTS DELAY
TIME
5F
0 / 1
00FF
1
0001 ∼ 0064 (1 ∼ 100)
Download from Www.Somanuals.com.3A5ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0001 ∼ 0064 (1 ∼ 100)
Multiplier
“OUT” CONTACTS HOLD
TIME
60
0 / 1
00FF
1
LOW SPEED SIGNAL
OUTPUT FREQ
61
62
63
64
65
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
FFFF
FFFF
FFFF
FFFF
00C0
0.01
0.01
0.01
0.01
0 ∼ Fmax
0 ∼ Fmax
0 ∼ Fmax
0 ∼ Fmax
ACC/DEC COMPLETE
DETECT BAND
SPEED REACH MAXIMUM
FREQUENCY
SPEED REACH MINIMUM
FREQUENCY
COMMERCIAL POWER/INV
SWITCHING OUTPUT
0000: OFF
(0)
(1)
0040: Auto switch on trip
0080: At COMMERCIAL POWER/INV
SWITCH FREQ
00C0: Both (1) and (2)
0 ∼ Fmax
(2)
(3)
COMMERCIAL
POWER/INV
66
67
2, 3
0 / 1
0 / 1
FFFF
0003
0.01
SWITCH FREQ
“FP” OUTPUT TERMINAL
PULSE FREQUENCY
0000: 48f
(0)
(1)
(2)
(0)
(1)
(2)
(3)
(4)
0001: 96f
0002: 360f
RR INPUT SPECIAL
FUNCTION SELECT
68
0 / 1
00E0
0000: Standard
0040: Fmax
0080: TACC/TDEC mult.
00C0: VB mult. Factor
0020: CL mult. Factor
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7: Input Terminal Selections
Setting
Value
Data
(Hex)
Function
Setting
Value
Data
(Hex)
Function
0
1
2
3
4
5
6
7
10C8
011C
021C
041C
081C
20C8
201B
C0C9
R
(reverse run)
28
29
30
31
32
33
34
35
04AF
08AF
10AF
20AF
40AF
04CE
01C7
02C7
Binary bit #6
Binary bit #7
Binary bit #8
Binary bit #9
SS1 (preset speed selection)
SS2 (preset speed selection)
SS3 (preset speed selection)
SS4 (preset speed selection)
Binary bit #10
F
(forward run)
No effect
RES (fault reset)
UP/DOWN frequency setting (UP)
ST (gate ON/OFF)
UP/DOWN frequency setting
(DOWN)
8
0CC8
081A
101B
021B
041B
JOG selection
36
37
38
39
40
04C7
08C7
10C7
02B9
C0C8
UP/DOWN frequency clear
PUSH-type RUN key
PUSH-type STOP key
No effect
9
Acc/dec #1/#2 selection
Emergency off
10
11
12
DC injection braking ON/OFF
Fundamental parameter
switching (V/F #2)
Forward/reverse run selection
13
14
15
16
17
18
19
20
21
22
23
011B
10CE
20CE
40CE
80CE
02CE
01CE
0AC9
06C9
10AE
20AE
Feedback control ON/OFF
Pattern run selection #1
Pattern run selection #2
Pattern run selection #3
Pattern run selection #4
Pattern run continue signal
Pattern run step trigger signal
JOG forward run
41
42
43
44
45
46
47
48
49
50
51
20C7
30C9
0198
0298
0498
0898
1098
2098
4098
8098
08CE
RUN
Binary data write
[LOCAL/REMOTE] key
[MON] key
[PRG] key
[UP] (▲) key
[DOWN] (▲) key
[READ/WRITE] key
[RUN] key
JOG reverse run
Binary bit #0
[STOP/CLEAR] key
Binary bit #1
Commercial power / inverter
switching signal
24
25
26
27
40AE
80AE
01AF
02AF
Binary bit #2
Binary bit #3
Binary bit #4
Binary bit #5
52
53
54
40C7
10CB
20CB
Reserved for option use
RR frequency switching input
IV frequency switching input
Note: In order for binary bit #0 ∼ #10 (setting values 22 ∼ 32) and UP/DOWN frequency setting (setting values 34 &
35) inputs to be valid, parameter FREQUENCY PRIORITY SELECTION #1 or FREQUENCY PRIORITY
SELECTION #2 in GROUP:FREQUENCY SETTING PARAMETERS must be set to 5 (BIN (binary setting or
UP/DOWN setting)).
Download from Www.Somanuals.com.3A7ll Manuals Search And Download.
Table 8: Output Terminal Selections (RCH, LOW, FL, OUT relay contacts)
Setting
Value
Data
(Hex)
Function
Setting
Value
Data
(Hex)
Function
0
1
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
0A00
Lower limit frequency
/Lower limit frequency
Upper limit frequency
/Upper limit frequency
Low speed signal
32
33
34
35
36
37
38
39
40
41
42
C5B7
CDB7
B5BB
BDBB
D5CF
DDCF
D5D8
DDD8
C5BB
CDBB
1400
Executing emergency off
/Executing emergency off
Executing retry
2
3
/Executing retry
4
Pattern run switching output
/Pattern run switching output
PID deviation limit
/PID deviation limit
Run/stop
5
/Low speed signal
6
Accel/decel complete
/Accel/decel complete
Selected speed reach signal
/Selected speed reach signal
Fault
7
8
9
/Run/stop
10
Severe fault (armature short, load-
end short, open phase, output
error, earth fault)
11
0B00
/Fault
43
1500
/Severe fault (armature short, load-
end short, open phase, output
error, earth fault)
12
13
14
15
16
17
0C00
0D00
95B5
9DB5
85C5
8DC5
Fault other than earth fault or
load-end overcurrent
44
45
46
47
48
49
1600
1700
Non-severe fault (overload,
overcurrent, overvoltage)
/Fault other than earth fault or
load-end overcurrent
/Non-severe fault (overload,
overcurrent, overvoltage)
Overcurrent pre-alarm
E5D8
EDD8
F5D8
FDD8
Commercial power / inverter
switching output #1
/Overcurrent pre-alarm
Inverter overload pre-alarm
/Inverter overload pre-alarm
/Commercial power / inverter
switching output #1
Commercial power / inverter
switching output #2
/Commercial power / inverter
switching output #2
18
19
20
21
22
23
24
25
26
27
28
29
30
31
95C5
9DC5
D5C5
DDC5
A5B4
ADB4
E5B4
EDB4
85B5
8DB5
85D1
8DD1
E5BB
EDBB
Motor overload pre-alarm
/Motor overload pre-alarm
Overheat pre-alarm
50
51
52
53
54
55
56
57
58
59
60
61
62
63
85C0
8DC0
F5B6
FDB6
1800
1900
A5D1
ADD1
1A00
1B00
A5B6
ADB6
1E00
1F00
Fan ON/OFF
/Fan ON/OFF
Executing JOG
/Overheat pre-alarm
/Executing JOG
Overvoltage pre-alarm
/Overvoltage pre-alarm
Undervoltage alarm
Local/remote operation
/Local/remote operation
Cumulative timer alarm
/Cumulative timer alarm
Communication error alarm
/Communication error alarm
F/R
/Undervoltage alarm
Undercurrent alarm
/Undercurrent alarm
Overtorque alarm
/Overtorque alarm
/F/R
Braking resistor OL pre-alarm
/Braking resistor OL pre-alarm
Run preparation complete
/Run preparation complete
38
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.5 GROUP:SPECIAL CONTROL PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
START-UP FREQUENCY
69
6A ∼ 6F
70
0 / 1
FFFF
0.01
0000 ∼ 03E8 (0.00 ∼ 10.00)
Reserved
END FREQUENCY
RUN FREQUENCY
0 / 1
0 / 1
0 / 1
FFFF
FFFF
FFFF
0.01
0.01
0.01
0000 ∼ 0BB8 (0.00 ∼ 30.00)
0000 ∼ Fmax
0000 ∼ 0BB8 (0.00 ∼ 30.00)
71
RUN FREQUENCY
HYSTERESIS
72
ENABLE JUMP
FREQUENCIES
73
0 / 1
0080
0000: Function OFF
0080: Function ON
(0)
(1)
JUMP FREQUENCY #1
74
75
1
0 / 1
0 / 1
FFFF
FFFF
0.01
0.01
0000 ∼ Fmax
0000 ∼ 0BB8 (0.00 ∼ 30.00)
JUMP FREQUENCY #1
BANDWIDTH
JUMP FREQUENCY #2
76
77
0 / 1
0 / 1
FFFF
FFFF
0.01
0.01
0000 ∼ Fmax
0000 ∼ 0BB8 (0.00 ∼ 30.00)
JUMP FREQUENCY #2
BANDWIDTH
JUMP FREQUENCY #3
78
79
0 / 1
0 / 1
FFFF
FFFF
0.01
0.01
0000 ∼ Fmax
0000 ∼ 0BB8 (0.00 ∼ 30.00)
JUMP FREQUENCY #3
BANDWIDTH
Reserved
7A ∼ 7F
PWM CARRIER FREQUENCY
80
0 / 1
00FF
0.1
0005 ∼ 0064 (0.5 ∼ 10.0)
(Note 1)
Note 1: Actual adjustment range depends on inverter rating.
Download from Www.Somanuals.com.3A9ll Manuals Search And Download.
11.2.6 GROUP:FREQUENCY SETTING PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
0001: RR
Multiplier
FREQUENCY PRIORITY
SELECTION #1
81
0 / 1
0007
(1)
(2)
(3)
(4)
(5)
(1)
(2)
(3)
(4)
(5)
(0)
(1)
(2)
(3)
(0)
(1)
0002: IV
0003: RX
0004: PG
0005: BIN
FREQUENCY PRIORITY
SELECTION #2
82
0 / 1
0038
0008: RR
0010: IV
0018: RX
0020: PG
0028: BIN
ANALOG INPUT FILTER
83
84
0 / 1
0 / 1
0003
0002
0000: No filter
0001: Small filter
0002: Medium filter
0003: Large filter
0000: Standard
0002: Adjustable
RR TERMINAL STANDARD
OR ADJUSTABLE
RR REFERENCE
85
86
87
88
89
1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
00FF
FFFF
00FF
FFFF
0004
1
0000 ∼ 0064 (0 ∼ 100)
SETTING POINT #1
RR REF POINT #1
FREQUENCY
0.01
1
0000 ∼ Fmax
RR REFERENCE
SETTING POINT #2
0000 ∼ 0064 (0 ∼ 100)
0000 ∼ Fmax
RR REF POINT #2
FREQUENCY
0.01
IV TERMINAL STANDARD
OR ADJUSTABLE
0000: Standard
0004: Adjustable
(0)
(1)
IV REFERENCE
8A
8B
8C
8D
8E
1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
00FF
FFFF
00FF
FFFF
0008
1
0000 ∼ 0064 (0 ∼ 100)
SETTING POINT #1
IV REF POINT #1
FREQUENCY
0.01
1
0000 ∼ Fmax
IV REFERENCE
SETTING POINT #2
0000 ∼ 0064 (0 ∼ 100)
0000 ∼ Fmax
IV REF POINT #2
FREQUENCY
0.01
RX TERMINAL STANDARD
OR ADJUSTABLE
0000: Standard
0008: Adjustable
(0)
(1)
RX REFERENCE
8F
1
0 / 1
00FF
1
009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
-Fmax ∼ Fmax
SETTING POINT #1
RX REF POINT #1
FREQUENCY
90
91
0 / 1
0 / 1
FFFF
00FF
0.02
1
RX REFERENCE
SETTING POINT #2
009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
-Fmax ∼ Fmax
RX REF POINT #2
FREQUENCY
92
93
0 / 1
0 / 1
FFFF
0010
0.02
PG TERMINAL STANDARD
OR ADJUSTABLE
0000: Standard
0010: Adjustable
(0)
(1)
PG REFERENCE
94
1
0 / 1
00FF
1
009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
-Fmax ∼ Fmax
SETTING POINT #1
PG REF POINT #1
FREQUENCY
95
96
0 / 1
0 / 1
FFFF
00FF
0.02
1
PG REFERENCE
SETTING POINT #2
009C ∼ 00FF, 0000 ∼ 0064
(-100 ∼ -1, 0 ∼ 100)
-Fmax ∼ Fmax
PG REF POINT #2
FREQUENCY
97
0 / 1
FFFF
0.02
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0000: Standard
Multiplier
BINARY INPUT STD OR
ADJUSTABLE
98
0 / 1
0001
(0)
(1)
0001: Adjustable
BINARY REF
99
9A
9B
9C
1
0 / 1
0 / 1
0 / 1
0 / 1
00FF
FFFF
00FF
FFFF
1
0000 ∼ 0064 (0 ∼ 100)
SETTING POINT #1
BINARY REF POINT
#1 FREQUENCY
0.02
1
-Fmax ∼ Fmax
BINARY REF
SETTING POINT #2
0000 ∼ 0064 (0 ∼ 100)
-Fmax ∼ Fmax
BINARY REF POINT
#2 FREQUENCY
0.02
0.01
JOG RUN FREQUENCY
9D
9E
0 / 1
0 / 1
FFFF
00C0
0000 ∼ 07D0 (0.00 ∼ 20.00)
0000: Decelerated stop
0040: Coast stop
JOG STOP
METHOD
Other
than 0
(0)
(1)
(2)
0080: DC injection stop
PRESET SPEED
SELECTION
9F
0 / 1
0 / 1
000F
0004
1
0000 ∼ 000F (0 ∼ 15)
Reserved
A0 ∼ FF
100
PRESET SPEED
MODE
ACTIVATION
Other
than 0
0000: Deactivated
0004: Activated
(0)
(1)
PRESET SPEED
#1 FREQUENCY
101
102
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#1 OPERATING
MODE
0004: (0)
0000: (1)
000C: (2)
0008: (3)
0404: (4)
0400: (5)
040C: (6)
0408: (7)
PRESET SPEED
#2 FREQUENCY
103
104
2 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#2 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#3 FREQUENCY
105
106
3 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#3 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#4 FREQUENCY
107
108
4 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#4 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#5 FREQUENCY
109
10A
5 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#5 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#6 FREQUENCY
10B
10C
6 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#6 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#7 FREQUENCY
10D
10E
7 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#7 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
Download from Www.Somanuals.com.4A1ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
PRESET SPEED
#8 FREQUENCY
10F
8 or
higher
1
FFFF
0.01
LL ∼ UL
PRESET SPEED
#8 OPERATING
MODE
110
1
040C
Same as PRESET SPEED #1
OPERATING MODE
1
PRESET SPEED
#9 FREQUENCY
111
112
9 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#9 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#10 FREQUENCY
113
114
10 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#10 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#11 FREQUENCY
115
116
11 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#11 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#12 FREQUENCY
117
118
12 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#12 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#13 FREQUENCY
119
11A
13 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#13 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#14 FREQUENCY
11B
11C
14 or
higher
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#14 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
PRESET SPEED
#15 FREQUENCY
11D
11E
15
1
1
FFFF
040C
0.01
1
LL ∼ UL
PRESET SPEED
#15 OPERATING
MODE
Same as PRESET SPEED #1
OPERATING MODE
42
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.7 GROUP:PROTECTION FUNCTION PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
DYNAMIC BRAKING
SELECTION
11F
0 / 1
0003
0000: no dynamic braking
(0)
0001: with dynamic braking, no DBR
overload trip
(1)
0003: with dynamic braking and
DBR overload trip
(2)
BRAKING RESISTOR
VALUE
120
121
122
2
0 / 1
0 / 1
0 / 1
FFFF
FFFF
0004
0.1
000A ∼ 2710 (1.0 ∼ 1000)
BRAKING RESISTOR
POWER RATING
0.01
0001 ∼ EA60 (0.01 ∼ 600.00)
OVERVOLTAGE STALL
PROTECTION
0000: ON
(0)
(1)
0004: OFF
DC INJECTION START
FREQUENCY
123
124
0 / 1
0 / 1
FFFF
00FF
0.01
1
0000 ∼ 2EE0 (0.00 ∼ 120.00)
DC INJECTION
CURRENT
Other
than 0
0000 ∼ 0064 (0 ∼ 100)
MAGNITUDE
DC INJECTION
TIME
125
126
0 / 1
0 / 1
00FF
0040
0.1
0000 ∼ 0064 (0.0 ∼ 10.0)
FWD/REV DC INJECTION
PRIORITY CTRL
0000: OFF
(0)
(1)
(0)
(1)
(0)
(1)
(2)
0040: ON
MOTOR SHAFT
STATIONARY CTRL
127
128
0 / 1
0 / 1
0080
0030
0000: OFF
0080: ON
EMERGENCY OFF MODE
SELECTION
0000: Coast stop
0010: Decelerated stop
0020: DC injection stop
EMERGENCY OFF DC
INJECTION TIME
129
12A
12B
2
0 / 1
0 / 1
0 / 1
00FF
00FF
00FF
0.1
1
0000 ∼ 0064 (0.0 ∼ 10.0)
NUMBER OF RETRY
ATTEMPTS
0000 ∼ 000A (0 ∼ 10)
TIME BETWEEN
RETRY ATTEMPTS
Other
than 0
0.1
0000 ∼ 0064 (0.0 ∼ 10.0)
REGENERATION POWER
RIDE-THROUGH
12C
0 / 1
0008
0000: OFF
0008: ON
(0)
(1)
REGENERATION
12D
12E
1
0 / 1
0 / 1
00FF
0018
0.1
0000 ∼ 00FA (0.0 ∼ 25.0)
RIDE-THROUGH TIME
AUTO-RESTART (MOTOR
SPEED SEARCH)
0000: OFF
(0)
(1)
(2)
(3)
0008: On power failure
0010: On ST make/break
0018: Both (1) and (2)
ELECTRONIC THERMAL
PROTECT LVL #1
12F
130
131
132
0 / 1
0 / 1
0 / 1
0 / 1
00FF
FFFF
00FF
0030
1
000A ∼ 0064 (10 ∼ 100)
0000 ∼ 0BB8 (0.00 ∼ 30.00)
0001 ∼ 00F0 (10 ∼ 2400)
OVERLOAD REDUCTION
START FREQ
0.01
10
MOTOR 150% OVERLOAD
TIME LIMIT
OVERLOAD SELECTION
0000: with motor overload trip,
without soft-stall
(0)
0010: with motor overload trip and
soft-stall
(1)
0020: without soft-stall or motor
overload trip
(2)
0030: with soft-stall, without motor
overload trip (3)
0000: ON
STALL PROTECTION
ENABLE
133
134
0 / 1
0 / 1
0040
00FF
(0)
(1)
0040: OFF
STALL PROTECTION
CURRENT LEVEL
0
1
000A ∼ 00D7 (10 ∼ 215)
Download from Www.Somanuals.com.4A3ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0000: Trip disabled
Multiplier
UNDERVOLTAGE TRIP
SELECTION
135
0 / 1
0080
(0)
(1)
0080: Trip (during run)
UNDERVOLTAGE DETECT
TIME
136
137
0 / 1
0 / 1
FFFF
0008
0.01
0000 ∼ 03E8 (0.00 ∼ 10.00)
LOW CURRENT DETECT
SELECTION
0000: Trip disabled
(0)
(1)
0008: Trip on detection
LOW CURRENT DETECT
LEVEL
138
139
140
0 / 1
0 / 1
0 / 1
00FF
00FF
0003
1
1
0000 ∼ 0064 (0 ∼ 100)
LOW CURRENT DETECTION
TIME
0000 ∼ 00FF (0 ∼ 255)
OUTPUT SHORT-CIRCUIT
DETECTION SELECT
0000: Standard motor
(0)
(1)
0001: High-speed motor
0002: Positioning use (standard
motor)
(2)
0003: Positioning use (high-speed
motor)
(3)
OVERTORQUE TRIP
SELECTION
141
0 / 1
0040
0000: Trip disabled
0040: Trip enabled
(0)
(1)
OVERTORQUE TRIP LEVEL
142
143
0 / 1
0 / 1
00FF
0002
1
0000 ∼ 00C8 (0 ∼ 200)
0000: Data cleared when powered
FAULT TRIP EEPROM
SAVE ENABLE
OFF
(0)
0002: Data retained when powered
OFF
(1)
COOLING FAN CONTROL
SELECTION
144
145
0 / 1
0 / 1
0004
0000: Automatic (temperature
detection)
(0)
(1)
0004: Always ON
CUMULATIVE RUN TIMER
ALARM SETTING
FFFF
0.02
0000 ∼ C34B (0.00 ∼ 999.90)
44
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.8 GROUP:PATTERN RUN CONTROL PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
0000: OFF
Multiplier
PATTERN RUN SELECTION
146
0 / 1
0008
(0)
(1)
(0)
(1)
(0)
0008: ON
PATTERN RUN
CONTINUE MODE
147
1
0 / 1
1
0001
00FF
0000: reset on stop
0001: switch when done
0000: Skip
PATTERN GROUP #1
SPEED #0
148
149
150
151
152
153
154
155
156
157
158
159
15A
15B
15C
15D
15E
15F
160
161
162
163
164
165
166
167
168
1
PATTERN GROUP #1
SPEED #1
0001 ∼ 000F: Speeds 1 ∼ 15
PATTERN GROUP #1
SPEED #2
PATTERN GROUP #1
SPEED #3
PATTERN GROUP #1
SPEED #4
PATTERN GROUP #1
SPEED #5
PATTERN GROUP #1
SPEED #6
PATTERN GROUP #1
SPEED #7
PATTERN GROUP #1
NUMBER OF CYCLES
0 / 1
1
00FF
00FF
1
1
0001 ∼ 00FF: 1 ∼ 255
0000: Skip
PATTERN GROUP #2
SPEED #0
(0)
PATTERN GROUP #2
SPEED #1
0001 ∼ 000F: Speeds 1 ∼ 15
PATTERN GROUP #2
SPEED #2
PATTERN GROUP #2
SPEED #3
PATTERN GROUP #2
SPEED #4
PATTERN GROUP #2
SPEED #5
PATTERN GROUP #2
SPEED #6
PATTERN GROUP #2
SPEED #7
PATTERN GROUP #2
NUMBER OF CYCLES
0 / 1
1
00FF
00FF
1
1
0001 ∼ 00FF: 1 ∼ 255
0000: Skip
PATTERN GROUP #3
SPEED #0
(0)
PATTERN GROUP #3
SPEED #1
0001 ∼ 000F: Speeds 1 ∼ 15
PATTERN GROUP #3
SPEED #2
PATTERN GROUP #3
SPEED #3
PATTERN GROUP #3
SPEED #4
PATTERN GROUP #3
SPEED #5
PATTERN GROUP #3
SPEED #6
PATTERN GROUP #3
SPEED #7
PATTERN GROUP #3
NUMBER OF CYCLES
0 / 1
00FF
1
0001 ∼ 00FF: 1 ∼ 255
Download from Www.Somanuals.com.4A5ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0000: Skip
Multiplier
PATTERN GROUP #4
SPEED #0
169
1
00FF
(0)
1
PATTERN GROUP #4
SPEED #1
16A
16B
16C
16D
16E
16F
170
171
172
0001 ∼ 000F: Speeds 1 ∼ 15
PATTERN GROUP #4
SPEED #2
PATTERN GROUP #4
SPEED #3
PATTERN GROUP #4
SPEED #4
PATTERN GROUP #4
SPEED #5
PATTERN GROUP #4
SPEED #6
PATTERN GROUP #4
SPEED #7
PATTERN GROUP #4
NUMBER OF CYCLES
0 / 1
1
00FF
00FF
1
0001 ∼ 00FF: 1 ∼ 255
SPEED #1 CONTINUE
MODE
0000: Count in seconds from time of
activation (0)
0001: Count in minutes from time of
activation (1)
0002: Count in seconds from speed
reach (2)
0003: Count in minutes from speed
reach
(3)
(4)
(5)
0004: Non-stop (continue until
STOP command)
0005: Continue until next step
command
SPEED #1 DRIVE
TIME
173
174
175
176
177
178
179
17A
17B
17C
17D
17E
17F
180
181
< 4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
1
1
1
1
1
1
1
1
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #2 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #2 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #3 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #3 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #4 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #4 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #5 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #5 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #6 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #6 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #7 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #7 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #8 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #8 DRIVE
TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
SPEED #9 CONTINUE
MODE
182
1
00FF
Same as SPEED #1 CONTINUE
MODE
SPEED #9 DRIVE
TIME
183
184
185
186
187
188
189
18A
18B
18C
18D
18E
18F
< 4
1
1
1
1
1
1
1
1
1
1
1
1
1
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
00FF
FFFF
1
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #10 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #10
DRIVE TIME
< 4
1
1
1
1
1
1
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #11 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #11
DRIVE TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #12 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #12
DRIVE TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #13 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #13
DRIVE TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #14 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #14
DRIVE TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
SPEED #15 CONTINUE
MODE
Same as SPEED #1 CONTINUE
MODE
SPEED #15
DRIVE TIME
< 4
0000 ∼ 1F40 (0 ∼ 8000)
Download from Www.Somanuals.com.4A7ll Manuals Search And Download.
11.2.9 GROUP:FEEDBACK CONTROL PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
0020: No feedback
Multiplier
FEEDBACK CONTROL
SELECTION
190
0 / 1
0060
(0)
(1)
(2)
(1)
(2)
(3)
(4)
(5)
0040: PID control
0060: Speed feedback
0004: RR input
FEEDBACK INPUT
SIGNAL SELECTION
191
1, 2
0 / 1
001C
0008: IV input
000C: RX input
0010: PG feedback
0014: RS232C input
0018: Communication/12-bit binary
interface board
(6)
001C: BIN input
(7)
PROPORTIONAL
GAIN
192
0 / 1
00FF
0.01
0001 ∼ 00FF (0.01 ∼ 2.55)
INTEGRAL GAIN
193
194
0 / 1
0 / 1
FFFF
00FF
0.01
0.1
0001 ∼ 8CA0 (0.01 ∼ 360.00)
0000 ∼ 00FF (0.0 ∼ 25.5)
ANTI-HUNTING
GAIN
LAG TIME
CONSTANT
195
196
197
0 / 1
0 / 1
0 / 1
00FF
FFFF
0080
1
0000 ∼ 00FF (0 ∼ 255)
PID LOWER LIMIT
FREQUENCY
0.01
0 ∼ Fmax
PID DEVIATION LIMIT
SELECTION
0000: No PID deviation limit
0080: PID deviation limited
(0)
(1)
PID DEVIATION
UPPER LIMIT
198
199
19A
19B
1
0 / 1
0 / 1
0 / 1
0 / 1
00FF
00FF
FFFF
0001
1
1
1
0000 ∼ 0032 (0 ∼ 50)
0000 ∼ 0032 (0 ∼ 50)
0001 ∼ 270F (1 ∼ 9999)
PID DEVIATION
LOWER LIMIT
PG INPUT: NUMBER OF
PULSES
PG INPUT: NUMBER OF
PHASES
0000: Single-phase input
0001: Two-phase input
0000: OFF
(1)
(2)
(0)
(1)
DROOPING CONTROL
ENABLE
19C
0 / 1
0002
0002: ON
DROOPING CONTROL
AMOUNT
19D
19E
1
0 / 1
0 / 1
00FF
0007
0.1
0000 ∼ 0064 (0 ∼ 10.0)
OVERRIDE CONTROL
SELECTION
0000: OFF
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(0)
(1)
(2)
(3)
(4)
0001: FCRR
0002: FCIV
0003: FCRX
0004: FCPG
0005: FCPNL
0006: FCOPT
0007: FCMLT
0000: Reference
0008: KRR
OVERRIDE
MULTIPLIER INPUT
SELECTION
19F
1A0
7
0 / 1
0038
0010: KIV
0018: KRX
0020: KBIN
OVERRIDE CHANGE
MULTIPLIER
0 / 1
FFFF
0.1
FC18 ∼ 03E8 (-100.0 ∼ 100.0)
Reserved
1A1 ∼
1CF
48
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.10 GROUP:COMMUNICATION SETTING PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
Reserved
1D0 ∼
200
RS232 BAUD RATE
201
1
0018
0000: 2400 baud
(0)
(1)
(2)
(0)
(1)
(0)
(1)
0008: 4800 baud
0010: 9600 baud
0000: 7 bits
NUMBER OF DATA BITS
PARITY SETTING
202
1
1
0040
0080
0040: 8 bits
.203
0000: Even parity
0080: Odd parity
INVERTER ID NUMBER
204
205
1
1
00FF
0007
1
0000 ∼ 00FF (0 ∼ 255) Note 1
0000: OFF
0001: RS485
COMMUNICATION
SELECTION
(0)
(1)
0002: Profibus, Modbus, DNet (2)
0003: TOSLINE S-20
(3)
(4)
(5)
(6)
0004: 12 bit binary input
0005: 3-digit BCD (0.1Hz)
0006: 3-digit BCD (1Hz)
MASTER/SLAVE
SELECTION
206
1
2
1
0018
0000: Slave
(0)
0008: Master (frequency command)
(1)
0010: Master (output frequency) (2)
RS485 BAUD RATE
207
208
1
1
0004
0003
0000: Normal mode
0004: High-speed mode
0000: OFF
(0)
(1)
(0)
(1)
(2)
(3)
TOSLINE-F10
COMMAND INPUT
0001: Frequency command
0002: Command input
0003: Both (1) and (2)
TOSLINE-F10
MONITOR OUTPUT
209
1
003C
0000: (0)
0004: (1)
0008: (2)
000C: (3)
0010: (4)
0014: (5)
0018: (6)
001C: (7)
0020: (8)
0024: (9)
0028: (10)
002C: (11)
0030: (12)
0034: (13)
0038: (14)
003C: (15 )
TOSLINE-F10 COMM
ERROR MODE
20A
1
0080
0000: Data cleared
0080: Data retained
(0)
(1)
TOSLINE-S20
20B
20C
20D
20E
20F
3
1
1
1
1
1
FFFF
FFFF
001F
001F
0001
1
1
1
1
1
0000 ∼ 03FF (0 ∼ 1023)
0000 ∼ 03FF (0 ∼ 1023)
0000 ∼ 001F (0 ∼ 31)
0000 ∼ 001F (0 ∼ 31)
RECEIVE ADDRESS
TOSLINE-S20
TRANSMIT ADDRESS
TOSLINE-S20
COMMAND INPUT
TOSLINE-S20
MONITOR OUTPUT
TOSLINE-S20 FREQ
REF ADDR SELECT
0000: Disable
0001: Enable
(0)
(1)
TOSLINE-S20
FREQ REFERENCE
ADDR
210
1
1
FFFF
1
0000 ∼ 03FF (0 ∼ 1023)
Note 1: Although the INVERTER ID NUMBER parameter can be set from 0 to 255, the allowable Profibus slave
addresses range only from 0 to 125. Therefore, if this parameter is set to a value from 126 to 255, the
Profibus interface card will trip “OPTION PCB ERROR” upon initialization.
Download from Www.Somanuals.com.4A9ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0000: Data cleared
Multiplier
TOSLINE-S20 COMM
ERROR MODE
211
1
0002
(0)
(1)
(0)
(1)
(0)
(1)
1
0002: Data retained
0000: No effect
0004: Reset
TOSLINE-S20 COMM
OPTION RESET
212
213
1
0004
0020
1
RS485/12-BIT BINARY
BIAS,GAIN
0 / 1
0000: OFF
0020: ON
RS485/12-BIT
214
215
1
0 / 1
0 / 1
00FF
FFFF
1
0000 ∼ 0064 (0 ∼ 100)
BINARY POINT #1
RS485/12-BIT
BINARY PT. #1
FREQ
0.01
0000 ∼ Fmax (0 ∼ Fmax)
RS485/12-BIT
216
217
0 / 1
0 / 1
00FF
FFFF
1
0000 ∼ 0064 (0 ∼ 100)
BINARY POINT #2
RS485/12-BIT
BINARY PT. #2
FREQ
0.01
0000 ∼ Fmax (0 ∼ Fmax)
11.2.11 GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
FM TERMINAL FUNCTION
SELECTION
218
0 / 1
FFFF
1194: Pre-comp ref. frequency
6686: Post-comp output freq.
1500: Frequency setting
2576: Output current
(0)
(1)
(2)
(3)
2689: DC voltage
(4)
5668: Output voltage
(5)
3684: Torque current
(6)
2688: Excitation current
7506: PID feedback value
0584: Motor overload ratio
0586: Inverter overload ratio
0588: DBR overload ratio
835C: Input power
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
835E: Output power
A000: Fixed output
2304: Peak output current
8302: Peak input voltage
FREQUENCY METER
ADJUSTMENT
219
21A
21B
0 / 1
0 / 1
0 / 1
FFFF
FFFF
FFFF
1
1
0000 ∼ FFFF
AM TERMINAL FUNCTION
SELECTION
Same as FM TERMINAL FUNCTION
SELECTION
CURRENT METER
ADJUSTMENT
0000 ∼ FFFF
50
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.12 GROUP:UTILITY PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
INDUSTRIAL
21C
0 / 1
00FF
0000: Std. Shpmt. setting
0001: Pump application
0002: Fan application
0003: Conveyor application
0004: Hoist application
0005: Textiles application
0006: Machine tools appl.
0000: Does nothing
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(0)
(1)
(2)
APPLICATIONS
(previous setting monitor for
read use only)
INDUSTRIAL
APPLICATIONS
21D
21E
0 / 1
00FF
00FF
0011: Pump application
0012: Fan application
0013: Conveyor application
0014: Hoist application
0015: Textiles application
0016: Machine tools appl.
0000: Does nothing
(for write use)
(∗)
STANDARD SETTING MODE
SELECTION
0 / 1
(∗)
0001: 50Hz std. Settings
0002: 60Hz std. Settings
0003: Factory settings
0004: Trip clear
0005: Save user-set param.
0006: TYPE 5 reset
0007: Initialize typeform
0000: Only RS232C valid
0001: Terminal input valid
0002: Panel input valid
COMMAND MODE
SELECTION
21F
220
221
0 / 1
0 / 1
0 / 1
0007
0038
00FB
0003: Communication interface input
valid
(3)
(4)
(0)
(1)
(2)
0004: local/remote valid
0000: Only RS232C valid
0008: Terminal input valid
0010: Panel input valid
FREQUENCY MODE
SELECTION
0018: Communication/12-bit binary
interface input valid
(3)
0020: local/remote valid
(4)
PANEL OPERATION MODE
SELECTION
1
1
0000 ∼ 003F (0 ∼ 63)
(except 0004, 0008, 000C....)
PASS NUMBER
222
223
224
225
226
227
0 / 1
2
00FF
FFFF
FFFF
FFFF
00FF
FFFF
0000 ∼ 0063 (0 ∼ 99)
(Monitor only)
CPU VERSION
ROM VERSION
3 or 6
1
(Monitor only)
EEPROM VERSION
INVERTER TYPEFORM
(Monitor only)
0
Refer to Table 9 (page 54)
0001 ∼ 0010 (1 ∼ 16)
STATUS MONITOR #1
DISPLAY SELECT
0 / 1
1
1
STATUS MONITOR #2
DISPLAY SELECT
228
229
22A
22B
22C
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
FFFF
FFFF
FFFF
FFFF
0003
0001 ∼ 0010 (1 ∼ 16)
0001 ∼ 0010 (1 ∼ 16)
0001 ∼ 0010 (1 ∼ 16)
0000 ∼ 4E20 (0.00 ∼ 200.00)
STATUS MONITOR #3
DISPLAY SELECT
1
STATUS MONITOR #4
DISPLAY SELECT
1
FREQUENCY UNITS SCALE
FACTOR
0.01
FREQUENCY DISPLAY
RESOLUTION
0000: 1Hz
(0)
(1)
(2)
0001: 0.1Hz
0002: 0.01Hz
Download from Www.Somanuals.com.5A1ll Manuals Search And Download.
Register
Function / Title
Bank
Mask
Adjustment Range
0000: 0.1 sec.
Multiplier
ACC/DEC TIME UNITS
SELECTION
22D
0 / 1
0004
(0)
(1)
(0)
(1)
(0)
(1)
(0)
(1)
(0)
(1)
(0)
(1)
(0)
(1)
0004: 0.01 sec.
0000: %
CURRENT UNITS
SELECTION
22E
22F
230
231
232
233
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0008
0010
0001
0040
0080
0001
0008: A
VOLTAGE UNITS
SELECTION
0000: %
0010: V
BLIND FUNCTION
SELECTION
0000: Blind
0001: Selective unblinding
0000: Blind
0040: Unblind
0000: Blind
0080: Unblind
0000: Blind
0001: Unblind
FUNDAMENTAL
PARAMS #2 BLIND
1
PANEL CONTROL
PARAMS BLIND
TERMINAL
SELECTION PARAMS
BLIND
SPECIAL CONTROL
PARAMS BLIND
234
235
236
0 / 1
0 / 1
0 / 1
0002
0004
0008
0000: Blind
(0)
(1)
(0)
(1)
(0)
(1)
0002: Unblind
0000: Blind
FREQUENCY SETTING
PARAMS BLIND
0004: Unblind
0000: Blind
PROTECTION
FUNCTION PARAMS
BLIND
0008: Unblind
PATTERN RUN
CONTROL PARAMS
BLIND
237
0 / 1
0010
0000: Blind
(0)
(1)
0010: Unblind
FEEDBACK CONTROL
PARAMS BLIND
238
239
23A
0 / 1
0 / 1
0 / 1
0020
0040
0080
0000: Blind
(0)
(1)
(0)
(1)
(0)
(1)
0020: Unblind
0000: Blind
COMMUNICATION
PARAMS BLIND
0040: Unblind
0000: Blind
INDUSTRIAL
APPL:PUMP PARAMS
BLIND
0080: Unblind
INDUSTRIAL
APPL:FAN PARAMS
BLIND
23B
0 / 1
0001
0000: Blind
(0)
(1)
0001: Unblind
INDUSTRIAL APPL:
CONVEYOR BLIND
23C
23D
23E
23F
0 / 1
0 / 1
0 / 1
0 / 1
0002
0004
0008
0010
0000: Blind
(0)
(1)
(0)
(1)
(0)
(1)
(0)
(1)
0002: Unblind
0000: Blind
INDUSTRIAL APPL:
HOIST BLIND
0004: Unblind
0000: Blind
INDUSTRIAL APPL:
TEXTILES BLIND
0008: Unblind
0000: Blind
INDUST
APPL:MACHINE
TOOLS BLIND
0010: Unblind
AM/FM ADJUSTMENT
PARAMS BLIND
240
241
0 / 1
0 / 1
0001
0004
0000: Blind
(0)
(1)
(0)
(1)
0001: Unblind
0000: Blind
MOTOR PARAMETERS
BLIND
0004: Unblind
52
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.13 GROUP:MOTOR RATING PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
0001: (2)
Multiplier
NUMBER OF MOTOR POLES
242
0 / 1
00FF
2
0002: (4)
0003: (6)
0004: (8)
0005: (10)
0006: (12)
0007: (14)
0008: (16)
MOTOR RATED CAPACITY
MOTOR TYPE
243
244
0 / 1
0 / 1
FFFF
0030
0.1
0001 ∼ 270F (0.1 ∼ 999.9)
0000:Toshiba EQPIII motor
0010:Toshiba STD motor
0020:Other
(0)
(1)
(2)
MOTOR RATED
VOLTAGE
245
2
0 / 1
0 / 1
00FF
00FF
5
0012 ∼ 0078 (90 ∼ 600)
(230 / 460v units)
(575v units)
246
247
001A ∼ 00AC (130 ∼ 860)
0000 ∼ 00C8 (0 ∼ 400)
MOTOR RATED
FREQUENCY
2
1
MOTOR RATED RPM
248
249
0 / 1
0
FFFF
0008
0000 ∼ 270F (0 ∼ 9999)
0000: Auto-tuning disabled
0008: Auto-tuning enabled
0000: Small
AUTO-TUNING ENABLE
(0)
(1)
(0)
(1)
(2)
(3)
LOAD MOMENT OF
INERTIA
24A
0 / 1
00C0
0040: Medium
0080: Large
00C0: Very large
Download from Www.Somanuals.com.5A3ll Manuals Search And Download.
Table 9: Inverter Typeform Codes
230v Class
460v Class
600v Class
Inverter
Model
Typeform
Data (Hex)
Inverter
Model
Typeform
Data (Hex)
Inverter
Model
Typeform
Data (Hex)
G3-2010
G3-2015
G3-2025
G3-2035
G3-2055
G3-2080
G3-2110
G3-2160
G3-2220
G3-2270
G3-2330
G3-2400
G3-4015
G3-4025
G3-4035
G3-4055
G3-4080
G3-4110
G3-4160
G3-4220
G3-4270
G3-4330
G3-4400
G3-4500
G3-4600
G3-4750
G3-410K
G3-412K
G3-415K
G3-420K
G3-425K
G3-430K
G3-6060
G3-6120
G3-6160
G3-6220
G3-6270
G3-6330
G3-6400
G3-6500
G3-6600
G3-6750
G3-610K
G3-612K
G3-615K
G3-620K
××21
××22
××23
××24
××25
××26
××27
××28
××29
××2A
××2B
××2C
××42
××43
××44
××45
××46
××47
××48
××49
××4A
××4B
××4C
××4D
××4E
××4F
××50
××51
××52
××53
××54
××55
××65
××67
××68
××69
××6A
××6B
××6C
××6D
××6E
××6F
××70
××71
××72
××73
Note: Due to the continual capacity expansion of the Toshiba adjustable speed drive
family, newly-released drive models may have typeform data which is not
documented in this table. If you encounter this situation, please contact
Toshiba International Corporation for verification of your model’s typeform
data.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
11.3 Inverter Fault Codes
LCD Display Message
Data
Explanation
(Hex)
NO ERROR
No error has been recorded since the last inverter reset or trip clear
Overcurrent during acceleration
××00
××01
××02
××03
××04
××05
××06
××07
××08
××09
××0A
××0B
××0C
××0D
××0E
××0F
××10
××11
××12
××13
OVERCURRENT (ACCEL)
(PRESS CLEAR)
OVERCURRENT (DECEL)
(PRESS CLEAR)
Overcurrent during deceleration
OVERCURRENT (RUN)
(PRESS CLEAR)
Overcurrent during constant-speed run
LOAD-END OVERCURRENT
(PRESS CLEAR)
Load-end overcurrent detected at start-up (output terminals, motor
wiring etc.)
U-PHASE SHORT CKT
(PRESS CLEAR)
U-phase armature short circuit
V-phase armature short circuit
W-phase armature short circuit
Lost input phase (option)
Lost output phase (option)
Overvoltage during acceleration
Overvoltage during deceleration
Overvoltage during constant-speed run
Inverter overload
V-PHASE SHORT CKT
(PRESS CLEAR)
W-PHASE SHORT CKT
(PRESS CLEAR)
LOST INPUT PHASE
(PRESS CLEAR)
LOST OUTPUT PHASE
(PRESS CLEAR)
OVERVOLTAGE (ACCEL)
(PRESS CLEAR)
OVERVOLTAGE (DECEL)
(PRESS CLEAR)
OVERVOLTAGE (RUN)
(PRESS CLEAR)
INVERTER OVERLOAD
(PRESS CLEAR)
MOTOR OVERLOAD
(PRESS CLEAR)
Motor overload
DBR OVERLOAD TRIP
(PRESS CLEAR)
Dynamic braking resistor overload
Inverter overheat
OVERHEAT TRIP
(PRESS CLEAR)
EMERGENCY OFF
(PRESS CLEAR)
Emergency off
EEPROM WRITE FAILURE
(PRESS CLEAR)
EEPROM failure during write
EEPROM failure during initial read
EEPROM READ FAILURE
(PRESS CLEAR)
Unused
××14
RAM ERROR
(PRESS CLEAR)
ROM ERROR
(PRESS CLEAR)
CPU ERROR
RAM error
××15
ROM error
××16
××17
××18
××19
CPU error
(PRESS CLEAR)
COMMUNICATION ERROR
(PRESS CLEAR)
GATE ARRAY FAULT
(PRESS CLEAR)
RS232C timer time-out
Gate array error
Download from Www.Somanuals.com.5A5ll Manuals Search And Download.
LCD Display Message
Data
(Hex)
Explanation
Output current detection circuit error
CURRENT DETECT ERROR
(PRESS CLEAR)
××1A
OPTION PCB ERROR
(PRESS CLEAR)
Option PCB error
××1B
OPTION ROM ERROR
Option ROM error
Low current
××1C
××1D
LOW CURRENT TRIP
(PRESS CLEAR)
UNDERVOLTAGE TRIP
(PRESS CLEAR)
Main circuit undervoltage
××1E
Unused
××1F
OVERTORQUE TRIP
(PRESS CLEAR)
Overtorque
××20
EARTH FAULT (SOFT)
(PRESS CLEAR)
Earth fault (software)
××21
××22
××23
××24
××25
××26
××27
××28
××29
EARTH FAULT (HARD)
(PRESS CLEAR)
Earth fault (hardware)
OPEN FUSE TRIP
(PRESS CLEAR)
Open fuse
DBR OVERCURRENT TRIP
(PRESS CLEAR)
Dynamic braking resistor overcurrent
Overcurrent in DC section during acceleration
Overcurrent in DC section during deceleration
Overcurrent in DC section during constant-speed run
Auto-tuning error
DC OVERCURRENT (ACC)
(PRESS CLEAR)
DC OVERCURRENT (DEC)
(PRESS CLEAR)
DC OVERCURRENT (RUN)
(PRESS CLEAR)
AUTO-TUNING ERROR
(PRESS CLEAR)
INV TYPEFORM ERROR
(PRESS READ/WRITE)
Inverter typeform error
56
Download from Www.Somanuals.com. All Manuals Search And Download.
12. GSD File
The following is a copy of the G3 Profibus interface card’s GSD file, which is used for
network commissioning and administration. An electronic version of this file can be
;============================================================
;
;
;
;
;
;
;
;
;
GSD File for Toshiba 3-series adjustable speed drive
;
;
;
;
;
;
;
;
;
Toshiba International Corporation
13131 W. Little York Rd.
Houston, TX 77041
(713) 466-0277
INV3-PROFIBUS
File name: ICC087B.GSD
;============================================================
;
Rev. 1
11.30.98
DH
Initial file entry
;
;============================================================
;
#Profibus_DP
; Unit Definition List:
GSD_Revision
Vendor_Name
Model_Name
Revision
Ident_Number
Protocol_Ident
Station_Type
FMS_supp
= 1
= "TOSHIBA"
= "G3/VFA5 Inverter Interface"
= "Rev. 1"
= 0x087B
= 0
= 0
= 0
Hardware_Release
Software_Release
;
= "Rev. A"
= "Ver. 1.0"
9.6_supp
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
19.2_supp
93.75_supp
187.5_supp
500_supp
1.5M_supp
3M_supp
6M_supp
12M_supp
;
MaxTsdr_9.6
MaxTsdr_19.2
MaxTsdr_93.75
MaxTsdr_187.5
MaxTsdr_500
MaxTsdr_1.5M
MaxTsdr_3M
MaxTsdr_6M
MaxTsdr_12M
;
= 60
= 60
= 60
= 60
= 100
= 150
= 250
= 450
= 800
Redundancy
Repeater_Ctrl_Sig
;
= 0
= 2
; Slave Specification:
24V_Pins
;
= 0
Implementation_Type
Freeze_Mode_supp
= "SPC3"
= 1
Download from Www.Somanuals.com.5A7ll Manuals Search And Download.
Sync_Mode_supp
Auto_Baud_supp
Set_Slave_Add_supp
Min_Slave_Intervall
;
Modular_Station
Max_Module
= 1
= 1
= 1
= 1
= 0
= 1
Max_Input_Len
Max_Output_Len
Max_Data_Len
;
= 16
= 8
= 24
; Module Definition:
Max_Diag_Data_Len
Slave_Family
OrderNumber
= 8
= 0
= "INV3-PROFIBUS"
Module = "Toshiba ASD:5w2b2w In, 2w2w Out" 0x54,0x11,0xD1,0x61,0xE1
EndModule
58
Download from Www.Somanuals.com. All Manuals Search And Download.
13. Notes
Download from Www.Somanuals.com.5A9ll Manuals Search And Download.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 West Little York Rd., Houston, TX 77041
Tel: [800] 231-1412 Fax: [713] 466-8773 Telex: 762078
Printed in U.S.A
Download from Www.Somanuals.com. All Manuals Search And Download.
|